Application                                            Drum Level Control Systems
Guide                                                     in the Process Industries




Drum Level Control Systems are used extensively throughout the process industries and the Utilities
to control the level of boiling water contained in boiler drums on process plant and help provide a
constant supply of steam.

If the level is too high, flooding of steam purification equipment can occur.

If the level is too low, reduction in efficiency of the treatment and recirculation function.
Pressure can also build to dangerous levels.

A drum level control system tightly controls the level whatever the disturbances, level change, increase/
decrease of steam demand, feedwater flow variations.




Suitable ABB products for use in Drum Level Control systems are:

• COMMANDER 300 Controller (for single-element systems)

• COMMANDER 1900 Controller (for single, two and three-element systems)

• MOD 30ML (for single, two and three-element systems)

• MODCELL




ABB Instrumentation
Drum Level Control Systems – in the Process Industries



                                            In the process industries, boiling water to make steam is a very important procedure.
Drum Level Control                          The control of water level is a major function in this process and it is achieved
                                            through a water steam interface established in a cylindrical vessel called the drum
Systems                                     which is usually lying on its side and located near the top of the boiler.

                                            Providing tight water level control in a drum is accomplished by utilizing one of
                                            three types of drum level control: single-element, two-element, or three-element. All
                                            three types of control strategies can be provided for utilizing one MOD 30ML
                                            Controller and supporting field products such as ABB electronic differential pressure
                                            transmitters (type 621D) and WEDGE™ flow elements.


                                            Maintaining the correct water level in the drum is critical for many reasons. A water
The Boiler Drum                             level that is too high causes flooding of the steam purification equipment; resulting
                                            in the carry over of water and impurities into the steam system. A water level that is
                                            too low results in a reduction in efficiency of the treatment and recirculation function.
                                            It can even result in tube failure due to overheating from lack of cooling water on the
                                            boiling surfaces. Normally drum level is expected to be held within 2 to 5cm of the
                                            set-point with some tolerance for temporary load changes.


                                            Under boiling conditions, steam supporting field products such as bubbles exist
Components Affecting                        below the water/steam level interface. These bubbles have volume and therefore
                                            displace water to create a misrepresentation of the true water level in the drum.
Drum Water Level                            Another effect upon drum level is pressure in the drum. Because steam bubbles
                                            compress under pressure (if the drum pressure changes due to load demands), the
                                            steam bubbles expand or contract respective to these pressure changes. A higher
                                            steam demand will cause the drum pressure to drop, and the steam bubbles to
                                            expand to give the appearance of a water level higher than it truly is. This fictitious
                                            higher water level causes the feedwater input to be shut down at a time when more
                                            water is really required. A surge in water level as a result of the drum pressure
                                            decreasing is called 'swell'. A water level decrease due to drum pressure increase
                                            is called 'shrink'.


                                            Figure 1 depicts three types of drum level control strategies with typical applications
Level Control                               for each. While single-element drum level control is acceptable for steady boiler
                                            load conditions; as load changes become more frequent, unpredictable, or severe;
Strategies                                  this type of level control cannot respond quickly enough to compensate. More
                                            information must be included and processed to predetermine the amount of water
                                            to be added to the drum to compensate for load changes. The addition of elements
                                            (flow and transmitter devices) enables the controller to predict the amount of water
                                            added to the drum to maintain drum level set-point.

                                             System Classification   Load Change Capabilities   Typical Applications
                                                                         Magnitude Rate

                                             Single-element              Moderate   Slow        Institutional and industrial heating plants
                                                                                                Steady process conditions

                                             Two-element               Moderate   Moderate      Industrial plants with essentially continuous
                                                                                                type processes and good feedwater
                                                                                                pressure regulation

                                             Three-element                 Wide Fast            Combination of batch and continuous type
                                                                                                operations such that plant steam load
                                                                                                characteristics varies continuously and
                                                                                                usually unpredictably. Most industrial power
                                                                                                applications fall into this category.


                                                         Figure 1 Application Chart for Drum Level Control System
Drum Level Control Systems – in the Process Industries



                      Figure 2 depicts the control scheme for single-element drum level control. In this
Single-Element Drum   configuration, only the water level in the drum is being measured (hence the term "
                      single element" ) . LT- 1 is an electronic differential pressure transmitter with a high
Level Control         static pressure range. The high side of the transmitter is connected to the bottom of
                      the drum. Because of the drum's static pressure, the low side of the transmitter is
                      connected to the top of the drum above the water/steam interface. This provides a
                      reference for the transmitter by cancelling the static pressure effect and allowing
                      only the water hydrostatic head to be measured.

