SlideShare una empresa de Scribd logo
1 de 56
© ABB Power Technology
1_114Q07- 1 -




                                      Transformers
                         Protection
                                      Protections
AGENDA
                            PRINCIPLES
                            LINES PROTECTION
                            TRANSFORMERS PROTECTION
                                INTRODUCTION
                                SELECTING A PROTECTIVE SYSTEM
                                     Differential protection
                                     Sudden pressure relay
                                     Overcurrent protection
                                     Transformer tank protection
                                     Typical protective scheme for power transformers
© ABB Power Technology




                            STATION BUS PROTECTION
1_114Q07- 2 -
AGENDA
                            PRINCIPLES
                            LINES PROTECTION
                            TRANSFORMERS PROTECTION
                                INTRODUCTION
                                SELECTING A PROTECTIVE SYSTEM
                                     Differential protection
                                     Sudden pressure relay
                                     Overcurrent protection
                                     Transformer tank protection
                                     Typical protective scheme for power transformers
© ABB Power Technology




                            STATION BUS PROTECTION
1_114Q07- 3 -
Introduction. Possible faults in a transformer


                            EXTERNAL                INTERNAL
                                External Short          Short circuits
                                 Circuits                     between turns
                                Overloads                    between windings
                                Overvoltages            Ground faults
                                                         Overtemperature
                                                         Overpressure
                                                         Miss of oil
© ABB Power Technology
1_114Q07- 4 -
Introduction. Transformers protections


                            INTERNAL                 ELECTRICAL
                                BUCHHOLZ (SPR)           SURGE ARRESTERS
                                THERMOMETER              OVERCURRENT RELAYS
                                THERMOSTAT                    PHASE
                                                               NEUTRAL
                                THERMAL IMAGE
                                OIL LEVEL                DIFFERENTIAL RELAY

                                PRESSURE RELIEF          THERMAL RELAY
                                 VALVE                    TANK RELAY
                                BUCHHOLZ-TAP             FUSES
© ABB Power Technology




                                 CHANGER
1_114Q07- 5 -
Magnetizing inrush
                         When a transformer is first energized, a transient magnetizing or
                          exciting inrush current may flow. This inrush current, which appears as
                          an internal fault to the differentially connected relays, may reach
                          instantaneous peaks of 8 to 30 times those for full load.
                         The factors controlling the duration and magnitude of the magnetizing
                          inrush are:
                              Size and location of the transformer bank
                              Size of the power system
                              Resistance in the power system from the source to the transformer bank
                              Type of iron used in the transformer core and its saturation density
                              Prior history, or residual flux level, of the bank
                              How the bank is energized
© ABB Power Technology
1_114Q07- 6 -
Initial inrush
                         When the excitation of a transformer bank is removed, the magnetizing
                          current goes to O.
                         The flux, following the hysteresis loop, then falls to some residual value
                           R. If the transformer were reenergized at the instant the voltage
                          waveform corresponds to the residual magnetic density within the core,
                          there would be a smooth continuation of the previous operation with no
                          magnetic transient.
                         In practice, however, the instant when switching takes place cannot be
                          controlled and a magnetizing transient is practically unavoidable.
© ABB Power Technology
1_114Q07- 7 -
Initial inrush
                         If the circuit is re-energized at the instant the flux would normally be at
                          its negative maximum value (- max) as the residual flux would have a
                          positive value and since magnetic flux can neither be created nor
                          destroyed instantly, the flux wave, instead of starting at its normal value
                          (- max) and rising along the dotted line, will start with the residual value
                          ( R) and trance the curve ( L).
© ABB Power Technology
1_114Q07- 8 -
Initial inrush
                         Curve t is a displaced
                          sinusoid, regardless of the
                          magnetic circuit's saturation
                          characteristics.
                              Theoretically, the value of
                                max is + (| R| + 2| max|).
                         In transformers designed for
                          some normal, economical
                          saturation density s, the
                          crest of t will produce super
                          saturation in the magnetic
                          circuit.
                         The result will be a very
                          large crest value in the
© ABB Power Technology




                          magnetizing current.
1_114Q07- 9 -
Initial inrush




                         For the first few cycles, the inrush current decays rapidly. Then,
                          however, the current subsides very slowly, sometimes taking many
                          seconds if the resistance is low.
                         The time constant of the circuit (L/R) is not, in fact, a constant: L varies
                          as a result of transformer saturation. During the first few cycles,
                          saturation is high and L is low. As the losses damp the circuit, the
                          saturation drops and L increases. According to a 1951 AIEE report, time
© ABB Power Technology




                          constants for inrush vary from 10 cycles for small units to as much as 1
1_114Q07- 10 -




                          min for large units.
Initial inrush
                         The resistance from the source to the bank determines the damping of
                          the current wave.
                         Banks near a generator will have a longer inrush because the
                          resistance is very low.
                         Likewise, large transformer units tend to have a long inrush as they
                          represent a large L relative to the system resistance.
                         At remote substations, the inrush will not be nearly so severe, since the
                          resistance in the connecting line will quickly damp the current.
© ABB Power Technology
1_114Q07- 11 -
Initial inrush
                         When there is more than one delta winding on a transformer bank, the
                          inrush will he influenced by the coupling between the different voltage
                          windings. Depending on the core construction, three-phase transformer
                          units may be subject to interphase coupling that could also affect the
                          inrush current.
                         Similar wave shapes would be encountered when energizing the wye
                          winding of a wye-delta bank, or an autotransformer. Here, the single-
                          phase shape would be distorted as a result of the interphase coupling
                          produced by the delta winding (or tertiary).
© ABB Power Technology
1_114Q07- 12 -
Initial inrush
                         Maximum inrush will not, of course, occur on every energization.
                              The probability of energizing at the worst condition is relatively low.
                              Energizing at maximum voltage will not produce an inrush with no residual.
                              In a three-phase bank, the inrush in each phase will vary appreciably.
                         The maximum inrush for a transformer bank can be calculated from the
                          excitation curve if available, and Table shows a typical calculation of an
                          inrush current (used phase A voltage as 0° reference).


                                              Closing    Peak value of inrush current wave (p.u.)
                                         S
                                               angle     Ia     Ib      Ic    Ia-Ib   Ib-Ic   Ic-Ia
                                       1.40     0°      5.60 -3.73    -3.73   8.33    -3.73 -8.33
                                       1.40    30°      5.10 — 1.87 -5.10     5.96    5.10    -9.20
© ABB Power Technology




                                       1.15     0°      6.53 -4.67    -4.67 10.20 -4.67 -10.20
                                       1.15    30°      6.03 — 2.80 -6.03     7.83    6.03 -11.06
1_114Q07- 13 -
Initial inrush
                         From these calculated values it can be seen that:
                              The lower the value of the saturation density flux S, the higher the inrush
                               peak value.
                              The maximum phase-current inrush occurs at the 0° closing angle (i.e., 0
                               voltage).
                              The maximum line-current inrush occurs at ± 30° closing angles.
                         Because of the delta connection of transformer winding or current
                          transformers, the maximum line-current in-rush value should be
                          considered when applying current to the differential relay.
                                                    Closing    Peak value of inrush current wave (p.u.)
                                               S
                                                     angle     Ia     Ib      Ic    Ia-Ib   Ib-Ic   Ic-Ia
                                             1.40     0°      5.60 -3.73    -3.73   8.33    -3.73 -8.33
                                             1.40    30°      5.10 — 1.87 -5.10     5.96    5.10    -9.20
© ABB Power Technology




                                             1.15     0°      6.53 -4.67    -4.67 10.20 -4.67 -10.20
                                             1.15    30°      6.03 — 2.80 -6.03     7.83    6.03 -11.06
1_114Q07- 14 -
Sympathetic inrush
                         When a bank is paralleled with a second energized bank, the energized
                          bank can experience a sympathetic inrush.
                         The offset inrush current of the bank being energized will find a parallel
                          path in the energized bank.
                         The dc component may saturate the transformer iron. creating an
                          apparent inrush.
                         The magnitude of this inrush depends on the value of the transformer
                          impedance relative to that of the rest of the system, which forms an
                          additional parallel circuit.
                         Again, the sympathetic inrush will always be less than the initial inrush.
© ABB Power Technology
1_114Q07- 15 -
Sympathetic inrush
                         The total current at breaker C is the sum of the initial inrush of bank A
                          and the sympathetic inrush of bank B.
                         Since this waveform looks like an offset fault current, it could cause
                          misoperation if a common set of harmonic restraint differential relays
                          were used for both banks.




