Oil Filled Transformer -
Accessories
1S.AYYADURAI
Accessories
 Every oil filled transformer has a variety of accessories
for different purposes. The most common of the accessory
, together with picture and description will be narrated .
 Liquid level gauge
 Liquid temperature gauge
 Pressure-vacuum gauge
 Pressure relief device
 Winding temperature gauge
 Transformer cooling fans
 High voltage bushings
 Low voltage bushings
 De-energized tap-changer
 Insulating liquid
2S.AYYADURAI
Liquid level gauge
 A liquid level indicator is provided
to aid in the systematic inspection
of the transformer under load. It
consists of a float-arm inside the
tank, an indicating pointer and a
magnetic coupling between the two
across a liquid-tight separation.
 The gauge may be furnished with
SPDT (Single Pole Double
Throw) alarm contacts to give a
remote annunciation of low liquid
level. For contact wiring and
terminal points, see the accessory
connection diagram furnished with
the transformer.
3S.AYYADURAI
Liquid Temperature gauge
Liquid Temperature gauge
 The temperature gauge is furnished to
indicate the top liquid temperature
in the tank in degrees Centigrade.
 The temperature-sensitive element is
mounted in a leak-proof well,
permitting removal of the thermometer
without lowering the oil level.
 The device is furnished with an
additional red pointer to show the
highest temperature attained since the
last reset.
 To reset the maximum indicator, turn
the knob in the center of the dial.
 The thermometer can be furnished with
two SPDT contacts for a high
temperature alarm, for energizing a fan
circuit or for a low temperature alarm.
4S.AYYADURAI
Pressure Relief Device
 All substation transformers are
furnished with a:
 Mechanical pressure relief valve (PRV), or
 Pressure relief device (PRD).
 The cover-mounted PRD consists of a
self-resetting, spring-loaded
Diaphragm and a
Mechanical operation indicator.
Should the tank pressure increase above
that for which the device is set, the gas
pressure will lift the diaphragm and let
the gas escape quickly. Immediately after
the pressure returns to normal,
the diaphragm will reset and reseal the
transformer.
 A mechanical indicator will protrude
vertically. This must be reset
manually to indicate subsequent
operations.
5S.AYYADURAI
Winding Temperature gauge
 Transformers may be furnished
with a winding
temperature gauge as
optional equipment. A
temperature sensitive stem is
mounted in a leakproof well,
permitting removal of both the
instrument and stem without
lowering the liquid level.
 The well is heated by both the
surrounding liquid and a heater
element which is energized
from a Current transformer
mounted inside the tank to
simulate the hot spot
winding temperature
gradient.
6S.AYYADURAI
Winding Temperature gauge
 The combination of the two temperatures are indicated on the gauge.
 An additional red pointer is furnished to show the highest
temperature attained since the last reset.
 The maximum indicator is resettable by means of a pushbutton
through the bottom of the dial bezel .
 The gauge has three separate SPDT switches for fan control and
alarm circuits.
 The equipment is calibrated to indicate the hottest spot of the
transformer windings. All contacts are factory set to operate at the
temperatures shown in the connection diagram. If readjustment of the
contacts is desired, the manufacturer has to be contacted for detailed
instruction
7S.AYYADURAI
 In order to increase the
transformer load
Without overheating the
windings, a set of fans can be
furnished as an optional item.
 Fan control consists of a
contact on either the liquid
temperature gauge or the
winding temperature gauge ,
and “Manual-Auto” control
switch .
 For continuous run, the
switch is turned to the
“Manual” position. In the
“Auto” position, the fans are
controlled by the contacts on
the temperature gauge.
Transformer Cooling Fans
8S.AYYADURAI
High Voltage Bushings
 High voltage leads for ratings
2 .4 kV and up are
normally brought through the
tank end wall using a
porcelain bushing.
 To prevent excessive
mechanical loading of
the bushing, only flexible
connections should be made to
the bushing terminal.
9S.AYYADURAI
LV BUSHING
 Low voltage leads for
ratings in the 1 .2 kV
Class are normally
brought through the
tank wall using an
indoor bushing. This is a
cast resin or porcelain
bushing
10S.AYYADURAI
Insulating liquid
 The insulating liquid in substation transformers
is conventional transformer oil
 When makeup liquid is required, use only approved
fluid of the same type that is in the transformer.
 It is important to check the proper liquid level in
the transformer at all times by periodically observing
the liquid level gauge.
 In addition, the dielectric strength of the
insulating liquid must be maintained at a high
value. A sample of the liquid will be tested within one
week after energisation, and annually thereafter.
11S.AYYADURAI
Power transformer- protection devices –
Buchholz (Gas) Relay
 The Buchholz protection is
a mechanical fault
detector for electrical
faults in oil-immersed
transformers.
 The Buchholz (gas) relay is
placed in the piping
between the transformer
main tank and the oil
conservator.
 The conservator pipe must
be inclined slightly for
reliable operation.
S.AYYADURAI 12
Buchholz (Gas) Relay
 The Buchholz protection is a fast and
sensitive fault detector.
 It works independent of the number of
transformer windings, tap changer
position and instrument transformers.
If the tap changer is of the on-tank
(container) type, having its own oil
enclosure with oil conservator, there is a
dedicated Buchholz relay for the tap
changer.
 A typical Buchholz protection
comprises a pivoted float (F) and a
pivoted vane (V) as shown in Figure 1.
 The float carries one mercury switch
and the vane also carries another
mercury switch. Normally, the casing is
filled with oil and the mercury switches
are open.
S.AYYADURAI 13
Buchholz (Gas) Relay
S.AYYADURAI 14
When minor fault occurs… within the transformer. Gases
