International Journal Of Computational Engineering Research (ijceronline.com) Vol. 3 Issue. 3
317
||Issn||2250-3005|| (Online) ||March||2013|| ||www.ijceronline.com||
Discrimination of Fault from Non-Fault Event in Transformer
Using Concept of Symmetrical Component
1,
Mr. R.V.KATRE, 2,
Prof. Mr. D. S. Chavan, 3,
Prof.S.S.Sardey
Abstract
In this paper a overcurrent protection using concept of symmetrical component for power transformer is
presented .first we review the concept of symmetrical component. Secondly we investigate how the concept of
symmetrical component can be used to improve the transformer protection scheme and how it helps to discriminate
the fault and non fault events. For this an algorithm and discrimination criteria is analysed for various fault
condition and switching event.
Keywords : Fault, overcurrent relay, symmetrical Components, type of Faults, Transformer energizing, PSCAD,
Switching event
1. Introduction
The Concept of symmetrical components provides a practical technology for understanding and analyzing
power system operation during unbalanced conditions such as those caused by faults between phases and/or ground,
open phases, unbalance impedances, and so on. Also, many protective relays operate from the symmetrical
component quantities. Thus a good understanding of this subject is of great value and a very important tool in
protection.
1.1 Methodology For Improved Protection Schemes:
For any unbalanced or nonsymmetrical network, such as unsymmetrical fault occurs or having
unbalanced load, symmetrical component conversion can decouple three-phase system into three independent
sequence equivalent networks, namely positive, negative and zero sequence network. Therefore these three
sequence networks can be analyzed separately. Then we can convert the sequence value back into phase
variables. This analysis procedure is commonly used in analyzing the unbalanced system network, including
fault. Symmetrical components can be viewed as a mathematical tool on which we can entirely based to analysis
system without converting back to phase variable. For example, the amplitude of zero sequence signifies the
degree of unbalance, and therefore can be used to detect the unbalanced fault.
1.2 Theoretical background
The symmetrical component transformation for an arbitrary three-phase set of variables (balanced or
unbalanced), for example the three-phase current, and inverse transformation is given in (1) and (2).
-------- (1)
Here I1 , I2 and I0 denote the positive, negative and zero sequences respectively. And
α =1∟1200
= − 0.5 + j0.866
In general application in power system analysis, we typically begin with information in “phase variables”
denoted by subscripts a, b, and c. Note that phase variables corresponds to actual physical quantities. The value
of converting physical quantities to symmetrical components is in visualizing and quantization the degree of
unbalanced system network. For a balanced three-phase system, it won’t be difficult to calculate that the zero
and negative sequences are zero, and the positive sequence is equal to phase a, no matter current or voltage.
2. Operation And Principle Of Overcurrent Relays
There are two characteristics for overcurrent relays:
1) definite- time characteristic and 2) inverse-time characteristic. In the definite-time characteristic relays, if
the current amplitude exceeds a pre-defined value, the relay trips after a definite time. In the protection of
motors, these relays are used to prevent the unbalanced operation of the motors. According to IEC standard
[19], the characteristic of inverse time overcurrent relays (excluding induction type) is depicted by the
following expression:
Discrimination Of Fault From Non-Fault Event In Transformer…
318
||Issn||2250-3005|| (Online) ||March||2013|| ||www.ijceronline.com||
----- (2)
T- the relay operation time;
C- constant for relay characteristic;
Is-current setting threshold;
I- current detected by relay (normally the effective
value) ; I > Is
α- constant representing inverse-time type α> 0
By assigning different values to α and C, different types of inverse characteristics are obtained.
2.1 Proposed Algorithm
Any three-phase voltage and current consist of three components in sequence space which are related
to each other as follows:
Here I1 ,I2 and I0 denote the positive, negative and zero sequences respectively. And
α =1∟1200
= − 0.5 + j0.866
Also 1+α+α2
=0 if currents Ia,, Ib and Ic are balanced (i.e., Ia,= I∟0, Ib = I ∟ -1200
and Ic = I ∟ +1200
). So
existence of the negative components means that the system is unbalanced. except over a transient period that
may be as a result of different switching method or non identical saturated case of three-phase transformers,
three phases are almost affected simultaneously during switching event. Consequently, the negative component
is not considerably changed in this case. On the other hand, faults are classified into symmetrical and
asymmetrical parts. The major feature of these faults is the large value of the negative component, such that
there are the theoretical following cases-
For phase–ground fault
…… (4)
Where Zf is the fault impedance between the line and ground Z0, is the zero component impedance Z1, is the
positive component impedance, and Z2 is the negative
component impedance.
For phase-phase fault:
….. (5)
For phase-phase- ground fault:
…… (6)
Therefore, the negative component in the asymmetrical faults is considerable. For symmetrical faults the
negative component tends to zero. Not often, the three-phase fault occurs and the negative component of the
current is negligible and almost equal to zero similar with the switching case. The criterion function for
discriminating fault from nonfault switching is defined as follows
. The criterion function for discriminating fault from non fault switching is defined as follows:
----- (7)
Since there is a considerable negative component in the asymmetrical fault case, according to criterion function
