version 3.4
Brick
                           010   Single Wythe
                           020   Composite
                           030   Anchored Veneer - Masonry Backup
                           040   Anchored Veneer - Steel Stud Backup
01   Brick                 050   Anchored Veneer - Wood Stud Backup
02   Concrete block        060   Anchored Veneer - Other Backup
03   Stone, rough          070   Adhered Veneer - Masonry Backup
04   Stone, dimensional    080   Adhered Veneer - Steel Stud Backup
06   Tile                  090   Adhered Veneer - Wood Stud Backup
07   Terrazzo              100   Adhered Veneer - Other Backup
08   Cement                110   Rain Screen Wall
09   Plaster / Stucco      120   Structural Masonry
10   Restoration           130   Flooring - Interior
11   Terra Cotta           140   Paving - Exterior
12   Refractory            150   Landscape Walls
13   AAC                   160   Fireplaces & Chimneys
14   Precast Concrete      210   Training Mockups
15   Accessories           220   Apprentice Contests
21   Structural Steel      310   Building Models
22   Cast-in-Place Conc.   400   Wall Type Analysis
23   Metal Siding          410   Diagrams
40   Wall Type Analysis    510   Modular/Bonding
50   Building Model        610   Sustainability / Energy-Efficiency
CONCEPTUAL WALL SECTION
DETAIL 01.030.0101   REV. 03/26/09
                                     © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                               1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                     AIR/MOISTURE/VAPOR
                                                                     BARRIER AS REQUIRED

                                                                             HORIZONTAL JOINT REIN-
                                                                             FORCEMENT W/ EYE & PINTLE
                                                                             WALL TIES @ 16” O.C.

                                                                             RIGID INSULATION

                                                                             GROUT & REINFORCEMENT
                                                                             AS REQUIRED




                                                                                    MECH. FASTENED
                                                                                    TERMINATION BAR W/
                                                                                    CONT. SEALANT @ TOP



                                                                                       CONCRETE
                                                                                       MASONRY BACKUP
      BRICK VENEER

                                                                                       FLEXIBLE FLASHING – SEAL
                                                                                       & ADHERE TO DRIP EDGE


                     WEEP VENT INSERTS

                           DRIP EDGE – SEAL AND
                           ADHERE TO FOUNDATION



BASE OF WALL DETAIL                  FLEX. FLASHING, DRIP EDGE, TERM. BAR
DETAIL 01.030.0301                                           REV. 09/25/09
                                                                                                © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                              1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                     AIR/MOISTURE/VAPOR
                                                                     BARRIER AS REQUIRED

                                                                            HORIZONTAL JOINT REIN-
                                                                            FORCEMENT W/ EYE & PINTLE
                                                                            WALL TIES @ 16” O.C.

                                                                            RIGID INSULATION

                                                                            GROUT & REINFORCEMENT
                                                                            AS REQUIRED




                                                                                   MECH. FASTENED
                                                                                   TERMINATION BAR W/
                                                                                   CONT. SEALANT @ TOP




                                                                                      CONCRETE
                                                                                      MASONRY BACKUP
     BRICK VENEER

                                                                                      FLEXIBLE FLASHING – SEAL
       MORTAR DROPPING                                                                & ADHERE TO DRIP EDGE
       COLLECTION DEVICE (MDCD)

                     WEEP VENT INSERTS


                           DRIP EDGE – SEAL AND
                           ADHERE TO FOUNDATION


BASE OF WALL DETAIL                 FLEX. FLASHING, DRIP EDGE, TERM. BAR, MDCD
DETAIL 01.030.0302                                                 REV. 09/25/09
                                                                                               © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                              1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                     AIR/MOISTURE/VAPOR
                                                                     BARRIER AS REQUIRED

                                                                            HORIZONTAL JOINT REIN-
                                                                            FORCEMENT W/ EYE & PINTLE
                                                                            WALL TIES @ 16” O.C.

                                                                            RIGID INSULATION

                                                                            GROUT & REINFORCEMENT
                                                                            AS REQUIRED




                                                                                   MECH. FASTENED
                                                                                   TERMINATION BAR W/
                                                                                   CONT. SEALANT @ TOP




                                                                                      CONCRETE
                                                                                      MASONRY BACKUP
     BRICK VENEER

                                                                                      FLEXIBLE FLASHING FLUSH
       MORTAR DROPPING                                                                W/ OUTSIDE FACE OF BRICK
       COLLECTION DEVICE (MDCD)

                     WEEP VENT INSERTS




BASE OF WALL DETAIL                  FLEX. FLASHING NO DRIP; TERM BAR, MDCD
DETAIL 01.030.0303                                              REV. 09/25/09
                                                                                               © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                          1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                AIR/MOISTURE/VAPOR
                                                                BARRIER AS REQUIRED

                                                                        HORIZONTAL JOINT
                                                                        REINFORCEMENT W/ EYE &
                                                                        PINTLE WALL TIES @ 16” O.C.

                                                                        RIGID INSULATION

                                                                        GROUT & REINFORCEMENT
                                                                        AS REQUIRED




   BRICK VENEER                                                                    CONCRETE
                                                                                   MASONRY BACKUP

   WEEP VENTS AT 2ND COURSE FOR
   AIR CIRCULATION RECOMMENDED                                                     DRAINAGE FLASHING
                                                                                   SYSTEM

            ADDITIONAL WEEP VENT
            INSERTS RECOMMENDED

                 WEEPS INTEGRAL TO DRAINAGE
                 FLASHING SYSTEM



BASE OF WALL DETAIL                 DRAINAGE FLASHING
DETAIL 01.030.0304                        REV. 09/25/09
                                                                                           © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED; 1”
                                                            MIN. REQ’D FOR DRAINAGE WALLS



                                                                  AIR/MOISTURE/VAPOR
                                                                  BARRIER AS REQUIRED

                                                                         HORIZONTAL JOINT
                                                                         REINFORCEMENT W/ EYE &
                                                                         PINTLE WALL TIES @ 16” O.C.

                                                                         RIGID INSULATION

                                                                         GROUT & REINFORCING
                                                                         AS REQUIRED


                                                                                AIR/MOISTURE/VAPOR
                                                                                BARRIER TO SEAL
                                                                                TRANSITION MEMBRANE

                                                                                RUBBERIZED ASPHALT
                                                                                TRANSITION MEMBRANE
                                                                                OVER TERM. BAR


                                                                                    CONCRETE
                                                                                    MASONRY BACKUP
     BRICK VENEER                                                                  PROPRIETARY DRAINGAGE
                                                                                   FLASHING SYSTEM W/
                                                                                   INTEGRAL DRIP EDGE, TERM.
                                                                                   BAR & WEEP SYSTEM

          ADDITIONAL WEEP VENT INSERTS
          AS REQ’D FOR VENILATED WALL

                     MESH WEEPS INTEGRAL TO
                     PROPRIETARY DRAINAGE
                     FLASHING SYSTEM


FOUNDATION DETAIL               PROPRIETARY DRAINAGE FLASHING (TOTAL FLASH)
DETAIL 01.030.0304                                              REV. 06/25/09
                                                                                            © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                                1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                          AIR/MOISTURE/VAPOR
                                                                          BARRIER AS REQUIRED

                                                                                 HORIZONTAL JOINT REIN-
                                                                                 FORCEMENT W/ EYE & PINTLE
                                                                                 WALL TIES @ 16” O.C.

                                                                                 RIGID INSULATION

                                                                                 GROUT & REINFORCEMENT
                                                                                 AS REQUIRED




                                                                                       RETURN FLASHING INTO
                                                                                       BED JOINT OF BLOCK
                                                                                       CONCRETE
                                                                                       MASONRY BACKUP



     BRICK VENEER

                                                                                           FLEXIBLE FLASHING – SEAL
                                                                                           & ADHERE TO DRIP EDGE


                     WEEP VENT INSERTS

                           DRIP EDGE – SEAL AND
                           ADHERE TO FOUNDATION



BASE OF WALL DETAIL                  FLEX. FLASHING IN CMU, DRIP EDGE
DETAIL 01.030.0305                                        REV. 09/25/09
                                                                                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                               1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                     AIR/MOISTURE/VAPOR
                                                                     BARRIER AS REQUIRED

                                                                               HORIZONTAL JOINT REIN-
                                                                               FORCEMENT W/ EYE & PINTLE
                                                                               WALL TIES @ 16” O.C.

                                                                               RIGID INSULATION

                                                                               GROUT & REINFORCEMENT
                                                                               AS REQUIRED

                                                                                     RETURN FLASHING INTO
                                                                                     BED JOINT OF BLOCK




                                                                                     CONCRETE
                                                                                     MASONRY BACKUP



     BRICK VENEER

                                                                                         FLEXIBLE FLASHING – SEAL
       MORTAR DROPPING                                                                   & ADHERE TO DRIP EDGE
       COLLECTION DEVICE (MDCD)

                     WEEP VENT INSERTS

                           DRIP EDGE – SEAL AND
                           ADHERE TO FOUNDATION



BASE OF WALL DETAIL                 FLEX. FLASHING IN CMU, DRIP EDGE, MDCD
DETAIL 01.030.0306                                             REV. 03/16/10
                                                                                                  © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                            1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                  AIR/MOISTURE/VAPOR
                                                                  BARRIER AS REQUIRED

                                                                          HORIZONTAL JOINT REIN-
                                                                          FORCEMENT W/ EYE & PINTLE
                                                                          WALL TIES @ 16” O.C.

                                                                          RIGID INSULATION

                                                                          GROUT & REINFORCEMENT
                                                                          AS REQUIRED



                                                                                 MECH. FASTENED
                                                                                 TERMINATION BAR W/
                                                                                 CONT. SEALANT @ TOP




   BRICK VENEER
                                                                                    CONCRETE
                                                                                    MASONRY BACKUP
    MORTAR DROPPING
    COLLECTION DEVICE (MDCD)
                                                                                    METAL FLASHING W/
                                                                                    INTEGRAL DRIP EDGE –
                                                                                    SEAL AND ADHERE
                                                                                    TO FOUNDATION
                      WEEP VENT INSERTS




BASE OF WALL DETAIL               METAL FLASHING W/ DRIP, TERM. BAR, MDCD
DETAIL 01.030.0311                                            REV. 09/25/09
                                                                                             © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                    1” MIN. REQ’D FOR DRAINAGE WALLS




                                                    CONCRETE
                                                    MASONRY BACKUP




                                                                  RIGID INSULATION

                                                                  GROUT & REINFORCEMENT
                                                                  AS REQUIRED



                                                                  HORIZONTAL JOINT REIN-
                                                                  FORCEMENT W/ EYE & PINTLE
                                                                  WALL TIES @ 16” O.C.




   BRICK VENEER                                                          METAL FLASHING
                                                                         RECEIVER SET IN
                                                                         CMU BED JOINT


                                                                            METAL FLASHING W/
                                                                            INTEGRAL DRIP EDGE –
                                                                            SEAL AND ADHERE
                                                                            TO FOUNDATION



                     WEEP VENT INSERTS




BASE OF WALL DETAIL       METAL FLASHING, METAL RECEIVER
DETAIL 01.030.0312                           REV. 09/25/09
                                                                                     © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                    1” MIN. REQ’D FOR DRAINAGE WALLS


                                                        CONCRETE
                                                        MASONRY BACKUP

                                                        RIGID INSULATION
                                                        AIR/MOISTURE/VAPOR
                                                        BARRIER AS REQUIRED
                                                                  GROUT & REINFORCEMENT
                                                                  AS REQUIRED
       BRICK VENEER

                                                                         HORIZONTAL JOINT REIN-
                                                                         FORCEMENT W/ EYE & PINTLE
             T/ BRICK                                                    WALL TIES @ 16” O.C.
             LEDGE
                                                                                  T/FDTN.
         4” MIN.




                                                                           MORTAR DROPPING
                                                                           COLLECTION DEVICE
                                                                           (MDCD)
   GRADE TO SLOPE                                                          FLASHING SYSTEM
   AWAY FROM WALL


                                                                              FOUNDATION



                                                    BELOW-GRADE INSULATION
                                                    AND WATERPROOFING


BASE OF WALL DETAIL     BRICK LEDGE, T/FDTN. ABOVE GRADE
DETAIL 01.030.0321                            REV. 09/25/09
                                                                                 © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                             1” MIN. REQ’D FOR DRAINAGE WALLS


                                                                 CONCRETE
                                                                 MASONRY BACKUP

                                                                 RIGID INSULATION
                                                                 AIR/MOISTURE/VAPOR
                                                                 BARRIER AS REQUIRED
                                                                           GROUT & REINFORCEMENT
                                                                           AS REQUIRED
       BRICK VENEER
                                                                           HORIZONTAL JOINT REIN-
                                                                           FORCEMENT W/ EYE & PINTLE
                                                                           WALL TIES @ 16” O.C.

                                                                           MORTAR DROPPING
                                                                           COLLECTION DEVICE (MDCD)
                                                                           FLASHING SYSTEM
                                                                                     T/FDTN.




   GRADE TO SLOPE                                                                 GROUT OR MORTAR FILL
   AWAY FROM WALL


    WATER RESISTANT                                                       FOUNDATION
    SURFACE TREATMENT AT
    BRICK BELOW GRADE
        BELOW-GRADE INSULATION                  T/ BRICK
        AND WATERPROOFING                       LEDGE




BASE OF WALL DETAIL              BRICK LEDGE, T/FDTN. BELOW GRADE
DETAIL 01.030.0322                                      REV. 01/27/11
                                                                                          © 2011 INTERNATIONAL MASONRY INSTITUTE
WOOD BLOCKING FOR
  WINDOW ANCHORAGE                                      ALTERNATE
                                                        FLASHING
                                                        LOCATION

                                                        WINDOW STOOL
                                                        NOT SHOWN

  WINDOW ASSEMBLY




  FLASHING                                                             RIGID FLASHING TO SPAN
  END DAM                                                              ACROSS DRAINAGE CAVITY
                                                                       RIGID INSULATION

                                                                       HORIZONTAL JOINT
                                                                       REINFORCEMENT




             MASONRY EXPANSION
             JOINT AS REQUIRED

                     MASONRY SILL W/ 1/8” x
                     1/8” CONT. SAW-CUT DRIP




SILL DETAIL            MASONRY SILL, RIGID FLASHING
DETAIL 01.030.0401                      REV. 07/28/09
                                                                                 © 2011 INTERNATIONAL MASONRY INSTITUTE
WINDOW ASSEMBLY
                                                                                  WINDOW STOOL
          STONE OR PRECAST CONC.
          SILL W/ 1/8” W. x 1/8” H.
          CONT. SAW-CUT DRIP

          THRU-WALL FLASHING W/ 2”
          MIN. VERTICAL END DAMS,
          EA. END; SUPPORT FLASHING
          ACROSS CAVITY IF FLEXIBLE
          FLASHING IS USED




                                                            CUT BLOCK
                                                            INTERIOR FINISH
                                                            CAVITY INSUL.
                                                            2” AIR SPACE
                     KEY DETAIL                             RECOMMENDED; 1” AIR
                                                            SPACE MIN. REQ’D BY
                                                            CODE FOR VENEERS



SILL DETAIL           MASONRY SILL, RIGID FLASHING, INTERIOR VIEW
DETAIL 01.030.0402                                    REV. 08/21/09
                                                                                            © 2011 INTERNATIONAL MASONRY INSTITUTE
SELF SUPPORTING BRICK
                           RETURN AT JAMB
                           TOOTHED INTO OUTER
                           WYTHE TO FORM 4”
                           CANTILEVER




                           SILL NOT SHOWN




           EXTERIOR VIEW                    CAVITY VIEW




UNSUPPORTED BRICK RETURN AT JAMB
DETAIL 01.030.0501         REV. 10/20/08
                                                          © 2011 INTERNATIONAL MASONRY INSTITUTE
EXTERIOR VIEW                   INTERIOR VIEW