                         Unit-type generator and transformer combinations have no initial inrush
© ABB Power Technology




                          problem because the unit is brought up to full voltage gradually.
1_114Q07- 16 -




                          Recovery and sympathetic inrush may be a problem, but as indicated
                          above, these conditions are less severe than initial inrush.
AGENDA
                            PRINCIPLES
                            LINES PROTECTION
                            TRANSFORMERS PROTECTION
                                INTRODUCTION
                                SELECTING A PROTECTIVE SYSTEM
                                     Differential protection
                                     Sudden pressure relay
                                     Overcurrent protection
                                     Transformer tank protection
                                     Typical protective scheme for power transformers
© ABB Power Technology




                            STATION BUS PROTECTION
1_114Q07- 17 -
Differential relaying for transformer protection
                            It compares the current entering the transformer with the current
                             leaving the element.
                                If they are equal there is no fault inside the zone of protection
                                If they are not equal it means that a fault occurs between the two ends




                                                                 87
© ABB Power Technology




                                             With internal fault Id > 0             Trip
                                          With external fault Id = 0              No trip
1_114Q07- 18 -
Differential relaying for transformer protection

                            Alternatively one could form an algebraic sum of the two currents
                             entering the protected element, which could be termed as differential
                             current (Id), and use a level detector relay to detect the presence of a
                             fault.
                                 In general this principle is capable of detecting very small
                                  magnitudes of fault.
                                 Its only drawback is that it requires currents from the extremities
                                  of a zone of protection
© ABB Power Technology
1_114Q07- 19 -
Differential relaying for transformer protection
                         Differential relays are the principal form of fault protection for
                          transformers rated at 10 MVA and above.
                         These relays, however, cannot be as sensitive as the differential relays
                          used for generator protection.
                         Transformer protection is further complicated by a variety of equipment
                          requiring special attention: multiple-winding transformer banks, zig-zag
                          transformers, voltage regulators, transformers in unit systems, and
                          three-phase trans-former banks with single-phase units.
© ABB Power Technology
1_114Q07- 20 -
Differential relaying for transformer protection
                         Transformer differential relays are subject to several factors, not
                          ordinarily present for generators or buses, that can cause miss-
                          operation:
                             Different voltage levels, including taps, that result in different
                              primary currents in the connecting circuits.
                             Possible mismatch of ratios among different current transformers.
                                  For units with ratio-changing taps, mismatch can also occur on the taps.
                                   Current transformer performance is different, particularly at high
                                   currents.
                             30° phase-angle        shift   introduced    by   transformer     wye-delta
                              connections.
                             Magnetizing inrush currents, which the differential relay sees as
                              internal faults.
© ABB Power Technology
1_114Q07- 21 -
Differential relaying for transformer protection



                                                           Id
                            To prevent miss-operation
                             percentage characteristics
                             are used, with line current        Operating zone
                             restraint.
© ABB Power Technology




                                                                                 (I1 + I2)/2
1_114Q07- 22 -
Differential relaying for transformer protection
                         Since the differential relays see the inrush current as an internal fault,
                          some method of distinguishing between fault and inrush current is
                          necessary.
                         Such methods include:
                              A differential relay with reduced sensitivity to the inrush wave (such
                               units have a higher pickup for the offset wave, plus time delay to
                               override the high initial peaks).
                              A harmonic restraint or a supervisory unit used in con-junction with
                               the differential relay
                              Desensitization of the differential relay during bank energization.
© ABB Power Technology
1_114Q07- 23 -
Differential relay for transformer protection
                         Induction relays are relatively insensitive
                          to the high percentage of harmonics
                          contained in magnetizing inrush current.
                         The relay shown consists of a percentage
                          differential unit and an indication
                          contactor switch.
                         The percentage differential unit, an
                          induction disc type, has an electromagnet
                          with poles above and below the disc.
                          There are two restraint coils on the lower
                          left-hand pole; the operating coil is wound
                          on the lower right-hand pole.
                         Both the left- and right-hand poles have
© ABB Power Technology




                          transformer winding, connected in parallel
                          to supply current to the upper-pole
1_114Q07- 24 -




                          windings.
Differential relay for transformer protection
                         The upper-pole current generates a flux in quadrature with the lower-
                          pole resultant flux, and the two fluxes react to produce a torque on the
                          disc.
                         Under normal load or in external fault, the currents in the two restraint
                          windings flow in the same direction.
                         These restraining currents are equal (or effectively equal) if auto-
                          balance taps are used to compensate from mismatch in current
                          transformer ratios - and if no significant current flows in the operating
                          coil winding.
                         As a result, only contact-opening torque is produced.
© ABB Power Technology
1_114Q07- 25 -
Differential relay for transformer protection
                         If the taps are mismatched or the main current transformers saturate
                          unequally on severe external faults, the effective difference between the
                          currents in the two restraining windings must flow in the operating coil.
                         The operating coil current required to overcome the restraining torque
                          and close the relay contacts is a function of the restraining current. For
                          an internal fault, the restraining currents are opposite, and restraining
                          torque tends to cancel out.
                         The more sensitive operating coil, however, is energized by the sum of
                          the two currents. As a result, a large amount of contact-closing torque is
                          produced.
© ABB Power Technology
1_114Q07- 26 -
Differential relay for transformer protection
                         In applying the relay, the current transformer ratio error should not
                          exceed 10% during maximum symmetrical external fault current. The
                          relay's 50% characteristic satisfactorily handles up to 35% of current
                          mismatch, including the transformer tap changing on load and current
                          transformer mismatch.
                         The relay's restraining windings have a continuous rating of 10 A; the
                          operating winding has a continuous rating of 5 A. To prevent
                          overloading the operating winding, however, no more than 5 A should
                          be allowed in the untapped restraining winding.
© ABB Power Technology
1_114Q07- 27 -
Variable-Percentage Transformer Differential Relay
                        This type of relays have a variable-percentage characteristic:
                             Percentage is low on light faults, where the current transformer
                              performance is good, and high on heavy faults, where current
                              transformer saturation may occur.
                             The variable-percentage characteristic is obtained via a saturation
                              transformer in the operating circuit.
                             This transformer also tends to shunt the dc component away from
                              the operating coil.
© ABB Power Technology
1_114Q07- 28 -
Variable-Percentage Transformer Differential Relay
                        The relay consists of an induction-type differential unit, a dc-indicating
                         contactor switch, and an optional ac-indicating instantaneous trip unit.
                        The induction-type differential unit contains four electromagnets,
                         operating on two discs fastened to a common shaft.
                        Of the electromagnets, one is the operating element and the other three
                         are restraint elements. On the center leg of each restraint
                         electromagnet are two primary coils and a secondary coil ; primary coils
                         are energized from the secondaries of the current transformers
                         connected to the bank to be protected.
© ABB Power Technology
1_114Q07- 29 -
Variable-Percentage Transformer Differential Relay
                        A 5-A current in the restraint coil will produce restraining torque. The
                         same 5-A current flowing in two restraint coils of the same restraint
                         electromagnet will have either additive or subtractive restraining effect,
                         depending on the polarity of the connection (Figure c).
                        This relay is well suited to protect transformer banks not subject to
                         severe magnetizing inrush, particularly if more than two restraining
                         circuits are needed. The relay has no built-in taps and generally
                         requires auxiliary current transformers for current matching. The
                         operating time of the differential unit is two to six cycles; no setting is
                         required.
                        The faster IIT unit is connected to the differential circuit. It is
                         recommended for transformer protection in applications where internal
                         fault current can exceed twice the maximum total current flowing
                         through the differential zone for a symmetrical external fault. The IIT
© ABB Power Technology