the value of R is close to zero. In the switching case, the negative component is very small and R is close to 1.
In the switching case, the negative component is very small and R is close to 1. Except over a transient period
that may be as a result of different switching methods or a non identical saturated case of three-phase
transformers, three phases are almost affected simultaneously and the three-phase network has not a major
Discrimination Of Fault From Non-Fault Event In Transformer…
319
||Issn||2250-3005|| (Online) ||March||2013|| ||www.ijceronline.com||
unbalance, during the switching event. In the calculation of I2 and I1 in equation (1), Ia ,Ib , and Ic are phasor
value (amplitude of the fundamental harmonic). Therefore, dc values and its harmonics are largely eliminated.
So the difference in dc value in the current is not important. According to the above, R<0.35 indicates the fault;
otherwise, over current is the result of switching. The suggested criterion is based on the different behavior of
the current components during fault and non fault conditions and is independent of the amplitude of the current
which is advantageous. The reason is that it operates based on the relative difference between the negative and
positive component of the current. Another advantage of the suggested criterion function is that its proper
operation is independent of the power system balancing. Actually, the suggested criterion function in the
asymmetrical distribution networks also operates properly. The reason is that during the asymmetrical fault, the
negative component of current increases and the value of R is much smaller than that before fault event. Thus,
it is enough that the threshold value be lower than at the value of R in the normal state of the network.
3. Simulation
To show the advantage of the proposed algorithm, a part of a distribution system shown in Fig.1 is
modeled; using the EMTDC/ PSCAD package. The network parameter of the 2-bus distribution system is
illustrated in this figure. Several nonfault events are applied to this system along with some short circuit events
at different times. The simulation results show that how the proposed algorithm could help the overcurrent relay
to discriminate fault from nonfault events. The following cases are presented here:
• Transformer energizing;
• Induction motor starting;
4. Transformer Energizing
When the primary winding of an unloaded transformer is switched on to normal voltage supply, it acts
as a nonlinear inductor. In this situation there is a transient inrush current that is required to establish the
magnetic field of the transformer. The magnitude of this current depends on the applied voltage magnitude at
the instant of switching, supply impedance, transformer size and design. Residual flux in the core can aggravate
the condition. The initial inrush current could reach values several times full load current and will decay with
time until a normal exciting current value is reached. The decay of the inrush current may vary from as short as
20 cycles to as long as minutes for highly inductive circuits. The inrush current contains both odd and even
order harmonics.In order to study a transformer energizing, various inrush current conditions were simulated at
different parts of the power system. Various parameters which have considerable effect on the characteristic of
the current signal (e.g., core residual magnetization, nonlinearity of transformer core and switching instant)
were changed and the current signal was analyzed by the proposed method. In all cases, correctness of the
proposed algorithm has been proved.
Malfunctioning of transformers is mainly because of following reasons:
Due to magnetizing inrush current, Harmonics generated due to occurrence of internal faults, Short Circuit in
core winding, Symmetrical or Asymmetrical Faults Symmetrical components consist of three quantities:
positive-sequence (exists during all system conditions, but are prevalent for balanced conditions on a power
system including three-phase faults); negative-sequence (exist during unbalanced conditions); zero-sequence
(exist when ground is involved in an unbalanced condition). Negative and zero-sequence components have
relatively large values during unbalanced fault conditions on a power system and can be used to determine when
these fault conditions occur. Negative-sequence components indicate phase-to-phase, phase-to-ground, and
phase-to-phase-to-ground faults. Zero sequence components indicate phase-to-ground and phase -to-phase-to-
ground faults
4.1 Inrush due to switching-in
Initial magnetizing due to switching a transformer in is considered the most severe case of an inrush.
When a transformer is de-energized (switched-off), the magnetizing voltage is taken away, the magnetizing
current goes to zero while the flux follows the hysteresis loop of the core. This results in certain remanent flux
left in the core. When, afterwards, the transformer is re-energized by an alternating sinusoidal voltage, the flux
becomes also sinusoidal but biased by the remanence. The residual flux may be as high as 80-90% of the rated
flux, and therefore, it may shift the flux-current trajectories far above the knee-point of the characteristic
resulting in both large peak values and heavy distortions of the magnetizing current A detailed study of a
typical case is presented below. In this case transformer at busbar 1-2 is switched on at instant t= 0.25s and
three-phase currents are measured at busbar 7. Fig. 2 shows these three-phase currents. As shown in Fig. 3,
except over a transient period, R is close to 1 and is larger than setting R= 0.35s that shows nonfault case. In this
case tripping signal is prevented.
Discrimination Of Fault From Non-Fault Event In Transformer…
320
||Issn||2250-3005|| (Online) ||March||2013|| ||www.ijceronline.com||
4.2 Fault
