Introduction to Arc Flash
Worker Training of Electrical Hazards Including
Arc Flash SH-16614-07
This material was produced under grant number
SH-16614-07 from the Occupational Safety and
Health Administration, U.S. Department of
Labor. It does not necessarily reflect the views
or policies of the U.S. Department of Labor, nor
does mention of trade names, commercial
products, or organizations imply endorsement by
the U.S. Government.

2
Overview
•
•
•
•
•
•
•
•
•
3

Introduction
Revisions to the NFPA 70E
Electrically Safe Work Conditions
Energized Electrical Work Permit
Flash Protection Boundary and Limits of
Approach
NFPA 70E Boundaries and Spaces
Flash Protection Calculations
Choosing Correct PPE
Reducing the Arc Flash Hazard
Introduction
• What is Arc Flash?
– Arc flash results from an arcing fault, where
the electric arcs and resulting radiation and
shrapnel cause severe skin burns, hearing
damage, and eye injuries.

4
Introduction
Why are we so interested in Arc Flash now?
– Numerous workers are injured and/or killed
each year while working on energized
equipment. Many of these casualties are a
result of arc flash.
– Working on energized equipment has become
commonplace in many industries.

5
Introduction
Injuries that can result from an arc flash:
– Burns
– Respiratory system damage
– Hearing damage
– Skin penetration from flying debris
– Eye and face injuries

6
Introduction
Important Temperatures
Skin temperature for curable burn
Skin temperature causing cell death
Ignition of clothing
Burning clothing
Metal droplets from arcing
Surface of sun
Arc terminals
7

176°F
205°F
752°-1472°F
1472°F
1832°F
9000°F
35,000°F
Introduction
• A First Degree Burn is red and sensitive to
touch. There is minimal skin damage and
only the skin surface is involved.
Example: Sunburn

8
Introduction
• A Second Degree Burn involves the first
and second layers of skin. The skin
reddens intensely and blisters develop.
Severe pain and swelling occur and
chance for infection is present.

9
Introduction
• A Third Degree Burn causes charring of
skin and coagulation of blood vessels just
below the skin surface. All three layers of
skin are affected. Extensive scarring
usually results.

10
Introduction
• Skin damage will occur based on the intensity of
the heat generated by an electrical arc accident.
The heat reaching the skin of the worker is
dependant on the following three factors:
– Power of the arc at the arc location
– Distance of the worker to the arc
– Time duration of the arc exposure

11
Introduction
• The intent of NFPA 70E regarding arc
flash is to provide guidelines which will
limit injury to the onset of second degree
burns.

12
Introduction
Inhalation Injuries
In addition to burns, an arc flash can
cause inhalation injuries. More than a
hundred known toxic substances are
present in fire smoke. When inhalation
injuries are combined with external burns
the chance of death can increase
significantly.
13
Introduction
• The pressure of an arc blast is caused by
the expansion of the metal as it vaporizes
and the heating of the air by the arc
energy. This accounts for the expulsion of
molten metal up to 10 feet away.
• In addition, the sudden expansion of an arc
blast creates loud sounds that can cause
hearing damage.
14
Revisions To The NFPA 70E
As a result of the injuries
and deaths related to arc
flash, changes/additions
have been incorporated
into the National Fire
Protection Association
publication number 70E,
the most recent version
being NFPA 70E-2004.
15
Revisions To The NFPA 70E
1. Only qualified persons shall be permitted to work
on electrical conductors or circuit parts that have
not been put into an electrically safe work
condition. (reference: NFPA 70E-2004 Section
110.8(A)(2) ©NFPA).
2. A flash hazard analysis shall be done in order to
protect personnel from the possibility of being
injured by an arc flash. (reference: NFPA 70E2004 Section 130.3 ©NFPA).
16
Revisions To The NFPA 70E
3. Employees working in areas where
electrical hazards are present shall be
provided with, and shall use, protective
equipment that is designed and
constructed for the specific part of the
body to be protected and for the work to
be performed (reference: NFPA 70E2004 Section 130.7(A) ©NFPA).

17
Revisions To The NFPA 70E
4. Personal protective equipment shall conform to
the standard given in Table 130.7(C)(8)
(reference: NFPA 70E-2004 130.7(C)(8)
©NFPA).
5. Arc Flash Protective Equipment: ……
The entire flash suit, including the hood’s face
shield, shall have an arc rating that is suitable
for the arc flash exposure (reference: NFPA
70E-2004 Section 130.7(C)(13)(a)).
18
Arc Flash Awareness
• NIOSH DVD:
Arc Flash Awareness
– Information and
discussion about arc
flash and comments
from workers injured
by an arc flash

19
Electrically Safe Work Conditions
• The equipment is not and cannot be energized:
To ensure an electrically safe work condition:
– Identify all power sources,
– Interrupt the load and disconnect power,
– Visually verify that a disconnect has opened the circuit,
– Locking out and tagging the circuit,
– Test for absence of voltage, and
– Ground all power conductors, if necessary.

20
Electrically Safe Work Conditions
• Lockout/Tagout
– A single qualified person de-energizing one
set of conductors.
– An unqualified person may never perform a
lockout/tagout, work on energized equipment,
or enter high risk areas.

21
Energized Electrical Work Permit
• When live parts over 50 volts are not
placed in an electrically safe work
condition it is considered energized
electrical work and must be down under a
written permit.
• Permit gives conditions and work practices
needed to protect employee from arc flash
or contact with live parts.
22
Energized Electrical Work Permit
An Energized Electrical Work Permit will include:
–
–
–
–
–
–
–
–

23

Circuit, equipment and location
Why working while energized.
Shock and arc flash hazard analysis
Safe work practices
Approach boundaries
Required PPE and tools
Access control
Proof of job briefing
Flash Protection Boundary and
Limits of Approach
• Definitions of Boundaries and Spaces
The closer you approach an exposed,
energized conductor or circuit part, the
greater the chance of an inadvertent
contact and the greater the injury that an
arc flash will cause. NFPA 70E-2004,
Annex C defines approach boundaries
and work spaces. The diagram on the next
slide illustrates these.
24
Flash Protection Boundary and
Limits of Approach

25

Approach/Flash Protection Boundaries
Flash Protection Boundary and
Limits of Approach
• Flash Protection Boundary
When an energized conductor is exposed,
you may not approach closer than the
flash boundary without wearing
appropriate personal protective clothing
and personal protective equipment.

26
Flash Protection Boundary and
Limits of Approach
• Flash Protection Boundary
IEEE defines “Flash Protection Boundary”
as: An approach limit at a distance from
live parts operating at 50 V or more that
are un-insulated or exposed within which a
person could receive a second degree
burn.
27
Flash Protection Boundary and
Limits of Approach
How Does Flash Protection Boundary Relate to
Working On Or Near Exposed Energized Parts?
• The radiant energy and molten material that is
released by an electric arc is capable of seriously
injuring or killing a human being at distances of up
to twenty feet.
The flash protection boundary is the closest
approach allowed by qualified or unqualified
persons without the use of arc flash PPE.
28
Flash Protection Boundary and
Limits of Approach
NFPA 70E 2004, Table 130.2(C) ©NFPA
Approach Boundaries to Live Parts for Shock Protection.
(All dimensions are distance from live part to employee.)
(1)

(2)

(3)

(4)

(5)

1

Limited Approach Boundary

Restricted Approach
Boundary1; Includes
Inadvertent Movement
Adder

Nominal System
Voltage Range,
Phase to Phase

Exposed
Fixed Circuit
Part

Less than 50

Not specified

Not specified

Not specified

Not specified

50 to 300

10 ft 0 in.

3 ft 6 in.

Avoid contact

Avoid contact

301 to 750

10 ft 0 in.

3 ft 6 in.

1 ft 0 in.

0 ft 1 in.

751 to 15 kV

10 ft 0 in.

5 ft 0 in.

2 ft 2 in.

0 ft 7 in.

15.1 kV to 36 kV

10 ft 0 in.

6 ft 0 in.

2 ft 7 in.

0 ft 10 in.

36.1 kV to 46 kV

10 ft 0 in.

8 ft 0 in.

2 ft 9 in.

1 ft 5 in.

46.1 kV to 72.5 kV

29

Exposed
Movable
Conductor

Prohibited
Approach
Boundary1

10 ft 0 in.

8 ft 0 in.

3 ft 3 in.

2 ft 1 in.
Flash Protection Boundary and
Limits of Approach
Typical NEC Label

30
Flash Protection Boundary and
Limits of Approach
Typical Detailed Label

31
NFPA 70E Boundaries and Spaces
Good safety practices minimize risk:
• Switch remotely if possible.
• Standing aside and away as much as
possible during switching.
• Avoid leaning on or touching switchgear
and metallic surfaces.
• Use proper tools and PPE.
32
NFPA 70E Boundaries and Spaces
• NFPA 70E, Section 130.3(B) states:
• If work will be performed within the flash
protection boundary, the flash hazard
analysis shall determine, and the
employer shall document, the incident
energy exposure of the worker in
(cal/cm2).
33
NFPA 70E Boundaries and Spaces
NFPA 70E, Section 130.3 (B) states:
• The incident energy exposure
level shall be based on the
working distance of the worker’s
face and chest areas from a
prospective arc source for the
specific task to be performed.

34
NFPA 70E Boundaries and Spaces
• NFPA 70E, Section 130.3(B) states:
Flame Resistant (FR) Clothing and Personal
Protective Equipment (PPE) shall be used by
the employee based upon the incident energy
exposure associated with the specific task.

35
Flash Protection Calculations
• The Incident Energy and Flash Protection
Boundary can be calculated in an Arc
Flash Hazard Analysis.
• There are two methods:
– NFPA 70E-2004, Annex D
– IEEE Std 1584TM

36
Flash Protection Calculations
Step 1
• Collect the System Installation Equipment
Data
Step 2
• Determine the Power System’s Modes of
Operation
– Normal operation, tie switched closed, dual
feeds
– Perform analysis for worst case condition
37
Flash Protection Calculations
Step 3
• Determine the Bolted Fault Currents
– Find symmetrical RMS current and X/R ratio at each point of
concern.
•
•
•

38

Theoretically worst case fault magnitude
Determines equipment interrupting ratings
Impedance at fault location is considered
to be zero ohms
Flash Protection Calculations
Step 4
• Determine the Arc Fault Currents
– The arc fault current for each location where
an arc flash hazard exists and the portion of
the current that flows through the closest
upstream device that will clear this fault must
be determined

39
Flash Protection Calculations
Arcing Fault Current is fault current flowing through
an electrical arc plasma.
•
•

Faults which are not bolted
Poor electrical connection
between conductors can cause
arcing
• Arcing results in tremendous
heat (35,000)

40
Flash Protection Calculations
Step 5
• From the Protective Device Characteristics,
Find the Arcing Duration
– The total clearing time of the fault will
determine the “time” factor in the incident
energy equation.

