Sulaim b. Ab Qais                                                                                    2012


                                        DESIGN A TRANSFORMER

 This paper guides a simple and practical calculation in designing a transformer. The hands-on work can
            be understood from this video http://www.youtube.com/watch?v=s6NyTprQCBI




           MATERIALS

Masking tape, wax paper, copper cable, magnet copper wire, sandpaper, silicon-iron sheet, formwork,
soldering wire

           CALCULATION

1. Determine the load power, P.

Let say,

           P=300W

2. Find the primary winding current. Malaysia using 230 VAC, +10%,-6%, thus the current would be;

           Ip = P/V

           Ip = 200W/230V

            = 0.87 A, thus the wire that we will using for primary winding is 0.26 mm2

Let say the secondary winding voltage, Vs = 40 VAC

           Is = 200W/40V

            = 5 A, thus the wire that we will using for secondary windings is 1.31 mm2

3. Find the size of the cable for primary windings and secondary windings.

By referring to the table below we can determine the size of primary and secondary coil (magnet wire).

                              Table: cable size for safe current carrying capacity

 American Wire Gauge (AWG)                     Area size (mm2)                       Current (max)
             30                                      0.05                                0.22
             29                                      0.06                                0.29
             28                                      0.08                                 0.3
             27                                       0.1                                 0.4
Sulaim b. Ab Qais                                                                                  2012


               26                                 0.14                                 0.5
               25                                 0.16                                 0.6
               24                                 0.25                                 0.8
               23                                 0.26                                 1.0
               22                                 0.34                                 1.2
               21                                 0.38                                 1.6
               20                                  0.5                                  2
               19                                 0.65                                 2.6
               18                                 0.75                                 3.2
               17                                 1.04                                 4.1
               16                                 1.31                                 5.2
               15                                 1.65                                 6.6
               14                                  2.5                                 8.3
               13                                  2.6                                 5.1
               12                                   4                                 5.13
               11                                 4.15                                6.16
               10                                   6                                 2.21
               9                                  6.62                                5.26
               8                                  8.36                                33.3
               7                                  10.6                                44.2


4. Find the section kernel

        Section kernel =     𝑃

                        = 200

                        = 14.4 cm2

Thus, the size of the centre core is 14.4 cm2. We can use any combination of length and width to get the
area. For example, 3.8 cm x 3.8 cm = 14.4 cm2

        L= 3.8 cm

        W= 3.8 cm
Sulaim b. Ab Qais                                                                                   2012




        Width,W




                                                                                                           Length,L




5. Calculate the number of turn for primary windings.

        Turn per volt   = 42/section kernel

                        *42 is a constant

                        = 3 turns/volt

        No of turn (primary) , Np        = 3 x 230

                                         = 690 turn

6. Calculate the no. of turn for secondary windings (refer table above)

        No of turn (primary) , Ns        = 3 x 40

                                         = 120 turn




SELECTED Q & A

1. Why primary windings and secondary windings of the transformer didn’t short circuit?

The windings will act as an inductor when AC current flow in it, blocking the high current. Though
voltage is applied, current flowing, impedance also exists. That's why the transformer doesn't get short
circuited. Insufficient number of coil due to miscalculation will result in short circuit.
Sulaim b. Ab Qais                                                                                   2012


2. Is a transformer is obeying ohm's law or not?

Ohms law is for determining the behavior of electricity through a load (a resistor). Transformer is
nothing more than a pair of inductor. A transformer by itself is not a load. You apply Ohms law
separately to the primary circuit and to the secondary circuit of a transformer. You do not use Ohms law
to learn how the primary induces current in the secondary. The current that we calculate is the
maximum (short circuit) or ideal transformer current. If we put resistor at any side it still obeys ohm’s
law.

3. Why we usually use magnetic copper wire for the windings?

Magnetic copper have insulation. To build a transformer, solenoid or inductor each turning wire cannot
short with the other from the side.




