8/20/2010                                      Deficiency Report                                      Page 1 of 15

                                      5th Avenue Building Inspections
                       Providing Real Estate, Insurance, Termite & Indoor Air Quality
                        Inspections For Residential, Commercial & New Construction
                                             Ph#: (561) 369-8363


                                      SAMPLE REPORT
SITE/GROUNDS

05. Sprinkler System          NEEDS REPAIR: Inoperable-not priming.

                              Heads: spraying onto structure-evidence of flooding on areas adjoining
                              enclosed room. Location: exterior of enclosed room.

                              Repair cost estimate: $200±.




08. Driveway                  NEEDS REPAIR: Asphalt driveway: significant damaged-deterioration.

                              Repair cost estimate: $400±.




     5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                    Deficiency Report                                             Page 2 of 15

                                    5th Avenue Building Inspections
                     Providing Real Estate, Insurance, Termite & Indoor Air Quality
                      Inspections For Residential, Commercial & New Construction
                                           Ph#: (561) 369-8363


EXTERIOR AREAS

04. Stucco Walls            NEEDS REPAIR: Frame wall: significant cracks-risk of water intrusion.
                            Location: outside of master bath-scattered locations. Repairperson should
                            check all perimeter areas prior to making repairs.

                            Repair cost estimate: $300±.




09. Exterior Areas          NEEDS REPAIR: Metal post: loose-not set properly, needs permanent
                            repairs. Location: porch at front.

                            Repair cost estimate: $300±.




ROOF/ATTIC

05. Roof Edge/Overhang      NEEDS REPAIR: Leak stains indicating evidence of edge leak on exterior
                            overhang. Location: 1. 2nd floor over garage door. 2. 2nd floor left side. 3.
                            rear over balcony. Budget additional expense for removal of gutters attached
                            to fascia board to facilitate repairs.




     5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                      Deficiency Report                                        Page 3 of 15

                                      5th Avenue Building Inspections
                       Providing Real Estate, Insurance, Termite & Indoor Air Quality
                        Inspections For Residential, Commercial & New Construction
                                             Ph#: (561) 369-8363

                              Leak stains and wood rot indicating evidence of edge leak on exterior
                              overhang. Location: 2nd floor balcony.

                              Repair cost estimate: $2,500±.




HEATING/COOLING

08. Air Handler Unit          NEEDS REPAIR: Coils-interior: dirt-debris buildup. Location of unit: A/C
                              closet.

                              Repair cost estimate: $300±.




     5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                     Deficiency Report                                           Page 4 of 15

                                     5th Avenue Building Inspections
                      Providing Real Estate, Insurance, Termite & Indoor Air Quality
                       Inspections For Residential, Commercial & New Construction
                                            Ph#: (561) 369-8363




09. Ductwork System          NEEDS REPAIR: Attic ductwork: damaged, laying on ground-should be
                             raised, leak stains-evidence of leakage, cloth duct tape on
                             connections-temporary fix, rip-tear on outer protective wrapping. Location:
                             including but not limited to (3) small sections near attic hatch-sections
                             should be replaced. FPL should be contacted for a ductwork system test and
                             home energy rebate survey www.fpl.com/residential/savings/index.shtml.

                             Repair cost estimate: $500±.




14. Condensate System        NEEDS REPAIR: Exterior drain: missing trap-creating a flood next to
                             exterior wall/slab. Requires reposition-extension or use splashblock
                             minimum 12" away from structure or equipment. Location: by A/C
                             condenser unit.

                             Repair cost estimate: $100±.




     5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                       Deficiency Report                                         Page 5 of 15

                                    5th Avenue Building Inspections
                     Providing Real Estate, Insurance, Termite & Indoor Air Quality
                      Inspections For Residential, Commercial & New Construction
                                           Ph#: (561) 369-8363




NEEDS REPAIR: Stains-grime indicating air leakage or not properly insulated. Location: guest bedroom
closet above front entry. Repairs may involve cleaning-replacement of affected materials and re-sealing
entire vent connection using antimicrobial mastic coating sealant.

Repair cost estimate: $150±.

15. Support/Plenum Base        NEEDS REPAIR: Support base: insulation loose-moisture stains due to
                               prior leakage, filter frame loose. Location: A/C closet. Should be sealed
                               with antimicrobial mastic coating due to moist air flow and exposure to
                               condensation.

                               NEEDS REPAIR: Microbial growth-high humidity splotches buildup on
                               support base, wall behind air handler, ceiling penetrations. Minimal
                               remediation would require removal-cleaning and disinfecting affected area
                               per EPA guidelines (www.epa.gov/mold/moldcleanup.html). Location:
                               garage.

                               Repair cost estimate: Depends on mold remediation assessment's and
                               estimating process




     5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                    Deficiency Report                                        Page 6 of 15

                                    5th Avenue Building Inspections
                     Providing Real Estate, Insurance, Termite & Indoor Air Quality
                      Inspections For Residential, Commercial & New Construction
                                           Ph#: (561) 369-8363




ELECTRICAL SYSTEM

08. Receptacles             NEEDS REPAIR: Weatherproof cover: missing, water intrusion. Location
                            of outlet: rear side area.

                            Hot and neutral wires reversed-unsafe wiring (reverse polarity). Outlet
                            working with risk of shock hazard. Location of outlet: left/front guest
                            bedroom.

                            Ungrounded-unsafe wiring (missing ground). Outlet working with risk of
                            shock hazard. Location of outlet: master bedroom.

                            Repair cost estimate: $150±.