41
Flash Protection Calculations
CURRENT IN AMPERES

The fault clearing time is
determined from the
Coordination Study’s
Time Current Curves.

1000

T4

T4

100

The total clearing time of
the primary fuse for a
secondary side fault is 1
second.

T4

1 sec

M2

1

T4 Main Phase
T4 - T5 Phase
TX Inrush

0.10

0.01

42

TIME IN SECONDS

HMCP 250 A
100 hp O/L

10

0.5 1

10

100

MCC Fdr Phase

1K

10K

T4 arc flash.tcc Ref. Voltage: 480 Current Scale x10^2 T4 arc flash.drw
Flash Protection Calculations
Step 6
• Record the System Voltages and
Equipment Classes
– For each bus or arc hazard location

Step 7
• Determine Working Distances
– Arc flash protection is always based on the
incident energy to a person’s face and body at
the working distance
43
Flash Protection Calculations
Step 8
• Determine Incident Energy
– This is best done using a software package.

• Calculating incident energy requires the
following parameters:
– Max. bolted 3-ph fault current available at the
equipment
– Total protective upstream device clearing time max
fault current
– Distance of worker from the arc
44
Flash Protection Calculations
Step 9
• Determine the Flash Protection Boundary
for All Equipment
– The incident energy for the flash-protection
boundary must be set at the minimum energy
beyond which a second degree burn could
occur - 1.2 cal/cm2

45
Flash Protection Calculations

Let’s take a quick look at the
NFPA 70E-2004 equations

46
Flash Protection Calculations
The estimated incident energy for an arc in
open air is:
EMA = 5271DA-1.9593 tA[0.0016F 2-0.0076F+0.8938]

EMA=maximum open arc incident energy (cal/cm 2)
DA=distance from arc electrodes (inches)
tA=arc duration (seconds)
F=bolted fault current in kA (16kA-50kA)
47
Flash Protection Calculations
The estimated incident energy for an arc in
a box is:
EMB = 1038.7DB-1.4738 tA[0.0093F2-0.3453F+5.9675]

EMB=max 20 in. cubic box incident energy (cal/cm 2)
DB=distance from arc electrodes (inches) for 18 in.
and greater
tA=arc duration (seconds)
F=bolted fault current in kA (16kA-50kA)
48
Flash Protection Calculations
• Test results have shown that the incident
energy for an open air arc is
approximately inversely proportional to the
distance squared.
• Enclosing a 3-ph arc in a box can increase
the incident energy from 1.5 to 3 times
depending upon the arc parameters and
box dimensions when compared to an
open air arc with the same parameters.
49
Flash Protection Calculations
There are resources on the
internet to assist in calculations:
•

http://
www.littelfuse.com/arccalc/calc.html

•

http://www.pnl.gov/contracts/esh-procedures/forms/sp00e230.xls

•

http://
www.bussmann.com/arcflash/index.aspx

50
Flash Protection Calculations
As well as software and spreadsheets:

51
Choosing Correct PPE
Section 130.7(A) states that employees
working in areas where there are electric
hazards shall be provided with, and shall
use, protective equipment that is designed
and constructed for the specific part of the
body to be protected and for the work to
be performed.

52
Choosing Correct PPE
• Personal Protective Equipment, PPE, for
the arc flash is the last line of defense.
• It is not intended to prevent all injuries, but
is intended to mitigate the impact of an arc
flash, should one occur.

53
Choosing Correct PPE
•

After the Arc-Flash Hazard Analysis has
been performed, PPE is selected as
follows:
Clothing’s ATPV or EBT (in cal/cm2)
>
Calculated Hazard Level (in cal/cm2)
*ATPV can be obtained from clothing manufacturer

54
Choosing Correct PPE
ATPV - Arc Thermal Performance
Exposure Value
EBT - Breakopen Threshold Energy
Rating
Calculated Hazard Level - Incident
Energy in cal/cm2
55
Choosing Correct PPE
• Specialized Arc-Flash
Protection Equipment:
Flash Suit

• Use: Hazard/Risk
Category 4

56
Choosing Correct PPE
• Specialized Arc-Flash
Protection Equipment:
Switching Coat,
ATPV = 42 cal/cm2

• Use: Hazard/Risk
Category 4

57
Choosing Correct PPE
• Specialized Arc-Flash
Protection Equipment:
Hood,
ATPV = 42 cal/cm2

• Use: Hazard/Risk
Category 4

58
Choosing Correct PPE
• Specialized Arc-Flash
Protection Equipment:
Face Shield -- Attaches to
Hard Hat

• Use: Hazard/Risk
Category 2

59
Choosing Correct PPE
• Specialized Arc-Flash
Protection Equipment:
Gloves and Leather
Protectors,
(ATPV Values not
Established for Rubber)

• Use: Hazard/Risk
Category 2, 3, and 4
for the Leather
Protectors
60
Choosing Correct PPE
• NFPA 70E, Section 130.7(C)(9)(a) states:
– When selected in lieu of the flash hazard
analysis of 130.3(A), Table 130.7(C)(9)(a)
shall be used to determine the hazard/risk
category for each task.

• NFPA 70E, Section 130.7(C)(10) states:
– Once the Hazard/Risk Category has been
identified, Table 130.7(C)(10) shall be used to
determine the required personal protective
equipment (PPE) for the task.
61
Choosing Correct PPE
The tables in NFPA 70E-2004 provide the
simplest methods for determining PPE
requirements. They provide instant
answers with almost no field data. The
tables provide limited application and are
conservative for most applications.
*These tables are not intended as a substitution for an arc hazard
analysis, but only as a guide.
62
Choosing Correct PPE
A simplified two-category approach is
found in NFPA 70E-2004, Table H-1 of
Annex H ©NFPA. This table assures adequate
PPE for electrical workers within facilities
with large and diverse electrical systems.

63
Choosing Correct PPE
The clothing listed in Table H-1 fulfills the
minimum FR clothing requirements of
NFPA 70E-2004, Tables 130.7(C)(9)(a)
and 130.7(C)(10) ©NFPA and should be used
with the other PPE appropriate for the
Hazard/ Risk Category that is found in of
NFPA 70E-2004, Table 130.7(C)(10) ©NFPA.

64
Choosing Correct PPE
Everyday Work Clothing

Applicable Tasks
All Hazard/Risk Category 1 or 2 tasks listed in Table
130.7(C)(9)(a) ©NFPA

FR long sleeve shirt (minimum
arc rating of 4) worn over an
untreated cotton T-shirt with FR
pants (minimum arc rating of 8)
Or
FR coveralls (minimum arc rating
of 4) worn over an untreated
cotton T-shirt with untreated
natural fiber pants.

65

On systems operating at less than 1000 V, these
tasks include all work except:
•

Insertion or removal of MCC buckets

•

Insertion or removal of power circuit breakers
with switchgear doors open

•

Removal of bolted covers from switchgear

On systems >1000 V, also includes operation,
insertion or removal of switching devices with
equipment enclosure doors closed.
Choosing Correct PPE
Electrical “Switching”
Clothing

Applicable Tasks

Multilayer FR flash jacket and FR
Bib overalls worn over FR coveralls
(minimum arc rating of 4)

All Hazard/Risk Category 1 or 2 tasks listed in
NFPA 70E, Part II, Table 3-3.9.1 ©NFPA

Or
Insulated FR coveralls (minimum
arc rating of 25) worn over
untreated natural fiber long
sleeve shirt with cotton blue
jeans and worn over an
untreated cotton T-shirt.

66

On systems ≥1000 V, tasks include work on
exposed energized parts of all equipment
On systems <1000 V, tasks include insertion or
removal of LV MCC buckets, insertion or removal of
power circuit breakers with the switchgear
enclosure doors open, and removal of bolted covers
from switchgear
Choosing Correct PPE
• NFPA 70E-2004, Section 130.7(C), Table
130.7(C)(9)(a) lists common work tasks
with respective Hazard/Risk category of
each task.
• After the Hazard Risk Category has been
determined from Table 130.7(C)(9)(a),
then Table 130.7(C)(10) is used to
determine the Protective Clothing and
Personal Protective Equipment required
for the task.
67
Choosing Correct PPE
Hazard/
Risk
Category

V-rated

V-rated

Gloves

Tools

CB or fused switch operation with enclosure doors closed

0

N

N

Reading a panel meter while operating a meter switch

0

N

N

CB or fused switch operation with enclosure doors open

1

N

N

Work on energized parts, including voltage testing

2*

Y

Y

Task (Assumes Equipment Is Energized, and Work Is Done
Within the Flash Protection Boundary)

68
Choosing Correct PPE
• NFPA 70E, Table 130.7(C)(11) lists the
characteristics and degrees of protection
for various Flame Resistant (FR) clothing
systems.

69
Choosing Correct PPE
NFPA 70E Table 130.7(C)(11) Typical Protective Clothing Systems

Clothing Description (Number of
clothing layers is given in
parenthesis)

Total
Weight

oz/yd2

Hazard
Risk
Category

Minimum Arc Thermal
Performance Exposure
Value (ATPV)* or
Breakdown Threshold
Energy (EBT)* Rating of
PPE
cal/cm2

0

Untreated Cotton (1)

4.5 - 7

N/A

1

FR shirt and FR pants (1)

4.5 - 8

5

2

Cotton underwear plus FR shirt and
FR pants (2)

9 - 12

8

3

Cotton underwear plus FR shirt and
FR pants plus FR coverall (3)

16 - 20

25

4

Cotton underwear plus FR shirt and
FR pants plus double layer switching
coat and pants (4)

24-30

40

* ATPV is defined as the incident energy that would just cause the onset of a second
degree burn.
* EBT is defined as the highest incident energy which did not cause FR fabric breakopen
and did not exceed the second degree burn criteria. E BT is reported when ATPV cannot
be measured due to fabric breakopen.

