TALAT Lectures 2504


                      Examples and Applications
                                 20 pages, 16 Figures

                                     Basic Level

      prepared by Steinar Lundberg, Hydro Aluminium Structures, Karmoy




Objectives:

− to calculate the required fire resistance of uninsulated and insulated load bearing
  structural members such as columns and beams on the basis of a simple calculation
  method and according to ENV 1999-1-2
− to point out more refined methods of analysis with the aid of computer programmes
− to present some approved and existing fire resistance rated applications, e.g. in the
  off-shore industry


Prerequisites:

− background in structural engineering
− TALAT lectures no. 2501-2503

REVICED NOVEMBER 1997 in connection with the Leonardo da Vinci project:
TAS/WP 1 by Steinar Lundberg.



Date of Issue: 1998
 EAA - European Aluminium Association
2504 Examples and Applications




Contents

2504    Examples and Applications ......................................................................2
 2504.01 Calculation Examples ................................................................................. 3
    2504.01.01 Simplified Method ................................................................................3
        a) Uninsulated Column ....................................................................................... 3
        b) Uninsulated Floor Beam ................................................................................ 6
        c) Insulated Column Inside a Wall...................................................................... 8
        d)Insulated Freestanding Column .................................................................... 10
        e) Insulated Beam ............................................................................................. 12
    2504.01.02 Computer Analysis..............................................................................14
 2504.02 Products ................................................................................................... 17
    2504.02.01 Prefabricated Fire Rated Walls ...........................................................17
    2504.02.02 Heat Radiation Shield .........................................................................18
    2504.02.03 Fire Rated Doors .................................................................................18
    2504.02.04 Fire Rated Penetrations .......................................................................19
 2504.03 References/Literature ............................................................................... 19
 2504.04 List of Figures............................................................................................ 20




TALAT 2504                                                     2
2504.01 Calculation Examples

          • Simplified method for temperature analysis, ENV 1999-1-2 for mechanical
            response
            − Uninsulated column
            − Uninsulated beam
            − Insulated column inside a wall
            − Insulated freestanding column
            − Insulated beam
          • Computer analysis for temperature development




2504.01.01 Simplified Method


         a) Uninsulated Column

The column is standing outside the building, but can be exposed to the fire through
window openings. The column is RHS 250 x10 and the required fire resistance is 10
minutes. The span of the column is 8000 mm and it is simply supported in both ends
(see Figure 2504.01.01). It is no welds in the column. The alloy and temper are EN AW
6082 T6 (f0 = 260 MPa).

The column is loaded with the following loads:

       • permanent loads: 150 kN
       • imposed loads:   330 kN

Partiell coefficient for permanent loads is, γG = 1,10 and for variable loads, γQ = 1,50.

The bearing capacity according to ENV 1999-1-1 is calculated to:

              Nb,Rd = 767 kN

The design value of the axial force:

              NEd = 1,10⋅150 kN + 1,50⋅330 kN = 660 kN




TALAT 2504                                      3
alu
                                                          Schema of the uninsulated column   2504.01.01
         Training in Aluminium Application Technologies




F/V calculated according to Figure 2503.03.01:

               F            3 ⋅ 0, 25
                 =                             = 78
               V 0, 25 ⋅ 0, 01⋅ 4 − 0, 012 ⋅ 4

Using Figure 2504.01.02 with the following input

               •         10 mins. fire resistance
               •         resulting emissivity = 0,2
               •         F/V = 78

the metal temperature of the column is 185 °C.

If the window breaks, and the flames engulf the column, the resulting emissivity must
be: εr = 0,7. The metal temperature of the column can be found from Figure 2503.03.04
With the following input:
             • 10 mins. Fire resistance
             • resulting emissivity = 0,7
             • F/V = 78

the metal temperature of the column is 410 °C.




TALAT 2504                                                                  4
Metal Temperature - Time Curves for εr = 0,2

                                                                                     600



                                               Metal temperature in degree Celsius
                                                                                     500
                                                                                                                     200        125
                                                                                     400
                                                                                                          300        150    100

                                                                                     300
                                                                                                                           75
                                                                                                                                  50
                                                                                                                                          37
                                                                                     200
                                                                                     185                                                  25
                                                                                     100

                                                                                      0
                                                                                           0          5         10         15        20        25   30
                                                                                                                     Time in minutes


                                              alu
                                                                                               Metal Temperature - Time Curves for εr = 0,2              2504.01.02
       Training in Aluminium Application Technologies




The 0,2% proof stress ratio, k0.2,θ , is found from ENV 1999-1-2 Table 3.1:

                                                                                                          0,79 − 0,65
      for 185 °C: k 0.2 ,θ = 0,79 −                                                                                   ⋅ 35 = 0,69
                                                                                                              50

                                                                                                          0,11 − 0
      for 410 °C: k 0.2 ,θ = 0,11 −                                                                                ⋅ 60 = 0,08
                                                                                                            200

The design buckling resistance of the column at 10 mins fire exposure, according to
ENV 1999-1-2, 4.2.2.4:

                                                                                                                               γ M1                            110
                                                                                                                                                                ,
      for 185 °C: N b , fi ,10, Rd = k 0.2 ,θ ⋅ N b , Rd ⋅                                                                                 = 0,69 ⋅ 767 kN ⋅           = 485kN
                                                                                                                            1,2 ⋅ γ M , fi                   1,2 ⋅ 1,0

                                                                                                                               γ M1                            110
                                                                                                                                                                ,
      for 410 °C: N b , fi ,10, Rd = k 0.2 ,θ ⋅ N b , Rd ⋅                                                                                 = 0,08 ⋅ 767 kN ⋅           = 56kN
                                                                                                                            1,2 ⋅ γ M , fi                   1,2 ⋅ 1,0

The design value of the axial force in a fire situation (accidental situation):

                        NEd = 1,00⋅150 kN + 1,00⋅330 kN = 480 kN

If the column is not engulfed in flames (εr = 0,2) the column will stand in 10 mins in an
internal fire in the building, if the column may be engulfed in flames (εr = 0,7) it has to
be fire protected.

The temperature of the column may also be calculated on the basis of a simplified
calculation method for thermal actions for external members. This method is described


TALAT 2504                                                                                                                            5
in ENV 1991-2-2 Annex C (Thermal actions for external members - simplified
calculation method) and in ENV 1999-1-2 Annex B (Heat transfer to external
aluminium structures). This method will probably give lower temperature in the
aluminium column.



         b) Uninsulated Floor Beam

The beam is bearing insulated floor elements and will be exposed directly to the fire (see
Figure 2504.01.03). The bottom flange of the beam is 20 mm thick. The required fire
resistance is 15 min. The span of the beam is 5000 mm. The alloy and temper are EN
AW 6082 T6 (f0 = 260 MPa).




                                                alu
                                                          Schema of the uninsulated Floor Beam   2504.01.03
         Training in Aluminium Application Technologies




The beam is loaded with the following loads:

       • permanent loads: 3,0 kN/m
       • imposed loads:   12,0 kN/m

Partiell coefficient for permanent loads is, γG = 1,10 and for variable loads, γQ = 1,50.

The bearing capacity according to ENV 1999-1-1 is calculated to:

                    Mc,Rd = 123 kNm

The design value of the bending moment at normal temperature:

                    MEd = 1/8(1,10⋅3,0 kN/m + 1,50⋅12,0 kN/m)(5,0m)2 = 66,6 kNm




TALAT 2504                                                                      6
The design value of the bending moment in a fire situation:

                                 MEd = 1/8(1,0⋅3,0 kN/m + 1,0⋅12,0 kN/m)(5,0m)2 = 46,9 kNm

F/V calculated according to Figure 2503.03.01

                                  F   1
                                    =     = 50
                                  V 0, 02

Using Figure 2504.01.04 with the following input

                                 •         15 min fire resistance
                                 •         resulting emissivity = 0,7
                                 •         F/V = 50

we find the metal temperature of the beam to be 450 °C.



                                Metal Temperature - Time Curves for εr = 0,7
                                                                                 600
                                           Metal temperature in degree Celsius




                                                                                                   300              100
                                                                                 500
                                                                                                         150
                                                                                 450               200              75
                                                                                 400
                                                                                                    125
                                                                                                                    50
                                                                                 300
                                                                                                                    37
                                                                                                                         25
                                                                                 200


                                                                                 100


                                                                                   0
                                                                                       0       5               10        15        20   25   30
                                                                                                                    Time in minutes



                                         alu
                                                                                       Metal Temperature - Time Curves for εr = 0,7           2504.01.04
  Training in Aluminium Application Technologies




The 0,2% proof stress ratio, k0.2,θ , is found from ENV 1999-1-2 Table 3.1:

                                                                                            0,11 − 0
                                  k 0.2 ,θ = 0,11 −                                                  ⋅ 100 = 0,055
                                                                                              200




TALAT 2504                                                                                                                    7
The design moment resistance of the beam at 15 min fire exposure and for a uniform
distributed temperature, according to ENV 1999-1-2, 4.2.2.3:

                                                 γ M1                        110
                                                                              ,
          M fi ,15, Rd = k 0.2 ,θ ⋅ M c , Rd ⋅            = 0,055 ⋅ 123kNm ⋅     = 7,4 kNm
                                                 γ M , fi                    1,0


          M fi ,15, Rd = 7,4 kNm ≤ M Ed = 66,6kN


The beam has to be fire protected. If a computer software is used for the temperature
analysis, the rules for a non-uniform temperature distribution can be used. These rules
will give a higher design moment resistance than the above calculated one, but not so
high as required.


         c) Insulated Column Inside a Wall

The column is standing inside a fire rated wall, and the lining of the wall is passing the
column (see Figure 2504.01.05). The lining consists of 18 mm gypsum boards and the
required fire resistance is 30 min. The column is a channel U 150 x 75 x 6 x 9 and the
alloy EN AW 6063 T6. (f0 = 170 MPa)

The span of the wall is 3300 mm, the column is prevented against buckling about the
weak axis and it is simply supported in both ends. It is no welds in the column.

