ELECTRICAL MACHINES-II
                   LAB MANUAL




  DEPARTMENT OF ELECTRICAL AND ELECTRONICS
                ENGINEERING

AARUPADAI VEEDU INSTITUTE OF TECHNOLOGY,
Old Mahabalipuram Road, Paiyanoor-603104, Kanchipuram (dt),
                        Tamilnadu

      VINAYAKA MISSIONS UNIVERSITY
                 SALEM, TAMILNADU
•   Name of the Laboratory : ELECTRICAL MACHINES-II

    •   Year/Semester       :   II/IV

    •   Branch              : EEE




HOD/EEE                                    Principal
PREFACE

This Laboratory book in Electrical Machines – II has been revised in order to be up to date with
Curriculum changes, laboratory equipment upgrading and the latest circuit simulation.
        Every effort has been made to correct all the known errors, but nobody is perfect,
if you find any additional errors or anything else you think is an error, Please contact the
HOD/EEE at eeeavit@gmail.com
       The Authors thanked all the staff members from the department for their valuable
Suggestion and contribution




The Authors
      Department of EEE
TABLE OF CONTENTS



           Safety Rules and operating Procedures                        I
           Laboratory Safety information                               II
           Guidelines for Laboratory Notebook                          III
           Troubleshooting Hints                                       IV
Sl.No                      Experiment Name                           Page No
   1.      Regulation of 3-phase alternator by EMF and MMF              1
           methods.
   2.      Regulation of 3-phase alternator by ZPF and ASA
           methods.
   3.      Slip test on 3-phase alternator.
   4.      Load characteristics of 3-phase alternator by bus bar
           loading.
   5.      V and inverted V curve of synchronous motors.
   6.      Load test on 3-phase induction motor.
   7.      No load and blocked rotor test on 3-phase induction
           motor.
   8.      Study of Synchronous induction motor.
   9.      Study of induction motor starters.
   10      Separation of losses in three-phase induction motor.
   .
   11      Load test on 1-phase induction motor.
   .
   12      Equivalent circuit and pre–determination of performance
           characteristics of single-phase induction motor.
   .

Appendix
LABORATORY PRACTICE

                                            SAFETY RULES


1. SAFETY is of paramount importance in the Electrical Engineering Laboratories.

2.Electricity NEVER EXECUSES careless persons. So, exercise enough care and attention in handling
electrical equipment and follow safety practices in the laboratory. (Electricity is a good servant but a bad
master).

3.Avoid direct contact with any voltage source and power line voltages. (Otherwise, any such contact may
subject you to electrical shock)

4.Wear rubber-soled shoes. (To insulate you from earth so that even if you accidentally contact a live
point, current will not flow through your body to earth and hence you will be protected from electrical
shock)

5.Wear laboratory-coat and avoid loose clothing. (Loose clothing may get caught on an
equipment/instrument and this may lead to an accident particularly if the equipment happens to be a
rotating machine)

6.Girl students should have their hair tucked under their coat or have it in a knot.

7.Do not wear any metallic rings, bangles, bracelets, wristwatches and neck chains. (When you move your
hand/body, such conducting items may create a short circuit or may touch a live point and thereby subject
you to electrical shock)

8.Be certain that your hands are dry and that you are not standing on wet floor. (Wet parts of the body
reduce the contact resistance thereby increasing the severity of the shock)

9.Ensure that the power is OFF before you start connecting up the circuit.(Otherwise you will be touching
the live parts in the circuit)

10.Get your circuit diagram approved by the staff member and connect up the circuit strictly as per the
approved circuit diagram.

11.Check power chords for any sign of damage and be certain that the chords use safety plugs and do not
defeat the safety feature of these plugs by using ungrounded plugs.

12.When using connection leads, check for any insulation damage in the leads and avoid such defective
leads.

13.Do not defeat any safety devices such as fuse or circuit breaker by shorting across it. Safety devices
protect YOU and your equipment.
14.Switch on the power to your circuit and equipment only after getting them checked up and approved
by the staff member.

15.Take the measurement with one hand in your pocket. (To avoid shock in case you accidentally touch
two points at different potentials with your two hands)

16.Do not make any change in the connection without the approval of the staff member.

17.In case you notice any abnormal condition in your circuit ( like insulation heating up, resistor heating
up etc ), switch off the power to your circuit immediately and inform the staff member.

18.Keep hot soldering iron in the holder when not in use.

19.After completing the experiment show your readings to the staff member and switch off the power to
your circuit after getting approval from the staff member.

20.While performing load-tests in the Electrical Machines Laboratory using the brake-drums:

       i.      Avoid the brake-drum from getting too hot by putting just enough water into the brake-
               drum at intervals; use the plastic bottle with a nozzle (available in the laboratory ) to pour
               the water.(When the drum gets too hot, it will burn out the braking belts)
       ii.     Do not stand in front of the brake-drum when the supply to the load-test circuit is switched
               off. (Otherwise, the hot water in the brake-drum will splash out on you)
       iii.    After completing the load-test, suck out the water in the brake-drum using the plastic bottle
               with nozzle and then dry off the drum with a spongewhich is available in the laboratory.
               (The water, if allowed to remain in the brake-drum, will corrode it)

21.Determine the correct rating of the fuse/s to be connected in the circuit after understanding correctly
the type of the experiment to be performed: no-load test or full-load test, the maximum current expected in
the circuit and accordingly use that fuse-rating.(While an over-rated fuse will damage the equipment and
other instruments like ammeters and watt-meters in case of over load, an under-rated fuse may not allow
one even to start the experiment)



22. At the time of starting a motor, the ammeter connected in the armature circuit overshoots, as the
starting current is around 5 times the full load rating of the motor. Moving coil ammeters being very
delicate, may get damaged due to high starting current. A switch has been provided on such meters to
disconnect the moving coil of the meter during starting. This switch should be closed after the motor
attains full speed. Moving iron ammeters and current coils of wattmeters are not so delicate and hence
these can stand short time overload due to high starting current. No such switch is therefore provided on
these meters. Moving iron meters are cheaper and more rugged compared to moving coil meters. Moving
iron meters can be used for both a.c. and d.c. measurement. Moving coil instruments are however more
sensitive and more accurate as compared to their moving iron counterparts and these can be used for d.c.
measurements only. Good features of moving coil instruments are not of much consequence for you as
other sources of errors in the experiments are many times more than those caused by these meters.

23. Some students have been found to damage meters by mishandling in the following ways:
i.   Keeping unnecessary material like books, lab records, unused meters etc. causing meters to
                 fall down the table.
         ii.     Putting pressure on the meter (specially glass) while making connections or while talking or
                 listening somebody.

STUDENTS ARE STRICTLY WARNED THAT FULL COST OF THE METER WILL BE
RECOVERED FROM THE INDIVIDUAL WHO HAS DAMAGED IT IN SUCH A
MANNER.

Copy these rules in your Lab Record. Observe these yourself and
help your friends to observe..


       I have read and understand these rules and procedures. I agree to abide by these rules
and procedures at all times while using these facilities. I understand that failure to follow
these rules and procedures will result in my immediate dismissal from the laboratory and
additional disciplinary action may be taken.




Signature                                             Date                            Lab
GUIDELINES FOR LABORATORY NOTEBOOK
The laboratory notebook is a record of all work pertaining to the experiment. This
record should be sufficiently complete so that you or anyone else of similar
technical background can duplicate the experiment and data by simply following
your laboratory notebook. Record everything directly into the notebook during the
experiment. Do not use scratch paper for recording data. Do not trust your memory
to fill in the details at a later time.
Organization in your notebook is important. Descriptive headings should be used to
separate and identify the various parts of the experiment. Record data in
chronological order. A neat, organized and complete record of an experiment is just
as important as the experimental work.

1. Heading:
                     The experiment identification (number) should be at the top
of each page.Your name and date should be at the top of the first page of each day's
experimental work.
2.Object:
                       A brief but complete statement of what you intend to find out
or verify in the experiment should be at the beginning of each experiment
3.Diagram:
                       A circuit diagram should be drawn and labeled so that the
actual experiment circuitry could be easily duplicated at any time in the future.
Be especially careful to record all circuit changes made during the experiment.
4.Equipment List:
                       List those items of equipment which have a direct effect on
the accuracy of the data. It may be necessary later to locate specific items of
equipment for rechecks if discrepancies develop in the results.
5.Procedure:
                      In general, lengthy explanations of procedures are
unnecessary. Be brief. Short commentaries along side the corresponding data
may be used. Keep in mind the fact that the experiment must be reproducible from
the information given in your notebook.
6.Data:
                       Think carefully about what data is required and prepare
    suitable
data tables. Record instrument readings directly. Do not use calculated results
in place of direct data; however, calculated results may be recorded in the same table
with the direct data. Data tables should be clearly identified and each data column
labeled and headed by the proper units of measure.
7.Calculations:
                       Not always necessary but equations and sample calculations
are often given to illustrate the treatment of the experimental data in obtaining the
results.


8.Graphs:
                         Graphs are used to present large amounts of data in a concise
visual form. Data to be presented in graphical form should be plotted in the
laboratory so that any questionable data points can be checked while the
experiment is still set up. The grid lines in the notebook can be used for most
graphs. If special graph paper is required, affix the graph permanently into the
notebook. Give all graphs a short descriptive title. Label and scale the axes.
Use units of measure. Label each curve if more than one on a graph.
9.Results:
                      The results should be presented in a form which makes the
interpretation easy. Large amounts of numerical results are generally presented in
graphical form. Tables are generally used for small amounts of results.
Theoretical and experimental results should be on the same graph or arrange in the
same table in a way for easy correlation of these results.
10.Conclusion:
                      This is your interpretation of the results of the experiment as
an engineer. Be brief and specific. Give reasons for important discrepancies.
TROUBLE SHOOTING HINTS

1. Be Sure that the power is turned ON

2. Be sure the ground connections are common

3. Be sure the circuit you build is identical to your circuit diagram (Do a node by node check)

4. Be sure that the supply voltages are correct

5. Be sure that the equipment is set up correctly and you are measuring the correct parameters

6.   If steps I through 5 are correct then you probably have used a component with the wrong

     value or one that doesn’t work. It is also possible that the equipment does not work

     (although this is not probable0 or the protoboard you are using may have some unwanted

     paths between nodes. To find your problem you must trace through the voltages in your

     circuit node by node and compare the signal you expect to have. Then if they are different

     use your engineering judgment to decide what is causing the different or ask your lab

     assistant
EXP.NO. 1                                                                             DATE:

    REGULATION OF 3–PHASE ALTERNATOR BY EMF AND MMF METHODS

AIM:
       To predetermine the regulation of 3-phase alternator by EMF and MMF methods and also
draw the vector diagrams.

APPARATURS REQUIRED:

SL.NO                Name of the Apparatus                 Type             Range       Quantity
   1           Ammeter                                     MC          0 – 1/2 A            1
   2           Ammeter                                      MI         0 – 5/10 A           1
   3           Voltmeter                                   MC          0 – 10 V             1
   4           Voltmeter                                    MI         0 – 600 V            1
   5           Rheostat                                 Wire wound     250 Ω, 1.5 A         1
   6           Rheostat                                 Wire wound     1200Ω, 0.8 A         1
   7           Tachometer                                 Digital            ---            1
   8           TPST knife switch                             --               --            1

THEORY:
        The regulation of a 3-phase alternator may be predetermined by conducting the Open
Circuit (OC) and the Sort Circuit (SC) tests. The methods employed for determination of
regulation are EMF or synchronous impedance method, MMF or Ampere Turns method and the
ZPF or Potier triangle method. In this experiment, the EMF and MMF methods are used. The OC
and SC graphs are plotted from the two tests. The synchronous impedance is found from the OC
test. The regulation is then determined at different power factors by calculations using vector
diagrams. The EMF method is also called pessimistic method as the value of regulation obtained
is much more than the actual value. The MMF method is also called optimistic method as the
value of regulation obtained is much less than the actual value. In the MMF method the armature
leakage reactance is treated as an additional armature reaction. In both methods the OC and SC
test data are utilized.

PRECAUTIONS:

       (i)        The motor field rheostat should be kept in the minimum resistance position.
       (ii)       The alternator field potential divider should be kept in the minimum voltage
                  position.
       (iii)      Initially all switches are in open position.

PROCEDURE: (FOR BOTH EMF AND MMF METHODS)

   1. Note down the name plate details of the motor and alternator.
   2. Connections are made as per the circuit diagram.
   3. Switch ON the supply by closing the DPST switch.
4. Using the Three point starter, start the motor to run at the synchronous speed by adjusting
      the motor field rheostat.
   5. Conduct Open Circuit test by varying the potential divider for various values of field
      current and tabulate the corresponding Open Circuit Voltage readings.
   6. Conduct Short Circuit test by closing the TPST switch and adjust the potential divider to
      set the rated armature current and tabulate the corresponding field current.
   7. The Stator resistance per phase is determined by connecting any one phase stator winding
      of the alternator as per the circuit diagram using MC voltmeter and ammeter of suitable
      ranges.

PROCEDURE TO DRAW GRAPH FOR EMF METHOD:
    1. Draw the Open Circuit Characteristic curve (Generated Voltage per phase VS Field
       current).
    2. Draw the Short Circuit Characteristics curve (Short circuit current VS Field current)
    3. From the graph find the open circuit voltage per phase (E1 (ph) for the rated short
       circuit current (Isc).
    4. By using respective formulae find the Zs, Xs, Eo and percentage regulation.

PROCEDURE TO DRAW GRAPH FOR MMF METHOD:
    1. Draw the Open Circuit Characteristic curve (Generated Voltage per phase VS Field
       current).
    2. Draw the Short Circuit Characteristics curve (Short circuit current VS Field current)
    3. Draw the line OL to represent


FORMULAE:
  1. Armature Resistance Ra =         Ω

   2. Synchronous Impedance Zs = O.C. voltage
                                S.C. current

   3. Synchronous Reactance Xs = √ Zs2 – Ra2

   4. Open circuit voltage for lagging p.f = √(VcosΦ + IaRa)2 + (VsinΦ + IaXs)2

   5. Open circuit voltage for leading p.f. = √(VcosΦ + IaRa)2 + (VsinΦ – IaXs)2

   6. Open circuit voltage for unity p.f =    √(V + IaRa)2 + ( IaXs)2

   7. Percentage regulation = Eo – V x 100
                                 V

RESULT:
      Thus the regulation of 3-phase alternator has been predetermined by the EMF and MMF
methods.
VIVA QUESTIONS:

  1. What is meant by voltage regulation?

  2. What is meant by Synchronous Impedance?

  3. What is OC test ?

  4. What is SC test?

  5. What is meant by mmf or field ampere turns?
REGULATION OF 3-PHASE ALTERNATOR BY EMF AND MMF METHODS

                                TABULAR COLUMNS

OPEN CIRCUIT TEST:

        Field Current (If)        Open Circuit Line      Open circuit Phase
S.No.                              Voltage (VoL)          Voltage (Voph)
               Amps                    Volts                   Volts




SHORT CIRCUIT TEST:

                                              Short Circuit Current (120%
           S.No.         Field Current (If)    to 150% of rated current)
                                                          (ISC)
                               Amps                      Amps
REGULATION OF 3-PHASE ALTERNATOR BY EMF AND MMF METHODS

                                  TABULAR COLUMNS

  EMF METHOD:

                                        Eph (V)                      % Regulation
  SL.NO.         Power
                 factor         Lag               Lead             Lag         Lead




  MMF METHOD:

                                                  Ifr          Eph (V)       % Regulation
SL.NO.     P.F      Vph   If1         If2         (A)
                    (V)   (A)         (A)   Lag       Lead   Lag     Lead   Lag       Lead
EXP.NO. 2                                                                           DATE:

   REGULATION OF 3-PHASE ALTERNATOR BY POTIER AND ASA METHODS

AIM:
        To predetermine the regulation of three phase alternator by Potier and ASA methods and
also to draw the vector diagrams.