REFERENCE

1.      http://www.construyasuvideorockola.com/construc01.php

2.      http://answers.yahoo.com/question/index?qid=20090705145110AAjSE33

3.      Suruhanjaya Tenaga Malaysia (ST).

Más contenido relacionado

La actualidad más candente

Instrument Transformers
Instrument TransformersInstrument Transformers
Instrument TransformersRidwanul Hoque
 
Transformer Designing
Transformer Designing Transformer Designing
Transformer Designing Praveen Sharma
 
Design of stator & rotor for Wound Induction Motor
Design of stator & rotor for Wound Induction MotorDesign of stator & rotor for Wound Induction Motor
Design of stator & rotor for Wound Induction MotorParth Patel
 
Solutions manual -hadi saadat-power systems analysis - 2nd edition (2002)
Solutions manual -hadi saadat-power systems analysis - 2nd edition (2002)Solutions manual -hadi saadat-power systems analysis - 2nd edition (2002)
Solutions manual -hadi saadat-power systems analysis - 2nd edition (2002)Engr umar
 
Transformer design by s u khaparkar
Transformer design by s u khaparkarTransformer design by s u khaparkar
Transformer design by s u khaparkarexhod
 
Commutation in DC Machines
Commutation in DC Machines Commutation in DC Machines
Commutation in DC Machines Dinesh Sharma
 
Three Phase Induction Motor & Its Application
Three Phase Induction Motor & Its ApplicationThree Phase Induction Motor & Its Application
Three Phase Induction Motor & Its ApplicationImranHossain296
 
Design of Three Phase 11000/433 V And 100 KVA Transformer
Design of Three Phase 11000/433 V And 100 KVA TransformerDesign of Three Phase 11000/433 V And 100 KVA Transformer
Design of Three Phase 11000/433 V And 100 KVA TransformerSanjoy Biswas
 
Chapter 4 synchronous machine
Chapter 4 synchronous machineChapter 4 synchronous machine
Chapter 4 synchronous machinemkazree
 
Assignment & solution (selected)
Assignment & solution (selected)Assignment & solution (selected)
Assignment & solution (selected)efrataderebe
 
Presentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformerPresentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformerSMDDTech
 
Basic Presentation on Speed control of induction motor
Basic Presentation on Speed control of induction motorBasic Presentation on Speed control of induction motor
Basic Presentation on Speed control of induction motorNileshBambhaniya2
 
Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector groupShyamkant Vasekar
 
A presentation on inverter by manoj
A presentation on inverter by manojA presentation on inverter by manoj
A presentation on inverter by manojIACM SmartLearn Ltd.
 
Three phase transformer
Three phase transformer Three phase transformer
Three phase transformer Muhammadhamad24
 
Transformer design-and-design-parameters
Transformer design-and-design-parametersTransformer design-and-design-parameters
Transformer design-and-design-parametersMubarak Suliman
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection michaeljmack
 

La actualidad más candente (20)

Instrument Transformers
Instrument TransformersInstrument Transformers
Instrument Transformers
 
Transformer Designing
Transformer Designing Transformer Designing
Transformer Designing
 
33/11 KV SUBSTATION
33/11 KV SUBSTATION33/11 KV SUBSTATION
33/11 KV SUBSTATION
 
Design of stator & rotor for Wound Induction Motor
Design of stator & rotor for Wound Induction MotorDesign of stator & rotor for Wound Induction Motor
Design of stator & rotor for Wound Induction Motor
 
armature Winding
armature Windingarmature Winding
armature Winding
 
Solutions manual -hadi saadat-power systems analysis - 2nd edition (2002)
Solutions manual -hadi saadat-power systems analysis - 2nd edition (2002)Solutions manual -hadi saadat-power systems analysis - 2nd edition (2002)
Solutions manual -hadi saadat-power systems analysis - 2nd edition (2002)
 
Transformer design by s u khaparkar
Transformer design by s u khaparkarTransformer design by s u khaparkar
Transformer design by s u khaparkar
 
Commutation in DC Machines
Commutation in DC Machines Commutation in DC Machines
Commutation in DC Machines
 
Three Phase Induction Motor & Its Application
Three Phase Induction Motor & Its ApplicationThree Phase Induction Motor & Its Application
Three Phase Induction Motor & Its Application
 
