Thermal management of high power density chips
     using a two-phase loop cooling system



                                 December 16, 2011
                                     Jeehoon Choi
Background – Trends in Computing H/W Technologies

                                                                        High performance /Specialization

                                                                                           Education
   Personal                                                                 Gaming
                                                                                                       Design
  Computing                                                                          Home            Optimization
                                                  Notebook, Netbook,             Entertainment
           High performance, high heat flux
           Low-cost/lightweight market change        PMP market
           Special market




Improved integration of technology
Increase of processing speed
Aggressive miniaturization
                                                                               Move to the MID
                                                                        (Mobile Internet Device) market
                                                          High
                                                          performance

                                                           High
                                                           efficiency

                                                          Power
                                                          consumption


                                     Client / Server
                                      Computing                          Personalization   Intelligence    Reality
Background – H/W cooling in a data center




 Cost Reduction – (cost per kWh / DC : 0.0964 USD)                                                               Current Efficiency Level       Efficiency Goal
    Energy Consumed Per Hour       Current Efficiency Level      Efficiency Goal    Electricity used per Year              876,000kW                512,220kW

        Enter Total IT Load                 50kW                     50kW              Annual Power Cost                84,446 USD                  50,246 USD

         Total Facility Load               100kW                     60kW            Annual Cabon Footprint                  528 Tons                314 Tons




  Annual Data Center Efficiency Savings
                                      Reduction In            Kilowatt Hours       Electricity Costs          CO2 Emissions             Equivalent To

                                         1 Year                354,780 kW            34,201 USD                 214 Tons                40 Fewer Cars

                                        5 Years               1,773,900 kW          171,004 USD                 1,070 Tons              202 Fewer Cars

                                        10 Years              3,547,800 kW          342,008 USD                 2,139 Tons              404 Fewer Cars
Background – How can we cool efficiently down servers and data rooms?




          Sever industries and markets have
         called for the development of enhanced
         cooling techniques that are able to meet
         these challenging needs under limitations
         imposed by small overall volume and
         weight, necessary in sever rack-mount or
         workstation systems. Besides the cooling
         technique is required to attend a large
         amount of heat transfer rates over
         considerable distances with minimal
         temperature drop.



                                                     Out-of-control airflow in the data rooms
Background – History on thermal management of H/W

                               CPUs’ Heat Loads
Trends/ Heat Loads
PC Technologies




                               GPUs’ Heat Loads                                         CPU Over-clocking :
                                                                                        200~250W
                               The others (RAM & etc.)
                                                                            Xeon Series                              Increase in the heat generation
                               Heat Load Trends
                                                                130W        150W                                     operating problems at high
                                                                                                                     temperatures

                                                         100W                                                           Requires high- performance
                                          50W                                                                                thermal systems
                               Pentium                                                   RAM, M/B & etc.
                               (15W)                                                    Increase heat flux
                     PC
                     popularization                                                                                             Next- generation
                                                                                                                               cooing technology
                     1980       1990        2000                2005                  2010

                                                           Passive & Active cooling
                         Personal                                                            Water cooling
                         computing
                         cooling
                                                                                               Heat pipe application cooling
Research
/Products




                                 Server                                                             Active cooling
                                 computing
                                 cooling
                                                                                                     Water cooling
Background – Taking note of                                                two-phase loop cooling systems


  The LHP is a two-phase heat transfer device
  with capillary pumping of working fluid. They are
  capable of transferring a large amount of heat                                       Q    
                                                                                            mc p T                  Q     
                                                                                                                          mh fg
  for distances up to several meters.

                                                                                      Sensible heat                 Latent heat
        Reservoir




                                        Loop Heat Pipe


                                           Vapor Line                                   The advantages of LHP
                    Evaporator Pump




                                                                             • High heat flux capability
                                                                Condenser



                                                                             • Capability to transfer energy over long distances
                                                                               without restriction due to routing of liquid & vapor line
                                         Liquid Line
Wick
                                                                             • Ability to operate over a gravitational field gradient
                          Conventional Heat pipe
                                      Liquid
                                                                             • No wick within the transport lines

                                                                             • Vapor and liquid flows separated;
                                                                               therefore, no entrainment
 Evaporator                                             Condenser
                                      Vapor

 This system comprises an evaporator and a condenser, as in conventional heat pipes, but differs in
 having separate vapor and liquid line, rather like the layout of the single phase heat exchanger system.
Motivation and Objectives
• One sever rack has the same heating power as a heating of a one-family house (~25kW).
• Cooling, power supply and data center infrastructure need twice as much electricity than the computers itself.
• Current techniques reached its physical limit.


                                            High Performance
                                             •Chip temperature - below 70 ℃
                                              from a large amount of heat flux
          Space constraints                 • Stability/Reliability
          • Long distance transport lines
          • Smaller/ thinner evaporator
          • Light-weight system             Design For Cost (DFC)
                                            •Design For Manufacturing (DFM)                              Hot w at er   Cold w at er
                                            •Design For Assembly (DFA)



 The two-phase loop cooling
system must be developed within
                                                  Evaporator                        Sever
certain constrains, associated, in                                Condenser
                                                                                    Rack- m ount 4
large part, with its application
high density technologies.                                                        Sever
                                                                                  Rack- m ount 3

                                     CPU
                                                                              Sever
                                            RAM                               Rack- m ount 2


                            Power
                            Supply                HDD

                                                                                                     Sever
                                                                                                     Rack- m ount 1
Theory – Principle of operation
                                                         When a heat load is applied to the evaporator fluid evaporates from the
                                                         surface of the wick. The capillary pumping forces in the wick prevent the
                                                         flow of the vapor from evaporator to LCC. As the pressure difference
                                                         between evaporator and LCC increases, the liquid is displaced from the
                                                         vapor transport line and the condenser and returned to the LCC.

