2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
1
Field-based Control : Freedom to
Choose the Ultimate DCS
John Rezabek
Process Control Specialist
Ashland, Inc.
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
2
What is Fieldbus Again?
• Fieldbus is a
communication protocol,
right?
• The “OSI Model”: Seven
Layers for “Open
Systems Interconnection”
• Foundation fieldbus
uniquely adds the “User
Layer” – why?
Physical Layer
Data Link Layer
Network Layer
Transport Layer
Session Layer
Presentation Layer
Application Layer
USER LAYER
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
3
Why Have a “User Layer”?
• Analog In, Analog Out, Digital In, Digital Out
• Do some scaling, linearization, filtering, configure fault
states & propagation, etc. outside the host / DCS
• Devices are “peers” with the host’s interface
• ARTHM, ISEL, SGCR, INT
• Relieve the HOST DCS of some compensation,
characterization, totalizers, etc.
• PID, CSEL, SPLTR
• Configure CONTROL IN FIELD DEVICES, using the
world’s only vendor-independent totally distributed
digital control system
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
4
Why “Distributed” Control?
• 1980’s costs for CPU and memory meant
many loops-per-controller for reasonable
“cost per loop”
• Users of the day wanted “single loop
integrity” = one fault > loose no more than
one loop
• Controller, I/O, and Network Redundancy
• Commercial model became “functionally”
distributed
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
5
The Need For Reliability
ARC Insight
10th June 2010
The global process industry loses $20
billion, or five percent of annual production, due
to unscheduled downtime and poor quality.
ARC estimates that almost 80 percent of these
losses are preventable, with 40 percent largely
due to operator error.
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
6
Fieldbus = Truly Distributed Control
• Foundation Fieldbus allows return to true
single-loop integrity
• Robust control independent of DCS, needs
only power, devices, and schedule (“LAS”)
• Intelligence of devices is
exploited, employing signal
status, diagnostics
• But – is it truly more reliable?
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
7
Fewer Components = Longer MTBF
PSU
PSU
 AND Foundation fieldbus
also communicates signal
status with every scan,
which enables smart mode
shedding, bumpless
transfer and initialization.
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
8
Digital All the Way
- Digital Closed Loop Control
Fieldbus
eliminates the
analog signal
Validity:
Good/Bad/
Uncertain
Initiate Fault-
State Command
Limited: High/Low
Bumpless Transfer
Windup Protection
Fault-state Status
Designed for
process control
Default behavior on Bad or
Uncertain PV is shed mode to
MAN and hold last output –
the same macrocycle the fault is
detected.
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
9
Process Variable Validity
Hardwired
 Device drives current <4
mA or >20 mA on device
failure
– Looks like process problem
 PID counteracts thus
tripping the loop
 Operator cannot tell the
difference between a
process alarm and a
device alarm
Fieldbus
 Device health indicated by
associated status
 Controller holds last
position on device failure
– Shutdown is optional
 Operator can easily
distinguish process
problem from a device
problem
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
10
FF – A Standard for High Availability
 Distributed Control, Speed, & Determinism
 Real-time value and status
 Status Propagation (CIF & CIC)
 Validated information
Quality and limits
 Windup protection
 Bumpless transfer for valves
 Fault-state for valves
 etc.
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
11
SIL - Putting a Number on Reliability
• Ed Marszal, ISA 84.001 and IEC 61508 expert,
author and president of Kenexis consultants
• Entered reliability numbers into reliability
models for safety system calculations
• “ FF is significantly better – MTTF (mean time
to fail) of 48.2 [years] versus MTTF of 15.9
[years]”
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
12
Reliability
Analogue
With CIF
15.9y
48.2y
MTTF
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
13
Customer Experience
CIF
enabled
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
14
Customer Experience
FOUNDATION Fieldbus
CIF with inherent backup capability
prevented 2 incorrect plant
shutdowns, which would have
resulted from communication
interruptions.
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
15
But . . . Isn’t Fieldbus “Slow”?
• Early devices had longer function block
execution times
• Many early jobs used FF for IO only
• Host PID to FF Macrocycle sync is not easily
addressed – oversample?
• Variable latencies, overly busy segments
• Add commissioning, diagnostics, downloads
• = Many bogged down segments
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
16
Control In The Field Study
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
17
Comparison
CIF
enabled
No CIF
125
625
105
ms
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
18
Settling Times: Fastest Process
50
54
58
62
Process output (%)
0 4 8 12 16 20
Time (seconds)
60%
Setpoint Case 1 - CIF
Case 3 - Control
in DCS (async)
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
19
Settling Times: Very Fast Process
50
54
58
62
Process output (%)
0 4 8 12 16 20
Time (seconds)
Setpoint Case 1 - CIF
Case 3 - Control
in DCS (async)
55%
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
20
Settling Times: Fast Process
50
54
58
62
Process output (%)
0 4 8 12 16 20
Time (seconds)
Setpoint Case 1 - CIF
Case 3 - Control
in DCS (async)
66%
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
21
Settling Times: Medium Process
50
54
58
62
Process output (%)
0 4 8 12 16 20
Time (seconds)
Setpoint Case 1 - CIF
Case 3 - Control
in DCS (async)
39%
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
22
Presence Of Disturbance: Fastest Process
Process output (%)
40 50 60 70 80 90 100
Time (seconds)
Setpoint Case 1 - CIF
Case 3 - Control
in DCS (async)
56
58
60
66
62
64
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
23
Presence Of Disturbance: Different Processes
Fastest
1.811
2.132
0.517
0.82
0.642
1.058
0.231
0.53
65% better
50% better
55% better
35% better
Very Fast
Fast
Medium
Setpoint CIF
1.811 control in
DCS (async)
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
24
ISC Study on Control in the Field
“Control in the field:
analysis of performance
benefits” study from ISC
(industrial systems and
control)
40-60% faster settling time
on setpoint change
30-50% better disturbance
rejection
Most significant for fast
processes (flow and
pressure)
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
25
Impact of Tighter Control Loop
Manual
Pneumatic
Analogue
Digital
Control limit
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
26
Recommended For Fast Loop Response
Control in the field using
FOUNDATION fieldbus technology is
recommended by SGSI for simple and cascading
loops, not for complex loops.
Major benefits identified by SGSI are reduced
process controller loading, reduced network
traffic enabling more loops per segment, as
well as very fast loop response.
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
27
Empirical Studies: CIF Fast as 4-20
Host
Host
Host
Host
Study by Daugherty, Coughran, and Ford,
“Effects of Macrocycle Time and Sampling
Rates on Control Loop Performance”
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
28
8 simple loops, CIC
Study by Daugherty, Coughran, and Ford,
“Effects of Macrocycle Time and Sampling
Rates on Control Loop Performance”
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
29
Same 8 loops, CIF (valve positioner)
Study by Daugherty, Coughran, and Ford,
“Effects of Macrocycle Time and Sampling
Rates on Control Loop Performance”
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
32
Blower – Combustion Air to Boiler
• Keeping the Blower out of the surge
region means a more stable flow
• More stable flow allows running closer to
constraints
• Running closer to constraints means less
fuel, CO2
AIR TO BOILER
AIR BLOWERPREHEATER
TOBURNERS
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
33
Inside “peak pressure” line, flow is unstable
Peak Pressure
Desired Flow fell here
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
34
Field-based control of blow-off valve
• Controls total flow
• Allows operation
close to low-flow
BMS trip point
• Saves fuel costs
and reduces CO2
emissions
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
35
Surge Control Scheme
Blow-off
Flow
Flow to
Burner
FIC
Inlet
Louvers
Σ FIC
(Total Flow)
Blow-off
Valve
Discharge
Pressure SGCR SP
PT (Discharge)
FT1
FT2
Blow-off Valve Pos.
Inlet Louver Positioner
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
36
Blower Anti-surge scheme
Flow to Burner
Total Flow
Setpoint
Total Flow
Controller
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
38
10,000 HP Turbine / Blower Anti-surge
• Large critical
un-spared
asset
• Typically runs
at 5000 to 7000
RPM
• Expensive to
repair; lost
production
even more
expensive
2012 End User Seminar
Fieldbus Foundation
© 1994 – 2012 Fieldbus Foundation
44
Summary
• FF was specified & designed to deliver
robust control by default – STANDARDIZED
across suppliers
• Control in Field Devices is being used in
critical process applications with fast cycle
time requirements
• Modern devices are executing function
blocks faster than ever
• (note: like cars, there are Yugos and Porches, so
choose according to your needs)