APPARATURS REQUIRED:

SL.NO           Name of the Apparatus                    Type           Range          Quantity
   1       Ammeter                                      MC           0 – 1/2 A              1
   2       Ammeter                                       MI          0 – 5/10 A             1
   3       Voltmeter                                    MC           0 – 10 V               1
   4       Voltmeter                                     MI          0 – 600 V              1
   5       Rheostat                                  Wire wound      250 Ω, 1.5 A           1
   6       Rheostat                                  Wire wound      1200Ω, 0.8 A           1
   7       Tachometer                                  Digital             ---              1
   8       TPST knife switch                              --                --              1

FORMULAE USED:

Percentage regulation = Eo – Vrated x 100      (For both POTIER & ASA methods)

                          Vrated
PRECAUTION:
    (i)   The motor field rheostat should be kept in the minimum resistance position.
    (ii)  The Alternator field potential divider should be in the position of minimum
          potential.
    (iii) Initially all switches are in open position.

PROCEDURE FOR BOTH POTIER AND ASA METHODS:

   1.   Note down the complete nameplate details of motor and alternator.
   2.   Connections are made as per the circuit diagram.
   3.   Switch on the supply by closing the DPST main switch.
   4.   Using the Three point starter, start the motor to run at the synchronous speed by varying
        the motor field rheostat.
   5.   Conduct an Open Circuit Test by varying the Potential Divider for various values of
        Field current and tabulate the corresponding Open circuit voltage readings.
   6.   Conduct a Short Circuit Test by closing the TPST knife switch and adjust the potential
        divider the set the rated Armature current, tabulate the corresponding Field current.
   7.   Conduct a ZPF test by adjusting the potential divider for full load current passing through
        either an inductive or capacitive load with zero power and tabulate the readings.
   8.   Conduct a Stator Resistance Test by giving connection as per the circuit diagram and
        tabulate the voltage and Current readings for various resistive loads.
PROCEDURE TO DRAW THE POTIER TRIANGLE (ZPF METHOD):
         (All the quantities are in per phase value)

  1. Draw the Open Circuit Characteristics (Generated Voltage per phase VS Field Current)
  2. Mark the point A at X-axis, which is obtained from short circuit test with full load
     armature current.
  3. From the ZPF test, mark the point B for the field current to the corresponding rated
     armature current and the rated voltage.
  4. Draw the ZPF curve which passing through the point A and B in such a way parallel to
     the open circuit characteristics curve.
  5. Draw the tangent for the OCC curve from the origin (i.e.) air gap line.
  6. Draw the line BC from B towards Y-axis, which is parallel and equal to OA.
  7. Draw the parallel line for the tangent from C to the OCC curve.
  8. Join the points B and D also drop the perpendicular line DE to BC, where the line DE
     represents armature leakage reactance drop (IXL)
          BE represents armature reaction excitation (Ifa).

  PROCEDURE TO DRAW THE VECTOR DIAGRAM (ZPF METHOD)

  1. Select the suitable voltage and current scale.
  2. For the corresponding power angle ( Lag, Lead, Unity) draw the voltage vector and
      current vector OB.
  3. Draw the vector AC with the magnitude of IRa drop, which should be parallel to the
      vector OB.
  4. Draw the perpendicular CD to AC from the point C with the magnitude of IXL drop.
  5. Join the points O and D, which will be equal to the air gap voltage (Eair).
  6. Find out the field current (Ifc) for the corresponding air gap voltage (Eair) from the OCC
      curve.
  7. Draw the vector OF with the magnitude of Ifc which should be perpendicular to the
      vector OD.
  8. Draw the vector FG from F with the magnitude Ifa in such a way it is parallel to the
      current vector OB.
  9. Join the points O and G, which will be equal to the field excitation current (If).
  10. Draw the perpendicular line to the vector OG from the point O and extend CD in such a
      manner to intersect the perpendicular line at the point H.
  11. Find out the open circuit voltage (Eo) for the corresponding field excitation current (If)
      from the OCC curve.
  12. Find out the regulation from the suitable formula.

PROCEDURE TO DRAW THE POTIER TRIANGLE (ASA METHOD):
         (All the quantities are in per phase value)

  1. Draw the Open Circuit Characteristics (Generated Voltage per phase VS Field Current)
  2. Mark the point A at X-axis, which is obtained from short circuit test with full load
     armature current.
  3. From the ZPF test, mark the point B for the field current to the corresponding rated
     armature current and the rated voltage.
4. Draw the ZPF curve which passing through the point A and B in such a way parallel to
       the open circuit characteristics curve.
   5. Draw the tangent for the OCC curve from the origin (i.e.) air gap line.
   6. Draw the line BC from B towards Y-axis, which is parallel and equal to OA.
   7. Draw the parallel line for the tangent from C to the OCC curve.
   8. Join the points B and D also drop the perpendicular line DE to BC, where the line DE
       represents armature leakage reactance drop (IXL)
            BE represents armature reaction excitation (Ifa).
   9. Extend the line BC towards the Y-axis up to the point O’. The same line intersects the air
       gap line at point G.
   10. Mark the point I in Y-axis with the magnitude of Eair and draw the line from I towards
       OCC curve which should be parallel to X-axis. Let this line cut the air gap line at point H
       and the OCC curve at point F.
   11. Mention the length O’G, HF and OA.


   PROCEDURE TO DRAW THE VECTOR DIAGRAM (ASA METHOD)
       (To find the field Excitation current If)

   1. Draw the vector with the magnitude O’G.
   2. From G draw a vector with the magnitude of GH (OA) in such a way to make an angle of
      (90 ± Φ) from the line O’G [ (90 + Φ) for lagging power factor and (90 – Φ) for leading
      power factor]
   3. Join the points O’ and, H also extend the vector O’F with the magnitude HF. Where O’F
      is the field excitation current (If).
   4. Find out the open circuit voltage (Eo) for the corresponding field excitation current (If)
      from the OCC curve.
   5. Find out the regulation from the suitable formula.


RESULT:

      Thus the regulation of 3-phase alternator has been predetermined by the Potier and ASA
methods.

VIVA QUESTIONS:

   1. What is meant by ZPF Test?

   2. What is Potier reactance? How is it determined by Potier triangle?

   3. What is meant by armature reaction reactance?

   4. What is the significance of the ASA modification of MMF method?

   5. What is air gap line in Potier method?
EXP.NO. 3                                                                              DATE:
                      SLIP TEST ON 3-PHASE ALTERNATOR

AIM:
       To conduct a slip test on 3-Ф alternator and pre-determine the regulation through vector
diagram.

APPARATUS REQUIRED:

S.no              Name of             Range              Type               Quantity
                  Apparatus
1                 Ammeter             (0-5)A             MI                 1
                                      (0-1)A             MC                 1
2                 Voltmeter           (0-150)V           MI                 1
                                      (0-5)V             MC                 1
3                 Rheostat            250 Ω /1.5A                           1
4                 Tachometer                             Digital            1
5                 TPST Switch                                               1
6                 Connecting                                                As reqd.
                  Wires

FUSE RATING:

(a)For Motor- 125% of rated current
              = 125% of 17A=21.25A=25A

(b)For Alternator- 125% of rated current
                      =125% of 4A= 5A

THEORY:

In a salient pole alternator, the reactance of magnetic circuit along is along its quad stator axis.
The alternator is driven by auxiliary prime mover at a speed slightly less than the synchronous
speed under these conditions. The armature current is when the armature current mmf is in line
with the field poles. The reactance by the magnetic field current is minimum. The ratio of
maximum voltage to minimum current gives the direct axis impedance and the ratio of minimum
voltage to maximum current gives the armature axis impedance.

PRECAUTIONS:

    1. The motor field rheostat should be kept in minimum.
    2. The direction of the rotation due to prime mover and the alternator on the motor should
       be the same.
    3. Initially all the switches are kept open.
PROCEDURE:

  1.   Note down the name plate details of motor and alternator.
  2.   Connections are made as per the circuit diagram.
  3.   Give the supply by closing the DPST switch.
  4.   Using the three point starter, start the motor to run at the synchronous speed by varying
       the motor field rheostat at the same time check whether the alternator field has been
       opened or not.
  5.   Apply 20% to 30% of the rated voltage to the armature of the alternator by adjusting the
       autotransformer.
  6.   To obtain the slip and the maximum oscillation of pointers the speed is reduced slightly
       lesser than the synchronous speed.
  7.   Maximum current, minimum current, maximum voltage and minimum voltage are noted.
  8.   Find out the direct and quadrature axis impedances.

  PROCEDURE TO DRAW THE VECTOR DIAGRAM:

  1. Draw the line OA that represents the rated voltage V.
  2. Draw the line OB vector to represent the rated current I, which makes an angle Φ (it may
      lag/lead/in phase) with the voltage.
  3. Draw the line AC vector to represent IRa drop, which is parallel to OB vector.
  4. Draw the perpendicular line CD to the line AC (IRa drop) that represents IXq drop.
  5. Draw the line from the origin through the point D, which represents the no load voltage
      (Eo).
  6. Draw the pole axis through origin, which should be perpendicular to vector OD.
  7. Draw a perpendicular line to the pole axis from the same point E which should pass
      through the point B [where vector OE represents Direct Axis Current (Id) and Vector EB
      represents Quadrature Axis Current (Iq)].
  8. Find out the reactive voltage drops IdXd and IqXq.
  9. Draw a parallel line (ie perpendicular to Id) to OD vector from the point C, with the
      magnitude of the drop IdXd (Line CF).
  10. Draw a parallel line (ie perpendicular to Iq) to OE vector from the point F, with the
      magnitude of the drop IqXq (Line FG).
  11. Let the point at where the IqXq drop meets the OD line be G. here the vector OG
      represents the no load voltage (Eo).
  12. Find out the voltage regulation by using the suitable formula.

FORMULAE USED:

  1. Rac=1.6Rac Ω

  2. Zd = Vmax/Imin Ω

  3. Zq = Vmin/Imax Ω

  4. Xd = √Zd2 – Rd2         Ω
5. Xq = √Zq2 – Rd2 Ω

    6. Id = Ia sinФ amps

    7. Iq = Ia cos Ф amps

    8. %Reg = (Eo-V/V)*100

       Where,

       Zd = direct axis impedance in Ω
       Zq = quadrate axis impedance in Ω
       Xd = direct axis reactance in Ω
       Xq = quadrate axis reactance in Ω
       Id = direct axis current in amps
       Ia = quadrate axis current in amps

GRAPH:

       Power Factor VS % regulation.


RESULT:

       Thus the pre-determination of regulation of 3-phase alternator by vector diagram was
obtained.



VIVA QUESTIONS:

           1. What is the purpose of slip test on 3 phase alternator?

           2. What is meant by direct axis reactance?

           3. What is meant by quadrature axis reactance?

           4. How is the regulation of alternator predetermined by slip test?

           5. What is the difference between salient pole alternator and cylindrical rotor type
              alternator?
SLIP TEST ON 3-PHASE ALTERNATOR

                                    TABULAR COLUMNS

  (i)        To find the Direct Axis and Quadrature axis impedances:

S.NO              Vmax              Vmin               Imax                 Imin

   1


   2



  (ii)       To predetermine % Regulation:

       S.NO
                   Power Factor                  % Regulation


                                      Lagging       Leading        Unity


         1              0.2                                            --


         2              0.4                                            --


         3              0.6                                            --


         4              0.8                                            --


         5              1.0
EXP.NO. 4                                                                       DATE:

           LOAD CHARACTERISTICS OF 3-PHASE ALTERNATOR
                      BY BUS BAR LOADING

AIM:
       To synchronize and operate the two electric sources in parallel with bus bar arrangement
and draw the performance characteristic curves.

NAME PLATE DETAILS:
          3Ǿ alternator            DC shunt motor                    3ǾLoad


FUSE RATING:
         125% of rated current (full load current)

          For DC shunt motor:

          For ac alternator

APPARATUS REQUIRED:

S.No Name of apparatus Type Range                         Quantity
  1     Ammeter                     MC        0-2A               1
  2     Ammeter                     MI        0 – 10 A           1
  3     Voltmeter                   MI        0 – 600 V          1
  4     Frequency meter             Reed      0 – 60 Hz          1
  5     Rheostat                    Wire      1200 Ω             1
                                    wound     0.8 A
  6     Rheostat                    Wire      250 Ω              1
                                    wound     1.5 A
  7     Tachometer                  Digital     --               1

PRECAUTIONS:
           (1) The motor field rheostat should be in minimum resistance position.
           (2) The Alternator field Potential divider should be at minimum voltage position.
           (3) Initially all switches are in open position.
PROCEDURE:
     SYNCHRONISATION:

           (1)         Note down the name plate details of motor and alternator.
           (2)         Connections are made as per the circuit diagram.
           (3)         Close the DPST switch.
           (4)         Using the 3-point starter start the motor, by varying motor field rheostat.
           (5)         By varying the potential divider , generated voltage is built up to rated
                       voltage.
           (6)         Now close the TPST switch.
           (7)         TPST is closed and by varying the potential divider the field current is varied
                       so that voltmeter reads the same voltage as measured above.
           (8)         When TPST is closed the lamps may flicker uniformly.
           (9)         If flickering is not uniform then the phase sequences of any two lines are
                       changed.
           (10)        Now synchronization switch is closed when lamps are in dark period .
           (11)        Now the two sources are synchronized.

           LOAD SHARING
             (1)        Connect the synchronized output with variable load.
             (2)        For various loads, note all the corresponding ammeter and voltmeter
                        readings.
             (3)        Draw the graph between respective voltage and currents (V1 Vs V2, V2 Vs
                        I1 and V1 Vs I1.).

V-CURVE
                 (1)    After synchronization the prime mover should be switched off and
                        Potential divider should be brought to the maximum position.
                 (2)    By adjusting the potential barrier tabulate the various Field currents
                         and corresponding Armature readings.
                 (3)     To obtain V- curve draw the graph between Armature current and
                         Field current

RESULT:
       The 3 phase alternator has been synchronized with the bus bars and the load
characteristics obtained.

VIVA QUESTIONS:
   1. What is meant by synchronization?

   2. What are the conditions for synchronization?

   3. What is infinite bus?

   4. What are the methods of synchronization?

   5. How can the voltage and frequency be adjusted?
EXP.NO. 5                                                                    DATE:

                   V AND INVERTED V CURVE OF THREE PHASE
                            SYNCHRONOUS MOTOR

AIM
       To draw the V and inverted V curves of a 3 phase Synchronous Motor.

NAME PLATE DETAILS:

3ǾSYNCHRONOUS MOTOR                                         DC EXCITATION



FUSE RATING:l
125% of rated current (full load current)
For DC excitation:
For synchronous motor:]


APPARATUS REQUIRED:
S.No Name of the  Type                        range           Quantity
     apparatus
1    Ammeter      MI                          (0-5)A          2

2.       Voltmeter                    MI      (0-600)V        2

3.       Ammeter                      MC      (0-2)A          1

4.       Rheostat                             200Ω,15         1
                                              A
5.       Wattmeter                    UPF                     2
                                              600V,5A
PRECAUTION:
    (1) The Potential barrier should be in maximum position.
    (2) The motor should be started without load .
    (3) Initially TPST switch is in open position.

PROCEDURE:
     (1)   Note down the name plate details of the motor.
     (2)   Connections are made as pr the circuit diagram..
     (3)   Close the TPST switch.
     (4)   By adjustingthe autotransformer from the minimum position to the maximum
           position the rated supply is given to motor. The motor starts as an induction motor.
     (5)   In order to give the excitation to the field for making it to run as the synchronous
           motor, close the DPST switch.
     (6)   By varying the field rheostat note down the excitation current, armature current and
           the power factor for various values of excitation.
     (7)   The same process has to be repeatedfor loaded condition.
     (8)   Later the motor is switched offand the graph is drawn.

GRAPH:
     The graph is drawn for-
         (1) Armature current Vs Excitation current.
         (2) Power factor Vs Excitation current.




RESULT:

    The V-curves and inverted V-curves of the 4 phase synchronous motor have been drawn.
EXP.NO. 6 A                                                                DATE:

     LOAD TEST ON 3-PHASE SQUIRREL CAGE INDUCTION MOTOR

AIM:
      To draw the performance characteristics of 3-phase squirrel cage induction motor by
conducting load test.

APPARATUS REQUIRED:

S.No              Name of           Range              Type              Qty.
                  apparatus
1.                Ammeter           (0-5)A             MI                1
2.                Voltmeter         (0-600)V           MI                1
3.                Wattmeter         (600V,5A)          UPF               2
4.                Tachometer                           Digital           1
5.                3-Ф                                                    1
                  autotransformer

FUSE RATING;

               125% of 4.8A=6A=10A

THEORY:

A 3-phase induction motor consists of stator and rotor with the other associated parts. In the
stator, a 3-phase winding is provided. The windings of the three phase are displaced in space by
120º.A 3-phase current is fed to the 3-phase winding. These windings produce a resultant
magnetic flux and it rotates in space like a solid magnetic poles being rotated magnetically.
PRECAUTIONS-

1.TPST switch is kept open initially.
2.Autotransformer is kept at min. voltage position.
3.There must be no load when starting the load.

