SlideShare una empresa de Scribd logo
1 de 42
Engineering Centre of Excellence
      ECoE - Doha, Qatar

Instrument training – 16th July 2011
 General Control valves.




                                 Prepared by: Gavhane D.V.
General Control valves.




              BY:-DNYANESHWAR GAVHANE



General Control Valves.           Prepared by: Gavhane D.V.   2
General Control valves.

     INTRODUCTION :-

      Control valves also called final control element are a most
      important element in the control system of a process plant.
       It is the last device in control loop.

     DEFINITION :-

      A control valve is a variable orifice used to regulate the flow
      of a process fluid in accordance with requirement of process.

     FUNCTION :-

      It absorbs the proper amount of pressure drop to maintain
      system balance under all operating conditions.



General Control Valves.                                Prepared by: Gavhane D.V.   3
Features of Control valves.
     THERE ARE FOUR FEATURES OF CONTROL VALVES :

       Capacity
       Rangeability
       Characteristics
       Pressure drop

       CAPACITY : The capacity is normally measured as Cv
       (Flow Coefficient) which is defined as :

       “The number of US gallons per minute of water at 60oF that
       will flow through a valves with 1psi pressure drop .

       RANGEABILITY : Rangeability of a Control Valve is the
       ratio of the maximum to the minimum controllable flow.



General Control Valves.                             Prepared by: Gavhane D.V.   4
Control valves and Flow Characteristics.
 The relationship between control valve capacity and valve stem
 travel is known as the Flow Characteristic of the control valve.




  The Curve shown are based on constant Pressure drop across
  the valve and called Inherent flow characteristics.

General Control Valves.                               Prepared by: Gavhane D.V.   5
Linear Characteristics.
    Flow Capacity increases linearly with valve (stem) travel. In
    which the valve differential pressure drop is Constant over the
    travel range.
    Linear valve plug shall for liquid level control and control
    application requiring constant gain.

    LINEAR VALVE TRAVEL IS DIRECTLY PROPORTIONAL TO
    THE VALVE STROKE

                                                   MORE THAN
     FOR SLOW                                      40%
     FLUID                                         OF SYTEM
     TRANSFER                                      PRESSURE
     PROCESS                                       DROP
                                                   ACROSS
                                                   VALVE



General Control Valves.                               Prepared by: Gavhane D.V.   6
Equal Percentage Characteristics.
  Flow Capacity increases exponentially with valve trim travel .Equal
  increment of valve travel produce equal percentage change in
  existing Cv.
  Equal Percentage valve plug shall be used where only small
  percentage of system drop is available in Control valve.

   EQUAL INCREMENT OF VALVE TRAVEL PRODUCE AN
   EQUAL PERCENT FLOW CHANGE

   FOR FAST FLIUD                                 HIGH
   TRANSFER                                       RANGEABILITY
   PROCESS




General Control Valves.                               Prepared by: Gavhane D.V.   7
Quick Opening Characteristics.
 Provides large changes in flow for very small changes in lift or in
 which a maximum Cv is achieved with minimal closure member travel.
 It has too high valve gain.

 LARGE INCREASE IN FLOW WITH A SMALL CHANGE IN VALVE
 STROKE

 Quick opening valve are usually specified for “ON-OFF” Service such
 as sequential operation in either batch or semi continuous process
 and in self actuated control valve .
 When maximum valve capacity must be obtain quickly.


 Cage- A part of a valve that surrounds the
 closure member & can provide Quick
 opening flow characterization.



General Control Valves.                             Prepared by: Gavhane D.V.
                                                                                8
Cavitation.
Cavitation is condition that occurs in liquid flow where the internal
pressure of liquid at set point falls below vapour pressure and vapour
bubbles form and at downstream rises above vapour pressure again.
As this pressure recovers so that bubbles collapse and cavitation take
place.
It is possible to predict where cavitation will occur by looking pressure
condition and valve recovery factor.( sigma Method )
Cavitation sounds like stone passing through the valve.
                                                    PRESSURE PROFILE ACROSS
      P                                             SINGLE SEATED CONTROL
                                                    VALVE

                                                         P

                                                                  Pv


                                              Bubble collapse
    Bubble form
                                         Vena Contracta
General Control Valves.                                      Prepared by: Gavhane D.V.   9
Effect of Cavitation.




      Erosion in rotary plug valve body induced by cavitation


General Control Valves.                              Prepared by: Gavhane D.V. 10
Flashing.
Flashing is condition that occurs with liquid flow where the Pressure fails
below it . There are then two phases flowing ( i.e. Liquid and vapour )
down stream.

Several damage can occur inside a valve due to erosion caused by the
impact of liquid droplet traveling at high speed.

         P1                                        PRESSURE PROFILE ACROSS
                                                   SINGLE SEATED CONTROL
                                                   VALVE



                                                            Pv

           Bubble form
                                                     P2     Bubble continue
                                                            down stream

                                       Vena Contracta
General Control Valves.                                 Prepared by: Gavhane D.V.   11
Effect of Flashing.




            Typical trim erosion damage due to flashing




General Control Valves.                          Prepared by: Gavhane D.V.   12
Velocity Profile across Single seated Valve.
        P1                                           PRESSURE PROFILE ACROSS
                                                     SINGLE SEATED CONTROL
                                                     VALVE



                                                          Pv
                                                    P2

                                                     V2
   V 1(Liquid)                                       (Liquid)

Pressure Recovery:- At vena contracta,the velocity is greatest & substantially
decrease in pressure .Further down stream, as the fluid stream expands into
a large area, Velocity decreases and pressure increases. This phenomena is
called Pressure recovery.
As a general ,globe valves have Lower pressure recovery than Ball and
Butterfly Valves.


  General Control Valves.                                Prepared by: Gavhane D.V.   13
Piping Influence/Reynolds Number/Choked Flow.

Piping Influenence:- Capacity reduction due to the presence of Reducer Up &
Down stream of the valve. Correction factor will be available from
manufacturer .
Reynolds Number :- For Reynolds number application such as viscous or
small flow , the basic sizing equation can not be used without
correction, since the equation is based on turbulence flow . Correction factor
will be available from manufacturer .(The ratio of dynamic forces to viscous
forces)
Usually the correction can be ignored when Reynolds number is greater than
4000,the correction will be 10% or less .
Choked Flow:- When the pressure at vena contracta drop below the vapor
pressure of the liquids, bubbles will form in the stream .The formation of
bubbles causes a crowding condition at vena contracta which tends to restrict
flow, and further increase in pressure drop will not produce increase in flow.
 In case of gas , choked flow means outlet velocity reaches sonic velocity.
The limiting Pressure difference ΔPt is called Maximum allowable differential
pressure for sizing.