70
Choosing Correct PPE
The equations in NFPA 70E-2004 provide
more accurate methods than tables for
determining PPE requirements. System
data and studies are required. The
equations are based upon limited fuse and
circuit breaker data.

71
Choosing Correct PPE
• Remember: PPE is the last line of
defense. PPE cannot prevent all
injuries and will only lessen the
impact of an arc flash. In many cases
the use of PPE has saved lives or
prevented serious injury.

72
Reducing The Arc Flash Hazard
OSHA 1910.333 severely limits the
situations in which work is performed
on or near equipment or circuits that
are or may be energized.

73
Reducing The Arc Flash Hazard
EQUIPMENT ALTERNATIVES
• Metal-Clad Switchgear
Structural design reduces the
possibility of arcing faults within the
enclosure.
74
Reducing The Arc Flash Hazard
EQUIPMENT ALTERNATIVES
• Arc Resistant Switchgear
EEMAC Standard G14-1 defines the
requirements for arc resistant
switchgear. Includes robust design
and pressure relief vents.
75
Reducing The Arc Flash Hazard
EQUIPMENT ALTERNATIVES
• Current-Limiter Power Circuit Breakers
Reduces the clearing time which
reduces the incident energy.

76
Reducing The Arc Flash Hazard
EQUIPMENT ALTERNATIVES
• Current-Limiting Reactors

Reduces the magnitude of fault
current which reduces the incident
energy.
77
Reducing The Arc Flash Hazard
EQUIPMENT ALTERNATIVES
• Zone Selective Interlocking of Circuit
Breakers
Deactivates the preset delay on the
circuit breaker closest to the fault,
which then trips with no intentional
delay.
78
Reducing The Arc Flash Hazard
Whatever the analysis method or
proposed method of solution, each
work task must be analyzed assuming
worst case conditions.

79
Reference Materials
•
•
•

•
•
•
•
•

80

Standard for Electrical Safety in the Workplace, NFPA 70E 2004 Edition
Controlling Electrical Hazards. OSHA Publication 3075, (2002). Also available as a 350 KB PDF,
71 pages. Provides a basic overview of electrical safety on the job, including information on how
electricity works, how to protect against electricity, and how OSHA can help.
Electrical Safety: Safety and Health for Electrical Trades Student Manual. US Department of
Health and Human Services (DHHS), National Institute for Occupational Safety and Health
(NIOSH), Publication No. 2002-123, (2002, January), 1.7 MB PDF, 88 pages. This student
manual is part of a safety and health curriculum for secondary and post-secondary electrical
trades courses. It is designed to engage the learner in recognizing, evaluating, and controlling
hazards associated with electrical work. http://www.cdc.gov/niosh/pdfs/02-123.pdf
Electrocutions Fatality Investigation Reports. National Institute for Occupational Safety and
Health (NIOSH) Safety and Health Topic. Provides information regarding hundreds of fatal
incidents involving electrocutions investigated by NIOSH and state investigators
Working Safely with Electricity. OSHA Fact Sheet, 353 KB PDF, 2 pages. Provides safety
information on working with generators, power lines, extension cords, and electrical equipment.
http://www.osha.gov/OshDoc/data_Hurricane_Facts/elect_safety.pdf
Lockout/Tagout. OSHA Fact Sheet, (2002), 212 KB PDF, 2 pages. A 92 KB PDF (Spanish
version) is also available.
http://www.cdc.gov/nasd/docs/d001501-d001600/d001514/d001514.html
Lockout-Tagout Interactive Training Program. OSHA. Includes selected references for training
and interactive case studies. http://www.osha.gov/dts/osta/lototraining/index.htm
NIOSH Arc Flash Awareness, NIOSH Publication No. 2007-116D
Questions?

81

Más contenido relacionado

La actualidad más candente

Electrical Safety, Personal Protective Equipment, & Z462 Compliance
Electrical Safety, Personal Protective Equipment, & Z462 ComplianceElectrical Safety, Personal Protective Equipment, & Z462 Compliance
Electrical Safety, Personal Protective Equipment, & Z462 ComplianceCCOHS
 
Practical Electrical Substation Safety for Engineers and Technicians
Practical Electrical Substation Safety for Engineers and TechniciansPractical Electrical Substation Safety for Engineers and Technicians
Practical Electrical Substation Safety for Engineers and TechniciansLiving Online
 
Electrical hazards & safety training
Electrical hazards & safety trainingElectrical hazards & safety training
Electrical hazards & safety trainingSYED HAIDER ABBAS
 
Arc Flash Safety Training by Pennsylvania Department of Labor and Indusry
Arc Flash Safety Training by Pennsylvania Department of Labor and IndusryArc Flash Safety Training by Pennsylvania Department of Labor and Indusry
Arc Flash Safety Training by Pennsylvania Department of Labor and IndusryAtlantic Training, LLC.
 
Electrical safety ppt
Electrical safety pptElectrical safety ppt
Electrical safety pptconstruction
 
Arc flash analysis and electrical hazards
Arc flash analysis and electrical hazardsArc flash analysis and electrical hazards
Arc flash analysis and electrical hazardsVB Engineering
 
Arc-Flash-safety-PPT-1.ppt
Arc-Flash-safety-PPT-1.pptArc-Flash-safety-PPT-1.ppt
Arc-Flash-safety-PPT-1.pptSHAILESH RAVAL
 
Electrical Safety Techniques
Electrical Safety TechniquesElectrical Safety Techniques
Electrical Safety TechniquesLiving Online
 
NFPA 70E Electrical Safety in the Workplace by Hortica
NFPA 70E  Electrical Safety in the Workplace by HorticaNFPA 70E  Electrical Safety in the Workplace by Hortica
NFPA 70E Electrical Safety in the Workplace by HorticaAtlantic Training, LLC.
 
Electrical hazards and their preventions
Electrical hazards and their preventionsElectrical hazards and their preventions
Electrical hazards and their preventionsShamili Kaparthi
 
Line Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relayLine Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relaydavid roy
 
Overhead line work ppt
Overhead line work pptOverhead line work ppt
Overhead line work pptDemsew Mitiku
 
Basic electrical safety
Basic electrical safetyBasic electrical safety
Basic electrical safetyumar farooq
 

La actualidad más candente (20)

Electrical Safety, Personal Protective Equipment, & Z462 Compliance
Electrical Safety, Personal Protective Equipment, & Z462 ComplianceElectrical Safety, Personal Protective Equipment, & Z462 Compliance
Electrical Safety, Personal Protective Equipment, & Z462 Compliance
 
Practical Electrical Substation Safety for Engineers and Technicians
Practical Electrical Substation Safety for Engineers and TechniciansPractical Electrical Substation Safety for Engineers and Technicians
Practical Electrical Substation Safety for Engineers and Technicians
 
Electrical hazards & safety training
Electrical hazards & safety trainingElectrical hazards & safety training
Electrical hazards & safety training
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Arc Flash Safety Training by Pennsylvania Department of Labor and Indusry
Arc Flash Safety Training by Pennsylvania Department of Labor and IndusryArc Flash Safety Training by Pennsylvania Department of Labor and Indusry
Arc Flash Safety Training by Pennsylvania Department of Labor and Indusry
 
Frank Conte Arc flash program
Frank Conte Arc flash programFrank Conte Arc flash program
Frank Conte Arc flash program
 
Electrical Safety by OSHA
Electrical Safety by OSHAElectrical Safety by OSHA
Electrical Safety by OSHA
 
Electrical Safety by OSHA
Electrical Safety by OSHAElectrical Safety by OSHA
Electrical Safety by OSHA
 
Electrical Safety
Electrical SafetyElectrical Safety
Electrical Safety
 
Electrical safety ppt
Electrical safety pptElectrical safety ppt
Electrical safety ppt
 
Arc flash analysis and electrical hazards
Arc flash analysis and electrical hazardsArc flash analysis and electrical hazards
Arc flash analysis and electrical hazards
 
Arc-Flash-safety-PPT-1.ppt
Arc-Flash-safety-PPT-1.pptArc-Flash-safety-PPT-1.ppt
Arc-Flash-safety-PPT-1.ppt
 
Electrical Safety Techniques
Electrical Safety TechniquesElectrical Safety Techniques
Electrical Safety Techniques
 
NFPA 70E Electrical Safety in the Workplace by Hortica
NFPA 70E  Electrical Safety in the Workplace by HorticaNFPA 70E  Electrical Safety in the Workplace by Hortica
NFPA 70E Electrical Safety in the Workplace by Hortica
 
Electrical hazards and their preventions
Electrical hazards and their preventionsElectrical hazards and their preventions
Electrical hazards and their preventions
 
Iec 60364 4-442
Iec 60364 4-442Iec 60364 4-442
Iec 60364 4-442
 
Line Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relayLine Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relay
 
Electrical Hazards in the Workplace
Electrical Hazards in the WorkplaceElectrical Hazards in the Workplace
Electrical Hazards in the Workplace
 
Overhead line work ppt
Overhead line work pptOverhead line work ppt
Overhead line work ppt
 
Basic electrical safety
Basic electrical safetyBasic electrical safety
Basic electrical safety
 

Destacado

Salisbury Arc Flash Protection Clothing & Kits - Arc Flash Hood, Arc Flash Co...
Salisbury Arc Flash Protection Clothing & Kits - Arc Flash Hood, Arc Flash Co...Salisbury Arc Flash Protection Clothing & Kits - Arc Flash Hood, Arc Flash Co...
Salisbury Arc Flash Protection Clothing & Kits - Arc Flash Hood, Arc Flash Co...Thorne & Derrick International
 
Salisbury Pro-Wear HRC2 Arc Flash Clothing & Protection Kit 8 cal/cm² ATPV
Salisbury Pro-Wear HRC2 Arc Flash Clothing & Protection Kit 8 cal/cm² ATPV Salisbury Pro-Wear HRC2 Arc Flash Clothing & Protection Kit 8 cal/cm² ATPV
Salisbury Pro-Wear HRC2 Arc Flash Clothing & Protection Kit 8 cal/cm² ATPV Thorne & Derrick International
 
Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...
Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...
Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...Thorne & Derrick International
 
CATU Insulating Rubber Gloves - Rubber Latex Gloves, Composite Gloves & Arc F...
CATU Insulating Rubber Gloves - Rubber Latex Gloves, Composite Gloves & Arc F...CATU Insulating Rubber Gloves - Rubber Latex Gloves, Composite Gloves & Arc F...
CATU Insulating Rubber Gloves - Rubber Latex Gloves, Composite Gloves & Arc F...Thorne & Derrick International
 
Electrical Safety In The Workplace by Crawford Engineering Services
Electrical Safety In The Workplace by Crawford Engineering ServicesElectrical Safety In The Workplace by Crawford Engineering Services
Electrical Safety In The Workplace by Crawford Engineering ServicesAtlantic Training, LLC.
 
