Motor Protection Circuit Breaker 
Series 8527/2 
www.stahl.de Load Disconnect Switches and Motor Starters E7/1 2013-02-27·EK00·III·en 
Series 8527/2 E7 
02966E00 
WebCode 8527A 
> For protection of Ex e and 
Ex d motors 
> Protects cables and 
plant equipment 
> Adjustable thermal overload 
release, phase failure sensitive 
> Electromagnetic 
instantaneous release 
> Robust enclosure made of glass 
fibre reinforced polyester resin 
> Optionally with 
– undervoltage release 
– shunt release 
– ammeter 
– auxiliary contacts 
Motor protection circuit breakers of Series 8527 are used where 
high short circuit currents are to be controlled and to protect both 
Ex e and Ex d motors. These switches are suitable to protect cables 
and the installation and can basically be used without a back-up 
fuse at 400 V. 
Breakers are operated by rotary handles enabling next to secure 
switching also to identify clearly switch settings. 
ATEX / IECEx / GOST 
Zone 0 1 2 20 21 22 
For use in x x x x
Motor Protection Circuit Breaker 
Series 8527/2 
Selection Table 
Version without accessories 
L1 L2 L3 
1 3 5 
I > I > I > 
2 4 6 
T1 T2 T3 
Current adjustment range Auxiliary contacts Order number Weight 
Motor protection 
circuit breakers 
without accessories 
Series 8527 
0.1 ... 0.16 A without 8527/21-01-0001 2.591 
0.1 ... 0.16 A 1 NC + 1 NO 8527/22-01-0201 2.610 
0.16 ... 0.25 A without 8527/21-02-0001 2.608 
1 NC + 1 NO 8527/22-02-0201 2.630 
0.25 ... 0.4 A without 8527/21-03-0001 2.610 
1 NC + 1 NO 8527/22-03-0201 2.630 
0.4 ... 0.63 A without 8527/21-04-0001 2.574 
1 NC + 1 NO 8527/22-04-0201 2.595 
0.63 ... 1 A without 8527/21-05-0001 2.600 
1 NC + 1 NO 8527/22-05-0201 2.620 
1 ... 1.6 A without 8527/21-06-0001 2.653 
1 NC + 1 NO 8527/22-06-0201 2.670 
1.6 ... 2.5 A without 8527/21-07-0001 2.633 
1 NC + 1 NO 8527/22-07-0201 2.650 
2.5 ... 4 A without 8527/21-08-0001 2.630 
1 NC + 1 NO 8527/22-08-0201 2.650 
4 ... 6.3 A without 8527/21-09-0001 2.600 
1 NC + 1 NO 8527/22-09-0201 2.620 
6.3 ... 9 A without 8527/21-10-0001 2.600 
1 NC + 1 NO 8527/22-10-0201 2.620 
9 ... 12.5 A without 8527/21-11-0001 2.500 
1 NC + 1 NO 8527/22-11-0201 2.520 
12.5 ... 16 A without 8527/21-12-0001 2.400 
1 NC + 1 NO 8527/22-12-0201 2.420 
16 ... 20 A without 8527/23-13-0002 4.200 
1 NC + 1 NO 8527/24-13-0202 3.520 
20 ... 22.5 A without 8527/23-14-0002 3.500 
1 NC + 1 NO 8527/24-14-0202 3.520 
On request: • Circuit breakers for the current adjustment range 25 ... 63 A (Type 8525) 
• Further accessories e. g. shunt release, ammeter, additional auxiliary contacts 
(2 NC + 2 NO) 
Load Disconnect Switches and Motor E7/2 Starters 2013-02-27·EK00·III·en
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
Motor Protection Circuit Breaker 
Series 8527/2 
Selection Table 
Version with undervoltage trip 
Current 
adjustment range 
Rated operational 
voltage Ue 
L1 L2 L3 
1 3 5 
I > I > I > 
2 4 6 
T1 T2 T3 
D1 
U < 
D2 
Auxiliary contacts Order number Weight 
kg 
Motor protection 
circuit breakers with 
undervoltage release 
Series 8527 
0.1 ... 0.16 A 230 V AC 
50 / 60 Hz 
without 8527/21-01-1061 2.610 
1 NC + 1 NO 8527/22-01-1261 2.610 
400 V AC 
50 / 60 Hz 
without 8527/21-01-1071 2.610 
1 NC + 1 NO 8527/22-01-1271 2.610 
500 V AC 
50 / 60 Hz 
without 8527/21-01-1091 2.610 
1 NC + 1 NO 8527/22-01-1291 2.610 
0.16 ... 0.25 A 230 V AC 
50 / 60 Hz 
without 8527/21-02-1061 2.630 
1 NC + 1 NO 8527/22-02-1261 2.630 
400 V AC 
50 / 60 Hz 
without 8527/21-02-1071 2.630 
1 NC + 1 NO 8527/22-02-1271 2.630 
500 V AC 
50 / 60 Hz 
without 8527/21-02-1091 2.630 
1 NC + 1 NO 8527/22-02-1291 2.630 
0.25 ... 0.4 A 230 V AC 
50 / 60 Hz 
without 8527/21-03-1061 2.630 
1 NC + 1 NO 8527/22-03-1261 2.630 
400 V AC 
50 / 60 Hz 
without 8527/21-03-1071 2.630 
1 NC + 1 NO 8527/22-03-1271 2.630 
500 V AC 
50 / 60 Hz 
without 8527/21-03-1091 2.630 
1 NC + 1 NO 8527/22-03-1291 2.630 
0.4 ... 0.63 A 230 V AC 
50 / 60 Hz 
without 8527/21-04-1061 2.595 
1 NC + 1 NO 8527/22-04-1261 2.595 
400 V AC 
50 / 60 Hz 
without 8527/21-04-1071 2.595 
1 NC + 1 NO 8527/22-04-1271 2.595 
500 V AC 
50 / 60 Hz 
without 8527/21-04-1091 2.595 
1 NC + 1 NO 8527/22-04-1291 2.595 
0.63 ... 1 A 230 V AC 
50 / 60 Hz 
without 8527/21-05-1061 2.620 
1 NC + 1 NO 8527/22-05-1261 2.620 
400 V AC 
50 / 60 Hz 
without 8527/21-05-1071 2.620 
1 NC + 1 NO 8527/22-05-1271 2.620 
500 V AC 
50 / 60 Hz 
without 8527/21-05-1091 2.620 
1 NC + 1 NO 8527/22-05-1291 2.620 
1 ... 1.6 A 230 V AC 
50 / 60 Hz 
without 8527/21-06-1061 2.670 
1 NC + 1 NO 8527/22-06-1261 2.670 
400 V AC 
50 / 60 Hz 
without 8527/21-06-1071 2.670 
1 NC + 1 NO 8527/22-06-1271 2.670 
500 V AC 
50 / 60 Hz 
without 8527/21-06-1091 2.670 
1 NC + 1 NO 8527/22-06-1291 2.670 
1.6 ... 2.5 A 230 V AC 
50 / 60 Hz 
without 8527/21-07-1061 2.650 
1 NC + 1 NO 8527/22-07-1261 2.650 
400 V AC 
50 / 60 Hz 
without 8527/21-07-1071 2.650 
1 NC + 1 NO 8527/22-07-1271 2.650 
500 V AC 
50 / 60 Hz 
without 8527/21-07-1091 2.650 
1 NC + 1 NO 8527/22-07-1291 2.650 
2013-02-27·EK00·III·en Load Disconnect Switches and Motor Starters E7/3
Motor Protection Circuit Breaker 
Series 8527/2 
Selection Table 
Version with undervoltage trip 
Motor protection 
circuit breakers with 