WINDOW JAMB & SILL DETAIL S
DETAIL 01.030.0502       REV. 02/19/08
                                                © 2011 INTERNATIONAL MASONRY INSTITUTE
HORIZONTAL JOINT
                                        INTERIOR FINISH   REINFORCEMENT W/
                                                          INTEGRAL WALL TIES
                                                          WINDOW STOOL




                                                                       BLOCKING


                                                                       WINDOW
                                                                       ASSEMBLY
       3D VIEW

                  2” AIR SPACE
                  RECOMMENDED;
                  1” MIN. REQ’D
                  FOR DRAINAGE
                  WALLS
                                                                         WINDOW
                                                                         SILL
               BRICK VENEER

               AIR/WATER/VAPOR                            FLASHING UNDER SILL
               BARRIER AS REQ’D                           W/ VERTICAL END DAM
                                                          @ BOTH ENDS OF SILL
               CONCRETE MASONRY
               BACKUP
               RIGID INSULATION




WINDOW JAMB DETAIL
DETAIL 01.030.0502.2D   REV. 02/19/08
                                                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
INTERIOR VIEW




       DETAIL FEATURES
       • LOOSE LINTEL AT BRICK
       • BOND BEAM AT BLOCK
       • LIGHT GAUGE SUPPORT              EXTERIOR VIEW
         ACROSS CAVITY




HEAD DETAIL             STEEL LINTEL & BOND BEAM
DETAIL 01.030.0601                    REV. 09/04/07
                                                                          © 2011 INTERNATIONAL MASONRY INSTITUTE
DETAIL FEATURES                  EXTERIOR VIEW   INTERIOR VIEW
         • LOOSE LINTEL AT BRICK
         • STEEL ANGLES AT BLOCK
         • LIGHT GAUGE SUPPORT
           ACROSS CAVITY




HEAD DETAIL            STEEL LINTEL W/ DOUBLE ANGLE
DETAIL 01.030.0603                       REV. 09/06/07
                                                                 © 2011 INTERNATIONAL MASONRY INSTITUTE
DETAIL FEATURES
• PLATE WELDED TO I-BEAM
• CUT BLOCK AROUND BEAM




HEAD DETAIL            PLATE WELDED TO STEEL BEAM
DETAIL 01.030.0604                     REV. 09/27/07
                                                       © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE
                                                           RECOMMENDED; 1”
                                  HORIZONTAL JOINT         MIN. REQ’D FOR
                                  REINFORCEMENT W/         DRAINAGE WALLS
                                  INTEGRAL WALL TIES
                                                           RIGID INSUL.
                                  THRU-WALL FLASHING W/
                                  METAL DRIP EDGE SET IN   ADJUSTABLE
                                  MASTIC OR SEALANT        SHELF ANGLE




     WEEP/VENT

                     TYPICAL FACE
     ADJUSTABLE      BRICK ABOVE &
     SHELF ANGLE     BELOW ANGLE
                     SEALANT & BACKER ROD
                     COMPRESSIBLE
                     FILLER, OPTIONAL




SHELF ANGLE DETAIL     TYP. FACE BRICK
DETAIL 01.030.0701         REV. 06/19/08
                                                                          © 2011 INTERNATIONAL MASONRY INSTITUTE
HORIZONTAL JOINT
      REINFORCEMENT W/
      INTEGRAL WALL TIES




  THRU-WALL FLASHING

   RIGID INSULATION




   ADJUSTABLE SHELF ANGLE

   WEEP VENT
   METAL DRIP EDGE SET IN
   MASTIC OR SEALANT


   SEALANT & BACKER ROD

   TYP. FACE BRICK ABOVE
   AND BELOW ANGLE


  COMPRESSIBLE FILLER,
  OPTIONAL
  2” AIR SPACE RECOMMENDED; 1”
  MIN. REQ’D FOR DRAINAGE WALLS


SHELF ANGLE DETAIL                TYP. FACE BRICK
DETAIL 01.030.0701.2D                 REV. 06/19/08
                                                      © 2011 INTERNATIONAL MASONRY INSTITUTE
HORIZONTAL JOINT              2” AIR SPACE
                         REINFORCEMENT W/              RECOMMENDED; 1”
                         INTEGRAL WALL TIES            MIN. REQ’D FOR
                                                       DRAINAGE WALLS
                              THRU-WALL FLASHING W/
                              METAL DRIP EDGE SET IN
                              MASTIC OR SEALANT
                                       RIGID INSUL.




    WEEP/VENT
         ADJUSTABLE.
         SHELF ANGLE
                       LIPPED BRICK,
                       OPTIONAL

                       SEALANT & BACKER ROD
                       COMPRESSIBLE
                       FILLER, OPTIONAL



SHELF ANGLE DETAIL     LIPPED BRICK
DETAIL 01.030.0702      REV. 10/14/07
                                                                 © 2011 INTERNATIONAL MASONRY INSTITUTE
HORIZONTAL JOINT
     REINFORCEMENT W/
     INTEGRAL WALL TIES

     RIGID INSULATION



     THRU-WALL FLASHING




     ADJUSTABLE SHELF ANGLE

     WEEP VENT
     METAL DRIP EDGE SET IN
     MASTIC OR SEALANT


     SEALANT & BACKER ROD
     LIPPED BRICK BELOW
     SHELF ANGLE


     COMPRESSIBLE FILLER,
     OPTIONAL

     2” AIR SPACE RECOMMENDED;
     1” MIN. REQ’D FOR DRAINAGE
     WALLS




SHELF ANGLE DETAIL                LIPPED BRICK
DETAIL 01.030.0702.2D               REV. 10/14/07
                                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
HORIZONTAL JOINT
                                         REINFORCEMENT W/
                                         INTEGRAL WALL TIES

                                         THRU-WALL FLASHING
                                         RIGID INSUL.

                                         MECH. FASTENED
                                         TERM. BAR

                                       ADJUSTABLE
                                       SHELF ANGLE




                                              WEEP VENT



       METAL DRIP
       EDGE SET IN
       MASTIC OR
       SEALANT


       2” AIR SPACE        TYP. FACE BRICK ABOVE
       RECOMMENDED;        AND BELOW ANGLE
       1” MIN. REQ’D FOR   SEALANT & BACKER ROD
       DRAINAGE WALLS
                           COMPRESSIBLE
                           FILLER, OPTIONAL




SHELF ANGLE DETAIL         TYP. FACE BRICK, TERM. BAR
DETAIL 01.030.0703                        REV. 06/19/08
                                                              © 2011 INTERNATIONAL MASONRY INSTITUTE
HORIZONTAL JOINT
  REINFORCEMENT W/
  INTEGRAL WALL TIES

  MECH. FASTENED
  TERMINATION BAR W/ CONT.
  BEAD OF SEALANT AT TOP

  THRU-WALL FLASHING

  RIGID INSULATION




  ADJUSTABLE SHELF ANGLE

  WEEP VENT
  METAL DRIP EDGE SET IN
  MASTIC OR SEALANT


  SEALANT & BACKER ROD

  TYP. FACE BRICK ABOVE
  AND BELOW ANGLE

  COMPRESSIBLE FILLER,
  OPTIONAL

  2” AIR SPACE RECOMMENDED;
  1” MIN. REQ’D FOR DRAINAGE
  WALLS

SHELF ANGLE DETAIL             TYP. FACE BRICK, TERM. BAR
DETAIL 01.030.0703.2D                        REV. 06/19/08
                                                             © 2011 INTERNATIONAL MASONRY INSTITUTE
CMU BACKUP

                     FACE BRICK                                               CAVITY INSUL.
                                                                              THRU-WALL
                                                                              FLASHING
                     ROOF MEMBRANE                                            CUT BLOCK
                                                                              BELOW FLASHING


                     COUNTER-
                     FLASHING
                     SHEET METAL
                     RECEIVER




                                                    THRU-WALL
                                                    FLASHING

                                                     WEEP
                                                     VENT




                                                    TERMINATION BAR
                                                    W/ CONT. SEALANT
                                                    ROOF STRUCTURE
                                                    HORIZONTAL JOINT REINF.
                                                    @ 16” O.C. W/ INTEGRAL
                                                    WALL TIES



ROOF DETAIL               HIGH WALL – LOW ROOF
DETAIL 01.030.0751                   REV. 11/6/07
                                                                                 © 2011 INTERNATIONAL MASONRY INSTITUTE
FACE BRICK


    THRU-WALL FLASHING

     WEEP VENT

     SHEET METAL RECEIVER


     COUNTERFLASHING
                                                 KEY DETAIL

    TERMINATION BAR
    W/ CONT. SEALANT

    CANT STRIP
    ROOF MEMBRANE




                                                   KEY SECTION




ROOF DETAIL            HIGH WALL – LOW ROOF
DETAIL 01.030.0751A               REV. 11/6/07
                                                     © 2011 INTERNATIONAL MASONRY INSTITUTE
MASONRY COPING: LIMESTONE, CAST
          STONE, CALCIUM SILICATE, OR                      S.S. DOWEL W/ SEALANT
          PRECAST CONCRETE; OVERHANG                       AROUND PENETRATIONS
          MASONRY WALL 1½” MIN.; SLOPED                    THROUGH FLASHING
          TOP
          1/8” SAW-CUT DRIP,
          BOTH SIDES OF
          WALL CAP                                         SEE DETAIL 01.759 FOR
                                                           WALL CAP JOINT OPTIONS

          SEALANT & BACKER
          ROD, BOTH SIDES                                  CANTED S.S. THRU-WALL
          OF WALL CAP                                      FLASHING W/ 1/2”
                                                           EXPOSED DRIP EDGE
          FACE BRICK
          SLOPED MORTAR
          BED TO SUPPORT
          CANTED FLASHING,                                 SEALANT BELOW DRIP,
          OPT.                                             OPT. (NOT SHOWN)

          RIGID INSULATION


          OPEN DRAINAGE
          CAVITY, OPTIONAL
          ABOVE ROOF LINE;
          ALSO SEE DETAIL                        GROUT & REINFORCING
          01.752                                 AS REQ’D.

                                                 HORIZONTAL JOINT
                                                 REINFORCEMENT
                                                 W/ WALL TIES




MASONRY WALL CAP                OPEN CAVITY
DETAIL 01.030.0801              REV. 011/04/08
                                                                       © 2011 INTERNATIONAL MASONRY INSTITUTE
MASONRY COPING: LIMESTONE, CAST
           STONE, CALCIUM SILICATE, OR
           PRECAST CONCRETE; OVERHANG                      S.S. DOWEL W/ SEALANT
           MASONRY WALL 1½” MIN.; SLOPED                   AROUND PENETRATIONS
           TOP                                             THROUGH FLASHING
           1/8” SAW-CUT DRIP,
           BOTH SIDES OF
           WALL CAP                                        SEE DETAIL 01.759 FOR
                                                           WALL CAP JOINT OPTIONS

           SEALANT & BACKER
           ROD, BOTH SIDES                                 THROUGH-WALL
           OF WALL CAP                                     FLASHING W/
                                                           1/2” DRIP EDGE
           GROUT OR MORTAR
           FILL FOR DOWEL
           ANCHORAGE AND
           FLASHING SUPPORT                                 SEALANT BELOW DRIP,
                                                            OPT. (NOT SHOWN)
           MESH TO RETAIN
           GROUT OR MORTAR
           FILL


           DRAINAGE CAVITY

                                                 GROUT & REINFORCING
           FACE BRICK                            AS REQ’D.

                                                 HORIZONTAL JOINT
           RIGID INSULATION                      REINFORCEMENT
                                                 W/ WALL TIES




MASONRY WALL CAP                FILLED CAVITY
DETAIL 01.030.0802              REV. 011/04/08
                                                                       © 2011 INTERNATIONAL MASONRY INSTITUTE
4” MIN. LAP JOINT W/ SEALANT
         FORMED METAL COPING
         ROOF MEMBRANE
         UNDER COPING
                                                    ROOF
         CONT. WOOD                                 MEMBRANE
         BLOCKING SLOPED
         1” PER FOOT, MIN.

         WOOD NAILER W/
         ANCHOR BOLTS



         BOND BEAM OR
         GROUT CORES                      SEALANT
         SOLID AT ANCHOR
         BOLTS


         CONT. CLEAT, BOTH
         SIDES W/ SLOTTED
         OR OVERSIZED
         HOLES @ 24” O.C.

         FACE BRICK




                     ROOF STRUCTURE




METAL COPING DETAIL
DETAIL 01.030.0803        REV. 11/20/07
                                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
FORMED METAL COPING                      ROOF MEMBRANE
                                                  UNDER COPING
        CONT. WOOD
        BLOCKING SLOPED
        1” PER FOOT, MIN.               CONT. CLEAT W/ SLOTTED OR
                                        OVERSIZED HOLES @ 24” O.C.
        CONT. CLEAT W/
        SLOTTED OR OVER-                SEALANT
        SIZED HOLES @ 24” O.C.          ROOF MEMBRANE
         WOOD NAILER W/                 CANT STRIP
         ANCHOR BOLTS

         SEALANT
        BOND BEAM OR
        GROUT CORES
        SOLID AT ANCHOR
        BOLTS

        FACE BRICK

        RIGID INSULATION

        CONCRETE MASONRY
        BACKUP TREATED W/
        AIR/ VAPOR/ MOISTURE
        BARRIER AS REQ’D




METAL COPING DETAIL
DETAIL 01.030.0803.2D   REV. 11/20/07
                                                            © 2011 INTERNATIONAL MASONRY INSTITUTE
OPTION 1                                      OPTION 2
                          RAKE BACK MORTAR AND                          SEALANT AND
                          APPLY SEALANT JOINT                           BACKER ROD




                                                 INCORRECT
                                                 TOOLED MORTAR JOINT




MASONRY COPING JOINTS
DETAIL 01.030.0811   REV. 11/04/08
                                                                       © 2011 INTERNATIONAL MASONRY INSTITUTE
MORTAR
                     WASH




ARCHITECTURAL EFFECT          PROJECTED COURSE
DETAIL 01.030.1001                  REV. 08/31/07
                                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
COLUMN DETAIL         AT INTERFACE WITH TUBE STEEL
DIAGRAM 01.030.1101                    REV. 07/31/09
                                                       © 2011 INTERNATIONAL MASONRY INSTITUTE
BEAM DETAIL          PLATE WELDED TO DEEP BEAM
DETAIL 01.030.1201                  REV. 03/02/09
                                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
HORIZONTAL JOINT
                                      REINFORCEMENT,
                                      DISCONTINUOUS AT
                                      MOVEMENT JOINT
                                      EXPANSION JOINT (EJ):
                                      SEALANT, BACKER                             CONTROL JOINT (CJ):
                                      ROD, & OPTIONAL                             PREFORMED
                                      COMPRESSIBLE FILLER                         GASKET, SEALANT,
                                      OF PRE- MOLDED FOAM                         & BACKER ROD
                                      OR NEOPRENE PAD

                                      CONTROL JOINT (CJ):
                                      PREFORMED GASKET,
                                      SEALANT, & BACKER ROD

                                      MOVEMENT JOINT (MJ):
                                      CONTROL JOINT AND/
                                      OR EXPANSION JOINT




    OPTION 1:                                                 OPTION 2:
    EJ & CJ ALIGNED                                           EJ & CJ OFFSET




MOVEMENT JOINT
DETAIL 01.030.1301    REV. 03/14/11
                                                                               © 2011 INTERNATIONAL MASONRY INSTITUTE
EXISTING WALL




                                                   ANCHOR TRANSFERS
                                                   TRANSVERSE LOADS AND ALLOWS
                                                   INDEPENDENT MOVEMENT OF
                                                   INTERSECTING WALLS




