Innovative Systems Design and Engineering                                                       www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011



   Laboratory Validation of Calculations of Magnetic Field
 Mitigation Underneath Transmission Lines Using Passive and
                    Active Shield Wires
                                                 Roshdy Radwan
      Department of Electrical Power and Machines, Faculty of Engineering, Cairo University, Giza, Egypt
                                        Email: roshdyradwan@yahoo.com


                                   Mazen Abdel-Salam (Corresponding author)
           Electrical Engineering Department, Faculty of Engineering, Assuit University, Assuit, Egypt
                                        Email: mazen2000as@yahoo.com


                                                Abdel-Bary Mahdy
      Department of Electrical Power and Machines, Faculty of Engineering, Cairo University, Giza, Egypt
                                         Email: abomohdy@yahoo.co.uk


                                                 Mohamed Samy
     Electrical Engineering Department, Faculty of Industrial Education, Beni Suief University, Beni Suief,
                                                 Egypt
                                     Email: mohamed_samy227@yahoo.com

Abstract
This paper is aimed at reporting experimental measurements and calculations of how the magnetic field
underneath overhead transmission lines is mitigated using passive and active shield wires. The magnetic
field values were compared to those calculated using the current simulation technique (CST). A laboratory
transmission line model representing the Egyptian 500 kV EHV line was built with dimensions scaled down
in the ratio 10:1. The flat single circuit of the line was modeled in the laboratory by phase separation of 1.2
m and conductor diameter of 2.76 mm at height of 1.9 m. The shield wires were spaced 4.3 m at a height of
1.45 m. Magnetic field measurements were carried out for load currents of 5.7 and 10 A. The field was
measured at 0.3 m above ground level with and without passive and active shield wires for several different
lateral positions. The measured and calculated field values generally agreed reasonably with an error
ranging between 2.5 and 20 % within the ROW. The maximum reduction of magnetic field from the passive
shield wires is 10% at the edge of right of way. With active shield wires carrying a current of 5 A (one half
of the conductor current), the reduction of magnetic field reached 17% at the edge of ROW.
Keywords: Current Simulation Technique, Magnetic Field Measurements, Magnetic Field Mitigation,
Shield Wires, Transmission Lines, Health Effects.
1.   Introduction
Prior to about 1982, electric fields were the main concern. With the publication of two papers by
(Wertheimer & Leeper 1979 and 1982) and the subsequent appearance of papers from other sources,
serious concerns have developed about magnetic field exposure. Therefore, calculation and measurement of
the magnetic field distribution underneath transmission lines is of great importance (Abdel-Salam 1999,
Swanson 1995, Caola 1983, Cruz 2002, Nicolaou 2011, Bakhashwain 2003, and Filippopouls 2005) and
should be elaborated on.




                                                     218
Innovative Systems Design and Engineering                                                      www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011

Several studies have reported that children living near high voltage transmission and distribution lines had a
higher cancer and leukemia incidence than other children (Chung 2007). However, limited studies have
been reported regarding adults who live near high voltage transmission and distribution lines. In addition,
various research work have suggested that exposure to electromagnetic fields could lead to DNA damages
in cells under certain conditions (Kim 2010).
These effects depend on factors such as mode of exposure, type of cell and intensity and duration of
exposure. For the above reasons, magnetic fields should be mitigated to overcome their harmful effects on
the people living or work adjacent to the transmission lines. There are many strategies and approaches to
cancel and mitigate magnetic fields underneath the power transmission lines (Stewart 1993, Jonsson 1994,
Memari 1996, Lindberg 1998, Pettersson 1996, Rashkes1998, Yamazaki 2000, Cruz 2003, Ippolito 2004,
Kalhor 2005, Faria 2007 and Romero 2007). One of the approaches is to use active or passive shield wires
underneath the line conductors.
The main purpose of this work is to validate experimental and calculation of magnetic field under
transmission lines with passive and active shield wires to assess how effective are these wires in mitigating
the magnetic field. The measurements were made underneath a laboratory model of 500 kV transmission
line. The calculations are based on the current simulation technique.
2.      Calculation method
The idea of current simulation technique is very simple and is similar to the charge simulation method
applied for calculating electric fields (Abdel-Salam & Radwan 1999 and 2010). For a three phase
transmission line of m subconductors per phase, the total number of subconductors is 3m as shown in Fig.
1. Each subconductor current is simulated by a finite number n of filamentary line currents distributed on a
fictitious cylindrical surface of radius Rs which is a fraction of the subconductor radius R. The simulation
currents ik, k = 1, 2, --------------, 3nm must satisfy the following conditions:
   1- Zero normal component of the magnetic field strength on the subconductors' surfaces, following
       Biot–Savart law.
   2- The sum of the filamentary line currents simulating the subconductor current must be equal to the
       subconductor current.
A set of equations are formulated at a number of boundary points chosen on the subconductors' surfaces to
satisfy the boundary conditions as follows:
3nm

p
k 1
        kj ki  0, j  1,2,3,..............,3m(n  1)                                                     (1)

       nq

     i      k
k ( q 1) n 1
                   I cq , q  1,2,3,..............,3m                                                    (2)

Where Pkj is the magnetic normal field coefficient determined by the coordinates of the j th boundary point
and the kth filamentary line current and is given by:
                   1
p                       sin  kj                                                                         (3)
     kj           2l kj

with     kj   kj   j     (Fig. 2).
The set of equations 1 and 2 are to be solved simultaneously for determining the 3nm unknown filamentary
line currents. Once the set of equations 1 and 2 are solved for the unknown filamentary line currents, the
deviation of the normal component of the magnetic field strength from the zero value is calculated at a set
of check-points arbitrary chosen on the subconductors' surfaces and considered as a measure of simulation
accuracy. When the simulation currents satisfy the boundary conditions at the check-points with a
considerable accuracy, the magnetic field could be calculated at any point in space is given by:




                                                         219
Innovative Systems Design and Engineering                                                      www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011


