Work station series for solar water heating control system


 Part 1: Operation instruction

Ⅰ. General information
 1. About this manual
     This manual describes the installation, function and operation of an integrated solar work station,
     which is suitable for split pressurized solar heating system. Before installing and operating the device,
     please read the following information carefully.


 2. Safety regulations
  ♦ Installation, commissioning and maintenance of the device may only be performed by professional
    personal.
  ♦ All operations that require opening the device are only to be conducted cleared from the power
    supply. All safety regulations for working on the power supply are valid.
  ♦ The device must not be installed in rooms where easily inflammable material (e.g. gas or oil)
    mixtures are present or may occur.
  ♦ Before connecting the work station, make sure that the energy supply matches the specifications of
    the device. Protect the solar station against overloading and short-circuiting.
  ♦ All devices connected to the work station must conform to the technical specifications of the device.
  ♦ As soon as it becomes evident that safe operation is no longer possible, please immediately take
    the device out of operation.
  ♦ Without lightning rod, please don’t use this device during a thunderstorm.


 3. Liability waiver
  ♦ Improper installation or operation can cause damages to material and persons. The manufacturer
    cannot monitor the compliance with these instructions or the circumstances and methods used for
    installation, operation, utilization and maintenance of this device. Damage by mishandling or
    improper installation on costumer site is immediately leading to warranty exclusion.
  ♦ As faults can never be excluded, we don’t offer a guarantee for the completeness of the drawings
    and texts of this manual, they only represent some examples. They can only be used on own risk.
    No liability is assumed for incorrect, incomplete or false information and the resulting damages.
  ♦ The manufacturer preserves the right to put changes to product, technical date or installation and
    operation instructions without prior notice.


 4. Symbols used
         Danger: Failure to observe these instructions can lead to injury of persons or safety risks.

         Attention: Failure to observe these instructions can result in damage to the product or
         environment.

         Note: Useful information and instructions.

 ì       Operation steps: Indication of operation steps.
                                                      1
Work station series for solar water heating control system

Ⅱ. Product information
  1. Components




      No            Components                            Function description
      1     Operating screen (LCD)     Display operating menu.
                                       Display system pressure (Max. 10 bar, normal working
       2    Manometer
                                       pressure is approx. 2 bar)
      3     Pump speed regulation      Three speed levels available, offers different flow rate.
      4     Circulation pump           WILO Star RS 15/6 (110V or 220V)
      5     Input and Output signals   Temperature sensors, power cord and other outputs.
      6     Security valve             Protect the system against over-pressure.
            Expansion vessel           Connect expansion vessel. Expansion vessel balances
      7
            connector                  the system pressure.
                                       Copper material, left side. Max. working temperature 150
      8     Return flow
                                       ℃, screw thread 1/2’ (DN15) as standard
      9     Mounting point             For fixing the solar pump station


 2. Technical data

    Dimension                             450×310×150mm
    Input voltage                         200V~240V AC or 100V~120V AC
    Power                                 ≤3W
    Accuracy of temperature measuring     ±1℃
    Range of temperature measuring        PT1000 : 0~199℃ NTC10K: 0~99℃
                                          2 x PT1000 sensor temperature probe ≤500℃,
                                                                     silicon cable ≤280℃;
    Input signals
                                          4 x NTC10K sensor temperature probe≤135℃,
                                                                        PVC cable ≤105℃
                                          1 x Auxiliary heating output (Max. load current: 15A)
    Output signals
                                          4 x Relay output (Max. load current: 3A)
    System design pressure                10 bar

                                                   2
Work station series for solar water heating control system

   Safety valve response pressure        6 bar
   WILO pump                             SR15/6
   Ambient temperature                   -10~50℃
   Water protection grade                IP40


3. Display signals

                 Weekday: 7days of week can be set (e.g. Week 1 means “Monday”).

                 Time: Setting hours and minutes.


                 Time-controlled auxiliary heating: Setting three heating time periods.

                 Time-controlled hot water circulation: Setting three time periods.

                 Storage temperature: As turning-on/off temperature value for auxiliary heating.

                 Solar system indication. 8 systems are available.


                 Frost protection.


                 Temperature-controlled circulation function


                 Overheating protection for storage.


                 High temperature protection for solar collector.


                 Holiday function.


                 Switch on/off auxiliary heating manually.

                 Forbid/permit using auxiliary heating.


                 Reset.


                 Extended temperature-difference circulation function


                 Recooling the system through by-pass


                 Temperature display.


                 Flow rate display.

                                                  3
Work station series for solar water heating control system

Ⅲ System description (8 systems available)
    Danger: If there is only one temperature sensor in water storage (usually in bottom part T2),
    it is possible, and that the auxiliary heating function will not be activated or deactivated at a
    right time, because the water temperature in top part of the storage (T3) cannot be measured.
    In this case, if you still want to use auxiliary heating function, control program will automaticall y
    take the signal from bottom temperature sensor (T2) instead of T3. However, water in top part
    of tank might often be overheated. It may cause damages to material and persons. So it is
    highly recommended not to use auxiliary heating in such a case.

    Note: To lock this function, please press “Choose Function” button until the signal”                   ”
    appears on the screen (see details in 3.8 Forbid/Permit auxiliary heating).


1. System 1: 1 collector array – 1 storage – 1 pump




   Description:
         The solar collector pump (P1) is activated as soon as the temperature difference
      between the collector array (T1) and the storage (T2) is reached. When the temperature
      difference between T1 and T2 drops below the switch-off temperature difference, or the
      storage (T3) reaches its maximum storage temperature, the solar pump (P1) will be
      switched off.
         T3 is used to measure the temperature of the top part of storage. If the turning-on
      condition for auxiliary heating is filled, the auxiliary heating will be activated

      T1: Temperature sensor for collector 1
      T2: Temperature sensor in the bottom part of storage 1
      T3: Temperature sensor in the top part of storage 1
      T4: Temperature sensor for hot water pipe
      P1: Solar collector pump
      P2: Solar circulation pump
      Note:
      1. T3, T4, P2 are suitable for system 1-8.
      2. T3 is alternative, when no sensor (T3) is installed in the top part of tank, control system
         will use the signal of sensor T2 automatically to control the auxiliary heating.




                                                    4
Work station series for solar water heating control system

2. System 2: 1 collector array – 2 storage – 2 pumps




    Description:
          When switch–on temperature difference between collector array (T1) and one of the
       storage (T2 or T5) is reached, the solar circuit pump (P1) or (P0) will switched on.
       According to the priority switching, tw o storages (T2, T5) will be loaded one by one. Until
       either of switch-off temperature difference between collector array (T1) and storage (T2,
       T5) is reached, or the maximum storage temperature is reached, pump stops working.

       T1: Temperature sensor for collector 1
       T2: Temperature sensor in the bottom part of storage 1
       T3: Temperature sensor in the top part of storage 1
       T4: Temperature sensor for hot water pipe
       T5: Temperature sensor in storage 2
       P0: Solar collector pump
       P1: Solar collector pump
   Note:
       The default priority storage is storage1.


3. System 3: 1 collector array – 2 storages– 1 pump – 1 valve




   Description:
       When switch–on temperature difference between collector array (T1) and one of the
     storage (T2 or T5) is reached, then the solar pump (P1) is switched on and valve (R1) is
     set to the correct position depending on the storage to be loaded. According to the priority
     switching, both storages (T2, T5) will be loaded one by one, until the relevant switch-off
     temperature difference between the collector array (T1) and storage are reached.
       (T2, T5) is reached or the maximum storage temperature of T2 or T5 is reached, pump
     and valve stop working.
                                                   5
Work station series for solar water heating control system
      T1: Temperature sensor for collector 1
      T2: Temperature sensor in the bottom part of storage 1
      T5: Temperature sensor in the bottom part of storage 2
      P1: Solar collector pump
      R1: Electromagnetic 3-way valve
   Note:
     1. When there is no power in the system, the electromagnetic valve (R1) must be set to
         storage (T2).
     2. The default priority storage is storage 1.


4. System 4: 2 collector arrays – 1 storage tank – 2 pumps




   Description:
        When switch–on temperature difference between storage (T2) and collector array (T1,
      T0) is reached, then solar pump (P1) for collector array 1 (T1) or solar circuit pump (P0) for
      collector array 2 (T0) is switched on, depending on where the temperature difference
      occurs firstly. If the switch-on temperature difference is reached for both collector arrays
      (T1, T0), then both pumps (P1, P0) are switched on. The pumps switch-off independentl y
      for each other. When either of relevant switch-off temperature difference between one or
      both collector arrays (T1, T0) and the storage (T2) falls below the threshold or the maximum
      storage temperature is reached, then the corresponding circuit pump is switched off.

      T0: Temperature sensor for collector 2
      T1: Temperature sensor for collector 1
      T2: Temperature sensor in the bottom part of storage1
      P0: Solar collector pump
      P1: Solar collector pump


5. System 5: 2 collector arrays – 1 storage – 1 pump – 1 valve




    Description:
                                                 6
Work station series for solar water heating control system
         The solar pump (P1) is switched on as soon as the switch–on temperature difference
       between one of the two collector arrays (T1, T0) and storage 1 (T2) is reached, the valve
       R1 is always set so that flow occurs through the warmer of the two collector arrays (T1,
       T2). The pump P1 switch-off as soon as the switch-off temperature difference between
       two collector arrays (T1, T0) and storage (T2) is reached or the maximum storage
       temperature is reached.