10. General Wiring          NEEDS REPAIR: Electrical wiring: splices exposed-missing cover.
                            Location: exterior rear by pool transformer panel.

                            A/C #1 breaker burnt-scorched. Location of panel: exterior by electric

     5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                    Deficiency Report                                             Page 7 of 15

                                    5th Avenue Building Inspections
                     Providing Real Estate, Insurance, Termite & Indoor Air Quality
                      Inspections For Residential, Commercial & New Construction
                                           Ph#: (561) 369-8363

                            meter.

                            Repair cost estimate: $200±.




13. Light Fixtures          NEEDS REPAIR: Fluorescent lights: inoperable-replace bulbs first.
                            Location: kitchen.

                            Fluorescent lights: tube bulbs flickering. Location: laundry room.

                            Repair cost estimate: $300±.


PLUMBING SYSTEM

04. Water Heater            NEEDS REPAIR: Pressure relief discharge pipe: reduced in size-must be
                            approved 3/4". On interior installation: extent to exterior to prevent random
                            dripping onto interior contents.

                            Repair cost estimate: $150±.


      5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                 UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                      Deficiency Report                                           Page 8 of 15

                                      5th Avenue Building Inspections
                       Providing Real Estate, Insurance, Termite & Indoor Air Quality
                        Inspections For Residential, Commercial & New Construction
                                             Ph#: (561) 369-8363




BATHROOMS

01. Bathrooms                 NEEDS REPAIR: Water hammering noise when hot water faucets are
                              turned off rapidly. Most of the time this condition can be corrected by
                              closing main valve and opening all faucet fixtures to allow air chambers to
                              fill with air or installing air chambers arrestors. Location: master bath.

                              Repair cost estimate: $200±.


03. Shower/Tub Stall          NEEDS REPAIR: Tub & shower tiles: grout failure-fungus, gaps, and grime
                              buildup on wall next to guest tub. Location: guest-master bathrooms.

                              Repair cost estimate: $300±.




     5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                   Deficiency Report                                          Page 9 of 15

                                    5th Avenue Building Inspections
                     Providing Real Estate, Insurance, Termite & Indoor Air Quality
                      Inspections For Residential, Commercial & New Construction
                                           Ph#: (561) 369-8363




INTERIOR AREAS

04. Interior Areas          NEEDS REPAIR: Moisture evidence-stains-evidence of leakage, plaster
                            damage on wall under windows. Location: enclosed room. Requires further
                            evaluation.

                            Repair cost estimate: $300±.




05. Windows                 NEEDS REPAIR: Crank missing, damaged-inoperable. Location: including
                            but not limited to kitchen, living room, guest bath, enclosed room.

                            Bottom frame: water intrusion-evidence of leakage at bottom frame, carpet
                            tack strips stained. Repairs may involve waterproofing exterior-interior
                            frame flashing/fasteners. Location: 1. master bedroom door (2). 2. Dining
                            room.

                            Repair cost estimate: $300±.




      5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                 UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                   Deficiency Report                                        Page 10 of 15

                                  5th Avenue Building Inspections
                   Providing Real Estate, Insurance, Termite & Indoor Air Quality
                    Inspections For Residential, Commercial & New Construction
                                         Ph#: (561) 369-8363




09. Slider Doors           NEEDS REPAIR: Track-rollers: dragging not working-rolling properly.
                           Location: kitchen nook.

                           Repair cost estimate: $150±




KITCHEN/LAUNDRY

01. Kitchen Plumbing       NEEDS REPAIR: Faucet handle: minor leakage when operated-repair
                           involves replacing internal parts or entire faucet. Location: kitchen.

                           Repair cost estimate: $100±.




     5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                     Deficiency Report                                            Page 11 of 15

                                     5th Avenue Building Inspections
                      Providing Real Estate, Insurance, Termite & Indoor Air Quality
                       Inspections For Residential, Commercial & New Construction
                                            Ph#: (561) 369-8363




02. Laundry Plumbing         NEEDS REPAIR: Washer shut-off valve handles: broken. Gate valves
                             should be replaced with a lever ball type to improve efficiency.

                             Repair cost estimate: $150±.




POOL/SPA SYSTEM

08. Pool Electrical          NEEDS REPAIR: Bonding wiring for pump motor: missing. Bonding of all
                             metal around pool is required to maintain the same voltage potential per the
                             NEC-consult pool contractor.

                             Repair cost estimate: $150±.




      5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                 UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                   Deficiency Report                                         Page 12 of 15

                                   5th Avenue Building Inspections
                    Providing Real Estate, Insurance, Termite & Indoor Air Quality
                     Inspections For Residential, Commercial & New Construction
                                          Ph#: (561) 369-8363




10. Drain/Skimmer           NEEDS REPAIR: Spa bottom floor drain cover: loose-not secured properly.

                            Repair cost estimate: $100±.




11. Filter/Pipes            REPAIR/REPLACE: Filter damaged-inoperable: internal components.

                            Repair cost estimate: $300±.




      5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                 UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                    Deficiency Report                                       Page 13 of 15

                                     5th Avenue Building Inspections
                      Providing Real Estate, Insurance, Termite & Indoor Air Quality
                       Inspections For Residential, Commercial & New Construction
                                            Ph#: (561) 369-8363




12. Pool/Spa Heater          NEEDS REPAIR: Pool heater digital panel: damaged cover.

                             Repair cost estimate: $150±.




