SlideShare una empresa de Scribd logo
1 de 49
Descargar para leer sin conexión
RECYCLED WATER EXPANSION PROJECT
JANUARY 2014
PROJECT NUMBER: WW-0002
PREPARED BY

AREA MAP

CR
O
SS

R
D

LOCATION MAP

YO
U
NT
VI
LL

E

PROJECT
LOCATION

BERINGER
POND

G
HI
HW
AY

SILVERADO WEST POND

29

STAG'S LEAP WINE
CELLARS POND

D

VER

N
LA

RI
NAPA

PROJECT
SITE

NE
LA

YOUNTVILLE JOINT
TREATMENT PLANT

CLOS DU VAL/
REGUSCI POND
LV
ER

DR

O
AD
L
AI
TR

RD
YA
E
V IN

W
VIE

SI

MONDAVI POND

CHIMNEY ROCK
POND

N

NOT TO SCALE

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

22 November 2013 - 2:41 PM

Plotted by: Ben Langston

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 G-001.dwg

BL

Designer MBJ

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

TW

Approved
(Project Director)
JANUARY 2014
Date
Scale

NONE

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

G-001

Sht

1

of

50
SYMBOLS

ABBREVIATIONS
SECTION DESIGNATION

@
AB
AC
APN
B
BLDG
BM
BOTT

SECTION DESIGNATIONS USE LETTERS
ON DRAWING WHERE SECTION IS TAKEN:

A
M101

SECTION DESIGNATION
DRAWING NUMBER WHERE SHOWN

SECTION DESIGNATION

SECTION

M100

SCALE: 1/4"=1'-0"

DRAWING NUMBER WHERE TAKEN
DRAWING NUMBER SHOWN AS " - " IF TAKEN & SHOWN ON SAME SHEET.

DETAIL DESIGNATION
DETAIL DESIGNATIONS USE NUMBERS
ON DRAWING WHERE SECTION IS TAKEN:

M101

DRAWING NUMBER WHERE SHOWN

M100

DETAIL DESIGNATION

NOMINAL PIPE DIAMETER
PIPE MATERIAL; SEE SPECIFICATIONS
FOR EQUIVALENT REPLACEMENT
FLOW STREAM IDENTIFIER
DESIGNATION FOR EXISTING PIPING (SCREENED):
PIPING SYSTEM DESIGNATIONS FOR EXISTING
PIPE INDICATE TYPE OF SERVICE ONLY AND
DO NOT IMPLY PIPE MATERIALS USED.
DESIGNATION FOR FUTURE PIPING (DASHED):

MAX
MH
MIN
MISC
MON
MTL
(N)
N
NC
NIC
NO
NSD
NTS

UNK

VERTICAL
VITRIFIED CLAY

W
W/
WM
W/S
WTR

NEW
NORTH
NORMALLY CLOSED
NOT IN CONTRACT
NUMBER
NAPA SANITATION DISTRICT
NOT TO SCALE

UNKNOWN

V, VERT
VC

MAXIMUM
MANHOLE
MINIMUM
MISCELLANEOUS
MONUMENT
MATERIAL

WATER, WEST
WITH
WATER METER
WATER SURFACE
WATER

LATERAL
LINEAR FEET
LONGITUDINAL

AMPERE,AMPS

AC

ALTERNATING CURRENT

AE

ANALYZER ELEMENT

AI

ANALOG INPUT

AO

ANALOG OUTPUT

kV

KILOVOLT

AWG

AMERICAN WIRE GAUGE

kVA

KILOVOLT AMPERES

kW

KILOWATT

BKR

6" PVC
4" PVC

EQUIPMENT NUMBER

8" DIP

DESIGNATION FOR NEW INSTRUMENTS:
FE-1

6" DIP

INSTRUMENT NUMBER

G-001

TITLE SHEET, AREA AND LOCATION MAPS

2

G-002

ABBREVIATIONS, LEGEND, SYMBOLS AND DRAWING
INDEX

3

G-003

OVERALL SITE PLAN, KEY MAP, CONTROL DIAGRAM AND
BORING LOCATIONS

JUNCTION BOX

BREAKER
LEVEL ELEMENT

OC
OD
OHE

MITIGATION MEASURES AND GENERAL NOTES

CIRCUIT BREAKER

LS

LEVEL SWITCH

5

C-101

INTENTIONALLY LEFT BLANK

CONCRETE EQUIPMENT PAD
CONTROL PANEL

LSH

HIGH-LEVEL SWITCH

6

C-102

RECYCLED WATER PLAN AND PROFILE - BERINGER

LSL

LOW-LEVEL SWITCH

7

C-103

RECYCLED WATER PLAN AND PROFILE - BERINGER

MAG

MAGNETIC

8

C-104

RECYCLED WATER PLAN AND PROFILE - BERINGER

9

C-105

RECYCLED WATER PLAN AND PROFILE - BERINGER

PCS

PROCESS CONTROL SYSTEM

10

C-106

RECYCLED WATER PLAN AND PROFILE - BERINGER

TSP

TWISTED SHIELDED PAIR

11

C-107

RECYCLED WATER PLAN AND PROFILE - BERINGER

TYP

TYPICAL

12

C-108

RECYCLED WATER PLAN AND PROFILE - MONDAVI

ULS

ULTRASONIC LEVEL SENSOR

13

C-109

CHIMNEY ROCK POND IMPROVEMENTS

V

VOLTS

14

C-110

CLOS DU VAL/REGUSCI POND IMPROVEMENTS

VA

VOLT-AMPERES

VFD

VARIABLE FREQUENCY DRIVE

15

C-111

STAG'S LEAP WINE CELLARS POND IMPROVEMENTS

W/

WITH

16

C-112

TREATMENT PLANT SITE PLAN

17

C-113

TREATMENT PLANT DEMOLITION, GRADING AND PAVING
PLAN

ELECTRICAL NOTES

18

C-114

TREATMENT PLANT PIPING PLAN

1.

R, RAD
RC
RCP
RGS
RD
ROW, R/W
RR
RTU
RW

G-004

CP

PORTLAND CEMENT CONCRETE
PROPERTY LINE
PROPERTY
POINT
POLYVINYL CHLORIDE PLASTIC

4

CEP

PCC
PL
PROP
PT
PVC

LEVEL INDICATING TRANSMITTER

CB

ON CENTER
OUTSIDE DIAMETER
OVERHEAD ELECTRIC

LIT

19

C-115

TREATMENT PLANT SITE PLAN

20

C-501

CIVIL DETAILS - 1

21

C-502

CIVIL DETAILS - 2

22

C-503

CIVIL DETAILS - 3

EVERY EFFORT HAS BEEN MADE TO IDENTIFY REMOTE ITEMS TO BE CONNECTED BY THE ELECTRICAL CONTRACTOR, EITHER IN THE
ELEMENTARIES OR IN THE SCHEDULES. HOWEVER, NOT ALL OF THE REMOTE DEVICES MAY HAVE BEEN SHOWN ON THE ELECTRICAL PLAN
DRAWINGS. REFER TO THE DRAWINGS OF RESPECTIVE TRADES TO LOCATE OR CONFIRM EQUIPMENT LOCATIONS.

23

C-504

CIVIL DETAILS - 4

24

C-505

CIVIL DETAILS - 5

GROUNDING: ELECTRICAL SYSTEMS SHALL BE GROUNDED AS SPECIFIED AND SHOWN ON THE CONTRACT DRAWINGS. WORK SHALL ALSO BE
PERFORMED IN ACCORDANCE WITH ARTICLE 250 OF THE MOST RECENT REVISION OF THE NATIONAL ELECTRIC CODE. REFER TO DETAILS FOR
GROUNDING SCHEMATICS AND FOR GENERAL GROUNDING REQUIREMENTS OF ELECTRICAL EQUIPMENT. GROUND GRID CONNECTIONS SHOWN
ON THE INDIVIDUAL PLANS ARE MINIMUM REQUIREMENTS. ALL REQUIRED CONNECTIONS ARE NOT SHOWN ON PLANS FOR BREVITY. CONTRACTOR
SHALL COORDINATE NEW CONNECTIONS TO THE EXISTING GROUND GRIDS AS NECESSARY. REFER TO GROUNDING NOTES BELOW AND
ELECTRICAL DETAILS FOR ADDITIONAL INFORMATION.

25

C-506

CIVIL DETAILS - 6

26

C-507

CIVIL DETAILS - 7

27

M-301

RECYCLED WATER PUMP STATION PLAN AND SECTION

S-100

GENERAL STRUCTURAL NOTES

29

S-101

TRICKLING FILTER STRUCTURAL MODIFICATIONS

30

S-102

TRICKLING FILTER VALVE VAULT AND WETWELL PLANS

31

S-103

TRICKLING FILTER VALVE VAULT DETAILS

32

S-104

TRICKLING FILTER VALVE VAULT DETAILS

33

E-101

TREATMENT PLANT ELECTRICAL SITE PLAN

34

E-200

ELECTRICAL CONDUIT RISER DIAGRAM

35

E-300

GOLF COURSE PUMP CONTROL PANEL

36

E-400

RTU DETAILS

37

E-501

DECHLORINATION SYSTEM MODIFICATIONS

38

E-502

ELECTRICAL DETAILS

39

E-503

ELECTRICAL DETAILS

40

E-504

ELECTRICAL DETAILS

41

E-505

ELECTRICAL DETAILS

42

E-506

ELECTRICAL DETAILS

43

E-507

ELECTRICAL DETAILS

44

E-508

ELECTRICAL DETAILS

45

E-509

PV PANEL DETAILS

46

I-100

I&C LEGEND

47

I-101

SCADA RISER DIAGRAM

48

I-102

ELECTRICAL SCADA POLE DETAILS

49

I-103

RTU U P&ID

50

I-104

RTU R P&ID

DC

DIRECT CURRENT

DO

DISCRETE OUTPUT

DS

DISCONNECT SWITCH

EMR

EQUIPMENT MOUNTING RACK

RADIUS
RELATIVE COMPACTION
REINFORCED CONCRETE PIPE
RIGID STEEL
ROAD
RIGHT-OF-WAY
RAILROAD
REMOTE TELEMETRY UNIT
RECYCLED WATER

EX

EXISTING

S
SCH
SD
SECT
SERV
SHT
SIG
SPEC
SQ
SS
SSMH
STA
STD
ST STL

SOUTH
SCHEDULE
STORM DRAIN
SECTION
SERVICE
SHEET
SIGNAL
SPECIFICATIONS
SQUARE
SANITARY SEWER
SANITARY SEWER MANHOLE
STATION
STANDARD
STAINLESS STEEL

HOA

HAND-OFF-AUTO SELECTOR-SWITCH

HP

HORSEPOWER

TC
T, TEL
TG, T/G
TOB
TS
TSP
TYP

TOP OF CURB
TELEPHONE
TOP OF GRATE
TOP OF BERM
TRAFFIC SIGNAL/SERVICE
TWISTED SHIELDED PAIR
TYPICAL

FE

FLOW ELEMENT

FIT

FLOW INDICATING TRANSMITTER

FO

FIBER OPTIC

G OR GRD

2.

3.

4.

TRUCK FILL VALVE
8" PVC RECLAIMED WATERLINE
6" PVC RECLAIMED WATERLINE

6.
VALVE ACTUATOR

GROUND

CONTRACTOR SHALL COORDINATE FINAL CONCRETE EQUIPMENT PAD (CEP) DIMENSIONS WITH FINAL DIMENSIONS OF EQUIPMENT AND OTHER
STRUCTURES TO BE MOUNTED ON PADS. REFER TO NOTES AND STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION. EXTERIOR CEP SHALL
MAINTAIN 4'-0” IN FRONT OF ELECTRICAL PANELS AND 6” ON SIDES.
ENCLOSURE DIMENSIONS SHOWN ON THE DRAWINGS ARE MINIMUM REQUIRED DIMENSIONS. ENCLOSURES SHALL BE SIZED TO ACCOMMODATE
EQUIPMENT, CONTROLS AND COMPONENTS AS SHOWN, SPECIFIED AND REQUIRED FOR AN OPERABLE SYSTEM.

EXACT EQUIPMENT CONDUIT CONNECTIONS ARE TO BE DETERMINED BY THE ELECTRICAL INSTALLER BASED UPON THE ACTUAL FIELD LOCATION
OF EQUIPMENT. INSTALL CONDUIT IN ACCORDANCE WITH SPECIFICATIONS.
ALL PENETRATIONS THROUGH EXISTING SOLID CONCRETE STRUCTURES WHERE SLEEVES HAVE NOT BEEN PROVIDED SHALL BE CORE DRILLED
AND SIZED TO ACCEPT MECHANICAL LINK SEALS. THROUGH NON-FIRE RATED WALLS, CORE HOLE AND SEAL AROUND CONDUIT WITH
NON-SHRINK GROUT. THROUGH EXTERIOR WALL SEAL WATER TIGHT WITH SILICONE MASONRY SEALANT.

4" PVC RECLAIMED WATERLINE
LEVEL ELEMENT
8" DIP RECLAIMED WATERLINE
6" DIP RECLAIMED WATERLINE

CHECK VALVE

7.

EQUIPMENT MOUNTING RACK (EMR): THE FINAL LOCATION OF THE EMR'S SHALL BE COORDINATED IN THE FIELD TO AVOID INTERFERENCE WITH
ACCESS TO THE PROCESS EQUIPMENT. REFER TO DETAILS FOR INDIVIDUAL APPLICATIONS AND LOCATIONS.

8.

EQUIPMENT REMOVALS: DISCONNECT AND REMOVE POWER/CONTROL CIRCUITS AND CONDUITS FROM THE RESPECTIVE EQUIPMENT.

9.

EQUIPMENT RELOCATIONS: DISCONNECT AND REMOVE POWER/CONTROL CIRCUITS AND CONDUCTORS FROM THE EQUIPMENT. EQUIPMENT
SHALL BE REMOVED AND RELOCATED TO THE NEW LOCATION SHOWN ON THE CONTRACT DRAWINGS.

10.

CONDUIT REMOVALS: DISCONNECT AND REMOVE EXPOSED PORTIONS OF CONDUIT FOR EQUIPMENT TO BE REMOVED AND/OR RELOCATED. CUT,
THREAD, COUPLE AND CAP EXISTING CONDUITS ADJACENT TO THE PENETRATION POINT WHERE THE CONDUITS ARE CONCEALED (IN WALLS,
CONCRETE SLABS, BELOW GRADE). REPAIR WALL PENETRATIONS TO A WEATHER-TIGHT CONDITION MATCHING EXISTING WALL MATERIALS.

EQUIPMENT
GATE VALVE
POND LEVEL INDICATOR AND
ELECTRICAL CONDUIT
REDUCER
POLE-MOUNTED CONTROL EQUIPMENT
AND PV PANEL
TEE
EDGE OF PAVEMENT
B1

GEOTECHNICAL BORINGS

90° BEND

11.

ARCHAEOLOGICAL BORINGS
FLOW METER
ANTENNA

12.

ROLL CURB
METER BOX

CONTRACTOR ACCESS/ HAUL ROUTES

13.

EXISTING
RW TURNOUT

INTERMEDIATE CONTOUR

CULVERT

EDGE OF PAVEMENT

SS PIPELINE

CATCH BASIN

SPOT ELEVATION

FENCE

INDEX CONTOUR

14.

MANHOLE

RW PIPELINE

EQUIPMENT TO REMAIN: PROVIDE NEW FEEDER OR BRANCH CIRCUIT CONDUIT AND WIRING TO EXISTING/RELOCATED EQUIPMENT REQUIRED TO
REMAIN IN SERVICE. CUT AND REUSE EXISTING CONDUIT RUNS WHERE PRACTICAL. CIRCUIT CONDUCTORS SHALL BE REPLACED THE ENTIRE
LENGTH OF THE CIRCUIT RUN.
ELECTRICAL PLANS: CONTRACTOR SHALL REFER TO ONE-LINES, SCHEMATICS, CONDUIT RISER DIAGRAMS AND DETAILS TO COORDINATE
CONDUIT AND CIRCUIT REQUIREMENTS FOR EACH SYSTEM.
FIBER OPTIC PATCH PANEL (FOPP) ENCLOSURE: ALL INDOOR FIBER OPTIC PATCH PANELS SHALL BE MOUNTED IN NEMA 12 ENCLOSURES IN
ORDER TO ACCOMMODATE CONDUIT ENTRIES AND EXITS AND TO FACILITATE CONDUIT ROUTING IN THE BUILDING. ALL EXTERIOR FIBER OPTIC
PATCH PANELS SHALL BE MOUNTED IN NEMA 4X ENCLOSURES.
CONDUIT PENETRATIONS: WHERE CONDUITS ARE TOO LARGE FOR TERMINATION INTO CABINETS, CONTROL PANELS, INSTRUMENT ENCLOSURES
OR OTHER ENCLOSURES DUE TO STANDARD KNOCK OUT SIZE, THE CONTRACTOR SHALL PROVIDE AN INTERMEDIATE PULL BOX IN ORDER TO
COORDINATE A TRANSITION IN CONDUIT SIZE. THIS SHALL BE COORDINATED WITH THE ENGINEER IN THE FIELD ON A CASE BY CASE BASIS.

BOLLARD

15.

16.

SPARE WIRING: WHERE SPARE POWER AND CONTROL WIRING IS REQUIRED PER THE DRAWINGS AND/OR SPECIFICATIONS, SPARE WIRE SHALL BE
PROVIDED WITH SUFFICIENT LENGTH TO EXTEND TO THE FURTHEST TERMINAL BLOCK/BUCKET/AREA OF THE ENCLOSURE BEING SERVED.
PROVIDE NAMEPLATE TO EXISTING PANELS AND EQUIPMENT INDICATING THE EQUIPMENT'S TAG NUMBER FOR ALL EXISTING EQUIPMENT THAT IS
TO BE CONNECTED TO THE RTU/SCADA FOR MONITORING AND CONTROL.

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

27 November 2013 - 2:14 PM

Plotted by: Ben Langston

Drawn

Job
Project
Manager Director

Cad File No:

DRAWING TITLE

CONDUIT OR CONDUCTOR

5.

8" PVC

PS3-1

1

JB

DRAWING NO.

C

NEW

DESIGNATION FOR NEW EQUIPMENT:

SHEET NO.

LE

LEGEND

EQUIPMENT DESIGNATION

INPUT/OUTPUT

A OR AMP

12" W

12" DI, W

I/O

DRAWING INDEX

28

JOINT TRENCH

LAT
LF
LONG

12" DI, W

INCH
INVERT
IRRIGATION

J/T

PIPE DESIGNATION

HORIZONTAL

IN
INV
IRR

DRAWING NUMBER SHOWN AS " - " IF TAKEN & SHOWN ON SAME SHEET.

GAS
GAUGE

H, HORIZ

SCALE: 1/4"=1'-0"

EXISTING
EAST
EACH
ELEVATION
EDGE OF PAVEMENT
EASEMENT
EXISTING
FIRE HYDRANT
FLOWLINE
FIRE SERVICE
FEET OR FOOT

G
G

DETAIL

DRAWING NUMBER WHERE TAKEN

DESIGNATION FOR NEW PIPING:

DEPARTMENT
DETAIL
DROP INLET
DIAMETER
DRAWING

(E)
E
EA
EL, ELEV
EP
ESMT
EX
FH
FL
FS
FT

ON DRAWING WHERE SECTION IS SHOWN:

1

CONDUIT
CATCH BASIN
CONTROLLED DENSITY FILL
CAST IRON
CURED-IN-PLACE PIPE
CLEAR
CENTERLINE
CORRUGATED METAL PIPE
CLEANOUT
CONCRETE
CONTROL
CENTER
CULVERT

DEPT
DET
DI
DIA
DWG

1

DETAIL DESIGNATION

BORING
BUILDING
BENCH MARK
BOTTOM

C
CB
CDF
CI
CIPP
CLR
CL
CMP
CO
CONC
CNTRL
CTR
CULV

ON DRAWING WHERE SECTION IS SHOWN:

A

AT
AGGREGATE BASE
ASBESTOS CEMENT
ASSESSORS PARCEL NUMBER

ELECTRICAL ABBREVIATIONS AND ELECTRICAL NOTES

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 G-002.dwg

BL

Designer MJ

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

NONE

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

G-002

Sht

2

of

50
R
D

CONTROL POINTS

SS

POINT # NORTHING

DESCRIPTION

EASTING ELEVATION

LE
IL
TV
N
U

D
R
EL
N
N
FI

80.94

SET NAIL AT AERIAL PANEL

1905352.16

6463204.02

76.61

SET NAIL AT AERIAL PANEL

1905780.94

6459791.17

85.67

SET NAIL AT AERIAL PANEL

1908117.50

6455949.72

145.15

SET NAIL AT AERIAL PANEL

1906589.50

6458350.20

97.80

SET NAIL AT AERIAL PANEL

1905895.06

6457683.06

106.86

SET NAIL AT AERIAL PANEL

1906563.60

6458210.20

101.37

SET NAIL AT AERIAL PANEL

1908307.06

6457487.87

103.96

SET NAIL AT AERIAL PANEL

1904864.96

6465099.96

83.79

SET NAIL AT AERIAL PANEL

1906594.91

6468391.52

81.92

SET NAIL AT AERIAL PANEL

1906999.97

6468920.74

88.53

SET NAIL AT AERIAL PANEL

1909584.23

6467279.11

134.37

SET NAIL AT AERIAL PANEL

1911651.29

6465338.64

153.40

SET NAIL AT AERIAL PANEL

1909397.25

6464425.86

128.07

SET NAIL AT AERIAL PANEL

1913252.17

6464212.92

96.29

SET NAIL AT AERIAL PANEL

421

YO

6461597.60

1905076.64

6458318.51

100.32

SET NAIL AT AERIAL PANEL

4

1906750.83

419

6

405

418

0
-1

SET NAIL AT AERIAL PANEL

417

0
-1

83.28

416

C

6461653.46

415

C

1907952.05

412

B6

404

414

C

SET NAIL AT AERIAL PANEL

411

05
-1

84.68

410

B5

6459963.58

413

BERINGER
POND

1906266.52

409

B4

SET NAIL AT AERIAL PANEL

408

N

91.48

407

C

6461011.03

403

07
-1

1912056.72

406

C
R
O

401

B7
YO
UN

O
AD

DR

D

* DO NOT DISTURB ANY SURVEY CONTROL OR BOUNDARY
MONUMENTS.

L
AI
TR

29

LA

N

LA

E
N

STAG'S LEAP WINE
CELLARS POND

11
1
C-

B2
B1

0
11
C-

N
LA

A
NAP

SO

2
-11 U
C R
TH 14
1
C-

GHD TOPOGRAPHICAL GROUND SURVEY, AUGUST 2011

* AERIAL SURVEY BY 3DI WEST, FLOWN AUGUST 16, 2011 FROM
EUGENE OREGON (JOB#11-06)

ER

AY

A

R

IA

B3

HORIZONTAL CONTROL: CALIFORNIA COORDINATE SYSTEM
ZONE 2 NAD 83

*

LV

HW

CONSTRUCTION
LAUYDOWN AREA

B8

VERTICAL BENCHMARK: FOUND BRASS DISK - “VET HOME”
ELEVATION 94.26 NAVD 88

*

1
-11
C
SI

T
EE
TR
TS

G
HI

C

O
IF
L

N

C

02
-1

C

03
-1

*

O

ER
RIV

DR

C-108
CLOS DU VAL/
REGUSCI POND

YOUNTVILLE JOINT
TREATMENT PLANT

SI
LV
ER

MONDAVI POND

O
AD
IL
AI
TR

ING
SH
WA

VI

D
AR
Y
NE

W
VIE

DR

C-109

TO

C-109

NS

CHIMNEY ROCK
POND

EE
TR
T
0

OVERALL SITE PLAN, KEY MAP, AND CONTROL DIAGRAM
Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

6 December 2013 - 4:46 PM

Plotted by: Aaron Foscato

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 G-003.dwg

600

900

1200'

SCALE 1"=600' AT ORIGINAL SIZE

Reuse of Documents

FINAL TOWN REVIEW NFC

300

BL

Designer MJ

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

G-003

Sht

3

of

50
MITIGATION MEASURES

GENERAL NOTES
GENERAL NOTES

PROJECT MEASURE 1: BASIC AIR QUALITY MEASURES
THE CONTRACTOR SHALL IMPLEMENT THE BAY AREA AIR QUALITY MANAGEMENT DISTRICT'S BASIC CONSTRUCTION MEASURES, WHICH
CONSIST OF THE FOLLOWING:
1.

ALL EXPOSED SURFACES (E.G., PARKING AREAS, STAGING AREAS, SOIL PILES, GRADED AREAS, AND UNPAVED ACCESS ROADS)
SHALL BE WATERED UP TO TWO TIMES PER DAY AS NECESSARY TO REDUCE DUST.
ALL HAUL TRUCKS TRANSPORTING SOIL, SAND, OR OTHER LOOSE MATERIAL OFF-SITE SHALL BE COVERED.
ALL VISIBLE MUD OR DIRT TRACK-OUT ONTO ADJACENT PUBLIC ROADS SHALL BE REMOVED USING WET POWER VACUUM STREET
SWEEPERS AT LEAST ONCE PER DAY. THE USE OF DRY POWER SWEEPING IS PROHIBITED.
ALL VEHICLE SPEEDS ON UNPAVED ROADS SHALL BE LIMITED TO 15 MPH.
ALL ROADWAYS, DRIVEWAYS, AND SIDEWALKS TO BE PAVED SHALL BE COMPLETED AS SOON AS POSSIBLE.
IDLING TIMES SHALL BE MINIMIZED EITHER BY SHUTTING EQUIPMENT OFF WHEN NOT IN USE OR REDUCING THE MAXIMUM IDLING
TIME TO 5 MINUTES (AS REQUIRED BY THE CALIFORNIA AIRBORNE TOXICS CONTROL MEASURE TITLE 13, SECTION 2485 OF
CALIFORNIA CODE OF REGULATIONS [CCR]). CLEAR SIGNAGE SHALL BE PROVIDED FOR CONSTRUCTION WORKERS AT ALL ACCESS
POINTS.
ALL CONSTRUCTION EQUIPMENT SHALL BE MAINTAINED AND PROPERLY TUNED IN ACCORDANCE WITH MANUFACTURER'S
SPECIFICATIONS. ALL EQUIPMENT SHALL BE CHECKED BY A CERTIFIED MECHANIC AND DETERMINED TO BE RUNNING IN PROPER
CONDITION PRIOR TO OPERATION.
POST A PUBLICLY VISIBLE SIGN WITH THE TELEPHONE NUMBER AND PERSON TO CONTACT AT THE LEAD AGENCY REGARDING
DUST COMPLAINTS. THIS PERSON SHALL RESPOND AND TAKE CORRECTIVE ACTION WITHIN 48 HOURS. THE AIR DISTRICT'S PHONE
NUMBER SHALL ALSO BE VISIBLE TO ENSURE COMPLIANCE WITH APPLICABLE REGULATIONS.

2.
3.
4.
5.
6.

7.

8.

PROJECT MEASURE 2: TRAFFIC CONTROL PLAN
THE CONTRACTOR SHALL DEVELOP A TRAFFIC CONTROL PLAN TO MINIMIZE THE IMPACTS OF CONSTRUCTION TRAFFIC ON PROJECT
AREA ROADWAYS AND AT KEY INTERSECTIONS USED DURING CONSTRUCTION. THE TRAFFIC CONTROL PLAN SHALL INCLUDE THE
FOLLOWING PROVISIONS AND MAY INCLUDE OTHER MEASURES IF A FURTHER NEED IS IDENTIFIED.
1.
2.

LOCATION(S) OF DESIGNATED PROJECT CONSTRUCTION STAGING AREAS.
POST WARNING SIGNAGE AT POINTS WHERE CONSTRUCTION TRAFFIC WILL ENTER OR LEAVE SOLANO DR, LAND LANE, AND
SILVERADO TRAIL
USE FLAG CONTROL DURING WORK HOURS WHEN EQUIPMENT OR MATERIALS ARE DELIVERED TO THE WORK AREA.
DETOUR ROUTES TO BE USED IN ORDER TO MAINTAIN ACCESS DURING VARIOUS PHASES OF THE PROJECT'S CONSTRUCTION.
RESTRICT ALL CONSTRUCTION TRAFFIC TO NORMAL DAYTIME BUSINESS HOURS, UNLESS THE TOWN IDENTIFIES A NEED FOR
OFF-HOURS ROUTING TO AVOID IMPACTS ON PEAK-HOUR COMMUTE TRAFFIC.
CONSULT WITH THE NAPA COUNTY FIRE DEPARTMENT AND PROVIDE NOTIFICATION OF THE TIMING, LOCATION, AND DURATION OF
CONSTRUCTION IN THE VICINITY OF THE YOUNTVILLE FIRE STATION.
IN ORDER TO MINIMIZE ANY POTENTIAL OVERLAP WITH OTHER CONSTRUCTION AND ROADWAY IMPROVEMENT PROJECT(S), THE
CONTRACTOR SHALL WORK WITH THE TOWN AND NAPA COUNTY TO IDENTIFY THE ROUTES AND INTERSECTIONS THAT SHOULD BE
AVOIDED, AS WELL AS APPROPRIATE ALTERNATE TRAVEL ROUTES OR TIMES. THE PLAN SHALL ADDRESS ROUTES TO MINIMIZE
CONSTRUCTION TRAFFIC ON STATE HIGHWAY 29 DURING PEAK HOURS.

3.
4.
5.
6.

IN THE CASE OF AN UNANTICIPATED ARCHAEOLOGICAL DISCOVERY, IF IT IS DETERMINED THAT THE FIND IS UNIQUE UNDER THE
NATIONAL HISTORIC PRESERVATION ACT (NHPA) AND/OR POTENTIALLY ELIGIBLE FOR LISTING IN THE NATIONAL REGISTER, AND THE
SITE CANNOT BE AVOIDED, THE CONTRACTOR SHALL DEVELOP A RESEARCH DESIGN AND EXCAVATION PLAN, PREPARED BY AN
ARCHAEOLOGIST, OUTLINING RECOVERY OF THE RESOURCE, ANALYSIS, AND REPORTING OF THE FIND. TREATMENT AND RESOLUTION
MAY INCLUDE MODIFYING THE PROJECT TO ALLOW THE MATERIALS TO BE LEFT IN PLACE, OR UNDERTAKING DATA RECOVERY OF THE
MATERIALS IN ACCORDANCE WITH STANDARD ARCHAEOLOGICAL METHODS; PROTECTION AND PRESERVATION OF RESOURCES IS
PREFERABLE IF FEASIBLE. THE RESEARCH DESIGN AND EXCAVATION PLAN SHALL BE SUBMITTED TO RECLAMATION STAFF WHO WOULD
NOTIFY THE SHPO AND THE NATIVE AMERICAN REPRESENTATIVES. RECLAMATION AND THE SWRCB SHALL APPROVE THE PLAN PRIOR
TO CONSTRUCTION BEING RESUMED. IN THE EVENT THAT THE CONTRACTOR MUST WORK IN THE STATE RIGHT-OF-WAY (I.E. STATE
HIGHWAY 29), THE CONTRACTOR SHALL SUBMIT A STANDARD ENCROACHMENT PERMIT APPLICATION TO CALTRANS DURING THE DESIGN
OF PHASE 3 OF THE PROJECT. IF AN UNANTICIPATED ARCHAEOLOGICAL DISCOVERY DURING GROUND-DISTURBING ACTIVITIES OCCURS
WITHIN THE STATE RIGHT-OF-WAY, THE CALTRANS OFFICE OF CULTURAL RESOURCE STUDIES, DISTRICT 4, SHALL BE CONTACTED.