In this case a phase-ground fault (A-G) occurs at busbar 1 at instant t= 0.25s and three-phase currents
are measured at busbar 7. Fig. 4 shows these three-phase currents. As shown in Fig. 5, R is close to zero that
shows a fault case in which the tripping signal is issued.
#1 #2 #1 #2
40.0 [MVAR] 80.0 [MW]
280.0 [MVAR] 800.0 [MW]
Ea
RLRL
A->G flt
Ia
V
A
Bus 1 Bus 3 bus 4Bus 2
Bus 5
Fig 1. 5-bus system model
Fig.2. 3- phase current due to transformer energizing
Fig 3. Value of R versus time due to transformer
Energizing
-80
-70
-60
-50
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
y
Ia1
Fig. 4 Three phase current due to fault (A-G)
Discrimination Of Fault From Non-Fault Event In Transformer…
321
||Issn||2250-3005|| (Online) ||March||2013|| ||www.ijceronline.com||
Fig. 5 Value of R versus time due to fault (A-G)
Three-phase currents are measured at the busbar 1 Fig. 4 shows these currents is close to zero which
indicates that there is a fault and the relay trips. In fact, one more advantage of the suggested algorithm is that,
in addition to the diagnosis of the fault in the individual occurrence from the nonfault case, it enables to
discriminate a fault from simultaneous switching properly. This is necessary because, if in the case of fault, the
operation of the relay is prevented and it is assumed switching case, it may lead to a serious damage.
5. Theoretical Analysis
6. Conclusion
In this paper, from simulations results it indicates that enhanced sensitivity can be achieved with a
symmetrical component based overcurrent protection. Also the paper presents a new algorithm- overcurrent
protection based on symmetrical component and shows vastly improved performance over conventional
techniques, to discriminate fault and non fault events like switching and magnetizing inrushes in transformer.
Undesirable operation of relay due to the switching is prevented. The capability of the new method has been
demonstrated by simulating various cases on a suitable power system for various types of asymmetrical faults.
7. Future Scope
Here only the fault cases related to Transformer is studied but in future it can be studied for Alternator,
Turbo-generators etc.
Discrimination Of Fault From Non-Fault Event In Transformer…
322
||Issn||2250-3005|| (Online) ||March||2013|| ||www.ijceronline.com||
Reference
[1] F. Wang and M. H. J. Bollen, “Quantification of transient current signals in the viewpoint of overcurrent relays,” in Proc. Power
Eng. Soc. General Meeting, Jul. 13–17, 2003, vol. 4, pp. 2122–2127.
[2] “Classification of component switching transients in the viewpoint of protection relays,” Elect. Power Syst. Res., vol. 64, pp. 197–
207, 2003.
[3] J. H. Brunke and H. J. Frohlich, “Elimination of transformer inrush currents by controlled switching-Part II: Application and
performance considerations,” IEEE Trans. Power Del., vol. 16, no. 2, pp. 281–285, Apr. 2001.
[4] M. A. Rahman and B. Jeyasurya, “A state-of-the-art review of transformer protection algorithms,” IEEE Trans. Power Del., vol. 3,
no. 2, pp. 534–544, Apr. 1988.
[5] P. Liu, O. P. Malik, C. Chen, G. S. Hope, and Y. Guo, “Improved operation of differential protection of power transformers for
internal faults,” IEEE Trans. Power Del., vol. 7, no. 4, pp. 1912–1919, Oct. 1992.
[6] T. S. Sidhu, M. S. Sachdev, H. C. Wood, and M. Nagpal, “Design, implementation and testing of a micro-processor-based high-
speed relay for detecting transformer winding faults,” IEEE Trans. Power Del., vol. 7, no. 1, pp. 108–117, sJan. 1992, .
[7] K. Yabe, “Power differential method for discrimination between fault and magnetizing inrush current in transformers,” IEEE Trans.
Power Del., vol. 3, no. 3, pp. 1109–1117, Jul. 1997.
[8] P. Bastard, M. Meunier, and H. Regal, “Neural network-based algorithm for power transformer differential relays,” Proc. Inst.
Elect. Eng. C, vol. 142, no. 4, pp. 386–392, 1995.
[9] M. C. Shin, C. W. Park, and J. H. Kim, “Fuzzy logic-based for large power transformer protection,” IEEE Trans. Power Del., vol.
18, no. 3, pp. 718–724, Jul. 2003.
[10] A. T. Johns and S. K. Salman, Digital Protection for Power Systems. Stevenage, U.K.: Peregrinus, 1995.
[11] S. Emmanouil, M. H. J. Bollen, and I. Y. H. Gu, “Expert system for classification and analysis of power system events,” IEEE
Trans. Power Del., vol. 17, no. 2, pp. 423–428, Apr. 2002.
[12] W. A. Elmore, C. A. Kramer, and S. E. Zocholl, “Effects of waveform distortion on protective relays,” IEEE Trans. Ind. Appl., vol.
29, no. 2, pp. 404–411, Mar./Apr. 1993.
[13] J. F. Witte, F. P. Decesaro, and S. R. Mendis, “Damaging long-term over voltages on industrial capacitor banks due to transformer
energization inrush currents,” IEEE Trans. Ind. Appl., vol. 30, no. 4, pp. 1107–1115, Jul./Aug. 1994.
[14] R. Rudenberg, Transient Performance of Electric Power System. Cambridge, MA: MIT Press, 1965.
[15] Improved Overcurrent Protection Using Symmetrical Components Saeed Lotfi-fard, Student Member, IEEE, Jawad Faiz, Senior
ion of Member, IEEE, and Reza Iravani, Fellow, IEEE
[16] Overcurrent Protection Solution based on symmetrical component Method; Mr. K. K. Rajput, Mrs. K. D. Thakur Mrs. C. H.
Chavan, Journal of Information ,knowledge and research in electronics and communication engineering, ISSN 0975-6779,Nov 10 to
Oct 11 ,Vol-01,issue-02.
Rohit Katre: M.Tech Student in Electrical Power Systems, Bharati Vidyapeeth Deemed
University College of Engineering, Pune, Maharashtra, India
Prof.D.S.Chavan: Ph D (Registered), ME (Electrical), BE (Electrical), DEE Associate
Professor, Co-Ordinator (R&D Cell), Co-Ordinator (PH.D.Programme Management) Bharati Vidyapeeth
Deemed University College Of Engineering Pune 411043. He Is Pursuing Ph D. He Received ME
(Electrical)(Power Systems) Achieved Rank Certificate In Pune University For ME
Prof. S.S.sardey.: ME (Electrical Power system), BE (Electrical), Assistant Professor, Bharati Vidyapeeth
Deemed University College Of Engineering Pune 411043.

