Field Testing of Second-Generation Residential Attic Using
Inorganic PCM Thermal Storage
Jan Kosny PhD., William Miller PhD., and Azam Mohiuddin Syed, Ph.D.
ORNL
August 2007
Background
The DOE Building Technologies (BT) Program has targeted the strategic goal of developing the next generation of
building envelope systems, with the ultimate objective of reducing the space conditioning requirements attributable
to attics by 50% compared to Building America (BA) regional baseline new construction. During 2005/06 computer
modeling and dynamic lab and field experiments lead to a new paradigm for designing thermally active building
envelopes. To meet BT’s goal, Oak Ridge National Lab’s Building Envelope Program (BEP) has worked with
several industries, universities, and collaborated with a sister national laboratory to merge key technologies into
prototype components for building envelopes.
Since residential attics are subjected to greater temperature extremes than any other component of the building
envelope, the first field experiments were conducted on new and unique attic material configurations containing,
PCM storage, reflective insulations, cool-roof surfaces, and air channels. Increasing the thermal capacitance of the
attic can reduce diurnal temperature swings, and, in turn, reduce both the total energy use and peak demand in
moderate and some cooling-dominant climates.
One of the first experimental modules tested during 2006/07 eliminated almost 90% of conventional attic heat gains
and losses crossing the roof deck. Infrared reflective roof products, above-sheathing ventilation, thermal mass,
thermal capacitance using phase change materials (PCMs) and radiant barriers were field tested to quantify attic
performance. During the week of July 16th 2007, a new test roof was constructed. This roof contains increased
amount of inorganic PCM (12 times higher storage capacity from the previous test roof) and improved configuration
of the above-sheathing ventilation channels.
Configuration Improvements in the Second Generation of the ORNL Roof Assembly
(2007)
First attic test module tested during 2006/07 had PCM thermal storage installed just above the sheathing. The
ORNL team used a multilayer configuration of PCM-enhanced polyurethane foams, PCM-impregnated fabrics, and
highly reflective aluminum foil. Loading of organic PCM was about 0.08 lb per ft2
of the surface area (0.39 kg/m2
).
Two types of PCMs were used. Their melting temperatures were around 78 and 90°F (26 and 32°C). The total
storage capacity of the PCM was about 4.8 Btu per ft2
(54 kJ/m2
) of the roof area. The first PCM roof used 4 in. (10-
cm.) air channels to exhaust excess heat during peak irradiance (subventing). Two low-emittance membranes were
placed above the roof sheathing with the low-emittance surfaces facing each other across the 4 in. air gap
(description is greatly simplified). PCM storage was placed above the roof deck but below the reflective foil.
Standing seam cool-painted metal roofing was used for this test assembly. Thus the thermal performance of this roof
assembly represents the combined effects of reduced thermal bridging, reflective insulation, cool-roof pigments,
PCM, and an attic subventing strategy.
In July 2007, a new roof assembly containing PCM thermal storage, reflective insulations, cool-roof surfaces, and
air channels was installed. In the second generation of the PCM roof, the ORNL team used a multilayer
configuration of bubble reflective insulation, 2-in. (5-cm) air cavity, 3/8-in. thick foil-faced foam supporting PCM
storage, inorganic PCM storage, 2-in. (5-cm) air cavity, and infrared reflective painted metal roof (SR28E81). The
air space adjacent the roof deck has two radiant barriers facing each other to negate almost all of the radiation heat
transfer crossing the air space. The phase change material (calcium chloride hydrate) is placed in the upper air space
and is contained in sealed aluminum pouches.
Page 2
3/8-in. EXPS
foam support
for PCM Roof Deck - OSB
Metal Roof
PCM Storage
Bubble
Radiant Insulation
Air Cavities for
Ventilation and
Heat Exhaust
3/8-in. EXPS
foam support
for PCM Roof Deck - OSB
Metal Roof
PCM Storage
Bubble
Radiant Insulation
Air Cavities for
Ventilation and
Heat Exhaust
FIGURE 1. Cross-section of the second generation of the residential attic containing dynamic
reflective insulation and sub-venting air channels.
PCM loading for installed in 2007 roof assembly was 12 times higher as in the roof installed in 2006. According to
the manufactures information, approximate cost of the PCM packages was about $5.00 per square foot. The PCM
loading was about 0.65 lb per ft2
of the surface area (~4.5 kg/m2). The melting temperature of the PCM was around
82°F (28°C). The total storage capacity of the PCM was about 58 Btu per ft2
(652 kJ/m2) of the roof area.
Figure 2 shows installation of the bottom reflective insulation, PCM storage, and custom spacers for installation of
PCM in the roof deck.
Figure 3 shows the completed 2007 PCM roof
Preliminary Test Results for August 2007
As stated above, during the week of July 16th
2007, second generation of the PCM test roof was constructed. This
roof contains 12 times more PCM storage capacity than the previous test roof built in summer 2006. The new roof
assembly also contains an improved configuration of the above-sheathing ventilation channels. At this time, two
separate air channels are utilized to remove heat from the PCM storage.