MITIGATION MEASURE CR-6: PROCEDURES FOR ENCOUNTERING HUMAN REMAINS
IF HUMAN REMAINS ARE DISCOVERED, POTENTIALLY DAMAGING ACTIVITIES SHALL BE HALTED AND NO FURTHER EXCAVATION OF THE
REMAINS OR NEARBY AREA CAN OCCUR UNTIL THE NAPA COUNTY CORONER HAS MADE NECESSARY FINDINGS AS TO THE ORIGIN OF
THE REMAINS, IN ACCORDANCE WITH THE HEALTH AND SAFETY CODE 7050.5. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE
COUNTY CORONER AND A PROFESSIONAL ARCHAEOLOGIST TO DETERMINE THE NATURE OF THE REMAINS. AT THE SAME TIME, AN
ARCHAEOLOGIST SHALL BE CONTACTED TO EVALUATE THE SITUATION. AS THE PROPERTY HAS BEEN REPEATEDLY TILLED AND GRADED,
THE POSSIBILITY EXISTS THAT HUMAN REMAINS MAY BE FRAGMENTARY AND MIXED WITH SURROUNDING SOILS. IF HUMAN REMAINS ARE
ENCOUNTERED, ALL GROUND DISTURBANCE WITHIN A 50 FEET DIAMETER AREA SHALL BE HALTED UNTIL THE ARCHAEOLOGIST AND THE
CORONER HAVE REVIEWED THE REMAINS. IF THE CORONER DETERMINES THAT THE REMAINS ARE OF NATIVE AMERICAN ORIGIN, THE
TOWN SHALL NOTIFY THE NATIVE AMERICAN HERITAGE COMMISSION WITHIN 24 HOURS OF IDENTIFICATION, AS WELL AS THE
RECLAMATION REPRESENTATIVE. THE COMMISSION THEN NOTIFIES THE MOST LIKELY DESCENDANT, WHO HAS 48 HOURS TO MAKE
RECOMMENDATIONS TO THE LANDOWNER FOR THE DISPOSITION OF THE REMAINS. REMAINS SHALL BE TREATED IN ACCORDANCE WITH
PUBLIC RESOURCES CODE §5097.9.

2.

CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS AND PAY ALL FEES PRIOR TO COMMENCEMENT OF
ANY WORK EXCEPT THOSE SPECIFICALLY NOTED IN SPECIFICATIONS AS PROVIDED BY TOWN OF
YOUNTVILLE

3.

CONTRACTOR SHALL OBTAIN AN ENCROACHMENT PERMIT FROM NAPA COUNTY, CA BEFORE START OF
WORK. CONTRACTOR SHALL COMPLY WITH ALL REQUIREMENTS OF THE PERMIT
WORK HOURS ARE LIMITED TO MONDAY THROUGH FRIDAY 8 A.M. TO 5 P.M. AT THE PROJECT SITE AND 7:30
A.M. TO 4 P.M. AT THE TREATMENT PLANT. TIME AT THE TREATMENT PLANT HAS SOME FLEXIBILITY;
HOWEVER DIFFERING HOURS NEED TO BE COORDINATED WITH DON MOORE, UTILITY OPERATIONS
SUPERVISOR. INSPECTION WILL BE AVAILABLE MONDAY THROUGH FRIDAY FROM 8 A.M. TO 4 P.M. ANY
WEEKEND WORK IS SUBJECT TO TOWN APPROVAL.

5.

PRE-CONSTRUCTION MEETING IS REQUIRED PRIOR TO BEGINNING OF WORK. CONTACT THE ENGINEER TO
SCHEDULE SUCH MEETING.

6.

IF PALEONTOLOGICAL RESOURCES (E.G., VERTEBRATE BONES, TEETH, OR ABUNDANT AND WELL-PRESERVED INVERTEBRATES OR
PLANTS) ARE ENCOUNTERED DURING CONSTRUCTION, THE TOWN SHALL HALT GROUND-DISTURBING WORK IN THE VICINITY OF THE
FIND. WORK NEAR THE FIND SHALL NOT BE RESUMED UNTIL A QUALIFIED PALEONTOLOGIST HAS EVALUATED THE MATERIALS AND
OFFER RECOMMENDATIONS FOR FURTHER ACTION, INCLUDING SALVAGE OF ANY SIGNIFICANT PALEONTOLOGICAL RESOURCES.

ANY DISCREPANCY DISCOVERED BY CONTRACTOR IN THESE PLANS OR ANY FIELD CONDITIONS
DISCOVERED BY CONTRACTOR THAT MAY DELAY OR OBSTRUCT THE PROPER COMPLETION OF THE WORK
PER THESE PLANS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND THE OWNER
IMMEDIATELY UPON DISCOVERY. SAID NOTIFICATION SHALL BE IN WRITING.

4.

MITIGATION MEASURE CR-5: PROTECTION AND PRESERVATION OF PALEONTOLOGICAL MATERIALS

1.

WITHIN 48 HOURS OF PAVING, ALL WATER VALVE BOXES WILL BE BROUGHT TO GRADE AND INSPECTION
REQUESTED.

GENERAL UNDERGROUND NOTES
1.

NO GUARANTEE IS INTENDED THAT UNDERGROUND OBSTRUCTIONS NOT SHOWN ON THESE PLANS MAY
BE ENCOUNTERED. THOSE SHOWN ARE BASED ON THE BEST INFORMATION AVAILABLE AND THE
CONTRACTOR IS CAUTIONED THAT THE OWNER, THE ENGINEERS, AND THE TOWN OF YOUNTVILLE
ASSUME NO RESPONSIBILITY FOR ANY OBSTRUCTIONS EITHER SHOWN OR NOT SHOWN ON THESE PLANS.
THE CONTRACTOR SHALL COOPERATE WITH ALL UTILITY COMPANIES WORKING WITHIN THE LIMITS OF
THIS PROJECT.

2.

CONTRACTOR SHALL NOT BEGIN EXCAVATION UNTIL ALL EXISTING UTILITIES HAVE BEEN MARKED IN THE
FIELD BY THE APPLICABLE ENTITY RESPONSIBLE FOR THAT PARTICULAR UTILITY. THE CONTRACTOR
SHALL NOTIFY EACH APPLICABLE ENTITY AT LEAST 24 HOURS BEFORE STARTING WORK.

3.

UNDERGROUND SERVICE ALERT: CALL TOLL FREE (800) 642-2444 AT LEAST 48 HOURS PRIOR TO
EXCAVATION.

4.

CONTRACTOR SHALL UNCOVER EXISTING BURIED UTILITIES IN THE PRESENCE OF UTILITY OWNER TO
VERIFY LOCATIONS AND ELEVATIONS OF UTILITIES. BURIED UTILITIES INCLUDE, BUT ARE NOT LIMITED TO,
WATER MAINS AND SERVICES, SEWER MAINS AND LATERALS, STORM DRAINS, GAS MAINS AND LATERALS,
ELECTRICAL DISTRIBUTION LINES, TELEPHONE AND CABLE TV LINES. ALL UTILITIES CONFLICTING WITH
THE PROPOSED CONSTRUCTION SHALL BE RELOCATED OR RESOLVED PRIOR TO THE START OF
CONSTRUCTION, OR CONFLICTING FACILITIES

5.

ALL UNDERGROUND IMPROVEMENTS SHALL BE INSTALLED AND APPROVED PRIOR TO PAVING.

6.

ALL MATERIAL, WORKMANSHIP AND CONSTRUCTION DETAILS SHALL CONFORM TO THE TOWN OF
YOUNTVILLE CONSTRUCTION STANDARD SPECIFICATIONS, INCLUDING ALL ADDENDA, STANDARD PLAN
AND SPECIAL PROVISION REVISIONS.

IF CONSTRUCTION DEWATERING IS REQUIRED, THE TOWN SHALL EVALUATE REASONABLE OPTIONS FOR DEWATERING MANAGEMENT.
THE FOLLOWING MANAGEMENT OPTIONS SHALL BE CONSIDERED:

7.

ITEMS SPECIFIED ON THE STANDARD PLANS ARE APPROVED FOR USE BY THE TOWN OF YOUNTVILLE. ALL
SUBSTITUTES OR ALTERATIONS SHALL BE SUBMITTED TO THE TOWN OF YOUNTVILLE FOR REVIEW AND
APPROVAL.

1.
2.
3.

RECYCLED WATER SYSTEM

MITIGATION MEASURE HYD- 1: STORM WATER POLLUTION PREVENTION PLAN

THE CONTRACTOR SHALL IMPLEMENT THE FOLLOWING MEASURES TO AVOID IMPACTS TO CALIFORNIA RED-LEGGED FROGS (CRLF)
DURING CONSTRUCTION WITHIN 50 FEET OF THE AGRICULTURAL IRRIGATION PONDS:

THE CONTRACTOR SHALL OBTAIN COVERAGE UNDER SWRCB (STATE WATER RESOURCES CONTROL BOARD) ORDER NO. 2009-0009-DWQ,
WASTE DISCHARGE REQUIREMENTS FOR DISCHARGES OF STORM WATER RUNOFF ASSOCIATED WITH CONSTRUCTION AND LAND
DISTURBANCE ACTIVITIES.
THE CONTRACTOR SHALL SUBMIT PERMIT REGISTRATION DOCUMENTS (NOTICE OF INTENT, RISK,
ASSESSMENT, SITE MAPS, SWPPP, ANNUAL FEE, AND CERTIFICATIONS) TO THE STATE WATER RESOURCES CONTROL BOARD. THE
SWPPP SHALL ADDRESS POLLUTANT SOURCES, NON-STORM WATER DISCHARGES RESULTING FROM CONSTRUCTION DEWATERING,
BEST MANAGEMENT PRACTICES, AND OTHER REQUIREMENTS SPECIFIED IN THE ORDER. THE BMPS SHALL INCLUDE ANY MEASURES
INCLUDED IN THE EROSION AND SEDIMENT CONTROL PLANS DEVELOPED FOR THE PROJECT TO MINIMIZE DISTURBANCE AFTER
GRADING OR CONSTRUCTION. THE SWPPP SHALL ALSO INCLUDE DUST CONTROL PRACTICES TO PREVENT WIND EROSION, SEDIMENT
TRACKING AND DUST GENERATION BY CONSTRUCTION EQUIPMENT. THE CONTRACTOR SHALL ENSURE THAT A QUALIFIED SWPPP
PRACTITIONER OVERSEES IMPLEMENTATION OF THE SWPPP, INCLUDING VISUAL INSPECTIONS, SAMPLING AND ANALYSIS, AND
ENSURING OVERALL COMPLIANCE.

1.

MITIGATION MEASURE HYD- 2: CONSTRUCTION DEWATERING

7.

MITIGATION MEASURE BIO-1: AVOID IMPACTS TO CALIFORNIA RED-LEGGED FROG

GROUND DISTURBING CONSTRUCTION ACTIVITIES SHALL BE LIMITED TO THE DRY SEASON PERIOD FROM APRIL 1 THROUGH
NOVEMBER 1 TO AVOID POTENTIAL RED-LEGGED FROG DISPERSAL EVENTS.
A QUALIFIED BIOLOGIST, HIRED BY THE CONTRACTOR BUT APPROVED BY THE TOWN, SHALL CONDUCT A PRE-CONSTRUCTION
SURVEY IMMEDIATELY PRECEDING ANY CONSTRUCTION ACTIVITY WITHIN 50 FEET OF THE IRRIGATION PONDS. THE BIOLOGIST
SHALL REMAIN ON-SITE DURING GROUND DISTURBING CONSTRUCTION WITHIN 50 FEET OF A POND.
IF A CRLF IS ENCOUNTERED DURING CONSTRUCTION, ALL CONSTRUCTION ACTIVITIES IN THE IMMEDIATE AREA SHALL CEASE
UNTIL THE ANIMAL MOVES AWAY OF ITS OWN VOLITION. CONSTRUCTION CANNOT BEGIN UNTIL THE CRLF HAS LEFT THE
CONSTRUCTION AREA. IF CRLF DO NOT LEAVE THE SITE TO ALLOW FOR CONSTRUCTION, THE TOWN SHALL CONTACT USFWS FOR
DIRECTION ON HOW TO PROCEED.
PRIOR TO THE START OF CONSTRUCTION, A USFWS-APPROVED BIOLOGIST SHALL TRAIN ALL CONSTRUCTION PERSONNEL
REGARDING HABITAT SENSITIVITY, IDENTIFICATION OF SPECIAL STATUS SPECIES, AND REQUIRED PRACTICES BEFORE THE START
OF CONSTRUCTION.
BECAUSE DUSK AND DAWN ARE OFTEN THE TIMES WHEN CRLF ARE MOST ACTIVELY FORAGING AND DISPERSING, ALL
CONSTRUCTION ACTIVITIES SHALL CEASE ONE-HALF HOUR BEFORE SUNSET AND SHALL NOT BEGIN PRIOR TO ONE-HALF HOUR
BEFORE SUNRISE. ALL VEHICLE PARKING SHALL BE RESTRICTED TO PREVIOUSLY DETERMINED STAGING AREAS OR EXISTING
ROADS.
THE FUELING AND MAINTENANCE OF VEHICLES AND OTHER EQUIPMENT SHALL OCCUR AT LEAST 20 METERS (65 FEET) FROM ANY
RIPARIAN HABITAT OR WATER BODY.

2.

3.

4.

5.

6.

IF CONSTRUCTION IS SCHEDULED TO START BETWEEN JANUARY 31 AND OCTOBER 1, A QUALIFIED BIOLOGIST, HIRED BY THE
CONTRACTOR BUT APPROVED BY THE TOWN, SHALL CONDUCT PRECONSTRUCTION NESTING SURVEYS WITHIN 48 HOURS OF
CONSTRUCTION FOR NESTING PASSERINES (SMALL SONGBIRDS) AND RAPTORS. TREES WITHIN A 200-FOOT RADIUS SHALL BE INCLUDED
IN THE SURVEYS. IF ACTIVE NESTS ARE LOCATED IN THE WORK AREA, THE BIOLOGIST, IN CONSULTATION WITH CDFG, (CALIFORNIA
DEPARTMENT OF FISH AND GAME), SHALL ESTABLISH AN APPROPRIATELY SIZED BUFFER AROUND THE NEST IN WHICH NO WORK WILL
BE ALLOWED UNTIL THE YOUNG HAVE SUCCESSFULLY FLEDGED. A MINIMUM OF A 50-FOOT BUFFER ZONE SHALL BE PLACED AROUND
PASSERINE NESTS AND 250-FOOT BUFFERS SHALL BE PLACED AROUND RAPTOR NESTS. IF A QUALIFIED BIOLOGIST DETERMINES THAT
LESS OF A BUFFER ZONE IS ACCEPTABLE, THE SIZE OF THE BUFFER ZONE MAY BE REDUCED UPON APPROVAL BY CDFG.
BIO-3:

AVOID

OR RESTORE

JURISDICTIONAL

WETLANDS

AND WATERS

TEMPORARILY

AFFECTED

BY

THE CONTRACTOR SHALL IMPLEMENT AVOIDANCE AND MINIMIZATION MEASURES, INCLUDING BEST MANAGEMENT PRACTICES (BMPS),
TO PROTECT JURISDICTIONAL WETLANDS AND WATERS DURING CONSTRUCTION. MATERIALS AND FLUIDS GENERATED BY
CONSTRUCTION ACTIVITIES SHALL BE PLACED AT LEAST 25 FEET AWAY FROM WETLAND AREAS OR DRAINAGES UNTIL THEY CAN BE
DISPOSED OF AT A PERMITTED SITE. ALL WETLANDS AND WATERS AREAS LOCATED ADJACENT TO THE CONSTRUCTION ZONE THAT
COULD BE AFFECTED BY CONSTRUCTION ACTIVITIES SHALL BE TEMPORARILY FENCED OFF AND DESIGNATED AS ENVIRONMENTALLY
SENSITIVE AREAS TO PREVENT ACCIDENTAL INTRUSION BY WORKERS AND EQUIPMENT.

IF DISCHARGING TO THE SANITARY SEWER, THE TOWN SHALL ISSUE A ONE-TIME DISCHARGE PERMIT OR OTHER TYPE OF APPROVAL
REQUIRING, AS NECESSARY, MEASURES FOR CHARACTERIZING THE DISCHARGE AND ENSURING FILTERING METHODS AND MONITORING
TO VERIFY THAT THE DISCHARGE IS COMPLIANT WITH THE TOWN'S LOCAL WASTEWATER DISCHARGE REQUIREMENTS.
IF DISCHARGING TO A LOCAL SURFACE WATER OR STORM DRAIN, THE DISCHARGE SHALL BE MANAGED AS A NON-STORM WATER
DISCHARGE AND CONTROL MEASURES SHALL BE INCLUDED IN THE SWPPP PREPARED UNDER ORDER NO. 2009-0009-DWQ. THE
CONTRACTOR SHALL CHARACTERIZE THE GROUNDWATER PRIOR TO DISCHARGE AND IMPLEMENT CONTROL MEASURES, SUCH AS
SETTLING AND/OR FILTRATION TO ENSURE THAT EXCESSIVE SEDIMENT IS NOT DISCHARGED, AND MANAGE DISCHARGE RATES TO
PREVENT EROSION DOWNSTREAM.

1.
2.
3.

INSTALL PIPELINES WHEN WETLANDS AND STREAMS ARE DRY.
RESTORE ORIGINAL CONTOURS AND DRAINAGE PATTERNS, BOTH INTO AND OUT OF THE WETLAND.
SPREAD A COVER OF STRAW, RICE STRAW IF AVAILABLE, OVER DISTURBED SOILS AND WORK INTO SOIL. THIS PRACTICE SHALL
NOT BE IMPLEMENTED IN WETLAND SOILS.
APPLY AN ORGANICALLY BASED TACKIFIER ON DISTURBED AREAS TO REDUCE AIR AND WATER EROSION OF SOILS.
PLANTS SHALL BE INSTALLED, MAINTAINED AND REPLACED SUCH THAT 70 PERCENT OF THE DESIGN PLANT DENSITY IS PRESENT
ON THE FIVE-YEAR ANNIVERSARY OF PLANT INSTALLATION.

4.
5.

THERE SHALL BE A FIVE HOUR MAXIMUM SHUTDOWN TIME OF EXISTING MAINS WHILE MAKING
CONNECTION. TWENTY-FOUR HOUR NOTICE OF SHUTDOWN TO BE GIVEN TO TOWN AND ALL WATER
CUSTOMERS BY CONTRACTOR. EXISTING VALVES ARE TO BE OPERATED BY TOWN PERSONNEL ONLY. NO
WATER MAIN CONNECTIONS ARE PERMITTED ON FRIDAY OR ON ANY DAY PRECEDING A HOLIDAY.

2.

START EXCAVATION BY EXPOSING CONNECTION POINT TO EXISTING MAIN TO DETERMINE ITS LINE AND
GRADE. START NEW MAIN 8-10 FEET FROM AND ON SAME GRADE (AND LINE IF APPLICABLE) AS EXISTING
MAIN.

3.

ALL TRENCHING, BACKFILL AND RESURFACING REQUIRED FOR INSTALLATION OF RECYCLED WATER
SYSTEM FACILITIES SHALL BE PER TOWN OF YOUNTVILLE STANDARD DRAWINGS.
ONLY TOWN OF YOUNTVILLE PERSONNEL SHALL OPERATE VALVES ON EXISTING WATER MAINS OR WATER
SERVICES.

5.

ALL METER BOXES, VAULTS AND PITS SHALL BE BEDDED ON A 3" MINIMUM THICK, 3/4" DRAIN ROCK, CL ll
AB, OR OTHER CLEAN MATERIAL WITH SAND EQUIVALENT OF 20 MINIMUM, UNCONTAMINATED BY NATIVE
SOIL, AGAINST COMPACTED OR UNDISTURBED BASE. THE GRAVEL BED SHALL EXTEND TO A MINIMUM OF
4" BEYOND ALL SIDES OF THE METER BOX. BOX SHALL BE SET FLUSH WITH TOP OF CURB, SIDEWALK OR
GROUND, WHICHEVER IS APPLICABLE.

6.

BEFORE COMBUSTIBLE MATERIALS MAY BE STORED OR CONSTRUCTED ON SITE, THE FIRE DEPARTMENT
MUST APPROVE FIRE FLOW AND ACCESS.

7.

AFTER A STREET HAS BEEN PAVED, ALL WATER VALVE BOXES WILL BE MARKED IN WHITE PAINT BEFORE
THE CLOSE OF THAT WORK DAY.

MITIGATION MEASURE NOI-1: NOISE REDUCTION MEASURES
DURING PROJECT CONSTRUCTION, THE CONTRACTOR(S) SHALL IMPLEMENT THE FOLLOWING MEASURES SUCH THAT NOISE FROM
CONSTRUCTION DOES NOT EXCEED 70 DBA AT NOISE-SENSITIVE USES DURING DAYTIME HOURS.
1.
2.
3.

4.

5.
THE FOLLOWING MEASURES SHALL BE IMPLEMENTED WHERE CONSTRUCTION IMPACTS TO JURISDICTIONAL WATERS AND WETLANDS
CANNOT FEASIBLY BE AVOIDED. A WETLAND AND WATERS RESTORATION PLAN SHALL BE PREPARED PRIOR TO CONSTRUCTION. THE
RESTORATION SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING MEASURES:

1.

4.

MITIGATION MEASURE BIO-2: CONDUCT PRECONSTRUCTION NESTING SURVEYS FOR NESTING PASSERINES AND RAPTORS

MITIGATION MEASURE
CONSTRUCTION

REUSE THE WATER ON-SITE FOR DUST CONTROL, COMPACTION, OR IRRIGATION.
RETAIN THE WATER ON-SITE IN A GRASSY OR POROUS AREA TO ALLOW INFILTRATION/EVAPORATION.
DISCHARGE (BY PERMIT) TO A SANITARY SEWER OR SURFACE WATER (THIS OPTION MAY REQUIRE A TEMPORARY METHOD TO
FILTER SEDIMENT-LADEN WATER PRIOR TO DISCHARGE).

6.

CONSTRUCTION WORK HOURS ARE LIMITED TO MONDAY THROUGH FRIDAY 8 A.M. TO 5 P.M. AT THE PROJECT SITE AND 7:30 A.M. TO
4 P.M. AT THE TREATMENT PLANT.
USE QUIETEST AVAILABLE EQUIPMENT AND ELECTRICALLY-POWERED EQUIPMENT, RATHER THAN INTERNAL COMBUSTION
ENGINES WHERE FEASIBLE.
EQUIPMENT AND ON-SITE TRUCKS USED FOR PROJECT CONSTRUCTION SHALL UTILIZE THE BEST AVAILABLE NOISE CONTROL
TECHNIQUES (E.G., IMPROVED MUFFLERS, EQUIPMENT REDESIGN, USE OF INTAKE SILENCERS, DUCTS, ENGINE ENCLOSURES, AND
ACOUSTICALLY ATTENUATING SHIELDS OR SHROUDS, WHEREVER FEASIBLE). ALL CONSTRUCTION EQUIPMENT SHALL BE
INSPECTED AT PERIODIC INTERVALS TO ENSURE PROPER MAINTENANCE AND RESULTING LOWER NOISE LEVELS.
IMPACT TOOLS (E.G., JACK HAMMERS, PAVEMENT BREAKERS) USED FOR PROJECT CONSTRUCTION SHALL BE HYDRAULICALLY OR
ELECTRICALLY POWERED WHEREVER POSSIBLE TO AVOID NOISE ASSOCIATED WITH COMPRESSED-AIR EXHAUST FROM
PNEUMATICALLY POWERED TOOLS. AN EXHAUST MUFFLER ON THE COMPRESSED-AIR EXHAUST SHALL BE USED; THIS MUFFLER
CAN LOWER NOISE LEVELS FROM THE EXHAUST BY UP TO ABOUT 10 DBA. EXTERNAL JACKETS ON THE TOOLS THEMSELVES SHALL
BE USED WHERE FEASIBLE, WHICH COULD ACHIEVE A REDUCTION OF 5 DBA.
A PRECONSTRUCTION MEETING SHALL BE HELD BETWEEN THE JOB INSPECTORS AND THE CONTRACTOR/ON-SITE PROJECT
MANAGER TO CONFIRM THAT NOISE MITIGATION AND PRACTICES ARE COMPLETED PRIOR TO COMMENCEMENT OF CONSTRUCTION
(INCLUDING CONSTRUCTION HOURS, NEIGHBORHOOD NOTIFICATION, ETC.).
AN ON-SITE COMPLAINT AND ENFORCEMENT MANAGER SHALL BE POSTED TO RESPOND TO AND TRACK ANY NOISE COMPLAINTS.
THE MANAGER SHALL BE RESPONSIBLE FOR RESPONDING TO ANY COMPLAINTS REGARDING CONSTRUCTION NOISE AND FOR
COORDINATING WITH THE ADJACENT LAND USES. THE MANAGER SHALL DETERMINE THE CAUSE OF ANY COMPLAINTS AND
COORDINATE WITH THE CONSTRUCTION TEAM TO IMPLEMENT EFFECTIVE MEASURES (CONSIDERED TECHNICALLY AND
ECONOMICALLY FEASIBLE) WARRANTED TO CORRECT THE PROBLEM. THE TELEPHONE NUMBER OF THE ON-SITE COMPLAINT AND
ENFORCEMENT MANAGER SHALL BE POSTED AT THE CONSTRUCTION SITE AND PROVIDED TO NEIGHBORS IN A NOTIFICATION
LETTER. THE MANAGER SHALL BE TRAINED TO USE A SOUND LEVEL METER AND SHOULD BE AVAILABLE DURING ALL
CONSTRUCTION HOURS TO RESPOND TO COMPLAINTS.

MITIGATION MEASURE CR-4: TREATMENT OF ARCHAEOLOGICAL RESOURCES DISCOVERED DURING CONSTRUCTION
IF ARCHAEOLOGICAL MATERIALS ARE ENCOUNTERED DURING CONSTRUCTION ACTIVITIES, THE PIECE OF EQUIPMENT THAT
ENCOUNTERS THE MATERIALS MUST BE STOPPED, AND THE FIND INSPECTED BY A QUALIFIED ARCHAEOLOGIST, HIRED BY THE
CONTRACTOR BUT APPROVED BY THE TOWN, TO EVALUATE THE MATERIALS AND RECOMMEND APPROPRIATE TREATMENT.
PREHISTORIC ARCHAEOLOGICAL MATERIALS MIGHT INCLUDE OBSIDIAN AND CHERT FLAKED-STONE TOOLS (E.G., PROJECTILE POINTS,
KNIVES, SCRAPERS) OR TOOLMAKING DEBRIS; CULTURALLY DARKENED SOIL (“MIDDEN”) CONTAINING HEAT-AFFECTED ROCKS,
ARTIFACTS, OR SHELLFISH REMAINS; AND STONE MILLING EQUIPMENT (E.G., MORTARS, PESTLES, HANDSTONES, OR MILLING SLABS);
AND BATTERED STONE TOOLS, SUCH AS HAMMERSTONES AND PITTED STONES. HISTORIC PERIOD MATERIALS MIGHT INCLUDE STONE,
CONCRETE, OR ADOBE FOOTINGS AND WALLS; FILLED WELLS OR PRIVIES; AND DEPOSITS OF METAL, GLASS, AND/OR CERAMIC REFUSE.

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

25 November 2013 - 1:32 PM

Plotted by: Ben Langston

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 G-004.dwg

BL

Designer MJ

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

NONE

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

G-004

Sht

4

of

50
GENERAL NOTES
1.

2.

154' RE-SEED DISTURBED AREA

CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS
PRIOR TO CONSTRUCTION. (GAS AND IRRIGATION)

4.

96

CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF
VINEYARD UTILITIES, GASLINES AND IRRIGATION WITHIN PROPOSED
ALIGNMENT PRIOR TO CONSTRUCTION.

3.

96

CONTRACTOR SHALL FIELD VERIFY LOCATION AND DEPTH OF EXISTING
RECYCLED WATER MAIN FOR CONNECTION WITH NEW MAIN.

CONTRACTOR TO FIELD VERIFY EXISTING GASLINE LOCATION PRIOR TO
CONSTRUCTION.

508' ASPHALT REPLACEMENT

STA. 29+03
GRADE BREAK
8" 22.5° BEND

STA. 28+04
8" 11.25° BEND
STA. 28+20
GRADE BREAK
8" 22.5° BEND

STA. 27+92

STA. 27+66
8" 11.25° BEND

STA. 27+46
8" 45° BEND

STA. 26+93
8" 90° BEND

88

STA. 26+41
8" GATE VALVE

92

STA. 26+38
EX. 8" RW

92

88

DEMOLITION
SAWCUT, REMOVE AND DISPOSE ASPHALT CONCRETE
(APPROXIMATELY 3" THICK)

80

POSITIVE SLOPE
8" PVC C-900 RW LINE
S
IVE
SIT
PO

76

80

ELEVATION

84

3' MIN
COVER

84

3.36'

ELEVATION

(E) GROUND

2034 SF
450 SF

REMOVE AND REPLACE RIPRAP IN KIND PER DTL 4, SHEET C-505

E
LOP

CONSTRUCTION
CONNECT TO EXISTING RECYCLED WATERLINE PER
DTL. 1, SHEET C-505.

76

POSITIVE SLOPE
8" PVC C-900 RW LINE

1 EA

INSTALL 8" C900 CLASS 150 PVC RECLAIMED WATERLINE
INSTALL 8" GATE VALVE, BOX AND COVER PER DTL 4, SHEET C-503

72

72

672 LF
1 EA

INSTALL ASPHALT REPLACEMENT PER DTL 2 SHEET C-503
RE-SEED DISTURBED AREA PER SPECIFICATIONS, 16' WIDTH

68
26+00

27+00

28+00

29+00

31+00

30+00

226 SY
274 SY

68
33+00

32+00

PARCEL LINE (TYP.)
EDGE OF ROAD (TYP.)
27

28+00

LAND LANE

E
00'42"
N30° 4'
37.9

E
'52"
°57 0'
6
N1 0.0
2

12'00
"W
27+00 53.34'

N59°1
8'00"E
54.83
'

N42°48'00"E
40.00'

30+00

8" PVC

31+00

8" PVC

32+00

19'
4'

26
25

15' WIDE TEMP.
CONSTRUCTION
EASEMENT

EDGE OF
VINEYARD (TYP.)

24

N 29 °

26+38

8" PVC

N44°57'41"E
573.00' 29+00

GASLINE - APPROXIMATE
LOCATION

MATCHLINE STA 33+00
SEE DRAWING C-103

RECYCLED WATERLINE PROFILE - BERINGER

CONTROL POINTS
POINT #

NORTHING

EASTING

DESCRIPTION

21

1907538.98

6461319.99

APPROX. CONNECT TO EX. 8" RW

22

1907540.80

6461323.00

VALVE

23

1907566.97

6461367.13

8" 90° BEND

24

1907613.54

6461341.12

8" 45° BEND

25

1907632.10

6461346.77

8" 11.25° BEND

26

1907665.52

6461365.92

8" 11.25° BEND

27

1907694.87

6461393.10

8" DEFLECTION

22
21

23

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

HORIZONTAL 1"=40' 0
AT ORIGINAL SIZE

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

6 December 2013 - 6:35 PM

Plotted by: Aaron Foscato

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-101 to C-107.dwg

RS

40'

60'

80'

VERTICAL 1"=4'
AT ORIGINAL SIZE

RECYCLED WATERLINE PLAN - BERINGER

20'
2'

4'

6'

8'

Designer MJ

0

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-102

Sht

7

of

50
GENERAL NOTES
1.

2.

CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS
PRIOR TO CONSTRUCTION.

3.

96

CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF
VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO
CONSTRUCTION.

CONTRACTOR TO FIELD VERIFY EXISTING GASLINE LOCATION PRIOR TO
CONSTRUCTION.

96
650' ASPHALT REPLACEMENT

92

92

88

88

DEMOLITION

(E) GROUND

84

80

80

POSITIVE SLOPE

2600 SF

ELEVATION

84
3' MIN
COVER

ELEVATION

SAWCUT, REMOVE AND DISPOSE ASPHALT CONCRETE
(APPROXIMATELY 3" THICK)

8" PVC C-900 RW LINE

CONSTRUCTION
76

76

289 SY

72

68

650 LF

INSTALL ASPHALT REPLACEMENT PER DTL 2 SHEET C-503

72

INSTALL 8" C900 CLASS 150 PVC RECLAIMED WATERLINE

68
39+50

33+00

34+00

35+00

36+00

38+00

37+00

39+00

RECYCLED WATERLINE PROFILE - BERINGER

8" PVC

35+00

34+00

36+00

8" PVC

15' WIDE TEMP.
CONSTRUCTION
EASEMENT

EDGE OF
VINEYARD (TYP.)

LAND LANE
GASLINE - APPROXIMATE
LOCATION

37+00

8" PVC

38+00

39+00

8" PVC

EDGE OF ROAD (TYP.)

MATCHLINE STA 39+50
SEE DRAWING C-104

PARCEL LINE (TYP.)

19'

MATCHLINE STA 33+00
SEE DRAWING C-102

CONTROL POINTS

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

HORIZONTAL 1"=40' 0
AT ORIGINAL SIZE

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

6 December 2013 - 6:38 PM

Plotted by: Aaron Foscato

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-101 to C-107.dwg

RS

40'

60'

80'

VERTICAL 1"=4'
AT ORIGINAL SIZE

RECYCLED WATERLINE PLAN - BERINGER

20'
2'

4'

6'

8'

Designer MJ

0

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-103

Sht

7

of

50
GENERAL NOTES
1.

4.