Alroc Tools - Cable Stripping & Preparation Tools For LV HV Cable Jointers
Alroc Tools - Cable Stripping & Preparation Tools For LV HV Cable JointersAlroc Tools - Cable Stripping & Preparation Tools For LV HV Cable Jointers
Alroc Tools - Cable Stripping & Preparation Tools For LV HV Cable JointersThorne & Derrick International
 
Electrical Safety by Industrial Safety Institute
Electrical Safety by Industrial Safety InstituteElectrical Safety by Industrial Safety Institute
Electrical Safety by Industrial Safety InstituteAtlantic Training, LLC.
 
CATU Insulating Boots - CATU Electrical Safety Equipment
CATU Insulating Boots - CATU Electrical Safety Equipment CATU Insulating Boots - CATU Electrical Safety Equipment
CATU Insulating Boots - CATU Electrical Safety Equipment Thorne & Derrick International
 
Introduction to Arc Flash Training by West Virginia University
Introduction to Arc Flash Training by West Virginia UniversityIntroduction to Arc Flash Training by West Virginia University
Introduction to Arc Flash Training by West Virginia UniversityAtlantic Training, LLC.
 
Cembre - Hydraulic Tools, Mechanical Tools, Crimping Tools, Cable Cutters, AT...
Cembre - Hydraulic Tools, Mechanical Tools, Crimping Tools, Cable Cutters, AT...Cembre - Hydraulic Tools, Mechanical Tools, Crimping Tools, Cable Cutters, AT...
Cembre - Hydraulic Tools, Mechanical Tools, Crimping Tools, Cable Cutters, AT...Thorne & Derrick International
 
Electrical Workplace Safety
Electrical Workplace SafetyElectrical Workplace Safety
Electrical Workplace SafetyRickCKnight
 
Electrical Hazards and Arc Flash Awareness by RCC
Electrical Hazards and Arc Flash Awareness by RCCElectrical Hazards and Arc Flash Awareness by RCC
Electrical Hazards and Arc Flash Awareness by RCCAtlantic Training, LLC.
 
Significant Changes To NFPA 70E by Hoydar Buck, Inc
Significant Changes To NFPA 70E by Hoydar Buck, IncSignificant Changes To NFPA 70E by Hoydar Buck, Inc
Significant Changes To NFPA 70E by Hoydar Buck, IncAtlantic Training, LLC.
 
Electrical Safety by Safety Management Education
Electrical Safety by Safety Management EducationElectrical Safety by Safety Management Education
Electrical Safety by Safety Management EducationAtlantic Training, LLC.
 
Salisbury Insulated Tools - Salisbury Insulated Products (S.I.P) - Insulated ...
Salisbury Insulated Tools - Salisbury Insulated Products (S.I.P) - Insulated ...Salisbury Insulated Tools - Salisbury Insulated Products (S.I.P) - Insulated ...
Salisbury Insulated Tools - Salisbury Insulated Products (S.I.P) - Insulated ...Thorne & Derrick International
 
Seaward KD1E High Voltage HV Indicators & Detectors, Phasing Units, Ammeters ...
Seaward KD1E High Voltage HV Indicators & Detectors, Phasing Units, Ammeters ...Seaward KD1E High Voltage HV Indicators & Detectors, Phasing Units, Ammeters ...
Seaward KD1E High Voltage HV Indicators & Detectors, Phasing Units, Ammeters ...Thorne & Derrick International
 
Arc flash practical solution guide to arc flash hazards-1
Arc flash practical solution guide to arc flash hazards-1Arc flash practical solution guide to arc flash hazards-1
Arc flash practical solution guide to arc flash hazards-1Aarjun Singh Panesar
 

Destacado (20)

Salisbury Arc Flash Protection Clothing & Kits - Arc Flash Hood, Arc Flash Co...
Salisbury Arc Flash Protection Clothing & Kits - Arc Flash Hood, Arc Flash Co...Salisbury Arc Flash Protection Clothing & Kits - Arc Flash Hood, Arc Flash Co...
Salisbury Arc Flash Protection Clothing & Kits - Arc Flash Hood, Arc Flash Co...
 
Salisbury Pro-Wear HRC2 Arc Flash Clothing & Protection Kit 8 cal/cm² ATPV
Salisbury Pro-Wear HRC2 Arc Flash Clothing & Protection Kit 8 cal/cm² ATPV Salisbury Pro-Wear HRC2 Arc Flash Clothing & Protection Kit 8 cal/cm² ATPV
Salisbury Pro-Wear HRC2 Arc Flash Clothing & Protection Kit 8 cal/cm² ATPV
 
2015 nfpa 70 e changes
2015 nfpa 70 e changes2015 nfpa 70 e changes
2015 nfpa 70 e changes
 
Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...
Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...
Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...
 
CATU Insulating Rubber Gloves - Rubber Latex Gloves, Composite Gloves & Arc F...
CATU Insulating Rubber Gloves - Rubber Latex Gloves, Composite Gloves & Arc F...CATU Insulating Rubber Gloves - Rubber Latex Gloves, Composite Gloves & Arc F...
CATU Insulating Rubber Gloves - Rubber Latex Gloves, Composite Gloves & Arc F...
 
Electrical Safety In The Workplace by Crawford Engineering Services
Electrical Safety In The Workplace by Crawford Engineering ServicesElectrical Safety In The Workplace by Crawford Engineering Services
Electrical Safety In The Workplace by Crawford Engineering Services
 
Nfpa 70 E
Nfpa 70 ENfpa 70 E
Nfpa 70 E
 
Alroc Tools - Cable Stripping & Preparation Tools For LV HV Cable Jointers
Alroc Tools - Cable Stripping & Preparation Tools For LV HV Cable JointersAlroc Tools - Cable Stripping & Preparation Tools For LV HV Cable Jointers
Alroc Tools - Cable Stripping & Preparation Tools For LV HV Cable Jointers
 
Electrical Safety by Industrial Safety Institute
Electrical Safety by Industrial Safety InstituteElectrical Safety by Industrial Safety Institute
Electrical Safety by Industrial Safety Institute
 
CATU Insulating Boots - CATU Electrical Safety Equipment
CATU Insulating Boots - CATU Electrical Safety Equipment CATU Insulating Boots - CATU Electrical Safety Equipment
CATU Insulating Boots - CATU Electrical Safety Equipment
 
Introduction to Arc Flash Training by West Virginia University
Introduction to Arc Flash Training by West Virginia UniversityIntroduction to Arc Flash Training by West Virginia University
Introduction to Arc Flash Training by West Virginia University
 
Cembre - Hydraulic Tools, Mechanical Tools, Crimping Tools, Cable Cutters, AT...
Cembre - Hydraulic Tools, Mechanical Tools, Crimping Tools, Cable Cutters, AT...Cembre - Hydraulic Tools, Mechanical Tools, Crimping Tools, Cable Cutters, AT...
Cembre - Hydraulic Tools, Mechanical Tools, Crimping Tools, Cable Cutters, AT...
 
Electrical Workplace Safety
Electrical Workplace SafetyElectrical Workplace Safety
Electrical Workplace Safety
 
Electrical Hazards and Arc Flash Awareness by RCC
Electrical Hazards and Arc Flash Awareness by RCCElectrical Hazards and Arc Flash Awareness by RCC
Electrical Hazards and Arc Flash Awareness by RCC
 
Significant Changes To NFPA 70E by Hoydar Buck, Inc
Significant Changes To NFPA 70E by Hoydar Buck, IncSignificant Changes To NFPA 70E by Hoydar Buck, Inc
Significant Changes To NFPA 70E by Hoydar Buck, Inc
 
Electrical Safety by Safety Management Education
Electrical Safety by Safety Management EducationElectrical Safety by Safety Management Education
Electrical Safety by Safety Management Education
 
Salisbury Insulated Tools - Salisbury Insulated Products (S.I.P) - Insulated ...
Salisbury Insulated Tools - Salisbury Insulated Products (S.I.P) - Insulated ...Salisbury Insulated Tools - Salisbury Insulated Products (S.I.P) - Insulated ...
Salisbury Insulated Tools - Salisbury Insulated Products (S.I.P) - Insulated ...
 
Weidmuller KT55 Cable Cutting Tools
Weidmuller KT55 Cable Cutting ToolsWeidmuller KT55 Cable Cutting Tools
Weidmuller KT55 Cable Cutting Tools
 
Seaward KD1E High Voltage HV Indicators & Detectors, Phasing Units, Ammeters ...
Seaward KD1E High Voltage HV Indicators & Detectors, Phasing Units, Ammeters ...Seaward KD1E High Voltage HV Indicators & Detectors, Phasing Units, Ammeters ...
Seaward KD1E High Voltage HV Indicators & Detectors, Phasing Units, Ammeters ...
 
Arc flash practical solution guide to arc flash hazards-1
Arc flash practical solution guide to arc flash hazards-1Arc flash practical solution guide to arc flash hazards-1
Arc flash practical solution guide to arc flash hazards-1
 

Similar a Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Work Conditions, Reducing Arc Flash Hazard, Choosing Correct Personal Protection Equipment PPE, What Is An Arc Flash?