                         unit should be set at 50% external fault current or a value higher than
                         transformer inrush current, whichever is greater.
1_114Q07- 30 -
Harmonic restraint Transformer Differential Relay
                        Since magnetizing inrush current has a high harmonic content,
                         particularly the second harmonic, this second harmonic can be used to
                         restrain and thus desensitize a relay during energization.
                        The method of harmonic restraint is not without its problems.
                        There must be enough restraint to avoid relay operation on inrush,
                         without making the relay insensitive to internal faults that may also have
                         some harmonic content.
© ABB Power Technology
1_114Q07- 31 -
Harmonic restraint Transformer Differential Relay
                        In the differential unit, (DU) air-gap transformers feed the restraint
                         circuits, and a non-air-gap transformer energizes the operating coil
                         circuit.
                        Since the rectified restraint outputs are connected in parallel, the relay
                         restraint is proportional to the maximum restraining current in any
                         restraint circuit.
© ABB Power Technology
1_114Q07- 32 -
Harmonic restraint Transformer Differential Relay
                        The percentage characteristic varies from around 20% on light faults,
                         where current transformer performance is good, to approximately 60%
                         on heavy fault, where current transformer saturation may occur.
                        This variable-percentage characteristic is obtained via the saturating
                         transformer in the operating coil circuit.
                        The minimum pickup is the current that will just close the differential unit
                         contacts, with the operating coil and one restraint coil energized.
                        The continuous rating of the relay is 10 to 22 A, depending on the relay
                         tap used.
© ABB Power Technology
1_114Q07- 33 -
Harmonic restraint Transformer Differential Relay
                        The harmonic restraint unit (HRU) has a second-harmonic blocking filter
                         in the operating coil circuit and a second-harmonic pass filter in the
                         restraint coil circuit.
                        Thus, the predominant second-harmonic characteristic of an inrush
                         current produces ample restraint with minimum operating energy.
                        The circuit is designed to hold open its contacts when the second-
                         harmonic component is higher than 15% of the fundamental.
                        This degree of restraint in the HRU is adequate to prevent relay
                         operation on practically all inrushes, even if the differential unit should
                         operate.
© ABB Power Technology
1_114Q07- 34 -
Harmonic restraint Transformer Differential Relay
                        For internal faults, ample operating energy is produced by the
                         fundamental frequency and harmonic other than the second.
                        The second harmonic is at a minimum during a fault. Since the HRU
                         will operate at the same pickup as the DU, the differential unit will
                         operate sensitively on internal faults.
                        For external faults, the differential unit (DU) will restrain.
                        The relay operating time is one cycle at 20 times tap value.
                        The instantaneous trip unit (IIT) is included to ensure high-speed
                         operation on heavy internal faults, where current transformer saturation
                         may delay HRU contact closing.
                        The IIT pickup is 10 times the relay tap value.
                        This setting will override the inrush peaks and maximum false
© ABB Power Technology




                         differential current on external faults.
1_114Q07- 35 -
Transformer Differential Relay Application
                        The following guidelines are designed to assist in selecting and
                         applying relays for transformer protection.
                             When two or more relays appear to be equally suitable, engineering
                              experience and economics will determine the final choice.
                        There is no clear-cut answer to the question of which relay or protective
                         method to apply.
                        As a general rule, however, the induction-disk differential relays are
                         used at substations remote from large generating sources where inrush
                         is not a problem and the kVA size of the bank is relatively small.
                        The more complex and more expensive harmonic relays are used at
                         generating stations and for large transformer units located close to
                         generating sources, where a severe inrush is highly likely.
© ABB Power Technology
1_114Q07- 36 -
Transformer Differential Relay Application
                            In general, the current transformers on the wye side of a wye-delta
                             bank must be connected in delta, and the current transformers on
                             the delta side connected in wye.
                            This arrangement (1) compensates for the 30° phase-angle shift
                             introduced by the wye-delta bank and (2) blocks the zero sequence
                             current from the differential circuit on external ground faults.
© ABB Power Technology
1_114Q07- 37 -
Transformer Differential Relay Application
                        Zero sequence current will flow in the differential circuit for external
                         ground faults on the wye side of a grounded wye-delta bank; if the
                         current transformers were connected in wye, the relays would miss-
                         operate.
                        With the current transformers connected in delta, the zero sequence
                         current circulates inside the current transformers, preventing relay miss-
                         operation.
© ABB Power Technology
1_114Q07- 38 -
Transformer Differential Relay Application
                            Relays should be connected to receive “in” and “out” currents that
                             are in phase for a balanced load condition.
                                 When there are more than two windings, all combinations must be
                                  considered, two at a time.
                            Relay taps or auxiliary current transformer ratios should be as close
                             as possible to the current ratios for a balanced maximum load
                             condition.
                                 When there are more than two winding, all combinations must he
                                  considered, two at a time, and based on the sane kVA capacity.
                            Only ground one point in the differential scheme, never do multiple-
                             point grounding.
© ABB Power Technology
1_114Q07- 39 -
Transformer Differential Relay Application
                            The percentage of current mismatch should always be checked to
                             ensure that the relay taps selected have an adequate safety margin.
                            When necessary, current mismatch values can be reduced by
                             changing current transformer taps or adding auxiliary current
                             transformers.
© ABB Power Technology
1_114Q07- 40 -
AGENDA
                            PRINCIPLES
                            LINES PROTECTION
                            TRANSFORMERS PROTECTION
                                INTRODUCTION
                                SELECTING A PROTECTIVE SYSTEM
                                     Differential protection
                                     Sudden pressure relay
                                     Overcurrent protection
                                     Transformer tank protection
                                     Typical protective scheme for power transformers
© ABB Power Technology




                            STATION BUS PROTECTION
1_114Q07- 41 -
Sudden-Pressure Relay (SPR)
                        With the application of a gas-pressure relay, many transformers can be
                         protected by a simple differential relay set insensitively in the inrush current.
                        The sudden-pressure relay (SPR), which operates on a rate of rise of gas in the
                         transformer, can be applied to any trans-former with a sealed air or gas
                         chamber above the oil level.
                        The relay is fastened to the tank or manhole cover, above the oil level. It will not
                         operate on static pressure or pressure changes resulting from normal operation
                         of the transformer.
© ABB Power Technology
1_114Q07- 42 -
Sudden-Pressure Relay (SPR)
                        The SPR relay is recommended for all units of 5000 kVA or more.
                        The SPR relay is far more sensitive to light internal faults than the differential
                         relay. The differential relay, however, is still required for faults in the bushing
                         and other areas outside the tank.
                        The SPR relay operating time varies from 1/2 cycle to 37 cycles, depending on
                         the size of the fault.
                        In the past, large-magnitude through-fault conditions on power transformers
                         have caused rate-of-change-of-pressure relays to occasionally operate falsely.
                         There has been reluctance on the part of some users to connect these rate-of-
                         change-of-pressure relays to trip, and they have therefore used them for
                         alarming only. Schemes have been devised to restrict tripping of the rate-of-
                         change-of-pressure device only to levels of current below which the transformer
                         differential relay cannot operate.
© ABB Power Technology
1_114Q07- 43 -
AGENDA
                            PRINCIPLES
                            LINES PROTECTION
                            TRANSFORMERS PROTECTION
                                INTRODUCTION
                                SELECTING A PROTECTIVE SYSTEM
                                     Differential protection
                                     Sudden pressure relay
                                     Overcurrent protection
                                     Transformer tank protection
                                     Typical protective scheme for power transformers
© ABB Power Technology




                            STATION BUS PROTECTION
1_114Q07- 44 -
Overcurrent and Backup Protection
                        To allow transformer overloading
                         when necessary, the pickup value of
                         phase overcurrent relays must be set                                             50/51
                         above this overload current.
                                                                           t
                        An inverse-time characteristic relay
                                                                                                 Curva trafo
                         usually     provides   the      best
                         coordination.
                                                                 Relé tiempo independ.               Relé tiempo inverso

                        Settings of 200 to 300% of the
                         transformer's self-cooled rating are
                         common, although higher values are                t0

                         some-times used.
                                                                                                               i
                        Fast operation is not possible, since                       In   n*In

                         the    transformer     relays   must
                         coordinate with all other relays they
© ABB Power Technology




