COLD-AISLE CONTAINMENT IN DATA CENTRES
                the smart concept for optimal energy use


                                                                                                  www.knuerr.com




                                           Application Report
                              Cold-Aisle Containment in Data Centres
                                      The smart concept for optimal energy use


  Cooling requirements in data centres are continually rising, causing conventional climate control systems to be
  overloaded.

  Switching to a water cooled systems is an option, but structurally and financially this is not always possible.

  Cold-Aisle Containment (CoolFlex) is another option. This option consistently separates cold and warm areas
  without requiring structurally changes to the data centre.

  Over several weeks the efficiency of CoolFlex was tested and proved. The test was conducted using fan heaters to
  simulate the heat load generated by servers.

  The result: At a thermal load of ca. 14kW per rack, the required temperature of 23°C in the cold aisle was
  reached. During further tests, several computer room air conditioning units (CRAC) were switched off to
  simulate an emergency. During these tests the cold aisle temperature of 23°C was only marginally
  exceeded.




                                                                                                                    1
COLD-AISLE CONTAINMENT IN DATA CENTRES
                the smart concept for optimal energy use


                                                                                                  www.knuerr.com



  Description of application:

  Test conditions
  The raised floor provided greater energy efficiency by directing cool air through perforated plates in the cold aisle
  and by sealing the cable entry in to the racks. Knürr isolated the cold and hot zones within the server racks using
  infill panels. All 4 cold aisles were then enclosed using cold aisle containment.

  The 342 KW heat capacity was simulated via fan heaters (38 x 9kW = 342 kW). 288 kW heat capacity was
  simulated within aisle 2. Aisle 1, 3 and 4 were not in use and therefore produced no heat. The remaining 54 kW
  were distributed throughout the room, simulating the heat capacity in the network and free standing racks.

  To minimise the loss of circulation and pressure caused by the raised floor, Knürr used special “grate catch”
  instead of perforated raised floor plates. All holes for cables through the floor were sealed to prevent hot air
  shortcuts.




  The CRAC units used were designed to use 250 kW in their energy-efficient, normal mode and 500 kW at high
  power mode. The capacity of the fans is proportional to the third power of the circulatory. Therefore it is more
  energy-efficient to run all CRAC units at lower speed, instead of using less CRAC units at their maximal speed. By
  consistently isolating cold and warm air, the nominal capacity of the CRAC units is increased, therefore the same
  number of CRAC units can run at a high power mode, without reducing redundancy.




                                                                                                                          2
COLD-AISLE CONTAINMENT IN DATA CENTRES
               the smart concept for optimal energy use


                                                                 www.knuerr.com



  Test areas
  Test 1: Energy-efficiency in normal mode
          6 CRAC units in normal mode (speed ca. 30%)
          Pressure test with a rising thermal load




         Results during full load(ca. 288 kW in aisle + 54 kW)
           Temperature of cold aisle: 23,0 °C
           Temperature of warm aisle: 37,0 °C


  Test 2: Emergency (Breakdown of 2 CACUs)
          3 CRAC units in emergency mode (speed ca. 80%)




         Results during full load(ca. 288 kW in aisle + 54 kW
            Temperature of cold aisle: 23,1 °C
            Temperature of warm aisle: 42,9 °C

                                                                                  3
COLD-AISLE CONTAINMENT IN DATA CENTRES
                the smart concept for optimal energy use


                                                                                                www.knuerr.com



  Test 3: Extreme emergency (Breakdown of 4 CACUs)
          2 CRAC units in emergency mode (speed 100%)




          Results during full load(ca. 288 kW in aisle + 54 kW)
            Temperature of cold aisle: 23,5 °C
            Temperature of warm aisle: 47,0 °C

          With only 2 CRAC units the temperature in the cold aisle did not exceed the required 24°C.
          After a time the fan heaters simulating server heat load failed due to a fail safe switch.



  Results and Conclusions
  To discover the maximum capacity of cold aisle containment by increasing the heat capacity in the data centre.
  - Load per Rack 3.6kW (Face: 3.5 m² = ca. 1‘000 W/m²) = possible!
  - Load per Rack 7.6kW (Face: 3.5 m² = ca. 2‘000 W/m²) = possible!
  - Load per Rack 10.8kW (Face: 3.5 m² = ca. 3‘000 W/m²) = possible!
  - Load per Rack 14.4kW (Face: 3.5 m² = ca. 4‘000 W/m²) = possible!