undervoltage release 
Series 8527 
Current 
adjustment range 
Rated operational 
voltage Ue 
2.5 ... 4 A 230 V AC 
50 / 60 Hz 
L1 L2 L3 
1 3 5 
I > I > I > 
2 4 6 
T1 T2 T3 
D1 
U < 
D2 
Auxiliary contacts Order number Weight 
kg 
without 8527/21-08-1061 2.650 
1 NC + 1 NO 8527/22-08-1261 2.650 
400 V AC 
50 / 60 Hz 
without 8527/21-08-1071 2.650 
1 NC + 1 NO 8527/22-08-1271 2.650 
500 V AC 
50 / 60 Hz 
without 8527/21-08-1091 2.650 
1 NC + 1 NO 8527/22-08-1291 2.650 
4 ... 6.3 A 230 V AC 
50 / 60 Hz 
without 8527/21-09-1061 2.620 
1 NC + 1 NO 8527/22-09-1261 2.620 
400 V AC 
50 / 60 Hz 
without 8527/21-09-1071 2.620 
1 NC + 1 NO 8527/22-09-1271 2.620 
500 V AC 
50 / 60 Hz 
without 8527/21-09-1091 2.620 
1 NC + 1 NO 8527/22-09-1291 2.620 
6.3 ... 9 A 230 V AC 
50 / 60 Hz 
without 8527/21-10-1061 2.620 
1 NC + 1 NO 8527/22-10-1261 2.620 
400 V AC 
50 / 60 Hz 
without 8527/21-10-1071 2.620 
1 NC + 1 NO 8527/22-10-1271 2.620 
500 V AC 
50 / 60 Hz 
without 8527/21-10-1091 2.620 
1 NC + 1 NO 8527/22-10-1291 2.620 
9 ... 12.5 A 230 V AC 
50 / 60 Hz 
without 8527/21-11-1061 2.520 
1 NC + 1 NO 8527/22-11-1261 2.520 
400 V AC 
50 / 60 Hz 
without 8527/21-11-1071 2.520 
1 NC + 1 NO 8527/22-11-1271 2.520 
500 V AC 
50 / 60 Hz 
without 8527/21-11-1091 2.520 
1 NC + 1 NO 8527/22-11-1291 2.520 
12.5 ... 16 A 230 V AC 
50 / 60 Hz 
without 8527/21-12-1061 2.420 
1 NC + 1 NO 8527/22-12-1261 2.420 
400 V AC 
50 / 60 Hz 
without 8527/21-12-1071 2.420 
1 NC + 1 NO 8527/22-12-1271 2.420 
500 V AC 
50 / 60 Hz 
without 8527/21-12-1091 2.420 
1 NC + 1 NO 8527/22-12-1291 2.420 
16 ... 20 A 230 V AC 
50 / 60 Hz 
without 8527/23-13-1062 4.220 
1 NC + 1 NO 8527/24-13-1262 3.520 
400 V AC 
50 / 60 Hz 
without 8527/23-13-1072 4.220 
1 NC + 1 NO 8527/24-13-1272 3.520 
500 V AC 
50 / 60 Hz 
without 8527/21-13-1092 4.220 
1 NC + 1 NO 8527/24-13-1292 3.520 
20 ... 22.5 A 230 V AC 
50 / 60 Hz 
without 8527/23-14-1062 3.520 
1 NC + 1 NO 8527/24-14-1262 3.520 
400 V AC 
50 / 60 Hz 
without 8527/23-14-1072 3.520 
1 NC + 1 NO 8527/24-14-1272 3.520 
500 V AC 
50 / 60 Hz 
without 8527/21-14-1092 3.520 
1 NC + 1 NO 8527/24-14-1292 3.520 
Load Disconnect Switches and Motor E7/4 Starters 2013-02-27·EK00·III·en
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
Motor Protection Circuit Breaker 
Series 8527/2 
Explosion Protection 
Global (IECEx) 
Gas IECEx BVS 08.0047 
Ex d e IIC T* 
Dust IECEx PTB 06.0090 (see type 8146/5) 
Ex tD A21 IP65 T** (see type 8146/5) 
Europe (ATEX) 
Gas DMT 02 ATEX E 026 
E II 2 G Ex d e IIC T* 
Dust PTB 01 ATEX 1024 (see type 8146/5) 
E II 2 D Ex tD A21 IP65 T** (see type 8146/5) 
Certificates and approvals 
Type Adjustment range T* T** 
8527/21, 8527/22 0.1 ... 0.25 A 
0.25 ... 12.5 A 
12.5 ... 16 A 
T6 
T5 
T4 
80 °C 
95 °C 
130 °C 
8527/23 0.1 ... 12.5 A T6 80 °C 
8527/24 16 ... 22.5 A T5 95 °C 
Certificates IECEx, ATEX, Canada (CSA), Kazakhstan (GOST-K), Russia (GOST-R), Belarus (GOST-B) 
Technical data 
Mechanical data 
Degree of protection IP66 acc. to IEC/EN 60529 
Enclosure material Polyester resin, glass-fibre-reinforced, dark grey, similar to RAL 7024 
Surface resistance ( 109 Ω, impact strength ) 7 J, flame-resistant, 
self-extinguishing according to IEC-92-1, UL 94, ASTM D 635-77 
Mounting / installation 
Mounting orientation arbitrary 
Cable entries 
Standard 
Type Accessories 
1) 
8161 Screw connec-tions 
8290 Stopping plug 
M25 x 1.5 M32 x 1.5 M25 x 1.5 
8527/21 without 
with 
23 
-- 
8527/22 without 
with 
23 
-- 
8527/23; 8527/24 without 
with 
- 
1 
22 
8527/25; 8527/26 
0.1 ... 12.5 A without 
with 
23 
-- 
12.5 ... 22.5 A without 
with 
- 
1 
22 
M25 x 1.5 for cables Ø 12 ... 17 mm 
M32 x 1.5 for cables Ø 10 ... 18 mm 
1) auxiliary contacts, undervoltage release, shunt release 
Wire Leads 
Switch insert 
Electrical data 
Rated operational 
voltage 
8527/21 
8527/22 
directly to fitted components 
Main contacts 1.5 ... 6 mm2 finely stranded 
Auxiliary contact 0.75 ... 1.5 mm2 finely stranded 
8527/23 
8527/24 
8527/25 
8527/26 
on terminals 0.5 ... 6 mm2 finely stranded 
Please note: 
Compare cable diameter with cable diameter range of cable entry 
max. 690 V AC, 50 / 60 Hz 
Rated operational 
current 
0.1 ... 22.5 A 
1- 
1- 
1- 
1- 
1- 
1.5 ... 10 mm2 solid 
0.75 ... 2.5 mm2 solid 
0.5 ... 10 mm2 solid 
2013-02-27·EK00·III·en Load Disconnect Switches and Motor Starters E7/5
Motor Protection Circuit Breaker 
Series 8527/2 
Technical data 
Contact Switching 
Capacity 
according to the selected adjustment range (AC) 
Service life 
230 V 400 V 500 V 690 V 
7.0 kW 12.4 kW 16 kW 22 kW 
electrical 105 operations 
mechanical 105 operations 
Main contacts 3-pole 
Short circuit protection 
Thermal overcurrent 
release 
Adjustment ran-ge 
from ... to 
Highest rated current of the short circuit fuse if ICC > ICS 
at 230 V AC at 400 V AC at 440 V AC at 500 V AC at 690 V AC 
ICS gG, 
aM 
ICS gG, 
aM 
ICS gG, 
aM 
ICS gG, 
0.1 A ... 0.16 A 
up to 
1.0 A ... 1.6 A 
Short-circuit proof, 
no fuse needed up to ICC = 100 kA 
1.6 A ... 2.5 A 40 kA 25 A 
2.5 A ... 4.0 A 60 kA 35 A / 
4.0 A ... 6.3 A 70 kA 50 A 40 kA 50 A 7 kA 40 A 
6.3 A ... 9.0 A 50 kA 80 A 30 kA 80 A 5 kA 50 A 
9.0 A ... 12.5 A 75 kA 80 A 45 kA 80 A 27 kA 80 A 4.5 kA 50 A 
