Clifford & Snell Hazardous Area Explosion Proof Sounders & Beacons
1. Clifford & Snell
Tom Cribb Road Thamesmead London UK SE28 0BH
Tel: +44 (0) 208 317 1717 or +44 (0) 208 316 4477 Fax: +44 (0) 208 317 2400
Email: sales@cliffordandsnell.com Web: www.cliffordandsnell.com
Audible & Visual Signals
WWW.CABLEJOINTS.CO.UK
THORNE & DERRICK UK
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
2. Clifford & Snell was originally established in 1929 and has a History of pioneering many elec-
tronic systems and devices. In 1967 the company was responsible for the introduction of the
world's first ever electronic sounder. This breakthrough in technology became the foundation
for a long and established role in the manufacture and development of future generations of
product.
The Company offers a comprehensive range, addressing a wide variety of applications and
industry sectors, including Hazardous Area, Industrial and Process Control, through to the Fire
and Security market. The nature of our industry demands quality and reliability at all times and
this is achieved by employing the very latest assembly and manufacturing techniques, within
our UK manufacturing facility.
Our customers require continuous quality of the highest standard and this is achieved through
our BS EN ISO 9001: 2000 Quality Management System, which ensures total control
throughout the entire manufacturing process. Clifford & Snell are committed to maintaining its
product approvals to address the industries needs on a worldwide basis and certification
includes UL, cULus, ATEX, GOST-R, IECEx, EN54-3, VdS and GL.
Areas such as Oil & Gas where Standards & Certification are an
essential part of the design criteria. The Yodalex range of
Explosion Proof Sounders, Strobes and Call Point Stations meet
the necessary industry standards and directives with compliance
to the North American UL, cULus, IECEx, European ATEX, and
for the Russian market, GOST-R, which allows compliance on a
truly global basis.
Industrial & Process Control
Hazardous Area
Industrial & Process Control is an important market and early
indication of a process breakdown, malfunction or overheating is
vital in relation to safety both from the perspective of
safeguarding employees as well as preventing costly equipment
damage and subsequent downtime and loss of productivity. The
Yodalarm sounders and Yodalight sounder/strobes provide an
audible and visual alarm function, with UL, cULus, GL,Vds and
the EN54-3 approval, allowing compatibility with a wide variety
of applications and industries.
Fire & General Signalling
For Fire and General Signalling applications the Yodac range
provides an ideal solution. With sound outputs up to 106dB,
32 international sound tones, AC or DC supply voltages, a
range of lens and strobe options and approvals such as EN54-3,
VdS, UL and cULus, this product offers an ideal signalling
solution across most industry sectors.
For more information visit our web site
www.cliffordandsnell.com
Company Profile
WWW.CABLEJOINTS.CO.UK
THORNE & DERRICK UK
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
3. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.comC l i f f o r d & S n e l l INDEX
DESCRIPTION TYPE
NO.
PAGE
NO.
APPROVALS
HAZARDOUS AREA
Yodalex Sounder UL / ATEX / GOST / IECEx 110 YO6 19 1
Yodalex Sounder/Strobe UL / ATEX / GOST / IECEx 110 YL6 19 1
Intrinsically Safe Sounders ATEX 105/110 YO3/YO4/YO5 21 4
Intrinsically Safe Flashing Beacons ATEX V4IS 21 5
Sounder UL / EN54-3 116/120 YO8/YO8S 21 7
Yodalex Strobe UL / ATEX / GOST / IECEx V6 19 1
INDUSTRIAL / FIRE SOUNDERS & STROBES (YODALARM - YODALIGHT)
Sounder / Strobe UL / EN54-3 116/120 YL8/YL8S 21 7
Sounder UL / EN54-3 / VdS / GL 110 YO5 21 8
Sounder / Strobe UL / EN54-3 / Vds 110 YL5 21 8
Sounder Multi-Stage EN54-3 106/116 YO4 /YO5/YO8 22 11
Sounder UL / EN54-3 / VdS 100 YO3 21 10
Xenon Strobe UL / VdS V4 Xenon 22 12
LED Flashing & Status Beacons V4 LED 22 13
GENERAL PURPOSE SOUNDERS
Carillon Sounder EN54-3 104 CN 22 14
Face Plate Sounder (Quad) EN54-3 96 FP 23 15
Sounder/Strobe EN54-3 100 YL2 23 16
LC Sounder 100 LC 23 17
Door Holder DH 23 18
MISCELLANEOUS
Mains Adaptor MA 23 18
Circuit Security Keyswitch KS 23 18
CLASSIFICATION REFERENCE TABLES 26
dB
Intrinsically Safe Status Beacons ATEX V4IS 21 6
Sounder / Strobe UL / EN54-3 / Vds 106 YL4 21 9
Sounder UL / EN54-3 / VdS 106 YO4 21 9
WIRING
DIAGRAMS
TONE TABLE 24
(See Wiring Diagrams column for Unit association)
WIRING DIAGRAMS 19
to 23
TONE TABLE (FOR USE WITH MULTI-STAGE SOUNDER MODELS YO4 - YO5 - YO8 ONLY) 25
Yodalex Directional Sounder ATEX / GOST / IECEx 115 YO9 20 2
Yodalex Call Point Stations ATEX / GOST / IECEx MCP 20 3
Intrinsically Safe Sounders/Strobes ATEX 105/110 YL4/YL5 21 4
4. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• Omni Directional high output sounder 110dB max @ 1 meter
• 2 stage alarm, independently selectable 2nd
stage
• All units share a common explosion proof housing
• Meets UL, CSA, GOST, ATEX and IECEx Approvals
• ATEX / IECEx Approved for Gas & Dust
• Zone 1 & 2, 21 & 22.
• Dual cable entry, cable in - cable out: c/w ATEX certified plug
and dustcover as standard on ATEX models; UL models
supplied with 2 x 1/2 inch NPT adaptors.
• Aluminium enclosure with stainless steel fasteners.
• Lens guard provided as standard
• Flash rate 1 per second.
• Weather proof flame retardant ABS horn
• 7 Lens colours in flame retardant polycarbonate, Clear (C), Opal (O),
Yellow (Y), Red (R), Amber (A), Blue (B), Green (G).
• Telephone Initiate option available - contact Sales Office
• 32 selectable tones meeting international regulations
• Sound selection via DIL switches.
• Temperature class T4 Standard, Class T6 Optional
TECHNICAL SPECIFICATION
276 (10.9”)
288 (11.3”)
420 (16.5”)
145 (5.7”)
DIMENSIONS mm
ATEX
Controlled document No. D7385-01-06 (CN100301) My Documents SALES DATA data sheetsYodalex
V6 Y06 YL6
OPERATING TEMPERATURES
STANDARD OPTIONAL
European IIB T4 (-35º to +60ºC or T6 (-35º to +40ºC)
European IIB+H2 T4 (-20º to +60ºC or T6 (-20º to +40ºC)
For T6 Class refer to Sales Office
APPROVAL SPECIFICATION
Underwriters Laboratories UL Standards
UL 464, UL 1203, UL 1638
Control No.8N30 (Sounder YO6 and Combined Unit YL6)
Control No.13JM (Strobe V6 only)
UL Classifications
Class I Division 1, Gas Group BCD
Class II Division 1, Gas Group EFG (Strobe V6 only)
CUL Canada
CSA C22.2 No.25-M1966, CSA C22.2 No. 30-M1986
European Standards
EN60079-0:2004 (EN50014:1997+Amendments 1 and 2)
EN60079-1:2004 (EN50018:2000) EN50281-1-1:1998.
ATEX Directive 94/9/EC
Baseefa02ATEX0212X II2 GD Ex d IIB T4 (or T6 see above)
Baseefa02ATEX0222X II2 GD Ex d IIB+H2T4 (or T6 see above)
Russian Approval International Certification
GOST-R IECEx
IIB only IIB+H2
75 (3”)
C l i f f o r d & S n e l l
Explosion Proof Sounders & Beacons
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
GOST-R
MAIN FEATURES
All dimensions quoted are approximate only and subject
to change without notice as are technical features
resulting from continual development and improvement.
Yodalex
Sounder YO6
Combined Sounder Strobe YL6
EU / RU / IN
UL
24Vdc
48Vdc
115Vac
230Vac
Supply Voltage
Certification
CONFIGURATOR
European
USA/Canada
Russian
International
Unit Type
Lens Colour
Strobe V6
24Vdc
48Vdc
115Vac
230Vac
Sounders only YO6
5 Joule 20 Joule10 Joule
Sounder/Strobe YL6
Strobe only V6
V6 OnlyV6 & YL6
or or
• IP66 NEMA 4X
• Sounder/Strobe 24Vdc (YL6) (UL, ATEX, GOST, IECEx) 570mA
• Sounder 24Vdc (YO6) (UL, ATEX, GOST, IECEx) 350mA
• Strobe 24Vdc (V6) 5 J (UL, ATEX, GOST, IECEx) 220mA
• 24Vdc (V6) 10J ( ATEX, GOST, IECEx) 500mA
• 24Vdc (V6) 20J ( ATEX, GOST, IECEx) 1.1A
• 48Vdc (V6) 5J (UL, ATEX, GOST, IECEx) 135mA
• 48Vdc (V6) 10J ( ATEX, GOST, IECEx) 300mA
• 48Vdc (V6) 20J ( ATEX, GOST, IECEx) 560mA
• Sounder 115Vac (YO6) (UL, ATEX, GOST, IECEx) 110mA
• Strobe 115Vac (V6) 5 J (UL, ATEX, GOST, IECEx) 90mA
• 115Vac (V6) 10J ( ATEX, GOST, IECEx) 105mA
• 115Vac (V6) 20J ( ATEX, GOST, IECEx) 260mA
• Sounder/Strobe 115Vac (YL6) 5J (UL, ATEX, GOST, IECEx) 200mA
• Sounder 230Vac (YO6) (UL, ATEX, GOST, IECEx) 55mA
• Strobe 230Vac (V6) 5J (UL, ATEX, GOST, IECEx) 45mA
• 230Vac (V6) 10J ( ATEX, GOST, IECEx) 53mA
• 230Vac (V6) 20J ( ATEX, GOST, IECEx) 170mA
Mounting
Bracket
provided.