                       Liquid
                                                                   4: vapor-liquid interface
                                                                                       Heat out

                                                                                                  3: condenser inlet                   Liquid flow through wick
                             Vapor
                                                                                                                                       Evaporation               Saturation line
                                                                                                                  Pressure

           Liquid                                                                                                        P1                                  1
           transport                    5 : condenser outlet                                                                                                             2
                                                                            Condenser
           line                                                                             Vapor                        P3                                              3
                                Liquid compensation                                         transport
                                                                                                                                        Liquid               4
                                Chamber (LCC)                                               line
                                                                                                                        P5        5                                                Pc ,max
                         6: Liquid                7: wick-liquid
  8: wick-vapor             inlet                    interface           Vapor removal channel                          P6                           7
     interface                                                                                                                6

                                                                                                                                                                             Pw
                                                                                                                                                     Vapor
                                                                                                                                                                     8
                                                                                                                        P8
                       1: vapor                                            2 : vapor line inlet
                                                                                                                                  T6                 T7      T4 T1
                                                                            Wick
                                     Evaporator                                                                                                                      Temperature
Evaporating meniscus
                                The wick structure provides capillary pressure force that transports the
                                condensate liquid back to the evaporator and ensures working fluid is evenly
                                distributed over evaporator surface.
Modeling – Temperature and Thermal resistance circuit
                                                           The maximum heat transfer capacity of electronics cooling systems is
                                                           determined based on the maximum permissible temperature at the
  Allowable junction temperature                           semiconductor chips which is normally less than 70°C. With a given constant
                                                           value of ambient temperature, the operating temperature is iteratively solved
                                                           for the given input value of applied heat load.
                                                     Thermal
                                                     grease              Liquid transport line
                                      Heat source

                                                                                                            Tc    Ths
                                          Q               Te                                Condenser                              Q
                                                    Tj               Evaporator                                         Ta
     Temperature profile




                                                               Tvi
                             Chip junction temp.
                                                                          Vapor transport line
                              Evaporator temp.
                           Vapor line inlet temp.

                                Heat sink temp.
                                Ambient temp.
                                                                                                                             Location
Total thermal resistance
Modeling – Heat sink design and simulation

 Max. heat dissipation capacity of condenser                                Cu




                                                                             Al


Overall surface efficiency
of condenser
                               Long Mean Temperature Difference (LMTD)



Force convection coefficient

                                                                         Fin thickness and fin height
                                                                         at given heat transfer coefficients
Modeling – Pressure balance
 Capillary pressure limits – pressure balance analysis


           Ploss                    Pc ,max                     Ploss        Pw        Pv           Pc                         Pl        Pg
                                                                        Maximum capillary pressure       Pc ,max

                                                           Pv
               Pressure profile




                                  Wick                                                               Wick
                                                                             Pc
                                   Pw           Vapor removal                                  Pl
                                                channel                                                                         Pw
                                                                            Tc                                                            Vapor
                                                                                                                                          transport
                                              Vapor transport line        Condenser Liquid transport line                                 line

                                                                                                                                              Location


 Pw   Wick pressure drop, due to liquid flow through the wick thickness




                                                                                                            Pressure profile
      Vapor pressure drop, necessary to cause the vapor to flow
 Pv   from the evaporator to the condenser.
 Pc   Condenser pressure drop
      The hydrostatic head due to the unfavorable slopes of the system in
      the gravitational field, ΔPg ,which may be zero, positive or negative,
      depending on relative positions of the condenser and the evaporator.
 Pl   Liquid pressure drop, required to return the liquid
      from the condenser to the evaporator.                                                                                         Pw    Pv          Pc   Pl
Modeling – Driving force of system

      Wick structure for capillary pressure


                      2
        Pc ,max
                      Reff                                               2
                                                         P    P2     P                                   1     1
                                                          1
                                                                          R       P      P2      P
                                   Qlatent   
                                             mh fg
                                                                                   1
                                                                                                         R1    R2
                                                     Pressure difference across        Geometry of meniscus
                                                     a curved liquid surface           at liquid-vapor interface
            Vapor                 Tv
            removal                                                                     CNTs
            space                                                                                        CNTs
                         Revp                                                                            Growth

                                  Twe                                                  Cu Wick
                                                                                                         Provided
Primary wick             Rw                                                       Cu Substrate

                                                                                  Alumina layer
                                  Twi                                                                   Anodization
                             Rb                                                                         process
                                                                                       Cu Wick
 The copper plate                 Te                                                                    Provided

                                                                                  Cu Substrate
                                  Q0
Modeling – Total pressure loss calculation (Component design)
                                     The pressure drop due to friction losses in                                             L u2
          Pressure loss              liquid and vapor flow through the loop (for                             P             f
                                     laminar or turbulent flows, circular or non-                                            D 2
                                     circular pipes, smooth or rough surfaces) is
                                     given by Darcy-Weisbach equation.                                        Q
                                                                                               u                                   Qlatent       
                                                                                                                                                 mh fg
                                                                                                              Ah fg

    Wick pressure drop                          Vapor line pressure drop                                   Liquid line pressure drop

                 
            tw l m          tw l Q                   32 Lvi vuv2
                                                                         32 Lvi vQ                              32 Lli l ul2               32 Lli l Q
     Pw                                       Pv                                                       P
            Aw l K         Aw l h fg K                Revl Dvl               4
                                                                          Dvl v h fg                    l
                                                                                                                 Rell Dll                      4
                                                                                                                                            Dll l h fg

     Hydrostatic head of liquid                    Condenser pressure drop


     Pg      l   gl sin                                   2    x2         (1 x)                    2         x2              (1 x)
                                              Pcon    G                                        G
                                                                    v   (1   ) l       z z2                       v        (1   ) l          z z1