Why Test Series - Arc Flash Evaluations CS-00158
Why Test Series - Arc Flash Evaluations CS-00158Why Test Series - Arc Flash Evaluations CS-00158
Why Test Series - Arc Flash Evaluations CS-00158Carolyn Dakis
 
Arc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyArc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyAtlantic Training, LLC.
 
arcflashsolutions2-160226132648
arcflashsolutions2-160226132648arcflashsolutions2-160226132648
arcflashsolutions2-160226132648Brian Y. Smith
 
Understanding Arc Flash presentation engineering
Understanding Arc Flash presentation engineeringUnderstanding Arc Flash presentation engineering
Understanding Arc Flash presentation engineeringSheeda2
 
Electrical Safety and NFPA 70E Study Sheet v2.0
Electrical Safety and NFPA 70E Study Sheet v2.0Electrical Safety and NFPA 70E Study Sheet v2.0
Electrical Safety and NFPA 70E Study Sheet v2.0Richard Gould
 
Arc Flash as it Relates to AC Drives
Arc Flash as it Relates to AC DrivesArc Flash as it Relates to AC Drives
Arc Flash as it Relates to AC DrivesFlow-Tech, Inc.
 
Electrical hazards
Electrical hazardsElectrical hazards
Electrical hazardsKashif Riaz
 
Arc flash analysis, electrical safety and risk assessment
Arc flash analysis, electrical safety and risk assessmentArc flash analysis, electrical safety and risk assessment
Arc flash analysis, electrical safety and risk assessmentPremium Power
 
Arc flash in Industry
Arc flash in Industry Arc flash in Industry
Arc flash in Industry Nicola Cassidy
 

Similar a Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Work Conditions, Reducing Arc Flash Hazard, Choosing Correct Personal Protection Equipment PPE, What Is An Arc Flash? (20)

Arc flash guidebook
Arc flash guidebookArc flash guidebook
Arc flash guidebook
 
Arc flash guidebook
Arc flash guidebookArc flash guidebook
Arc flash guidebook
 
Arc flash
Arc flashArc flash
Arc flash
 
Arc flash
Arc flashArc flash
Arc flash
 
Arc flash q
Arc flash qArc flash q
Arc flash q
 
NFPA 70E Training By SASCO
NFPA 70E Training By SASCONFPA 70E Training By SASCO
NFPA 70E Training By SASCO
 
Why Test Series - Arc Flash Evaluations CS-00158
Why Test Series - Arc Flash Evaluations CS-00158Why Test Series - Arc Flash Evaluations CS-00158
Why Test Series - Arc Flash Evaluations CS-00158
 
Arc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyArc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of Technology
 
Electrical Safety Training by ISRI
Electrical Safety Training by ISRIElectrical Safety Training by ISRI
Electrical Safety Training by ISRI
 
arcflashsolutions2-160226132648
arcflashsolutions2-160226132648arcflashsolutions2-160226132648
arcflashsolutions2-160226132648
 
Understanding Arc Flash presentation engineering
Understanding Arc Flash presentation engineeringUnderstanding Arc Flash presentation engineering
Understanding Arc Flash presentation engineering
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Electrical Safety and NFPA 70E Study Sheet v2.0
Electrical Safety and NFPA 70E Study Sheet v2.0Electrical Safety and NFPA 70E Study Sheet v2.0
Electrical Safety and NFPA 70E Study Sheet v2.0
 
Arc Flash as it Relates to AC Drives
Arc Flash as it Relates to AC DrivesArc Flash as it Relates to AC Drives
Arc Flash as it Relates to AC Drives
 
Electrical hazards
Electrical hazardsElectrical hazards
Electrical hazards
 
Safety In Electrical Jobs.pdf
Safety In Electrical Jobs.pdfSafety In Electrical Jobs.pdf
Safety In Electrical Jobs.pdf
 
HVM NFPA 70E White Paper
HVM NFPA 70E White PaperHVM NFPA 70E White Paper
HVM NFPA 70E White Paper
 
Arc flash analysis, electrical safety and risk assessment
Arc flash analysis, electrical safety and risk assessmentArc flash analysis, electrical safety and risk assessment
Arc flash analysis, electrical safety and risk assessment
 
Arc flash in Industry
Arc flash in Industry Arc flash in Industry
Arc flash in Industry
 
What is an arc flash?
What is an arc flash? What is an arc flash?
What is an arc flash?
 

Más de Thorne & Derrick International

Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...Thorne & Derrick International
 
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical EqptTHORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical EqptThorne & Derrick International
 
The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018Thorne & Derrick International
 
3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick International3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick InternationalThorne & Derrick International
 
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-AThorne & Derrick International
 
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...Thorne & Derrick International
 
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...Thorne & Derrick International
 
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam RowePepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam RoweThorne & Derrick International
 
Ultrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification DemandUltrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification DemandThorne & Derrick International
 
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282DSIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282DThorne & Derrick International
 
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...Thorne & Derrick International
 
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec SheetFiloform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec SheetThorne & Derrick International
 

Más de Thorne & Derrick International (20)

Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...
 
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical EqptTHORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
 
The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018
 
3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick International3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick International
 
CATU Electrical Safety Catalogue
CATU Electrical Safety CatalogueCATU Electrical Safety Catalogue
CATU Electrical Safety Catalogue
 
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
 
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
 
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
 
Roxtec Cable Transit - B Frame Dimensional Drawing
Roxtec Cable Transit - B Frame Dimensional DrawingRoxtec Cable Transit - B Frame Dimensional Drawing
Roxtec Cable Transit - B Frame Dimensional Drawing
 
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam RowePepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
 
T&D Experts In Equipment For Explosive Atmospheres
T&D Experts In Equipment For Explosive AtmospheresT&D Experts In Equipment For Explosive Atmospheres
T&D Experts In Equipment For Explosive Atmospheres
 
Ultrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification DemandUltrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification Demand
 
Emtelle Fibre Optic Cables - Product Catalogue 2016
Emtelle Fibre Optic Cables - Product Catalogue 2016Emtelle Fibre Optic Cables - Product Catalogue 2016
Emtelle Fibre Optic Cables - Product Catalogue 2016
 
Thorne & Derrick Process Heating Brochure 2016
Thorne & Derrick Process Heating Brochure 2016Thorne & Derrick Process Heating Brochure 2016
Thorne & Derrick Process Heating Brochure 2016
 
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282DSIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
 
Ripley Utility Tool Cable Preparation Tools
Ripley Utility Tool Cable Preparation ToolsRipley Utility Tool Cable Preparation Tools
Ripley Utility Tool Cable Preparation Tools
 
RIDGID micro CD100 Combustible Gas Detector
RIDGID micro CD100 Combustible Gas DetectorRIDGID micro CD100 Combustible Gas Detector
RIDGID micro CD100 Combustible Gas Detector
 
Itron Fact Sheet
Itron Fact SheetItron Fact Sheet
Itron Fact Sheet
 
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
 
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec SheetFiloform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
 

Último

DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenHervé Boutemy
 
SALESFORCE EDUCATION CLOUD | FEXLE SERVICES
SALESFORCE EDUCATION CLOUD | FEXLE SERVICESSALESFORCE EDUCATION CLOUD | FEXLE SERVICES
SALESFORCE EDUCATION CLOUD | FEXLE SERVICESmohitsingh558521
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Mark Simos
 
The State of Passkeys with FIDO Alliance.pptx
The State of Passkeys with FIDO Alliance.pptxThe State of Passkeys with FIDO Alliance.pptx
The State of Passkeys with FIDO Alliance.pptxLoriGlavin3
 
Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 3652toLead Limited
 
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxLoriGlavin3
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxLoriGlavin3
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyAlfredo García Lavilla
 
Connect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationConnect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationSlibray Presentation
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupFlorian Wilhelm
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Mattias Andersson
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brandgvaughan
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr BaganFwdays
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfMounikaPolabathina
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsRizwan Syed
 
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxA Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxLoriGlavin3
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersRaghuram Pandurangan
 
The Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and ConsThe Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and ConsPixlogix Infotech
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek SchlawackFwdays
 

Último (20)

DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache Maven
 
SALESFORCE EDUCATION CLOUD | FEXLE SERVICES
SALESFORCE EDUCATION CLOUD | FEXLE SERVICESSALESFORCE EDUCATION CLOUD | FEXLE SERVICES
SALESFORCE EDUCATION CLOUD | FEXLE SERVICES
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
 
The State of Passkeys with FIDO Alliance.pptx
The State of Passkeys with FIDO Alliance.pptxThe State of Passkeys with FIDO Alliance.pptx
The State of Passkeys with FIDO Alliance.pptx
 
Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365
 
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easy
 
Connect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationConnect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck Presentation
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project Setup
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brand
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdf
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL Certs
 
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxA Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information Developers
 
The Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and ConsThe Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and Cons
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
 

Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Work Conditions, Reducing Arc Flash Hazard, Choosing Correct Personal Protection Equipment PPE, What Is An Arc Flash?