  General Control Valves.                                Prepared by: Gavhane D.V.   14
Contents of Control Valve:– Data Sheet
     PROJECT:-                                                        GPS DOC NO:-                          -



                                                                   SUB CONTRACTOR
CONTRACT NO:-
                                                                   DOC NO:-
                                                                                                                              SHEET NO:-          1 OF 1

     DOCUMENT                       SPECIFICATION AND DATASHEETS                                                                   DATE:-
                                                                    CLIENT DOC NO:-
     NAME:-                         FOR CONTROL VALVES                                                                         REV NO:-

                                                            DATASHEET - CONTROL VALVES
1                          TAG
      GENERAL
       DATA




2                          SERVICE                                 BLANKET FUEL GAS FROM OIL STORAGE TANK 0-T-3603
3                          LINE NO. / PID NO.                      0-14"-FG-43 0017-AA3-H(E) / S2-01-YS207019-PID-P-5004 Sht 1 of 2
4                          FLUID                                   TANK VENT/FUEL GAS                           CRITICAL PRESS. Pc
5                                                                      UNIT        MAX FLOW      NORM FLOW        MIN FLOW           SHUT-OFF
6                          FLOW RATE                                   m3/h           5166            1847           525.3                  -
7                          INLET PRESSURE                             psi(g)         0.0568          0.093           0.0975          15 bar(g)
8                          OUTLET PRESSURE                            psi(g)          0.037          0.0087         0.00234
       SERVICE CONDITION




9                          INLET TEMPERATURE                         Degree C          50              50              50           100(Note 1)
                                                                     - /kg/m3 /
10                         SPEC WT/DENSITY/ MOL WT                                /-/1.378/40.30 /-/1.378 /40.30 /-/ 1.381/40.30            -
                                                                     kg/kmole
11                         VISCOSITY /SPEC HEAT RATIO                  Cp /       0.00924/1.133 0.00924/1.133 0.00924/1.133                 -
12                         VAPOR PRESSURE                             inH2O            NA              NA              NA                   -
13                         REQUIRED CV                                                                                                      -
14                         TRAVEL                                       %                                                                   0
15                         ALLOWABLE /PREDICTED SPL                    dBA            < 85/           < 85/           < 85/                 -
16                         SET POINT                                 inH2O(g)         2.75            2.75            2.75



General Control Valves.                                                                                                       Prepared by: Gavhane D.V.    15
Contents of Control Valve:– Data Sheet.
                                                                                                                                 SINGLE-ACTING FAIL SAFE
17                  PIPE LINE SIZE &         IN         14" & SCH20         56                           TYPE                    SPRING RETURN –DIAPHRAGM
                                                                                                                                 TYPE
     LINE


                    SCHEDULE
18                                           OUT        14" & SCH20         57                           MFR & MODEL                                VTS
                                                    HEAT CONSERVATION
19                  PIPE LINE INSULATION                                    58                           SIZE / EFF.AREA                            VTS
                                                   (ELECTRICAL TRACING)
20                  VALVE SIZING                         ISA S75.01         59                           ON/OFF                               MODULATING             YES
     SPEC.& CODES




                                                                                  ACTUATOR (PNEUMATIC)
                    VALVE SEAT LEAKAGE
21                                                   IV AS PER FCI 70-2     60                           SPRING ACTION ON FAIL                    CLOSE
                    CLASS
                                                                                                         MAX ALLOWABLE
22                                                                          61                                                                      VTS
                                                                                                         PRESS.
23                                                                          62                           MIN REQUIRED PRESS.                        VTS
24                                                                          63                           AVAILABLE AIR SUPPLY     MIN     NOR            MAX DESIGN
25                  TYPE                                BUTTERFLY           64                           PRESSURE        kPag     400         850        900      1000
26                  SIZE                                    VTS             65                           BENCH RANGE                                VTS
                                                                                                         ACTUATOR
27                  MAX PRESS./TEMP.                        VTS             66                                                                      VTS
                                                                                                         ORIENTATION
28                  BODY/BONNET MATERIAL             A105 or A216 WCB       67                           HANDWHEEL     TYPE             YES                     VTS
                                                                                                         AIR FAILURE LOCK
29                  LINER MATERIAL / ID                                     68                                                   REQD. SET AT                  Note 5
                                                                                                         RELAY
30                                                                          69                           AIR BOTTLE               REQD. WITH ACCESSORIES
     VALVE BODY




31                  END CONNECTION     IN/ OUT           FLANGED            70                           FIRE SAFE                                  YES
32                  RATING & FLANGE FACE FINI.      150# RF ASME B16.5      71                           INPUT SIGNAL                             4-20 mA
33                  END EXTENSION/MATERIAL         ASTM A105 carbon steel   72                           TYPE                    ELECTRO-PNEUMATIC (HART)
                                                                                  POSITIONER             EXPLOSION
34                  FLOW DIRECTION                          YES             73                                                                     EExd
                                                                                                         PROTECTION
                                                                                                         ON INCR SIGNAL
35                  TYPE OF BONNET                        BOLTED            74                                                          FIELD REVERSIBLE
                                                                                                         OUTPUT INCR/DECR
36                  LUB & ISO VALVE / LUBE                                  75                           GAUGES         Yes        BYPASS                      Yes
37                  PACKING MATERIAL                       PTFE             76                           CAM CHARACTERISTIC
38                  PACKING TYPE                            VTS             77                           MFR & MODEL                                VTS
                                                                                 SWITC




39                                                          VTS             78                           TYPE                                 -                QTY       -
                                                                                  HES




                    BONNET GASKET
40                  MFR & MODEL                             VTS             79                           MFR & MODEL                                 -


General Control Valves.                                                                                                            Prepared by: Gavhane D.V.                 16
Contents of Control Valve:– Data Sheet .
 41                 TYPE                                        VTS                80                CONTACTS/RATING                     -

 42                 SIZE       RATED TRAVEL              VTS               VTS     81                ACTUATION POINTS                    -

 43                 CHARACTERISTIC                              VTS                82

 44                 BALANCED/UNBALANCED                         VTS                83                MATERIAL                  DIE CAST ALUMINIUM

                    RATED                       CV VTS     FL   VTS   XT     VTS   84                FILTER SIZE                  < or = 25 Micron
         TRIM




 45




                                                                                        AIR FILTER
 46                 PLUG/BALL/DISC MATERIAL                     F6                 85                SET PRESSURE
                                                      F6 SEAT HARD FACED WITH                        INTEGRAL PRESS.
                    SEAT MATERIAL                                                  86                                               50mm DIAL
 47                                                          STELLITE6.                              GAUGE

 48                 CAGE/GUIDE MATERIAL                         VTS                87                CONNECTION                      1/2"NPT

 49                 STEM MATERIAL                               F6                 88                MFR & MODEL                       VTS

 50                                                                                89

 51                 NEC CLASS GR. DIV.                                             90                HYDRO PRESS.                      YES
      ACCESSORIES
       SPECIALS /




 52                 IEC ZONE GR. TEMP. CLASS CLASS I, ZONE 2 , GROUP IIA & T3 91                     SEAT LEAKAGE TEST                 YES




                                                                                        TESTS
 53                                                                                92                CAPACITY TEST                     YES

 54                                                                                93

 55                                                                                94

 NOTES :                      VTS-Vendor To Specify




General Control Valves.                                                                                                  Prepared by: Gavhane D.V.   17
Globe Control Valve Construction. .




General Control Valves.               Prepared by: Gavhane D.V.   18
General Control Valve Classification.