As presented in Figure 4, the summertime heat transfer penetrating the roof deck of the asphalt shingle conventional
roof (SR093E89) reaches a peak of about 28 Btu per hr per square foot of roof deck. A conventional shingle
(SR11E89) with radiant barrier attached to the underside of the sheathing (facing into attic) was used for comparison
of how effective a radiant barrier facing into the attic would be as compared to the conventional roof and the roof
with above-sheathing ventilation. The roof wit radiant barrier facing the attic plenum, dropped deck heat flow by
about 20% - of the heat penetrating through the asphalt shingle roof (with solar reflectance 0.093). For comparison,
the second generation ORNL PCM roof dropped the heat flux to less than 5 Btu per hr per square foot of roof deck
for field testing at ORNL when outdoor temperatures were exceeding 95°F.
Page 3
FIGURE 2. Installation of the second generation PCM attic containing dynamic reflective
insulation and sub-venting air channels.
FIGURE 3. Top view of the second generation of the ORNL PCM roof. An infrared reflective
painted metal roof (SR28E81) was used.
Page 4
Temperature profiles for the same three roofs are depicted in Figure 5. The solid lines represent roof top
surface temperatures. The dashed lines represent roof sheathing temperatures (facing attic). Roof surface
temperatures were almost the same for all three roofs, with their maximums reaching 170°F, and night
minimums being close to 60°F. However, temperatures of the roof sheathing (facing attic) were very
different and reveal the thermal effectiveness of the roof and attic assemblies.
-15
-10
-5
0
5
10
15
20
25
30
72 96 120 144 168
Time into Week (hrs)
RoofHeatFlux
[Btu/(hr·ft
2
)]
Control - Asphalt Shingle (SR093E89)
Weatherwood with Techshield (SR11E89)
PVDF Metal (SR28E81), 2x-(2-in) Airgaps, PCM, Astroboard, 2x-RB
0 24 48 72 96
FIGURE 4. Roof heat fluxes recorded during field testing conducted in August 2007 on adjacent
shed-type attic assemblies on ORNL’s Envelope Systems Research Apparatus.
The maximum sheathing temperature for PCM roof was only close to 100°F, which is about 65°F lower than the
maximum temperature recorded on the roof surface. The outdoor temperature was close to 95°F. Therefore, the
PCM roof significantly reduced solar peak loads, making bottom temperature of the roof sheathing very close to the
ambient air. The result was achieved by utilizing reflective insulation, cool roof surface, above sheathing
ventilation, and PCM thermal storage.
The phase change materials caused a slight shift in peak heat flow (about 2 to 3 hours later in the afternoon) as
compared to the more conventional roof and attic assemblies (Figure 5. view vertical blue dashed lines). The data
also shows that the PCM is able to charge and discharging heat over the diurnal cycle even when outdoor air
temperature reached highs of 100°F. It is also very important to note that the PCMs release heat back to the sky at
night. The asphalt shingle roofs have the greatest night sky radiation losses, and the painted metal systems (cool roof
coating) show night time heat losses that are less than that of the shingle roofs especially because of the phase
change materials release of stored energy. This finding may be very useful for commercial cool roofs (for example
in Northern California).
60
80
100
120
140
160
180
0 24 48 72
Time into Week (hrs)
Temperature(
o
F)
Control - Asphalt Shingle (SR093E89)
Weatherwood with Techshield (SR11E89)
PVDF Metal (SR28E81), 2x-(2-in) Airgaps, PCM, Astroboard, 2x-RB
Control - Asphalt Shingle (SR093E89)
Weatherwood with Techshield (SR11E89)
PVDF Metal (SR28E81), 2x-(2-in) Airgaps, PCM, Astroboard, 2x-RB
Surface
Sheathing facing
FIGURE 5. Temperature profiles recorded during field testing conducted in August 2007 on
adjacent shed-type attic assemblies on ORNL’s Envelope Systems Research Apparatus.
As a 2007 upgrade, the second generation prototype roof used above sheathing ventilation in two separate 2-in air
spaces1
above the sheathing providing improved heat removal from the PCM storage. During the winter season,
these two air cavities will be sealed. These two cavities together with the PCM storage will work, at that time, as a
solar collector. Solar energy stored during the day will be transferred to the interior of the building reducing roof-
generated heating loads. During September 2007, a similar material will be installed and field-tested on the ORNL
experimental wall.
Research Plans for the Second Generation ORNL PCM Roof
1.During October 2007 roof will be opened and PCM storage will be inspected for leaking.
2. In October 2007 air cavities in the PCM roof will be blocked to stop free air ventilation.
3. In April 2008 air cavities in the PCM roof will be opened again to allow natural air ventilation
4. After 122 months field testing is completed, selected PCM pouches will be sent to producer for further
analysis
SUMMARY
The DOE Building Technologies (BT) Program through the Building Integration program of Building
America (BA) is working to develop affordable, energy efficient and environmentally compliant Zero
Energy Buildings (ZEB) by 2025. The roof tested on the ESRA (cool painted metal with two 2-in air
1
Renegade Roof Systems, Inc. patented metal batten for ventilation above the sheathing.
spaces shows excellent performance and helps curtail building envelope energy consumption. Testing will
be continued for the full twelve months period.