More Related Content

What's hot

Symmetrical components......
Symmetrical components......Symmetrical components......
Symmetrical components......Santhi Anumula
 
Up/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
Up/Down Converter Linear Model with Feed Forward and Feedback Stability AnalysisUp/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
Up/Down Converter Linear Model with Feed Forward and Feedback Stability AnalysisCSCJournals
 
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...idescitation
 
symmetrical component of power system
symmetrical component of power systemsymmetrical component of power system
symmetrical component of power systemsneh pratap singh
 
Synthesis of unsymmetrical phasors from their symmetrical components
Synthesis of unsymmetrical phasors from their symmetrical componentsSynthesis of unsymmetrical phasors from their symmetrical components
Synthesis of unsymmetrical phasors from their symmetrical componentsAbhishek Choksi
 
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...vaibyfrndz
 
Power System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterPower System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterIJERA Editor
 
FAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongFAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongArmstrong Okai Ababio
 
POWER QUALITY IMPROVEMENT IN DC DRIVES BY SUPPRESSING
POWER QUALITY IMPROVEMENT IN DC DRIVES BY SUPPRESSINGPOWER QUALITY IMPROVEMENT IN DC DRIVES BY SUPPRESSING
POWER QUALITY IMPROVEMENT IN DC DRIVES BY SUPPRESSINGAravind Naragund
 
Symmetrical components
Symmetrical componentsSymmetrical components
Symmetrical componentsSirat Mahmood
 
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...IJPEDS-IAES
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Power System Operation
 
Unsymmetrical fault in transmission line
Unsymmetrical fault in transmission lineUnsymmetrical fault in transmission line
Unsymmetrical fault in transmission linevishalgohel12195
 
An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...
An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...
An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...IDES Editor
 
report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...Vikram Rawani
 
Symmetrical component method for 3 phase power representation
Symmetrical component method for 3 phase power representationSymmetrical component method for 3 phase power representation
Symmetrical component method for 3 phase power representationNisarg Amin
 
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...ijtsrd
 
Power system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filterPower system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filtereSAT Publishing House
 
Power Quality Improvement in Distribution System using ANN Based Shunt Active...
Power Quality Improvement in Distribution System using ANN Based Shunt Active...Power Quality Improvement in Distribution System using ANN Based Shunt Active...
Power Quality Improvement in Distribution System using ANN Based Shunt Active...IAES-IJPEDS
 
Analysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrixAnalysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrixTrupesh Rupareliya
 

What's hot (20)

Symmetrical components......
Symmetrical components......Symmetrical components......
Symmetrical components......
 
Up/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
Up/Down Converter Linear Model with Feed Forward and Feedback Stability AnalysisUp/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
Up/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
 
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
 
symmetrical component of power system
symmetrical component of power systemsymmetrical component of power system
symmetrical component of power system
 
Synthesis of unsymmetrical phasors from their symmetrical components
Synthesis of unsymmetrical phasors from their symmetrical componentsSynthesis of unsymmetrical phasors from their symmetrical components
Synthesis of unsymmetrical phasors from their symmetrical components
 
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
 
Power System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterPower System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power Filter
 
FAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongFAULT Analysis presentation Armstrong
FAULT Analysis presentation Armstrong
 
POWER QUALITY IMPROVEMENT IN DC DRIVES BY SUPPRESSING
POWER QUALITY IMPROVEMENT IN DC DRIVES BY SUPPRESSINGPOWER QUALITY IMPROVEMENT IN DC DRIVES BY SUPPRESSING
POWER QUALITY IMPROVEMENT IN DC DRIVES BY SUPPRESSING
 
Symmetrical components
Symmetrical componentsSymmetrical components
Symmetrical components
 
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
 
Unsymmetrical fault in transmission line
Unsymmetrical fault in transmission lineUnsymmetrical fault in transmission line
Unsymmetrical fault in transmission line
 
An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...
An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...
An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...
 
report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...
 
Symmetrical component method for 3 phase power representation
Symmetrical component method for 3 phase power representationSymmetrical component method for 3 phase power representation
Symmetrical component method for 3 phase power representation
 
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
 
Power system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filterPower system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filter
 
Power Quality Improvement in Distribution System using ANN Based Shunt Active...
Power Quality Improvement in Distribution System using ANN Based Shunt Active...Power Quality Improvement in Distribution System using ANN Based Shunt Active...
Power Quality Improvement in Distribution System using ANN Based Shunt Active...
 
Analysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrixAnalysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrix
 

Viewers also liked

Chainsaw Ticket - Tree Felling
Chainsaw Ticket - Tree FellingChainsaw Ticket - Tree Felling
Chainsaw Ticket - Tree Fellingfitecaustralia
 
A Paper on Problems Generated By Junk Food in India
A Paper on Problems Generated By Junk Food in IndiaA Paper on Problems Generated By Junk Food in India
A Paper on Problems Generated By Junk Food in Indiaijceronline
 
Description of condensation and evaporation processes in cylindrical-type por...
Description of condensation and evaporation processes in cylindrical-type por...Description of condensation and evaporation processes in cylindrical-type por...
Description of condensation and evaporation processes in cylindrical-type por...ijceronline
 
Effect on heat transfer for laminar flow over Backward Facing Step with squar...
Effect on heat transfer for laminar flow over Backward Facing Step with squar...Effect on heat transfer for laminar flow over Backward Facing Step with squar...
Effect on heat transfer for laminar flow over Backward Facing Step with squar...ijceronline
 

Viewers also liked (7)

B03308011
B03308011B03308011
B03308011
 
Ba03303280331
Ba03303280331Ba03303280331
Ba03303280331
 
Chainsaw Ticket - Tree Felling
Chainsaw Ticket - Tree FellingChainsaw Ticket - Tree Felling
Chainsaw Ticket - Tree Felling
 
Ax03303120316
Ax03303120316Ax03303120316
Ax03303120316
 
A Paper on Problems Generated By Junk Food in India
A Paper on Problems Generated By Junk Food in IndiaA Paper on Problems Generated By Junk Food in India
A Paper on Problems Generated By Junk Food in India
 
Description of condensation and evaporation processes in cylindrical-type por...
Description of condensation and evaporation processes in cylindrical-type por...Description of condensation and evaporation processes in cylindrical-type por...
Description of condensation and evaporation processes in cylindrical-type por...
 
Effect on heat transfer for laminar flow over Backward Facing Step with squar...
Effect on heat transfer for laminar flow over Backward Facing Step with squar...Effect on heat transfer for laminar flow over Backward Facing Step with squar...
Effect on heat transfer for laminar flow over Backward Facing Step with squar...
 