                      CONTROL VALVE




      LINEAR                                  ROTARY
      MOTION                                  MOTION


                                      Eccentric plug
Diaphragm valve   GLOBE VALVE            Butterfly
   Gate valve         Globe                Ball
                      Angle
                    Three way




General Control Valves.                 Prepared by: Gavhane D.V.   19
General Types of Control Valve.
                                  CONTROL VALVE TYPES

              VALVE TYPES BASED ON PLUG CONSTRUCTION ARE

     GLOBE VALVE                         BALL VALVE                BUTTERFLY VALVE

Control:- Linear & equal %        Control:- Quick opening         Control:- Linear & equal %
Use:- Throttling Service,         And linear.                     Uses:- Fully open / closed or
Flow Regulation, Frequent         Uses:- Fully open / closed      Throttling services, Frequent
Operation                         limited-throttling              Operation, Minimal fluid
Application:- Liquid, Vapour,     Application:- Most liquids      Trapping in line.
Gases, Corrosive Substances       High temperature, slurries      Application:-Liquids, gases,
Slurries.                         Advantage:- High capacity       Slurries, Liquids with
Advantage: Efficient throttling   Low leakage and Maint.          suspended Solids.
Available in multiple ports.      Tight sealing with low torque   Advantage :- High Capacity
Accurate Flow control.            Disadvantage:- poor             Good flow control, Low Press.
Disadvantage: High pressure       Throttling characteristics      Drop, Low cost and Maint.
Drop, more expensive.             Prone to Cavitation             Disadvantage:- High torque
                                                                  Required for control
                                                                  Prone to cavitation at lower
ECENTRIC PLUG / CAMFLEX            DIAPHRAGM KNIFE GATE
                                                                  Flows.

 General Control Valves.                                              Prepared by: Gavhane D.V.   20
Eccentric Plug / Camflex Valve Construction.




 Side view of an eccentric plug valve
     Shown in partially open…..




 General Control Valves.                Prepared by: Gavhane D.V.   21
Eccentric Disk/Ball/Knife Valve Construction
  Eccentric Disk Valve   V-Notch Ball Valve   Knife Gate Valve




 General Control Valves.                       Prepared by: Gavhane D.V.   22
Butterfly/Angle/Three Way Valve Construction




 General Control Valves.             Prepared by: Gavhane D.V.   23
Diaphrgm Type Valve Construction.




                          Seal over a seat ( Straight type)




                              Weir type ( Saddle type)

General Control Valves.               Prepared by: Gavhane D.V.   24
General Types of Actuators .
    Actuator is the part of the valve that responds to the applied signal and
    causes modification of the fluid flow through stem & plug.
TYPES OF ACTUATORS:
1) Diaphragm Actuator
    Direct Acting
    Reverse Acting
    Size depends on output thrust required and supply air pressure
    available.
2) Piston Actuator
    Use of high pressure air to 150 psig., eliminating the need of pressure
    regulator.
    Used where High & Fast Stroking Speed is required.
3) Electro hydraulic Actuator:
    Electro-hydraulic Actuator is single unit contains Hydraulic Pump
    and Reservoir & Electric Motor.
    Ideal for isolated locations
4) Manual Actuator
    Used where no auto control is required
General Control Valves.                                  Prepared by: Gavhane D.V.   25
Direct – Acting Actuators .




General Control Valves.       Prepared by: Gavhane D.V.   26
Actuators Fail-Safe Requirements.
Fail Safe is the action of the actuator by which the valve CLOSES (FC)
or OPENS (FO) fully in case of air supply failure.




General Control Valves.                               Prepared by: Gavhane D.V.   27
General Types of Bonnet & Accessories .
Bonnet -
   Bonnet is a part of the valve body assembly through which the valve
   plug stem or rotary shaft moves.
Types Of Bonnets
   Plain or Std Bonnet :-Operating Temp below 2000 c.
   Finned Bonnet :- Operating Temp above 2000 c or Equal.
   Extension Bonnet :- Operating Temp below 00 c or Equal.
   Extension Bonnet :- Operating Temp above 4500 c.
   Bellow Seal Bonnet :- where no stem leakage is tolerated For Toxic,
   Expensive Fluids.

General Control Valve - Accessories
   •Positioners
   •Limit Switches
   •Solenoid Valves
   •Position Transmitters
   •Volume Boosters

General Control Valves.                              Prepared by: Gavhane D.V.   28
General Construction of Bonnet .
 Forged –Valve         Finned   Extension      Bellow Seal
    Bonnet             Bonnet    Bonnet     Bonnet ( Enviro Seal)




                 Std./ plain
                  Bonnet

General Control Valves.                       Prepared by: Gavhane D.V.   29
Control valves Characteristics.
 PROCESS       APPLICATION         INHERANT
                                   CHARACTERISTICS
 PRESSURE      LIQUIDS             EQUAL %
               GAS (LOW FLOWS )    EQUAL %
               GAS (LARGE FLOWS)
               ΔPmax/Δpmin < 5     LINEAR
               ΔPmax/Δpmin > 5     EQUAL %
 Temperature   Liquids & Gases     EQUAL %

 Flow          Load Changes        EQUAL %
               Set point change    LINEAR


 Level         ΔPmax/Δpmin < 5     LINEAR
               ΔPmax/Δpmin > 5     EQUAL %




General Control Valves.                Prepared by: Gavhane D.V.   30
Control valves :- Interface

 PROCESS INTERFACE
    Process to provide process data to Instrument for specifying the
    valve
    Instrument to provide slected valve size to Process for
    incorporating in P&IDs
    Instrument to provide instrument air consumption figures for the
    valves to Process to decide air line & header sizes.
 PIPING INTERFACE
    Instrument to provide Face to Face Dimensions, End Connection
    Size & Rating, Actuator Height & Orientation, Envelope
    Dimensions (for 3-D Model), Weight, etc.
    Piping to provide location of control valves to Instrument for
    deciding instrument air manifolds.
    Piping to provide Pipe Material Specification to Instrument for
    specifying the valves.


General Control Valves.                              Prepared by: Gavhane D.V.   31
Control valves Body Material.
Frequently Used Valve Body Cast Materials Are:
   CARBON STEEL (ASTM A216 GR WCC) up to 4270 C
   CHROME MOLY STEEL (ASTM A217 GR WC9) up to 5930 C
   CARBON MOLY STEEL (ASTM A217 GR C5) up to 5930 C
   304L STAINLESS STEEL (ASTM A351 GR CF3) up to 8160 C
   316 STAINLESS STEEL (ASTM A351 GR CF8M) up to 8160 C
   CAST IRON (ASTM A126) up to 2320 C

Special Materials Used Depending On The Process Requirements
   HASTEALLOY B
   HASTEALLOY C
   MONEL ALLOY




General Control Valves.                          Prepared by: Gavhane D.V.   32
Control valves Trim Material.

Frequently Used Valve Trim Materials Are:
• 302 SS       : ASTM A 276 TYPE 302
• 304 SS       : ASTM A 276 TYPE 304
• 316 SS       : ASTM A 276 TYPE 316
• 316 L SS : ASTM A 276 TYPE 316L
• 410 SS       : ASTM A 276 TYPE 410
• 17-4 pH SS : ASTM A 461 GR 630
  [High Tensile Strength, High Yield point, Hardened Material]
• HASTEALLOY ``B’’ : ASTM A 335
• HASTEALLOY ``C’’ : ASTM A 336




General Control Valves.                                Prepared by: Gavhane D.V.   33
Control valves Codes and Standards.
ANSI B 16.34 :
• Covers Pressure, Temperature rating, Dimensions, Materials, NDT
  Requirements
ANSI B 16.5 :
• Covers design of flanges and flanged fittings
MSS SP 67 :
• Covers design and test performance requirements of Butterfly valves and
  divides in to three leak classes.
ANSI B 16.10:
• Face to Face dimensions
ANSI B 16.37:
 Hydrostatic testing
LEAKAGE RATES AS PER ANSI/FCI 70-2
 Formerly (ANSI B 16.104) for seat leak classes and testing procedures
- FCI

General Control Valves.                               Prepared by: Gavhane D.V.   34
Vendor Design Documents- Sizing & Selection
Step # 1:- Define the system
Example :- The system is pumping water from one tank to another through a
piping system total pressure drop is 150psi.The fluid is water at 700F.Design
(maximum) flow of 150 gpm,operating flow rate of 110 gpm,and minimum flow rate
of 25gpm. Pipe diameter is 3 inches. At 700F, water has has a specific gravity of1.0
Key Variables:- Total pressure drop , design flow ,operating flow, minimum flow
                diameter, specific gravity.