  The cold aisle containment could possibly discharge a higher heat load however the fan heater fail safe thermostat
  caused at collapsed after 4'000W/m². Also the test equipment was not calibrated for higher heat load. Therefore
  we could not demonstrate the limits of the cold aisle containment.

  Note: It is important to note that during this pilot project, fan heaters were used to demonstrate the cooling
  capacity. Fan heaters can only simulate the heat generated by servers, as they have a lower flow volume across
  the server. We are positive, that in a real situation, 10 to 12 KW per rack should be possible (various other experts
  do not differentiate between the use of fan heater and real servers)




                                                                                                                      4
COLD-AISLE CONTAINMENT IN DATA CENTRES
             the smart concept for optimal energy use


                                                        www.knuerr.com


  Pictures of test site




                                                                         5
COLD-AISLE CONTAINMENT IN DATA CENTRES
                  the smart concept for optimal energy use


                                                                                                 www.knuerr.com



  Services provided
  Using trained personnel, Knürr is able to provide the following services:
  Consulting, calculation, and simulation of a solution.
  Simple installation into existing racks (dependent of make of rack).
  Integration and installation without the need for down time.
   • Data Centres Thermal Assessment
       - Review of thermal demands and air flow within the data centre
       - Thermal imaging of the computer centre, several aisles and/or racks
       - Proposal of cost effective measures
       - Complete report, with achievable improvements
   • “Cold Aisle Containment” implementation of the solution
       - Site visit (inclusive demarcation of project specific items, especially competitor racks)
       - Creation of project plan
       - Detailed pricing offer




  Knürr AG
  Mariakirchener Straße 38
  94424 Arnstorf
  Telefon +49 (0) 87 23-27-0
  Telefax +49 (0) 87 23-27-154
  E-Mail: info@knuerr.com
  www.knuerr.com




                                                                                                                  6

Más contenido relacionado

La actualidad más candente

District Cooling Jenny Dahlberg, Fortum
District Cooling   Jenny Dahlberg, FortumDistrict Cooling   Jenny Dahlberg, Fortum
District Cooling Jenny Dahlberg, FortumNiklas Johnsson
 
Heat gain valuees foe equipment
Heat gain valuees foe equipmentHeat gain valuees foe equipment
Heat gain valuees foe equipmentsaba arif
 
12 Cooling Load Calculations
12 Cooling Load Calculations12 Cooling Load Calculations
12 Cooling Load Calculationsspsu
 
Keith_Coulson_poster
Keith_Coulson_posterKeith_Coulson_poster
Keith_Coulson_posterKeith Coulson
 
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NRELBits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NRELinside-BigData.com
 
Saving energy with cooling towers
Saving energy with cooling towersSaving energy with cooling towers
Saving energy with cooling towersAbdelrahim Ramadan
 
PowerplantProposal (1)
PowerplantProposal (1)PowerplantProposal (1)
PowerplantProposal (1)RJ Robledo
 
JIE_hybrid_PVT_model
JIE_hybrid_PVT_modelJIE_hybrid_PVT_model
JIE_hybrid_PVT_modelSam Sim
 
Presentation DCP(revised)
Presentation DCP(revised)Presentation DCP(revised)
Presentation DCP(revised)Daniel udau
 
Energy saving by evaporative cooling in AHUs
Energy saving by evaporative cooling in AHUsEnergy saving by evaporative cooling in AHUs
Energy saving by evaporative cooling in AHUsCAREL Industries S.p.A
 
Cold storage design
Cold storage designCold storage design
Cold storage designengrhanif04
 
Boris Shapiro Controls expeiences
Boris Shapiro Controls expeiencesBoris Shapiro Controls expeiences
Boris Shapiro Controls expeiencesBoris Shapiro PE
 
ICRERA_Presentation_SSimms
ICRERA_Presentation_SSimmsICRERA_Presentation_SSimms
ICRERA_Presentation_SSimmsSam Sim
 
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...ijiert bestjournal
 

La actualidad más candente (20)