STA. 41+33
8" 22.5° BEND

CONTRACTOR TO FIELD VERIFY EXISTING GASLINE LOCATION PRIOR TO
CONSTRUCTION.

88

SAWCUT, REMOVE AND DISPOSE ASPHALT CONCRETE
(APPROXIMATELY 3" THICK)

(E) GROUND

84

84

80

DEMOLITION

POSITIVE SLOPE

80

ELEVATION

STA. 40+95
EXISTING WATERLINE
APPROX. LOCATION
STA. 41+05
8" 22.5° BEND

STA. 40+72
8" GATE VALVE
STA. 40+75

STA. 40+69
8" 90° BEND

TRIM EXISTING TREES AND BUSHES AS NEEDED UNDER THE DIRECTION
OF A LICENSED ARBORIST.

92

3' MIN
COVER

ELEVATION

88

CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS
PRIOR TO CONSTRUCTION.

96

775' RE-SEED
DISTURBED AREA

125' ASPHALT REPLACEMENT

92

2.

3.

96

CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF
VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO
CONSTRUCTION.

504 SF
15 LF

REMOVE AND DISPOSE EXISTING WIRE FENCE
REMOVE AND REPLACE VEGETATION AND IRRIGATION
LINES IN KIND AS NEEDED.

1 LS

8" PVC C-900 RW LINE

CONSTRUCTION
76

76

INSTALL 8" C900 CLASS 150 PVC RECLAIMED WATERLINE

900 LF

INSTALL 8" GATE VALVE, BOX AND COVER PER DTL 4, SHEET C-503

56 SY

INSTALL ASPHALT REPLACEMENT PER DTL 2 SHEET C-503

72

72

1 EA

1378 SY

RE-SEED DISTURBED AREA PER SPECIFICATIONS, 16' WIDTH

15 LF

REPLACE WIRE FENCE IN KIND

68

68

39+50

40+00

41+00

42+00

44+00

43+00

45+00

46+00

47+00

48+00

48+50

RECYCLED WATERLINE PROFILE - BERINGER
CONTROL POINTS
POINT #

RW
RW

EDGE OF VINEYARD
ROAD (TYP.)

N44°54'24"E
651.85'

42+00

8"W
35'1
64° .62'
N43°35'36"W N 27
36.01'

43+00

44+00

8" PVC

8" PVC

45+00

46+00

47+00

8" PVC

7'

9.5

15' WIDE TEMP.
CONSTRUCTION
EASEMENT

6'

SOIL BORING (TYP.)

31

48+00

B7

6'

RW

N40°09'18"W
1337.64'

RW

PARCEL LINE (TYP.)

MATCHLINE STA 48+50
SEE C-105

40+00

EDGE OF
VINEYARD (TYP.)

30

RW

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC

1/7/14

100% SUBMITTAL

5/24/13

Note: * indicates signatures on original issue of drawing or last revision of drawing
Plotted by: Aaron Foscato

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-101 to C-107.dwg

RS

20'

40'

60'

6462256.27

VALVE

1908588.08

6462233.34

8" 22.5° BEND

1908599.93

6462208.39

8" 22.5° BEND

80'

VERTICAL 1"=4'
AT ORIGINAL SIZE

RECYCLED WATERLINE PLAN - BERINGER

6 December 2013 - 6:40 PM

1908564.24

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

HORIZONTAL 1"=40' 0
AT ORIGINAL SIZE

Plot Date:

8" 90° BEND

15' WIDE TEMP.
CONSTRUCTION
EASEMENT

32

Revision

6462258.17

32

41+00

No

1908561.99

31

EDGE OF
ROAD (TYP.)

DESCRIPTION

30

29

EASTING

29

SEE C-103
MATCHLINE STA 39+50

NORTHING

2'

4'

6'

8'

Designer MJ

0

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-104

Sht

8

of

50
GENERAL NOTES
1.

2.

96

CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS
PRIOR TO CONSTRUCTION.

96

STA. 54+70
8" 90° BEND

STA. 54+74
8" GATE VALVE
STA. 54+84

900' RE-SEED DISTURBED AREA

92

92

88
(E) GROUND

84
3' MIN
COVER

84

POSITIVE SLOPE

8" PVC C-900 RW LINE

80

DEMOLITION
ELEVATION

88

ELEVATION

CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF
VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO
CONSTRUCTION.

80

CONSTRUCTION
76

76

INSTALL 8" C900 CLASS 150 PVC RECLAIMED WATERLINE

900 LF

INSTALL 8" GATE VALVE, BOX AND COVER PER DTL 4, SHEET C-503

72
48+50

50+00

51+00

52+00

53+00

54+00

55+00

56+00

57+00

1600 SY

RE-SEED DISTURBED AREA PER SPECIFICATIONS, 16' WIDTH

72
49+00

1 EA

57+50

EDGE OF VINEYARD
ROAD (TYP.)

CONTROL POINTS
POINT #

50+00

51+00

52+00

8" PVC

53+00

6'

15' WIDE TEMP. CONSTRUCTION
EASEMENT (TYP.)

34

PARCEL LINE (TYP.)

36

DESCRIPTION

1909148.14

6461745.86

PVC RW LINE

1909622.29

6461345.81

8" 90° BEND

36

B6

EASTING

35

54+00

N40°09'18"W
1337.64'

13.5'

6'

8" PVC

5.5'

49+00

NORTHING

34

35

1909624.50

6461348.04

VALVE

55+00

SEE C-104
MATCHLINE STA 48+50

RECYCLED WATERLINE PROFILE - BERINGER

EDGE OF
VINEYARD (TYP.)

N45°18'29"E
917.44'

56+00
8" PVC

57+00

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

RECYCLED WATERLINE PLAN - BERINGER
Reuse of Documents

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

5 December 2013 - 1:57 PM

Plotted by: Ben Langston

Drawn

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-101 to C-107.dwg

RS

20'

40'

60'

80'

VERTICAL 1"=4'
AT ORIGINAL SIZE

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

Job
Project
Manager Director

HORIZONTAL 1"=40' 0
AT ORIGINAL SIZE

MATCHLINE STA 57+50
SEE C-106

2'

4'

6'

8'

Designer MJ

0

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-105

Sht

9

of

50
GENERAL NOTES
1.

CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF
VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO
CONSTRUCTION.

3.

CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS
PRIOR TO CONSTRUCTION.

STA. 64+02

STA. 63+91
8" GATE VALVE

STA. 63+88
8" 90° BEND

348' ASPHALT REPLACEMENT

92

92

88

3' MIN
COVER

3' MIN
COVER

(E) GROUND

84

84

POSITIVE SLOPE

POSITIVE SLOPE

ELEVATION

88

ELEVATION

CONTRACTOR SHALL FIELD VERIFY LOCATION AND DEPTH OF EXISTING
RECYCLED WATER MAIN FOR CONNECTION WITH NEW MAIN..

2.

652' RE-SEED DISTURBED AREA

DEMOLITION
SAWCUT, REMOVE AND DISPOSE ASPHALT CONCRETE
(APPROXIMATELY 3" THICK)

1392 SF

8" PVC C-900 RW LINE

80

80

76

76

57+50

58+00

59+00

60+00

61+00

62+00

63+00

64+00

65+00

66+00

67+00

CONSTRUCTION

67+50

INSTALL 8" C900 CLASS 150 PVC RECLAIMED WATERLINE

RECYCLED WATERLINE PROFILE - BERINGER

1000 LF

INSTALL 8" GATE VALVE, BOX AND COVER PER DTL 4, SHEET C-503

SEE C-107
MATCHLINE STA 67+50

1 EA
155 SY

INSTALL ASPHALT REPLACEMENT PER DTL 2 SHEET C-503

1159 SY

67+00 8" PVC

RE-SEED DISTURBED AREA PER SPECIFICATIONS, 16' WIDTH

N44°42'35"W
665.48'

CONTROL POINTS
POINT #

DESCRIPTION

1910267.52

6461998.01

8" 90° BEND

38

1910269.19

6461996.36

VALVE

SEE C-105
MATCHLINE STA 57+50

8" PVC

65+00

66+00

EASTING

37

PARCEL LINE (TYP.)

NORTHING

15' WIDE TEMP. CONSTRUCTION
EASEMENT

B5
EDGE OF VINEYARD
ROAD (TYP.)

58+00

8" PVC

60+00

59+00

N45°18'29"E
917.44'

61+00

62+00

8" PVC

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

38

63+00
64+00

37

15' WIDE TEMP. CONSTRUCTION
EASEMENT
HORIZONTAL 1"=40' 0
AT ORIGINAL SIZE

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

6 December 2013 - 6:43 PM

Plotted by: Aaron Foscato

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-101 to C-107.dwg

RS

40'

60'

80'

VERTICAL 1"=4'
AT ORIGINAL SIZE

RECYCLED WATERLINE PLAN - BERINGER

20'
2'

4'

6'

8'

Designer MJ

0

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-106

Sht

10

of

50
100

STA. 78+18
8" 90° BEND (2)

96

ELEVATION

STA. 77+63
8" 90° BEND

STA. 75+51
8" 90° BEND

STA. 70+53
8" 90° BEND

92
(E) GROUND

(E) GROUND
3' MIN
COVER

ELEVATION

96

92

104

266' 3/8" MINUS ROAD MIX GRAVEL REPLACEMENT

STA. 78+10
METERING
VALVE VAULT

801' ASPHALT REPLACEMENT

STA. 78+64

100

STA. 78+43

STA. 78+32
8" 45° BEND
STA. 78+36
8" 45° BEND

104

STA. 78+66
8" 22.5° BEND
PIPE DISCHARGE
DET. 2, SHT. C-501

21' 3/8" MINUS ROAD MIX GRAVEL REPLACEMENT

3' MIN
COVER

3' MIN
COVER

88

POSITIVE SLOPE

88

8" PVC C-900 RW LINE

84

84

6" PVC RW TO
6" DIP. RW

POSITIVE SLOPE

8" PVC C-900 RW LINE

80

80

67+50

68+00

69+00

70+00

71+00

72+00

73+00

74+00

75+00

76+00

77+00

78+00

79+00

79+50

RECYCLED WATERLINE PROFILE - BERINGER
GENERAL NOTES
1.

2.

CONTROL POINTS
NORTHING

EASTING

DESCRIPTION

39

1910740.46

6461529.84

8" 90° BEND

40

1911090.08

6461884.66

8" 90° BEND

41

1911241.13

6461735.82

8" 90° BEND

42

1911209.53

6461703.46

METER

43

1911160.51

6461654.30

8" DISCHARGE

42

BERINGER POND
78+78

8" DIP

N45°19'03"E
107.18'

CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS
PRIOR TO CONSTRUCTION.

41

DEMOLITION

78+00

SAWCUT, REMOVE AND DISPOSE ASPHALT CONCRETE
(APPROXIMATELY 3" THICK)

3204 SF

43
20 LF

REMOVE AND DISPOSE EXISTING FENCE

8" PVC

PARCEL LINE (TYP.)

CONSTRUCTION
INSTALL 6' HIGH CHAIN LINK FENCE SEE DTL. 2 SHEET C-505

77+00

EDGE OF VINEYARD
ROAD (TYP.)

20 LF

70+00

N44°42'35"W
665.48'

15' WIDE TEMP. CONSTRUCTION
EASEMENT

N44°34'39"W
212.05'

69+00

72+00

N45°25'21"E
498.13'

15' WIDE TEMP.
CONSTRUCTION EASEMENT

1 EA
1 EA

PARCEL LINE (TYP.)

1072 LF

POND LEVEL MONITOR, INSTALL PER DTL 2, SHEET C-502

1 EA

EQUIPMENT MOUNTING RACK. SEE DTL 1, SHEET E-506
EDGE OF VINEYARD
ROAD (TYP.)

INSTALL 8" C900 CLASS 150 PVC RECLAIMED WATERLINE

1 EA

POLE MOUNTED SCADA ANTENNA, SEE DTL 2, SHEET I-102 (NPI)

76+00

8" PVC

SEE LEFT
MATCHLINE STA 72+50

68+00

INSTALL METERING VALVE ASSEMBLY AND VAULT PER DTL 6,
SHEET C-502
DISCHARGE INTO POND PER DTL 2, SHEET C-501

39

8" PVC 71+00

SEE C-106
MATCHLINE STA 67+50

POINT #

25' WIDE TEMP. CONSTRUCTION
EASEMENT (TYP.)

CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF
VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO
CONSTRUCTION.

1 EA

INSTALL 1" CONDUIT FROM METERING VALVE TO CONTROL PANEL

8" PVC

73+00

74+00

N45°25'21"E
498.13'

75+00

15' WIDE TEMP. CONSTRUCTION
EASEMENT (TYP.)

INSTALL 1" CONDUIT FROM POND LEVEL JUNCTION BOX TO SCADA
CONTROL PANEL

8" PVC

60 LF
60 LF
1 EA

SCADA PANEL INSTALLATION. SEE DTL 3 ON SHEET E-506 (NPI)
LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

40

B4

356 SY

INSTALL ASPHALT REPLACEMENT PER DTL 2 SHEET C-503

37 SY

RE-SEED DISTURBED AREA PER SPECIFICATIONS, 16' WIDTH

1 EA

CROSSING PCC PAD REFER TO DTL 3, SHEET C-501
INSTALL 1/2" MINUS ROAD MIX GRAVEL (2" THICK) ENTIRE
WIDTH OF ROAD

HORIZONTAL 1"=40' 0
AT ORIGINAL SIZE

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

6 December 2013 - 6:44 PM

Plotted by: Aaron Foscato

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-101 to C-107.dwg

BL

40'

60'

80'

VERTICAL 1"=4'
AT ORIGINAL SIZE

MATCHLINE STA 72+50
SEE RIGHT

RECYCLED WATERLINE PLAN - BERINGER

20'
2'

4'

6'

510 SY
56 LF

INSTALL 8" CLASS 350 DIP FOR RECLAIMED WATER

8'

Designer MJ

0

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-107

Sht

11

of

50
STA. 10+03
EX. GATE VALVE

GENERAL NOTES

STA. 11+85

STA. 10+97

STA. 10+79

108

104

CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF
VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO
CONSTRUCTION.

3.

108

CONTRACTOR SHALL FIELD VERIFY LOCATION AND DEPTH OF EXISTING
RECYCLED WATER MAIN FOR CONNECTION WITH NEW MAIN..

2.

112

STA. 10+45
6" 45° BEND

STA. 10+26
6" 45° BEND

STA. 10+05
EX. 6" RW

STA. 10+00
EX. 6" TEE

1.

CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS
PRIOR TO CONSTRUCTION.

4.

112

CONTRACTOR SHALL REMOVE AND RETURN TO OWNER THE TEMPORARY
RW SERVICE.

104

DEMOLITION

92

ELEVATION

STA. 11+85
6" PIPE DISCHARGE
DET. 2 SHT. C-501

STA. 11+30
6" PVC RW TO
6" DIP. RW

92

STA. 11+22
METERING VALVE
VAULT

96

STA. 11+04
6" 45° BEND

96

REMOVE AND RETURN TO OWNER EXISTING 6" RECYCLED
WATER LINE

100

STA. 10+65
6" 45° BEND

ELEVATION

100

143 LF

CONSTRUCTION
CONNECT TO EXISTING RECYCLED WATERLINE PER
DTL. 1, SHEET C-505.

1 EA

INSTALL 6" C-900 CLASS 150 PVC RECLAIMED WATERLINE

130 LF

INSTALL METERING VALVE ASSEMBLY AND VAULT PER DTL 6,
SHEET C-502

84

2' MIN
COVER

1 EA

POLE W/SCADA PANEL, ANTENNA, AND SOLAR POWER SOURCE, SEE
DTL 1 SHEET I-102 (NPI)

(E) GROUND

84

1 EA

POND LEVEL MONITOR, INSTALL PER DTL 2, SHEET C-502

88

1 EA

DISCHARGE INTO POND PER DTL 2, SHEET C-501

88

1 EA

INSTALL 1" CONDUIT FROM METERING VALVE TO CONTROL PANEL
POSITIVE
SLOPE

80

INSTALL 1" CONDUIT FROM POND LEVEL JUNCTION BOX TO SCADA
CONTROL PANEL

80
6" PVC C-900 RW LINE

95 LF
45 LF
1 EA

SCADA PANEL INSTALLATION. SEE DTL 2 ON SHEET E-507 (NPI)

9+50

10+00

290 SY

RE-SEED DISTURBED AREA PER SPECIFICATIONS, 16' WIDTH

12+00

11+00

INSTALL 1/2" MINUS ROAD MIX GRAVEL (2" THICK) ENTIRE
WIDTH OF ROAD

EDGE OF VINEYARD
ROAD (TYP.)

32 SY

INSTALL 6" CLASS 350 DIP FOR RECLAIMED WATER

RECYCLED WATERLINE PROFILE - MONDAVI

55 LF

CONTROL POINTS
POINT #

NORTHING

EASTING

DESCRIPTION

44

1904991.69

6465137.91

APPROX. CONNECT TO EX. 6" RW

45

1904961.92

6465080.55

6" 45° BEND

46

1904978.14

6465029.33

6" 45° BEND

47

1904976.31

6465025.79

METER

48

1904953.79

6464982.41

6" DISCHARGE

MONDAVI POND
44
64.63'

6" PVC

S62°34'19"W

11
+0
0

45° BEND

C
PV
6"

3'
.7 1"W
53 5'4
2
2°
N7

10+00

45

48

52.86'
S62°34'19"W

11+67

47
TEMP. CONSTRUCTION
EASEMENT (TYP.)

45° BEND

46

HORIZONTAL 1"=40' 0
AT ORIGINAL SIZE

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

25 November 2013 - 1:36 PM

Plotted by: Ben Langston

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-108.dwg

BL/MC

40'

60'

80'

VERTICAL 1"=4'
AT ORIGINAL SIZE

RECYCLE WATERLINE PLAN - MONDAVI

20'
2'

4'

6'

8'

Designer MJ

0

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-108

Sht

12

of

50
GENERAL NOTES
1.

2.

CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS
PRIOR TO CONSTRUCTION.

3.

N

CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF
VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO
CONSTRUCTION.

CONTRACTOR SHALL VERIFY AVAILABILITY OF POWER FOR METERING
VALVE AND CONTROL PANEL. CONTRACTOR SHALL PROVIDE NEW SOLAR
POWER SOURCE PER DET. 1, SHEET I-103 AS NECESSARY.

DEMOLITION
SEE GENERAL NOTE 3.

49

REMOVE AND SALVAGE EXISTING METER AND VAULT

1 EA

10' WIDE TEMP.
CONSTRUCTION
EASEMENT (TYP.)

10' WIDE TEMP.
CONSTRUCTION
EASEMENT (TYP.)

CONSTRUCTION
SI L
OT
AD
IL
RA
A

N
OW TIO
' R OCA
35 . L
X
RO
PP

AP

1 EA

EQUIPMENT MOUNTING RACK. SEE DTL 1, SHEET E-506

1 EA

POLE MOUNTED SCADA ANTENNA, SEE DTL 2, SHEET I-102 (NPI)

N
OW TIO
2' R OCA
4
.L
OX
PR

1 EA

POND LEVEL MONITOR, INSTALL PER DTL 2, SHEET C-502

R
VE

INSTALL METERING VALVE ASSEMBLY AND VAULT PER DTL 6,
SHEET C-502

1 EA

INSTALL 1" CONDUIT FROM METERING VALVE TO CONTROL PANEL
INSTALL 1" CONDUIT FROM POND LEVEL JUNCTION BOX TO SCADA
CONTROL PANEL
0

CHIMNEY ROCK POND IMPROVEMENTS

15

30

45

60'

362 LF
95 LF

POLE W/SCADA PANEL AND ANTENNA, SEE DTL 4 ON SHEET I-102 (NPI)
SCADA PANEL INSTALLATION. SEE DTL 4, SHEET E-507 (NPI)

SCALE 1"=30' AT ORIGINAL SIZE

1 EA
1 EA

RE-SEED DISTURBED AREA PER SPECIFICATIONS, 10' WIDTH
INSTALL RTU CABINET. SEE DETAILS 3 & 4, SHEET E-507 (NPI)

N

1 LS

CONNECT TO EXISTING 120V PANELBOARD. PROVIDE NEW
BREAKER AS NECESSARY

N

507 SY

1 LS

CONTROL POINTS
POINT #

DESCRIPTION

1902672.89

6471416.04

METER

SI L

10' WIDE TEMP.
CONSTRUCTION
EASEMENT (TYP.)

EASTING

49

CHIMNEY ROCK

NORTHING

R
VE
OT
AD
IL
RA

SEE LEFT

SEE ABOVE

SITE MAP

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

CHIMNEY ROCK POND
0

CHIMNEY ROCK POND IMPROVEMENTS

15

30

45

60'

SCALE 1"=30' AT ORIGINAL SIZE

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

25 November 2013 - 1:52 PM

Plotted by: Ben Langston

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-109.dwg

200

300

400'

SCALE 1"=200' AT ORIGINAL SIZE

Reuse of Documents

FINAL TOWN REVIEW NFC

100

0

BL/MC

Designer MJ

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-109

Sht

13

of

50
GENERAL NOTES
1.

CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF
VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO
CONSTRUCTION.

2.

CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS
PRIOR TO CONSTRUCTION.

DEMOLITION

SILVERADO TRAIL

REMOVE AND SALVAGE EXISTING METER AND VAULT

1 EA

CONSTRUCTION
INSTALL METERING VALVE ASSEMBLY AND VAULT PER DTL 6,
SHEET C-502
POND LEVEL MONITOR, INSTALL PER DTL 2, SHEET C-502

1 EA

EQUIPMENT MOUNTING RACK. SEE DTL 1, SHEET E-506

1 EA

POLE MOUNTED SCADA ANTENNA, SEE DTL 2, SHEET I-102 (NPI)

CLOS DU VAL/REGUSCI POND

1 EA

1 EA

INSTALL 1" CONDUIT FROM METERING VALVE TO CONTROL PANEL

345 LF

INSTALL 1" CONDUIT FROM POND LEVEL JUNCTION BOX TO SCADA
CONTROL PANEL

40 LF
1 EA

SCADA PANEL INSTALLATION. SEE DTL 2 ON SHEET E-506 (NPI)

428 SY

EX. 6" PVC

RE-SEED DISTURBED AREA PER SPECIFICATIONS, 10' WIDTH

CONTROL POINTS
POINT #

NORTHING

EASTING

DESCRIPTION

50

1905056.06

6469820.50

METER

50

25' WIDE TEMP. CONSTRUCTION
EASEMENT (TYP.)
35'ROW
APPROX. LOCATION

42'ROW
APPROX. LOCATION

25' WIDE TEMP. CONSTRUCTION
EASEMENT (TYP.)

10' WIDE TEMP. CONSTRUCTION
EASEMENT (TYP.)

20

0

CLOS DU VAL/REGUSCI POND IMPROVEMENTS

40

60

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

80'

SCALE 1"=40' AT ORIGINAL SIZE

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

25 November 2013 - 2:04 PM

Plotted by: Ben Langston

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-110.dwg

BL/MC

Designer MJ

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-110

Sht

14

of

50
GENERAL NOTES
1.

CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF
VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO
CONSTRUCTION.

2.

CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS
PRIOR TO CONSTRUCTION.

3.

CONTRACTOR TO VERIFY PIPE SIZE AND MATERIAL IN THE FIELD.

4.

EXISTING GATE VALVES AT DEMOLITION KEYNOTE 8 ARE ABOVE GROUND
AT THIS LOCATION.

10' WIDE TEMP. CONSTRUCTION
EASEMENT

DEMOLITION
STAG'S LEAP WINE CELLARS POND
REMOVE AND SALVAGE EXISTING GATE VALVE.

2 EA

REMOVE AND SALVAGE EXISTING METER AND VAULT

1 EA

CONSTRUCTION
INSTALL METERING VALVE ASSEMBLY AND VAULT PER DTL 6,
SHEET C-502
POND LEVEL MONITOR, INSTALL PER DTL 2, SHEET C-502

1 EA

POLE MOUNTED SCADA ANTENNA, SEE DTL 2, SHEET I-102 (NPI)

1 EA

INSTALL 1" CONDUIT FROM METERING VALVE TO CONTROL PANEL

8 LF

INSTALL 1" CONDUIT FROM POND LEVEL JUNCTION BOX TO SCADA
CONTROL PANEL
20'x20' TEMP. CONSTRUCTION
EASEMENT

1 EA

POLE W/SCADA PANEL, ANTENNA, AND SOLAR POWER SOURCE, SEE
DTL 1 SHEET I-102 (NPI)

20'x20' TEMP. CONSTRUCTION
EASEMENT

1 EA

20 LF

SCADA PANEL INSTALLATION. SEE DTL 5 ON SHEET E-506 AND DTL 5
ON SHEET E-506 (NPI)

1 EA
156 SY

RE-SEED DISTURBED AREA PER SPECIFICATIONS, 10' WIDTH

STAG'S LEAP WINE CELLARS POND IMPROVEMENTS

CAP END OF TEE AND EXISTING PIPE
CONNECT EXISTING PIPES ONCE GATE VALVE HAS BEEN REMOVED

STAG'S LEAP
WINE CELLARS

2 EA
1 EA

SEE LEFT

CONTROL POINTS
POINT #

NORTHING

EASTING

DESCRIPTION

51

1906025.79

6469185.36

METER

51
20'x20' TEMP. CONSTRUCTION
EASEMENT

SILVE
T
RADO

T
RADO

RAIL

SILVE
RAIL

W
35' RO TION
A
X. LOC
APPRO

W
42' RO
ATION
X. LOC
PR O
AP

EX. 6"
PVC

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

SEE LEFT

STAG'S LEAP WINE CELLARS POND IMPROVEMENTS

0

15

30

45

60'

0

SITE MAP

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

6 December 2013 - 6:30 PM

Plotted by: Aaron Foscato

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-111.dwg

200

300

400'

SCALE 1"=200' AT ORIGINAL SIZE

SCALE 1"=30' AT ORIGINAL SIZE

FINAL TOWN REVIEW NFC

100

BL/MC

Designer MJ

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-111

Sht

15

of

50
GENERAL NOTES

LE

M

SETTLING
VAULTS

UTILITY BUILDING

DEMOLITION
REMOVE AND DISPOSE EXISTING BARB WIRE FENCE FROM LOCATION
"A" TO LOCATION "B"
LE

330 LF

20'x40' CONTRACTOR
OFFICE TRAILER LOCATION

FILTRATION

CONSTRUCTION

PANELBOARD B TO OPERATOR
1- 3/4" BURIED CONDUIT
W/ 2- #12 AND 1- #12 G

INSTALL 6' HIGH CHAIN LINK FENCE SEE DTL. 2 SHEET C-505

PANELBOARD B

350 LF

INSTALL 8-FIBER CABLE FROM MASTER RTU TO RTU R, FREE OF
SPLICES IN EXISTING CONDUIT (NPI)

AERATOR

653 LF

INSTALL CARD READER PEDESTAL AND CONDUIT TO
ACCESS CONTROL UNIT PER DETAILS 1-5, SHEET C-507

OPERATOR TO
PEDESTAL
1 - 3/4" BURIED
CONDUIT SPARE

1 LS

PROVIDE GATE OPERATOR PER DET 2 ON C-506

CONTROL BUILDING

1 LS

195 LF

INSTALL 2 - 3/4" CONDUITS. SEE DETAILS 6 & 7,
SHEET E-507 AND DETAILS 1 ,2 & 3, SHEET E-508.
ACCESS CONTROL UNIT FOR CCTV CAMERA AND GATE
OPERATOR CONTROL PROVIDED AND INSTALLED BY OTHERS

CONTRACTOR PARKING
AND LAYDOWN AREA

NPI

INSTALL AMERISTAR PASSPORT COMMERCIAL ROLL GATE PER
DETAILS 1-4, SHEET C-506.
SEE DRAWING C-115
FOR DETAIL IN THIS AREA

INSTALL 2-3/4" CONDUITS FROM GATE OPERATOR TO PEDESTAL

SEE SHEETS C-113,
C-114 AND E-101
FOR DETAIL IN
THIS AREA

PULL FIBER CABLE THROUGH
EXISTING 2" CONDUIT. FIELD
VERIFY EXISTING LOCATION.

1 LS
66 LF

EXISTING PULL BOX

OPERATOR TO PEDESTAL
1 - 3/4" BURIED CONDUIT
W/ 2 - #16 AND 1 - #12 G
1 - 3/4" BURIED CONDUIT SPARE

EXISTING PULL BOX

RECYCLED WATER
WET WELL PUMP
SAMPLING, ANALYZER, AND
PUMPING STATION AREA

0

TREATMENT PLANT SITE PLAN
Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC

1/7/14

100% SUBMITTAL

5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

26 November 2013 - 5:04 PM

Plotted by: Ben Langston

20

30

40'

SCALE 1"=20' AT ORIGINAL SIZE

Reuse of Documents

No

10

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-112.dwg

BL

Designer MJ

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-112

Sht

16

of

50
GENERAL NOTES

DEMOLITION
SAWCUT, REMOVE AND DISPOSE ASPHALT CONCRETE
(APPROXIMATELY 4" THICK)

150 SF

REMOVE AND RETURN TO OWNER EXISTING 6" RECYCLED
WATER LINE

24 LF

REMOVE AND DISPOSE EXISTING FLOW METER AND BOX. REPLACE
WITH 6" PIPE

1 EA

CONSTRUCTION

R=15'

RECYCLED WATER WET WELL, SEE DTL 3, SHEET C-502
CHLORINE ANALYZER, SEE DTL 2 ON SHEET E-501

1 LS

RECYCLED WATER PUMP STATION UPGRADES, SEE SHEET M-301
WATER

1 EA

SAMPLING PUMP AND PIPING, SEE DETAILS 1 & 2, SHEET C-504
TREE LOCATION

1 LS

1 LS

WATER

INSTALL 6' HIGH CHAIN LINK FENCE SEE DTL. 2 SHEET C-505

* LF

INSTALL 6' HIGH CHAIN LINK DOUBLE GATE, 16' WIDTH,
SEE DTL. 2 SHEET C-505

1 EA

INSTALL REMOVABLE BOLLARD PER DTL 1, SHEET C-502

2 EA

INSTALL 4" ROLLED CURB AND GUTTER AT LOCATIONS SHOWN PER
TOWN OF YOUNTVILLE STANDARD DTL ST-4 WITH OPTIONAL POUR.

WATER

71 LF

INSTALL 4" ASPHALT PAVEMENT TURNOUT PER DTL 6,
SHEET C-503 IN LOCATIONS SHOWN

147 SY

4' CONCRETE CURB OPENING. SHAPE AND GRADE TO DRAIN
TOWARDS V-DITCH.

1 EA

INSTALL RIPRAP (D50=6") LINED V-DITCH 1' DEEP WITH 3:1
SIDE SLOPES. INCLUDES GEOTEXTILE LINER UNDER RIPRAP.

15 LF

INSTALL 6' HIGH CHAIN LINK MAN GATE, 4' WIDTH,
SEE DTL 2 SHEET C-505
INSTALL NEW BILCO DOOR AT RECYCLED WATER WET WELL PER
DETAILS 1 AND 2, SHEET S-104

*

1 LS

INSTALL "TRUCK FILL STATION HOURS OF OPERATION M-F, 8-4" SIGN.
ATTACH SIGN TO FENCE NEXT TO TRUCK FILL STATION.

REFER TO SHEET
C-114 FOR PIPING
PLAN

1 EA

1 EA

QUANTITY IS REFLECTED ON SHEET C-112

CONTROL POINTS
POINT #

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

25 November 2013 - 3:23 PM

Plotted by: Ben Langston

Drawn

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-113.dwg

EP

1905678.93

6458550.02

99.16

BOC

1905668.29

6458531.64

99.05

BOC

1905657.65

6458513.26

98.95

BOC

1905658.81

6458510.28

98.57

FL

1905644.22

6458518.79

97.00

FL

1905639.10

6458521.78

96.00

FL

1905655.08

6458508.78

98.95

BOC

1905660.66

6458488.61

99.70

BOC

1905662.78

6458487.45

EXISTING

EP

1905664.63

6458486.40

EXISTING

SAWCUT

1905685.95

6458523.23

EXISTING

SAWCUT

1905690.92

6458552.38

EX FENCE

1905687.77

6458546.77

FENCE

77

1905686.36

6458546.37

FENCE

78

1905678.56

6458550.88

FENCE

79

1905676.35

6458547.07

4' PED. GATE

80

1905664.63

6458526.91

16' DBL. GATE CL

81

1905658.91

6458516.94

FENCE

1905656.51

6458518.32

FENCE

83

No

98.87

82

Job
Project
Manager Director

6458548.78

76

5/24/13

1905681.10

75

100% SUBMITTAL

EP

74

1/7/14

98.93

73

FINAL TOWN REVIEW NFC

6458545.83

72

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

1905686.30

71

Designer MJ

EP

70

BL

EXISTING

69

Drawn

6458549.22

68

Reuse of Documents

1905698.67

67

SCALE 1"=5' AT ORIGINAL SIZE

SAWCUT

66

TREATMENT PLANT DEMOLITION, GRADING AND PAVING PLAN

EXISTING

65

10'

6458548.22

64

7.5

1905700.41

63

5

DESCRIPTION

62

2.5

ELEV.