Más contenido relacionado

La actualidad más candente

Petrobras rom demonstration miguel borges - petrobras
Petrobras rom demonstration   miguel borges - petrobrasPetrobras rom demonstration   miguel borges - petrobras
Petrobras rom demonstration miguel borges - petrobrasFieldComm Group
 
FOUNDATION for ROM End User Perspective
FOUNDATION for ROM End User PerspectiveFOUNDATION for ROM End User Perspective
FOUNDATION for ROM End User PerspectiveFieldComm Group
 
Fieldbus Foundation Celebrates 20 Years!
Fieldbus Foundation Celebrates 20 Years!Fieldbus Foundation Celebrates 20 Years!
Fieldbus Foundation Celebrates 20 Years!FieldComm Group
 
Interoperable ROM DCS Integration
Interoperable ROM DCS IntegrationInteroperable ROM DCS Integration
Interoperable ROM DCS IntegrationFieldComm Group
 
Larry o brien fieldbus foundation english
Larry o brien fieldbus foundation englishLarry o brien fieldbus foundation english
Larry o brien fieldbus foundation englishFieldComm Group
 
Training and Education Presentation
Training and Education PresentationTraining and Education Presentation
Training and Education PresentationFieldComm Group
 
Foundation for rom general assembly
Foundation for rom general assemblyFoundation for rom general assembly
Foundation for rom general assemblyFieldComm Group
 
The Fieldbus Diagnostics Difference
The Fieldbus Diagnostics DifferenceThe Fieldbus Diagnostics Difference
The Fieldbus Diagnostics DifferenceFieldComm Group
 
Control in the Field - Feb 2011
Control in the Field - Feb 2011Control in the Field - Feb 2011
Control in the Field - Feb 2011FieldComm Group
 
Industrial Automation Infrastructure
Industrial Automation InfrastructureIndustrial Automation Infrastructure
Industrial Automation InfrastructurePanduit
 
Plant Wide Benefits of Ethernet IP
Plant Wide Benefits of Ethernet IPPlant Wide Benefits of Ethernet IP
Plant Wide Benefits of Ethernet IPPanduit
 
Industrial Automation Infrastructure
Industrial Automation InfrastructureIndustrial Automation Infrastructure
Industrial Automation InfrastructurePanduit
 
Update on european data centre standards socitm 2013
Update on european data centre standards   socitm 2013Update on european data centre standards   socitm 2013
Update on european data centre standards socitm 2013Capitoline LLP
 
The Impact of the Small Cell Forum Release Program - Caroline Gabriel
The Impact of the Small Cell Forum Release Program - Caroline GabrielThe Impact of the Small Cell Forum Release Program - Caroline Gabriel
The Impact of the Small Cell Forum Release Program - Caroline GabrielSmall Cell Forum
 
Spectrum day-2009-intelsat
Spectrum day-2009-intelsatSpectrum day-2009-intelsat
Spectrum day-2009-intelsatSSPI Brasil
 
Internet of Things - structured approach to the physical plant network - Rock...
Internet of Things - structured approach to the physical plant network - Rock...Internet of Things - structured approach to the physical plant network - Rock...
Internet of Things - structured approach to the physical plant network - Rock...Carotek
 
Cyient FTTH Presentation APAC FTTH Conference 2014
Cyient FTTH Presentation APAC FTTH Conference 2014Cyient FTTH Presentation APAC FTTH Conference 2014
Cyient FTTH Presentation APAC FTTH Conference 2014Kiran Solipuram. DEP, CFHP
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580Schneider Electric
 
BMC Engage 2015 Breakout Session #420 - #ITSM_SUCCESS-Final_3.5 (1)
BMC Engage 2015 Breakout Session #420 - #ITSM_SUCCESS-Final_3.5 (1)BMC Engage 2015 Breakout Session #420 - #ITSM_SUCCESS-Final_3.5 (1)
BMC Engage 2015 Breakout Session #420 - #ITSM_SUCCESS-Final_3.5 (1)Phil Bautista
 
Rear Admiral Tony Dalton Presentation to Williams Foundation Seminar on Integ...
Rear Admiral Tony Dalton Presentation to Williams Foundation Seminar on Integ...Rear Admiral Tony Dalton Presentation to Williams Foundation Seminar on Integ...
Rear Admiral Tony Dalton Presentation to Williams Foundation Seminar on Integ...ICSA, LLC
 

La actualidad más candente (20)

Petrobras rom demonstration miguel borges - petrobras
Petrobras rom demonstration   miguel borges - petrobrasPetrobras rom demonstration   miguel borges - petrobras
Petrobras rom demonstration miguel borges - petrobras
 
FOUNDATION for ROM End User Perspective
FOUNDATION for ROM End User PerspectiveFOUNDATION for ROM End User Perspective
FOUNDATION for ROM End User Perspective
 
Fieldbus Foundation Celebrates 20 Years!
Fieldbus Foundation Celebrates 20 Years!Fieldbus Foundation Celebrates 20 Years!
Fieldbus Foundation Celebrates 20 Years!
 
Interoperable ROM DCS Integration
Interoperable ROM DCS IntegrationInteroperable ROM DCS Integration
Interoperable ROM DCS Integration
 
Larry o brien fieldbus foundation english
Larry o brien fieldbus foundation englishLarry o brien fieldbus foundation english
Larry o brien fieldbus foundation english
 
Training and Education Presentation
Training and Education PresentationTraining and Education Presentation
Training and Education Presentation
 
Foundation for rom general assembly
Foundation for rom general assemblyFoundation for rom general assembly
Foundation for rom general assembly
 
The Fieldbus Diagnostics Difference
The Fieldbus Diagnostics DifferenceThe Fieldbus Diagnostics Difference
The Fieldbus Diagnostics Difference
 
Control in the Field - Feb 2011
Control in the Field - Feb 2011Control in the Field - Feb 2011
Control in the Field - Feb 2011
 
Industrial Automation Infrastructure
Industrial Automation InfrastructureIndustrial Automation Infrastructure
Industrial Automation Infrastructure
 
Plant Wide Benefits of Ethernet IP
Plant Wide Benefits of Ethernet IPPlant Wide Benefits of Ethernet IP
Plant Wide Benefits of Ethernet IP
 
Industrial Automation Infrastructure
Industrial Automation InfrastructureIndustrial Automation Infrastructure
Industrial Automation Infrastructure
 
Update on european data centre standards socitm 2013
Update on european data centre standards   socitm 2013Update on european data centre standards   socitm 2013
Update on european data centre standards socitm 2013
 
The Impact of the Small Cell Forum Release Program - Caroline Gabriel
The Impact of the Small Cell Forum Release Program - Caroline GabrielThe Impact of the Small Cell Forum Release Program - Caroline Gabriel
The Impact of the Small Cell Forum Release Program - Caroline Gabriel
 
Spectrum day-2009-intelsat
Spectrum day-2009-intelsatSpectrum day-2009-intelsat
Spectrum day-2009-intelsat
 
Internet of Things - structured approach to the physical plant network - Rock...
Internet of Things - structured approach to the physical plant network - Rock...Internet of Things - structured approach to the physical plant network - Rock...
Internet of Things - structured approach to the physical plant network - Rock...
 