12.5 A ... 16.0 A 60 kA 100 A 40 kA 100 A 22 kA 100 A 4 kA 50 A 
16.0 A ... 20.0 A 55 kA 100 A 35 kA 100 A 22 kA 100 A 3.5 kA 50 A 
20.0 A ... 22.5 A 50 kA 125 A 30 kA 125 A 20 kA 125 A 3 kA 50 A 
ICS = Rated short-circuit breaking capacity 
ICC = Projected short circuit current at the installation location 
according to the adjustment range of the switch, selectable on the switch 
see tripping characteristic curve 
Electromagnetic 
quick release 
Ambient conditions 
Ambient temperature 
range 
Adjustment range Operate value set at factory 
0.16 ... 0.63 A 7.5 ... 12.0 In 
1.0 ... 2.5 A 9.0 ... 14.0 In 
2.5 ... 4.0 A 10.0 ... 15.0 In 
4.0 ... 6.3 A 10.0 ... 15.0 In 
9.0 ... 22.5 A 12.5 ... 17.5 In 
-20 ... +40 °C 
Mechanical data 
Switching handle Labelling: 0 - I; can be locked with 3 padlocks in 0-position 
aM 
40 A 
Colour: 
Standard: Handle black, protective collar black 
Special version: Handle red, protective collar yellow (for EM-STOP function) 
Auxiliary contacts 
Device version optional: without; 1 NC + 1 NO; 2 NCs + 2 NOs 
Electrical data 
Rated operational 
voltage Ue 
max. 500 V AC 
Rated operational 
current 
AC-15: 24 V / 2.5 A; 230 V / 2 A; 400 V / 1 A 
DC-13: 24 V / 2.5 A; 60 V / 2.5 A; 110 V / 0.6 A; 220 V / 0.25 A 
ICS gG, 
aM 
10 kA 40 kA 
Load Disconnect Switches and Motor E7/6 Starters 2013-02-27·EK00·III·en
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
Motor Protection Circuit Breaker 
Series 8527/2 
Technical data 
Undervoltage release 
Electrical data 
Function in case of voltage interruption, circuit-breaker triggers; this prevents unwanted restarting, 
e.g. of a motor 
Pick-up voltage ) 0.85 x Uc 
Drop-out 0.7 ... 0.35 x Uc 
Power consumption 
Inrush 0.9 VA 
Holding 0.9 VA 
Shunt release 
Electrical data 
Function for remote tripping of circuit-breakers by applying actuating voltage 
Pick-up voltage ) 0.85 x Uc 
Relative duty cycle Switches off automatically via integrated contact switch 
Power consumption 
Inrush 24 ... 60 V: 14.4 ... 90 VA; 110 ... 240 V: 13 ... 61 VA; 220 ... 415 V: 17.6 ... 62.3 VA 
Holding Switches off automatically via integrated contact switch 
Ammeter 
Device version Type 8405; dimensions 64 mm x 64 mm 
Electrical data 
Movement Moving iron: class 2.5; direct measuring; overload scale 1:2 
Measuring range according to the adjustment range of the switch 
Overload capacity 2 x Ie 25 s, 50 x Ie 1 s 
2013-02-27·EK00·III·en Load Disconnect Switches and Motor Starters E7/7
Motor Protection Circuit Breaker 
Series 8527/2 
Adjustment ran-ge 
of the motor 
protection switch 
Tripping time of the motor protection switch with 
3 4 5 6 7.2 8 
times rated current, 3-pole from cold state. 
A ... A s s s s s s 
0.1 ... 0.16 15.0 9.0 6.5 4.8 3.7 3.2 
0.16 ... 0.25 16.0 10.0 6.8 5.2 4.0 3.6 
0.25 ... 0.4 16.0 9.7 6.5 5.0 3.8 3.3 
0.4 ... 0.63 17.0 10.2 7.3 5.7 4.4 3.9 
0.63 ... 1.0 17.5 10.2 7.2 5.5 4.2 3.8 
1.0 ... 1.6 17.0 10.0 7.1 5.6 4.4 4.0 
1.6 ... 2.5 18.0 10.3 7.5 5.9 4.7 4.2 
2.5 ... 4.0 18.4 11.5 8.1 6.4 5.0 4.6 
4.0 ... 6.3 19.0 12.0 8.5 6.7 5.3 4.9 
6.3 ... 9.0 18.2 11.5 7.9 6.0 4.5 3.8 
9.0 ... 12.5 19.0 11.5 8.0 6.0 4.6 4.0 
12.5 ... 16.0 19.5 11.5 7.5 5.4 4.0 3.3 
16.0 ... 20.0 20.0 11.5 7.8 5.7 4.2 3.5 
20.0 ... 22.5 20.0 10.4 7.0 5.0 3.7 3.2 
11050E00 11051E00 
1) Multiples of the rated operational current 
2) Tripping time 
3) 2-pole 
4) 3-pole 
5) Electromagnetic release 
Load Disconnect Switches and Motor E7/8 Starters 2013-02-27·EK00·III·en
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
Motor Protection Circuit Breaker 
Series 8527/2 
11052E00 11053E00 
11054E00 11055E00 
1) Multiples of the rated operational current 
2) Tripping time 
3) 2-pole 
4) 3-pole 
5) Electromagnetic release 
2013-02-27·EK00·III·en Load Disconnect Switches and Motor Starters E7/9
Motor Protection Circuit Breaker 
Series 8527/2 
11056E00 11057E00 
11058E00 11059E00 
1) Multiples of the rated operational current 
2) Tripping time 
3) 2-pole 
4) 3-pole 
5) Electromagnetic release 
Load Disconnect Switches and Motor E7/10 Starters 2013-02-27·EK00·III·en
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
E7 
Motor Protection Circuit Breaker 
Series 8527/2 
11060E00 11061E00 
11062E00 11063E00 
1) Multiples of the rated operational current 
2) Tripping time 
3) 2-pole 
4) 3-pole 
5) Electromagnetic release 
2013-02-27·EK00·III·en Load Disconnect Switches and Motor Starters E7/11
Motor Protection Circuit Breaker 
Series 8527/2 
Dimensional Drawings (All Dimensions in mm) - Subject to Alterations 
04793E00 04794E00 04795E00 
8527/21 8527/22 8527/23; 8527/24 
04796E00 
8527/25; 8527/26 
Cable entries 
Type Accessories Cable glands 8161 Stopping plugs 8290 
M25 x 1.5 M32 x 1.5 M25 x 1.5 
8527/21 without 
with 
A + B 
A, B, C 
- - 
- - 
C 
- - 
8527/22 without 
with 
A + B 
A, B, C 
- - 
- - 
C 
- - 
8527/23; 8527/24 without 
with 
- - 
C 
A + B 
A + B 
C 
- - 
8527/25; 8527/26 
0.1 ... 12.5 A without 
with 
A + B 
A, B, C 
- - 
- - 
C 
- - 
12.5 ... 22.5 A without 
with 
- - 
C 
A + B 
A + B 
C 
- - 
We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. 
The illustrations cannot be considered binding. 
Load Disconnect Switches and Motor E7/12 Starters 2013-02-27·EK00·III·en