Step # 2:- Define Max. Allowable Pressure Drop For The Valve
    When defining the allowable pressure drop across the valve, you should first
investigate the pump.What is its maximum available head? Remember that the
system pressure drop is limited by the pump. Essentially the Net Positive Suction
Head Available (NPSHA) minus the Net Positive Suction Head Required (NPSHR)
is the maximum available pressure drop for the valve to use and this must not be
exceeded or another pump will be needed. The usual rule of thumb is that a valve
should be designed to use 10-15% of the total pressure drop or 10 psi, whichever
is greater.
 For above example step#1 system, 10% of the total pressure drop is 15 psi which
is what we'll use as our allowable pressure drop when the valve is wide open (the
pump is our system is easily capable of the additional pressure drop).


 General Control Valves.                                      Prepared by: Gavhane D.V.   35
STEP #3: Calculate the valve characteristic




 General Control Valves.                      Prepared by: Gavhane D.V.   36
Step#4:-Preliminary Valve Selection

The Cv value should be used as a guide in the valve selection, not a hard
and fast rule. Some other considerations are:
  a. Never use a valve that is less than half the pipe size
  b. Avoid using the lower 10% and upper 20% of the valve stroke. The
      valve is much easier to control in the 10-80% stroke range.

Before a valve can be selected, we have to decide what type of valve will
be used . For our case, we'll assume we're using an equal percentage,
globe valve . The valve chart for this type of valve is shown below. This
is a typical chart that will be supplied by the manufacturer.

For our case, it appears the 2 inch valve will work well for our Cv value at
about 80-85% of the stroke range. Notice that we're not trying to squeeze
our Cv into the 1 1/2 valve which would need to be at 100% stroke to
handle our maximum flow.


General Control Valves.                                  Prepared by: Gavhane D.V.   37
Typical Chart Supplied by Manufacturer.




General Control Valves.                   Prepared by: Gavhane D.V.   38
Step# 5:-Check Cv & Stroke % at Min. Flow

If the stroke percentage falls below 10% at our minimum flow, a smaller
valve may have to be used in some cases.
Judgments plays role in many cases. For example, is your system more
likely to operate closer to the maximum flowrates more often than the
minimum flowrates?
 Or is it more likely to operate near the minimum flow rate for extended
periods of time. It's difficult to find the perfect valve, but you should find
one that operates well most of the time. Let's check the valve we've
selected for our system:




General Control Valves.                                    Prepared by: Gavhane D.V.   39
Step#6:Check Gain across Applicable Flow Rates
• Gain is defined as:

•

•   Now, at our three flowrates:
    Qmin = 25 gpm
    Qop = 110 gpm
    Qdes = 150 gpm
    we have corresponding Cv values of 6.5, 28, and 39. The corresponding
    stroke percentages are 35%, 73%, and 85% respectively. Now we construct
    the following table:
    Flow (gpm)     Stroke (%)      Change in (gpm)   Change in Stroke (%)
          25             35            110-25=85               73-35=38
         110             73
         150             85            150-110=40              85-73=12


    Gain #1 = 85/38 = 2.2
    Gain #2 = 40/12 = 3.3

General Control Valves.                                        Prepared by: Gavhane D.V.   40
General Control valve Gain.
The difference between these values should be less than 50% of the
higher value.
0.5 (3.3) = 1.65
and 3.3 - 1.65 = 1.65. Since 2.2 is closer than 50%, there should be
problem with controlling the valve. Also note that the gain should never
be less than 0.50.
Turndown :- It is ratio of the calculated Cv at maximum condition to the
calculated Cv minimum.
Rangeability :- It is ratio of Cv of the valve fully open to the minimum Cv
at which it can control.
The rangebility of the selected valve must exceed the turndown
requirements of the application.




General Control Valves.                                  Prepared by: Gavhane D.V.   41
General Control valves.




    Any Question ?




General Control Valves.   Prepared by: Gavhane D.V.   42

Más contenido relacionado

La actualidad más candente

Basic Control Valve Sizing and Selection
Basic Control Valve Sizing and SelectionBasic Control Valve Sizing and Selection
Basic Control Valve Sizing and SelectionISA Boston Section
 
Different types of control valves
Different types of control valvesDifferent types of control valves
Different types of control valvesPrem Baboo
 
Control Valve Types
Control Valve TypesControl Valve Types
Control Valve TypesBrannon Gant
 
Valves
ValvesValves
ValvesSABIC
 
Control valve Working and Types with Parts. Terms use in Control Valve
Control valve Working and Types with Parts. Terms use in Control ValveControl valve Working and Types with Parts. Terms use in Control Valve
Control valve Working and Types with Parts. Terms use in Control ValveInstrumentation Knowledge
 
Design and analysis of control valve with a multi stage anti cavitation trim
Design and analysis of control valve with a multi stage anti cavitation trimDesign and analysis of control valve with a multi stage anti cavitation trim
Design and analysis of control valve with a multi stage anti cavitation trimnaz4u
 
CONTROL VALVE questions.pdf
CONTROL VALVE questions.pdfCONTROL VALVE questions.pdf
CONTROL VALVE questions.pdfAmiTG34
 
Mechanical Valve
Mechanical ValveMechanical Valve
Mechanical ValveNathan
 
Valve Selection & Sizing
Valve Selection & SizingValve Selection & Sizing
Valve Selection & SizingRanjeet Kumar
 
VALVES AND THEIR TYPES
VALVES AND THEIR TYPESVALVES AND THEIR TYPES
VALVES AND THEIR TYPESMadhur Mahajan
 
Valves_Control valve_Actuators.ppt
Valves_Control valve_Actuators.pptValves_Control valve_Actuators.ppt
Valves_Control valve_Actuators.pptKAhmedRehman
 
Pressure Relief valve sizing and design
Pressure Relief valve sizing and designPressure Relief valve sizing and design
Pressure Relief valve sizing and designHéctor Nguema Ondo
 

La actualidad más candente (20)

Basic Control Valve Sizing and Selection
Basic Control Valve Sizing and SelectionBasic Control Valve Sizing and Selection
Basic Control Valve Sizing and Selection
 
Valves
Valves Valves
Valves
 
Industrial valves
Industrial valvesIndustrial valves
Industrial valves
 
Different types of control valves
Different types of control valvesDifferent types of control valves
Different types of control valves
 
Control valves
Control valves Control valves
Control valves
 
Valves
ValvesValves
Valves
 
Control Valve Types
Control Valve TypesControl Valve Types
Control Valve Types
 
Valves
ValvesValves
Valves
 
Control valve ppt
Control valve pptControl valve ppt
Control valve ppt
 
Control valves
Control valvesControl valves
Control valves
 
Control valves
Control  valvesControl  valves
Control valves
 
Control valve Working and Types with Parts. Terms use in Control Valve
Control valve Working and Types with Parts. Terms use in Control ValveControl valve Working and Types with Parts. Terms use in Control Valve
Control valve Working and Types with Parts. Terms use in Control Valve
 
Design and analysis of control valve with a multi stage anti cavitation trim
Design and analysis of control valve with a multi stage anti cavitation trimDesign and analysis of control valve with a multi stage anti cavitation trim
Design and analysis of control valve with a multi stage anti cavitation trim
 
Selection of Valves
Selection of ValvesSelection of Valves
Selection of Valves
 
CONTROL VALVE questions.pdf
CONTROL VALVE questions.pdfCONTROL VALVE questions.pdf
CONTROL VALVE questions.pdf
 
Mechanical Valve
Mechanical ValveMechanical Valve
Mechanical Valve
 
Valve Selection & Sizing
Valve Selection & SizingValve Selection & Sizing
Valve Selection & Sizing
 
VALVES AND THEIR TYPES
VALVES AND THEIR TYPESVALVES AND THEIR TYPES
VALVES AND THEIR TYPES
 
Valves_Control valve_Actuators.ppt
Valves_Control valve_Actuators.pptValves_Control valve_Actuators.ppt
Valves_Control valve_Actuators.ppt
 
Pressure Relief valve sizing and design
Pressure Relief valve sizing and designPressure Relief valve sizing and design
Pressure Relief valve sizing and design
 

Similar a 01 General Control Valves Training.