Cyient FTTH Presentation APAC FTTH Conference 2014
Cyient FTTH Presentation APAC FTTH Conference 2014Cyient FTTH Presentation APAC FTTH Conference 2014
Cyient FTTH Presentation APAC FTTH Conference 2014
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580
 
BMC Engage 2015 Breakout Session #420 - #ITSM_SUCCESS-Final_3.5 (1)
BMC Engage 2015 Breakout Session #420 - #ITSM_SUCCESS-Final_3.5 (1)BMC Engage 2015 Breakout Session #420 - #ITSM_SUCCESS-Final_3.5 (1)
BMC Engage 2015 Breakout Session #420 - #ITSM_SUCCESS-Final_3.5 (1)
 
Rear Admiral Tony Dalton Presentation to Williams Foundation Seminar on Integ...
Rear Admiral Tony Dalton Presentation to Williams Foundation Seminar on Integ...Rear Admiral Tony Dalton Presentation to Williams Foundation Seminar on Integ...
Rear Admiral Tony Dalton Presentation to Williams Foundation Seminar on Integ...
 

Destacado

BASICS OF FIELDBUS
BASICS OF FIELDBUSBASICS OF FIELDBUS
BASICS OF FIELDBUSShivam Singh
 
7 Ye YingMin Diagnostics and Maintenance
7 Ye YingMin Diagnostics and Maintenance7 Ye YingMin Diagnostics and Maintenance
7 Ye YingMin Diagnostics and MaintenanceFieldComm Group
 
6 Bai Guo Hua FOUNDATION in the Power Generation Industry
6 Bai Guo Hua FOUNDATION in the Power Generation Industry6 Bai Guo Hua FOUNDATION in the Power Generation Industry
6 Bai Guo Hua FOUNDATION in the Power Generation IndustryFieldComm Group
 
Alexandre lopes braskem portuguese
Alexandre lopes braskem portugueseAlexandre lopes braskem portuguese
Alexandre lopes braskem portugueseFieldComm Group
 
Marcos peluso emerson english
Marcos peluso emerson englishMarcos peluso emerson english
Marcos peluso emerson englishFieldComm Group
 
Foundation for rom user perspective 1 18-12
Foundation for rom user perspective 1 18-12Foundation for rom user perspective 1 18-12
Foundation for rom user perspective 1 18-12FieldComm Group
 
Foundation Fieldbus
Foundation FieldbusFoundation Fieldbus
Foundation FieldbusJustin Baby
 

Destacado (8)

BASICS OF FIELDBUS
BASICS OF FIELDBUSBASICS OF FIELDBUS
BASICS OF FIELDBUS
 
7 Ye YingMin Diagnostics and Maintenance
7 Ye YingMin Diagnostics and Maintenance7 Ye YingMin Diagnostics and Maintenance
7 Ye YingMin Diagnostics and Maintenance
 
6 Bai Guo Hua FOUNDATION in the Power Generation Industry
6 Bai Guo Hua FOUNDATION in the Power Generation Industry6 Bai Guo Hua FOUNDATION in the Power Generation Industry
6 Bai Guo Hua FOUNDATION in the Power Generation Industry
 
Alexandre lopes braskem portuguese
Alexandre lopes braskem portugueseAlexandre lopes braskem portuguese
Alexandre lopes braskem portuguese
 
Marcos peluso emerson english
Marcos peluso emerson englishMarcos peluso emerson english
Marcos peluso emerson english
 
Foundation for rom user perspective 1 18-12
Foundation for rom user perspective 1 18-12Foundation for rom user perspective 1 18-12
Foundation for rom user perspective 1 18-12
 
Foundation Fieldbus
Foundation FieldbusFoundation Fieldbus
Foundation Fieldbus
 
Foundation fieldbus
Foundation fieldbusFoundation fieldbus
Foundation fieldbus
 

Similar a Benefits of foundation in the operational phase

Pro sphere customer technical
Pro sphere customer technicalPro sphere customer technical
Pro sphere customer technicalsolarisyougood
 
OpenFlow: What is it Good For?
OpenFlow: What is it Good For? OpenFlow: What is it Good For?
OpenFlow: What is it Good For? APNIC
 
DB2 for z/O S Data Sharing
DB2 for z/O S  Data  SharingDB2 for z/O S  Data  Sharing
DB2 for z/O S Data SharingSurekha Parekh
 
Implementation of WaterCoach SeqFEWS
Implementation of WaterCoach SeqFEWS Implementation of WaterCoach SeqFEWS
Implementation of WaterCoach SeqFEWS Lindsay Millard
 
SolarWinds Online Federal User Group
SolarWinds Online Federal User GroupSolarWinds Online Federal User Group
SolarWinds Online Federal User GroupSolarWinds
 
Software Defined Networking/Openflow: A path to Programmable Networks
Software Defined Networking/Openflow: A path to Programmable NetworksSoftware Defined Networking/Openflow: A path to Programmable Networks
Software Defined Networking/Openflow: A path to Programmable NetworksMyNOG
 
Network Performance Monitor (NPM) 10.4: New Features, Tips and Tricks for
Network Performance Monitor (NPM) 10.4: New Features, Tips and Tricks for Network Performance Monitor (NPM) 10.4: New Features, Tips and Tricks for
Network Performance Monitor (NPM) 10.4: New Features, Tips and Tricks for SolarWinds
 
Polyteda Power DRC/LVS July 2016
Polyteda Power DRC/LVS July 2016Polyteda Power DRC/LVS July 2016
Polyteda Power DRC/LVS July 2016Oleksandra Nazola
 
PowerDRC/LVS 2.2 released by POLYTEDA
PowerDRC/LVS 2.2 released by POLYTEDAPowerDRC/LVS 2.2 released by POLYTEDA
PowerDRC/LVS 2.2 released by POLYTEDAAlexander Grudanov
 
2.ibm flex system manager overview
2.ibm flex system manager overview2.ibm flex system manager overview
2.ibm flex system manager overviewsolarisyougood
 
JDSU - Delivering dynamic networks for a personalized experience
JDSU - Delivering dynamic networks for a personalized experienceJDSU - Delivering dynamic networks for a personalized experience
JDSU - Delivering dynamic networks for a personalized experienceSmall Cell Forum
 
Ims12 workbench data visualization - IMS UG May 2014 Sydney & Melbourne
Ims12   workbench data visualization - IMS UG May 2014 Sydney & MelbourneIms12   workbench data visualization - IMS UG May 2014 Sydney & Melbourne
Ims12 workbench data visualization - IMS UG May 2014 Sydney & MelbourneRobert Hain
 
POLYTEDA: Power DRC/LVS, June 2017
POLYTEDA: Power DRC/LVS, June 2017POLYTEDA: Power DRC/LVS, June 2017
POLYTEDA: Power DRC/LVS, June 2017Oleksandra Nazola
 
New Product Release Roundup: SAM, NPM, & VNQM
New Product Release Roundup: SAM, NPM, & VNQMNew Product Release Roundup: SAM, NPM, & VNQM
New Product Release Roundup: SAM, NPM, & VNQMSolarWinds
 
Beyond the Brokers | Emma Humber and Andrew Borley, IBM
Beyond the Brokers | Emma Humber and Andrew Borley, IBMBeyond the Brokers | Emma Humber and Andrew Borley, IBM
Beyond the Brokers | Emma Humber and Andrew Borley, IBMHostedbyConfluent
 
VMworld 2013: US Air National Guard - DoD Private Cloud Initiative –How Virtu...
VMworld 2013: US Air National Guard - DoD Private Cloud Initiative –How Virtu...VMworld 2013: US Air National Guard - DoD Private Cloud Initiative –How Virtu...
VMworld 2013: US Air National Guard - DoD Private Cloud Initiative –How Virtu...VMworld
 
Best Practices for Migrating Previous Versions of Cisco Unified Communications
Best Practices for Migrating Previous Versions of Cisco Unified CommunicationsBest Practices for Migrating Previous Versions of Cisco Unified Communications
Best Practices for Migrating Previous Versions of Cisco Unified CommunicationsCisco Canada
 

Similar a Benefits of foundation in the operational phase (20)

Pro sphere customer technical
Pro sphere customer technicalPro sphere customer technical
Pro sphere customer technical
 
Interconnect Product Portfolio
Interconnect Product PortfolioInterconnect Product Portfolio
Interconnect Product Portfolio
 
OpenFlow: What is it Good For?
OpenFlow: What is it Good For? OpenFlow: What is it Good For?
OpenFlow: What is it Good For?
 