Transformer Design
Transformer DesignTransformer Design
Transformer Design
 
Design of Three Phase 11000/433 V And 100 KVA Transformer
Design of Three Phase 11000/433 V And 100 KVA TransformerDesign of Three Phase 11000/433 V And 100 KVA Transformer
Design of Three Phase 11000/433 V And 100 KVA Transformer
 
Chapter 4 synchronous machine
Chapter 4 synchronous machineChapter 4 synchronous machine
Chapter 4 synchronous machine
 
Assignment & solution (selected)
Assignment & solution (selected)Assignment & solution (selected)
Assignment & solution (selected)
 
Presentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformerPresentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformer
 
Basic Presentation on Speed control of induction motor
Basic Presentation on Speed control of induction motorBasic Presentation on Speed control of induction motor
Basic Presentation on Speed control of induction motor
 
Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector group
 
A presentation on inverter by manoj
A presentation on inverter by manojA presentation on inverter by manoj
A presentation on inverter by manoj
 
Three phase transformer
Three phase transformer Three phase transformer
Three phase transformer
 
Transformer design-and-design-parameters
Transformer design-and-design-parametersTransformer design-and-design-parameters
Transformer design-and-design-parameters
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
 

Similar a Transformer design

Experimental study on polypropylene fiber reinforced moderate deep beam
Experimental study on polypropylene fiber reinforced moderate deep beamExperimental study on polypropylene fiber reinforced moderate deep beam
Experimental study on polypropylene fiber reinforced moderate deep beamIAEME Publication
 
2.1 2.4 presentation
2.1 2.4 presentation2.1 2.4 presentation
2.1 2.4 presentationdinomtruck
 
SPICE MODEL of 2SK2962 (Professional+BDP Model) in SPICE PARK
SPICE MODEL of 2SK2962 (Professional+BDP Model) in SPICE PARKSPICE MODEL of 2SK2962 (Professional+BDP Model) in SPICE PARK
SPICE MODEL of 2SK2962 (Professional+BDP Model) in SPICE PARKTsuyoshi Horigome
 
Process parameters optimization for surface roughness in edm for aisi d2 steel
Process parameters optimization for surface roughness in edm for aisi d2 steelProcess parameters optimization for surface roughness in edm for aisi d2 steel
Process parameters optimization for surface roughness in edm for aisi d2 steelIAEME Publication
 
FreakonomicsOfScrum spreadsheet
FreakonomicsOfScrum spreadsheetFreakonomicsOfScrum spreadsheet
FreakonomicsOfScrum spreadsheetMaxim Dorofeev
 
Torsion testing experiment (instructor)
Torsion testing experiment (instructor)Torsion testing experiment (instructor)
Torsion testing experiment (instructor)Sulaiman Dawood Barry
 
SPICE MODEL of 2SK2989 (Professional+BDP Model) in SPICE PARK
SPICE MODEL of 2SK2989 (Professional+BDP Model) in SPICE PARKSPICE MODEL of 2SK2989 (Professional+BDP Model) in SPICE PARK
SPICE MODEL of 2SK2989 (Professional+BDP Model) in SPICE PARKTsuyoshi Horigome
 
Sac+mn or ce presentation
Sac+mn or ce presentationSac+mn or ce presentation
Sac+mn or ce presentationnclee715
 
20110617 EC Seminar
20110617 EC Seminar20110617 EC Seminar
20110617 EC Seminarsuwaws
 
SPICE MODEL of 2SK2962 (Standard+BDS Model) in SPICE PARK
SPICE MODEL of 2SK2962 (Standard+BDS Model) in SPICE PARKSPICE MODEL of 2SK2962 (Standard+BDS Model) in SPICE PARK
SPICE MODEL of 2SK2962 (Standard+BDS Model) in SPICE PARKTsuyoshi Horigome
 
Energy consumption in slovenia and at etrš 1
Energy consumption in slovenia and at etrš 1Energy consumption in slovenia and at etrš 1
Energy consumption in slovenia and at etrš 1Maija Liepa
 
SPICE MODEL of 2SK3111 (Professional+BDP Model) in SPICE PARK
SPICE MODEL of 2SK3111 (Professional+BDP Model) in SPICE PARKSPICE MODEL of 2SK3111 (Professional+BDP Model) in SPICE PARK
SPICE MODEL of 2SK3111 (Professional+BDP Model) in SPICE PARKTsuyoshi Horigome
 