K   Permeability
                                                              2G 2      z z2                                        z z2
x   Mass quality                                                               fv x2   2
                                                                                       v   dz g sin                        [   v       (1        )]x 2 dz
                                                              v Dcon
                                                                        z z1                                      z z1
    (vapor mass flux/total mass flux)

G   Mass flux     (G      
                          m / A)             Void fraction
                                                                                                             0.36                   0.07     1
    Correlations from the friction                                                     0.64
                                                                               1 x                 v                           l
    pressure drop in each phase                                 1 0.28
    (Ref. the Lockhart-Martinelli method)                                       x                      l                       v
Outcome – Simulation program on the basis of system pressure balance
 The results of the predicted design parameters
help not only to understand the system
performance of at various conditions, but also to
provide details of how the system operates. We
have developed the simulation program for the
system design optimization with the effect of
design parameters using the objective function,
design variables and design boundaries.




                                                    Design variable and boundaries




                Visualization program for
           optimization design and simulation
                                                    Parametric studies of the design
                                                    variables and boundaries
Future work – Improvement factors
 Max. Heat transfer capacity                          System operating temperature

The capillary pumping performance of                 -Vapor temperature
wick structure has important effect on system.        ;less than 40°C level at given heat loads
It is necessary to develop the high performance
evaporator mounted with superior wick structures.                   n
                                                                                  dP
                                                                        Pi           T
                                                               i 1                dT
                    Straight pores
                                                                                  Liquid flow through wick
                                                                                   Evaporation               Saturation line
                                                    Pressure

                                                               P1                                        1
                                                                                                                     2
                                                               P3                                                    3
                                                                                    Liquid               4

                                                           P5                5                                                 Pc ,max
                                                           P6                                    7
                                                                         6


                                                                                                 Vapor
                                                                                                                 8
                                                           P8


                                                                             T6                   T7     T4 T1
                                                                                                                 Temperature
Future work – Material properties 1
Working fluid and Material selection

 As part of a design procedure for a targeted            Operating temperature range
application, the selection of the working fluid is the    of various working fluids
first step. The working fluid determines the range of
the operating temperature and must satisfy a
number of criteria. In the second step, it is
necessary to decide the compatibility between the
working fluid and the material to avoid chemical
reactions. The chemical reactions would cause the
degradation of the mechanical strength or the
tightness of the LHP, or the existence of non-
condensable gases which could alter the LHP
operation.

       Compatibility metals with working fluids
       (C: compatible, NC: incompatible)
Future work – Material properties 2
Merit number                             h fg   The effect of working fluid on heat transfer
The ranking of working fluid             c pl   capability and/or system operating temperature


        l   h fg   l   h fg   l            l    The friction factor associated
 M                                c
                                  l pl                                                Maximum capillary pressure
                       c pl                     with pressure loss of system      l
              l               l            l
Future work – Material properties 3
                                                                                                      Constant
                                Temperature                         Tcritical                      pressure curves

                                                  Sub-cooled
                                                 liquid region                      B
                                                                          A     C

                                                                                D
                                                                                          Superheated
                                                                 Liquid vapor mix/         vapor region
                                   Saturated
                                                                 two-phase region                    Saturated
                                   liquid line
                                                                                                     vapor line


                                                                                        Entropy




                                                 Vapor temperature vs. Vapor pressure
                                       Change hfg by controlling the evaporator pressure
Summary – Research roadmap

  Design objective          Design requirements
                                                                             Materials
Sever rack-mount cooling    Heat load, Chip temperature,                (with working fluid)
                            Ambient temperature, Weight,
                            Space constraints, Noise level,
                            Transport line length, Cost, etc.




                                        Component Models
            Experiment                                                     System Model
           Investigation              Condenser, Transport line,
                                      Evaporator, Airflow, etc.

                                                                         System Simulation
         Wick fabrication
                                         Design parameters
                                         (key correlations)                  Prototype
            Theoretical                                                 Design and Modeling
                                      Pressure loss, Void fraction
              Models                  Heat transfer coefficient, etc.
                                                                           Prototype test
Summary – Works
             Project schedule and plan                                        Detailed design prototypes

 Detail design and concept generation                           Heat source            Total heat dissipation condition on one
                                                                                       or multi chips (Specially, CPUs)
-A prototype model with compact condenser with a fan can                               ; more than 300W
 be mounted inside a sever rack-mount.                                                  (One CPU is more than 14 W/cm2)
                                                                Allowable              Below 60 ℃
-Analyzing parameters, operating conditions, constraints,
                                                                junction               * Steady state condition
 etc. to build the systems.
                                                                temp. of chips
-Thermodynamic cycle and operating limits to understand         Evaporator             40mm (width) x 40mm(length)
 the physical concepts and operating principle of the loop      dimension              x less than 5mm (height)
 scheme.
                                                                Transport line         Between 0.5 m and 1.0 m
                                                                Length                 (Taking note of flexible tubes)
-Selection of working fluid/material/wick structure.


 Evaporator sample fabrication and investigation
                                                                                                Evaporator
                                                                                                                  Condenser
-Theoretical and experimental investigation
 (Obtaining wick characters – Nano/Micro application)

 Updated system algorism and design refinement                                   CPU
 based on previous findings                                                              RAM

 -To apply new parameters to the optimization program                Power
                                                                     Supply                    HDD
 - Comparison of experimental reviews with simulation results
Thank you very much !!!