The column is loaded with the following loads:

       • permanent loads: 15 kN
       • imposed loads:   60 kN

Partiell coefficient for permanent loads is, γG = 1,10 and for variable loads, γQ = 1,50.

The bearing capacity according to ENV 1999-1-1 is calculated to:

         Nb,Rd = 226 kN

The design value of the axial force at normal temperature:

         NEd = 1,10⋅15 kN + 1,50⋅60 kN = 106,5 kN

The design value of the axial force in fire situation:

         NEd = 1,0⋅15 kN + 1,0⋅60 kN = 75 kN




TALAT 2504                                                    8
alu
                                                           Schema of the insulated column inside a wall     2504.01.05
          Training in Aluminium Application Technologies




Fi/V is calculated according to Figure 2503.03.06:

                  Fi     1
                     =       = 111
                  V    0,009

Figure 2503.03.08 gives the insulation correction factor:

                C = 1/160 * 111 + 0,5 = 1,19

The equivalent insulation thickness is

                tequ = 1,19 * 18 mm = 21,4 mm

Figure 2503.03.11 gives a metal temperature of the column of 250 °C.

The 0,2% proof stress ratio, k0.2,θ , is found from ENV 1999-1-2 Table 3.1:

                 k 0.2 ,θ = 0,38

The design buckling resistance of the column at 30 mins fire exposure, according to
ENV 1999-1-2, 4.2.2.4:

                                                                        γ M1                           110
                                                                                                        ,
         N b , fi ,30, Rd = k 0.2 ,θ ⋅ N b , Rd ⋅                                   = 0,38 ⋅ 226kN ⋅           = 78,7 kN
                                                                     1,2 ⋅ γ M , fi                  1,2 ⋅ 1,0

         N b , fi ,30, Rd = 78,7 kN ≥ N Ed = 75kN


TALAT 2504                                                                         9
d)Insulated Freestanding Column

The column is insulated by a 70 mm vermiculite board (see Figure 2504.01.06). The
required fire resistance is 60 min. The column is a RHS 250 x 10, the alloy and temper
are EN AW 6082 T6 (f0 = 260 MPa). The span of the column is 8000 mm, and it is
simply supported in both ends. It is no welds in the column. The column is similar to
that in the first example about the external column.




                                                                Vermiculite



                                    Aluminium




                                                alu
                                                          Schema of the insulated Freestanding column   2504.01.06
         Training in Aluminium Application Technologies




The column is loaded with the following loads:

       • permanent loads: 150 kN
       • imposed loads:   330 kN

Partiell coefficient for permanent loads is, γG = 1,10 and for variable loads, γQ = 1,50.

The bearing capacity according to ENV 1999-1-1 is calculated to:

                    Nb,Rd = 767 kN

The design value of the axial force for normal temperature:

                    NEd = 1,10⋅150 kN + 1,50⋅330 kN = 660 kN

The design value of the axial force in fire situation:

                    NEd = 1,0⋅150 kN + 1,0⋅330 kN = 480 kN


TALAT 2504                                                                        10
Fi/V is calculated according to Figure 2503.03.06 (TALAT Lecture 2503):

                         Fi           0, 25 ⋅ 4
                            =                             = 104
                         V 0, 25 ⋅ 4 ⋅ 0, 01 − 0, 012 ⋅ 4

Figure 2503.03.08 gives the insulation correction factor

                        C = 1/625 * 104 + 0,8 = 0,97

Equivalent insulation thickness

                        tequ = 0,97 * 70 mm = 68 mm


                                                Equivalent Insulation Thickness Versus Metal
                                                  Temperature for 60 Min Fire Resistance
                                                                           600
                                                                           550
                                    Metal temperature in degree Celsius




                                                                           500
                                                                           450                                      300
                                                                                                          150
                                                                           400
                                                                           350                      100             200

                                                                           300
                                                                                                                  125
                                                                           250                          75

                                                                           200                37     50

                                                                           150
                                                                                                   25
                                                                           100
                                                                                50
                                                                                 0
                                                                                  0   12,5   25    37,5      50     62,5   75   87,5   100 112,5 125
                                                                                                   Equivalent insulation thickness in mm


                                                                                        Equivalent Insulation Thickness Versus Metal
                                                                          alu
                                                                                          Temperature for 60 Min Fire Resistance                  2504.01.07
       Training in Aluminium Application Technologies




Figure 2504.01.07 shows the metal temperature of the column to be 180 °C.

The 0,2% proof stress ratio, k0.2,θ , is found from ENV 1999-1-2 Table 3.1:

                                                                                      0,79 − 0,65
              k 0.2 ,θ = 0,79 −                                                                   ⋅ 30 = 0,71
                                                                                          50

The design buckling resistance of the column at 60 mins fire exposure, according to
ENV 1999-1-2, 4.2.2.4:

                                                                                                        γ M1                            110
                                                                                                                                         ,
               N b , fi ,60, Rd = k 0.2 ,θ ⋅ N b , Rd ⋅                                                             = 0,71 ⋅ 767 kN ⋅           = 499 kN
                                                                                                     1,2 ⋅ γ M , fi                   1,2 ⋅ 1,0




TALAT 2504                                                                                                                 11
N b , fi ,60, Rd = 499 kN ≥ N Ed = 480kN


         e) Insulated Beam

The floor beam as shown in Figure 2504.01.08 is insulated with 75 mm rockwool with
density 120 kg/m³. The required fire resistance is 90 minutes. The beam is an I 450 x
200 x 12 x 25. The span of the beam is 8000 mm. The alloy and temper are EN AW
6082 T6 (f0 = 260 MPa).


                                                                     Calculation Example

                                                            Insulated floor beam
                                                           90 min. fire resistance

                                                                  20 kN/ m


                                                                                                    Beam: I 450 x 200 x 12 x 25
                                                                    8000
                                                                                                    Alloy: 6082 - T6
                                                                                                           I = 515.8 x 106 mm4
                                                                                                          W = 2.29 x 106 mm3
                                                               Cross section:

                     Floor
                                                                                            Insulation
                                                                                     Beam



                                                 alu
                                                                  Insulated Beam: Calculation Example                     2504.01.08
          Training in Aluminium Application Technologies




The beam is loaded with the following loads:

       • permanent loads: 4,0 kN/m
       • imposed loads:   16,0 kN/m

Partiell coefficient for permanent loads is, γG = 1,10 and for variable loads, γQ = 1,50.

The bearing capacity according to ENV 1999-1-1 is calculated to:

         Mc,Rd = 617 kNm

The design value of the bending moment at normal temperature:

         MEd = 1/8(1,10⋅4,0 kN/m + 1,50⋅16,0 kN/m)(8,0m)2 = 227 kNm

This over-capacity is caused by the deflection criteria which states that the maximum
allowable deflection is 1/250 of span. This beam has a deflection in the middle of the
span of 1/270 of span.



TALAT 2504                                                                                  12
The design value of the bending moment in a fire situation:

        MEd = 1/8(1,0⋅4,0 kN/m + 1,0⋅16,0 kN/m)(8,0m)2 = 160 kNm


Fi/V is calculated according to Figure 2503.03.06

           Fi           0,45 ⋅ 2 + 0,2
              =                               = 74
           V    0,2 ⋅ 0,025 ⋅ 2 + 0,4 ⋅ 0,012

From Figure 2503.03.08 the insulation correction factor is determined as C = 1,0. The
equivalent insulation thickness is tequ = 1,0 * 75 mm = 75 mm.



                                Equivalent Insulation Thickness Versus Metal
                                  Temperature for 90 Min Fire Resistance
                                                                              600
                                                                              550
                                       Metal temperature in degree Celsius




                                                                              500
                                                                              450
                                                                                                                                   300
                                                                              400
                                                                                                                                 200
                                                                              350
                                                                                                                     125
                                                                              300                                            150

                                                                              250                                          100
                                                                                                                 75
                                                                              200
                                                                                                                 50
                                                                              150                          37
                                                                                                      25
                                                                              100
                                                                                   50
                                                                                   0
                                                                                    25    37,5   50    62,5     75     87,5 100 112,5 125 137,5 150
                                                                                                  Equivalent insulation thickness in mm

                                                                                            Equivalent Insulation Thickness Versus Metal
                                                                             alu

                                                                                              Temperature for 90 Min Fire Resistance                  2504.01.09
        Training in Aluminium Application Technologies




The metal temperature in the beam is 230 °C (Figure 2504.01.09).

The 0,2% proof stress ratio, k0.2,θ , is found from ENV 1999-1-2 Table 3.1:

                                                                                        0,65 − 0,38
          k 0.2 ,θ = 0,65 −                                                                         ⋅ 30 = 0,49
                                                                                            50

The design moment resistance of the beam at 90 mins fire exposure and for a uniform
distributed temperature, according to ENV 1999-1-2, 4.2.2.3:

                                                                                                       γ M1                        110
                                                                                                                                    ,
           M fi ,15, Rd = k 0.2 ,θ ⋅ M c , Rd ⋅                                                                 = 0,49 ⋅ 617 kNm ⋅     = 333kNm
                                                                                                       γ M , fi                    1,0

           M fi ,15, Rd = 333kNm ≥ M Ed = 160kNm


TALAT 2504                                                                                                                         13
2504.01.02 Computer Analysis

In this example a computer analysis programme is used to find the metal temperature of
the aluminium structure. The programme used is called TASEF (Temperature Analysis
of Structures Exposed to Fire) and has been developed by Statens Provningsanstalt in
Sweden. The programme is commercialized. [18]

The structure which is analyzed is the same as shown in Figure 2504.01.08. The cross
section of the insulated floor beam is divided into a grid of nodes, for which the
temperature rise is calculated by the computer analysis programme (Figure 2504.01.10).
The nodes No. 31 and 38 get the highest temperatures, they will also be the nodes with
the highest stress. The temperature rise at node 31 and 38 is shown in Figure
2504.01.11. The temperature in nodes no 31 and 38 after 90 min exposure is 207 °C.
Using the simplified method the temperature was calculated to 230 °C.