Similar to Ay03303170322

IRJET- Improve Power Quality in Power Grid using STATCOM with Hysteresis ...
IRJET-  	  Improve Power Quality in Power Grid using STATCOM with Hysteresis ...IRJET-  	  Improve Power Quality in Power Grid using STATCOM with Hysteresis ...
IRJET- Improve Power Quality in Power Grid using STATCOM with Hysteresis ...IRJET Journal
 
Unit -1 Introdcution to PSA.pptx
Unit -1  Introdcution to PSA.pptxUnit -1  Introdcution to PSA.pptx
Unit -1 Introdcution to PSA.pptxSanjeevKumarkumar11
 
Pst presentation ms f19_008
Pst presentation ms f19_008Pst presentation ms f19_008
Pst presentation ms f19_008hamza zaheer
 
Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...
Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...
Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...IAES-IJPEDS
 
DigSILENT PF - 06 (es) short circuit theory
DigSILENT PF - 06 (es) short circuit theoryDigSILENT PF - 06 (es) short circuit theory
DigSILENT PF - 06 (es) short circuit theoryHimmelstern
 
DigSILENT PF - 05 short circuit theory
DigSILENT PF - 05 short circuit theoryDigSILENT PF - 05 short circuit theory
DigSILENT PF - 05 short circuit theoryHimmelstern
 
Improved dynamic response of dstatcom using genetic algorithm
Improved dynamic response of dstatcom using genetic algorithmImproved dynamic response of dstatcom using genetic algorithm
Improved dynamic response of dstatcom using genetic algorithmAlexander Decker
 
IRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply SystemIRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply SystemIRJET Journal
 
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET Journal
 
Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...eSAT Journals
 
Analysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load inAnalysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load ineSAT Publishing House
 
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET-  	  Design a Fuzzy Distance Relay Including STATCOM EffectsIRJET-  	  Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET- Design a Fuzzy Distance Relay Including STATCOM EffectsIRJET Journal
 
Control of grid connected inverter system for sinusoidal current injection wi...
Control of grid connected inverter system for sinusoidal current injection wi...Control of grid connected inverter system for sinusoidal current injection wi...
Control of grid connected inverter system for sinusoidal current injection wi...ijiert bestjournal
 
Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculationsRonald Santos
 
UNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEMUNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEMerramansaini1947
 
IRJET- Performance Analysis of Induction Motor using IoT
IRJET-  	  Performance Analysis of Induction Motor using IoTIRJET-  	  Performance Analysis of Induction Motor using IoT
IRJET- Performance Analysis of Induction Motor using IoTIRJET Journal
 

Similar to Ay03303170322 (20)

IRJET- Improve Power Quality in Power Grid using STATCOM with Hysteresis ...
IRJET-  	  Improve Power Quality in Power Grid using STATCOM with Hysteresis ...IRJET-  	  Improve Power Quality in Power Grid using STATCOM with Hysteresis ...
IRJET- Improve Power Quality in Power Grid using STATCOM with Hysteresis ...
 
E044043336
E044043336E044043336
E044043336
 
Unit -1 Introdcution to PSA.pptx
Unit -1  Introdcution to PSA.pptxUnit -1  Introdcution to PSA.pptx
Unit -1 Introdcution to PSA.pptx
 
Kf3517721775
Kf3517721775Kf3517721775
Kf3517721775
 
Pst presentation ms f19_008
Pst presentation ms f19_008Pst presentation ms f19_008
Pst presentation ms f19_008
 
Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...
Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...
Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...
 
DigSILENT PF - 06 (es) short circuit theory
DigSILENT PF - 06 (es) short circuit theoryDigSILENT PF - 06 (es) short circuit theory
DigSILENT PF - 06 (es) short circuit theory
 
DigSILENT PF - 05 short circuit theory
DigSILENT PF - 05 short circuit theoryDigSILENT PF - 05 short circuit theory
DigSILENT PF - 05 short circuit theory
 
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
 
Improved dynamic response of dstatcom using genetic algorithm
Improved dynamic response of dstatcom using genetic algorithmImproved dynamic response of dstatcom using genetic algorithm
Improved dynamic response of dstatcom using genetic algorithm
 
IRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply SystemIRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply System
 
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
 
Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...
 
Analysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load inAnalysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load in
 
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET-  	  Design a Fuzzy Distance Relay Including STATCOM EffectsIRJET-  	  Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
 
Control of grid connected inverter system for sinusoidal current injection wi...
Control of grid connected inverter system for sinusoidal current injection wi...Control of grid connected inverter system for sinusoidal current injection wi...
Control of grid connected inverter system for sinusoidal current injection wi...
 
Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculations
 
P.u systems.pptx
P.u systems.pptxP.u systems.pptx
P.u systems.pptx
 
UNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEMUNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEM
 
IRJET- Performance Analysis of Induction Motor using IoT
IRJET-  	  Performance Analysis of Induction Motor using IoTIRJET-  	  Performance Analysis of Induction Motor using IoT
IRJET- Performance Analysis of Induction Motor using IoT
 

Recently uploaded

Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...Alkin Tezuysal
 
The State of Passkeys with FIDO Alliance.pptx
The State of Passkeys with FIDO Alliance.pptxThe State of Passkeys with FIDO Alliance.pptx
The State of Passkeys with FIDO Alliance.pptxLoriGlavin3
 
Manual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance AuditManual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance AuditSkynet Technologies
 
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxLoriGlavin3
 
Scale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterScale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterMydbops
 
Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...
Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...
Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...Scott Andery
 
Modern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better StrongerModern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better Strongerpanagenda
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc
 
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024BookNet Canada
 
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptxThe Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptxLoriGlavin3
 
Testing tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examplesTesting tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examplesKari Kakkonen
 
How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.Curtis Poe
 
Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...Farhan Tariq
 
Emixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native developmentEmixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native developmentPim van der Noll
 
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxA Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxLoriGlavin3
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersRaghuram Pandurangan
 
Potential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and InsightsPotential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and InsightsRavi Sanghani
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfMounikaPolabathina
 
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Mark Goldstein
 
Moving Beyond Passwords: FIDO Paris Seminar.pdf
Moving Beyond Passwords: FIDO Paris Seminar.pdfMoving Beyond Passwords: FIDO Paris Seminar.pdf
Moving Beyond Passwords: FIDO Paris Seminar.pdfLoriGlavin3
 

Recently uploaded (20)

Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
 
The State of Passkeys with FIDO Alliance.pptx
The State of Passkeys with FIDO Alliance.pptxThe State of Passkeys with FIDO Alliance.pptx
The State of Passkeys with FIDO Alliance.pptx
 
Manual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance AuditManual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance Audit
 
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
 
Scale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterScale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL Router
 
Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...
Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...
Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...
 