                      A constant head reservoir is required to maintain a consistent head in the reference
                      leg of the transmitter. This is often referred to as a ''wet leg" The output of the electronic
                      DP transmitter is the process Input for the MOD 30ML Controller, (LC-1), and the
                      output is then compared to a drum level set-point. Any discrepancy between set-
                      point and drum level causes an output from the MOD 30ML controller in
                      compensation. Because controller action is reverse, as the drum level Increases, a
                      resultant output signal will decrease to close the feedwater control valve. The output
                      of the Controller is fed to the feedwater control valve (FCV-1). If the feedwater valve
                      is pneumatic, an lP (current-to-pressure) converter is required to change the
                      Controller current output to accommodate the pneumatic valve.

                      Note that the response from the controller to the feedwater control valve is reactive;
                      i.e. feedwater is added only in response to a drop in drum level. This type of control
                      is acceptable if steam load changes are not dramatic because the controller can
                      respond well to steady demands. In applications where steam load changes become
                      frequent and unpredictable, a reactive strategy is better suited. This type of system
                      requires more field devices for input.



                                 Steam
                                                                                      LX    Constant Head
                                                                                       1      Reservoir



                         Water/Steam
                          Interface
                                                                                      LT     Drum Level
                                                                                       1     Transmitter
                            Water with
                          Steam Bubbles                                               LC     Drum Level
                                               Boiler                                  1      Controller
                                               Drum                   FCV
                                                                       1              FK
                                                                                       1    A
                                                                                                M

                                                                                                Feedwater


                                                                              Feedwater
                                                                               Control
                                                                                Valve


                                       Figure 2 Single-element drum level control system
Drum Level Control Systems – in the Process Industries


                                            A two-element drum level control system is capable of providing close adherence
Two-Element Drum                            of drum level to its set-point under steady-state conditions as well as being capable
                                            of providing the required tight control during a transient. Its performance during
Level Control System                        transient conditions permits its use on many industrial boiler applications. Such
                                            applications are characterized by adequately-sized drums used with load changes
                                            of moderate rate and degree. These characteristics are usually found in plants with
                                            continuous-type processes, and those with mixed heating and processing demands.
                                            Caution should be exercised in its use on systems without reasonably constant
                                            feedwater pressure.

                                            The term 'two-element' is derived from two variables: steam flow and drum level
                                            influence on the feedwater valve position. It is often classified as a combination
                                            'feed-forward-feedback' system because the steam flow demand is fed forward as
                                            the primary index of the feedwater valve position. The drum level signal becomes
                                            the feedback which is used to constantly trim the accuracy of the feed-forward
                                            system and provide final control of the water/steam interface in the drum.

                                            Refer to Figure 3 for the control scheme of a two-element drum level control. Note
                                            the left side of the doted line is identical to that used in single-element control.
                                            Additional equipment required for two-element drum level control consists of a steam
                                            flow measuring device, a differential pressure transmitter, a square root extractor, a
                                            feedwater flow computer and a feedwater flow mode transfer station. At first this
                                            may appear like a large investment in order to gain stable drum level control, but as
                                            you will see this is not necessarily true.

                                            How it works:
                                            Steam flow is measured by the steam flow transmitter (FT-1), its signal is fed to the
                                            feedwater flow computer (FC-1) after processing through the square root extractor
                                            (FY-1). As in the single-element level control, the drum level is measured by the
                                            level transmitter (LT-1) and its signal is transmitted to the drum level controller (LC-
                                            1). In the drum level controller, the process signal is compared to the drum level set-
                                            point, where a required corrective output signal to maintain the drum level is
                                            produced. This corrective signal is sent to the feedwater flow computer. The
                                            feedwater flow computer combines the signal from the two variables, and produces
                                            an output signal to the feedwater control valve (FCV-1). Auto/Manual transfer of the
                                            feedwater control valve is accomplished via FK-1.

                                            Nearly all of the load change work is done by the feed-forward system, for example,
                                            a pound of feedwater change is made for every pound of steam flow change. The
                                            drum level control system is used for compensation only.

                                            It is expected that the drum level will be maintained very closely to the set-point
                                            value. This is true in spite of the low-to-moderate volume/throughput ratio and a
                                            wide operating range. As a result, integral response (reset) is a necessary function
                                            in the drum level controller.

                                            Using one MOD 30ML Controller, four of the functions in the two-element control
                                            scheme are accomplished: level control (LC-1), square root extraction (FY-1),
                                            feedwater flow computation (FC-1), and feedwater flow mode transfer (FK-1). The
                                            MOD 30ML Controller is a multi-functional controller providing level control for
                                            LC-1. Utilizing the linearization block in the ML will provide the required square root
                                            function to obtain a linear signal from the steam flow transmitter. A math block in the
                                            Controller enables feedwater flow computations. Finally, a feedwater flow transfer
Drum Level Control Systems – in the Process Industries


                       station is easily provided for with an operator-accessible Auto/Manual button on the
…Two-Element Drum      Controller display. Once in manual, the controller output is ramped up or down by
                       an operator using keys on the controller display. Should a totalized steam flow be
Level Control System   required,                                                                       the
                       MOD 30ML Controller provides an eight-digit display of the totalized value.

                       FT-1 is an ABB electronic transmitter providing accuracy of 0.2% and is rugged
                       enough to handle static pressures up to 6000 PSI.