Más contenido relacionado

Destacado

Plumber colorado springs co open rooter
Plumber colorado springs co   open rooterPlumber colorado springs co   open rooter
Plumber colorado springs co open rooterplumber80903
 
Lazette Harnish: America's Most-Visited Tourist Places
Lazette Harnish: America's Most-Visited Tourist PlacesLazette Harnish: America's Most-Visited Tourist Places
Lazette Harnish: America's Most-Visited Tourist PlacesLazette Harnish
 
Oportunidades y desafíos del Acuerdo Comercial del Perú con la India
Oportunidades y desafíos del Acuerdo Comercial del Perú con la IndiaOportunidades y desafíos del Acuerdo Comercial del Perú con la India
Oportunidades y desafíos del Acuerdo Comercial del Perú con la India Carlos Alberto Aquino Rodriguez
 
Sintesis informativa 22 de marzo 2017
Sintesis informativa 22 de marzo 2017Sintesis informativa 22 de marzo 2017
Sintesis informativa 22 de marzo 2017megaradioexpress
 
Moodle is dead... Iain Bruce, James Blair, Michael O'Loughlin
Moodle is dead... 	Iain Bruce, James Blair, Michael O'LoughlinMoodle is dead... 	Iain Bruce, James Blair, Michael O'Loughlin
Moodle is dead... Iain Bruce, James Blair, Michael O'LoughlinIreland & UK Moodlemoot 2012
 
Ringmakers of-saturn---norman-r.-bergrun
Ringmakers of-saturn---norman-r.-bergrunRingmakers of-saturn---norman-r.-bergrun
Ringmakers of-saturn---norman-r.-bergrunLex Pit
 
Curriculum vitae ana_ma_orti_gonzalez_curriculweb
Curriculum vitae ana_ma_orti_gonzalez_curriculwebCurriculum vitae ana_ma_orti_gonzalez_curriculweb
Curriculum vitae ana_ma_orti_gonzalez_curriculwebUNIVERSIDAD DE SEVILLA
 
Rural Supermarkets by Abhishek Bhatia
Rural Supermarkets by Abhishek BhatiaRural Supermarkets by Abhishek Bhatia
Rural Supermarkets by Abhishek BhatiaAbhishek Bhatia
 
Global impact of_wwii
Global impact of_wwiiGlobal impact of_wwii
Global impact of_wwiiMatt Scully
 

Destacado (14)

MagenTys Service Overview
MagenTys Service OverviewMagenTys Service Overview
MagenTys Service Overview
 
Goyescas
GoyescasGoyescas
Goyescas
 
Plumber colorado springs co open rooter
Plumber colorado springs co   open rooterPlumber colorado springs co   open rooter
Plumber colorado springs co open rooter
 
Lazette Harnish: America's Most-Visited Tourist Places
Lazette Harnish: America's Most-Visited Tourist PlacesLazette Harnish: America's Most-Visited Tourist Places
Lazette Harnish: America's Most-Visited Tourist Places
 
Oportunidades y desafíos del Acuerdo Comercial del Perú con la India
Oportunidades y desafíos del Acuerdo Comercial del Perú con la IndiaOportunidades y desafíos del Acuerdo Comercial del Perú con la India
Oportunidades y desafíos del Acuerdo Comercial del Perú con la India
 
Religion and Enviroment
Religion and EnviromentReligion and Enviroment
Religion and Enviroment
 
Sintesis informativa 22 de marzo 2017
Sintesis informativa 22 de marzo 2017Sintesis informativa 22 de marzo 2017
Sintesis informativa 22 de marzo 2017
 
Moodle is dead... Iain Bruce, James Blair, Michael O'Loughlin
Moodle is dead... 	Iain Bruce, James Blair, Michael O'LoughlinMoodle is dead... 	Iain Bruce, James Blair, Michael O'Loughlin
Moodle is dead... Iain Bruce, James Blair, Michael O'Loughlin
 
Ringmakers of-saturn---norman-r.-bergrun
Ringmakers of-saturn---norman-r.-bergrunRingmakers of-saturn---norman-r.-bergrun
Ringmakers of-saturn---norman-r.-bergrun
 
Csodálatunk tárgyai
Csodálatunk tárgyaiCsodálatunk tárgyai
Csodálatunk tárgyai
 
Curriculum vitae ana_ma_orti_gonzalez_curriculweb
Curriculum vitae ana_ma_orti_gonzalez_curriculwebCurriculum vitae ana_ma_orti_gonzalez_curriculweb
Curriculum vitae ana_ma_orti_gonzalez_curriculweb
 
Rural Supermarkets by Abhishek Bhatia
Rural Supermarkets by Abhishek BhatiaRural Supermarkets by Abhishek Bhatia
Rural Supermarkets by Abhishek Bhatia
 
wp-cli
wp-cliwp-cli
wp-cli
 
Global impact of_wwii
Global impact of_wwiiGlobal impact of_wwii
Global impact of_wwii
 

Similar a Two phase loop cooling system

云计算核心技术架构分论坛 一石三鸟 性能 功耗及成本
云计算核心技术架构分论坛 一石三鸟 性能 功耗及成本云计算核心技术架构分论坛 一石三鸟 性能 功耗及成本
云计算核心技术架构分论坛 一石三鸟 性能 功耗及成本Riquelme624
 
Eco friendly hd-ds_wp_final
Eco friendly hd-ds_wp_finalEco friendly hd-ds_wp_final
Eco friendly hd-ds_wp_finalGirish Narkar
 
Green computing
Green computingGreen computing
Green computingisha_rana
 
PowerColor PCS+ Vortex II sales kit
PowerColor PCS+ Vortex II sales kitPowerColor PCS+ Vortex II sales kit
PowerColor PCS+ Vortex II sales kitPowerColor
 
Pcs vortex_ii_sales_kit
Pcs  vortex_ii_sales_kitPcs  vortex_ii_sales_kit
Pcs vortex_ii_sales_kitPowerColor
 
Productive parallel programming for intel xeon phi coprocessors
Productive parallel programming for intel xeon phi coprocessorsProductive parallel programming for intel xeon phi coprocessors
Productive parallel programming for intel xeon phi coprocessorsinside-BigData.com
 
