1. 40.037 STABILISER (CVT)
Approval Date: January 2008 Version: 2
Purpose
• For protection of sensitive instruments as per instruments requirement
Specifications
type ferro magnetic resonance type constant voltage
transformer
capacity approx. 1 to 3 kVA, depending on capacity of
instrument or group of instruments supported
input voltage 170 to 270 VAC, 50 Hz ± 5%
output 220 VAC ± 2%, 50 Hz
efficiency > 85%
Features
• Meters for reading of input and output voltage
Equipment Specification: STABILISER (CVT) Version 2 40.037-1/1