       T0: Temperature sensor for collector 2
       T1: Temperature sensor for collector 1
       T2: Temperature sensor in the bottom part of storage 1
       P1: Solar collector pump
       R1: Electromagnetic 3-way valve
   Note:
      When there is no power in the system, the electromagnetic valve (R1) must be set to collector
      array 1.


6. System 6: 2 collector arrays – 2 storages – 1 pump – 2 valves




   Description:
        When switch-on temperature difference between two storage (T2, T5) and collector array
     1 (T1) or collector array 2 (T0) is reached, then the solar circuit pump (P1) is switched on,
     electromagnetic valve (R2) switches the relevant storage into the solar circuit, and
     electromagnetic valve (R1) switches the affected collector array (T1 or T2) into the solar
     circuit. Pump (P1) stops working when the switch-off temperature difference between either
     or both collector arrays and its corresponding storage 1 (T2) and storage 2 (T5) falls below
     the threshold or the maximum storage temperature (T2 or T5) is reached.

     T0: Temperature sensor for collector 2
     T1: Temperature sensor for collector 1
     T2: Temperature sensor in the bottom part of storage 1
     T5: Temperature sensor in the bottom part of storage 2
     P1: Solar collector pump 1
     R1: Electromagnetic 3-way valve
     R2: Electromagnetic 3-way valve
   Note:
     1. When there is no power in the system, the electromagnetic valve (R2) must be set to
        storage 1 (T2), the electromagnetic valve (R1) must be set to collector array 1(T1).
     2. Default priority tank is storage 1.

                                                 7
Work station series for solar water heating control system

7. System 7: 2 collector arrays – 2 storages – 2 pumps – 1 valve




   Description:
       When switch-on temperature difference between one of the two storages (T2, T5) and
     collector array 1 (T1) or collector array 2 (T0) is exceeded, then the switching valve R2
     switched the corresponding collector array (T1 or T0) into the solar circuit. Depending on
     which storage has reached the switch-on temperature, solar pump (P1) for storage 1 (T2)
     or solar pump (P0) for storage 2 (T5) is switched on. The switching valve R2 is always set
     so that flow occurs through the warmer of the two collector arrays. Both storages (T2, T5)
     will be loaded one by one, according to the priority switching, until either the relevant
     switch-off temperature difference falls below the threshold, or the maximum storage
     temperature (T2 or T5) is reached.

      T0: Temperature sensor for collector 2
      T1: Temperature sensor for collector 1
      T2: Temperature sensor in the bottom part of storage 1
      T5: Temperature sensor in the bottom part of storage 2
      P0: Solar collector pump
      P1: Solar collector pump
      R2: Electromagnetic 3-way valve
   Note:
     1. When there is no power in the system, the electromagnetic valve (R2) must be set to
        collector array 1(T1).
     2. Default priority storage is storage 1.


8. System 8: 2 collector arrays – 2 storages – 2 pumps – 1 valve




    Description:
        When switch-on temperature difference between one of the two storage (T2, T5) and
      collector array1 (T1) and collector array2 (T0) is reached, then the switching valve (R2)

                                               8
Work station series for solar water heating control system
  switches relevant storage (T2, or T5) to the solar circuit. Then either solar circuit pump P1 for
  collector array 1 (T1) or solar circuit pump P0 for collector array 2 (T0) is switch-on,
  Depending on where the temperature difference occurs. If the switch-on temperature
  difference is reached between collector arrays (T1, T0), then both pumps (P1, P0) are
  switch-on. Pump (P1, P0) switch-off independently of each other, when both of relevant
  switch-off temperature difference between collector arrays (T1, T0) and relevant storage (T2
  or T5) falls below the threshold, or the maximum storage temperature is reached.

  T0: Temperature sensor for collector 2
  T1: Temperature sensor for collector 1
  T2: Temperature sensor in the bottom part of storage 1
  T5: Temperature sensor in the bottom part of storage 2
  P0: Solar collector pimp 2
  P1: Solar collector pump 1
  R2: Electromagnetic 3-way valve
Note:
  1. When no power is in the system, the electromagnetic valve (R2) must be set to storage 1
     (T1).
  2. Default priority storage is storage 1.




                                              9
Work station series for solar water heating control system

Ⅳ Functions and operation
        Danger: Before connecting the power supply, make sure that the storage, solar collector, solar
        work station and all temperature sensors are good connected!

        Note: For safety, auxiliary heating is locked at delivery state. The single “       ” displays on the
        screen. If you want to use this function, please see operation: 3.6 Forbid/Permit using auxiliary
        heating.


 1. Setting week and time
  After power supply is switched on, please firstly set the time
  of the system.
ì Press “System Setting” button until the signal “Week ”
   displays on the screen.
ì Press “ ” “ ” button to set weekday.
ì Press “Confirm” button to save the setting; press “Cancel”
   button to cancel the setting.
ì   Press “System Setting” button again until “ ” displays on
    the screen.
ì   Press “ ” button to set hour, press “ ” button to set minute.
ì   Press “Confirm” button to save the setting; press “Cancel”
    button to cancel the setting.


 2. Selecting a system

ì   Press “System Setting” button until the signal “        ” displays on the screen.
ì   Press “ ” “ ” button to select a system.
ì   Press “Confirm” button to confirm the setting.
ì   Press “Cancel” button to cancel the setting.


 3. Temperature difference circulation function
    The solar control program works on the principle of temperature difference circulation. Solar
    pump P1 is triggered, as soon as the preset temperature difference between collector and
    storage is reached. If there is more than one storage or one collector array, system will compare
    the temperature difference between collectors and storage automatically.

ì   Press “System Setting” button, until “    ” displays on the screen.
ì   Press “ ” “ ” button to adjust storage temperature. Default value: 60℃, setting range: 45~75℃.
ì   Press “Confirm” button to save the setting. Press “Cancel” button to cancel this function.
ì   At the same time the menu shows “10℃”, the default value of switch-on temperature difference.
ì   Press “ ” “ ” button to adjust it. Setting range: 5~20℃.
ì   Press “Confirm” button to save the setting. Press “Cancel”
    button to cancel this function.
ì   Then the menu shows “5℃”, the default value of switch-off
                                                     10
Work station series for solar water heating control system
     temperature difference.
ì    Press “ ” “ ” button to adjust it, adjustable range: 2~12℃.
ì    Press “Confirm” button to confirm the setting. Press “Cancel”
     button to cancel the function.

      Note: Between 60~70℃ scale can form more easily; we usually set the storage temperature at
      60℃.


 4. Time-controlled auxiliary heating
    Solar thermal system can be combined with electric boiler or gas/oil boiler. The system is supported
    with a default program which can be customized to meet your individual needs. You can create a
    timer program with up to three time periods to heat the water to a desired value. During the three
    preset time periods, auxiliary heating starts working, when the water temperature in top part of
    storage (T3) is below preset turning-on temperature, and it stops working, when T3 exceeds the
    required temperature.

        Note: Default setting: the first time period: 04:00 turning-on, 05:00 turning-off; the second time
            period: 10:00~10:00; the third time period: 17:00
            turning-on, 22:00 turning-off.

ì    Press “System Setting” button until the signal “             ”
     appears.
ì    Press “ ” “ ” button to set the start time of the first time
     period. Press “ ” to adjust hours, press “ ” button to adjust
     minutes.
ì    Press “Confirm” button to save the settings, press “Cancel” button to cancel the settings.
ì    Immediately after setting the first time period, the display enters into the operating menu of next time
     period.
ì    Perform like above steps, the other two time periods can be set.

        Note: If you want to shut off one of the three time periods, you can set a same value for both
        start time and ending time, e.g., you can set both the start and ending time of second time period
        at 10:00 am.


5. Time-controlled circulation function
     This function needs an extra circulation pump (P2). You can set up a timer program with up to three
     time periods. This pump can be triggered at times when hot water will be needed.

        Note: Within the preset three time periods, pump P2 always stops for 15 minutes after operating
        for 3 minutes.
        Note: Default setting: the first time period: 06:00 turning-on, 08:00 turning-off; the second time
        period: 10:00~10:00; the third time period: 19:00 turning-on, 21:00 turning-off. Three time
periods should be set within one day (24 hours).

ì    Press “System Setting”, until “         ” displays on the

                                                     11
Work station series for solar water heating control system
    screen.
ì   Press “ ” “ ” button to adjust the start time and end time of first time period. Press “ ” button to
    adjust hours, press “ ” button to adjust minutes.
ì   Press “Confirm” button to confirm the setting, press “Cancel” button to cancel this setting.
ì   Immediately after setting the first time period, the display enters into the operating menu of next time
    period.
ì   Perform like above steps, the other two time periods can be set.

       Note: If you want to shut off one of the three time periods, you can set a same value for both
       start time and ending time, e.g., you can set both the start and ending time of second time period
       at 10:00 am.


6. Temperature-controlled circulation function
    Solar system provides temperature-controlled hot water circulation function. This function needs an
    extra hot water circulation pump (P2) and a sensor (T4). When the temperature of T4 falls below the
    preset temperature value, the circulation pump (P2) starts operating, until the temperature exceeds
    the preset temperature.

ì   Press “Choose Function”, until “        ” displays on the

    screen.
ì   Press “ ” “ ” button to adjust the temperature value,
    default value: 40℃, setting range: 20~50℃. Press “ ”
    button to adjust hours, press “ ” button to adjust minutes.
ì   Press “Confirm” button to confirm the setting, press
    “Cancel” button to cancel this setting.

     Note: In order to avoid measuring error, the position of sensor T4 should be minimum 1.5m far
     from the storage.