2 holes x
M8 clearance
IIB+H2
Gas Group C,D
IIB
Gas group B
IECEx
Telephone Initiate
5. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: cliffordandsnell@aol.com
Web Site: www.cliffordandsnell.com
• High sound output 115dB at 1 metre
• Light weight Glass Reinforced Polyester (GRP) Exd
Enclosure - for use in potentially explosive areas
• Low current consumption
• ATEX / IECEx Approved Gas & Dust. Zones 1 & 2, 21 & 22.
• Enclosure finished in Red High Performance Paint with ABS
Flare Assembly
• 2 stage alarm, independently selectable second stage
• Dual 20mm gland entries. Unit supplied with one approved
stopping plug and one dust cover
• Monitoring facility (DC only)
• Adjustable stainless steel ratchet bracket providing positive
setting
• 32 selectable tones meeting international regulations
• Sound selection via 5 way DIL switch
• Temperature class T6 standard
TECHNICAL SPECIFICATION
• IP 66 rated
• Weight 4.5 Kg
• Sound output 115dB(A) at 1 mtr
• Relative Humidity 95% @ 40ºC
• Certified Temperature Range
-20ºC to +60ºC IIB and IIC
Contact Sales Office for Low Temp. Unit –60°C to +60°C
• Operating Voltage 24Vdc, 48Vdc
115Vac / 230Vac
• Current consumption 24Vdc 300mA
48Vdc 160mA
115Vac 80mA
230Vac 45mA
MAIN FEATURES
Controlled document No.D7500-008-03 (CN100301) H/Data/ALARMS ENG/Data/SALES DATA/ Data Sheet Finals/YO9
MOUNTING
Stainless steel mounting bracket provided. Holes to suit M6,
Pitch 60mm.
Yodalex Standard Temperature
Explosion Proof Sounder
Unit type YO9
IIB
Gas Group
24Vdc
115Vac / 230Vac
APPROVAL SPECIFICATION
European Standards
EN60079-0:2006
EN60079-1:2004
ATEX
Baseefa 08ATEX0189X Ex d IIC T6
Ex tD A21 IP66 Tamb (-20ºC to +60ºC)
Baseefa 08ATEX0191X Ex d IIB T6
Ex tD A21 IP66 Tamb (-20ºC to +60ºC)
International Standards
IEC Ex08.0061X IEC Ex IIC
IEC Ex08.0062X IEC Ex IIB
Russian Approval UL APPROVAL PENDING
GOST-R
316 (12.44’’)
142(5.6”)
Two 20mm gland entries. 1 fitted with
ATEX approved stopping plug and 2nd dust cap
C l i f f o r d & S n e l l
210(8.26”)
DIMENSIONS mm
Supply
Voltage
ATEX
CONFIGURATOR
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
IIC
48Vdc
60(2.4”)
Certification
European
International
210 (8.26’’)
IECEx
Russian
GOST-R
6. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• Break Glass and Push Button Call Point Station
• Light Weight Glass Reinforced Polyester (GRP) Ex d Enclosure
• Dual 20mm gland entries, one fitted with approved stopping plug
(2 * M20 holes located at the top of the Call Point. Glands supplied
separately)
• Monitoring facility (DC only)
• ATEX / IECEx / GOST-R approved Gas and Dust
• Weather resistant high performance red paint finish as standard
• High intensity Red LED can be fitted as an optional extra to indicate
operation. Available up to 24Vdc
• Meets the requirements of BS EN 54-11
• Break Glass version - Optional stainless steel Lift Flap
Test Key provided as standard
• Push Button version - Push to operate - Reset Key provided.
Protection Flap as standard
TECHNICAL SPECIFICATION
• IP 66 rated
• Weight Approx. 1Kg
• Relative Humidity 95% @ 40 degC
• Cetified Temp –55ºC to +70ºC
• Voltage Up to 250V
• Switch Ratings DC 12 - 30V 5A (resitive) or 3A (Inductive)
• 30 - 50V 1A resitive or inductive
• AC 12 - 250V 5A resistive or inductive
• Suitable for Zones 1 & 2, 21 & 22.
• Up to 4 cable entries. Top Entries 2 * as standard.
• Internal earth continuity provided as standard
• 7 way 2.5mm terminal block mounted on a PCB.
• Single Pole change over switch supplied as standard and fitted directly
onto the 7 way connector.
MAIN FEATURES
Controlled document No.D7489-01-02 (CN100301) My DocumentsSALES DATAdata
MOUNTING
Via holes through the Back Box. See Installation Instructions.
Unit type APPROVAL SPECIFICATION
C l i f f o r d & S n e l l
DIMENSIONS (mm)
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
Manual Call Points
Yodalex
Break Glass
Switches
Single Pole
Double Pole
Additional
Options
(User to specify
resistor & diode
values)
Lift FLap
End Of Line Resistor
In line Resistor
IN Line & EOL resistor
Push Button
CONFIGURATOR
Break Glass (BG)
Push Button (PB)
Explosion Proof
132.5 (5.2”)
74 (2.9”)
132.5 (5.2”)
98 (3.9”)
A B
C D
Duty Label (Customer to specify wording)
Tag Label (Customer to specify wording)
LED
Labels
Entries 2 * M20 top entries A+B standard
(Suffix A = AC or D = DC. Example SPD = single pole dc switch)
Finish Red (standard). (Other options upon application)
Standards for Manual Call Points
European Standards (ATEX)
EN60079-0:2006 & EN60079-1:2007
EN61241-0:2004 & EN61241-1:2004
Break Glass Baseefa08ATEX0269 Ex II2 GD Ex tD A21 (Tamb –55°C to +70°C)
Push Button Baseefa08ATEX0269 Ex II2 GD EX tD A21 (Tamb –55°C to +70°C)
International Standards (IECEx)
IEC60079-0:2004 Edition 4 & IEC60079-1:2007 Edition 6
IEC61241-0:2004 Edition 1 & IEC61241-1: 2004 Edition 1
Break Glass IECEx BAS 08.0089 Ex II2 GD Ex tD A21 (Tamb –55°C to +70°C)
Push Button IECEx BAS 08.0089 Ex II2 GD Ex tD A21 (Tamb –55°C to +70°C)
Russian Approval
GOST-R
IECEx
GOST-R
Certification
European
International
Russian
(For other options select positions of entries required and list)
ATEX
7. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• BASEEFA approved
• 2 stage alarm
• Rugged construction
• 32 selectable tones meeting international regulations
• Meets PFEER sound signals recommended by UKOOA
• Enclosure made from ABS flame retardant plastic
• Monitoring facility
• High sound output
• Stainless steel fixings
• Continuously rated
• Sound selection via DIL switch
TECHNICAL SPECIFICATION
• Relative humidity 95% @ 40 deg C
• Weight: YO3is 0.40Kg
YO4is 0.49Kg
YO5is 0.85Kg
• For use in zones 0,1,2
• IP55 rated YO3, YO4 and YL4
• IP56 rated YO5 and YL5
• Volume control fitted on T4 class only
• Operating voltage 12Vdc, 18Vdc or
24Vdc via barriers
• Sound output YO3/4 100dB(A) @ 1 mtr Max
YO5 105dB(A) @ 1 mtr Max
• European models ISC & ISD
• Operating temp –25deg C to +40deg C
• II 1G Ex.ia IIC, T4 or T6 YO3,YO4 and YO5
• II 1G Ex.ia IIC, T4 YL4 and YL5
• Voltage upper limit controlled by barrier
• D7277 Operating & Installation Instructions YO3,YO4 and YO5
• D7441 Operating & Installation Instructions I.S. Beacons
The PFEER sound signals recommended by UKOOA are:
General Alarm Sound Signal 15 Interrupted tone 1000 Hz
PAPA Sound Signal 31 Reverse Sweep 1200-500 Hz
Toxic Gas Sound signal 11 Continuous Tone 1000 Hz
MAIN FEATURES
Intrinsically Safe
Audible and Visual Alarms
T4 Only
YL4
YO3/4
Unit Type Sounder YO3
Opto-coupled
APPROVAL SPECIFICATION
European Standards
Baseefa Certificate No. BAS02ATEX1190X YO3, YO4 and YO5
Baseefa certificate No. Baseefa08ATEX0194X YL4 and YL5
EN60079-0:2006 EN60079-11:2007
C l i f f o r d & S n e l l
YO3 YO4 YO5 YO5/YL5 YO3/YO4/YL4
Mounting: Via internal fixing holes
Sounder YO4
Sounder YO5
Temp Classification
Dim. For YO3 For YO5
Dim A 118 (4.7”) 169 (6.7”)
Dim B 102 (4.0”) 153 (6.0”)
Dim C 89 (3.5”) 134 (5.3”)
Dim D 85 (3.4”) 128 (5.0”)
Dim E 18 (0.7”) 23 (0.9”)
Dim F 6 (0.2”) 8 (0.3”)
European Approved Barriers
(See application notes)
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
DIMENSIONS mm
All dimensions quoted are approximate only and subject to change without notice as are technical
features resulting from continual development and improvement.