    1 nm   ( y  yk )ax  ( x  xk )a y ( y  yk )ax  ( x  xk )a y 
H   ik                                                                                               (4)
   2 k 1  ( x  xk ) 2  ( y  yk ) 2    ( x  xk ) 2  ( y  y k ) 2 
Where (x, y) and (xk ,yk) are the calculation point and the location of the kth simulation line current
respectively.
To calculate the magnetic field from the transmission line and shield wires the following simplifying
assumptions are considered:
   1. Phase and shield conductors are straight and infinitely long, located at a height equal to the lowest
       point of the conductor sag [two-dimensional (2-D) problem] (Cruz 2003).
   2. Investigated transmission line configurations are without ground wires.
   3. Induced current effect on phase current is negligible.
   4. Passive shield wires carry zero current.
   5. Each two shield wires constitute a single loop and each three wires constitute two loops with a
       common wire.
   6. Cross-sectional area of the shield wires is half that of the phase conductor. This is because the
       maximum shield current is variable up to half the phase current.
3.    Experimental model
An experimental laboratory model was built to validate the calculation of the magnetic field obtained by the
current simulation technique. The model was constructed at the high voltage laboratory of the faculty of
Engineering Cairo University as a scale model of the actual of the 500 kV Egyptian transmission line as
shown in Fig. 3 (a).
A horizontally arranged three phase power transmission line was built and fed from a three-phase star
supply. Each phase has one conductor with cross section of 6 mm2. One loop consisting of two shield wires,
each of area 3 mm2, is positioned underneath line conductors. The phase currents were 5.7 and 10 A and the
shield current varied in the range 10 to 50% of the phase current. Fig. 3 (b, c) shows the arrangement of the
phase conductors, control and measuring instruments for the model experiment.
The line conductors were supported by a wooden frame. The ends of the three phase conductors were
connected together as a star connection at one end. The parameters which affect the measured magnetic
field are the values of the phase and loop currents, the height Hs of the shield wires above the ground
surface and the spacing S between shield wires. Three digital multi-meters were used to measure the phase
currents in the range 0 to 10 A with accuracy of 0.5%.
Two types of variable resistors were used to control the phase currents and the loop current in case of active
shielding as shown in Fig 3 (c). The first one was used to control the phase currents up to a maximum value
of 15 A, at a voltage ranging from 200 to 250 V. The second one was used in controlling shield wire current
up to 30 A at 200 V.
An AC ammeter model 2013 with accuracy of 0.5% was used to measure the current in the shield wires.
Two miniature circuit breakers were used for the phase and loop circuits with maximum current of 20 A at
380 V. A power frequency field meter model 113 manufactured by the Electric Field Measurements
Company was used to measure the magnetic field.
4.    Results and discussions
The current simulation technique is applied to the experimental model shown in Fig. 3. Measurements of
the magnetic field under the laboratory model were carried out. Figures 4 to 11 show the calculated and
measured results of the magnetic fields at load current 10 A.
Figure 4 shows the measured and calculated magnetic field values with passive shield wires at a height of
one meter from ground level. The error between the measured and calculated values did not exceed 12%




                                                                      220
Innovative Systems Design and Engineering                                                     www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011

within the ROW as shown in Fig. 5. When the shield wire height was changed from 1 to 1.45 m, the results
obtained followed the same trend as before with field reduction of about 10%, Figs. 6 and 7.
Figure 8 plots the measured and calculated magnetic field values with active shield wires at a height of 1 m
from ground surface for different wire currents. The error between the measured and calculated values
ranged between 5 and 20% when the active shield wire current is one half of the conductor current, see Fig.
9. When the height of the shield wire was changed to 1.45 m, the results obtained for the magnetic field,
Figs. 10 and 11, followed the same trend as those shown in Figs. 8 and 9.
When the load current was changed from 10 – 5.7 A the results obtained, Figs. 12 to 15, followed the same
trend as those shown in Figs. 4 – 5 and Figs. 10 – 11.
5.   Conclusions
Passive shield wires have an appreciable effect on magnetic field reduction at ground level (0.3 m)
underneath the line; the maximum reduction may reach 10%.
Active shield wires have considerable effect on the measured magnetic field underneath the transmission
line model; this reduction of the field may reach 17% at the edge of the ROW. The reduction in the
magnetic field increases with the increase of the current in the shield wires.
For the laboratory model, the dependency of the measured magnetic field values on the phase current and
shield wires' current is the same as the calculated one. The error between the measured magnetic field
values and those calculated reached up to 20%.


References
Wertheimer, N. and Leeper, E. (1979), "Electrical wiring configurations and childhood cancer", Am. J.
Epidemiol. (109) 273–284.
Wertheimer, N. and Leeper, E. (1982), "Adult cancer related to electrical wires near the home", Int. J.
Epidemiol. (11) 345 – 455.
Abdel-Salam, M., Abdullah, H., El-Mohandes, M.Th. and El-Kishky, H. (1999), "Calculation of magnetic
fields from electric power transmission lines", Electric Power Systems Research, vol. 49, pp 99–105.
Swanson, J. (1995), "Magnetic Fields from Transmission Lines: Comparison of Calculation and
measurements", IEE Proc. -Generation Transmission. Distribution, vol. 142, no. 5, pp 481 – 486.
Caola, R.J., Deno, D.W. and Dymek, V.S.W. (1983), "Measurements of Electric and Magnetic Fields in
and Around Homes near a 500 kV Transmission Line", IEEE Transactions on Power Apparatus and
Systems, vol. PAS-102, no. 10, October.
Cruz P., Izquierdo, C., Burgos, M., Ferrer, L.F., Soto, F., Llanos, C. and Pacheco, J.D. (2002), "Magnetic
field mitigation in power lines with passive and active loops" Proceeding of Cigré Session, Paper No. 36-
107, Paris.
Nicolaou, C.P., Papadakis, A.P., Razis, P.A., Kyriacou, G.A. and Sahalos, J.N. (2011), "Measurements and
predictions of electric and magnetic fields from power lines" ", Electric Power Systems Research, vol. 81,
pp 1107–1116.
Bakhashwain, J.M., Shwehdi, M.H., Johar, U.M. and AL-Naim, A.A. (2003), "Magnetic Fields
Measurement and Evaluation of EHV Transmission Lines in Saudi Arabia", Proceedings of the
International Conference on Non-Ionizing Radiation at UNITEN (ICNIR 2003) Electromagnetic Fields and
Our Health 20th –22nd October.
Filippopouls, G. and Tsanakas, D. (2005) "Analytical calculation of the magnetic field produced by electric
power lines", IEEE Transaction on Power Delivery, vol. 20, no. 2, pp. 1474 –1482.
Chung, Yi-Li., Sung, F.-C., Chen, F-L., Lee, P-C., Silva, M. and Mezei, G. (2007), "Extremely-low-
frequency magnetic field exposure of children at schools near high voltage transmission lines", Science of
the Total Environment, Vol. 376, pp 151– 159.