DB2 for z/O S Data Sharing
DB2 for z/O S  Data  SharingDB2 for z/O S  Data  Sharing
DB2 for z/O S Data Sharing
 
Implementation of WaterCoach SeqFEWS
Implementation of WaterCoach SeqFEWS Implementation of WaterCoach SeqFEWS
Implementation of WaterCoach SeqFEWS
 
SolarWinds Online Federal User Group
SolarWinds Online Federal User GroupSolarWinds Online Federal User Group
SolarWinds Online Federal User Group
 
Software Defined Networking/Openflow: A path to Programmable Networks
Software Defined Networking/Openflow: A path to Programmable NetworksSoftware Defined Networking/Openflow: A path to Programmable Networks
Software Defined Networking/Openflow: A path to Programmable Networks
 
Coming Soon
Coming SoonComing Soon
Coming Soon
 
Network Performance Monitor (NPM) 10.4: New Features, Tips and Tricks for
Network Performance Monitor (NPM) 10.4: New Features, Tips and Tricks for Network Performance Monitor (NPM) 10.4: New Features, Tips and Tricks for
Network Performance Monitor (NPM) 10.4: New Features, Tips and Tricks for
 
Polyteda Power DRC/LVS July 2016
Polyteda Power DRC/LVS July 2016Polyteda Power DRC/LVS July 2016
Polyteda Power DRC/LVS July 2016
 
PowerDRC/LVS 2.2 released by POLYTEDA
PowerDRC/LVS 2.2 released by POLYTEDAPowerDRC/LVS 2.2 released by POLYTEDA
PowerDRC/LVS 2.2 released by POLYTEDA
 
2.ibm flex system manager overview
2.ibm flex system manager overview2.ibm flex system manager overview
2.ibm flex system manager overview
 
JDSU - Delivering dynamic networks for a personalized experience
JDSU - Delivering dynamic networks for a personalized experienceJDSU - Delivering dynamic networks for a personalized experience
JDSU - Delivering dynamic networks for a personalized experience
 
Ims12 workbench data visualization - IMS UG May 2014 Sydney & Melbourne
Ims12   workbench data visualization - IMS UG May 2014 Sydney & MelbourneIms12   workbench data visualization - IMS UG May 2014 Sydney & Melbourne
Ims12 workbench data visualization - IMS UG May 2014 Sydney & Melbourne
 
POLYTEDA: Power DRC/LVS, June 2017
POLYTEDA: Power DRC/LVS, June 2017POLYTEDA: Power DRC/LVS, June 2017
POLYTEDA: Power DRC/LVS, June 2017
 
New Product Release Roundup: SAM, NPM, & VNQM
New Product Release Roundup: SAM, NPM, & VNQMNew Product Release Roundup: SAM, NPM, & VNQM
New Product Release Roundup: SAM, NPM, & VNQM
 
Beyond the Brokers | Emma Humber and Andrew Borley, IBM
Beyond the Brokers | Emma Humber and Andrew Borley, IBMBeyond the Brokers | Emma Humber and Andrew Borley, IBM
Beyond the Brokers | Emma Humber and Andrew Borley, IBM
 
VMworld 2013: US Air National Guard - DoD Private Cloud Initiative –How Virtu...
VMworld 2013: US Air National Guard - DoD Private Cloud Initiative –How Virtu...VMworld 2013: US Air National Guard - DoD Private Cloud Initiative –How Virtu...
VMworld 2013: US Air National Guard - DoD Private Cloud Initiative –How Virtu...
 
Best Practices for Migrating Previous Versions of Cisco Unified Communications
Best Practices for Migrating Previous Versions of Cisco Unified CommunicationsBest Practices for Migrating Previous Versions of Cisco Unified Communications
Best Practices for Migrating Previous Versions of Cisco Unified Communications
 
workshop.ppt
workshop.pptworkshop.ppt
workshop.ppt
 

Más de FieldComm Group

Andreas Agostin Installation Solutions
Andreas Agostin Installation SolutionsAndreas Agostin Installation Solutions
Andreas Agostin Installation SolutionsFieldComm Group
 
Cenpes ff rom demo overview renato ogeda - petrobras
Cenpes ff rom demo overview   renato ogeda - petrobrasCenpes ff rom demo overview   renato ogeda - petrobras
Cenpes ff rom demo overview renato ogeda - petrobrasFieldComm Group
 
Cenpes ff rom demo wireless backhaul edgar hofmann - petrobras
Cenpes ff rom demo wireless backhaul   edgar hofmann - petrobrasCenpes ff rom demo wireless backhaul   edgar hofmann - petrobras
Cenpes ff rom demo wireless backhaul edgar hofmann - petrobrasFieldComm Group
 
1 Ling Rong - Keynote Presentation Chinese
1 Ling Rong - Keynote Presentation Chinese1 Ling Rong - Keynote Presentation Chinese
1 Ling Rong - Keynote Presentation ChineseFieldComm Group
 
1 Ling Rong - Keynote Presentation English
1 Ling Rong - Keynote Presentation English1 Ling Rong - Keynote Presentation English
1 Ling Rong - Keynote Presentation EnglishFieldComm Group
 
8 Dave Glanzer Technology Update
8 Dave Glanzer Technology Update8 Dave Glanzer Technology Update
8 Dave Glanzer Technology UpdateFieldComm Group
 
5 Huang Weibo Importance of Training
5 Huang Weibo Importance of Training5 Huang Weibo Importance of Training
5 Huang Weibo Importance of TrainingFieldComm Group
 
4 Larry O'Brien FOUNDATION for ROM
4 Larry O'Brien FOUNDATION for ROM4 Larry O'Brien FOUNDATION for ROM
4 Larry O'Brien FOUNDATION for ROMFieldComm Group
 
3 Liu Zhiqiang FOUNDATION Project Best Practices
3 Liu Zhiqiang FOUNDATION Project Best Practices3 Liu Zhiqiang FOUNDATION Project Best Practices
3 Liu Zhiqiang FOUNDATION Project Best PracticesFieldComm Group
 
2 Wei Hua Installation and Commissioning
2 Wei Hua Installation and Commissioning2 Wei Hua Installation and Commissioning
2 Wei Hua Installation and CommissioningFieldComm Group
 
Quality training and fctp
Quality training and fctpQuality training and fctp
Quality training and fctpFieldComm Group
 
Field device integration evolution in asset integration
Field device integration evolution in asset integrationField device integration evolution in asset integration
Field device integration evolution in asset integrationFieldComm Group
 

Más de FieldComm Group (13)

Andreas Agostin Installation Solutions
Andreas Agostin Installation SolutionsAndreas Agostin Installation Solutions
Andreas Agostin Installation Solutions
 
Sf taga3 a
Sf taga3 aSf taga3 a
Sf taga3 a
 
Cenpes ff rom demo overview renato ogeda - petrobras
Cenpes ff rom demo overview   renato ogeda - petrobrasCenpes ff rom demo overview   renato ogeda - petrobras
Cenpes ff rom demo overview renato ogeda - petrobras
 
Cenpes ff rom demo wireless backhaul edgar hofmann - petrobras
Cenpes ff rom demo wireless backhaul   edgar hofmann - petrobrasCenpes ff rom demo wireless backhaul   edgar hofmann - petrobras
Cenpes ff rom demo wireless backhaul edgar hofmann - petrobras
 