  • 2. Worker Training of Electrical Hazards Including Arc Flash SH-16614-07 This material was produced under grant number SH-16614-07 from the Occupational Safety and Health Administration, U.S. Department of Labor. It does not necessarily reflect the views or policies of the U.S. Department of Labor, nor does mention of trade names, commercial products, or organizations imply endorsement by the U.S. Government. 2
  • 3. Overview • • • • • • • • • 3 Introduction Revisions to the NFPA 70E Electrically Safe Work Conditions Energized Electrical Work Permit Flash Protection Boundary and Limits of Approach NFPA 70E Boundaries and Spaces Flash Protection Calculations Choosing Correct PPE Reducing the Arc Flash Hazard
  • 4. Introduction • What is Arc Flash? – Arc flash results from an arcing fault, where the electric arcs and resulting radiation and shrapnel cause severe skin burns, hearing damage, and eye injuries. 4
  • 5. Introduction Why are we so interested in Arc Flash now? – Numerous workers are injured and/or killed each year while working on energized equipment. Many of these casualties are a result of arc flash. – Working on energized equipment has become commonplace in many industries. 5
  • 6. Introduction Injuries that can result from an arc flash: – Burns – Respiratory system damage – Hearing damage – Skin penetration from flying debris – Eye and face injuries 6
  • 7. Introduction Important Temperatures Skin temperature for curable burn Skin temperature causing cell death Ignition of clothing Burning clothing Metal droplets from arcing Surface of sun Arc terminals 7 176°F 205°F 752°-1472°F 1472°F 1832°F 9000°F 35,000°F
  • 8. Introduction • A First Degree Burn is red and sensitive to touch. There is minimal skin damage and only the skin surface is involved. Example: Sunburn 8
  • 9. Introduction • A Second Degree Burn involves the first and second layers of skin. The skin reddens intensely and blisters develop. Severe pain and swelling occur and chance for infection is present. 9
  • 10. Introduction • A Third Degree Burn causes charring of skin and coagulation of blood vessels just below the skin surface. All three layers of skin are affected. Extensive scarring usually results. 10
  • 11. Introduction • Skin damage will occur based on the intensity of the heat generated by an electrical arc accident. The heat reaching the skin of the worker is dependant on the following three factors: – Power of the arc at the arc location – Distance of the worker to the arc – Time duration of the arc exposure 11
  • 12. Introduction • The intent of NFPA 70E regarding arc flash is to provide guidelines which will limit injury to the onset of second degree burns. 12
  • 13. Introduction Inhalation Injuries In addition to burns, an arc flash can cause inhalation injuries. More than a hundred known toxic substances are present in fire smoke. When inhalation injuries are combined with external burns the chance of death can increase significantly. 13
  • 14. Introduction • The pressure of an arc blast is caused by the expansion of the metal as it vaporizes and the heating of the air by the arc energy. This accounts for the expulsion of molten metal up to 10 feet away. • In addition, the sudden expansion of an arc blast creates loud sounds that can cause hearing damage. 14
  • 15. Revisions To The NFPA 70E As a result of the injuries and deaths related to arc flash, changes/additions have been incorporated into the National Fire Protection Association publication number 70E, the most recent version being NFPA 70E-2004. 15
  • 16. Revisions To The NFPA 70E 1. Only qualified persons shall be permitted to work on electrical conductors or circuit parts that have not been put into an electrically safe work condition. (reference: NFPA 70E-2004 Section 110.8(A)(2) ©NFPA). 2. A flash hazard analysis shall be done in order to protect personnel from the possibility of being injured by an arc flash. (reference: NFPA 70E2004 Section 130.3 ©NFPA). 16
  • 17. Revisions To The NFPA 70E 3. Employees working in areas where electrical hazards are present shall be provided with, and shall use, protective equipment that is designed and constructed for the specific part of the body to be protected and for the work to be performed (reference: NFPA 70E2004 Section 130.7(A) ©NFPA). 17
  • 18. Revisions To The NFPA 70E 4. Personal protective equipment shall conform to the standard given in Table 130.7(C)(8) (reference: NFPA 70E-2004 130.7(C)(8) ©NFPA). 5. Arc Flash Protective Equipment: …… The entire flash suit, including the hood’s face shield, shall have an arc rating that is suitable for the arc flash exposure (reference: NFPA 70E-2004 Section 130.7(C)(13)(a)). 18
  • 19. Arc Flash Awareness • NIOSH DVD: Arc Flash Awareness – Information and discussion about arc flash and comments from workers injured by an arc flash 19
  • 20. Electrically Safe Work Conditions • The equipment is not and cannot be energized: To ensure an electrically safe work condition: – Identify all power sources, – Interrupt the load and disconnect power, – Visually verify that a disconnect has opened the circuit, – Locking out and tagging the circuit, – Test for absence of voltage, and – Ground all power conductors, if necessary. 20
  • 21. Electrically Safe Work Conditions • Lockout/Tagout – A single qualified person de-energizing one set of conductors. – An unqualified person may never perform a lockout/tagout, work on energized equipment, or enter high risk areas. 21
  • 22. Energized Electrical Work Permit • When live parts over 50 volts are not placed in an electrically safe work condition it is considered energized electrical work and must be down under a written permit. • Permit gives conditions and work practices needed to protect employee from arc flash or contact with live parts. 22
  • 23. Energized Electrical Work Permit An Energized Electrical Work Permit will include: – – – – – – – – 23 Circuit, equipment and location Why working while energized. Shock and arc flash hazard analysis Safe work practices Approach boundaries Required PPE and tools Access control Proof of job briefing
  • 24. Flash Protection Boundary and Limits of Approach • Definitions of Boundaries and Spaces The closer you approach an exposed, energized conductor or circuit part, the greater the chance of an inadvertent contact and the greater the injury that an arc flash will cause. NFPA 70E-2004, Annex C defines approach boundaries and work spaces. The diagram on the next slide illustrates these. 24
  • 25. Flash Protection Boundary and Limits of Approach 25 Approach/Flash Protection Boundaries
  • 26. Flash Protection Boundary and Limits of Approach • Flash Protection Boundary When an energized conductor is exposed, you may not approach closer than the flash boundary without wearing appropriate personal protective clothing and personal protective equipment. 26
  • 27. Flash Protection Boundary and Limits of Approach • Flash Protection Boundary IEEE defines “Flash Protection Boundary” as: An approach limit at a distance from live parts operating at 50 V or more that are un-insulated or exposed within which a person could receive a second degree burn. 27
  • 28. Flash Protection Boundary and Limits of Approach How Does Flash Protection Boundary Relate to Working On Or Near Exposed Energized Parts? • The radiant energy and molten material that is released by an electric arc is capable of seriously injuring or killing a human being at distances of up to twenty feet. The flash protection boundary is the closest approach allowed by qualified or unqualified persons without the use of arc flash PPE. 28
  • 29. Flash Protection Boundary and Limits of Approach NFPA 70E 2004, Table 130.2(C) ©NFPA Approach Boundaries to Live Parts for Shock Protection. (All dimensions are distance from live part to employee.) (1) (2) (3) (4) (5) 1 Limited Approach Boundary Restricted Approach Boundary1; Includes Inadvertent Movement Adder Nominal System Voltage Range, Phase to Phase Exposed Fixed Circuit Part Less than 50 Not specified Not specified Not specified Not specified 50 to 300 10 ft 0 in. 3 ft 6 in. Avoid contact Avoid contact 301 to 750 10 ft 0 in. 3 ft 6 in. 1 ft 0 in. 0 ft 1 in. 751 to 15 kV 10 ft 0 in. 5 ft 0 in. 2 ft 2 in. 0 ft 7 in. 15.1 kV to 36 kV 10 ft 0 in. 6 ft 0 in. 2 ft 7 in. 0 ft 10 in. 36.1 kV to 46 kV 10 ft 0 in. 8 ft 0 in. 2 ft 9 in. 1 ft 5 in. 46.1 kV to 72.5 kV 29 Exposed Movable Conductor Prohibited Approach Boundary1 10 ft 0 in. 8 ft 0 in. 3 ft 3 in. 2 ft 1 in.
  • 30. Flash Protection Boundary and Limits of Approach Typical NEC Label 30
  • 31. Flash Protection Boundary and Limits of Approach Typical Detailed Label 31
  • 32. NFPA 70E Boundaries and Spaces Good safety practices minimize risk: • Switch remotely if possible. • Standing aside and away as much as possible during switching. • Avoid leaning on or touching switchgear and metallic surfaces. • Use proper tools and PPE. 32
  • 33. NFPA 70E Boundaries and Spaces • NFPA 70E, Section 130.3(B) states: • If work will be performed within the flash protection boundary, the flash hazard analysis shall determine, and the employer shall document, the incident energy exposure of the worker in (cal/cm2). 33
  • 34. NFPA 70E Boundaries and Spaces NFPA 70E, Section 130.3 (B) states: • The incident energy exposure level shall be based on the working distance of the worker’s face and chest areas from a prospective arc source for the specific task to be performed. 34
  • 35. NFPA 70E Boundaries and Spaces • NFPA 70E, Section 130.3(B) states: Flame Resistant (FR) Clothing and Personal Protective Equipment (PPE) shall be used by the employee based upon the incident energy exposure associated with the specific task. 35
  • 36. Flash Protection Calculations • The Incident Energy and Flash Protection Boundary can be calculated in an Arc Flash Hazard Analysis. • There are two methods: – NFPA 70E-2004, Annex D – IEEE Std 1584TM 36
  • 37. Flash Protection Calculations Step 1 • Collect the System Installation Equipment Data Step 2 • Determine the Power System’s Modes of Operation – Normal operation, tie switched closed, dual feeds – Perform analysis for worst case condition 37
  • 38. Flash Protection Calculations Step 3 • Determine the Bolted Fault Currents – Find symmetrical RMS current and X/R ratio at each point of concern. • • • 38 Theoretically worst case fault magnitude Determines equipment interrupting ratings Impedance at fault location is considered to be zero ohms
  • 39. Flash Protection Calculations Step 4 • Determine the Arc Fault Currents – The arc fault current for each location where an arc flash hazard exists and the portion of the current that flows through the closest upstream device that will clear this fault must be determined 39
  • 40. Flash Protection Calculations Arcing Fault Current is fault current flowing through an electrical arc plasma. • • Faults which are not bolted Poor electrical connection between conductors can cause arcing • Arcing results in tremendous heat (35,000) 40
  • 41. Flash Protection Calculations Step 5 • From the Protective Device Characteristics, Find the Arcing Duration – The total clearing time of the fault will determine the “time” factor in the incident energy equation. 41
  • 42. Flash Protection Calculations CURRENT IN AMPERES The fault clearing time is determined from the Coordination Study’s Time Current Curves. 1000 T4 T4 100 The total clearing time of the primary fuse for a secondary side fault is 1 second. T4 1 sec M2 1 T4 Main Phase T4 - T5 Phase TX Inrush 0.10 0.01 42 TIME IN SECONDS HMCP 250 A 100 hp O/L 10 0.5 1 10 100 MCC Fdr Phase 1K 10K T4 arc flash.tcc Ref. Voltage: 480 Current Scale x10^2 T4 arc flash.drw
  • 43. Flash Protection Calculations Step 6 • Record the System Voltages and Equipment Classes – For each bus or arc hazard location Step 7 • Determine Working Distances – Arc flash protection is always based on the incident energy to a person’s face and body at the working distance 43