                                                    221
Innovative Systems Design and Engineering                                                   www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011

Kim, J., Ha, C.S., Lee, H.J. and Song, K. (2010), "Repetitive exposure to a 60 Hz time-varying magnetic
field induces DNA double-strand breaks and apoptosis in human cells", Biochemical and Biophysical
Research Communications vol.400, pp 739–744.
Stewart, J.R., Dale, S.J. and Klein, K.W. (1993), "Magnetic field reduction using high phase order lines",
IEEE Transaction on Power Delivery, vol. 8, no. 2, pp 628 – 636.
Jonsson, U., Larsson, A. and Sjödin, J.O. (1994), "Optimized reduction of the magnetic field near Swedish
400 kV lines by advanced control of shield wire currents. Test results and economic evaluation", IEEE
Transaction on Power Delivery., vol. 9, no. 2, 961– 969.
Memari A.R. and Janischewskyj, W. (1996), "Mitigation of magnetic field near power line" ,IEEE
Transaction on Power Delivery, vol. 11, no. 3, pp 1577– 1586.
Lindberg, L. (1998), "Reduction of magnetic fields from electric power and installation lines", IEE
Proceedings on Science, Measurement and Technology, vol. 145, no. 5, pp 215 – 221.
Pettersson, P. (1996), "Principles in transmission line magnetic field reduction", IEEE Transaction on
Power Delivery, vol. 11, no. 3, pp 1587–1592.
Rashkes, V.S. and Lordan, R. (1998), "Magnetic field reduction methods: efficiency and cost", IEEE
Transaction on Power Delivery, vol. 13, no. 2. pp. 5521–559.
Yamazaki, K., Kawamoto, T. and Fujinami, H. (2000), "Requirements for Power Line Magnetic Field
Mitigation Using a Passive Loop Conductor", IEEE Transactions on Power Delivery, vol. 15, no. 2, pp
646– 651.
Cruz, P., Izquierdo, C. and Burgos, M. (2003), "Optimum Passive Shields for Mitigation of Power Lines
Magnetic Field", IEEE Transaction on Power Delivery, vol. 18, no. 4, pp 1357 – 1362.
Ippolito, L. and Siano, P. (2004), "Using multi-objective optimal power flow for reducing magnetic fields
from power lines", Electric Power Systems Research, vol. 68, pp 93 – 101.
Kalhor, H.A. and Zunoubi, M. R. (2005), "Mitigation of power frequency fields by proper choice of line
configuration and shielding", journal of Electromagnetics, vol. 25, no. 3, pp 231–243.
Faria, J.A.B. and Almeida, M.E. (2007), "accurate calculation of magnetic field intensity due to overhead
power lines with or without mitigation loops with or without capacitor compensation", IEEE Transaction on
Power Delivery, vol. 22, no. 2, pp 951– 959.
Romero, P.C., Santos, J.R., López, J.C.D., Jaén, A.V. and Ramos, J.L.M. (2007), "A Comparative Analysis
of Passive Loop-Based Magnetic Field Mitigation of Overhead Lines", IEEE Transaction on Power
Delivery, vol. 22, no. 3, pp 1773 - 1781.
Radwan, R. M., Abdel-Salam, M., Mahdy, A.M. and Samy, M.M. (2010), "Mitigation of Electric Fields
Underneath EHV Transmission Lines Using Active and Passive Shield Wires," Proceedings of the 8th
Regional Conference for National Committee of CIGRE in the Arab Countries, October 18-20, Doha,
Qatar.




                                                   222
Innovative Systems Design and Engineering                                                  www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011




         Fig. 1: Three phase transmission line above ground with the images of line conductors.




                                                  223
Innovative Systems Design and Engineering                                                   www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011

         Fig. 2: Normal and tangential field components at a point on the subconductor surface.




                                                    (a)
                         CB

                                    R Ammeter 1                                 The Loop
                                                                                Conductor




   Three Phase                          Ammeter 2
   Supply                           R




                                        Ammeter 3
                                    R



                                                    (b)

                                    Ammeter

                                        CB
                                              R


                     Single Phase
                        Supply                      R1



                                                 (c)
    Fig. 3 Arrangement of phase conductors and shield wires of an experimental circuit for the model




                                                    224
Innovative Systems Design and Engineering                                                                           www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011

(a) Transmission line model configuration (b) experimental model and (c) Active circuit to drive current in
                                                the loop.

                                        0.008
                                                                                       Passive Calculated
                                                                                       Passive Measured
                                        0.007                                          Calculated No shield
                                                                                       Measured No shield
                                        0.006
         Magnetic field denstity (µT)




                                        0.005


                                        0.004


                                        0.003


                                        0.002


                                        0.001


                                           0
                                                1.2   1.7   2.2       2.7        3.2            3.7           4.2
                                                                  Distance (m)
  Fig. 4: Comparison of the calculated and measured values of magnetic field distribution at 0.3 m height
 above the ground surface with and without passive shield wires, Hs=1 m, S=4.3 m. Phase current = 10 A.




                                                                     225
Innovative Systems Design and Engineering                                                                                                                           www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011

                             50
                                                                                                                                      Perecntage Error of
                                                                                                                                      Passive Shield
                             40
         Precentage Error%



                             30




                             20
                                                                                               Edge of ROW

                             10




                              0
                                                         1.2         1.4       1.6   1.8   2   2.2    2.4    2.6    2.8   3     3.2   3.4     3.6   3.8         4   4.2


                       -10
                                                                                                        Distance (m)
 Fig. 5: Percentage error of the magnetic field distribution at 0.3 m height above the ground surface using
                    passive shield wires with Hs=1 m, S=4.3 m. Phase current = 10 A.
                                                                 0.008
                                                                                                                                Passive Calculated
                                                                                                                                Passive Measured
                                                                 0.007                                                          Calculated No shield
                                                                                                                                Measured No shield
                                                                 0.006
                                  Magnetic field denstity (µT)




                                                                 0.005



                                                                 0.004



                                                                 0.003



                                                                 0.002



                                                                 0.001



                                                                    0
                                                                         1.2         1.7        2.2           2.7         3.2           3.7               4.2
                                                                                                       Distance (m)

  Fig. 6: Comparison of the calculated and measured values of magnetic field distribution at 0.3 m height
 above the ground level with and without passive shield wires, Hs=1.45 m, S=4.3 m. Phase current = 10 A.