Modern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better StrongerModern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
 
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
 
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptxThe Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
 
Testing tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examplesTesting tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examples
 
How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.
 
Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...
 
Emixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native developmentEmixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native development
 
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxA Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information Developers
 
Potential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and InsightsPotential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and Insights
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdf
 
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
 
Moving Beyond Passwords: FIDO Paris Seminar.pdf
Moving Beyond Passwords: FIDO Paris Seminar.pdfMoving Beyond Passwords: FIDO Paris Seminar.pdf
Moving Beyond Passwords: FIDO Paris Seminar.pdf
 

Ay03303170322

  • 1. International Journal Of Computational Engineering Research (ijceronline.com) Vol. 3 Issue. 3 317 ||Issn||2250-3005|| (Online) ||March||2013|| ||www.ijceronline.com|| Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component 1, Mr. R.V.KATRE, 2, Prof. Mr. D. S. Chavan, 3, Prof.S.S.Sardey Abstract In this paper a overcurrent protection using concept of symmetrical component for power transformer is presented .first we review the concept of symmetrical component. Secondly we investigate how the concept of symmetrical component can be used to improve the transformer protection scheme and how it helps to discriminate the fault and non fault events. For this an algorithm and discrimination criteria is analysed for various fault condition and switching event. Keywords : Fault, overcurrent relay, symmetrical Components, type of Faults, Transformer energizing, PSCAD, Switching event 1. Introduction The Concept of symmetrical components provides a practical technology for understanding and analyzing power system operation during unbalanced conditions such as those caused by faults between phases and/or ground, open phases, unbalance impedances, and so on. Also, many protective relays operate from the symmetrical component quantities. Thus a good understanding of this subject is of great value and a very important tool in protection. 1.1 Methodology For Improved Protection Schemes: For any unbalanced or nonsymmetrical network, such as unsymmetrical fault occurs or having unbalanced load, symmetrical component conversion can decouple three-phase system into three independent sequence equivalent networks, namely positive, negative and zero sequence network. Therefore these three sequence networks can be analyzed separately. Then we can convert the sequence value back into phase variables. This analysis procedure is commonly used in analyzing the unbalanced system network, including fault. Symmetrical components can be viewed as a mathematical tool on which we can entirely based to analysis system without converting back to phase variable. For example, the amplitude of zero sequence signifies the degree of unbalance, and therefore can be used to detect the unbalanced fault. 1.2 Theoretical background The symmetrical component transformation for an arbitrary three-phase set of variables (balanced or unbalanced), for example the three-phase current, and inverse transformation is given in (1) and (2). -------- (1) Here I1 , I2 and I0 denote the positive, negative and zero sequences respectively. And α =1∟1200 = − 0.5 + j0.866 In general application in power system analysis, we typically begin with information in “phase variables” denoted by subscripts a, b, and c. Note that phase variables corresponds to actual physical quantities. The value of converting physical quantities to symmetrical components is in visualizing and quantization the degree of unbalanced system network. For a balanced three-phase system, it won’t be difficult to calculate that the zero and negative sequences are zero, and the positive sequence is equal to phase a, no matter current or voltage. 2. Operation And Principle Of Overcurrent Relays There are two characteristics for overcurrent relays: 1) definite- time characteristic and 2) inverse-time characteristic. In the definite-time characteristic relays, if the current amplitude exceeds a pre-defined value, the relay trips after a definite time. In the protection of motors, these relays are used to prevent the unbalanced operation of the motors. According to IEC standard [19], the characteristic of inverse time overcurrent relays (excluding induction type) is depicted by the following expression:
  • 2. Discrimination Of Fault From Non-Fault Event In Transformer… 318 ||Issn||2250-3005|| (Online) ||March||2013|| ||www.ijceronline.com|| ----- (2) T- the relay operation time; C- constant for relay characteristic; Is-current setting threshold; I- current detected by relay (normally the effective value) ; I > Is α- constant representing inverse-time type α> 0 By assigning different values to α and C, different types of inverse characteristics are obtained. 