                                                       NEW WALL




                            SEALANT, BACKER ROD,
                            AND COMPRESSIBLE
                            FILLER




ISOLATION JOINT
DETAIL 01.030.1311     REV. 06/18/08
                                                                  © 2011 INTERNATIONAL MASONRY INSTITUTE
MASONRY EXPANSION JOINT
                                          ALIGNED W/ WINDOW JAMB;
                                          COMPRESSIBLE FILLER, BACKER
                                          ROD & SEALANT




                                                        FLASHING END DAM
                                                        RETURNED INTO HEAD JOINT

                                                        BACKER ROD OR COMPRESSIBLE
                                                        MATERIAL AT END OF LINTEL TO
                                                        AVOID RESTRAINT OF
     FLASHING SYSTEM                                    MOVEMENT, AND AT FRONT EDGE
     W/ DRIP EDGE                                       OF LINTEL TO PROVIDE BACKER
                                                        FOR SEALANT
     STRUCT. STEEL
     LINTEL




                                                        FLASHING MEMBRANE OR
                                                        PLASTIC BEARING PAD BENEATH
                                                        BEARING AREA OF ANGLE TO
                                                        CREATE SLIP PLANE


                                       WINDOW SYSTEM




EXPANSION JOINT         AT WINDOW
DETAIL 01.030.1321     REV. 08/09/09
                                                                        © 2011 INTERNATIONAL MASONRY INSTITUTE
RIGID INSULATION                                                           WATER-RESISTANT
                                                                             MEMBRANE
  2” AIR SPACE
  RECOMMENDED;                                                               METAL STUDS
  1” MIN. REQ’D FOR
  DRAINAGE WALLS                                                             5/8” EXTERIOR
                                                                             SHEATHING

  ADJUSTABLE WALL TIES
  @ 16” O.C. VERTICALLY
  AND 24” O.C.
  HORIZONTALLY




      BRICK VENEER
                                                                                 THRU-WALL FLASHING
                                                                                 8” VERTICAL MIN.,
                                                                                 ADHERED TO METAL
                                                                                 DRIP EDGE
           MECH. FASTENED
           TERMINATION BAR



               FOUNDATION




                          WEEP VENT

                            METAL DRIP EDGE SET
                            IN MASTIC OR SEALANT




BASE OF WALL DETAIL                 FLEX. FLASHING, DRIP EDGE, TERM. BAR
DETAIL 01.040.0301                                           REV. 11/06/07
                                                                                       © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
 1” MIN. REQ’D FOR DRAINAGE
 WALLS

 METAL STUDS
 5/8” EXTERIOR SHEATHING
 ADJUSTABLE WALL TIES @
 16” O.C. VERTICALLY AND
 24” O.C. HORIZONTALLY
 WATER-RESISTANT MEMBRANE

 RIGID INSULATION

 BRICK VENEER

 MECH. FASTENED TERM. BAR

                                                                       KEY DETAIL
                                                                       SEE 02.101
 THRU-WALL FLASHING 8”
 VERTICAL MIN., ADHERED
 TO METAL DRIP EDGE
 WEEP VENT

 METAL DRIP EDGE SET
 IN MASTIC OR SEALANT

 FOUNDATION




BASE OF WALL DETAIL           FLEX. FLASHING, DRIP EDGE, TERM. BAR
DETAIL 01.040.0301.2D                                  REV. 11/13/07
                                                                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
RIGID INSULATION                                                                 WATER-RESISTANT
                                                                                   MEMBRANE
  2” AIR SPACE
  RECOMMENDED;                                                                     METAL STUDS
  1” MIN. REQ’D FOR
  DRAINAGE WALLS                                                                   5/8” EXTERIOR
                                                                                   SHEATHING

  ADJUSTABLE WALL TIES
  @ 16” O.C. VERTICALLY
  AND 24” O.C.
  HORIZONTALLY                                                                        CAVITY INSERT/ MORTAR
                                                                                      COLLECTION DEVICE


                                                                                       MECH. FASTENED
      BRICK VENEER                                                                     TERMINATION BAR

                                                                                       THRU-WALL FLASHING
                                                                                       8” VERTICAL MIN.,
                                                                                       ADHERED TO METAL
                                                                                       DRIP EDGE




               FOUNDATION




                          WEEP VENT

                            METAL DRIP EDGE SET
                            IN MASTIC OR SEALANT




BASE OF WALL DETAIL                 FLEX. FLASHING, DRIP EDGE, TERM. BAR, MDCD
DETAIL 01.040.0302                                                 REV. 11/13/07
                                                                                             © 2011 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
 1” MIN. REQ’D FOR DRAINAGE
 WALLS

 METAL STUDS
 5/8” EXTERIOR SHEATHING
 ADJUSTABLE WALL TIES @
 16” O.C. VERTICALLY AND
 24” O.C. HORIZONTALLY

 WATER-RESISTANT MEMBRANE

 MECH. FASTENED TERM. BAR
 BRICK VENEER

 RIGID INSULATION

 CAVITY INSERT/ MORTAR
 COLLECTION DEVICE                                                  KEY DETAIL
                                                                    SEE 02.102
 THRU-WALL FLASHING 8”
 VERTICAL MIN., ADHERED
 TO METAL DRIP EDGE
 WEEP VENT
 METAL DRIP EDGE SET
 IN MASTIC OR SEALANT

 FOUNDATION




BASE OF WALL DETAIL           FLEX. FLASHING, DRIP EDGE, TERM. BAR, MDCD
DETAIL 01.040.0302.2D                                        REV. 11/13/07
                                                                                 © 2011 INTERNATIONAL MASONRY INSTITUTE
DETAIL FEATURES
• BELOW GRADE BRICK
• GROUT SUPPORTS FLASHING
  BELOW GRADE
• TERMINATION BAR
• CAVITY INSERT
• ADJUSTABLE VENEER TIES
• AIR BARRIER



BASE OF WALL DETAIL         BRICK LEDGE, T/ FOUNDATION BELOW GRADE
DETAIL 01.040.0311                                        REV. 09/27/07
                                                                          © 2011 INTERNATIONAL MASONRY INSTITUTE
DETAIL FEATURES
• 2-PART FLASHING
• ADJUSTABLE VENEER TIES
• AIR INFILTRATION BARRIER
  (HOUSEWRAP)



SILL DETAIL
DETAIL 01.040.0401           REV. 08/31/07
                                             © 2011 INTERNATIONAL MASONRY INSTITUTE
INTERIOR VIEW




                                         EXTERIOR VIEW
 DETAIL FEATURES
 • NO RETURN AT CAVITY


WINDOW JAMB DETAIL
DETAIL 01.040.0501       REV. 09/16/07
                                                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
WATER RESISTANT BARRIER
                     (HOUSEWRAP) MUST BE USED
                     IF SHEATHING IS NOT WATER
                     RESISTANT AND JOINTS IN
                     SHEATHING ARE NOT TAPED AND
                     SEALED. LAP WATER RESISTANT
                     BARRIER OVER TOP OF FLASHING




                                        WOOD STUDS


                                        RIGID
                                        INSULATION
                                        SHEATHING

                                        WATER RESISTANT
                                        BARRIER
                                                                                               PLAN
                                        ADJUSTABLE VENEER
                                        ANCHORS FASTENED
                                        THROUGH INSULATION
                                        & SHEATHING TO STUDS
                                        2” AIR SPACE RECOMMENDED;
                                        1” REQ’D FOR DRAINAGE WALLS
      BACKING SYSTEM                    FLASHING W/ TERMINATION BAR



BASE OF WALL DETAIL         FLEX. FLASHING, TERM. BAR
DETAIL 01.050.0301                       REV. 02/14/07
                                                                      © 2011 INTERNATIONAL MASONRY INSTITUTE
BASE OF WALL         ADHERED VENEER OVER CMU, NO DRAINAGE MAT
DETAIL 01.070.0301                                REV. 12/10/09
                                                                  © 2011 INTERNATIONAL MASONRY INSTITUTE
BASE OF WALL         ADHERED VENEER OVER CMU, DRAINAGE MAT
DETAIL 01.070.0302                             REV. 12/10/09
                                                               © 2011 INTERNATIONAL MASONRY INSTITUTE
5”± WIDE FILLER STRIP
                                                              AT CORNERS
    4’-0” x 4’-0” METAL STUD/                                 CMU BACKUP W/ AIR
    GLASS MAT REINFORCED                                      BARRIER BY DCTC
    GYPSUM BACKUP                                             INSTRUCTORS
    CONSTRUCTED ON SITE
    BY S.S. SCHWARZ
    MASONRY ON MAY 19,
    2010




   15# BUILDING FELT                                                                               AREA OF PANEL
                                                                                                   INSTALLATION
                                                                                                   DEMONSTRATION

   TYVEK WRB



   KEENE DRAINAGE
   MAT AT METAL STUD
   PORTION ONLY




   DEMONSTRATE GROUTING                                                                          STARTER
   JOINTS W/ SPECMIX                                                                             CHANNEL AT
   POLYMER MODIFIED                                                                              BASE COURSE
   MORTAR APPLIED USING
   GROUT BAG                                                                      ENGINEERED THIN BRICK
                                                                                  PANEL SYSTEM MECH.
                                                                                  FASTENED TO CMU
   NOTE: ALL COMPONENTS OF ENGINEERED                                             BACKUP
   THIN BRICK SYSTEM INCLUDING BRICK
   PANELS, FILLER STRIPS, STARTER
   CHANNEL, BUILDING FELT, DRAINAGE MAT,
   GROUT AND BAKER BAGS TO BE PROVIDED
   BY S.S. SCHWARZ MASONRY; DCTC TO
   PROVIDE TYVEK.


THIN BRICK MOCKUP                 PREFAB. BRICK PANELS, CMU & STEEL STUD BACKUPS
DETAIL 01.070.2101                                                     REV. 5/11/10
                                                                                            © 2010 INTERNATIONAL MASONRY INSTITUTE
STONE CAP IN MORTAR
                                                  SETTING BED

                                                        LEVEL SCRATCH COAT
                                                        AT TOP OF WALL
                                                              LATH OVER TOP OF WALL;
                                                              LAP OVER WALL LATH 4” MIN.
  TYPE S MORTAR
  SCRATCH COAT                                                           SELF-ADHERING FLASHING
                                                                         OVER TOP OF WALL
                                                                         CONSTRUCTION; LAP OVER
                                                                         WATER RESISTANT BARRIER
                                                                                 SLOPING SOLID SHIM,
                                                                                 E.G. BEVELED SIDING
  TYPE S MORTAR
  SETTING BED




  ADHERED VENEER



                                                                                 EXTERIOR GYPSUM
                                                                                 SHEATHING


                                                                                  METAL STUD
                          METAL LATH                                              FRAMING


                           WATER RESISTANT
                           BARRIER



TOP OF WALL          SHEATHING & METAL STUDS
DETAIL 01.080.0801                REV. 05/13/08
                                                                                     © 2011 INTERNATIONAL MASONRY INSTITUTE
INTERIOR FINISH


                                                                       WOOD FRAMING
  DOUBLE LAP WATER
  RESISTANT BARRIER                                                    INSULATION
  AROUND CORNER 16”
  MIN.
                                                                       EXTERIOR GYPSUM
                                                                       SHEATHING



                                                                       WATER RESISTANT
  DOUBLE LAP LATH                                                      BARRIER, 2 LAYERS
  AROUND CORNER                                                        RECOMMENDED
  TO FRAMING,
  16” MIN.                                                             METAL LATH


                                                                       MORTAR SCRATCH
                                                                       COAT

                                                                       MORTAR SETTING
                                                                       BED




   ADHERED VENEER




CORNER DETAIL         GYP. SHEATHING & WOOD STUDS, OUTSIDE CORNER
DETAIL 01.090.1501                                     REV. 05/27/08
                                                                              © 2011 INTERNATIONAL MASONRY INSTITUTE
CHIMNEY

     CLAY FLUE                       FIRESTOP INSUL., 2” MIN.
     LINER
     BRICK INFILL

     PARGE BRICK AT
     SMOKE CHAMBER
                                     MANTEL SHELF
     DAMPER                          STEEL ANGLE TO
                                     SUPPORT CORBELED
     SMOKE CHAMBER                   BRICK INFILL ABOVE


     SMOKE SHELF                      FACE

     FIREBACK                         FIREPLACE OPENING

     FIRESTOP INSUL                   LINTEL

                                        RAISED HEARTH
     FIREBOX


     FRESH AIR
     INTAKE


     ASH PIT


     FOUNDATION




FIREPLACE DETAIL
DETAIL 01.160.0101   REV. 01/18/11
                                                          © 2011 INTERNATIONAL MASONRY INSTITUTE
SPARK ARRESTOR
              FORMWORK, TO BE        SEALANT
              REMOVED
                                      CAST IN PLACE
                                      REINFORCED
              CEMENTITIOUS            CONCRETE
              BACKER UNIT             CHIMNEY CAP

              ½” INSULATION FOR
              BOND BREAK

              CLAY FLUE LINER
              SET IN FIRECLAY
              MORTAR                  CONT. FLASHING
                                      UNDER CAP


                                      BRICK OR CMU INFILL
        ROOFING MATERIAL
        MAY VARY


                                      BABY TINS.
                                      COUNTERFLASHING
                                      NOT SHOWN




CHIMNEY DETAIL
DETAIL 01.160.0201   REV. 01/18/11
                                                © 2011 INTERNATIONAL MASONRY INSTITUTE
#4 REBAR, MIN.
                                              FLOOR FRAMING

                                              2” MIN. CLEARANCE TO
                                              COMBUSTIBLES, OR
                                              PER CODE




   4” MIN.




                                                                         PLYWOOD &
                                                                         COMBUSTIBLE
                                                                         FORMWORK MUST
                                                                         BE REMOVED


                                                                CEMENTITIOUS BACKER
                                                                UNIT OR OTHER
                                                                NONCOMBUSTIBLE
                                                                FORMWORK

                                     CMU OR CONCRETE
                                     FOUNDATION
                                     HEARTH SLAB
                                     SUPPORT WALL




HEARTH SUPPORT SLAB
DETAIL 01.160.0301   REV. 01/18/10
                                                                                      © 2011 INTERNATIONAL MASONRY INSTITUTE
RIGID INSUL.


                                             8” CMU BACKUP
                                             W/ BITUMINOUS
                                             DAMPPROOF
                                             COATING

                                             MODULAR FACE
                                             BRICK
5’-4”




                                             S.S. FLASHING &
                                             RECEIVER




                                             WEEP VENTS
                                             @ 24” O.C.        5


                                     6’-0”
                                                                   SECTION
                                                               3
                                                                   NOT TO SCALE
            ELEVATION
        2
            NOT TO SCALE



MOCKUP #01
SHEET 01.210.0102    REV. 01/28/08
                                                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
HORIZONTAL JOINT
                                      REINFORCEMENT W/ EYE &
                                      PINTLE WALL TIES @ 16” O.C.
                                                                                       16”
                                                 MODULAR FACE BRICK
                                                 2” THICK RIGID INSUL.    3 5/8” 2¾”   2”       7 5/8”


                                                     8” CMU BACKUP
                                                     W/ BITUMINOUS
                                                     DAMPPROOF
                                                     COATING


                                                         3” x 3” 28 GA.
                                                         S.S. RECEIVER
                                                         EMBEDDED
                                                         INTO CMU
                                                         BACKUP



                                                        WEEP VENTS
                                                        @ 24” O.C.




                                                 8” L. x 6½” H. 28 GA.
      3D VIEW                                    S.S. FLASHING ON
  4                                              SLOPED MORTAR BED
      NOT TO SCALE                                                                              DETAIL
                                                                                            5
                                                                                                NOT TO SCALE
                                                 ½” 45° HEMMED
                                                 DRIP EDGE



MOCKUP #01           BASE DETAIL
SHEET 01.210.0103     REV. 01/28/08
                                                                                                © 2011 INTERNATIONAL MASONRY INSTITUTE
8” CMU BACKUP W/
                                             BITUMINOUS
                                             DAMPPROOF COATING

                                             RIGID INSULATION

                                                            HOR. JOINT REINF./
                                                            WALL TIES


                                                            MODULAR
                                                            FACE BRICK

                                                            S.S. TERM. BAR

                                                            10” H. CAVITY
4’-8”




                                                            INSERT
                                                            SELF-ADHERING
                                                            RUBBERIZED
                                                            ASPHALT
                                                            FLASHING



                                                            S.S. DRIP

                                                            WEEP VENTS       5
                                                            @ 24” O.C.