                                                                                                            226
Innovative Systems Design and Engineering                                                                                                          www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011


                                                50

                                                                                                                                  Perecentage Error
                                                45                                                                                of Passive Shields


                                                40


                                                35
                           Percentage Error %




                                                30


                                                25


                                                20


                                                15                                      Edge of ROW

                                                10


                                                 5


                                                 0
                                                          1.2   1.4   1.6   1.8   2     2.2   2.4   2.6   2.8     3   3.2   3.4    3.6   3.8   4   4.2

                                                                                               Distance (m)
 Fig. 7: Percentage error of the magnetic field distribution at 0.3 m height above the ground surface using
                   passive shield wires with Hs=1.45 m, S=4.3 m. Phase current = 10 A.

                                    0.008
                                                                                                                 Calculated No shield
                                                                                                                 Calculated (Ish/I)=0.1
                                                                                                                 Calculated (Ish/I)=0.2
                                    0.007                                                                        Calculated (Ish/I)=0.3
                                                                                                                 Calculated (Ish/I)=0.4
                                                                                                                 Calculated (Ish/I)=0.5
                                                                                                                 Measured No shield
                                    0.006                                                                        Measured (Ish/I)=0.1
                                                                                                                 Measured (Ish/I)=0.2
      Magnetic field density (µT)




                                                                                                                 Measured (Ish/I)=0.3
                                                                                                                 Measured (Ish/I)=0.4
                                                                                                                 Measured (Ish/I)=0.5
                                    0.005



                                    0.004



                                    0.003



                                    0.002



                                    0.001



                                                     0
                                                         1.2          1.7         2.2           2.7             3.2         3.7          4.2
                                                                                         Distance (m)




                                                                                                    227
Innovative Systems Design and Engineering                                                                                                                                www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011

  Fig. 8: Comparison of the calculated and measured values of magnetic field distribution at 0.3 m height
  above the ground surface with and without active shield wires, Hs=1 m, S=4.3 m, variable shield wires'
                                      current. Phase current = 10 A.

               40
                                                                                                                                            Error (Ish/I=.1)
                                                                                                                                            Error(Ish/I=.2)
               30                                                                                                                           Error(Ish/I=.3)
                                                                                                                                            Error (Ish/I=.4)
                                                                                                                                            Error (Ish/I=.5)
                                                                                                 Edge of ROW
               20
   Perecentage Error %




               10



                         0
                             1.2               1.4                  1.6        1.8   2     2.2   2.4    2.6   2.79   3   3.2   3.4    3.6    3.8         4   4.2


          -10



          -20



          -30



          -40                                                                                    Distance (m)

  Fig. 9: Percentage error of the magnetic field distribution at 0.3 m height above the ground surface with
                 variable shield wires' current with Hs=1 m, S=4.3 m. Phase current = 10 A.
                                                                 0.008
                                                                                                                                 Calculated No shield
                                                                                                                                 Calculated (Ish/I)=0.1
                                                                 0.007                                                           Calculated (Ish/I)=0.2
                                                                                                                                 Calculated (Ish/I)=0.3
                                                                                                                                 Calculated (Ish/I)=0.4
                                                                                                                                 Calculated (Ish/I)=0.5
                                                                 0.006                                                           Measured No shield
                                   Magnetic field density (µT)




                                                                                                                                 Measured (Ish/I)=0.1
                                                                                                                                 Measured (Ish/I)=0.2
                                                                 0.005                                                           Measured (Ish/I)=0.3
                                                                                                                                 Measured (Ish/I)=0.4
                                                                                                                                 Measured (Ish/I)=0.5
                                                                 0.004


                                                                 0.003


                                                                 0.002


                                                                 0.001


                                                                    0
                                                                         1.2             1.7           2.2          2.7         3.2                3.7             4.2
                                                                                                               Distance (m)




                                                                                                               228
Innovative Systems Design and Engineering                                                                            www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011

  Fig. 10: Comparison of the calculated and measured values of magnetic field distribution at 0.3 m height
 above the ground surface with and without active shield wires, Hs=1.45 m, S=4.3 m, variable shield wires'
                                       current. Phase current = 10 A.

                           100
                                        Error(Ish/I)=0.1
                            90
                                        Error(Ish/I)=0.2
                                        Error(Ish/I)=0.3
                            80
                                        Error(Ish/I)=0.4
                            70          Error(Ish/I)=0.5

                            60
      Percentage Error %




                            50

                            40

                            30                                  Edge of ROW
                            20

                            10

                             0
                                 1.2   1.4   1.6     1.8   2   2.2   2.4     2.6   2.8   3   3.2   3.4   3.6   3.8      4
                           -10

                           -20

                           -30
                                                                     Distance (m)
  Fig. 11: Percentage error of the magnetic field distribution at 0.3 m height above the ground surface at
              variable shield wires' current with Hs=1.45 m, S=4.3 m. Phase current = 10 A.




                                                                       229
Innovative Systems Design and Engineering                                                                                                                              www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011

                                                           0.006
                                                                                                                                            Passive Calculated
                                                                                                                                            Passive Measured
                                                           0.005

                                   Magnetic field denstity (µT)
                                                                                                                                            Calculated No
                                                                                                                                            shield
                                                                                                                                            Measured No shield
                                                           0.004



                                                           0.003



                                                           0.002



                                                           0.001



                                                                    0
                                                                        1.2           1.7             2.2                 2.7         3.2            3.7         4.2
                                                                                                                  Distance (m)
 Fig. 12: Comparison of the calculated and measured values of magnetic field distribution at 0.3 m height
 above the ground surface with and without passive shield wires, Hs=1 m, S=4.3 m. Phase current = 5.7 A.