2.1 Proposed Algorithm Any three-phase voltage and current consist of three components in sequence space which are related to each other as follows: Here I1 ,I2 and I0 denote the positive, negative and zero sequences respectively. And α =1∟1200 = − 0.5 + j0.866 Also 1+α+α2 =0 if currents Ia,, Ib and Ic are balanced (i.e., Ia,= I∟0, Ib = I ∟ -1200 and Ic = I ∟ +1200 ). So existence of the negative components means that the system is unbalanced. except over a transient period that may be as a result of different switching method or non identical saturated case of three-phase transformers, three phases are almost affected simultaneously during switching event. Consequently, the negative component is not considerably changed in this case. On the other hand, faults are classified into symmetrical and asymmetrical parts. The major feature of these faults is the large value of the negative component, such that there are the theoretical following cases- For phase–ground fault …… (4) Where Zf is the fault impedance between the line and ground Z0, is the zero component impedance Z1, is the positive component impedance, and Z2 is the negative component impedance. For phase-phase fault: ….. (5) For phase-phase- ground fault: …… (6) Therefore, the negative component in the asymmetrical faults is considerable. For symmetrical faults the negative component tends to zero. Not often, the three-phase fault occurs and the negative component of the current is negligible and almost equal to zero similar with the switching case. The criterion function for discriminating fault from nonfault switching is defined as follows . The criterion function for discriminating fault from non fault switching is defined as follows: ----- (7) Since there is a considerable negative component in the asymmetrical fault case, according to criterion function the value of R is close to zero. In the switching case, the negative component is very small and R is close to 1. In the switching case, the negative component is very small and R is close to 1. Except over a transient period that may be as a result of different switching methods or a non identical saturated case of three-phase transformers, three phases are almost affected simultaneously and the three-phase network has not a major
  • 3. Discrimination Of Fault From Non-Fault Event In Transformer… 319 ||Issn||2250-3005|| (Online) ||March||2013|| ||www.ijceronline.com|| unbalance, during the switching event. In the calculation of I2 and I1 in equation (1), Ia ,Ib , and Ic are phasor value (amplitude of the fundamental harmonic). Therefore, dc values and its harmonics are largely eliminated. So the difference in dc value in the current is not important. According to the above, R<0.35 indicates the fault; otherwise, over current is the result of switching. The suggested criterion is based on the different behavior of the current components during fault and non fault conditions and is independent of the amplitude of the current which is advantageous. The reason is that it operates based on the relative difference between the negative and positive component of the current. Another advantage of the suggested criterion function is that its proper operation is independent of the power system balancing. Actually, the suggested criterion function in the asymmetrical distribution networks also operates properly. The reason is that during the asymmetrical fault, the negative component of current increases and the value of R is much smaller than that before fault event. Thus, it is enough that the threshold value be lower than at the value of R in the normal state of the network. 3. Simulation To show the advantage of the proposed algorithm, a part of a distribution system shown in Fig.1 is modeled; using the EMTDC/ PSCAD package. The network parameter of the 2-bus distribution system is illustrated in this figure. Several nonfault events are applied to this system along with some short circuit events at different times. The simulation results show that how the proposed algorithm could help the overcurrent relay to discriminate fault from nonfault events. The following cases are presented here: • Transformer energizing; • Induction motor starting; 4. Transformer Energizing When the primary winding of an unloaded transformer is switched on to normal voltage supply, it acts as a nonlinear inductor. In this situation there is a transient inrush current that is required to establish the magnetic field of the transformer. The magnitude of this current depends on the applied voltage magnitude at the instant of switching, supply impedance, transformer size and design. Residual flux in the core can aggravate the condition. The initial inrush current could reach values several times full load current and will decay with time until a normal exciting current value is reached. The decay of the inrush current may vary from as short as 20 cycles to as long as minutes for highly inductive circuits. The inrush current contains both odd and even order harmonics.In order to study a transformer energizing, various inrush current conditions were simulated at different parts of the power system. Various parameters which have considerable effect on the characteristic of the current signal (e.g., core residual magnetization, nonlinearity of transformer core and switching instant) were changed and the current signal was analyzed by the proposed method. In all cases, correctness of the proposed algorithm has been proved. Malfunctioning of transformers is mainly because of following reasons: Due to magnetizing inrush current, Harmonics generated due to occurrence of internal faults, Short Circuit in core winding, Symmetrical or Asymmetrical Faults Symmetrical components consist of three quantities: positive-sequence (exists during all system conditions, but are prevalent for balanced conditions on a power system including three-phase faults); negative-sequence (exist during unbalanced conditions); zero-sequence (exist when ground is involved in an unbalanced condition). Negative and zero-sequence components have relatively large values during unbalanced fault conditions on a power system and can be used to determine when these fault conditions occur. Negative-sequence components indicate phase-to-phase, phase-to-ground, and phase-to-phase-to-ground faults. Zero sequence components indicate phase-to-ground and phase -to-phase-to- ground faults 4.1 Inrush due to switching-in Initial magnetizing due to switching a transformer in is considered the most severe case of an inrush. When a transformer is de-energized (switched-off), the magnetizing voltage is taken away, the magnetizing current goes to zero while the flux follows the hysteresis loop of the core. This results in certain remanent flux left in the core. When, afterwards, the transformer is re-energized by an alternating sinusoidal voltage, the flux becomes also sinusoidal but biased by the remanence. The residual flux may be as high as 80-90% of the rated flux, and therefore, it may shift the flux-current trajectories far above the knee-point of the characteristic resulting in both large peak values and heavy distortions of the magnetizing current A detailed study of a typical case is presented below. In this case transformer at busbar 1-2 is switched on at instant t= 0.25s and three-phase currents are measured at busbar 7. Fig. 2 shows these three-phase currents. As shown in Fig. 3, except over a transient period, R is close to 1 and is larger than setting R= 0.35s that shows nonfault case. In this case tripping signal is prevented.