61

0

EASTING

60

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

NORTHING

1905652.24

6458510.92

FENCE

84

1905661.34

6458500.36

FENCE

85

1905646.37

6458473.91

FENCE

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-113

Sht

17

of

50
GENERAL NOTES

DEMOLITION

CONSTRUCTION
INSTALL TRUCK FILL STATION AND 4" METER, SEE DTL 1, SHEET
C-503

1 LS

INSTALL AIR RELEASE AND 4" CAST IRON SWING CHECK VALVE PER
DTL 5, SHEET C-502

1 EA

INSTALL 4" FLOW METER AND VAULT PER DTL 4, SHEET C-502

3 EA

INSTALL 4" GATE VALVE, BOX AND COVER PER DTL 4, SHEET C-503

4 EA

INSTALL 6" X 4" REDUCER (NPI)

4 EA

INSTALL MJ 4" X 4" X 4" TEE (NPI)

2 EA
90 LF

INSTALL 4" CLASS 350 DIP FOR RECLAIMED WATER
INSTALL 4" 90° BEND (NPI)
CONNECT TO EXISTING PIPE WITH TRANSITION COUPLING

4 EA

WATER

4"RW

WATER

3 EA

WATER

4"RW

TREATMENT PLANT PIPING PLAN

0

2.5

5

7.5

10'

SCALE 1"=5' AT ORIGINAL SIZE

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

25 November 2013 - 3:28 PM

Plotted by: Ben Langston

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-114.dwg

BL

Designer MJ

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-114

Sht

18

of

50
GENERAL NOTES

LE

M

DEMOLITION
REMOVE AND DISPOSE OF EXISTING VALVE ACTUATOR

2 EA

REMOVE AND DISPOSE OF EXISTING BUTTERFLY VALVE

1 EA

REMOVE AND DISPOSE EXISTING TRICKLING FILTER
SUCTION LINE

4 EA

EXISTING
PANELBOARD D & E
EXISTING
SWITCHBOARD B

CONSTRUCTION

UTILITY BUILDING

INSTALL NEW BUTTERFLY VALVE PER DETAILS 4 & 5, SHEET C-504
INSTALL NEW VALVE ACTUATOR AND VALVE EXTENSION PER DETAILS
4 & 5, SHEET C-504.

1 LS

INSTALL NEW 1-1/4" SCHEDULE 80 PVC WATER LINE THREADED INTO
EXISTING RECLAIMED WATERLINE PER DTL 5, SHEET C-503.

RW

1 LS

INSTALL NEW CHLORINE ANALYZER AND PUMP, PER DTL 3 AND DTL 6
ON SHEET C-504

OPERATOR
INTERFACE
TERMINAL

1 LS

INSTALL 2ND SODIUM BISULFATE INJECTOR PUMP PER DTL 4, SHEET
C-501

EXISTING
MANHOLE

2 EA

FUZZY FILTER UPGRADES PER SECTION 11995 OF THE
SPECIFICATIONS

EXISTING
MULTITRONICS
FLOW METER

1 EA

50 LF

INSTALL NEW ULTRASONIC LEVEL SENSOR,
SEE DTL 5,SHEET E-505

LE

2 EA

1 LS

INSTALL 8-FIBER CABLE FROM MASTER RTU TO RTU R, FREE OF
SPLICES IN EXISTING CONDUIT (NPI)

RW

1 LS

INSTALL RTU U, SEE DTL 2, SHEET E-400 (NPI)

20X40 CONTRACTOR
OFFCE TRAILER LOCATION

1 LS

INSTALL MASTER RTU, SEE SHEET E-400 (NPI)

RW

INSTALL CAT6 ETHERNET CONNECTION BETWEEN RTU U AND
MASTER RTU IN EXISTING CONDUIT (NPI)

* LF

INSTALL NEW GRATING AND ALUMINUM SUPPORT
BEAMS, CONNECTIONS, ETC. AT TRICKLING FILTER
VALVE VAULTS SEE SHEET S-103

1 LS

1 LS

TRICKLING FILTER WET WELL PIPE REPLACEMENTS,
PER DTL 3, SHEET C-505

RW

INSTALL NEW BILCO DOOR AT TRICKLING FILTER WET WELLS
SEE SHEET S-104

1 LS

1 EA

INSTALL CATWALK IN EXISTING WETWELL PER DTL 2, SHEET S-102

2 EA

QUANTITY IS REFLECTED ON SHEET C-112

RW

*

* LF

INSTALL 1 1/4" STAINLESS STEEL FOOT VALVE PER DTL 5,
SHEET C-503
RW

INSTALL 2 - 3/4" CONDUITS. SEE DETAILS 6 & 7,
SHEET E-507 AND DETAILS 1 ,2 & 3, SHEET E-508.

RW

EXISTING
PANELBOARD B

CONTROL
BUILDING

CONTRACTOR PARKING
AND LAYDOWN AREA
RW

LOCATION OF EXISTING UTILITIES AND
STRUCTURES ARE FROM THE BEST INFORMATION
AVAILABLE. EXACT LOCATION AND
COMPLETENESS ARE NOT GUARANTEED.
CONTACTOR SHALL NOTIFY UNDERGROUND
SERVICES ALERT (800) 227-2600 A MINIMUM OF 48
HOURS PRIOR TO ANY EXCAVATION AND
POTHOLE FOR EXACT LOCATION.

0

TREATMENT PLANT SITE PLAN

5

10

15

20'

SCALE 1"=10' AT ORIGINAL SIZE

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

25 November 2013 - 3:33 PM

Plotted by: Ben Langston

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-115.dwg

BL

Designer MJ

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ/RG

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-115

Sht

19

of

50
2.00' MIN

EXISTING GROUND

1 .0

0'
2 .0

ESA

CONSTRUCTION ACTIVIVIES

0'

6" CLASS 350 DIP

1 .5

0'

10" CMP CAP
HIGH VISIBILITY FABRIC

10" CMP

6" HOLE FOR DIP

WL

4'-0"

4 .3

END VIEW

WL VARIES
4'±

2'X1'X1' CONCRETE PAD
WITH STAINLESS STEEL
BOLTED PIPE STRAP

POST

3'

4.00' MIN.

CUT TOP OF PIPE PER
DIMENSIONS SHOWN
2'-0"
MIN

10" CMP
8"

8"

SECTION

1

8"

2"

8"

CUT PIPE OUTLET
TO 45°

TEMPORARY FENCE (TYPE ESA)

2

PROFILE VIEW

SCALE : NTS

PLAN

POND DISCHARGE DETAIL
SCALE : NTS

24.50'

2.00' MIN

ADD WOOD SUPPORT SHELF
WITH PLASTIC SUPPORTS,
IWAKE EW-SERIES
DOSING PUMP MODEL NO.
EWB31Y1-VC AND
ASSOCIATED CONTROLS

2.72'

19.92'
6" 45° BEND
FLGxFLG

6" 90° BEND
FLGxFLG

6" 45° BEND
FLGxFLG
2'X1'X1' CONCRETE PAD WITH
STAINLESS STEEL
BOLTED PIPE STRAP

FOR CONTINUATION SEE
DETAIL 2 THIS SHEET

2.00' MIN

6" CLASS 350 DIP

6" CLASS 350 DIP

PIPE SUPPORT (TYP)
PER

7

C-503

PIPE COATING PER SPECIFICATIONS SECTION 09800
EXISTING CONCRETE PAD
PROTECT IN PLACE
1.00'

6" 90° BEND
FLGxFLG

6" CLASS 350 DIP
METERING VALVE BOX PER DTL 6, SHEET C-502.

3

PIPE DISCHARGE
DETAIL
SCALE : N.T.S.

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

27 November 2013 - 3:06 PM

Plotted by: Ben Langston

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-501.dwg

4

BL/MC

Designer MJ

SODIUM BISULFITE PUMP
SCALE : NTS

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-501

Sht

20

of

50
JUNCTION BOX
(SEE NOTE)

FLEXIBLE CONDUIT FROM JUNCTION BOX
TO 5' PAST LOW WATER MARK,18"
MINIMUM SUNLIGHT (UV) RESISTANT FOR
EXTERIOR APPLICATIONS
(FOR CLOS DU VAL SITE ONLY)

4"

PROVIDE WIRE TIE TO SUPPORT
MANUFACTURERS CABLE FROM
GALVANIZED WIRE CABLE

4.0'
TO CONTROL

MANUFACTURE CABLE FOR
LEVEL SENSOR

CONCRETE

MIN.

SCALE : NTS

CHRISTY N48 UTILITY BOX 30" X 48" WITH A
2PC. TRAFFIC RATED STEEL CHECKER
PLATE. PROVIDE EXTRUSIONS AS NEEDED
TO REACH EXISTING PIPE DEPTH.

POND EMBANKMENT

INSTALL 4" ENDRESS HAUSER
PROLINE PROMAG 53W
ELECTROMAGNETIC FLOW METER
DETECTOR WITH REMOTE READOUT

0'-6"

STAINLESS STEEL
CABLE GRIP WIRE
HARNESS

6" ABS PIPE WITH
CARBON BLACK

0'-6"

OUTSIDE OF PIPE
SHALL INCLUDE
PAINTED LEVEL
MARKINGS

BEGIN HOLES 3-FEET
ABOVE BOTTOM

REMOVABLE BOLLARD

316 STAINLESS
STEEL QUICK
LINK

4" DIAMETER
CONCRETE 12" DEEP
SUBMERSIBLE LEVEL
TRANSDUCER CABLE

5-GALLON BUCKET
FILLED WITH CONCRETE

MATCH EXISTING

4" DIP

PIPE CAP

2

WET WELL - PLAN VIEW

16'

CABLES

REMOVE EXISTING
MANHOLE LID AND INSTALL
BILCO DOOR PER
STRUCTURAL SHEETS

LEVEL MONITOR

MOUNT JUNCTION BOX ON
EMBANKMENT. LENGTH OF
SUBMERSED CABLE TO BE FIELD
VERIFIED AND IS SITE SPECIFIC.

LEVEL SENSOR

INSTALL FLYGT
MODEL CS 3085 MT
3"/3" SUBMERSIBLE
PUMP. ATTACH AND
WIRE A LOW LEVEL
INDICATOR FLOAT
SWITCH.

INSTALL 4" CLASS 350 DIP
DISCHARGE PIPE

NOTE:

FLEXIBLE COUPLING
ADAPTOR (TYP)

-

1'-2"

ATTACH 1/8" Ø
GALVANIZED WIRE CABLE
TO ABS PIPE AND
JUNCTION BOX BASE

INSTALL ANCHORS (4) 5GALLON BUCKETS FILLED
WITH CONCRETE ON
OPPOSITE SIDES OF POLE
WITH EMBEDDED 316
STAINLESS STEEL
EYE-BOLT

16"Ø

1

SUBMERGED
CABLE

(4) 1/8" Ø STAINLESS STEEL
CABLES

MIN.

3'-0"
6"

HIGH WATER

16'

1"

FINISH GRADE

316 STAINLESS STEEL 1/2"
EYE-BOLT. EMBED BOLT 6"
INTO CONCRETE

A

4.0'

SEE CABLE GRIP ANCHOR
AND DETAIL BELOW

SLOPE ALL AROUND

1'-3"

(4) ATTACH CABLES TO
PIPE WITH STAINLESS
STEEL STRAPPING AND
HARDWARE

4'-0'

3'-0"

TRAFFICGUARD
LOCKING ROUND POST
"RPL4" BOLLARD OR
APPROVED EQUAL

3'-0"

ANCHOR BUCKETS

LEVEL MONITOR

ANCHOR LAYOUT PLAN

INSTALL 4" UNION
FITTING

SCALE : NTS

ELECTRICAL CONDUIT
ENTRY INTO WET WELL PER
DETAIL 3, SHEET E-505.
PROVIDE CONDUIT AND
CONDUCTORS AS
IDENTIFIED ON SHEET E-200
PENETRATE THROUGH WET
WELL AND INSTALL 4" CLASS
350 DIP DISCHARGE PIPE

4" WATTS MODEL 97FB-CIB
BASKET STRAINER OR
APPROVED EQUAL

8" AB BASE

4

COUPLING

CONC UTILITY BOX
(CHRISTY 48"x30")

FLOW METER VAULT

8" (TYP.)

(E) 16" TE

(E) 16" TE

TO OUTFALL
METERING
BOX (E)

ADJUSTABLE PIPE
SUPPORT PER

SCALE : NTS

7

CHRISTY N48 UTILITY BOX
30" X 48" WITH A 2PC.
TRAFFIC RATED STEEL
CHECKER PLATE

1" BRASS NIPPLE
1" BRASS BALL VALVE
1" DOUBLE STRAP
TAPPING SADDLE
4" DIP

FLEXIBLE
CONDUIT

3" CLASS 350 DIP DISCHARGE
PIPE. ATTACH PIPE TO WALL
OF WET WELL WITH ST. STL.
BRACKETS.

TO SCADA
4" GATE VALVE BOX
AND COVER (TYP)

PRECAST VAULT

INSTALL AND WIRE
LOW FLOW INDICATOR
FLOAT SWITCH

(E) DUCTILE IRON
FROM
DISTRIBUTION
SYSTEM

MATCH EXISTING

INSTALL 4" CAST IRON
SWING CHECK VALVE

J-BOX

4" GATE VALVE BOX
AND COVER (TYP)

TO STORAGE
POND

6" MIN

STEEL PIPE AND FITTINGS
(SIZED TO MATCH VALVE
OUTLET)
EXTEND TO 4" BELOW THE
CENTERLINE OF THE MAIN
LINE COVER END WITH 16
MESH S.S. SCREEN

COMBINATION AIR VALVE
OR AIR RELEASE VALVE

E-503

FLEXIBLE COUPLING
ADAPTOR (TYP)

4" RESTRAINED FLEX
COUPLING (TYP.)

4" CLAVAL MODEL 133-01
METERING VALVE OR
APPROVED EQUAL

COATING PER 09800
INSTALL FLYGT MODEL CS
3085 MT 3"/3" SUBMERSIBLE
PUMP
(E) DUCTILE IRON

REDUCER SIZE
VARIES (TYP)

TO OUTFALL
METERING
BOX (E)

6"
8" AB BASE

1'x1'x1' CONC. FOOTER
DUCTILE IRON PIPE

DIP PIPE

FLEXIBLE COUPLING
ADAPTOR (TYP)

5

AIR RELEASE/CHECK VALVE VAULT

6

SCALE : NTS

METERING VALVE VAULT

SUPPORT VALVES IN BOX WITH
BRICKS OR REDWOOD BLOCKS
UNDER FLANGES.

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC

1/7/14

100% SUBMITTAL

5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

27 November 2013 - 3:07 PM

Plotted by: Ben Langston

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-502.dwg

3

SCALE : NTS

Reuse of Documents

No

WET WELL - SECTION A

NOTE:

8" AB BASE

BL/MC

Designer MJ

RECYCLED WATER WET WELL
SCALE : NTS

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-502

Sht

21

of

50
1/2" MINUS 2" THICK FOR
ENTIRE WIDTH OF ROAD
WHERE SHOWN ON PLANS

X'

3" WIDE PURPLE PLASTIC
CAUTION TAPE, MARKED
"RECYCLED WATERLINE
BURIED BELOW"
3' MIN

4" BUTTERFLY
VALVE

#4 STEEL BARS AT 12"
O.C. EACH WAY

12"

TYPE 2 BEDDING

6" MIN

4" ASPHALT
6" AGGREGATE BASE
COURSE

INSULATED TRACER
WIRE #12 COPPER

3" MIN

3" MIN

4" EPOXY COATED
CLASS 350 DIP

INITIAL BACKFILL

36"

12"

INSULATED TRACER
WIRE #12 COPPER

3'X3'X6"
CONC SLAB

SUBSEQUENT BACKFILL

3' MIN

24" MIN
(TYP)

6" MIN

6" RIPPED, MOISTURE
CONDITIONED AND
RECOMPACTED
SUBGRADE

INITIAL BACKFILL

4" RUBBER DUST CAP

4" 90° BEND

3" WIDE PURPLE PLASTIC
CAUTION TAPE, MARKED
"RECYCLED WATERLINE
BURIED BELOW"

SEEDING

4" ASPHAULT

4" FLANGED MALE NPT

SUBSEQUENT BACKFILL

4" THREADED MALE FITTING
CAMLOCK QUICK
CONNECT WITH PLUG

X'

GRAVEL ROAD

4" STAINLESS STEEL THREADED
SAFETY BREAK-AWAY COUPLING

SUBGRADE COMPACTED
TO 95% RC

TYPE 2 BEDDING

6" MIN

6" MIN

NOTE:
INSTALL 2 REMOVABLE BOLLARDS AROUND
TRUCK FILL STATION FOR PROTECTION.
USE FLANGED PIPE BACK TO DISCHARGE
HEADER.

TO METER

TYPICAL TRENCH SECTION (ASPHAULT AREAS)

3

SCALE : NTS

AC PAVEMENT SECTION

6

SCALE : NTS

SCALE : NTS

TRUCK FILL STATION
SCALE : NTS

CHRISTY G5 PURPLE
VALVE BOX WITH LID
MARKED "RECYCLED
WATER" OR "RW"

STREET GRADE

DIMENSION TABLE (INCHES)
SUPPORTED PIPE

2" A.C. (MIN)
CLASS "C"
CONCRETE
COLLAR

6"
12" MIN
(TYP)

EXISTING MANHOLE
ADJUSTABLE PIPE
SADDLE SUPPORT

5' MAX

(1)
E

PURPLE 8" DIA. P.V.C. PIPE RISER

"D" SEE TABLE
MECHANICAL JOINT W/
MEGALUG (OR EQUIVALENT)
RESTRAINT OR PUSH-ON
JOINT

CONNECT AND
EXTEND 1 1/4" SCH. 80
PVC SUCTION LINE
DOWN EXISTING
MANHOLE WALL.
MOUNT PIPE ON WALL
WITH UNISTRUT

INSULATED TRACER WIRE
#12 COPPER WITH 2"-3"
PIG TAIL (TYP.)

A
(2)

3/4" 316 S.S. WEDGE
ANCHOR (TYP OF 4)

B

1/2" PLATE
(4)

1" NON-SHRINK
GROUT
FIN. FLOOR OR
12"x12"x12" CONC.
PAD WITH #4@10"
E.W., E.F.

NOTES:
1. BUTTERFLY VALVES SHALL BE INSTALLED FOR 12" AND LARGER PIPES.
VALVE NUTS SHALL BE PLACED ON THE SIDE OF THE MAIN CLOSEST TO
THE NEAREST CURB.

A

B

C

2 1/2
3
3 1/2
4
5
6
8
10
12
14
16
18
20
24
30
32
36

1" DISCHARGE LINE

VARIES

6" MIN.

PIPE
SIZE

1" MIN.

1

2

TYPICAL TRENCH SECTION
(GRAVEL AND RESEEDED AREAS)

1 1/2
1 1/2
1 1/2
2 1/2
2 1/2
2 1/2
2 1/2
2 1/2
2 1/2
3
3
3 1/2
3 1/2
4
4
4
4

2 1/2
2 1/2
2 1/2
3
3
3
3
3
3
4
4
6
6
6
6
6
6

9
9
9
9
9
9
9
9
9
11
11
13 1/2
13 1/2
13 1/2
15
18
18

D
3 1/2
3 3/4
4
4 1/4
4 7/8
5 1/2
6 7/8
8 1/2
9 15/16
10 15/16
12 3/8
13 7/8
15 3/8
17 15/16
21 5/16
22 1/2
24 1/2

E
MIN

MAX

8
8 1/4
8 1/2
9 1/4
10
10 1/2
11 3/4
13 1/2
15
16 1/4
17 3/4
19 1/2
21
23 3/4
27
28 1/4
30 1/4

13
13 1/4
13 1/2
14
14 3/4
15 1/4
16 1/2
18 1/4
19 3/4
20 3/4
22 1/4
24
25 1/2
28 1/4
31 1/2
32 3/4
34 3/4

NOTES:

EXISTING 15"
RECLAIMED
WATERLINE

3. THE TWO (2) INCH SQUARE OPERATING NUT ON ALL VALVES SHALL BE INSTALLED AT A
MAXIMUM OF 5-FEET IN DEPTH MEASURED FROM THE TOP OF THE OPERATING NUT TO FINISHED
GRADE. ALL OPERATING NUTS INSTALLED AT A DEPTH GREATER THAN 5-FEET SHALL INCLUDE A
VALVE EXTENSION TO RAISE THE OPERATING NUT TO 24-INCHES FROM FINISHED GRADE.

ADJUSTABLE PIPE SUPPORT, GRINNELL FIG. 264 OR
EQUAL.
PIPE STANCHION SADDLE DESIGNED FOR PIPE 4"-36".
PIPE LARGER THAN 36" SHALL BE SUPPORTED BY A
STANCHION SADDLE DESIGNED BY THE MANUFACTURER.

4.

C

PIPE SADDLE WITH U-BOLT, GRINNELL FIG. 259 OR
EQUAL.

3.

2. VALVE RING SHALL BE SET BELOW GRADE PRIOR TO PLACING FINISHED PAVEMENT AND
THEN CUT AND ADJUSTED TO FINISHED GRADE.

1.

2.

LEVELING NUTS

PROVIDE 5/8" BOLT HOLE (TYP. OF 4) 1-1/2" OFF EDGE OF
BEARING PLATE.

1 1/4" STAINLESS
STEEL FOOT VALVE

4. VALVE EXTENSIONS (IF REQUIRED) SHALL BE ROUND OR SQUARE 1.5-INCH DIAMETER STEEL
ROD, WELDED CONSTRUCTION, HOT DIPPED GALVANIZED WITH TOP CENTERING RING AND
AWWA 2" OPERATING NUTS TOP AND BOTTOM (PIPELINE PRODUCTS SX-900 OR SIMILAR).
SOCKET END SHALL BE DRILLED AND TAPPED WITH TWO (2) 1/4" SET SCREWS INSTALLED ON
OPPOSITE SIDES. OPERATING NUT SHALL BE DRILLED WITH RECESSES TO ACCEPT THE TWO (2)
1/4" SET SCREWS. SET SCREWS SHALL BE SECURELY FASTENED TO THE OPERATING NUT.

7

PIPE SUPPORT
SCALE : NTS

5. WATER VALVES SHALL BE OPERATED BY TOWN PERSONNEL ONLY.
20'

6. ALL NEW VALVES SHALL BE MARKED ON THE NEW RW LINE.

4

GATE VALVE

5

SCALE : NTS

1 1/4" PIPE THREADING DETAIL

1 1/4" SCHEDULE 80 PVC
WATERLINE THREADED
INSIDE EXISTING 15"
RECLAIMED WATERLINE

SCALE : NTS

Reuse of Documents

Drawn

This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the
property of GHD Inc. and shall not be reused in whole or
in part for any other project without GHD Inc.'s written
authorization. © GHD Inc. 2012

FINAL TOWN REVIEW NFC
100% SUBMITTAL
No

1/7/14
5/24/13

Revision

Plot Date:

Note: * indicates signatures on original issue of drawing or last revision of drawing

6 December 2013 - 6:42 PM

Plotted by: Aaron Foscato

Drawn

Job
Project
Manager Director

Cad File No:

Date

N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-503.dwg

BL/MC

Designer MJ

Client
Project

Drafting SD
Check

GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com

Design
Check

WZ

Approved
(Project Director)
JANUARY 2014
Date
Scale

AS SHOWN

This Drawing shall not be used
for Construction unless Signed
and Sealed For Construction

Title

Contract No.
Original Size

C-503

Sht

22

of

50
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications
Recycled water project draft plans and specifications

Más contenido relacionado

Destacado

2014-05-12 255 138th Street NYCTA Structural Drawings
2014-05-12 255 138th Street NYCTA Structural Drawings2014-05-12 255 138th Street NYCTA Structural Drawings
2014-05-12 255 138th Street NYCTA Structural DrawingsTodd Mordoh
 
SSL, FFL, SFL Abbreviations
SSL, FFL, SFL AbbreviationsSSL, FFL, SFL Abbreviations
SSL, FFL, SFL AbbreviationsEhlelt Mancha
 
SSL & TLS Architecture short
SSL & TLS Architecture shortSSL & TLS Architecture short
SSL & TLS Architecture shortAvirot Mitamura
 
Bagaimana membuat sebuah p&id
Bagaimana membuat sebuah p&idBagaimana membuat sebuah p&id
Bagaimana membuat sebuah p&idDina Khairani
 
Blueprint Reading- Introduction
Blueprint Reading- IntroductionBlueprint Reading- Introduction
Blueprint Reading- Introductionflrbc1avtech
 
Reading floor plans
Reading floor plansReading floor plans
Reading floor plansjayneross
 
Engineering drawing (engineering lettering) lesson 3
Engineering drawing (engineering lettering) lesson 3Engineering drawing (engineering lettering) lesson 3
Engineering drawing (engineering lettering) lesson 3hermiraguilar
 
Engineering Drawing
Engineering DrawingEngineering Drawing
Engineering DrawingLai Chun Tat
 
Architectural drawings
Architectural drawingsArchitectural drawings
Architectural drawingsSomnath Bhui
 
ARCHITECTURAL STANDARDS
ARCHITECTURAL STANDARDSARCHITECTURAL STANDARDS
ARCHITECTURAL STANDARDSstuti31
 
Architecture drawing presentation
Architecture drawing presentationArchitecture drawing presentation
Architecture drawing presentationCarlson Ko
 
Engineering drawing (introduction of engineering drawing) lesson 1
Engineering drawing (introduction of engineering drawing) lesson 1Engineering drawing (introduction of engineering drawing) lesson 1
Engineering drawing (introduction of engineering drawing) lesson 1hermiraguilar
 
Basic blueprint reading
Basic blueprint readingBasic blueprint reading
Basic blueprint readingJames Shearer
 
Plan symbols
Plan symbolsPlan symbols
Plan symbolsgopaltry
 

Destacado (17)

2014-05-12 255 138th Street NYCTA Structural Drawings
2014-05-12 255 138th Street NYCTA Structural Drawings2014-05-12 255 138th Street NYCTA Structural Drawings
2014-05-12 255 138th Street NYCTA Structural Drawings
 
SSL, FFL, SFL Abbreviations
SSL, FFL, SFL AbbreviationsSSL, FFL, SFL Abbreviations
SSL, FFL, SFL Abbreviations
 
SSL & TLS Architecture short
SSL & TLS Architecture shortSSL & TLS Architecture short
SSL & TLS Architecture short
 
Bagaimana membuat sebuah p&id
Bagaimana membuat sebuah p&idBagaimana membuat sebuah p&id
Bagaimana membuat sebuah p&id
 
Blueprint Reading- Introduction
Blueprint Reading- IntroductionBlueprint Reading- Introduction
Blueprint Reading- Introduction
 
Reading floor plans
Reading floor plansReading floor plans
Reading floor plans
 
Engineering drawing (engineering lettering) lesson 3
Engineering drawing (engineering lettering) lesson 3Engineering drawing (engineering lettering) lesson 3
Engineering drawing (engineering lettering) lesson 3
 
Signs & Symbols
Signs & SymbolsSigns & Symbols
Signs & Symbols
 
Engineering Drawing
Engineering DrawingEngineering Drawing
Engineering Drawing
 
Architectural drawings
Architectural drawingsArchitectural drawings
Architectural drawings
 
Plan, section, elevation revised
Plan, section, elevation revisedPlan, section, elevation revised
Plan, section, elevation revised
 
ARCHITECTURAL STANDARDS
ARCHITECTURAL STANDARDSARCHITECTURAL STANDARDS
ARCHITECTURAL STANDARDS
 
Architecture drawing presentation
Architecture drawing presentationArchitecture drawing presentation
Architecture drawing presentation
 
Engineering drawing (introduction of engineering drawing) lesson 1
Engineering drawing (introduction of engineering drawing) lesson 1Engineering drawing (introduction of engineering drawing) lesson 1
Engineering drawing (introduction of engineering drawing) lesson 1
 
Basic blueprint reading
Basic blueprint readingBasic blueprint reading
Basic blueprint reading
 
Plan symbols
Plan symbolsPlan symbols
Plan symbols
 
Engineering Drawing
Engineering DrawingEngineering Drawing
Engineering Drawing
 

Similar a Recycled water project draft plans and specifications

Similar a Recycled water project draft plans and specifications (20)

ADU Plan 5 - 1200 sqft (1).pdf
ADU Plan 5 - 1200 sqft (1).pdfADU Plan 5 - 1200 sqft (1).pdf
ADU Plan 5 - 1200 sqft (1).pdf
 
KFC - Surprise, AZ
KFC - Surprise, AZKFC - Surprise, AZ
KFC - Surprise, AZ
 
POWER SYSTEM.pdf
POWER SYSTEM.pdfPOWER SYSTEM.pdf
POWER SYSTEM.pdf
 
E3.pdf
E3.pdfE3.pdf
E3.pdf
 
ProcContSite
ProcContSiteProcContSite
ProcContSite
 
15RDM01-2016-Academy Utility Plan
15RDM01-2016-Academy Utility Plan15RDM01-2016-Academy Utility Plan
15RDM01-2016-Academy Utility Plan
 
layout
layoutlayout
layout
 
Pasinaya-Townhomes-Thickened-Slab-1.pdf
Pasinaya-Townhomes-Thickened-Slab-1.pdfPasinaya-Townhomes-Thickened-Slab-1.pdf
Pasinaya-Townhomes-Thickened-Slab-1.pdf
 
Farmers PDC Chino CA
Farmers PDC Chino CAFarmers PDC Chino CA
Farmers PDC Chino CA
 
LA FLORESTA
LA FLORESTALA FLORESTA
LA FLORESTA
 
Brisbane ferries project drawings
Brisbane ferries project drawingsBrisbane ferries project drawings
Brisbane ferries project drawings
 
IS252_PAA
IS252_PAAIS252_PAA
IS252_PAA
 
Plant irrigation ppt
Plant irrigation pptPlant irrigation ppt
Plant irrigation ppt
 
SAMPLE PORTFOLIO
SAMPLE PORTFOLIOSAMPLE PORTFOLIO
SAMPLE PORTFOLIO
 
Mt Sinai WH Rplcmnt 081016
Mt Sinai WH Rplcmnt 081016Mt Sinai WH Rplcmnt 081016
Mt Sinai WH Rplcmnt 081016
 
BN-DS-E2_02.pdf
BN-DS-E2_02.pdfBN-DS-E2_02.pdf
BN-DS-E2_02.pdf
 
1 T1 Bigler Site 2 6-1-2022.pdf
1 T1 Bigler Site 2 6-1-2022.pdf1 T1 Bigler Site 2 6-1-2022.pdf
1 T1 Bigler Site 2 6-1-2022.pdf
 
Construction Documents Fall 2014
Construction Documents Fall 2014Construction Documents Fall 2014
Construction Documents Fall 2014
 
STANDARD ROAD DETAILS City of Richardson, Texas City USA
STANDARD ROAD DETAILS City of Richardson, Texas City USASTANDARD ROAD DETAILS City of Richardson, Texas City USA
STANDARD ROAD DETAILS City of Richardson, Texas City USA
 
Symbols.pdf
Symbols.pdfSymbols.pdf
Symbols.pdf
 

Más de kristinemassey

Drought conditions and mandates rev pn
Drought conditions and mandates rev pnDrought conditions and mandates rev pn
Drought conditions and mandates rev pnkristinemassey
 
Demery and assoc madison and yount street community presentation 3 4-14
Demery and assoc madison and yount street community presentation 3 4-14Demery and assoc madison and yount street community presentation 3 4-14
Demery and assoc madison and yount street community presentation 3 4-14kristinemassey
 
Ada transition plan and washington park public meeting power point washingt...
Ada transition plan and washington park public meeting power point   washingt...Ada transition plan and washington park public meeting power point   washingt...
Ada transition plan and washington park public meeting power point washingt...kristinemassey
 
Ada transition plan public meeting power point
Ada transition plan public meeting power pointAda transition plan public meeting power point
Ada transition plan public meeting power pointkristinemassey
 
2012 06-13 draft facilities planning report
2012 06-13 draft facilities planning report2012 06-13 draft facilities planning report
2012 06-13 draft facilities planning reportkristinemassey
 
Napa rhna 5 30-12 public workshop power point
Napa rhna 5 30-12 public workshop power pointNapa rhna 5 30-12 public workshop power point
Napa rhna 5 30-12 public workshop power pointkristinemassey
 
Tour of ww collection system 11 4-2011
Tour of ww collection system 11 4-2011Tour of ww collection system 11 4-2011
Tour of ww collection system 11 4-2011kristinemassey
 
Tour of w and ww systems 3 15-11
Tour of w and ww systems 3 15-11Tour of w and ww systems 3 15-11
Tour of w and ww systems 3 15-11kristinemassey
 

Más de kristinemassey (9)

Drought conditions and mandates rev pn
Drought conditions and mandates rev pnDrought conditions and mandates rev pn
Drought conditions and mandates rev pn
 
Demery and assoc madison and yount street community presentation 3 4-14
Demery and assoc madison and yount street community presentation 3 4-14Demery and assoc madison and yount street community presentation 3 4-14
Demery and assoc madison and yount street community presentation 3 4-14
 
Ada transition plan and washington park public meeting power point washingt...
Ada transition plan and washington park public meeting power point   washingt...Ada transition plan and washington park public meeting power point   washingt...
Ada transition plan and washington park public meeting power point washingt...
 