     5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                       Deficiency Report                                     Page 14 of 15

                                    5th Avenue Building Inspections
                     Providing Real Estate, Insurance, Termite & Indoor Air Quality
                      Inspections For Residential, Commercial & New Construction
                                           Ph#: (561) 369-8363


Electric heater inoperable-unable to test-system not working due to damaged pool filter.




03. Pool Equipment             NEEDS REPAIR. Support base: damaged-using
                               temporary-unconventional support.

                               Repair cost estimate: $200±



14. Pool Site                  NEEDS REPAIR: Fence gate: locking hardware damage-inoperable, not
                               closing properly. Location: right side area.

                               Repair cost estimate: $150±.




      5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                 UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
8/20/2010                                     Deficiency Report                                               Page 15 of 15

                                    5th Avenue Building Inspections
                     Providing Real Estate, Insurance, Termite & Indoor Air Quality
                      Inspections For Residential, Commercial & New Construction
                                           Ph#: (561) 369-8363




07. Pump/Motor:    NEEDS REPAIR. Bubbles in jets inside pool indicating air intrusion-requires further evaluation.

Pool pump: Leaking at pump to motor connection.

Repair cost estimate: $300±.




     5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG.
                                UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
Florida Department of Agriculture and Consumer Services
                                                             Division of Agricultural Environmental Services

                                             WOOD-DESTROYING ORGANISMS INSPECTION REPORT

                                                    Section 482.226, Florida Statutes and Chapter 5E-14.142,F.A.C.

                                                                 SECTION 1 - GENERAL INFORMATION
 Inspection Company:
 5th Avenue Building Inspections                                                                                     Business License Number:   JB104982
     Inspection Company Name
                                                                                                                     Phone Number:     (561) 369-8363
     Company Address

7456 Liverpool Ct. Boynton Beach, FL 33472                                                                           Date of Inspection:   XXXXXX
     Company City, State and Zip Code
Inspector's Name and Identification Card Number:                              Joey Caballero                                               JE61018
                                                                                      Print Name                                                     ID Card No.
Address of Property Inspected: XXXXX Avenue, Delray Beach, FL
Structure(s) on Property Inspected: Single Family Home.
Inspection and Report requested by: XXXXXXX
                                                               Name and Contact Information
Report Sent to Requestor and to: Client.
                                                              Name and Contact Information if different from above
                      SECTION 2 - INSPECTION FINDINGS - CONSUMERS SHOULD READ THIS SECTION CAREFULLY
 THIS REPORT IS MADE ON THE BASIS OF WHAT WAS VISIBLE AND READILY ACCESSIBLE AT THE TIME OF INSPECTION AND
 DOES NOT CONSTITUTE A GUARANTEE OF THE ABSENCE OF WOOD-DESTROYING ORGANISMS (WDOs) OR DAMAGE OR
 OTHER EVIDENCE UNLESS THIS REPORT SPECIFICALLY STATES HEREIN THE EXTENT OF SUCH GUARANTEE.
 This report does not cover areas such as, but not limited to, those that are enclosed or inaccessible, areas concealed by wall-coverings, floor coverings,
 furniture, equipment, stored articles, insulation or any portion of the structure in which inspection would necessitate removing or defacing any part of the
 structure.
 This property was not inspected for any fungi other than wood-decaying fungi, and no opinion on health related effects or indoor air quality is provided or
 rendered by this report. Individuals licensed to perform pest control are not required, authorized or licensed to inspect or report for any fungi other than
 wood-destroying fungi, nor to report or comment on health or indoor air quality issues related to any fungi. Persons concerned about these issues should
 consult with a certified industrial hygienist or other person trained and qualified to render such opinions. A wood-destroying organism (WDO) means an
 arthropod or plant life which damages and can reinfest seasoned wood in a structure, namely, termites, powder post beetles, old house borers, and
 wood-decaying fungi.
 NOTE: This is NOT a structural damage report. It should be understood that there may be damage, including possible hidden damage present.
 FURTHER INVESTIGATION BY QUALIFIED EXPERTS OF THE BUILDING TRADE SHOULD BE MADE TO DETERMINE THE
 STRUCTURAL SOUNDNESS OF THE PROPERTY.

 Based on a visual inspection of accessible areas, the following findings were observed:
 (See Page 2, Section 3 to determine which areas of the inspected structure(s) may have been inaccessible.)

A.         NO visible signs of WDO(s) (live, evidence or damage) observed.

B. X VISIBLE evidence of WDO(s) was observed as follows:

            1. LIVE WDO(s) :
                                        (Common Name of Organism and Location)
      X     2. EVIDENCE of WDO(s) (dead wood-destroying insects parts, frass, shelter tubes, exit holes, or other evidence):
              1. Wood Destroying Organism frass/galleries: attic several areas.
           2. Wood decaying fungi (damaged wood): exterior fascia trim at front and right side at numerous areas.
                                        (Common Name, Description and Location - Describe evidence)


      X     3. DAMAGE caused by WDO(s) was observed and noted as follows:
              1. Wood Destroying Organism frass/galleries: attic several areas.
           2. Wood decaying fungi (damaged wood): exterior fascia trim at front and right side at numerous areas.
                                        (Common Name, Description and Location of all visible damage - Describe damage)




 DACS 13645, Rev 05/08
 Page 1 of 7
SECTION 3 - OBSTRUCTIONS AND INACCESSIBLE AREAS: The following areas of the structure(s) inspected were obstructed or inaccessible.
NO INFORMATION on the status of wood-destroying organisms or damage from wood-destroying organisms in these areas is provided in this
report.
 In addition to those areas described in consumer information on Page 1, Section 2; the following specific areas were not visible
 and/or accessible for inspection. The descriptions and reasons for inaccessibility are stated below:

    X Attic                      SPECIFIC AREAS: Unable to be fully traverse attic/roof structure areas.
                                  REASON: Insulation, general wiring, HVAC system, structure design-clearance of areas less than 48"
                                 height and 22" in width.