How to be green in the cloud
How to be green in the cloudHow to be green in the cloud
How to be green in the cloudVMEngine
 
Keynote Speech - Low Power Seminar, Jain College, October 5th 2012
Keynote Speech - Low Power Seminar, Jain College, October 5th 2012Keynote Speech - Low Power Seminar, Jain College, October 5th 2012
Keynote Speech - Low Power Seminar, Jain College, October 5th 2012Dr. Shivananda Koteshwar
 
PoE.Standards, technologies and solutions
PoE.Standards, technologies and solutionsPoE.Standards, technologies and solutions
PoE.Standards, technologies and solutionsEvaldas Paliliūnas
 
AMD Opteron 6200 and 4200 Series Presentation
AMD Opteron 6200 and 4200 Series PresentationAMD Opteron 6200 and 4200 Series Presentation
AMD Opteron 6200 and 4200 Series PresentationAMD
 
Sun sparc enterprise t5140 and t5240 servers customer presentation
Sun sparc enterprise t5140 and t5240 servers customer presentationSun sparc enterprise t5140 and t5240 servers customer presentation
Sun sparc enterprise t5140 and t5240 servers customer presentationxKinAnx
 
Trilogy - Henk Groenendijk
Trilogy - Henk GroenendijkTrilogy - Henk Groenendijk
Trilogy - Henk GroenendijkHPDutchWorld
 
Power Optimization Through Manycore Multiprocessing
Power Optimization Through Manycore MultiprocessingPower Optimization Through Manycore Multiprocessing
Power Optimization Through Manycore Multiprocessingchiportal
 
DataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure PresentationDataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure PresentationMuhammad Asad Rashid
 
MAHLE Data Recorder 2 (MDR2)
MAHLE Data Recorder 2 (MDR2)MAHLE Data Recorder 2 (MDR2)
MAHLE Data Recorder 2 (MDR2)Brian Trimboli
 
Holistic approaches to green it gregynog colloquium - june 2011
Holistic approaches to green it   gregynog colloquium - june 2011Holistic approaches to green it   gregynog colloquium - june 2011
Holistic approaches to green it gregynog colloquium - june 2011gregynog
 

Similar a Two phase loop cooling system (20)

云计算核心技术架构分论坛 一石三鸟 性能 功耗及成本
云计算核心技术架构分论坛 一石三鸟 性能 功耗及成本云计算核心技术架构分论坛 一石三鸟 性能 功耗及成本
云计算核心技术架构分论坛 一石三鸟 性能 功耗及成本
 
Eco friendly hd-ds_wp_final
Eco friendly hd-ds_wp_finalEco friendly hd-ds_wp_final
Eco friendly hd-ds_wp_final
 
IT Energy Waste - Green IT Expo 2009
IT Energy Waste - Green IT Expo 2009IT Energy Waste - Green IT Expo 2009
IT Energy Waste - Green IT Expo 2009
 
Green computing
Green computingGreen computing
Green computing
 
PowerColor PCS+ Vortex II sales kit
PowerColor PCS+ Vortex II sales kitPowerColor PCS+ Vortex II sales kit
PowerColor PCS+ Vortex II sales kit
 
Pcs vortex_ii_sales_kit
Pcs  vortex_ii_sales_kitPcs  vortex_ii_sales_kit
Pcs vortex_ii_sales_kit
 
Productive parallel programming for intel xeon phi coprocessors
Productive parallel programming for intel xeon phi coprocessorsProductive parallel programming for intel xeon phi coprocessors
Productive parallel programming for intel xeon phi coprocessors
 
How to be green in the cloud
How to be green in the cloudHow to be green in the cloud
How to be green in the cloud
 
Keynote Speech - Low Power Seminar, Jain College, October 5th 2012
Keynote Speech - Low Power Seminar, Jain College, October 5th 2012Keynote Speech - Low Power Seminar, Jain College, October 5th 2012
Keynote Speech - Low Power Seminar, Jain College, October 5th 2012
 
PoE.Standards, technologies and solutions
PoE.Standards, technologies and solutionsPoE.Standards, technologies and solutions
PoE.Standards, technologies and solutions
 
AMD Opteron 6200 and 4200 Series Presentation
AMD Opteron 6200 and 4200 Series PresentationAMD Opteron 6200 and 4200 Series Presentation
AMD Opteron 6200 and 4200 Series Presentation
 
Gamatronics Solutions for Data Centers
Gamatronics Solutions for Data CentersGamatronics Solutions for Data Centers
Gamatronics Solutions for Data Centers
 
Sun sparc enterprise t5140 and t5240 servers customer presentation
Sun sparc enterprise t5140 and t5240 servers customer presentationSun sparc enterprise t5140 and t5240 servers customer presentation
Sun sparc enterprise t5140 and t5240 servers customer presentation
 
Tachion
TachionTachion
Tachion
 
Trilogy - Henk Groenendijk
Trilogy - Henk GroenendijkTrilogy - Henk Groenendijk
Trilogy - Henk Groenendijk
 
Power Optimization Through Manycore Multiprocessing
Power Optimization Through Manycore MultiprocessingPower Optimization Through Manycore Multiprocessing
Power Optimization Through Manycore Multiprocessing
 
DataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure PresentationDataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure Presentation
 
Greencomputing by nadeemsarshar
Greencomputing by nadeemsarsharGreencomputing by nadeemsarshar
Greencomputing by nadeemsarshar
 
MAHLE Data Recorder 2 (MDR2)
MAHLE Data Recorder 2 (MDR2)MAHLE Data Recorder 2 (MDR2)
MAHLE Data Recorder 2 (MDR2)
 