PROCEDURE-

1.Connections are given as per circuit diagram.
2.3-Ф induction motor is started with DOL starter.
3. If the pointer of one of the wattmeter readings reverses, interchange the current coil terminals
and take the reading as negative.
3.The no load readings are taken.
4. The motor is loaded step by step till we get the rated current and the readings of the voltmeter,
ammeter, wattmeters, spring balance are noted.

FORMULAE USED-

       1)   % slip= (Ns-N/Ns)*100
       2)   Input Power = (W1+W2)watts
       3)   Output Power = 2∏NT/60 watts
       4)   Torque = 9.81*(S1-S2)*R N-m
       5)   % efficiency = (o/p power/i/p power)* 100

GRAPHS-

       1)   Output Power vs Efficiency
       2)   Output Power vs Torque
       3)   Output Power vs Speed
       4)   Output Power vs %s


RESULT
Thus the performance characteristics of a 3-Ф squirrel cage induction motor by conducting load
test has been drawn.
EXP.NO. 6 B                                                                 DATE:

        LOAD TEST ON 3-PHASE SLIP RING INDUCTION MOTOR

AIM :
       To conduct a direct load test on a 3-phase slip ring induction motor and to draw the
performance characteristics.


APPARATUS REQUIRED :

S.NO              NAME OF            RANGE              TYPE               QTY.
                  APPARATUS
1                 Ammeter                               MI                 1
                                     (0-10)A
2                 Voltmeter          (0-600)V           MI                 1
3                 Wattmeter          (600V,10A)         UPF                2
4                 Tachometer                            Digital            1



FUSE RATING-

FOR- STATOR- 125% 0f 7.5A = 10A
FOR ROTOR – 125% of 11A = 15A

THEORY:

Slip ring induction motor is also called as phase wound motor. The motor is wound for as many
poles as the no. of stator poles and always wound 3-Ф even while the stator is wound two-phase.
The other three windings are brought out and connected to three insulated slip-rings mounted on
the shaft with brushes resting on them. These three brushes are further externally connected to a
three phase star connected rheostat. This makes possible the introduction of an additional
resistance in the rotor circuit during starting period for increasing starting torque of the motor.
PRECAUTIONS:

   1. TPST switch is kept open initially.
   2. The external resistance in the rotor circuit should be kept at max. value.

PROCEDURE:
  1. Connections are given as per circuit diagram.
  2. After observing precautions motor is started on no load.
  3. As speed increases, the external resistance is gradually cut out.
  4. The no-load readings are taken.
  5. If the pointer in one of the wattmeter reverses, interchange the current coil terminals and
     take the reading as negative.
  6. The meter readings are then noted for various load conditions.

FORMULAE USED:

    1.   Torque= (S1-S2)*9.81*100 N-m
    2.   O/P Power= 2πNT/60 watts
    3.   I /P Power = (W1+W2) watts
    4.   η % = (o/p power/ i/p power)*100
    5.   %s = (Ns-N)/Ns*100

GRAPHS:

   1.    O/P power vs Speed
   2.    O/P power vs Torque
   3.    O/P Power vs η
   4.    O/P Power vs slip
   5.    Torque vs Speed
   6.    Torque vs Slip


RESULT:

The load test on 3-Ф slip ring induction motor was conducted and the performance
characteristics curves were plotted.
EXP.NO. 7                                                                    DATE:

            NO LOAD AND BLOCKED ROTOR TEST ON 3- PHASE
                         INDUCTION MOTOR

AIM:        To conduct the no load & blocked rotor test on 3- phase induction motor
              & to draw the equivalent circuit of 3- phase squirrel cage induction motor.


APPARATUS REQUIRED :-
z
S.NO               NAME OF             RANGE               TYPE               QTY
                   APPARATUS
1.                 Voltmeter           (0-600)V            MI                 01
                                       (0-150)V            MI                 01
2.                 Ammeter             (0-10)A             MI                 01
3.                 Wattmeter           (600V,5A)           UPF                01
                                       (150V,10A)          LPF                01
4.                 Connecting wire                                            As required




FUSE RATING :-

       125/100 * 7.5 A ≈ 10A



THEORY :-

A 3-phase induction motor consists of stator, rotor & other associated parts. In the stator
,a 3- phase winding (provided) are displaced in space by 120. A3- phase current is fed to the
winding so that a resultant rotating magnetic flux is generated. The rotor starts rotating due to the
induction effect produced due the relative velocity between the rotor
Winding & the rotating flux.

PRECAUTIONS          :-

NO LOAD TEST –

(1).   Initially TPST switch is kept open.
(2).   Autotransformer must be kept at minimum potential position.
(3).   The machine must be started at no load.
BLOCKED ROTOR TEST -

(1). Initially the TPST switch is kept open.
(2). Autotransformer must be kept at minimum potential position.
(3). The machine should be started on full load.


PROCEDURE :-

NO LOAD TEST -

(1).   Connections are given as per the circuit diagram.
(2).   Precautions are observed and motor is started on the no load.
(3).   Autotransformer is varied to have rated voltage applied.
(4).   The meter readings are then tabulated.


BLOCKED ROTOR TEST :-

(1).   Connections are given as per circuit diagram.
(2).   Precautions are observed and motor is started on full load or blocked rotor position.
(3).   Autotransformer is varied to have rated current flowing in motor.
(4).   The meter readings are then tabulated.

FORMULA USED-


FOR NO LOAD TEST-

Wsc = √3 Vo IoCOSФ watts
Iw = Io cosФ amps
 Ro= V0/ Iw Ω
Xo= Vo/Iu Ω

FOR BLOCKED ROTOR TEST-

Wsc =3I2*Ro watts
Ro1 = Wsc/3(Isc)2 Ω
Zo1 = Vsc/Isc Ω
Xo1 = √Zo1^2-Ro1^2 Ω

RESULT:-

       Thus the no load and blocked rotor test on 3-Фsquirrel cage induction motor is performed
and the equivalent circuit of 3-phase squirrel cage induction motor has been drawn.
TABULAR COLUMNS


NO LOAD TEST:

S.No    Voltage          Current        Wattmeter            W1 x     Wattmeter       W2 x
          Voc              Ioc          readings (W1)        mf1      readings (W2)   mf2
                                        Observed             Actual   Observed        Actual
        Volts            Amps                                Watts                    Watts
  1




                Voc= open circuit voltage
                Ioc = open circuit current


BLOCKED ROTOR TEST:

S.No.    Voltage           Current            Wattmeter      W1 x     Wattmeter    W2 x
           Vsc               Isc              readings(W1)   mf1      readings(W2) mf2
                                              Observed       Actual   observed     Actual
            Volts          Amps                              Watts                 Watts
  1.


                Vsc = short circuit voltage
                Isc = short circuit current
EXP.NO. 8                                                                        DATE:

                    STUDY OF SYNCHRONOUS INDUCTION MOTOR

AIM:-
      To study the construction, working principle and performance characteristics of
Synchronous Induction Motor.

APPARATUS REQUIRED:-

                     3 Phase Synchronous Induction Motor with loading arrangement
                     Auto Induction Starter panel – 1
                     TPDT knife switch - 1
                     Tachometer - 1

THEORY:-

            In the applications where high starting torque and constant speed are desired then
synchronous induction motor can be used. It has the advantages of both synchronous motor and
induction motor. The synchronous motor gives constant speed whereas induction motors can be
started against full load torque.

           Consider a normal slip ring induction motor having three phase winding on the rotor
as shown in the figure.

           The motor is connected to the exciter which gives d.c. supply to the rotor through slip
rings. One phase carries full d.c. current while the other two carries half the full d.c. current as
they are connected in parallel. Due to this d.c. excitation, permanent poles (N and S) formed on
the rotor.

           Initially it is run as a slip ring induction motor with the help of starting resistances.
When the resistances are cut out the motor runs with a slip. Now the connections are changed
and the exciter is connected in series with the rotor windings which will remain in the circuit
permanently.

            As the motor is running as induction motor initially high starting torque (up to twice
full load value) can be developed. When the d.c. excitation is provided it is pulled into
synchronism and starts running at constant speed. Thus synchronous induction motor provides
constant speed, large starting torque, low starting current and power factor correction.

PRECAUTIONS:

           1. The motor should be started without load.
           2. The rotor resistance starter should be kept in the maximum resistance position
              while starting.
           3. The field potential divider should be kept in the maximum resistance position.
PROCEDURE:

          1. Note down the name plate details of the motor.
          2. Connections are given as per the circuit diagram.
          3. Close the TPST switch in order to supply the rated voltage to the motor.
          4. Start the motor by closing the TPDT switch (position 123) with the rotor
             resistance starter in maximum resistance position to run the motor at rated speed.
          5. Change the position of TPDT switch (position 1’2’3’) in order to excite the rotor
             by DC source where the excitation should be given gradually through the
             potential divider to maintain the synchronous speed.
          6. The resistance if the stator can be measured using Dc supply with voltmeter and
             ammeter or directly using a multimeter.

RESULT:

          The working principle and performance characteristics of the synchronous induction
motor have been studied.
EXP.NO. 9                                                                     DATE:

                      STUDY OF INDUCTION MOTOR STARTERS

AIM:
       To study and connect
              (1) Direct Online Starter

              (2) Auto transformer Starter

              (3) Star Delta Starter

              (4) Rotor Resistance Starter


APPARATUS REQUIRED:
SL.NO            NAME OF APPARATUS                                                QUANTITY
   1.                   DOL Starter                                                 1 No.
   2.             Auto transformer Starter                                          1 No.
  3.                 Star Delta Starter                                             1 No.
   4.             Rotor Resistance Starter                                          1 No.

THEORY:
NECESSITY OF STARTERS:
        An induction motor is similar to a secondary short circuit three phase transformer so if
normal voltage is applied to the motor it takes 5 to 6 times of normal current from the mains and
starting torque is also increased to around 1.5 to 2.5 times of their full load torque. This initial
excessive starting current is objectionable, because it will produce large line voltage drop,
which in turn will affect the operation of the other electrical equipments connected to the same
mains. So the starters are used to reduce the starting current of induction motor and also to
protect the motor and also used to protect the motor from overloading and low voltages.

TYPES OF STARTERS:
          (1) Direct Online Starter

              (2) Auto transformer Starter

              (3) Star Delta Starter

              (4) Rotor Resistance Starter



DIRECT ON LINE STARTER [DOL STARTER]:-

  Generally when the starter winding of on induction motor are connected to the
  Supply directly .a very large current of about 5-8 times full load current flow initially.
  such a starting .of the induction motor is called direct on line starting. The initial stage
current decreases of the motor starts accelerating and running at normal speed.
     Unlike d.c motors where such a starting can damage the windings due to a lsent 0/- back
Emf at start induction motor can le started .This way through out not expandly in a short space
of time called cycling .The only effect of the shorting is the sudden line voltage drop that occurs
which may affect other electrically equipments on the same time line .hence direct an line
starting is not advisable for motor with rating greater than 5 HP. The points to be kept in mind
for DOL starting are

           •   Whether other electrical equipment connected to the same lines can with stand
               The sudden voltage fluctuation caused by the starting.
           •   Whether the generator and distribution system can with stand the high voltage
               Dip and large current drawn .
           •   In case of loads having high inertia like centrifugal oil separate time may also be a
               factor

   REASON FOR AVOIDING FAST CYCLING
   At start the starting current Ist is about 5-8 times normal full load current .therefore
   The starting heat generated itself is related to 1st as

                                  Hst α Ist2
   And Hst is 26-64 times normal heating also at start there is no winding and other losses .
Hence repeated starting in short space of time or fast cycling may cause successive heat and
damage of coil .

    HOW THE STARTER WORKS:

                 Control circuit:
                           Thus circuit consists of conductor coil in series with start button stop
Button and over load trip contacts is called control circuit. When the start button is pressed the
control circuit energized to via lines of the 3 phase supply is connected the control coil the
contactor classes and starts
     The motor after releasing the start .It spring back but the contactor is kept enargised by
    another auxillary winding . When the stop button is released proceed, it break the circuits
     & the contactors trips & the motor stops.
    Under excess current leaving drawn the over current trip coil are energized magnetic coil or
the normally open (NO) the overload trip contact and stop the motor.

AUTO TRANSFORMER STARTER
      This stator is useful and suitable for motor in which each and of the 3-phase are not all
throughout and hence are not suitable for star delta starting gapped or variable autotransformer
can be used for starting.
 The autotransformer are generally used for large motor drives like electric cargo pumps because
of cost factors .

  STAR-DELTA-STARTER
     This starter is used in case of motor which are built normally with a delta connected stator
winding. Basically it consist a two way switch that connected the motor star type of the time
 of start and delta type under normal running connection . The advantages of having a star
connected winding the voltage applied over each motor phase is reduced to 1/√ 3 times the
normal value and the current to 1/√3 time normal value . But the starting torque is also reduced
by a factor of 1/√3.
ROTOR RHEOSTAR STATOR
                            This stator is used for starting slip motors in this the stator terminal are
     Connected to supply via a variable resistance in series to the stator circuit .
     The controlling resistance is after connected rheostat type with resistance being gradually
cot out as
     Motor gain speed. The two advantages of this starting is:-
     1) starting current is reduced
     2) starting torque is increased due to power factor improvement.
     The controlling rheostat may be of speed or contactor type and may also be manual or auto
noted.
     The starter also consist of low voltage and over current protective devices. There is inter
locking mechanism for ensuring proper operation of line contactor and starter.
     This method is similar to the starter used for starting dc motor in which too, the resistance is
cut out gradually ones the motor was started running normally.

 PRECAUTIONS:
     (1) All connections should be tight.

        (2) Metallic body of every equipment used must be properly earthed.


PROCEDURE:
  1. Connect the DOL starter with the motor terminal in one side and motor switch on another
     side as shown in figure.

    2. Put ON the switch and press the start button (green) of the starter to start the motor.

    3. Press the stop button (red) to stop the motor.

    4. Connect the auto transformer terminals with the motor terminals and motor switch as
       shown in figure.

    5. Now adjust the required settings on autotransformer starter that is above 60%.

    6. Out ON the switch, now the motor will start running. When the motor speed reaches to
       about 80% of the normal speed, then move the handle of the starter and to other side for
       giving full voltage to the motor.

    7. Connect the Star Delta starter with the motor on one side and motor switch in another
       side as shown in figure.

    8. Put on the switch and move the handle of the starter first in downward position thus
       connecting the winding first in Star and after a few seconds move it in upward position
       thus connecting the winding in Delta connection.

    9. Connect the rotor resistance starter with the motor on one side and motor switch on
       another side as shown in figure.
10. Put ON the switch and start the motor with the rotor resistance.

RESULT:

               Hence various types of the three phase induction motor starters have been
studied.
EXP.NO. 10                                                                   DATE:

      SEPARATION OF LOSSES IN THREE PHASE SQUIRREL CAGE
                      INDUCTION MOTOR

AIM:
      To separate the no load losses of a 3 phase squirrel cage induction motor as iron losses
and mechanical losses.

NAME PLATE DETAILS:

3Ø induction motor                                                     Auto Transformer




FUSE RATING:

     No load :10% of rated current (full load current).


APPARATUS REQUIRED:
S.No Name of the apparatus              Type     Range         Quantity


1.        Ammeter                       MI       (0-10)A       1

                                        MC       (0-1)A        1

2.        Voltmeter                     MI       (0-600)V      1

                                        MC       (0-5)V        1

3.        Wattmeter                     LPF      600V,5A       2

4.        3-Ф Auto Transformer                   (415/0-470)   1
                                                 V
          Rheostat
5.                                               1200Ω/0.8A        1


PRECAUTIONS:
(1) The autotransformer should be kept in minimum voltage position.
(2) the motor should not be loaded throughout the experiment.
PROCEDURE:

(1) Connections should be made as per the circuit diagram.
(2) by giving three phase supply , start the motor.
(3)vary the autotransformer till rated speed is attainsd and note the input power, voltage and
current.
(4)repeat the same procedure for and tabulate the reading.
(5)find the stator copper loss and constant loss by respective formulas.
(6)draw the suitable graph to find the mechanical losses.
(7)obtain the core los by separating the mechanical loss fom constant losses.