produced by minor faults rise from the fault location to the
top of the transformer. Then the gas bubbles pass up the
piping to the conservator. The gas bubbles will be trapped in
the casing of the Buchholz protection.
This means that the gas replaces the oil in the casing. As
the oil level falls, the float (F) will follow and the mercury
switch tilts and closes an alarm circuit.
Buchholz (Gas) Relay
S.AYYADURAI 15
When major fault occurs…
It is also assumed that a major fault, either to earth of
between phases or windings, occurs within the
transformer. Such faults rapidly produce large volumes of
gas (more than 50 cm3/(kWs) and oil vapor which cannot
escape.
They therefore produce a steep buildup of pressure and
displace oil. This sets up a rapid flow from the transformer
towards the conservator. The vane (V) responds to high oil
and gas flow in the pipe to the conservator. In this case, the
mercury switch closes a trip circuit. The operating time of
the trip contact depends on the location of the fault and
the magnitude of the fault current.
Buchholz (Gas) Relay
S.AYYADURAI 16
• The gas accumulator relay also
provides a long-term accumulation of
gasses associated with overheating of
various parts of the transformer
conductor and insulation systems.
• This will detect fault sources in their
early stages and prevent significant
damage.
• When the transformer is first put into
service, the air trapped in the windings
may give unnecessary alarm signals. It
is customary to remove the air in the
power transformers by vacuum
treatment during the filling of the
transformer tank with oil.
• The gas accumulated without this
treatment will, of course, be air, which
can be confirmed by seeing that it is not
inflammable.
Pressure Relay
S.AYYADURAI 17
Many power transformers with an on-tank-type tap changer have a pressure
protection for the separate tap changer oil compartment. This protection
detects a sudden rate-of-increase of pressure inside the tap changer oil
enclosure.
When the pressure in front of the piston exceeds the counter force of the spring,
the piston will move operating the switching contacts.
The micro switch inside the switching unit is hermetically sealed and pressurized
with nitrogen gas.
Pressure Relay
S.AYYADURAI 18
An internal fault in an oil-filled transformer is usually accompanied by
overpressure in the transformer tank.
The simplest form of pressure relief device is the widely used frangible disk.
The surge of oil caused by a heavy internal fault bursts the disk and allows
the oil to discharge rapidly. Relieving and limiting the pressure rise prevent
explosive rupture of the tank and consequent fire.
S.AYYADURAI 19
Pressure Relay
Pressure Relay
S.AYYADURAI 20
A drawback of the frangible disk is that the oil remaining in
the tank is left exposed to the atmosphere after a rupture.
This is avoided in a more effective device, the pressure relief
valve, which opens to allow the discharge of oil if the pressure
exceeds the pre-adjusted limit.
By providing the transformer with a pressure relief valve, the
overpressure can be limited to a magnitude harmless to the
transformer.
If the abnormal pressure is relatively high, this spring-
controlled valve can operate within a few milliseconds and
provide fast tripping when suitable contacts are fitted.
 The valve closes automatically as the internal pressure falls
below a critical level.
Oil Level Monitor Device
S.AYYADURAI 21
Transformers with oil conservator(s) (expansion tank) often have an oil level
monitor.
Usually, the monitor has two contacts for alarm. One contact is for
maximum oil level alarm and the other contact is for minimum oil level
alarm.
capillary-type top-oil thermometer
S.AYYADURAI 22
The figure shows the construction of a capillary-type top-oil
thermometer, where the bulb is situated in a “pocket” surrounded by
oil on top of the transformer.
The bulb is connected to the measuring bellow inside the main unit via
a capillary tube. The bellow moves the indicator through mechanical
linkages, resulting in the operation of the contacts at set temperatures.
capillary-type top-oil thermometer
S.AYYADURAI 23
•The top-oil temperature may be considerably lower than the winding
temperature, especially shortly after a sudden load increase.
•This means that the top-oil thermometer is not an effective overheating
protection.
•However, where the policy towards transformers’ loss of life permits,
tripping on top-oil temperature may be satisfactory. This has the added
advantage of directly monitoring the oil temperature to ensure that it does
not reach the flash temperature.
Winding Thermometer
S.AYYADURAI 24
The winding thermometer, shown in the figure below, responds to both
the top-oil temperature and the heating effect of the load current.
Winding Thermometer
S.AYYADURAI 25
The winding thermometer creates an
image of the hottest part of the winding.
The top-oil temperature is measured .
 The measurement is further expanded
with a current signal proportional to the
loading current in the winding.
This current signal is taken from a
current transformer located inside the
bushing of that particular winding.
This current is lead to a resistor element
in the main unit.
This resistor heats up, and as a result of
the current flowing through it, it will in
its turn heat up the measurement
bellow, resulting in an increased indicator
movement.Top-oil thermometer and winding
thermometer main units fitted on the side of a
power transformer
Winding Thermometer
S.AYYADURAI 26
.
The winding thermometer can have one to four contacts,
which sequentially close at successively higher temperature.
With four contacts fitted, the two lowest levels are commonly
used to start fans or pumps for forced cooling, the third level
to initiate an alarm and the fourth step to trip load breakers or
de-energize the transformer or both.
In case a power transformer is fitted with top-oil thermometer
and winding thermometer, the latter one normally takes care of
the forced cooling control.
S.AYYADURAI 27