District Cooling Jenny Dahlberg, Fortum
District Cooling   Jenny Dahlberg, FortumDistrict Cooling   Jenny Dahlberg, Fortum
District Cooling Jenny Dahlberg, Fortum
 
Heat gain valuees foe equipment
Heat gain valuees foe equipmentHeat gain valuees foe equipment
Heat gain valuees foe equipment
 
11 mn01 review 3
11 mn01 review 311 mn01 review 3
11 mn01 review 3
 
12 Cooling Load Calculations
12 Cooling Load Calculations12 Cooling Load Calculations
12 Cooling Load Calculations
 
Keith_Coulson_poster
Keith_Coulson_posterKeith_Coulson_poster
Keith_Coulson_poster
 
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NRELBits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
 
Natural efficiency: available now!
Natural efficiency: available now!Natural efficiency: available now!
Natural efficiency: available now!
 
Saving energy with cooling towers
Saving energy with cooling towersSaving energy with cooling towers
Saving energy with cooling towers
 
PowerplantProposal (1)
PowerplantProposal (1)PowerplantProposal (1)
PowerplantProposal (1)
 
District Cooling And Desalination
District Cooling And DesalinationDistrict Cooling And Desalination
District Cooling And Desalination
 
JIE_hybrid_PVT_model
JIE_hybrid_PVT_modelJIE_hybrid_PVT_model
JIE_hybrid_PVT_model
 
Presentation DCP(revised)
Presentation DCP(revised)Presentation DCP(revised)
Presentation DCP(revised)
 
Final pwpt Presentation
Final pwpt PresentationFinal pwpt Presentation
Final pwpt Presentation
 
Energy saving by evaporative cooling in AHUs
Energy saving by evaporative cooling in AHUsEnergy saving by evaporative cooling in AHUs
Energy saving by evaporative cooling in AHUs
 
Cold storage design
Cold storage designCold storage design
Cold storage design
 
Appa
AppaAppa
Appa
 
Boris Shapiro Controls expeiences
Boris Shapiro Controls expeiencesBoris Shapiro Controls expeiences
Boris Shapiro Controls expeiences
 
Soft Magnetic Nanocrystalline Materials for Inductors and Shielding Applicati...
Soft Magnetic Nanocrystalline Materials for Inductors and Shielding Applicati...Soft Magnetic Nanocrystalline Materials for Inductors and Shielding Applicati...
Soft Magnetic Nanocrystalline Materials for Inductors and Shielding Applicati...
 
ICRERA_Presentation_SSimms
ICRERA_Presentation_SSimmsICRERA_Presentation_SSimms
ICRERA_Presentation_SSimms
 
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...
 

Similar a Optimal Data Centre Cooling with Cold-Aisle Containment

Apc cooling solutions
Apc cooling solutionsApc cooling solutions
Apc cooling solutionspeperoca
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationGreg Stover
 
Ppt4 exp leeds - alan real and jon summers ( university of leeds ) experien...
Ppt4   exp leeds - alan real and jon summers ( university of leeds ) experien...Ppt4   exp leeds - alan real and jon summers ( university of leeds ) experien...
Ppt4 exp leeds - alan real and jon summers ( university of leeds ) experien...JISC's Green ICT Programme
 
Commercial Overview SCS Session 1 Server Rack Strategies
Commercial Overview   SCS Session 1   Server Rack StrategiesCommercial Overview   SCS Session 1   Server Rack Strategies
Commercial Overview SCS Session 1 Server Rack Strategiespaul_mathews
 
Sb lambda in-row_ver.1.3_en
Sb lambda in-row_ver.1.3_enSb lambda in-row_ver.1.3_en
Sb lambda in-row_ver.1.3_enYury Naumov
 
What's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & MoreWhat's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & MoreUpsite Technologies
 
PAC 2.5 Efficiency is Attainable, What are you Waiting for?
PAC 2.5 Efficiency is Attainable, What are you Waiting for?PAC 2.5 Efficiency is Attainable, What are you Waiting for?
PAC 2.5 Efficiency is Attainable, What are you Waiting for?SchneiderITB
 
Datacenter event - pitch - qarnot computing - paul benoit - 15-09-14
Datacenter event - pitch - qarnot computing - paul benoit - 15-09-14Datacenter event - pitch - qarnot computing - paul benoit - 15-09-14
Datacenter event - pitch - qarnot computing - paul benoit - 15-09-14Karim Network
 