7. Switching on/off auxiliary heating manually
    If you want to use warm water immediately, but the water
    temperature doesn’t reach the desired value, you can switch
    on/off the auxiliary heating manually.

ì   Press “confirm” button, until “     ” displays on the screen
    to switch on auxiliary heating manually.
ì   Press “Cancel” button to switch off auxiliary heating
    manually.


8. Forbid/Permit using auxiliary heating

ì   Press “Choose Function” button, until “     ” displays on the
    screen.
ì   Press “Confirm” button to save the setting and forbid
    auxiliary heating.

                                                    12
Work station series for solar water heating control system

ì    Press “Choose Function” button until “ ” displays on the screen.
ì    Press “Cancel” button to cancel the setting and permit auxiliary heating.

        Note: When forbid auxiliary heating, customer can’t switch on/off auxiliary heating manually and
        time-controlled auxiliary heating function is also automatically deactivated.


9. Frost protection
    In winter, when the temperature of collector drops below the preprogrammed starting temperature of
    frost protection (default value 5℃), solar pump P1 starts working. When collector temperature
    exceeds the switch-off temperature of frost protection, pump P1 stops working and the system exits
    frost protection.

ì    Press “Choose Function”, until “    ” displays on the screen.
ì    Press “ ” “ ” button to adjust the temperature of frost
     protection. Setting range: 3℃–10℃.
ì    Press “Confirm” button to confirm the setting, press “Cancel”
     button to deactivate this function.


10. Storage overheating protection
    To avoid overheating of water storage, system is supported with an overheating protection function.
    When the temperature of storage (T3) is higher than the maximum temperature, even the condition of
    temperature difference circulation is reached, solar pump is still forbidden to operate.

ì    Press “Choose Function” button, until          displays on the
     screen.
ì    Press “ ” “ ” button to adjust the maximum storage
     temperature. Default value: 80℃, setting range: 60–90℃.
ì    Press “Confirm” button to confirm the setting, press “Cancel”
     button to quit the function.


11. High temperature protection of solar system
    When collector temperature reaches 115℃, and meanwhile the storage doesn’t reach the max.
    temperature, the high temperature protection function of solar
    system will be activated.

ì    Press “Choose Function”, until        displays on the screen.
ì    Press “ ” “ ” button to adjust the maximum collector
     temperature. Default value: 115℃, setting range: 100–130℃.
ì    Press “Confirm” button to confirm the setting, press “Cancel”
     button to quit this function.


12. Recooling the system by through by –pass
    This function can realize recooling the solar system through an extra installed radiator (by-pass).



                                                    13
Work station series for solar water heating control system
Attention: The by-pass is controlled by corresponding electromagnetic 3-way valve R2, but the
operation menu shows R1, it’s an error indication!

ì    Press “Choose Function”, until “       ”displays on the
     screen.
ì    Press “ ” “ ” button to adjust the switch-on
     temperature (T1). Default value: 80℃, setting range:
     60~90℃.
ì    Press “Confirm” button to confirm the setting, press
     “Cancel” button to quit this function.


13. Extended temperature-difference circulation function
    The Following described function can extend a simple “1 collector array-1 storage” solar system with
    an additional temperature difference circulation.

        Note: Only if the input T0, T5 and output R2 are not occupied, this function can be activated.



ì    Press “Choose Function”, until “      ” displays on the screen.
ì    Press “Confirm” button to activate this function. Press “Cancel”
     button to quit this function.




14. Holiday function
    If you intend to be absent for an extended period (holiday), or hot water is not required for an
    extended period, you can activate the holiday function. This function is activated nightly(22:00-06:
    00)to re-cool the storage and to prevent high thermal loads of the solar system due to completely
    heated storage.

ì    Press “Choose Function”, until “     ” displays on the screen, it
     indicates that the function is active.
ì    Press “Confirm” button to confirm this setting. Press “Cancel”
     button to deactivate this function.

        Note: When using holiday function, system will lock
        auxiliary heating automatically.


15. Anti-bacteria protection
    To safeguard the water hygiene, solar system will monitor the storage temperature. If the
    temperature never reaches 70℃ in every 7 days, auxiliary heating will be activated automatically and
    heats the storage temperate to 70℃.


16. Collector emergency cut-off
    When the temperature of collector reaches or exceeds 120℃, in order to prevent evaporation of heat
                                                     14
Work station series for solar water heating control system
     medium liquid and protect other components of solar system, solar circulation pump will be stopped
     compulsively, until the temperature of collector gets lower.


17. Memory function
     In case of power failure, solar control system is able to remain the preset parameters unchanged.


18. Reset Function
     If necessary, all the settings (except time setting) can be reset
     to the factory settings.

ì     Press “Choose Function” button, until “      ” displays on the
      screen.
ì     Press “Confirm” button, all of parameters will be reset to
      factory settings.


19. Manual operations
     Customers can monitor the flow rate anytime by viewing the
     signal “      ” on main operating menu. And when there are
     no other operations and it returns to main menu, they can also
     activate some functions by pressing different buttons directly.

ì     Press “Confirm” button to switch on/off solar collector pump
      (P1) manually.
ì     Press “Cancel” button to switch on/off solar hot water circulation pump (P2) manually.
ì     Press “ ” “ ” button repeatedly to check the temperature values in different part of solar system.




Ⅴ Fault messages
         Danger: Never try to repair the solar pumping station yourself! Consult a specialist in case of an
         error.

   The following table explains the error messages and corresponding handling indication. Most of the
   problems can be found in the list below.
No.         Familiar problem                  Possible reason                    Solution
       Pump works but no flow rate        There is probably too much air       Replenish heat medium liquid
 1
       displays.                          in the pipeline.                     and exhaust the air.
                                                                               When storage temperature
                                          Storage reaches max. temp.
       System has temp. difference                                             drops, pump starts working.
 2
       but pump doesn’t work.             Solar collector reaches its max. When collector temperature
                                          temp..                           drops, pump starts working.
                                          There is probable broken circuit
       Pump doesn’t work, and the                                           Check the sensor wiring and
 3                                        or short circuit with temperature
       signal “   ” blinks.                                                 replace sensors if necessary.
                                          sensors.


                                                      15
Work station series for solar water heating control system

                                            Auxiliary heating is forbidden.               Activate it manually.
 4     Auxiliary heating doesn’t work.      Temperature sensor has broken Check sensor connection and
                                            circuit or short circuit.     make the wiring again.
       Auxiliary heating still operates
 5                                          Anti-bacteria function starts up.             It’s normal.
       at 23:00.
                                            There is air leakage in solar                 Check the pipeline           and
 6     System pressure drops.
                                            system.                                       exhaust the air.

       Pump works but system                Frost function is activated.
 7                                                                                        No error.
       doesn’t have temp. difference,       Holiday function is activated.


     The solar work station SP118 shows error messages in the main operating menu if there is a problem
     with temperature sensor.
  Error
                         meaning                         Possible cause                          Error rectification
 message
                There is broken circuit Sensor wiring interrupted, not                    Check resistance value,
    <FF℃>
                with sensor connections. connected or short circuit.                      replace sensor if necessary.
                There is a short circuit       Sensor wiring interrupted, not             Check resistance value,
    <FE℃>
                with sensor connections.       connected or short circuit.                replace sensor if necessary.

      Note: A potentially defective sensor can be checked using an ohmmeter. To do this, the sensor
      must be disconnected. Its resistance value can be compared with the figures below, small
      deviation is acceptable.
PT1000 resistance value
℃        0      10       20     30        40        50             60      70      80       90        100    110    120
         1000   1039     1077   1116      1155      1194           1232    1270    1309     1347      1385   1422   1460

NTC 10K B=3950 resistance value
℃       0        10       20         30        40        50         60      70      80        90       100   110       120
        33620    20174    12535      8037      5301      3588       2486    1759    1270      933      697   529       407




                                                              16
Work station series for solar water heating control system


Part 2: Installation instruction
ⅠGeneral information
 1. Safety
 Before installing the device, please read this manual carefully. Please note that the installation
 must be executed according to relevant technical rules. The installation must be adapted to the
 conditions provided by the customer. Damages by improper using or incorrect modification of
 installation and construction are on costumer site.

     Attention: This manual is for trained personals only!


     Note: As faults can never be excluded, we don’t offer a guarantee for the completeness of the
     drawings and texts of this manual, they only represent some examples.

 2. Input and output signals




      1      T3 connector                 7    P0 pump or R1 electromagnetic 3-way valve
      2      T2 connector                 8    Power cord and auxiliary heating connection
      3      T0 connector                 9    R2 electromagnetic 3-way valve
      4      Power switch                10    T5 connector
      5      T1 connector                11    T4 connector
      6      P2 pump


3. System demonstration




                                               17
Work station series for solar water heating control system

ⅡMounting
1. Open the package carton and take out the solar control system carefully.
  Determine the mounting position of the solar control system, considering the mounting place for
   expansion vessel. See picture 1.




                                            Picture 1
2. Drill the holes for dowels, put the dowels into the holes, fixed the solar control system on the
  wall using fastening screws. The solar control system must be vertically installed. See picture 2.




                                                 Picture 2

 3. Use two wrenches to connect the pipes. See picture 3.




                                                 Picture 3

  4. Install an auto air vent next to the interface of solar collector. See picture 4.



                                                    18
Work station series for solar water heating control system




 5. Determine the mounting place for the expansion vessel. Connect the expansion vessel. See
 picture5.




                                              Picture 5

6. Install a 3-way ball valve above the work station, it can be used for filling heat medium (fill
  valve); install a 3-way ball valve below the work station for draining (drain valve). See picture 6.
  There is already a non-return valve installed inside the work station between fill and drain
  valve.