                                     6’-0”
                                                                                 SECTION
                                                                             3
                                                                                 NOT TO SCALE
            ELEVATION
        2
            NOT TO SCALE



MOCKUP #02
SHEET 01.210.0202    REV. 01/30/08
                                                                                  © 2011 INTERNATIONAL MASONRY INSTITUTE
HORIZONTAL JOINT
                                      REINFORCEMENT W/ EYE &
                                      PINTLE WALL TIES @ 16” O.C.
                                                                                        16”
                                                 MODULAR FACE BRICK
                                                 2” THICK RIGID INSUL.     3 5/8” 2¾”   2”       7 5/8”


                                                     ¾” S.S.
                                                     TERMINATION
                                                     BAR W/ CONT.
                                                     SEALANT @ TOP
                                                       2” THICK x 10” H.
                                                       CAVITY INSERT




                                                         8” CMU
                                                         BACKUP W/
                                                         BITUMINOUS
                                                         DAMPPROOF
                                                         COATING



                                                 WEEP VENTS
                                                 @ 24” O.C.
                                                 40 MIL SELF-ADHERING
      3D VIEW                                    RUBBERIZED ASPHALT
  4                                              FLASHING ON SLOPED
      NOT TO SCALE                                                                               DETAIL
                                                 MORTAR BED                                  5
                                                                                                 NOT TO SCALE
                                                 3” WIDE S.S. W/ 45°
                                                 HEMMED DRIP EDGE
                                                 PROJECTING ½” FROM
                                                 FACE OF BRICK, SET IN
                                                 MASTIC (OPT.) ON
                                                 SLOPED MORTAR BED
MOCKUP #02           BASE DETAIL
SHEET 01.210.0203     REV. 01/30/08
                                                                                                 © 2011 INTERNATIONAL MASONRY INSTITUTE
RIGID INSULATION
                                             8” CMU BACKUP W/
                                             BITUMINOUS
                                             DAMPPROOF COATING

                                                        HOR. JOINT REINF.W/
                                                        WALL TIES @ THIRD
                                                        BLOCK COURSE; NO
                                                        WALL TIES @ BASE
                                                        COURSE REINF.

                                                            MODULAR
                                                            FACE BRICK

                                                            10” H. CAVITY
4’-8”




                                                            INSERT



                                                            5 OZ. COPPER
                                                            FLASHING




                                                            WEEP VENTS        5
                                                            @ 24” O.C.


                                     6’-0”
                                                                                  SECTION
                                                                              3
                                                                                  NOT TO SCALE
            ELEVATION
        2
            NOT TO SCALE



MOCKUP #03
SHEET 01.210.0302    REV. 02/05/08
                                                                                   © 2011 INTERNATIONAL MASONRY INSTITUTE
2” THICK RIGID INSUL.
                                                                              16”
                                       MODULAR FACE BRICK
                                                                 3 5/8” 2¾”   2”       7 5/8”

                                           8” CMU BACKUP
                                           W/ BITUMINOUS
                                           DAMPPROOF
                                           COATING


                                             2” THICK x 10” H.
                                             CAVITY INSERT




                                               HOR. JOINT
                                               REINF. W/OUT
                                               WALL TIES @
                                               BASE COURSE




                                       WEEP VENTS
                                       @ 24” O.C.

      3D VIEW                         5 OZ. COPPER FLASHING
  4                                   ON SLOPED MORTAR BED,
      NOT TO SCALE                                                                     DETAIL
                                      EMBEDDED INTO CMU                            5
                                      BACKUP                                           NOT TO SCALE




MOCKUP #03           BASE DETAIL
SHEET 01.210.0303     REV. 02/05/08
                                                                                       © 2011 INTERNATIONAL MASONRY INSTITUTE
3D OVERVIEW
                                    1
                                        NOT TO SCALE



MOCKUP #04
SHEET 01.210.0401   REV. 02/19/08
                                                       © 2011 INTERNATIONAL MASONRY INSTITUTE
3 5/8” 2¾” 2”   7 5/8””

                                     1” S.S. TERM. BAR W/
                                     CONT. SEALANT
                                     40 MIL SELF-ADHERING
                                     RUBBERIZED ASPHALT                                   2” RIGID INSUL.
                                     FLASHING
                                     3½” x 3½” x 3/16”
                                     STEEL ANGLE W/ 4”
                                     BEARING EA. END

                                     WEEP VENTS @ 24” O.C.
          4
                                     ½” 45° S.S. HEMMED                                  (2) 3½” x 3½” x 3/16”
                                     DRIP EDGE, 3” WIDE                                  STEEL ANGLES, 8”
                                                                 HEAD DETAIL             BEARING EA. END
  5’-4”




                                                             4
                                                                 NOT TO SCALE
                                     40 MIL SELF-ADHERING
                                     RUBBERIZED ASPHALT
                                     FLASHING

                                     SLOPE BRICK
                                     ROWLOCK SILL 15º
                                     COTTON SASH CORD                                     HALF-HIGH
          5                          ROPE WICK @ 16” O.C.                                 BLOCK AT SILL
                                     26 GA. STAINLESS
                                     STEEL EXTENDING
                                     INTO CMU BACKUP TO
                                     SUPPORT THRU-WALL
                                     FLASHING ACROSS AIR
                                     SPACE; ½” 45° HEMMED
                                     DRIP EDGE


              SECTION                                            SILL DETAIL
          3                                                  5
              NOT TO SCALE                                       NOT TO SCALE

MOCKUP #04
SHEET 01.210.0403    REV. 02/19/08
                                                                                       © 2011 INTERNATIONAL MASONRY INSTITUTE
40 MIL SELF-ADHERING RUBBERIZED
                                      ASPHALT THRU-WALL FLASHING
           2” VERTICAL END DAM,       26 GA. STAINLESS STEEL
           FIELD FORMED WITH          EXTENDING INTO CMU BACKUP
           RUBBERIZED ASPHALT         TO SUPPORT THRU-WALL
           FLASHING                   FLASHING ACROSS AIR SPACE;
                                      ½” 45° HEMMED DRIP EDGE




                                      COTTON SASH CORD
     SILL DETAIL                      ROPE WICK @ 16” O.C.                  SILL DETAIL
 6                                                                      7
     NOT TO SCALE                                                           NOT TO SCALE
                                      SLOPE BRICK
                                      ROWLOCK SILL 15º




MOCKUP #04          SILL DETAILS
SHEET 01.210.0404     REV. 02/19/08
                                                                            © 2011 INTERNATIONAL MASONRY INSTITUTE
RIGID INSULATION

                                                          HORIZONTAL JOINT
                                                          REINFORCEMENT W/ EYE &
                                                          PINTLE WALL TIES @ 16” O.C.
                                                          ¾” S.S. TERMINATION
                                                          BAR W/ CONT.
                                                          SEALANT @ TOP

                                                          40 MIL SELF-ADHERING
                                                          RUBBERIZED ASPHALT
                                                          THRU-WALL FLASHING

                                                                  3½” x 3½” x 3/16”
  WEEP VENTS                                                      STEEL ANGLE W/ 4”
  @ 24” O.C.                                                      BEARING EA. END


  MODULAR                                                     (2) 3½” x 3½” x 3/16”
  FACE BRICK                                                  STEEL ANGLES, 8”
                                                              BEARING EA. END
                                                                      RETURN FACE
  26 GA. STAINLESS                                                    BRICK AT JAMBS
  STEEL ½”, 45°
  HEMMED DRIP EDGE




                                HEAD DETAIL     2” VERTICAL END DAM,
                            8                   FIELD FORMED WITH
                                NOT TO SCALE    RUBBERIZED ASPHALT
                                                FLASHING

MOCKUP #04          HEAD DETAIL
SHEET 01.210.0405    REV. 02/19/08
                                                                          © 2011 INTERNATIONAL MASONRY INSTITUTE
MOCKUP #05
SHEET 01.210.0501   REV. 10/09/08
                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
MOCKUP #05
SHEET 01.210.0502   REV. 10/09/08
                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
MOCKUP #05
SHEET 01.210.0503   REV. 10/09/08
                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
MOCKUP #05
SHEET 01.210.0504   REV. 10/09/08
                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
MOCKUP #05
SHEET 01.210.0505   REV. 10/09/08
                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
MOCKUP #05
SHEET 01.210.0506   REV. 10/09/08
                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
MOCKUP #05
SHEET 01.210.0507   REV. 10/09/08
                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
MOCKUP #05
SHEET 01.210.0509   REV. 10/09/08
                                    © 2011 INTERNATIONAL MASONRY INSTITUTE
FULL HEAD JOINTS
DIAGRAM 01.410.0101   REV. 07/29/09
                                      © 2011 INTERNATIONAL MASONRY INSTITUTE
NOTE:
                                                                       STRUCTURAL ELEMENTS
                                                                       MAY VARY, AND ARE SHOWN
                                                                       FOR ILLUSTRATION ONLY


                                                                       CAVITY INSULATION NOT
                                                                       SHOWN FOR CLARITY OF
                                                                       DETAIL



                                                                       CARRY FLASHING ½” MIN.
                                                                       BEYOND END OF LINTEL
                                                                       AND TURN UP TO FORM
                                                                       END DAM IN HEAD JOINT



                                                                     2” RECOMMENDED;
                                                                     1” MIN.




                      SEALANT                            EXTEND FLASHING
                                                         FLUSH OR BEYOND
                                                         FACE OF MASONRY




END DAM DIAGRAM                 FIELD-FORMED FLASHING END DAM
DIAGRAM 01.410.0201                                REV. 02/04/11
                                                                                        © 2011 INTERNATIONAL MASONRY INSTITUTE
NOTE:
                                                                            STRUCTURAL ELEMENTS
                                                                            MAY VARY, AND ARE SHOWN
                                                                            FOR ILLUSTRATION ONLY
                                                                            CAVITY INSULATION NOT
                                                                            SHOWN FOR CLARITY OF
                                                                            DETAIL



                                                                            CARRY FLASHING ½” MIN.
                                                                            BEYOND END OF LINTEL
                                                                                 PREFABRICATED END DAM
                                                                                 IN HEAD JOINT; SET IN
                                                                                 MASTIC IF FLASHING IS NOT
                                                                                 SELF-ADHERING. END DAM
                                                                                 PLACED PRIOR TO
                                                                                 THROUGH-WALL FLASHING


                                                                                      2” RECOMMENDED;
                                                                                      1” MIN.



                                                          EXTEND FLASHING
                      SEALANT                             FLUSH OR BEYOND
                                                          FACE OF MASONRY




END DAM DIAGRAM                 PREFABRICATED FLASHING END DAM
DIAGRAM 01.410.0202                                 REV. 02/04/11
                                                                                            © 2011 INTERNATIONAL MASONRY INSTITUTE
1/2”



                                                   1/8”                                        3/4”



                                                          ALLOWABLE   SOURCE: BUILDING CODE
                                         JOINT            TOLERANCE   REQUIREMENTS FOR MASONRY
                                                                      STRUCTURES (ACI 530-05/ASCE 5-
                                         BED JOINT    ±1/8”           05/TMS 402-05) REPORTED BY THE
                                  1/4”   HEAD JOINT   -1/4”, +3/8”    MASONRY STANDARDS JOINT
                                         COLLAR JOINT -1/4”, +3/8”    COMMITTEE (MSJC)




                                                                                     AREA OF DETAIL




                                  3/8”




                  3/8”                                                ELEVATION

MORTAR JOINT TOLERANCES
DIAGRAM 01.410.0301      REV. 08/06/09
                                                                                      © 2011 INTERNATIONAL MASONRY INSTITUTE
MAX. PERMISSIBLE
                DISTORTION PER ASTM
                TABLE




FACE BRICK – ALLOWABLE DISTORTION
DIAGRAM 01.410.0401                   REV. 11/04/08
                                                      © 2011 INTERNATIONAL MASONRY INSTITUTE
I
                              C
                          D
                              L   D



                                              H = WALL HEIGHT
                                              D = ALLOWABLE
                                                  VARIATION FROM
                                                  PLUMB AT ANY POINT

                                             WHEN H < 10’-0”
                                                  D < 1/4“

                                             WHEN H < 20’-0”
                                                  D < 3/8“

                      H                      WHEN H > 20’-0”
                                                  D < 1/2“




ALLOWABLE VARIATIONS OF MASONRY       OUT-OF-PLUMB
DIAGRAM 01.410.1411                    REV. 08/24//09
                                                                © 2011 INTERNATIONAL MASONRY INSTITUTE
L


                                                  d
                                                                                                     I
                                                                                                     C
                                                                                                     L
                                                  d




                      L = LENGTH OF WALL              WHEN L < 10’-0”
                                                           d < 1/4“
                      d = ALLOWABLE
                          VARIATION FROM
                          PLAN AT ANY POINT           WHEN L < 20’-0”
                                                           d < 3/8“

                                                      WHEN L > 20’-0”
                                                           d < 1/2“




ALLOWABLE VARIATIONS OF MASONRY                          OUT-OF-LINE
DIAGRAM 01.410.1412                                     REV. 08/24//09
                                                                         © 2011 INTERNATIONAL MASONRY INSTITUTE
≥20’-0”

                                  I
                                  C
                                  L


                        ≤10’-0”
       1/4”




                                                                                 1/2”
1/2”




                                                                        1/4”
ALLOWABLE VARIATIONS OF MASONRY       OUT-OF-LEVEL
DIAGRAM 01.410.1413                    REV. 08/24//09
                                                        © 2011 INTERNATIONAL MASONRY INSTITUTE
18.00% MORTAR                             12.21% MORTAR




                      ONE SQUARE FOOT                         ONE SQUARE FOOT
                      MODULAR BRICK, RUNNING BOND             UTILITY BRICK, RUNNING BOND

      BED JOINTS  4 @ 12” x 3/8” =    18.000 SQ. IN.
      HEAD JOINTS 8 @ 2.3125” x 3/8” = 6.938 SQ. IN.          3 @ 12” x 3/8” =   13.500 SQ. IN.
                  2 @ 1.3125” x 3/8” = 0.984 SQ. IN.          3 @ 3.625” x 3/8” = 4.078 SQ. IN.