                                                                                               FE
                                                                                                1


                                                                                                            Steam
                                                                 Constant Head
                                                                   Reservoir
                              Steam
                                                                   LX
                                                                                          FT           Flow
                                                                    1
                                                                                           1        Transmitter

                                                                        Drum Level        FY        √      Square Root
                                                                                           1                 Extractor
                         Water/Steam                                    Transmitter
                          Interface                               LT
                                                                   1
                                                                        Drum Level
                                                                         Controller
                           Water with                             LC                      FC        ∑ Feedwater Flow
                                                                   1                       1
                         Steam Bubbles Boiler                                                           Computer
                                       Drum                                       A
                                                                   FCV
                                                                    1
                                                                                      M   FK            Feedwater Flow
                                                                                           1             Mode Transfer
                                                                                                            Station


                                                                                                            Feedwater

                                                                            Feedwater
                                                                             Control
                                                                              Valve


                                       Figure 3 Two-element drum level control system
Drum Level Control Systems – in the Process Industries



                                            In most drum level control applications, the two-element drum level control will
Three-Element Drum                          maintain the required water/steam interface level – even under moderate load
                                            changes. However, If an unstable feedwater system exists exhibiting a variable
Level Control System                        feed header-to-drum pressure differential, or if large unpredictable steam demands
                                            are frequent, a three-element drum level control scheme should be considered. As
                                            implied from the previous information, this control strategy supplies control of
                                            feedwater flow in relationship to steam flow.

                                            The performance of the three-element control system during transient conditions
                                            makes it very useful for general industrial and utility boiler applications. It handles
                                            loads exhibiting wide and rapid rates of change. Plants which exhibit load
                                            characteristics of this type are those with mixed, continuous, and batch processing
                                            demands. It is also recommended where normal load characteristics are fairly steady;
                                            but upsets can be sudden, unpredictable and/or a significant portion of the load.

                                            How it works:
                                            Figure 4 shows the control scheme for three-element drum level control. To the left
                                            of the dotted line, the instrumentation is the same as that for the two-element drum
                                            level control, with one exception: the output of the feedwater flow computer now
                                            becomes the set-point of the feedwater flow controller (FIC-2). Equipment required
                                            to complete our three-element drum level control scheme includes an additional
                                            flow device (FE-2) and differential pressure transmitter (FT-2).

                                            The area to the left of the dotted line in figure 4 functions the same as that of a two-
                                            element drum level control. We can pick up the operation for this scheme where the
                                            output signal of the feedwater flow computer (the combination of steam flow and
                                            drum level) enters the feedwater controller (FIC-2).

                                            This in effect becomes the set-point to this controller. Feedwater flow Is measured
                                            by the transmitter (FT-2). The output signal of the feedwater flow transmitter is
                                            linearized by the square root extractor, (FY-2). This signal is the process variable to
                                            the feedwater controller and is compared to the output of the feedwater flow computer
                                            (set-point). The feedwater flow controller produces the necessary corrective signal
                                            to maintain feedwater flow at its set-point by the adjustment of the feedwater control
                                            valve (FCV-1).

                                            As in the two-element drum level control scheme, nearly all of the work necessary to
                                            compensate for load change is done by the feed-forward system (i.e. a pound of
                                            feedwater change is made for every pound of steam flow change). The drum level
                                            portion of the control scheme is used only in a compensating role. Despite low-to-
                                            moderate volume/ throughput ratio and a wide operating range, it is expected the
                                            drum level will be maintained very close to set-point. Achieving this requires use of
                                            the integrating response and reset in both the drum level and feedwater controllers.

                                            This application may suggest that an additional controller is required for the feedwater
                                            flow controller, however this Is not true. The MOD 30ML Controller is a multi-loop
                                            unit. An easily-configured feed-forward command in the MOD 30ML means no
                                            additional wiring is required to have the drum level controller and feedwater controller
                                            working together. Feedwater flow computations are effortlessly done in the maths
                                            block of the controller, all square root functions are performed within.

                                            The feedwater flow element (FE-2), is an ABB WEDGE unit. A reliable, rugged, yet
                                            accurate measuring device that will be in service for many years. Many models
                                            include the option of mounting the transmitter on the WEDGE itself, thus eliminating
                                            the need for expensive lead lines, valves and flanges.
Drum Level Control Systems – in the Process Industries



                              The feedwater flow transmitter (FT-2), is an ABB electronic differential pressure
…Three-Element Drum           transmitter. If the system is appropriately designed. FT-1. FT-2, and LT-1 may be the
                              same type of transmitter. This means stocking only one type of transmitter In the
Level Control System          case of a transmitter failure.