                             Aluminium beam
                                 0                        0.100     0.175     0.300
                    0        1                                                    7   y
                                                                                          Metal temperature in degree Celsius




                             8                                                   14
                                                                                                                                80
                      15                                                        21
                0.100 22                                                        28

                                                                                                                                60


                                                                                                                                40


                                                                                                                                20


                                                                                                                                 0
                                                                                                                                     0      0.3    0.6     0.9     1.2   1.5
                                                          31
                      29                                                         35
                                                                                                                                               Exposure time in hour
                0.450 36                                       38                42
                      43                                                         49
                      50                                                         56                                                      Mean Temperature rise of the
                0.525 57                                                         63                                                      Insulated beam
                               x



                                                                      Relation Between Mean Rise of Temperature
                                                alu

                                                                                and Duration of Exposure
                                                                                                                                                                  2504.01.10
         Training in Aluminium Application Technologies




TALAT 2504                                                                                                                      14
250


                                                              200


                                                              150


                                                              100


                                                              50


                                                               0
                                                                    0         0,5            1           1,5
                                                                            Exposure time in hour



                                                               Temperature evolution at node 31 and 38 of the
                                                     alu
                                                                                                                  2504.01.11
             Training in Aluminium Application Technologies                  insulated beam



The temperature distribution in the whole model (all nodes) after 90 minutes standard
fire exposure is shown in Figure 2504.01.10. Temperatures at the "aluminium nodes"
are given in Figure 2504.01.12.




                                                              Temperature at the "aluminium nodes" after 90 min
                                               alu

                                                                                of exposure
                                                                                                                  2504.01.12
        Training in Aluminium Application Technologies




To analyze the temperature rise in an insulated construction with a computer programme
gives more exact results than the simplified calculation method described in TALAT
Lecture 2503. The simplified method, however, leads to results on the safe side and can
successfully be used.

(The input data and the results of the analysis are appended as copies of the computer
print-out.)



TALAT 2504                                                                                15
For the free standing column exposed to fire on all sides insulated with 70 mm
vermiculite board the 60 min. fire resistance was calculated earlier. The metal
temperature was found to be 180 °C. Using a computer analysis and a critical metal
temperature of 200 °C the insulation thicknesses for various insulation materials are
given in the table of Figure 2504.01.13.

Equally, for beams under a floor covered with a 100 mm insulation the necessary
insulation thicknesses for a critical metal temperature of 200 °C and fire resistances of
30, 60 and 90 minutes are computer calculated for various insulation materials as given
in the table of Figure 2504.01.14.

For gypsum boards and calcium silicate boards the simplified method gives inaccurate
values. The values in the figured tables are based on computer analysis and are more
correct than values calculated by use of the simplified method.




                                                                  Necessary insulation thicknesses for a beam under an insulated floor.
                                                         100 mm
                                                                  Thicknesses are calculated using 200 °C as critical metal temperature.


                                                           Section            In sulation m a teria l                  In sulation thickn ess
                                                                                                             30 m in            60 m in         90 m in
                                                                                                         fire re sista nce fire resistance fire re sista nce
                                                     I 30 0x20 0x12 x4 0   Ro ckwool, 1 20 kg/m              8 mm             24 m m            45 m m
                                                                           Ro ckwool, 3 00 kg/m              6 mm             16 m m            30 m m
                                                                           Ce ram ic fibre, 13 0 kg /m       7 mm             19 m m            35 m m
                                                                           G ypsum b oard s                 12 m m            30 m m            45 m m
                                                                           Ca lcium silikat boards          10 m m            25 m m            43 m m
                                                     I 30 0x20 0x8x20      Ro ckwool, 1 20 kg/m             16 m m            42 m m            72 m m
                                                                           Ro ckwool, 3 00 kg/m             11 m m            28 m m            48 m m
                                                                           Ce ram ic fibre, 13 0 kg /m      13 m m            33 m m            56 m m
                                                                           G ypsum b oard s                 15 m m            34 m m            47 m m
                                                                           Ca lcium silikat boards          17 m m            38 m m            60 m m
                                                     I 30 0x20 0x4x10      R ockw ool, 120 kg/m             29 m m            67 m m            105 m m
                                                                           R ockw ool, 300 kg/m             20 m m            45 m m            70 m m
                                                                           Ceram ic fibre, 130 kg/m         23 m m            52 m m            81 m m
                                                                           G ypsum boards                   21 m m            37 m m            54 m m
                                                                           C alcium silikat boards          29 m m            51 m m            80 m m


                                                              Necessary Insulation Thicknesses for a Beam Under
                                               alu
                                                                                                                                                 2504.01.14
        Training in Aluminium Application Technologies                        an Insulated Floor




TALAT 2504                                                                                                16
2504.02                                   Products


2504.02.01 Prefabricated Fire Rated Walls

Prefabricated walls are available with fire resistance characteristics from 30 minutes
standard fire to 120 minutes hydrocarbon fire. They are made of aluminium alloy
extrusions and sheets and insulation materials. These walls have also been used on oil
platforms in the North Sea during the last years. The advantages of these walls are their
light weight, the little maintenance needed and the easy erection.

The insulation of these walls is fixed on the unexposed side or in the middle if the wall
is to be exposed to the fire on both sides. The front plates protect the insulation against
the environment and distribute the windload to the side members. During a fire the front
plate will melt and the insulation will be directly exposed to the fire.

In all prefabricated walls for the oil industry (see Figure 2504.02.01) the insulation
material is non-combustible. In some countries combustible insulation is allowed to be
used with special approval from the authorities.




                                         alu          H 120 Rated Aluminium Prefabricated Wall Installed on
  Training in Aluminium Application Technologies   Hydro´sOil Patform Oseberg A in the North Sea .Autumn 1990.   2504.02.01


For that reason a sandwich structure with aluminium alloy sheets as skin and
combustible rigid foam as core frequently must be tested by a fire technology laboratory
before the authorities give their approval. Often some specific requirements have to be
met. These conditions can consist of limitations to where the approved structure may be
used, of requirements on specific properties of the material used in the structure and/or
of frequent production controls by an impartial institution.


TALAT 2504                                                                         17
2504.02.02 Heat Radiation Shield

Due to aluminium alloys' excellent reflection of heat radiation, shields of aluminium are
used as heat radiation shield (Figure 2504.02.02). There are, however, some limitations:
                  •        the shield must not be covered by soot during the heat radiation exposure.
                  •        the heat radiation on the shield must not exceed 15 kW/m² (exact calculation
                           must be performed).




                                         alu       Aluminium Heat Radiation Shield to Protect the Lifeboats
  Training in Aluminium Application Technologies    from Burning Blow Out on the Drilling Rig "West Delta".   2504.02.02




2504.02.03 Fire Rated Doors

Several fire doors in aluminium with a fire rate up to A60 (60 mins. fire resistance) are
available on the market. The doorleaf is fabricated of aluminium alloys and insulation,
while the doorframe is made of steel or stainless steel.

Both, hinged doors and sliding doors are fire classified.




TALAT 2504                                                                      18
2504.02.04 Fire Rated Penetrations

During the fabrication of a living quarter for an oil platform in the North Sea, entirely
built of aluminium alloys (Snorre), some manufacturers developed fire rated
penetrations with aluminium alloy sleeves and penetration frames.




2504.03 References/Literature


[1]    Drysdale, Dougal: An Introduction to Fire Dynamics. John Wiley & Sons. 1987,
       ISBN 0-471-90613-1

[2]    NFPA/SFPE: Handbook of Fire Protection Engineering. NFPA/SFPE. 1988,
       ISBN 0-87765-353-4

[3]    Sterner, E. / Wickstrøm, U.: TASEF - User Manual. Statens Provningsanstalt.
       1990, ISBN 91-7848-210-0

[4]    Landrø, Harald: Verification of the fire resistance of construction elements and
       structures. SINTEF 1983.

[5]    ISO 834-1975 (E). Fire resistance tests - Elements of building construction.

[6]    ECCS-TC3: European Recommendations for the Fire Safety of Steel Structures.
       Elsevier 1983. ISBN 0-444-42120-3

[7]    GYPROC: Gyproc Håndbok. 1986. (In Swedish).

[8]    Holmen, J.P.: Heat Transfer. McGraw-Hill. Publ. Comp. 1990. ISBN 0-07-
       909388-4

[9]    Aluminium-Zentrale (Ed.): Aluminium Taschenbuch. Aluminium Verlag
       Düsseldorf, 1983. ISBN 3-87017-169-3 (In German)

[10]   Carborundum Resistant Materials: Fiberfrax Manual 1987.

[11]   Elkem Rockwool: Innføring i passive brannsikring. 1991. (In Norwegian).

[12]   NBR: NS 3478. Design rules for structural member for fire resistance. 1979. (In
       Norwegian).




TALAT 2504                                    19
[13]   Hydro Aluminium Structures a.s: Revisjon av NS 3471, Kap. 14.2 Brannteknisk
       dimensjonering. 1992. (In Norwegian).

[14]   Andersson, Leif & Jansson, Bengt: En undersøkning av gipsskivans termiske
       egenskaper - Teori och försök. Lund University 1986 (In Swedish).

[15]   CEN/TC 250/SC 9: ENV 1999-1-2. Design of aluminium structures. Part 1.2.
       Structural fire design. 1997.