  • 44. Flash Protection Calculations Step 8 • Determine Incident Energy – This is best done using a software package. • Calculating incident energy requires the following parameters: – Max. bolted 3-ph fault current available at the equipment – Total protective upstream device clearing time max fault current – Distance of worker from the arc 44
  • 45. Flash Protection Calculations Step 9 • Determine the Flash Protection Boundary for All Equipment – The incident energy for the flash-protection boundary must be set at the minimum energy beyond which a second degree burn could occur - 1.2 cal/cm2 45
  • 46. Flash Protection Calculations Let’s take a quick look at the NFPA 70E-2004 equations 46
  • 47. Flash Protection Calculations The estimated incident energy for an arc in open air is: EMA = 5271DA-1.9593 tA[0.0016F 2-0.0076F+0.8938] EMA=maximum open arc incident energy (cal/cm 2) DA=distance from arc electrodes (inches) tA=arc duration (seconds) F=bolted fault current in kA (16kA-50kA) 47
  • 48. Flash Protection Calculations The estimated incident energy for an arc in a box is: EMB = 1038.7DB-1.4738 tA[0.0093F2-0.3453F+5.9675] EMB=max 20 in. cubic box incident energy (cal/cm 2) DB=distance from arc electrodes (inches) for 18 in. and greater tA=arc duration (seconds) F=bolted fault current in kA (16kA-50kA) 48
  • 49. Flash Protection Calculations • Test results have shown that the incident energy for an open air arc is approximately inversely proportional to the distance squared. • Enclosing a 3-ph arc in a box can increase the incident energy from 1.5 to 3 times depending upon the arc parameters and box dimensions when compared to an open air arc with the same parameters. 49
  • 50. Flash Protection Calculations There are resources on the internet to assist in calculations: • http:// www.littelfuse.com/arccalc/calc.html • http://www.pnl.gov/contracts/esh-procedures/forms/sp00e230.xls • http:// www.bussmann.com/arcflash/index.aspx 50
  • 51. Flash Protection Calculations As well as software and spreadsheets: 51
  • 52. Choosing Correct PPE Section 130.7(A) states that employees working in areas where there are electric hazards shall be provided with, and shall use, protective equipment that is designed and constructed for the specific part of the body to be protected and for the work to be performed. 52
  • 53. Choosing Correct PPE • Personal Protective Equipment, PPE, for the arc flash is the last line of defense. • It is not intended to prevent all injuries, but is intended to mitigate the impact of an arc flash, should one occur. 53
  • 54. Choosing Correct PPE • After the Arc-Flash Hazard Analysis has been performed, PPE is selected as follows: Clothing’s ATPV or EBT (in cal/cm2) > Calculated Hazard Level (in cal/cm2) *ATPV can be obtained from clothing manufacturer 54
  • 55. Choosing Correct PPE ATPV - Arc Thermal Performance Exposure Value EBT - Breakopen Threshold Energy Rating Calculated Hazard Level - Incident Energy in cal/cm2 55
  • 56. Choosing Correct PPE • Specialized Arc-Flash Protection Equipment: Flash Suit • Use: Hazard/Risk Category 4 56
  • 57. Choosing Correct PPE • Specialized Arc-Flash Protection Equipment: Switching Coat, ATPV = 42 cal/cm2 • Use: Hazard/Risk Category 4 57
  • 58. Choosing Correct PPE • Specialized Arc-Flash Protection Equipment: Hood, ATPV = 42 cal/cm2 • Use: Hazard/Risk Category 4 58
  • 59. Choosing Correct PPE • Specialized Arc-Flash Protection Equipment: Face Shield -- Attaches to Hard Hat • Use: Hazard/Risk Category 2 59
  • 60. Choosing Correct PPE • Specialized Arc-Flash Protection Equipment: Gloves and Leather Protectors, (ATPV Values not Established for Rubber) • Use: Hazard/Risk Category 2, 3, and 4 for the Leather Protectors 60
  • 61. Choosing Correct PPE • NFPA 70E, Section 130.7(C)(9)(a) states: – When selected in lieu of the flash hazard analysis of 130.3(A), Table 130.7(C)(9)(a) shall be used to determine the hazard/risk category for each task. • NFPA 70E, Section 130.7(C)(10) states: – Once the Hazard/Risk Category has been identified, Table 130.7(C)(10) shall be used to determine the required personal protective equipment (PPE) for the task. 61
  • 62. Choosing Correct PPE The tables in NFPA 70E-2004 provide the simplest methods for determining PPE requirements. They provide instant answers with almost no field data. The tables provide limited application and are conservative for most applications. *These tables are not intended as a substitution for an arc hazard analysis, but only as a guide. 62
  • 63. Choosing Correct PPE A simplified two-category approach is found in NFPA 70E-2004, Table H-1 of Annex H ©NFPA. This table assures adequate PPE for electrical workers within facilities with large and diverse electrical systems. 63
  • 64. Choosing Correct PPE The clothing listed in Table H-1 fulfills the minimum FR clothing requirements of NFPA 70E-2004, Tables 130.7(C)(9)(a) and 130.7(C)(10) ©NFPA and should be used with the other PPE appropriate for the Hazard/ Risk Category that is found in of NFPA 70E-2004, Table 130.7(C)(10) ©NFPA. 64
  • 65. Choosing Correct PPE Everyday Work Clothing Applicable Tasks All Hazard/Risk Category 1 or 2 tasks listed in Table 130.7(C)(9)(a) ©NFPA FR long sleeve shirt (minimum arc rating of 4) worn over an untreated cotton T-shirt with FR pants (minimum arc rating of 8) Or FR coveralls (minimum arc rating of 4) worn over an untreated cotton T-shirt with untreated natural fiber pants. 65 On systems operating at less than 1000 V, these tasks include all work except: • Insertion or removal of MCC buckets • Insertion or removal of power circuit breakers with switchgear doors open • Removal of bolted covers from switchgear On systems >1000 V, also includes operation, insertion or removal of switching devices with equipment enclosure doors closed.
  • 66. Choosing Correct PPE Electrical “Switching” Clothing Applicable Tasks Multilayer FR flash jacket and FR Bib overalls worn over FR coveralls (minimum arc rating of 4) All Hazard/Risk Category 1 or 2 tasks listed in NFPA 70E, Part II, Table 3-3.9.1 ©NFPA Or Insulated FR coveralls (minimum arc rating of 25) worn over untreated natural fiber long sleeve shirt with cotton blue jeans and worn over an untreated cotton T-shirt. 66 On systems ≥1000 V, tasks include work on exposed energized parts of all equipment On systems <1000 V, tasks include insertion or removal of LV MCC buckets, insertion or removal of power circuit breakers with the switchgear enclosure doors open, and removal of bolted covers from switchgear
  • 67. Choosing Correct PPE • NFPA 70E-2004, Section 130.7(C), Table 130.7(C)(9)(a) lists common work tasks with respective Hazard/Risk category of each task. • After the Hazard Risk Category has been determined from Table 130.7(C)(9)(a), then Table 130.7(C)(10) is used to determine the Protective Clothing and Personal Protective Equipment required for the task. 67
  • 68. Choosing Correct PPE Hazard/ Risk Category V-rated V-rated Gloves Tools CB or fused switch operation with enclosure doors closed 0 N N Reading a panel meter while operating a meter switch 0 N N CB or fused switch operation with enclosure doors open 1 N N Work on energized parts, including voltage testing 2* Y Y Task (Assumes Equipment Is Energized, and Work Is Done Within the Flash Protection Boundary) 68
  • 69. Choosing Correct PPE • NFPA 70E, Table 130.7(C)(11) lists the characteristics and degrees of protection for various Flame Resistant (FR) clothing systems. 69
  • 70. Choosing Correct PPE NFPA 70E Table 130.7(C)(11) Typical Protective Clothing Systems Clothing Description (Number of clothing layers is given in parenthesis) Total Weight oz/yd2 Hazard Risk Category Minimum Arc Thermal Performance Exposure Value (ATPV)* or Breakdown Threshold Energy (EBT)* Rating of PPE cal/cm2 0 Untreated Cotton (1) 4.5 - 7 N/A 1 FR shirt and FR pants (1) 4.5 - 8 5 2 Cotton underwear plus FR shirt and FR pants (2) 9 - 12 8 3 Cotton underwear plus FR shirt and FR pants plus FR coverall (3) 16 - 20 25 4 Cotton underwear plus FR shirt and FR pants plus double layer switching coat and pants (4) 24-30 40 * ATPV is defined as the incident energy that would just cause the onset of a second degree burn. * EBT is defined as the highest incident energy which did not cause FR fabric breakopen and did not exceed the second degree burn criteria. E BT is reported when ATPV cannot be measured due to fabric breakopen. 70
  • 71. Choosing Correct PPE The equations in NFPA 70E-2004 provide more accurate methods than tables for determining PPE requirements. System data and studies are required. The equations are based upon limited fuse and circuit breaker data. 71
  • 72. Choosing Correct PPE • Remember: PPE is the last line of defense. PPE cannot prevent all injuries and will only lessen the impact of an arc flash. In many cases the use of PPE has saved lives or prevented serious injury. 72
  • 73. Reducing The Arc Flash Hazard OSHA 1910.333 severely limits the situations in which work is performed on or near equipment or circuits that are or may be energized. 73
  • 74. Reducing The Arc Flash Hazard EQUIPMENT ALTERNATIVES • Metal-Clad Switchgear Structural design reduces the possibility of arcing faults within the enclosure. 74
  • 75. Reducing The Arc Flash Hazard EQUIPMENT ALTERNATIVES • Arc Resistant Switchgear EEMAC Standard G14-1 defines the requirements for arc resistant switchgear. Includes robust design and pressure relief vents. 75
  • 76. Reducing The Arc Flash Hazard EQUIPMENT ALTERNATIVES • Current-Limiter Power Circuit Breakers Reduces the clearing time which reduces the incident energy. 76
  • 77. Reducing The Arc Flash Hazard EQUIPMENT ALTERNATIVES • Current-Limiting Reactors Reduces the magnitude of fault current which reduces the incident energy. 77
  • 78. Reducing The Arc Flash Hazard EQUIPMENT ALTERNATIVES • Zone Selective Interlocking of Circuit Breakers Deactivates the preset delay on the circuit breaker closest to the fault, which then trips with no intentional delay. 78
  • 79. Reducing The Arc Flash Hazard Whatever the analysis method or proposed method of solution, each work task must be analyzed assuming worst case conditions. 79
  • 80. Reference Materials • • • • • • • • 80 Standard for Electrical Safety in the Workplace, NFPA 70E 2004 Edition Controlling Electrical Hazards. OSHA Publication 3075, (2002). Also available as a 350 KB PDF, 71 pages. Provides a basic overview of electrical safety on the job, including information on how electricity works, how to protect against electricity, and how OSHA can help. Electrical Safety: Safety and Health for Electrical Trades Student Manual. US Department of Health and Human Services (DHHS), National Institute for Occupational Safety and Health (NIOSH), Publication No. 2002-123, (2002, January), 1.7 MB PDF, 88 pages. This student manual is part of a safety and health curriculum for secondary and post-secondary electrical trades courses. It is designed to engage the learner in recognizing, evaluating, and controlling hazards associated with electrical work. http://www.cdc.gov/niosh/pdfs/02-123.pdf Electrocutions Fatality Investigation Reports. National Institute for Occupational Safety and Health (NIOSH) Safety and Health Topic. Provides information regarding hundreds of fatal incidents involving electrocutions investigated by NIOSH and state investigators Working Safely with Electricity. OSHA Fact Sheet, 353 KB PDF, 2 pages. Provides safety information on working with generators, power lines, extension cords, and electrical equipment. http://www.osha.gov/OshDoc/data_Hurricane_Facts/elect_safety.pdf Lockout/Tagout. OSHA Fact Sheet, (2002), 212 KB PDF, 2 pages. A 92 KB PDF (Spanish version) is also available. http://www.cdc.gov/nasd/docs/d001501-d001600/d001514/d001514.html Lockout-Tagout Interactive Training Program. OSHA. Includes selected references for training and interactive case studies. http://www.osha.gov/dts/osta/lototraining/index.htm NIOSH Arc Flash Awareness, NIOSH Publication No. 2007-116D