                                              Picture 6

7. Filling the system
   ◆ Connect a separate pump to the filling valve with pressure hose.
   ◆ Open the filling and draining valve, fill the system with the separate pump. Heat medium liquid
                                                 19
Work station series for solar water heating control system
     (usually use water-glycol mixture as heat medium, 50% glycol and 50% water) will be pumped
     into the system until it is filled up.
   ◆ Close the drain valve and continue to fill the system with medium liquid until the system pressure
     is not lower than 2 bar (the system pressure can be read from the manometer).
   ◆ Close the filling connector and switch off the pump.


Ⅲ Electrical wiring
 1. Insert the temperature sensors into storage and solar collector. Connect these sensors to the work
    station correspondingly. See picture 7.




                                                 Picture 7

 2. Connect auxiliary heating wire if available. Cable (coffee) for the “L”, cable (blue) for “N” line, cable
     (yellow-green) for the ground wire.




 3. To connect external circulation pumps or any electromagnetic valves, firstly loose the aviation
    socket and dismount it as indicated below. Connect the wire to aviation socket, number 1
    connects “N” wire, number 2 connects ground wire, number 3 connects “L” wire. Reassemble the
    aviation socket and connect it to the solar control system.




 4. Tighten all joints and screw connections. Then plug the power supply into a socket.
                                                     20
Work station series for solar water heating control system

Ⅳ Commissioning

 1. Switch on the power of solar control system. Press “Confirm” button (in main operating menu) to
    activate the solar collector pump (P1) manually and let the system circulate for a moment. See
    picture 10.




                                              Picture 10

 2. Observe the flow rate of solar control system which displays on LCD screen. If the flow rate is
    not regular, it indicates that there must be air still in the system. Open the air vent valve several
    times to relief the air.




                                                Picture 11

 3. When the flow rate becomes regular, observe the system pressure from manometer. If the
    pressure is lower than 2 bars, refill the system with heat medium to increase the pressure.




                                                Picture 12

 4. Carry out a pressure test of all system joints again for leaks. The solar system must be vented
     several times after some operating hours. Refill the system if necessary.
 5. Refill the system if necessary.
 6. Remove the separate pump for filling after commissioning.

                                                   21
Work station series for solar water heating control system


 7. If there is auxiliary heating wire connected, press “Choose Function” button until “         ” signal
   displays on screen. It means switch on auxiliary heating manually. Then customer can use
   auxiliary heating function.


Ⅴ Replace the pump
 1. The integrated solar collector pump could be replaced if it gets broken. Disconnect the power
     supply of solar control system. Loose the screw and open the metal cover.




 2. Remove the front half of the insulation material from system




 3. Open the terminal box, and disconnect the power supply connection.




 4. Loose the screws and open the WILO pump.




                                                 22
Work station series for solar water heating control system




5. R p c teo o ewt an wWIO p mp
    el eh l n i
      a     d    h e    L u .




6 F s nteWIOp mpsrw .
 . at h
     e    L u   ce s




7 C n e th p w r u p a a a dc s tetr n l o .
 . o n c te o e s p l g i n l e h emi b x
                    y   n    o        a




8 Atc tef n h l h fa cv r
 . t h h r t a te o m o e.
    a    o    f



                                 23
Woks t n sr sfrsl w trh ai c nrl yt
                                  r t i ei o o r ae e t g o t ss m
                                    ao     e    a        n    o   e




 9 Atc teme lo e a dfs ntesrw a a .
  . t hh
     a     a c v r n a t h ce s g i
                       e          n




Ⅵ Packing list

             N.
              o      Im
                     t
                     e           S e i ai
                                  p ci t n
                                     f o
                                      c         Q at
                                                 u ni
                                                    ty
             1    Wok t i
                    r s tn
                       ao       40 30 10
                                 5 × 1 × 5 mm    1pc
             2     P w ri
                    o e le
                        n                        1pc
             3    P 1 0 s no
                   T 0 0 e sr        1m
                                      5         2p s
                                                  c
             4     N Cs n o
                    T e sr           3m         4p s
                                                  c
             5     Fx dsrw
                    ie ce                       1b g
                                                  a
             6      Ma u l
                      na                         1pc




                                24

Más contenido relacionado

La actualidad más candente

Testo 112 datasheet 2012
Testo 112 datasheet 2012Testo 112 datasheet 2012
Testo 112 datasheet 2012
Testo Limited
 
Testo 922 datasheet 2012
Testo 922 datasheet 2012Testo 922 datasheet 2012
Testo 922 datasheet 2012
Testo Limited
 
Lal burner control
Lal burner controlLal burner control
Lal burner control
Eko Kiswanto
 
Fcc 01 free-coolin-controller
Fcc 01 free-coolin-controllerFcc 01 free-coolin-controller
Fcc 01 free-coolin-controller
erdinc klima
 
Controllers manual-controller carrier-owners-manual-of-kjr-12_b-1438306116
Controllers manual-controller carrier-owners-manual-of-kjr-12_b-1438306116Controllers manual-controller carrier-owners-manual-of-kjr-12_b-1438306116
Controllers manual-controller carrier-owners-manual-of-kjr-12_b-1438306116
Albert Bylykbashi
 
Testo 845 datasheet 2012
Testo 845 datasheet 2012Testo 845 datasheet 2012
Testo 845 datasheet 2012
Testo Limited
 
Testo 512 datasheet 2012
Testo 512 datasheet 2012Testo 512 datasheet 2012
Testo 512 datasheet 2012
Testo Limited
 

La actualidad más candente (20)

Hướng dẫn sử dụng máy đo nhiệt độ Testo 610
Hướng dẫn sử dụng máy đo nhiệt độ Testo 610Hướng dẫn sử dụng máy đo nhiệt độ Testo 610
Hướng dẫn sử dụng máy đo nhiệt độ Testo 610
 
Testo 112 datasheet 2012
Testo 112 datasheet 2012Testo 112 datasheet 2012
Testo 112 datasheet 2012
 
Testo 922 datasheet 2012
Testo 922 datasheet 2012Testo 922 datasheet 2012
Testo 922 datasheet 2012
 
Hướng dẫn sử dụng máy đo đa năng Testo 550 KIT
Hướng dẫn sử dụng máy đo đa năng Testo 550 KIT Hướng dẫn sử dụng máy đo đa năng Testo 550 KIT
Hướng dẫn sử dụng máy đo đa năng Testo 550 KIT
 
TMT127-187-128-188
TMT127-187-128-188TMT127-187-128-188
TMT127-187-128-188
 
E top controls thermostat catalog
E top controls thermostat catalogE top controls thermostat catalog
E top controls thermostat catalog
 
Barrel blazer-system-manual
Barrel blazer-system-manualBarrel blazer-system-manual
Barrel blazer-system-manual
 
Eta pcba coating line introduction
Eta pcba coating line introductionEta pcba coating line introduction
Eta pcba coating line introduction
 
GR320RB
GR320RBGR320RB
GR320RB
 
Caldeira Roca R-20/20
Caldeira Roca R-20/20Caldeira Roca R-20/20
Caldeira Roca R-20/20
 
Regulators
RegulatorsRegulators
Regulators
 
Hướng dẫn sử dụng máy đo tốc độ vòng quay testo 460
Hướng dẫn sử dụng máy đo tốc độ vòng quay testo 460Hướng dẫn sử dụng máy đo tốc độ vòng quay testo 460
Hướng dẫn sử dụng máy đo tốc độ vòng quay testo 460
 
Lighting
LightingLighting
Lighting
 
Lal burner control
Lal burner controlLal burner control
Lal burner control
 
Fcc 01 free-coolin-controller
Fcc 01 free-coolin-controllerFcc 01 free-coolin-controller
Fcc 01 free-coolin-controller
 
Controllers manual-controller carrier-owners-manual-of-kjr-12_b-1438306116
Controllers manual-controller carrier-owners-manual-of-kjr-12_b-1438306116Controllers manual-controller carrier-owners-manual-of-kjr-12_b-1438306116
Controllers manual-controller carrier-owners-manual-of-kjr-12_b-1438306116
 
Eta e series reflow oven
Eta e series reflow ovenEta e series reflow oven
Eta e series reflow oven
 
Testo 845 datasheet 2012
Testo 845 datasheet 2012Testo 845 datasheet 2012
Testo 845 datasheet 2012
 
ETA IR Oven Introduction
ETA IR Oven IntroductionETA IR Oven Introduction
ETA IR Oven Introduction
 
Testo 512 datasheet 2012
Testo 512 datasheet 2012Testo 512 datasheet 2012
Testo 512 datasheet 2012
 

Destacado

Квіти біля школи
Квіти біля школиКвіти біля школи
Квіти біля школи
kalyna1996
 
Hypotheek
HypotheekHypotheek
Hypotheek
advweb4
 
Plantilla tuneos
Plantilla tuneosPlantilla tuneos
Plantilla tuneos
KALUKIS
 
Luc benoist-az-ezoterizmus
Luc benoist-az-ezoterizmusLuc benoist-az-ezoterizmus
Luc benoist-az-ezoterizmus
Timea1
 
Yonder 2016 Deck-1
Yonder 2016 Deck-1Yonder 2016 Deck-1
Yonder 2016 Deck-1
Mark Yardley
 

Destacado (20)

построение персонального имиджа
построение персонального имиджапостроение персонального имиджа
построение персонального имиджа
 
Квіти біля школи
Квіти біля школиКвіти біля школи
Квіти біля школи
 
"For the first time in Europe Digital ID providers and OpenID service for Rom...
"For the first time in Europe Digital ID providers and OpenID service for Rom..."For the first time in Europe Digital ID providers and OpenID service for Rom...
"For the first time in Europe Digital ID providers and OpenID service for Rom...
 