Ada transition plan public meeting power point
Ada transition plan public meeting power pointAda transition plan public meeting power point
Ada transition plan public meeting power point
 
Measure a foc 080713
Measure a foc 080713Measure a foc 080713
Measure a foc 080713
 
2012 06-13 draft facilities planning report
2012 06-13 draft facilities planning report2012 06-13 draft facilities planning report
2012 06-13 draft facilities planning report
 
Napa rhna 5 30-12 public workshop power point
Napa rhna 5 30-12 public workshop power pointNapa rhna 5 30-12 public workshop power point
Napa rhna 5 30-12 public workshop power point
 
Tour of ww collection system 11 4-2011
Tour of ww collection system 11 4-2011Tour of ww collection system 11 4-2011
Tour of ww collection system 11 4-2011
 
Tour of w and ww systems 3 15-11
Tour of w and ww systems 3 15-11Tour of w and ww systems 3 15-11
Tour of w and ww systems 3 15-11
 

Último

原版定制卡尔加里大学毕业证(UC毕业证)留信学历认证
原版定制卡尔加里大学毕业证(UC毕业证)留信学历认证原版定制卡尔加里大学毕业证(UC毕业证)留信学历认证
原版定制卡尔加里大学毕业证(UC毕业证)留信学历认证diploma001
 
定制(Waikato毕业证书)新西兰怀卡托大学毕业证成绩单原版一比一
定制(Waikato毕业证书)新西兰怀卡托大学毕业证成绩单原版一比一定制(Waikato毕业证书)新西兰怀卡托大学毕业证成绩单原版一比一
定制(Waikato毕业证书)新西兰怀卡托大学毕业证成绩单原版一比一Fs
 
LinkedIn Strategic Guidelines April 2024
LinkedIn Strategic Guidelines April 2024LinkedIn Strategic Guidelines April 2024
LinkedIn Strategic Guidelines April 2024Bruce Bennett
 
Gurgaon Call Girls: Free Delivery 24x7 at Your Doorstep G.G.N = 8377087607
Gurgaon Call Girls: Free Delivery 24x7 at Your Doorstep G.G.N = 8377087607Gurgaon Call Girls: Free Delivery 24x7 at Your Doorstep G.G.N = 8377087607
Gurgaon Call Girls: Free Delivery 24x7 at Your Doorstep G.G.N = 8377087607dollysharma2066
 
定制(UQ毕业证书)澳洲昆士兰大学毕业证成绩单原版一比一
定制(UQ毕业证书)澳洲昆士兰大学毕业证成绩单原版一比一定制(UQ毕业证书)澳洲昆士兰大学毕业证成绩单原版一比一
定制(UQ毕业证书)澳洲昆士兰大学毕业证成绩单原版一比一lvtagr7
 
AI ppt introduction , advandtage pros and cons.pptx
AI ppt introduction , advandtage pros and cons.pptxAI ppt introduction , advandtage pros and cons.pptx
AI ppt introduction , advandtage pros and cons.pptxdeepakkrlkr2002
 
办理老道明大学毕业证成绩单|购买美国ODU文凭证书
办理老道明大学毕业证成绩单|购买美国ODU文凭证书办理老道明大学毕业证成绩单|购买美国ODU文凭证书
办理老道明大学毕业证成绩单|购买美国ODU文凭证书saphesg8
 
Introduction to phyton , important topic
Introduction to phyton , important topicIntroduction to phyton , important topic
Introduction to phyton , important topicakpgenious67
 
Ioannis Tzachristas Self-Presentation for MBA.pdf
Ioannis Tzachristas Self-Presentation for MBA.pdfIoannis Tzachristas Self-Presentation for MBA.pdf
Ioannis Tzachristas Self-Presentation for MBA.pdfjtzach
 
LinkedIn for Your Job Search in April 2024
LinkedIn for Your Job Search in April 2024LinkedIn for Your Job Search in April 2024
LinkedIn for Your Job Search in April 2024Bruce Bennett
 
Protection of Children in context of IHL and Counter Terrorism
Protection of Children in context of IHL and  Counter TerrorismProtection of Children in context of IHL and  Counter Terrorism
Protection of Children in context of IHL and Counter TerrorismNilendra Kumar
 
Back on Track: Navigating the Return to Work after Parental Leave
Back on Track: Navigating the Return to Work after Parental LeaveBack on Track: Navigating the Return to Work after Parental Leave
Back on Track: Navigating the Return to Work after Parental LeaveMarharyta Nedzelska
 
Digital Marketing Training Institute in Mohali, India
Digital Marketing Training Institute in Mohali, IndiaDigital Marketing Training Institute in Mohali, India
Digital Marketing Training Institute in Mohali, IndiaDigital Discovery Institute
 
办理学位证(Massey证书)新西兰梅西大学毕业证成绩单原版一比一
办理学位证(Massey证书)新西兰梅西大学毕业证成绩单原版一比一办理学位证(Massey证书)新西兰梅西大学毕业证成绩单原版一比一
办理学位证(Massey证书)新西兰梅西大学毕业证成绩单原版一比一A SSS
 
AICTE PPT slide of Engineering college kr pete
AICTE PPT slide of Engineering college kr peteAICTE PPT slide of Engineering college kr pete
AICTE PPT slide of Engineering college kr peteshivubhavv
 
Escort Service Andheri WhatsApp:+91-9833363713
Escort Service Andheri WhatsApp:+91-9833363713Escort Service Andheri WhatsApp:+91-9833363713
Escort Service Andheri WhatsApp:+91-9833363713Riya Pathan
 
Black and White Minimalist Co Letter.pdf
Black and White Minimalist Co Letter.pdfBlack and White Minimalist Co Letter.pdf
Black and White Minimalist Co Letter.pdfpadillaangelina0023
 
Ch. 9- __Skin, hair and nail Assessment (1).pdf
Ch. 9- __Skin, hair and nail Assessment (1).pdfCh. 9- __Skin, hair and nail Assessment (1).pdf
Ch. 9- __Skin, hair and nail Assessment (1).pdfJamalYaseenJameelOde
 
定制(SCU毕业证书)南十字星大学毕业证成绩单原版一比一
定制(SCU毕业证书)南十字星大学毕业证成绩单原版一比一定制(SCU毕业证书)南十字星大学毕业证成绩单原版一比一
定制(SCU毕业证书)南十字星大学毕业证成绩单原版一比一z xss
 
定制英国克兰菲尔德大学毕业证成绩单原版一比一
定制英国克兰菲尔德大学毕业证成绩单原版一比一定制英国克兰菲尔德大学毕业证成绩单原版一比一
定制英国克兰菲尔德大学毕业证成绩单原版一比一z zzz
 

Último (20)

原版定制卡尔加里大学毕业证(UC毕业证)留信学历认证
原版定制卡尔加里大学毕业证(UC毕业证)留信学历认证原版定制卡尔加里大学毕业证(UC毕业证)留信学历认证
原版定制卡尔加里大学毕业证(UC毕业证)留信学历认证
 
定制(Waikato毕业证书)新西兰怀卡托大学毕业证成绩单原版一比一
定制(Waikato毕业证书)新西兰怀卡托大学毕业证成绩单原版一比一定制(Waikato毕业证书)新西兰怀卡托大学毕业证成绩单原版一比一
定制(Waikato毕业证书)新西兰怀卡托大学毕业证成绩单原版一比一
 
LinkedIn Strategic Guidelines April 2024
LinkedIn Strategic Guidelines April 2024LinkedIn Strategic Guidelines April 2024
LinkedIn Strategic Guidelines April 2024
 
Gurgaon Call Girls: Free Delivery 24x7 at Your Doorstep G.G.N = 8377087607
Gurgaon Call Girls: Free Delivery 24x7 at Your Doorstep G.G.N = 8377087607Gurgaon Call Girls: Free Delivery 24x7 at Your Doorstep G.G.N = 8377087607
Gurgaon Call Girls: Free Delivery 24x7 at Your Doorstep G.G.N = 8377087607
 
定制(UQ毕业证书)澳洲昆士兰大学毕业证成绩单原版一比一
定制(UQ毕业证书)澳洲昆士兰大学毕业证成绩单原版一比一定制(UQ毕业证书)澳洲昆士兰大学毕业证成绩单原版一比一
定制(UQ毕业证书)澳洲昆士兰大学毕业证成绩单原版一比一
 
AI ppt introduction , advandtage pros and cons.pptx
AI ppt introduction , advandtage pros and cons.pptxAI ppt introduction , advandtage pros and cons.pptx
AI ppt introduction , advandtage pros and cons.pptx
 
办理老道明大学毕业证成绩单|购买美国ODU文凭证书
办理老道明大学毕业证成绩单|购买美国ODU文凭证书办理老道明大学毕业证成绩单|购买美国ODU文凭证书
办理老道明大学毕业证成绩单|购买美国ODU文凭证书
 
Introduction to phyton , important topic
Introduction to phyton , important topicIntroduction to phyton , important topic
Introduction to phyton , important topic
 
Ioannis Tzachristas Self-Presentation for MBA.pdf
Ioannis Tzachristas Self-Presentation for MBA.pdfIoannis Tzachristas Self-Presentation for MBA.pdf
Ioannis Tzachristas Self-Presentation for MBA.pdf
 
LinkedIn for Your Job Search in April 2024
LinkedIn for Your Job Search in April 2024LinkedIn for Your Job Search in April 2024
LinkedIn for Your Job Search in April 2024
 
Protection of Children in context of IHL and Counter Terrorism
Protection of Children in context of IHL and  Counter TerrorismProtection of Children in context of IHL and  Counter Terrorism
Protection of Children in context of IHL and Counter Terrorism
 
Back on Track: Navigating the Return to Work after Parental Leave
Back on Track: Navigating the Return to Work after Parental LeaveBack on Track: Navigating the Return to Work after Parental Leave
Back on Track: Navigating the Return to Work after Parental Leave
 
Digital Marketing Training Institute in Mohali, India
Digital Marketing Training Institute in Mohali, IndiaDigital Marketing Training Institute in Mohali, India
Digital Marketing Training Institute in Mohali, India
 
办理学位证(Massey证书)新西兰梅西大学毕业证成绩单原版一比一
办理学位证(Massey证书)新西兰梅西大学毕业证成绩单原版一比一办理学位证(Massey证书)新西兰梅西大学毕业证成绩单原版一比一
办理学位证(Massey证书)新西兰梅西大学毕业证成绩单原版一比一
 
AICTE PPT slide of Engineering college kr pete
AICTE PPT slide of Engineering college kr peteAICTE PPT slide of Engineering college kr pete
AICTE PPT slide of Engineering college kr pete
 
Escort Service Andheri WhatsApp:+91-9833363713
Escort Service Andheri WhatsApp:+91-9833363713Escort Service Andheri WhatsApp:+91-9833363713
Escort Service Andheri WhatsApp:+91-9833363713
 
Black and White Minimalist Co Letter.pdf
Black and White Minimalist Co Letter.pdfBlack and White Minimalist Co Letter.pdf
Black and White Minimalist Co Letter.pdf
 
Ch. 9- __Skin, hair and nail Assessment (1).pdf
Ch. 9- __Skin, hair and nail Assessment (1).pdfCh. 9- __Skin, hair and nail Assessment (1).pdf
Ch. 9- __Skin, hair and nail Assessment (1).pdf
 
定制(SCU毕业证书)南十字星大学毕业证成绩单原版一比一
定制(SCU毕业证书)南十字星大学毕业证成绩单原版一比一定制(SCU毕业证书)南十字星大学毕业证成绩单原版一比一
定制(SCU毕业证书)南十字星大学毕业证成绩单原版一比一
 
定制英国克兰菲尔德大学毕业证成绩单原版一比一
定制英国克兰菲尔德大学毕业证成绩单原版一比一定制英国克兰菲尔德大学毕业证成绩单原版一比一
定制英国克兰菲尔德大学毕业证成绩单原版一比一
 