Más contenido relacionado

La actualidad más candente

220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & MaintenanceHimansu Pradhan
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Electrical Grid Substation
Electrical Grid SubstationElectrical Grid Substation
Electrical Grid SubstationAng Sovann
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guideSlides Hub
 
Differential relay
Differential relayDifferential relay
Differential relayChetan Patil
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformerssiddharam kantoli
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the LightningAmeen San
 
Presentation on Distribution Transformer by nirob dhilon chowdhury
Presentation on Distribution Transformer by nirob dhilon chowdhuryPresentation on Distribution Transformer by nirob dhilon chowdhury
Presentation on Distribution Transformer by nirob dhilon chowdhuryNirob Chowdhury
 
Power Electronics-Introduction
Power Electronics-IntroductionPower Electronics-Introduction
Power Electronics-Introductionsangeetha rakhi
 
Maintenance schedule of Substation.
Maintenance schedule of Substation.Maintenance schedule of Substation.
Maintenance schedule of Substation.Sheikh Nazmul Islam
 
Basics of electrical control panel
Basics of electrical control panelBasics of electrical control panel
Basics of electrical control panelCHACKOCHEN MATHEW
 
buchholz relay on transformer
buchholz relay on transformerbuchholz relay on transformer
buchholz relay on transformerAbhishekLalkiya
 
Presentation on 132/33 KVSubstation Training
Presentation on 132/33 KVSubstation Training Presentation on 132/33 KVSubstation Training
Presentation on 132/33 KVSubstation Training Sakshi Rastogi
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1Md Irshad Ahmad
 
Sub stations-air insulated substations
Sub stations-air insulated substationsSub stations-air insulated substations
Sub stations-air insulated substationsbhanu lucky
 