                         overreach.
1_114Q07- 45 -
Overcurrent and Backup Protection
                        Overcurrent relays cannot be used for primary protection without the
                         risk of internal faults causing extensive damage to the transformer.
                        Fast operation on heavy internal faults is obtained by using
                         instantaneous trip units in the overcurrent relays.
                        These units may be set at 125% of the maximum through fault, which is
                         usually a low-side three-phase fault.
                        The setting should be above the inrush current. Often, instantaneous
                         trip units cannot be used because the fault currents are too small.
                        An overcurrent relay set to protect the main windings of an
                         autotransformer or three-winding transformer offers almost no
                         protection to the tertiary windings, which have a much smaller kVA.
                        Also, these tertiary windings may carry very heavy currents during
                         ground faults. In such cases, tertiary overcurrent protection must be
© ABB Power Technology




                         provided.
1_114Q07- 46 -
Overcurrent and Backup Protection
                        A through fault external to a transformer results in an overload that can
                         cause transformer failure if the fault is not cleared promptly.
                        It is widely recognized that damage to transformers from through faults
                         is the results of thermal and mechanical effects.
                             The thermal effect has been well understood for years.
                             The mechanical effect has recently gained increased recognition as a major
                              concern of transformer failure.
                             This results from the cumulative nature of some of the mechanical effects,
                              particularly insulation compression, insulation wear, and friction-induced
                              displacement.
                             The damage that occurs as a result of these cumulative effects is a function
                              of not only the magnitude and duration of through faults, but also the total
                              number of such faults.
© ABB Power Technology
1_114Q07- 47 -
Overcurrent and Backup Protection
                        The transformer can be isolated from the fault before damage occurs by
                         using fuses or overcurrent relays.

                                               50/51N




                                                                        50/51G
                                              2-3 50/51
© ABB Power Technology
1_114Q07- 48 -
Distance Relaying for Backup Protection
                        Directional distance relaying can be used for transformer backup
                         protection when the setting or coordination of the overcurrent relays is a
                         problem.
                        The directional distance relays are connected to operate when the fault
                         current flows toward the protected transformer.
                        They are set to reach into, but not beyond, the transformer.
© ABB Power Technology
1_114Q07- 49 -
AGENDA
                            PRINCIPLES
                            LINES PROTECTION
                            TRANSFORMERS PROTECTION
                                INTRODUCTION
                                SELECTING A PROTECTIVE SYSTEM
                                     Differential protection
                                     Sudden pressure relay
                                     Overcurrent protection
                                     Transformer tank protection
                                     Typical protective scheme for power transformers
© ABB Power Technology




                            STATION BUS PROTECTION
1_114Q07- 50 -
Transformer Tank protection
                            This is a low cost protection against some of the internal faults of the
                             transformer, which consists of an overcurrent relay which measures
                             the current flow through the ground connection of the transformer tank.
                            It detects hence the ground faults of the transformer and bushings
                             trough the metallic tank.
                            To achieve this the transformer must be completely isolated from
                             ground (putting some isolating      material under the transformer
                             wheels), and a toroid current transformer is needed surrounding the
                             only ground connection cable.
© ABB Power Technology




                                                                                       64
1_114Q07- 51 -
Transformer Tank protection
                            To prevent incorrect tripping (because of possible faults in the
                             connection cables to fans, etc) it is necessary to take some measure
                             as the indicated in fig, and to coordinate with the neutral protection.
© ABB Power Technology
1_114Q07- 52 -
AGENDA
                            PRINCIPLES
                            LINES PROTECTION
                            TRANSFORMERS PROTECTION
                                INTRODUCTION
                                SELECTING A PROTECTIVE SYSTEM
                                     Differential protection
                                     Sudden pressure relay
                                     Overcurrent protection
                                     Transformer tank protection
                                     Typical protective scheme for power transformers
© ABB Power Technology




                            STATION BUS PROTECTION
1_114Q07- 53 -
Typical protective scheme for power transformers
                        Figure illustrates how a primary
                         breaker can be used for
                         transformer protection.
                        The basic protection is provided
                         by the 87T transformer differential
                         relays.
                        Device 50/51, an inverse-time
                         relay with IIT unit, provides
                         transformer  primary  winding
                         backup protection for phase
                         faults;
                             either device 50G (with a zero
                              sequence current transformer) or
                              50N/51N can be used as
© ABB Power Technology




                              transformer    primary    winding
                              backup for ground faults.
1_114Q07- 54 -
Typical protective scheme for power transformers
                        Transformer overload, low-voltage
                         bus, and feeder backup protection
                         are provided by device 51 on the
                         transformer secondary side.
                        Since the low-voltage side is
                         medium-resistance-grounded,     a
                         ground relay (51G) should be used
                         to trip breaker 52-1 for low-side
                         ground faults and for resistor
                         thermal protection.
                        Device 151G, which trips breaker
                         52-11, provides feeder ground
                         backup, whereas device 63, such
                         as a type SPR relay, offers highly
© ABB Power Technology




                         sensitive protection for light faults.
1_114Q07- 55 -
Typical protective scheme for power transformers
                        The current transformer ratings in
                         this scheme should be compatible
                         with the transformer short-time
                         overload capability: approximately
                         200% of transformer selfcooled
                         rating for wye-connected current
                         transformers and 350% ( · 200%)
                         for     delta-connected    current
                         transformers.
                        The neutral current transformer
                         rating should be 50% of the
                         maximum resistor current rating.
© ABB Power Technology
1_114Q07- 56 -

Más contenido relacionado

La actualidad más candente

Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introductionH. Kheir
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION moiz89
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601SARAVANAN A
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protectionashwin fcc
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guideSlides Hub
 
ETAP - Coordination and protecion 2
ETAP -  Coordination and protecion 2ETAP -  Coordination and protecion 2
ETAP - Coordination and protecion 2Himmelstern
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & MaintenanceHimansu Pradhan
 
Power system protection
Power system protectionPower system protection
Power system protectionAnu Priya
 
Fault Calculations
Fault CalculationsFault Calculations
Fault Calculationsmichaeljmack
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.Hemendra Kumar Rajput
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protectionsrini09
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection michaeljmack
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersSARAVANAN A
 
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...jbpatel7290
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current ProtectionSARAVANAN A
 

La actualidad más candente (20)

Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introduction
 
Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protection
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
 
CT and VT.pptx
CT and VT.pptxCT and VT.pptx
CT and VT.pptx
 
ETAP - Coordination and protecion 2
ETAP -  Coordination and protecion 2ETAP -  Coordination and protecion 2
ETAP - Coordination and protecion 2
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Power system protection
Power system protectionPower system protection
Power system protection
 
Fault Calculations
Fault CalculationsFault Calculations
Fault Calculations
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protection
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
 

Similar a ABB - TRANSFORMERS-PROTECTION-COURSE (2001)

BPMI TRANSFORMER PROTECTION.pptx.pdf
BPMI TRANSFORMER PROTECTION.pptx.pdfBPMI TRANSFORMER PROTECTION.pptx.pdf
BPMI TRANSFORMER PROTECTION.pptx.pdfssuser2e69dc
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSHIVANICHAUUHAN1
 
FUZZY LOGIC PROJECTS ABSTRACT:Fuzzy logic based differential relay for power ...
FUZZY LOGIC PROJECTS ABSTRACT:Fuzzy logic based differential relay for power ...FUZZY LOGIC PROJECTS ABSTRACT:Fuzzy logic based differential relay for power ...
FUZZY LOGIC PROJECTS ABSTRACT:Fuzzy logic based differential relay for power ...ASHOKKUMAR RAMAR
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.pptThien Phan Bản
 
ELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFjang041
 
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).pptos-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).pptThien Phan Bản
 
Madan mohan malaviya
Madan mohan malaviyaMadan mohan malaviya
Madan mohan malaviyaAnuj Bansal
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3Md Irshad Ahmad
 

Similar a ABB - TRANSFORMERS-PROTECTION-COURSE (2001) (20)

Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
 
BPMI TRANSFORMER PROTECTION.pptx.pdf
BPMI TRANSFORMER PROTECTION.pptx.pdfBPMI TRANSFORMER PROTECTION.pptx.pdf
BPMI TRANSFORMER PROTECTION.pptx.pdf
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptx
 