    X Interior                   SPECIFIC AREAS: Interior baseboards, walls, and floor areas.
                                  REASON: Covered with furniture, personal items, cabinets, wall coverings, and floor coverings.

    X Exterior                   SPECIFIC AREAS: Perimeter foundation, areas above roof or (10) feet above ground floor.
                                  REASON: Landscaping, shrubbery, mulch, wall siding, and obstructions.

         Crawlspace              SPECIFIC AREAS: N/A
                                  REASON:

    X Other:                     SPECIFIC AREAS: General access disclaimer.
                                  REASON: Dismantling and/or destructive work to provide access not within the scope of inspection.

                                      SECTION 4 - NOTICE OF INSPECTION AND TREATMENT INFORMATION

 EVIDENCE of previous treatment observed:          [ ] Yes      [X] No         If Yes, the structure exhibits evidence of previous treatment.
 List what was observed:
                                                                (State what visible evidence was observed to suggest previous treatment)

 NOTE: The inspecting company can give no assurance with regard to work done by other companies. The company that performed the treatment
 should be contacted for information on treatment history and any warranty or service agreement which may be in place.

 A Notice of Inspection has been affixed to the structure at: Attic access.
                                                                                      (State the location)

  This Company has treated the structure(s) at the time of the inspection [ ] Yes          [X] No
          If Yes: Common name of organism treated:
                                                                         (Common name of organism)
          Name of Pesticide Used:                                                                 Terms and Conditions of Treatment:

           Method of treatment:            [ ] Whole structure           [ ] Spot treatment:

          Specify Treatment Notice Location:

                                           SECTION 5 - COMMENTS AND FINANCIAL DISCLOSURE
 Comments:
 No warranty or guarantee is expressed or implied. Warranties are available from Pest Control Company who provides the treatment or have
 previously treated the property. Recommend yearly inspection since there are numerous areas not readily accessible during the initial inspection.

 Neither the company (licensee) nor the inspector has any financial interest in the property inspected or is associated in any way in the transaction or with any
 party to the transaction other than for inspection purposes.


Signature of Licensee or Agent:
                                             Joey Caballero                                                                  Date:     XXXXXXX




Address of Property Inspected:     XXXXXX, Delray Beach, FL                                                     Inspection Date:       XXXXXXX




 DACS 13645, Rev 05/08
 Page 2 of 7
DACS 13645, Rev 05/08
Page 3 of 7
DACS 13645, Rev 05/08
Page 4 of 7
DACS 13645, Rev 05/08
Page 5 of 7
DACS 13645, Rev 05/08
Page 6 of 7
DACS 13645, Rev 05/08
Page 7 of 7

More Related Content

Similar to Sample report

Sum 2700 graceland st chvy chs md 20800
Sum 2700 graceland st chvy chs md 20800Sum 2700 graceland st chvy chs md 20800
Sum 2700 graceland st chvy chs md 20800Andrew Ling
 
A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010orderinspections
 
A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010orderinspections
 
2012 sample report 50-55 year old house
2012 sample report 50-55 year old house2012 sample report 50-55 year old house
2012 sample report 50-55 year old housetk99
 
2012 sample report 50year old house
2012 sample report 50year old house2012 sample report 50year old house
2012 sample report 50year old housetk99
 
FORENSIC ANALYSIS OF COLLAPSE OF SURFSIDE CONDMINIMUM, MIAMI
FORENSIC ANALYSIS OF COLLAPSE OF SURFSIDE CONDMINIMUM, MIAMIFORENSIC ANALYSIS OF COLLAPSE OF SURFSIDE CONDMINIMUM, MIAMI
FORENSIC ANALYSIS OF COLLAPSE OF SURFSIDE CONDMINIMUM, MIAMIIRJET Journal
 
2700 graceland st chevy chase md 20800
2700 graceland st chevy chase md 208002700 graceland st chevy chase md 20800
2700 graceland st chevy chase md 20800Andrew Ling
 
Nano-Clear Protects Concrete Block in Shower Stall
Nano-Clear Protects Concrete Block in Shower StallNano-Clear Protects Concrete Block in Shower Stall
Nano-Clear Protects Concrete Block in Shower StallIndustrial Solutions USA
 
Apex Inspections Sample Report 2010
Apex Inspections Sample Report 2010Apex Inspections Sample Report 2010
Apex Inspections Sample Report 2010orderinspections
 
Conductive Flooring
Conductive FlooringConductive Flooring
Conductive FlooringRana Imran
 
HT & LT Bus Ducts Manufacturer in Telangana and Andhra Pradesh
HT & LT Bus Ducts Manufacturer in Telangana and Andhra PradeshHT & LT Bus Ducts Manufacturer in Telangana and Andhra Pradesh
HT & LT Bus Ducts Manufacturer in Telangana and Andhra PradeshMohit Bathineni
 
House Inspection Report
House Inspection ReportHouse Inspection Report
House Inspection Reportpnnazz
 
Piping sample report
Piping sample reportPiping sample report
Piping sample reportram111eg
 
Bruperite Testing Report
Bruperite Testing ReportBruperite Testing Report
Bruperite Testing Reportstrama3
 

Similar to Sample report (20)