SLD-LINE LENGTH-NAMEPLATE DETAILS OF 765/400/220KV EQUIPMENT DETAILS-TYPES OF...
SLD-LINE LENGTH-NAMEPLATE DETAILS OF 765/400/220KV EQUIPMENT DETAILS-TYPES OF...SLD-LINE LENGTH-NAMEPLATE DETAILS OF 765/400/220KV EQUIPMENT DETAILS-TYPES OF...
SLD-LINE LENGTH-NAMEPLATE DETAILS OF 765/400/220KV EQUIPMENT DETAILS-TYPES OF...Pavan choudhary
 

La actualidad más candente (20)

220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Inverter
InverterInverter
Inverter
 
Electrical Grid Substation
Electrical Grid SubstationElectrical Grid Substation
Electrical Grid Substation
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guide
 
Differential relay
Differential relayDifferential relay
Differential relay
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the Lightning
 
Types of relay
Types of relayTypes of relay
Types of relay
 
Presentation on Distribution Transformer by nirob dhilon chowdhury
Presentation on Distribution Transformer by nirob dhilon chowdhuryPresentation on Distribution Transformer by nirob dhilon chowdhury
Presentation on Distribution Transformer by nirob dhilon chowdhury
 
Power Electronics-Introduction
Power Electronics-IntroductionPower Electronics-Introduction
Power Electronics-Introduction
 
Maintenance schedule of Substation.
Maintenance schedule of Substation.Maintenance schedule of Substation.
Maintenance schedule of Substation.
 
Basics of electrical control panel
Basics of electrical control panelBasics of electrical control panel
Basics of electrical control panel
 
buchholz relay on transformer
buchholz relay on transformerbuchholz relay on transformer
buchholz relay on transformer
 
Presentation on 132/33 KVSubstation Training
Presentation on 132/33 KVSubstation Training Presentation on 132/33 KVSubstation Training
Presentation on 132/33 KVSubstation Training
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1
 
Sub stations-air insulated substations
Sub stations-air insulated substationsSub stations-air insulated substations
Sub stations-air insulated substations
 
Substations
Substations Substations
Substations
 
SLD-LINE LENGTH-NAMEPLATE DETAILS OF 765/400/220KV EQUIPMENT DETAILS-TYPES OF...
SLD-LINE LENGTH-NAMEPLATE DETAILS OF 765/400/220KV EQUIPMENT DETAILS-TYPES OF...SLD-LINE LENGTH-NAMEPLATE DETAILS OF 765/400/220KV EQUIPMENT DETAILS-TYPES OF...
SLD-LINE LENGTH-NAMEPLATE DETAILS OF 765/400/220KV EQUIPMENT DETAILS-TYPES OF...
 

Destacado

PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv JimitPRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv JimitJimit Dhruv
 
Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"Harshit Srivastava
 
Proteksi sistem-tenaga-listrik
Proteksi sistem-tenaga-listrikProteksi sistem-tenaga-listrik
Proteksi sistem-tenaga-listrikJohari Zhou Hao Li
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)J. FR
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devicesRahul Aman
 
Manufaturing transformer
Manufaturing transformerManufaturing transformer
Manufaturing transformersuman
 
151706423 maintenance-and-troubleshooting-of-electric-motors
151706423 maintenance-and-troubleshooting-of-electric-motors151706423 maintenance-and-troubleshooting-of-electric-motors
151706423 maintenance-and-troubleshooting-of-electric-motorshomeworkping4
 
Macam relay proteksi
Macam relay proteksiMacam relay proteksi
Macam relay proteksiRidwan Satria
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersLiving Online
 
Insulation Resistance Testing / Megger
Insulation Resistance Testing / Megger Insulation Resistance Testing / Megger
Insulation Resistance Testing / Megger Roland Manansala
 
Presentation on power distribution, operation and maintenance in comilla pbs 1
Presentation on power distribution, operation and maintenance in comilla pbs 1Presentation on power distribution, operation and maintenance in comilla pbs 1
Presentation on power distribution, operation and maintenance in comilla pbs 1Kawsar Ahmed
 
Temperature measurement part i
Temperature measurement   part iTemperature measurement   part i
Temperature measurement part iBurdwan University
 
Dissolved Gas Analysis in Transformer Oil
Dissolved Gas Analysis in Transformer OilDissolved Gas Analysis in Transformer Oil
Dissolved Gas Analysis in Transformer OilSatish Patel
 