                      100
                                                                  PR of Passive Shielding

                              80                                  PR of No Shield


                              60
         Percentage Error %




                              40
                                                                                                      Edge of ROW

                              20



                               0
                                    1.2                            1.4        1.6   1.8     2   2.2         2.4     2.6     2.8   3    3.2     3.4   3.6   3.8   4     4.2


                          -20



                          -40
                                                                                                                  Distance (m)




                                                                                                                   230
Innovative Systems Design and Engineering                                                         www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011

 Fig. 13: Percentage error of the magnetic field distribution at 0.3 m height above the ground surface using
                    passive shield wires with Hs=1 m, S=4.3 m. Phase current = 5.7 A.
                                      0.006
                                                                                     Calculated No shield
                                                                                     Calculated (Ish/I)=0.2
                                                                                     Calculated (Ish/I)=.3
                                                                                     Calculated (Ish/I)=0.4
                                      0.005                                          Calculated (Ish/I)=.5
                                                                                     Measured No shield
                                                                                     Measured (Ish/I)=.2
        Magnetic field density (µT)




                                                                                     Measured (Ish/I)=.3
                                      0.004                                          Measured (Ish/I)=0.4
                                                                                     Measured (Ish/I)=.5



                                      0.003




                                      0.002




                                      0.001




                                         0
                                              1.2   1.7   2.2         2.7      3.2      3.7               4.2
                                                                Distance (m)

 Fig. 14: Comparison of the calculated and measured values of magnetic field distribution at 0.3 m height
above the ground surface with and without active shield wires, Hs=1.45 m, S=4.3 m, variable shield wires'
                                     current. Phase current = 5.7 A.




                                                                231
Innovative Systems Design and Engineering                                                                         www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 4, 2011

                       35
                                                                                                      Error   No shield
                                                                                                      Error   (Ish/I=.2)
                                                                                                      Error   (Ish/I=.3)
                                                                                                      Error   (Ish/I=0.4)
                       25
                                                                                                      Error   (Ish/I=.5)

                                                                  Edge of ROW
      Percentage Error %



                       15




                           5



                                1.2   1.4   1.6   1.8   2   2.2    2.4    2.6   2.8   3   3.2   3.4     3.6     3.8    4

                           -5




                   -15




                   -25
                                                                  Distance (m)
  Fig. 15: Percentage error of the magnetic field distribution at 0.3 m height above the ground surface at
              variable shield wires' current with Hs=1.45 m, S=4.3 m. Phase current = 5.7 A.




                                                                    232

Más contenido relacionado

La actualidad más candente

Performance evaluation of reversible logic based cntfet demultiplexer 2
Performance evaluation of reversible logic based cntfet demultiplexer 2Performance evaluation of reversible logic based cntfet demultiplexer 2
Performance evaluation of reversible logic based cntfet demultiplexer 2IAEME Publication
 
Partially filled electrode for DMF devices
Partially filled electrode for DMF devicesPartially filled electrode for DMF devices
Partially filled electrode for DMF devicesWaleed Salman
 
Hamiltonian Approach for Electromagnetic Field in One-dimensional Photonic Cr...
Hamiltonian Approach for Electromagnetic Field in One-dimensional Photonic Cr...Hamiltonian Approach for Electromagnetic Field in One-dimensional Photonic Cr...
Hamiltonian Approach for Electromagnetic Field in One-dimensional Photonic Cr...IRJET Journal
 
A novel model of rf mems shunt switch
A novel model of rf mems shunt switchA novel model of rf mems shunt switch
A novel model of rf mems shunt switcheSAT Publishing House
 
paper 0654 - MicroTAS
paper 0654 - MicroTASpaper 0654 - MicroTAS
paper 0654 - MicroTASWaleed Salman
 
PhD defense
PhD defensePhD defense
PhD defenseaamir064
 
23 15028 15028 novel artificial ijeecs 1570310073(edit)
23 15028 15028 novel artificial ijeecs  1570310073(edit)23 15028 15028 novel artificial ijeecs  1570310073(edit)
23 15028 15028 novel artificial ijeecs 1570310073(edit)nooriasukmaningtyas
 
Modeling the transport of charge carriers in the active devices diode submicr...
Modeling the transport of charge carriers in the active devices diode submicr...Modeling the transport of charge carriers in the active devices diode submicr...
Modeling the transport of charge carriers in the active devices diode submicr...IJERA Editor
 
Effect of mesh grid structure in reducing hot carrier effect of nmos device s...
Effect of mesh grid structure in reducing hot carrier effect of nmos device s...Effect of mesh grid structure in reducing hot carrier effect of nmos device s...
Effect of mesh grid structure in reducing hot carrier effect of nmos device s...ijcsa
 
2 d electrical resistivity tomography (ert) survey using the multi electrode ...
2 d electrical resistivity tomography (ert) survey using the multi electrode ...2 d electrical resistivity tomography (ert) survey using the multi electrode ...
2 d electrical resistivity tomography (ert) survey using the multi electrode ...Alexander Decker
 
The dynamical-casimir-effect-in-superconducting-microwave-circuits
The dynamical-casimir-effect-in-superconducting-microwave-circuitsThe dynamical-casimir-effect-in-superconducting-microwave-circuits
The dynamical-casimir-effect-in-superconducting-microwave-circuitsvilla1451
 
Electronic bands structure and gap in mid-infrared detector InAs/GaSb type II...
Electronic bands structure and gap in mid-infrared detector InAs/GaSb type II...Electronic bands structure and gap in mid-infrared detector InAs/GaSb type II...
Electronic bands structure and gap in mid-infrared detector InAs/GaSb type II...IJERA Editor
 
Our fourth publication
Our fourth publicationOur fourth publication
Our fourth publicationFraser Harris
 
Isolation of MIMO Antenna with Electromagnetic Band Gap Structure
Isolation of MIMO Antenna with Electromagnetic Band Gap StructureIsolation of MIMO Antenna with Electromagnetic Band Gap Structure
Isolation of MIMO Antenna with Electromagnetic Band Gap StructureAysu COSKUN
 
Modeling of solar array and analyze the current transient
Modeling of solar array and analyze the current transientModeling of solar array and analyze the current transient
Modeling of solar array and analyze the current transientEditor Jacotech
 

La actualidad más candente (19)

Performance evaluation of reversible logic based cntfet demultiplexer 2
Performance evaluation of reversible logic based cntfet demultiplexer 2Performance evaluation of reversible logic based cntfet demultiplexer 2
Performance evaluation of reversible logic based cntfet demultiplexer 2
 
Ieee depth
Ieee depthIeee depth
Ieee depth
 
400
400400
400
 
Partially filled electrode for DMF devices
Partially filled electrode for DMF devicesPartially filled electrode for DMF devices
Partially filled electrode for DMF devices
 
Hamiltonian Approach for Electromagnetic Field in One-dimensional Photonic Cr...
Hamiltonian Approach for Electromagnetic Field in One-dimensional Photonic Cr...Hamiltonian Approach for Electromagnetic Field in One-dimensional Photonic Cr...
Hamiltonian Approach for Electromagnetic Field in One-dimensional Photonic Cr...
 