Sum 2700 graceland st chvy chs md 20800
Sum 2700 graceland st chvy chs md 20800Sum 2700 graceland st chvy chs md 20800
Sum 2700 graceland st chvy chs md 20800
 
Termite Report for 4670 Glen St La Mesa CA
Termite Report for 4670 Glen St La Mesa CATermite Report for 4670 Glen St La Mesa CA
Termite Report for 4670 Glen St La Mesa CA
 
A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010
 
A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010A thru Z Inspections Sample Report 2010
A thru Z Inspections Sample Report 2010
 
2012 sample report 50-55 year old house
2012 sample report 50-55 year old house2012 sample report 50-55 year old house
2012 sample report 50-55 year old house
 
2012 sample report 50year old house
2012 sample report 50year old house2012 sample report 50year old house
2012 sample report 50year old house
 
FORENSIC ANALYSIS OF COLLAPSE OF SURFSIDE CONDMINIMUM, MIAMI
FORENSIC ANALYSIS OF COLLAPSE OF SURFSIDE CONDMINIMUM, MIAMIFORENSIC ANALYSIS OF COLLAPSE OF SURFSIDE CONDMINIMUM, MIAMI
FORENSIC ANALYSIS OF COLLAPSE OF SURFSIDE CONDMINIMUM, MIAMI
 
1 samplereport
1 samplereport1 samplereport
1 samplereport
 
2700 graceland st chevy chase md 20800
2700 graceland st chevy chase md 208002700 graceland st chevy chase md 20800
2700 graceland st chevy chase md 20800
 
Nano-Clear Protects Concrete Block in Shower Stall
Nano-Clear Protects Concrete Block in Shower StallNano-Clear Protects Concrete Block in Shower Stall
Nano-Clear Protects Concrete Block in Shower Stall
 
Eifs Sample
Eifs SampleEifs Sample
Eifs Sample
 
Apex Inspections Sample Report 2010
Apex Inspections Sample Report 2010Apex Inspections Sample Report 2010
Apex Inspections Sample Report 2010
 
Apex sample report
Apex sample reportApex sample report
Apex sample report
 
Sample
SampleSample
Sample
 
Conductive Flooring
Conductive FlooringConductive Flooring
Conductive Flooring
 
HT & LT Bus Ducts Manufacturer in Telangana and Andhra Pradesh
HT & LT Bus Ducts Manufacturer in Telangana and Andhra PradeshHT & LT Bus Ducts Manufacturer in Telangana and Andhra Pradesh
HT & LT Bus Ducts Manufacturer in Telangana and Andhra Pradesh
 
House Inspection Report
House Inspection ReportHouse Inspection Report
House Inspection Report
 
Property Inspection Report
Property Inspection ReportProperty Inspection Report
Property Inspection Report
 
Piping sample report
Piping sample reportPiping sample report
Piping sample report
 
Bruperite Testing Report
Bruperite Testing ReportBruperite Testing Report
Bruperite Testing Report
 

Recently uploaded

How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.Curtis Poe
 
Time Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directionsTime Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directionsNathaniel Shimoni
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc
 
[Webinar] SpiraTest - Setting New Standards in Quality Assurance
[Webinar] SpiraTest - Setting New Standards in Quality Assurance[Webinar] SpiraTest - Setting New Standards in Quality Assurance
[Webinar] SpiraTest - Setting New Standards in Quality AssuranceInflectra
 
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptxPasskey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptxLoriGlavin3
 
How to Effectively Monitor SD-WAN and SASE Environments with ThousandEyes
How to Effectively Monitor SD-WAN and SASE Environments with ThousandEyesHow to Effectively Monitor SD-WAN and SASE Environments with ThousandEyes
How to Effectively Monitor SD-WAN and SASE Environments with ThousandEyesThousandEyes
 
Manual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance AuditManual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance AuditSkynet Technologies
 
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024BookNet Canada
 
So einfach geht modernes Roaming fuer Notes und Nomad.pdf
So einfach geht modernes Roaming fuer Notes und Nomad.pdfSo einfach geht modernes Roaming fuer Notes und Nomad.pdf
So einfach geht modernes Roaming fuer Notes und Nomad.pdfpanagenda
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfMounikaPolabathina
 
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Mark Goldstein
 
(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...
(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...
(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...AliaaTarek5
 
UiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to HeroUiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to HeroUiPathCommunity
 
A Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersA Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersNicole Novielli
 
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...Wes McKinney
 
Long journey of Ruby standard library at RubyConf AU 2024
Long journey of Ruby standard library at RubyConf AU 2024Long journey of Ruby standard library at RubyConf AU 2024
Long journey of Ruby standard library at RubyConf AU 2024Hiroshi SHIBATA
 
Scale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterScale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterMydbops
 
Take control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test SuiteTake control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test SuiteDianaGray10
 
Generative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdfGenerative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdfIngrid Airi González
 
Data governance with Unity Catalog Presentation
Data governance with Unity Catalog PresentationData governance with Unity Catalog Presentation
Data governance with Unity Catalog PresentationKnoldus Inc.
 

Recently uploaded (20)

How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.
 