More Related Content

What's hot

Top 10 rotating equipment engineer interview questions and answers
Top 10 rotating equipment engineer interview questions and answersTop 10 rotating equipment engineer interview questions and answers
Top 10 rotating equipment engineer interview questions and answersjomgori
 
INTRODUCTION TO PIPING AND PIPE LINES.pptx
INTRODUCTION TO PIPING AND PIPE LINES.pptxINTRODUCTION TO PIPING AND PIPE LINES.pptx
INTRODUCTION TO PIPING AND PIPE LINES.pptxHusaim
 
Piping components, materials, codes and standards part 1- pipe
Piping components, materials, codes and standards   part 1- pipePiping components, materials, codes and standards   part 1- pipe
Piping components, materials, codes and standards part 1- pipeAlireza Niakani
 
fundamentals of Piping engineering
fundamentals of Piping engineeringfundamentals of Piping engineering
fundamentals of Piping engineeringMobinVarghese8
 
pipe shedule chart
pipe shedule chartpipe shedule chart
pipe shedule chartArun K
 
Flanges
FlangesFlanges
FlangesK0042
 
Fundamental of Pipe / Pipeline used in Process Piping.
Fundamental of Pipe / Pipeline used in Process Piping.Fundamental of Pipe / Pipeline used in Process Piping.
Fundamental of Pipe / Pipeline used in Process Piping.Varun Patel
 
Pipe manufacturing and types
Pipe manufacturing and typesPipe manufacturing and types
Pipe manufacturing and typesnajeeb muhamed
 
Unit 12 grammar presentation
Unit 12 grammar presentationUnit 12 grammar presentation
Unit 12 grammar presentationAnne Agard
 
Rotating Equipment Engineer
Rotating Equipment  EngineerRotating Equipment  Engineer
Rotating Equipment EngineerPrem Kumar R
 

What's hot (20)

Top 10 rotating equipment engineer interview questions and answers
Top 10 rotating equipment engineer interview questions and answersTop 10 rotating equipment engineer interview questions and answers
Top 10 rotating equipment engineer interview questions and answers
 
1760 1750 control valves
1760 1750 control valves1760 1750 control valves
1760 1750 control valves
 
INTRODUCTION TO PIPING AND PIPE LINES.pptx
INTRODUCTION TO PIPING AND PIPE LINES.pptxINTRODUCTION TO PIPING AND PIPE LINES.pptx
INTRODUCTION TO PIPING AND PIPE LINES.pptx
 
Piping components, materials, codes and standards part 1- pipe
Piping components, materials, codes and standards   part 1- pipePiping components, materials, codes and standards   part 1- pipe
Piping components, materials, codes and standards part 1- pipe
 
fundamentals of Piping engineering
fundamentals of Piping engineeringfundamentals of Piping engineering
fundamentals of Piping engineering
 
Components for Pipe Support Deflection & Restraint
Components for Pipe Support Deflection & RestraintComponents for Pipe Support Deflection & Restraint
Components for Pipe Support Deflection & Restraint
 
Pipe schedule 1
Pipe schedule 1Pipe schedule 1
Pipe schedule 1
 
U.S. Bellows Expansion Joints In-Depth Webinar
U.S. Bellows Expansion Joints In-Depth WebinarU.S. Bellows Expansion Joints In-Depth Webinar
U.S. Bellows Expansion Joints In-Depth Webinar
 
pipe shedule chart
pipe shedule chartpipe shedule chart
pipe shedule chart
 
Flanges
FlangesFlanges
Flanges
 
Fundamental of Pipe / Pipeline used in Process Piping.
Fundamental of Pipe / Pipeline used in Process Piping.Fundamental of Pipe / Pipeline used in Process Piping.
Fundamental of Pipe / Pipeline used in Process Piping.
 
Pipe Support Field Inspection, Installation & Maintenance
Pipe Support Field Inspection, Installation & MaintenancePipe Support Field Inspection, Installation & Maintenance
Pipe Support Field Inspection, Installation & Maintenance
 
Introduction to piping design
Introduction to piping designIntroduction to piping design
Introduction to piping design
 
Pipe manufacturing and types
Pipe manufacturing and typesPipe manufacturing and types
Pipe manufacturing and types
 
Engineering & Design of Pipe Supports
Engineering & Design of Pipe SupportsEngineering & Design of Pipe Supports
Engineering & Design of Pipe Supports
 
Unit 12 grammar presentation
Unit 12 grammar presentationUnit 12 grammar presentation
Unit 12 grammar presentation
 
Catalogo puriar
Catalogo puriarCatalogo puriar
Catalogo puriar
 
Mechanical seals
Mechanical sealsMechanical seals
Mechanical seals
 
Pressure vessel
Pressure vesselPressure vessel
Pressure vessel
 
Rotating Equipment Engineer
Rotating Equipment  EngineerRotating Equipment  Engineer
Rotating Equipment Engineer
 

Viewers also liked

Viewers also liked (17)

Motor protection circuit_breaker
Motor protection circuit_breakerMotor protection circuit_breaker
Motor protection circuit_breaker
 
HRM - MCB
HRM - MCBHRM - MCB
HRM - MCB
 
Mccb &amp; mcb
Mccb &amp; mcbMccb &amp; mcb
Mccb &amp; mcb
 
Lec transmission line
Lec transmission lineLec transmission line
Lec transmission line
 
BMS Automation wiring
BMS Automation wiringBMS Automation wiring
BMS Automation wiring
 
Final Prresentation
Final PrresentationFinal Prresentation
Final Prresentation
 
Mcb hr policy
Mcb hr policyMcb hr policy
Mcb hr policy
 
Breakers v. fuses[1]
Breakers v. fuses[1]Breakers v. fuses[1]
Breakers v. fuses[1]
 
Busbar Design
Busbar DesignBusbar Design
Busbar Design
 
ppt of EEE(MCB)
ppt of EEE(MCB)ppt of EEE(MCB)
ppt of EEE(MCB)
 
PPT ON MCB
PPT ON MCBPPT ON MCB
PPT ON MCB
 
Motor protection
Motor protectionMotor protection
Motor protection
 
Wiring techniques in maxillofacial surgery
Wiring techniques in maxillofacial surgeryWiring techniques in maxillofacial surgery
Wiring techniques in maxillofacial surgery
 
Bms system basic
Bms system  basicBms system  basic
Bms system basic
 
Electrical wiring BY Jemish
Electrical wiring BY JemishElectrical wiring BY Jemish
Electrical wiring BY Jemish
 
ELECTRICAL WIRING
ELECTRICAL WIRINGELECTRICAL WIRING
ELECTRICAL WIRING
 
LinkedIn SlideShare: Knowledge, Well-Presented
LinkedIn SlideShare: Knowledge, Well-PresentedLinkedIn SlideShare: Knowledge, Well-Presented
LinkedIn SlideShare: Knowledge, Well-Presented
 

Similar to Stahl 8527 Motor Protection Circuit Breakers– ATEX Zone 1 Zone 2 Hazardous Area Load Disconnectors And Motor Starters