Overvoltages 1
Overvoltages 1Overvoltages 1
Overvoltages 1
 
Solid State Relay
Solid State RelaySolid State Relay
Solid State Relay
 
FUZZY LOGIC PROJECTS ABSTRACT:Fuzzy logic based differential relay for power ...
FUZZY LOGIC PROJECTS ABSTRACT:Fuzzy logic based differential relay for power ...FUZZY LOGIC PROJECTS ABSTRACT:Fuzzy logic based differential relay for power ...
FUZZY LOGIC PROJECTS ABSTRACT:Fuzzy logic based differential relay for power ...
 
unit_2.ppt
unit_2.pptunit_2.ppt
unit_2.ppt
 
Class presentation.pptx
Class presentation.pptxClass presentation.pptx
Class presentation.pptx
 
distance relay
distance relaydistance relay
distance relay
 
ECNG 6503 # 3
ECNG 6503 # 3ECNG 6503 # 3
ECNG 6503 # 3
 
unit_2.ppt
unit_2.pptunit_2.ppt
unit_2.ppt
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppt
 
ELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEF
 
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).pptos-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
 
Adaptive Relaying,Report
Adaptive Relaying,ReportAdaptive Relaying,Report
Adaptive Relaying,Report
 
Madan mohan malaviya
Madan mohan malaviyaMadan mohan malaviya
Madan mohan malaviya
 
Inrush current
Inrush currentInrush current
Inrush current
 
Ke2517881796
Ke2517881796Ke2517881796
Ke2517881796
 
Ke2517881796
Ke2517881796Ke2517881796
Ke2517881796
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3
 

Último

Traction part 2 - EOS Model JAX Bridges.
Traction part 2 - EOS Model JAX Bridges.Traction part 2 - EOS Model JAX Bridges.
Traction part 2 - EOS Model JAX Bridges.Anamaria Contreras
 
Financial-Statement-Analysis-of-Coca-cola-Company.pptx
Financial-Statement-Analysis-of-Coca-cola-Company.pptxFinancial-Statement-Analysis-of-Coca-cola-Company.pptx
Financial-Statement-Analysis-of-Coca-cola-Company.pptxsaniyaimamuddin
 
Investment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy CheruiyotInvestment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy Cheruiyotictsugar
 
Cyber Security Training in Office Environment
Cyber Security Training in Office EnvironmentCyber Security Training in Office Environment
Cyber Security Training in Office Environmentelijahj01012
 
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCRashishs7044
 
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu MenzaYouth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menzaictsugar
 
Church Building Grants To Assist With New Construction, Additions, And Restor...
Church Building Grants To Assist With New Construction, Additions, And Restor...Church Building Grants To Assist With New Construction, Additions, And Restor...
Church Building Grants To Assist With New Construction, Additions, And Restor...Americas Got Grants
 
Kenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith PereraKenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith Pereraictsugar
 
Kenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby AfricaKenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby Africaictsugar
 
TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024Adnet Communications
 
Guide Complete Set of Residential Architectural Drawings PDF
Guide Complete Set of Residential Architectural Drawings PDFGuide Complete Set of Residential Architectural Drawings PDF
Guide Complete Set of Residential Architectural Drawings PDFChandresh Chudasama
 
Digital Transformation in the PLM domain - distrib.pdf
Digital Transformation in the PLM domain - distrib.pdfDigital Transformation in the PLM domain - distrib.pdf
Digital Transformation in the PLM domain - distrib.pdfJos Voskuil
 
Organizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessOrganizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessSeta Wicaksana
 
Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!
Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!
Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!Doge Mining Website
 
The-Ethical-issues-ghhhhhhhhjof-Byjus.pptx
The-Ethical-issues-ghhhhhhhhjof-Byjus.pptxThe-Ethical-issues-ghhhhhhhhjof-Byjus.pptx
The-Ethical-issues-ghhhhhhhhjof-Byjus.pptxmbikashkanyari
 
Buy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy Verified Accounts
 
Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Seta Wicaksana
 
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607dollysharma2066
 
Chapter 9 PPT 4th edition.pdf internal audit
Chapter 9 PPT 4th edition.pdf internal auditChapter 9 PPT 4th edition.pdf internal audit
Chapter 9 PPT 4th edition.pdf internal auditNhtLNguyn9
 

Último (20)

Traction part 2 - EOS Model JAX Bridges.
Traction part 2 - EOS Model JAX Bridges.Traction part 2 - EOS Model JAX Bridges.
Traction part 2 - EOS Model JAX Bridges.
 
Financial-Statement-Analysis-of-Coca-cola-Company.pptx
Financial-Statement-Analysis-of-Coca-cola-Company.pptxFinancial-Statement-Analysis-of-Coca-cola-Company.pptx
Financial-Statement-Analysis-of-Coca-cola-Company.pptx
 
Investment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy CheruiyotInvestment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy Cheruiyot
 
Cyber Security Training in Office Environment
Cyber Security Training in Office EnvironmentCyber Security Training in Office Environment
Cyber Security Training in Office Environment
 
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
 
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu MenzaYouth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
 
Church Building Grants To Assist With New Construction, Additions, And Restor...
Church Building Grants To Assist With New Construction, Additions, And Restor...Church Building Grants To Assist With New Construction, Additions, And Restor...
Church Building Grants To Assist With New Construction, Additions, And Restor...
 
Kenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith PereraKenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith Perera
 
Kenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby AfricaKenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby Africa
 
TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024
 
Guide Complete Set of Residential Architectural Drawings PDF
Guide Complete Set of Residential Architectural Drawings PDFGuide Complete Set of Residential Architectural Drawings PDF
Guide Complete Set of Residential Architectural Drawings PDF
 
Digital Transformation in the PLM domain - distrib.pdf
Digital Transformation in the PLM domain - distrib.pdfDigital Transformation in the PLM domain - distrib.pdf
Digital Transformation in the PLM domain - distrib.pdf
 
Organizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessOrganizational Structure Running A Successful Business
Organizational Structure Running A Successful Business
 
Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!
Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!
Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!
 
The-Ethical-issues-ghhhhhhhhjof-Byjus.pptx
The-Ethical-issues-ghhhhhhhhjof-Byjus.pptxThe-Ethical-issues-ghhhhhhhhjof-Byjus.pptx
The-Ethical-issues-ghhhhhhhhjof-Byjus.pptx
 
Buy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail Accounts
 
Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...
 
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
 
Chapter 9 PPT 4th edition.pdf internal audit
Chapter 9 PPT 4th edition.pdf internal auditChapter 9 PPT 4th edition.pdf internal audit
Chapter 9 PPT 4th edition.pdf internal audit
 
No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...
No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...
No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...
 

ABB - TRANSFORMERS-PROTECTION-COURSE (2001)