Time Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directionsTime Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directions
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
 
[Webinar] SpiraTest - Setting New Standards in Quality Assurance
[Webinar] SpiraTest - Setting New Standards in Quality Assurance[Webinar] SpiraTest - Setting New Standards in Quality Assurance
[Webinar] SpiraTest - Setting New Standards in Quality Assurance
 
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptxPasskey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptx
 
How to Effectively Monitor SD-WAN and SASE Environments with ThousandEyes
How to Effectively Monitor SD-WAN and SASE Environments with ThousandEyesHow to Effectively Monitor SD-WAN and SASE Environments with ThousandEyes
How to Effectively Monitor SD-WAN and SASE Environments with ThousandEyes
 
Manual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance AuditManual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance Audit
 
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
 
So einfach geht modernes Roaming fuer Notes und Nomad.pdf
So einfach geht modernes Roaming fuer Notes und Nomad.pdfSo einfach geht modernes Roaming fuer Notes und Nomad.pdf
So einfach geht modernes Roaming fuer Notes und Nomad.pdf
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdf
 
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
 
(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...
(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...
(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...
 
UiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to HeroUiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to Hero
 
A Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersA Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software Developers
 
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
 
Long journey of Ruby standard library at RubyConf AU 2024
Long journey of Ruby standard library at RubyConf AU 2024Long journey of Ruby standard library at RubyConf AU 2024
Long journey of Ruby standard library at RubyConf AU 2024
 
Scale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterScale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL Router
 
Take control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test SuiteTake control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test Suite
 
Generative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdfGenerative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdf
 
Data governance with Unity Catalog Presentation
Data governance with Unity Catalog PresentationData governance with Unity Catalog Presentation
Data governance with Unity Catalog Presentation
 