                                      25.922 SQ. IN. MORTAR                     17.578 SQ. IN. MORTAR




ELEVATIONS             MORTAR JOINT MATERIAL TAKEOFF
DIAGRAM 01.410.0311                      REV. 08/10/09
                                                                                                  © 2011 INTERNATIONAL MASONRY INSTITUTE
WHEN WINDOWS ARE
                                                SPACED CLOSE
                                                TOGETHER, LOCATE
                                                VERTICAL EXPANSION
                                                JOINTS AT WINDOW
                                                JAMBS




                                                WHEN WINDOWS ARE
                                                SPACED FAR APART,
                                                LOCATE VERTICAL
                                                EXPANSION JOINTS
                                                BETWEEN WINDOWS




ELEVATIONS            MOVEMENT JOINT LAYOUT
DIAGRAM 01.410.1311             REV. 08/10/09
                                                  © 2011 INTERNATIONAL MASONRY INSTITUTE
80’-0”




                                                                                   20’-0”
                                                            1/2”            1/2”
                      2¼”        1¼”   1”    1”




                            STEEL      CONCRETE                    BRICK
                            (AISC)       (ACI)                     (MSJC)




ALLOWABLE CONSTRUCTION TOLERANCES
DIAGRAM 01.410.1401                         REV. 08/21/09
                                                                                            © 2011 INTERNATIONAL MASONRY INSTITUTE
Concrete Block
                            010   Single Wythe
                            020   Composite
                            030   Anchored Veneer - Masonry Backup
                            040   Anchored Veneer - Steel Stud Backup
01   Brick                  050   Anchored Veneer - Wood Stud Backup
02   Concrete block         060   Anchored Veneer - Other Backup
03   Stone, rough           070   Adhered Veneer - Masonry Backup
04   Stone, dimensional     080   Adhered Veneer - Steel Stud Backup
06   Tile                   090   Adhered Veneer - Wood Stud Backup
07   Terrazzo               100   Adhered Veneer - Other Backup
08   Cement                 110   Rain Screen Wall
09   Plaster / Stucco       120   Structural Masonry
10   Restoration            130   Flooring - Interior
11   Terra Cotta            140   Paving - Exterior
12   Refractory             150   Landscape Walls
13   AAC                    160   Fireplaces & Chimneys
14   Precast Concrete       210   Training Mockups
15   Accessories            220   Apprentice Contests
21   Structural Steel       310   Building Models
22   Cast-in-Place Conc.    400   Wall Type Analysis
23   Metal Siding           410   Diagrams
40   Wall Type Analysis     510   Modular/Bonding
50   Building Model         610   Sustainability / Energy-Efficiency
VERTICAL REINFORCEMENT
         AS REQ’D




         HORIZONTAL JOINT
         REINFORCEMENT




         GROUT AS REQ’D



         DOWELS MAY BE BENT
         UP TO 1” LATERALLY
         PER 6” VERTICALLY


         CMU SHOWN IN
         LONGITUDINAL
         SECTION



         FOUNDATION




FOUNDATION DOWEL ALIGNMENT
DETAIL 02.010.0301                REV. 02/22/09
                                                  © 2011 INTERNATIONAL MASONRY INSTITUTE
GROUT & VERTICAL
                                                             REINFORCEMENT AS REQ’D




                                                                    HORIZONTAL JOINT
                                                                    REINFORCEMENT
      SINGLE WYTHE
      CONCRETE
      MASONRY
                                                                              NOTE: STRUCTURAL
                                                                              ELEMENTS MAY VARY
                                                                              AND ARE SHOWN FOR
                                                                              ILLUSTRATION ONLY




                 TWO WYTHES OF CMU
                 AT BASE COURSE



                           CUT FLASHING AROUND
                           CELLS TO BE GROUTED

                                           FOUNDATION




BASE OF WALL           SINGLE WYTHE BLOCK, SPLIT BASE COURSE
DETAIL 02.010.0311                                 REV. 06/30/11
                                                                                       © 2011 INTERNATIONAL MASONRY INSTITUTE
GROUT & VERTICAL
                                                       REINFORCEMENT AS REQ’D



                                                                     INTERIOR FINISH
                                                                     MAY VARY




                                                                            HORIZONTAL JOINT
                                                                            REINFORCEMENT


                                                                                NOTE: STRUCTURAL
                                                                                ELEMENTS MAY VARY
                                                                                AND ARE SHOWN FOR
                                                                                ILLUSTRATION ONLY
     SINGLE WYTHE
     CONCRETE MASONRY
                                                                                TERMINATION BAR
          SEAL AROUND DOWEL
          PENETRATION (SEALANT
          NOT SHOWN FOR CLARITY)

                        FLASHING


                             FOUNDATION




BASE OF WALL          SINGLE WYTHE BLOCK, FLASHING @ INSIDE FACE
DETAIL 02.010.0312                                   REV. 06/30/11
                                                                                       © 2011 INTERNATIONAL MASONRY INSTITUTE
GROUT & VERTICAL
                                                            REINFORCEMENT AS REQ’D




                                                                HORIZONTAL JOINT
                                                                REINFORCEMENT



                                                                     NOTE: STRUCTURAL
                                                                     ELEMENTS MAY VARY
                                                                     AND ARE SHOWN FOR
                                                                     ILLUSTRATION ONLY



            SINGLE WYTHE                                               PROPRIETARY
            CONCRETE                                                   MESH INSERT
            MASONRY


                                                                            FOUNDATION




                     PROPRIETARY SINGLE WYTHE
                     BLOCK FLASHING/ WEEP SYSTEM




BASE OF WALL            SINGLE WYTHE BLOCK, PROPRIETARY FLASHING/WEEPS
DETAIL 02.010.0313                                          REV. 06/30/11
                                                                                     © 2011 INTERNATIONAL MASONRY INSTITUTE
GROUT & VERTICAL
                                                     REINFORCEMENT AS REQ’D


                                                          NOTE: STRUCTURAL
                                                          ELEMENTS MAY VARY
        HORIZONTAL JOINT                                  AND ARE SHOWN FOR
        REINFORCEMENT                                     ILLUSTRATION ONLY




                                                             WINDOW SYSTEM




                     FLASHING
                     END DAM
                                                               SILL




                                FLASHING

                                  SINGLE WYTHE
                                  CONCRETE MASONRY




SILL DETAIL          SINGLE WYTHE BLOCK
DETAIL 02.010.0401           REV. 06/30/11
                                                                              © 2011 INTERNATIONAL MASONRY INSTITUTE
FLOOR CONNECTION DETAIL
DETAIL 02.010.0701   REV. 08/31/07
                                     © 2011 INTERNATIONAL MASONRY INSTITUTE
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4
Masonry Detailing Series v.3.4

Más contenido relacionado

La actualidad más candente

Causes and prevention of cracks in buildings
Causes and prevention of cracks in buildingsCauses and prevention of cracks in buildings
Causes and prevention of cracks in buildingsSUPREETH Suppi
 
PRESTRESSED CONCRETE STRUCTURES
PRESTRESSED CONCRETE STRUCTURESPRESTRESSED CONCRETE STRUCTURES
PRESTRESSED CONCRETE STRUCTURESTarun kumar
 
PRECAST CONCRETE STAIRS
  PRECAST CONCRETE STAIRS  PRECAST CONCRETE STAIRS
PRECAST CONCRETE STAIRSAbhishek Mewada
 
Prefabricated Structure and its installation process
Prefabricated Structure and its installation processPrefabricated Structure and its installation process
Prefabricated Structure and its installation processUdayram Patil
 
curtain wall -skin of building
 curtain wall -skin of building curtain wall -skin of building
curtain wall -skin of buildingabidha karthu
 
Raft foundation ppt by kamal bhatia
Raft foundation ppt by kamal bhatiaRaft foundation ppt by kamal bhatia
Raft foundation ppt by kamal bhatiakamal bhatia
 
03 Curtain-wall Presentation
03 Curtain-wall Presentation03 Curtain-wall Presentation
03 Curtain-wall Presentation★ Aybige Tek
 
Ct pad-foundation
Ct pad-foundationCt pad-foundation
Ct pad-foundationWan Nee
 
Post-tensioning in Prestressed Concrete
Post-tensioning in Prestressed ConcretePost-tensioning in Prestressed Concrete
Post-tensioning in Prestressed ConcreteDavinderpal Singh
 
Advanced Building Materials
Advanced Building MaterialsAdvanced Building Materials
Advanced Building MaterialsSrishti Mehta
 
Specifications of buildings
Specifications of buildingsSpecifications of buildings
Specifications of buildingsSimarpreet Singh
 

La actualidad más candente (20)

Curtain walls
Curtain wallsCurtain walls
Curtain walls
 
Space frames!
Space frames!Space frames!
Space frames!
 
Precast-concrete Details
Precast-concrete DetailsPrecast-concrete Details
Precast-concrete Details
 
Partition walls
Partition wallsPartition walls
Partition walls
 
Causes and prevention of cracks in buildings
Causes and prevention of cracks in buildingsCauses and prevention of cracks in buildings
Causes and prevention of cracks in buildings
 
PRESTRESSED CONCRETE STRUCTURES
PRESTRESSED CONCRETE STRUCTURESPRESTRESSED CONCRETE STRUCTURES
PRESTRESSED CONCRETE STRUCTURES
 
PRECAST CONCRETE STAIRS
  PRECAST CONCRETE STAIRS  PRECAST CONCRETE STAIRS
PRECAST CONCRETE STAIRS
 
Puf panels
Puf panelsPuf panels
Puf panels
 
Prefabricated Structure and its installation process
Prefabricated Structure and its installation processPrefabricated Structure and its installation process
Prefabricated Structure and its installation process
 
curtain wall -skin of building
 curtain wall -skin of building curtain wall -skin of building
curtain wall -skin of building
 
Raft foundation ppt by kamal bhatia
Raft foundation ppt by kamal bhatiaRaft foundation ppt by kamal bhatia
Raft foundation ppt by kamal bhatia
 
Tensile structures
Tensile structuresTensile structures
Tensile structures
 
03 Curtain-wall Presentation
03 Curtain-wall Presentation03 Curtain-wall Presentation
03 Curtain-wall Presentation
 
Cladding
CladdingCladding
Cladding
 
Ct pad-foundation
Ct pad-foundationCt pad-foundation
Ct pad-foundation
 
Aluminium doors and Windows
Aluminium doors and WindowsAluminium doors and Windows
Aluminium doors and Windows
 
Post-tensioning in Prestressed Concrete
Post-tensioning in Prestressed ConcretePost-tensioning in Prestressed Concrete
Post-tensioning in Prestressed Concrete
 
Advanced Building Materials
Advanced Building MaterialsAdvanced Building Materials
Advanced Building Materials
 
High rise building construction
High rise building constructionHigh rise building construction
High rise building construction
 
Specifications of buildings
Specifications of buildingsSpecifications of buildings
Specifications of buildings
 

Destacado

Cold Weather Requirements for Masonry Construction
Cold Weather Requirements for Masonry ConstructionCold Weather Requirements for Masonry Construction
Cold Weather Requirements for Masonry ConstructionScott Conwell, FAIA, FCSI
 
Stone Masonry BUILDING CONSTRUCTION
Stone Masonry BUILDING CONSTRUCTIONStone Masonry BUILDING CONSTRUCTION
Stone Masonry BUILDING CONSTRUCTIONRavindra Patnayaka
 
Types of stone masonry
Types of stone masonryTypes of stone masonry
Types of stone masonryPrabha Karan
 
Single Wythe CMU Detailing - Featuring Architectural Illustrations, Rendering...
Single Wythe CMU Detailing - Featuring Architectural Illustrations, Rendering...Single Wythe CMU Detailing - Featuring Architectural Illustrations, Rendering...
Single Wythe CMU Detailing - Featuring Architectural Illustrations, Rendering...jasonyana
 
Masonry structures behavior and design
Masonry structures behavior and designMasonry structures behavior and design
Masonry structures behavior and designNour Samir
 
MORTAR AND CONCRETE HOLLOW BLOCKS
MORTAR AND CONCRETE HOLLOW BLOCKSMORTAR AND CONCRETE HOLLOW BLOCKS
MORTAR AND CONCRETE HOLLOW BLOCKSCarlo Mendoza
 
Failures In Masonry Structures Lec 1
Failures In Masonry Structures Lec 1Failures In Masonry Structures Lec 1
Failures In Masonry Structures Lec 1Teja Ande
 
Masonry Presentation
Masonry PresentationMasonry Presentation
Masonry Presentationflrbc1avtech
 
Modeling masonry in Revit
Modeling masonry in RevitModeling masonry in Revit
Modeling masonry in RevitHuytraining
 

Destacado (20)

Benefits of Building With Masonry
Benefits of Building With MasonryBenefits of Building With Masonry
Benefits of Building With Masonry
 
Quality Control for Masonry
Quality Control for MasonryQuality Control for Masonry
Quality Control for Masonry
 
Cold Weather Requirements for Masonry Construction
Cold Weather Requirements for Masonry ConstructionCold Weather Requirements for Masonry Construction
Cold Weather Requirements for Masonry Construction
 
Stone Masonry BUILDING CONSTRUCTION
Stone Masonry BUILDING CONSTRUCTIONStone Masonry BUILDING CONSTRUCTION
Stone Masonry BUILDING CONSTRUCTION
 
Design of masonry structures 2004
Design of masonry structures 2004Design of masonry structures 2004
Design of masonry structures 2004
 
Types of stone masonry
Types of stone masonryTypes of stone masonry
Types of stone masonry
 
Single Wythe CMU Detailing - Featuring Architectural Illustrations, Rendering...
Single Wythe CMU Detailing - Featuring Architectural Illustrations, Rendering...Single Wythe CMU Detailing - Featuring Architectural Illustrations, Rendering...
Single Wythe CMU Detailing - Featuring Architectural Illustrations, Rendering...
 
Masonry structures behavior and design
Masonry structures behavior and designMasonry structures behavior and design
Masonry structures behavior and design
 
MORTAR AND CONCRETE HOLLOW BLOCKS
MORTAR AND CONCRETE HOLLOW BLOCKSMORTAR AND CONCRETE HOLLOW BLOCKS
MORTAR AND CONCRETE HOLLOW BLOCKS
 
Tips for optimizing structural masonry
Tips for optimizing structural masonryTips for optimizing structural masonry
Tips for optimizing structural masonry
 
Failures In Masonry Structures Lec 1
Failures In Masonry Structures Lec 1Failures In Masonry Structures Lec 1
Failures In Masonry Structures Lec 1
 
Masonry Presentation
Masonry PresentationMasonry Presentation
Masonry Presentation
 
04 masonry
04 masonry04 masonry
04 masonry
 
Modeling masonry in Revit
Modeling masonry in RevitModeling masonry in Revit
Modeling masonry in Revit
 
Concrete block
Concrete blockConcrete block
Concrete block
 
Masonry
MasonryMasonry
Masonry
 
Hollow Block
Hollow Block Hollow Block
Hollow Block
 
Cement & concrete blocks
Cement & concrete blocksCement & concrete blocks
Cement & concrete blocks
 
BT 1: Concrete Hollow Blocks
BT 1: Concrete Hollow BlocksBT 1: Concrete Hollow Blocks
BT 1: Concrete Hollow Blocks
 
Stone masonry
Stone masonryStone masonry
Stone masonry
 

Más de Scott Conwell, FAIA, FCSI (8)

Design Considerations for Large Format Tile
Design Considerations for Large Format TileDesign Considerations for Large Format Tile
Design Considerations for Large Format Tile
 
Flashing & Air Barrier
Flashing & Air BarrierFlashing & Air Barrier
Flashing & Air Barrier
 
Air Barrier & Flashing
Air Barrier & FlashingAir Barrier & Flashing
Air Barrier & Flashing
 
Terra Cotta Rainscreen
Terra Cotta RainscreenTerra Cotta Rainscreen
Terra Cotta Rainscreen
 
Brick Veneer Steel Stud Wall
Brick Veneer Steel Stud WallBrick Veneer Steel Stud Wall
Brick Veneer Steel Stud Wall
 
Brick and Block Cavity Wall
Brick and Block Cavity WallBrick and Block Cavity Wall
Brick and Block Cavity Wall
 
Designing with Tile
Designing with TileDesigning with Tile
Designing with Tile
 
Masonry for sustainability
Masonry for sustainabilityMasonry for sustainability
Masonry for sustainability
 