Holistic approaches to green it gregynog colloquium - june 2011
Holistic approaches to green it   gregynog colloquium - june 2011Holistic approaches to green it   gregynog colloquium - june 2011
Holistic approaches to green it gregynog colloquium - june 2011
 

Último

Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxLoriGlavin3
 
Scale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterScale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterMydbops
 
Design pattern talk by Kaya Weers - 2024 (v2)
Design pattern talk by Kaya Weers - 2024 (v2)Design pattern talk by Kaya Weers - 2024 (v2)
Design pattern talk by Kaya Weers - 2024 (v2)Kaya Weers
 
Testing tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examplesTesting tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examplesKari Kakkonen
 
A Framework for Development in the AI Age
A Framework for Development in the AI AgeA Framework for Development in the AI Age
A Framework for Development in the AI AgeCprime
 
Abdul Kader Baba- Managing Cybersecurity Risks and Compliance Requirements i...
Abdul Kader Baba- Managing Cybersecurity Risks  and Compliance Requirements i...Abdul Kader Baba- Managing Cybersecurity Risks  and Compliance Requirements i...
Abdul Kader Baba- Managing Cybersecurity Risks and Compliance Requirements i...itnewsafrica
 
Potential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and InsightsPotential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and InsightsRavi Sanghani
 
UiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to HeroUiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to HeroUiPathCommunity
 
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptxThe Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptxLoriGlavin3
 
Microsoft 365 Copilot: How to boost your productivity with AI – Part one: Ado...
Microsoft 365 Copilot: How to boost your productivity with AI – Part one: Ado...Microsoft 365 Copilot: How to boost your productivity with AI – Part one: Ado...
Microsoft 365 Copilot: How to boost your productivity with AI – Part one: Ado...Nikki Chapple
 
Data governance with Unity Catalog Presentation
Data governance with Unity Catalog PresentationData governance with Unity Catalog Presentation
Data governance with Unity Catalog PresentationKnoldus Inc.
 
Connecting the Dots for Information Discovery.pdf
Connecting the Dots for Information Discovery.pdfConnecting the Dots for Information Discovery.pdf
Connecting the Dots for Information Discovery.pdfNeo4j
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxLoriGlavin3
 
Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...Farhan Tariq
 
2024 April Patch Tuesday
2024 April Patch Tuesday2024 April Patch Tuesday
2024 April Patch TuesdayIvanti
 
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...Alkin Tezuysal
 
Generative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdfGenerative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdfIngrid Airi González
 
So einfach geht modernes Roaming fuer Notes und Nomad.pdf
So einfach geht modernes Roaming fuer Notes und Nomad.pdfSo einfach geht modernes Roaming fuer Notes und Nomad.pdf
So einfach geht modernes Roaming fuer Notes und Nomad.pdfpanagenda
 
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024BookNet Canada
 
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Mark Goldstein
 

Último (20)

Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
 
Scale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterScale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL Router
 
Design pattern talk by Kaya Weers - 2024 (v2)
Design pattern talk by Kaya Weers - 2024 (v2)Design pattern talk by Kaya Weers - 2024 (v2)
Design pattern talk by Kaya Weers - 2024 (v2)
 
Testing tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examplesTesting tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examples
 
A Framework for Development in the AI Age
A Framework for Development in the AI AgeA Framework for Development in the AI Age
A Framework for Development in the AI Age
 
Abdul Kader Baba- Managing Cybersecurity Risks and Compliance Requirements i...
Abdul Kader Baba- Managing Cybersecurity Risks  and Compliance Requirements i...Abdul Kader Baba- Managing Cybersecurity Risks  and Compliance Requirements i...
Abdul Kader Baba- Managing Cybersecurity Risks and Compliance Requirements i...
 
Potential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and InsightsPotential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and Insights
 
UiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to HeroUiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to Hero
 
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptxThe Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
 
Microsoft 365 Copilot: How to boost your productivity with AI – Part one: Ado...
Microsoft 365 Copilot: How to boost your productivity with AI – Part one: Ado...Microsoft 365 Copilot: How to boost your productivity with AI – Part one: Ado...
Microsoft 365 Copilot: How to boost your productivity with AI – Part one: Ado...
 
Data governance with Unity Catalog Presentation
Data governance with Unity Catalog PresentationData governance with Unity Catalog Presentation
Data governance with Unity Catalog Presentation
 
Connecting the Dots for Information Discovery.pdf
Connecting the Dots for Information Discovery.pdfConnecting the Dots for Information Discovery.pdf
Connecting the Dots for Information Discovery.pdf
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
 
Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...
 
2024 April Patch Tuesday
2024 April Patch Tuesday2024 April Patch Tuesday
2024 April Patch Tuesday
 
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
 
Generative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdfGenerative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdf
 
So einfach geht modernes Roaming fuer Notes und Nomad.pdf
So einfach geht modernes Roaming fuer Notes und Nomad.pdfSo einfach geht modernes Roaming fuer Notes und Nomad.pdf
So einfach geht modernes Roaming fuer Notes und Nomad.pdf
 