[16]   CEN/TC 250/SC 1: ENV 1991-2-2. Basis of design and actions on structures.
       Part 2.2. Actions on structures exposed to fire. 1995

[17]   CEN/TC 250/SC 9: ENV 1999-1-1. Design of aluminium structures. Part 1.1.
       General rules. 1997

[18]   Ulf Wickström, TASEF (Temperature Analysis of Structures Exposed to Fire),
       V. 3.0 PC, Computer Programme for the determination of fire resistance of
       structural elements with or without insulation. Swedish National Testing
       Institute



2504.04 List of Figures

Figure No.   Figure Title (Overhead)
2504.01.01   Schema of the Uninsulated Column
2504.01.02   Metal Temperature-Time Curves for εr = 0,2
2504.01.03   Schema of the Uninsulated Floor Beam
2504.01.04   Metal Temperature-Time Curves for εr = 0,7
2504.01.05   Schema of the Insulated Column Inside a Wall
2504.01.06   Schema of the Insulated Freestanding Column
2504.01.07   Equivalent Insulation Thickness Versus Metal Temperature for 60 Min Fire
             Resistance
2504.01.08   Insulated Beam: Calculation example
2504.01.09   Equivalent Insulation Thickness Versus Metal Temperature for 90 Min. Fire
             Resistance
2504.01.10   Relation Between Mean Rise of Temperature and Duration of Exposure
2504.01.11   Temperature Evolution at Nodes 31 and 38 of the Insulated Beam
2504.01.12   Temperatures at the Aluminium Nodes after 90 min of Exposure
2504.01.13   Necessary Insulation Thicknesses for a Column Exposed to Fire
2504.01.14   Necessary Insulation Thicknesses for a Beam Under an Insulated Floor
2504.02.01   H120 Rated Aluminium Prefabricated Wall Installed on Hydro’s Oil Platform
             Oseberg A in the North Sea Autumn 1990.
2504.02.02   Aluminium Heat Radiation Shield to Protect the Lifeboats From a Burning
             Blow Out on the Drilling Rig “West Delta“



TALAT 2504                                20

Más contenido relacionado

Similar a Examples and Applications of Fire Resistance Calculations for Aluminum Structures

Development Of A Pvdf Based Sensor
Development Of A Pvdf Based SensorDevelopment Of A Pvdf Based Sensor
Development Of A Pvdf Based SensorNuno Pimenta
 
Thermally Matched Strain Gauges (Mc Gough)
Thermally Matched Strain Gauges (Mc Gough)Thermally Matched Strain Gauges (Mc Gough)
Thermally Matched Strain Gauges (Mc Gough)pmcgough
 
006 column components
006 column components006 column components
006 column componentsnobleglass
 
006 column components
006 column components006 column components
006 column componentsnobleglass
 
Villar ciasem 2007
Villar ciasem 2007Villar ciasem 2007
Villar ciasem 2007Karina Mello
 
An integrated framework for analysis of stochastic models of biochemical reac...
An integrated framework for analysis of stochastic models of biochemical reac...An integrated framework for analysis of stochastic models of biochemical reac...
An integrated framework for analysis of stochastic models of biochemical reac...Michal Komorowski
 
Original PNP Transistor BC557C C557C 557 TO-92 New
Original PNP Transistor BC557C C557C 557 TO-92 NewOriginal PNP Transistor BC557C C557C 557 TO-92 New
Original PNP Transistor BC557C C557C 557 TO-92 NewAUTHELECTRONIC
 
Original PNP Transistor BC556BG 556B BC556B BC556 556 TO-92 New
Original PNP Transistor BC556BG 556B BC556B BC556 556 TO-92 NewOriginal PNP Transistor BC556BG 556B BC556B BC556 556 TO-92 New
Original PNP Transistor BC556BG 556B BC556B BC556 556 TO-92 NewAUTHELECTRONIC
 
Catalog MCCB dòng BW0 Fuji Electric mới nhất 2019
Catalog MCCB dòng BW0 Fuji Electric mới nhất 2019Catalog MCCB dòng BW0 Fuji Electric mới nhất 2019
Catalog MCCB dòng BW0 Fuji Electric mới nhất 2019CTY TNHH HẠO PHƯƠNG
 
5141 2015 Yi_Ren lab report
5141 2015 Yi_Ren lab report5141 2015 Yi_Ren lab report
5141 2015 Yi_Ren lab reportYi Ren
 
Low voltage-insulators-spacing-columns
Low voltage-insulators-spacing-columnsLow voltage-insulators-spacing-columns
Low voltage-insulators-spacing-columnsTeknomega S.r.l.
 
Eaf Makale
Eaf MakaleEaf Makale
Eaf Makalemetudgn
 
NEW INNOVATIONS IN ARC FURNACE TECHNOLOGY BY CVS MAKINA
NEW INNOVATIONS IN ARC FURNACE TECHNOLOGY BY CVS MAKINANEW INNOVATIONS IN ARC FURNACE TECHNOLOGY BY CVS MAKINA
NEW INNOVATIONS IN ARC FURNACE TECHNOLOGY BY CVS MAKINAmetudgn
 

Similar a Examples and Applications of Fire Resistance Calculations for Aluminum Structures (20)

Csbmm 2003 villar
Csbmm 2003 villarCsbmm 2003 villar
Csbmm 2003 villar
 
Development Of A Pvdf Based Sensor
Development Of A Pvdf Based SensorDevelopment Of A Pvdf Based Sensor
Development Of A Pvdf Based Sensor
 
Thermally Matched Strain Gauges (Mc Gough)
Thermally Matched Strain Gauges (Mc Gough)Thermally Matched Strain Gauges (Mc Gough)
Thermally Matched Strain Gauges (Mc Gough)
 
006 column components
006 column components006 column components
006 column components
 
006 column components
006 column components006 column components
006 column components
 
Taconic Tac-LED-10
Taconic Tac-LED-10Taconic Tac-LED-10
Taconic Tac-LED-10
 
Villar ciasem 2007
Villar ciasem 2007Villar ciasem 2007
Villar ciasem 2007
 
Ws sinamics-sm150-gm150-igbt-ru c
Ws sinamics-sm150-gm150-igbt-ru cWs sinamics-sm150-gm150-igbt-ru c
Ws sinamics-sm150-gm150-igbt-ru c
 
An integrated framework for analysis of stochastic models of biochemical reac...
An integrated framework for analysis of stochastic models of biochemical reac...An integrated framework for analysis of stochastic models of biochemical reac...
An integrated framework for analysis of stochastic models of biochemical reac...
 
Extending Asphalt Pavement Life Using Thin Whitetopping
Extending Asphalt Pavement Life Using Thin WhitetoppingExtending Asphalt Pavement Life Using Thin Whitetopping
Extending Asphalt Pavement Life Using Thin Whitetopping
 
Glamet panel
Glamet panelGlamet panel
Glamet panel
 
Original PNP Transistor BC557C C557C 557 TO-92 New
Original PNP Transistor BC557C C557C 557 TO-92 NewOriginal PNP Transistor BC557C C557C 557 TO-92 New
Original PNP Transistor BC557C C557C 557 TO-92 New
 
Original PNP Transistor BC556BG 556B BC556B BC556 556 TO-92 New
Original PNP Transistor BC556BG 556B BC556B BC556 556 TO-92 NewOriginal PNP Transistor BC556BG 556B BC556B BC556 556 TO-92 New
Original PNP Transistor BC556BG 556B BC556B BC556 556 TO-92 New
 
Csbmm 2002 otavio
Csbmm 2002 otavioCsbmm 2002 otavio
Csbmm 2002 otavio
 
Catalog MCCB dòng BW0 Fuji Electric mới nhất 2019
Catalog MCCB dòng BW0 Fuji Electric mới nhất 2019Catalog MCCB dòng BW0 Fuji Electric mới nhất 2019
Catalog MCCB dòng BW0 Fuji Electric mới nhất 2019
 
5141 2015 Yi_Ren lab report
5141 2015 Yi_Ren lab report5141 2015 Yi_Ren lab report
5141 2015 Yi_Ren lab report
 
Final
FinalFinal
Final
 
Low voltage-insulators-spacing-columns
Low voltage-insulators-spacing-columnsLow voltage-insulators-spacing-columns
Low voltage-insulators-spacing-columns
 
Eaf Makale
Eaf MakaleEaf Makale
Eaf Makale
 
NEW INNOVATIONS IN ARC FURNACE TECHNOLOGY BY CVS MAKINA
NEW INNOVATIONS IN ARC FURNACE TECHNOLOGY BY CVS MAKINANEW INNOVATIONS IN ARC FURNACE TECHNOLOGY BY CVS MAKINA
NEW INNOVATIONS IN ARC FURNACE TECHNOLOGY BY CVS MAKINA
 

Más de CORE-Materials

Testing Techniques for Composite Materials
Testing Techniques for Composite MaterialsTesting Techniques for Composite Materials
Testing Techniques for Composite MaterialsCORE-Materials
 
Composite Forming Techniques
Composite Forming TechniquesComposite Forming Techniques
Composite Forming TechniquesCORE-Materials
 
The role of technology in sporting performance
The role of technology in sporting performanceThe role of technology in sporting performance
The role of technology in sporting performanceCORE-Materials
 
Chemical analysis in the electron microscope
Chemical analysis in the electron microscopeChemical analysis in the electron microscope
Chemical analysis in the electron microscopeCORE-Materials
 
The scanning electron microscope
The scanning electron microscopeThe scanning electron microscope
The scanning electron microscopeCORE-Materials
 
The transmission electron microscope
The transmission electron microscopeThe transmission electron microscope
The transmission electron microscopeCORE-Materials
 
Electrons and their interaction with the specimen
Electrons and their interaction with the specimenElectrons and their interaction with the specimen
Electrons and their interaction with the specimenCORE-Materials
 
Electron microscopy and other techniques
Electron microscopy and other techniquesElectron microscopy and other techniques
Electron microscopy and other techniquesCORE-Materials
 
Microscopy with light and electrons
Microscopy with light and electronsMicroscopy with light and electrons
Microscopy with light and electronsCORE-Materials
 
TALAT Lecture 5301: The Surface Treatment and Coil Coating of Aluminium
TALAT Lecture 5301: The Surface Treatment and Coil Coating of AluminiumTALAT Lecture 5301: The Surface Treatment and Coil Coating of Aluminium
TALAT Lecture 5301: The Surface Treatment and Coil Coating of AluminiumCORE-Materials
 
TALAT Lecture 5205: Plating on Aluminium
TALAT Lecture 5205: Plating on AluminiumTALAT Lecture 5205: Plating on Aluminium
TALAT Lecture 5205: Plating on AluminiumCORE-Materials
 
TALAT Lecture 5203: Anodizing of Aluminium
TALAT Lecture 5203: Anodizing of AluminiumTALAT Lecture 5203: Anodizing of Aluminium
TALAT Lecture 5203: Anodizing of AluminiumCORE-Materials
 
TALAT Lecture 5202: Conversion Coatings
TALAT Lecture 5202: Conversion CoatingsTALAT Lecture 5202: Conversion Coatings
TALAT Lecture 5202: Conversion CoatingsCORE-Materials
 