Dcd 2012 liquid cooling presentation
Dcd 2012 liquid cooling presentationDcd 2012 liquid cooling presentation
Dcd 2012 liquid cooling presentationScicomm
 
Critical design elements for high power density data centers
Critical design elements for high power density data centersCritical design elements for high power density data centers
Critical design elements for high power density data centersInternap
 
Data center cooling solution
Data center cooling solution Data center cooling solution
Data center cooling solution Bradr998
 
Aurora hpc energy efficiency
Aurora hpc energy efficiencyAurora hpc energy efficiency
Aurora hpc energy efficiencyEurotech Aurora
 
Data Center Lessons Learned
Data Center Lessons LearnedData Center Lessons Learned
Data Center Lessons LearnedTom Greenbaum
 
Sb in rack-ver.1.0_en
Sb in rack-ver.1.0_enSb in rack-ver.1.0_en
Sb in rack-ver.1.0_enYury Naumov
 
Mechanical Engineering Seminar 2017_3
Mechanical Engineering Seminar 2017_3Mechanical Engineering Seminar 2017_3
Mechanical Engineering Seminar 2017_3Nicholas Naing
 
TurboCryogenics Tech Brief
TurboCryogenics Tech BriefTurboCryogenics Tech Brief
TurboCryogenics Tech Briefenvestex
 
Utilization of Computer Room Cooling Infrastructure: Measurement Reveals Oppo...
Utilization of Computer Room Cooling Infrastructure: Measurement Reveals Oppo...Utilization of Computer Room Cooling Infrastructure: Measurement Reveals Oppo...
Utilization of Computer Room Cooling Infrastructure: Measurement Reveals Oppo...Upsite Technologies
 
Power Point Data Centre Uk Limited Apc
Power Point Data Centre Uk Limited ApcPower Point Data Centre Uk Limited Apc
Power Point Data Centre Uk Limited Apccharles1010
 

Similar a Optimal Data Centre Cooling with Cold-Aisle Containment (20)

Apc cooling solutions
Apc cooling solutionsApc cooling solutions
Apc cooling solutions
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure Optimization
 
Ppt4 exp leeds - alan real and jon summers ( university of leeds ) experien...
Ppt4   exp leeds - alan real and jon summers ( university of leeds ) experien...Ppt4   exp leeds - alan real and jon summers ( university of leeds ) experien...
Ppt4 exp leeds - alan real and jon summers ( university of leeds ) experien...
 
Commercial Overview SCS Session 1 Server Rack Strategies
Commercial Overview   SCS Session 1   Server Rack StrategiesCommercial Overview   SCS Session 1   Server Rack Strategies
Commercial Overview SCS Session 1 Server Rack Strategies
 
Sb lambda in-row_ver.1.3_en
Sb lambda in-row_ver.1.3_enSb lambda in-row_ver.1.3_en
Sb lambda in-row_ver.1.3_en
 
What's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & MoreWhat's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & More
 
PAC 2.5 Efficiency is Attainable, What are you Waiting for?
PAC 2.5 Efficiency is Attainable, What are you Waiting for?PAC 2.5 Efficiency is Attainable, What are you Waiting for?
PAC 2.5 Efficiency is Attainable, What are you Waiting for?
 
Datacenter event - pitch - qarnot computing - paul benoit - 15-09-14
Datacenter event - pitch - qarnot computing - paul benoit - 15-09-14Datacenter event - pitch - qarnot computing - paul benoit - 15-09-14
Datacenter event - pitch - qarnot computing - paul benoit - 15-09-14
 
Dcd 2012 liquid cooling presentation
Dcd 2012 liquid cooling presentationDcd 2012 liquid cooling presentation
Dcd 2012 liquid cooling presentation
 
Critical design elements for high power density data centers
Critical design elements for high power density data centersCritical design elements for high power density data centers
Critical design elements for high power density data centers
 
Data center cooling solution
Data center cooling solution Data center cooling solution
Data center cooling solution
 
Aurora hpc energy efficiency
Aurora hpc energy efficiencyAurora hpc energy efficiency
Aurora hpc energy efficiency
 