                                                         FE
                                                          1


                                                                                            Steam

      Steam                         Constant Head
                                      Reservoir
                               LX
                                                    FT           Flow
                                1
                                                     1        Transmitter

                                    Drum Level      FY        √ Square Root                  √
                                                     1                                FY
  Water/Steam                       Transmitter                   Extractor
   Interface                   LT                                                      2
                                1
                                    Drum Level            ∑
                                     Controller
   Water with                  LC                   FY                                FIC                    FT      Flow
 Steam Bubbles Boiler           1                    3                                 2                      2   Transmitter
                                            Feedwater Flow
               Drum                         Computer             FCV          A
                                                                  1               M
                                                                                      FK     Feedwater Flow
                                                                                       1      Mode Transfer
                                                                                                 Station


                                                                                                         Feedwater

                                                                                                    FE   Feedwater Flow
                                                                         Feedwater                   2
                                                                          Control                           Element
                                                                           Valve



                        Figure 4 Three-element drum level control system
DLC#_1GG.pdf
                                                                                                                                     Issue A




                                                                               The Company's policy is one of continuous product
                                                                               improvement and the right is reserved to modify the
                                                                                                                                     AG/DLC




                                                                               information contained herein without notice.

                                                                               © ABB 1997                                  (8.97)




ABB Kent-Taylor Ltd.       ABB Instrumentation Inc.   ABB Kent-Taylor SpA
St. Neots                  PO Box 20550, Rochester    22016 Lenno
Cambs.                     New York 14602-0550        Como
England, PE19 3EU          USA                        Italy
Tel: +44 (0) 1480 475321   Tel: +1 716 292 6050       Tel: +39 (0) 344 58111
Fax: +44 (0) 1480 217948   Fax: +1 716 273 6207       Fax: +39 (0) 344 56278

Más contenido relacionado

La actualidad más candente

Parametric Studies of an Automotive Air Conditioning System
Parametric Studies of an Automotive Air Conditioning System Parametric Studies of an Automotive Air Conditioning System
Parametric Studies of an Automotive Air Conditioning System IDES Editor
 
Cih taco3-calc flow---web-bill
Cih taco3-calc flow---web-billCih taco3-calc flow---web-bill
Cih taco3-calc flow---web-billMazhar Sheikh
 
Water to Water Heat Recovery
Water to Water Heat RecoveryWater to Water Heat Recovery
Water to Water Heat RecoveryIllinois ASHRAE
 
Thermosyphon Reboiler & its type with operational parameter.
Thermosyphon  Reboiler & its type with operational parameter.Thermosyphon  Reboiler & its type with operational parameter.
Thermosyphon Reboiler & its type with operational parameter.Govind Keshavrao Patil
 
Water Management in Thermal Power Plants .pdf
Water Management in Thermal Power Plants .pdfWater Management in Thermal Power Plants .pdf
Water Management in Thermal Power Plants .pdfeldoctol
 
Design of thermosyphon reboiler
Design of thermosyphon reboilerDesign of thermosyphon reboiler
Design of thermosyphon reboilerHarshad Vaghela
 
Life cycle analysis of hvac desining multi split vrf system
Life cycle analysis of hvac desining multi split vrf systemLife cycle analysis of hvac desining multi split vrf system
Life cycle analysis of hvac desining multi split vrf systemSYED KHURSHID ALAM ARZOO
 
Chilled water plants
Chilled water plantsChilled water plants
Chilled water plantsAwais Jalali
 

La actualidad más candente (9)

Parametric Studies of an Automotive Air Conditioning System
Parametric Studies of an Automotive Air Conditioning System Parametric Studies of an Automotive Air Conditioning System
Parametric Studies of an Automotive Air Conditioning System
 
Cih taco3-calc flow---web-bill
Cih taco3-calc flow---web-billCih taco3-calc flow---web-bill
Cih taco3-calc flow---web-bill
 
Water to Water Heat Recovery
Water to Water Heat RecoveryWater to Water Heat Recovery
Water to Water Heat Recovery
 
Enclosure climatecontrol
Enclosure climatecontrolEnclosure climatecontrol
Enclosure climatecontrol
 
Thermosyphon Reboiler & its type with operational parameter.
Thermosyphon  Reboiler & its type with operational parameter.Thermosyphon  Reboiler & its type with operational parameter.
Thermosyphon Reboiler & its type with operational parameter.
 
Water Management in Thermal Power Plants .pdf
Water Management in Thermal Power Plants .pdfWater Management in Thermal Power Plants .pdf
Water Management in Thermal Power Plants .pdf
 
Design of thermosyphon reboiler
Design of thermosyphon reboilerDesign of thermosyphon reboiler
Design of thermosyphon reboiler
 
Life cycle analysis of hvac desining multi split vrf system
Life cycle analysis of hvac desining multi split vrf systemLife cycle analysis of hvac desining multi split vrf system
Life cycle analysis of hvac desining multi split vrf system
 
Chilled water plants
Chilled water plantsChilled water plants
Chilled water plants
 

Similar a Dlc 1gg

Boiler drum's water level control
Boiler drum's water level controlBoiler drum's water level control
Boiler drum's water level controlMukul kashiwal
 