CONFIGURATOR
Controlled document No. D7421-01-04 (CN100301)My Documents SALES DATA data sheetsIntrinsically Safe Sounders
ATEX
YO3 - YO4 / YL4 - YO5 / YL5
YO3
Mounting: Via external lugs
2 x Ø F fixing holes
A
D
C
B
C
E
YO4 YO5 YL4 YL5
M20 Cable mounting hole at Dim E
Models Y03 and YO5
Model YL5 (dimensions not shown same
as for YO5)
57.5(2.3”)
88(3.5”) 88(3.5”)
9(0.4”)
276(10.9”)
90(3.5”) 81(3.2”)
81(3.2”) 90(3.5”)
180(7.1”)
Model YO4
Model YL4
YL5
YO5
Combination Unit - YL4
Combination Unit - YL5
YL4 YL5
8. • BASEEFA (ATEX) approved
• 8 LED array allowing condition or status alert in flashing mode
• Continuously rated
• High light intensity
• Long life LED design
• Reliable and simple to install
• Red / White flame retardant ABS plastic enclosure
• Anti static enclosure and lens
• Up to 4 modules in any combination of lens colour ranging
from Red, Amber, Green, Opal, Blue, Clear
• Each beacon should be wired independently.
TECHNICAL SPECIFICATIONDIMENSIONS mm
MAIN FEATURES
Controlled document No. D7471-01-02 (CN100301) My DocumentsSALES DATAdata sheets
MOUNTING
All units are supplied separate from the back box for ease of
installation. The back box should be mounted to a reasonably
flat surface or bulkhead. A gasket is supplied, should the
surface be uneven, or if the unit is to be used in wet
conditions. The installation is completed by fitting the beacon
onto the back box by means of the supplied screws.
LINE MONITORING
Monitoring via reverse polarity
End of line resistor minimum 3K3 ohms 0.5 watts wire-wound
or metal film type
CONFIGURATOR
Unit Type
V4 LED Intrinsically Safe
‘Flashing’ Beacon
Supply Voltage
AmberRed
Base Colours
White
Red Flame
ORDERING INFORMATION
Base Colours:
RF = Red flame
WN = White
RN = Red Normal
All dimensions quoted are approximate only and subject to
change without notice as are technical features resulting
from continual development and improvement.
C l i f f o r d & S n e l l
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
Intrinsically Safe LED ‘Flashing’ Beacons
• For use in Zones 0, 1 and 2
• Operating voltage 12Vdc, 18Vdc, 24Vdc via ATEX
approved barriers
• Operating temp range –20 to + 40deg C
• Storage temp range –40 to + 70deg C
• Relative humidity 90% @ 40deg C
• IP65 rated
• Flash rate 1 per second
• Weight: Single 0.15 Kg, Double 0.3 Kg, Triple 0.45 Kg,
Quad 0.6 Kg
• EEx ia IIC T4
APPROVAL SPECIFICATION
ATEX DIRECTIVE - 9/94/EC
EN 60079-0:2004 (EN50014:1997 + Amendments 1 & 2)
EN60079 –1:2004 (EN50020:2002) EN50284:1999
Baseefa certificate No. BAS05ATEX0075
12, 18 & 24Vdc
Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email:sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
Intrinsically Safe
‘Flashing’ Beacons
2nd
3rd
4th
1st
90 (3.5”)
90 (3.5”)
90 (3.5”)
90 (3.5”)
90 (3.5”)
Green Opal Blue Clear
1st
2nd
3rd
4th
1st 1st
2nd 2nd
1st
3rd
Depth = 81 (3.2”)
Single Double
Triple
Quad
Number of Modules (leave blank if single unit)
or 2,3 or 4
Triple
Quadruple
X
ATEX
Yodac
Single
Double
Lens Colours
Red Normal
9. • BASEEFA (ATEX) approved
• 8 LED array allowing condition or status alert in ‘on or off ’ mode
• Continuously rated
• High light intensity
• Long life LED design
• Reliable and simple to install
• Red / White flame retardant ABS plastic enclosure
• Anti static enclosure and lens
• Up to 4 modules in any combination of lens colour ranging from
Red, Amber, Green, Opal, Blue, Clear
• Each beacon should be wired independently.
TECHNICAL SPECIFICATIONDIMENSIONS mm
MAIN FEATURES
Controlled document No. D7472-01-02 (CN100301) My DocumentsSALES DATAdata sheetsYodac
MOUNTING
All units are supplied separate from the back box for ease of
installation. The back box should be mounted to a reasonably flat
surface or bulkhead. A gasket is supplied, should the surface be
uneven, or if the unit is to be used in wet conditions.
The installation is completed by fitting the beacon onto the back box
by means of the supplied screws.
LINE MONITORING
Monitoring via reverse polarity
End of line resistor minimum 3K3 ohms 0.5 watts wire-wound or
metal film type
CONFIGURATOR
Unit Type
V4 LED Intrinsically Safe
‘Status’ Beacon
Supply Voltage
AmberRed
Lens Colours
Base Colours
White
Red Flame
ORDERING INFORMATION
Base Colours:
RF = Red flame
WN = White
RN = Red Normal
C l i f f o r d & S n e l l
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
Intrinsically Safe LED ‘Status’ Beacons
• For use in Zones 0, 1 and 2
• Operating voltage 12Vdc, 18Vdc, 24Vdc via ATEX
approved barriers
• Operating temp range –20 to + 40deg C
• Storage temp range –40 to + 70deg C
• Relative humidity 90% @ 40deg C
• IP65 rated
• Weight: Single 0.15 Kg, Double 0.3 Kg, Triple 0.45 Kg, Quad
0.6 Kg
• EEx ia IIC T4
APPROVAL SPECIFICATION
ATEX DIRECTIVE - 9/94/EC
EN60079-0:2004 (EN50014:1997 + Amendments 1 & 2)
EN60079-1:2004 (EN50020:2002) EN50284:1999
Baseefa certificate No. BAS05ATEX0075
12, 18 & 24Vdc Via
ATEX approved barriers
Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
Intrinsically Safe
‘Status’ Beacons
2nd
3rd
4th
1st
90 (3.5”)
90 (3.5”)
90 (3.5”)
90 (3.5”)
90 (3.5”)
Green Opal Blue Clear
1st
2nd
3rd
4th
1st 1st
2nd 2nd
1st
3rd
Depth = 81 (3.2”)
Single
Double
Triple
Quad
All dimensions quoted are approximate only and subject
to change without notice as are technical features resulting
from continual development and improvement.
Number of Modules (leave blank if single unit)
or 2,3 or 4
Single
Triple
Quadruple
Double
X
ATEX
Yodac
Red Normal
10. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• 2 stage alarm
• High sound output
• 3 wire polarised DC and AC, or 2 wire bi-polar for DC only
• Independently selectable second stage
• Complies with BS 5839
• Choice of 6 lens colours: Amber (A), Red (R), Green (G),
Opal (O), Blue (B) and Clear (C) made from flame retardant
polycarbonate plastic
• Continuously rated
• Flame retardant ABS plastic enclosure
• Strobe - 2.5 and 5.0 joule.
• Stainless steel fixings
• 32 selectable tones meeting international regulations
• Sound selection via DIL switch
TECHNICAL SPECIFICATION
• Operating temperature –25 to +55 deg C
• Storage temperature –40 to +70 deg C
• Operating voltage 12Vdc, 24Vdc, 48Vdc (UL= 24Vdc only)
115Vac, 230Vac +/- 10%
• DC second stage alarm signal is via polarised or 2 wire
bi-polar connection
• IP 54 rated as std, IP 65 (WR) to order
• Weight YO8 + Super dc = 2.90Kg ac = 3.28Kg
YL8 + Super dc = 3.21Kg ac = 3.58Kg
• Separate input and output terminals on YO8, optional on YL8
• Relative humidity 90% @ 40deg C
• Sound output YO8/YL8 Vdc 116dB(A) at 1 mtr
• Sound output YO8/YL8 Super 120dB(A) at 1 mtr
• Minimum current consumption 300mA
The PFEER sound signals recommended by UKOOA are:
General Alarm Sound Signal 15 Interrupted tone 1000 Hz
PAPA Sound Signal 31 Reverse Sweep 1200-500 Hz
Toxic Gas Sound signal 11 Continuous Tone 1000 Hz
MAIN FEATURES
Controlled document No. D7409-01-04 (CN100301) My DocumentsSALES DATAdata sheetsY08-YL8
MOUNTING
The YO8/YL8 series alarm units should be mounted to a reasonably flat
wall or bulkhead of suitable material using the lugs projecting from the side
of the case. The lugs are bored 10mm on 250mm centres. The minimum
recommended length of fixing screws is 30mm. To maintain the integrity of
the weather seal, the cable must be fitted using a suitable sealed gland.
Unit type
12VdcSupply
Voltage
Red Flame
YO8
YL8/YL8 Super
LINE MONITORING (DC Only)
- 3 Wire 2 stage or 2 wire single stage, monitor via reverse polarity
- 2 Wire 2 stage i.e. bi-polar inputs, monitor via threshold
(applied voltage <1V)
End of line resistor. Minimum 3K3 ohm 0.5 watts, wire-wound or metal
film type.