1 Ling Rong - Keynote Presentation Chinese
1 Ling Rong - Keynote Presentation Chinese1 Ling Rong - Keynote Presentation Chinese
1 Ling Rong - Keynote Presentation Chinese
 
1 Ling Rong - Keynote Presentation English
1 Ling Rong - Keynote Presentation English1 Ling Rong - Keynote Presentation English
1 Ling Rong - Keynote Presentation English
 
8 Dave Glanzer Technology Update
8 Dave Glanzer Technology Update8 Dave Glanzer Technology Update
8 Dave Glanzer Technology Update
 
5 Huang Weibo Importance of Training
5 Huang Weibo Importance of Training5 Huang Weibo Importance of Training
5 Huang Weibo Importance of Training
 
4 Larry O'Brien FOUNDATION for ROM
4 Larry O'Brien FOUNDATION for ROM4 Larry O'Brien FOUNDATION for ROM
4 Larry O'Brien FOUNDATION for ROM
 
3 Liu Zhiqiang FOUNDATION Project Best Practices
3 Liu Zhiqiang FOUNDATION Project Best Practices3 Liu Zhiqiang FOUNDATION Project Best Practices
3 Liu Zhiqiang FOUNDATION Project Best Practices
 
2 Wei Hua Installation and Commissioning
2 Wei Hua Installation and Commissioning2 Wei Hua Installation and Commissioning
2 Wei Hua Installation and Commissioning
 
Quality training and fctp
Quality training and fctpQuality training and fctp
Quality training and fctp
 
Field device integration evolution in asset integration
Field device integration evolution in asset integrationField device integration evolution in asset integration
Field device integration evolution in asset integration
 

Último

Anypoint Code Builder , Google Pub sub connector and MuleSoft RPA
Anypoint Code Builder , Google Pub sub connector and MuleSoft RPAAnypoint Code Builder , Google Pub sub connector and MuleSoft RPA
Anypoint Code Builder , Google Pub sub connector and MuleSoft RPAshyamraj55
 
IaC & GitOps in a Nutshell - a FridayInANuthshell Episode.pdf
IaC & GitOps in a Nutshell - a FridayInANuthshell Episode.pdfIaC & GitOps in a Nutshell - a FridayInANuthshell Episode.pdf
IaC & GitOps in a Nutshell - a FridayInANuthshell Episode.pdfDaniel Santiago Silva Capera
 
UiPath Platform: The Backend Engine Powering Your Automation - Session 1
UiPath Platform: The Backend Engine Powering Your Automation - Session 1UiPath Platform: The Backend Engine Powering Your Automation - Session 1
UiPath Platform: The Backend Engine Powering Your Automation - Session 1DianaGray10
 
UiPath Community: AI for UiPath Automation Developers
UiPath Community: AI for UiPath Automation DevelopersUiPath Community: AI for UiPath Automation Developers
UiPath Community: AI for UiPath Automation DevelopersUiPathCommunity
 
NIST Cybersecurity Framework (CSF) 2.0 Workshop
NIST Cybersecurity Framework (CSF) 2.0 WorkshopNIST Cybersecurity Framework (CSF) 2.0 Workshop
NIST Cybersecurity Framework (CSF) 2.0 WorkshopBachir Benyammi
 
The Data Metaverse: Unpacking the Roles, Use Cases, and Tech Trends in Data a...
The Data Metaverse: Unpacking the Roles, Use Cases, and Tech Trends in Data a...The Data Metaverse: Unpacking the Roles, Use Cases, and Tech Trends in Data a...
The Data Metaverse: Unpacking the Roles, Use Cases, and Tech Trends in Data a...Aggregage
 
Introduction to Matsuo Laboratory (ENG).pptx
Introduction to Matsuo Laboratory (ENG).pptxIntroduction to Matsuo Laboratory (ENG).pptx
Introduction to Matsuo Laboratory (ENG).pptxMatsuo Lab
 
AI You Can Trust - Ensuring Success with Data Integrity Webinar
AI You Can Trust - Ensuring Success with Data Integrity WebinarAI You Can Trust - Ensuring Success with Data Integrity Webinar
AI You Can Trust - Ensuring Success with Data Integrity WebinarPrecisely
 
UiPath Solutions Management Preview - Northern CA Chapter - March 22.pdf
UiPath Solutions Management Preview - Northern CA Chapter - March 22.pdfUiPath Solutions Management Preview - Northern CA Chapter - March 22.pdf
UiPath Solutions Management Preview - Northern CA Chapter - March 22.pdfDianaGray10
 
UiPath Studio Web workshop series - Day 7
UiPath Studio Web workshop series - Day 7UiPath Studio Web workshop series - Day 7
UiPath Studio Web workshop series - Day 7DianaGray10
 
ADOPTING WEB 3 FOR YOUR BUSINESS: A STEP-BY-STEP GUIDE
ADOPTING WEB 3 FOR YOUR BUSINESS: A STEP-BY-STEP GUIDEADOPTING WEB 3 FOR YOUR BUSINESS: A STEP-BY-STEP GUIDE
ADOPTING WEB 3 FOR YOUR BUSINESS: A STEP-BY-STEP GUIDELiveplex
 
Building AI-Driven Apps Using Semantic Kernel.pptx
Building AI-Driven Apps Using Semantic Kernel.pptxBuilding AI-Driven Apps Using Semantic Kernel.pptx
Building AI-Driven Apps Using Semantic Kernel.pptxUdaiappa Ramachandran
 
IESVE Software for Florida Code Compliance Using ASHRAE 90.1-2019
IESVE Software for Florida Code Compliance Using ASHRAE 90.1-2019IESVE Software for Florida Code Compliance Using ASHRAE 90.1-2019
IESVE Software for Florida Code Compliance Using ASHRAE 90.1-2019IES VE
 
UiPath Studio Web workshop series - Day 8
UiPath Studio Web workshop series - Day 8UiPath Studio Web workshop series - Day 8
UiPath Studio Web workshop series - Day 8DianaGray10
 
AI Fame Rush Review – Virtual Influencer Creation In Just Minutes
AI Fame Rush Review – Virtual Influencer Creation In Just MinutesAI Fame Rush Review – Virtual Influencer Creation In Just Minutes
AI Fame Rush Review – Virtual Influencer Creation In Just MinutesMd Hossain Ali
 
Comparing Sidecar-less Service Mesh from Cilium and Istio
Comparing Sidecar-less Service Mesh from Cilium and IstioComparing Sidecar-less Service Mesh from Cilium and Istio
Comparing Sidecar-less Service Mesh from Cilium and IstioChristian Posta
 
VoIP Service and Marketing using Odoo and Asterisk PBX
VoIP Service and Marketing using Odoo and Asterisk PBXVoIP Service and Marketing using Odoo and Asterisk PBX
VoIP Service and Marketing using Odoo and Asterisk PBXTarek Kalaji
 
Cybersecurity Workshop #1.pptx
Cybersecurity Workshop #1.pptxCybersecurity Workshop #1.pptx
Cybersecurity Workshop #1.pptxGDSC PJATK
 
How Accurate are Carbon Emissions Projections?
How Accurate are Carbon Emissions Projections?How Accurate are Carbon Emissions Projections?
How Accurate are Carbon Emissions Projections?IES VE
 

Último (20)

Anypoint Code Builder , Google Pub sub connector and MuleSoft RPA
Anypoint Code Builder , Google Pub sub connector and MuleSoft RPAAnypoint Code Builder , Google Pub sub connector and MuleSoft RPA
Anypoint Code Builder , Google Pub sub connector and MuleSoft RPA
 
201610817 - edge part1
201610817 - edge part1201610817 - edge part1
201610817 - edge part1
 