  • 1. © ABB Power Technology 1_114Q07- 1 - Transformers Protection Protections
  • 2. AGENDA  PRINCIPLES  LINES PROTECTION  TRANSFORMERS PROTECTION  INTRODUCTION  SELECTING A PROTECTIVE SYSTEM  Differential protection  Sudden pressure relay  Overcurrent protection  Transformer tank protection  Typical protective scheme for power transformers © ABB Power Technology  STATION BUS PROTECTION 1_114Q07- 2 -
  • 3. AGENDA  PRINCIPLES  LINES PROTECTION  TRANSFORMERS PROTECTION  INTRODUCTION  SELECTING A PROTECTIVE SYSTEM  Differential protection  Sudden pressure relay  Overcurrent protection  Transformer tank protection  Typical protective scheme for power transformers © ABB Power Technology  STATION BUS PROTECTION 1_114Q07- 3 -
  • 4. Introduction. Possible faults in a transformer  EXTERNAL  INTERNAL  External Short  Short circuits Circuits  between turns  Overloads  between windings  Overvoltages  Ground faults  Overtemperature  Overpressure  Miss of oil © ABB Power Technology 1_114Q07- 4 -
  • 5. Introduction. Transformers protections  INTERNAL  ELECTRICAL  BUCHHOLZ (SPR)  SURGE ARRESTERS  THERMOMETER  OVERCURRENT RELAYS  THERMOSTAT  PHASE  NEUTRAL  THERMAL IMAGE  OIL LEVEL  DIFFERENTIAL RELAY  PRESSURE RELIEF  THERMAL RELAY VALVE  TANK RELAY  BUCHHOLZ-TAP  FUSES © ABB Power Technology CHANGER 1_114Q07- 5 -
  • 6. Magnetizing inrush  When a transformer is first energized, a transient magnetizing or exciting inrush current may flow. This inrush current, which appears as an internal fault to the differentially connected relays, may reach instantaneous peaks of 8 to 30 times those for full load.  The factors controlling the duration and magnitude of the magnetizing inrush are:  Size and location of the transformer bank  Size of the power system  Resistance in the power system from the source to the transformer bank  Type of iron used in the transformer core and its saturation density  Prior history, or residual flux level, of the bank  How the bank is energized © ABB Power Technology 1_114Q07- 6 -
  • 7. Initial inrush  When the excitation of a transformer bank is removed, the magnetizing current goes to O.  The flux, following the hysteresis loop, then falls to some residual value R. If the transformer were reenergized at the instant the voltage waveform corresponds to the residual magnetic density within the core, there would be a smooth continuation of the previous operation with no magnetic transient.  In practice, however, the instant when switching takes place cannot be controlled and a magnetizing transient is practically unavoidable. © ABB Power Technology 1_114Q07- 7 -
  • 8. Initial inrush  If the circuit is re-energized at the instant the flux would normally be at its negative maximum value (- max) as the residual flux would have a positive value and since magnetic flux can neither be created nor destroyed instantly, the flux wave, instead of starting at its normal value (- max) and rising along the dotted line, will start with the residual value ( R) and trance the curve ( L). © ABB Power Technology 1_114Q07- 8 -
  • 9. Initial inrush  Curve t is a displaced sinusoid, regardless of the magnetic circuit's saturation characteristics.  Theoretically, the value of max is + (| R| + 2| max|).  In transformers designed for some normal, economical saturation density s, the crest of t will produce super saturation in the magnetic circuit.  The result will be a very large crest value in the © ABB Power Technology magnetizing current. 1_114Q07- 9 -
  • 10. Initial inrush  For the first few cycles, the inrush current decays rapidly. Then, however, the current subsides very slowly, sometimes taking many seconds if the resistance is low.  The time constant of the circuit (L/R) is not, in fact, a constant: L varies as a result of transformer saturation. During the first few cycles, saturation is high and L is low. As the losses damp the circuit, the saturation drops and L increases. According to a 1951 AIEE report, time © ABB Power Technology constants for inrush vary from 10 cycles for small units to as much as 1 1_114Q07- 10 - min for large units.
  • 11. Initial inrush  The resistance from the source to the bank determines the damping of the current wave.  Banks near a generator will have a longer inrush because the resistance is very low.  Likewise, large transformer units tend to have a long inrush as they represent a large L relative to the system resistance.  At remote substations, the inrush will not be nearly so severe, since the resistance in the connecting line will quickly damp the current. © ABB Power Technology 1_114Q07- 11 -
  • 12. Initial inrush  When there is more than one delta winding on a transformer bank, the inrush will he influenced by the coupling between the different voltage windings. Depending on the core construction, three-phase transformer units may be subject to interphase coupling that could also affect the inrush current.  Similar wave shapes would be encountered when energizing the wye winding of a wye-delta bank, or an autotransformer. Here, the single- phase shape would be distorted as a result of the interphase coupling produced by the delta winding (or tertiary). © ABB Power Technology 1_114Q07- 12 -
  • 13. Initial inrush  Maximum inrush will not, of course, occur on every energization.  The probability of energizing at the worst condition is relatively low.  Energizing at maximum voltage will not produce an inrush with no residual.  In a three-phase bank, the inrush in each phase will vary appreciably.  The maximum inrush for a transformer bank can be calculated from the excitation curve if available, and Table shows a typical calculation of an inrush current (used phase A voltage as 0° reference). Closing Peak value of inrush current wave (p.u.) S angle Ia Ib Ic Ia-Ib Ib-Ic Ic-Ia 1.40 0° 5.60 -3.73 -3.73 8.33 -3.73 -8.33 1.40 30° 5.10 — 1.87 -5.10 5.96 5.10 -9.20 © ABB Power Technology 1.15 0° 6.53 -4.67 -4.67 10.20 -4.67 -10.20 1.15 30° 6.03 — 2.80 -6.03 7.83 6.03 -11.06 1_114Q07- 13 -
  • 14. Initial inrush  From these calculated values it can be seen that:  The lower the value of the saturation density flux S, the higher the inrush peak value.  The maximum phase-current inrush occurs at the 0° closing angle (i.e., 0 voltage).  The maximum line-current inrush occurs at ± 30° closing angles.  Because of the delta connection of transformer winding or current transformers, the maximum line-current in-rush value should be considered when applying current to the differential relay. Closing Peak value of inrush current wave (p.u.) S angle Ia Ib Ic Ia-Ib Ib-Ic Ic-Ia 1.40 0° 5.60 -3.73 -3.73 8.33 -3.73 -8.33 1.40 30° 5.10 — 1.87 -5.10 5.96 5.10 -9.20 © ABB Power Technology 1.15 0° 6.53 -4.67 -4.67 10.20 -4.67 -10.20 1.15 30° 6.03 — 2.80 -6.03 7.83 6.03 -11.06 1_114Q07- 14 -
  • 15. Sympathetic inrush  When a bank is paralleled with a second energized bank, the energized bank can experience a sympathetic inrush.  The offset inrush current of the bank being energized will find a parallel path in the energized bank.  The dc component may saturate the transformer iron. creating an apparent inrush.  The magnitude of this inrush depends on the value of the transformer impedance relative to that of the rest of the system, which forms an additional parallel circuit.  Again, the sympathetic inrush will always be less than the initial inrush. © ABB Power Technology 1_114Q07- 15 -
  • 16. Sympathetic inrush  The total current at breaker C is the sum of the initial inrush of bank A and the sympathetic inrush of bank B.  Since this waveform looks like an offset fault current, it could cause misoperation if a common set of harmonic restraint differential relays were used for both banks.  Unit-type generator and transformer combinations have no initial inrush © ABB Power Technology problem because the unit is brought up to full voltage gradually. 1_114Q07- 16 - Recovery and sympathetic inrush may be a problem, but as indicated above, these conditions are less severe than initial inrush.
  • 17. AGENDA  PRINCIPLES  LINES PROTECTION  TRANSFORMERS PROTECTION  INTRODUCTION  SELECTING A PROTECTIVE SYSTEM  Differential protection  Sudden pressure relay  Overcurrent protection  Transformer tank protection  Typical protective scheme for power transformers © ABB Power Technology  STATION BUS PROTECTION 1_114Q07- 17 -
  • 18. Differential relaying for transformer protection  It compares the current entering the transformer with the current leaving the element.  If they are equal there is no fault inside the zone of protection  If they are not equal it means that a fault occurs between the two ends 87 © ABB Power Technology With internal fault Id > 0 Trip With external fault Id = 0 No trip 1_114Q07- 18 -
  • 19. Differential relaying for transformer protection  Alternatively one could form an algebraic sum of the two currents entering the protected element, which could be termed as differential current (Id), and use a level detector relay to detect the presence of a fault.  In general this principle is capable of detecting very small magnitudes of fault.  Its only drawback is that it requires currents from the extremities of a zone of protection © ABB Power Technology 1_114Q07- 19 -
  • 20. Differential relaying for transformer protection  Differential relays are the principal form of fault protection for transformers rated at 10 MVA and above.  These relays, however, cannot be as sensitive as the differential relays used for generator protection.  Transformer protection is further complicated by a variety of equipment requiring special attention: multiple-winding transformer banks, zig-zag transformers, voltage regulators, transformers in unit systems, and three-phase trans-former banks with single-phase units. © ABB Power Technology 1_114Q07- 20 -