Informatica
InformaticaInformatica
Informatica
 
Artigos
ArtigosArtigos
Artigos
 
Hypotheek
HypotheekHypotheek
Hypotheek
 
Dao consulting capabilities
Dao consulting capabilitiesDao consulting capabilities
Dao consulting capabilities
 
Nowa Forma Swarzędz
Nowa Forma SwarzędzNowa Forma Swarzędz
Nowa Forma Swarzędz
 
Plantilla tuneos
Plantilla tuneosPlantilla tuneos
Plantilla tuneos
 
Kapsam denetim ve mali müşavirlik hizmetleri sirküler no 2012 03
Kapsam denetim ve mali müşavirlik hizmetleri sirküler no 2012 03Kapsam denetim ve mali müşavirlik hizmetleri sirküler no 2012 03
Kapsam denetim ve mali müşavirlik hizmetleri sirküler no 2012 03
 
Librepensamiento perpetuus (versión digitalizada, 2016)
Librepensamiento perpetuus (versión digitalizada, 2016)Librepensamiento perpetuus (versión digitalizada, 2016)
Librepensamiento perpetuus (versión digitalizada, 2016)
 
Luc benoist-az-ezoterizmus
Luc benoist-az-ezoterizmusLuc benoist-az-ezoterizmus
Luc benoist-az-ezoterizmus
 
презентация лшлр 2012-2
презентация лшлр 2012-2презентация лшлр 2012-2
презентация лшлр 2012-2
 
las tics educativas
las tics educativaslas tics educativas
las tics educativas
 
SIPES Houston Presentation by Charles Goodson of PetroQuest Energy
SIPES Houston Presentation by Charles Goodson of PetroQuest EnergySIPES Houston Presentation by Charles Goodson of PetroQuest Energy
SIPES Houston Presentation by Charles Goodson of PetroQuest Energy
 
MCD 2012 inschrijving open!
MCD 2012 inschrijving open!MCD 2012 inschrijving open!
MCD 2012 inschrijving open!
 
Тест на запоминание слов
Тест на запоминание словТест на запоминание слов
Тест на запоминание слов
 
Yonder 2016 Deck-1
Yonder 2016 Deck-1Yonder 2016 Deck-1
Yonder 2016 Deck-1
 
The Impact of Globalization
The Impact of GlobalizationThe Impact of Globalization
The Impact of Globalization
 
Eng report final
Eng report finalEng report final
Eng report final
 

Similar a Solar Work Station SP118

Water Temperature
Water TemperatureWater Temperature
Water Temperature
Theju Paul
 
AC-AC Voltage Controller of Power Supply for Heater on Drying System
AC-AC Voltage Controller of Power Supply for Heater on Drying SystemAC-AC Voltage Controller of Power Supply for Heater on Drying System
AC-AC Voltage Controller of Power Supply for Heater on Drying System
TELKOMNIKA JOURNAL
 

Similar a Solar Work Station SP118 (20)

Sr868c6 manual+ultisolar-new-energy-co-ltd-solar-water-heaters-controllers-wo...
Sr868c6 manual+ultisolar-new-energy-co-ltd-solar-water-heaters-controllers-wo...Sr868c6 manual+ultisolar-new-energy-co-ltd-solar-water-heaters-controllers-wo...
Sr868c6 manual+ultisolar-new-energy-co-ltd-solar-water-heaters-controllers-wo...
 
Inkbird ITC-308
Inkbird ITC-308Inkbird ITC-308
Inkbird ITC-308
 
Inkbird itc 308
Inkbird itc 308Inkbird itc 308
Inkbird itc 308
 
Anole Hot Runner Controller
Anole Hot Runner ControllerAnole Hot Runner Controller
Anole Hot Runner Controller
 
Ultisolar New Energy Solar Water Heater Controllers Catalogue
Ultisolar New Energy Solar Water Heater Controllers CatalogueUltisolar New Energy Solar Water Heater Controllers Catalogue
Ultisolar New Energy Solar Water Heater Controllers Catalogue
 
Water Temperature
Water TemperatureWater Temperature
Water Temperature
 
Solar Work Station SP328
Solar Work Station SP328Solar Work Station SP328
Solar Work Station SP328
 
High performance temperature controller for Infant Incubator
High performance temperature controller for Infant IncubatorHigh performance temperature controller for Infant Incubator
High performance temperature controller for Infant Incubator
 
Dom icondens he-26c-manual
Dom icondens he-26c-manualDom icondens he-26c-manual
Dom icondens he-26c-manual
 
Manual of Thermostat Fan Coil 4Pipes MH8 series - MCO HOME
Manual of Thermostat Fan Coil 4Pipes MH8 series - MCO HOME Manual of Thermostat Fan Coil 4Pipes MH8 series - MCO HOME
Manual of Thermostat Fan Coil 4Pipes MH8 series - MCO HOME
 
HEL-ZW-THERM-FL2 Manual
HEL-ZW-THERM-FL2 ManualHEL-ZW-THERM-FL2 Manual
HEL-ZW-THERM-FL2 Manual
 
Temperature sensor smt172
Temperature sensor   smt172Temperature sensor   smt172
Temperature sensor smt172
 
NTPC Major Training Report
NTPC Major Training ReportNTPC Major Training Report
NTPC Major Training Report
 
AC-AC Voltage Controller of Power Supply for Heater on Drying System
AC-AC Voltage Controller of Power Supply for Heater on Drying SystemAC-AC Voltage Controller of Power Supply for Heater on Drying System
AC-AC Voltage Controller of Power Supply for Heater on Drying System
 
B737NG Anti ice and rain
B737NG Anti ice and rainB737NG Anti ice and rain
B737NG Anti ice and rain
 
Dual temperature water chillers cwfl 500 for 500 w fiber laser-cwfl-500
Dual temperature water chillers cwfl 500 for 500 w fiber laser-cwfl-500Dual temperature water chillers cwfl 500 for 500 w fiber laser-cwfl-500
Dual temperature water chillers cwfl 500 for 500 w fiber laser-cwfl-500
 
Control system-lab
Control system-labControl system-lab
Control system-lab
 
Mh8 fc um
Mh8 fc umMh8 fc um
Mh8 fc um
 
Z-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdf
Z-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdfZ-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdf
Z-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdf
 
Laser cooling systems cwfl 1000 with dual digital temperature controller cwfl...
Laser cooling systems cwfl 1000 with dual digital temperature controller cwfl...Laser cooling systems cwfl 1000 with dual digital temperature controller cwfl...
Laser cooling systems cwfl 1000 with dual digital temperature controller cwfl...
 

Último

FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
dollysharma2066
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
amitlee9823
 
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Sheetaleventcompany
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usage
Matteo Carbone
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
Renandantas16
 
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
lizamodels9
 

Último (20)

BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRLBAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
 
Uneak White's Personal Brand Exploration Presentation
Uneak White's Personal Brand Exploration PresentationUneak White's Personal Brand Exploration Presentation
Uneak White's Personal Brand Exploration Presentation
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMAN
 
RSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors DataRSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors Data
 
Business Model Canvas (BMC)- A new venture concept
Business Model Canvas (BMC)-  A new venture conceptBusiness Model Canvas (BMC)-  A new venture concept
Business Model Canvas (BMC)- A new venture concept
 
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptxB.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
 
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
 
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
 
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usage
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
 
Falcon Invoice Discounting platform in india
Falcon Invoice Discounting platform in indiaFalcon Invoice Discounting platform in india
Falcon Invoice Discounting platform in india
 
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service AvailableCall Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptx
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
 