24Vdc
48Vdc
115Vac
Material
YO8/YL8 YO8/YL8 Super YL8 + SuperYO8 + Super
DIMENSIONS mm
Unit type YL8
12Vdc 2.5 joules
Supply
Voltage
and
Flash
Energy
24Vdc 2.5 joules
24Vdc 5.0 joules
48Vdc 5.0 joules
115Vac 5.0 joules
230Vac 5.0 joules
Lens Colour
Red FlameMaterial
SUPER Units
APPROVAL SPECIFICATION
UL 1638, UL 464
C22.2 No. 205-M1983, CAN/ULC-5526-M87
BS EN 54-3 : 2001 incorporates amendment A1 : 2002
DIN EN 54, Teil 3 (10/01)
VdS 2504 (12/96) VdS 2203 (03/01) VdS 2344 (12/05)
11 (0.4”)
269 (10.6”)
250 (9.8”)
2 x Dia 10
fixing holes
216(8.5”)
57.5(2.3”)
88 (3.5”)
YL ONLY
153 (6.0”)
230Vac
IP65 (std on UL units)
24 (0.9”)
SUPER Units
C l i f f o r d & S n e l l
CONFIGURATOR
M20 Cable
Mounting hole
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
Industrial Audible and Visual Alarm
Yodalarm & Yodalight
Certification USA/Canada
Certification USA/Canada
Vdc Vdc
YO8 + Super YL8 + Super
Vac Vac
All dimensions quoted are approximate only and subject to change
Without notice as are technical features resulting from continual development and improvement.
YO8/YO8 Super
KM91259
IP65 (std on UL units)
11. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• 2 Stage alarm
• 3 wire polarised DC (Not additional voltage option) & AC, or 2 wire
bi-polar for DC only.
• Choice of 6 lens colours: Amber (A), Red (R), Green (G),
Opal (O), Blue (B) and Clear (C) made from flame retardant
polycarbonate plastic
• High sound output
• Complies with BS 5839
• Low current consumption
• Continuously rated
• Robust, reliable and simple to install
• Flame retardant ABS plastic enclosure
• Strobe 2.5 and 5.0 joule
• 32 selectable tones meeting international regulations
• Sound selection via 5 way DIL switch
• Stainless steel fixings
TECHNICAL SPECIFICATION
• Operating temperature UL: -35ºC to +66ºC
• EN54-3 : -25ºC to +55ºC
• VdS: -25ºC to +40ºC
• Operating voltage 12Vdc, 24Vdc, 48Vdc
115Vac, 230Vac +/- 10%
(12Vdc versions will produce approx. 6dB less output)
• Additional voltage options (Sounders only)
Combined 24Vdc and 48Vdc (BT). 110Vdc
• Relative humidity 90% @ 40deg C
• Sound output 110dB(A) at 1 mtr
• IP54 rated as standard. IP65 rated (WR) to order.
• Weight: YO5 dc = 0.71Kg ac = 0.81Kg
YL5 dc = 1.01Kg ac = 1.09Kg
• Volume control allowing 18dB(A) adjustment
• Minimum current consumption 20mA. Sounder only
• Optional independent 2nd stage via second DIL switch (DC only)
MAIN FEATURES
Controlled document No. D7408-01-05 (CN100301) My DocumentsSALES DATAdata sheetsY05-YL5
MOUNTING
The YO5/YL5 series alarm units should be mounted to a reasonably
flat wall or bulkhead of suitable material using the lugs projecting from
the side of the case. The lugs are bored 8mm on 153mm centres. The
minimum recommended length of fixing screws is 25mm. To maintain
the integrity of the weather seal, the cable entry must be fitted using a
suitable sealed gland.
Unit Type
24Vdc
Supply
voltage
Red Flame
YO5
All dimensions quoted are approximate only and subject to change without notice as are
technical features resulting from continual development and improvement.
3 Wire, 2 stage or 2 wire, single stage: - monitor via reverse polarity
2 Wire, 2 stage i.e. bi-polar inputs: - monitor via threshold (applied
voltage <1V)
End of line resistor: - minimum 3K3 ohm, 0.5 watts, wire-wound or
metal film type.
48Vdc
115Vac
230Vac
Material
YO5 Vdc YO5 Vac YL5 Vdc YL5 Vac
DIMENSIONS mm
12Vdc 2.5 joules
Strobe
supply
Voltage
and
Flash
Energy
24Vdc 2.5 joules
24Vdc 5.0 joules
48Vdc 5.0 joules
115Vac 5.0 joules
230Vac 5.0 joules
Lens Colour
Red FlameMaterial
Optional Ind 2nd Stage DC Only
APPROVAL SPECIFICATION
UL 1638, UL 464
C22.2 No. 205-M1983, CAN/ULC-5526-M87
BS EN 54-3 : 2001 incorporates amendment A1 : 2002
DIN EN 54, Teil 3 (10/01)
VdS 2504 (12/96) VdS 2203 (03/01) VdS 2344 (12/05) VdS approval applies
to selected models only. Contact sales for details - Cert. No. G28702
Germanischer Lloyd Approval. (YO5 only)
9 (0.4”)
169 (6.7”)
153 (6”)
2 x Ø8 fixing
holes.
134(5.3”)
57.5(2.3”)
88 (3.5”)
YL ONLY
128 (5.0”)
24Vdc and 48Vdc
110Vdc
IP65 (std on UL units)
C l i f f o r d & S n e l l
IP65 (std on UL units)
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
CONFIGURATOR
M20 Cable
Mounting hole
23 (0.9”)
Industrial Audible and Visual Alarm
Yodalarm & Yodalight
Certification USA/Canada
Certification USA/Canada
Unit Type YL5
YL5 YO5
KM91259
VdS
G L
12Vdc ( NOT BS EN 54-3 )
Optional Ind 2nd Stage DC Only LINE MONITORING (DC ONLY) excludes
additional voltage options
Certification Vds (dc only)
Certification Vds (dc only)
12. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• 2 Stage alarm
• High sound output
• 3 wire polarised DC (Not additional voltage option) & AC, or 2 wire bi-
polar for DC only.
• 3 wire AC second stage control
• Complies with BS 5839
• Strobe 2.5 and 5 joule.
• Choice of 6 lens colours: Amber (A), Red (R), Green (G),
Opal (O), Blue (B) and Clear (C) made from flame retardant
polycarbonate plastic
• Red / white flame retardant ABS plastic enclosure.
• Continuously rated
• Flush mounting base available
• 32 selectable tones meeting international regulations
• Sound selection via 5 way DIL switch
TECHNICAL SPECIFICATION
• Operating temperature UL: -35ºC to +66ºC
• EN54-3: -25ºC to +55ºC
• VdS: -25ºC to +40ºC
• Operating voltage 12Vdc, 24Vdc, 48Vdc
115Vac, 230Vac +/- 10%
(12Vdc versions will produce approx. 6dB less output)
• Additional voltage options (Sounders only)
Combined 24Vdc and 48Vdc (BT)
110Vdc
• Relative humidity 95% @ 40 deg C
• Sound output 106dB(A) at 1 mtr
• IP54 rated as standard. Rated IP65 (WR) to order
• Weight: YO4 dc = 0.25Kg ac = 0.35Kg
YL4 dc = 0.51Kg ac = 0.57Kg
• Volume control allowing 18dB(A) adjustment
• Minimum current consumption 20mA
• Optional independent 2nd stage via second DIL switch (DC only)
MAIN FEATURES
Controlled document No. D7406-01-05 (CN100301) My DocumentsSALES DATAdata sheetsY04-YL4
MOUNTING
The YO4/YL4 series alarm should be mounted to a reasonably flat wall or
bulkhead of suitable material using the internal fixing holes. The recom-
mended fixing screws are dia 4.5 mm max x 20 mm long. To maintain the
integrity of the weather seal, the cable must be fitted
using a suitable sealed gland.
Unit type
24Vdc
Supply
Voltage
Red Flame
YO4
All dimensions quoted are approximate only and subject to change without notice
as are technical features resulting from continual development and improvement.
YL4
LINE MONITORING (DC Only) excludes
additional voltage options
3 Wire, 2 stage or 2 wire, single stage: - monitor via reverse polarity
2 Wire, 2 stage i.e. bi-polar inputs: - monitor via threshold (applied
voltage <1V)
End of line resistor: - minimum 3K3 ohm, 0.5 watts, wire-wound or metal
film type.
48Vdc
115Vac
230Vac
Material
Red Normal
White
YO4 Vdc YO4 Vac YL4 Vdc YL4 Vac
DIMENSIONS mm
12Vdc 2.5 joulesStrobe
Supply
Voltage
and
Flash
Energy
24Vdc 2.5 joules
24Vdc 5.0 joules
48Vdc 5.0 joules
115Vac 5.0 joules
230Vac 5.0 joules
Lens Colour
Red FlameMaterial
Red Normal
White
90 (3.5”)
81 (3.2”)
183 (7.2”)
APPROVAL SPECIFICATION
UL 1638, UL 464
C22.2 No. 205-M1983, CAN/ULC-5526-M87
BS EN 54-3 : 2001 incorporates amendment A1 : 2002
DIN EN 54, Teil 3 (10/01)
VdS 2504 (12/96) VdS 2203 (03/01) VdS 2344 (12/05) - Cert. No.G28702
VdS approval applies to selected models only. Contact sales for details
C l i f f o r d & S n e l l
CONFIGURATOR
IP65 (std on UL units)
Optional Ind 2nd Stage DC Only
IP65 (std on UL units)
Optional Ind 2nd Stage DC Only
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
Industrial Audible and Visual Alarm
Yodac
24Vdc and 48Vdc
110Vdc
Certification USA/Canada
Certification USA/Canada
Unit Type YL4
KM91259
YO4
VdS
12Vdc (NOT BS EN 54-3)
Certification Vds (DC Only)
Certification Vds (DC Only)
13. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• 2 stage alarm
• 3 wire polarised DC (Not additional voltage option) & AC, or
2 wire bi-polar for DC only
• 3 wire AC second stage control
• Complies with BS 5839
• Flame retardant ABS plastic enclosure
• Stainless steel fixings
• Continuously rated
• 32 Selectable tones meeting international regulations
• Sound selection via 5 way DIL switch
TECHNICAL SPECIFICATION
• Operating temperature range –25 to +55 deg C
• Storage temperature range –40 deg C to +70 deg C
• Operating voltage 12Vdc, 24Vdc, 48Vdc
115Vac, 230Vac +/- 10%
(12Vdc versions will produce approx. 6dB less output)
• Additional voltage options (Sounders only)
24Vdc and 48Vdc (BT)
110Vdc
• Relative humidity 90% @ 40deg C
• Sound output 100dB(A) @ 1mtr
• Weight dc = 0.32Kg ac = 0.39Kg
• IP 54 rated as standard. Rated IP 65 (WR) to order
• Volume control allowing 18dB(A) adjustment
• Minimum current consumption 20mA
• Optional independent 2nd stage via second DIL switch
DIMENSIONS mm
MAIN FEATURES
Controlled document No. D7405-01-04 (CN100301) My DocumentsSALES DATAdata sheetsY03
MOUNTING
The YO3 series alarm should be mounted to a reasonably flat wall or
bulkhead of suitable material using the lugs projecting from the side of
the case. The lugs are bored 6mm clearance on 102mm centres. The
minimum recommended length of fixing screws is 25mm. To maintain
the integrity of the weather seal, the cable must be fitted using a
suitable sealed gland.