Destacado (20)

Transformers stdm
Transformers stdmTransformers stdm
Transformers stdm
 
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv JimitPRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
 
Transformer
TransformerTransformer
Transformer
 
Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"
 
Transformer
TransformerTransformer
Transformer
 
Proteksi sistem-tenaga-listrik
Proteksi sistem-tenaga-listrikProteksi sistem-tenaga-listrik
Proteksi sistem-tenaga-listrik
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 
Transformer construction,types and working
Transformer construction,types and workingTransformer construction,types and working
Transformer construction,types and working
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
 
Low Resistance Testing
Low Resistance TestingLow Resistance Testing
Low Resistance Testing
 
2
22
2
 
Manufaturing transformer
Manufaturing transformerManufaturing transformer
Manufaturing transformer
 
151706423 maintenance-and-troubleshooting-of-electric-motors
151706423 maintenance-and-troubleshooting-of-electric-motors151706423 maintenance-and-troubleshooting-of-electric-motors
151706423 maintenance-and-troubleshooting-of-electric-motors
 
Macam relay proteksi
Macam relay proteksiMacam relay proteksi
Macam relay proteksi
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
 
Insulation Resistance Testing / Megger
Insulation Resistance Testing / Megger Insulation Resistance Testing / Megger
Insulation Resistance Testing / Megger
 
Transformer
TransformerTransformer
Transformer
 
Presentation on power distribution, operation and maintenance in comilla pbs 1
Presentation on power distribution, operation and maintenance in comilla pbs 1Presentation on power distribution, operation and maintenance in comilla pbs 1
Presentation on power distribution, operation and maintenance in comilla pbs 1
 
Temperature measurement part i
Temperature measurement   part iTemperature measurement   part i
Temperature measurement part i
 
Dissolved Gas Analysis in Transformer Oil
Dissolved Gas Analysis in Transformer OilDissolved Gas Analysis in Transformer Oil
Dissolved Gas Analysis in Transformer Oil
 

Similar a Oil filled transformer accessories - copy

DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...
DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...
DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...Jobin Abraham
 
hydroelectric power plant_overview.ppt
hydroelectric power plant_overview.ppthydroelectric power plant_overview.ppt
hydroelectric power plant_overview.pptAnonymousYoutuber2
 
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...GlobeCore
 
Control Valves .pdf
Control Valves .pdfControl Valves .pdf
Control Valves .pdfmarcos849547
 
Valves_Control valve_Actuators.ppt
Valves_Control valve_Actuators.pptValves_Control valve_Actuators.ppt
Valves_Control valve_Actuators.pptKAhmedRehman
 
Transformer Accessories for Testing and Protection
Transformer Accessories for Testing and ProtectionTransformer Accessories for Testing and Protection
Transformer Accessories for Testing and ProtectionSAGAR D
 
Principle of operation of the vtr regulator valve
Principle of operation of the vtr regulator valvePrinciple of operation of the vtr regulator valve
Principle of operation of the vtr regulator valveBESSEM GHARBI
 
Globecore transformer oil purification plant cmm 2,2
Globecore transformer oil purification plant cmm  2,2Globecore transformer oil purification plant cmm  2,2
Globecore transformer oil purification plant cmm 2,2GlobeCore
 
Technical description bvg 2014 (upgrading) (en) light
Technical description bvg 2014 (upgrading) (en) lightTechnical description bvg 2014 (upgrading) (en) light
Technical description bvg 2014 (upgrading) (en) lightAdicomp s.r.l
 
Yankee safety by_dk_singhal
Yankee safety by_dk_singhalYankee safety by_dk_singhal
Yankee safety by_dk_singhalDevesh Singhal
 

Similar a Oil filled transformer accessories - copy (20)

DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...
DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...
DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...
 
hydroelectric power plant_overview.ppt
hydroelectric power plant_overview.ppthydroelectric power plant_overview.ppt
hydroelectric power plant_overview.ppt
 
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
 
Transformer
TransformerTransformer
Transformer
 
Control Valve.pdf
Control Valve.pdfControl Valve.pdf
Control Valve.pdf
 
Control Valves .pdf
Control Valves .pdfControl Valves .pdf
Control Valves .pdf
 
Valves_Control valve_Actuators.ppt
Valves_Control valve_Actuators.pptValves_Control valve_Actuators.ppt
Valves_Control valve_Actuators.ppt
 