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 May
 

Solar Work Station SP118

  • 1.
  • 2. CONTENT Part 1: Operation instruction Ⅰ General information .……………………………………… 1 Ⅱ Product description ..……………………………………… 2 Ⅲ System description…………………………………………5 Ⅳ Function description………………………………………10 Ⅴ Fault message …………………………………………… 15 Part 2: Installation instruction Ⅰ General information ………………………………………17 Ⅱ Mounting……………………………………………………18 Ⅲ Electrical wiring……………………………………………20 Ⅳ Commissioning.……………………………………………21 Ⅴ Replacing pump……………………………………………22 Ⅵ Packing list…………………………………………………24
  • 3. Work station series for solar water heating control system Part 1: Operation instruction Ⅰ. General information 1. About this manual This manual describes the installation, function and operation of an integrated solar work station, which is suitable for split pressurized solar heating system. Before installing and operating the device, please read the following information carefully. 2. Safety regulations ♦ Installation, commissioning and maintenance of the device may only be performed by professional personal. ♦ All operations that require opening the device are only to be conducted cleared from the power supply. All safety regulations for working on the power supply are valid. ♦ The device must not be installed in rooms where easily inflammable material (e.g. gas or oil) mixtures are present or may occur. ♦ Before connecting the work station, make sure that the energy supply matches the specifications of the device. Protect the solar station against overloading and short-circuiting. ♦ All devices connected to the work station must conform to the technical specifications of the device. ♦ As soon as it becomes evident that safe operation is no longer possible, please immediately take the device out of operation. ♦ Without lightning rod, please don’t use this device during a thunderstorm. 3. Liability waiver ♦ Improper installation or operation can cause damages to material and persons. The manufacturer cannot monitor the compliance with these instructions or the circumstances and methods used for installation, operation, utilization and maintenance of this device. Damage by mishandling or improper installation on costumer site is immediately leading to warranty exclusion. ♦ As faults can never be excluded, we don’t offer a guarantee for the completeness of the drawings and texts of this manual, they only represent some examples. They can only be used on own risk. No liability is assumed for incorrect, incomplete or false information and the resulting damages. ♦ The manufacturer preserves the right to put changes to product, technical date or installation and operation instructions without prior notice. 4. Symbols used Danger: Failure to observe these instructions can lead to injury of persons or safety risks. Attention: Failure to observe these instructions can result in damage to the product or environment. Note: Useful information and instructions. ì Operation steps: Indication of operation steps. 1
  • 4. Work station series for solar water heating control system Ⅱ. Product information 1. Components No Components Function description 1 Operating screen (LCD) Display operating menu. Display system pressure (Max. 10 bar, normal working 2 Manometer pressure is approx. 2 bar) 3 Pump speed regulation Three speed levels available, offers different flow rate. 4 Circulation pump WILO Star RS 15/6 (110V or 220V) 5 Input and Output signals Temperature sensors, power cord and other outputs. 6 Security valve Protect the system against over-pressure. Expansion vessel Connect expansion vessel. Expansion vessel balances 7 connector the system pressure. Copper material, left side. Max. working temperature 150 8 Return flow ℃, screw thread 1/2’ (DN15) as standard 9 Mounting point For fixing the solar pump station 2. Technical data Dimension 450×310×150mm Input voltage 200V~240V AC or 100V~120V AC Power ≤3W Accuracy of temperature measuring ±1℃ Range of temperature measuring PT1000 : 0~199℃ NTC10K: 0~99℃ 2 x PT1000 sensor temperature probe ≤500℃, silicon cable ≤280℃; Input signals 4 x NTC10K sensor temperature probe≤135℃, PVC cable ≤105℃ 1 x Auxiliary heating output (Max. load current: 15A) Output signals 4 x Relay output (Max. load current: 3A) System design pressure 10 bar 2
  • 5. Work station series for solar water heating control system Safety valve response pressure 6 bar WILO pump SR15/6 Ambient temperature -10~50℃ Water protection grade IP40 3. Display signals Weekday: 7days of week can be set (e.g. Week 1 means “Monday”). Time: Setting hours and minutes. Time-controlled auxiliary heating: Setting three heating time periods. Time-controlled hot water circulation: Setting three time periods. Storage temperature: As turning-on/off temperature value for auxiliary heating. Solar system indication. 8 systems are available. Frost protection. Temperature-controlled circulation function Overheating protection for storage. High temperature protection for solar collector. Holiday function. Switch on/off auxiliary heating manually. Forbid/permit using auxiliary heating. Reset. Extended temperature-difference circulation function Recooling the system through by-pass Temperature display. Flow rate display. 3
  • 6. Work station series for solar water heating control system Ⅲ System description (8 systems available) Danger: If there is only one temperature sensor in water storage (usually in bottom part T2), it is possible, and that the auxiliary heating function will not be activated or deactivated at a right time, because the water temperature in top part of the storage (T3) cannot be measured. In this case, if you still want to use auxiliary heating function, control program will automaticall y take the signal from bottom temperature sensor (T2) instead of T3. However, water in top part of tank might often be overheated. It may cause damages to material and persons. So it is highly recommended not to use auxiliary heating in such a case. Note: To lock this function, please press “Choose Function” button until the signal” ” appears on the screen (see details in 3.8 Forbid/Permit auxiliary heating). 1. System 1: 1 collector array – 1 storage – 1 pump Description: The solar collector pump (P1) is activated as soon as the temperature difference between the collector array (T1) and the storage (T2) is reached. When the temperature difference between T1 and T2 drops below the switch-off temperature difference, or the storage (T3) reaches its maximum storage temperature, the solar pump (P1) will be switched off. T3 is used to measure the temperature of the top part of storage. If the turning-on condition for auxiliary heating is filled, the auxiliary heating will be activated T1: Temperature sensor for collector 1 T2: Temperature sensor in the bottom part of storage 1 T3: Temperature sensor in the top part of storage 1 T4: Temperature sensor for hot water pipe P1: Solar collector pump P2: Solar circulation pump Note: 1. T3, T4, P2 are suitable for system 1-8. 2. T3 is alternative, when no sensor (T3) is installed in the top part of tank, control system will use the signal of sensor T2 automatically to control the auxiliary heating. 4
  • 7. Work station series for solar water heating control system 2. System 2: 1 collector array – 2 storage – 2 pumps Description: When switch–on temperature difference between collector array (T1) and one of the storage (T2 or T5) is reached, the solar circuit pump (P1) or (P0) will switched on. According to the priority switching, tw o storages (T2, T5) will be loaded one by one. Until either of switch-off temperature difference between collector array (T1) and storage (T2, T5) is reached, or the maximum storage temperature is reached, pump stops working. T1: Temperature sensor for collector 1 T2: Temperature sensor in the bottom part of storage 1 T3: Temperature sensor in the top part of storage 1 T4: Temperature sensor for hot water pipe T5: Temperature sensor in storage 2 P0: Solar collector pump P1: Solar collector pump Note: The default priority storage is storage1. 3. System 3: 1 collector array – 2 storages– 1 pump – 1 valve Description: When switch–on temperature difference between collector array (T1) and one of the storage (T2 or T5) is reached, then the solar pump (P1) is switched on and valve (R1) is set to the correct position depending on the storage to be loaded. According to the priority switching, both storages (T2, T5) will be loaded one by one, until the relevant switch-off temperature difference between the collector array (T1) and storage are reached. (T2, T5) is reached or the maximum storage temperature of T2 or T5 is reached, pump and valve stop working. 5
  • 8. Work station series for solar water heating control system T1: Temperature sensor for collector 1 T2: Temperature sensor in the bottom part of storage 1 T5: Temperature sensor in the bottom part of storage 2 P1: Solar collector pump R1: Electromagnetic 3-way valve Note: 1. When there is no power in the system, the electromagnetic valve (R1) must be set to storage (T2). 2. The default priority storage is storage 1. 4. System 4: 2 collector arrays – 1 storage tank – 2 pumps Description: When switch–on temperature difference between storage (T2) and collector array (T1, T0) is reached, then solar pump (P1) for collector array 1 (T1) or solar circuit pump (P0) for collector array 2 (T0) is switched on, depending on where the temperature difference occurs firstly. If the switch-on temperature difference is reached for both collector arrays (T1, T0), then both pumps (P1, P0) are switched on. The pumps switch-off independentl y for each other. When either of relevant switch-off temperature difference between one or both collector arrays (T1, T0) and the storage (T2) falls below the threshold or the maximum storage temperature is reached, then the corresponding circuit pump is switched off. T0: Temperature sensor for collector 2 T1: Temperature sensor for collector 1 T2: Temperature sensor in the bottom part of storage1 P0: Solar collector pump P1: Solar collector pump 5. System 5: 2 collector arrays – 1 storage – 1 pump – 1 valve Description: 6
  • 9. Work station series for solar water heating control system The solar pump (P1) is switched on as soon as the switch–on temperature difference between one of the two collector arrays (T1, T0) and storage 1 (T2) is reached, the valve R1 is always set so that flow occurs through the warmer of the two collector arrays (T1, T2). The pump P1 switch-off as soon as the switch-off temperature difference between two collector arrays (T1, T0) and storage (T2) is reached or the maximum storage temperature is reached. T0: Temperature sensor for collector 2 T1: Temperature sensor for collector 1 T2: Temperature sensor in the bottom part of storage 1 P1: Solar collector pump R1: Electromagnetic 3-way valve Note: When there is no power in the system, the electromagnetic valve (R1) must be set to collector array 1. 6. System 6: 2 collector arrays – 2 storages – 1 pump – 2 valves Description: When switch-on temperature difference between two storage (T2, T5) and collector array 1 (T1) or collector array 2 (T0) is reached, then the solar circuit pump (P1) is switched on, electromagnetic valve (R2) switches the relevant storage into the solar circuit, and electromagnetic valve (R1) switches the affected collector array (T1 or T2) into the solar circuit. Pump (P1) stops working when the switch-off temperature difference between either or both collector arrays and its corresponding storage 1 (T2) and storage 2 (T5) falls below the threshold or the maximum storage temperature (T2 or T5) is reached. T0: Temperature sensor for collector 2 T1: Temperature sensor for collector 1 T2: Temperature sensor in the bottom part of storage 1 T5: Temperature sensor in the bottom part of storage 2 P1: Solar collector pump 1 R1: Electromagnetic 3-way valve R2: Electromagnetic 3-way valve Note: 1. When there is no power in the system, the electromagnetic valve (R2) must be set to storage 1 (T2), the electromagnetic valve (R1) must be set to collector array 1(T1). 2. Default priority tank is storage 1. 7