Unit type
Material
Red Flame
118 (4.7”)
Industrial Audible Alarm
Yodalarm
YO3
All dimensions quoted are approximate only and subject to change without notice as are
technical features resulting from continual development and improvement.
102 (4”)
89 (3.5”)
85 (3.4”)
89 (3.5”)
18 (0.7”)
M20 Cable
Mounting
hole
3 Wire, 2 stage or 2 wire, single stage: - monitor via reverse polarity
2 Wire, 2 stage i.e. bi-polar inputs: - monitor via threshold (applied
voltage <1V)
End of line resistor: - minimum 3K3 ohm, 0.5 watts, wire-wound or
metal film type.
2 x Ø6 Fixing Holes
APPROVAL SPECIFICATION
UL 464
C22.2 No.205-M1983
BS EN 54-3 : 2001 incorporates amendment A1 : 2002
DIN EN 54, Teil 3 (10/01)
VdS 2504 (12/96) VdS 2203 (03/01) VdS 2344 (12/05)
Cert. No. G28702
C l i f f o r d & S n e l l
IP 65 (std on UL units)
CONFIGURATOR
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
KM
24Vdc and 48Vdc
110Vdc
Certification USA/Canada
Vdc Vac
Supply
voltage
VdS
12Vdc
(NOT BS EN 54-3)
24Vdc
48Vdc
115Vac
230Vac
LINE MONITORING (DC ONLY) excludes
additional voltage options
Optional Independant
2nd Stage DC only
(Standard on UL Models)
Certification Vds (DC Only)
14. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• Up to 8 individually selectable stages
• 32 selectable tones meeting international regulations
• Each stage is determined by a 5 way DIL switch
(For switch settings see Tone Table Page 22)
• Complies with BS 5839
• Red flame retardant ABS plastic enclosure.
• Continuously rated
• Can be used in conjunction with the V4 range of
beacons to form a combination Sounder/Strobe
MAIN FEATURES
Controlled document No. D7473-01-01 (CN100047)My DocsSALES DATAdata sheets
MOUNTING
The YO4/YO5/YO8 series alarm should be mounted to a
reasonably flat wall or bulkhead of suitable material using the
internal fixing holes for YO4 or the external lugs for YO5/YO8.
Recommended fixing screws : -
for YO4 = 4.5 mm max dia. x 20 mm long,
for YO5 = 8mm max dia. x 25mm long and
for YO8 = 10mm max dia.x 30mm long.
To maintain the integrity of the weather seal, the cable must be
fitted using a suitable sealed gland.Unit Type
24VdcSupply
Voltage
Red Flame
YO4
All dimensions quoted are approximate only and subject to
change without notice as are technical features resulting
from continual development and improvement.
YO4
LINE MONITORING (DC Only)
2 wire polarised, single stage, monitor via reverse polarity.
End of line resistor, minimum 3K3 ohm, 0.5 watts, wire-wound
or metal film type.
Material
YO4
DIMENSIONS mm
90 (3.5”)
C l i f f o r d & S n e l l
TECHNICAL SPECIFICATION
• Operating temperature –25 to +55 deg C
• Storage temperature –40 to +70 deg C
• Operating voltages +/- 10%
YO4 dc only
YO5 dc or ac
YO8 dc or ac
• Relative humidity 95% @ 40 deg C
• IP65 (WR) as standard
• Weight YO4 0.22Kg
YO5 0.55Kg
YO8 2.50Kg
CONFIGURATOR
IP65 Standard
Multi-Stage
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
Multi-Stage Alarms
YO5
9
(0.4”)
169 (6.7”)
153 (6”)
2 x Ø8
fixing
holes.
YO4YO5 YO5
YO5
YO8
81
(3.2”)
90
(3.5”)
128
(5.0”)
134
(5.3”)
269 (10.6”)
250 (9.8”)
219
(8.6”)
2 x Ø10
fixing
holes
159
(6.3”)
11
(0.4”)
YO4 YO5 YO8
YO8 YO8
YO8
48Vdc
115Vac
230Vac
15. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• Continuously rated
• Strobe 2.5 and 5 joule
• High flash intensity
• 360 degree visibility
• Reliable and simple to install
• Complements audible alarm system
• Flush mounting base available
• Red / White flame retardant ABS plastic enclosure
• Lens colours: Amber (A), Red (R), Green (G), Opal (O),
Blue (B) and Clear (C) made from flame retardant
polycarbonate plastic.
• Steady lamp version available upon request
TECHNICAL SPECIFICATION
• Operating temperature range UL: -35ºC to +66ºC
• EN54-3: -25ºC to +55ºC
• VdS: -25ºC to +40ºC
• Relative humidity 90% @ 40ºC
• IP65 Rated
• Weight: dc = 0.26Kg ac = 0.25Kg
• Operating voltage 12Vdc or 24Vdc or 48Vdc
115Vac or 230Vac
• Current consumption (Flash Energy). See design data below.
DIMENSIONS mm
MAIN FEATURES
Controlled document No. D7410-01-05 (CN100301)My DocumentsSALES DATAdata sheetsV4
MOUNTING
All units are supplied separate from the back box for ease of
installation. The back box must be mounted with the two cable
entries at the top or bottom. The back box should be mounted to
a reasonably flat surface or to a standard wiring box, using any
of the internal mounting holes. A gasket is supplied, should the
surface be uneven, or if the unit is to be used in wet conditions.
To maintain the integrity of the weather seal, the cable must be
fitted using a suitable sealed gland. The installation is completed
by fitting the beacon onto the back box by means of the supplied
screws.
LINE MONITORING
Monitoring via reverse polarity
End of line resistance. Minimum 3K3 ohms 0.5 watts wire-wound
or metal film type
90 (3.5”)
90 (3.5”)
81 (3.2”)
49 (1.9”)
Unit Type
12Vdc 2.5 joules
24Vdc 2.5 joules
Strobe
supply
Voltage
and
Flash
Energy
Lens Colours
Base Colours
All dimensions quoted are approximate only and subject to change without notice as are
technical features resulting from continual development and improvement.
C l i f f o r d & S n e l l
Operating Voltage 12Vdc 24Vdc 48Vdc 115Vac 230Vac
Flash Energy (Joules) 2.5 2.5 - 5 5 5 5
Light output, opal lens
Candela sec 4.5 4.5 - 14 14 14 14
Current consumption
(mA) 300 150 - 250 135 130 70
CAUTION: High voltages are present within the beacon when
operational.
DESIGN DATA
24Vdc 5.0 joules
48Vdc 5.0 joules
115Vac 5.0 joules
230Vac 5.0 joules
Red Flame
Red Normal
White
APPROVAL SPECIFICATION
UL 1638
CAN/ULC-S526-M87
DIN EN 54, Teil 3 (10/01)
VdS 2504(12/96) VdS 2203(03/01) VdS 2344(12/05) - Cert.No.G28714
DC Type AC Type
CONFIGURATOR
Clifford & Snell a division of Signature Industries part of the Digital Angel Corporation
Xenon Strobe - Visual Flashing Alarm
Yodac
Strobe
Certification USA/Canada
VdS
Certification Vds (DC Only)
16. • For use as a Safe Area visual alarm
• 8 or 12 LED array allowing option of ‘status’ or ‘flashing’ mode. See
CONFIGURATOR for coding
• Continuously rated
• High light intensity
• Long life LED design
• Reliable and simple to install
• Red / White flame retardant ABS plastic enclosure
• Up to 4 modules in any combination of lens colour ranging from
Red, Amber, Green, Opal, Blue, Clear
• Each beacon should be wired independently.
TECHNICAL SPECIFICATION
DIMENSIONS mm
MAIN FEATURES
Controlled document No. D7474-01-02 (CN100301) My DocumentsSALES DATA data sheetsYodac
MOUNTING
All units are supplied separate from the back box for ease of
installation. The back box should be mounted to a reasonably flat
surface or bulkhead. A gasket is supplied, should the surface be
uneven, or if the unit is to be used in wet conditions.
The installation is completed by fitting the beacon onto the back box
by means of the supplied screws.
LINE MONITORING
Monitoring via reverse polarity
End of line resistor: - minimum 3K3 ohms, 0.5 watts wire-wound or
metal film type.