IaC & GitOps in a Nutshell - a FridayInANuthshell Episode.pdf
IaC & GitOps in a Nutshell - a FridayInANuthshell Episode.pdfIaC & GitOps in a Nutshell - a FridayInANuthshell Episode.pdf
IaC & GitOps in a Nutshell - a FridayInANuthshell Episode.pdf
 
UiPath Platform: The Backend Engine Powering Your Automation - Session 1
UiPath Platform: The Backend Engine Powering Your Automation - Session 1UiPath Platform: The Backend Engine Powering Your Automation - Session 1
UiPath Platform: The Backend Engine Powering Your Automation - Session 1
 
UiPath Community: AI for UiPath Automation Developers
UiPath Community: AI for UiPath Automation DevelopersUiPath Community: AI for UiPath Automation Developers
UiPath Community: AI for UiPath Automation Developers
 
NIST Cybersecurity Framework (CSF) 2.0 Workshop
NIST Cybersecurity Framework (CSF) 2.0 WorkshopNIST Cybersecurity Framework (CSF) 2.0 Workshop
NIST Cybersecurity Framework (CSF) 2.0 Workshop
 
The Data Metaverse: Unpacking the Roles, Use Cases, and Tech Trends in Data a...
The Data Metaverse: Unpacking the Roles, Use Cases, and Tech Trends in Data a...The Data Metaverse: Unpacking the Roles, Use Cases, and Tech Trends in Data a...
The Data Metaverse: Unpacking the Roles, Use Cases, and Tech Trends in Data a...
 
Introduction to Matsuo Laboratory (ENG).pptx
Introduction to Matsuo Laboratory (ENG).pptxIntroduction to Matsuo Laboratory (ENG).pptx
Introduction to Matsuo Laboratory (ENG).pptx
 
AI You Can Trust - Ensuring Success with Data Integrity Webinar
AI You Can Trust - Ensuring Success with Data Integrity WebinarAI You Can Trust - Ensuring Success with Data Integrity Webinar
AI You Can Trust - Ensuring Success with Data Integrity Webinar
 
UiPath Solutions Management Preview - Northern CA Chapter - March 22.pdf
UiPath Solutions Management Preview - Northern CA Chapter - March 22.pdfUiPath Solutions Management Preview - Northern CA Chapter - March 22.pdf
UiPath Solutions Management Preview - Northern CA Chapter - March 22.pdf
 
UiPath Studio Web workshop series - Day 7
UiPath Studio Web workshop series - Day 7UiPath Studio Web workshop series - Day 7
UiPath Studio Web workshop series - Day 7
 
ADOPTING WEB 3 FOR YOUR BUSINESS: A STEP-BY-STEP GUIDE
ADOPTING WEB 3 FOR YOUR BUSINESS: A STEP-BY-STEP GUIDEADOPTING WEB 3 FOR YOUR BUSINESS: A STEP-BY-STEP GUIDE
ADOPTING WEB 3 FOR YOUR BUSINESS: A STEP-BY-STEP GUIDE
 
Building AI-Driven Apps Using Semantic Kernel.pptx
Building AI-Driven Apps Using Semantic Kernel.pptxBuilding AI-Driven Apps Using Semantic Kernel.pptx
Building AI-Driven Apps Using Semantic Kernel.pptx
 
IESVE Software for Florida Code Compliance Using ASHRAE 90.1-2019
IESVE Software for Florida Code Compliance Using ASHRAE 90.1-2019IESVE Software for Florida Code Compliance Using ASHRAE 90.1-2019
IESVE Software for Florida Code Compliance Using ASHRAE 90.1-2019
 
UiPath Studio Web workshop series - Day 8
UiPath Studio Web workshop series - Day 8UiPath Studio Web workshop series - Day 8
UiPath Studio Web workshop series - Day 8
 
AI Fame Rush Review – Virtual Influencer Creation In Just Minutes
AI Fame Rush Review – Virtual Influencer Creation In Just MinutesAI Fame Rush Review – Virtual Influencer Creation In Just Minutes
AI Fame Rush Review – Virtual Influencer Creation In Just Minutes
 
Comparing Sidecar-less Service Mesh from Cilium and Istio
Comparing Sidecar-less Service Mesh from Cilium and IstioComparing Sidecar-less Service Mesh from Cilium and Istio
Comparing Sidecar-less Service Mesh from Cilium and Istio
 
VoIP Service and Marketing using Odoo and Asterisk PBX
VoIP Service and Marketing using Odoo and Asterisk PBXVoIP Service and Marketing using Odoo and Asterisk PBX
VoIP Service and Marketing using Odoo and Asterisk PBX
 
Cybersecurity Workshop #1.pptx
Cybersecurity Workshop #1.pptxCybersecurity Workshop #1.pptx
Cybersecurity Workshop #1.pptx
 
How Accurate are Carbon Emissions Projections?
How Accurate are Carbon Emissions Projections?How Accurate are Carbon Emissions Projections?
How Accurate are Carbon Emissions Projections?
 