A novel model of rf mems shunt switch
A novel model of rf mems shunt switchA novel model of rf mems shunt switch
A novel model of rf mems shunt switch
 
paper 0654 - MicroTAS
paper 0654 - MicroTASpaper 0654 - MicroTAS
paper 0654 - MicroTAS
 
PhD defense
PhD defensePhD defense
PhD defense
 
172
172172
172
 
23 15028 15028 novel artificial ijeecs 1570310073(edit)
23 15028 15028 novel artificial ijeecs  1570310073(edit)23 15028 15028 novel artificial ijeecs  1570310073(edit)
23 15028 15028 novel artificial ijeecs 1570310073(edit)
 
Modeling the transport of charge carriers in the active devices diode submicr...
Modeling the transport of charge carriers in the active devices diode submicr...Modeling the transport of charge carriers in the active devices diode submicr...
Modeling the transport of charge carriers in the active devices diode submicr...
 
Effect of mesh grid structure in reducing hot carrier effect of nmos device s...
Effect of mesh grid structure in reducing hot carrier effect of nmos device s...Effect of mesh grid structure in reducing hot carrier effect of nmos device s...
Effect of mesh grid structure in reducing hot carrier effect of nmos device s...
 
2 d electrical resistivity tomography (ert) survey using the multi electrode ...
2 d electrical resistivity tomography (ert) survey using the multi electrode ...2 d electrical resistivity tomography (ert) survey using the multi electrode ...
2 d electrical resistivity tomography (ert) survey using the multi electrode ...
 
The dynamical-casimir-effect-in-superconducting-microwave-circuits
The dynamical-casimir-effect-in-superconducting-microwave-circuitsThe dynamical-casimir-effect-in-superconducting-microwave-circuits
The dynamical-casimir-effect-in-superconducting-microwave-circuits
 
Electronic bands structure and gap in mid-infrared detector InAs/GaSb type II...
Electronic bands structure and gap in mid-infrared detector InAs/GaSb type II...Electronic bands structure and gap in mid-infrared detector InAs/GaSb type II...
Electronic bands structure and gap in mid-infrared detector InAs/GaSb type II...
 
Our fourth publication
Our fourth publicationOur fourth publication
Our fourth publication
 
Presentation
PresentationPresentation
Presentation
 
Isolation of MIMO Antenna with Electromagnetic Band Gap Structure
Isolation of MIMO Antenna with Electromagnetic Band Gap StructureIsolation of MIMO Antenna with Electromagnetic Band Gap Structure
Isolation of MIMO Antenna with Electromagnetic Band Gap Structure
 
Modeling of solar array and analyze the current transient
Modeling of solar array and analyze the current transientModeling of solar array and analyze the current transient
Modeling of solar array and analyze the current transient
 

Destacado

Mediabiz International in the news - 2010-11
Mediabiz International in the news - 2010-11Mediabiz International in the news - 2010-11
Mediabiz International in the news - 2010-11Frederic Guarino
 
schemi luce di Andrea Liberini
schemi luce di Andrea Liberinischemi luce di Andrea Liberini
schemi luce di Andrea Liberiniliberinilibby
 
Brand engagement - Brand Breakfast 9 July 2014
Brand engagement - Brand Breakfast 9 July 2014Brand engagement - Brand Breakfast 9 July 2014
Brand engagement - Brand Breakfast 9 July 2014CharityComms
 
Special report by epic research 15.03.13
Special report by epic research 15.03.13Special report by epic research 15.03.13
Special report by epic research 15.03.13Epic Daily Report
 
Jamak fundraising ad_3.5x4.5
Jamak fundraising ad_3.5x4.5Jamak fundraising ad_3.5x4.5
Jamak fundraising ad_3.5x4.5kckozf
 
Diversion para abuelos y nietos
Diversion para abuelos y nietos Diversion para abuelos y nietos
Diversion para abuelos y nietos Baby'n'Joy
 
Κοινωνία και Οικονομία
Κοινωνία και ΟικονομίαΚοινωνία και Οικονομία
Κοινωνία και ΟικονομίαFlora Vivalamusica
 
El mas grande hombre de la Historia
El mas grande hombre de la HistoriaEl mas grande hombre de la Historia
El mas grande hombre de la HistoriaVision Vision316
 
Offre tertiaire relation clients
Offre tertiaire relation clients Offre tertiaire relation clients
Offre tertiaire relation clients regionalp
 
Skypecommunication/Ashbridgeschool-9thprimaryschoolofLarissa
Skypecommunication/Ashbridgeschool-9thprimaryschoolofLarissaSkypecommunication/Ashbridgeschool-9thprimaryschoolofLarissa
Skypecommunication/Ashbridgeschool-9thprimaryschoolofLarissakalliopiperri
 
ADOLESCENCIA
ADOLESCENCIAADOLESCENCIA
ADOLESCENCIAluneta78
 
When TEASing is a Good Thing
When TEASing is a Good ThingWhen TEASing is a Good Thing
When TEASing is a Good ThingJan North
 

Destacado (20)

в столовой
в столовойв столовой
в столовой
 
Ijetcas14 390
Ijetcas14 390Ijetcas14 390
Ijetcas14 390
 
Mediabiz International in the news - 2010-11
Mediabiz International in the news - 2010-11Mediabiz International in the news - 2010-11
Mediabiz International in the news - 2010-11
 
schemi luce di Andrea Liberini
schemi luce di Andrea Liberinischemi luce di Andrea Liberini
schemi luce di Andrea Liberini
 
Brand engagement - Brand Breakfast 9 July 2014
Brand engagement - Brand Breakfast 9 July 2014Brand engagement - Brand Breakfast 9 July 2014
Brand engagement - Brand Breakfast 9 July 2014
 
Ez parkolók
Ez parkolókEz parkolók
Ez parkolók
 
Special report by epic research 15.03.13
Special report by epic research 15.03.13Special report by epic research 15.03.13
Special report by epic research 15.03.13
 
Jamak fundraising ad_3.5x4.5
Jamak fundraising ad_3.5x4.5Jamak fundraising ad_3.5x4.5
Jamak fundraising ad_3.5x4.5
 
Epics fall 2010
Epics fall 2010Epics fall 2010
Epics fall 2010
 
El hijo prodigo
El hijo prodigoEl hijo prodigo
El hijo prodigo
 
Diversion para abuelos y nietos
Diversion para abuelos y nietos Diversion para abuelos y nietos
Diversion para abuelos y nietos
 