Notas del editor

  1. NIOSH Suggested Discussion Questions: If one of the incidents in the video had happened to you, how would it have changed your life or the life of your family? Have you ever experienced an arc flash? What happened? Did you change any safety practices in your work after the incident? What were they? What are some behaviors that you can change to help prevent an arc flash incident to yourself and/or to your fellow electricians? What PPE is recommended for your task? What are some of the excuses electricians use for not wearing appropriate PPE? In, general, as electricians become more experienced, do you think their safety habits change? How? After viewing this video, which, if any, of your safety work habits would you like to change? Do you have any suggestions for your supervisor that you feel could help prevent an arc flash incident from happening to you or any of your co-workers? What suggestions do you have for your company to help prevent arc flash incidents? Arc Flash Awareness: DHHS(NIOSH) Publication No. 2007-116D Ordering Information: Copies of NIOSH documents are available from: NIOSH-Publications Dissemination 4676 Columbia Parkway Cincinnati, OH 45226-1998 Fax: 513-533-8573, Phone: 1-800-35-NIOSH Email: pubstaft@cdc.gov, website: www.cdc.gov/niosh
  2. The NEC warning label should remind a qualified worker who intends to open the equipment for analysis or work that a serious hazard exists and that the worker should follow appropriate work practices and wear appropriate PPE for the specific hazard (a non qualified worker must not be opening the equipment).
  3. The NEC 2002, section 110.16 requirement for labeling does not call for any quantification of the incident energy, however, some companies are choosing to provide more information on the arc flash label as shown above. The manufacturer of the equipment is normally not aware of the site specific configuration of the power system at the point where the equipment will be connected or aware of the site specific tasks that will be evaluated. The installer or the owner of the equipment must label the equipment.
  4. Arc-flash protection is always based on the incident energy level on the person’s face and body at the working distance, not the incident energy on the hands or arms. The degree of injury in a burn depends on the percentage of a person’s skin that is burned. The head and body are a large percentage of total skin surface area and injury to these areas is much more life threatening than burns on the extremities.
  5. Data required for this study is similar to data collected for typical short-circuit and protective device coordination studies, however it also requires information on low-voltage distribution and control equipment plus its feeders and large branch circuits. This information is used to determine the time of arc duration from the protective device time current curves.
  6. Find the symmetrical root-mean-square (RMS) bolted fault current and X/R ratio at each point of concern for the 1.5 to 4 cycle case. This includes all locations where people could be working. It is important to include all cables. Conservatively high fault levels do not necessarily increase safety, they may reduce it. Don’t add a safety factor. Higher current can give shorter arc fault duration and the wrong energy value. Lower fault currents often persist longer than higher currents because of the characteristic shape of most protective-device time-current curves. Common causes of bolted faults: 1. Re-energizing without removing temporary grounding. 2. Incorrect connection of a parallel run of cables to a motor terminal box. Instead of connecting a-a, b-b, c-c; connections are a-b, a-b, c-c.
  7. The arc fault current for each location where an arc flash hazard exists and the portion of that current that flows through the closest upstream protective device that will clear this fault must be determined. The arc fault current depends primarily on the bolted fault current. The bolted fault current in the protective device can be found from the short-circuit study by looking at the detailed bus fault printout or looking at the fault levels that are “one-bus-away”. It is important to separate fault contributions from all other sources that will not flow through the protective device that will clear the fault. This includes alternate feeder and downstream motor fault contributions. The arc fault currents can then be calculated. The calculated arc fault current will be lower than the bolted fault current due to arc impedance, especially for applications less than 1000 V.
  8. There are two types of protective devices in power distribution systems. These are fuses or circuit breakers. For fuses, the manufacturer’s time-current curves may include both melting and clearing time. If so, use the clearing time. If they show only the average melt time, add to that time 15% for times up to 0.03 seconds, and 10% above 0.03 seconds to determine total clearing time. For Current Limiting Fuses (CLF), use the maximum clearing time from the fuse time current curve if fault current is not in the current limiting range. The current limit point is at the 0.01 sec point on the fuse curve. For one to two times the limit point in amps, use 0.008 seconds (1/2 cycle). For over two times the limit point, use 0.004 seconds (1/4 cycle). For circuit breakers with integral trip units, the manufacturer’s time-current curves include both the tripping time and the clearing time. The total clearing time as shown by the top band of the curve is the time value that should be used. For relay operated circuit breakers, the relay curves show only the relay operating time in the time-delay region. For relays operating in their instantaneous region, allow 16 milliseconds on 60 Hz systems for operation. The circuit breaker opening time must be added to the relay time to give a total clearing time.
  9. &lt;number&gt; Equation 1 provides smaller values of the flash boundary because actual transformer ratings and power system impedances are used. Equation must not be applied without an accurate up-to-date short circuit analysis at the point of exposure. For transformers rated below .75 MVA, multiply transformer MVA by 1.25.
  10. For each bus, document the system voltage and the class of equipment. For example, record whether the equipment is metal-enclosed switchgear or metal-clad switchgear. IEEE 1584, Table - Classes of equipment and typical bus gaps Arc-flash protection is always based on the incident energy level on the person’s face and body at the working distance, not the incident energy on the hands or arms. The degree of injury in a burn depends on the percentage of a person’s skin that is burned. The head and body are a large percentage of total skin surface area and injury to these areas is much more life threatening than burns on the extremities.
  11. The equations in IEEE 1584-2002 are available in spreadsheet format. These equations have been incorporated into the packages of power system software vendors.
  12. lg is the log10 Ia is arcing current in kA K is -0.153 for open configurations, and is -0.097 for box configurations Ibf is bolted fault current for 3-ph symmetrical RMS in kA V is system voltage in kV G is the gap between conductors in mm
  13. NFPA equations for “Open Air” and “Arc in a Box” are valid for 600 V or below.
  14. NFPA equations for “Open Air” and “Arc in a Box” are valid for 600 V or below.
  15. A simplified two-category approach is found in NFPA 70E-2000, Table F-1 of Part II, Appendix F NFPA. This table assures adequate PPE for electrical workers within facilities with large and diverse electrical systems. The clothing listed in Table F-1 fulfills the minimum FR clothing requirements of NFPA 70E-2000, Tables 3-3.9.1 and 3-3.9.2 NFPA and should be used with the other PPE appropriate for the Hazard/ Risk Category that is found in of NFPA 70E-2000, Table 3-3.9.2 NFPA.
  16. A simplified two-category approach is found in NFPA 70E-2000, Table F-1 of Part II, Appendix F NFPA. This table assures adequate PPE for electrical workers within facilities with large and diverse electrical systems. The clothing listed in Table F-1 fulfills the minimum FR clothing requirements of NFPA 70E-2000, Tables 3-3.9.1 and 3-3.9.2 NFPA and should be used with the other PPE appropriate for the Hazard/ Risk Category that is found in of NFPA 70E-2000, Table 3-3.9.2 NFPA.
  17. A simplified two-category approach is found in NFPA 70E-2000, Table F-1 of Part II, Appendix F NFPA. This table assures adequate PPE for electrical workers within facilities with large and diverse electrical systems. The clothing listed in Table F-1 fulfills the minimum FR clothing requirements of NFPA 70E-2000, Tables 3-3.9.1 and 3-3.9.2 NFPA and should be used with the other PPE appropriate for the Hazard/ Risk Category that is found in of NFPA 70E-2000, Table 3-3.9.2 NFPA.
  18. A simplified two-category approach is found in NFPA 70E-2000, Table F-1 of Part II, Appendix F NFPA. This table assures adequate PPE for electrical workers within facilities with large and diverse electrical systems. The clothing listed in Table F-1 fulfills the minimum FR clothing requirements of NFPA 70E-2000, Tables 3-3.9.1 and 3-3.9.2 NFPA and should be used with the other PPE appropriate for the Hazard/ Risk Category that is found in of NFPA 70E-2000, Table 3-3.9.2 NFPA.
  19. &lt;number&gt; 1910.333(a)(1) &quot;Deenergized parts.&quot; Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs. Note 1: Examples of increased or additional hazards include interruption of life support equipment, deactivation of emergency alarm systems, shutdown of hazardous location ventilation equipment, or removal of illumination for an area. Note 2: Examples of work that may be performed on or near energized circuit parts because of infeasibility due to equipment design or operational limitations include testing of electric circuits that can only be performed with the circuit energized and work on circuits that form an integral part of a continuous industrial process in a chemical plant that would otherwise need to be completely shut down in order to permit work on one circuit or piece of equipment.
  20. &lt;number&gt;
  21. &lt;number&gt;
  22. &lt;number&gt;
  23. &lt;number&gt;
  24. &lt;number&gt;
  25. &lt;number&gt;