Transformer Accessories for Testing and Protection
Transformer Accessories for Testing and ProtectionTransformer Accessories for Testing and Protection
Transformer Accessories for Testing and Protection
 
Gas street
Gas streetGas street
Gas street
 
Principle of operation of the vtr regulator valve
Principle of operation of the vtr regulator valvePrinciple of operation of the vtr regulator valve
Principle of operation of the vtr regulator valve
 
motorised valves
motorised valvesmotorised valves
motorised valves
 
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
 
Ammonia Booster Compressor
Ammonia Booster CompressorAmmonia Booster Compressor
Ammonia Booster Compressor
 
Globecore transformer oil purification plant cmm 2,2
Globecore transformer oil purification plant cmm  2,2Globecore transformer oil purification plant cmm  2,2
Globecore transformer oil purification plant cmm 2,2
 
Chiller ppt
Chiller pptChiller ppt
Chiller ppt
 
Rexarc Acetylene Generators - Part I
Rexarc Acetylene Generators - Part IRexarc Acetylene Generators - Part I
Rexarc Acetylene Generators - Part I
 
Replacement Parts Industries (RPI) Everything You Ever Wanted to Know About S...
Replacement Parts Industries (RPI) Everything You Ever Wanted to Know About S...Replacement Parts Industries (RPI) Everything You Ever Wanted to Know About S...
Replacement Parts Industries (RPI) Everything You Ever Wanted to Know About S...
 
Technical description bvg 2014 (upgrading) (en) light
Technical description bvg 2014 (upgrading) (en) lightTechnical description bvg 2014 (upgrading) (en) light
Technical description bvg 2014 (upgrading) (en) light
 
mn03010.pdf
mn03010.pdfmn03010.pdf
mn03010.pdf
 
Yankee safety by_dk_singhal
Yankee safety by_dk_singhalYankee safety by_dk_singhal
Yankee safety by_dk_singhal
 

Último

notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Arindam Chakraborty, Ph.D., P.E. (CA, TX)
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdfSuman Jyoti
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfRagavanV2
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfRagavanV2
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueBhangaleSonal
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...tanu pandey
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 

Último (20)

Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 

Oil filled transformer accessories - copy

  • 1. Oil Filled Transformer - Accessories 1S.AYYADURAI
  • 2. Accessories  Every oil filled transformer has a variety of accessories for different purposes. The most common of the accessory , together with picture and description will be narrated .  Liquid level gauge  Liquid temperature gauge  Pressure-vacuum gauge  Pressure relief device  Winding temperature gauge  Transformer cooling fans  High voltage bushings  Low voltage bushings  De-energized tap-changer  Insulating liquid 2S.AYYADURAI
  • 3. Liquid level gauge  A liquid level indicator is provided to aid in the systematic inspection of the transformer under load. It consists of a float-arm inside the tank, an indicating pointer and a magnetic coupling between the two across a liquid-tight separation.  The gauge may be furnished with SPDT (Single Pole Double Throw) alarm contacts to give a remote annunciation of low liquid level. For contact wiring and terminal points, see the accessory connection diagram furnished with the transformer. 3S.AYYADURAI
  • 4. Liquid Temperature gauge Liquid Temperature gauge  The temperature gauge is furnished to indicate the top liquid temperature in the tank in degrees Centigrade.  The temperature-sensitive element is mounted in a leak-proof well, permitting removal of the thermometer without lowering the oil level.  The device is furnished with an additional red pointer to show the highest temperature attained since the last reset.  To reset the maximum indicator, turn the knob in the center of the dial.  The thermometer can be furnished with two SPDT contacts for a high temperature alarm, for energizing a fan circuit or for a low temperature alarm. 4S.AYYADURAI
  • 5. Pressure Relief Device  All substation transformers are furnished with a:  Mechanical pressure relief valve (PRV), or  Pressure relief device (PRD).  The cover-mounted PRD consists of a self-resetting, spring-loaded Diaphragm and a Mechanical operation indicator. Should the tank pressure increase above that for which the device is set, the gas pressure will lift the diaphragm and let the gas escape quickly. Immediately after the pressure returns to normal, the diaphragm will reset and reseal the transformer.  A mechanical indicator will protrude vertically. This must be reset manually to indicate subsequent operations. 5S.AYYADURAI
  • 6. Winding Temperature gauge  Transformers may be furnished with a winding temperature gauge as optional equipment. A temperature sensitive stem is mounted in a leakproof well, permitting removal of both the instrument and stem without lowering the liquid level.  The well is heated by both the surrounding liquid and a heater element which is energized from a Current transformer mounted inside the tank to simulate the hot spot winding temperature gradient. 6S.AYYADURAI
  • 7. Winding Temperature gauge  The combination of the two temperatures are indicated on the gauge.  An additional red pointer is furnished to show the highest temperature attained since the last reset.  The maximum indicator is resettable by means of a pushbutton through the bottom of the dial bezel .  The gauge has three separate SPDT switches for fan control and alarm circuits.  The equipment is calibrated to indicate the hottest spot of the transformer windings. All contacts are factory set to operate at the temperatures shown in the connection diagram. If readjustment of the contacts is desired, the manufacturer has to be contacted for detailed instruction 7S.AYYADURAI
  • 8.  In order to increase the transformer load Without overheating the windings, a set of fans can be furnished as an optional item.  Fan control consists of a contact on either the liquid temperature gauge or the winding temperature gauge , and “Manual-Auto” control switch .  For continuous run, the switch is turned to the “Manual” position. In the “Auto” position, the fans are controlled by the contacts on the temperature gauge. Transformer Cooling Fans 8S.AYYADURAI
  • 9. High Voltage Bushings  High voltage leads for ratings 2 .4 kV and up are normally brought through the tank end wall using a porcelain bushing.  To prevent excessive mechanical loading of the bushing, only flexible connections should be made to the bushing terminal. 9S.AYYADURAI
  • 10. LV BUSHING  Low voltage leads for ratings in the 1 .2 kV Class are normally brought through the tank wall using an indoor bushing. This is a cast resin or porcelain bushing 10S.AYYADURAI
  • 11. Insulating liquid  The insulating liquid in substation transformers is conventional transformer oil  When makeup liquid is required, use only approved fluid of the same type that is in the transformer.  It is important to check the proper liquid level in the transformer at all times by periodically observing the liquid level gauge.  In addition, the dielectric strength of the insulating liquid must be maintained at a high value. A sample of the liquid will be tested within one week after energisation, and annually thereafter. 11S.AYYADURAI
  • 12. Power transformer- protection devices – Buchholz (Gas) Relay  The Buchholz protection is a mechanical fault detector for electrical faults in oil-immersed transformers.  The Buchholz (gas) relay is placed in the piping between the transformer main tank and the oil conservator.  The conservator pipe must be inclined slightly for reliable operation. S.AYYADURAI 12
  • 13. Buchholz (Gas) Relay  The Buchholz protection is a fast and sensitive fault detector.  It works independent of the number of transformer windings, tap changer position and instrument transformers. If the tap changer is of the on-tank (container) type, having its own oil enclosure with oil conservator, there is a dedicated Buchholz relay for the tap changer.  A typical Buchholz protection comprises a pivoted float (F) and a pivoted vane (V) as shown in Figure 1.  The float carries one mercury switch and the vane also carries another mercury switch. Normally, the casing is filled with oil and the mercury switches are open. S.AYYADURAI 13