Κοινωνία και Οικονομία
Κοινωνία και ΟικονομίαΚοινωνία και Οικονομία
Κοινωνία και Οικονομία
 
Blackberrymc
BlackberrymcBlackberrymc
Blackberrymc
 
El mas grande hombre de la Historia
El mas grande hombre de la HistoriaEl mas grande hombre de la Historia
El mas grande hombre de la Historia
 
032147
032147032147
032147
 
Offre tertiaire relation clients
Offre tertiaire relation clients Offre tertiaire relation clients
Offre tertiaire relation clients
 
mujeres maestras
mujeres maestras mujeres maestras
mujeres maestras
 
Skypecommunication/Ashbridgeschool-9thprimaryschoolofLarissa
Skypecommunication/Ashbridgeschool-9thprimaryschoolofLarissaSkypecommunication/Ashbridgeschool-9thprimaryschoolofLarissa
Skypecommunication/Ashbridgeschool-9thprimaryschoolofLarissa
 
ADOLESCENCIA
ADOLESCENCIAADOLESCENCIA
ADOLESCENCIA
 
When TEASing is a Good Thing
When TEASing is a Good ThingWhen TEASing is a Good Thing
When TEASing is a Good Thing
 

Similar a 22 m. abdel salam--218-232

Three Dimensional Modelling of MISFET
Three Dimensional Modelling of MISFETThree Dimensional Modelling of MISFET
Three Dimensional Modelling of MISFETIJERA Editor
 
Microstrip line discontinuities simulation at microwave frequencies
Microstrip line discontinuities simulation at microwave frequenciesMicrostrip line discontinuities simulation at microwave frequencies
Microstrip line discontinuities simulation at microwave frequenciesAlexander Decker
 
IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...
IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...
IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...ISAR Publications
 
Design of rotating electrical machines
Design of rotating electrical machinesDesign of rotating electrical machines
Design of rotating electrical machinesBinodKumarSahu5
 
Cbse Class 12 Physics Sample Paper 2010 Model 1
Cbse Class 12 Physics Sample Paper 2010 Model 1Cbse Class 12 Physics Sample Paper 2010 Model 1
Cbse Class 12 Physics Sample Paper 2010 Model 1Sunaina Rawat
 
Design and manufacturing of iris waveguide filters for satellite communication
Design and manufacturing of iris waveguide filters for satellite communicationDesign and manufacturing of iris waveguide filters for satellite communication
Design and manufacturing of iris waveguide filters for satellite communicationTELKOMNIKA JOURNAL
 
Cassie-Negar Poster 9-28-15 CC
Cassie-Negar Poster 9-28-15 CCCassie-Negar Poster 9-28-15 CC
Cassie-Negar Poster 9-28-15 CCCassandra Clark
 
Radiation beam scanning for leaky wave antenna by using slots
Radiation beam scanning for leaky wave antenna by using slotsRadiation beam scanning for leaky wave antenna by using slots
Radiation beam scanning for leaky wave antenna by using slotsTELKOMNIKA JOURNAL
 
EVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVEL
EVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVELEVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVEL
EVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVELPiero Belforte
 
IRJET- Electrostatic Field Effect on Human Body Due to 400kv Overhead Transmi...
IRJET- Electrostatic Field Effect on Human Body Due to 400kv Overhead Transmi...IRJET- Electrostatic Field Effect on Human Body Due to 400kv Overhead Transmi...
IRJET- Electrostatic Field Effect on Human Body Due to 400kv Overhead Transmi...IRJET Journal
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)ijceronline
 
Effect of Piezoelectric Layer on Beam Parameters using Zigzag Theory
Effect of Piezoelectric Layer on Beam Parameters using Zigzag TheoryEffect of Piezoelectric Layer on Beam Parameters using Zigzag Theory
Effect of Piezoelectric Layer on Beam Parameters using Zigzag TheoryIDES Editor
 
Control Radiation Pattern for Half Width Microstrip Leaky Wave Antenna by Usi...
Control Radiation Pattern for Half Width Microstrip Leaky Wave Antenna by Usi...Control Radiation Pattern for Half Width Microstrip Leaky Wave Antenna by Usi...
Control Radiation Pattern for Half Width Microstrip Leaky Wave Antenna by Usi...IJECEIAES
 

Similar a 22 m. abdel salam--218-232 (20)

Three Dimensional Modelling of MISFET
Three Dimensional Modelling of MISFETThree Dimensional Modelling of MISFET
Three Dimensional Modelling of MISFET
 
minas
minasminas
minas
 
D1103042431
D1103042431D1103042431
D1103042431
 
Microstrip line discontinuities simulation at microwave frequencies
Microstrip line discontinuities simulation at microwave frequenciesMicrostrip line discontinuities simulation at microwave frequencies
Microstrip line discontinuities simulation at microwave frequencies
 
Microstripline
MicrostriplineMicrostripline
Microstripline
 
IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...
IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...
IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...
 
Design of rotating electrical machines
Design of rotating electrical machinesDesign of rotating electrical machines
Design of rotating electrical machines
 
05617901
0561790105617901
05617901
 
Cbse Class 12 Physics Sample Paper 2010 Model 1
Cbse Class 12 Physics Sample Paper 2010 Model 1Cbse Class 12 Physics Sample Paper 2010 Model 1
Cbse Class 12 Physics Sample Paper 2010 Model 1
 
Design and manufacturing of iris waveguide filters for satellite communication
Design and manufacturing of iris waveguide filters for satellite communicationDesign and manufacturing of iris waveguide filters for satellite communication
Design and manufacturing of iris waveguide filters for satellite communication
 
Cassie-Negar Poster 9-28-15 CC
Cassie-Negar Poster 9-28-15 CCCassie-Negar Poster 9-28-15 CC
Cassie-Negar Poster 9-28-15 CC
 
Radiation beam scanning for leaky wave antenna by using slots
Radiation beam scanning for leaky wave antenna by using slotsRadiation beam scanning for leaky wave antenna by using slots
Radiation beam scanning for leaky wave antenna by using slots
 
EVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVEL
EVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVELEVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVEL
EVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVEL
 
00103262
0010326200103262
00103262
 
IRJET- Electrostatic Field Effect on Human Body Due to 400kv Overhead Transmi...
IRJET- Electrostatic Field Effect on Human Body Due to 400kv Overhead Transmi...IRJET- Electrostatic Field Effect on Human Body Due to 400kv Overhead Transmi...
IRJET- Electrostatic Field Effect on Human Body Due to 400kv Overhead Transmi...
 