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
 
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
 

Two phase loop cooling system

  • 1. Thermal management of high power density chips using a two-phase loop cooling system December 16, 2011 Jeehoon Choi
  • 2. Background – Trends in Computing H/W Technologies High performance /Specialization Education Personal Gaming Design Computing Home Optimization Notebook, Netbook, Entertainment High performance, high heat flux Low-cost/lightweight market change PMP market Special market Improved integration of technology Increase of processing speed Aggressive miniaturization Move to the MID (Mobile Internet Device) market High performance High efficiency Power consumption Client / Server Computing Personalization Intelligence Reality
  • 3. Background – H/W cooling in a data center Cost Reduction – (cost per kWh / DC : 0.0964 USD) Current Efficiency Level Efficiency Goal Energy Consumed Per Hour Current Efficiency Level Efficiency Goal Electricity used per Year 876,000kW 512,220kW Enter Total IT Load 50kW 50kW Annual Power Cost 84,446 USD 50,246 USD Total Facility Load 100kW 60kW Annual Cabon Footprint 528 Tons 314 Tons Annual Data Center Efficiency Savings Reduction In Kilowatt Hours Electricity Costs CO2 Emissions Equivalent To 1 Year 354,780 kW 34,201 USD 214 Tons 40 Fewer Cars 5 Years 1,773,900 kW 171,004 USD 1,070 Tons 202 Fewer Cars 10 Years 3,547,800 kW 342,008 USD 2,139 Tons 404 Fewer Cars
  • 4. Background – How can we cool efficiently down servers and data rooms? Sever industries and markets have called for the development of enhanced cooling techniques that are able to meet these challenging needs under limitations imposed by small overall volume and weight, necessary in sever rack-mount or workstation systems. Besides the cooling technique is required to attend a large amount of heat transfer rates over considerable distances with minimal temperature drop. Out-of-control airflow in the data rooms
  • 5. Background – History on thermal management of H/W CPUs’ Heat Loads Trends/ Heat Loads PC Technologies GPUs’ Heat Loads CPU Over-clocking : 200~250W The others (RAM & etc.) Xeon Series Increase in the heat generation Heat Load Trends 130W 150W operating problems at high temperatures 100W Requires high- performance 50W thermal systems Pentium RAM, M/B & etc. (15W) Increase heat flux PC popularization Next- generation cooing technology 1980 1990 2000 2005 2010 Passive & Active cooling Personal Water cooling computing cooling Heat pipe application cooling Research /Products Server Active cooling computing cooling Water cooling
  • 6. Background – Taking note of two-phase loop cooling systems The LHP is a two-phase heat transfer device with capillary pumping of working fluid. They are capable of transferring a large amount of heat Q  mc p T Q  mh fg for distances up to several meters. Sensible heat Latent heat Reservoir Loop Heat Pipe Vapor Line The advantages of LHP Evaporator Pump • High heat flux capability Condenser • Capability to transfer energy over long distances without restriction due to routing of liquid & vapor line Liquid Line Wick • Ability to operate over a gravitational field gradient Conventional Heat pipe Liquid • No wick within the transport lines • Vapor and liquid flows separated; therefore, no entrainment Evaporator Condenser Vapor This system comprises an evaporator and a condenser, as in conventional heat pipes, but differs in having separate vapor and liquid line, rather like the layout of the single phase heat exchanger system.
  • 7. Motivation and Objectives • One sever rack has the same heating power as a heating of a one-family house (~25kW). • Cooling, power supply and data center infrastructure need twice as much electricity than the computers itself. • Current techniques reached its physical limit. High Performance •Chip temperature - below 70 ℃ from a large amount of heat flux Space constraints • Stability/Reliability • Long distance transport lines • Smaller/ thinner evaporator • Light-weight system Design For Cost (DFC) •Design For Manufacturing (DFM) Hot w at er Cold w at er •Design For Assembly (DFA) The two-phase loop cooling system must be developed within Evaporator Sever certain constrains, associated, in Condenser Rack- m ount 4 large part, with its application high density technologies. Sever Rack- m ount 3 CPU Sever RAM Rack- m ount 2 Power Supply HDD Sever Rack- m ount 1
  • 8. Theory – Principle of operation When a heat load is applied to the evaporator fluid evaporates from the surface of the wick. The capillary pumping forces in the wick prevent the flow of the vapor from evaporator to LCC. As the pressure difference between evaporator and LCC increases, the liquid is displaced from the vapor transport line and the condenser and returned to the LCC. Liquid 4: vapor-liquid interface Heat out 3: condenser inlet Liquid flow through wick Vapor Evaporation Saturation line Pressure Liquid P1 1 transport 5 : condenser outlet 2 Condenser line Vapor P3 3 Liquid compensation transport Liquid 4 Chamber (LCC) line P5 5 Pc ,max 6: Liquid 7: wick-liquid 8: wick-vapor inlet interface Vapor removal channel P6 7 interface 6 Pw Vapor 8 P8 1: vapor 2 : vapor line inlet T6 T7 T4 T1 Wick Evaporator Temperature Evaporating meniscus The wick structure provides capillary pressure force that transports the condensate liquid back to the evaporator and ensures working fluid is evenly distributed over evaporator surface.
  • 9. Modeling – Temperature and Thermal resistance circuit The maximum heat transfer capacity of electronics cooling systems is determined based on the maximum permissible temperature at the Allowable junction temperature semiconductor chips which is normally less than 70°C. With a given constant value of ambient temperature, the operating temperature is iteratively solved for the given input value of applied heat load. Thermal grease Liquid transport line Heat source Tc Ths Q Te Condenser Q Tj Evaporator Ta Temperature profile Tvi Chip junction temp. Vapor transport line Evaporator temp. Vapor line inlet temp. Heat sink temp. Ambient temp. Location Total thermal resistance
  • 10. Modeling – Heat sink design and simulation Max. heat dissipation capacity of condenser Cu Al Overall surface efficiency of condenser Long Mean Temperature Difference (LMTD) Force convection coefficient Fin thickness and fin height at given heat transfer coefficients