CONFIGURATOR
C l i f f o r d & S n e l l
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
LED ‘Flashing’ & ‘Status’ Beacons
Yodac
• Operating voltage 12Vdc/24Vdc
• Operating temp range –20 to + 40deg C
• Storage temp range –40 to + 70deg C
• Relative humidity 90% @ 40deg C
• IP65 rated
• Weight: - Single = 0.15 Kg Double = 0.3 Kg
Triple = 0.45 Kg Quad = 0.6 Kg
Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
‘Flashing’ & ‘Status’
Beacons
2nd
3rd
4th
1st
90 (3.5”) 90 (3.5”)
90 (3.5”)
1st 1st
2nd 2nd
1st
3rd
Depth = 81 (3.2”)
Single Double
Triple
Quad
All dimensions quoted are approximate only and subject
to change without notice as are technical features resulting
from continual development and improvement.
Supply Voltage
AmberRed
Lens Colours
Base Colours
White
Red Flame
Green Opal Blue Clear
1st
2nd
3rd
4th
Number of Modules (leave blank if single
unit)
Single
Triple
Quadruple
Double
Red Normal
24Vdc
12Vdc
Number of LED’s
8 Array
12 Array
‘Flashing’
‘Status’
Unit type
V4 LED
90 (3.5”)
90 (3.5”)
17. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• Versatile compact sounder
• Low current consumption
• High sound output
• 2 stage alarm by 2 wire bi-polar and 3 wire polarised control
• Continuously rated
• Complies with BS 5839
• Easy installation
• For 3 wire 2 stage alarm systems, line integrity maybe
monitored via reverse polarity
• 32 selectable tones meeting international regulations
• Sound selection via 5 way DIL switch
• Red flame retardant ABS plastic enclosure
TECHNICAL SPECIFICATION
• Operating temperature –25 to +40 deg C
• Storage temperature –40 to +70 deg C
• Operating voltage 10 - 30Vdc
• Relative humidity 95% @ 40 deg C
• IP65 rated
• Cable gland entry must be suitably sealed
• Weight 0.28Kg
• Sound output 104dB(A) @ 1 mtr
• Volume control giving 18dB(A) adjustment
• Minimum current consumption 20mA
MAIN FEATURES
Controlled document No. D7412-01-03 (CN100047)My DocumentsSALES DATAdata sheetsCARILLON
MOUNTING
The Carillon alarm units should be mounted to a reasonably flat
wall or bulkhead of suitable material using the internal fixing holes (mounting
gasket supplied).
The recommended fixing screws are dia 4.5max x 20mm long.
To maintain the integrity of the weather seal, the cable must be fitted using a
suitable sealed gland.
Electronic Sounder
LINE MONITORING (DC Only)
3 Wire 2 stage or 2 wire single stage, monitor via reverse polarity
2 Wire 2 stage i.e. bi-polar inputs, monitor via threshold (applied voltage <1V)
End of line resistor: - minimum 3K3 ohm, 0.5 watts, wire-wound or metal
film type.
DIMENSIONS mm
C l i f f o r d & S n e l l
All dimensions are approximate only and subject to change without notice as are technical features resulting
from continual development and improvement
100 (3.9”)
110(4.3”)
90 (3.5”)
80 (3.2”)
50(2”)
APPROVAL SPECIFICATION
BS EN 54-3 : 2001 incorporates amendment A1 : 2002
CONFIGURATOR
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
Unit Type
Supply Voltage 10 - 30Vdc
Material
Carillon
Red Normal
KM91259
18. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• General purpose sounder for indoor use only
• Single stage alarm
• Choice of 4 sound signals
• Suitable as bedhead alarm
• Surface or flush mounting base available
• Red / white flame retardant ABS plastic enclosure
• Complies with BS 5839
• Low current consumption
TECHNICAL SPECIFICATION
• Operating temp range –30 to +55 deg C
• Storage temp –40 to +70 deg C
• Operating voltage 24Vdc +/-10%
• Relative humidity 95% @ 40 deg C
• Approximate weight 0.125 Kg
• IP44 rated
• Sound output 96dB @ 1 mtr
• Minimum current consumption 13mA
MAIN FEATURES
Controlled document No. D7411-01-03 (CN100047)My DocumentsSALES DATAdata sheetsQUADALARM
MOUNTING
The FP series alarm units should be mounted to a reasonably flat
wall or bulkhead of suitable material using the internal fixing holes.
The recommended fixing screws are dia 4.5max x 20mm long.
Face Plate - Electronic
FLUSH TYPE
LINE MONITORING (DC Only)
Line monitoring via reverse polarity
End of line resistor: - minimum 3K3 ohm, 0.5 watts, wire-wound or metal
film type.
Unit Type Yodac Range
Supply Voltage 24Vdc
Base Colour
SurfaceMounting
Flush
TONE TABLE
First Sound Frequency Rep. Selection Link Sound mA
Stage Description Rate A+C B+D
Signal
1 Alternate two-tone 800 -1000 0.5 Y Y 96 20
2 Continuous note 1000 - Y - 95 19
3 Interrupted tone 1000 0.5 - - 95 18
4 Alternate two-tone 430 - 470 1.0 - Y 93 13
Sound output level and current consumption values are for 24Vdc
input supply. Values for 12Vdc are - 6dB(A) and 50% mA of 24Vdc
values. Sound output values are measured at 1 mtr.
Red Normal
White
Face Plate Sounder ORDERING INFORMATION
Base Colours:
RN = Red normal
WN = White
C l i f f o r d & S n e l l
All dimensions quoted are approximate only and subject to change without notice as are technical features
resulting from continual development and improvement.
APPROVAL SPECIFICATION
BS EN 54-3 : 2001 incorporates amendment A1 : 2002
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
CONFIGURATOR
SURFACE TYPE
Flush Type will interface
with standard electrical back
box.
Yodac
92 (3.6”)
92(3.6”)44(1.7”)
21 (0.8”) 23 (0.9”)
KM91259
DIMENSIONS mm
19. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• Fully integrated Sounder Strobe Combination Unit
• Single stage alarm
• Unique compact design
• Suitable for indoor use only
• Continuously rated
• Suitable as bedhead alarm
• Volume control as standard
• Low current consumption
• Separate light, Sound or Combination function
• Parabolic reflector produces high intensity light output (3J)
• Complies with BS5839
• Optional lens colours are available in Red, Amber and Clear
Polycarbonate plastic
• Red/White flame retardant ABS plastic enclosure.
• 32 Selectable tones meeting international regulations
• Sound selection via DIL switch
TECHNICAL SPECIFICATION
• Relative humidity 90% @ 40 deg C
• Operating voltage 24Vdc +/- 10%
• Operating temperature –25 deg C to +40 deg C
• Storage temperature –40 deg C to +70 deg C
• Light output 40 candela (effective) on x-axis
• Flash rate 1 per second
• Sound output 100dB(A) max @ 1mtr
• Minimum current consumption - Strobe 60mA
• Minimum current consumption - Sounder 20mA
• Weight 0.29 Kg
• Separate in - out supply connections for looping to other YL2 units
DIMENSIONS mm
MAIN FEATURES
Controlled document No. D7395-01-03 (CN100047) My DocumentsSALES DATAData SheetsYL2
MOUNTING
The YL2 should be mounted to a reasonably flat wall or bulkhead of
suitable material, using any of the internal mounting holes. The instal-
lation is completed by fitting the unit onto the back box by means of
the screws provided.
105 (4.1”)
105 (4.1”)
Unit Type
24VdcSupply Voltage
Red
Amber
Clear
Lens Colours
Material
19 (0.8”)
45 (1.8”) 36 (1.4”)
20 Dia cable entry hole
Audible and Visual Alarm
YL2
All dimensions quoted are approximate only and subject to change without notice as are
technical features resulting from continual development and improvement.
NOTE: FOR INDOOR USE ONLY
C l i f f o r d & S n e l l
APPROVAL SPECIFICATION
BS EN 54-3 : 2001 incorporates amendment A1 : 2002
Red Normal
White
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
CONFIGURATOR
KM91259
20. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
• Choice of two sound signals
• Surface or flush mount available
• Red / white flame retardant ABS plastic enclosure
• High sound output
• Low current consumption
• Continuously rated
• Complies with BS5839
TECHNICAL SPECIFICATION
• Operating voltage 24Vdc +/-10%
• Operating temp range –25 to +55 deg C
• Relative humidity 95% @ 40 deg C
• IP54 rated
• Sound output 24Vdc 100dB @ 1 mtr
(12Vdc versions will produce approx. 6dB less output)
• Current consumption 24Vdc 30mA
• Weight 0.25Kg
MAIN FEATURES
Controlled document No. D7415-01-03 (CN100047)My DocumentsSALES DATAdata sheets Type LC
MOUNTING
The Low Cost Sounder series alarm units should be mounted to a
reasonably flat wall or bulkhead of suitable material using the internal
fixing holes (mounting gasket supplied). The recommended fixing screws
are dia 4.5 mm max x 20 mm long.
90 (3.5”)
Unit type
24VdcSupply
voltage
Electronic Sounder
Yodac
Yodac
All dimensions quoted are approximate only and subject to change without notice as are technical features
resulting from continual development and improvement.
FOR MONITORING SOUNDER LINES BY SUPPLY
For monitoring Negative Vdc to terminal 1
Positive Vdc to terminal 2
For continuous tone alarm signal Reverse polarity
Polarised input available by cutting LINK
32 (1.3”)
Base Colour Red Normal
White
Low Cost Sounder
DIMENSIONS mm
C l i f f o r d & S n e l l
49 (1.9”)
90 (3.5”)
Base Style
Surface
Flush
FOR MONITORING SOUNDER LINES BY
THRESHOLD VOLTAGE METHOD
For monitoring, Vdc applied must be less than 1 volt
For alarm signal, connect as described below observing polarity
appropriate to alarm selected.