Basic Fluid Dynamics - Control Valves
Basic Fluid Dynamics - Control Valves  Basic Fluid Dynamics - Control Valves
Basic Fluid Dynamics - Control Valves Brannon Gant
 
Valve sizing reference
Valve sizing referenceValve sizing reference
Valve sizing referencemanjunath8685
 
Flow control valves
Flow control valvesFlow control valves
Flow control valvesPranit Mehta
 
Problems faced in conrol valves ppt
Problems faced in conrol valves pptProblems faced in conrol valves ppt
Problems faced in conrol valves pptPrem Baboo
 
Pressure control valves
Pressure control valvesPressure control valves
Pressure control valvesShrenik Baid
 
Cavitation Reduction in Industrial Process Control Valves
Cavitation Reduction in Industrial Process Control ValvesCavitation Reduction in Industrial Process Control Valves
Cavitation Reduction in Industrial Process Control ValvesCTi Controltech
 
Cavitation Control in Process Control Valves
Cavitation Control in Process Control ValvesCavitation Control in Process Control Valves
Cavitation Control in Process Control ValvesAnalynk Wireless, LLC
 
Controlling Cavitation in Industrial Control Valves
Controlling Cavitation in Industrial Control ValvesControlling Cavitation in Industrial Control Valves
Controlling Cavitation in Industrial Control ValvesCTi Controltech
 
Process control valve engineering
Process control valve engineeringProcess control valve engineering
Process control valve engineeringislam deif
 
Difference Types of Control Valves Presentation.pdf
Difference Types of Control Valves Presentation.pdfDifference Types of Control Valves Presentation.pdf
Difference Types of Control Valves Presentation.pdfSouraj Ranjan Patel
 
McCrometer V Cone Flowmeter Installation, Operations, Maintenace
McCrometer V Cone Flowmeter Installation, Operations, MaintenaceMcCrometer V Cone Flowmeter Installation, Operations, Maintenace
McCrometer V Cone Flowmeter Installation, Operations, MaintenaceFlow-Tech, Inc.
 
Oil field equipment the part two (2)pptx
Oil field equipment the part two (2)pptxOil field equipment the part two (2)pptx
Oil field equipment the part two (2)pptxssuser355c2a
 
Control valves for thermal power plants
Control valves for thermal power plantsControl valves for thermal power plants
Control valves for thermal power plantsSHIVAJI CHOUDHURY
 

Similar a 01 General Control Valves Training. (20)

General Control Valve Study
General Control Valve StudyGeneral Control Valve Study
General Control Valve Study
 
Control Valves Book.pdf
Control Valves Book.pdfControl Valves Book.pdf
Control Valves Book.pdf
 
Basic Fluid Dynamics - Control Valves
Basic Fluid Dynamics - Control Valves  Basic Fluid Dynamics - Control Valves
Basic Fluid Dynamics - Control Valves
 
Valve sizing reference
Valve sizing referenceValve sizing reference
Valve sizing reference
 
Control valve-sizing
Control valve-sizingControl valve-sizing
Control valve-sizing
 
Flow control valves
Flow control valvesFlow control valves
Flow control valves
 
Problems faced in conrol valves ppt
Problems faced in conrol valves pptProblems faced in conrol valves ppt
Problems faced in conrol valves ppt
 
servo-valves
 servo-valves servo-valves
servo-valves
 
Pressure control valves
Pressure control valvesPressure control valves
Pressure control valves
 
Cavitation Reduction in Industrial Process Control Valves
Cavitation Reduction in Industrial Process Control ValvesCavitation Reduction in Industrial Process Control Valves
Cavitation Reduction in Industrial Process Control Valves
 
Cavitation Control in Process Control Valves
Cavitation Control in Process Control ValvesCavitation Control in Process Control Valves
Cavitation Control in Process Control Valves
 
Controlling Cavitation in Industrial Control Valves
Controlling Cavitation in Industrial Control ValvesControlling Cavitation in Industrial Control Valves
Controlling Cavitation in Industrial Control Valves
 
Cavitation Control in Industrial Valves
Cavitation Control in Industrial ValvesCavitation Control in Industrial Valves
Cavitation Control in Industrial Valves
 
Process control valve engineering
Process control valve engineeringProcess control valve engineering
Process control valve engineering
 
Nova ovv
Nova ovvNova ovv
Nova ovv
 
Difference Types of Control Valves Presentation.pdf
Difference Types of Control Valves Presentation.pdfDifference Types of Control Valves Presentation.pdf
Difference Types of Control Valves Presentation.pdf
 
McCrometer V Cone Flowmeter Installation, Operations, Maintenace
McCrometer V Cone Flowmeter Installation, Operations, MaintenaceMcCrometer V Cone Flowmeter Installation, Operations, Maintenace
McCrometer V Cone Flowmeter Installation, Operations, Maintenace
 
Oil field equipment the part two (2)pptx
Oil field equipment the part two (2)pptxOil field equipment the part two (2)pptx
Oil field equipment the part two (2)pptx
 
1.1 Introduction to Art.lift.ppt
1.1  Introduction  to Art.lift.ppt1.1  Introduction  to Art.lift.ppt
1.1 Introduction to Art.lift.ppt
 
Control valves for thermal power plants
Control valves for thermal power plantsControl valves for thermal power plants
Control valves for thermal power plants
 