Masonry Detailing Series v.3.4

  • 2. Brick 010 Single Wythe 020 Composite 030 Anchored Veneer - Masonry Backup 040 Anchored Veneer - Steel Stud Backup 01 Brick 050 Anchored Veneer - Wood Stud Backup 02 Concrete block 060 Anchored Veneer - Other Backup 03 Stone, rough 070 Adhered Veneer - Masonry Backup 04 Stone, dimensional 080 Adhered Veneer - Steel Stud Backup 06 Tile 090 Adhered Veneer - Wood Stud Backup 07 Terrazzo 100 Adhered Veneer - Other Backup 08 Cement 110 Rain Screen Wall 09 Plaster / Stucco 120 Structural Masonry 10 Restoration 130 Flooring - Interior 11 Terra Cotta 140 Paving - Exterior 12 Refractory 150 Landscape Walls 13 AAC 160 Fireplaces & Chimneys 14 Precast Concrete 210 Training Mockups 15 Accessories 220 Apprentice Contests 21 Structural Steel 310 Building Models 22 Cast-in-Place Conc. 400 Wall Type Analysis 23 Metal Siding 410 Diagrams 40 Wall Type Analysis 510 Modular/Bonding 50 Building Model 610 Sustainability / Energy-Efficiency
  • 3. CONCEPTUAL WALL SECTION DETAIL 01.030.0101 REV. 03/26/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 4. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED MECH. FASTENED TERMINATION BAR W/ CONT. SEALANT @ TOP CONCRETE MASONRY BACKUP BRICK VENEER FLEXIBLE FLASHING – SEAL & ADHERE TO DRIP EDGE WEEP VENT INSERTS DRIP EDGE – SEAL AND ADHERE TO FOUNDATION BASE OF WALL DETAIL FLEX. FLASHING, DRIP EDGE, TERM. BAR DETAIL 01.030.0301 REV. 09/25/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 5. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED MECH. FASTENED TERMINATION BAR W/ CONT. SEALANT @ TOP CONCRETE MASONRY BACKUP BRICK VENEER FLEXIBLE FLASHING – SEAL MORTAR DROPPING & ADHERE TO DRIP EDGE COLLECTION DEVICE (MDCD) WEEP VENT INSERTS DRIP EDGE – SEAL AND ADHERE TO FOUNDATION BASE OF WALL DETAIL FLEX. FLASHING, DRIP EDGE, TERM. BAR, MDCD DETAIL 01.030.0302 REV. 09/25/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 6. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED MECH. FASTENED TERMINATION BAR W/ CONT. SEALANT @ TOP CONCRETE MASONRY BACKUP BRICK VENEER FLEXIBLE FLASHING FLUSH MORTAR DROPPING W/ OUTSIDE FACE OF BRICK COLLECTION DEVICE (MDCD) WEEP VENT INSERTS BASE OF WALL DETAIL FLEX. FLASHING NO DRIP; TERM BAR, MDCD DETAIL 01.030.0303 REV. 09/25/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 7. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REINFORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED BRICK VENEER CONCRETE MASONRY BACKUP WEEP VENTS AT 2ND COURSE FOR AIR CIRCULATION RECOMMENDED DRAINAGE FLASHING SYSTEM ADDITIONAL WEEP VENT INSERTS RECOMMENDED WEEPS INTEGRAL TO DRAINAGE FLASHING SYSTEM BASE OF WALL DETAIL DRAINAGE FLASHING DETAIL 01.030.0304 REV. 09/25/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 8. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REINFORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCING AS REQUIRED AIR/MOISTURE/VAPOR BARRIER TO SEAL TRANSITION MEMBRANE RUBBERIZED ASPHALT TRANSITION MEMBRANE OVER TERM. BAR CONCRETE MASONRY BACKUP BRICK VENEER PROPRIETARY DRAINGAGE FLASHING SYSTEM W/ INTEGRAL DRIP EDGE, TERM. BAR & WEEP SYSTEM ADDITIONAL WEEP VENT INSERTS AS REQ’D FOR VENILATED WALL MESH WEEPS INTEGRAL TO PROPRIETARY DRAINAGE FLASHING SYSTEM FOUNDATION DETAIL PROPRIETARY DRAINAGE FLASHING (TOTAL FLASH) DETAIL 01.030.0304 REV. 06/25/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 9. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED RETURN FLASHING INTO BED JOINT OF BLOCK CONCRETE MASONRY BACKUP BRICK VENEER FLEXIBLE FLASHING – SEAL & ADHERE TO DRIP EDGE WEEP VENT INSERTS DRIP EDGE – SEAL AND ADHERE TO FOUNDATION BASE OF WALL DETAIL FLEX. FLASHING IN CMU, DRIP EDGE DETAIL 01.030.0305 REV. 09/25/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 10. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED RETURN FLASHING INTO BED JOINT OF BLOCK CONCRETE MASONRY BACKUP BRICK VENEER FLEXIBLE FLASHING – SEAL MORTAR DROPPING & ADHERE TO DRIP EDGE COLLECTION DEVICE (MDCD) WEEP VENT INSERTS DRIP EDGE – SEAL AND ADHERE TO FOUNDATION BASE OF WALL DETAIL FLEX. FLASHING IN CMU, DRIP EDGE, MDCD DETAIL 01.030.0306 REV. 03/16/10 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 11. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED MECH. FASTENED TERMINATION BAR W/ CONT. SEALANT @ TOP BRICK VENEER CONCRETE MASONRY BACKUP MORTAR DROPPING COLLECTION DEVICE (MDCD) METAL FLASHING W/ INTEGRAL DRIP EDGE – SEAL AND ADHERE TO FOUNDATION WEEP VENT INSERTS BASE OF WALL DETAIL METAL FLASHING W/ DRIP, TERM. BAR, MDCD DETAIL 01.030.0311 REV. 09/25/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 12. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS CONCRETE MASONRY BACKUP RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. BRICK VENEER METAL FLASHING RECEIVER SET IN CMU BED JOINT METAL FLASHING W/ INTEGRAL DRIP EDGE – SEAL AND ADHERE TO FOUNDATION WEEP VENT INSERTS BASE OF WALL DETAIL METAL FLASHING, METAL RECEIVER DETAIL 01.030.0312 REV. 09/25/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 13. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS CONCRETE MASONRY BACKUP RIGID INSULATION AIR/MOISTURE/VAPOR BARRIER AS REQUIRED GROUT & REINFORCEMENT AS REQUIRED BRICK VENEER HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE T/ BRICK WALL TIES @ 16” O.C. LEDGE T/FDTN. 4” MIN. MORTAR DROPPING COLLECTION DEVICE (MDCD) GRADE TO SLOPE FLASHING SYSTEM AWAY FROM WALL FOUNDATION BELOW-GRADE INSULATION AND WATERPROOFING BASE OF WALL DETAIL BRICK LEDGE, T/FDTN. ABOVE GRADE DETAIL 01.030.0321 REV. 09/25/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 14. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS CONCRETE MASONRY BACKUP RIGID INSULATION AIR/MOISTURE/VAPOR BARRIER AS REQUIRED GROUT & REINFORCEMENT AS REQUIRED BRICK VENEER HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. MORTAR DROPPING COLLECTION DEVICE (MDCD) FLASHING SYSTEM T/FDTN. GRADE TO SLOPE GROUT OR MORTAR FILL AWAY FROM WALL WATER RESISTANT FOUNDATION SURFACE TREATMENT AT BRICK BELOW GRADE BELOW-GRADE INSULATION T/ BRICK AND WATERPROOFING LEDGE BASE OF WALL DETAIL BRICK LEDGE, T/FDTN. BELOW GRADE DETAIL 01.030.0322 REV. 01/27/11 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 15. WOOD BLOCKING FOR WINDOW ANCHORAGE ALTERNATE FLASHING LOCATION WINDOW STOOL NOT SHOWN WINDOW ASSEMBLY FLASHING RIGID FLASHING TO SPAN END DAM ACROSS DRAINAGE CAVITY RIGID INSULATION HORIZONTAL JOINT REINFORCEMENT MASONRY EXPANSION JOINT AS REQUIRED MASONRY SILL W/ 1/8” x 1/8” CONT. SAW-CUT DRIP SILL DETAIL MASONRY SILL, RIGID FLASHING DETAIL 01.030.0401 REV. 07/28/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 16. WINDOW ASSEMBLY WINDOW STOOL STONE OR PRECAST CONC. SILL W/ 1/8” W. x 1/8” H. CONT. SAW-CUT DRIP THRU-WALL FLASHING W/ 2” MIN. VERTICAL END DAMS, EA. END; SUPPORT FLASHING ACROSS CAVITY IF FLEXIBLE FLASHING IS USED CUT BLOCK INTERIOR FINISH CAVITY INSUL. 2” AIR SPACE KEY DETAIL RECOMMENDED; 1” AIR SPACE MIN. REQ’D BY CODE FOR VENEERS SILL DETAIL MASONRY SILL, RIGID FLASHING, INTERIOR VIEW DETAIL 01.030.0402 REV. 08/21/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 17. SELF SUPPORTING BRICK RETURN AT JAMB TOOTHED INTO OUTER WYTHE TO FORM 4” CANTILEVER SILL NOT SHOWN EXTERIOR VIEW CAVITY VIEW UNSUPPORTED BRICK RETURN AT JAMB DETAIL 01.030.0501 REV. 10/20/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 18. EXTERIOR VIEW INTERIOR VIEW WINDOW JAMB & SILL DETAIL S DETAIL 01.030.0502 REV. 02/19/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 19. HORIZONTAL JOINT INTERIOR FINISH REINFORCEMENT W/ INTEGRAL WALL TIES WINDOW STOOL BLOCKING WINDOW ASSEMBLY 3D VIEW 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS WINDOW SILL BRICK VENEER AIR/WATER/VAPOR FLASHING UNDER SILL BARRIER AS REQ’D W/ VERTICAL END DAM @ BOTH ENDS OF SILL CONCRETE MASONRY BACKUP RIGID INSULATION WINDOW JAMB DETAIL DETAIL 01.030.0502.2D REV. 02/19/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 20. INTERIOR VIEW DETAIL FEATURES • LOOSE LINTEL AT BRICK • BOND BEAM AT BLOCK • LIGHT GAUGE SUPPORT EXTERIOR VIEW ACROSS CAVITY HEAD DETAIL STEEL LINTEL & BOND BEAM DETAIL 01.030.0601 REV. 09/04/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 21. DETAIL FEATURES EXTERIOR VIEW INTERIOR VIEW • LOOSE LINTEL AT BRICK • STEEL ANGLES AT BLOCK • LIGHT GAUGE SUPPORT ACROSS CAVITY HEAD DETAIL STEEL LINTEL W/ DOUBLE ANGLE DETAIL 01.030.0603 REV. 09/06/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 22. DETAIL FEATURES • PLATE WELDED TO I-BEAM • CUT BLOCK AROUND BEAM HEAD DETAIL PLATE WELDED TO STEEL BEAM DETAIL 01.030.0604 REV. 09/27/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 23. 2” AIR SPACE RECOMMENDED; 1” HORIZONTAL JOINT MIN. REQ’D FOR REINFORCEMENT W/ DRAINAGE WALLS INTEGRAL WALL TIES RIGID INSUL. THRU-WALL FLASHING W/ METAL DRIP EDGE SET IN ADJUSTABLE MASTIC OR SEALANT SHELF ANGLE WEEP/VENT TYPICAL FACE ADJUSTABLE BRICK ABOVE & SHELF ANGLE BELOW ANGLE SEALANT & BACKER ROD COMPRESSIBLE FILLER, OPTIONAL SHELF ANGLE DETAIL TYP. FACE BRICK DETAIL 01.030.0701 REV. 06/19/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 24. HORIZONTAL JOINT REINFORCEMENT W/ INTEGRAL WALL TIES THRU-WALL FLASHING RIGID INSULATION ADJUSTABLE SHELF ANGLE WEEP VENT METAL DRIP EDGE SET IN MASTIC OR SEALANT SEALANT & BACKER ROD TYP. FACE BRICK ABOVE AND BELOW ANGLE COMPRESSIBLE FILLER, OPTIONAL 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS SHELF ANGLE DETAIL TYP. FACE BRICK DETAIL 01.030.0701.2D REV. 06/19/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 25. HORIZONTAL JOINT 2” AIR SPACE REINFORCEMENT W/ RECOMMENDED; 1” INTEGRAL WALL TIES MIN. REQ’D FOR DRAINAGE WALLS THRU-WALL FLASHING W/ METAL DRIP EDGE SET IN MASTIC OR SEALANT RIGID INSUL. WEEP/VENT ADJUSTABLE. SHELF ANGLE LIPPED BRICK, OPTIONAL SEALANT & BACKER ROD COMPRESSIBLE FILLER, OPTIONAL SHELF ANGLE DETAIL LIPPED BRICK DETAIL 01.030.0702 REV. 10/14/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 26. HORIZONTAL JOINT REINFORCEMENT W/ INTEGRAL WALL TIES RIGID INSULATION THRU-WALL FLASHING ADJUSTABLE SHELF ANGLE WEEP VENT METAL DRIP EDGE SET IN MASTIC OR SEALANT SEALANT & BACKER ROD LIPPED BRICK BELOW SHELF ANGLE COMPRESSIBLE FILLER, OPTIONAL 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS SHELF ANGLE DETAIL LIPPED BRICK DETAIL 01.030.0702.2D REV. 10/14/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 27. HORIZONTAL JOINT REINFORCEMENT W/ INTEGRAL WALL TIES THRU-WALL FLASHING RIGID INSUL. MECH. FASTENED TERM. BAR ADJUSTABLE SHELF ANGLE WEEP VENT METAL DRIP EDGE SET IN MASTIC OR SEALANT 2” AIR SPACE TYP. FACE BRICK ABOVE RECOMMENDED; AND BELOW ANGLE 1” MIN. REQ’D FOR SEALANT & BACKER ROD DRAINAGE WALLS COMPRESSIBLE FILLER, OPTIONAL SHELF ANGLE DETAIL TYP. FACE BRICK, TERM. BAR DETAIL 01.030.0703 REV. 06/19/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 28. HORIZONTAL JOINT REINFORCEMENT W/ INTEGRAL WALL TIES MECH. FASTENED TERMINATION BAR W/ CONT. BEAD OF SEALANT AT TOP THRU-WALL FLASHING RIGID INSULATION ADJUSTABLE SHELF ANGLE WEEP VENT METAL DRIP EDGE SET IN MASTIC OR SEALANT SEALANT & BACKER ROD TYP. FACE BRICK ABOVE AND BELOW ANGLE COMPRESSIBLE FILLER, OPTIONAL 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS SHELF ANGLE DETAIL TYP. FACE BRICK, TERM. BAR DETAIL 01.030.0703.2D REV. 06/19/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 29. CMU BACKUP FACE BRICK CAVITY INSUL. THRU-WALL FLASHING ROOF MEMBRANE CUT BLOCK BELOW FLASHING COUNTER- FLASHING SHEET METAL RECEIVER THRU-WALL FLASHING WEEP VENT TERMINATION BAR W/ CONT. SEALANT ROOF STRUCTURE