TONE TABLE
Continuous tone (800Hz) Positive Vdc to terminal 1
Negative Vdc to terminal 2
Alternative tones (800Hz/1000Hz) Reverse polarity
Surface
49 (1.9”)
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
CONFIGURATOR
ORDERING INFORMATION
Base Colours:
RN = Red normal
WN = White
9 (0.4”)
Flush Type will interface
with standard electrical back
Flush
21. Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.com
Controlled document No. D7420-01-03 My DocumentsSALES DATAdata sheetsKeyswitch-Mains Adapter and Door Holder
Keyswitch (KS) Mains Adapter
(MA) Door Holder (DH)
C l i f f o r d & S n e l l
MOUNTING
These units should be mounted to a reasonably flat surface of
suitable material using internal fixing holes. The recommended
fixing screws are dia 4.5mm max x 20mm long.
When installing the Door Holder unit, ensure the armature is mounted
in line and secured using the screws provided.
DH KS MA DH DC Version DH AC Version
All dimensions quoted are approximate only and subject to change without
notice as are technical features resulting from continual
development and improvement.
Unit Type
Keyswitch
Mains Adapter
Mains Adapter
Keyswitch
Colour
Red Normal
White
Supply Voltage
Yodac Range
Door Holder
Colour
24Vdc
230Vac
Door Holder
White
DIMENSIONS mm
Keyswitch
Type (KS)
Door Holder
Type (DH)
Mains Adapter
Type (MA)
DATA APPLICABLE TO ALL UNITS:
• Temperature range Operating -25 to +55 deg C
Storage -40 to +70 deg C
• Relative humidity 95% at 40 deg C
• For indoor use only
• Red / white flame retardant ABS plastic enclosure
• Terminal capacity CSA-2.5 mm2
MAIN FEATURES AND SPECIFICATIONS
Keyswitch type KS
• Suitable for security of circuit operation
• Flush mounting base available
• Switch action Single pole changeover
• Contact rating non inductive (A) 2 at 240Vac
4 at 28Vdc
• Number of keys supplied 2
• Approximate weight (g) 120
MAIN FEATURES AND SPECIFICATIONS
Mains Adapter type MA
• An adapter to enable 12Vdc and 24Vdc to be powered from
230Vac mains supply
• Compact design
• Selectable output
• Input supply 230Vac 50/60 Hz
• Output supply 12Vdc or 24Vdc selectable
• Internal fuse 500(mA)
• Maximum output current 300(mA) 12V setting
200(mA) 24V setting
• Approximate weight 290(g)
MAIN FEATURES AND SPECIFICATIONS
Door Holder type DH
• An electromagnetic door holder which can be electrically released in
the event of fire
• Test / override button
• Integral reset
• Supplied complete with armature plate
• Operating voltage 24Vdc, 230Vac 50/60 Hz
• Voltage tolerance dc +/- 25%, ac +/- 10%
• Current consumption dc 80mA, ac 60mA
• Holding force 11.3Kg (25lb)
• Maximum residual force 0.8Kg (1.8lb)
• Approximate weight 0.41 Kg dc
0.45 Kg ac
• IP44 Rated
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
CONFIGURATOR
230Vac
Switching
Voltages
Yodac
90 (3.5”)
All units
90 (3.5”)
All units
41 (1.6”) MA
46 (1.8”) KS
48 (1.9”) DH
22. Controlled document No. D7488-01-01 (CN100047)My Docoments SALES DATADATA SHEETSClifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
Earth
Connection
To Next Sounder
432
TB3
1
34
TB2
2
Sound Selection
Pressure Unit Connector
x
y
TB1
to next strobe
14321
0v
Sounder
& Strobe
Sounder
+24v dc Earth
Strobe
+24v dc
LK2 removed (link 24v dc)
LK1 (link 0v)
(On other side of PCB)
(On other side of PCB)
SW1 SW2
AC ALARM CONNECTION AND SOUND SIGNAL SELECTION
See Tone Table for switch settings
STANDARD DC ALARM CONNECTION AND SOUND SIGNAL SELECTION
See Tone Table for switch settings
Two stage alarm by third core.
Strobe shown with common 0V.
Line monitoring by reversal.
Select alarm stage 1 on SW1.
Select alarm stage 2 on SW2.
NOTE: - The two stage control always operates as follows: -
The first stage sounds by supplying volts to a unit via control switch ’x’. This switch
remains on and the second stage signal is controlled by switching volts to the third
terminal via switch ’y’.
For other options and full operating and installation instructions see website www.cliffordandsnell.com
SOUNDER
STROBE
N
SW—A
SOUNDER
2nd STAGE
CONTROL PANEL
TB1 TB2 TB3 TB4 TB1 TB2 TB3 TB4
TO NEXT
SOUNDER
AND STROBE
Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.comC l i f f o r d & S n e l l
Wiring Diagrams
TYPICAL CONNECTION DIAGRAMS FOR YODALEX FLAMEPROOF AUDIBLE AND VISUAL ALARMS
MODELS V6 - YO6 - YL6
23. Controlled document No. D7491-01-01 (CN100047)My Docoments SALES DATADATA SHEETClifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.comC l i f f o r d & S n e l l
Wiring Diagrams
XENON STROBE - VISUAL ALARM - YODAC - MODEL V4
The power supply for the Xenon Beacons (STROBES) is via the on-board terminal block.
For DC: - Terminal (+) for +ve and Terminal (-) for 0V.
For AC: - Terminal (L) for LIVE and Terminal (N) for NEUTRAL.
CAUTION: - High voltages are present within the beacon when operational.
1 2 3 4 5
1 2 3 4
ON
1 2 3 4 5
1 2 3 4
ON
ELECTRONIC SOUNDER - MODEL CARILLON
0V +ve
(X)
(Y)
(X) 0V +ve
(Y) +ve 0V
VOLUME CONTROL VOLUME CONTROL
LED FLASHING AND STATUS BEACONS - MODEL V4LED
Sound signal selection is made by setting of the PCB mounted switches. For switch settings see the Tone Table on page 21.
MULTI - STAGE ALARMS - MODELS YO4 - YO5 - YO8
The power supply for the Multi-Stage Alarms is via the on-board terminal block.
DC only: - Terminal (+) for +ve and Terminal (-) for 0V.
For all stages connect 0v to terminal 1. For 1st Stage connect +ve to terminal 2. For 2nd Stage connect +ve to
terminal 3, etc., up to 8th Stage with +ve connected to terminal 9.
NOTE: ONLY APPROPRIATE TWO WIRES ARE REQUIRED TO BE CONNECTED FOR EACH STAGE
FOR AC UNITS 0V = NEUTRAL and +ve = LIVE
For Sound Selection all stages have independently selectable 5 way dil switches. SW1 = Stage 1, SW2 = Stage 2, etc.
For sound selection of each stage see the Sound Selection table on page 22.
1st Stage
2nd Stage
8th Stage
1st STAGE
2nd STAGE
24. Controlled document No. D7490-01-01 (CN100047)My Documents SALES DATADATA SHEETClifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.comC l i f f o r d & S n e l l
Wiring Diagrams
INPUT OUTPUT
SUPPLY SUPPLY TO NEXT MODEL
SOUND SELECTION SWITCH VOLUME 4x2 WAY INPUT AND
OPEN=0, CLOSE=1 CONTROL OUTPUT TERMINALS
DC INPUT - 2nd STAGE WITH THIRD WIRE DC INPUT - 2nd STAGE BY SUPPLY REVERSAL
AC INPUT MODELS YL4 - YL5 - YL8
SOUNDERS
MODELS YO3 - YO4 - YO5
INTRINSICALLY SAFE SOUNDERS
MODELS YO3 - YO4 - YO5
INTRINSICALLY SAFE LED’STATUS’ AND ‘FLASHING’ BEACONS
MODELS V4 IS
INDUSTRIAL AUDIBLE AND VISUAL ALARMS YODALARM AND YODALIGHT
MODELS YO8/YL8 - YO8/YL8 SUPER
AC INPUT
DC INPUT
COMBINATION UNITS
25. Controlled document No. D7492-01-01 (CN100047)My Docoments SALES DATADATA SHEET
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.comC l i f f o r d & S n e l l
Wiring Diagrams
KS (KEYSWITCH) - MA (MAINS ADAPTER) - DH (DOOR HOLDER)
QUADALARM - FACE PLATE - ELECTRONIC
TYPE LC - ELECTRONIC SOUNDER
A
B
C
D
0V +ve
A
1000Hz
B C D
1
2
3
4
800Hz
1000Hz
1000Hz
470Hz
430Hz
0.5S
0.5S
1S
Terminal 1
LINK IN
Terminal 2
Sound
+
Cont
--
-- +
Alt
Terminal 1
LINK OUT
Terminal 2
Sound
+
Cont
--
-- +
Off
1 2
TB1
Continuous tone (800Hz) Positive Vdc to Terminal 1
Negative Vdc to Terminal 2
Alternate tones (800 / 1000Hz) Reverse polarity
Connect DC or AC supply to the terminals as labelled.
Earth continuity of cable sheath or conduit is maintained by fitting earth tags to the
entry fittings and linking them together inside the back box.
On AC units the earth wire MUST be connected to terminal marked
AUDIBLE AND VISUAL ALARM– MODEL YL2
DC INPUT– SEPARATE CONTROL OF SOUNDER AND STROBE. DC INPUT - COMMON CONTROL OF SOUNDER AND STROBE
FOR COMBINED SOUNDER AND
STROBE FIT WIRE LINK JOINING
TERMINALS 3 AND 5.