Data Center Cooling Study on Liquid Cooling
Data Center Cooling Study on Liquid CoolingData Center Cooling Study on Liquid Cooling
Data Center Cooling Study on Liquid Cooling
 
Data Center Lessons Learned
Data Center Lessons LearnedData Center Lessons Learned
Data Center Lessons Learned
 
Design computerroom
Design computerroomDesign computerroom
Design computerroom
 
Sb in rack-ver.1.0_en
Sb in rack-ver.1.0_enSb in rack-ver.1.0_en
Sb in rack-ver.1.0_en
 
Mechanical Engineering Seminar 2017_3
Mechanical Engineering Seminar 2017_3Mechanical Engineering Seminar 2017_3
Mechanical Engineering Seminar 2017_3
 
TurboCryogenics Tech Brief
TurboCryogenics Tech BriefTurboCryogenics Tech Brief
TurboCryogenics Tech Brief
 
Utilization of Computer Room Cooling Infrastructure: Measurement Reveals Oppo...
Utilization of Computer Room Cooling Infrastructure: Measurement Reveals Oppo...Utilization of Computer Room Cooling Infrastructure: Measurement Reveals Oppo...
Utilization of Computer Room Cooling Infrastructure: Measurement Reveals Oppo...
 
Power Point Data Centre Uk Limited Apc
Power Point Data Centre Uk Limited ApcPower Point Data Centre Uk Limited Apc
Power Point Data Centre Uk Limited Apc
 

Último

Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfAddepto
 
The Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and ConsThe Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and ConsPixlogix Infotech
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii SoldatenkoFwdays
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyAlfredo García Lavilla
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr BaganFwdays
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupFlorian Wilhelm
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersRaghuram Pandurangan
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Mattias Andersson
 
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxLoriGlavin3
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Commit University
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubKalema Edgar
 
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptxThe Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptxLoriGlavin3
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024Stephanie Beckett
 
From Family Reminiscence to Scholarly Archive .
From Family Reminiscence to Scholarly Archive .From Family Reminiscence to Scholarly Archive .
From Family Reminiscence to Scholarly Archive .Alan Dix
 
Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebUiPathCommunity
 
DSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningDSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningLars Bell
 
SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024Lorenzo Miniero
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenHervé Boutemy
 
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxA Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxLoriGlavin3
 

Último (20)

Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdf
 
The Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and ConsThe Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and Cons
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easy
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project Setup
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information Developers
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?
 
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding Club
 
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptxThe Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024
 
From Family Reminiscence to Scholarly Archive .
From Family Reminiscence to Scholarly Archive .From Family Reminiscence to Scholarly Archive .
From Family Reminiscence to Scholarly Archive .
 
Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio Web
 
DSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningDSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine Tuning
 
SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache Maven
 
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxA Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
 