TALAT Lecture 5105: Surface Treatment of Aluminium
TALAT Lecture 5105: Surface Treatment of AluminiumTALAT Lecture 5105: Surface Treatment of Aluminium
TALAT Lecture 5105: Surface Treatment of AluminiumCORE-Materials
 
TALAT Lecture 5104: Basic Approaches to Prevent Corrosion of Aluminium
TALAT Lecture 5104: Basic Approaches to Prevent Corrosion of AluminiumTALAT Lecture 5104: Basic Approaches to Prevent Corrosion of Aluminium
TALAT Lecture 5104: Basic Approaches to Prevent Corrosion of AluminiumCORE-Materials
 
TALAT Lecture 5103: Corrosion Control of Aluminium - Forms of Corrosion and P...
TALAT Lecture 5103: Corrosion Control of Aluminium - Forms of Corrosion and P...TALAT Lecture 5103: Corrosion Control of Aluminium - Forms of Corrosion and P...
TALAT Lecture 5103: Corrosion Control of Aluminium - Forms of Corrosion and P...CORE-Materials
 
TALAT Lecture 5102: Reactivity of the Aluminium Surface in Aqueous Solutions
TALAT Lecture 5102: Reactivity of the Aluminium Surface in Aqueous SolutionsTALAT Lecture 5102: Reactivity of the Aluminium Surface in Aqueous Solutions
TALAT Lecture 5102: Reactivity of the Aluminium Surface in Aqueous SolutionsCORE-Materials
 

Más de CORE-Materials (20)

Drawing Processes
Drawing ProcessesDrawing Processes
Drawing Processes
 
Testing Techniques for Composite Materials
Testing Techniques for Composite MaterialsTesting Techniques for Composite Materials
Testing Techniques for Composite Materials
 
Composite Forming Techniques
Composite Forming TechniquesComposite Forming Techniques
Composite Forming Techniques
 
The role of technology in sporting performance
The role of technology in sporting performanceThe role of technology in sporting performance
The role of technology in sporting performance
 
Chemical analysis in the electron microscope
Chemical analysis in the electron microscopeChemical analysis in the electron microscope
Chemical analysis in the electron microscope
 
The scanning electron microscope
The scanning electron microscopeThe scanning electron microscope
The scanning electron microscope
 
The transmission electron microscope
The transmission electron microscopeThe transmission electron microscope
The transmission electron microscope
 
Electron diffraction
Electron diffractionElectron diffraction
Electron diffraction
 
Electrons and their interaction with the specimen
Electrons and their interaction with the specimenElectrons and their interaction with the specimen
Electrons and their interaction with the specimen
 
Electron microscopy and other techniques
Electron microscopy and other techniquesElectron microscopy and other techniques
Electron microscopy and other techniques
 
Microscopy with light and electrons
Microscopy with light and electronsMicroscopy with light and electrons
Microscopy with light and electrons
 
Durability of Materials
Durability of MaterialsDurability of Materials
Durability of Materials
 
TALAT Lecture 5301: The Surface Treatment and Coil Coating of Aluminium
TALAT Lecture 5301: The Surface Treatment and Coil Coating of AluminiumTALAT Lecture 5301: The Surface Treatment and Coil Coating of Aluminium
TALAT Lecture 5301: The Surface Treatment and Coil Coating of Aluminium
 
TALAT Lecture 5205: Plating on Aluminium
TALAT Lecture 5205: Plating on AluminiumTALAT Lecture 5205: Plating on Aluminium
TALAT Lecture 5205: Plating on Aluminium
 
TALAT Lecture 5203: Anodizing of Aluminium
TALAT Lecture 5203: Anodizing of AluminiumTALAT Lecture 5203: Anodizing of Aluminium
TALAT Lecture 5203: Anodizing of Aluminium
 
TALAT Lecture 5202: Conversion Coatings
TALAT Lecture 5202: Conversion CoatingsTALAT Lecture 5202: Conversion Coatings
TALAT Lecture 5202: Conversion Coatings
 
TALAT Lecture 5105: Surface Treatment of Aluminium
TALAT Lecture 5105: Surface Treatment of AluminiumTALAT Lecture 5105: Surface Treatment of Aluminium
TALAT Lecture 5105: Surface Treatment of Aluminium
 
TALAT Lecture 5104: Basic Approaches to Prevent Corrosion of Aluminium
TALAT Lecture 5104: Basic Approaches to Prevent Corrosion of AluminiumTALAT Lecture 5104: Basic Approaches to Prevent Corrosion of Aluminium
TALAT Lecture 5104: Basic Approaches to Prevent Corrosion of Aluminium
 
TALAT Lecture 5103: Corrosion Control of Aluminium - Forms of Corrosion and P...
TALAT Lecture 5103: Corrosion Control of Aluminium - Forms of Corrosion and P...TALAT Lecture 5103: Corrosion Control of Aluminium - Forms of Corrosion and P...
TALAT Lecture 5103: Corrosion Control of Aluminium - Forms of Corrosion and P...
 
TALAT Lecture 5102: Reactivity of the Aluminium Surface in Aqueous Solutions
TALAT Lecture 5102: Reactivity of the Aluminium Surface in Aqueous SolutionsTALAT Lecture 5102: Reactivity of the Aluminium Surface in Aqueous Solutions
TALAT Lecture 5102: Reactivity of the Aluminium Surface in Aqueous Solutions
 

Último

Daily Lesson Plan in Mathematics Quarter 4
Daily Lesson Plan in Mathematics Quarter 4Daily Lesson Plan in Mathematics Quarter 4
Daily Lesson Plan in Mathematics Quarter 4JOYLYNSAMANIEGO
 
ROLES IN A STAGE PRODUCTION in arts.pptx
ROLES IN A STAGE PRODUCTION in arts.pptxROLES IN A STAGE PRODUCTION in arts.pptx
ROLES IN A STAGE PRODUCTION in arts.pptxVanesaIglesias10
 
ANG SEKTOR NG agrikultura.pptx QUARTER 4
ANG SEKTOR NG agrikultura.pptx QUARTER 4ANG SEKTOR NG agrikultura.pptx QUARTER 4
ANG SEKTOR NG agrikultura.pptx QUARTER 4MiaBumagat1
 
ICS2208 Lecture6 Notes for SL spaces.pdf
ICS2208 Lecture6 Notes for SL spaces.pdfICS2208 Lecture6 Notes for SL spaces.pdf
ICS2208 Lecture6 Notes for SL spaces.pdfVanessa Camilleri
 
Measures of Position DECILES for ungrouped data
Measures of Position DECILES for ungrouped dataMeasures of Position DECILES for ungrouped data
Measures of Position DECILES for ungrouped dataBabyAnnMotar
 
Oppenheimer Film Discussion for Philosophy and Film
Oppenheimer Film Discussion for Philosophy and FilmOppenheimer Film Discussion for Philosophy and Film
Oppenheimer Film Discussion for Philosophy and FilmStan Meyer
 
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...Nguyen Thanh Tu Collection
 
ClimART Action | eTwinning Project
ClimART Action    |    eTwinning ProjectClimART Action    |    eTwinning Project
ClimART Action | eTwinning Projectjordimapav
 
Keynote by Prof. Wurzer at Nordex about IP-design
Keynote by Prof. Wurzer at Nordex about IP-designKeynote by Prof. Wurzer at Nordex about IP-design
Keynote by Prof. Wurzer at Nordex about IP-designMIPLM
 
EMBODO Lesson Plan Grade 9 Law of Sines.docx
EMBODO Lesson Plan Grade 9 Law of Sines.docxEMBODO Lesson Plan Grade 9 Law of Sines.docx
EMBODO Lesson Plan Grade 9 Law of Sines.docxElton John Embodo
 
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...Postal Advocate Inc.
 
Dust Of Snow By Robert Frost Class-X English CBSE
Dust Of Snow By Robert Frost Class-X English CBSEDust Of Snow By Robert Frost Class-X English CBSE
Dust Of Snow By Robert Frost Class-X English CBSEaurabinda banchhor
 
TEACHER REFLECTION FORM (NEW SET........).docx
TEACHER REFLECTION FORM (NEW SET........).docxTEACHER REFLECTION FORM (NEW SET........).docx
TEACHER REFLECTION FORM (NEW SET........).docxruthvilladarez
 
4.16.24 Poverty and Precarity--Desmond.pptx
4.16.24 Poverty and Precarity--Desmond.pptx4.16.24 Poverty and Precarity--Desmond.pptx
4.16.24 Poverty and Precarity--Desmond.pptxmary850239
 
Presentation Activity 2. Unit 3 transv.pptx
Presentation Activity 2. Unit 3 transv.pptxPresentation Activity 2. Unit 3 transv.pptx
Presentation Activity 2. Unit 3 transv.pptxRosabel UA
 
Influencing policy (training slides from Fast Track Impact)
Influencing policy (training slides from Fast Track Impact)Influencing policy (training slides from Fast Track Impact)
Influencing policy (training slides from Fast Track Impact)Mark Reed
 
Field Attribute Index Feature in Odoo 17
Field Attribute Index Feature in Odoo 17Field Attribute Index Feature in Odoo 17
Field Attribute Index Feature in Odoo 17Celine George
 
Expanded definition: technical and operational
Expanded definition: technical and operationalExpanded definition: technical and operational
Expanded definition: technical and operationalssuser3e220a
 

Último (20)

Daily Lesson Plan in Mathematics Quarter 4
Daily Lesson Plan in Mathematics Quarter 4Daily Lesson Plan in Mathematics Quarter 4
Daily Lesson Plan in Mathematics Quarter 4
 
ROLES IN A STAGE PRODUCTION in arts.pptx
ROLES IN A STAGE PRODUCTION in arts.pptxROLES IN A STAGE PRODUCTION in arts.pptx
ROLES IN A STAGE PRODUCTION in arts.pptx
 
ANG SEKTOR NG agrikultura.pptx QUARTER 4
ANG SEKTOR NG agrikultura.pptx QUARTER 4ANG SEKTOR NG agrikultura.pptx QUARTER 4
ANG SEKTOR NG agrikultura.pptx QUARTER 4
 