  • 21. Differential relaying for transformer protection  Transformer differential relays are subject to several factors, not ordinarily present for generators or buses, that can cause miss- operation:  Different voltage levels, including taps, that result in different primary currents in the connecting circuits.  Possible mismatch of ratios among different current transformers.  For units with ratio-changing taps, mismatch can also occur on the taps. Current transformer performance is different, particularly at high currents.  30° phase-angle shift introduced by transformer wye-delta connections.  Magnetizing inrush currents, which the differential relay sees as internal faults. © ABB Power Technology 1_114Q07- 21 -
  • 22. Differential relaying for transformer protection Id  To prevent miss-operation percentage characteristics are used, with line current Operating zone restraint. © ABB Power Technology (I1 + I2)/2 1_114Q07- 22 -
  • 23. Differential relaying for transformer protection  Since the differential relays see the inrush current as an internal fault, some method of distinguishing between fault and inrush current is necessary.  Such methods include:  A differential relay with reduced sensitivity to the inrush wave (such units have a higher pickup for the offset wave, plus time delay to override the high initial peaks).  A harmonic restraint or a supervisory unit used in con-junction with the differential relay  Desensitization of the differential relay during bank energization. © ABB Power Technology 1_114Q07- 23 -
  • 24. Differential relay for transformer protection  Induction relays are relatively insensitive to the high percentage of harmonics contained in magnetizing inrush current.  The relay shown consists of a percentage differential unit and an indication contactor switch.  The percentage differential unit, an induction disc type, has an electromagnet with poles above and below the disc.  There are two restraint coils on the lower left-hand pole; the operating coil is wound on the lower right-hand pole.  Both the left- and right-hand poles have © ABB Power Technology transformer winding, connected in parallel to supply current to the upper-pole 1_114Q07- 24 - windings.
  • 25. Differential relay for transformer protection  The upper-pole current generates a flux in quadrature with the lower- pole resultant flux, and the two fluxes react to produce a torque on the disc.  Under normal load or in external fault, the currents in the two restraint windings flow in the same direction.  These restraining currents are equal (or effectively equal) if auto- balance taps are used to compensate from mismatch in current transformer ratios - and if no significant current flows in the operating coil winding.  As a result, only contact-opening torque is produced. © ABB Power Technology 1_114Q07- 25 -
  • 26. Differential relay for transformer protection  If the taps are mismatched or the main current transformers saturate unequally on severe external faults, the effective difference between the currents in the two restraining windings must flow in the operating coil.  The operating coil current required to overcome the restraining torque and close the relay contacts is a function of the restraining current. For an internal fault, the restraining currents are opposite, and restraining torque tends to cancel out.  The more sensitive operating coil, however, is energized by the sum of the two currents. As a result, a large amount of contact-closing torque is produced. © ABB Power Technology 1_114Q07- 26 -
  • 27. Differential relay for transformer protection  In applying the relay, the current transformer ratio error should not exceed 10% during maximum symmetrical external fault current. The relay's 50% characteristic satisfactorily handles up to 35% of current mismatch, including the transformer tap changing on load and current transformer mismatch.  The relay's restraining windings have a continuous rating of 10 A; the operating winding has a continuous rating of 5 A. To prevent overloading the operating winding, however, no more than 5 A should be allowed in the untapped restraining winding. © ABB Power Technology 1_114Q07- 27 -
  • 28. Variable-Percentage Transformer Differential Relay  This type of relays have a variable-percentage characteristic:  Percentage is low on light faults, where the current transformer performance is good, and high on heavy faults, where current transformer saturation may occur.  The variable-percentage characteristic is obtained via a saturation transformer in the operating circuit.  This transformer also tends to shunt the dc component away from the operating coil. © ABB Power Technology 1_114Q07- 28 -
  • 29. Variable-Percentage Transformer Differential Relay  The relay consists of an induction-type differential unit, a dc-indicating contactor switch, and an optional ac-indicating instantaneous trip unit.  The induction-type differential unit contains four electromagnets, operating on two discs fastened to a common shaft.  Of the electromagnets, one is the operating element and the other three are restraint elements. On the center leg of each restraint electromagnet are two primary coils and a secondary coil ; primary coils are energized from the secondaries of the current transformers connected to the bank to be protected. © ABB Power Technology 1_114Q07- 29 -
  • 30. Variable-Percentage Transformer Differential Relay  A 5-A current in the restraint coil will produce restraining torque. The same 5-A current flowing in two restraint coils of the same restraint electromagnet will have either additive or subtractive restraining effect, depending on the polarity of the connection (Figure c).  This relay is well suited to protect transformer banks not subject to severe magnetizing inrush, particularly if more than two restraining circuits are needed. The relay has no built-in taps and generally requires auxiliary current transformers for current matching. The operating time of the differential unit is two to six cycles; no setting is required.  The faster IIT unit is connected to the differential circuit. It is recommended for transformer protection in applications where internal fault current can exceed twice the maximum total current flowing through the differential zone for a symmetrical external fault. The IIT © ABB Power Technology unit should be set at 50% external fault current or a value higher than transformer inrush current, whichever is greater. 1_114Q07- 30 -
  • 31. Harmonic restraint Transformer Differential Relay  Since magnetizing inrush current has a high harmonic content, particularly the second harmonic, this second harmonic can be used to restrain and thus desensitize a relay during energization.  The method of harmonic restraint is not without its problems.  There must be enough restraint to avoid relay operation on inrush, without making the relay insensitive to internal faults that may also have some harmonic content. © ABB Power Technology 1_114Q07- 31 -
  • 32. Harmonic restraint Transformer Differential Relay  In the differential unit, (DU) air-gap transformers feed the restraint circuits, and a non-air-gap transformer energizes the operating coil circuit.  Since the rectified restraint outputs are connected in parallel, the relay restraint is proportional to the maximum restraining current in any restraint circuit. © ABB Power Technology 1_114Q07- 32 -
  • 33. Harmonic restraint Transformer Differential Relay  The percentage characteristic varies from around 20% on light faults, where current transformer performance is good, to approximately 60% on heavy fault, where current transformer saturation may occur.  This variable-percentage characteristic is obtained via the saturating transformer in the operating coil circuit.  The minimum pickup is the current that will just close the differential unit contacts, with the operating coil and one restraint coil energized.  The continuous rating of the relay is 10 to 22 A, depending on the relay tap used. © ABB Power Technology 1_114Q07- 33 -
  • 34. Harmonic restraint Transformer Differential Relay  The harmonic restraint unit (HRU) has a second-harmonic blocking filter in the operating coil circuit and a second-harmonic pass filter in the restraint coil circuit.  Thus, the predominant second-harmonic characteristic of an inrush current produces ample restraint with minimum operating energy.  The circuit is designed to hold open its contacts when the second- harmonic component is higher than 15% of the fundamental.  This degree of restraint in the HRU is adequate to prevent relay operation on practically all inrushes, even if the differential unit should operate. © ABB Power Technology 1_114Q07- 34 -
  • 35. Harmonic restraint Transformer Differential Relay  For internal faults, ample operating energy is produced by the fundamental frequency and harmonic other than the second.  The second harmonic is at a minimum during a fault. Since the HRU will operate at the same pickup as the DU, the differential unit will operate sensitively on internal faults.  For external faults, the differential unit (DU) will restrain.  The relay operating time is one cycle at 20 times tap value.  The instantaneous trip unit (IIT) is included to ensure high-speed operation on heavy internal faults, where current transformer saturation may delay HRU contact closing.  The IIT pickup is 10 times the relay tap value.  This setting will override the inrush peaks and maximum false © ABB Power Technology differential current on external faults. 1_114Q07- 35 -
  • 36. Transformer Differential Relay Application  The following guidelines are designed to assist in selecting and applying relays for transformer protection.  When two or more relays appear to be equally suitable, engineering experience and economics will determine the final choice.  There is no clear-cut answer to the question of which relay or protective method to apply.  As a general rule, however, the induction-disk differential relays are used at substations remote from large generating sources where inrush is not a problem and the kVA size of the bank is relatively small.  The more complex and more expensive harmonic relays are used at generating stations and for large transformer units located close to generating sources, where a severe inrush is highly likely. © ABB Power Technology 1_114Q07- 36 -