01 General Control Valves Training.

  • 1. Engineering Centre of Excellence ECoE - Doha, Qatar Instrument training – 16th July 2011 General Control valves. Prepared by: Gavhane D.V.
  • 2. General Control valves. BY:-DNYANESHWAR GAVHANE General Control Valves. Prepared by: Gavhane D.V. 2
  • 3. General Control valves. INTRODUCTION :- Control valves also called final control element are a most important element in the control system of a process plant. It is the last device in control loop. DEFINITION :- A control valve is a variable orifice used to regulate the flow of a process fluid in accordance with requirement of process. FUNCTION :- It absorbs the proper amount of pressure drop to maintain system balance under all operating conditions. General Control Valves. Prepared by: Gavhane D.V. 3
  • 4. Features of Control valves. THERE ARE FOUR FEATURES OF CONTROL VALVES : Capacity Rangeability Characteristics Pressure drop CAPACITY : The capacity is normally measured as Cv (Flow Coefficient) which is defined as : “The number of US gallons per minute of water at 60oF that will flow through a valves with 1psi pressure drop . RANGEABILITY : Rangeability of a Control Valve is the ratio of the maximum to the minimum controllable flow. General Control Valves. Prepared by: Gavhane D.V. 4
  • 5. Control valves and Flow Characteristics. The relationship between control valve capacity and valve stem travel is known as the Flow Characteristic of the control valve. The Curve shown are based on constant Pressure drop across the valve and called Inherent flow characteristics. General Control Valves. Prepared by: Gavhane D.V. 5
  • 6. Linear Characteristics. Flow Capacity increases linearly with valve (stem) travel. In which the valve differential pressure drop is Constant over the travel range. Linear valve plug shall for liquid level control and control application requiring constant gain. LINEAR VALVE TRAVEL IS DIRECTLY PROPORTIONAL TO THE VALVE STROKE MORE THAN FOR SLOW 40% FLUID OF SYTEM TRANSFER PRESSURE PROCESS DROP ACROSS VALVE General Control Valves. Prepared by: Gavhane D.V. 6
  • 7. Equal Percentage Characteristics. Flow Capacity increases exponentially with valve trim travel .Equal increment of valve travel produce equal percentage change in existing Cv. Equal Percentage valve plug shall be used where only small percentage of system drop is available in Control valve. EQUAL INCREMENT OF VALVE TRAVEL PRODUCE AN EQUAL PERCENT FLOW CHANGE FOR FAST FLIUD HIGH TRANSFER RANGEABILITY PROCESS General Control Valves. Prepared by: Gavhane D.V. 7
  • 8. Quick Opening Characteristics. Provides large changes in flow for very small changes in lift or in which a maximum Cv is achieved with minimal closure member travel. It has too high valve gain. LARGE INCREASE IN FLOW WITH A SMALL CHANGE IN VALVE STROKE Quick opening valve are usually specified for “ON-OFF” Service such as sequential operation in either batch or semi continuous process and in self actuated control valve . When maximum valve capacity must be obtain quickly. Cage- A part of a valve that surrounds the closure member & can provide Quick opening flow characterization. General Control Valves. Prepared by: Gavhane D.V. 8
  • 9. Cavitation. Cavitation is condition that occurs in liquid flow where the internal pressure of liquid at set point falls below vapour pressure and vapour bubbles form and at downstream rises above vapour pressure again. As this pressure recovers so that bubbles collapse and cavitation take place. It is possible to predict where cavitation will occur by looking pressure condition and valve recovery factor.( sigma Method ) Cavitation sounds like stone passing through the valve. PRESSURE PROFILE ACROSS P SINGLE SEATED CONTROL VALVE P Pv Bubble collapse Bubble form Vena Contracta General Control Valves. Prepared by: Gavhane D.V. 9
  • 10. Effect of Cavitation. Erosion in rotary plug valve body induced by cavitation General Control Valves. Prepared by: Gavhane D.V. 10
  • 11. Flashing. Flashing is condition that occurs with liquid flow where the Pressure fails below it . There are then two phases flowing ( i.e. Liquid and vapour ) down stream. Several damage can occur inside a valve due to erosion caused by the impact of liquid droplet traveling at high speed. P1 PRESSURE PROFILE ACROSS SINGLE SEATED CONTROL VALVE Pv Bubble form P2 Bubble continue down stream Vena Contracta General Control Valves. Prepared by: Gavhane D.V. 11
  • 12. Effect of Flashing. Typical trim erosion damage due to flashing General Control Valves. Prepared by: Gavhane D.V. 12
  • 13. Velocity Profile across Single seated Valve. P1 PRESSURE PROFILE ACROSS SINGLE SEATED CONTROL VALVE Pv P2 V2 V 1(Liquid) (Liquid) Pressure Recovery:- At vena contracta,the velocity is greatest & substantially decrease in pressure .Further down stream, as the fluid stream expands into a large area, Velocity decreases and pressure increases. This phenomena is called Pressure recovery. As a general ,globe valves have Lower pressure recovery than Ball and Butterfly Valves. General Control Valves. Prepared by: Gavhane D.V. 13
  • 14. Piping Influence/Reynolds Number/Choked Flow. Piping Influenence:- Capacity reduction due to the presence of Reducer Up & Down stream of the valve. Correction factor will be available from manufacturer . Reynolds Number :- For Reynolds number application such as viscous or small flow , the basic sizing equation can not be used without correction, since the equation is based on turbulence flow . Correction factor will be available from manufacturer .(The ratio of dynamic forces to viscous forces) Usually the correction can be ignored when Reynolds number is greater than 4000,the correction will be 10% or less . Choked Flow:- When the pressure at vena contracta drop below the vapor pressure of the liquids, bubbles will form in the stream .The formation of bubbles causes a crowding condition at vena contracta which tends to restrict flow, and further increase in pressure drop will not produce increase in flow. In case of gas , choked flow means outlet velocity reaches sonic velocity. The limiting Pressure difference ΔPt is called Maximum allowable differential pressure for sizing. General Control Valves. Prepared by: Gavhane D.V. 14
  • 15. Contents of Control Valve:– Data Sheet PROJECT:- GPS DOC NO:- - SUB CONTRACTOR CONTRACT NO:- DOC NO:- SHEET NO:- 1 OF 1 DOCUMENT SPECIFICATION AND DATASHEETS DATE:- CLIENT DOC NO:- NAME:- FOR CONTROL VALVES REV NO:- DATASHEET - CONTROL VALVES 1 TAG GENERAL DATA 2 SERVICE BLANKET FUEL GAS FROM OIL STORAGE TANK 0-T-3603 3 LINE NO. / PID NO. 0-14"-FG-43 0017-AA3-H(E) / S2-01-YS207019-PID-P-5004 Sht 1 of 2 4 FLUID TANK VENT/FUEL GAS CRITICAL PRESS. Pc 5 UNIT MAX FLOW NORM FLOW MIN FLOW SHUT-OFF 6 FLOW RATE m3/h 5166 1847 525.3 - 7 INLET PRESSURE psi(g) 0.0568 0.093 0.0975 15 bar(g) 8 OUTLET PRESSURE psi(g) 0.037 0.0087 0.00234 SERVICE CONDITION 9 INLET TEMPERATURE Degree C 50 50 50 100(Note 1) - /kg/m3 / 10 SPEC WT/DENSITY/ MOL WT /-/1.378/40.30 /-/1.378 /40.30 /-/ 1.381/40.30 - kg/kmole 11 VISCOSITY /SPEC HEAT RATIO Cp / 0.00924/1.133 0.00924/1.133 0.00924/1.133 - 12 VAPOR PRESSURE inH2O NA NA NA - 13 REQUIRED CV - 14 TRAVEL % 0 15 ALLOWABLE /PREDICTED SPL dBA < 85/ < 85/ < 85/ - 16 SET POINT inH2O(g) 2.75 2.75 2.75 General Control Valves. Prepared by: Gavhane D.V. 15