Benefits of foundation in the operational phase

  • 1. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 1 Field-based Control : Freedom to Choose the Ultimate DCS John Rezabek Process Control Specialist Ashland, Inc.
  • 2. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 2 What is Fieldbus Again? • Fieldbus is a communication protocol, right? • The “OSI Model”: Seven Layers for “Open Systems Interconnection” • Foundation fieldbus uniquely adds the “User Layer” – why? Physical Layer Data Link Layer Network Layer Transport Layer Session Layer Presentation Layer Application Layer USER LAYER
  • 3. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 3 Why Have a “User Layer”? • Analog In, Analog Out, Digital In, Digital Out • Do some scaling, linearization, filtering, configure fault states & propagation, etc. outside the host / DCS • Devices are “peers” with the host’s interface • ARTHM, ISEL, SGCR, INT • Relieve the HOST DCS of some compensation, characterization, totalizers, etc. • PID, CSEL, SPLTR • Configure CONTROL IN FIELD DEVICES, using the world’s only vendor-independent totally distributed digital control system
  • 4. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 4 Why “Distributed” Control? • 1980’s costs for CPU and memory meant many loops-per-controller for reasonable “cost per loop” • Users of the day wanted “single loop integrity” = one fault > loose no more than one loop • Controller, I/O, and Network Redundancy • Commercial model became “functionally” distributed
  • 5. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 5 The Need For Reliability ARC Insight 10th June 2010 The global process industry loses $20 billion, or five percent of annual production, due to unscheduled downtime and poor quality. ARC estimates that almost 80 percent of these losses are preventable, with 40 percent largely due to operator error.
  • 6. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 6 Fieldbus = Truly Distributed Control • Foundation Fieldbus allows return to true single-loop integrity • Robust control independent of DCS, needs only power, devices, and schedule (“LAS”) • Intelligence of devices is exploited, employing signal status, diagnostics • But – is it truly more reliable?
  • 7. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 7 Fewer Components = Longer MTBF PSU PSU  AND Foundation fieldbus also communicates signal status with every scan, which enables smart mode shedding, bumpless transfer and initialization.
  • 8. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 8 Digital All the Way - Digital Closed Loop Control Fieldbus eliminates the analog signal Validity: Good/Bad/ Uncertain Initiate Fault- State Command Limited: High/Low Bumpless Transfer Windup Protection Fault-state Status Designed for process control Default behavior on Bad or Uncertain PV is shed mode to MAN and hold last output – the same macrocycle the fault is detected.
  • 9. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 9 Process Variable Validity Hardwired  Device drives current <4 mA or >20 mA on device failure – Looks like process problem  PID counteracts thus tripping the loop  Operator cannot tell the difference between a process alarm and a device alarm Fieldbus  Device health indicated by associated status  Controller holds last position on device failure – Shutdown is optional  Operator can easily distinguish process problem from a device problem
  • 10. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 10 FF – A Standard for High Availability  Distributed Control, Speed, & Determinism  Real-time value and status  Status Propagation (CIF & CIC)  Validated information Quality and limits  Windup protection  Bumpless transfer for valves  Fault-state for valves  etc.
  • 11. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 11 SIL - Putting a Number on Reliability • Ed Marszal, ISA 84.001 and IEC 61508 expert, author and president of Kenexis consultants • Entered reliability numbers into reliability models for safety system calculations • “ FF is significantly better – MTTF (mean time to fail) of 48.2 [years] versus MTTF of 15.9 [years]”
  • 12. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 12 Reliability Analogue With CIF 15.9y 48.2y MTTF
  • 13. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 13 Customer Experience CIF enabled
  • 14. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 14 Customer Experience FOUNDATION Fieldbus CIF with inherent backup capability prevented 2 incorrect plant shutdowns, which would have resulted from communication interruptions.
  • 15. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 15 But . . . Isn’t Fieldbus “Slow”? • Early devices had longer function block execution times • Many early jobs used FF for IO only • Host PID to FF Macrocycle sync is not easily addressed – oversample? • Variable latencies, overly busy segments • Add commissioning, diagnostics, downloads • = Many bogged down segments
  • 16. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 16 Control In The Field Study
  • 17. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 17 Comparison CIF enabled No CIF 125 625 105 ms
  • 18. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 18 Settling Times: Fastest Process 50 54 58 62 Process output (%) 0 4 8 12 16 20 Time (seconds) 60% Setpoint Case 1 - CIF Case 3 - Control in DCS (async)
  • 19. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 19 Settling Times: Very Fast Process 50 54 58 62 Process output (%) 0 4 8 12 16 20 Time (seconds) Setpoint Case 1 - CIF Case 3 - Control in DCS (async) 55%
  • 20. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 20 Settling Times: Fast Process 50 54 58 62 Process output (%) 0 4 8 12 16 20 Time (seconds) Setpoint Case 1 - CIF Case 3 - Control in DCS (async) 66%
  • 21. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 21 Settling Times: Medium Process 50 54 58 62 Process output (%) 0 4 8 12 16 20 Time (seconds) Setpoint Case 1 - CIF Case 3 - Control in DCS (async) 39%
  • 22. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 22 Presence Of Disturbance: Fastest Process Process output (%) 40 50 60 70 80 90 100 Time (seconds) Setpoint Case 1 - CIF Case 3 - Control in DCS (async) 56 58 60 66 62 64
  • 23. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 23 Presence Of Disturbance: Different Processes Fastest 1.811 2.132 0.517 0.82 0.642 1.058 0.231 0.53 65% better 50% better 55% better 35% better Very Fast Fast Medium Setpoint CIF 1.811 control in DCS (async)
  • 24. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 24 ISC Study on Control in the Field “Control in the field: analysis of performance benefits” study from ISC (industrial systems and control) 40-60% faster settling time on setpoint change 30-50% better disturbance rejection Most significant for fast processes (flow and pressure)
  • 25. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 25 Impact of Tighter Control Loop Manual Pneumatic Analogue Digital Control limit
  • 26. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 26 Recommended For Fast Loop Response Control in the field using FOUNDATION fieldbus technology is recommended by SGSI for simple and cascading loops, not for complex loops. Major benefits identified by SGSI are reduced process controller loading, reduced network traffic enabling more loops per segment, as well as very fast loop response.
  • 27. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 27 Empirical Studies: CIF Fast as 4-20 Host Host Host Host Study by Daugherty, Coughran, and Ford, “Effects of Macrocycle Time and Sampling Rates on Control Loop Performance”
  • 28. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 28 8 simple loops, CIC Study by Daugherty, Coughran, and Ford, “Effects of Macrocycle Time and Sampling Rates on Control Loop Performance”
  • 29. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 29 Same 8 loops, CIF (valve positioner) Study by Daugherty, Coughran, and Ford, “Effects of Macrocycle Time and Sampling Rates on Control Loop Performance”
  • 30. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 32 Blower – Combustion Air to Boiler • Keeping the Blower out of the surge region means a more stable flow • More stable flow allows running closer to constraints • Running closer to constraints means less fuel, CO2 AIR TO BOILER AIR BLOWERPREHEATER TOBURNERS
  • 31. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 33 Inside “peak pressure” line, flow is unstable Peak Pressure Desired Flow fell here
  • 32. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 34 Field-based control of blow-off valve • Controls total flow • Allows operation close to low-flow BMS trip point • Saves fuel costs and reduces CO2 emissions
  • 33. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 35 Surge Control Scheme Blow-off Flow Flow to Burner FIC Inlet Louvers Σ FIC (Total Flow) Blow-off Valve Discharge Pressure SGCR SP PT (Discharge) FT1 FT2 Blow-off Valve Pos. Inlet Louver Positioner
  • 34. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 36 Blower Anti-surge scheme Flow to Burner Total Flow Setpoint Total Flow Controller
  • 35. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 38 10,000 HP Turbine / Blower Anti-surge • Large critical un-spared asset • Typically runs at 5000 to 7000 RPM • Expensive to repair; lost production even more expensive
  • 36. 2012 End User Seminar Fieldbus Foundation © 1994 – 2012 Fieldbus Foundation 44 Summary • FF was specified & designed to deliver robust control by default – STANDARDIZED across suppliers • Control in Field Devices is being used in critical process applications with fast cycle time requirements • Modern devices are executing function blocks faster than ever • (note: like cars, there are Yugos and Porches, so choose according to your needs)