Más contenido relacionado

La actualidad más candente

NBEC 2014 - Conventional Roofs: Measuring Impacts of Insulation Strategy and ...
NBEC 2014 - Conventional Roofs: Measuring Impacts of Insulation Strategy and ...NBEC 2014 - Conventional Roofs: Measuring Impacts of Insulation Strategy and ...
NBEC 2014 - Conventional Roofs: Measuring Impacts of Insulation Strategy and ...RDH Building Science
 
Residential Energy Audit Report
Residential Energy Audit ReportResidential Energy Audit Report
Residential Energy Audit ReportMichael Clarke
 
Does_My_Building_Envelope_Really_Need_a_Retrofit
Does_My_Building_Envelope_Really_Need_a_RetrofitDoes_My_Building_Envelope_Really_Need_a_Retrofit
Does_My_Building_Envelope_Really_Need_a_RetrofitKyle Taylor
 
St. James Church - Energy Audit Report
St. James Church - Energy Audit ReportSt. James Church - Energy Audit Report
St. James Church - Energy Audit ReportMichael Clarke
 
Ultra super critical power plant materials
Ultra super critical power plant materialsUltra super critical power plant materials
Ultra super critical power plant materialsS S Ananthan Ananthan
 
Heatsink using additive manufacturing
Heatsink using additive manufacturingHeatsink using additive manufacturing
Heatsink using additive manufacturingAnkit Sutaria
 
Masonry Veneer Support Details: Thermal Bridging
Masonry Veneer Support Details: Thermal BridgingMasonry Veneer Support Details: Thermal Bridging
Masonry Veneer Support Details: Thermal BridgingRDH Building Science
 
Transsolar%20 concept%20for%20the%20nbia
Transsolar%20 concept%20for%20the%20nbiaTranssolar%20 concept%20for%20the%20nbia
Transsolar%20 concept%20for%20the%20nbiaBenedikt von Liel
 
New generation in pre heating technology
New generation in pre heating technologyNew generation in pre heating technology
New generation in pre heating technologymetudgn
 
Enhancing Energy Efficiency of Thermochemical Vacuum-Processes and Systems
Enhancing Energy Efficiency of Thermochemical Vacuum-Processes and SystemsEnhancing Energy Efficiency of Thermochemical Vacuum-Processes and Systems
Enhancing Energy Efficiency of Thermochemical Vacuum-Processes and SystemsALD Vacuum Systems Inc.
 
ORNL Study on ASV Ventilation_ Ornl apr 2007 b ginf a41 t1-us-07-1
ORNL Study on ASV Ventilation_ Ornl apr 2007 b ginf a41 t1-us-07-1ORNL Study on ASV Ventilation_ Ornl apr 2007 b ginf a41 t1-us-07-1
ORNL Study on ASV Ventilation_ Ornl apr 2007 b ginf a41 t1-us-07-1Cool Roof Innovations
 
Entropic Ecology indoors: Energy Efficiency in Data Centre Design
Entropic Ecology indoors: Energy Efficiency in Data Centre Design Entropic Ecology indoors: Energy Efficiency in Data Centre Design
Entropic Ecology indoors: Energy Efficiency in Data Centre Design SustainableEnergyAut
 
Deep Energy Retrofit of a High-Rise MURB
Deep Energy Retrofit of a High-Rise MURBDeep Energy Retrofit of a High-Rise MURB
Deep Energy Retrofit of a High-Rise MURBRDH Building Science
 

La actualidad más candente (20)

NBEC 2014 - Conventional Roofs: Measuring Impacts of Insulation Strategy and ...
NBEC 2014 - Conventional Roofs: Measuring Impacts of Insulation Strategy and ...NBEC 2014 - Conventional Roofs: Measuring Impacts of Insulation Strategy and ...
NBEC 2014 - Conventional Roofs: Measuring Impacts of Insulation Strategy and ...
 