PVC Control cables 1.5 mm SWA
PVC Control cables 1.5 mm SWAPVC Control cables 1.5 mm SWA
PVC Control cables 1.5 mm SWAprysmianaus
 
Weg low-voltage-switch-control-gear-50019086-brochure-english
Weg low-voltage-switch-control-gear-50019086-brochure-englishWeg low-voltage-switch-control-gear-50019086-brochure-english
Weg low-voltage-switch-control-gear-50019086-brochure-englishDaniel García
 
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vnCatalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vnDien Ha The
 
Catalog rccb va rcbo abb
Catalog rccb va rcbo abbCatalog rccb va rcbo abb
Catalog rccb va rcbo abbDien Ha The
 
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...Thorne & Derrick International
 
Stahl 6039 Series Tubular Light Fittings ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl 6039 Series Tubular Light Fittings  ATEX Zone 1 Zone 2 Hazardous Area L...Stahl 6039 Series Tubular Light Fittings  ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl 6039 Series Tubular Light Fittings ATEX Zone 1 Zone 2 Hazardous Area L...Thorne & Derrick International
 
Servo tek selection_guide_brochure
Servo tek selection_guide_brochureServo tek selection_guide_brochure
Servo tek selection_guide_brochureElectromate
 
Stahl 6521_4 Floodlight - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6521_4 Floodlight - ATEX Zone 1 Zone 2 Hazardous Area LightingStahl 6521_4 Floodlight - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6521_4 Floodlight - ATEX Zone 1 Zone 2 Hazardous Area LightingThorne & Derrick International
 
Metallised Polyester Film Capacitors in India
Metallised Polyester Film Capacitors in IndiaMetallised Polyester Film Capacitors in India
Metallised Polyester Film Capacitors in IndiaDeki Electronics
 
Edwards Signaling 873DPO-G1 Installation Manual
Edwards Signaling 873DPO-G1 Installation ManualEdwards Signaling 873DPO-G1 Installation Manual
Edwards Signaling 873DPO-G1 Installation ManualJMAC Supply
 
Edwards Signaling 874-N5 Installation Manual
Edwards Signaling 874-N5 Installation ManualEdwards Signaling 874-N5 Installation Manual
Edwards Signaling 874-N5 Installation ManualJMAC Supply
 
Stahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area LightingStahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area LightingThorne & Derrick International
 
Az273 053-52-american-zettler-datasheet-110398
Az273 053-52-american-zettler-datasheet-110398Az273 053-52-american-zettler-datasheet-110398
Az273 053-52-american-zettler-datasheet-110398Luis Puma
 
Catalog cs contactor d range
Catalog cs contactor d rangeCatalog cs contactor d range
Catalog cs contactor d rangeThuan Kieu
 
Catalog cs contactor d range-dienhathe.vn
Catalog cs contactor d range-dienhathe.vnCatalog cs contactor d range-dienhathe.vn
Catalog cs contactor d range-dienhathe.vnDien Ha The
 
Catalog cs contactor d range
Catalog cs contactor d rangeCatalog cs contactor d range
Catalog cs contactor d rangeDien Ha The
 
Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...
Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...
Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...Thorne & Derrick International
 

Similar to Stahl 8527 Motor Protection Circuit Breakers– ATEX Zone 1 Zone 2 Hazardous Area Load Disconnectors And Motor Starters (20)

Mcb c60 h dc
Mcb c60 h dcMcb c60 h dc
Mcb c60 h dc
 
PVC Control cables 1.5 mm SWA
PVC Control cables 1.5 mm SWAPVC Control cables 1.5 mm SWA
PVC Control cables 1.5 mm SWA
 
Weg low-voltage-switch-control-gear-50019086-brochure-english
Weg low-voltage-switch-control-gear-50019086-brochure-englishWeg low-voltage-switch-control-gear-50019086-brochure-english
Weg low-voltage-switch-control-gear-50019086-brochure-english
 
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vnCatalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
 
Catalog rccb va rcbo abb
Catalog rccb va rcbo abbCatalog rccb va rcbo abb
Catalog rccb va rcbo abb
 
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
 
Stahl 6039 Series Tubular Light Fittings ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl 6039 Series Tubular Light Fittings  ATEX Zone 1 Zone 2 Hazardous Area L...Stahl 6039 Series Tubular Light Fittings  ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl 6039 Series Tubular Light Fittings ATEX Zone 1 Zone 2 Hazardous Area L...
 
Renewable energy
Renewable energyRenewable energy
Renewable energy
 
Renewable energy
Renewable energyRenewable energy
Renewable energy
 
Servo tek selection_guide_brochure
Servo tek selection_guide_brochureServo tek selection_guide_brochure
Servo tek selection_guide_brochure
 
Stahl 6521_4 Floodlight - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6521_4 Floodlight - ATEX Zone 1 Zone 2 Hazardous Area LightingStahl 6521_4 Floodlight - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6521_4 Floodlight - ATEX Zone 1 Zone 2 Hazardous Area Lighting
 
Metallised Polyester Film Capacitors in India
Metallised Polyester Film Capacitors in IndiaMetallised Polyester Film Capacitors in India
Metallised Polyester Film Capacitors in India
 
Edwards Signaling 873DPO-G1 Installation Manual
Edwards Signaling 873DPO-G1 Installation ManualEdwards Signaling 873DPO-G1 Installation Manual
Edwards Signaling 873DPO-G1 Installation Manual
 
Edwards Signaling 874-N5 Installation Manual
Edwards Signaling 874-N5 Installation ManualEdwards Signaling 874-N5 Installation Manual
Edwards Signaling 874-N5 Installation Manual
 
Stahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area LightingStahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area Lighting
 
Az273 053-52-american-zettler-datasheet-110398
Az273 053-52-american-zettler-datasheet-110398Az273 053-52-american-zettler-datasheet-110398
Az273 053-52-american-zettler-datasheet-110398
 
Catalog cs contactor d range
Catalog cs contactor d rangeCatalog cs contactor d range
Catalog cs contactor d range
 
Catalog cs contactor d range-dienhathe.vn
Catalog cs contactor d range-dienhathe.vnCatalog cs contactor d range-dienhathe.vn
Catalog cs contactor d range-dienhathe.vn
 
Catalog cs contactor d range
Catalog cs contactor d rangeCatalog cs contactor d range
Catalog cs contactor d range
 
Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...
Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...
Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...
 

More from Thorne & Derrick International

Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...Thorne & Derrick International
 
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical EqptTHORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical EqptThorne & Derrick International
 
The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018Thorne & Derrick International
 
3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick International3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick InternationalThorne & Derrick International
 
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-AThorne & Derrick International
 
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...Thorne & Derrick International
 
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...Thorne & Derrick International
 
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam RowePepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam RoweThorne & Derrick International
 
Ultrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification DemandUltrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification DemandThorne & Derrick International
 
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282DSIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282DThorne & Derrick International
 
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...Thorne & Derrick International
 
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec SheetFiloform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec SheetThorne & Derrick International
 

More from Thorne & Derrick International (20)

Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...
 