ICS2208 Lecture6 Notes for SL spaces.pdf
ICS2208 Lecture6 Notes for SL spaces.pdfICS2208 Lecture6 Notes for SL spaces.pdf
ICS2208 Lecture6 Notes for SL spaces.pdf
 
Measures of Position DECILES for ungrouped data
Measures of Position DECILES for ungrouped dataMeasures of Position DECILES for ungrouped data
Measures of Position DECILES for ungrouped data
 
Oppenheimer Film Discussion for Philosophy and Film
Oppenheimer Film Discussion for Philosophy and FilmOppenheimer Film Discussion for Philosophy and Film
Oppenheimer Film Discussion for Philosophy and Film
 
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
 
ClimART Action | eTwinning Project
ClimART Action    |    eTwinning ProjectClimART Action    |    eTwinning Project
ClimART Action | eTwinning Project
 
Keynote by Prof. Wurzer at Nordex about IP-design
Keynote by Prof. Wurzer at Nordex about IP-designKeynote by Prof. Wurzer at Nordex about IP-design
Keynote by Prof. Wurzer at Nordex about IP-design
 
EMBODO Lesson Plan Grade 9 Law of Sines.docx
EMBODO Lesson Plan Grade 9 Law of Sines.docxEMBODO Lesson Plan Grade 9 Law of Sines.docx
EMBODO Lesson Plan Grade 9 Law of Sines.docx
 
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
 
Dust Of Snow By Robert Frost Class-X English CBSE
Dust Of Snow By Robert Frost Class-X English CBSEDust Of Snow By Robert Frost Class-X English CBSE
Dust Of Snow By Robert Frost Class-X English CBSE
 
TEACHER REFLECTION FORM (NEW SET........).docx
TEACHER REFLECTION FORM (NEW SET........).docxTEACHER REFLECTION FORM (NEW SET........).docx
TEACHER REFLECTION FORM (NEW SET........).docx
 
4.16.24 Poverty and Precarity--Desmond.pptx
4.16.24 Poverty and Precarity--Desmond.pptx4.16.24 Poverty and Precarity--Desmond.pptx
4.16.24 Poverty and Precarity--Desmond.pptx
 
Presentation Activity 2. Unit 3 transv.pptx
Presentation Activity 2. Unit 3 transv.pptxPresentation Activity 2. Unit 3 transv.pptx
Presentation Activity 2. Unit 3 transv.pptx
 
Paradigm shift in nursing research by RS MEHTA
Paradigm shift in nursing research by RS MEHTAParadigm shift in nursing research by RS MEHTA
Paradigm shift in nursing research by RS MEHTA
 
Influencing policy (training slides from Fast Track Impact)
Influencing policy (training slides from Fast Track Impact)Influencing policy (training slides from Fast Track Impact)
Influencing policy (training slides from Fast Track Impact)
 
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptxLEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
 
Field Attribute Index Feature in Odoo 17
Field Attribute Index Feature in Odoo 17Field Attribute Index Feature in Odoo 17
Field Attribute Index Feature in Odoo 17
 
Expanded definition: technical and operational
Expanded definition: technical and operationalExpanded definition: technical and operational
Expanded definition: technical and operational
 

Examples and Applications of Fire Resistance Calculations for Aluminum Structures