Recycled water project draft plans and specifications

  • 1. RECYCLED WATER EXPANSION PROJECT JANUARY 2014 PROJECT NUMBER: WW-0002 PREPARED BY AREA MAP CR O SS R D LOCATION MAP YO U NT VI LL E PROJECT LOCATION BERINGER POND G HI HW AY SILVERADO WEST POND 29 STAG'S LEAP WINE CELLARS POND D VER N LA RI NAPA PROJECT SITE NE LA YOUNTVILLE JOINT TREATMENT PLANT CLOS DU VAL/ REGUSCI POND LV ER DR O AD L AI TR RD YA E V IN W VIE SI MONDAVI POND CHIMNEY ROCK POND N NOT TO SCALE Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 22 November 2013 - 2:41 PM Plotted by: Ben Langston Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 G-001.dwg BL Designer MBJ Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check TW Approved (Project Director) JANUARY 2014 Date Scale NONE This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size G-001 Sht 1 of 50
  • 2. SYMBOLS ABBREVIATIONS SECTION DESIGNATION @ AB AC APN B BLDG BM BOTT SECTION DESIGNATIONS USE LETTERS ON DRAWING WHERE SECTION IS TAKEN: A M101 SECTION DESIGNATION DRAWING NUMBER WHERE SHOWN SECTION DESIGNATION SECTION M100 SCALE: 1/4"=1'-0" DRAWING NUMBER WHERE TAKEN DRAWING NUMBER SHOWN AS " - " IF TAKEN & SHOWN ON SAME SHEET. DETAIL DESIGNATION DETAIL DESIGNATIONS USE NUMBERS ON DRAWING WHERE SECTION IS TAKEN: M101 DRAWING NUMBER WHERE SHOWN M100 DETAIL DESIGNATION NOMINAL PIPE DIAMETER PIPE MATERIAL; SEE SPECIFICATIONS FOR EQUIVALENT REPLACEMENT FLOW STREAM IDENTIFIER DESIGNATION FOR EXISTING PIPING (SCREENED): PIPING SYSTEM DESIGNATIONS FOR EXISTING PIPE INDICATE TYPE OF SERVICE ONLY AND DO NOT IMPLY PIPE MATERIALS USED. DESIGNATION FOR FUTURE PIPING (DASHED): MAX MH MIN MISC MON MTL (N) N NC NIC NO NSD NTS UNK VERTICAL VITRIFIED CLAY W W/ WM W/S WTR NEW NORTH NORMALLY CLOSED NOT IN CONTRACT NUMBER NAPA SANITATION DISTRICT NOT TO SCALE UNKNOWN V, VERT VC MAXIMUM MANHOLE MINIMUM MISCELLANEOUS MONUMENT MATERIAL WATER, WEST WITH WATER METER WATER SURFACE WATER LATERAL LINEAR FEET LONGITUDINAL AMPERE,AMPS AC ALTERNATING CURRENT AE ANALYZER ELEMENT AI ANALOG INPUT AO ANALOG OUTPUT kV KILOVOLT AWG AMERICAN WIRE GAUGE kVA KILOVOLT AMPERES kW KILOWATT BKR 6" PVC 4" PVC EQUIPMENT NUMBER 8" DIP DESIGNATION FOR NEW INSTRUMENTS: FE-1 6" DIP INSTRUMENT NUMBER G-001 TITLE SHEET, AREA AND LOCATION MAPS 2 G-002 ABBREVIATIONS, LEGEND, SYMBOLS AND DRAWING INDEX 3 G-003 OVERALL SITE PLAN, KEY MAP, CONTROL DIAGRAM AND BORING LOCATIONS JUNCTION BOX BREAKER LEVEL ELEMENT OC OD OHE MITIGATION MEASURES AND GENERAL NOTES CIRCUIT BREAKER LS LEVEL SWITCH 5 C-101 INTENTIONALLY LEFT BLANK CONCRETE EQUIPMENT PAD CONTROL PANEL LSH HIGH-LEVEL SWITCH 6 C-102 RECYCLED WATER PLAN AND PROFILE - BERINGER LSL LOW-LEVEL SWITCH 7 C-103 RECYCLED WATER PLAN AND PROFILE - BERINGER MAG MAGNETIC 8 C-104 RECYCLED WATER PLAN AND PROFILE - BERINGER 9 C-105 RECYCLED WATER PLAN AND PROFILE - BERINGER PCS PROCESS CONTROL SYSTEM 10 C-106 RECYCLED WATER PLAN AND PROFILE - BERINGER TSP TWISTED SHIELDED PAIR 11 C-107 RECYCLED WATER PLAN AND PROFILE - BERINGER TYP TYPICAL 12 C-108 RECYCLED WATER PLAN AND PROFILE - MONDAVI ULS ULTRASONIC LEVEL SENSOR 13 C-109 CHIMNEY ROCK POND IMPROVEMENTS V VOLTS 14 C-110 CLOS DU VAL/REGUSCI POND IMPROVEMENTS VA VOLT-AMPERES VFD VARIABLE FREQUENCY DRIVE 15 C-111 STAG'S LEAP WINE CELLARS POND IMPROVEMENTS W/ WITH 16 C-112 TREATMENT PLANT SITE PLAN 17 C-113 TREATMENT PLANT DEMOLITION, GRADING AND PAVING PLAN ELECTRICAL NOTES 18 C-114 TREATMENT PLANT PIPING PLAN 1. R, RAD RC RCP RGS RD ROW, R/W RR RTU RW G-004 CP PORTLAND CEMENT CONCRETE PROPERTY LINE PROPERTY POINT POLYVINYL CHLORIDE PLASTIC 4 CEP PCC PL PROP PT PVC LEVEL INDICATING TRANSMITTER CB ON CENTER OUTSIDE DIAMETER OVERHEAD ELECTRIC LIT 19 C-115 TREATMENT PLANT SITE PLAN 20 C-501 CIVIL DETAILS - 1 21 C-502 CIVIL DETAILS - 2 22 C-503 CIVIL DETAILS - 3 EVERY EFFORT HAS BEEN MADE TO IDENTIFY REMOTE ITEMS TO BE CONNECTED BY THE ELECTRICAL CONTRACTOR, EITHER IN THE ELEMENTARIES OR IN THE SCHEDULES. HOWEVER, NOT ALL OF THE REMOTE DEVICES MAY HAVE BEEN SHOWN ON THE ELECTRICAL PLAN DRAWINGS. REFER TO THE DRAWINGS OF RESPECTIVE TRADES TO LOCATE OR CONFIRM EQUIPMENT LOCATIONS. 23 C-504 CIVIL DETAILS - 4 24 C-505 CIVIL DETAILS - 5 GROUNDING: ELECTRICAL SYSTEMS SHALL BE GROUNDED AS SPECIFIED AND SHOWN ON THE CONTRACT DRAWINGS. WORK SHALL ALSO BE PERFORMED IN ACCORDANCE WITH ARTICLE 250 OF THE MOST RECENT REVISION OF THE NATIONAL ELECTRIC CODE. REFER TO DETAILS FOR GROUNDING SCHEMATICS AND FOR GENERAL GROUNDING REQUIREMENTS OF ELECTRICAL EQUIPMENT. GROUND GRID CONNECTIONS SHOWN ON THE INDIVIDUAL PLANS ARE MINIMUM REQUIREMENTS. ALL REQUIRED CONNECTIONS ARE NOT SHOWN ON PLANS FOR BREVITY. CONTRACTOR SHALL COORDINATE NEW CONNECTIONS TO THE EXISTING GROUND GRIDS AS NECESSARY. REFER TO GROUNDING NOTES BELOW AND ELECTRICAL DETAILS FOR ADDITIONAL INFORMATION. 25 C-506 CIVIL DETAILS - 6 26 C-507 CIVIL DETAILS - 7 27 M-301 RECYCLED WATER PUMP STATION PLAN AND SECTION S-100 GENERAL STRUCTURAL NOTES 29 S-101 TRICKLING FILTER STRUCTURAL MODIFICATIONS 30 S-102 TRICKLING FILTER VALVE VAULT AND WETWELL PLANS 31 S-103 TRICKLING FILTER VALVE VAULT DETAILS 32 S-104 TRICKLING FILTER VALVE VAULT DETAILS 33 E-101 TREATMENT PLANT ELECTRICAL SITE PLAN 34 E-200 ELECTRICAL CONDUIT RISER DIAGRAM 35 E-300 GOLF COURSE PUMP CONTROL PANEL 36 E-400 RTU DETAILS 37 E-501 DECHLORINATION SYSTEM MODIFICATIONS 38 E-502 ELECTRICAL DETAILS 39 E-503 ELECTRICAL DETAILS 40 E-504 ELECTRICAL DETAILS 41 E-505 ELECTRICAL DETAILS 42 E-506 ELECTRICAL DETAILS 43 E-507 ELECTRICAL DETAILS 44 E-508 ELECTRICAL DETAILS 45 E-509 PV PANEL DETAILS 46 I-100 I&C LEGEND 47 I-101 SCADA RISER DIAGRAM 48 I-102 ELECTRICAL SCADA POLE DETAILS 49 I-103 RTU U P&ID 50 I-104 RTU R P&ID DC DIRECT CURRENT DO DISCRETE OUTPUT DS DISCONNECT SWITCH EMR EQUIPMENT MOUNTING RACK RADIUS RELATIVE COMPACTION REINFORCED CONCRETE PIPE RIGID STEEL ROAD RIGHT-OF-WAY RAILROAD REMOTE TELEMETRY UNIT RECYCLED WATER EX EXISTING S SCH SD SECT SERV SHT SIG SPEC SQ SS SSMH STA STD ST STL SOUTH SCHEDULE STORM DRAIN SECTION SERVICE SHEET SIGNAL SPECIFICATIONS SQUARE SANITARY SEWER SANITARY SEWER MANHOLE STATION STANDARD STAINLESS STEEL HOA HAND-OFF-AUTO SELECTOR-SWITCH HP HORSEPOWER TC T, TEL TG, T/G TOB TS TSP TYP TOP OF CURB TELEPHONE TOP OF GRATE TOP OF BERM TRAFFIC SIGNAL/SERVICE TWISTED SHIELDED PAIR TYPICAL FE FLOW ELEMENT FIT FLOW INDICATING TRANSMITTER FO FIBER OPTIC G OR GRD 2. 3. 4. TRUCK FILL VALVE 8" PVC RECLAIMED WATERLINE 6" PVC RECLAIMED WATERLINE 6. VALVE ACTUATOR GROUND CONTRACTOR SHALL COORDINATE FINAL CONCRETE EQUIPMENT PAD (CEP) DIMENSIONS WITH FINAL DIMENSIONS OF EQUIPMENT AND OTHER STRUCTURES TO BE MOUNTED ON PADS. REFER TO NOTES AND STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION. EXTERIOR CEP SHALL MAINTAIN 4'-0” IN FRONT OF ELECTRICAL PANELS AND 6” ON SIDES. ENCLOSURE DIMENSIONS SHOWN ON THE DRAWINGS ARE MINIMUM REQUIRED DIMENSIONS. ENCLOSURES SHALL BE SIZED TO ACCOMMODATE EQUIPMENT, CONTROLS AND COMPONENTS AS SHOWN, SPECIFIED AND REQUIRED FOR AN OPERABLE SYSTEM. EXACT EQUIPMENT CONDUIT CONNECTIONS ARE TO BE DETERMINED BY THE ELECTRICAL INSTALLER BASED UPON THE ACTUAL FIELD LOCATION OF EQUIPMENT. INSTALL CONDUIT IN ACCORDANCE WITH SPECIFICATIONS. ALL PENETRATIONS THROUGH EXISTING SOLID CONCRETE STRUCTURES WHERE SLEEVES HAVE NOT BEEN PROVIDED SHALL BE CORE DRILLED AND SIZED TO ACCEPT MECHANICAL LINK SEALS. THROUGH NON-FIRE RATED WALLS, CORE HOLE AND SEAL AROUND CONDUIT WITH NON-SHRINK GROUT. THROUGH EXTERIOR WALL SEAL WATER TIGHT WITH SILICONE MASONRY SEALANT. 4" PVC RECLAIMED WATERLINE LEVEL ELEMENT 8" DIP RECLAIMED WATERLINE 6" DIP RECLAIMED WATERLINE CHECK VALVE 7. EQUIPMENT MOUNTING RACK (EMR): THE FINAL LOCATION OF THE EMR'S SHALL BE COORDINATED IN THE FIELD TO AVOID INTERFERENCE WITH ACCESS TO THE PROCESS EQUIPMENT. REFER TO DETAILS FOR INDIVIDUAL APPLICATIONS AND LOCATIONS. 8. EQUIPMENT REMOVALS: DISCONNECT AND REMOVE POWER/CONTROL CIRCUITS AND CONDUITS FROM THE RESPECTIVE EQUIPMENT. 9. EQUIPMENT RELOCATIONS: DISCONNECT AND REMOVE POWER/CONTROL CIRCUITS AND CONDUCTORS FROM THE EQUIPMENT. EQUIPMENT SHALL BE REMOVED AND RELOCATED TO THE NEW LOCATION SHOWN ON THE CONTRACT DRAWINGS. 10. CONDUIT REMOVALS: DISCONNECT AND REMOVE EXPOSED PORTIONS OF CONDUIT FOR EQUIPMENT TO BE REMOVED AND/OR RELOCATED. CUT, THREAD, COUPLE AND CAP EXISTING CONDUITS ADJACENT TO THE PENETRATION POINT WHERE THE CONDUITS ARE CONCEALED (IN WALLS, CONCRETE SLABS, BELOW GRADE). REPAIR WALL PENETRATIONS TO A WEATHER-TIGHT CONDITION MATCHING EXISTING WALL MATERIALS. EQUIPMENT GATE VALVE POND LEVEL INDICATOR AND ELECTRICAL CONDUIT REDUCER POLE-MOUNTED CONTROL EQUIPMENT AND PV PANEL TEE EDGE OF PAVEMENT B1 GEOTECHNICAL BORINGS 90° BEND 11. ARCHAEOLOGICAL BORINGS FLOW METER ANTENNA 12. ROLL CURB METER BOX CONTRACTOR ACCESS/ HAUL ROUTES 13. EXISTING RW TURNOUT INTERMEDIATE CONTOUR CULVERT EDGE OF PAVEMENT SS PIPELINE CATCH BASIN SPOT ELEVATION FENCE INDEX CONTOUR 14. MANHOLE RW PIPELINE EQUIPMENT TO REMAIN: PROVIDE NEW FEEDER OR BRANCH CIRCUIT CONDUIT AND WIRING TO EXISTING/RELOCATED EQUIPMENT REQUIRED TO REMAIN IN SERVICE. CUT AND REUSE EXISTING CONDUIT RUNS WHERE PRACTICAL. CIRCUIT CONDUCTORS SHALL BE REPLACED THE ENTIRE LENGTH OF THE CIRCUIT RUN. ELECTRICAL PLANS: CONTRACTOR SHALL REFER TO ONE-LINES, SCHEMATICS, CONDUIT RISER DIAGRAMS AND DETAILS TO COORDINATE CONDUIT AND CIRCUIT REQUIREMENTS FOR EACH SYSTEM. FIBER OPTIC PATCH PANEL (FOPP) ENCLOSURE: ALL INDOOR FIBER OPTIC PATCH PANELS SHALL BE MOUNTED IN NEMA 12 ENCLOSURES IN ORDER TO ACCOMMODATE CONDUIT ENTRIES AND EXITS AND TO FACILITATE CONDUIT ROUTING IN THE BUILDING. ALL EXTERIOR FIBER OPTIC PATCH PANELS SHALL BE MOUNTED IN NEMA 4X ENCLOSURES. CONDUIT PENETRATIONS: WHERE CONDUITS ARE TOO LARGE FOR TERMINATION INTO CABINETS, CONTROL PANELS, INSTRUMENT ENCLOSURES OR OTHER ENCLOSURES DUE TO STANDARD KNOCK OUT SIZE, THE CONTRACTOR SHALL PROVIDE AN INTERMEDIATE PULL BOX IN ORDER TO COORDINATE A TRANSITION IN CONDUIT SIZE. THIS SHALL BE COORDINATED WITH THE ENGINEER IN THE FIELD ON A CASE BY CASE BASIS. BOLLARD 15. 16. SPARE WIRING: WHERE SPARE POWER AND CONTROL WIRING IS REQUIRED PER THE DRAWINGS AND/OR SPECIFICATIONS, SPARE WIRE SHALL BE PROVIDED WITH SUFFICIENT LENGTH TO EXTEND TO THE FURTHEST TERMINAL BLOCK/BUCKET/AREA OF THE ENCLOSURE BEING SERVED. PROVIDE NAMEPLATE TO EXISTING PANELS AND EQUIPMENT INDICATING THE EQUIPMENT'S TAG NUMBER FOR ALL EXISTING EQUIPMENT THAT IS TO BE CONNECTED TO THE RTU/SCADA FOR MONITORING AND CONTROL. Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 27 November 2013 - 2:14 PM Plotted by: Ben Langston Drawn Job Project Manager Director Cad File No: DRAWING TITLE CONDUIT OR CONDUCTOR 5. 8" PVC PS3-1 1 JB DRAWING NO. C NEW DESIGNATION FOR NEW EQUIPMENT: SHEET NO. LE LEGEND EQUIPMENT DESIGNATION INPUT/OUTPUT A OR AMP 12" W 12" DI, W I/O DRAWING INDEX 28 JOINT TRENCH LAT LF LONG 12" DI, W INCH INVERT IRRIGATION J/T PIPE DESIGNATION HORIZONTAL IN INV IRR DRAWING NUMBER SHOWN AS " - " IF TAKEN & SHOWN ON SAME SHEET. GAS GAUGE H, HORIZ SCALE: 1/4"=1'-0" EXISTING EAST EACH ELEVATION EDGE OF PAVEMENT EASEMENT EXISTING FIRE HYDRANT FLOWLINE FIRE SERVICE FEET OR FOOT G G DETAIL DRAWING NUMBER WHERE TAKEN DESIGNATION FOR NEW PIPING: DEPARTMENT DETAIL DROP INLET DIAMETER DRAWING (E) E EA EL, ELEV EP ESMT EX FH FL FS FT ON DRAWING WHERE SECTION IS SHOWN: 1 CONDUIT CATCH BASIN CONTROLLED DENSITY FILL CAST IRON CURED-IN-PLACE PIPE CLEAR CENTERLINE CORRUGATED METAL PIPE CLEANOUT CONCRETE CONTROL CENTER CULVERT DEPT DET DI DIA DWG 1 DETAIL DESIGNATION BORING BUILDING BENCH MARK BOTTOM C CB CDF CI CIPP CLR CL CMP CO CONC CNTRL CTR CULV ON DRAWING WHERE SECTION IS SHOWN: A AT AGGREGATE BASE ASBESTOS CEMENT ASSESSORS PARCEL NUMBER ELECTRICAL ABBREVIATIONS AND ELECTRICAL NOTES Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 G-002.dwg BL Designer MJ Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale NONE This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size G-002 Sht 2 of 50
  • 3. R D CONTROL POINTS SS POINT # NORTHING DESCRIPTION EASTING ELEVATION LE IL TV N U D R EL N N FI 80.94 SET NAIL AT AERIAL PANEL 1905352.16 6463204.02 76.61 SET NAIL AT AERIAL PANEL 1905780.94 6459791.17 85.67 SET NAIL AT AERIAL PANEL 1908117.50 6455949.72 145.15 SET NAIL AT AERIAL PANEL 1906589.50 6458350.20 97.80 SET NAIL AT AERIAL PANEL 1905895.06 6457683.06 106.86 SET NAIL AT AERIAL PANEL 1906563.60 6458210.20 101.37 SET NAIL AT AERIAL PANEL 1908307.06 6457487.87 103.96 SET NAIL AT AERIAL PANEL 1904864.96 6465099.96 83.79 SET NAIL AT AERIAL PANEL 1906594.91 6468391.52 81.92 SET NAIL AT AERIAL PANEL 1906999.97 6468920.74 88.53 SET NAIL AT AERIAL PANEL 1909584.23 6467279.11 134.37 SET NAIL AT AERIAL PANEL 1911651.29 6465338.64 153.40 SET NAIL AT AERIAL PANEL 1909397.25 6464425.86 128.07 SET NAIL AT AERIAL PANEL 1913252.17 6464212.92 96.29 SET NAIL AT AERIAL PANEL 421 YO 6461597.60 1905076.64 6458318.51 100.32 SET NAIL AT AERIAL PANEL 4 1906750.83 419 6 405 418 0 -1 SET NAIL AT AERIAL PANEL 417 0 -1 83.28 416 C 6461653.46 415 C 1907952.05 412 B6 404 414 C SET NAIL AT AERIAL PANEL 411 05 -1 84.68 410 B5 6459963.58 413 BERINGER POND 1906266.52 409 B4 SET NAIL AT AERIAL PANEL 408 N 91.48 407 C 6461011.03 403 07 -1 1912056.72 406 C R O 401 B7 YO UN O AD DR D * DO NOT DISTURB ANY SURVEY CONTROL OR BOUNDARY MONUMENTS. L AI TR 29 LA N LA E N STAG'S LEAP WINE CELLARS POND 11 1 C- B2 B1 0 11 C- N LA A NAP SO 2 -11 U C R TH 14 1 C- GHD TOPOGRAPHICAL GROUND SURVEY, AUGUST 2011 * AERIAL SURVEY BY 3DI WEST, FLOWN AUGUST 16, 2011 FROM EUGENE OREGON (JOB#11-06) ER AY A R IA B3 HORIZONTAL CONTROL: CALIFORNIA COORDINATE SYSTEM ZONE 2 NAD 83 * LV HW CONSTRUCTION LAUYDOWN AREA B8 VERTICAL BENCHMARK: FOUND BRASS DISK - “VET HOME” ELEVATION 94.26 NAVD 88 * 1 -11 C SI T EE TR TS G HI C O IF L N C 02 -1 C 03 -1 * O ER RIV DR C-108 CLOS DU VAL/ REGUSCI POND YOUNTVILLE JOINT TREATMENT PLANT SI LV ER MONDAVI POND O AD IL AI TR ING SH WA VI D AR Y NE W VIE DR C-109 TO C-109 NS CHIMNEY ROCK POND EE TR T 0 OVERALL SITE PLAN, KEY MAP, AND CONTROL DIAGRAM Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 6 December 2013 - 4:46 PM Plotted by: Aaron Foscato Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 G-003.dwg 600 900 1200' SCALE 1"=600' AT ORIGINAL SIZE Reuse of Documents FINAL TOWN REVIEW NFC 300 BL Designer MJ Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size G-003 Sht 3 of 50
  • 4. MITIGATION MEASURES GENERAL NOTES GENERAL NOTES PROJECT MEASURE 1: BASIC AIR QUALITY MEASURES THE CONTRACTOR SHALL IMPLEMENT THE BAY AREA AIR QUALITY MANAGEMENT DISTRICT'S BASIC CONSTRUCTION MEASURES, WHICH CONSIST OF THE FOLLOWING: 1. ALL EXPOSED SURFACES (E.G., PARKING AREAS, STAGING AREAS, SOIL PILES, GRADED AREAS, AND UNPAVED ACCESS ROADS) SHALL BE WATERED UP TO TWO TIMES PER DAY AS NECESSARY TO REDUCE DUST. ALL HAUL TRUCKS TRANSPORTING SOIL, SAND, OR OTHER LOOSE MATERIAL OFF-SITE SHALL BE COVERED. ALL VISIBLE MUD OR DIRT TRACK-OUT ONTO ADJACENT PUBLIC ROADS SHALL BE REMOVED USING WET POWER VACUUM STREET SWEEPERS AT LEAST ONCE PER DAY. THE USE OF DRY POWER SWEEPING IS PROHIBITED. ALL VEHICLE SPEEDS ON UNPAVED ROADS SHALL BE LIMITED TO 15 MPH. ALL ROADWAYS, DRIVEWAYS, AND SIDEWALKS TO BE PAVED SHALL BE COMPLETED AS SOON AS POSSIBLE. IDLING TIMES SHALL BE MINIMIZED EITHER BY SHUTTING EQUIPMENT OFF WHEN NOT IN USE OR REDUCING THE MAXIMUM IDLING TIME TO 5 MINUTES (AS REQUIRED BY THE CALIFORNIA AIRBORNE TOXICS CONTROL MEASURE TITLE 13, SECTION 2485 OF CALIFORNIA CODE OF REGULATIONS [CCR]). CLEAR SIGNAGE SHALL BE PROVIDED FOR CONSTRUCTION WORKERS AT ALL ACCESS POINTS. ALL CONSTRUCTION EQUIPMENT SHALL BE MAINTAINED AND PROPERLY TUNED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. ALL EQUIPMENT SHALL BE CHECKED BY A CERTIFIED MECHANIC AND DETERMINED TO BE RUNNING IN PROPER CONDITION PRIOR TO OPERATION. POST A PUBLICLY VISIBLE SIGN WITH THE TELEPHONE NUMBER AND PERSON TO CONTACT AT THE LEAD AGENCY REGARDING DUST COMPLAINTS. THIS PERSON SHALL RESPOND AND TAKE CORRECTIVE ACTION WITHIN 48 HOURS. THE AIR DISTRICT'S PHONE NUMBER SHALL ALSO BE VISIBLE TO ENSURE COMPLIANCE WITH APPLICABLE REGULATIONS. 2. 3. 4. 5. 6. 7. 8. PROJECT MEASURE 2: TRAFFIC CONTROL PLAN THE CONTRACTOR SHALL DEVELOP A TRAFFIC CONTROL PLAN TO MINIMIZE THE IMPACTS OF CONSTRUCTION TRAFFIC ON PROJECT AREA ROADWAYS AND AT KEY INTERSECTIONS USED DURING CONSTRUCTION. THE TRAFFIC CONTROL PLAN SHALL INCLUDE THE FOLLOWING PROVISIONS AND MAY INCLUDE OTHER MEASURES IF A FURTHER NEED IS IDENTIFIED. 1. 2. LOCATION(S) OF DESIGNATED PROJECT CONSTRUCTION STAGING AREAS. POST WARNING SIGNAGE AT POINTS WHERE CONSTRUCTION TRAFFIC WILL ENTER OR LEAVE SOLANO DR, LAND LANE, AND SILVERADO TRAIL USE FLAG CONTROL DURING WORK HOURS WHEN EQUIPMENT OR MATERIALS ARE DELIVERED TO THE WORK AREA. DETOUR ROUTES TO BE USED IN ORDER TO MAINTAIN ACCESS DURING VARIOUS PHASES OF THE PROJECT'S CONSTRUCTION. RESTRICT ALL CONSTRUCTION TRAFFIC TO NORMAL DAYTIME BUSINESS HOURS, UNLESS THE TOWN IDENTIFIES A NEED FOR OFF-HOURS ROUTING TO AVOID IMPACTS ON PEAK-HOUR COMMUTE TRAFFIC. CONSULT WITH THE NAPA COUNTY FIRE DEPARTMENT AND PROVIDE NOTIFICATION OF THE TIMING, LOCATION, AND DURATION OF CONSTRUCTION IN THE VICINITY OF THE YOUNTVILLE FIRE STATION. IN ORDER TO MINIMIZE ANY POTENTIAL OVERLAP WITH OTHER CONSTRUCTION AND ROADWAY IMPROVEMENT PROJECT(S), THE CONTRACTOR SHALL WORK WITH THE TOWN AND NAPA COUNTY TO IDENTIFY THE ROUTES AND INTERSECTIONS THAT SHOULD BE AVOIDED, AS WELL AS APPROPRIATE ALTERNATE TRAVEL ROUTES OR TIMES. THE PLAN SHALL ADDRESS ROUTES TO MINIMIZE CONSTRUCTION TRAFFIC ON STATE HIGHWAY 29 DURING PEAK HOURS. 3. 4. 5. 6. IN THE CASE OF AN UNANTICIPATED ARCHAEOLOGICAL DISCOVERY, IF IT IS DETERMINED THAT THE FIND IS UNIQUE UNDER THE NATIONAL HISTORIC PRESERVATION ACT (NHPA) AND/OR POTENTIALLY ELIGIBLE FOR LISTING IN THE NATIONAL REGISTER, AND THE SITE CANNOT BE AVOIDED, THE CONTRACTOR SHALL DEVELOP A RESEARCH DESIGN AND EXCAVATION PLAN, PREPARED BY AN ARCHAEOLOGIST, OUTLINING RECOVERY OF THE RESOURCE, ANALYSIS, AND REPORTING OF THE FIND. TREATMENT AND RESOLUTION MAY INCLUDE MODIFYING THE PROJECT TO ALLOW THE MATERIALS TO BE LEFT IN PLACE, OR UNDERTAKING DATA RECOVERY OF THE MATERIALS IN ACCORDANCE WITH STANDARD ARCHAEOLOGICAL METHODS; PROTECTION AND PRESERVATION OF RESOURCES IS PREFERABLE IF FEASIBLE. THE RESEARCH DESIGN AND EXCAVATION PLAN SHALL BE SUBMITTED TO RECLAMATION STAFF WHO WOULD NOTIFY THE SHPO AND THE NATIVE AMERICAN REPRESENTATIVES. RECLAMATION AND THE SWRCB SHALL APPROVE THE PLAN PRIOR TO CONSTRUCTION BEING RESUMED. IN THE EVENT THAT THE CONTRACTOR MUST WORK IN THE STATE RIGHT-OF-WAY (I.E. STATE HIGHWAY 29), THE CONTRACTOR SHALL SUBMIT A STANDARD ENCROACHMENT PERMIT APPLICATION TO CALTRANS DURING THE DESIGN OF PHASE 3 OF THE PROJECT. IF AN UNANTICIPATED ARCHAEOLOGICAL DISCOVERY DURING GROUND-DISTURBING ACTIVITIES OCCURS WITHIN THE STATE RIGHT-OF-WAY, THE CALTRANS OFFICE OF CULTURAL RESOURCE STUDIES, DISTRICT 4, SHALL BE CONTACTED. MITIGATION MEASURE CR-6: PROCEDURES FOR ENCOUNTERING HUMAN REMAINS IF HUMAN REMAINS ARE DISCOVERED, POTENTIALLY DAMAGING ACTIVITIES SHALL BE HALTED AND NO FURTHER EXCAVATION OF THE REMAINS OR NEARBY AREA CAN OCCUR UNTIL THE NAPA COUNTY CORONER HAS MADE NECESSARY FINDINGS AS TO THE ORIGIN OF THE REMAINS, IN ACCORDANCE WITH THE HEALTH AND SAFETY CODE 7050.5. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COUNTY CORONER AND A PROFESSIONAL ARCHAEOLOGIST TO DETERMINE THE NATURE OF THE REMAINS. AT THE SAME TIME, AN ARCHAEOLOGIST SHALL BE CONTACTED TO EVALUATE THE SITUATION. AS THE PROPERTY HAS BEEN REPEATEDLY TILLED AND GRADED, THE POSSIBILITY EXISTS THAT HUMAN REMAINS MAY BE FRAGMENTARY AND MIXED WITH SURROUNDING SOILS. IF HUMAN REMAINS ARE ENCOUNTERED, ALL GROUND DISTURBANCE WITHIN A 50 FEET DIAMETER AREA SHALL BE HALTED UNTIL THE ARCHAEOLOGIST AND THE CORONER HAVE REVIEWED THE REMAINS. IF THE CORONER DETERMINES THAT THE REMAINS ARE OF NATIVE AMERICAN ORIGIN, THE TOWN SHALL NOTIFY THE NATIVE AMERICAN HERITAGE COMMISSION WITHIN 24 HOURS OF IDENTIFICATION, AS WELL AS THE RECLAMATION REPRESENTATIVE. THE COMMISSION THEN NOTIFIES THE MOST LIKELY DESCENDANT, WHO HAS 48 HOURS TO MAKE RECOMMENDATIONS TO THE LANDOWNER FOR THE DISPOSITION OF THE REMAINS. REMAINS SHALL BE TREATED IN ACCORDANCE WITH PUBLIC RESOURCES CODE §5097.9. 2. CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS AND PAY ALL FEES PRIOR TO COMMENCEMENT OF ANY WORK EXCEPT THOSE SPECIFICALLY NOTED IN SPECIFICATIONS AS PROVIDED BY TOWN OF YOUNTVILLE 3. CONTRACTOR SHALL OBTAIN AN ENCROACHMENT PERMIT FROM NAPA COUNTY, CA BEFORE START OF WORK. CONTRACTOR SHALL COMPLY WITH ALL REQUIREMENTS OF THE PERMIT WORK HOURS ARE LIMITED TO MONDAY THROUGH FRIDAY 8 A.M. TO 5 P.M. AT THE PROJECT SITE AND 7:30 A.M. TO 4 P.M. AT THE TREATMENT PLANT. TIME AT THE TREATMENT PLANT HAS SOME FLEXIBILITY; HOWEVER DIFFERING HOURS NEED TO BE COORDINATED WITH DON MOORE, UTILITY OPERATIONS SUPERVISOR. INSPECTION WILL BE AVAILABLE MONDAY THROUGH FRIDAY FROM 8 A.M. TO 4 P.M. ANY WEEKEND WORK IS SUBJECT TO TOWN APPROVAL. 5. PRE-CONSTRUCTION MEETING IS REQUIRED PRIOR TO BEGINNING OF WORK. CONTACT THE ENGINEER TO SCHEDULE SUCH MEETING. 6. IF PALEONTOLOGICAL RESOURCES (E.G., VERTEBRATE BONES, TEETH, OR ABUNDANT AND WELL-PRESERVED INVERTEBRATES OR PLANTS) ARE ENCOUNTERED DURING CONSTRUCTION, THE TOWN SHALL HALT GROUND-DISTURBING WORK IN THE VICINITY OF THE FIND. WORK NEAR THE FIND SHALL NOT BE RESUMED UNTIL A QUALIFIED PALEONTOLOGIST HAS EVALUATED THE MATERIALS AND OFFER RECOMMENDATIONS FOR FURTHER ACTION, INCLUDING SALVAGE OF ANY SIGNIFICANT PALEONTOLOGICAL RESOURCES. ANY DISCREPANCY DISCOVERED BY CONTRACTOR IN THESE PLANS OR ANY FIELD CONDITIONS DISCOVERED BY CONTRACTOR THAT MAY DELAY OR OBSTRUCT THE PROPER COMPLETION OF THE WORK PER THESE PLANS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND THE OWNER IMMEDIATELY UPON DISCOVERY. SAID NOTIFICATION SHALL BE IN WRITING. 4. MITIGATION MEASURE CR-5: PROTECTION AND PRESERVATION OF PALEONTOLOGICAL MATERIALS 1. WITHIN 48 HOURS OF PAVING, ALL WATER VALVE BOXES WILL BE BROUGHT TO GRADE AND INSPECTION REQUESTED. GENERAL UNDERGROUND NOTES 1. NO GUARANTEE IS INTENDED THAT UNDERGROUND OBSTRUCTIONS NOT SHOWN ON THESE PLANS MAY BE ENCOUNTERED. THOSE SHOWN ARE BASED ON THE BEST INFORMATION AVAILABLE AND THE CONTRACTOR IS CAUTIONED THAT THE OWNER, THE ENGINEERS, AND THE TOWN OF YOUNTVILLE ASSUME NO RESPONSIBILITY FOR ANY OBSTRUCTIONS EITHER SHOWN OR NOT SHOWN ON THESE PLANS. THE CONTRACTOR SHALL COOPERATE WITH ALL UTILITY COMPANIES WORKING WITHIN THE LIMITS OF THIS PROJECT. 2. CONTRACTOR SHALL NOT BEGIN EXCAVATION UNTIL ALL EXISTING UTILITIES HAVE BEEN MARKED IN THE FIELD BY THE APPLICABLE ENTITY RESPONSIBLE FOR THAT PARTICULAR UTILITY. THE CONTRACTOR SHALL NOTIFY EACH APPLICABLE ENTITY AT LEAST 24 HOURS BEFORE STARTING WORK. 3. UNDERGROUND SERVICE ALERT: CALL TOLL FREE (800) 642-2444 AT LEAST 48 HOURS PRIOR TO EXCAVATION. 4. CONTRACTOR SHALL UNCOVER EXISTING BURIED UTILITIES IN THE PRESENCE OF UTILITY OWNER TO VERIFY LOCATIONS AND ELEVATIONS OF UTILITIES. BURIED UTILITIES INCLUDE, BUT ARE NOT LIMITED TO, WATER MAINS AND SERVICES, SEWER MAINS AND LATERALS, STORM DRAINS, GAS MAINS AND LATERALS, ELECTRICAL DISTRIBUTION LINES, TELEPHONE AND CABLE TV LINES. ALL UTILITIES CONFLICTING WITH THE PROPOSED CONSTRUCTION SHALL BE RELOCATED OR RESOLVED PRIOR TO THE START OF CONSTRUCTION, OR CONFLICTING FACILITIES 5. ALL UNDERGROUND IMPROVEMENTS SHALL BE INSTALLED AND APPROVED PRIOR TO PAVING. 6. ALL MATERIAL, WORKMANSHIP AND CONSTRUCTION DETAILS SHALL CONFORM TO THE TOWN OF YOUNTVILLE CONSTRUCTION STANDARD SPECIFICATIONS, INCLUDING ALL ADDENDA, STANDARD PLAN AND SPECIAL PROVISION REVISIONS. IF CONSTRUCTION DEWATERING IS REQUIRED, THE TOWN SHALL EVALUATE REASONABLE OPTIONS FOR DEWATERING MANAGEMENT. THE FOLLOWING MANAGEMENT OPTIONS SHALL BE CONSIDERED: 7. ITEMS SPECIFIED ON THE STANDARD PLANS ARE APPROVED FOR USE BY THE TOWN OF YOUNTVILLE. ALL SUBSTITUTES OR ALTERATIONS SHALL BE SUBMITTED TO THE TOWN OF YOUNTVILLE FOR REVIEW AND APPROVAL. 1. 2. 3. RECYCLED WATER SYSTEM MITIGATION MEASURE HYD- 1: STORM WATER POLLUTION PREVENTION PLAN THE CONTRACTOR SHALL IMPLEMENT THE FOLLOWING MEASURES TO AVOID IMPACTS TO CALIFORNIA RED-LEGGED FROGS (CRLF) DURING CONSTRUCTION WITHIN 50 FEET OF THE AGRICULTURAL IRRIGATION PONDS: THE CONTRACTOR SHALL OBTAIN COVERAGE UNDER SWRCB (STATE WATER RESOURCES CONTROL BOARD) ORDER NO. 2009-0009-DWQ, WASTE DISCHARGE REQUIREMENTS FOR DISCHARGES OF STORM WATER RUNOFF ASSOCIATED WITH CONSTRUCTION AND LAND DISTURBANCE ACTIVITIES. THE CONTRACTOR SHALL SUBMIT PERMIT REGISTRATION DOCUMENTS (NOTICE OF INTENT, RISK, ASSESSMENT, SITE MAPS, SWPPP, ANNUAL FEE, AND CERTIFICATIONS) TO THE STATE WATER RESOURCES CONTROL BOARD. THE SWPPP SHALL ADDRESS POLLUTANT SOURCES, NON-STORM WATER DISCHARGES RESULTING FROM CONSTRUCTION DEWATERING, BEST MANAGEMENT PRACTICES, AND OTHER REQUIREMENTS SPECIFIED IN THE ORDER. THE BMPS SHALL INCLUDE ANY MEASURES INCLUDED IN THE EROSION AND SEDIMENT CONTROL PLANS DEVELOPED FOR THE PROJECT TO MINIMIZE DISTURBANCE AFTER GRADING OR CONSTRUCTION. THE SWPPP SHALL ALSO INCLUDE DUST CONTROL PRACTICES TO PREVENT WIND EROSION, SEDIMENT TRACKING AND DUST GENERATION BY CONSTRUCTION EQUIPMENT. THE CONTRACTOR SHALL ENSURE THAT A QUALIFIED SWPPP PRACTITIONER OVERSEES IMPLEMENTATION OF THE SWPPP, INCLUDING VISUAL INSPECTIONS, SAMPLING AND ANALYSIS, AND ENSURING OVERALL COMPLIANCE. 