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical EqptTHORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
 
The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018
 
3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick International3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick International
 
CATU Electrical Safety Catalogue
CATU Electrical Safety CatalogueCATU Electrical Safety Catalogue
CATU Electrical Safety Catalogue
 
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
 
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
 
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
 
Roxtec Cable Transit - B Frame Dimensional Drawing
Roxtec Cable Transit - B Frame Dimensional DrawingRoxtec Cable Transit - B Frame Dimensional Drawing
Roxtec Cable Transit - B Frame Dimensional Drawing
 
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam RowePepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
 
T&D Experts In Equipment For Explosive Atmospheres
T&D Experts In Equipment For Explosive AtmospheresT&D Experts In Equipment For Explosive Atmospheres
T&D Experts In Equipment For Explosive Atmospheres
 
Ultrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification DemandUltrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification Demand
 
Emtelle Fibre Optic Cables - Product Catalogue 2016
Emtelle Fibre Optic Cables - Product Catalogue 2016Emtelle Fibre Optic Cables - Product Catalogue 2016
Emtelle Fibre Optic Cables - Product Catalogue 2016
 
Thorne & Derrick Process Heating Brochure 2016
Thorne & Derrick Process Heating Brochure 2016Thorne & Derrick Process Heating Brochure 2016
Thorne & Derrick Process Heating Brochure 2016
 
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282DSIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
 
Ripley Utility Tool Cable Preparation Tools
Ripley Utility Tool Cable Preparation ToolsRipley Utility Tool Cable Preparation Tools
Ripley Utility Tool Cable Preparation Tools
 
RIDGID micro CD100 Combustible Gas Detector
RIDGID micro CD100 Combustible Gas DetectorRIDGID micro CD100 Combustible Gas Detector
RIDGID micro CD100 Combustible Gas Detector
 
Itron Fact Sheet
Itron Fact SheetItron Fact Sheet
Itron Fact Sheet
 
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
 
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec SheetFiloform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
 

Stahl 8527 Motor Protection Circuit Breakers– ATEX Zone 1 Zone 2 Hazardous Area Load Disconnectors And Motor Starters