  • 10. Work station series for solar water heating control system 7. System 7: 2 collector arrays – 2 storages – 2 pumps – 1 valve Description: When switch-on temperature difference between one of the two storages (T2, T5) and collector array 1 (T1) or collector array 2 (T0) is exceeded, then the switching valve R2 switched the corresponding collector array (T1 or T0) into the solar circuit. Depending on which storage has reached the switch-on temperature, solar pump (P1) for storage 1 (T2) or solar pump (P0) for storage 2 (T5) is switched on. The switching valve R2 is always set so that flow occurs through the warmer of the two collector arrays. Both storages (T2, T5) will be loaded one by one, according to the priority switching, until either the relevant switch-off temperature difference falls below the threshold, or the maximum storage temperature (T2 or T5) is reached. T0: Temperature sensor for collector 2 T1: Temperature sensor for collector 1 T2: Temperature sensor in the bottom part of storage 1 T5: Temperature sensor in the bottom part of storage 2 P0: Solar collector pump P1: Solar collector pump R2: Electromagnetic 3-way valve Note: 1. When there is no power in the system, the electromagnetic valve (R2) must be set to collector array 1(T1). 2. Default priority storage is storage 1. 8. System 8: 2 collector arrays – 2 storages – 2 pumps – 1 valve Description: When switch-on temperature difference between one of the two storage (T2, T5) and collector array1 (T1) and collector array2 (T0) is reached, then the switching valve (R2) 8
  • 11. Work station series for solar water heating control system switches relevant storage (T2, or T5) to the solar circuit. Then either solar circuit pump P1 for collector array 1 (T1) or solar circuit pump P0 for collector array 2 (T0) is switch-on, Depending on where the temperature difference occurs. If the switch-on temperature difference is reached between collector arrays (T1, T0), then both pumps (P1, P0) are switch-on. Pump (P1, P0) switch-off independently of each other, when both of relevant switch-off temperature difference between collector arrays (T1, T0) and relevant storage (T2 or T5) falls below the threshold, or the maximum storage temperature is reached. T0: Temperature sensor for collector 2 T1: Temperature sensor for collector 1 T2: Temperature sensor in the bottom part of storage 1 T5: Temperature sensor in the bottom part of storage 2 P0: Solar collector pimp 2 P1: Solar collector pump 1 R2: Electromagnetic 3-way valve Note: 1. When no power is in the system, the electromagnetic valve (R2) must be set to storage 1 (T1). 2. Default priority storage is storage 1. 9
  • 12. Work station series for solar water heating control system Ⅳ Functions and operation Danger: Before connecting the power supply, make sure that the storage, solar collector, solar work station and all temperature sensors are good connected! Note: For safety, auxiliary heating is locked at delivery state. The single “ ” displays on the screen. If you want to use this function, please see operation: 3.6 Forbid/Permit using auxiliary heating. 1. Setting week and time After power supply is switched on, please firstly set the time of the system. ì Press “System Setting” button until the signal “Week ” displays on the screen. ì Press “ ” “ ” button to set weekday. ì Press “Confirm” button to save the setting; press “Cancel” button to cancel the setting. ì Press “System Setting” button again until “ ” displays on the screen. ì Press “ ” button to set hour, press “ ” button to set minute. ì Press “Confirm” button to save the setting; press “Cancel” button to cancel the setting. 2. Selecting a system ì Press “System Setting” button until the signal “ ” displays on the screen. ì Press “ ” “ ” button to select a system. ì Press “Confirm” button to confirm the setting. ì Press “Cancel” button to cancel the setting. 3. Temperature difference circulation function The solar control program works on the principle of temperature difference circulation. Solar pump P1 is triggered, as soon as the preset temperature difference between collector and storage is reached. If there is more than one storage or one collector array, system will compare the temperature difference between collectors and storage automatically. ì Press “System Setting” button, until “ ” displays on the screen. ì Press “ ” “ ” button to adjust storage temperature. Default value: 60℃, setting range: 45~75℃. ì Press “Confirm” button to save the setting. Press “Cancel” button to cancel this function. ì At the same time the menu shows “10℃”, the default value of switch-on temperature difference. ì Press “ ” “ ” button to adjust it. Setting range: 5~20℃. ì Press “Confirm” button to save the setting. Press “Cancel” button to cancel this function. ì Then the menu shows “5℃”, the default value of switch-off 10
  • 13. Work station series for solar water heating control system temperature difference. ì Press “ ” “ ” button to adjust it, adjustable range: 2~12℃. ì Press “Confirm” button to confirm the setting. Press “Cancel” button to cancel the function. Note: Between 60~70℃ scale can form more easily; we usually set the storage temperature at 60℃. 4. Time-controlled auxiliary heating Solar thermal system can be combined with electric boiler or gas/oil boiler. The system is supported with a default program which can be customized to meet your individual needs. You can create a timer program with up to three time periods to heat the water to a desired value. During the three preset time periods, auxiliary heating starts working, when the water temperature in top part of storage (T3) is below preset turning-on temperature, and it stops working, when T3 exceeds the required temperature. Note: Default setting: the first time period: 04:00 turning-on, 05:00 turning-off; the second time period: 10:00~10:00; the third time period: 17:00 turning-on, 22:00 turning-off. ì Press “System Setting” button until the signal “ ” appears. ì Press “ ” “ ” button to set the start time of the first time period. Press “ ” to adjust hours, press “ ” button to adjust minutes. ì Press “Confirm” button to save the settings, press “Cancel” button to cancel the settings. ì Immediately after setting the first time period, the display enters into the operating menu of next time period. ì Perform like above steps, the other two time periods can be set. Note: If you want to shut off one of the three time periods, you can set a same value for both start time and ending time, e.g., you can set both the start and ending time of second time period at 10:00 am. 5. Time-controlled circulation function This function needs an extra circulation pump (P2). You can set up a timer program with up to three time periods. This pump can be triggered at times when hot water will be needed. Note: Within the preset three time periods, pump P2 always stops for 15 minutes after operating for 3 minutes. Note: Default setting: the first time period: 06:00 turning-on, 08:00 turning-off; the second time period: 10:00~10:00; the third time period: 19:00 turning-on, 21:00 turning-off. Three time periods should be set within one day (24 hours). ì Press “System Setting”, until “ ” displays on the 11
  • 14. Work station series for solar water heating control system screen. ì Press “ ” “ ” button to adjust the start time and end time of first time period. Press “ ” button to adjust hours, press “ ” button to adjust minutes. ì Press “Confirm” button to confirm the setting, press “Cancel” button to cancel this setting. ì Immediately after setting the first time period, the display enters into the operating menu of next time period. ì Perform like above steps, the other two time periods can be set. Note: If you want to shut off one of the three time periods, you can set a same value for both start time and ending time, e.g., you can set both the start and ending time of second time period at 10:00 am. 6. Temperature-controlled circulation function Solar system provides temperature-controlled hot water circulation function. This function needs an extra hot water circulation pump (P2) and a sensor (T4). When the temperature of T4 falls below the preset temperature value, the circulation pump (P2) starts operating, until the temperature exceeds the preset temperature. ì Press “Choose Function”, until “ ” displays on the screen. ì Press “ ” “ ” button to adjust the temperature value, default value: 40℃, setting range: 20~50℃. Press “ ” button to adjust hours, press “ ” button to adjust minutes. ì Press “Confirm” button to confirm the setting, press “Cancel” button to cancel this setting. Note: In order to avoid measuring error, the position of sensor T4 should be minimum 1.5m far from the storage. 7. Switching on/off auxiliary heating manually If you want to use warm water immediately, but the water temperature doesn’t reach the desired value, you can switch on/off the auxiliary heating manually. ì Press “confirm” button, until “ ” displays on the screen to switch on auxiliary heating manually. ì Press “Cancel” button to switch off auxiliary heating manually. 8. Forbid/Permit using auxiliary heating ì Press “Choose Function” button, until “ ” displays on the screen. ì Press “Confirm” button to save the setting and forbid auxiliary heating. 12
  • 15. Work station series for solar water heating control system ì Press “Choose Function” button until “ ” displays on the screen. ì Press “Cancel” button to cancel the setting and permit auxiliary heating. Note: When forbid auxiliary heating, customer can’t switch on/off auxiliary heating manually and time-controlled auxiliary heating function is also automatically deactivated. 9. Frost protection In winter, when the temperature of collector drops below the preprogrammed starting temperature of frost protection (default value 5℃), solar pump P1 starts working. When collector temperature exceeds the switch-off temperature of frost protection, pump P1 stops working and the system exits frost protection. ì Press “Choose Function”, until “ ” displays on the screen. ì Press “ ” “ ” button to adjust the temperature of frost protection. Setting range: 3℃–10℃. ì Press “Confirm” button to confirm the setting, press “Cancel” button to deactivate this function. 10. Storage overheating protection To avoid overheating of water storage, system is supported with an overheating protection function. When the temperature of storage (T3) is higher than the maximum temperature, even the condition of temperature difference circulation is reached, solar pump is still forbidden to operate. ì Press “Choose Function” button, until displays on the screen. ì Press “ ” “ ” button to adjust the maximum storage temperature. Default value: 80℃, setting range: 60–90℃. ì Press “Confirm” button to confirm the setting, press “Cancel” button to quit the function. 11. High temperature protection of solar system When collector temperature reaches 115℃, and meanwhile the storage doesn’t reach the max. temperature, the high temperature protection function of solar system will be activated. ì Press “Choose Function”, until displays on the screen. ì Press “ ” “ ” button to adjust the maximum collector temperature. Default value: 115℃, setting range: 100–130℃. ì Press “Confirm” button to confirm the setting, press “Cancel” button to quit this function. 12. Recooling the system by through by –pass This function can realize recooling the solar system through an extra installed radiator (by-pass). 13