HORIZONTAL JOINT REINF. @ 16” O.C. W/ INTEGRAL WALL TIES ROOF DETAIL HIGH WALL – LOW ROOF DETAIL 01.030.0751 REV. 11/6/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 30. FACE BRICK THRU-WALL FLASHING WEEP VENT SHEET METAL RECEIVER COUNTERFLASHING KEY DETAIL TERMINATION BAR W/ CONT. SEALANT CANT STRIP ROOF MEMBRANE KEY SECTION ROOF DETAIL HIGH WALL – LOW ROOF DETAIL 01.030.0751A REV. 11/6/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 31. MASONRY COPING: LIMESTONE, CAST STONE, CALCIUM SILICATE, OR S.S. DOWEL W/ SEALANT PRECAST CONCRETE; OVERHANG AROUND PENETRATIONS MASONRY WALL 1½” MIN.; SLOPED THROUGH FLASHING TOP 1/8” SAW-CUT DRIP, BOTH SIDES OF WALL CAP SEE DETAIL 01.759 FOR WALL CAP JOINT OPTIONS SEALANT & BACKER ROD, BOTH SIDES CANTED S.S. THRU-WALL OF WALL CAP FLASHING W/ 1/2” EXPOSED DRIP EDGE FACE BRICK SLOPED MORTAR BED TO SUPPORT CANTED FLASHING, SEALANT BELOW DRIP, OPT. OPT. (NOT SHOWN) RIGID INSULATION OPEN DRAINAGE CAVITY, OPTIONAL ABOVE ROOF LINE; ALSO SEE DETAIL GROUT & REINFORCING 01.752 AS REQ’D. HORIZONTAL JOINT REINFORCEMENT W/ WALL TIES MASONRY WALL CAP OPEN CAVITY DETAIL 01.030.0801 REV. 011/04/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 32. MASONRY COPING: LIMESTONE, CAST STONE, CALCIUM SILICATE, OR PRECAST CONCRETE; OVERHANG S.S. DOWEL W/ SEALANT MASONRY WALL 1½” MIN.; SLOPED AROUND PENETRATIONS TOP THROUGH FLASHING 1/8” SAW-CUT DRIP, BOTH SIDES OF WALL CAP SEE DETAIL 01.759 FOR WALL CAP JOINT OPTIONS SEALANT & BACKER ROD, BOTH SIDES THROUGH-WALL OF WALL CAP FLASHING W/ 1/2” DRIP EDGE GROUT OR MORTAR FILL FOR DOWEL ANCHORAGE AND FLASHING SUPPORT SEALANT BELOW DRIP, OPT. (NOT SHOWN) MESH TO RETAIN GROUT OR MORTAR FILL DRAINAGE CAVITY GROUT & REINFORCING FACE BRICK AS REQ’D. HORIZONTAL JOINT RIGID INSULATION REINFORCEMENT W/ WALL TIES MASONRY WALL CAP FILLED CAVITY DETAIL 01.030.0802 REV. 011/04/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 33. 4” MIN. LAP JOINT W/ SEALANT FORMED METAL COPING ROOF MEMBRANE UNDER COPING ROOF CONT. WOOD MEMBRANE BLOCKING SLOPED 1” PER FOOT, MIN. WOOD NAILER W/ ANCHOR BOLTS BOND BEAM OR GROUT CORES SEALANT SOLID AT ANCHOR BOLTS CONT. CLEAT, BOTH SIDES W/ SLOTTED OR OVERSIZED HOLES @ 24” O.C. FACE BRICK ROOF STRUCTURE METAL COPING DETAIL DETAIL 01.030.0803 REV. 11/20/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 34. FORMED METAL COPING ROOF MEMBRANE UNDER COPING CONT. WOOD BLOCKING SLOPED 1” PER FOOT, MIN. CONT. CLEAT W/ SLOTTED OR OVERSIZED HOLES @ 24” O.C. CONT. CLEAT W/ SLOTTED OR OVER- SEALANT SIZED HOLES @ 24” O.C. ROOF MEMBRANE WOOD NAILER W/ CANT STRIP ANCHOR BOLTS SEALANT BOND BEAM OR GROUT CORES SOLID AT ANCHOR BOLTS FACE BRICK RIGID INSULATION CONCRETE MASONRY BACKUP TREATED W/ AIR/ VAPOR/ MOISTURE BARRIER AS REQ’D METAL COPING DETAIL DETAIL 01.030.0803.2D REV. 11/20/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 35. OPTION 1 OPTION 2 RAKE BACK MORTAR AND SEALANT AND APPLY SEALANT JOINT BACKER ROD INCORRECT TOOLED MORTAR JOINT MASONRY COPING JOINTS DETAIL 01.030.0811 REV. 11/04/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 36. MORTAR WASH ARCHITECTURAL EFFECT PROJECTED COURSE DETAIL 01.030.1001 REV. 08/31/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 37. COLUMN DETAIL AT INTERFACE WITH TUBE STEEL DIAGRAM 01.030.1101 REV. 07/31/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 38. BEAM DETAIL PLATE WELDED TO DEEP BEAM DETAIL 01.030.1201 REV. 03/02/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 39. HORIZONTAL JOINT REINFORCEMENT, DISCONTINUOUS AT MOVEMENT JOINT EXPANSION JOINT (EJ): SEALANT, BACKER CONTROL JOINT (CJ): ROD, & OPTIONAL PREFORMED COMPRESSIBLE FILLER GASKET, SEALANT, OF PRE- MOLDED FOAM & BACKER ROD OR NEOPRENE PAD CONTROL JOINT (CJ): PREFORMED GASKET, SEALANT, & BACKER ROD MOVEMENT JOINT (MJ): CONTROL JOINT AND/ OR EXPANSION JOINT OPTION 1: OPTION 2: EJ & CJ ALIGNED EJ & CJ OFFSET MOVEMENT JOINT DETAIL 01.030.1301 REV. 03/14/11 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 40. EXISTING WALL ANCHOR TRANSFERS TRANSVERSE LOADS AND ALLOWS INDEPENDENT MOVEMENT OF INTERSECTING WALLS NEW WALL SEALANT, BACKER ROD, AND COMPRESSIBLE FILLER ISOLATION JOINT DETAIL 01.030.1311 REV. 06/18/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 41. MASONRY EXPANSION JOINT ALIGNED W/ WINDOW JAMB; COMPRESSIBLE FILLER, BACKER ROD & SEALANT FLASHING END DAM RETURNED INTO HEAD JOINT BACKER ROD OR COMPRESSIBLE MATERIAL AT END OF LINTEL TO AVOID RESTRAINT OF FLASHING SYSTEM MOVEMENT, AND AT FRONT EDGE W/ DRIP EDGE OF LINTEL TO PROVIDE BACKER FOR SEALANT STRUCT. STEEL LINTEL FLASHING MEMBRANE OR PLASTIC BEARING PAD BENEATH BEARING AREA OF ANGLE TO CREATE SLIP PLANE WINDOW SYSTEM EXPANSION JOINT AT WINDOW DETAIL 01.030.1321 REV. 08/09/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 42. RIGID INSULATION WATER-RESISTANT MEMBRANE 2” AIR SPACE RECOMMENDED; METAL STUDS 1” MIN. REQ’D FOR DRAINAGE WALLS 5/8” EXTERIOR SHEATHING ADJUSTABLE WALL TIES @ 16” O.C. VERTICALLY AND 24” O.C. HORIZONTALLY BRICK VENEER THRU-WALL FLASHING 8” VERTICAL MIN., ADHERED TO METAL DRIP EDGE MECH. FASTENED TERMINATION BAR FOUNDATION WEEP VENT METAL DRIP EDGE SET IN MASTIC OR SEALANT BASE OF WALL DETAIL FLEX. FLASHING, DRIP EDGE, TERM. BAR DETAIL 01.040.0301 REV. 11/06/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 43. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS METAL STUDS 5/8” EXTERIOR SHEATHING ADJUSTABLE WALL TIES @ 16” O.C. VERTICALLY AND 24” O.C. HORIZONTALLY WATER-RESISTANT MEMBRANE RIGID INSULATION BRICK VENEER MECH. FASTENED TERM. BAR KEY DETAIL SEE 02.101 THRU-WALL FLASHING 8” VERTICAL MIN., ADHERED TO METAL DRIP EDGE WEEP VENT METAL DRIP EDGE SET IN MASTIC OR SEALANT FOUNDATION BASE OF WALL DETAIL FLEX. FLASHING, DRIP EDGE, TERM. BAR DETAIL 01.040.0301.2D REV. 11/13/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 44. RIGID INSULATION WATER-RESISTANT MEMBRANE 2” AIR SPACE RECOMMENDED; METAL STUDS 1” MIN. REQ’D FOR DRAINAGE WALLS 5/8” EXTERIOR SHEATHING ADJUSTABLE WALL TIES @ 16” O.C. VERTICALLY AND 24” O.C. HORIZONTALLY CAVITY INSERT/ MORTAR COLLECTION DEVICE MECH. FASTENED BRICK VENEER TERMINATION BAR THRU-WALL FLASHING 8” VERTICAL MIN., ADHERED TO METAL DRIP EDGE FOUNDATION WEEP VENT METAL DRIP EDGE SET IN MASTIC OR SEALANT BASE OF WALL DETAIL FLEX. FLASHING, DRIP EDGE, TERM. BAR, MDCD DETAIL 01.040.0302 REV. 11/13/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 45. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS METAL STUDS 5/8” EXTERIOR SHEATHING ADJUSTABLE WALL TIES @ 16” O.C. VERTICALLY AND 24” O.C. HORIZONTALLY WATER-RESISTANT MEMBRANE MECH. FASTENED TERM. BAR BRICK VENEER RIGID INSULATION CAVITY INSERT/ MORTAR COLLECTION DEVICE KEY DETAIL SEE 02.102 THRU-WALL FLASHING 8” VERTICAL MIN., ADHERED TO METAL DRIP EDGE WEEP VENT METAL DRIP EDGE SET IN MASTIC OR SEALANT FOUNDATION BASE OF WALL DETAIL FLEX. FLASHING, DRIP EDGE, TERM. BAR, MDCD DETAIL 01.040.0302.2D REV. 11/13/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 46. DETAIL FEATURES • BELOW GRADE BRICK • GROUT SUPPORTS FLASHING BELOW GRADE • TERMINATION BAR • CAVITY INSERT • ADJUSTABLE VENEER TIES • AIR BARRIER BASE OF WALL DETAIL BRICK LEDGE, T/ FOUNDATION BELOW GRADE DETAIL 01.040.0311 REV. 09/27/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 47. DETAIL FEATURES • 2-PART FLASHING • ADJUSTABLE VENEER TIES • AIR INFILTRATION BARRIER (HOUSEWRAP) SILL DETAIL DETAIL 01.040.0401 REV. 08/31/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 48. INTERIOR VIEW EXTERIOR VIEW DETAIL FEATURES • NO RETURN AT CAVITY WINDOW JAMB DETAIL DETAIL 01.040.0501 REV. 09/16/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 49. WATER RESISTANT BARRIER (HOUSEWRAP) MUST BE USED IF SHEATHING IS NOT WATER RESISTANT AND JOINTS IN SHEATHING ARE NOT TAPED AND SEALED. LAP WATER RESISTANT BARRIER OVER TOP OF FLASHING WOOD STUDS RIGID INSULATION SHEATHING WATER RESISTANT BARRIER PLAN ADJUSTABLE VENEER ANCHORS FASTENED THROUGH INSULATION & SHEATHING TO STUDS 2” AIR SPACE RECOMMENDED; 1” REQ’D FOR DRAINAGE WALLS BACKING SYSTEM FLASHING W/ TERMINATION BAR BASE OF WALL DETAIL FLEX. FLASHING, TERM. BAR DETAIL 01.050.0301 REV. 02/14/07 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 50. BASE OF WALL ADHERED VENEER OVER CMU, NO DRAINAGE MAT DETAIL 01.070.0301 REV. 12/10/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 51. BASE OF WALL ADHERED VENEER OVER CMU, DRAINAGE MAT DETAIL 01.070.0302 REV. 12/10/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 52. 5”± WIDE FILLER STRIP AT CORNERS 4’-0” x 4’-0” METAL STUD/ CMU BACKUP W/ AIR GLASS MAT REINFORCED BARRIER BY DCTC GYPSUM BACKUP INSTRUCTORS CONSTRUCTED ON SITE BY S.S. SCHWARZ MASONRY ON MAY 19, 2010 15# BUILDING FELT AREA OF PANEL INSTALLATION DEMONSTRATION TYVEK WRB KEENE DRAINAGE MAT AT METAL STUD PORTION ONLY DEMONSTRATE GROUTING STARTER JOINTS W/ SPECMIX CHANNEL AT POLYMER MODIFIED BASE COURSE MORTAR APPLIED USING GROUT BAG ENGINEERED THIN BRICK PANEL SYSTEM MECH. FASTENED TO CMU NOTE: ALL COMPONENTS OF ENGINEERED BACKUP THIN BRICK SYSTEM INCLUDING BRICK PANELS, FILLER STRIPS, STARTER CHANNEL, BUILDING FELT, DRAINAGE MAT, GROUT AND BAKER BAGS TO BE PROVIDED BY S.S. SCHWARZ MASONRY; DCTC TO PROVIDE TYVEK. THIN BRICK MOCKUP PREFAB. BRICK PANELS, CMU & STEEL STUD BACKUPS DETAIL 01.070.2101 REV. 5/11/10 © 2010 INTERNATIONAL MASONRY INSTITUTE
  • 53. STONE CAP IN MORTAR SETTING BED LEVEL SCRATCH COAT AT TOP OF WALL LATH OVER TOP OF WALL; LAP OVER WALL LATH 4” MIN. TYPE S MORTAR SCRATCH COAT SELF-ADHERING FLASHING OVER TOP OF WALL CONSTRUCTION; LAP OVER WATER RESISTANT BARRIER SLOPING SOLID SHIM, E.G. BEVELED SIDING TYPE S MORTAR SETTING BED ADHERED VENEER EXTERIOR GYPSUM SHEATHING METAL STUD METAL LATH FRAMING WATER RESISTANT BARRIER TOP OF WALL SHEATHING & METAL STUDS DETAIL 01.080.0801 REV. 05/13/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 54. INTERIOR FINISH WOOD FRAMING DOUBLE LAP WATER RESISTANT BARRIER INSULATION AROUND CORNER 16” MIN. EXTERIOR GYPSUM SHEATHING WATER RESISTANT DOUBLE LAP LATH BARRIER, 2 LAYERS AROUND CORNER RECOMMENDED TO FRAMING, 16” MIN. METAL LATH MORTAR SCRATCH COAT MORTAR SETTING BED ADHERED VENEER CORNER DETAIL GYP. SHEATHING & WOOD STUDS, OUTSIDE CORNER DETAIL 01.090.1501 REV. 05/27/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 55. CHIMNEY CLAY FLUE FIRESTOP INSUL., 2” MIN. LINER BRICK INFILL PARGE BRICK AT SMOKE CHAMBER MANTEL SHELF DAMPER STEEL ANGLE TO SUPPORT CORBELED SMOKE CHAMBER BRICK INFILL ABOVE SMOKE SHELF FACE FIREBACK FIREPLACE OPENING FIRESTOP INSUL LINTEL RAISED HEARTH FIREBOX FRESH AIR INTAKE ASH PIT FOUNDATION FIREPLACE DETAIL DETAIL 01.160.0101 REV. 01/18/11 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 56. SPARK ARRESTOR FORMWORK, TO BE SEALANT REMOVED CAST IN PLACE REINFORCED CEMENTITIOUS CONCRETE BACKER UNIT CHIMNEY CAP ½” INSULATION FOR BOND BREAK CLAY FLUE LINER SET IN FIRECLAY MORTAR CONT. FLASHING UNDER CAP BRICK OR CMU INFILL ROOFING MATERIAL MAY VARY BABY TINS. COUNTERFLASHING NOT SHOWN CHIMNEY DETAIL DETAIL 01.160.0201 REV. 01/18/11 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 57. #4 REBAR, MIN. FLOOR FRAMING 2” MIN. CLEARANCE TO COMBUSTIBLES, OR PER CODE 4” MIN. PLYWOOD & COMBUSTIBLE FORMWORK MUST BE REMOVED CEMENTITIOUS BACKER UNIT OR OTHER NONCOMBUSTIBLE FORMWORK CMU OR CONCRETE FOUNDATION HEARTH SLAB SUPPORT WALL HEARTH SUPPORT SLAB DETAIL 01.160.0301 REV. 01/18/10 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 58. RIGID INSUL. 