BCE SUPERCIRC Heater
BCE SUPERCIRC HeaterBCE SUPERCIRC Heater
BCE SUPERCIRC Heater
 
AIA Chicago Presentation
AIA Chicago PresentationAIA Chicago Presentation
AIA Chicago Presentation
 
Ft3610541057
Ft3610541057Ft3610541057
Ft3610541057
 
Residential Energy Audit Report
Residential Energy Audit ReportResidential Energy Audit Report
Residential Energy Audit Report
 
PCM coated Heat sinks
PCM coated Heat sinksPCM coated Heat sinks
PCM coated Heat sinks
 
Does_My_Building_Envelope_Really_Need_a_Retrofit
Does_My_Building_Envelope_Really_Need_a_RetrofitDoes_My_Building_Envelope_Really_Need_a_Retrofit
Does_My_Building_Envelope_Really_Need_a_Retrofit
 
St. James Church - Energy Audit Report
St. James Church - Energy Audit ReportSt. James Church - Energy Audit Report
St. James Church - Energy Audit Report
 
building2.energy
building2.energybuilding2.energy
building2.energy
 
Ultra super critical power plant materials
Ultra super critical power plant materialsUltra super critical power plant materials
Ultra super critical power plant materials
 
Heatsink using additive manufacturing
Heatsink using additive manufacturingHeatsink using additive manufacturing
Heatsink using additive manufacturing
 
Masonry Veneer Support Details: Thermal Bridging
Masonry Veneer Support Details: Thermal BridgingMasonry Veneer Support Details: Thermal Bridging
Masonry Veneer Support Details: Thermal Bridging
 
Transsolar%20 concept%20for%20the%20nbia
Transsolar%20 concept%20for%20the%20nbiaTranssolar%20 concept%20for%20the%20nbia
Transsolar%20 concept%20for%20the%20nbia
 
New generation in pre heating technology
New generation in pre heating technologyNew generation in pre heating technology
New generation in pre heating technology
 
Enhancing Energy Efficiency of Thermochemical Vacuum-Processes and Systems
Enhancing Energy Efficiency of Thermochemical Vacuum-Processes and SystemsEnhancing Energy Efficiency of Thermochemical Vacuum-Processes and Systems
Enhancing Energy Efficiency of Thermochemical Vacuum-Processes and Systems
 
Pcm material
Pcm materialPcm material
Pcm material
 
ORNL Study on ASV Ventilation_ Ornl apr 2007 b ginf a41 t1-us-07-1
ORNL Study on ASV Ventilation_ Ornl apr 2007 b ginf a41 t1-us-07-1ORNL Study on ASV Ventilation_ Ornl apr 2007 b ginf a41 t1-us-07-1
ORNL Study on ASV Ventilation_ Ornl apr 2007 b ginf a41 t1-us-07-1
 
Entropic Ecology indoors: Energy Efficiency in Data Centre Design
Entropic Ecology indoors: Energy Efficiency in Data Centre Design Entropic Ecology indoors: Energy Efficiency in Data Centre Design
Entropic Ecology indoors: Energy Efficiency in Data Centre Design
 
Deep Energy Retrofit of a High-Rise MURB
Deep Energy Retrofit of a High-Rise MURBDeep Energy Retrofit of a High-Rise MURB
Deep Energy Retrofit of a High-Rise MURB
 
THERMAL BRIDGING
THERMAL BRIDGINGTHERMAL BRIDGING
THERMAL BRIDGING
 

Similar a Pcm roof ii

Thermal simulation report
Thermal simulation reportThermal simulation report
Thermal simulation reportDion Marsh
 
drainage capabilities and heat loss of different inverted roof assemblies
drainage capabilities and heat loss of different inverted roof assembliesdrainage capabilities and heat loss of different inverted roof assemblies
drainage capabilities and heat loss of different inverted roof assembliesAmiran Bokhua
 
Radiant ventilated roofing presentation 15 02.1
Radiant ventilated roofing presentation 15 02.1Radiant ventilated roofing presentation 15 02.1
Radiant ventilated roofing presentation 15 02.1Cool Roof Innovations
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...IRJET Journal
 
Solar thermal control of building integrated phase change materials an experi...
Solar thermal control of building integrated phase change materials an experi...Solar thermal control of building integrated phase change materials an experi...
Solar thermal control of building integrated phase change materials an experi...eSAT Journals
 
themal barrier coating report
 themal barrier coating report themal barrier coating report
themal barrier coating reportshubham bhombe
 
Advanced solar thermal storage walls
Advanced solar thermal storage wallsAdvanced solar thermal storage walls
Advanced solar thermal storage wallssrikanth reddy
 
1new themal barrier coating report
1new themal barrier coating report1new themal barrier coating report
1new themal barrier coating reportshubham bhombe
 