  • 1. E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 Motor Protection Circuit Breaker Series 8527/2 www.stahl.de Load Disconnect Switches and Motor Starters E7/1 2013-02-27·EK00·III·en Series 8527/2 E7 02966E00 WebCode 8527A > For protection of Ex e and Ex d motors > Protects cables and plant equipment > Adjustable thermal overload release, phase failure sensitive > Electromagnetic instantaneous release > Robust enclosure made of glass fibre reinforced polyester resin > Optionally with – undervoltage release – shunt release – ammeter – auxiliary contacts Motor protection circuit breakers of Series 8527 are used where high short circuit currents are to be controlled and to protect both Ex e and Ex d motors. These switches are suitable to protect cables and the installation and can basically be used without a back-up fuse at 400 V. Breakers are operated by rotary handles enabling next to secure switching also to identify clearly switch settings. ATEX / IECEx / GOST Zone 0 1 2 20 21 22 For use in x x x x
  • 2. Motor Protection Circuit Breaker Series 8527/2 Selection Table Version without accessories L1 L2 L3 1 3 5 I > I > I > 2 4 6 T1 T2 T3 Current adjustment range Auxiliary contacts Order number Weight Motor protection circuit breakers without accessories Series 8527 0.1 ... 0.16 A without 8527/21-01-0001 2.591 0.1 ... 0.16 A 1 NC + 1 NO 8527/22-01-0201 2.610 0.16 ... 0.25 A without 8527/21-02-0001 2.608 1 NC + 1 NO 8527/22-02-0201 2.630 0.25 ... 0.4 A without 8527/21-03-0001 2.610 1 NC + 1 NO 8527/22-03-0201 2.630 0.4 ... 0.63 A without 8527/21-04-0001 2.574 1 NC + 1 NO 8527/22-04-0201 2.595 0.63 ... 1 A without 8527/21-05-0001 2.600 1 NC + 1 NO 8527/22-05-0201 2.620 1 ... 1.6 A without 8527/21-06-0001 2.653 1 NC + 1 NO 8527/22-06-0201 2.670 1.6 ... 2.5 A without 8527/21-07-0001 2.633 1 NC + 1 NO 8527/22-07-0201 2.650 2.5 ... 4 A without 8527/21-08-0001 2.630 1 NC + 1 NO 8527/22-08-0201 2.650 4 ... 6.3 A without 8527/21-09-0001 2.600 1 NC + 1 NO 8527/22-09-0201 2.620 6.3 ... 9 A without 8527/21-10-0001 2.600 1 NC + 1 NO 8527/22-10-0201 2.620 9 ... 12.5 A without 8527/21-11-0001 2.500 1 NC + 1 NO 8527/22-11-0201 2.520 12.5 ... 16 A without 8527/21-12-0001 2.400 1 NC + 1 NO 8527/22-12-0201 2.420 16 ... 20 A without 8527/23-13-0002 4.200 1 NC + 1 NO 8527/24-13-0202 3.520 20 ... 22.5 A without 8527/23-14-0002 3.500 1 NC + 1 NO 8527/24-14-0202 3.520 On request: • Circuit breakers for the current adjustment range 25 ... 63 A (Type 8525) • Further accessories e. g. shunt release, ammeter, additional auxiliary contacts (2 NC + 2 NO) Load Disconnect Switches and Motor E7/2 Starters 2013-02-27·EK00·III·en
  • 3. E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 Motor Protection Circuit Breaker Series 8527/2 Selection Table Version with undervoltage trip Current adjustment range Rated operational voltage Ue L1 L2 L3 1 3 5 I > I > I > 2 4 6 T1 T2 T3 D1 U < D2 Auxiliary contacts Order number Weight kg Motor protection circuit breakers with undervoltage release Series 8527 0.1 ... 0.16 A 230 V AC 50 / 60 Hz without 8527/21-01-1061 2.610 1 NC + 1 NO 8527/22-01-1261 2.610 400 V AC 50 / 60 Hz without 8527/21-01-1071 2.610 1 NC + 1 NO 8527/22-01-1271 2.610 500 V AC 50 / 60 Hz without 8527/21-01-1091 2.610 1 NC + 1 NO 8527/22-01-1291 2.610 0.16 ... 0.25 A 230 V AC 50 / 60 Hz without 8527/21-02-1061 2.630 1 NC + 1 NO 8527/22-02-1261 2.630 400 V AC 50 / 60 Hz without 8527/21-02-1071 2.630 1 NC + 1 NO 8527/22-02-1271 2.630 500 V AC 50 / 60 Hz without 8527/21-02-1091 2.630 1 NC + 1 NO 8527/22-02-1291 2.630 0.25 ... 0.4 A 230 V AC 50 / 60 Hz without 8527/21-03-1061 2.630 1 NC + 1 NO 8527/22-03-1261 2.630 400 V AC 50 / 60 Hz without 8527/21-03-1071 2.630 1 NC + 1 NO 8527/22-03-1271 2.630 500 V AC 50 / 60 Hz without 8527/21-03-1091 2.630 1 NC + 1 NO 8527/22-03-1291 2.630 0.4 ... 0.63 A 230 V AC 50 / 60 Hz without 8527/21-04-1061 2.595 1 NC + 1 NO 8527/22-04-1261 2.595 400 V AC 50 / 60 Hz without 8527/21-04-1071 2.595 1 NC + 1 NO 8527/22-04-1271 2.595 500 V AC 50 / 60 Hz without 8527/21-04-1091 2.595 1 NC + 1 NO 8527/22-04-1291 2.595 0.63 ... 1 A 230 V AC 50 / 60 Hz without 8527/21-05-1061 2.620 1 NC + 1 NO 8527/22-05-1261 2.620 400 V AC 50 / 60 Hz without 8527/21-05-1071 2.620 1 NC + 1 NO 8527/22-05-1271 2.620 500 V AC 50 / 60 Hz without 8527/21-05-1091 2.620 1 NC + 1 NO 8527/22-05-1291 2.620 1 ... 1.6 A 230 V AC 50 / 60 Hz without 8527/21-06-1061 2.670 1 NC + 1 NO 8527/22-06-1261 2.670 400 V AC 50 / 60 Hz without 8527/21-06-1071 2.670 1 NC + 1 NO 8527/22-06-1271 2.670 500 V AC 50 / 60 Hz without 8527/21-06-1091 2.670 1 NC + 1 NO 8527/22-06-1291 2.670 1.6 ... 2.5 A 230 V AC 50 / 60 Hz without 8527/21-07-1061 2.650 1 NC + 1 NO 8527/22-07-1261 2.650 400 V AC 50 / 60 Hz without 8527/21-07-1071 2.650 1 NC + 1 NO 8527/22-07-1271 2.650 500 V AC 50 / 60 Hz without 8527/21-07-1091 2.650 1 NC + 1 NO 8527/22-07-1291 2.650 2013-02-27·EK00·III·en Load Disconnect Switches and Motor Starters E7/3
  • 4. Motor Protection Circuit Breaker Series 8527/2 Selection Table Version with undervoltage trip Motor protection circuit breakers with undervoltage release Series 8527 Current adjustment range Rated operational voltage Ue 2.5 ... 4 A 230 V AC 50 / 60 Hz L1 L2 L3 1 3 5 I > I > I > 2 4 6 T1 T2 T3 D1 U < D2 Auxiliary contacts Order number Weight kg without 8527/21-08-1061 2.650 1 NC + 1 NO 8527/22-08-1261 2.650 400 V AC 50 / 60 Hz without 8527/21-08-1071 2.650 1 NC + 1 NO 8527/22-08-1271 2.650 500 V AC 50 / 60 Hz without 8527/21-08-1091 2.650 1 NC + 1 NO 8527/22-08-1291 2.650 4 ... 6.3 A 230 V AC 50 / 60 Hz without 8527/21-09-1061 2.620 1 NC + 1 NO 8527/22-09-1261 2.620 400 V AC 50 / 60 Hz without 8527/21-09-1071 2.620 1 NC + 1 NO 8527/22-09-1271 2.620 500 V AC 50 / 60 Hz without 8527/21-09-1091 2.620 1 NC + 1 NO 8527/22-09-1291 2.620 6.3 ... 9 A 230 V AC 50 / 60 Hz without 8527/21-10-1061 2.620 1 NC + 1 NO 8527/22-10-1261 2.620 400 V AC 50 / 60 Hz without 8527/21-10-1071 2.620 1 NC + 1 NO 8527/22-10-1271 2.620 500 V AC 50 / 60 Hz without 8527/21-10-1091 2.620 1 NC + 1 NO 8527/22-10-1291 2.620 9 ... 12.5 A 230 V AC 50 / 60 Hz without 8527/21-11-1061 2.520 1 NC + 1 NO 8527/22-11-1261 2.520 400 V AC 50 / 60 Hz without 8527/21-11-1071 2.520 1 NC + 1 NO 8527/22-11-1271 2.520 500 V AC 50 / 60 Hz without 8527/21-11-1091 2.520 1 NC + 1 NO 8527/22-11-1291 2.520 12.5 ... 16 A 230 V AC 50 / 60 Hz without 8527/21-12-1061 2.420 1 NC + 1 NO 8527/22-12-1261 2.420 400 V AC 50 / 60 Hz without 8527/21-12-1071 2.420 1 NC + 1 NO 8527/22-12-1271 2.420 500 V AC 50 / 60 Hz without 8527/21-12-1091 2.420 1 NC + 1 NO 8527/22-12-1291 2.420 16 ... 20 A 230 V AC 50 / 60 Hz without 8527/23-13-1062 4.220 1 NC + 1 NO 8527/24-13-1262 3.520 400 V AC 50 / 60 Hz without 8527/23-13-1072 4.220 1 NC + 1 NO 8527/24-13-1272 3.520 500 V AC 50 / 60 Hz without 8527/21-13-1092 4.220 1 NC + 1 NO 8527/24-13-1292 3.520 20 ... 22.5 A 230 V AC 50 / 60 Hz without 8527/23-14-1062 3.520 1 NC + 1 NO 8527/24-14-1262 3.520 400 V AC 50 / 60 Hz without 8527/23-14-1072 3.520 1 NC + 1 NO 8527/24-14-1272 3.520 500 V AC 50 / 60 Hz without 8527/21-14-1092 3.520 1 NC + 1 NO 8527/24-14-1292 3.520 Load Disconnect Switches and Motor E7/4 Starters 2013-02-27·EK00·III·en