Sample report

  • 1. 8/20/2010 Deficiency Report Page 1 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 SAMPLE REPORT SITE/GROUNDS 05. Sprinkler System NEEDS REPAIR: Inoperable-not priming. Heads: spraying onto structure-evidence of flooding on areas adjoining enclosed room. Location: exterior of enclosed room. Repair cost estimate: $200±. 08. Driveway NEEDS REPAIR: Asphalt driveway: significant damaged-deterioration. Repair cost estimate: $400±. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 2. 8/20/2010 Deficiency Report Page 2 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 EXTERIOR AREAS 04. Stucco Walls NEEDS REPAIR: Frame wall: significant cracks-risk of water intrusion. Location: outside of master bath-scattered locations. Repairperson should check all perimeter areas prior to making repairs. Repair cost estimate: $300±. 09. Exterior Areas NEEDS REPAIR: Metal post: loose-not set properly, needs permanent repairs. Location: porch at front. Repair cost estimate: $300±. ROOF/ATTIC 05. Roof Edge/Overhang NEEDS REPAIR: Leak stains indicating evidence of edge leak on exterior overhang. Location: 1. 2nd floor over garage door. 2. 2nd floor left side. 3. rear over balcony. Budget additional expense for removal of gutters attached to fascia board to facilitate repairs. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 3. 8/20/2010 Deficiency Report Page 3 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 Leak stains and wood rot indicating evidence of edge leak on exterior overhang. Location: 2nd floor balcony. Repair cost estimate: $2,500±. HEATING/COOLING 08. Air Handler Unit NEEDS REPAIR: Coils-interior: dirt-debris buildup. Location of unit: A/C closet. Repair cost estimate: $300±. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 4. 8/20/2010 Deficiency Report Page 4 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 09. Ductwork System NEEDS REPAIR: Attic ductwork: damaged, laying on ground-should be raised, leak stains-evidence of leakage, cloth duct tape on connections-temporary fix, rip-tear on outer protective wrapping. Location: including but not limited to (3) small sections near attic hatch-sections should be replaced. FPL should be contacted for a ductwork system test and home energy rebate survey www.fpl.com/residential/savings/index.shtml. Repair cost estimate: $500±. 14. Condensate System NEEDS REPAIR: Exterior drain: missing trap-creating a flood next to exterior wall/slab. Requires reposition-extension or use splashblock minimum 12" away from structure or equipment. Location: by A/C condenser unit. Repair cost estimate: $100±. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 5. 8/20/2010 Deficiency Report Page 5 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 NEEDS REPAIR: Stains-grime indicating air leakage or not properly insulated. Location: guest bedroom closet above front entry. Repairs may involve cleaning-replacement of affected materials and re-sealing entire vent connection using antimicrobial mastic coating sealant. Repair cost estimate: $150±. 15. Support/Plenum Base NEEDS REPAIR: Support base: insulation loose-moisture stains due to prior leakage, filter frame loose. Location: A/C closet. Should be sealed with antimicrobial mastic coating due to moist air flow and exposure to condensation. NEEDS REPAIR: Microbial growth-high humidity splotches buildup on support base, wall behind air handler, ceiling penetrations. Minimal remediation would require removal-cleaning and disinfecting affected area per EPA guidelines (www.epa.gov/mold/moldcleanup.html). Location: garage. Repair cost estimate: Depends on mold remediation assessment's and estimating process 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 6. 8/20/2010 Deficiency Report Page 6 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 ELECTRICAL SYSTEM 08. Receptacles NEEDS REPAIR: Weatherproof cover: missing, water intrusion. Location of outlet: rear side area. Hot and neutral wires reversed-unsafe wiring (reverse polarity). Outlet working with risk of shock hazard. Location of outlet: left/front guest bedroom. Ungrounded-unsafe wiring (missing ground). Outlet working with risk of shock hazard. Location of outlet: master bedroom. Repair cost estimate: $150±. 10. General Wiring NEEDS REPAIR: Electrical wiring: splices exposed-missing cover. Location: exterior rear by pool transformer panel. A/C #1 breaker burnt-scorched. Location of panel: exterior by electric 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 7. 8/20/2010 Deficiency Report Page 7 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 meter. Repair cost estimate: $200±. 13. Light Fixtures NEEDS REPAIR: Fluorescent lights: inoperable-replace bulbs first. Location: kitchen. Fluorescent lights: tube bulbs flickering. Location: laundry room. Repair cost estimate: $300±. PLUMBING SYSTEM 04. Water Heater NEEDS REPAIR: Pressure relief discharge pipe: reduced in size-must be approved 3/4". On interior installation: extent to exterior to prevent random dripping onto interior contents. Repair cost estimate: $150±. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 8. 8/20/2010 Deficiency Report Page 8 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 BATHROOMS 01. Bathrooms NEEDS REPAIR: Water hammering noise when hot water faucets are turned off rapidly. Most of the time this condition can be corrected by closing main valve and opening all faucet fixtures to allow air chambers to fill with air or installing air chambers arrestors. Location: master bath. Repair cost estimate: $200±. 03. Shower/Tub Stall NEEDS REPAIR: Tub & shower tiles: grout failure-fungus, gaps, and grime buildup on wall next to guest tub. Location: guest-master bathrooms. Repair cost estimate: $300±. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 9. 8/20/2010 Deficiency Report Page 9 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 INTERIOR AREAS 04. Interior Areas NEEDS REPAIR: Moisture evidence-stains-evidence of leakage, plaster damage on wall under windows. Location: enclosed room. Requires further evaluation. Repair cost estimate: $300±. 05. Windows NEEDS REPAIR: Crank missing, damaged-inoperable. Location: including but not limited to kitchen, living room, guest bath, enclosed room. Bottom frame: water intrusion-evidence of leakage at bottom frame, carpet tack strips stained. Repairs may involve waterproofing exterior-interior frame flashing/fasteners. Location: 1. master bedroom door (2). 2. Dining room. Repair cost estimate: $300±. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 10. 8/20/2010 Deficiency Report Page 10 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 09. Slider Doors NEEDS REPAIR: Track-rollers: dragging not working-rolling properly. Location: kitchen nook. Repair cost estimate: $150± KITCHEN/LAUNDRY 01. Kitchen Plumbing NEEDS REPAIR: Faucet handle: minor leakage when operated-repair involves replacing internal parts or entire faucet. Location: kitchen. Repair cost estimate: $100±. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 11. 8/20/2010 Deficiency Report Page 11 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 02. Laundry Plumbing NEEDS REPAIR: Washer shut-off valve handles: broken. Gate valves should be replaced with a lever ball type to improve efficiency. Repair cost estimate: $150±. POOL/SPA SYSTEM 08. Pool Electrical NEEDS REPAIR: Bonding wiring for pump motor: missing. Bonding of all metal around pool is required to maintain the same voltage potential per the NEC-consult pool contractor. Repair cost estimate: $150±. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 12. 8/20/2010 Deficiency Report Page 12 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 10. Drain/Skimmer NEEDS REPAIR: Spa bottom floor drain cover: loose-not secured properly. Repair cost estimate: $100±. 11. Filter/Pipes REPAIR/REPLACE: Filter damaged-inoperable: internal components. Repair cost estimate: $300±. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 13. 