Importance of three elements boiler drum level control and its installation i...
Importance of three elements boiler drum level control and its installation i...Importance of three elements boiler drum level control and its installation i...
Importance of three elements boiler drum level control and its installation i...ijics
 
Boiler instrumentation-and-controls
Boiler instrumentation-and-controlsBoiler instrumentation-and-controls
Boiler instrumentation-and-controlsDARSHAN B S
 
Flow Control Using Variable Frequency Drive In Water Treatment Process of Dei...
Flow Control Using Variable Frequency Drive In Water Treatment Process of Dei...Flow Control Using Variable Frequency Drive In Water Treatment Process of Dei...
Flow Control Using Variable Frequency Drive In Water Treatment Process of Dei...IJTET Journal
 
Boiler Drum level measurement in Thermal Power Stations
Boiler Drum level measurement in Thermal Power StationsBoiler Drum level measurement in Thermal Power Stations
Boiler Drum level measurement in Thermal Power StationsManohar Tatwawadi
 
Boiler Feed Water Control
Boiler Feed Water ControlBoiler Feed Water Control
Boiler Feed Water Controlno suhaila
 
Flooding of a distillation column
Flooding of a distillation columnFlooding of a distillation column
Flooding of a distillation columnKarnav Rana
 
Electrical thermal plant boiler temperature and water level monitoring
Electrical thermal plant boiler temperature and water level monitoringElectrical thermal plant boiler temperature and water level monitoring
Electrical thermal plant boiler temperature and water level monitoringEcway Technologies
 
Electrical thermal plant boiler temperature and water level monitoring
Electrical thermal plant boiler temperature and water level monitoringElectrical thermal plant boiler temperature and water level monitoring
Electrical thermal plant boiler temperature and water level monitoringEcwayt
 
Electrical thermal plant boiler temperature and water level monitoring
Electrical thermal plant boiler temperature and water level monitoringElectrical thermal plant boiler temperature and water level monitoring
Electrical thermal plant boiler temperature and water level monitoringEcwaytech
 
Boiler automation new
Boiler automation newBoiler automation new
Boiler automation newAmar Gupta
 
TECHNIQUE TO REDUCE DUMP LOAD IN ISOLATED HYDRO POWER PLANT BY LOAD FREQUENCY...
TECHNIQUE TO REDUCE DUMP LOAD IN ISOLATED HYDRO POWER PLANT BY LOAD FREQUENCY...TECHNIQUE TO REDUCE DUMP LOAD IN ISOLATED HYDRO POWER PLANT BY LOAD FREQUENCY...
TECHNIQUE TO REDUCE DUMP LOAD IN ISOLATED HYDRO POWER PLANT BY LOAD FREQUENCY...Journal For Research
 
Power Plant Instrumentation & Control
Power Plant Instrumentation & ControlPower Plant Instrumentation & Control
Power Plant Instrumentation & ControlDebyenduChakroborty
 

Similar a Dlc 1gg (20)

Boiler drum's water level control
Boiler drum's water level controlBoiler drum's water level control
Boiler drum's water level control
 
Importance of three elements boiler drum level control and its installation i...
Importance of three elements boiler drum level control and its installation i...Importance of three elements boiler drum level control and its installation i...
Importance of three elements boiler drum level control and its installation i...
 
Boiler instrumentation-and-controls
Boiler instrumentation-and-controlsBoiler instrumentation-and-controls
Boiler instrumentation-and-controls
 
Flow Control Using Variable Frequency Drive In Water Treatment Process of Dei...
Flow Control Using Variable Frequency Drive In Water Treatment Process of Dei...Flow Control Using Variable Frequency Drive In Water Treatment Process of Dei...
Flow Control Using Variable Frequency Drive In Water Treatment Process of Dei...
 
Shrink and swell
Shrink and swellShrink and swell
Shrink and swell
 
Boiler Drum level measurement in Thermal Power Stations
Boiler Drum level measurement in Thermal Power StationsBoiler Drum level measurement in Thermal Power Stations
Boiler Drum level measurement in Thermal Power Stations
 
Boiler Feed Water Control
Boiler Feed Water ControlBoiler Feed Water Control
Boiler Feed Water Control
 
Flooding of a distillation column
Flooding of a distillation columnFlooding of a distillation column
Flooding of a distillation column
 
Electrical thermal plant boiler temperature and water level monitoring
Electrical thermal plant boiler temperature and water level monitoringElectrical thermal plant boiler temperature and water level monitoring
Electrical thermal plant boiler temperature and water level monitoring
 
Electrical thermal plant boiler temperature and water level monitoring
Electrical thermal plant boiler temperature and water level monitoringElectrical thermal plant boiler temperature and water level monitoring
Electrical thermal plant boiler temperature and water level monitoring
 
Electrical thermal plant boiler temperature and water level monitoring
Electrical thermal plant boiler temperature and water level monitoringElectrical thermal plant boiler temperature and water level monitoring
Electrical thermal plant boiler temperature and water level monitoring
 