GRAPH:
The graph drawn between constant losses(watts) and input voltage(volts).

MODEL CALCULATIONS:

  1. Input power(W) =(W1+W2)in watts
  2. Stator copper loss =3I2Rs in watts
  3. Constant loss/phase(Wc)= (W-3I2Rs)/3 in watts
  4 Core loss/phase (Wi)= (constant loss/phase)-mechanical loss



RESULT:
        Thus the no load losses of 3-phase squirrel cage induction motor was separated as core
losses and mechanical losses.
EXP.NO. 11                                                                   DATE:

                LOAD TEST ON SINGLE PHASE INDUCTION MOTOR

AIM:
       To determine the performance characteristic of a given single phase capacitor start
induction motor by conducting load test.


APPARATUS REQUIRED:


           SL. NO         APPARATUS            RANGE              TYPE      QUANTITY
               1          Voltmeter         (0-300)V               MI             1
               2          Ammeter           (0-10)A               MI              1
               3          Wattmeter        300 V, 10A              UPF            1
               4          Tachometer                                              1
               5          Connecting wires                                  As required


FUSE RATING :

         Fuse rating = 125% of rated current = 125/100 * 7.5
                     ≈ 10A


THEORY:

         The single phase induction motor is more or less a polyphase induction motor. The only
         difference is that is given supply in single phase. This motor connect and motor function
         without any initial start the motor having some part which is called starter and rotor.
These
         are two types of starting a 1 phase induction motor namely capacitor-start and other is
split-
         phase. These motors are widely used in domestic purpose.


 PRECAUTION:

    1)     Before switching on the supply the variac is kept in minimum position.

    2)     Initially these should be on no load while starting the motor.
PROCEDURE:

   1)  Connections are given as per the circuit diagram.
   2)   Switch on the supply at no load condition.
   3)  Apply the rotor voltage to the motor using the variac and note down the readings at
     ammeter
       And wattmeter.
   4) Vary the load in suitable steps and note down all the meter readings till fill load
     condition.



FORMULA USED:
  1) Torque ,T = (S1~S2)*9.81*R N.m

   2) Output power = 2π NT/60*W

   3) Effecting (η%) = 0/P Power/I/p Power*100

   4) Slip (%S) = NS – N/NS*100

   5) Power factor = Cos φ=W/VI

GRAPH :

   1)   Output Power Vs speed
   2)   Output power Vs Torque
   3)   Output power Vs Effecting
   4)   Output power Vs slip
   5)   Output power Vs Power factor

RESULT:
         Thus load test on the single phase induction motor has been conducted and its
performance characteristics determined.
TABULAR COLUMN
                                                                                   m.f =
Sl.No.      VL        IL     Speed(N)      S1     S2      S1 ̃~ S2   Torque Wattmeter Reading       Output Efficiency
            V         A         RPM        Kg     Kg        Kg        N-m                           Power        η    PF= cosΦ
                                                                            Observed Actual            W       %

1
2

3
4
5
6
7
8

     MODEL CALCULATION:

     Input power = W x m.f =       Watts                % slip = (Ns – N)/Ns x 100    pf= cosΦ = W/VLIL
     Output power = 2лNT/ 60 Watts

     Torque T= (S1~S2)*9.81*R N-m, where R is the radius of the brake drum in metre

                       Output power
     Efficiency η =                      x 100
                           Input power
EXP.NO. 12                                                                   DATE:

    EQUIVALENT CIURCUIT AND PRE-DETERMINATION OF PERFORMANCE
             CHARACTERISTICS OF 1Ф INDUCTION MOTOR

AIM:
        To draw the performance characteristics of a single phase induction motor by conducting
the no-load and blocked rotor test.

APPARATUS REQUIRED:

S.No              Name of            Range              Type               Qty.
                  Apparatus
1                 Voltmeter          (0-300)V           MI                 1
                                     (0-150)V           MI                 1
2                 Ammeter            (0-10)A            MI                 1
                                     (0-2)A             MI                 1
3                 Wattmeter          (330V,10A)         UPF                1
                                     (300V,5A)          LPF                1
4                 Connecting                                               As reqd.
                  wires


FUSE RATING:

125% of 7.6A=10A

THEORY:

A 1-Ф induction motor consists of stator,rotor and other associated parts.In the rotor of a single
phase winding is provided.The windings of a 1- Ф winding(provided) are displaced in space by
120º.A single phase current is fed to the windings so that a resultant rotating magnetic flux is
generated.The rotor starts rotating due to the induction effect produced due to the relative
velocity between the rotor winding and the rotating flux.

PRECAUTIONS:

NO LOAD TEST:

    •   Initially TPST Switch is kept open.
    •   Autotransformer is kept at minimum potential position.
    •   The machines must be started on no load.
BLOCKED ROTOR TEST:

   •    Initially the TPST Switch is kept open.
   •    Autotransformer is kept at minimum potential position.
   •    The machine must be started at full load(blocked rotor).

PROCEDURE:

NO LOAD TEST:

    1. Connections are given as per the circuit diagram.
    2. Precautions are observed and the motor is started at no load.
    3. Autotransformer is varied to have a rated voltage applied.

BLOCKED ROTOR TEST:

   1.   Connections are given as per the circuit diagram.
   2.   Precautions are observed and motor is started on full load or blocked rotor position.
   3.   Autotransformer is varied to have rated current flowing in motor.
   4.   Meter readings are the noted.


   Reff = 1.5*Rdc

   FORMULAE-

   NO LOAD TEST-

        •   cos Ф = Wo/VoIo
        •   Iw = Io cosФ
        •   Im = Io sin Ф
        •   Ro = Vo/Iw
        •   Xo = Vo/Im


BLOCKED ROTOR TEST-

Zsc = Vsc/Isc Ω
Rsc = Wsc/Isc2 Ω
Xsc = √(Zsc2 – Rsc2) Ω


RESULT-

Thus the no load and blocked rotor test on the single phase induction motor has been conducted
and the equivalent circuit has been drawn.
TABULATION

                     NO LOAD TEST-


S.No.   Vo(volts)     Io(amps)          Wo(watts)
                                  m.f   Observed Acual




               BLOCKED ROTOR TEST-


S.No.   Vsc(volts)    Isc(amps)         Wsc(watts)
                                  m.f   Observed Actual

More Related Content

What's hot

Electronic circuit design lab manual
Electronic circuit design lab manualElectronic circuit design lab manual
Electronic circuit design lab manualawais ahmad
 
ppt of Three phase fault analysis with auto reset for temporary fault and tri...
ppt of Three phase fault analysis with auto reset for temporary fault and tri...ppt of Three phase fault analysis with auto reset for temporary fault and tri...
ppt of Three phase fault analysis with auto reset for temporary fault and tri...Vikram Rawani
 
Current Source Inverter and Voltage Source Inverter
Current Source Inverter and Voltage Source Inverter Current Source Inverter and Voltage Source Inverter
Current Source Inverter and Voltage Source Inverter Sadanand Purohit
 
Function relay types
Function relay typesFunction relay types
Function relay typesjawaharramaya
 
Unit 05 Protection of feeders and bus-bars
Unit  05 Protection of feeders and bus-bars Unit  05 Protection of feeders and bus-bars
Unit 05 Protection of feeders and bus-bars PremanandDesai
 
Electrical transmission line
Electrical transmission lineElectrical transmission line
Electrical transmission lineDhananjay Jha
 
GENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEGENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEJamil Abdullah
 
1-ф to 1-ф Cycloconverter ppt
1-ф to 1-ф Cycloconverter ppt1-ф to 1-ф Cycloconverter ppt
1-ф to 1-ф Cycloconverter pptUtsav Yagnik
 
132 33kv substation documentation
132 33kv substation documentation132 33kv substation documentation
132 33kv substation documentationRajashekar Gurrala
 
04 universal motor
04 universal motor04 universal motor
04 universal motorRamesh Meti
 
Design of dc armature winding
Design of dc armature windingDesign of dc armature winding
Design of dc armature windingAbhishek Choksi
 
3 phase Transmission Line fault detector edit 1-3.pptx
3 phase Transmission Line fault detector edit 1-3.pptx3 phase Transmission Line fault detector edit 1-3.pptx
3 phase Transmission Line fault detector edit 1-3.pptxKrishna2017
 
Methods of Voltage Control
Methods of Voltage ControlMethods of Voltage Control
Methods of Voltage ControlYashvi Mehta
 
Firing angle control
Firing angle controlFiring angle control
Firing angle controljawaharramaya
 
Operating Principle of DC Generator
Operating Principle of DC GeneratorOperating Principle of DC Generator
Operating Principle of DC GeneratorBiswas Babu Pokharel
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYRaviraj solanki
 
digita storage oscilloscope (dso)
digita storage oscilloscope (dso)digita storage oscilloscope (dso)
digita storage oscilloscope (dso)Parind Patel
 

What's hot (20)

Electronic circuit design lab manual
Electronic circuit design lab manualElectronic circuit design lab manual
Electronic circuit design lab manual
 
ppt of Three phase fault analysis with auto reset for temporary fault and tri...
ppt of Three phase fault analysis with auto reset for temporary fault and tri...ppt of Three phase fault analysis with auto reset for temporary fault and tri...
ppt of Three phase fault analysis with auto reset for temporary fault and tri...
 
Current Source Inverter and Voltage Source Inverter
Current Source Inverter and Voltage Source Inverter Current Source Inverter and Voltage Source Inverter
Current Source Inverter and Voltage Source Inverter
 
Function relay types
Function relay typesFunction relay types
Function relay types
 
Unit 05 Protection of feeders and bus-bars
Unit  05 Protection of feeders and bus-bars Unit  05 Protection of feeders and bus-bars
Unit 05 Protection of feeders and bus-bars
 
Electrical transmission line
Electrical transmission lineElectrical transmission line
Electrical transmission line
 
GENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEGENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGE
 
1-ф to 1-ф Cycloconverter ppt
1-ф to 1-ф Cycloconverter ppt1-ф to 1-ф Cycloconverter ppt
1-ф to 1-ф Cycloconverter ppt
 
132 33kv substation documentation
132 33kv substation documentation132 33kv substation documentation
132 33kv substation documentation
 
Per unit analysis
Per unit analysisPer unit analysis
Per unit analysis
 
04 universal motor
04 universal motor04 universal motor
04 universal motor
 
Classes of motor duty
Classes of motor dutyClasses of motor duty
Classes of motor duty
 
Design of dc armature winding
Design of dc armature windingDesign of dc armature winding
Design of dc armature winding
 
3 phase Transmission Line fault detector edit 1-3.pptx
3 phase Transmission Line fault detector edit 1-3.pptx3 phase Transmission Line fault detector edit 1-3.pptx
3 phase Transmission Line fault detector edit 1-3.pptx
 
Methods of Voltage Control
Methods of Voltage ControlMethods of Voltage Control
Methods of Voltage Control
 
Firing angle control
Firing angle controlFiring angle control
Firing angle control
 
Operating Principle of DC Generator
Operating Principle of DC GeneratorOperating Principle of DC Generator
Operating Principle of DC Generator
 
Single line diagram
Single line diagramSingle line diagram
Single line diagram
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAY
 
digita storage oscilloscope (dso)
digita storage oscilloscope (dso)digita storage oscilloscope (dso)
digita storage oscilloscope (dso)
 

Viewers also liked

Electrical machines 2 lab manual
Electrical machines 2 lab manualElectrical machines 2 lab manual
Electrical machines 2 lab manualNaga Sai Chaitanya
 
Basic electrical lab manual
Basic electrical lab manualBasic electrical lab manual
Basic electrical lab manualDevashish Meena
 
Electrical machine lab
Electrical machine labElectrical machine lab
Electrical machine labDHEERAJ DHAKAR
 
2 electrical machines lab
2 electrical machines lab2 electrical machines lab
2 electrical machines labzeta eksa
 
Engineering practice lab manual for electronics
Engineering practice lab manual for electronicsEngineering practice lab manual for electronics
Engineering practice lab manual for electronicsPadhu Ar
 
Single phasing of three phase induction motor
Single phasing of three phase induction motorSingle phasing of three phase induction motor
Single phasing of three phase induction motorJUNAID SK
 
No-load & blocked rotor test, Equivalent circuit, Phasor diagram
No-load & blocked rotor test, Equivalent circuit, Phasor diagramNo-load & blocked rotor test, Equivalent circuit, Phasor diagram
No-load & blocked rotor test, Equivalent circuit, Phasor diagramAbhishek Choksi
 
Power System Modelling And Simulation Lab
Power System Modelling And Simulation LabPower System Modelling And Simulation Lab
Power System Modelling And Simulation LabSachin Airan
 
Introduction to Electrical Engineering Laboratory
Introduction to Electrical Engineering LaboratoryIntroduction to Electrical Engineering Laboratory
Introduction to Electrical Engineering LaboratoryIsuru Premaratne
 
Mech viva questions and_answers
Mech viva questions and_answersMech viva questions and_answers
Mech viva questions and_answershitusp
 
269010454 electrical-machines-lab-manual-for-petrochemaical
269010454 electrical-machines-lab-manual-for-petrochemaical269010454 electrical-machines-lab-manual-for-petrochemaical
269010454 electrical-machines-lab-manual-for-petrochemaicalsampathkumar Mtech Chemical Engg
 
Chapter 5 mukesh gurjar
Chapter 5 mukesh gurjarChapter 5 mukesh gurjar
Chapter 5 mukesh gurjarMukesh gurjar
 
Modeling and Testing of Induction Motors
Modeling and Testing of Induction MotorsModeling and Testing of Induction Motors
Modeling and Testing of Induction MotorsBirju Besra
 
POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )
POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )
POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )Mathankumar S
 
NUMERICAL METHODS WITH MATLAB : bisection,mueller's,newton-raphson,false poin...
NUMERICAL METHODS WITH MATLAB : bisection,mueller's,newton-raphson,false poin...NUMERICAL METHODS WITH MATLAB : bisection,mueller's,newton-raphson,false poin...
NUMERICAL METHODS WITH MATLAB : bisection,mueller's,newton-raphson,false poin...Parhamsagharchi
 

Viewers also liked (20)

Electrical machines 2 lab manual
Electrical machines 2 lab manualElectrical machines 2 lab manual
Electrical machines 2 lab manual
 
Basic electrical lab manual
Basic electrical lab manualBasic electrical lab manual
Basic electrical lab manual
 
Electrical machine lab
Electrical machine labElectrical machine lab
Electrical machine lab
 
Machine lab manual
Machine lab manualMachine lab manual
Machine lab manual
 
2 electrical machines lab
2 electrical machines lab2 electrical machines lab
2 electrical machines lab
 
Engineering practice lab manual for electronics
Engineering practice lab manual for electronicsEngineering practice lab manual for electronics
Engineering practice lab manual for electronics
 
Single phasing of three phase induction motor
Single phasing of three phase induction motorSingle phasing of three phase induction motor
Single phasing of three phase induction motor
 
No-load & blocked rotor test, Equivalent circuit, Phasor diagram
No-load & blocked rotor test, Equivalent circuit, Phasor diagramNo-load & blocked rotor test, Equivalent circuit, Phasor diagram
No-load & blocked rotor test, Equivalent circuit, Phasor diagram
 
Power System Modelling And Simulation Lab
Power System Modelling And Simulation LabPower System Modelling And Simulation Lab
Power System Modelling And Simulation Lab
 
Power Electronics lab manual BE EEE
Power Electronics lab manual BE EEEPower Electronics lab manual BE EEE
Power Electronics lab manual BE EEE
 
Manuval
ManuvalManuval
Manuval
 
BHEL HARIDWAR
BHEL HARIDWARBHEL HARIDWAR
BHEL HARIDWAR
 
Introduction to Electrical Engineering Laboratory
Introduction to Electrical Engineering LaboratoryIntroduction to Electrical Engineering Laboratory
Introduction to Electrical Engineering Laboratory
 
Mech viva questions and_answers
Mech viva questions and_answersMech viva questions and_answers
Mech viva questions and_answers
 
269010454 electrical-machines-lab-manual-for-petrochemaical
269010454 electrical-machines-lab-manual-for-petrochemaical269010454 electrical-machines-lab-manual-for-petrochemaical
269010454 electrical-machines-lab-manual-for-petrochemaical
 
Transformers
TransformersTransformers
Transformers
 
Chapter 5 mukesh gurjar
Chapter 5 mukesh gurjarChapter 5 mukesh gurjar
Chapter 5 mukesh gurjar
 
Modeling and Testing of Induction Motors
Modeling and Testing of Induction MotorsModeling and Testing of Induction Motors
Modeling and Testing of Induction Motors
 
POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )
POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )
POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )
 
NUMERICAL METHODS WITH MATLAB : bisection,mueller's,newton-raphson,false poin...
NUMERICAL METHODS WITH MATLAB : bisection,mueller's,newton-raphson,false poin...NUMERICAL METHODS WITH MATLAB : bisection,mueller's,newton-raphson,false poin...
NUMERICAL METHODS WITH MATLAB : bisection,mueller's,newton-raphson,false poin...
 