8/20/2010 Deficiency Report Page 13 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 12. Pool/Spa Heater NEEDS REPAIR: Pool heater digital panel: damaged cover. Repair cost estimate: $150±. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 14. 8/20/2010 Deficiency Report Page 14 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 Electric heater inoperable-unable to test-system not working due to damaged pool filter. 03. Pool Equipment NEEDS REPAIR. Support base: damaged-using temporary-unconventional support. Repair cost estimate: $200± 14. Pool Site NEEDS REPAIR: Fence gate: locking hardware damage-inoperable, not closing properly. Location: right side area. Repair cost estimate: $150±. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 15. 8/20/2010 Deficiency Report Page 15 of 15 5th Avenue Building Inspections Providing Real Estate, Insurance, Termite & Indoor Air Quality Inspections For Residential, Commercial & New Construction Ph#: (561) 369-8363 07. Pump/Motor: NEEDS REPAIR. Bubbles in jets inside pool indicating air intrusion-requires further evaluation. Pool pump: Leaking at pump to motor connection. Repair cost estimate: $300±. 5TH AVENUE BUILDING INSPECTIONS INC. * ""PROTECTING HOMEBUYERS SINCE 1989"" * www.HOUSEINSPECTORS.ORG. UNAUTHORIZED USE OF THIS REPORT IS PROHIBITED
  • 16. Florida Department of Agriculture and Consumer Services Division of Agricultural Environmental Services WOOD-DESTROYING ORGANISMS INSPECTION REPORT Section 482.226, Florida Statutes and Chapter 5E-14.142,F.A.C. SECTION 1 - GENERAL INFORMATION Inspection Company: 5th Avenue Building Inspections Business License Number: JB104982 Inspection Company Name Phone Number: (561) 369-8363 Company Address 7456 Liverpool Ct. Boynton Beach, FL 33472 Date of Inspection: XXXXXX Company City, State and Zip Code Inspector's Name and Identification Card Number: Joey Caballero JE61018 Print Name ID Card No. Address of Property Inspected: XXXXX Avenue, Delray Beach, FL Structure(s) on Property Inspected: Single Family Home. Inspection and Report requested by: XXXXXXX Name and Contact Information Report Sent to Requestor and to: Client. Name and Contact Information if different from above SECTION 2 - INSPECTION FINDINGS - CONSUMERS SHOULD READ THIS SECTION CAREFULLY THIS REPORT IS MADE ON THE BASIS OF WHAT WAS VISIBLE AND READILY ACCESSIBLE AT THE TIME OF INSPECTION AND DOES NOT CONSTITUTE A GUARANTEE OF THE ABSENCE OF WOOD-DESTROYING ORGANISMS (WDOs) OR DAMAGE OR OTHER EVIDENCE UNLESS THIS REPORT SPECIFICALLY STATES HEREIN THE EXTENT OF SUCH GUARANTEE. This report does not cover areas such as, but not limited to, those that are enclosed or inaccessible, areas concealed by wall-coverings, floor coverings, furniture, equipment, stored articles, insulation or any portion of the structure in which inspection would necessitate removing or defacing any part of the structure. This property was not inspected for any fungi other than wood-decaying fungi, and no opinion on health related effects or indoor air quality is provided or rendered by this report. Individuals licensed to perform pest control are not required, authorized or licensed to inspect or report for any fungi other than wood-destroying fungi, nor to report or comment on health or indoor air quality issues related to any fungi. Persons concerned about these issues should consult with a certified industrial hygienist or other person trained and qualified to render such opinions. A wood-destroying organism (WDO) means an arthropod or plant life which damages and can reinfest seasoned wood in a structure, namely, termites, powder post beetles, old house borers, and wood-decaying fungi. NOTE: This is NOT a structural damage report. It should be understood that there may be damage, including possible hidden damage present. FURTHER INVESTIGATION BY QUALIFIED EXPERTS OF THE BUILDING TRADE SHOULD BE MADE TO DETERMINE THE STRUCTURAL SOUNDNESS OF THE PROPERTY. Based on a visual inspection of accessible areas, the following findings were observed: (See Page 2, Section 3 to determine which areas of the inspected structure(s) may have been inaccessible.) A. NO visible signs of WDO(s) (live, evidence or damage) observed. B. X VISIBLE evidence of WDO(s) was observed as follows: 1. LIVE WDO(s) : (Common Name of Organism and Location) X 2. EVIDENCE of WDO(s) (dead wood-destroying insects parts, frass, shelter tubes, exit holes, or other evidence): 1. Wood Destroying Organism frass/galleries: attic several areas. 2. Wood decaying fungi (damaged wood): exterior fascia trim at front and right side at numerous areas. (Common Name, Description and Location - Describe evidence) X 3. DAMAGE caused by WDO(s) was observed and noted as follows: 1. Wood Destroying Organism frass/galleries: attic several areas. 2. Wood decaying fungi (damaged wood): exterior fascia trim at front and right side at numerous areas. (Common Name, Description and Location of all visible damage - Describe damage) DACS 13645, Rev 05/08 Page 1 of 7
  • 17. SECTION 3 - OBSTRUCTIONS AND INACCESSIBLE AREAS: The following areas of the structure(s) inspected were obstructed or inaccessible. NO INFORMATION on the status of wood-destroying organisms or damage from wood-destroying organisms in these areas is provided in this report. In addition to those areas described in consumer information on Page 1, Section 2; the following specific areas were not visible and/or accessible for inspection. The descriptions and reasons for inaccessibility are stated below: X Attic SPECIFIC AREAS: Unable to be fully traverse attic/roof structure areas. REASON: Insulation, general wiring, HVAC system, structure design-clearance of areas less than 48" height and 22" in width. X Interior SPECIFIC AREAS: Interior baseboards, walls, and floor areas. REASON: Covered with furniture, personal items, cabinets, wall coverings, and floor coverings. X Exterior SPECIFIC AREAS: Perimeter foundation, areas above roof or (10) feet above ground floor. REASON: Landscaping, shrubbery, mulch, wall siding, and obstructions. Crawlspace SPECIFIC AREAS: N/A REASON: X Other: SPECIFIC AREAS: General access disclaimer. REASON: Dismantling and/or destructive work to provide access not within the scope of inspection. SECTION 4 - NOTICE OF INSPECTION AND TREATMENT INFORMATION EVIDENCE of previous treatment observed: [ ] Yes [X] No If Yes, the structure exhibits evidence of previous treatment. List what was observed: (State what visible evidence was observed to suggest previous treatment) NOTE: The inspecting company can give no assurance with regard to work done by other companies. The company that performed the treatment should be contacted for information on treatment history and any warranty or service agreement which may be in place. A Notice of Inspection has been affixed to the structure at: Attic access. (State the location) This Company has treated the structure(s) at the time of the inspection [ ] Yes [X] No If Yes: Common name of organism treated: (Common name of organism) Name of Pesticide Used: Terms and Conditions of Treatment: Method of treatment: [ ] Whole structure [ ] Spot treatment: Specify Treatment Notice Location: SECTION 5 - COMMENTS AND FINANCIAL DISCLOSURE Comments: No warranty or guarantee is expressed or implied. Warranties are available from Pest Control Company who provides the treatment or have previously treated the property. Recommend yearly inspection since there are numerous areas not readily accessible during the initial inspection. Neither the company (licensee) nor the inspector has any financial interest in the property inspected or is associated in any way in the transaction or with any party to the transaction other than for inspection purposes. Signature of Licensee or Agent: Joey Caballero Date: XXXXXXX Address of Property Inspected: XXXXXX, Delray Beach, FL Inspection Date: XXXXXXX DACS 13645, Rev 05/08 Page 2 of 7
  • 18. DACS 13645, Rev 05/08 Page 3 of 7
  • 19. DACS 13645, Rev 05/08 Page 4 of 7
  • 20. DACS 13645, Rev 05/08 Page 5 of 7
  • 21. DACS 13645, Rev 05/08 Page 6 of 7
  • 22. DACS 13645, Rev 05/08 Page 7 of 7