Sound Signal selection is made by setting of the PCB mounted switches. For switch settings see the Tone Table on page 24.
26. Controlled document No. D8157-01-01 (CN100301)My Docoments SALES DATADATA SHEETSClifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
For other options and full operating and installation instructions see website www.cliffordandsnell.com
Tom Cribb Road, Thamesmead,
London SE28 0BH
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
Fax: +44 (0)20 8317 2400
Email: sales@cliffordandsnell.com
Web Site: www.cliffordandsnell.comC l i f f o r d & S n e l l
Wiring Diagrams
TYPICAL CONNECTION DIAGRAMS FOR YODALEX STANDARD TEMP. EXPLOSION PROOF SOUNDER
MODEL YO9
A
MODELS: - BREAK GLASS, PUSH BUTTON
121212
LIVENEUTRALCONTROL
SOUND SELECTION
ON ON
SW 1 SW 2
1 2 3 4 5 1 2 3 4 5
PRESSURE UNIT
CONNECTOR
LIVE
NEUTRAL
SOUNDER
2ND STAGE
CONTROL PANEL
SOUND SELECTION
ON ON
SW 1 SW 2
1 2 3 4 5 1 2 3 4 5
PRESSURE UNIT
CONNECTOR
1234
TB1
1234
TB2
X
Y
SOUNDER
+24vdc 0v
TO NEXT SOUNDER
SOUND SELECTION
ON ON
SW 1 SW 2
1 2 3 4 5 1 2 3 4 5
PRESSURE UNIT
CONNECTOR
1234
TB1
1234
TB2
TO NEXT SOUNDER
+24vdc 0v
(stage 1)
0v +24vdc
(stage 2)
A. Two stage alarm by third core
Line monitoring by supply reversal
Select alarm stage 1 on SW1
Select alarm stage 2 on SW2
B. Two stage alarm by supply reversal
Line monitoring by threshold method (<1v)
Select alarm stage 1 on SW1
Select alarm stage 2 on SW2
Strobe operated from separate supply
1
2
3
4
5
6
7
MONITORING
RESISTOR
END OF
LINE
DEVICE
IN
IN
OUT
OUT
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
IN
IN
OUT
END OF
LINE
DEVICE
IN
OUT
A B
When supplied without the monitoring resistor the Call Point should
be connected as shown in 'A' or 'B' above.
The Call Point is supplied in two versions: - supplied with or without a monitoring resistor.
The version with the monitoring resistor should be connected as shown above. Check panel instructions to ensure
the correct value resistor is fitted.
If not required, remove and connect as shown in 'A' or 'B'
Ratings: - Vac: 250V max. / 12 V min. Imax: 5A resistive. Vdc: 30V max. / 12V min.
Contact resistance: 50 millioms max. Conductor size: 2.5 sq.mm max. per terminal.
NORMALLY OPEN WITH
SERIES MONITORING
INTERNAL SWITCH
CONNECTIONS ARMED
NORMALLY
OPEN
NORMALLY
CLOSED
TYPICAL CONNECTION DIAGRAMS FOR MANUAL CALL POINTS
AC ALARM CONNECTIONS AND SOUND
SIGNAL SELECTION
DC ALARM CONNECTION AND SOUND
SIGNAL SELECTION
27. FREQUENCY SOUND DIL
SWITCH
12345 (ON = 1)
REP RATE
(SEC)
SPECIAL APPLICATION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Alternate two-tone
Alternate two-tone
Alternate fast two-tone
Alternate fast two-tone
Alternate two-tone
Alternate two-tone
Alternate v.fast two-tone
Alternate v.fast two-tone
Alternate two-tone
Continuous note
Continuous note
Continuous note
Continuous note
Continuous note
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Int, fast, rising volume
Fast siren
Rising constant, fall
ISO 8201 Evacuation
Fast whoop
Slow whoop
Reverse sweep
Siren
800-1000
2500-3100
800-1000
2500-3100
440-554
430-470
800-1000
2500-3200
440-554
700
1000
1000
2300
440
1000
420
1000
2500
2500
700
1000
700
700
720
1400
250-1200
1000
800-1000
500-1000
500-1200
1200-500
500-1200
11111
01111
10111
00111
11011
01011
10011
00011
11101
01101
10101
00101
11001
01001
10001
00001
11110
01110
10110
00110
11010
01010
10010
00010
11100
01100
10100
00100
11000
01000
10000
00000
0.5
0.5
0.25
0.25
0.4/0.1
1.0
0.13
0.07
2.0
-
-
-
-
-
2.0
1.25
0.5
0.25
0.5
6/12
1.0
4.0
0.25
0.7/0.3
0.25
0.085
10/40/10
As std
0.15
4.5
1.0
3.0
Fire alarms - Level crossing
Security alarms
Increased urgency - Level crossing
Security deterrent
AFNOR, France
-
-
-
Turn out, Sweden
All-clear, Sweden
-
-
-
-
-
AS2220, Australia
-
-
-
Pre-vitalmessage, Sweden
-
Air-raid alarm, Sweden
Local warning, Sweden
Industrial alarm, Germany
-
-
Industrial alarm, Germany
Int’l evacuation alarm
-
Evacuation, The Netherlands
Evacuation, Germany
-
Tone Table
Controlled document No. D7493-01-02 (CN100301)My DocumentsSALES DATADATA SHEETSClifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
28. FREQUENCY SOUND DIL
SWITCH
12345 (ON=1)
REP RATE
(SEC)
SPECIAL APPLICATION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Alternate two-tone
Alternate two-tone
Alternate fast two-tone
Alternate fast two-tone
Alternate two-tone
Alternate two-tone
Alternate v.fast two-tone
Alternate v.fast two-tone
Alternate two-tone
Continuous note
Continuous note
Continuous note
Continuous note
Continuous note
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Interrupted tone
Int, fast, rising volume
Fast siren
Rising constant, fall
ISO 8201 Evacuation
Fast whoop
Slow whoop
Reverse sweep
Siren
800-1000
2500-3100
800-1000
2500-3100
440-554
430-470
800-1000
2500-3200
440-554
700
1000
1000
2300
440
1000
420
1000
2500
2500
700
1000
700
700
720
1400
250-1200
1000
800-1000
500-1000
500-1200
1200-500
500-1200
00000
10000
01000
11000
00100
10100
01100
11100
00010
10010
01010
11010
00110
10110
01110
11110
00001
10001
01001
11001
00101
10101
01101
11101
00011
10011
01011
11011
00111
10111
01111
11111
0.5
0.5
0.25
0.25
0.4/0.1
1.0
0.13
0.07
2.0
-
-
-
-
-
2.0
1.25
0.5
0.25
0.5
6/12
1.0
4.0
0.25
0.7/0.3
0.25
0.085
10/40/10
As std
0.15
4.5
1.0
3.0
Fire alarms - Level crossing
Security alarms
Increased urgency - Level crossing
Security deterrent
AFNOR, France
-
-
-
Turn out, Sweden
All-clear, Sweden
-
-
-
-
-
AS2220, Australia
-
-
-
Pre-vitalmessage, Sweden
-
Air-raid alarm, Sweden
Local warning, Sweden
Industrial alarm, Germany
-
-
Industrial alarm, Germany
Int’l evacuation alarm
-
Evacuation, The Netherlands
Evacuation, Germany
-
Tone Table
Controlled document No. D8115-01-02 (CN100301)My DocumentsSALES DATAdata sheetsClifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
NOTE: THIS TABLE IS FOR USE WITH MULTI–STAGE SOUNDERS ONLY MODELS YO4 - YO5 - YO8
29. Zone 0 (Gases)
Zone 20 (Dust)
Zone 1 (Gases)
Zone 21 (Dust)
Zone 2 (Gases)
Zone 22 (Dust)
Where an ignitable mixture can exist for long periods
of time under normal operating conditions
Where an ignitable mixture can exist some of the time
under normal operating condition
Where an ignitable mixture is not likely to exist under
normal operating conditions
450 T1 T1
300 T2 T2
280 T2 T2A
260 T2 T2B
230 T2 T2C
215 T2 T2D
200 T3 T3
180 T3 T3A
165 T3 T3B
160 T3 T3C
135 T4 T4
120 T4 T4A
100 T5 T5
85 T6 T6
0 Non Protected
1 Protected against objects greater
that 50mm
2 Protected against objects greater
that 12.5mm
3 Protected against objects greater
that 2.5mm
4 Protected against objects greater
that 1.0mm
5 Dust Protected
6 Dust Tight
0 Non Protected
1 Protected against vertical drip-
ping water
2 Protected against dripping
water when tilted at 15 degrees
3 Protected against spraying
water
4 Protected against splashing
water
5 Protected against water jets
6 Protected against powerfully
water jets
7 Protected against temporary
immersion 15cm to 1m
8 Protected against continuous
immersion
1st Digit protection against solid objects 2nd Digit protection against moisture
North American X-Ref Guide
NEMA 3 similar to IP54
NEMA 4 similar to IP55
NEMA 4X similar to IP56
NEMA 6 similar to IP67
INGRESS PROTECTION IP XX
TEMPERATURE CLASSIFICATION
TEMPERATURES CLASSIFICATION
In Degrees C IEC NORTH AMERICA
NORTH AMERICAN CLASSIFICATION EUROPEAN & IEC CLASSIFICATION
Flammable Gases, Vapours or Liquids
Combustible Dust
Ignitable Fibers
Class l
Class ll
Class lll
Div 1
Div 2
Clifford & Snell a division of Signature Industires Ltd part of the Digital Angel Corporation Controlled document No. D7494-01-01 (CN100047)My Documents SALES DATADATA SHEETS