Industrial Boiler Optimization Toolkit
Industrial Boiler Optimization ToolkitIndustrial Boiler Optimization Toolkit
Industrial Boiler Optimization Toolkit
 
Boiler automation new
Boiler automation newBoiler automation new
Boiler automation new
 
DOT 2002 Functional Approach to Flow Assurance
DOT 2002 Functional Approach to Flow AssuranceDOT 2002 Functional Approach to Flow Assurance
DOT 2002 Functional Approach to Flow Assurance
 
Cascade control
Cascade controlCascade control
Cascade control
 
B035208015
B035208015B035208015
B035208015
 
F05732228
F05732228F05732228
F05732228
 
Drun level control
Drun level controlDrun level control
Drun level control
 
TECHNIQUE TO REDUCE DUMP LOAD IN ISOLATED HYDRO POWER PLANT BY LOAD FREQUENCY...
TECHNIQUE TO REDUCE DUMP LOAD IN ISOLATED HYDRO POWER PLANT BY LOAD FREQUENCY...TECHNIQUE TO REDUCE DUMP LOAD IN ISOLATED HYDRO POWER PLANT BY LOAD FREQUENCY...
TECHNIQUE TO REDUCE DUMP LOAD IN ISOLATED HYDRO POWER PLANT BY LOAD FREQUENCY...
 
Power Plant Instrumentation & Control
Power Plant Instrumentation & ControlPower Plant Instrumentation & Control
Power Plant Instrumentation & Control
 