  • 5. E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 Motor Protection Circuit Breaker Series 8527/2 Explosion Protection Global (IECEx) Gas IECEx BVS 08.0047 Ex d e IIC T* Dust IECEx PTB 06.0090 (see type 8146/5) Ex tD A21 IP65 T** (see type 8146/5) Europe (ATEX) Gas DMT 02 ATEX E 026 E II 2 G Ex d e IIC T* Dust PTB 01 ATEX 1024 (see type 8146/5) E II 2 D Ex tD A21 IP65 T** (see type 8146/5) Certificates and approvals Type Adjustment range T* T** 8527/21, 8527/22 0.1 ... 0.25 A 0.25 ... 12.5 A 12.5 ... 16 A T6 T5 T4 80 °C 95 °C 130 °C 8527/23 0.1 ... 12.5 A T6 80 °C 8527/24 16 ... 22.5 A T5 95 °C Certificates IECEx, ATEX, Canada (CSA), Kazakhstan (GOST-K), Russia (GOST-R), Belarus (GOST-B) Technical data Mechanical data Degree of protection IP66 acc. to IEC/EN 60529 Enclosure material Polyester resin, glass-fibre-reinforced, dark grey, similar to RAL 7024 Surface resistance ( 109 Ω, impact strength ) 7 J, flame-resistant, self-extinguishing according to IEC-92-1, UL 94, ASTM D 635-77 Mounting / installation Mounting orientation arbitrary Cable entries Standard Type Accessories 1) 8161 Screw connec-tions 8290 Stopping plug M25 x 1.5 M32 x 1.5 M25 x 1.5 8527/21 without with 23 -- 8527/22 without with 23 -- 8527/23; 8527/24 without with - 1 22 8527/25; 8527/26 0.1 ... 12.5 A without with 23 -- 12.5 ... 22.5 A without with - 1 22 M25 x 1.5 for cables Ø 12 ... 17 mm M32 x 1.5 for cables Ø 10 ... 18 mm 1) auxiliary contacts, undervoltage release, shunt release Wire Leads Switch insert Electrical data Rated operational voltage 8527/21 8527/22 directly to fitted components Main contacts 1.5 ... 6 mm2 finely stranded Auxiliary contact 0.75 ... 1.5 mm2 finely stranded 8527/23 8527/24 8527/25 8527/26 on terminals 0.5 ... 6 mm2 finely stranded Please note: Compare cable diameter with cable diameter range of cable entry max. 690 V AC, 50 / 60 Hz Rated operational current 0.1 ... 22.5 A 1- 1- 1- 1- 1- 1.5 ... 10 mm2 solid 0.75 ... 2.5 mm2 solid 0.5 ... 10 mm2 solid 2013-02-27·EK00·III·en Load Disconnect Switches and Motor Starters E7/5
  • 6. Motor Protection Circuit Breaker Series 8527/2 Technical data Contact Switching Capacity according to the selected adjustment range (AC) Service life 230 V 400 V 500 V 690 V 7.0 kW 12.4 kW 16 kW 22 kW electrical 105 operations mechanical 105 operations Main contacts 3-pole Short circuit protection Thermal overcurrent release Adjustment ran-ge from ... to Highest rated current of the short circuit fuse if ICC > ICS at 230 V AC at 400 V AC at 440 V AC at 500 V AC at 690 V AC ICS gG, aM ICS gG, aM ICS gG, aM ICS gG, 0.1 A ... 0.16 A up to 1.0 A ... 1.6 A Short-circuit proof, no fuse needed up to ICC = 100 kA 1.6 A ... 2.5 A 40 kA 25 A 2.5 A ... 4.0 A 60 kA 35 A / 4.0 A ... 6.3 A 70 kA 50 A 40 kA 50 A 7 kA 40 A 6.3 A ... 9.0 A 50 kA 80 A 30 kA 80 A 5 kA 50 A 9.0 A ... 12.5 A 75 kA 80 A 45 kA 80 A 27 kA 80 A 4.5 kA 50 A 12.5 A ... 16.0 A 60 kA 100 A 40 kA 100 A 22 kA 100 A 4 kA 50 A 16.0 A ... 20.0 A 55 kA 100 A 35 kA 100 A 22 kA 100 A 3.5 kA 50 A 20.0 A ... 22.5 A 50 kA 125 A 30 kA 125 A 20 kA 125 A 3 kA 50 A ICS = Rated short-circuit breaking capacity ICC = Projected short circuit current at the installation location according to the adjustment range of the switch, selectable on the switch see tripping characteristic curve Electromagnetic quick release Ambient conditions Ambient temperature range Adjustment range Operate value set at factory 0.16 ... 0.63 A 7.5 ... 12.0 In 1.0 ... 2.5 A 9.0 ... 14.0 In 2.5 ... 4.0 A 10.0 ... 15.0 In 4.0 ... 6.3 A 10.0 ... 15.0 In 9.0 ... 22.5 A 12.5 ... 17.5 In -20 ... +40 °C Mechanical data Switching handle Labelling: 0 - I; can be locked with 3 padlocks in 0-position aM 40 A Colour: Standard: Handle black, protective collar black Special version: Handle red, protective collar yellow (for EM-STOP function) Auxiliary contacts Device version optional: without; 1 NC + 1 NO; 2 NCs + 2 NOs Electrical data Rated operational voltage Ue max. 500 V AC Rated operational current AC-15: 24 V / 2.5 A; 230 V / 2 A; 400 V / 1 A DC-13: 24 V / 2.5 A; 60 V / 2.5 A; 110 V / 0.6 A; 220 V / 0.25 A ICS gG, aM 10 kA 40 kA Load Disconnect Switches and Motor E7/6 Starters 2013-02-27·EK00·III·en
  • 7. E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 Motor Protection Circuit Breaker Series 8527/2 Technical data Undervoltage release Electrical data Function in case of voltage interruption, circuit-breaker triggers; this prevents unwanted restarting, e.g. of a motor Pick-up voltage ) 0.85 x Uc Drop-out 0.7 ... 0.35 x Uc Power consumption Inrush 0.9 VA Holding 0.9 VA Shunt release Electrical data Function for remote tripping of circuit-breakers by applying actuating voltage Pick-up voltage ) 0.85 x Uc Relative duty cycle Switches off automatically via integrated contact switch Power consumption Inrush 24 ... 60 V: 14.4 ... 90 VA; 110 ... 240 V: 13 ... 61 VA; 220 ... 415 V: 17.6 ... 62.3 VA Holding Switches off automatically via integrated contact switch Ammeter Device version Type 8405; dimensions 64 mm x 64 mm Electrical data Movement Moving iron: class 2.5; direct measuring; overload scale 1:2 Measuring range according to the adjustment range of the switch Overload capacity 2 x Ie 25 s, 50 x Ie 1 s 2013-02-27·EK00·III·en Load Disconnect Switches and Motor Starters E7/7
  • 8. Motor Protection Circuit Breaker Series 8527/2 Adjustment ran-ge of the motor protection switch Tripping time of the motor protection switch with 3 4 5 6 7.2 8 times rated current, 3-pole from cold state. A ... A s s s s s s 0.1 ... 0.16 15.0 9.0 6.5 4.8 3.7 3.2 0.16 ... 0.25 16.0 10.0 6.8 5.2 4.0 3.6 0.25 ... 0.4 16.0 9.7 6.5 5.0 3.8 3.3 0.4 ... 0.63 17.0 10.2 7.3 5.7 4.4 3.9 0.63 ... 1.0 17.5 10.2 7.2 5.5 4.2 3.8 1.0 ... 1.6 17.0 10.0 7.1 5.6 4.4 4.0 1.6 ... 2.5 18.0 10.3 7.5 5.9 4.7 4.2 2.5 ... 4.0 18.4 11.5 8.1 6.4 5.0 4.6 4.0 ... 6.3 19.0 12.0 8.5 6.7 5.3 4.9 6.3 ... 9.0 18.2 11.5 7.9 6.0 4.5 3.8 9.0 ... 12.5 19.0 11.5 8.0 6.0 4.6 4.0 12.5 ... 16.0 19.5 11.5 7.5 5.4 4.0 3.3 16.0 ... 20.0 20.0 11.5 7.8 5.7 4.2 3.5 20.0 ... 22.5 20.0 10.4 7.0 5.0 3.7 3.2 11050E00 11051E00 1) Multiples of the rated operational current 2) Tripping time 3) 2-pole 4) 3-pole 5) Electromagnetic release Load Disconnect Switches and Motor E7/8 Starters 2013-02-27·EK00·III·en
  • 9. E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 Motor Protection Circuit Breaker Series 8527/2 11052E00 11053E00 11054E00 11055E00 1) Multiples of the rated operational current 2) Tripping time 3) 2-pole 4) 3-pole 5) Electromagnetic release 2013-02-27·EK00·III·en Load Disconnect Switches and Motor Starters E7/9
  • 10. Motor Protection Circuit Breaker Series 8527/2 11056E00 11057E00 11058E00 11059E00 1) Multiples of the rated operational current 2) Tripping time 3) 2-pole 4) 3-pole 5) Electromagnetic release Load Disconnect Switches and Motor E7/10 Starters 2013-02-27·EK00·III·en
  • 11. E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 Motor Protection Circuit Breaker Series 8527/2 11060E00 11061E00 11062E00 11063E00 1) Multiples of the rated operational current 2) Tripping time 3) 2-pole 4) 3-pole 5) Electromagnetic release 2013-02-27·EK00·III·en Load Disconnect Switches and Motor Starters E7/11
  • 12. Motor Protection Circuit Breaker Series 8527/2 Dimensional Drawings (All Dimensions in mm) - Subject to Alterations 04793E00 04794E00 04795E00 8527/21 8527/22 8527/23; 8527/24 04796E00 8527/25; 8527/26 Cable entries Type Accessories Cable glands 8161 Stopping plugs 8290 M25 x 1.5 M32 x 1.5 M25 x 1.5 8527/21 without with A + B A, B, C - - - - C - - 8527/22 without with A + B A, B, C - - - - C - - 8527/23; 8527/24 without with - - C A + B A + B C - - 8527/25; 8527/26 0.1 ... 12.5 A without with A + B A, B, C - - - - C - - 12.5 ... 22.5 A without with - - C A + B A + B C - - We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding. Load Disconnect Switches and Motor E7/12 Starters 2013-02-27·EK00·III·en