Optimal Data Centre Cooling with Cold-Aisle Containment

  • 1. COLD-AISLE CONTAINMENT IN DATA CENTRES the smart concept for optimal energy use www.knuerr.com Application Report Cold-Aisle Containment in Data Centres The smart concept for optimal energy use Cooling requirements in data centres are continually rising, causing conventional climate control systems to be overloaded. Switching to a water cooled systems is an option, but structurally and financially this is not always possible. Cold-Aisle Containment (CoolFlex) is another option. This option consistently separates cold and warm areas without requiring structurally changes to the data centre. Over several weeks the efficiency of CoolFlex was tested and proved. The test was conducted using fan heaters to simulate the heat load generated by servers. The result: At a thermal load of ca. 14kW per rack, the required temperature of 23°C in the cold aisle was reached. During further tests, several computer room air conditioning units (CRAC) were switched off to simulate an emergency. During these tests the cold aisle temperature of 23°C was only marginally exceeded. 1
  • 2. COLD-AISLE CONTAINMENT IN DATA CENTRES the smart concept for optimal energy use www.knuerr.com Description of application: Test conditions The raised floor provided greater energy efficiency by directing cool air through perforated plates in the cold aisle and by sealing the cable entry in to the racks. Knürr isolated the cold and hot zones within the server racks using infill panels. All 4 cold aisles were then enclosed using cold aisle containment. The 342 KW heat capacity was simulated via fan heaters (38 x 9kW = 342 kW). 288 kW heat capacity was simulated within aisle 2. Aisle 1, 3 and 4 were not in use and therefore produced no heat. The remaining 54 kW were distributed throughout the room, simulating the heat capacity in the network and free standing racks. To minimise the loss of circulation and pressure caused by the raised floor, Knürr used special “grate catch” instead of perforated raised floor plates. All holes for cables through the floor were sealed to prevent hot air shortcuts. The CRAC units used were designed to use 250 kW in their energy-efficient, normal mode and 500 kW at high power mode. The capacity of the fans is proportional to the third power of the circulatory. Therefore it is more energy-efficient to run all CRAC units at lower speed, instead of using less CRAC units at their maximal speed. By consistently isolating cold and warm air, the nominal capacity of the CRAC units is increased, therefore the same number of CRAC units can run at a high power mode, without reducing redundancy. 2
  • 3. COLD-AISLE CONTAINMENT IN DATA CENTRES the smart concept for optimal energy use www.knuerr.com Test areas Test 1: Energy-efficiency in normal mode 6 CRAC units in normal mode (speed ca. 30%) Pressure test with a rising thermal load Results during full load(ca. 288 kW in aisle + 54 kW) Temperature of cold aisle: 23,0 °C Temperature of warm aisle: 37,0 °C Test 2: Emergency (Breakdown of 2 CACUs) 3 CRAC units in emergency mode (speed ca. 80%) Results during full load(ca. 288 kW in aisle + 54 kW Temperature of cold aisle: 23,1 °C Temperature of warm aisle: 42,9 °C 3
  • 4. COLD-AISLE CONTAINMENT IN DATA CENTRES the smart concept for optimal energy use www.knuerr.com Test 3: Extreme emergency (Breakdown of 4 CACUs) 2 CRAC units in emergency mode (speed 100%) Results during full load(ca. 288 kW in aisle + 54 kW) Temperature of cold aisle: 23,5 °C Temperature of warm aisle: 47,0 °C With only 2 CRAC units the temperature in the cold aisle did not exceed the required 24°C. After a time the fan heaters simulating server heat load failed due to a fail safe switch. Results and Conclusions To discover the maximum capacity of cold aisle containment by increasing the heat capacity in the data centre. - Load per Rack 3.6kW (Face: 3.5 m² = ca. 1‘000 W/m²) = possible! - Load per Rack 7.6kW (Face: 3.5 m² = ca. 2‘000 W/m²) = possible! - Load per Rack 10.8kW (Face: 3.5 m² = ca. 3‘000 W/m²) = possible! - Load per Rack 14.4kW (Face: 3.5 m² = ca. 4‘000 W/m²) = possible! The cold aisle containment could possibly discharge a higher heat load however the fan heater fail safe thermostat caused at collapsed after 4'000W/m². Also the test equipment was not calibrated for higher heat load. Therefore we could not demonstrate the limits of the cold aisle containment. Note: It is important to note that during this pilot project, fan heaters were used to demonstrate the cooling capacity. Fan heaters can only simulate the heat generated by servers, as they have a lower flow volume across the server. We are positive, that in a real situation, 10 to 12 KW per rack should be possible (various other experts do not differentiate between the use of fan heater and real servers) 4
  • 5. COLD-AISLE CONTAINMENT IN DATA CENTRES the smart concept for optimal energy use www.knuerr.com Pictures of test site 5
  • 6. COLD-AISLE CONTAINMENT IN DATA CENTRES the smart concept for optimal energy use www.knuerr.com Services provided Using trained personnel, Knürr is able to provide the following services: Consulting, calculation, and simulation of a solution. Simple installation into existing racks (dependent of make of rack). Integration and installation without the need for down time. • Data Centres Thermal Assessment - Review of thermal demands and air flow within the data centre - Thermal imaging of the computer centre, several aisles and/or racks - Proposal of cost effective measures - Complete report, with achievable improvements • “Cold Aisle Containment” implementation of the solution - Site visit (inclusive demarcation of project specific items, especially competitor racks) - Creation of project plan - Detailed pricing offer Knürr AG Mariakirchener Straße 38 94424 Arnstorf Telefon +49 (0) 87 23-27-0 Telefax +49 (0) 87 23-27-154 E-Mail: info@knuerr.com www.knuerr.com 6