  • 16. Contents of Control Valve:– Data Sheet. SINGLE-ACTING FAIL SAFE 17 PIPE LINE SIZE & IN 14" & SCH20 56 TYPE SPRING RETURN –DIAPHRAGM TYPE LINE SCHEDULE 18 OUT 14" & SCH20 57 MFR & MODEL VTS HEAT CONSERVATION 19 PIPE LINE INSULATION 58 SIZE / EFF.AREA VTS (ELECTRICAL TRACING) 20 VALVE SIZING ISA S75.01 59 ON/OFF MODULATING YES SPEC.& CODES ACTUATOR (PNEUMATIC) VALVE SEAT LEAKAGE 21 IV AS PER FCI 70-2 60 SPRING ACTION ON FAIL CLOSE CLASS MAX ALLOWABLE 22 61 VTS PRESS. 23 62 MIN REQUIRED PRESS. VTS 24 63 AVAILABLE AIR SUPPLY MIN NOR MAX DESIGN 25 TYPE BUTTERFLY 64 PRESSURE kPag 400 850 900 1000 26 SIZE VTS 65 BENCH RANGE VTS ACTUATOR 27 MAX PRESS./TEMP. VTS 66 VTS ORIENTATION 28 BODY/BONNET MATERIAL A105 or A216 WCB 67 HANDWHEEL TYPE YES VTS AIR FAILURE LOCK 29 LINER MATERIAL / ID 68 REQD. SET AT Note 5 RELAY 30 69 AIR BOTTLE REQD. WITH ACCESSORIES VALVE BODY 31 END CONNECTION IN/ OUT FLANGED 70 FIRE SAFE YES 32 RATING & FLANGE FACE FINI. 150# RF ASME B16.5 71 INPUT SIGNAL 4-20 mA 33 END EXTENSION/MATERIAL ASTM A105 carbon steel 72 TYPE ELECTRO-PNEUMATIC (HART) POSITIONER EXPLOSION 34 FLOW DIRECTION YES 73 EExd PROTECTION ON INCR SIGNAL 35 TYPE OF BONNET BOLTED 74 FIELD REVERSIBLE OUTPUT INCR/DECR 36 LUB & ISO VALVE / LUBE 75 GAUGES Yes BYPASS Yes 37 PACKING MATERIAL PTFE 76 CAM CHARACTERISTIC 38 PACKING TYPE VTS 77 MFR & MODEL VTS SWITC 39 VTS 78 TYPE - QTY - HES BONNET GASKET 40 MFR & MODEL VTS 79 MFR & MODEL - General Control Valves. Prepared by: Gavhane D.V. 16
  • 17. Contents of Control Valve:– Data Sheet . 41 TYPE VTS 80 CONTACTS/RATING - 42 SIZE RATED TRAVEL VTS VTS 81 ACTUATION POINTS - 43 CHARACTERISTIC VTS 82 44 BALANCED/UNBALANCED VTS 83 MATERIAL DIE CAST ALUMINIUM RATED CV VTS FL VTS XT VTS 84 FILTER SIZE < or = 25 Micron TRIM 45 AIR FILTER 46 PLUG/BALL/DISC MATERIAL F6 85 SET PRESSURE F6 SEAT HARD FACED WITH INTEGRAL PRESS. SEAT MATERIAL 86 50mm DIAL 47 STELLITE6. GAUGE 48 CAGE/GUIDE MATERIAL VTS 87 CONNECTION 1/2"NPT 49 STEM MATERIAL F6 88 MFR & MODEL VTS 50 89 51 NEC CLASS GR. DIV. 90 HYDRO PRESS. YES ACCESSORIES SPECIALS / 52 IEC ZONE GR. TEMP. CLASS CLASS I, ZONE 2 , GROUP IIA & T3 91 SEAT LEAKAGE TEST YES TESTS 53 92 CAPACITY TEST YES 54 93 55 94 NOTES : VTS-Vendor To Specify General Control Valves. Prepared by: Gavhane D.V. 17
  • 18. Globe Control Valve Construction. . General Control Valves. Prepared by: Gavhane D.V. 18
  • 19. General Control Valve Classification. CONTROL VALVE LINEAR ROTARY MOTION MOTION Eccentric plug Diaphragm valve GLOBE VALVE Butterfly Gate valve Globe Ball Angle Three way General Control Valves. Prepared by: Gavhane D.V. 19
  • 20. General Types of Control Valve. CONTROL VALVE TYPES VALVE TYPES BASED ON PLUG CONSTRUCTION ARE GLOBE VALVE BALL VALVE BUTTERFLY VALVE Control:- Linear & equal % Control:- Quick opening Control:- Linear & equal % Use:- Throttling Service, And linear. Uses:- Fully open / closed or Flow Regulation, Frequent Uses:- Fully open / closed Throttling services, Frequent Operation limited-throttling Operation, Minimal fluid Application:- Liquid, Vapour, Application:- Most liquids Trapping in line. Gases, Corrosive Substances High temperature, slurries Application:-Liquids, gases, Slurries. Advantage:- High capacity Slurries, Liquids with Advantage: Efficient throttling Low leakage and Maint. suspended Solids. Available in multiple ports. Tight sealing with low torque Advantage :- High Capacity Accurate Flow control. Disadvantage:- poor Good flow control, Low Press. Disadvantage: High pressure Throttling characteristics Drop, Low cost and Maint. Drop, more expensive. Prone to Cavitation Disadvantage:- High torque Required for control Prone to cavitation at lower ECENTRIC PLUG / CAMFLEX DIAPHRAGM KNIFE GATE Flows. General Control Valves. Prepared by: Gavhane D.V. 20
  • 21. Eccentric Plug / Camflex Valve Construction. Side view of an eccentric plug valve Shown in partially open….. General Control Valves. Prepared by: Gavhane D.V. 21
  • 22. Eccentric Disk/Ball/Knife Valve Construction Eccentric Disk Valve V-Notch Ball Valve Knife Gate Valve General Control Valves. Prepared by: Gavhane D.V. 22
  • 23. Butterfly/Angle/Three Way Valve Construction General Control Valves. Prepared by: Gavhane D.V. 23
  • 24. Diaphrgm Type Valve Construction. Seal over a seat ( Straight type) Weir type ( Saddle type) General Control Valves. Prepared by: Gavhane D.V. 24
  • 25. General Types of Actuators . Actuator is the part of the valve that responds to the applied signal and causes modification of the fluid flow through stem & plug. TYPES OF ACTUATORS: 1) Diaphragm Actuator Direct Acting Reverse Acting Size depends on output thrust required and supply air pressure available. 2) Piston Actuator Use of high pressure air to 150 psig., eliminating the need of pressure regulator. Used where High & Fast Stroking Speed is required. 3) Electro hydraulic Actuator: Electro-hydraulic Actuator is single unit contains Hydraulic Pump and Reservoir & Electric Motor. Ideal for isolated locations 4) Manual Actuator Used where no auto control is required General Control Valves. Prepared by: Gavhane D.V. 25
  • 26. Direct – Acting Actuators . General Control Valves. Prepared by: Gavhane D.V. 26
  • 27. Actuators Fail-Safe Requirements. Fail Safe is the action of the actuator by which the valve CLOSES (FC) or OPENS (FO) fully in case of air supply failure. General Control Valves. Prepared by: Gavhane D.V. 27
  • 28. General Types of Bonnet & Accessories . Bonnet - Bonnet is a part of the valve body assembly through which the valve plug stem or rotary shaft moves. Types Of Bonnets Plain or Std Bonnet :-Operating Temp below 2000 c. Finned Bonnet :- Operating Temp above 2000 c or Equal. Extension Bonnet :- Operating Temp below 00 c or Equal. Extension Bonnet :- Operating Temp above 4500 c. Bellow Seal Bonnet :- where no stem leakage is tolerated For Toxic, Expensive Fluids. General Control Valve - Accessories •Positioners •Limit Switches •Solenoid Valves •Position Transmitters •Volume Boosters General Control Valves. Prepared by: Gavhane D.V. 28
  • 29. General Construction of Bonnet . Forged –Valve Finned Extension Bellow Seal Bonnet Bonnet Bonnet Bonnet ( Enviro Seal) Std./ plain Bonnet General Control Valves. Prepared by: Gavhane D.V. 29