Thermal energy storage for buildings with PCM pellets
Thermal energy storage for buildings with PCM pelletsThermal energy storage for buildings with PCM pellets
Thermal energy storage for buildings with PCM pelletsRamin Abhari
 
Multi Hole Film Cooling with Integrally Woven SiC-SiC Wall Panels
Multi Hole Film Cooling with Integrally Woven SiC-SiC Wall PanelsMulti Hole Film Cooling with Integrally Woven SiC-SiC Wall Panels
Multi Hole Film Cooling with Integrally Woven SiC-SiC Wall PanelsJayesh Mehta
 
Advanced CFD_Numerical_Analysis
Advanced CFD_Numerical_AnalysisAdvanced CFD_Numerical_Analysis
Advanced CFD_Numerical_AnalysisPeter McGibney
 
Experimental Investigation of Graphene coated Al cuboid crammed with PCM`s fo...
Experimental Investigation of Graphene coated Al cuboid crammed with PCM`s fo...Experimental Investigation of Graphene coated Al cuboid crammed with PCM`s fo...
Experimental Investigation of Graphene coated Al cuboid crammed with PCM`s fo...IRJET Journal
 
PRACTICAL ISSUES ASSOICATED WITH THE USE OF INFRARED THERMOGRAPHY FOR DETECTI...
PRACTICAL ISSUES ASSOICATED WITH THE USE OF INFRARED THERMOGRAPHY FOR DETECTI...PRACTICAL ISSUES ASSOICATED WITH THE USE OF INFRARED THERMOGRAPHY FOR DETECTI...
PRACTICAL ISSUES ASSOICATED WITH THE USE OF INFRARED THERMOGRAPHY FOR DETECTI...John Kingsley
 
MEC441 - Solar Panel Cooling System
MEC441 - Solar Panel Cooling SystemMEC441 - Solar Panel Cooling System
MEC441 - Solar Panel Cooling SystemLuis Lituma
 

Similar a Pcm roof ii (20)

Thermal simulation report
Thermal simulation reportThermal simulation report
Thermal simulation report
 
drainage capabilities and heat loss of different inverted roof assemblies
drainage capabilities and heat loss of different inverted roof assembliesdrainage capabilities and heat loss of different inverted roof assemblies
drainage capabilities and heat loss of different inverted roof assemblies
 
Radiant ventilated roofing presentation 15 02.1
Radiant ventilated roofing presentation 15 02.1Radiant ventilated roofing presentation 15 02.1
Radiant ventilated roofing presentation 15 02.1
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...
 
Solar thermal control of building integrated phase change materials an experi...
Solar thermal control of building integrated phase change materials an experi...Solar thermal control of building integrated phase change materials an experi...
Solar thermal control of building integrated phase change materials an experi...
 
themal barrier coating report
 themal barrier coating report themal barrier coating report
themal barrier coating report
 
Advanced solar thermal storage walls
Advanced solar thermal storage wallsAdvanced solar thermal storage walls
Advanced solar thermal storage walls
 
1new themal barrier coating report
1new themal barrier coating report1new themal barrier coating report
1new themal barrier coating report
 
Radiant cooling
Radiant coolingRadiant cooling
Radiant cooling
 
Title24 ca techreport
Title24 ca techreportTitle24 ca techreport
Title24 ca techreport
 
Thermal energy storage for buildings with PCM pellets
Thermal energy storage for buildings with PCM pelletsThermal energy storage for buildings with PCM pellets
Thermal energy storage for buildings with PCM pellets
 
Multi Hole Film Cooling with Integrally Woven SiC-SiC Wall Panels
Multi Hole Film Cooling with Integrally Woven SiC-SiC Wall PanelsMulti Hole Film Cooling with Integrally Woven SiC-SiC Wall Panels
Multi Hole Film Cooling with Integrally Woven SiC-SiC Wall Panels
 
Advanced CFD_Numerical_Analysis
Advanced CFD_Numerical_AnalysisAdvanced CFD_Numerical_Analysis
Advanced CFD_Numerical_Analysis
 
Experimental Investigation of Graphene coated Al cuboid crammed with PCM`s fo...
Experimental Investigation of Graphene coated Al cuboid crammed with PCM`s fo...Experimental Investigation of Graphene coated Al cuboid crammed with PCM`s fo...
Experimental Investigation of Graphene coated Al cuboid crammed with PCM`s fo...
 
Radiant Ceiling Cooling
Radiant Ceiling CoolingRadiant Ceiling Cooling
Radiant Ceiling Cooling
 
PRACTICAL ISSUES ASSOICATED WITH THE USE OF INFRARED THERMOGRAPHY FOR DETECTI...
PRACTICAL ISSUES ASSOICATED WITH THE USE OF INFRARED THERMOGRAPHY FOR DETECTI...PRACTICAL ISSUES ASSOICATED WITH THE USE OF INFRARED THERMOGRAPHY FOR DETECTI...
PRACTICAL ISSUES ASSOICATED WITH THE USE OF INFRARED THERMOGRAPHY FOR DETECTI...
 