  • 1. TALAT Lectures 2504 Examples and Applications 20 pages, 16 Figures Basic Level prepared by Steinar Lundberg, Hydro Aluminium Structures, Karmoy Objectives: − to calculate the required fire resistance of uninsulated and insulated load bearing structural members such as columns and beams on the basis of a simple calculation method and according to ENV 1999-1-2 − to point out more refined methods of analysis with the aid of computer programmes − to present some approved and existing fire resistance rated applications, e.g. in the off-shore industry Prerequisites: − background in structural engineering − TALAT lectures no. 2501-2503 REVICED NOVEMBER 1997 in connection with the Leonardo da Vinci project: TAS/WP 1 by Steinar Lundberg. Date of Issue: 1998  EAA - European Aluminium Association
  • 2. 2504 Examples and Applications Contents 2504 Examples and Applications ......................................................................2 2504.01 Calculation Examples ................................................................................. 3 2504.01.01 Simplified Method ................................................................................3 a) Uninsulated Column ....................................................................................... 3 b) Uninsulated Floor Beam ................................................................................ 6 c) Insulated Column Inside a Wall...................................................................... 8 d)Insulated Freestanding Column .................................................................... 10 e) Insulated Beam ............................................................................................. 12 2504.01.02 Computer Analysis..............................................................................14 2504.02 Products ................................................................................................... 17 2504.02.01 Prefabricated Fire Rated Walls ...........................................................17 2504.02.02 Heat Radiation Shield .........................................................................18 2504.02.03 Fire Rated Doors .................................................................................18 2504.02.04 Fire Rated Penetrations .......................................................................19 2504.03 References/Literature ............................................................................... 19 2504.04 List of Figures............................................................................................ 20 TALAT 2504 2
  • 3. 2504.01 Calculation Examples • Simplified method for temperature analysis, ENV 1999-1-2 for mechanical response − Uninsulated column − Uninsulated beam − Insulated column inside a wall − Insulated freestanding column − Insulated beam • Computer analysis for temperature development 2504.01.01 Simplified Method a) Uninsulated Column The column is standing outside the building, but can be exposed to the fire through window openings. The column is RHS 250 x10 and the required fire resistance is 10 minutes. The span of the column is 8000 mm and it is simply supported in both ends (see Figure 2504.01.01). It is no welds in the column. The alloy and temper are EN AW 6082 T6 (f0 = 260 MPa). The column is loaded with the following loads: • permanent loads: 150 kN • imposed loads: 330 kN Partiell coefficient for permanent loads is, γG = 1,10 and for variable loads, γQ = 1,50. The bearing capacity according to ENV 1999-1-1 is calculated to: Nb,Rd = 767 kN The design value of the axial force: NEd = 1,10⋅150 kN + 1,50⋅330 kN = 660 kN TALAT 2504 3
  • 4. alu Schema of the uninsulated column 2504.01.01 Training in Aluminium Application Technologies F/V calculated according to Figure 2503.03.01: F 3 ⋅ 0, 25 = = 78 V 0, 25 ⋅ 0, 01⋅ 4 − 0, 012 ⋅ 4 Using Figure 2504.01.02 with the following input • 10 mins. fire resistance • resulting emissivity = 0,2 • F/V = 78 the metal temperature of the column is 185 °C. If the window breaks, and the flames engulf the column, the resulting emissivity must be: εr = 0,7. The metal temperature of the column can be found from Figure 2503.03.04 With the following input: • 10 mins. Fire resistance • resulting emissivity = 0,7 • F/V = 78 the metal temperature of the column is 410 °C. TALAT 2504 4
  • 5. Metal Temperature - Time Curves for εr = 0,2 600 Metal temperature in degree Celsius 500 200 125 400 300 150 100 300 75 50 37 200 185 25 100 0 0 5 10 15 20 25 30 Time in minutes alu Metal Temperature - Time Curves for εr = 0,2 2504.01.02 Training in Aluminium Application Technologies The 0,2% proof stress ratio, k0.2,θ , is found from ENV 1999-1-2 Table 3.1: 0,79 − 0,65 for 185 °C: k 0.2 ,θ = 0,79 − ⋅ 35 = 0,69 50 0,11 − 0 for 410 °C: k 0.2 ,θ = 0,11 − ⋅ 60 = 0,08 200 The design buckling resistance of the column at 10 mins fire exposure, according to ENV 1999-1-2, 4.2.2.4: γ M1 110 , for 185 °C: N b , fi ,10, Rd = k 0.2 ,θ ⋅ N b , Rd ⋅ = 0,69 ⋅ 767 kN ⋅ = 485kN 1,2 ⋅ γ M , fi 1,2 ⋅ 1,0 γ M1 110 , for 410 °C: N b , fi ,10, Rd = k 0.2 ,θ ⋅ N b , Rd ⋅ = 0,08 ⋅ 767 kN ⋅ = 56kN 1,2 ⋅ γ M , fi 1,2 ⋅ 1,0 The design value of the axial force in a fire situation (accidental situation): NEd = 1,00⋅150 kN + 1,00⋅330 kN = 480 kN If the column is not engulfed in flames (εr = 0,2) the column will stand in 10 mins in an internal fire in the building, if the column may be engulfed in flames (εr = 0,7) it has to be fire protected. The temperature of the column may also be calculated on the basis of a simplified calculation method for thermal actions for external members. This method is described TALAT 2504 5
  • 6. in ENV 1991-2-2 Annex C (Thermal actions for external members - simplified calculation method) and in ENV 1999-1-2 Annex B (Heat transfer to external aluminium structures). This method will probably give lower temperature in the aluminium column. b) Uninsulated Floor Beam The beam is bearing insulated floor elements and will be exposed directly to the fire (see Figure 2504.01.03). The bottom flange of the beam is 20 mm thick. The required fire resistance is 15 min. The span of the beam is 5000 mm. The alloy and temper are EN AW 6082 T6 (f0 = 260 MPa). alu Schema of the uninsulated Floor Beam 2504.01.03 Training in Aluminium Application Technologies The beam is loaded with the following loads: • permanent loads: 3,0 kN/m • imposed loads: 12,0 kN/m Partiell coefficient for permanent loads is, γG = 1,10 and for variable loads, γQ = 1,50. The bearing capacity according to ENV 1999-1-1 is calculated to: Mc,Rd = 123 kNm The design value of the bending moment at normal temperature: MEd = 1/8(1,10⋅3,0 kN/m + 1,50⋅12,0 kN/m)(5,0m)2 = 66,6 kNm TALAT 2504 6
  • 7. The design value of the bending moment in a fire situation: MEd = 1/8(1,0⋅3,0 kN/m + 1,0⋅12,0 kN/m)(5,0m)2 = 46,9 kNm F/V calculated according to Figure 2503.03.01 F 1 = = 50 V 0, 02 Using Figure 2504.01.04 with the following input • 15 min fire resistance • resulting emissivity = 0,7 • F/V = 50 we find the metal temperature of the beam to be 450 °C. Metal Temperature - Time Curves for εr = 0,7 600 Metal temperature in degree Celsius 300 100 500 150 450 200 75 400 125 50 300 37 25 200 100 0 0 5 10 15 20 25 30 Time in minutes alu Metal Temperature - Time Curves for εr = 0,7 2504.01.04 Training in Aluminium Application Technologies The 0,2% proof stress ratio, k0.2,θ , is found from ENV 1999-1-2 Table 3.1: 0,11 − 0 k 0.2 ,θ = 0,11 − ⋅ 100 = 0,055 200 TALAT 2504 7
  • 8. The design moment resistance of the beam at 15 min fire exposure and for a uniform distributed temperature, according to ENV 1999-1-2, 4.2.2.3: γ M1 110 , M fi ,15, Rd = k 0.2 ,θ ⋅ M c , Rd ⋅ = 0,055 ⋅ 123kNm ⋅ = 7,4 kNm γ M , fi 1,0 M fi ,15, Rd = 7,4 kNm ≤ M Ed = 66,6kN The beam has to be fire protected. If a computer software is used for the temperature analysis, the rules for a non-uniform temperature distribution can be used. These rules will give a higher design moment resistance than the above calculated one, but not so high as required. c) Insulated Column Inside a Wall The column is standing inside a fire rated wall, and the lining of the wall is passing the column (see Figure 2504.01.05). The lining consists of 18 mm gypsum boards and the required fire resistance is 30 min. The column is a channel U 150 x 75 x 6 x 9 and the alloy EN AW 6063 T6. (f0 = 170 MPa) The span of the wall is 3300 mm, the column is prevented against buckling about the weak axis and it is simply supported in both ends. It is no welds in the column. The column is loaded with the following loads: • permanent loads: 15 kN • imposed loads: 60 kN Partiell coefficient for permanent loads is, γG = 1,10 and for variable loads, γQ = 1,50. The bearing capacity according to ENV 1999-1-1 is calculated to: Nb,Rd = 226 kN The design value of the axial force at normal temperature: NEd = 1,10⋅15 kN + 1,50⋅60 kN = 106,5 kN The design value of the axial force in fire situation: NEd = 1,0⋅15 kN + 1,0⋅60 kN = 75 kN TALAT 2504 8
  • 9. alu Schema of the insulated column inside a wall 2504.01.05 Training in Aluminium Application Technologies Fi/V is calculated according to Figure 2503.03.06: Fi 1 = = 111 V 0,009 Figure 2503.03.08 gives the insulation correction factor: C = 1/160 * 111 + 0,5 = 1,19 The equivalent insulation thickness is tequ = 1,19 * 18 mm = 21,4 mm Figure 2503.03.11 gives a metal temperature of the column of 250 °C. The 0,2% proof stress ratio, k0.2,θ , is found from ENV 1999-1-2 Table 3.1: k 0.2 ,θ = 0,38 The design buckling resistance of the column at 30 mins fire exposure, according to ENV 1999-1-2, 4.2.2.4: γ M1 110 , N b , fi ,30, Rd = k 0.2 ,θ ⋅ N b , Rd ⋅ = 0,38 ⋅ 226kN ⋅ = 78,7 kN 1,2 ⋅ γ M , fi 1,2 ⋅ 1,0 N b , fi ,30, Rd = 78,7 kN ≥ N Ed = 75kN TALAT 2504 9
  • 10. d)Insulated Freestanding Column The column is insulated by a 70 mm vermiculite board (see Figure 2504.01.06). The required fire resistance is 60 min. The column is a RHS 250 x 10, the alloy and temper are EN AW 6082 T6 (f0 = 260 MPa). The span of the column is 8000 mm, and it is simply supported in both ends. It is no welds in the column. The column is similar to that in the first example about the external column. Vermiculite Aluminium alu Schema of the insulated Freestanding column 2504.01.06 Training in Aluminium Application Technologies The column is loaded with the following loads: • permanent loads: 150 kN • imposed loads: 330 kN Partiell coefficient for permanent loads is, γG = 1,10 and for variable loads, γQ = 1,50. The bearing capacity according to ENV 1999-1-1 is calculated to: Nb,Rd = 767 kN The design value of the axial force for normal temperature: NEd = 1,10⋅150 kN + 1,50⋅330 kN = 660 kN The design value of the axial force in fire situation: NEd = 1,0⋅150 kN + 1,0⋅330 kN = 480 kN TALAT 2504 10
  • 11. Fi/V is calculated according to Figure 2503.03.06 (TALAT Lecture 2503): Fi 0, 25 ⋅ 4 = = 104 V 0, 25 ⋅ 4 ⋅ 0, 01 − 0, 012 ⋅ 4 Figure 2503.03.08 gives the insulation correction factor C = 1/625 * 104 + 0,8 = 0,97 Equivalent insulation thickness tequ = 0,97 * 70 mm = 68 mm Equivalent Insulation Thickness Versus Metal Temperature for 60 Min Fire Resistance 600 550 Metal temperature in degree Celsius 500 450 300 150 400 350 100 200 300 125 250 75 200 37 50 150 25 100 50 0 0 12,5 25 37,5 50 62,5 75 87,5 100 112,5 125 Equivalent insulation thickness in mm Equivalent Insulation Thickness Versus Metal alu Temperature for 60 Min Fire Resistance 2504.01.07 Training in Aluminium Application Technologies Figure 2504.01.07 shows the metal temperature of the column to be 180 °C. The 0,2% proof stress ratio, k0.2,θ , is found from ENV 1999-1-2 Table 3.1: 0,79 − 0,65 k 0.2 ,θ = 0,79 − ⋅ 30 = 0,71 50 The design buckling resistance of the column at 60 mins fire exposure, according to ENV 1999-1-2, 4.2.2.4: γ M1 110 , N b , fi ,60, Rd = k 0.2 ,θ ⋅ N b , Rd ⋅ = 0,71 ⋅ 767 kN ⋅ = 499 kN 1,2 ⋅ γ M , fi 1,2 ⋅ 1,0 TALAT 2504 11