  • 30. Control valves Characteristics. PROCESS APPLICATION INHERANT CHARACTERISTICS PRESSURE LIQUIDS EQUAL % GAS (LOW FLOWS ) EQUAL % GAS (LARGE FLOWS) ΔPmax/Δpmin < 5 LINEAR ΔPmax/Δpmin > 5 EQUAL % Temperature Liquids & Gases EQUAL % Flow Load Changes EQUAL % Set point change LINEAR Level ΔPmax/Δpmin < 5 LINEAR ΔPmax/Δpmin > 5 EQUAL % General Control Valves. Prepared by: Gavhane D.V. 30
  • 31. Control valves :- Interface PROCESS INTERFACE Process to provide process data to Instrument for specifying the valve Instrument to provide slected valve size to Process for incorporating in P&IDs Instrument to provide instrument air consumption figures for the valves to Process to decide air line & header sizes. PIPING INTERFACE Instrument to provide Face to Face Dimensions, End Connection Size & Rating, Actuator Height & Orientation, Envelope Dimensions (for 3-D Model), Weight, etc. Piping to provide location of control valves to Instrument for deciding instrument air manifolds. Piping to provide Pipe Material Specification to Instrument for specifying the valves. General Control Valves. Prepared by: Gavhane D.V. 31
  • 32. Control valves Body Material. Frequently Used Valve Body Cast Materials Are: CARBON STEEL (ASTM A216 GR WCC) up to 4270 C CHROME MOLY STEEL (ASTM A217 GR WC9) up to 5930 C CARBON MOLY STEEL (ASTM A217 GR C5) up to 5930 C 304L STAINLESS STEEL (ASTM A351 GR CF3) up to 8160 C 316 STAINLESS STEEL (ASTM A351 GR CF8M) up to 8160 C CAST IRON (ASTM A126) up to 2320 C Special Materials Used Depending On The Process Requirements HASTEALLOY B HASTEALLOY C MONEL ALLOY General Control Valves. Prepared by: Gavhane D.V. 32
  • 33. Control valves Trim Material. Frequently Used Valve Trim Materials Are: • 302 SS : ASTM A 276 TYPE 302 • 304 SS : ASTM A 276 TYPE 304 • 316 SS : ASTM A 276 TYPE 316 • 316 L SS : ASTM A 276 TYPE 316L • 410 SS : ASTM A 276 TYPE 410 • 17-4 pH SS : ASTM A 461 GR 630 [High Tensile Strength, High Yield point, Hardened Material] • HASTEALLOY ``B’’ : ASTM A 335 • HASTEALLOY ``C’’ : ASTM A 336 General Control Valves. Prepared by: Gavhane D.V. 33
  • 34. Control valves Codes and Standards. ANSI B 16.34 : • Covers Pressure, Temperature rating, Dimensions, Materials, NDT Requirements ANSI B 16.5 : • Covers design of flanges and flanged fittings MSS SP 67 : • Covers design and test performance requirements of Butterfly valves and divides in to three leak classes. ANSI B 16.10: • Face to Face dimensions ANSI B 16.37: Hydrostatic testing LEAKAGE RATES AS PER ANSI/FCI 70-2 Formerly (ANSI B 16.104) for seat leak classes and testing procedures - FCI General Control Valves. Prepared by: Gavhane D.V. 34
  • 35. Vendor Design Documents- Sizing & Selection Step # 1:- Define the system Example :- The system is pumping water from one tank to another through a piping system total pressure drop is 150psi.The fluid is water at 700F.Design (maximum) flow of 150 gpm,operating flow rate of 110 gpm,and minimum flow rate of 25gpm. Pipe diameter is 3 inches. At 700F, water has has a specific gravity of1.0 Key Variables:- Total pressure drop , design flow ,operating flow, minimum flow diameter, specific gravity. Step # 2:- Define Max. Allowable Pressure Drop For The Valve When defining the allowable pressure drop across the valve, you should first investigate the pump.What is its maximum available head? Remember that the system pressure drop is limited by the pump. Essentially the Net Positive Suction Head Available (NPSHA) minus the Net Positive Suction Head Required (NPSHR) is the maximum available pressure drop for the valve to use and this must not be exceeded or another pump will be needed. The usual rule of thumb is that a valve should be designed to use 10-15% of the total pressure drop or 10 psi, whichever is greater. For above example step#1 system, 10% of the total pressure drop is 15 psi which is what we'll use as our allowable pressure drop when the valve is wide open (the pump is our system is easily capable of the additional pressure drop). General Control Valves. Prepared by: Gavhane D.V. 35
  • 36. STEP #3: Calculate the valve characteristic General Control Valves. Prepared by: Gavhane D.V. 36
  • 37. Step#4:-Preliminary Valve Selection The Cv value should be used as a guide in the valve selection, not a hard and fast rule. Some other considerations are: a. Never use a valve that is less than half the pipe size b. Avoid using the lower 10% and upper 20% of the valve stroke. The valve is much easier to control in the 10-80% stroke range. Before a valve can be selected, we have to decide what type of valve will be used . For our case, we'll assume we're using an equal percentage, globe valve . The valve chart for this type of valve is shown below. This is a typical chart that will be supplied by the manufacturer. For our case, it appears the 2 inch valve will work well for our Cv value at about 80-85% of the stroke range. Notice that we're not trying to squeeze our Cv into the 1 1/2 valve which would need to be at 100% stroke to handle our maximum flow. General Control Valves. Prepared by: Gavhane D.V. 37
  • 38. Typical Chart Supplied by Manufacturer. General Control Valves. Prepared by: Gavhane D.V. 38
  • 39. Step# 5:-Check Cv & Stroke % at Min. Flow If the stroke percentage falls below 10% at our minimum flow, a smaller valve may have to be used in some cases. Judgments plays role in many cases. For example, is your system more likely to operate closer to the maximum flowrates more often than the minimum flowrates? Or is it more likely to operate near the minimum flow rate for extended periods of time. It's difficult to find the perfect valve, but you should find one that operates well most of the time. Let's check the valve we've selected for our system: General Control Valves. Prepared by: Gavhane D.V. 39
  • 40. Step#6:Check Gain across Applicable Flow Rates • Gain is defined as: • • Now, at our three flowrates: Qmin = 25 gpm Qop = 110 gpm Qdes = 150 gpm we have corresponding Cv values of 6.5, 28, and 39. The corresponding stroke percentages are 35%, 73%, and 85% respectively. Now we construct the following table: Flow (gpm) Stroke (%) Change in (gpm) Change in Stroke (%) 25 35 110-25=85 73-35=38 110 73 150 85 150-110=40 85-73=12 Gain #1 = 85/38 = 2.2 Gain #2 = 40/12 = 3.3 General Control Valves. Prepared by: Gavhane D.V. 40
  • 41. General Control valve Gain. The difference between these values should be less than 50% of the higher value. 0.5 (3.3) = 1.65 and 3.3 - 1.65 = 1.65. Since 2.2 is closer than 50%, there should be problem with controlling the valve. Also note that the gain should never be less than 0.50. Turndown :- It is ratio of the calculated Cv at maximum condition to the calculated Cv minimum. Rangeability :- It is ratio of Cv of the valve fully open to the minimum Cv at which it can control. The rangebility of the selected valve must exceed the turndown requirements of the application. General Control Valves. Prepared by: Gavhane D.V. 41
  • 42. General Control valves. Any Question ? General Control Valves. Prepared by: Gavhane D.V. 42