Ijmet 06 09_012
Ijmet 06 09_012Ijmet 06 09_012
Ijmet 06 09_012
 
Sac soe
Sac soeSac soe
Sac soe
 
MEC441 - Solar Panel Cooling System
MEC441 - Solar Panel Cooling SystemMEC441 - Solar Panel Cooling System
MEC441 - Solar Panel Cooling System
 

Más de Cool Roof Innovations

Roof lube business opportunity november 11.2
Roof lube   business opportunity  november 11.2Roof lube   business opportunity  november 11.2
Roof lube business opportunity november 11.2Cool Roof Innovations
 
Roof lube 25 point inspection & dealer installer bundles
Roof lube  25 point  inspection & dealer installer bundlesRoof lube  25 point  inspection & dealer installer bundles
Roof lube 25 point inspection & dealer installer bundlesCool Roof Innovations
 
Asv rci building envelope symposium 2010-brochure
Asv rci building envelope symposium 2010-brochureAsv rci building envelope symposium 2010-brochure
Asv rci building envelope symposium 2010-brochureCool Roof Innovations
 
Asv 21st century tile roofs 2008-10-vandewater
Asv 21st century tile roofs 2008-10-vandewaterAsv 21st century tile roofs 2008-10-vandewater
Asv 21st century tile roofs 2008-10-vandewaterCool Roof Innovations
 
Assessment of public policies affecting cool metal roofs tmi case_study_28
Assessment of public policies affecting cool metal roofs tmi case_study_28Assessment of public policies affecting cool metal roofs tmi case_study_28
Assessment of public policies affecting cool metal roofs tmi case_study_28Cool Roof Innovations
 
California energy commision cec title24-policy letter
California energy commision  cec title24-policy letterCalifornia energy commision  cec title24-policy letter
California energy commision cec title24-policy letterCool Roof Innovations
 
Above sheathing ventilation presentation (mca scott kriner-20080229)
Above sheathing ventilation presentation   (mca  scott kriner-20080229)Above sheathing ventilation presentation   (mca  scott kriner-20080229)
Above sheathing ventilation presentation (mca scott kriner-20080229)Cool Roof Innovations
 

Más de Cool Roof Innovations (8)

Roof lube business opportunity november 11.2
Roof lube   business opportunity  november 11.2Roof lube   business opportunity  november 11.2
Roof lube business opportunity november 11.2
 
Roof lube 25 point inspection & dealer installer bundles
Roof lube  25 point  inspection & dealer installer bundlesRoof lube  25 point  inspection & dealer installer bundles
Roof lube 25 point inspection & dealer installer bundles
 
Asv rci building envelope symposium 2010-brochure
Asv rci building envelope symposium 2010-brochureAsv rci building envelope symposium 2010-brochure
Asv rci building envelope symposium 2010-brochure
 
Asv 21st century tile roofs 2008-10-vandewater
Asv 21st century tile roofs 2008-10-vandewaterAsv 21st century tile roofs 2008-10-vandewater
Asv 21st century tile roofs 2008-10-vandewater
 
Assessment of public policies affecting cool metal roofs tmi case_study_28
Assessment of public policies affecting cool metal roofs tmi case_study_28Assessment of public policies affecting cool metal roofs tmi case_study_28
Assessment of public policies affecting cool metal roofs tmi case_study_28
 
California energy commision cec title24-policy letter
California energy commision  cec title24-policy letterCalifornia energy commision  cec title24-policy letter
California energy commision cec title24-policy letter
 
Radiant barrier energy saving study
Radiant barrier   energy saving studyRadiant barrier   energy saving study
Radiant barrier energy saving study
 
Above sheathing ventilation presentation (mca scott kriner-20080229)
Above sheathing ventilation presentation   (mca  scott kriner-20080229)Above sheathing ventilation presentation   (mca  scott kriner-20080229)
Above sheathing ventilation presentation (mca scott kriner-20080229)
 