  • 37. Transformer Differential Relay Application  In general, the current transformers on the wye side of a wye-delta bank must be connected in delta, and the current transformers on the delta side connected in wye.  This arrangement (1) compensates for the 30° phase-angle shift introduced by the wye-delta bank and (2) blocks the zero sequence current from the differential circuit on external ground faults. © ABB Power Technology 1_114Q07- 37 -
  • 38. Transformer Differential Relay Application  Zero sequence current will flow in the differential circuit for external ground faults on the wye side of a grounded wye-delta bank; if the current transformers were connected in wye, the relays would miss- operate.  With the current transformers connected in delta, the zero sequence current circulates inside the current transformers, preventing relay miss- operation. © ABB Power Technology 1_114Q07- 38 -
  • 39. Transformer Differential Relay Application  Relays should be connected to receive “in” and “out” currents that are in phase for a balanced load condition.  When there are more than two windings, all combinations must be considered, two at a time.  Relay taps or auxiliary current transformer ratios should be as close as possible to the current ratios for a balanced maximum load condition.  When there are more than two winding, all combinations must he considered, two at a time, and based on the sane kVA capacity.  Only ground one point in the differential scheme, never do multiple- point grounding. © ABB Power Technology 1_114Q07- 39 -
  • 40. Transformer Differential Relay Application  The percentage of current mismatch should always be checked to ensure that the relay taps selected have an adequate safety margin.  When necessary, current mismatch values can be reduced by changing current transformer taps or adding auxiliary current transformers. © ABB Power Technology 1_114Q07- 40 -
  • 41. AGENDA  PRINCIPLES  LINES PROTECTION  TRANSFORMERS PROTECTION  INTRODUCTION  SELECTING A PROTECTIVE SYSTEM  Differential protection  Sudden pressure relay  Overcurrent protection  Transformer tank protection  Typical protective scheme for power transformers © ABB Power Technology  STATION BUS PROTECTION 1_114Q07- 41 -
  • 42. Sudden-Pressure Relay (SPR)  With the application of a gas-pressure relay, many transformers can be protected by a simple differential relay set insensitively in the inrush current.  The sudden-pressure relay (SPR), which operates on a rate of rise of gas in the transformer, can be applied to any trans-former with a sealed air or gas chamber above the oil level.  The relay is fastened to the tank or manhole cover, above the oil level. It will not operate on static pressure or pressure changes resulting from normal operation of the transformer. © ABB Power Technology 1_114Q07- 42 -
  • 43. Sudden-Pressure Relay (SPR)  The SPR relay is recommended for all units of 5000 kVA or more.  The SPR relay is far more sensitive to light internal faults than the differential relay. The differential relay, however, is still required for faults in the bushing and other areas outside the tank.  The SPR relay operating time varies from 1/2 cycle to 37 cycles, depending on the size of the fault.  In the past, large-magnitude through-fault conditions on power transformers have caused rate-of-change-of-pressure relays to occasionally operate falsely. There has been reluctance on the part of some users to connect these rate-of- change-of-pressure relays to trip, and they have therefore used them for alarming only. Schemes have been devised to restrict tripping of the rate-of- change-of-pressure device only to levels of current below which the transformer differential relay cannot operate. © ABB Power Technology 1_114Q07- 43 -
  • 44. AGENDA  PRINCIPLES  LINES PROTECTION  TRANSFORMERS PROTECTION  INTRODUCTION  SELECTING A PROTECTIVE SYSTEM  Differential protection  Sudden pressure relay  Overcurrent protection  Transformer tank protection  Typical protective scheme for power transformers © ABB Power Technology  STATION BUS PROTECTION 1_114Q07- 44 -
  • 45. Overcurrent and Backup Protection  To allow transformer overloading when necessary, the pickup value of phase overcurrent relays must be set 50/51 above this overload current. t  An inverse-time characteristic relay Curva trafo usually provides the best coordination. Relé tiempo independ. Relé tiempo inverso  Settings of 200 to 300% of the transformer's self-cooled rating are common, although higher values are t0 some-times used. i  Fast operation is not possible, since In n*In the transformer relays must coordinate with all other relays they © ABB Power Technology overreach. 1_114Q07- 45 -
  • 46. Overcurrent and Backup Protection  Overcurrent relays cannot be used for primary protection without the risk of internal faults causing extensive damage to the transformer.  Fast operation on heavy internal faults is obtained by using instantaneous trip units in the overcurrent relays.  These units may be set at 125% of the maximum through fault, which is usually a low-side three-phase fault.  The setting should be above the inrush current. Often, instantaneous trip units cannot be used because the fault currents are too small.  An overcurrent relay set to protect the main windings of an autotransformer or three-winding transformer offers almost no protection to the tertiary windings, which have a much smaller kVA.  Also, these tertiary windings may carry very heavy currents during ground faults. In such cases, tertiary overcurrent protection must be © ABB Power Technology provided. 1_114Q07- 46 -
  • 47. Overcurrent and Backup Protection  A through fault external to a transformer results in an overload that can cause transformer failure if the fault is not cleared promptly.  It is widely recognized that damage to transformers from through faults is the results of thermal and mechanical effects.  The thermal effect has been well understood for years.  The mechanical effect has recently gained increased recognition as a major concern of transformer failure.  This results from the cumulative nature of some of the mechanical effects, particularly insulation compression, insulation wear, and friction-induced displacement.  The damage that occurs as a result of these cumulative effects is a function of not only the magnitude and duration of through faults, but also the total number of such faults. © ABB Power Technology 1_114Q07- 47 -
  • 48. Overcurrent and Backup Protection  The transformer can be isolated from the fault before damage occurs by using fuses or overcurrent relays. 50/51N 50/51G 2-3 50/51 © ABB Power Technology 1_114Q07- 48 -
  • 49. Distance Relaying for Backup Protection  Directional distance relaying can be used for transformer backup protection when the setting or coordination of the overcurrent relays is a problem.  The directional distance relays are connected to operate when the fault current flows toward the protected transformer.  They are set to reach into, but not beyond, the transformer. © ABB Power Technology 1_114Q07- 49 -
  • 50. AGENDA  PRINCIPLES  LINES PROTECTION  TRANSFORMERS PROTECTION  INTRODUCTION  SELECTING A PROTECTIVE SYSTEM  Differential protection  Sudden pressure relay  Overcurrent protection  Transformer tank protection  Typical protective scheme for power transformers © ABB Power Technology  STATION BUS PROTECTION 1_114Q07- 50 -
  • 51. Transformer Tank protection  This is a low cost protection against some of the internal faults of the transformer, which consists of an overcurrent relay which measures the current flow through the ground connection of the transformer tank.  It detects hence the ground faults of the transformer and bushings trough the metallic tank.  To achieve this the transformer must be completely isolated from ground (putting some isolating material under the transformer wheels), and a toroid current transformer is needed surrounding the only ground connection cable. © ABB Power Technology 64 1_114Q07- 51 -
  • 52. Transformer Tank protection  To prevent incorrect tripping (because of possible faults in the connection cables to fans, etc) it is necessary to take some measure as the indicated in fig, and to coordinate with the neutral protection. © ABB Power Technology 1_114Q07- 52 -
  • 53. AGENDA  PRINCIPLES  LINES PROTECTION  TRANSFORMERS PROTECTION  INTRODUCTION  SELECTING A PROTECTIVE SYSTEM  Differential protection  Sudden pressure relay  Overcurrent protection  Transformer tank protection  Typical protective scheme for power transformers © ABB Power Technology  STATION BUS PROTECTION 1_114Q07- 53 -
  • 54. Typical protective scheme for power transformers  Figure illustrates how a primary breaker can be used for transformer protection.  The basic protection is provided by the 87T transformer differential relays.  Device 50/51, an inverse-time relay with IIT unit, provides transformer primary winding backup protection for phase faults;  either device 50G (with a zero sequence current transformer) or 50N/51N can be used as © ABB Power Technology transformer primary winding backup for ground faults. 1_114Q07- 54 -
  • 55. Typical protective scheme for power transformers  Transformer overload, low-voltage bus, and feeder backup protection are provided by device 51 on the transformer secondary side.  Since the low-voltage side is medium-resistance-grounded, a ground relay (51G) should be used to trip breaker 52-1 for low-side ground faults and for resistor thermal protection.  Device 151G, which trips breaker 52-11, provides feeder ground backup, whereas device 63, such as a type SPR relay, offers highly © ABB Power Technology sensitive protection for light faults. 1_114Q07- 55 -
  • 56. Typical protective scheme for power transformers  The current transformer ratings in this scheme should be compatible with the transformer short-time overload capability: approximately 200% of transformer selfcooled rating for wye-connected current transformers and 350% ( · 200%) for delta-connected current transformers.  The neutral current transformer rating should be 50% of the maximum resistor current rating. © ABB Power Technology 1_114Q07- 56 -