  • 14. Buchholz (Gas) Relay S.AYYADURAI 14 When minor fault occurs… within the transformer. Gases produced by minor faults rise from the fault location to the top of the transformer. Then the gas bubbles pass up the piping to the conservator. The gas bubbles will be trapped in the casing of the Buchholz protection. This means that the gas replaces the oil in the casing. As the oil level falls, the float (F) will follow and the mercury switch tilts and closes an alarm circuit.
  • 15. Buchholz (Gas) Relay S.AYYADURAI 15 When major fault occurs… It is also assumed that a major fault, either to earth of between phases or windings, occurs within the transformer. Such faults rapidly produce large volumes of gas (more than 50 cm3/(kWs) and oil vapor which cannot escape. They therefore produce a steep buildup of pressure and displace oil. This sets up a rapid flow from the transformer towards the conservator. The vane (V) responds to high oil and gas flow in the pipe to the conservator. In this case, the mercury switch closes a trip circuit. The operating time of the trip contact depends on the location of the fault and the magnitude of the fault current.
  • 16. Buchholz (Gas) Relay S.AYYADURAI 16 • The gas accumulator relay also provides a long-term accumulation of gasses associated with overheating of various parts of the transformer conductor and insulation systems. • This will detect fault sources in their early stages and prevent significant damage. • When the transformer is first put into service, the air trapped in the windings may give unnecessary alarm signals. It is customary to remove the air in the power transformers by vacuum treatment during the filling of the transformer tank with oil. • The gas accumulated without this treatment will, of course, be air, which can be confirmed by seeing that it is not inflammable.
  • 17. Pressure Relay S.AYYADURAI 17 Many power transformers with an on-tank-type tap changer have a pressure protection for the separate tap changer oil compartment. This protection detects a sudden rate-of-increase of pressure inside the tap changer oil enclosure. When the pressure in front of the piston exceeds the counter force of the spring, the piston will move operating the switching contacts. The micro switch inside the switching unit is hermetically sealed and pressurized with nitrogen gas.
  • 18. Pressure Relay S.AYYADURAI 18 An internal fault in an oil-filled transformer is usually accompanied by overpressure in the transformer tank. The simplest form of pressure relief device is the widely used frangible disk. The surge of oil caused by a heavy internal fault bursts the disk and allows the oil to discharge rapidly. Relieving and limiting the pressure rise prevent explosive rupture of the tank and consequent fire.
  • 20. Pressure Relay S.AYYADURAI 20 A drawback of the frangible disk is that the oil remaining in the tank is left exposed to the atmosphere after a rupture. This is avoided in a more effective device, the pressure relief valve, which opens to allow the discharge of oil if the pressure exceeds the pre-adjusted limit. By providing the transformer with a pressure relief valve, the overpressure can be limited to a magnitude harmless to the transformer. If the abnormal pressure is relatively high, this spring- controlled valve can operate within a few milliseconds and provide fast tripping when suitable contacts are fitted.  The valve closes automatically as the internal pressure falls below a critical level.
  • 21. Oil Level Monitor Device S.AYYADURAI 21 Transformers with oil conservator(s) (expansion tank) often have an oil level monitor. Usually, the monitor has two contacts for alarm. One contact is for maximum oil level alarm and the other contact is for minimum oil level alarm.
  • 22. capillary-type top-oil thermometer S.AYYADURAI 22 The figure shows the construction of a capillary-type top-oil thermometer, where the bulb is situated in a “pocket” surrounded by oil on top of the transformer. The bulb is connected to the measuring bellow inside the main unit via a capillary tube. The bellow moves the indicator through mechanical linkages, resulting in the operation of the contacts at set temperatures.
  • 23. capillary-type top-oil thermometer S.AYYADURAI 23 •The top-oil temperature may be considerably lower than the winding temperature, especially shortly after a sudden load increase. •This means that the top-oil thermometer is not an effective overheating protection. •However, where the policy towards transformers’ loss of life permits, tripping on top-oil temperature may be satisfactory. This has the added advantage of directly monitoring the oil temperature to ensure that it does not reach the flash temperature.
  • 24. Winding Thermometer S.AYYADURAI 24 The winding thermometer, shown in the figure below, responds to both the top-oil temperature and the heating effect of the load current.
  • 25. Winding Thermometer S.AYYADURAI 25 The winding thermometer creates an image of the hottest part of the winding. The top-oil temperature is measured .  The measurement is further expanded with a current signal proportional to the loading current in the winding. This current signal is taken from a current transformer located inside the bushing of that particular winding. This current is lead to a resistor element in the main unit. This resistor heats up, and as a result of the current flowing through it, it will in its turn heat up the measurement bellow, resulting in an increased indicator movement.Top-oil thermometer and winding thermometer main units fitted on the side of a power transformer
  • 26. Winding Thermometer S.AYYADURAI 26 . The winding thermometer can have one to four contacts, which sequentially close at successively higher temperature. With four contacts fitted, the two lowest levels are commonly used to start fans or pumps for forced cooling, the third level to initiate an alarm and the fourth step to trip load breakers or de-energize the transformer or both. In case a power transformer is fitted with top-oil thermometer and winding thermometer, the latter one normally takes care of the forced cooling control.