Dlc 1gg

  • 1. Application Drum Level Control Systems Guide in the Process Industries Drum Level Control Systems are used extensively throughout the process industries and the Utilities to control the level of boiling water contained in boiler drums on process plant and help provide a constant supply of steam. If the level is too high, flooding of steam purification equipment can occur. If the level is too low, reduction in efficiency of the treatment and recirculation function. Pressure can also build to dangerous levels. A drum level control system tightly controls the level whatever the disturbances, level change, increase/ decrease of steam demand, feedwater flow variations. Suitable ABB products for use in Drum Level Control systems are: • COMMANDER 300 Controller (for single-element systems) • COMMANDER 1900 Controller (for single, two and three-element systems) • MOD 30ML (for single, two and three-element systems) • MODCELL ABB Instrumentation
  • 2. Drum Level Control Systems – in the Process Industries In the process industries, boiling water to make steam is a very important procedure. Drum Level Control The control of water level is a major function in this process and it is achieved through a water steam interface established in a cylindrical vessel called the drum Systems which is usually lying on its side and located near the top of the boiler. Providing tight water level control in a drum is accomplished by utilizing one of three types of drum level control: single-element, two-element, or three-element. All three types of control strategies can be provided for utilizing one MOD 30ML Controller and supporting field products such as ABB electronic differential pressure transmitters (type 621D) and WEDGE™ flow elements. Maintaining the correct water level in the drum is critical for many reasons. A water The Boiler Drum level that is too high causes flooding of the steam purification equipment; resulting in the carry over of water and impurities into the steam system. A water level that is too low results in a reduction in efficiency of the treatment and recirculation function. It can even result in tube failure due to overheating from lack of cooling water on the boiling surfaces. Normally drum level is expected to be held within 2 to 5cm of the set-point with some tolerance for temporary load changes. Under boiling conditions, steam supporting field products such as bubbles exist Components Affecting below the water/steam level interface. These bubbles have volume and therefore displace water to create a misrepresentation of the true water level in the drum. Drum Water Level Another effect upon drum level is pressure in the drum. Because steam bubbles compress under pressure (if the drum pressure changes due to load demands), the steam bubbles expand or contract respective to these pressure changes. A higher steam demand will cause the drum pressure to drop, and the steam bubbles to expand to give the appearance of a water level higher than it truly is. This fictitious higher water level causes the feedwater input to be shut down at a time when more water is really required. A surge in water level as a result of the drum pressure decreasing is called 'swell'. A water level decrease due to drum pressure increase is called 'shrink'. Figure 1 depicts three types of drum level control strategies with typical applications Level Control for each. While single-element drum level control is acceptable for steady boiler load conditions; as load changes become more frequent, unpredictable, or severe; Strategies this type of level control cannot respond quickly enough to compensate. More information must be included and processed to predetermine the amount of water to be added to the drum to compensate for load changes. The addition of elements (flow and transmitter devices) enables the controller to predict the amount of water added to the drum to maintain drum level set-point. System Classification Load Change Capabilities Typical Applications Magnitude Rate Single-element Moderate Slow Institutional and industrial heating plants Steady process conditions Two-element Moderate Moderate Industrial plants with essentially continuous type processes and good feedwater pressure regulation Three-element Wide Fast Combination of batch and continuous type operations such that plant steam load characteristics varies continuously and usually unpredictably. Most industrial power applications fall into this category. Figure 1 Application Chart for Drum Level Control System
  • 3. Drum Level Control Systems – in the Process Industries Figure 2 depicts the control scheme for single-element drum level control. In this Single-Element Drum configuration, only the water level in the drum is being measured (hence the term " single element" ) . LT- 1 is an electronic differential pressure transmitter with a high Level Control static pressure range. The high side of the transmitter is connected to the bottom of the drum. Because of the drum's static pressure, the low side of the transmitter is connected to the top of the drum above the water/steam interface. This provides a reference for the transmitter by cancelling the static pressure effect and allowing only the water hydrostatic head to be measured. A constant head reservoir is required to maintain a consistent head in the reference leg of the transmitter. This is often referred to as a ''wet leg" The output of the electronic DP transmitter is the process Input for the MOD 30ML Controller, (LC-1), and the output is then compared to a drum level set-point. Any discrepancy between set- point and drum level causes an output from the MOD 30ML controller in compensation. Because controller action is reverse, as the drum level Increases, a resultant output signal will decrease to close the feedwater control valve. The output of the Controller is fed to the feedwater control valve (FCV-1). If the feedwater valve is pneumatic, an lP (current-to-pressure) converter is required to change the Controller current output to accommodate the pneumatic valve. Note that the response from the controller to the feedwater control valve is reactive; i.e. feedwater is added only in response to a drop in drum level. This type of control is acceptable if steam load changes are not dramatic because the controller can respond well to steady demands. In applications where steam load changes become frequent and unpredictable, a reactive strategy is better suited. This type of system requires more field devices for input. Steam LX Constant Head 1 Reservoir Water/Steam Interface LT Drum Level 1 Transmitter Water with Steam Bubbles LC Drum Level Boiler 1 Controller Drum FCV 1 FK 1 A M Feedwater Feedwater Control Valve Figure 2 Single-element drum level control system
  • 4. Drum Level Control Systems – in the Process Industries A two-element drum level control system is capable of providing close adherence Two-Element Drum of drum level to its set-point under steady-state conditions as well as being capable of providing the required tight control during a transient. Its performance during Level Control System transient conditions permits its use on many industrial boiler applications. Such applications are characterized by adequately-sized drums used with load changes of moderate rate and degree. These characteristics are usually found in plants with continuous-type processes, and those with mixed heating and processing demands. Caution should be exercised in its use on systems without reasonably constant feedwater pressure. The term 'two-element' is derived from two variables: steam flow and drum level influence on the feedwater valve position. It is often classified as a combination 'feed-forward-feedback' system because the steam flow demand is fed forward as the primary index of the feedwater valve position. The drum level signal becomes the feedback which is used to constantly trim the accuracy of the feed-forward system and provide final control of the water/steam interface in the drum. Refer to Figure 3 for the control scheme of a two-element drum level control. Note the left side of the doted line is identical to that used in single-element control. Additional equipment required for two-element drum level control consists