Pcm roof ii

  • 1. Field Testing of Second-Generation Residential Attic Using Inorganic PCM Thermal Storage Jan Kosny PhD., William Miller PhD., and Azam Mohiuddin Syed, Ph.D. ORNL August 2007 Background The DOE Building Technologies (BT) Program has targeted the strategic goal of developing the next generation of building envelope systems, with the ultimate objective of reducing the space conditioning requirements attributable to attics by 50% compared to Building America (BA) regional baseline new construction. During 2005/06 computer modeling and dynamic lab and field experiments lead to a new paradigm for designing thermally active building envelopes. To meet BT’s goal, Oak Ridge National Lab’s Building Envelope Program (BEP) has worked with several industries, universities, and collaborated with a sister national laboratory to merge key technologies into prototype components for building envelopes. Since residential attics are subjected to greater temperature extremes than any other component of the building envelope, the first field experiments were conducted on new and unique attic material configurations containing, PCM storage, reflective insulations, cool-roof surfaces, and air channels. Increasing the thermal capacitance of the attic can reduce diurnal temperature swings, and, in turn, reduce both the total energy use and peak demand in moderate and some cooling-dominant climates. One of the first experimental modules tested during 2006/07 eliminated almost 90% of conventional attic heat gains and losses crossing the roof deck. Infrared reflective roof products, above-sheathing ventilation, thermal mass, thermal capacitance using phase change materials (PCMs) and radiant barriers were field tested to quantify attic performance. During the week of July 16th 2007, a new test roof was constructed. This roof contains increased amount of inorganic PCM (12 times higher storage capacity from the previous test roof) and improved configuration of the above-sheathing ventilation channels. Configuration Improvements in the Second Generation of the ORNL Roof Assembly (2007) First attic test module tested during 2006/07 had PCM thermal storage installed just above the sheathing. The ORNL team used a multilayer configuration of PCM-enhanced polyurethane foams, PCM-impregnated fabrics, and highly reflective aluminum foil. Loading of organic PCM was about 0.08 lb per ft2 of the surface area (0.39 kg/m2 ). Two types of PCMs were used. Their melting temperatures were around 78 and 90°F (26 and 32°C). The total storage capacity of the PCM was about 4.8 Btu per ft2 (54 kJ/m2 ) of the roof area. The first PCM roof used 4 in. (10- cm.) air channels to exhaust excess heat during peak irradiance (subventing). Two low-emittance membranes were placed above the roof sheathing with the low-emittance surfaces facing each other across the 4 in. air gap (description is greatly simplified). PCM storage was placed above the roof deck but below the reflective foil. Standing seam cool-painted metal roofing was used for this test assembly. Thus the thermal performance of this roof assembly represents the combined effects of reduced thermal bridging, reflective insulation, cool-roof pigments, PCM, and an attic subventing strategy. In July 2007, a new roof assembly containing PCM thermal storage, reflective insulations, cool-roof surfaces, and air channels was installed. In the second generation of the PCM roof, the ORNL team used a multilayer configuration of bubble reflective insulation, 2-in. (5-cm) air cavity, 3/8-in. thick foil-faced foam supporting PCM storage, inorganic PCM storage, 2-in. (5-cm) air cavity, and infrared reflective painted metal roof (SR28E81). The air space adjacent the roof deck has two radiant barriers facing each other to negate almost all of the radiation heat transfer crossing the air space. The phase change material (calcium chloride hydrate) is placed in the upper air space and is contained in sealed aluminum pouches.
  • 2. Page 2 3/8-in. EXPS foam support for PCM Roof Deck - OSB Metal Roof PCM Storage Bubble Radiant Insulation Air Cavities for Ventilation and Heat Exhaust 3/8-in. EXPS foam support for PCM Roof Deck - OSB Metal Roof PCM Storage Bubble Radiant Insulation Air Cavities for Ventilation and Heat Exhaust FIGURE 1. Cross-section of the second generation of the residential attic containing dynamic reflective insulation and sub-venting air channels. PCM loading for installed in 2007 roof assembly was 12 times higher as in the roof installed in 2006. According to the manufactures information, approximate cost of the PCM packages was about $5.00 per square foot. The PCM loading was about 0.65 lb per ft2 of the surface area (~4.5 kg/m2). The melting temperature of the PCM was around 82°F (28°C). The total storage capacity of the PCM was about 58 Btu per ft2 (652 kJ/m2) of the roof area. Figure 2 shows installation of the bottom reflective insulation, PCM storage, and custom spacers for installation of PCM in the roof deck. Figure 3 shows the completed 2007 PCM roof Preliminary Test Results for August 2007 As stated above, during the week of July 16th 2007, second generation of the PCM test roof was constructed. This roof contains 12 times more PCM storage capacity than the previous test roof built in summer 2006. The new roof assembly also contains an improved configuration of the above-sheathing ventilation channels. At this time, two separate air channels are utilized to remove heat from the PCM storage. As