Similar to Em ii lab manual 28.10.08 latest

Basic Electronics Repair (Training Course).pdf
Basic Electronics Repair (Training Course).pdfBasic Electronics Repair (Training Course).pdf
Basic Electronics Repair (Training Course).pdfivan ion
 
Lab manual for_electronic_circuits_final_march_13_2011
Lab manual for_electronic_circuits_final_march_13_2011Lab manual for_electronic_circuits_final_march_13_2011
Lab manual for_electronic_circuits_final_march_13_2011Sachin Pal
 
Hướng dẫn sử dụng Testo 770
Hướng dẫn sử dụng Testo 770Hướng dẫn sử dụng Testo 770
Hướng dẫn sử dụng Testo 770Tenmars Việt Nam
 
G4L3 - ELECTRICAL TESTERS.pptx
G4L3 - ELECTRICAL TESTERS.pptxG4L3 - ELECTRICAL TESTERS.pptx
G4L3 - ELECTRICAL TESTERS.pptxSamuelRomerOlalia
 
Hướng dẫn sử dụng máy đo điện trở cách điện Tenmars TM-507
Hướng dẫn sử dụng máy đo điện trở cách điện Tenmars TM-507Hướng dẫn sử dụng máy đo điện trở cách điện Tenmars TM-507
Hướng dẫn sử dụng máy đo điện trở cách điện Tenmars TM-507Tenmars Việt Nam
 
Hướng dẫn sử dụng Testo 770-1
Hướng dẫn sử dụng Testo 770-1Hướng dẫn sử dụng Testo 770-1
Hướng dẫn sử dụng Testo 770-1Tenmars Việt Nam
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear johny renoald
 
Hướng dẫn sử dụng Testo 760
Hướng dẫn sử dụng Testo 760Hướng dẫn sử dụng Testo 760
Hướng dẫn sử dụng Testo 760Tenmars Việt Nam
 
Hướng dẫn sử dụng đồng hồ vạn năng Testo 760
Hướng dẫn sử dụng đồng hồ vạn năng Testo 760Hướng dẫn sử dụng đồng hồ vạn năng Testo 760
Hướng dẫn sử dụng đồng hồ vạn năng Testo 760Tenmars Việt Nam
 
Hướng dẫn sử dụng Testo 760-1
Hướng dẫn sử dụng Testo 760-1Hướng dẫn sử dụng Testo 760-1
Hướng dẫn sử dụng Testo 760-1Tenmars Việt Nam
 

Similar to Em ii lab manual 28.10.08 latest (20)

Gopi's mcs lab man
Gopi's mcs lab manGopi's mcs lab man
Gopi's mcs lab man
 
Sm lab manual
Sm lab manualSm lab manual
Sm lab manual
 
Basic Electronics Repair (Training Course).pdf
Basic Electronics Repair (Training Course).pdfBasic Electronics Repair (Training Course).pdf
Basic Electronics Repair (Training Course).pdf
 
DaY 1.docx
DaY 1.docxDaY 1.docx
DaY 1.docx
 
Lab manual for_electronic_circuits_final_march_13_2011
Lab manual for_electronic_circuits_final_march_13_2011Lab manual for_electronic_circuits_final_march_13_2011
Lab manual for_electronic_circuits_final_march_13_2011
 
Maurice Kariuki
Maurice KariukiMaurice Kariuki
Maurice Kariuki
 
class 18.08.2020.pptx
class 18.08.2020.pptxclass 18.08.2020.pptx
class 18.08.2020.pptx
 
DATA LOGGER
DATA LOGGER DATA LOGGER
DATA LOGGER
 
electronics lab.doc
electronics lab.docelectronics lab.doc
electronics lab.doc
 
Hướng dẫn sử dụng Testo 770
Hướng dẫn sử dụng Testo 770Hướng dẫn sử dụng Testo 770
Hướng dẫn sử dụng Testo 770
 
G4L3 - ELECTRICAL TESTERS.pptx
G4L3 - ELECTRICAL TESTERS.pptxG4L3 - ELECTRICAL TESTERS.pptx
G4L3 - ELECTRICAL TESTERS.pptx
 
Hướng dẫn sử dụng máy đo điện trở cách điện Tenmars TM-507
Hướng dẫn sử dụng máy đo điện trở cách điện Tenmars TM-507Hướng dẫn sử dụng máy đo điện trở cách điện Tenmars TM-507
Hướng dẫn sử dụng máy đo điện trở cách điện Tenmars TM-507
 
Hướng dẫn sử dụng Testo 770-1
Hướng dẫn sử dụng Testo 770-1Hướng dẫn sử dụng Testo 770-1
Hướng dẫn sử dụng Testo 770-1
 
Huong dan su dung Teso 770-1
Huong dan su dung Teso 770-1Huong dan su dung Teso 770-1
Huong dan su dung Teso 770-1
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
Hướng dẫn sử dụng Testo 760
Hướng dẫn sử dụng Testo 760Hướng dẫn sử dụng Testo 760
Hướng dẫn sử dụng Testo 760
 
Hướng dẫn sử dụng đồng hồ vạn năng Testo 760
Hướng dẫn sử dụng đồng hồ vạn năng Testo 760Hướng dẫn sử dụng đồng hồ vạn năng Testo 760
Hướng dẫn sử dụng đồng hồ vạn năng Testo 760
 
Pneumatic Lab 3 JJ512
Pneumatic Lab 3 JJ512Pneumatic Lab 3 JJ512
Pneumatic Lab 3 JJ512
 
Hướng dẫn sử dụng Testo 760-1
Hướng dẫn sử dụng Testo 760-1Hướng dẫn sử dụng Testo 760-1
Hướng dẫn sử dụng Testo 760-1
 
Pe lab
Pe labPe lab
Pe lab
 

Recently uploaded

EMBODO Lesson Plan Grade 9 Law of Sines.docx
EMBODO Lesson Plan Grade 9 Law of Sines.docxEMBODO Lesson Plan Grade 9 Law of Sines.docx
EMBODO Lesson Plan Grade 9 Law of Sines.docxElton John Embodo
 
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...Postal Advocate Inc.
 
Presentation Activity 2. Unit 3 transv.pptx
Presentation Activity 2. Unit 3 transv.pptxPresentation Activity 2. Unit 3 transv.pptx
Presentation Activity 2. Unit 3 transv.pptxRosabel UA
 
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17Celine George
 
Grade 9 Quarter 4 Dll Grade 9 Quarter 4 DLL.pdf
Grade 9 Quarter 4 Dll Grade 9 Quarter 4 DLL.pdfGrade 9 Quarter 4 Dll Grade 9 Quarter 4 DLL.pdf
Grade 9 Quarter 4 Dll Grade 9 Quarter 4 DLL.pdfJemuel Francisco
 
Oppenheimer Film Discussion for Philosophy and Film
Oppenheimer Film Discussion for Philosophy and FilmOppenheimer Film Discussion for Philosophy and Film
Oppenheimer Film Discussion for Philosophy and FilmStan Meyer
 
TEACHER REFLECTION FORM (NEW SET........).docx
TEACHER REFLECTION FORM (NEW SET........).docxTEACHER REFLECTION FORM (NEW SET........).docx
TEACHER REFLECTION FORM (NEW SET........).docxruthvilladarez
 
4.16.24 Poverty and Precarity--Desmond.pptx
4.16.24 Poverty and Precarity--Desmond.pptx4.16.24 Poverty and Precarity--Desmond.pptx
4.16.24 Poverty and Precarity--Desmond.pptxmary850239
 
How to Add Barcode on PDF Report in Odoo 17
How to Add Barcode on PDF Report in Odoo 17How to Add Barcode on PDF Report in Odoo 17
How to Add Barcode on PDF Report in Odoo 17Celine George
 
Textual Evidence in Reading and Writing of SHS
Textual Evidence in Reading and Writing of SHSTextual Evidence in Reading and Writing of SHS
Textual Evidence in Reading and Writing of SHSMae Pangan
 
The Contemporary World: The Globalization of World Politics
The Contemporary World: The Globalization of World PoliticsThe Contemporary World: The Globalization of World Politics
The Contemporary World: The Globalization of World PoliticsRommel Regala
 
Virtual-Orientation-on-the-Administration-of-NATG12-NATG6-and-ELLNA.pdf
Virtual-Orientation-on-the-Administration-of-NATG12-NATG6-and-ELLNA.pdfVirtual-Orientation-on-the-Administration-of-NATG12-NATG6-and-ELLNA.pdf
Virtual-Orientation-on-the-Administration-of-NATG12-NATG6-and-ELLNA.pdfErwinPantujan2
 
4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptxmary850239
 
ROLES IN A STAGE PRODUCTION in arts.pptx
ROLES IN A STAGE PRODUCTION in arts.pptxROLES IN A STAGE PRODUCTION in arts.pptx
ROLES IN A STAGE PRODUCTION in arts.pptxVanesaIglesias10
 
Activity 2-unit 2-update 2024. English translation
Activity 2-unit 2-update 2024. English translationActivity 2-unit 2-update 2024. English translation
Activity 2-unit 2-update 2024. English translationRosabel UA
 
Integumentary System SMP B. Pharm Sem I.ppt
Integumentary System SMP B. Pharm Sem I.pptIntegumentary System SMP B. Pharm Sem I.ppt
Integumentary System SMP B. Pharm Sem I.pptshraddhaparab530
 
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptxMULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptxAnupkumar Sharma
 

Recently uploaded (20)

EMBODO Lesson Plan Grade 9 Law of Sines.docx
EMBODO Lesson Plan Grade 9 Law of Sines.docxEMBODO Lesson Plan Grade 9 Law of Sines.docx
EMBODO Lesson Plan Grade 9 Law of Sines.docx
 
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
 
Presentation Activity 2. Unit 3 transv.pptx
Presentation Activity 2. Unit 3 transv.pptxPresentation Activity 2. Unit 3 transv.pptx
Presentation Activity 2. Unit 3 transv.pptx
 
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
 
Grade 9 Quarter 4 Dll Grade 9 Quarter 4 DLL.pdf
Grade 9 Quarter 4 Dll Grade 9 Quarter 4 DLL.pdfGrade 9 Quarter 4 Dll Grade 9 Quarter 4 DLL.pdf
Grade 9 Quarter 4 Dll Grade 9 Quarter 4 DLL.pdf
 
Oppenheimer Film Discussion for Philosophy and Film
Oppenheimer Film Discussion for Philosophy and FilmOppenheimer Film Discussion for Philosophy and Film
Oppenheimer Film Discussion for Philosophy and Film
 
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptxLEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
 
TEACHER REFLECTION FORM (NEW SET........).docx
TEACHER REFLECTION FORM (NEW SET........).docxTEACHER REFLECTION FORM (NEW SET........).docx
TEACHER REFLECTION FORM (NEW SET........).docx
 
4.16.24 Poverty and Precarity--Desmond.pptx
4.16.24 Poverty and Precarity--Desmond.pptx4.16.24 Poverty and Precarity--Desmond.pptx
4.16.24 Poverty and Precarity--Desmond.pptx
 
How to Add Barcode on PDF Report in Odoo 17
How to Add Barcode on PDF Report in Odoo 17How to Add Barcode on PDF Report in Odoo 17
How to Add Barcode on PDF Report in Odoo 17
 
Textual Evidence in Reading and Writing of SHS
Textual Evidence in Reading and Writing of SHSTextual Evidence in Reading and Writing of SHS
Textual Evidence in Reading and Writing of SHS
 
The Contemporary World: The Globalization of World Politics
The Contemporary World: The Globalization of World PoliticsThe Contemporary World: The Globalization of World Politics
The Contemporary World: The Globalization of World Politics
 
Virtual-Orientation-on-the-Administration-of-NATG12-NATG6-and-ELLNA.pdf
Virtual-Orientation-on-the-Administration-of-NATG12-NATG6-and-ELLNA.pdfVirtual-Orientation-on-the-Administration-of-NATG12-NATG6-and-ELLNA.pdf
Virtual-Orientation-on-the-Administration-of-NATG12-NATG6-and-ELLNA.pdf
 
4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx
 
ROLES IN A STAGE PRODUCTION in arts.pptx
ROLES IN A STAGE PRODUCTION in arts.pptxROLES IN A STAGE PRODUCTION in arts.pptx
ROLES IN A STAGE PRODUCTION in arts.pptx
 
Activity 2-unit 2-update 2024. English translation
Activity 2-unit 2-update 2024. English translationActivity 2-unit 2-update 2024. English translation
Activity 2-unit 2-update 2024. English translation
 
Integumentary System SMP B. Pharm Sem I.ppt
Integumentary System SMP B. Pharm Sem I.pptIntegumentary System SMP B. Pharm Sem I.ppt
Integumentary System SMP B. Pharm Sem I.ppt
 
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptxMULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
 
FINALS_OF_LEFT_ON_C'N_EL_DORADO_2024.pptx
FINALS_OF_LEFT_ON_C'N_EL_DORADO_2024.pptxFINALS_OF_LEFT_ON_C'N_EL_DORADO_2024.pptx
FINALS_OF_LEFT_ON_C'N_EL_DORADO_2024.pptx
 
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptxYOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
 