1. MITIGATION MEASURE HYD- 2: CONSTRUCTION DEWATERING 7. MITIGATION MEASURE BIO-1: AVOID IMPACTS TO CALIFORNIA RED-LEGGED FROG GROUND DISTURBING CONSTRUCTION ACTIVITIES SHALL BE LIMITED TO THE DRY SEASON PERIOD FROM APRIL 1 THROUGH NOVEMBER 1 TO AVOID POTENTIAL RED-LEGGED FROG DISPERSAL EVENTS. A QUALIFIED BIOLOGIST, HIRED BY THE CONTRACTOR BUT APPROVED BY THE TOWN, SHALL CONDUCT A PRE-CONSTRUCTION SURVEY IMMEDIATELY PRECEDING ANY CONSTRUCTION ACTIVITY WITHIN 50 FEET OF THE IRRIGATION PONDS. THE BIOLOGIST SHALL REMAIN ON-SITE DURING GROUND DISTURBING CONSTRUCTION WITHIN 50 FEET OF A POND. IF A CRLF IS ENCOUNTERED DURING CONSTRUCTION, ALL CONSTRUCTION ACTIVITIES IN THE IMMEDIATE AREA SHALL CEASE UNTIL THE ANIMAL MOVES AWAY OF ITS OWN VOLITION. CONSTRUCTION CANNOT BEGIN UNTIL THE CRLF HAS LEFT THE CONSTRUCTION AREA. IF CRLF DO NOT LEAVE THE SITE TO ALLOW FOR CONSTRUCTION, THE TOWN SHALL CONTACT USFWS FOR DIRECTION ON HOW TO PROCEED. PRIOR TO THE START OF CONSTRUCTION, A USFWS-APPROVED BIOLOGIST SHALL TRAIN ALL CONSTRUCTION PERSONNEL REGARDING HABITAT SENSITIVITY, IDENTIFICATION OF SPECIAL STATUS SPECIES, AND REQUIRED PRACTICES BEFORE THE START OF CONSTRUCTION. BECAUSE DUSK AND DAWN ARE OFTEN THE TIMES WHEN CRLF ARE MOST ACTIVELY FORAGING AND DISPERSING, ALL CONSTRUCTION ACTIVITIES SHALL CEASE ONE-HALF HOUR BEFORE SUNSET AND SHALL NOT BEGIN PRIOR TO ONE-HALF HOUR BEFORE SUNRISE. ALL VEHICLE PARKING SHALL BE RESTRICTED TO PREVIOUSLY DETERMINED STAGING AREAS OR EXISTING ROADS. THE FUELING AND MAINTENANCE OF VEHICLES AND OTHER EQUIPMENT SHALL OCCUR AT LEAST 20 METERS (65 FEET) FROM ANY RIPARIAN HABITAT OR WATER BODY. 2. 3. 4. 5. 6. IF CONSTRUCTION IS SCHEDULED TO START BETWEEN JANUARY 31 AND OCTOBER 1, A QUALIFIED BIOLOGIST, HIRED BY THE CONTRACTOR BUT APPROVED BY THE TOWN, SHALL CONDUCT PRECONSTRUCTION NESTING SURVEYS WITHIN 48 HOURS OF CONSTRUCTION FOR NESTING PASSERINES (SMALL SONGBIRDS) AND RAPTORS. TREES WITHIN A 200-FOOT RADIUS SHALL BE INCLUDED IN THE SURVEYS. IF ACTIVE NESTS ARE LOCATED IN THE WORK AREA, THE BIOLOGIST, IN CONSULTATION WITH CDFG, (CALIFORNIA DEPARTMENT OF FISH AND GAME), SHALL ESTABLISH AN APPROPRIATELY SIZED BUFFER AROUND THE NEST IN WHICH NO WORK WILL BE ALLOWED UNTIL THE YOUNG HAVE SUCCESSFULLY FLEDGED. A MINIMUM OF A 50-FOOT BUFFER ZONE SHALL BE PLACED AROUND PASSERINE NESTS AND 250-FOOT BUFFERS SHALL BE PLACED AROUND RAPTOR NESTS. IF A QUALIFIED BIOLOGIST DETERMINES THAT LESS OF A BUFFER ZONE IS ACCEPTABLE, THE SIZE OF THE BUFFER ZONE MAY BE REDUCED UPON APPROVAL BY CDFG. BIO-3: AVOID OR RESTORE JURISDICTIONAL WETLANDS AND WATERS TEMPORARILY AFFECTED BY THE CONTRACTOR SHALL IMPLEMENT AVOIDANCE AND MINIMIZATION MEASURES, INCLUDING BEST MANAGEMENT PRACTICES (BMPS), TO PROTECT JURISDICTIONAL WETLANDS AND WATERS DURING CONSTRUCTION. MATERIALS AND FLUIDS GENERATED BY CONSTRUCTION ACTIVITIES SHALL BE PLACED AT LEAST 25 FEET AWAY FROM WETLAND AREAS OR DRAINAGES UNTIL THEY CAN BE DISPOSED OF AT A PERMITTED SITE. ALL WETLANDS AND WATERS AREAS LOCATED ADJACENT TO THE CONSTRUCTION ZONE THAT COULD BE AFFECTED BY CONSTRUCTION ACTIVITIES SHALL BE TEMPORARILY FENCED OFF AND DESIGNATED AS ENVIRONMENTALLY SENSITIVE AREAS TO PREVENT ACCIDENTAL INTRUSION BY WORKERS AND EQUIPMENT. IF DISCHARGING TO THE SANITARY SEWER, THE TOWN SHALL ISSUE A ONE-TIME DISCHARGE PERMIT OR OTHER TYPE OF APPROVAL REQUIRING, AS NECESSARY, MEASURES FOR CHARACTERIZING THE DISCHARGE AND ENSURING FILTERING METHODS AND MONITORING TO VERIFY THAT THE DISCHARGE IS COMPLIANT WITH THE TOWN'S LOCAL WASTEWATER DISCHARGE REQUIREMENTS. IF DISCHARGING TO A LOCAL SURFACE WATER OR STORM DRAIN, THE DISCHARGE SHALL BE MANAGED AS A NON-STORM WATER DISCHARGE AND CONTROL MEASURES SHALL BE INCLUDED IN THE SWPPP PREPARED UNDER ORDER NO. 2009-0009-DWQ. THE CONTRACTOR SHALL CHARACTERIZE THE GROUNDWATER PRIOR TO DISCHARGE AND IMPLEMENT CONTROL MEASURES, SUCH AS SETTLING AND/OR FILTRATION TO ENSURE THAT EXCESSIVE SEDIMENT IS NOT DISCHARGED, AND MANAGE DISCHARGE RATES TO PREVENT EROSION DOWNSTREAM. 1. 2. 3. INSTALL PIPELINES WHEN WETLANDS AND STREAMS ARE DRY. RESTORE ORIGINAL CONTOURS AND DRAINAGE PATTERNS, BOTH INTO AND OUT OF THE WETLAND. SPREAD A COVER OF STRAW, RICE STRAW IF AVAILABLE, OVER DISTURBED SOILS AND WORK INTO SOIL. THIS PRACTICE SHALL NOT BE IMPLEMENTED IN WETLAND SOILS. APPLY AN ORGANICALLY BASED TACKIFIER ON DISTURBED AREAS TO REDUCE AIR AND WATER EROSION OF SOILS. PLANTS SHALL BE INSTALLED, MAINTAINED AND REPLACED SUCH THAT 70 PERCENT OF THE DESIGN PLANT DENSITY IS PRESENT ON THE FIVE-YEAR ANNIVERSARY OF PLANT INSTALLATION. 4. 5. THERE SHALL BE A FIVE HOUR MAXIMUM SHUTDOWN TIME OF EXISTING MAINS WHILE MAKING CONNECTION. TWENTY-FOUR HOUR NOTICE OF SHUTDOWN TO BE GIVEN TO TOWN AND ALL WATER CUSTOMERS BY CONTRACTOR. EXISTING VALVES ARE TO BE OPERATED BY TOWN PERSONNEL ONLY. NO WATER MAIN CONNECTIONS ARE PERMITTED ON FRIDAY OR ON ANY DAY PRECEDING A HOLIDAY. 2. START EXCAVATION BY EXPOSING CONNECTION POINT TO EXISTING MAIN TO DETERMINE ITS LINE AND GRADE. START NEW MAIN 8-10 FEET FROM AND ON SAME GRADE (AND LINE IF APPLICABLE) AS EXISTING MAIN. 3. ALL TRENCHING, BACKFILL AND RESURFACING REQUIRED FOR INSTALLATION OF RECYCLED WATER SYSTEM FACILITIES SHALL BE PER TOWN OF YOUNTVILLE STANDARD DRAWINGS. ONLY TOWN OF YOUNTVILLE PERSONNEL SHALL OPERATE VALVES ON EXISTING WATER MAINS OR WATER SERVICES. 5. ALL METER BOXES, VAULTS AND PITS SHALL BE BEDDED ON A 3" MINIMUM THICK, 3/4" DRAIN ROCK, CL ll AB, OR OTHER CLEAN MATERIAL WITH SAND EQUIVALENT OF 20 MINIMUM, UNCONTAMINATED BY NATIVE SOIL, AGAINST COMPACTED OR UNDISTURBED BASE. THE GRAVEL BED SHALL EXTEND TO A MINIMUM OF 4" BEYOND ALL SIDES OF THE METER BOX. BOX SHALL BE SET FLUSH WITH TOP OF CURB, SIDEWALK OR GROUND, WHICHEVER IS APPLICABLE. 6. BEFORE COMBUSTIBLE MATERIALS MAY BE STORED OR CONSTRUCTED ON SITE, THE FIRE DEPARTMENT MUST APPROVE FIRE FLOW AND ACCESS. 7. AFTER A STREET HAS BEEN PAVED, ALL WATER VALVE BOXES WILL BE MARKED IN WHITE PAINT BEFORE THE CLOSE OF THAT WORK DAY. MITIGATION MEASURE NOI-1: NOISE REDUCTION MEASURES DURING PROJECT CONSTRUCTION, THE CONTRACTOR(S) SHALL IMPLEMENT THE FOLLOWING MEASURES SUCH THAT NOISE FROM CONSTRUCTION DOES NOT EXCEED 70 DBA AT NOISE-SENSITIVE USES DURING DAYTIME HOURS. 1. 2. 3. 4. 5. THE FOLLOWING MEASURES SHALL BE IMPLEMENTED WHERE CONSTRUCTION IMPACTS TO JURISDICTIONAL WATERS AND WETLANDS CANNOT FEASIBLY BE AVOIDED. A WETLAND AND WATERS RESTORATION PLAN SHALL BE PREPARED PRIOR TO CONSTRUCTION. THE RESTORATION SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING MEASURES: 1. 4. MITIGATION MEASURE BIO-2: CONDUCT PRECONSTRUCTION NESTING SURVEYS FOR NESTING PASSERINES AND RAPTORS MITIGATION MEASURE CONSTRUCTION REUSE THE WATER ON-SITE FOR DUST CONTROL, COMPACTION, OR IRRIGATION. RETAIN THE WATER ON-SITE IN A GRASSY OR POROUS AREA TO ALLOW INFILTRATION/EVAPORATION. DISCHARGE (BY PERMIT) TO A SANITARY SEWER OR SURFACE WATER (THIS OPTION MAY REQUIRE A TEMPORARY METHOD TO FILTER SEDIMENT-LADEN WATER PRIOR TO DISCHARGE). 6. CONSTRUCTION WORK HOURS ARE LIMITED TO MONDAY THROUGH FRIDAY 8 A.M. TO 5 P.M. AT THE PROJECT SITE AND 7:30 A.M. TO 4 P.M. AT THE TREATMENT PLANT. USE QUIETEST AVAILABLE EQUIPMENT AND ELECTRICALLY-POWERED EQUIPMENT, RATHER THAN INTERNAL COMBUSTION ENGINES WHERE FEASIBLE. EQUIPMENT AND ON-SITE TRUCKS USED FOR PROJECT CONSTRUCTION SHALL UTILIZE THE BEST AVAILABLE NOISE CONTROL TECHNIQUES (E.G., IMPROVED MUFFLERS, EQUIPMENT REDESIGN, USE OF INTAKE SILENCERS, DUCTS, ENGINE ENCLOSURES, AND ACOUSTICALLY ATTENUATING SHIELDS OR SHROUDS, WHEREVER FEASIBLE). ALL CONSTRUCTION EQUIPMENT SHALL BE INSPECTED AT PERIODIC INTERVALS TO ENSURE PROPER MAINTENANCE AND RESULTING LOWER NOISE LEVELS. IMPACT TOOLS (E.G., JACK HAMMERS, PAVEMENT BREAKERS) USED FOR PROJECT CONSTRUCTION SHALL BE HYDRAULICALLY OR ELECTRICALLY POWERED WHEREVER POSSIBLE TO AVOID NOISE ASSOCIATED WITH COMPRESSED-AIR EXHAUST FROM PNEUMATICALLY POWERED TOOLS. AN EXHAUST MUFFLER ON THE COMPRESSED-AIR EXHAUST SHALL BE USED; THIS MUFFLER CAN LOWER NOISE LEVELS FROM THE EXHAUST BY UP TO ABOUT 10 DBA. EXTERNAL JACKETS ON THE TOOLS THEMSELVES SHALL BE USED WHERE FEASIBLE, WHICH COULD ACHIEVE A REDUCTION OF 5 DBA. A PRECONSTRUCTION MEETING SHALL BE HELD BETWEEN THE JOB INSPECTORS AND THE CONTRACTOR/ON-SITE PROJECT MANAGER TO CONFIRM THAT NOISE MITIGATION AND PRACTICES ARE COMPLETED PRIOR TO COMMENCEMENT OF CONSTRUCTION (INCLUDING CONSTRUCTION HOURS, NEIGHBORHOOD NOTIFICATION, ETC.). AN ON-SITE COMPLAINT AND ENFORCEMENT MANAGER SHALL BE POSTED TO RESPOND TO AND TRACK ANY NOISE COMPLAINTS. THE MANAGER SHALL BE RESPONSIBLE FOR RESPONDING TO ANY COMPLAINTS REGARDING CONSTRUCTION NOISE AND FOR COORDINATING WITH THE ADJACENT LAND USES. THE MANAGER SHALL DETERMINE THE CAUSE OF ANY COMPLAINTS AND COORDINATE WITH THE CONSTRUCTION TEAM TO IMPLEMENT EFFECTIVE MEASURES (CONSIDERED TECHNICALLY AND ECONOMICALLY FEASIBLE) WARRANTED TO CORRECT THE PROBLEM. THE TELEPHONE NUMBER OF THE ON-SITE COMPLAINT AND ENFORCEMENT MANAGER SHALL BE POSTED AT THE CONSTRUCTION SITE AND PROVIDED TO NEIGHBORS IN A NOTIFICATION LETTER. THE MANAGER SHALL BE TRAINED TO USE A SOUND LEVEL METER AND SHOULD BE AVAILABLE DURING ALL CONSTRUCTION HOURS TO RESPOND TO COMPLAINTS. MITIGATION MEASURE CR-4: TREATMENT OF ARCHAEOLOGICAL RESOURCES DISCOVERED DURING CONSTRUCTION IF ARCHAEOLOGICAL MATERIALS ARE ENCOUNTERED DURING CONSTRUCTION ACTIVITIES, THE PIECE OF EQUIPMENT THAT ENCOUNTERS THE MATERIALS MUST BE STOPPED, AND THE FIND INSPECTED BY A QUALIFIED ARCHAEOLOGIST, HIRED BY THE CONTRACTOR BUT APPROVED BY THE TOWN, TO EVALUATE THE MATERIALS AND RECOMMEND APPROPRIATE TREATMENT. PREHISTORIC ARCHAEOLOGICAL MATERIALS MIGHT INCLUDE OBSIDIAN AND CHERT FLAKED-STONE TOOLS (E.G., PROJECTILE POINTS, KNIVES, SCRAPERS) OR TOOLMAKING DEBRIS; CULTURALLY DARKENED SOIL (“MIDDEN”) CONTAINING HEAT-AFFECTED ROCKS, ARTIFACTS, OR SHELLFISH REMAINS; AND STONE MILLING EQUIPMENT (E.G., MORTARS, PESTLES, HANDSTONES, OR MILLING SLABS); AND BATTERED STONE TOOLS, SUCH AS HAMMERSTONES AND PITTED STONES. HISTORIC PERIOD MATERIALS MIGHT INCLUDE STONE, CONCRETE, OR ADOBE FOOTINGS AND WALLS; FILLED WELLS OR PRIVIES; AND DEPOSITS OF METAL, GLASS, AND/OR CERAMIC REFUSE. Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 25 November 2013 - 1:32 PM Plotted by: Ben Langston Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 G-004.dwg BL Designer MJ Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale NONE This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size G-004 Sht 4 of 50
  • 5. GENERAL NOTES 1. 2. 154' RE-SEED DISTURBED AREA CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS PRIOR TO CONSTRUCTION. (GAS AND IRRIGATION) 4. 96 CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF VINEYARD UTILITIES, GASLINES AND IRRIGATION WITHIN PROPOSED ALIGNMENT PRIOR TO CONSTRUCTION. 3. 96 CONTRACTOR SHALL FIELD VERIFY LOCATION AND DEPTH OF EXISTING RECYCLED WATER MAIN FOR CONNECTION WITH NEW MAIN. CONTRACTOR TO FIELD VERIFY EXISTING GASLINE LOCATION PRIOR TO CONSTRUCTION. 508' ASPHALT REPLACEMENT STA. 29+03 GRADE BREAK 8" 22.5° BEND STA. 28+04 8" 11.25° BEND STA. 28+20 GRADE BREAK 8" 22.5° BEND STA. 27+92 STA. 27+66 8" 11.25° BEND STA. 27+46 8" 45° BEND STA. 26+93 8" 90° BEND 88 STA. 26+41 8" GATE VALVE 92 STA. 26+38 EX. 8" RW 92 88 DEMOLITION SAWCUT, REMOVE AND DISPOSE ASPHALT CONCRETE (APPROXIMATELY 3" THICK) 80 POSITIVE SLOPE 8" PVC C-900 RW LINE S IVE SIT PO 76 80 ELEVATION 84 3' MIN COVER 84 3.36' ELEVATION (E) GROUND 2034 SF 450 SF REMOVE AND REPLACE RIPRAP IN KIND PER DTL 4, SHEET C-505 E LOP CONSTRUCTION CONNECT TO EXISTING RECYCLED WATERLINE PER DTL. 1, SHEET C-505. 76 POSITIVE SLOPE 8" PVC C-900 RW LINE 1 EA INSTALL 8" C900 CLASS 150 PVC RECLAIMED WATERLINE INSTALL 8" GATE VALVE, BOX AND COVER PER DTL 4, SHEET C-503 72 72 672 LF 1 EA INSTALL ASPHALT REPLACEMENT PER DTL 2 SHEET C-503 RE-SEED DISTURBED AREA PER SPECIFICATIONS, 16' WIDTH 68 26+00 27+00 28+00 29+00 31+00 30+00 226 SY 274 SY 68 33+00 32+00 PARCEL LINE (TYP.) EDGE OF ROAD (TYP.) 27 28+00 LAND LANE E 00'42" N30° 4' 37.9 E '52" °57 0' 6 N1 0.0 2 12'00 "W 27+00 53.34' N59°1 8'00"E 54.83 ' N42°48'00"E 40.00' 30+00 8" PVC 31+00 8" PVC 32+00 19' 4' 26 25 15' WIDE TEMP. CONSTRUCTION EASEMENT EDGE OF VINEYARD (TYP.) 24 N 29 ° 26+38 8" PVC N44°57'41"E 573.00' 29+00 GASLINE - APPROXIMATE LOCATION MATCHLINE STA 33+00 SEE DRAWING C-103 RECYCLED WATERLINE PROFILE - BERINGER CONTROL POINTS POINT # NORTHING EASTING DESCRIPTION 21 1907538.98 6461319.99 APPROX. CONNECT TO EX. 8" RW 22 1907540.80 6461323.00 VALVE 23 1907566.97 6461367.13 8" 90° BEND 24 1907613.54 6461341.12 8" 45° BEND 25 1907632.10 6461346.77 8" 11.25° BEND 26 1907665.52 6461365.92 8" 11.25° BEND 27 1907694.87 6461393.10 8" DEFLECTION 22 21 23 LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. HORIZONTAL 1"=40' 0 AT ORIGINAL SIZE Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 6 December 2013 - 6:35 PM Plotted by: Aaron Foscato Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-101 to C-107.dwg RS 40' 60' 80' VERTICAL 1"=4' AT ORIGINAL SIZE RECYCLED WATERLINE PLAN - BERINGER 20' 2' 4' 6' 8' Designer MJ 0 Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-102 Sht 7 of 50
  • 6. GENERAL NOTES 1. 2. CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS PRIOR TO CONSTRUCTION. 3. 96 CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO CONSTRUCTION. CONTRACTOR TO FIELD VERIFY EXISTING GASLINE LOCATION PRIOR TO CONSTRUCTION. 96 650' ASPHALT REPLACEMENT 92 92 88 88 DEMOLITION (E) GROUND 84 80 80 POSITIVE SLOPE 2600 SF ELEVATION 84 3' MIN COVER ELEVATION SAWCUT, REMOVE AND DISPOSE ASPHALT CONCRETE (APPROXIMATELY 3" THICK) 8" PVC C-900 RW LINE CONSTRUCTION 76 76 289 SY 72 68 650 LF INSTALL ASPHALT REPLACEMENT PER DTL 2 SHEET C-503 72 INSTALL 8" C900 CLASS 150 PVC RECLAIMED WATERLINE 68 39+50 33+00 34+00 35+00 36+00 38+00 37+00 39+00 RECYCLED WATERLINE PROFILE - BERINGER 8" PVC 35+00 34+00 36+00 8" PVC 15' WIDE TEMP. CONSTRUCTION EASEMENT EDGE OF VINEYARD (TYP.) LAND LANE GASLINE - APPROXIMATE LOCATION 37+00 8" PVC 38+00 39+00 8" PVC EDGE OF ROAD (TYP.) MATCHLINE STA 39+50 SEE DRAWING C-104 PARCEL LINE (TYP.) 19' MATCHLINE STA 33+00 SEE DRAWING C-102 CONTROL POINTS LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. HORIZONTAL 1"=40' 0 AT ORIGINAL SIZE Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 6 December 2013 - 6:38 PM Plotted by: Aaron Foscato Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-101 to C-107.dwg RS 40' 60' 80' VERTICAL 1"=4' AT ORIGINAL SIZE RECYCLED WATERLINE PLAN - BERINGER 20' 2' 4' 6' 8' Designer MJ 0 Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-103 Sht 7 of 50
  • 7. GENERAL NOTES 1. 4. STA. 41+33 8" 22.5° BEND CONTRACTOR TO FIELD VERIFY EXISTING GASLINE LOCATION PRIOR TO CONSTRUCTION. 88 SAWCUT, REMOVE AND DISPOSE ASPHALT CONCRETE (APPROXIMATELY 3" THICK) (E) GROUND 84 84 80 DEMOLITION POSITIVE SLOPE 80 ELEVATION STA. 40+95 EXISTING WATERLINE APPROX. LOCATION STA. 41+05 8" 22.5° BEND STA. 40+72 8" GATE VALVE STA. 40+75 STA. 40+69 8" 90° BEND TRIM EXISTING TREES AND BUSHES AS NEEDED UNDER THE DIRECTION OF A LICENSED ARBORIST. 92 3' MIN COVER ELEVATION 88 CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS PRIOR TO CONSTRUCTION. 96 775' RE-SEED DISTURBED AREA 125' ASPHALT REPLACEMENT 92 2. 3. 96 CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO CONSTRUCTION. 504 SF 15 LF REMOVE AND DISPOSE EXISTING WIRE FENCE REMOVE AND REPLACE VEGETATION AND IRRIGATION LINES IN KIND AS NEEDED. 1 LS 8" PVC C-900 RW LINE CONSTRUCTION 76 76 INSTALL 8" C900 CLASS 150 PVC RECLAIMED WATERLINE 900 LF INSTALL 8" GATE VALVE, BOX AND COVER PER DTL 4, SHEET C-503 56 SY INSTALL ASPHALT REPLACEMENT PER DTL 2 SHEET C-503 72 72 1 EA 1378 SY RE-SEED DISTURBED AREA PER SPECIFICATIONS, 16' WIDTH 15 LF REPLACE WIRE FENCE IN KIND 68 68 39+50 40+00 41+00 42+00 44+00 43+00 45+00 46+00 47+00 48+00 48+50 RECYCLED WATERLINE PROFILE - BERINGER CONTROL POINTS POINT # RW RW EDGE OF VINEYARD ROAD (TYP.) N44°54'24"E 651.85' 42+00 8"W 35'1 64° .62' N43°35'36"W N 27 36.01' 43+00 44+00 8" PVC 8" PVC 45+00 46+00 47+00 8" PVC 7' 9.5 15' WIDE TEMP. CONSTRUCTION EASEMENT 6' SOIL BORING (TYP.) 31 48+00 B7 6' RW N40°09'18"W 1337.64' RW PARCEL LINE (TYP.) MATCHLINE STA 48+50 SEE C-105 40+00 EDGE OF VINEYARD (TYP.) 30 RW Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 1/7/14 100% SUBMITTAL 5/24/13 Note: * indicates signatures on original issue of drawing or last revision of drawing Plotted by: Aaron Foscato Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-101 to C-107.dwg RS 20' 40' 60' 6462256.27 VALVE 1908588.08 6462233.34 8" 22.5° BEND 1908599.93 6462208.39 8" 22.5° BEND 80' VERTICAL 1"=4' AT ORIGINAL SIZE RECYCLED WATERLINE PLAN - BERINGER 6 December 2013 - 6:40 PM 1908564.24 LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. HORIZONTAL 1"=40' 0 AT ORIGINAL SIZE Plot Date: 8" 90° BEND 15' WIDE TEMP. CONSTRUCTION EASEMENT 32 Revision 6462258.17 32 41+00 No 1908561.99 31 EDGE OF ROAD (TYP.) DESCRIPTION 30 29 EASTING 29 SEE C-103 MATCHLINE STA 39+50 NORTHING 2' 4' 6' 8' Designer MJ 0 Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-104 Sht 8 of 50
  • 8. GENERAL NOTES 1. 2. 96 CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS PRIOR TO CONSTRUCTION. 96 STA. 54+70 8" 90° BEND STA. 54+74 8" GATE VALVE STA. 54+84 900' RE-SEED DISTURBED AREA 92 92 88 (E) GROUND 84 3' MIN COVER 84 POSITIVE SLOPE 8" PVC C-900 RW LINE 80 DEMOLITION ELEVATION 88 ELEVATION CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO CONSTRUCTION. 80 CONSTRUCTION 76 76 INSTALL 8" C900 CLASS 150 PVC RECLAIMED WATERLINE 900 LF INSTALL 8" GATE VALVE, BOX AND COVER PER DTL 4, SHEET C-503 72 48+50 50+00 51+00 52+00 53+00 54+00 55+00 56+00 57+00 1600 SY RE-SEED DISTURBED AREA PER SPECIFICATIONS, 16' WIDTH 72 49+00 1 EA 57+50 EDGE OF VINEYARD ROAD (TYP.) CONTROL POINTS POINT # 50+00 51+00 52+00 8" PVC 53+00 6' 15' WIDE TEMP. CONSTRUCTION EASEMENT (TYP.) 34 PARCEL LINE (TYP.) 36 DESCRIPTION 1909148.14 6461745.86 PVC RW LINE 1909622.29 6461345.81 8" 90° BEND 36 B6 EASTING 35 54+00 N40°09'18"W 1337.64' 13.5' 6' 8" PVC 5.5' 49+00 NORTHING 34 35 1909624.50 6461348.04 VALVE 55+00 SEE C-104 MATCHLINE STA 48+50 RECYCLED WATERLINE PROFILE - BERINGER EDGE OF VINEYARD (TYP.) N45°18'29"E 917.44' 56+00 8" PVC 57+00 LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. RECYCLED WATERLINE PLAN - BERINGER Reuse of Documents FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 5 December 2013 - 1:57 PM Plotted by: Ben Langston Drawn Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-101 to C-107.dwg RS 20' 40' 60' 80' VERTICAL 1"=4' AT ORIGINAL SIZE Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 Job Project Manager Director HORIZONTAL 1"=40' 0 AT ORIGINAL SIZE MATCHLINE STA 57+50 SEE C-106 2' 4' 6' 8' Designer MJ 0 Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-105 Sht 9 of 50
  • 9. GENERAL NOTES 1. CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO CONSTRUCTION. 3. CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS PRIOR TO CONSTRUCTION. STA. 64+02 STA. 63+91 8" GATE VALVE STA. 63+88 8" 90° BEND 348' ASPHALT REPLACEMENT 92 92 88 3' MIN COVER 3' MIN COVER (E) GROUND 84 84 POSITIVE SLOPE POSITIVE SLOPE ELEVATION 88 ELEVATION CONTRACTOR SHALL FIELD VERIFY LOCATION AND DEPTH OF EXISTING RECYCLED WATER MAIN FOR CONNECTION WITH NEW MAIN.. 2. 652' RE-SEED DISTURBED AREA DEMOLITION SAWCUT, REMOVE AND DISPOSE ASPHALT CONCRETE (APPROXIMATELY 3" THICK) 1392 SF 8" PVC C-900 RW LINE 80 80 76 76 57+50 58+00 59+00 60+00 61+00 62+00 63+00 64+00 65+00 66+00 67+00 CONSTRUCTION 67+50 INSTALL 8" C900 CLASS 150 PVC RECLAIMED WATERLINE RECYCLED WATERLINE PROFILE - BERINGER 1000 LF INSTALL 8" GATE VALVE, BOX AND COVER PER DTL 4, SHEET C-503 SEE C-107 MATCHLINE STA 67+50 1 EA 155 SY INSTALL ASPHALT REPLACEMENT PER DTL 2 SHEET C-503 1159 SY 67+00 8" PVC RE-SEED DISTURBED AREA PER SPECIFICATIONS, 16' WIDTH N44°42'35"W 665.48' CONTROL POINTS POINT # DESCRIPTION 1910267.52 6461998.01 8" 90° BEND 38 1910269.19 6461996.36 VALVE SEE C-105 MATCHLINE STA 57+50 8" PVC 65+00 66+00 EASTING 37 PARCEL LINE (TYP.) NORTHING 15' WIDE TEMP. CONSTRUCTION EASEMENT B5 EDGE OF VINEYARD ROAD (TYP.) 58+00 8" PVC 60+00 59+00 N45°18'29"E 917.44' 61+00 62+00 8" PVC LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. 38 63+00 64+00 37 15' WIDE TEMP. CONSTRUCTION EASEMENT HORIZONTAL 1"=40' 0 AT ORIGINAL SIZE Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 6 December 2013 - 6:43 PM Plotted by: Aaron Foscato Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-101 to C-107.dwg RS 40' 60' 80' VERTICAL 1"=4' AT ORIGINAL SIZE RECYCLED WATERLINE PLAN - BERINGER 20' 2' 4' 6' 8' Designer MJ 0 Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-106 Sht 10 of 50
  • 10. 100 STA. 78+18 8" 90° BEND (2) 96 ELEVATION STA. 77+63 8" 90° BEND STA. 75+51 8" 90° BEND STA. 70+53 8" 90° BEND 92 (E) GROUND (E) GROUND 3' MIN COVER ELEVATION 96 92 104 266' 3/8" MINUS ROAD MIX GRAVEL REPLACEMENT STA. 78+10 METERING VALVE VAULT 801' ASPHALT REPLACEMENT STA. 78+64 100 STA. 78+43 STA. 78+32 8" 45° BEND STA. 78+36 8" 45° BEND 104 STA. 78+66 8" 22.5° BEND PIPE DISCHARGE DET. 2, SHT. C-501 21' 3/8" MINUS ROAD MIX GRAVEL REPLACEMENT 3' MIN COVER 3' MIN COVER 88 POSITIVE SLOPE 88 8" PVC C-900 RW LINE 84 84 6" PVC RW TO 6" DIP. RW POSITIVE SLOPE 8" PVC C-900 RW LINE 80 80 67+50 68+00 69+00 70+00 71+00 72+00 73+00 74+00 75+00 76+00 77+00 78+00 79+00 79+50 RECYCLED WATERLINE PROFILE - BERINGER GENERAL NOTES 1. 2. CONTROL POINTS NORTHING EASTING DESCRIPTION 39 1910740.46 6461529.84 8" 90° BEND 40 1911090.08 6461884.66 8" 90° BEND 41 1911241.13 6461735.82 8" 90° BEND 42 1911209.53 6461703.46 METER 43 1911160.51 6461654.30 8" DISCHARGE 42 BERINGER POND 78+78 8" DIP N45°19'03"E 107.18' CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS PRIOR TO CONSTRUCTION. 41 DEMOLITION 78+00 SAWCUT, REMOVE AND DISPOSE ASPHALT CONCRETE (APPROXIMATELY 3" THICK) 3204 SF 43 20 LF REMOVE AND DISPOSE EXISTING FENCE 8" PVC PARCEL LINE (TYP.) CONSTRUCTION INSTALL 6' HIGH CHAIN LINK FENCE SEE DTL. 2 SHEET C-505 77+00 EDGE OF VINEYARD ROAD (TYP.) 20 LF 70+00 N44°42'35"W 665.48' 15' WIDE TEMP. CONSTRUCTION EASEMENT N44°34'39"W 212.05' 69+00 72+00 N45°25'21"E 498.13' 15' WIDE TEMP. CONSTRUCTION EASEMENT 1 EA 1 EA PARCEL LINE (TYP.) 1072 LF POND LEVEL MONITOR, INSTALL PER DTL 2, SHEET C-502 1 EA EQUIPMENT MOUNTING RACK. SEE DTL 1, SHEET E-506 EDGE OF VINEYARD ROAD (TYP.) INSTALL 8" C900 CLASS 150 PVC RECLAIMED WATERLINE 1 EA POLE MOUNTED SCADA ANTENNA, SEE DTL 2, SHEET I-102 (NPI) 76+00 8" PVC SEE LEFT MATCHLINE STA 72+50 68+00 INSTALL METERING VALVE ASSEMBLY AND VAULT PER DTL 6, SHEET C-502 DISCHARGE INTO POND PER DTL 2, SHEET C-501 39 8" PVC 71+00 SEE C-106 MATCHLINE STA 67+50 POINT # 25' WIDE TEMP. CONSTRUCTION EASEMENT (TYP.) CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO CONSTRUCTION. 1 EA INSTALL 1" CONDUIT FROM METERING VALVE TO CONTROL PANEL 8" PVC 73+00 74+00 N45°25'21"E 498.13' 75+00 15' WIDE TEMP. CONSTRUCTION EASEMENT (TYP.) INSTALL 1" CONDUIT FROM POND LEVEL JUNCTION BOX TO SCADA CONTROL PANEL 8" PVC 60 LF 60 LF 1 EA SCADA PANEL INSTALLATION. SEE DTL 3 ON SHEET E-506 (NPI) LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. 40 B4 356 SY INSTALL ASPHALT REPLACEMENT PER DTL 2 SHEET C-503 37 SY RE-SEED DISTURBED AREA PER SPECIFICATIONS, 16' WIDTH 1 EA CROSSING PCC PAD REFER TO DTL 3, SHEET C-501 INSTALL 1/2" MINUS ROAD MIX GRAVEL (2" THICK) ENTIRE WIDTH OF ROAD HORIZONTAL 1"=40' 0 AT ORIGINAL SIZE Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 6 December 2013 - 6:44 PM Plotted by: Aaron Foscato Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-101 to C-107.dwg BL 40' 60' 80' VERTICAL 1"=4' AT ORIGINAL SIZE MATCHLINE STA 72+50 SEE RIGHT RECYCLED WATERLINE PLAN - BERINGER 20' 2' 4' 6' 510 SY 56 LF INSTALL 8" CLASS 350 DIP FOR RECLAIMED WATER 8' Designer MJ 0 Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-107 Sht 11 of 50
  • 11. STA. 10+03 EX. GATE VALVE GENERAL NOTES STA. 11+85 STA. 10+97 STA. 10+79 108 104 CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO CONSTRUCTION. 3. 108 CONTRACTOR SHALL FIELD VERIFY LOCATION AND DEPTH OF EXISTING RECYCLED WATER MAIN FOR CONNECTION WITH NEW MAIN.. 2. 112 STA. 10+45 6" 45° BEND STA. 10+26 6" 45° BEND STA. 10+05 EX. 6" RW STA. 10+00 EX. 6" TEE 1. CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS PRIOR TO CONSTRUCTION. 4. 112 CONTRACTOR SHALL REMOVE AND RETURN TO OWNER THE TEMPORARY RW SERVICE. 104 DEMOLITION 92 ELEVATION STA. 11+85 6" PIPE DISCHARGE DET. 2 SHT. C-501 STA. 11+30 6" PVC RW TO 6" DIP. RW 92 STA. 11+22 METERING VALVE VAULT 96 STA. 11+04 6" 45° BEND 96 REMOVE AND RETURN TO OWNER EXISTING 6" RECYCLED WATER LINE 100 STA. 10+65 6" 45° BEND ELEVATION 100 143 LF CONSTRUCTION CONNECT TO EXISTING RECYCLED WATERLINE PER DTL. 1, SHEET C-505. 1 EA INSTALL 6" C-900 CLASS 150 PVC RECLAIMED WATERLINE 130 LF INSTALL METERING VALVE ASSEMBLY AND VAULT PER DTL 6, SHEET C-502 84 2' MIN COVER 1 EA POLE W/SCADA PANEL, ANTENNA, AND SOLAR POWER SOURCE, SEE DTL 1 SHEET I-102 (NPI) (E) GROUND 84 1 EA POND LEVEL MONITOR, INSTALL PER DTL 2, SHEET C-502 88 1 EA DISCHARGE INTO POND PER DTL 2, SHEET C-501 88 1 EA INSTALL 1" CONDUIT FROM METERING VALVE TO CONTROL PANEL POSITIVE SLOPE 80 INSTALL 1" CONDUIT FROM POND LEVEL JUNCTION BOX TO SCADA CONTROL PANEL 80 6" PVC C-900 RW LINE 95 LF 45 LF 1 EA SCADA PANEL INSTALLATION. SEE DTL 2 ON SHEET E-507 (NPI) 9+50 10+00 290 SY RE-SEED DISTURBED AREA PER SPECIFICATIONS, 16' WIDTH 12+00 11+00 INSTALL 1/2" MINUS ROAD MIX GRAVEL (2" THICK) ENTIRE WIDTH OF ROAD EDGE OF VINEYARD ROAD (TYP.) 32 SY INSTALL 6" CLASS 350 DIP FOR RECLAIMED WATER RECYCLED WATERLINE PROFILE - MONDAVI 55 LF CONTROL POINTS POINT # NORTHING EASTING DESCRIPTION 44 1904991.69 6465137.91 APPROX. CONNECT TO EX. 6" RW 45 1904961.92 6465080.55 6" 45° BEND 46 1904978.14 6465029.33 6" 45° BEND 47 1904976.31 6465025.79 METER 48 1904953.79 6464982.41 6" DISCHARGE MONDAVI POND 44 64.63' 6" PVC S62°34'19"W 11 +0 0 45° BEND C PV 6" 3' .7 1"W 53 5'4 2 2° N7 10+00 45 48 52.86' S62°34'19"W 11+67 47 TEMP. CONSTRUCTION EASEMENT (TYP.) 45° BEND 46 HORIZONTAL 1"=40' 0 AT ORIGINAL SIZE Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 25 November 2013 - 1:36 PM Plotted by: Ben Langston Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-108.dwg BL/MC 40' 60' 80' VERTICAL 1"=4' AT ORIGINAL SIZE RECYCLE WATERLINE PLAN - MONDAVI 20' 2' 4' 6' 8' Designer MJ 0 LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-108 Sht 12 of 50