  • 11. Modeling – Pressure balance Capillary pressure limits – pressure balance analysis Ploss Pc ,max Ploss Pw Pv Pc Pl Pg Maximum capillary pressure Pc ,max Pv Pressure profile Wick Wick Pc Pw Vapor removal Pl channel Pw Tc Vapor transport Vapor transport line Condenser Liquid transport line line Location Pw Wick pressure drop, due to liquid flow through the wick thickness Pressure profile Vapor pressure drop, necessary to cause the vapor to flow Pv from the evaporator to the condenser. Pc Condenser pressure drop The hydrostatic head due to the unfavorable slopes of the system in the gravitational field, ΔPg ,which may be zero, positive or negative, depending on relative positions of the condenser and the evaporator. Pl Liquid pressure drop, required to return the liquid from the condenser to the evaporator. Pw Pv Pc Pl
  • 12. Modeling – Driving force of system Wick structure for capillary pressure 2 Pc ,max Reff 2 P P2 P 1 1 1 R P P2 P Qlatent  mh fg 1 R1 R2 Pressure difference across Geometry of meniscus a curved liquid surface at liquid-vapor interface Vapor Tv removal CNTs space CNTs Revp Growth Twe Cu Wick Provided Primary wick Rw Cu Substrate Alumina layer Twi Anodization Rb process Cu Wick The copper plate Te Provided Cu Substrate Q0
  • 13. Modeling – Total pressure loss calculation (Component design) The pressure drop due to friction losses in L u2 Pressure loss liquid and vapor flow through the loop (for P f laminar or turbulent flows, circular or non- D 2 circular pipes, smooth or rough surfaces) is given by Darcy-Weisbach equation. Q u Qlatent  mh fg Ah fg Wick pressure drop Vapor line pressure drop Liquid line pressure drop  tw l m tw l Q 32 Lvi vuv2 32 Lvi vQ 32 Lli l ul2 32 Lli l Q Pw Pv P Aw l K Aw l h fg K Revl Dvl 4 Dvl v h fg l Rell Dll 4 Dll l h fg Hydrostatic head of liquid Condenser pressure drop Pg l gl sin 2 x2 (1 x) 2 x2 (1 x) Pcon G G v (1 ) l z z2 v (1 ) l z z1 K Permeability 2G 2 z z2 z z2 x Mass quality fv x2 2 v dz g sin [ v (1 )]x 2 dz v Dcon z z1 z z1 (vapor mass flux/total mass flux) G Mass flux (G  m / A) Void fraction 0.36 0.07 1 Correlations from the friction 0.64 1 x v l pressure drop in each phase 1 0.28 (Ref. the Lockhart-Martinelli method) x l v
  • 14. Outcome – Simulation program on the basis of system pressure balance The results of the predicted design parameters help not only to understand the system performance of at various conditions, but also to provide details of how the system operates. We have developed the simulation program for the system design optimization with the effect of design parameters using the objective function, design variables and design boundaries. Design variable and boundaries Visualization program for optimization design and simulation Parametric studies of the design variables and boundaries
  • 15. Future work – Improvement factors Max. Heat transfer capacity System operating temperature The capillary pumping performance of -Vapor temperature wick structure has important effect on system. ;less than 40°C level at given heat loads It is necessary to develop the high performance evaporator mounted with superior wick structures. n dP Pi T i 1 dT Straight pores Liquid flow through wick Evaporation Saturation line Pressure P1 1 2 P3 3 Liquid 4 P5 5 Pc ,max P6 7 6 Vapor 8 P8 T6 T7 T4 T1 Temperature
  • 16. Future work – Material properties 1 Working fluid and Material selection As part of a design procedure for a targeted Operating temperature range application, the selection of the working fluid is the of various working fluids first step. The working fluid determines the range of the operating temperature and must satisfy a number of criteria. In the second step, it is necessary to decide the compatibility between the working fluid and the material to avoid chemical reactions. The chemical reactions would cause the degradation of the mechanical strength or the tightness of the LHP, or the existence of non- condensable gases which could alter the LHP operation. Compatibility metals with working fluids (C: compatible, NC: incompatible)
  • 17. Future work – Material properties 2 Merit number h fg The effect of working fluid on heat transfer The ranking of working fluid c pl capability and/or system operating temperature l h fg l h fg l l The friction factor associated M c l pl Maximum capillary pressure c pl with pressure loss of system l l l l
  • 18. Future work – Material properties 3 Constant Temperature Tcritical pressure curves Sub-cooled liquid region B A C D Superheated Liquid vapor mix/ vapor region Saturated two-phase region Saturated liquid line vapor line Entropy Vapor temperature vs. Vapor pressure Change hfg by controlling the evaporator pressure
  • 19. Summary – Research roadmap Design objective Design requirements Materials Sever rack-mount cooling Heat load, Chip temperature, (with working fluid) Ambient temperature, Weight, Space constraints, Noise level, Transport line length, Cost, etc. Component Models Experiment System Model Investigation Condenser, Transport line, Evaporator, Airflow, etc. System Simulation Wick fabrication Design parameters (key correlations) Prototype Theoretical Design and Modeling Pressure loss, Void fraction Models Heat transfer coefficient, etc. Prototype test
  • 20. Summary – Works Project schedule and plan Detailed design prototypes Detail design and concept generation Heat source Total heat dissipation condition on one or multi chips (Specially, CPUs) -A prototype model with compact condenser with a fan can ; more than 300W be mounted inside a sever rack-mount. (One CPU is more than 14 W/cm2) Allowable Below 60 ℃ -Analyzing parameters, operating conditions, constraints, junction * Steady state condition etc. to build the systems. temp. of chips -Thermodynamic cycle and operating limits to understand Evaporator 40mm (width) x 40mm(length) the physical concepts and operating principle of the loop dimension x less than 5mm (height) scheme. Transport line Between 0.5 m and 1.0 m Length (Taking note of flexible tubes) -Selection of working fluid/material/wick structure. Evaporator sample fabrication and investigation Evaporator Condenser -Theoretical and experimental investigation (Obtaining wick characters – Nano/Micro application) Updated system algorism and design refinement CPU based on previous findings RAM -To apply new parameters to the optimization program Power Supply HDD - Comparison of experimental reviews with simulation results
  • 21. Thank you very much !!!