Em ii lab manual 28.10.08 latest

  • 1. ELECTRICAL MACHINES-II LAB MANUAL DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING AARUPADAI VEEDU INSTITUTE OF TECHNOLOGY, Old Mahabalipuram Road, Paiyanoor-603104, Kanchipuram (dt), Tamilnadu VINAYAKA MISSIONS UNIVERSITY SALEM, TAMILNADU
  • 2. Name of the Laboratory : ELECTRICAL MACHINES-II • Year/Semester : II/IV • Branch : EEE HOD/EEE Principal
  • 3. PREFACE This Laboratory book in Electrical Machines – II has been revised in order to be up to date with Curriculum changes, laboratory equipment upgrading and the latest circuit simulation. Every effort has been made to correct all the known errors, but nobody is perfect, if you find any additional errors or anything else you think is an error, Please contact the HOD/EEE at eeeavit@gmail.com The Authors thanked all the staff members from the department for their valuable Suggestion and contribution The Authors Department of EEE
  • 4. TABLE OF CONTENTS Safety Rules and operating Procedures I Laboratory Safety information II Guidelines for Laboratory Notebook III Troubleshooting Hints IV Sl.No Experiment Name Page No 1. Regulation of 3-phase alternator by EMF and MMF 1 methods. 2. Regulation of 3-phase alternator by ZPF and ASA methods. 3. Slip test on 3-phase alternator. 4. Load characteristics of 3-phase alternator by bus bar loading. 5. V and inverted V curve of synchronous motors. 6. Load test on 3-phase induction motor. 7. No load and blocked rotor test on 3-phase induction motor. 8. Study of Synchronous induction motor. 9. Study of induction motor starters. 10 Separation of losses in three-phase induction motor. . 11 Load test on 1-phase induction motor. . 12 Equivalent circuit and pre–determination of performance characteristics of single-phase induction motor. . Appendix
  • 5. LABORATORY PRACTICE SAFETY RULES 1. SAFETY is of paramount importance in the Electrical Engineering Laboratories. 2.Electricity NEVER EXECUSES careless persons. So, exercise enough care and attention in handling electrical equipment and follow safety practices in the laboratory. (Electricity is a good servant but a bad master). 3.Avoid direct contact with any voltage source and power line voltages. (Otherwise, any such contact may subject you to electrical shock) 4.Wear rubber-soled shoes. (To insulate you from earth so that even if you accidentally contact a live point, current will not flow through your body to earth and hence you will be protected from electrical shock) 5.Wear laboratory-coat and avoid loose clothing. (Loose clothing may get caught on an equipment/instrument and this may lead to an accident particularly if the equipment happens to be a rotating machine) 6.Girl students should have their hair tucked under their coat or have it in a knot. 7.Do not wear any metallic rings, bangles, bracelets, wristwatches and neck chains. (When you move your hand/body, such conducting items may create a short circuit or may touch a live point and thereby subject you to electrical shock) 8.Be certain that your hands are dry and that you are not standing on wet floor. (Wet parts of the body reduce the contact resistance thereby increasing the severity of the shock) 9.Ensure that the power is OFF before you start connecting up the circuit.(Otherwise you will be touching the live parts in the circuit) 10.Get your circuit diagram approved by the staff member and connect up the circuit strictly as per the approved circuit diagram. 11.Check power chords for any sign of damage and be certain that the chords use safety plugs and do not defeat the safety feature of these plugs by using ungrounded plugs. 12.When using connection leads, check for any insulation damage in the leads and avoid such defective leads. 13.Do not defeat any safety devices such as fuse or circuit breaker by shorting across it. Safety devices protect YOU and your equipment.
  • 6. 14.Switch on the power to your circuit and equipment only after getting them checked up and approved by the staff member. 15.Take the measurement with one hand in your pocket. (To avoid shock in case you accidentally touch two points at different potentials with your two hands) 16.Do not make any change in the connection without the approval of the staff member. 17.In case you notice any abnormal condition in your circuit ( like insulation heating up, resistor heating up etc ), switch off the power to your circuit immediately and inform the staff member. 18.Keep hot soldering iron in the holder when not in use. 19.After completing the experiment show your readings to the staff member and switch off the power to your circuit after getting approval from the staff member. 20.While performing load-tests in the Electrical Machines Laboratory using the brake-drums: i. Avoid the brake-drum from getting too hot by putting just enough water into the brake- drum at intervals; use the plastic bottle with a nozzle (available in the laboratory ) to pour the water.(When the drum gets too hot, it will burn out the braking belts) ii. Do not stand in front of the brake-drum when the supply to the load-test circuit is switched off. (Otherwise, the hot water in the brake-drum will splash out on you) iii. After completing the load-test, suck out the water in the brake-drum using the plastic bottle with nozzle and then dry off the drum with a spongewhich is available in the laboratory. (The water, if allowed to remain in the brake-drum, will corrode it) 21.Determine the correct rating of the fuse/s to be connected in the circuit after understanding correctly the type of the experiment to be performed: no-load test or full-load test, the maximum current expected in the circuit and accordingly use that fuse-rating.(While an over-rated fuse will damage the equipment and other instruments like ammeters and watt-meters in case of over load, an under-rated fuse may not allow one even to start the experiment) 22. At the time of starting a motor, the ammeter connected in the armature circuit overshoots, as the starting current is around 5 times the full load rating of the motor. Moving coil ammeters being very delicate, may get damaged due to high starting current. A switch has been provided on such meters to disconnect the moving coil of the meter during starting. This switch should be closed after the motor attains full speed. Moving iron ammeters and current coils of wattmeters are not so delicate and hence these can stand short time overload due to high starting current. No such switch is therefore provided on these meters. Moving iron meters are cheaper and more rugged compared to moving coil meters. Moving iron meters can be used for both a.c. and d.c. measurement. Moving coil instruments are however more sensitive and more accurate as compared to their moving iron counterparts and these can be used for d.c. measurements only. Good features of moving coil instruments are not of much consequence for you as other sources of errors in the experiments are many times more than those caused by these meters. 23. Some students have been found to damage meters by mishandling in the following ways:
  • 7. i. Keeping unnecessary material like books, lab records, unused meters etc. causing meters to fall down the table. ii. Putting pressure on the meter (specially glass) while making connections or while talking or listening somebody. STUDENTS ARE STRICTLY WARNED THAT FULL COST OF THE METER WILL BE RECOVERED FROM THE INDIVIDUAL WHO HAS DAMAGED IT IN SUCH A MANNER. Copy these rules in your Lab Record. Observe these yourself and help your friends to observe.. I have read and understand these rules and procedures. I agree to abide by these rules and procedures at all times while using these facilities. I understand that failure to follow these rules and procedures will result in my immediate dismissal from the laboratory and additional disciplinary action may be taken. Signature Date Lab
  • 8. GUIDELINES FOR LABORATORY NOTEBOOK The laboratory notebook is a record of all work pertaining to the experiment. This record should be sufficiently complete so that you or anyone else of similar technical background can duplicate the experiment and data by simply following your laboratory notebook. Record everything directly into the notebook during the experiment. Do not use scratch paper for recording data. Do not trust your memory to fill in the details at a later time. Organization in your notebook is important. Descriptive headings should be used to separate and identify the various parts of the experiment. Record data in chronological order. A neat, organized and complete record of an experiment is just as important as the experimental work. 1. Heading: The experiment identification (number) should be at the top of each page.Your name and date should be at the top of the first page of each day's experimental work. 2.Object: A brief but complete statement of what you intend to find out or verify in the experiment should be at the beginning of each experiment 3.Diagram: A circuit diagram should be drawn and labeled so that the actual experiment circuitry could be easily duplicated at any time in the future. Be especially careful to record all circuit changes made during the experiment. 4.Equipment List: List those items of equipment which have a direct effect on the accuracy of the data. It may be necessary later to locate specific items of equipment for rechecks if discrepancies develop in the results. 5.Procedure: In general, lengthy explanations of procedures are unnecessary. Be brief. Short commentaries along side the corresponding data may be used. Keep in mind the fact that the experiment must be reproducible from the information given in your notebook. 6.Data: Think carefully about what data is required and prepare suitable data tables. Record instrument readings directly. Do not use calculated results in place of direct data; however, calculated results may be recorded in the same table with the direct data. Data tables should be clearly identified and each data column labeled and headed by the proper units of measure. 7.Calculations: Not always necessary but equations and sample calculations are often given to illustrate the treatment of the experimental data in obtaining the
  • 9. results. 8.Graphs: Graphs are used to present large amounts of data in a concise visual form. Data to be presented in graphical form should be plotted in the laboratory so that any questionable data points can be checked while the experiment is still set up. The grid lines in the notebook can be used for most graphs. If special graph paper is required, affix the graph permanently into the notebook. Give all graphs a short descriptive title. Label and scale the axes. Use units of measure. Label each curve if more than one on a graph. 9.Results: The results should be presented in a form which makes the interpretation easy. Large amounts of numerical results are generally presented in graphical form. Tables are generally used for small amounts of results. Theoretical and experimental results should be on the same graph or arrange in the same table in a way for easy correlation of these results. 10.Conclusion: This is your interpretation of the results of the experiment as an engineer. Be brief and specific. Give reasons for important discrepancies.
  • 10. TROUBLE SHOOTING HINTS 1. Be Sure that the power is turned ON 2. Be sure the ground connections are common 3. Be sure the circuit you build is identical to your circuit diagram (Do a node by node check) 4. Be sure that the supply voltages are correct 5. Be sure that the equipment is set up correctly and you are measuring the correct parameters 6. If steps I through 5 are correct then you probably have used a component with the wrong value or one that doesn’t work. It is also possible that the equipment does not work (although this is not probable0 or the protoboard you are using may have some unwanted paths between nodes. To find your problem you must trace through the voltages in your circuit node by node and compare the signal you expect to have. Then if they are different use your engineering judgment to decide what is causing the different or ask your lab assistant
  • 11.
  • 12. EXP.NO. 1 DATE: REGULATION OF 3–PHASE ALTERNATOR BY EMF AND MMF METHODS AIM: To predetermine the regulation of 3-phase alternator by EMF and MMF methods and also draw the vector diagrams. APPARATURS REQUIRED: SL.NO Name of the Apparatus Type Range Quantity 1 Ammeter MC 0 – 1/2 A 1 2 Ammeter MI 0 – 5/10 A 1 3 Voltmeter MC 0 – 10 V 1 4 Voltmeter MI 0 – 600 V 1 5 Rheostat Wire wound 250 Ω, 1.5 A 1 6 Rheostat Wire wound 1200Ω, 0.8 A 1 7 Tachometer Digital --- 1 8 TPST knife switch -- -- 1 THEORY: The regulation of a 3-phase alternator may be predetermined by conducting the Open Circuit (OC) and the Sort Circuit (SC) tests. The methods employed for determination of regulation are EMF or synchronous impedance method, MMF or Ampere Turns method and the ZPF or Potier triangle method. In this experiment, the EMF and MMF methods are used. The OC and SC graphs are plotted from the two tests. The synchronous impedance is found from the OC test. The regulation is then determined at different power factors by calculations using vector diagrams. The EMF method is also called pessimistic method as the value of regulation obtained is much more than the actual value. The MMF method is also called optimistic method as the value of regulation obtained is much less than the actual value. In the MMF method the armature leakage reactance is treated as an additional armature reaction. In both methods the OC and SC test data are utilized. PRECAUTIONS: (i) The motor field rheostat should be kept in the minimum resistance position. (ii) The alternator field potential divider should be kept in the minimum voltage position. (iii) Initially all switches are in open position. PROCEDURE: (FOR BOTH EMF AND MMF METHODS) 1. Note down the name plate details of the motor and alternator. 2. Connections are made as per the circuit diagram. 3. Switch ON the supply by closing the DPST switch.
  • 13. 4. Using the Three point starter, start the motor to run at the synchronous speed by adjusting the motor field rheostat. 5. Conduct Open Circuit test by varying the potential divider for various values of field current and tabulate the corresponding Open Circuit Voltage readings. 6. Conduct Short Circuit test by closing the TPST switch and adjust the potential divider to set the rated armature current and tabulate the corresponding field current. 7. The Stator resistance per phase is determined by connecting any one phase stator winding of the alternator as per the circuit diagram using MC voltmeter and ammeter of suitable ranges. PROCEDURE TO DRAW GRAPH FOR EMF METHOD: 1. Draw the Open Circuit Characteristic curve (Generated Voltage per phase VS Field current). 2. Draw the Short Circuit Characteristics curve (Short circuit current VS Field current) 3. From the graph find the open circuit voltage per phase (E1 (ph) for the rated short circuit current (Isc). 4. By using respective formulae find the Zs, Xs, Eo and percentage regulation. PROCEDURE TO DRAW GRAPH FOR MMF METHOD: 1. Draw the Open Circuit Characteristic curve (Generated Voltage per phase VS Field current). 2. Draw the Short Circuit Characteristics curve (Short circuit current VS Field current) 3. Draw the line OL to represent FORMULAE: 1. Armature Resistance Ra = Ω 2. Synchronous Impedance Zs = O.C. voltage S.C. current 3. Synchronous Reactance Xs = √ Zs2 – Ra2 4. Open circuit voltage for lagging p.f = √(VcosΦ + IaRa)2 + (VsinΦ + IaXs)2 5. Open circuit voltage for leading p.f. = √(VcosΦ + IaRa)2 + (VsinΦ – IaXs)2 6. Open circuit voltage for unity p.f = √(V + IaRa)2 + ( IaXs)2 7. Percentage regulation = Eo – V x 100 V RESULT: Thus the regulation of 3-phase alternator has been predetermined by the EMF and MMF methods.
  • 14. VIVA QUESTIONS: 1. What is meant by voltage regulation? 2. What is meant by Synchronous Impedance? 3. What is OC test ? 4. What is SC test? 5. What is meant by mmf or field ampere turns?
  • 15. REGULATION OF 3-PHASE ALTERNATOR BY EMF AND MMF METHODS TABULAR COLUMNS OPEN CIRCUIT TEST: Field Current (If) Open Circuit Line Open circuit Phase S.No. Voltage (VoL) Voltage (Voph) Amps Volts Volts SHORT CIRCUIT TEST: Short Circuit Current (120% S.No. Field Current (If) to 150% of rated current) (ISC) Amps Amps
  • 16. REGULATION OF 3-PHASE ALTERNATOR BY EMF AND MMF METHODS TABULAR COLUMNS EMF METHOD: Eph (V) % Regulation SL.NO. Power factor Lag Lead Lag Lead MMF METHOD: Ifr Eph (V) % Regulation SL.NO. P.F Vph If1 If2 (A) (V) (A) (A) Lag Lead Lag Lead Lag Lead
  • 17.
  • 18. EXP.NO. 2 DATE: REGULATION OF 3-PHASE ALTERNATOR BY POTIER AND ASA METHODS AIM: To predetermine the regulation of three phase alternator by Potier and ASA methods and also to draw the vector diagrams. APPARATURS REQUIRED: SL.NO Name of the Apparatus Type Range Quantity 1 Ammeter MC 0 – 1/2 A 1 2 Ammeter MI 0 – 5/10 A 1 3 Voltmeter MC 0 – 10 V 1 4 Voltmeter MI 0 – 600 V 1 5 Rheostat Wire wound 250 Ω, 1.5 A 1 6 Rheostat Wire wound 1200Ω, 0.8 A 1 7 Tachometer Digital --- 1 8 TPST knife switch -- -- 1 FORMULAE USED: Percentage regulation = Eo – Vrated x 100 (For both POTIER & ASA methods) Vrated PRECAUTION: (i) The motor field rheostat should be kept in the minimum resistance position. (ii) The Alternator field potential divider should be in the position of minimum potential. (iii) Initially all switches are in open position. PROCEDURE FOR BOTH POTIER AND ASA METHODS: 1. Note down the complete nameplate details of motor and alternator. 2. Connections are made as per the circuit diagram. 3. Switch on the supply by closing the DPST main switch. 4. Using the Three point starter, start the motor to run at the synchronous speed by varying the motor field rheostat. 5. Conduct an Open Circuit Test by varying the Potential Divider for various values of Field current and tabulate the corresponding Open circuit voltage readings. 6. Conduct a Short Circuit Test by closing the TPST knife switch and adjust the potential divider the set the rated Armature current, tabulate the corresponding Field current. 7. Conduct a ZPF test by adjusting the potential divider for full load current passing through either an inductive or capacitive load with zero power and tabulate the readings. 8. Conduct a Stator Resistance Test by giving connection as per the circuit diagram and tabulate the voltage and Current readings for various resistive loads.