  • 12. GENERAL NOTES 1. 2. CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS PRIOR TO CONSTRUCTION. 3. N CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO CONSTRUCTION. CONTRACTOR SHALL VERIFY AVAILABILITY OF POWER FOR METERING VALVE AND CONTROL PANEL. CONTRACTOR SHALL PROVIDE NEW SOLAR POWER SOURCE PER DET. 1, SHEET I-103 AS NECESSARY. DEMOLITION SEE GENERAL NOTE 3. 49 REMOVE AND SALVAGE EXISTING METER AND VAULT 1 EA 10' WIDE TEMP. CONSTRUCTION EASEMENT (TYP.) 10' WIDE TEMP. CONSTRUCTION EASEMENT (TYP.) CONSTRUCTION SI L OT AD IL RA A N OW TIO ' R OCA 35 . L X RO PP AP 1 EA EQUIPMENT MOUNTING RACK. SEE DTL 1, SHEET E-506 1 EA POLE MOUNTED SCADA ANTENNA, SEE DTL 2, SHEET I-102 (NPI) N OW TIO 2' R OCA 4 .L OX PR 1 EA POND LEVEL MONITOR, INSTALL PER DTL 2, SHEET C-502 R VE INSTALL METERING VALVE ASSEMBLY AND VAULT PER DTL 6, SHEET C-502 1 EA INSTALL 1" CONDUIT FROM METERING VALVE TO CONTROL PANEL INSTALL 1" CONDUIT FROM POND LEVEL JUNCTION BOX TO SCADA CONTROL PANEL 0 CHIMNEY ROCK POND IMPROVEMENTS 15 30 45 60' 362 LF 95 LF POLE W/SCADA PANEL AND ANTENNA, SEE DTL 4 ON SHEET I-102 (NPI) SCADA PANEL INSTALLATION. SEE DTL 4, SHEET E-507 (NPI) SCALE 1"=30' AT ORIGINAL SIZE 1 EA 1 EA RE-SEED DISTURBED AREA PER SPECIFICATIONS, 10' WIDTH INSTALL RTU CABINET. SEE DETAILS 3 & 4, SHEET E-507 (NPI) N 1 LS CONNECT TO EXISTING 120V PANELBOARD. PROVIDE NEW BREAKER AS NECESSARY N 507 SY 1 LS CONTROL POINTS POINT # DESCRIPTION 1902672.89 6471416.04 METER SI L 10' WIDE TEMP. CONSTRUCTION EASEMENT (TYP.) EASTING 49 CHIMNEY ROCK NORTHING R VE OT AD IL RA SEE LEFT SEE ABOVE SITE MAP LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. CHIMNEY ROCK POND 0 CHIMNEY ROCK POND IMPROVEMENTS 15 30 45 60' SCALE 1"=30' AT ORIGINAL SIZE Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 25 November 2013 - 1:52 PM Plotted by: Ben Langston Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-109.dwg 200 300 400' SCALE 1"=200' AT ORIGINAL SIZE Reuse of Documents FINAL TOWN REVIEW NFC 100 0 BL/MC Designer MJ Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-109 Sht 13 of 50
  • 13. GENERAL NOTES 1. CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO CONSTRUCTION. 2. CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS PRIOR TO CONSTRUCTION. DEMOLITION SILVERADO TRAIL REMOVE AND SALVAGE EXISTING METER AND VAULT 1 EA CONSTRUCTION INSTALL METERING VALVE ASSEMBLY AND VAULT PER DTL 6, SHEET C-502 POND LEVEL MONITOR, INSTALL PER DTL 2, SHEET C-502 1 EA EQUIPMENT MOUNTING RACK. SEE DTL 1, SHEET E-506 1 EA POLE MOUNTED SCADA ANTENNA, SEE DTL 2, SHEET I-102 (NPI) CLOS DU VAL/REGUSCI POND 1 EA 1 EA INSTALL 1" CONDUIT FROM METERING VALVE TO CONTROL PANEL 345 LF INSTALL 1" CONDUIT FROM POND LEVEL JUNCTION BOX TO SCADA CONTROL PANEL 40 LF 1 EA SCADA PANEL INSTALLATION. SEE DTL 2 ON SHEET E-506 (NPI) 428 SY EX. 6" PVC RE-SEED DISTURBED AREA PER SPECIFICATIONS, 10' WIDTH CONTROL POINTS POINT # NORTHING EASTING DESCRIPTION 50 1905056.06 6469820.50 METER 50 25' WIDE TEMP. CONSTRUCTION EASEMENT (TYP.) 35'ROW APPROX. LOCATION 42'ROW APPROX. LOCATION 25' WIDE TEMP. CONSTRUCTION EASEMENT (TYP.) 10' WIDE TEMP. CONSTRUCTION EASEMENT (TYP.) 20 0 CLOS DU VAL/REGUSCI POND IMPROVEMENTS 40 60 LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. 80' SCALE 1"=40' AT ORIGINAL SIZE Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 25 November 2013 - 2:04 PM Plotted by: Ben Langston Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-110.dwg BL/MC Designer MJ Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-110 Sht 14 of 50
  • 14. GENERAL NOTES 1. CONTRACTOR SHALL COORDINATE WITH VINEYARD OWNER LOCATION OF VINEYARD UTILITIES WITHIN PROPOSED ALIGNMENT PRIOR TO CONSTRUCTION. 2. CONTRACTOR SHALL POTHOLE AND LOCATE PRIVATE UTILITY LOCATIONS PRIOR TO CONSTRUCTION. 3. CONTRACTOR TO VERIFY PIPE SIZE AND MATERIAL IN THE FIELD. 4. EXISTING GATE VALVES AT DEMOLITION KEYNOTE 8 ARE ABOVE GROUND AT THIS LOCATION. 10' WIDE TEMP. CONSTRUCTION EASEMENT DEMOLITION STAG'S LEAP WINE CELLARS POND REMOVE AND SALVAGE EXISTING GATE VALVE. 2 EA REMOVE AND SALVAGE EXISTING METER AND VAULT 1 EA CONSTRUCTION INSTALL METERING VALVE ASSEMBLY AND VAULT PER DTL 6, SHEET C-502 POND LEVEL MONITOR, INSTALL PER DTL 2, SHEET C-502 1 EA POLE MOUNTED SCADA ANTENNA, SEE DTL 2, SHEET I-102 (NPI) 1 EA INSTALL 1" CONDUIT FROM METERING VALVE TO CONTROL PANEL 8 LF INSTALL 1" CONDUIT FROM POND LEVEL JUNCTION BOX TO SCADA CONTROL PANEL 20'x20' TEMP. CONSTRUCTION EASEMENT 1 EA POLE W/SCADA PANEL, ANTENNA, AND SOLAR POWER SOURCE, SEE DTL 1 SHEET I-102 (NPI) 20'x20' TEMP. CONSTRUCTION EASEMENT 1 EA 20 LF SCADA PANEL INSTALLATION. SEE DTL 5 ON SHEET E-506 AND DTL 5 ON SHEET E-506 (NPI) 1 EA 156 SY RE-SEED DISTURBED AREA PER SPECIFICATIONS, 10' WIDTH STAG'S LEAP WINE CELLARS POND IMPROVEMENTS CAP END OF TEE AND EXISTING PIPE CONNECT EXISTING PIPES ONCE GATE VALVE HAS BEEN REMOVED STAG'S LEAP WINE CELLARS 2 EA 1 EA SEE LEFT CONTROL POINTS POINT # NORTHING EASTING DESCRIPTION 51 1906025.79 6469185.36 METER 51 20'x20' TEMP. CONSTRUCTION EASEMENT SILVE T RADO T RADO RAIL SILVE RAIL W 35' RO TION A X. LOC APPRO W 42' RO ATION X. LOC PR O AP EX. 6" PVC LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. SEE LEFT STAG'S LEAP WINE CELLARS POND IMPROVEMENTS 0 15 30 45 60' 0 SITE MAP Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 6 December 2013 - 6:30 PM Plotted by: Aaron Foscato Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-111.dwg 200 300 400' SCALE 1"=200' AT ORIGINAL SIZE SCALE 1"=30' AT ORIGINAL SIZE FINAL TOWN REVIEW NFC 100 BL/MC Designer MJ Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-111 Sht 15 of 50
  • 15. GENERAL NOTES LE M SETTLING VAULTS UTILITY BUILDING DEMOLITION REMOVE AND DISPOSE EXISTING BARB WIRE FENCE FROM LOCATION "A" TO LOCATION "B" LE 330 LF 20'x40' CONTRACTOR OFFICE TRAILER LOCATION FILTRATION CONSTRUCTION PANELBOARD B TO OPERATOR 1- 3/4" BURIED CONDUIT W/ 2- #12 AND 1- #12 G INSTALL 6' HIGH CHAIN LINK FENCE SEE DTL. 2 SHEET C-505 PANELBOARD B 350 LF INSTALL 8-FIBER CABLE FROM MASTER RTU TO RTU R, FREE OF SPLICES IN EXISTING CONDUIT (NPI) AERATOR 653 LF INSTALL CARD READER PEDESTAL AND CONDUIT TO ACCESS CONTROL UNIT PER DETAILS 1-5, SHEET C-507 OPERATOR TO PEDESTAL 1 - 3/4" BURIED CONDUIT SPARE 1 LS PROVIDE GATE OPERATOR PER DET 2 ON C-506 CONTROL BUILDING 1 LS 195 LF INSTALL 2 - 3/4" CONDUITS. SEE DETAILS 6 & 7, SHEET E-507 AND DETAILS 1 ,2 & 3, SHEET E-508. ACCESS CONTROL UNIT FOR CCTV CAMERA AND GATE OPERATOR CONTROL PROVIDED AND INSTALLED BY OTHERS CONTRACTOR PARKING AND LAYDOWN AREA NPI INSTALL AMERISTAR PASSPORT COMMERCIAL ROLL GATE PER DETAILS 1-4, SHEET C-506. SEE DRAWING C-115 FOR DETAIL IN THIS AREA INSTALL 2-3/4" CONDUITS FROM GATE OPERATOR TO PEDESTAL SEE SHEETS C-113, C-114 AND E-101 FOR DETAIL IN THIS AREA PULL FIBER CABLE THROUGH EXISTING 2" CONDUIT. FIELD VERIFY EXISTING LOCATION. 1 LS 66 LF EXISTING PULL BOX OPERATOR TO PEDESTAL 1 - 3/4" BURIED CONDUIT W/ 2 - #16 AND 1 - #12 G 1 - 3/4" BURIED CONDUIT SPARE EXISTING PULL BOX RECYCLED WATER WET WELL PUMP SAMPLING, ANALYZER, AND PUMPING STATION AREA 0 TREATMENT PLANT SITE PLAN Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 1/7/14 100% SUBMITTAL 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 26 November 2013 - 5:04 PM Plotted by: Ben Langston 20 30 40' SCALE 1"=20' AT ORIGINAL SIZE Reuse of Documents No 10 LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-112.dwg BL Designer MJ Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-112 Sht 16 of 50
  • 16. GENERAL NOTES DEMOLITION SAWCUT, REMOVE AND DISPOSE ASPHALT CONCRETE (APPROXIMATELY 4" THICK) 150 SF REMOVE AND RETURN TO OWNER EXISTING 6" RECYCLED WATER LINE 24 LF REMOVE AND DISPOSE EXISTING FLOW METER AND BOX. REPLACE WITH 6" PIPE 1 EA CONSTRUCTION R=15' RECYCLED WATER WET WELL, SEE DTL 3, SHEET C-502 CHLORINE ANALYZER, SEE DTL 2 ON SHEET E-501 1 LS RECYCLED WATER PUMP STATION UPGRADES, SEE SHEET M-301 WATER 1 EA SAMPLING PUMP AND PIPING, SEE DETAILS 1 & 2, SHEET C-504 TREE LOCATION 1 LS 1 LS WATER INSTALL 6' HIGH CHAIN LINK FENCE SEE DTL. 2 SHEET C-505 * LF INSTALL 6' HIGH CHAIN LINK DOUBLE GATE, 16' WIDTH, SEE DTL. 2 SHEET C-505 1 EA INSTALL REMOVABLE BOLLARD PER DTL 1, SHEET C-502 2 EA INSTALL 4" ROLLED CURB AND GUTTER AT LOCATIONS SHOWN PER TOWN OF YOUNTVILLE STANDARD DTL ST-4 WITH OPTIONAL POUR. WATER 71 LF INSTALL 4" ASPHALT PAVEMENT TURNOUT PER DTL 6, SHEET C-503 IN LOCATIONS SHOWN 147 SY 4' CONCRETE CURB OPENING. SHAPE AND GRADE TO DRAIN TOWARDS V-DITCH. 1 EA INSTALL RIPRAP (D50=6") LINED V-DITCH 1' DEEP WITH 3:1 SIDE SLOPES. INCLUDES GEOTEXTILE LINER UNDER RIPRAP. 15 LF INSTALL 6' HIGH CHAIN LINK MAN GATE, 4' WIDTH, SEE DTL 2 SHEET C-505 INSTALL NEW BILCO DOOR AT RECYCLED WATER WET WELL PER DETAILS 1 AND 2, SHEET S-104 * 1 LS INSTALL "TRUCK FILL STATION HOURS OF OPERATION M-F, 8-4" SIGN. ATTACH SIGN TO FENCE NEXT TO TRUCK FILL STATION. REFER TO SHEET C-114 FOR PIPING PLAN 1 EA 1 EA QUANTITY IS REFLECTED ON SHEET C-112 CONTROL POINTS POINT # Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 25 November 2013 - 3:23 PM Plotted by: Ben Langston Drawn Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-113.dwg EP 1905678.93 6458550.02 99.16 BOC 1905668.29 6458531.64 99.05 BOC 1905657.65 6458513.26 98.95 BOC 1905658.81 6458510.28 98.57 FL 1905644.22 6458518.79 97.00 FL 1905639.10 6458521.78 96.00 FL 1905655.08 6458508.78 98.95 BOC 1905660.66 6458488.61 99.70 BOC 1905662.78 6458487.45 EXISTING EP 1905664.63 6458486.40 EXISTING SAWCUT 1905685.95 6458523.23 EXISTING SAWCUT 1905690.92 6458552.38 EX FENCE 1905687.77 6458546.77 FENCE 77 1905686.36 6458546.37 FENCE 78 1905678.56 6458550.88 FENCE 79 1905676.35 6458547.07 4' PED. GATE 80 1905664.63 6458526.91 16' DBL. GATE CL 81 1905658.91 6458516.94 FENCE 1905656.51 6458518.32 FENCE 83 No 98.87 82 Job Project Manager Director 6458548.78 76 5/24/13 1905681.10 75 100% SUBMITTAL EP 74 1/7/14 98.93 73 FINAL TOWN REVIEW NFC 6458545.83 72 This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 1905686.30 71 Designer MJ EP 70 BL EXISTING 69 Drawn 6458549.22 68 Reuse of Documents 1905698.67 67 SCALE 1"=5' AT ORIGINAL SIZE SAWCUT 66 TREATMENT PLANT DEMOLITION, GRADING AND PAVING PLAN EXISTING 65 10' 6458548.22 64 7.5 1905700.41 63 5 DESCRIPTION 62 2.5 ELEV. 61 0 EASTING 60 LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. NORTHING 1905652.24 6458510.92 FENCE 84 1905661.34 6458500.36 FENCE 85 1905646.37 6458473.91 FENCE Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-113 Sht 17 of 50
  • 17. GENERAL NOTES DEMOLITION CONSTRUCTION INSTALL TRUCK FILL STATION AND 4" METER, SEE DTL 1, SHEET C-503 1 LS INSTALL AIR RELEASE AND 4" CAST IRON SWING CHECK VALVE PER DTL 5, SHEET C-502 1 EA INSTALL 4" FLOW METER AND VAULT PER DTL 4, SHEET C-502 3 EA INSTALL 4" GATE VALVE, BOX AND COVER PER DTL 4, SHEET C-503 4 EA INSTALL 6" X 4" REDUCER (NPI) 4 EA INSTALL MJ 4" X 4" X 4" TEE (NPI) 2 EA 90 LF INSTALL 4" CLASS 350 DIP FOR RECLAIMED WATER INSTALL 4" 90° BEND (NPI) CONNECT TO EXISTING PIPE WITH TRANSITION COUPLING 4 EA WATER 4"RW WATER 3 EA WATER 4"RW TREATMENT PLANT PIPING PLAN 0 2.5 5 7.5 10' SCALE 1"=5' AT ORIGINAL SIZE Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 25 November 2013 - 3:28 PM Plotted by: Ben Langston Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-114.dwg BL Designer MJ LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-114 Sht 18 of 50
  • 18. GENERAL NOTES LE M DEMOLITION REMOVE AND DISPOSE OF EXISTING VALVE ACTUATOR 2 EA REMOVE AND DISPOSE OF EXISTING BUTTERFLY VALVE 1 EA REMOVE AND DISPOSE EXISTING TRICKLING FILTER SUCTION LINE 4 EA EXISTING PANELBOARD D & E EXISTING SWITCHBOARD B CONSTRUCTION UTILITY BUILDING INSTALL NEW BUTTERFLY VALVE PER DETAILS 4 & 5, SHEET C-504 INSTALL NEW VALVE ACTUATOR AND VALVE EXTENSION PER DETAILS 4 & 5, SHEET C-504. 1 LS INSTALL NEW 1-1/4" SCHEDULE 80 PVC WATER LINE THREADED INTO EXISTING RECLAIMED WATERLINE PER DTL 5, SHEET C-503. RW 1 LS INSTALL NEW CHLORINE ANALYZER AND PUMP, PER DTL 3 AND DTL 6 ON SHEET C-504 OPERATOR INTERFACE TERMINAL 1 LS INSTALL 2ND SODIUM BISULFATE INJECTOR PUMP PER DTL 4, SHEET C-501 EXISTING MANHOLE 2 EA FUZZY FILTER UPGRADES PER SECTION 11995 OF THE SPECIFICATIONS EXISTING MULTITRONICS FLOW METER 1 EA 50 LF INSTALL NEW ULTRASONIC LEVEL SENSOR, SEE DTL 5,SHEET E-505 LE 2 EA 1 LS INSTALL 8-FIBER CABLE FROM MASTER RTU TO RTU R, FREE OF SPLICES IN EXISTING CONDUIT (NPI) RW 1 LS INSTALL RTU U, SEE DTL 2, SHEET E-400 (NPI) 20X40 CONTRACTOR OFFCE TRAILER LOCATION 1 LS INSTALL MASTER RTU, SEE SHEET E-400 (NPI) RW INSTALL CAT6 ETHERNET CONNECTION BETWEEN RTU U AND MASTER RTU IN EXISTING CONDUIT (NPI) * LF INSTALL NEW GRATING AND ALUMINUM SUPPORT BEAMS, CONNECTIONS, ETC. AT TRICKLING FILTER VALVE VAULTS SEE SHEET S-103 1 LS 1 LS TRICKLING FILTER WET WELL PIPE REPLACEMENTS, PER DTL 3, SHEET C-505 RW INSTALL NEW BILCO DOOR AT TRICKLING FILTER WET WELLS SEE SHEET S-104 1 LS 1 EA INSTALL CATWALK IN EXISTING WETWELL PER DTL 2, SHEET S-102 2 EA QUANTITY IS REFLECTED ON SHEET C-112 RW * * LF INSTALL 1 1/4" STAINLESS STEEL FOOT VALVE PER DTL 5, SHEET C-503 RW INSTALL 2 - 3/4" CONDUITS. SEE DETAILS 6 & 7, SHEET E-507 AND DETAILS 1 ,2 & 3, SHEET E-508. RW EXISTING PANELBOARD B CONTROL BUILDING CONTRACTOR PARKING AND LAYDOWN AREA RW LOCATION OF EXISTING UTILITIES AND STRUCTURES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. CONTACTOR SHALL NOTIFY UNDERGROUND SERVICES ALERT (800) 227-2600 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND POTHOLE FOR EXACT LOCATION. 0 TREATMENT PLANT SITE PLAN 5 10 15 20' SCALE 1"=10' AT ORIGINAL SIZE Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 25 November 2013 - 3:33 PM Plotted by: Ben Langston Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-115.dwg BL Designer MJ Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ/RG Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-115 Sht 19 of 50
  • 19. 2.00' MIN EXISTING GROUND 1 .0 0' 2 .0 ESA CONSTRUCTION ACTIVIVIES 0' 6" CLASS 350 DIP 1 .5 0' 10" CMP CAP HIGH VISIBILITY FABRIC 10" CMP 6" HOLE FOR DIP WL 4'-0" 4 .3 END VIEW WL VARIES 4'± 2'X1'X1' CONCRETE PAD WITH STAINLESS STEEL BOLTED PIPE STRAP POST 3' 4.00' MIN. CUT TOP OF PIPE PER DIMENSIONS SHOWN 2'-0" MIN 10" CMP 8" 8" SECTION 1 8" 2" 8" CUT PIPE OUTLET TO 45° TEMPORARY FENCE (TYPE ESA) 2 PROFILE VIEW SCALE : NTS PLAN POND DISCHARGE DETAIL SCALE : NTS 24.50' 2.00' MIN ADD WOOD SUPPORT SHELF WITH PLASTIC SUPPORTS, IWAKE EW-SERIES DOSING PUMP MODEL NO. EWB31Y1-VC AND ASSOCIATED CONTROLS 2.72' 19.92' 6" 45° BEND FLGxFLG 6" 90° BEND FLGxFLG 6" 45° BEND FLGxFLG 2'X1'X1' CONCRETE PAD WITH STAINLESS STEEL BOLTED PIPE STRAP FOR CONTINUATION SEE DETAIL 2 THIS SHEET 2.00' MIN 6" CLASS 350 DIP 6" CLASS 350 DIP PIPE SUPPORT (TYP) PER 7 C-503 PIPE COATING PER SPECIFICATIONS SECTION 09800 EXISTING CONCRETE PAD PROTECT IN PLACE 1.00' 6" 90° BEND FLGxFLG 6" CLASS 350 DIP METERING VALVE BOX PER DTL 6, SHEET C-502. 3 PIPE DISCHARGE DETAIL SCALE : N.T.S. Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 27 November 2013 - 3:06 PM Plotted by: Ben Langston Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-501.dwg 4 BL/MC Designer MJ SODIUM BISULFITE PUMP SCALE : NTS Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-501 Sht 20 of 50
  • 20. JUNCTION BOX (SEE NOTE) FLEXIBLE CONDUIT FROM JUNCTION BOX TO 5' PAST LOW WATER MARK,18" MINIMUM SUNLIGHT (UV) RESISTANT FOR EXTERIOR APPLICATIONS (FOR CLOS DU VAL SITE ONLY) 4" PROVIDE WIRE TIE TO SUPPORT MANUFACTURERS CABLE FROM GALVANIZED WIRE CABLE 4.0' TO CONTROL MANUFACTURE CABLE FOR LEVEL SENSOR CONCRETE MIN. SCALE : NTS CHRISTY N48 UTILITY BOX 30" X 48" WITH A 2PC. TRAFFIC RATED STEEL CHECKER PLATE. PROVIDE EXTRUSIONS AS NEEDED TO REACH EXISTING PIPE DEPTH. POND EMBANKMENT INSTALL 4" ENDRESS HAUSER PROLINE PROMAG 53W ELECTROMAGNETIC FLOW METER DETECTOR WITH REMOTE READOUT 0'-6" STAINLESS STEEL CABLE GRIP WIRE HARNESS 6" ABS PIPE WITH CARBON BLACK 0'-6" OUTSIDE OF PIPE SHALL INCLUDE PAINTED LEVEL MARKINGS BEGIN HOLES 3-FEET ABOVE BOTTOM REMOVABLE BOLLARD 316 STAINLESS STEEL QUICK LINK 4" DIAMETER CONCRETE 12" DEEP SUBMERSIBLE LEVEL TRANSDUCER CABLE 5-GALLON BUCKET FILLED WITH CONCRETE MATCH EXISTING 4" DIP PIPE CAP 2 WET WELL - PLAN VIEW 16' CABLES REMOVE EXISTING MANHOLE LID AND INSTALL BILCO DOOR PER STRUCTURAL SHEETS LEVEL MONITOR MOUNT JUNCTION BOX ON EMBANKMENT. LENGTH OF SUBMERSED CABLE TO BE FIELD VERIFIED AND IS SITE SPECIFIC. LEVEL SENSOR INSTALL FLYGT MODEL CS 3085 MT 3"/3" SUBMERSIBLE PUMP. ATTACH AND WIRE A LOW LEVEL INDICATOR FLOAT SWITCH. INSTALL 4" CLASS 350 DIP DISCHARGE PIPE NOTE: FLEXIBLE COUPLING ADAPTOR (TYP) - 1'-2" ATTACH 1/8" Ø GALVANIZED WIRE CABLE TO ABS PIPE AND JUNCTION BOX BASE INSTALL ANCHORS (4) 5GALLON BUCKETS FILLED WITH CONCRETE ON OPPOSITE SIDES OF POLE WITH EMBEDDED 316 STAINLESS STEEL EYE-BOLT 16"Ø 1 SUBMERGED CABLE (4) 1/8" Ø STAINLESS STEEL CABLES MIN. 3'-0" 6" HIGH WATER 16' 1" FINISH GRADE 316 STAINLESS STEEL 1/2" EYE-BOLT. EMBED BOLT 6" INTO CONCRETE A 4.0' SEE CABLE GRIP ANCHOR AND DETAIL BELOW SLOPE ALL AROUND 1'-3" (4) ATTACH CABLES TO PIPE WITH STAINLESS STEEL STRAPPING AND HARDWARE 4'-0' 3'-0" TRAFFICGUARD LOCKING ROUND POST "RPL4" BOLLARD OR APPROVED EQUAL 3'-0" ANCHOR BUCKETS LEVEL MONITOR ANCHOR LAYOUT PLAN INSTALL 4" UNION FITTING SCALE : NTS ELECTRICAL CONDUIT ENTRY INTO WET WELL PER DETAIL 3, SHEET E-505. PROVIDE CONDUIT AND CONDUCTORS AS IDENTIFIED ON SHEET E-200 PENETRATE THROUGH WET WELL AND INSTALL 4" CLASS 350 DIP DISCHARGE PIPE 4" WATTS MODEL 97FB-CIB BASKET STRAINER OR APPROVED EQUAL 8" AB BASE 4 COUPLING CONC UTILITY BOX (CHRISTY 48"x30") FLOW METER VAULT 8" (TYP.) (E) 16" TE (E) 16" TE TO OUTFALL METERING BOX (E) ADJUSTABLE PIPE SUPPORT PER SCALE : NTS 7 CHRISTY N48 UTILITY BOX 30" X 48" WITH A 2PC. TRAFFIC RATED STEEL CHECKER PLATE 1" BRASS NIPPLE 1" BRASS BALL VALVE 1" DOUBLE STRAP TAPPING SADDLE 4" DIP FLEXIBLE CONDUIT 3" CLASS 350 DIP DISCHARGE PIPE. ATTACH PIPE TO WALL OF WET WELL WITH ST. STL. BRACKETS. TO SCADA 4" GATE VALVE BOX AND COVER (TYP) PRECAST VAULT INSTALL AND WIRE LOW FLOW INDICATOR FLOAT SWITCH (E) DUCTILE IRON FROM DISTRIBUTION SYSTEM MATCH EXISTING INSTALL 4" CAST IRON SWING CHECK VALVE J-BOX 4" GATE VALVE BOX AND COVER (TYP) TO STORAGE POND 6" MIN STEEL PIPE AND FITTINGS (SIZED TO MATCH VALVE OUTLET) EXTEND TO 4" BELOW THE CENTERLINE OF THE MAIN LINE COVER END WITH 16 MESH S.S. SCREEN COMBINATION AIR VALVE OR AIR RELEASE VALVE E-503 FLEXIBLE COUPLING ADAPTOR (TYP) 4" RESTRAINED FLEX COUPLING (TYP.) 4" CLAVAL MODEL 133-01 METERING VALVE OR APPROVED EQUAL COATING PER 09800 INSTALL FLYGT MODEL CS 3085 MT 3"/3" SUBMERSIBLE PUMP (E) DUCTILE IRON REDUCER SIZE VARIES (TYP) TO OUTFALL METERING BOX (E) 6" 8" AB BASE 1'x1'x1' CONC. FOOTER DUCTILE IRON PIPE DIP PIPE FLEXIBLE COUPLING ADAPTOR (TYP) 5 AIR RELEASE/CHECK VALVE VAULT 6 SCALE : NTS METERING VALVE VAULT SUPPORT VALVES IN BOX WITH BRICKS OR REDWOOD BLOCKS UNDER FLANGES. Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 1/7/14 100% SUBMITTAL 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 27 November 2013 - 3:07 PM Plotted by: Ben Langston Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-502.dwg 3 SCALE : NTS Reuse of Documents No WET WELL - SECTION A NOTE: 8" AB BASE BL/MC Designer MJ RECYCLED WATER WET WELL SCALE : NTS Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-502 Sht 21 of 50
  • 21. 1/2" MINUS 2" THICK FOR ENTIRE WIDTH OF ROAD WHERE SHOWN ON PLANS X' 3" WIDE PURPLE PLASTIC CAUTION TAPE, MARKED "RECYCLED WATERLINE BURIED BELOW" 3' MIN 4" BUTTERFLY VALVE #4 STEEL BARS AT 12" O.C. EACH WAY 12" TYPE 2 BEDDING 6" MIN 4" ASPHALT 6" AGGREGATE BASE COURSE INSULATED TRACER WIRE #12 COPPER 3" MIN 3" MIN 4" EPOXY COATED CLASS 350 DIP INITIAL BACKFILL 36" 12" INSULATED TRACER WIRE #12 COPPER 3'X3'X6" CONC SLAB SUBSEQUENT BACKFILL 3' MIN 24" MIN (TYP) 6" MIN 6" RIPPED, MOISTURE CONDITIONED AND RECOMPACTED SUBGRADE INITIAL BACKFILL 4" RUBBER DUST CAP 4" 90° BEND 3" WIDE PURPLE PLASTIC CAUTION TAPE, MARKED "RECYCLED WATERLINE BURIED BELOW" SEEDING 4" ASPHAULT 4" FLANGED MALE NPT SUBSEQUENT BACKFILL 4" THREADED MALE FITTING CAMLOCK QUICK CONNECT WITH PLUG X' GRAVEL ROAD 4" STAINLESS STEEL THREADED SAFETY BREAK-AWAY COUPLING SUBGRADE COMPACTED TO 95% RC TYPE 2 BEDDING 6" MIN 6" MIN NOTE: INSTALL 2 REMOVABLE BOLLARDS AROUND TRUCK FILL STATION FOR PROTECTION. USE FLANGED PIPE BACK TO DISCHARGE HEADER. TO METER TYPICAL TRENCH SECTION (ASPHAULT AREAS) 3 SCALE : NTS AC PAVEMENT SECTION 6 SCALE : NTS SCALE : NTS TRUCK FILL STATION SCALE : NTS CHRISTY G5 PURPLE VALVE BOX WITH LID MARKED "RECYCLED WATER" OR "RW" STREET GRADE DIMENSION TABLE (INCHES) SUPPORTED PIPE 2" A.C. (MIN) CLASS "C" CONCRETE COLLAR 6" 12" MIN (TYP) EXISTING MANHOLE ADJUSTABLE PIPE SADDLE SUPPORT 5' MAX (1) E PURPLE 8" DIA. P.V.C. PIPE RISER "D" SEE TABLE MECHANICAL JOINT W/ MEGALUG (OR EQUIVALENT) RESTRAINT OR PUSH-ON JOINT CONNECT AND EXTEND 1 1/4" SCH. 80 PVC SUCTION LINE DOWN EXISTING MANHOLE WALL. MOUNT PIPE ON WALL WITH UNISTRUT INSULATED TRACER WIRE #12 COPPER WITH 2"-3" PIG TAIL (TYP.) A (2) 3/4" 316 S.S. WEDGE ANCHOR (TYP OF 4) B 1/2" PLATE (4) 1" NON-SHRINK GROUT FIN. FLOOR OR 12"x12"x12" CONC. PAD WITH #4@10" E.W., E.F. NOTES: 1. BUTTERFLY VALVES SHALL BE INSTALLED FOR 12" AND LARGER PIPES. VALVE NUTS SHALL BE PLACED ON THE SIDE OF THE MAIN CLOSEST TO THE NEAREST CURB. A B C 2 1/2 3 3 1/2 4 5 6 8 10 12 14 16 18 20 24 30 32 36 1" DISCHARGE LINE VARIES 6" MIN. PIPE SIZE 1" MIN. 1 2 TYPICAL TRENCH SECTION (GRAVEL AND RESEEDED AREAS) 1 1/2 1 1/2 1 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 3 3 3 1/2 3 1/2 4 4 4 4 2 1/2 2 1/2 2 1/2 3 3 3 3 3 3 4 4 6 6 6 6 6 6 9 9 9 9 9 9 9 9 9 11 11 13 1/2 13 1/2 13 1/2 15 18 18 D 3 1/2 3 3/4 4 4 1/4 4 7/8 5 1/2 6 7/8 8 1/2 9 15/16 10 15/16 12 3/8 13 7/8 15 3/8 17 15/16 21 5/16 22 1/2 24 1/2 E MIN MAX 8 8 1/4 8 1/2 9 1/4 10 10 1/2 11 3/4 13 1/2 15 16 1/4 17 3/4 19 1/2 21 23 3/4 27 28 1/4 30 1/4 13 13 1/4 13 1/2 14 14 3/4 15 1/4 16 1/2 18 1/4 19 3/4 20 3/4 22 1/4 24 25 1/2 28 1/4 31 1/2 32 3/4 34 3/4 NOTES: EXISTING 15" RECLAIMED WATERLINE 3. THE TWO (2) INCH SQUARE OPERATING NUT ON ALL VALVES SHALL BE INSTALLED AT A MAXIMUM OF 5-FEET IN DEPTH MEASURED FROM THE TOP OF THE OPERATING NUT TO FINISHED GRADE. ALL OPERATING NUTS INSTALLED AT A DEPTH GREATER THAN 5-FEET SHALL INCLUDE A VALVE EXTENSION TO RAISE THE OPERATING NUT TO 24-INCHES FROM FINISHED GRADE. ADJUSTABLE PIPE SUPPORT, GRINNELL FIG. 264 OR EQUAL. PIPE STANCHION SADDLE DESIGNED FOR PIPE 4"-36". PIPE LARGER THAN 36" SHALL BE SUPPORTED BY A STANCHION SADDLE DESIGNED BY THE MANUFACTURER. 4. C PIPE SADDLE WITH U-BOLT, GRINNELL FIG. 259 OR EQUAL. 3. 2. VALVE RING SHALL BE SET BELOW GRADE PRIOR TO PLACING FINISHED PAVEMENT AND THEN CUT AND ADJUSTED TO FINISHED GRADE. 1. 2. LEVELING NUTS PROVIDE 5/8" BOLT HOLE (TYP. OF 4) 1-1/2" OFF EDGE OF BEARING PLATE. 1 1/4" STAINLESS STEEL FOOT VALVE 4. VALVE EXTENSIONS (IF REQUIRED) SHALL BE ROUND OR SQUARE 1.5-INCH DIAMETER STEEL ROD, WELDED CONSTRUCTION, HOT DIPPED GALVANIZED WITH TOP CENTERING RING AND AWWA 2" OPERATING NUTS TOP AND BOTTOM (PIPELINE PRODUCTS SX-900 OR SIMILAR). SOCKET END SHALL BE DRILLED AND TAPPED WITH TWO (2) 1/4" SET SCREWS INSTALLED ON OPPOSITE SIDES. OPERATING NUT SHALL BE DRILLED WITH RECESSES TO ACCEPT THE TWO (2) 1/4" SET SCREWS. SET SCREWS SHALL BE SECURELY FASTENED TO THE OPERATING NUT. 7 PIPE SUPPORT SCALE : NTS 5. WATER VALVES SHALL BE OPERATED BY TOWN PERSONNEL ONLY. 20' 6. ALL NEW VALVES SHALL BE MARKED ON THE NEW RW LINE. 4 GATE VALVE 5 SCALE : NTS 1 1/4" PIPE THREADING DETAIL 1 1/4" SCHEDULE 80 PVC WATERLINE THREADED INSIDE EXISTING 15" RECLAIMED WATERLINE SCALE : NTS Reuse of Documents Drawn This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD Inc. and shall not be reused in whole or in part for any other project without GHD Inc.'s written authorization. © GHD Inc. 2012 FINAL TOWN REVIEW NFC 100% SUBMITTAL No 1/7/14 5/24/13 Revision Plot Date: Note: * indicates signatures on original issue of drawing or last revision of drawing 6 December 2013 - 6:42 PM Plotted by: Aaron Foscato Drawn Job Project Manager Director Cad File No: Date N:USSanta RosaProjects12027 - The Town of Yountville12027-11-001 Recycled Water Expansion Project06-CADSheets1202711001 C-503.dwg BL/MC Designer MJ Client Project Drafting SD Check GHD Inc. 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com Design Check WZ Approved (Project Director) JANUARY 2014 Date Scale AS SHOWN This Drawing shall not be used for Construction unless Signed and Sealed For Construction Title Contract No. Original Size C-503 Sht 22 of 50