8” CMU BACKUP W/ BITUMINOUS DAMPPROOF COATING MODULAR FACE BRICK 5’-4” S.S. FLASHING & RECEIVER WEEP VENTS @ 24” O.C. 5 6’-0” SECTION 3 NOT TO SCALE ELEVATION 2 NOT TO SCALE MOCKUP #01 SHEET 01.210.0102 REV. 01/28/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 59. HORIZONTAL JOINT REINFORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. 16” MODULAR FACE BRICK 2” THICK RIGID INSUL. 3 5/8” 2¾” 2” 7 5/8” 8” CMU BACKUP W/ BITUMINOUS DAMPPROOF COATING 3” x 3” 28 GA. S.S. RECEIVER EMBEDDED INTO CMU BACKUP WEEP VENTS @ 24” O.C. 8” L. x 6½” H. 28 GA. 3D VIEW S.S. FLASHING ON 4 SLOPED MORTAR BED NOT TO SCALE DETAIL 5 NOT TO SCALE ½” 45° HEMMED DRIP EDGE MOCKUP #01 BASE DETAIL SHEET 01.210.0103 REV. 01/28/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 60. 8” CMU BACKUP W/ BITUMINOUS DAMPPROOF COATING RIGID INSULATION HOR. JOINT REINF./ WALL TIES MODULAR FACE BRICK S.S. TERM. BAR 10” H. CAVITY 4’-8” INSERT SELF-ADHERING RUBBERIZED ASPHALT FLASHING S.S. DRIP WEEP VENTS 5 @ 24” O.C. 6’-0” SECTION 3 NOT TO SCALE ELEVATION 2 NOT TO SCALE MOCKUP #02 SHEET 01.210.0202 REV. 01/30/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 61. HORIZONTAL JOINT REINFORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. 16” MODULAR FACE BRICK 2” THICK RIGID INSUL. 3 5/8” 2¾” 2” 7 5/8” ¾” S.S. TERMINATION BAR W/ CONT. SEALANT @ TOP 2” THICK x 10” H. CAVITY INSERT 8” CMU BACKUP W/ BITUMINOUS DAMPPROOF COATING WEEP VENTS @ 24” O.C. 40 MIL SELF-ADHERING 3D VIEW RUBBERIZED ASPHALT 4 FLASHING ON SLOPED NOT TO SCALE DETAIL MORTAR BED 5 NOT TO SCALE 3” WIDE S.S. W/ 45° HEMMED DRIP EDGE PROJECTING ½” FROM FACE OF BRICK, SET IN MASTIC (OPT.) ON SLOPED MORTAR BED MOCKUP #02 BASE DETAIL SHEET 01.210.0203 REV. 01/30/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 62. RIGID INSULATION 8” CMU BACKUP W/ BITUMINOUS DAMPPROOF COATING HOR. JOINT REINF.W/ WALL TIES @ THIRD BLOCK COURSE; NO WALL TIES @ BASE COURSE REINF. MODULAR FACE BRICK 10” H. CAVITY 4’-8” INSERT 5 OZ. COPPER FLASHING WEEP VENTS 5 @ 24” O.C. 6’-0” SECTION 3 NOT TO SCALE ELEVATION 2 NOT TO SCALE MOCKUP #03 SHEET 01.210.0302 REV. 02/05/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 63. 2” THICK RIGID INSUL. 16” MODULAR FACE BRICK 3 5/8” 2¾” 2” 7 5/8” 8” CMU BACKUP W/ BITUMINOUS DAMPPROOF COATING 2” THICK x 10” H. CAVITY INSERT HOR. JOINT REINF. W/OUT WALL TIES @ BASE COURSE WEEP VENTS @ 24” O.C. 3D VIEW 5 OZ. COPPER FLASHING 4 ON SLOPED MORTAR BED, NOT TO SCALE DETAIL EMBEDDED INTO CMU 5 BACKUP NOT TO SCALE MOCKUP #03 BASE DETAIL SHEET 01.210.0303 REV. 02/05/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 64. 3D OVERVIEW 1 NOT TO SCALE MOCKUP #04 SHEET 01.210.0401 REV. 02/19/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 65. 3 5/8” 2¾” 2” 7 5/8”” 1” S.S. TERM. BAR W/ CONT. SEALANT 40 MIL SELF-ADHERING RUBBERIZED ASPHALT 2” RIGID INSUL. FLASHING 3½” x 3½” x 3/16” STEEL ANGLE W/ 4” BEARING EA. END WEEP VENTS @ 24” O.C. 4 ½” 45° S.S. HEMMED (2) 3½” x 3½” x 3/16” DRIP EDGE, 3” WIDE STEEL ANGLES, 8” HEAD DETAIL BEARING EA. END 5’-4” 4 NOT TO SCALE 40 MIL SELF-ADHERING RUBBERIZED ASPHALT FLASHING SLOPE BRICK ROWLOCK SILL 15º COTTON SASH CORD HALF-HIGH 5 ROPE WICK @ 16” O.C. BLOCK AT SILL 26 GA. STAINLESS STEEL EXTENDING INTO CMU BACKUP TO SUPPORT THRU-WALL FLASHING ACROSS AIR SPACE; ½” 45° HEMMED DRIP EDGE SECTION SILL DETAIL 3 5 NOT TO SCALE NOT TO SCALE MOCKUP #04 SHEET 01.210.0403 REV. 02/19/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 66. 40 MIL SELF-ADHERING RUBBERIZED ASPHALT THRU-WALL FLASHING 2” VERTICAL END DAM, 26 GA. STAINLESS STEEL FIELD FORMED WITH EXTENDING INTO CMU BACKUP RUBBERIZED ASPHALT TO SUPPORT THRU-WALL FLASHING FLASHING ACROSS AIR SPACE; ½” 45° HEMMED DRIP EDGE COTTON SASH CORD SILL DETAIL ROPE WICK @ 16” O.C. SILL DETAIL 6 7 NOT TO SCALE NOT TO SCALE SLOPE BRICK ROWLOCK SILL 15º MOCKUP #04 SILL DETAILS SHEET 01.210.0404 REV. 02/19/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 67. RIGID INSULATION HORIZONTAL JOINT REINFORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. ¾” S.S. TERMINATION BAR W/ CONT. SEALANT @ TOP 40 MIL SELF-ADHERING RUBBERIZED ASPHALT THRU-WALL FLASHING 3½” x 3½” x 3/16” WEEP VENTS STEEL ANGLE W/ 4” @ 24” O.C. BEARING EA. END MODULAR (2) 3½” x 3½” x 3/16” FACE BRICK STEEL ANGLES, 8” BEARING EA. END RETURN FACE 26 GA. STAINLESS BRICK AT JAMBS STEEL ½”, 45° HEMMED DRIP EDGE HEAD DETAIL 2” VERTICAL END DAM, 8 FIELD FORMED WITH NOT TO SCALE RUBBERIZED ASPHALT FLASHING MOCKUP #04 HEAD DETAIL SHEET 01.210.0405 REV. 02/19/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 68. MOCKUP #05 SHEET 01.210.0501 REV. 10/09/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 69. MOCKUP #05 SHEET 01.210.0502 REV. 10/09/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 70. MOCKUP #05 SHEET 01.210.0503 REV. 10/09/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 71. MOCKUP #05 SHEET 01.210.0504 REV. 10/09/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 72. MOCKUP #05 SHEET 01.210.0505 REV. 10/09/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 73. MOCKUP #05 SHEET 01.210.0506 REV. 10/09/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 74. MOCKUP #05 SHEET 01.210.0507 REV. 10/09/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 75. MOCKUP #05 SHEET 01.210.0509 REV. 10/09/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 76. FULL HEAD JOINTS DIAGRAM 01.410.0101 REV. 07/29/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 77. NOTE: STRUCTURAL ELEMENTS MAY VARY, AND ARE SHOWN FOR ILLUSTRATION ONLY CAVITY INSULATION NOT SHOWN FOR CLARITY OF DETAIL CARRY FLASHING ½” MIN. BEYOND END OF LINTEL AND TURN UP TO FORM END DAM IN HEAD JOINT 2” RECOMMENDED; 1” MIN. SEALANT EXTEND FLASHING FLUSH OR BEYOND FACE OF MASONRY END DAM DIAGRAM FIELD-FORMED FLASHING END DAM DIAGRAM 01.410.0201 REV. 02/04/11 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 78. NOTE: STRUCTURAL ELEMENTS MAY VARY, AND ARE SHOWN FOR ILLUSTRATION ONLY CAVITY INSULATION NOT SHOWN FOR CLARITY OF DETAIL CARRY FLASHING ½” MIN. BEYOND END OF LINTEL PREFABRICATED END DAM IN HEAD JOINT; SET IN MASTIC IF FLASHING IS NOT SELF-ADHERING. END DAM PLACED PRIOR TO THROUGH-WALL FLASHING 2” RECOMMENDED; 1” MIN. EXTEND FLASHING SEALANT FLUSH OR BEYOND FACE OF MASONRY END DAM DIAGRAM PREFABRICATED FLASHING END DAM DIAGRAM 01.410.0202 REV. 02/04/11 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 79. 1/2” 1/8” 3/4” ALLOWABLE SOURCE: BUILDING CODE JOINT TOLERANCE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-05/ASCE 5- BED JOINT ±1/8” 05/TMS 402-05) REPORTED BY THE 1/4” HEAD JOINT -1/4”, +3/8” MASONRY STANDARDS JOINT COLLAR JOINT -1/4”, +3/8” COMMITTEE (MSJC) AREA OF DETAIL 3/8” 3/8” ELEVATION MORTAR JOINT TOLERANCES DIAGRAM 01.410.0301 REV. 08/06/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 80. MAX. PERMISSIBLE DISTORTION PER ASTM TABLE FACE BRICK – ALLOWABLE DISTORTION DIAGRAM 01.410.0401 REV. 11/04/08 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 81. I C D L D H = WALL HEIGHT D = ALLOWABLE VARIATION FROM PLUMB AT ANY POINT WHEN H < 10’-0” D < 1/4“ WHEN H < 20’-0” D < 3/8“ H WHEN H > 20’-0” D < 1/2“ ALLOWABLE VARIATIONS OF MASONRY OUT-OF-PLUMB DIAGRAM 01.410.1411 REV. 08/24//09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 82. L d I C L d L = LENGTH OF WALL WHEN L < 10’-0” d < 1/4“ d = ALLOWABLE VARIATION FROM PLAN AT ANY POINT WHEN L < 20’-0” d < 3/8“ WHEN L > 20’-0” d < 1/2“ ALLOWABLE VARIATIONS OF MASONRY OUT-OF-LINE DIAGRAM 01.410.1412 REV. 08/24//09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 83. ≥20’-0” I C L ≤10’-0” 1/4” 1/2” 1/2” 1/4” ALLOWABLE VARIATIONS OF MASONRY OUT-OF-LEVEL DIAGRAM 01.410.1413 REV. 08/24//09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 84. 18.00% MORTAR 12.21% MORTAR ONE SQUARE FOOT ONE SQUARE FOOT MODULAR BRICK, RUNNING BOND UTILITY BRICK, RUNNING BOND BED JOINTS 4 @ 12” x 3/8” = 18.000 SQ. IN. HEAD JOINTS 8 @ 2.3125” x 3/8” = 6.938 SQ. IN. 3 @ 12” x 3/8” = 13.500 SQ. IN. 2 @ 1.3125” x 3/8” = 0.984 SQ. IN. 3 @ 3.625” x 3/8” = 4.078 SQ. IN. 25.922 SQ. IN. MORTAR 17.578 SQ. IN. MORTAR ELEVATIONS MORTAR JOINT MATERIAL TAKEOFF DIAGRAM 01.410.0311 REV. 08/10/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 85. WHEN WINDOWS ARE SPACED CLOSE TOGETHER, LOCATE VERTICAL EXPANSION JOINTS AT WINDOW JAMBS WHEN WINDOWS ARE SPACED FAR APART, LOCATE VERTICAL EXPANSION JOINTS BETWEEN WINDOWS ELEVATIONS MOVEMENT JOINT LAYOUT DIAGRAM 01.410.1311 REV. 08/10/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 86. 80’-0” 20’-0” 1/2” 1/2” 2¼” 1¼” 1” 1” STEEL CONCRETE BRICK (AISC) (ACI) (MSJC) ALLOWABLE CONSTRUCTION TOLERANCES DIAGRAM 01.410.1401 REV. 08/21/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 87. Concrete Block 010 Single Wythe 020 Composite 030 Anchored Veneer - Masonry Backup 040 Anchored Veneer - Steel Stud Backup 01 Brick 050 Anchored Veneer - Wood Stud Backup 02 Concrete block 060 Anchored Veneer - Other Backup 03 Stone, rough 070 Adhered Veneer - Masonry Backup 04 Stone, dimensional 080 Adhered Veneer - Steel Stud Backup 06 Tile 090 Adhered Veneer - Wood Stud Backup 07 Terrazzo 100 Adhered Veneer - Other Backup 08 Cement 110 Rain Screen Wall 09 Plaster / Stucco 120 Structural Masonry 10 Restoration 130 Flooring - Interior 11 Terra Cotta 140 Paving - Exterior 12 Refractory 150 Landscape Walls 13 AAC 160 Fireplaces & Chimneys 14 Precast Concrete 210 Training Mockups 15 Accessories 220 Apprentice Contests 21 Structural Steel 310 Building Models 22 Cast-in-Place Conc. 400 Wall Type Analysis 23 Metal Siding 410 Diagrams 40 Wall Type Analysis 510 Modular/Bonding 50 Building Model 610 Sustainability / Energy-Efficiency
  • 88. VERTICAL REINFORCEMENT AS REQ’D HORIZONTAL JOINT REINFORCEMENT GROUT AS REQ’D DOWELS MAY BE BENT UP TO 1” LATERALLY PER 6” VERTICALLY CMU SHOWN IN LONGITUDINAL SECTION FOUNDATION FOUNDATION DOWEL ALIGNMENT DETAIL 02.010.0301 REV. 02/22/09 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 89. GROUT & VERTICAL REINFORCEMENT AS REQ’D HORIZONTAL JOINT REINFORCEMENT SINGLE WYTHE CONCRETE MASONRY NOTE: STRUCTURAL ELEMENTS MAY VARY AND ARE SHOWN FOR ILLUSTRATION ONLY TWO WYTHES OF CMU AT BASE COURSE CUT FLASHING AROUND CELLS TO BE GROUTED FOUNDATION BASE OF WALL SINGLE WYTHE BLOCK, SPLIT BASE COURSE DETAIL 02.010.0311 REV. 06/30/11 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 90. GROUT & VERTICAL REINFORCEMENT AS REQ’D INTERIOR FINISH MAY VARY HORIZONTAL JOINT REINFORCEMENT NOTE: STRUCTURAL ELEMENTS MAY VARY AND ARE SHOWN FOR ILLUSTRATION ONLY SINGLE WYTHE CONCRETE MASONRY TERMINATION BAR SEAL AROUND DOWEL PENETRATION (SEALANT NOT SHOWN FOR CLARITY) FLASHING FOUNDATION BASE OF WALL SINGLE WYTHE BLOCK, FLASHING @ INSIDE FACE DETAIL 02.010.0312 REV. 06/30/11 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 91. GROUT & VERTICAL REINFORCEMENT AS REQ’D HORIZONTAL JOINT REINFORCEMENT NOTE: STRUCTURAL ELEMENTS MAY VARY AND ARE SHOWN FOR ILLUSTRATION ONLY SINGLE WYTHE PROPRIETARY CONCRETE MESH INSERT MASONRY FOUNDATION PROPRIETARY SINGLE WYTHE BLOCK FLASHING/ WEEP SYSTEM BASE OF WALL SINGLE WYTHE BLOCK, PROPRIETARY FLASHING/WEEPS DETAIL 02.010.0313 REV. 06/30/11 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 92. GROUT & VERTICAL REINFORCEMENT AS REQ’D NOTE: STRUCTURAL ELEMENTS MAY VARY HORIZONTAL JOINT AND ARE SHOWN FOR REINFORCEMENT ILLUSTRATION ONLY WINDOW SYSTEM FLASHING END DAM SILL FLASHING SINGLE WYTHE CONCRETE MASONRY SILL DETAIL SINGLE WYTHE BLOCK DETAIL 02.010.0401 REV. 06/30/11 © 2011 INTERNATIONAL MASONRY INSTITUTE
  • 93. FLOOR CONNECTION DETAIL DETAIL 02.010.0701 REV. 08/31/07 © 2011 INTERNATIONAL MASONRY INSTITUTE