  • 19. PROCEDURE TO DRAW THE POTIER TRIANGLE (ZPF METHOD): (All the quantities are in per phase value) 1. Draw the Open Circuit Characteristics (Generated Voltage per phase VS Field Current) 2. Mark the point A at X-axis, which is obtained from short circuit test with full load armature current. 3. From the ZPF test, mark the point B for the field current to the corresponding rated armature current and the rated voltage. 4. Draw the ZPF curve which passing through the point A and B in such a way parallel to the open circuit characteristics curve. 5. Draw the tangent for the OCC curve from the origin (i.e.) air gap line. 6. Draw the line BC from B towards Y-axis, which is parallel and equal to OA. 7. Draw the parallel line for the tangent from C to the OCC curve. 8. Join the points B and D also drop the perpendicular line DE to BC, where the line DE represents armature leakage reactance drop (IXL) BE represents armature reaction excitation (Ifa). PROCEDURE TO DRAW THE VECTOR DIAGRAM (ZPF METHOD) 1. Select the suitable voltage and current scale. 2. For the corresponding power angle ( Lag, Lead, Unity) draw the voltage vector and current vector OB. 3. Draw the vector AC with the magnitude of IRa drop, which should be parallel to the vector OB. 4. Draw the perpendicular CD to AC from the point C with the magnitude of IXL drop. 5. Join the points O and D, which will be equal to the air gap voltage (Eair). 6. Find out the field current (Ifc) for the corresponding air gap voltage (Eair) from the OCC curve. 7. Draw the vector OF with the magnitude of Ifc which should be perpendicular to the vector OD. 8. Draw the vector FG from F with the magnitude Ifa in such a way it is parallel to the current vector OB. 9. Join the points O and G, which will be equal to the field excitation current (If). 10. Draw the perpendicular line to the vector OG from the point O and extend CD in such a manner to intersect the perpendicular line at the point H. 11. Find out the open circuit voltage (Eo) for the corresponding field excitation current (If) from the OCC curve. 12. Find out the regulation from the suitable formula. PROCEDURE TO DRAW THE POTIER TRIANGLE (ASA METHOD): (All the quantities are in per phase value) 1. Draw the Open Circuit Characteristics (Generated Voltage per phase VS Field Current) 2. Mark the point A at X-axis, which is obtained from short circuit test with full load armature current. 3. From the ZPF test, mark the point B for the field current to the corresponding rated armature current and the rated voltage.
  • 20. 4. Draw the ZPF curve which passing through the point A and B in such a way parallel to the open circuit characteristics curve. 5. Draw the tangent for the OCC curve from the origin (i.e.) air gap line. 6. Draw the line BC from B towards Y-axis, which is parallel and equal to OA. 7. Draw the parallel line for the tangent from C to the OCC curve. 8. Join the points B and D also drop the perpendicular line DE to BC, where the line DE represents armature leakage reactance drop (IXL) BE represents armature reaction excitation (Ifa). 9. Extend the line BC towards the Y-axis up to the point O’. The same line intersects the air gap line at point G. 10. Mark the point I in Y-axis with the magnitude of Eair and draw the line from I towards OCC curve which should be parallel to X-axis. Let this line cut the air gap line at point H and the OCC curve at point F. 11. Mention the length O’G, HF and OA. PROCEDURE TO DRAW THE VECTOR DIAGRAM (ASA METHOD) (To find the field Excitation current If) 1. Draw the vector with the magnitude O’G. 2. From G draw a vector with the magnitude of GH (OA) in such a way to make an angle of (90 ± Φ) from the line O’G [ (90 + Φ) for lagging power factor and (90 – Φ) for leading power factor] 3. Join the points O’ and, H also extend the vector O’F with the magnitude HF. Where O’F is the field excitation current (If). 4. Find out the open circuit voltage (Eo) for the corresponding field excitation current (If) from the OCC curve. 5. Find out the regulation from the suitable formula. RESULT: Thus the regulation of 3-phase alternator has been predetermined by the Potier and ASA methods. VIVA QUESTIONS: 1. What is meant by ZPF Test? 2. What is Potier reactance? How is it determined by Potier triangle? 3. What is meant by armature reaction reactance? 4. What is the significance of the ASA modification of MMF method? 5. What is air gap line in Potier method?
  • 21.
  • 22.
  • 23. EXP.NO. 3 DATE: SLIP TEST ON 3-PHASE ALTERNATOR AIM: To conduct a slip test on 3-Ф alternator and pre-determine the regulation through vector diagram. APPARATUS REQUIRED: S.no Name of Range Type Quantity Apparatus 1 Ammeter (0-5)A MI 1 (0-1)A MC 1 2 Voltmeter (0-150)V MI 1 (0-5)V MC 1 3 Rheostat 250 Ω /1.5A 1 4 Tachometer Digital 1 5 TPST Switch 1 6 Connecting As reqd. Wires FUSE RATING: (a)For Motor- 125% of rated current = 125% of 17A=21.25A=25A (b)For Alternator- 125% of rated current =125% of 4A= 5A THEORY: In a salient pole alternator, the reactance of magnetic circuit along is along its quad stator axis. The alternator is driven by auxiliary prime mover at a speed slightly less than the synchronous speed under these conditions. The armature current is when the armature current mmf is in line with the field poles. The reactance by the magnetic field current is minimum. The ratio of maximum voltage to minimum current gives the direct axis impedance and the ratio of minimum voltage to maximum current gives the armature axis impedance. PRECAUTIONS: 1. The motor field rheostat should be kept in minimum. 2. The direction of the rotation due to prime mover and the alternator on the motor should be the same. 3. Initially all the switches are kept open.
  • 24. PROCEDURE: 1. Note down the name plate details of motor and alternator. 2. Connections are made as per the circuit diagram. 3. Give the supply by closing the DPST switch. 4. Using the three point starter, start the motor to run at the synchronous speed by varying the motor field rheostat at the same time check whether the alternator field has been opened or not. 5. Apply 20% to 30% of the rated voltage to the armature of the alternator by adjusting the autotransformer. 6. To obtain the slip and the maximum oscillation of pointers the speed is reduced slightly lesser than the synchronous speed. 7. Maximum current, minimum current, maximum voltage and minimum voltage are noted. 8. Find out the direct and quadrature axis impedances. PROCEDURE TO DRAW THE VECTOR DIAGRAM: 1. Draw the line OA that represents the rated voltage V. 2. Draw the line OB vector to represent the rated current I, which makes an angle Φ (it may lag/lead/in phase) with the voltage. 3. Draw the line AC vector to represent IRa drop, which is parallel to OB vector. 4. Draw the perpendicular line CD to the line AC (IRa drop) that represents IXq drop. 5. Draw the line from the origin through the point D, which represents the no load voltage (Eo). 6. Draw the pole axis through origin, which should be perpendicular to vector OD. 7. Draw a perpendicular line to the pole axis from the same point E which should pass through the point B [where vector OE represents Direct Axis Current (Id) and Vector EB represents Quadrature Axis Current (Iq)]. 8. Find out the reactive voltage drops IdXd and IqXq. 9. Draw a parallel line (ie perpendicular to Id) to OD vector from the point C, with the magnitude of the drop IdXd (Line CF). 10. Draw a parallel line (ie perpendicular to Iq) to OE vector from the point F, with the magnitude of the drop IqXq (Line FG). 11. Let the point at where the IqXq drop meets the OD line be G. here the vector OG represents the no load voltage (Eo). 12. Find out the voltage regulation by using the suitable formula. FORMULAE USED: 1. Rac=1.6Rac Ω 2. Zd = Vmax/Imin Ω 3. Zq = Vmin/Imax Ω 4. Xd = √Zd2 – Rd2 Ω
  • 25. 5. Xq = √Zq2 – Rd2 Ω 6. Id = Ia sinФ amps 7. Iq = Ia cos Ф amps 8. %Reg = (Eo-V/V)*100 Where, Zd = direct axis impedance in Ω Zq = quadrate axis impedance in Ω Xd = direct axis reactance in Ω Xq = quadrate axis reactance in Ω Id = direct axis current in amps Ia = quadrate axis current in amps GRAPH: Power Factor VS % regulation. RESULT: Thus the pre-determination of regulation of 3-phase alternator by vector diagram was obtained. VIVA QUESTIONS: 1. What is the purpose of slip test on 3 phase alternator? 2. What is meant by direct axis reactance? 3. What is meant by quadrature axis reactance? 4. How is the regulation of alternator predetermined by slip test? 5. What is the difference between salient pole alternator and cylindrical rotor type alternator?
  • 26. SLIP TEST ON 3-PHASE ALTERNATOR TABULAR COLUMNS (i) To find the Direct Axis and Quadrature axis impedances: S.NO Vmax Vmin Imax Imin 1 2 (ii) To predetermine % Regulation: S.NO Power Factor % Regulation Lagging Leading Unity 1 0.2 -- 2 0.4 -- 3 0.6 -- 4 0.8 -- 5 1.0
  • 27.
  • 28. EXP.NO. 4 DATE: LOAD CHARACTERISTICS OF 3-PHASE ALTERNATOR BY BUS BAR LOADING AIM: To synchronize and operate the two electric sources in parallel with bus bar arrangement and draw the performance characteristic curves. NAME PLATE DETAILS: 3Ǿ alternator DC shunt motor 3ǾLoad FUSE RATING: 125% of rated current (full load current) For DC shunt motor: For ac alternator APPARATUS REQUIRED: S.No Name of apparatus Type Range Quantity 1 Ammeter MC 0-2A 1 2 Ammeter MI 0 – 10 A 1 3 Voltmeter MI 0 – 600 V 1 4 Frequency meter Reed 0 – 60 Hz 1 5 Rheostat Wire 1200 Ω 1 wound 0.8 A 6 Rheostat Wire 250 Ω 1 wound 1.5 A 7 Tachometer Digital -- 1 PRECAUTIONS: (1) The motor field rheostat should be in minimum resistance position. (2) The Alternator field Potential divider should be at minimum voltage position. (3) Initially all switches are in open position.
  • 29. PROCEDURE: SYNCHRONISATION: (1) Note down the name plate details of motor and alternator. (2) Connections are made as per the circuit diagram. (3) Close the DPST switch. (4) Using the 3-point starter start the motor, by varying motor field rheostat. (5) By varying the potential divider , generated voltage is built up to rated voltage. (6) Now close the TPST switch. (7) TPST is closed and by varying the potential divider the field current is varied so that voltmeter reads the same voltage as measured above. (8) When TPST is closed the lamps may flicker uniformly. (9) If flickering is not uniform then the phase sequences of any two lines are changed. (10) Now synchronization switch is closed when lamps are in dark period . (11) Now the two sources are synchronized. LOAD SHARING (1) Connect the synchronized output with variable load. (2) For various loads, note all the corresponding ammeter and voltmeter readings. (3) Draw the graph between respective voltage and currents (V1 Vs V2, V2 Vs I1 and V1 Vs I1.). V-CURVE (1) After synchronization the prime mover should be switched off and Potential divider should be brought to the maximum position. (2) By adjusting the potential barrier tabulate the various Field currents and corresponding Armature readings. (3) To obtain V- curve draw the graph between Armature current and Field current RESULT: The 3 phase alternator has been synchronized with the bus bars and the load characteristics obtained. VIVA QUESTIONS: 1. What is meant by synchronization? 2. What are the conditions for synchronization? 3. What is infinite bus? 4. What are the methods of synchronization? 5. How can the voltage and frequency be adjusted?
  • 30.
  • 31.
  • 32. EXP.NO. 5 DATE: V AND INVERTED V CURVE OF THREE PHASE SYNCHRONOUS MOTOR AIM To draw the V and inverted V curves of a 3 phase Synchronous Motor. NAME PLATE DETAILS: 3ǾSYNCHRONOUS MOTOR DC EXCITATION FUSE RATING:l 125% of rated current (full load current) For DC excitation: For synchronous motor:] APPARATUS REQUIRED: S.No Name of the Type range Quantity apparatus 1 Ammeter MI (0-5)A 2 2. Voltmeter MI (0-600)V 2 3. Ammeter MC (0-2)A 1 4. Rheostat 200Ω,15 1 A 5. Wattmeter UPF 2 600V,5A
  • 33.
  • 34. PRECAUTION: (1) The Potential barrier should be in maximum position. (2) The motor should be started without load . (3) Initially TPST switch is in open position. PROCEDURE: (1) Note down the name plate details of the motor. (2) Connections are made as pr the circuit diagram.. (3) Close the TPST switch. (4) By adjustingthe autotransformer from the minimum position to the maximum position the rated supply is given to motor. The motor starts as an induction motor. (5) In order to give the excitation to the field for making it to run as the synchronous motor, close the DPST switch. (6) By varying the field rheostat note down the excitation current, armature current and the power factor for various values of excitation. (7) The same process has to be repeatedfor loaded condition. (8) Later the motor is switched offand the graph is drawn. GRAPH: The graph is drawn for- (1) Armature current Vs Excitation current. (2) Power factor Vs Excitation current. RESULT: The V-curves and inverted V-curves of the 4 phase synchronous motor have been drawn.
  • 35.
  • 36. EXP.NO. 6 A DATE: LOAD TEST ON 3-PHASE SQUIRREL CAGE INDUCTION MOTOR AIM: To draw the performance characteristics of 3-phase squirrel cage induction motor by conducting load test. APPARATUS REQUIRED: S.No Name of Range Type Qty. apparatus 1. Ammeter (0-5)A MI 1 2. Voltmeter (0-600)V MI 1 3. Wattmeter (600V,5A) UPF 2 4. Tachometer Digital 1 5. 3-Ф 1 autotransformer FUSE RATING; 125% of 4.8A=6A=10A THEORY: A 3-phase induction motor consists of stator and rotor with the other associated parts. In the stator, a 3-phase winding is provided. The windings of the three phase are displaced in space by 120º.A 3-phase current is fed to the 3-phase winding. These windings produce a resultant magnetic flux and it rotates in space like a solid magnetic poles being rotated magnetically.
  • 37.
  • 38. PRECAUTIONS- 1.TPST switch is kept open initially. 2.Autotransformer is kept at min. voltage position. 3.There must be no load when starting the load. PROCEDURE- 1.Connections are given as per circuit diagram. 2.3-Ф induction motor is started with DOL starter. 3. If the pointer of one of the wattmeter readings reverses, interchange the current coil terminals and take the reading as negative. 3.The no load readings are taken. 4. The motor is loaded step by step till we get the rated current and the readings of the voltmeter, ammeter, wattmeters, spring balance are noted. FORMULAE USED- 1) % slip= (Ns-N/Ns)*100 2) Input Power = (W1+W2)watts 3) Output Power = 2∏NT/60 watts 4) Torque = 9.81*(S1-S2)*R N-m 5) % efficiency = (o/p power/i/p power)* 100 GRAPHS- 1) Output Power vs Efficiency 2) Output Power vs Torque 3) Output Power vs Speed 4) Output Power vs %s RESULT Thus the performance characteristics of a 3-Ф squirrel cage induction motor by conducting load test has been drawn.
  • 39.
  • 40. EXP.NO. 6 B DATE: LOAD TEST ON 3-PHASE SLIP RING INDUCTION MOTOR AIM : To conduct a direct load test on a 3-phase slip ring induction motor and to draw the performance characteristics. APPARATUS REQUIRED : S.NO NAME OF RANGE TYPE QTY. APPARATUS 1 Ammeter MI 1 (0-10)A 2 Voltmeter (0-600)V MI 1 3 Wattmeter (600V,10A) UPF 2 4 Tachometer Digital 1 FUSE RATING- FOR- STATOR- 125% 0f 7.5A = 10A FOR ROTOR – 125% of 11A = 15A THEORY: Slip ring induction motor is also called as phase wound motor. The motor is wound for as many poles as the no. of stator poles and always wound 3-Ф even while the stator is wound two-phase. The other three windings are brought out and connected to three insulated slip-rings mounted on the shaft with brushes resting on them. These three brushes are further externally connected to a three phase star connected rheostat. This makes possible the introduction of an additional resistance in the rotor circuit during starting period for increasing starting torque of the motor.
  • 41.
  • 42. PRECAUTIONS: 1. TPST switch is kept open initially. 2. The external resistance in the rotor circuit should be kept at max. value. PROCEDURE: 1. Connections are given as per circuit diagram. 2. After observing precautions motor is started on no load. 3. As speed increases, the external resistance is gradually cut out. 4. The no-load readings are taken. 5. If the pointer in one of the wattmeter reverses, interchange the current coil terminals and take the reading as negative. 6. The meter readings are then noted for various load conditions. FORMULAE USED: 1. Torque= (S1-S2)*9.81*100 N-m 2. O/P Power= 2πNT/60 watts 3. I /P Power = (W1+W2) watts 4. η % = (o/p power/ i/p power)*100 5. %s = (Ns-N)/Ns*100 GRAPHS: 1. O/P power vs Speed 2. O/P power vs Torque 3. O/P Power vs η 4. O/P Power vs slip 5. Torque vs Speed 6. Torque vs Slip RESULT: The load test on 3-Ф slip ring induction motor was conducted and the performance characteristics curves were plotted.
  • 43.