  • 12. N b , fi ,60, Rd = 499 kN ≥ N Ed = 480kN e) Insulated Beam The floor beam as shown in Figure 2504.01.08 is insulated with 75 mm rockwool with density 120 kg/m³. The required fire resistance is 90 minutes. The beam is an I 450 x 200 x 12 x 25. The span of the beam is 8000 mm. The alloy and temper are EN AW 6082 T6 (f0 = 260 MPa). Calculation Example Insulated floor beam 90 min. fire resistance 20 kN/ m Beam: I 450 x 200 x 12 x 25 8000 Alloy: 6082 - T6 I = 515.8 x 106 mm4 W = 2.29 x 106 mm3 Cross section: Floor Insulation Beam alu Insulated Beam: Calculation Example 2504.01.08 Training in Aluminium Application Technologies The beam is loaded with the following loads: • permanent loads: 4,0 kN/m • imposed loads: 16,0 kN/m Partiell coefficient for permanent loads is, γG = 1,10 and for variable loads, γQ = 1,50. The bearing capacity according to ENV 1999-1-1 is calculated to: Mc,Rd = 617 kNm The design value of the bending moment at normal temperature: MEd = 1/8(1,10⋅4,0 kN/m + 1,50⋅16,0 kN/m)(8,0m)2 = 227 kNm This over-capacity is caused by the deflection criteria which states that the maximum allowable deflection is 1/250 of span. This beam has a deflection in the middle of the span of 1/270 of span. TALAT 2504 12
  • 13. The design value of the bending moment in a fire situation: MEd = 1/8(1,0⋅4,0 kN/m + 1,0⋅16,0 kN/m)(8,0m)2 = 160 kNm Fi/V is calculated according to Figure 2503.03.06 Fi 0,45 ⋅ 2 + 0,2 = = 74 V 0,2 ⋅ 0,025 ⋅ 2 + 0,4 ⋅ 0,012 From Figure 2503.03.08 the insulation correction factor is determined as C = 1,0. The equivalent insulation thickness is tequ = 1,0 * 75 mm = 75 mm. Equivalent Insulation Thickness Versus Metal Temperature for 90 Min Fire Resistance 600 550 Metal temperature in degree Celsius 500 450 300 400 200 350 125 300 150 250 100 75 200 50 150 37 25 100 50 0 25 37,5 50 62,5 75 87,5 100 112,5 125 137,5 150 Equivalent insulation thickness in mm Equivalent Insulation Thickness Versus Metal alu Temperature for 90 Min Fire Resistance 2504.01.09 Training in Aluminium Application Technologies The metal temperature in the beam is 230 °C (Figure 2504.01.09). The 0,2% proof stress ratio, k0.2,θ , is found from ENV 1999-1-2 Table 3.1: 0,65 − 0,38 k 0.2 ,θ = 0,65 − ⋅ 30 = 0,49 50 The design moment resistance of the beam at 90 mins fire exposure and for a uniform distributed temperature, according to ENV 1999-1-2, 4.2.2.3: γ M1 110 , M fi ,15, Rd = k 0.2 ,θ ⋅ M c , Rd ⋅ = 0,49 ⋅ 617 kNm ⋅ = 333kNm γ M , fi 1,0 M fi ,15, Rd = 333kNm ≥ M Ed = 160kNm TALAT 2504 13
  • 14. 2504.01.02 Computer Analysis In this example a computer analysis programme is used to find the metal temperature of the aluminium structure. The programme used is called TASEF (Temperature Analysis of Structures Exposed to Fire) and has been developed by Statens Provningsanstalt in Sweden. The programme is commercialized. [18] The structure which is analyzed is the same as shown in Figure 2504.01.08. The cross section of the insulated floor beam is divided into a grid of nodes, for which the temperature rise is calculated by the computer analysis programme (Figure 2504.01.10). The nodes No. 31 and 38 get the highest temperatures, they will also be the nodes with the highest stress. The temperature rise at node 31 and 38 is shown in Figure 2504.01.11. The temperature in nodes no 31 and 38 after 90 min exposure is 207 °C. Using the simplified method the temperature was calculated to 230 °C. Aluminium beam 0 0.100 0.175 0.300 0 1 7 y Metal temperature in degree Celsius 8 14 80 15 21 0.100 22 28 60 40 20 0 0 0.3 0.6 0.9 1.2 1.5 31 29 35 Exposure time in hour 0.450 36 38 42 43 49 50 56 Mean Temperature rise of the 0.525 57 63 Insulated beam x Relation Between Mean Rise of Temperature alu and Duration of Exposure 2504.01.10 Training in Aluminium Application Technologies TALAT 2504 14
  • 15. 250 200 150 100 50 0 0 0,5 1 1,5 Exposure time in hour Temperature evolution at node 31 and 38 of the alu 2504.01.11 Training in Aluminium Application Technologies insulated beam The temperature distribution in the whole model (all nodes) after 90 minutes standard fire exposure is shown in Figure 2504.01.10. Temperatures at the "aluminium nodes" are given in Figure 2504.01.12. Temperature at the "aluminium nodes" after 90 min alu of exposure 2504.01.12 Training in Aluminium Application Technologies To analyze the temperature rise in an insulated construction with a computer programme gives more exact results than the simplified calculation method described in TALAT Lecture 2503. The simplified method, however, leads to results on the safe side and can successfully be used. (The input data and the results of the analysis are appended as copies of the computer print-out.) TALAT 2504 15
  • 16. For the free standing column exposed to fire on all sides insulated with 70 mm vermiculite board the 60 min. fire resistance was calculated earlier. The metal temperature was found to be 180 °C. Using a computer analysis and a critical metal temperature of 200 °C the insulation thicknesses for various insulation materials are given in the table of Figure 2504.01.13. Equally, for beams under a floor covered with a 100 mm insulation the necessary insulation thicknesses for a critical metal temperature of 200 °C and fire resistances of 30, 60 and 90 minutes are computer calculated for various insulation materials as given in the table of Figure 2504.01.14. For gypsum boards and calcium silicate boards the simplified method gives inaccurate values. The values in the figured tables are based on computer analysis and are more correct than values calculated by use of the simplified method. Necessary insulation thicknesses for a beam under an insulated floor. 100 mm Thicknesses are calculated using 200 °C as critical metal temperature. Section In sulation m a teria l In sulation thickn ess 30 m in 60 m in 90 m in fire re sista nce fire resistance fire re sista nce I 30 0x20 0x12 x4 0 Ro ckwool, 1 20 kg/m 8 mm 24 m m 45 m m Ro ckwool, 3 00 kg/m 6 mm 16 m m 30 m m Ce ram ic fibre, 13 0 kg /m 7 mm 19 m m 35 m m G ypsum b oard s 12 m m 30 m m 45 m m Ca lcium silikat boards 10 m m 25 m m 43 m m I 30 0x20 0x8x20 Ro ckwool, 1 20 kg/m 16 m m 42 m m 72 m m Ro ckwool, 3 00 kg/m 11 m m 28 m m 48 m m Ce ram ic fibre, 13 0 kg /m 13 m m 33 m m 56 m m G ypsum b oard s 15 m m 34 m m 47 m m Ca lcium silikat boards 17 m m 38 m m 60 m m I 30 0x20 0x4x10 R ockw ool, 120 kg/m 29 m m 67 m m 105 m m R ockw ool, 300 kg/m 20 m m 45 m m 70 m m Ceram ic fibre, 130 kg/m 23 m m 52 m m 81 m m G ypsum boards 21 m m 37 m m 54 m m C alcium silikat boards 29 m m 51 m m 80 m m Necessary Insulation Thicknesses for a Beam Under alu 2504.01.14 Training in Aluminium Application Technologies an Insulated Floor TALAT 2504 16
  • 17. 2504.02 Products 2504.02.01 Prefabricated Fire Rated Walls Prefabricated walls are available with fire resistance characteristics from 30 minutes standard fire to 120 minutes hydrocarbon fire. They are made of aluminium alloy extrusions and sheets and insulation materials. These walls have also been used on oil platforms in the North Sea during the last years. The advantages of these walls are their light weight, the little maintenance needed and the easy erection. The insulation of these walls is fixed on the unexposed side or in the middle if the wall is to be exposed to the fire on both sides. The front plates protect the insulation against the environment and distribute the windload to the side members. During a fire the front plate will melt and the insulation will be directly exposed to the fire. In all prefabricated walls for the oil industry (see Figure 2504.02.01) the insulation material is non-combustible. In some countries combustible insulation is allowed to be used with special approval from the authorities. alu H 120 Rated Aluminium Prefabricated Wall Installed on Training in Aluminium Application Technologies Hydro´sOil Patform Oseberg A in the North Sea .Autumn 1990. 2504.02.01 For that reason a sandwich structure with aluminium alloy sheets as skin and combustible rigid foam as core frequently must be tested by a fire technology laboratory before the authorities give their approval. Often some specific requirements have to be met. These conditions can consist of limitations to where the approved structure may be used, of requirements on specific properties of the material used in the structure and/or of frequent production controls by an impartial institution. TALAT 2504 17
  • 18. 2504.02.02 Heat Radiation Shield Due to aluminium alloys' excellent reflection of heat radiation, shields of aluminium are used as heat radiation shield (Figure 2504.02.02). There are, however, some limitations: • the shield must not be covered by soot during the heat radiation exposure. • the heat radiation on the shield must not exceed 15 kW/m² (exact calculation must be performed). alu Aluminium Heat Radiation Shield to Protect the Lifeboats Training in Aluminium Application Technologies from Burning Blow Out on the Drilling Rig "West Delta". 2504.02.02 2504.02.03 Fire Rated Doors Several fire doors in aluminium with a fire rate up to A60 (60 mins. fire resistance) are available on the market. The doorleaf is fabricated of aluminium alloys and insulation, while the doorframe is made of steel or stainless steel. Both, hinged doors and sliding doors are fire classified. TALAT 2504 18
  • 19. 2504.02.04 Fire Rated Penetrations During the fabrication of a living quarter for an oil platform in the North Sea, entirely built of aluminium alloys (Snorre), some manufacturers developed fire rated penetrations with aluminium alloy sleeves and penetration frames. 2504.03 References/Literature [1] Drysdale, Dougal: An Introduction to Fire Dynamics. John Wiley & Sons. 1987, ISBN 0-471-90613-1 [2] NFPA/SFPE: Handbook of Fire Protection Engineering. NFPA/SFPE. 1988, ISBN 0-87765-353-4 [3] Sterner, E. / Wickstrøm, U.: TASEF - User Manual. Statens Provningsanstalt. 1990, ISBN 91-7848-210-0 [4] Landrø, Harald: Verification of the fire resistance of construction elements and structures. SINTEF 1983. [5] ISO 834-1975 (E). Fire resistance tests - Elements of building construction. [6] ECCS-TC3: European Recommendations for the Fire Safety of Steel Structures. Elsevier 1983. ISBN 0-444-42120-3 [7] GYPROC: Gyproc Håndbok. 1986. (In Swedish). [8] Holmen, J.P.: Heat Transfer. McGraw-Hill. Publ. Comp. 1990. ISBN 0-07- 909388-4 [9] Aluminium-Zentrale (Ed.): Aluminium Taschenbuch. Aluminium Verlag Düsseldorf, 1983. ISBN 3-87017-169-3 (In German) [10] Carborundum Resistant Materials: Fiberfrax Manual 1987. [11] Elkem Rockwool: Innføring i passive brannsikring. 1991. (In Norwegian). [12] NBR: NS 3478. Design rules for structural member for fire resistance. 1979. (In Norwegian). TALAT 2504 19
  • 20. [13] Hydro Aluminium Structures a.s: Revisjon av NS 3471, Kap. 14.2 Brannteknisk dimensjonering. 1992. (In Norwegian). [14] Andersson, Leif & Jansson, Bengt: En undersøkning av gipsskivans termiske egenskaper - Teori och försök. Lund University 1986 (In Swedish). [15] CEN/TC 250/SC 9: ENV 1999-1-2. Design of aluminium structures. Part 1.2. Structural fire design. 1997. [16] CEN/TC 250/SC 1: ENV 1991-2-2. Basis of design and actions on structures. Part 2.2. Actions on structures exposed to fire. 1995 [17] CEN/TC 250/SC 9: ENV 1999-1-1. Design of aluminium structures. Part 1.1. General rules. 1997 [18] Ulf Wickström, TASEF (Temperature Analysis of Structures Exposed to Fire), V. 3.0 PC, Computer Programme for the determination of fire resistance of structural elements with or without insulation. Swedish National Testing Institute 2504.04 List of Figures Figure No. Figure Title (Overhead) 2504.01.01 Schema of the Uninsulated Column 2504.01.02 Metal Temperature-Time Curves for εr = 0,2 2504.01.03 Schema of the Uninsulated Floor Beam 2504.01.04 Metal Temperature-Time Curves for εr = 0,7 2504.01.05 Schema of the Insulated Column Inside a Wall 2504.01.06 Schema of the Insulated Freestanding Column 2504.01.07 Equivalent Insulation Thickness Versus Metal Temperature for 60 Min Fire Resistance 2504.01.08 Insulated Beam: Calculation example 2504.01.09 Equivalent Insulation Thickness Versus Metal Temperature for 90 Min. Fire Resistance 2504.01.10 Relation Between Mean Rise of Temperature and Duration of Exposure 2504.01.11 Temperature Evolution at Nodes 31 and 38 of the Insulated Beam 2504.01.12 Temperatures at the Aluminium Nodes after 90 min of Exposure 2504.01.13 Necessary Insulation Thicknesses for a Column Exposed to Fire 2504.01.14 Necessary Insulation Thicknesses for a Beam Under an Insulated Floor 2504.02.01 H120 Rated Aluminium Prefabricated Wall Installed on Hydro’s Oil Platform Oseberg A in the North Sea Autumn 1990. 2504.02.02 Aluminium Heat Radiation Shield to Protect the Lifeboats From a Burning Blow Out on the Drilling Rig “West Delta“ TALAT 2504 20