Notas del editor

  1. Generically, “fieldbus” describes a communication protocol. Foundation fieldbus uniquely adds the user layer. Other fieldbus protocols do not have a user layer.
  2. In the late 70’s and 80’s, we started out with digital microprocessor-based DCS’s, which revolutionized our discipline.Not long after, “smart” devices (transmitters and valve positioners) appeared, and it didn’t take long for users to ask them to be integrated. After years of proprietary integration, ISA convened the SP-50 committee to devise a standard. It is the work of this committee that grew in WorldFIP and ISP which later merged to form FF.It was the USERS that wanted a USER LAYER. Vendors were not crazy about it.The “User layer” – device-resident standard function blocks – Are a unique feature of foundation fieldbus.AI, AO, DI, DO (MAI, MDI, etc.) are the minimum required to use data from FF in the host. Even they are configurable to do scaling, alarming, square root extraction, etc. outside the DCS. A lot of power already. In addition to the PV (process variable) they also pass along signal status every time they’re executed.ARTHM, ISEL, SGCR, INT and related FB’s are available in many devices – more chances to off-load computing tasks from the DCS using standard FB’s.PID, CSEL, SPLTR (PID control, control selector &amp; splitter) are among the blocks used for CONTROL IN THE FIELD, a feature end users wanted to achieve truly distributed control . . . ASK – what other control system is vendor-independent and totally distributed? (answer = pneumatics)ASK – Why didn’t we like pneumatics? (answer = sloppy, unreliable, lack of precision)
  3. Why do we tolerate “many eggs in one basket” HOST DCS of today?Ask what, if anything, single-loop integrity means to attendees“Functionally” meaning controller, operator interface, network management, historian etc in separate boxes.ASK: Can anyone comment on the number of loops per controller in their system?
  4. &quot;The global process industry loses $20 billion, or five percent of annual production, due to unscheduled downtime and poor quality. ARC estimates that almost 80 percent of these losses are preventable, with 40 percent largely due to operator error.&quot;ARC Insight June 10 2010Operator error? How much because of acting on invalid information, or plugged lines, failed sensors, failure to detect a “flatlining” level?
  5. Discuss mode shedding, bumpless transfer, anti-reset windup, behavior of loops when limited, etc.We are ALREADY relying on the field devices – when your positioner is having a bad day, the “loop” will have troubles NO MATTER WHERE PID is solved.
  6. The SAME PEOPLE that forged the robust DCS of the 80’s and 90’s were active on the SP50 committee, and infused their lessons learnt into the design of the user layer. NOT ONLY are there fewer things to fail and no dependence on the DCS or its infrastructure, EVERY TRANSMISSION (nominally, once a second or faster) communicates signal status (good, uncertain, bad, limited, etc.) and the FF FB’s do SMART THINGS by default (shed to manual, bumpless transfer) as well as providing for configurable behaviour (e.g., propagate fault forward and fault state to value).Everyone know what is meant by mode shedding? (go to a safe or stable mode, e.g. manual, on a fault)Everyone know what is meant by bumpless transfer? (smoothly transition from MAN &gt; AUTO &gt; CAS, for example) What is a “bump”? (it’s an upset, a process upset)Any lunatics in the crowd, do not obtain a firearm and shoot your instruments.Compare reliability of components for control in DCS (= Process Control System) vs CIF (Control in the Field)Examine the established MTTF (mean time to failure) figures for each of the components in the systemFor control in the DCS (LHS diagram) there are more partsTransmitterValveCablesTerminationsPower SupplyAI CardAO CardBackplaneControllerController Power SupplyFor CIF (Control in the Field) there are fewer partsTransmitterValveCableTerminations (&lt;half)Fieldbus Power Supply
  7. CIF is as reliable as the devices – which you’re relying on already.Plus, FF user layer adds in-built standard thoughtful features to further improve process integrity, availability, and robustness.Value and Status known EVERY (macro)CYCLE – e.g. once, twice, 4 times A SECOND, at the prescribed time within &lt; 1 millisecond. NO OTHER BUS CAN CLAIM THIS.YOU JUST DON’T GET THIS WITH “POLLED” DATA!Status Propagation - GRACEFUL DEGRADATION / FAULT TOLERANCE IS BUILT-IN, STANDARD!ASK: Who would say self-inflicted screw-ups are more common than random hardware or software faults?ASK: What’s a common self-inflicted screw-up in your plant? (Bubba goes out to work on FT-88204 and instead gets on FT-88203) The SECOND he powers it down, any associated loop will shed to manual WITHIN THE SAME MACROCYCLE.Windup protection – “Limited” status propagates to slave PID, up to cascade master if implemented.Bumpless Transfer – hooks are there to prevent process upsets from mode changes.Fault state – configurable; default is “hold last position” = highest availability.
  8. Can we apply Safety Integrity Level (SIL) calculations to evaluate basic controls? The same components make up both “loops” – why not?We asked Marszal of Kenexis Consultants to run the numbers, the same way they do for SIL analyses (a sample SIL analysis is shown)Point out that that the FIELD DEVICES (red and yellow pie slices) contribute most to PFD (probability to fail dangerous) and Spurious trip rate.ASK: What should be improved to increase reliability? (answer = devices, diagnostics)
  9. Slide 43 shows fault tree for analogue system with control in DCSMTTF = 15.9 yearsSlide 44 shows fault tree for FOUNDATION Fieldbus with Control in FieldMTTF = 48.2 yearsEquipment less prone to fail because of predictive intelligence and proactive intelligenceAbsolute values aren&apos;t realistic - as input comes from safety figures; but relative values are robustI’ve heard of projects where “all the critical loops are left 4-20 mA”. In light of this analysis, would you agree to such a strategy?
  10. Shin-Etsu plant, the card in DCS (computer) failed, but instead of shutting down the plant, able to use Control in the Field for direct communication between measurement device and valve - continue operating while change card in DCS - avoid shutdownThis is the inherent back-up capability of CIF
  11. Following findings based on study by Industrial Systems and Control Ltd - &apos;Control in the Field: Analysis of Performance Benefits&apos;Industrial Systems and Control Ltd is spin-off from Strathclyde UniversityControl Engineering Consultancy, and TrainingStudy instigated by Fieldbus Foundation EMEA
  12. Compare CIF:This example has a Rosemount 8800D FlowmeterFisher Valve Positioner20ms - AI execution in flowmeter30ms - data transfer from flowmeter to PID (proportional–integral–derivative controller) in valve positioner30ms - PID execution in valve positioner25ms - execution of instruction in valve positionerTotal latency - 105msWhich is lower than sample rate - 150ms (how often sample for instructions)With Control in Process Control System:For same set up but with control in process control system, not field20ms - AI execution in flowmeter30ms data transfer from flowmeter to PID in PCS20ms - PID execution in PCS30ms - data transfer from PCS to valve positioner25ms - execution of instruction in valve positionerTotal latency - 125msBut, asynchronous, so latency increases to 625ms because of jitter [ask for clarification on how this works if needed]Sample rate is 500msAssessment was made in simulationA simple continuous process model, coupled to a discrete PI controllerIMPORTANT - controllers tuned to same stability to allow comparisonRepeated for different process dynamicsSpeed of response to set point change and disturbance rejection assessedResults follow on next few slides
  13. Only show Setpoint, case 1 - CIF, and case 3 - asyncDifference in performance is difference in time taken for process output to settle at 60% for 1 and 3
  14. Only show Setpoint, case 1 - CIF, and case 3 - asyncDifference in performance is difference in time taken for process output to settle at 60% for 1 and 3
  15. Only show Setpoint, case 1 - CIF, and case 3 - asyncDifference in performance is difference in time taken for process output to settle at 60% for 1 and 3
  16. Only show Setpoint, case 1 - CIF, and case 3 - asyncDifference in performance is difference in time taken for process output to settle at 60% for 1 and 3
  17. Only show Setpoint, case 1 - CIF, and case 3 - asyncGraph shows ability of process control to get process output to return to setpoint without deviating to greatly when disturbed[e.g. like ability of refrigerator to get back to 2 degrees without going too hot or cold when the door is opened a lot]CIF deviates far less than case 3, which ends up quite far from the set-pointFor fast process loops (e.g. flow, some temperature) CIF provides 40-60% faster settling time than asynchronous control in the DCS
  18. “Control in the field: analysis of performance benefits” study from ISC (industrial systems and control)http://www.isc-ltd.com/
  19. If control is not tight, need to leave large margin for error in case disturbance means values go beyond control limitBecause control is tighter with CIF, it&apos;s possible to set setpoint much nearer to the control limitCan push control limits harder - aiding e.g. energy efficiency / product quality /raw material utilisation
  20. Great for theoretical and simulation, what about real world empirical tests?
  21. The test bed was a liquid pressure control in the supplier’s flow lab – some decent sized valves and pipe.Using high-speed monitoring / recording, they measured the “response time” defined as the time from a detectable disturbance or change in the PV, until the air signal to the valve began to change from steady state.RED line is Control-in-fieldYELLOW line is pure 4-20 mA (on their host only)BLUE / GREEN is control in host with various ratios of controller cycle time / FF macrocycle time.DASHED line is response period = configured cycle timeCONTROL RESPONSE PERIOD defined as the time from the introduction of a disturbance (measurement deviation) to detecting a signal to the valve actuator (change in pneumatic signal) using high-speed sensors and recording / test equipment (NOT DCS TRENDS).
  22. Like Shell Global Solutions says, when you do control in the controller, you consume a lot of the segment cycle time (macrocycle) UNNECESARILY. FOUNDATION™ Fieldbus is DESIGNED for control in field devices – It’s equally or more reliableIt’s equal or faster than 4-20 mAYou’re relying on the devices ANYHOW . . . When users and their consultants insist on old-school CIC, it’s like choosing an outstanding steak and cooking it WELL DONE . . . It takes too long and when you eat it, you wonder “what’s so great about this? Might as well just get some ole’ HART Hamburger!
  23. I don’t know of anyone who actually would install 16 devices including 8 control valves (loops) on a single segment, but this graphic shows that with judiciously chosen instruments, even EIGHT simple loops can execute in less than 0.5 seconds.Q: What do I mean by “judiciously chosen instruments”?(Choose the ones that can go fast) “Cadillac” shown, but Fisker-Karma and Toyota are catching up.