  • 44. EXP.NO. 7 DATE: NO LOAD AND BLOCKED ROTOR TEST ON 3- PHASE INDUCTION MOTOR AIM: To conduct the no load & blocked rotor test on 3- phase induction motor & to draw the equivalent circuit of 3- phase squirrel cage induction motor. APPARATUS REQUIRED :- z S.NO NAME OF RANGE TYPE QTY APPARATUS 1. Voltmeter (0-600)V MI 01 (0-150)V MI 01 2. Ammeter (0-10)A MI 01 3. Wattmeter (600V,5A) UPF 01 (150V,10A) LPF 01 4. Connecting wire As required FUSE RATING :- 125/100 * 7.5 A ≈ 10A THEORY :- A 3-phase induction motor consists of stator, rotor & other associated parts. In the stator ,a 3- phase winding (provided) are displaced in space by 120. A3- phase current is fed to the winding so that a resultant rotating magnetic flux is generated. The rotor starts rotating due to the induction effect produced due the relative velocity between the rotor Winding & the rotating flux. PRECAUTIONS :- NO LOAD TEST – (1). Initially TPST switch is kept open. (2). Autotransformer must be kept at minimum potential position. (3). The machine must be started at no load.
  • 45.
  • 46. BLOCKED ROTOR TEST - (1). Initially the TPST switch is kept open. (2). Autotransformer must be kept at minimum potential position. (3). The machine should be started on full load. PROCEDURE :- NO LOAD TEST - (1). Connections are given as per the circuit diagram. (2). Precautions are observed and motor is started on the no load. (3). Autotransformer is varied to have rated voltage applied. (4). The meter readings are then tabulated. BLOCKED ROTOR TEST :- (1). Connections are given as per circuit diagram. (2). Precautions are observed and motor is started on full load or blocked rotor position. (3). Autotransformer is varied to have rated current flowing in motor. (4). The meter readings are then tabulated. FORMULA USED- FOR NO LOAD TEST- Wsc = √3 Vo IoCOSФ watts Iw = Io cosФ amps Ro= V0/ Iw Ω Xo= Vo/Iu Ω FOR BLOCKED ROTOR TEST- Wsc =3I2*Ro watts Ro1 = Wsc/3(Isc)2 Ω Zo1 = Vsc/Isc Ω Xo1 = √Zo1^2-Ro1^2 Ω RESULT:- Thus the no load and blocked rotor test on 3-Фsquirrel cage induction motor is performed and the equivalent circuit of 3-phase squirrel cage induction motor has been drawn.
  • 47. TABULAR COLUMNS NO LOAD TEST: S.No Voltage Current Wattmeter W1 x Wattmeter W2 x Voc Ioc readings (W1) mf1 readings (W2) mf2 Observed Actual Observed Actual Volts Amps Watts Watts 1 Voc= open circuit voltage Ioc = open circuit current BLOCKED ROTOR TEST: S.No. Voltage Current Wattmeter W1 x Wattmeter W2 x Vsc Isc readings(W1) mf1 readings(W2) mf2 Observed Actual observed Actual Volts Amps Watts Watts 1. Vsc = short circuit voltage Isc = short circuit current
  • 48.
  • 49. EXP.NO. 8 DATE: STUDY OF SYNCHRONOUS INDUCTION MOTOR AIM:- To study the construction, working principle and performance characteristics of Synchronous Induction Motor. APPARATUS REQUIRED:- 3 Phase Synchronous Induction Motor with loading arrangement Auto Induction Starter panel – 1 TPDT knife switch - 1 Tachometer - 1 THEORY:- In the applications where high starting torque and constant speed are desired then synchronous induction motor can be used. It has the advantages of both synchronous motor and induction motor. The synchronous motor gives constant speed whereas induction motors can be started against full load torque. Consider a normal slip ring induction motor having three phase winding on the rotor as shown in the figure. The motor is connected to the exciter which gives d.c. supply to the rotor through slip rings. One phase carries full d.c. current while the other two carries half the full d.c. current as they are connected in parallel. Due to this d.c. excitation, permanent poles (N and S) formed on the rotor. Initially it is run as a slip ring induction motor with the help of starting resistances. When the resistances are cut out the motor runs with a slip. Now the connections are changed and the exciter is connected in series with the rotor windings which will remain in the circuit permanently. As the motor is running as induction motor initially high starting torque (up to twice full load value) can be developed. When the d.c. excitation is provided it is pulled into synchronism and starts running at constant speed. Thus synchronous induction motor provides constant speed, large starting torque, low starting current and power factor correction. PRECAUTIONS: 1. The motor should be started without load. 2. The rotor resistance starter should be kept in the maximum resistance position while starting. 3. The field potential divider should be kept in the maximum resistance position.
  • 50. PROCEDURE: 1. Note down the name plate details of the motor. 2. Connections are given as per the circuit diagram. 3. Close the TPST switch in order to supply the rated voltage to the motor. 4. Start the motor by closing the TPDT switch (position 123) with the rotor resistance starter in maximum resistance position to run the motor at rated speed. 5. Change the position of TPDT switch (position 1’2’3’) in order to excite the rotor by DC source where the excitation should be given gradually through the potential divider to maintain the synchronous speed. 6. The resistance if the stator can be measured using Dc supply with voltmeter and ammeter or directly using a multimeter. RESULT: The working principle and performance characteristics of the synchronous induction motor have been studied.
  • 51.
  • 52. EXP.NO. 9 DATE: STUDY OF INDUCTION MOTOR STARTERS AIM: To study and connect (1) Direct Online Starter (2) Auto transformer Starter (3) Star Delta Starter (4) Rotor Resistance Starter APPARATUS REQUIRED: SL.NO NAME OF APPARATUS QUANTITY 1. DOL Starter 1 No. 2. Auto transformer Starter 1 No. 3. Star Delta Starter 1 No. 4. Rotor Resistance Starter 1 No. THEORY: NECESSITY OF STARTERS: An induction motor is similar to a secondary short circuit three phase transformer so if normal voltage is applied to the motor it takes 5 to 6 times of normal current from the mains and starting torque is also increased to around 1.5 to 2.5 times of their full load torque. This initial excessive starting current is objectionable, because it will produce large line voltage drop, which in turn will affect the operation of the other electrical equipments connected to the same mains. So the starters are used to reduce the starting current of induction motor and also to protect the motor and also used to protect the motor from overloading and low voltages. TYPES OF STARTERS: (1) Direct Online Starter (2) Auto transformer Starter (3) Star Delta Starter (4) Rotor Resistance Starter DIRECT ON LINE STARTER [DOL STARTER]:- Generally when the starter winding of on induction motor are connected to the Supply directly .a very large current of about 5-8 times full load current flow initially. such a starting .of the induction motor is called direct on line starting. The initial stage
  • 53. current decreases of the motor starts accelerating and running at normal speed. Unlike d.c motors where such a starting can damage the windings due to a lsent 0/- back Emf at start induction motor can le started .This way through out not expandly in a short space of time called cycling .The only effect of the shorting is the sudden line voltage drop that occurs which may affect other electrically equipments on the same time line .hence direct an line
  • 54.
  • 55. starting is not advisable for motor with rating greater than 5 HP. The points to be kept in mind for DOL starting are • Whether other electrical equipment connected to the same lines can with stand The sudden voltage fluctuation caused by the starting. • Whether the generator and distribution system can with stand the high voltage Dip and large current drawn . • In case of loads having high inertia like centrifugal oil separate time may also be a factor REASON FOR AVOIDING FAST CYCLING At start the starting current Ist is about 5-8 times normal full load current .therefore The starting heat generated itself is related to 1st as Hst α Ist2 And Hst is 26-64 times normal heating also at start there is no winding and other losses . Hence repeated starting in short space of time or fast cycling may cause successive heat and damage of coil . HOW THE STARTER WORKS: Control circuit: Thus circuit consists of conductor coil in series with start button stop Button and over load trip contacts is called control circuit. When the start button is pressed the control circuit energized to via lines of the 3 phase supply is connected the control coil the contactor classes and starts The motor after releasing the start .It spring back but the contactor is kept enargised by another auxillary winding . When the stop button is released proceed, it break the circuits & the contactors trips & the motor stops. Under excess current leaving drawn the over current trip coil are energized magnetic coil or the normally open (NO) the overload trip contact and stop the motor. AUTO TRANSFORMER STARTER This stator is useful and suitable for motor in which each and of the 3-phase are not all throughout and hence are not suitable for star delta starting gapped or variable autotransformer can be used for starting. The autotransformer are generally used for large motor drives like electric cargo pumps because of cost factors . STAR-DELTA-STARTER This starter is used in case of motor which are built normally with a delta connected stator winding. Basically it consist a two way switch that connected the motor star type of the time of start and delta type under normal running connection . The advantages of having a star connected winding the voltage applied over each motor phase is reduced to 1/√ 3 times the normal value and the current to 1/√3 time normal value . But the starting torque is also reduced by a factor of 1/√3.
  • 56.
  • 57. ROTOR RHEOSTAR STATOR This stator is used for starting slip motors in this the stator terminal are Connected to supply via a variable resistance in series to the stator circuit . The controlling resistance is after connected rheostat type with resistance being gradually cot out as Motor gain speed. The two advantages of this starting is:- 1) starting current is reduced 2) starting torque is increased due to power factor improvement. The controlling rheostat may be of speed or contactor type and may also be manual or auto noted. The starter also consist of low voltage and over current protective devices. There is inter locking mechanism for ensuring proper operation of line contactor and starter. This method is similar to the starter used for starting dc motor in which too, the resistance is cut out gradually ones the motor was started running normally. PRECAUTIONS: (1) All connections should be tight. (2) Metallic body of every equipment used must be properly earthed. PROCEDURE: 1. Connect the DOL starter with the motor terminal in one side and motor switch on another side as shown in figure. 2. Put ON the switch and press the start button (green) of the starter to start the motor. 3. Press the stop button (red) to stop the motor. 4. Connect the auto transformer terminals with the motor terminals and motor switch as shown in figure. 5. Now adjust the required settings on autotransformer starter that is above 60%. 6. Out ON the switch, now the motor will start running. When the motor speed reaches to about 80% of the normal speed, then move the handle of the starter and to other side for giving full voltage to the motor. 7. Connect the Star Delta starter with the motor on one side and motor switch in another side as shown in figure. 8. Put on the switch and move the handle of the starter first in downward position thus connecting the winding first in Star and after a few seconds move it in upward position thus connecting the winding in Delta connection. 9. Connect the rotor resistance starter with the motor on one side and motor switch on another side as shown in figure.
  • 58. 10. Put ON the switch and start the motor with the rotor resistance. RESULT: Hence various types of the three phase induction motor starters have been studied.
  • 59.
  • 60. EXP.NO. 10 DATE: SEPARATION OF LOSSES IN THREE PHASE SQUIRREL CAGE INDUCTION MOTOR AIM: To separate the no load losses of a 3 phase squirrel cage induction motor as iron losses and mechanical losses. NAME PLATE DETAILS: 3Ø induction motor Auto Transformer FUSE RATING: No load :10% of rated current (full load current). APPARATUS REQUIRED: S.No Name of the apparatus Type Range Quantity 1. Ammeter MI (0-10)A 1 MC (0-1)A 1 2. Voltmeter MI (0-600)V 1 MC (0-5)V 1 3. Wattmeter LPF 600V,5A 2 4. 3-Ф Auto Transformer (415/0-470) 1 V Rheostat 5. 1200Ω/0.8A 1 PRECAUTIONS: (1) The autotransformer should be kept in minimum voltage position. (2) the motor should not be loaded throughout the experiment.
  • 61.
  • 62. PROCEDURE: (1) Connections should be made as per the circuit diagram. (2) by giving three phase supply , start the motor. (3)vary the autotransformer till rated speed is attainsd and note the input power, voltage and current. (4)repeat the same procedure for and tabulate the reading. (5)find the stator copper loss and constant loss by respective formulas. (6)draw the suitable graph to find the mechanical losses. (7)obtain the core los by separating the mechanical loss fom constant losses. GRAPH: The graph drawn between constant losses(watts) and input voltage(volts). MODEL CALCULATIONS: 1. Input power(W) =(W1+W2)in watts 2. Stator copper loss =3I2Rs in watts 3. Constant loss/phase(Wc)= (W-3I2Rs)/3 in watts 4 Core loss/phase (Wi)= (constant loss/phase)-mechanical loss RESULT: Thus the no load losses of 3-phase squirrel cage induction motor was separated as core losses and mechanical losses.
  • 63.
  • 64. EXP.NO. 11 DATE: LOAD TEST ON SINGLE PHASE INDUCTION MOTOR AIM: To determine the performance characteristic of a given single phase capacitor start induction motor by conducting load test. APPARATUS REQUIRED: SL. NO APPARATUS RANGE TYPE QUANTITY 1 Voltmeter (0-300)V MI 1 2 Ammeter (0-10)A MI 1 3 Wattmeter 300 V, 10A UPF 1 4 Tachometer 1 5 Connecting wires As required FUSE RATING : Fuse rating = 125% of rated current = 125/100 * 7.5 ≈ 10A THEORY: The single phase induction motor is more or less a polyphase induction motor. The only difference is that is given supply in single phase. This motor connect and motor function without any initial start the motor having some part which is called starter and rotor. These are two types of starting a 1 phase induction motor namely capacitor-start and other is split- phase. These motors are widely used in domestic purpose. PRECAUTION: 1) Before switching on the supply the variac is kept in minimum position. 2) Initially these should be on no load while starting the motor.
  • 65. PROCEDURE: 1) Connections are given as per the circuit diagram. 2) Switch on the supply at no load condition. 3) Apply the rotor voltage to the motor using the variac and note down the readings at ammeter And wattmeter. 4) Vary the load in suitable steps and note down all the meter readings till fill load condition. FORMULA USED: 1) Torque ,T = (S1~S2)*9.81*R N.m 2) Output power = 2π NT/60*W 3) Effecting (η%) = 0/P Power/I/p Power*100 4) Slip (%S) = NS – N/NS*100 5) Power factor = Cos φ=W/VI GRAPH : 1) Output Power Vs speed 2) Output power Vs Torque 3) Output power Vs Effecting 4) Output power Vs slip 5) Output power Vs Power factor RESULT: Thus load test on the single phase induction motor has been conducted and its performance characteristics determined.
  • 66.
  • 67. TABULAR COLUMN m.f = Sl.No. VL IL Speed(N) S1 S2 S1 ̃~ S2 Torque Wattmeter Reading Output Efficiency V A RPM Kg Kg Kg N-m Power η PF= cosΦ Observed Actual W % 1 2 3 4 5 6 7 8 MODEL CALCULATION: Input power = W x m.f = Watts % slip = (Ns – N)/Ns x 100 pf= cosΦ = W/VLIL Output power = 2лNT/ 60 Watts Torque T= (S1~S2)*9.81*R N-m, where R is the radius of the brake drum in metre Output power Efficiency η = x 100 Input power
  • 68.
  • 69. EXP.NO. 12 DATE: EQUIVALENT CIURCUIT AND PRE-DETERMINATION OF PERFORMANCE CHARACTERISTICS OF 1Ф INDUCTION MOTOR AIM: To draw the performance characteristics of a single phase induction motor by conducting the no-load and blocked rotor test. APPARATUS REQUIRED: S.No Name of Range Type Qty. Apparatus 1 Voltmeter (0-300)V MI 1 (0-150)V MI 1 2 Ammeter (0-10)A MI 1 (0-2)A MI 1 3 Wattmeter (330V,10A) UPF 1 (300V,5A) LPF 1 4 Connecting As reqd. wires FUSE RATING: 125% of 7.6A=10A THEORY: A 1-Ф induction motor consists of stator,rotor and other associated parts.In the rotor of a single phase winding is provided.The windings of a 1- Ф winding(provided) are displaced in space by 120º.A single phase current is fed to the windings so that a resultant rotating magnetic flux is generated.The rotor starts rotating due to the induction effect produced due to the relative velocity between the rotor winding and the rotating flux. PRECAUTIONS: NO LOAD TEST: • Initially TPST Switch is kept open. • Autotransformer is kept at minimum potential position. • The machines must be started on no load.
  • 70.
  • 71. BLOCKED ROTOR TEST: • Initially the TPST Switch is kept open. • Autotransformer is kept at minimum potential position. • The machine must be started at full load(blocked rotor). PROCEDURE: NO LOAD TEST: 1. Connections are given as per the circuit diagram. 2. Precautions are observed and the motor is started at no load. 3. Autotransformer is varied to have a rated voltage applied. BLOCKED ROTOR TEST: 1. Connections are given as per the circuit diagram. 2. Precautions are observed and motor is started on full load or blocked rotor position. 3. Autotransformer is varied to have rated current flowing in motor. 4. Meter readings are the noted. Reff = 1.5*Rdc FORMULAE- NO LOAD TEST- • cos Ф = Wo/VoIo • Iw = Io cosФ • Im = Io sin Ф • Ro = Vo/Iw • Xo = Vo/Im BLOCKED ROTOR TEST- Zsc = Vsc/Isc Ω Rsc = Wsc/Isc2 Ω Xsc = √(Zsc2 – Rsc2) Ω RESULT- Thus the no load and blocked rotor test on the single phase induction motor has been conducted and the equivalent circuit has been drawn.
  • 72. TABULATION NO LOAD TEST- S.No. Vo(volts) Io(amps) Wo(watts) m.f Observed Acual BLOCKED ROTOR TEST- S.No. Vsc(volts) Isc(amps) Wsc(watts) m.f Observed Actual