  • 4. Discrimination Of Fault From Non-Fault Event In Transformer… 320 ||Issn||2250-3005|| (Online) ||March||2013|| ||www.ijceronline.com|| 4.2 Fault In this case a phase-ground fault (A-G) occurs at busbar 1 at instant t= 0.25s and three-phase currents are measured at busbar 7. Fig. 4 shows these three-phase currents. As shown in Fig. 5, R is close to zero that shows a fault case in which the tripping signal is issued. #1 #2 #1 #2 40.0 [MVAR] 80.0 [MW] 280.0 [MVAR] 800.0 [MW] Ea RLRL A->G flt Ia V A Bus 1 Bus 3 bus 4Bus 2 Bus 5 Fig 1. 5-bus system model Fig.2. 3- phase current due to transformer energizing Fig 3. Value of R versus time due to transformer Energizing -80 -70 -60 -50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 y Ia1 Fig. 4 Three phase current due to fault (A-G)
  • 5. Discrimination Of Fault From Non-Fault Event In Transformer… 321 ||Issn||2250-3005|| (Online) ||March||2013|| ||www.ijceronline.com|| Fig. 5 Value of R versus time due to fault (A-G) Three-phase currents are measured at the busbar 1 Fig. 4 shows these currents is close to zero which indicates that there is a fault and the relay trips. In fact, one more advantage of the suggested algorithm is that, in addition to the diagnosis of the fault in the individual occurrence from the nonfault case, it enables to discriminate a fault from simultaneous switching properly. This is necessary because, if in the case of fault, the operation of the relay is prevented and it is assumed switching case, it may lead to a serious damage. 5. Theoretical Analysis 6. Conclusion In this paper, from simulations results it indicates that enhanced sensitivity can be achieved with a symmetrical component based overcurrent protection. Also the paper presents a new algorithm- overcurrent protection based on symmetrical component and shows vastly improved performance over conventional techniques, to discriminate fault and non fault events like switching and magnetizing inrushes in transformer. Undesirable operation of relay due to the switching is prevented. The capability of the new method has been demonstrated by simulating various cases on a suitable power system for various types of asymmetrical faults. 7. Future Scope Here only the fault cases related to Transformer is studied but in future it can be studied for Alternator, Turbo-generators etc.
  • 6. Discrimination Of Fault From Non-Fault Event In Transformer… 322 ||Issn||2250-3005|| (Online) ||March||2013|| ||www.ijceronline.com|| Reference [1] F. Wang and M. H. J. Bollen, “Quantification of transient current signals in the viewpoint of overcurrent relays,” in Proc. Power Eng. Soc. General Meeting, Jul. 13–17, 2003, vol. 4, pp. 2122–2127. [2] “Classification of component switching transients in the viewpoint of protection relays,” Elect. Power Syst. Res., vol. 64, pp. 197– 207, 2003. [3] J. H. Brunke and H. J. Frohlich, “Elimination of transformer inrush currents by controlled switching-Part II: Application and performance considerations,” IEEE Trans. Power Del., vol. 16, no. 2, pp. 281–285, Apr. 2001. [4] M. A. Rahman and B. Jeyasurya, “A state-of-the-art review of transformer protection algorithms,” IEEE Trans. Power Del., vol. 3, no. 2, pp. 534–544, Apr. 1988. [5] P. Liu, O. P. Malik, C. Chen, G. S. Hope, and Y. Guo, “Improved operation of differential protection of power transformers for internal faults,” IEEE Trans. Power Del., vol. 7, no. 4, pp. 1912–1919, Oct. 1992. [6] T. S. Sidhu, M. S. Sachdev, H. C. Wood, and M. Nagpal, “Design, implementation and testing of a micro-processor-based high- speed relay for detecting transformer winding faults,” IEEE Trans. Power Del., vol. 7, no. 1, pp. 108–117, sJan. 1992, . [7] K. Yabe, “Power differential method for discrimination between fault and magnetizing inrush current in transformers,” IEEE Trans. Power Del., vol. 3, no. 3, pp. 1109–1117, Jul. 1997. [8] P. Bastard, M. Meunier, and H. Regal, “Neural network-based algorithm for power transformer differential relays,” Proc. Inst. Elect. Eng. C, vol. 142, no. 4, pp. 386–392, 1995. [9] M. C. Shin, C. W. Park, and J. H. Kim, “Fuzzy logic-based for large power transformer protection,” IEEE Trans. Power Del., vol. 18, no. 3, pp. 718–724, Jul. 2003. [10] A. T. Johns and S. K. Salman, Digital Protection for Power Systems. Stevenage, U.K.: Peregrinus, 1995. [11] S. Emmanouil, M. H. J. Bollen, and I. Y. H. Gu, “Expert system for classification and analysis of power system events,” IEEE Trans. Power Del., vol. 17, no. 2, pp. 423–428, Apr. 2002. [12] W. A. Elmore, C. A. Kramer, and S. E. Zocholl, “Effects of waveform distortion on protective relays,” IEEE Trans. Ind. Appl., vol. 29, no. 2, pp. 404–411, Mar./Apr. 1993. [13] J. F. Witte, F. P. Decesaro, and S. R. Mendis, “Damaging long-term over voltages on industrial capacitor banks due to transformer energization inrush currents,” IEEE Trans. Ind. Appl., vol. 30, no. 4, pp. 1107–1115, Jul./Aug. 1994. [14] R. Rudenberg, Transient Performance of Electric Power System. Cambridge, MA: MIT Press, 1965. [15] Improved Overcurrent Protection Using Symmetrical Components Saeed Lotfi-fard, Student Member, IEEE, Jawad Faiz, Senior ion of Member, IEEE, and Reza Iravani, Fellow, IEEE [16] Overcurrent Protection Solution based on symmetrical component Method; Mr. K. K. Rajput, Mrs. K. D. Thakur Mrs. C. H. Chavan, Journal of Information ,knowledge and research in electronics and communication engineering, ISSN 0975-6779,Nov 10 to Oct 11 ,Vol-01,issue-02. Rohit Katre: M.Tech Student in Electrical Power Systems, Bharati Vidyapeeth Deemed University College of Engineering, Pune, Maharashtra, India Prof.D.S.Chavan: Ph D (Registered), ME (Electrical), BE (Electrical), DEE Associate Professor, Co-Ordinator (R&D Cell), Co-Ordinator (PH.D.Programme Management) Bharati Vidyapeeth Deemed University College Of Engineering Pune 411043. He Is Pursuing Ph D. He Received ME (Electrical)(Power Systems) Achieved Rank Certificate In Pune University For ME Prof. S.S.sardey.: ME (Electrical Power system), BE (Electrical), Assistant Professor, Bharati Vidyapeeth Deemed University College Of Engineering Pune 411043.