presented in Figure 4, the summertime heat transfer penetrating the roof deck of the asphalt shingle conventional roof (SR093E89) reaches a peak of about 28 Btu per hr per square foot of roof deck. A conventional shingle (SR11E89) with radiant barrier attached to the underside of the sheathing (facing into attic) was used for comparison of how effective a radiant barrier facing into the attic would be as compared to the conventional roof and the roof with above-sheathing ventilation. The roof wit radiant barrier facing the attic plenum, dropped deck heat flow by about 20% - of the heat penetrating through the asphalt shingle roof (with solar reflectance 0.093). For comparison, the second generation ORNL PCM roof dropped the heat flux to less than 5 Btu per hr per square foot of roof deck for field testing at ORNL when outdoor temperatures were exceeding 95°F.
  • 3. Page 3 FIGURE 2. Installation of the second generation PCM attic containing dynamic reflective insulation and sub-venting air channels. FIGURE 3. Top view of the second generation of the ORNL PCM roof. An infrared reflective painted metal roof (SR28E81) was used.
  • 4. Page 4 Temperature profiles for the same three roofs are depicted in Figure 5. The solid lines represent roof top surface temperatures. The dashed lines represent roof sheathing temperatures (facing attic). Roof surface temperatures were almost the same for all three roofs, with their maximums reaching 170°F, and night minimums being close to 60°F. However, temperatures of the roof sheathing (facing attic) were very different and reveal the thermal effectiveness of the roof and attic assemblies. -15 -10 -5 0 5 10 15 20 25 30 72 96 120 144 168 Time into Week (hrs) RoofHeatFlux [Btu/(hr·ft 2 )] Control - Asphalt Shingle (SR093E89) Weatherwood with Techshield (SR11E89) PVDF Metal (SR28E81), 2x-(2-in) Airgaps, PCM, Astroboard, 2x-RB 0 24 48 72 96 FIGURE 4. Roof heat fluxes recorded during field testing conducted in August 2007 on adjacent shed-type attic assemblies on ORNL’s Envelope Systems Research Apparatus. The maximum sheathing temperature for PCM roof was only close to 100°F, which is about 65°F lower than the maximum temperature recorded on the roof surface. The outdoor temperature was close to 95°F. Therefore, the PCM roof significantly reduced solar peak loads, making bottom temperature of the roof sheathing very close to the ambient air. The result was achieved by utilizing reflective insulation, cool roof surface, above sheathing ventilation, and PCM thermal storage. The phase change materials caused a slight shift in peak heat flow (about 2 to 3 hours later in the afternoon) as compared to the more conventional roof and attic assemblies (Figure 5. view vertical blue dashed lines). The data also shows that the PCM is able to charge and discharging heat over the diurnal cycle even when outdoor air temperature reached highs of 100°F. It is also very important to note that the PCMs release heat back to the sky at night. The asphalt shingle roofs have the greatest night sky radiation losses, and the painted metal systems (cool roof coating) show night time heat losses that are less than that of the shingle roofs especially because of the phase change materials release of stored energy. This finding may be very useful for commercial cool roofs (for example in Northern California).
  • 5. 60 80 100 120 140 160 180 0 24 48 72 Time into Week (hrs) Temperature( o F) Control - Asphalt Shingle (SR093E89) Weatherwood with Techshield (SR11E89) PVDF Metal (SR28E81), 2x-(2-in) Airgaps, PCM, Astroboard, 2x-RB Control - Asphalt Shingle (SR093E89) Weatherwood with Techshield (SR11E89) PVDF Metal (SR28E81), 2x-(2-in) Airgaps, PCM, Astroboard, 2x-RB Surface Sheathing facing FIGURE 5. Temperature profiles recorded during field testing conducted in August 2007 on adjacent shed-type attic assemblies on ORNL’s Envelope Systems Research Apparatus. As a 2007 upgrade, the second generation prototype roof used above sheathing ventilation in two separate 2-in air spaces1 above the sheathing providing improved heat removal from the PCM storage. During the winter season, these two air cavities will be sealed. These two cavities together with the PCM storage will work, at that time, as a solar collector. Solar energy stored during the day will be transferred to the interior of the building reducing roof- generated heating loads. During September 2007, a similar material will be installed and field-tested on the ORNL experimental wall. Research Plans for the Second Generation ORNL PCM Roof 1.During October 2007 roof will be opened and PCM storage will be inspected for leaking. 2. In October 2007 air cavities in the PCM roof will be blocked to stop free air ventilation. 3. In April 2008 air cavities in the PCM roof will be opened again to allow natural air ventilation 4. After 122 months field testing is completed, selected PCM pouches will be sent to producer for further analysis SUMMARY The DOE Building Technologies (BT) Program through the Building Integration program of Building America (BA) is working to develop affordable, energy efficient and environmentally compliant Zero Energy Buildings (ZEB) by 2025. The roof tested on the ESRA (cool painted metal with two 2-in air 1 Renegade Roof Systems, Inc. patented metal batten for ventilation above the sheathing.
  • 6. spaces shows excellent performance and helps curtail building envelope energy consumption. Testing will be continued for the full twelve months period.