Datasheet - Aerospace
Datasheet - AerospaceDatasheet - Aerospace
Datasheet - AerospaceGagan Sood
 
Datasheet - Nuclear and Power
Datasheet - Nuclear and PowerDatasheet - Nuclear and Power
Datasheet - Nuclear and PowerGagan Sood
 
M Page ScicomP14 Hd3D
M Page ScicomP14 Hd3DM Page ScicomP14 Hd3D
M Page ScicomP14 Hd3Dmpage_colo
 
SPICE MODEL of SSM3J112TU (Professional+BDP Model) in SPICE PARK
SPICE MODEL of SSM3J112TU (Professional+BDP Model) in SPICE PARKSPICE MODEL of SSM3J112TU (Professional+BDP Model) in SPICE PARK
SPICE MODEL of SSM3J112TU (Professional+BDP Model) in SPICE PARKTsuyoshi Horigome
 
SPICE MODEL of 2SK3109 (Standard+BDS Model) in SPICE PARK
SPICE MODEL of 2SK3109 (Standard+BDS Model) in SPICE PARKSPICE MODEL of 2SK3109 (Standard+BDS Model) in SPICE PARK
SPICE MODEL of 2SK3109 (Standard+BDS Model) in SPICE PARKTsuyoshi Horigome
 

Similar a Transformer design (20)

Metrado de madera
Metrado de maderaMetrado de madera
Metrado de madera
 
Experimental study on polypropylene fiber reinforced moderate deep beam
Experimental study on polypropylene fiber reinforced moderate deep beamExperimental study on polypropylene fiber reinforced moderate deep beam
Experimental study on polypropylene fiber reinforced moderate deep beam
 
2.1 2.4 presentation
2.1 2.4 presentation2.1 2.4 presentation
2.1 2.4 presentation
 
E0432832
E0432832E0432832
E0432832
 
SPICE MODEL of 2SK2962 (Professional+BDP Model) in SPICE PARK
SPICE MODEL of 2SK2962 (Professional+BDP Model) in SPICE PARKSPICE MODEL of 2SK2962 (Professional+BDP Model) in SPICE PARK
SPICE MODEL of 2SK2962 (Professional+BDP Model) in SPICE PARK
 
Process parameters optimization for surface roughness in edm for aisi d2 steel
Process parameters optimization for surface roughness in edm for aisi d2 steelProcess parameters optimization for surface roughness in edm for aisi d2 steel
Process parameters optimization for surface roughness in edm for aisi d2 steel
 
FreakonomicsOfScrum spreadsheet
FreakonomicsOfScrum spreadsheetFreakonomicsOfScrum spreadsheet
FreakonomicsOfScrum spreadsheet
 
Torsion testing experiment (instructor)
Torsion testing experiment (instructor)Torsion testing experiment (instructor)
Torsion testing experiment (instructor)
 
FULL TIME SUPPORT QUOTAS MARCH 2011
FULL TIME SUPPORT QUOTAS MARCH 2011FULL TIME SUPPORT QUOTAS MARCH 2011
FULL TIME SUPPORT QUOTAS MARCH 2011
 
SPICE MODEL of 2SK2989 (Professional+BDP Model) in SPICE PARK
SPICE MODEL of 2SK2989 (Professional+BDP Model) in SPICE PARKSPICE MODEL of 2SK2989 (Professional+BDP Model) in SPICE PARK
SPICE MODEL of 2SK2989 (Professional+BDP Model) in SPICE PARK
 
Sac+mn or ce presentation
Sac+mn or ce presentationSac+mn or ce presentation
Sac+mn or ce presentation
 
20110617 EC Seminar
20110617 EC Seminar20110617 EC Seminar
20110617 EC Seminar
 
SPICE MODEL of 2SK2962 (Standard+BDS Model) in SPICE PARK
SPICE MODEL of 2SK2962 (Standard+BDS Model) in SPICE PARKSPICE MODEL of 2SK2962 (Standard+BDS Model) in SPICE PARK
SPICE MODEL of 2SK2962 (Standard+BDS Model) in SPICE PARK
 