of a steam flow measuring device, a differential pressure transmitter, a square root extractor, a feedwater flow computer and a feedwater flow mode transfer station. At first this may appear like a large investment in order to gain stable drum level control, but as you will see this is not necessarily true. How it works: Steam flow is measured by the steam flow transmitter (FT-1), its signal is fed to the feedwater flow computer (FC-1) after processing through the square root extractor (FY-1). As in the single-element level control, the drum level is measured by the level transmitter (LT-1) and its signal is transmitted to the drum level controller (LC- 1). In the drum level controller, the process signal is compared to the drum level set- point, where a required corrective output signal to maintain the drum level is produced. This corrective signal is sent to the feedwater flow computer. The feedwater flow computer combines the signal from the two variables, and produces an output signal to the feedwater control valve (FCV-1). Auto/Manual transfer of the feedwater control valve is accomplished via FK-1. Nearly all of the load change work is done by the feed-forward system, for example, a pound of feedwater change is made for every pound of steam flow change. The drum level control system is used for compensation only. It is expected that the drum level will be maintained very closely to the set-point value. This is true in spite of the low-to-moderate volume/throughput ratio and a wide operating range. As a result, integral response (reset) is a necessary function in the drum level controller. Using one MOD 30ML Controller, four of the functions in the two-element control scheme are accomplished: level control (LC-1), square root extraction (FY-1), feedwater flow computation (FC-1), and feedwater flow mode transfer (FK-1). The MOD 30ML Controller is a multi-functional controller providing level control for LC-1. Utilizing the linearization block in the ML will provide the required square root function to obtain a linear signal from the steam flow transmitter. A math block in the Controller enables feedwater flow computations. Finally, a feedwater flow transfer
  • 5. Drum Level Control Systems – in the Process Industries station is easily provided for with an operator-accessible Auto/Manual button on the …Two-Element Drum Controller display. Once in manual, the controller output is ramped up or down by an operator using keys on the controller display. Should a totalized steam flow be Level Control System required, the MOD 30ML Controller provides an eight-digit display of the totalized value. FT-1 is an ABB electronic transmitter providing accuracy of 0.2% and is rugged enough to handle static pressures up to 6000 PSI. FE 1 Steam Constant Head Reservoir Steam LX FT Flow 1 1 Transmitter Drum Level FY √ Square Root 1 Extractor Water/Steam Transmitter Interface LT 1 Drum Level Controller Water with LC FC ∑ Feedwater Flow 1 1 Steam Bubbles Boiler Computer Drum A FCV 1 M FK Feedwater Flow 1 Mode Transfer Station Feedwater Feedwater Control Valve Figure 3 Two-element drum level control system
  • 6. Drum Level Control Systems – in the Process Industries In most drum level control applications, the two-element drum level control will Three-Element Drum maintain the required water/steam interface level – even under moderate load changes. However, If an unstable feedwater system exists exhibiting a variable Level Control System feed header-to-drum pressure differential, or if large unpredictable steam demands are frequent, a three-element drum level control scheme should be considered. As implied from the previous information, this control strategy supplies control of feedwater flow in relationship to steam flow. The performance of the three-element control system during transient conditions makes it very useful for general industrial and utility boiler applications. It handles loads exhibiting wide and rapid rates of change. Plants which exhibit load characteristics of this type are those with mixed, continuous, and batch processing demands. It is also recommended where normal load characteristics are fairly steady; but upsets can be sudden, unpredictable and/or a significant portion of the load. How it works: Figure 4 shows the control scheme for three-element drum level control. To the left of the dotted line, the instrumentation is the same as that for the two-element drum level control, with one exception: the output of the feedwater flow computer now becomes the set-point of the feedwater flow controller (FIC-2). Equipment required to complete our three-element drum level control scheme includes an additional flow device (FE-2) and differential pressure transmitter (FT-2). The area to the left of the dotted line in figure 4 functions the same as that of a two- element drum level control. We can pick up the operation for this scheme where the output signal of the feedwater flow computer (the combination of steam flow and drum level) enters the feedwater controller (FIC-2). This in effect becomes the set-point to this controller. Feedwater flow Is measured by the transmitter (FT-2). The output signal of the feedwater flow transmitter is linearized by the square root extractor, (FY-2). This signal is the process variable to the feedwater controller and is compared to the output of the feedwater flow computer (set-point). The feedwater flow controller produces the necessary corrective signal to maintain feedwater flow at its set-point by the adjustment of the feedwater control valve (FCV-1). As in the two-element drum level control scheme, nearly all of the work necessary to compensate for load change is done by the feed-forward system (i.e. a pound of feedwater change is made for every pound of steam flow change). The drum level portion of the control scheme is used only in a compensating role. Despite low-to- moderate volume/ throughput ratio and a wide operating range, it is expected the drum level will be maintained very close to set-point. Achieving this requires use of the integrating response and reset in both the drum level and feedwater controllers. This application may suggest that an additional controller is required for the feedwater flow controller, however this Is not true. The MOD 30ML Controller is a multi-loop unit. An easily-configured feed-forward command in the MOD 30ML means no additional wiring is required to have the drum level controller and feedwater controller working together. Feedwater flow computations are effortlessly done in the maths block of the controller, all square root functions are performed within. The feedwater flow element (FE-2), is an ABB WEDGE unit. A reliable, rugged, yet accurate measuring device that will be in service for many years. Many models include the option of mounting the transmitter on the WEDGE itself, thus eliminating the need for expensive lead lines, valves and flanges.
  • 7. Drum Level Control Systems – in the Process Industries The feedwater flow transmitter (FT-2), is an ABB electronic differential pressure …Three-Element Drum transmitter. If the system is appropriately designed. FT-1. FT-2, and LT-1 may be the same type of transmitter. This means stocking only one type of transmitter In the Level Control System case of a transmitter failure. FE 1 Steam Steam Constant Head Reservoir LX FT Flow 1 1 Transmitter Drum Level FY √ Square Root √ 1 FY Water/Steam Transmitter Extractor Interface LT 2 1 Drum Level ∑ Controller Water with LC FY FIC FT Flow Steam Bubbles Boiler 1 3 2 2 Transmitter Feedwater Flow Drum Computer FCV A 1 M FK Feedwater Flow 1 Mode Transfer Station Feedwater FE Feedwater Flow Feedwater 2 Control Element Valve Figure 4 Three-element drum level control system
  • 8. DLC#_1GG.pdf Issue A The Company's policy is one of continuous product improvement and the right is reserved to modify the AG/DLC information contained herein without notice. © ABB 1997 (8.97) ABB Kent-Taylor Ltd. ABB Instrumentation Inc. ABB Kent-Taylor SpA St. Neots PO Box 20550, Rochester 22016 Lenno Cambs. New York 14602-0550 Como England, PE19 3EU USA Italy Tel: +44 (0) 1480 475321 Tel: +1 716 292 6050 Tel: +39 (0) 344 58111 Fax: +44 (0) 1480 217948 Fax: +1 716 273 6207 Fax: +39 (0) 344 56278