  • 16. Work station series for solar water heating control system Attention: The by-pass is controlled by corresponding electromagnetic 3-way valve R2, but the operation menu shows R1, it’s an error indication! ì Press “Choose Function”, until “ ”displays on the screen. ì Press “ ” “ ” button to adjust the switch-on temperature (T1). Default value: 80℃, setting range: 60~90℃. ì Press “Confirm” button to confirm the setting, press “Cancel” button to quit this function. 13. Extended temperature-difference circulation function The Following described function can extend a simple “1 collector array-1 storage” solar system with an additional temperature difference circulation. Note: Only if the input T0, T5 and output R2 are not occupied, this function can be activated. ì Press “Choose Function”, until “ ” displays on the screen. ì Press “Confirm” button to activate this function. Press “Cancel” button to quit this function. 14. Holiday function If you intend to be absent for an extended period (holiday), or hot water is not required for an extended period, you can activate the holiday function. This function is activated nightly(22:00-06: 00)to re-cool the storage and to prevent high thermal loads of the solar system due to completely heated storage. ì Press “Choose Function”, until “ ” displays on the screen, it indicates that the function is active. ì Press “Confirm” button to confirm this setting. Press “Cancel” button to deactivate this function. Note: When using holiday function, system will lock auxiliary heating automatically. 15. Anti-bacteria protection To safeguard the water hygiene, solar system will monitor the storage temperature. If the temperature never reaches 70℃ in every 7 days, auxiliary heating will be activated automatically and heats the storage temperate to 70℃. 16. Collector emergency cut-off When the temperature of collector reaches or exceeds 120℃, in order to prevent evaporation of heat 14
  • 17. Work station series for solar water heating control system medium liquid and protect other components of solar system, solar circulation pump will be stopped compulsively, until the temperature of collector gets lower. 17. Memory function In case of power failure, solar control system is able to remain the preset parameters unchanged. 18. Reset Function If necessary, all the settings (except time setting) can be reset to the factory settings. ì Press “Choose Function” button, until “ ” displays on the screen. ì Press “Confirm” button, all of parameters will be reset to factory settings. 19. Manual operations Customers can monitor the flow rate anytime by viewing the signal “ ” on main operating menu. And when there are no other operations and it returns to main menu, they can also activate some functions by pressing different buttons directly. ì Press “Confirm” button to switch on/off solar collector pump (P1) manually. ì Press “Cancel” button to switch on/off solar hot water circulation pump (P2) manually. ì Press “ ” “ ” button repeatedly to check the temperature values in different part of solar system. Ⅴ Fault messages Danger: Never try to repair the solar pumping station yourself! Consult a specialist in case of an error. The following table explains the error messages and corresponding handling indication. Most of the problems can be found in the list below. No. Familiar problem Possible reason Solution Pump works but no flow rate There is probably too much air Replenish heat medium liquid 1 displays. in the pipeline. and exhaust the air. When storage temperature Storage reaches max. temp. System has temp. difference drops, pump starts working. 2 but pump doesn’t work. Solar collector reaches its max. When collector temperature temp.. drops, pump starts working. There is probable broken circuit Pump doesn’t work, and the Check the sensor wiring and 3 or short circuit with temperature signal “ ” blinks. replace sensors if necessary. sensors. 15
  • 18. Work station series for solar water heating control system Auxiliary heating is forbidden. Activate it manually. 4 Auxiliary heating doesn’t work. Temperature sensor has broken Check sensor connection and circuit or short circuit. make the wiring again. Auxiliary heating still operates 5 Anti-bacteria function starts up. It’s normal. at 23:00. There is air leakage in solar Check the pipeline and 6 System pressure drops. system. exhaust the air. Pump works but system Frost function is activated. 7 No error. doesn’t have temp. difference, Holiday function is activated. The solar work station SP118 shows error messages in the main operating menu if there is a problem with temperature sensor. Error meaning Possible cause Error rectification message There is broken circuit Sensor wiring interrupted, not Check resistance value, <FF℃> with sensor connections. connected or short circuit. replace sensor if necessary. There is a short circuit Sensor wiring interrupted, not Check resistance value, <FE℃> with sensor connections. connected or short circuit. replace sensor if necessary. Note: A potentially defective sensor can be checked using an ohmmeter. To do this, the sensor must be disconnected. Its resistance value can be compared with the figures below, small deviation is acceptable. PT1000 resistance value ℃ 0 10 20 30 40 50 60 70 80 90 100 110 120 1000 1039 1077 1116 1155 1194 1232 1270 1309 1347 1385 1422 1460 NTC 10K B=3950 resistance value ℃ 0 10 20 30 40 50 60 70 80 90 100 110 120 33620 20174 12535 8037 5301 3588 2486 1759 1270 933 697 529 407 16
  • 19. Work station series for solar water heating control system Part 2: Installation instruction ⅠGeneral information 1. Safety Before installing the device, please read this manual carefully. Please note that the installation must be executed according to relevant technical rules. The installation must be adapted to the conditions provided by the customer. Damages by improper using or incorrect modification of installation and construction are on costumer site. Attention: This manual is for trained personals only! Note: As faults can never be excluded, we don’t offer a guarantee for the completeness of the drawings and texts of this manual, they only represent some examples. 2. Input and output signals 1 T3 connector 7 P0 pump or R1 electromagnetic 3-way valve 2 T2 connector 8 Power cord and auxiliary heating connection 3 T0 connector 9 R2 electromagnetic 3-way valve 4 Power switch 10 T5 connector 5 T1 connector 11 T4 connector 6 P2 pump 3. System demonstration 17
  • 20. Work station series for solar water heating control system ⅡMounting 1. Open the package carton and take out the solar control system carefully. Determine the mounting position of the solar control system, considering the mounting place for expansion vessel. See picture 1. Picture 1 2. Drill the holes for dowels, put the dowels into the holes, fixed the solar control system on the wall using fastening screws. The solar control system must be vertically installed. See picture 2. Picture 2 3. Use two wrenches to connect the pipes. See picture 3. Picture 3 4. Install an auto air vent next to the interface of solar collector. See picture 4. 18
  • 21. Work station series for solar water heating control system 5. Determine the mounting place for the expansion vessel. Connect the expansion vessel. See picture5. Picture 5 6. Install a 3-way ball valve above the work station, it can be used for filling heat medium (fill valve); install a 3-way ball valve below the work station for draining (drain valve). See picture 6. There is already a non-return valve installed inside the work station between fill and drain valve. Picture 6 7. Filling the system ◆ Connect a separate pump to the filling valve with pressure hose. ◆ Open the filling and draining valve, fill the system with the separate pump. Heat medium liquid 19
  • 22. Work station series for solar water heating control system (usually use water-glycol mixture as heat medium, 50% glycol and 50% water) will be pumped into the system until it is filled up. ◆ Close the drain valve and continue to fill the system with medium liquid until the system pressure is not lower than 2 bar (the system pressure can be read from the manometer). ◆ Close the filling connector and switch off the pump. Ⅲ Electrical wiring 1. Insert the temperature sensors into storage and solar collector. Connect these sensors to the work station correspondingly. See picture 7. Picture 7 2. Connect auxiliary heating wire if available. Cable (coffee) for the “L”, cable (blue) for “N” line, cable (yellow-green) for the ground wire. 3. To connect external circulation pumps or any electromagnetic valves, firstly loose the aviation socket and dismount it as indicated below. Connect the wire to aviation socket, number 1 connects “N” wire, number 2 connects ground wire, number 3 connects “L” wire. Reassemble the aviation socket and connect it to the solar control system. 4. Tighten all joints and screw connections. Then plug the power supply into a socket. 20
  • 23. Work station series for solar water heating control system Ⅳ Commissioning 1. Switch on the power of solar control system. Press “Confirm” button (in main operating menu) to activate the solar collector pump (P1) manually and let the system circulate for a moment. See picture 10. Picture 10 2. Observe the flow rate of solar control system which displays on LCD screen. If the flow rate is not regular, it indicates that there must be air still in the system. Open the air vent valve several times to relief the air. Picture 11 3. When the flow rate becomes regular, observe the system pressure from manometer. If the pressure is lower than 2 bars, refill the system with heat medium to increase the pressure. Picture 12 4. Carry out a pressure test of all system joints again for leaks. The solar system must be vented several times after some operating hours. Refill the system if necessary. 5. Refill the system if necessary. 6. Remove the separate pump for filling after commissioning. 21
  • 24. Work station series for solar water heating control system 7. If there is auxiliary heating wire connected, press “Choose Function” button until “ ” signal displays on screen. It means switch on auxiliary heating manually. Then customer can use auxiliary heating function. Ⅴ Replace the pump 1. The integrated solar collector pump could be replaced if it gets broken. Disconnect the power supply of solar control system. Loose the screw and open the metal cover. 2. Remove the front half of the insulation material from system 3. Open the terminal box, and disconnect the power supply connection. 4. Loose the screws and open the WILO pump. 22
  • 25. Work station series for solar water heating control system 5. R p c teo o ewt an wWIO p mp el eh l n i a d h e L u . 6 F s nteWIOp mpsrw . . at h e L u ce s 7 C n e th p w r u p a a a dc s tetr n l o . . o n c te o e s p l g i n l e h emi b x y n o a 8 Atc tef n h l h fa cv r . t h h r t a te o m o e. a o f 23
  • 26. Woks t n sr sfrsl w trh ai c nrl yt r t i ei o o r ae e t g o t ss m ao e a n o e 9 Atc teme lo e a dfs ntesrw a a . . t hh a a c v r n a t h ce s g i e n Ⅵ Packing list N. o Im t e S e i ai p ci t n f o c Q at u ni ty 1 Wok t i r s tn ao 40 30 10 5 × 1 × 5 mm 1pc 2 P w ri o e le n 1pc 3 P 1 0 s no T 0 0 e sr 1m 5 2p s c 4 N Cs n o T e sr 3m 4p s c 5 Fx dsrw ie ce 1b g a 6 Ma u l na 1pc 24