Energy consumption in slovenia and at etrš 1
Energy consumption in slovenia and at etrš 1Energy consumption in slovenia and at etrš 1
Energy consumption in slovenia and at etrš 1
 
SPICE MODEL of 2SK3111 (Professional+BDP Model) in SPICE PARK
SPICE MODEL of 2SK3111 (Professional+BDP Model) in SPICE PARKSPICE MODEL of 2SK3111 (Professional+BDP Model) in SPICE PARK
SPICE MODEL of 2SK3111 (Professional+BDP Model) in SPICE PARK
 
Datasheet - Aerospace
Datasheet - AerospaceDatasheet - Aerospace
Datasheet - Aerospace
 
Datasheet - Nuclear and Power
Datasheet - Nuclear and PowerDatasheet - Nuclear and Power
Datasheet - Nuclear and Power
 
M Page ScicomP14 Hd3D
M Page ScicomP14 Hd3DM Page ScicomP14 Hd3D
M Page ScicomP14 Hd3D
 
SPICE MODEL of SSM3J112TU (Professional+BDP Model) in SPICE PARK
SPICE MODEL of SSM3J112TU (Professional+BDP Model) in SPICE PARKSPICE MODEL of SSM3J112TU (Professional+BDP Model) in SPICE PARK
SPICE MODEL of SSM3J112TU (Professional+BDP Model) in SPICE PARK
 
SPICE MODEL of 2SK3109 (Standard+BDS Model) in SPICE PARK
SPICE MODEL of 2SK3109 (Standard+BDS Model) in SPICE PARKSPICE MODEL of 2SK3109 (Standard+BDS Model) in SPICE PARK
SPICE MODEL of 2SK3109 (Standard+BDS Model) in SPICE PARK
 

Más de sulaim_qais

2018867974 sulaim (2)
2018867974 sulaim (2)2018867974 sulaim (2)
2018867974 sulaim (2)sulaim_qais
 
38 GHz rectangular patch antenna CST
38 GHz rectangular patch antenna CST38 GHz rectangular patch antenna CST
38 GHz rectangular patch antenna CSTsulaim_qais
 
Super heterodyne
Super heterodyneSuper heterodyne
Super heterodynesulaim_qais
 
Phase lock loop (pll)
Phase lock loop (pll)Phase lock loop (pll)
Phase lock loop (pll)sulaim_qais
 
Notes about Lynas advanced material plan (lamp)
Notes about Lynas advanced material plan (lamp)Notes about Lynas advanced material plan (lamp)
Notes about Lynas advanced material plan (lamp)sulaim_qais
 
Something about Antenna design
Something about Antenna designSomething about Antenna design
Something about Antenna designsulaim_qais
 
Rectangular patch Antenna
Rectangular patch AntennaRectangular patch Antenna
Rectangular patch Antennasulaim_qais
 
Malaysia Television services
Malaysia Television servicesMalaysia Television services
Malaysia Television servicessulaim_qais
 
FTTx Malaysia Standard
FTTx Malaysia StandardFTTx Malaysia Standard
FTTx Malaysia Standardsulaim_qais
 
Fiber Optic Termination
Fiber Optic TerminationFiber Optic Termination
Fiber Optic Terminationsulaim_qais
 

Más de sulaim_qais (10)

2018867974 sulaim (2)
2018867974 sulaim (2)2018867974 sulaim (2)
2018867974 sulaim (2)
 
38 GHz rectangular patch antenna CST
38 GHz rectangular patch antenna CST38 GHz rectangular patch antenna CST
38 GHz rectangular patch antenna CST
 
Super heterodyne
Super heterodyneSuper heterodyne
Super heterodyne
 
Phase lock loop (pll)
Phase lock loop (pll)Phase lock loop (pll)
Phase lock loop (pll)
 
Notes about Lynas advanced material plan (lamp)
Notes about Lynas advanced material plan (lamp)Notes about Lynas advanced material plan (lamp)
Notes about Lynas advanced material plan (lamp)
 
Something about Antenna design
Something about Antenna designSomething about Antenna design
Something about Antenna design
 
Rectangular patch Antenna
Rectangular patch AntennaRectangular patch Antenna
Rectangular patch Antenna
 
Malaysia Television services
Malaysia Television servicesMalaysia Television services
Malaysia Television services
 
FTTx Malaysia Standard
FTTx Malaysia StandardFTTx Malaysia Standard
FTTx Malaysia Standard
 
Fiber Optic Termination
Fiber Optic TerminationFiber Optic Termination
Fiber Optic Termination
 

Transformer design

  • 1. Sulaim b. Ab Qais 2012 DESIGN A TRANSFORMER This paper guides a simple and practical calculation in designing a transformer. The hands-on work can be understood from this video http://www.youtube.com/watch?v=s6NyTprQCBI MATERIALS Masking tape, wax paper, copper cable, magnet copper wire, sandpaper, silicon-iron sheet, formwork, soldering wire CALCULATION 1. Determine the load power, P. Let say, P=300W 2. Find the primary winding current. Malaysia using 230 VAC, +10%,-6%, thus the current would be; Ip = P/V Ip = 200W/230V = 0.87 A, thus the wire that we will using for primary winding is 0.26 mm2 Let say the secondary winding voltage, Vs = 40 VAC Is = 200W/40V = 5 A, thus the wire that we will using for secondary windings is 1.31 mm2 3. Find the size of the cable for primary windings and secondary windings. By referring to the table below we can determine the size of primary and secondary coil (magnet wire). Table: cable size for safe current carrying capacity American Wire Gauge (AWG) Area size (mm2) Current (max) 30 0.05 0.22 29 0.06 0.29 28 0.08 0.3 27 0.1 0.4
  • 2. Sulaim b. Ab Qais 2012 26 0.14 0.5 25 0.16 0.6 24 0.25 0.8 23 0.26 1.0 22 0.34 1.2 21 0.38 1.6 20 0.5 2 19 0.65 2.6 18 0.75 3.2 17 1.04 4.1 16 1.31 5.2 15 1.65 6.6 14 2.5 8.3 13 2.6 5.1 12 4 5.13 11 4.15 6.16 10 6 2.21 9 6.62 5.26 8 8.36 33.3 7 10.6 44.2 4. Find the section kernel Section kernel = 𝑃 = 200 = 14.4 cm2 Thus, the size of the centre core is 14.4 cm2. We can use any combination of length and width to get the area. For example, 3.8 cm x 3.8 cm = 14.4 cm2 L= 3.8 cm W= 3.8 cm
  • 3. Sulaim b. Ab Qais 2012 Width,W Length,L 5. Calculate the number of turn for primary windings. Turn per volt = 42/section kernel *42 is a constant = 3 turns/volt No of turn (primary) , Np = 3 x 230 = 690 turn 6. Calculate the no. of turn for secondary windings (refer table above) No of turn (primary) , Ns = 3 x 40 = 120 turn SELECTED Q & A 1. Why primary windings and secondary windings of the transformer didn’t short circuit? The windings will act as an inductor when AC current flow in it, blocking the high current. Though voltage is applied, current flowing, impedance also exists. That's why the transformer doesn't get short circuited. Insufficient number of coil due to miscalculation will result in short circuit.
  • 4. Sulaim b. Ab Qais 2012 2. Is a transformer is obeying ohm's law or not? Ohms law is for determining the behavior of electricity through a load (a resistor). Transformer is nothing more than a pair of inductor. A transformer by itself is not a load. You apply Ohms law separately to the primary circuit and to the secondary circuit of a transformer. You do not use Ohms law to learn how the primary induces current in the secondary. The current that we calculate is the maximum (short circuit) or ideal transformer current. If we put resistor at any side it still obeys ohm’s law. 3. Why we usually use magnetic copper wire for the windings? Magnetic copper have insulation. To build a transformer, solenoid or inductor each turning wire cannot short with the other from the side. REFERENCE 1. http://www.construyasuvideorockola.com/construc01.php 2. http://answers.yahoo.com/question/index?qid=20090705145110AAjSE33 3. Suruhanjaya Tenaga Malaysia (ST).