Et36891896
Et36891896Et36891896
Et36891896
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)
 
Active shielding
Active shieldingActive shielding
Active shielding
 
Effect of Piezoelectric Layer on Beam Parameters using Zigzag Theory
Effect of Piezoelectric Layer on Beam Parameters using Zigzag TheoryEffect of Piezoelectric Layer on Beam Parameters using Zigzag Theory
Effect of Piezoelectric Layer on Beam Parameters using Zigzag Theory
 
Control Radiation Pattern for Half Width Microstrip Leaky Wave Antenna by Usi...
Control Radiation Pattern for Half Width Microstrip Leaky Wave Antenna by Usi...Control Radiation Pattern for Half Width Microstrip Leaky Wave Antenna by Usi...
Control Radiation Pattern for Half Width Microstrip Leaky Wave Antenna by Usi...
 

Más de Alexander Decker

Abnormalities of hormones and inflammatory cytokines in women affected with p...
Abnormalities of hormones and inflammatory cytokines in women affected with p...Abnormalities of hormones and inflammatory cytokines in women affected with p...
Abnormalities of hormones and inflammatory cytokines in women affected with p...Alexander Decker
 
A validation of the adverse childhood experiences scale in
A validation of the adverse childhood experiences scale inA validation of the adverse childhood experiences scale in
A validation of the adverse childhood experiences scale inAlexander Decker
 
A usability evaluation framework for b2 c e commerce websites
A usability evaluation framework for b2 c e commerce websitesA usability evaluation framework for b2 c e commerce websites
A usability evaluation framework for b2 c e commerce websitesAlexander Decker
 
A universal model for managing the marketing executives in nigerian banks
A universal model for managing the marketing executives in nigerian banksA universal model for managing the marketing executives in nigerian banks
A universal model for managing the marketing executives in nigerian banksAlexander Decker
 
A unique common fixed point theorems in generalized d
A unique common fixed point theorems in generalized dA unique common fixed point theorems in generalized d
A unique common fixed point theorems in generalized dAlexander Decker
 
A trends of salmonella and antibiotic resistance
A trends of salmonella and antibiotic resistanceA trends of salmonella and antibiotic resistance
A trends of salmonella and antibiotic resistanceAlexander Decker
 
A transformational generative approach towards understanding al-istifham
A transformational  generative approach towards understanding al-istifhamA transformational  generative approach towards understanding al-istifham
A transformational generative approach towards understanding al-istifhamAlexander Decker
 
A time series analysis of the determinants of savings in namibia
A time series analysis of the determinants of savings in namibiaA time series analysis of the determinants of savings in namibia
A time series analysis of the determinants of savings in namibiaAlexander Decker
 
A therapy for physical and mental fitness of school children
A therapy for physical and mental fitness of school childrenA therapy for physical and mental fitness of school children
A therapy for physical and mental fitness of school childrenAlexander Decker
 
A theory of efficiency for managing the marketing executives in nigerian banks
A theory of efficiency for managing the marketing executives in nigerian banksA theory of efficiency for managing the marketing executives in nigerian banks
A theory of efficiency for managing the marketing executives in nigerian banksAlexander Decker
 
A systematic evaluation of link budget for
A systematic evaluation of link budget forA systematic evaluation of link budget for
A systematic evaluation of link budget forAlexander Decker
 
A synthetic review of contraceptive supplies in punjab
A synthetic review of contraceptive supplies in punjabA synthetic review of contraceptive supplies in punjab
A synthetic review of contraceptive supplies in punjabAlexander Decker
 
A synthesis of taylor’s and fayol’s management approaches for managing market...
A synthesis of taylor’s and fayol’s management approaches for managing market...A synthesis of taylor’s and fayol’s management approaches for managing market...
A synthesis of taylor’s and fayol’s management approaches for managing market...Alexander Decker
 
A survey paper on sequence pattern mining with incremental
A survey paper on sequence pattern mining with incrementalA survey paper on sequence pattern mining with incremental
A survey paper on sequence pattern mining with incrementalAlexander Decker
 
A survey on live virtual machine migrations and its techniques
A survey on live virtual machine migrations and its techniquesA survey on live virtual machine migrations and its techniques
A survey on live virtual machine migrations and its techniquesAlexander Decker
 
A survey on data mining and analysis in hadoop and mongo db
A survey on data mining and analysis in hadoop and mongo dbA survey on data mining and analysis in hadoop and mongo db
A survey on data mining and analysis in hadoop and mongo dbAlexander Decker
 
A survey on challenges to the media cloud
A survey on challenges to the media cloudA survey on challenges to the media cloud
A survey on challenges to the media cloudAlexander Decker
 
A survey of provenance leveraged
A survey of provenance leveragedA survey of provenance leveraged
A survey of provenance leveragedAlexander Decker
 
A survey of private equity investments in kenya
A survey of private equity investments in kenyaA survey of private equity investments in kenya
A survey of private equity investments in kenyaAlexander Decker
 
A study to measures the financial health of
A study to measures the financial health ofA study to measures the financial health of
A study to measures the financial health ofAlexander Decker
 

Más de Alexander Decker (20)

Abnormalities of hormones and inflammatory cytokines in women affected with p...
Abnormalities of hormones and inflammatory cytokines in women affected with p...Abnormalities of hormones and inflammatory cytokines in women affected with p...
Abnormalities of hormones and inflammatory cytokines in women affected with p...
 
A validation of the adverse childhood experiences scale in
A validation of the adverse childhood experiences scale inA validation of the adverse childhood experiences scale in
A validation of the adverse childhood experiences scale in
 
A usability evaluation framework for b2 c e commerce websites
A usability evaluation framework for b2 c e commerce websitesA usability evaluation framework for b2 c e commerce websites
A usability evaluation framework for b2 c e commerce websites
 
A universal model for managing the marketing executives in nigerian banks
A universal model for managing the marketing executives in nigerian banksA universal model for managing the marketing executives in nigerian banks
A universal model for managing the marketing executives in nigerian banks
 
A unique common fixed point theorems in generalized d
A unique common fixed point theorems in generalized dA unique common fixed point theorems in generalized d
A unique common fixed point theorems in generalized d
 
A trends of salmonella and antibiotic resistance
A trends of salmonella and antibiotic resistanceA trends of salmonella and antibiotic resistance
A trends of salmonella and antibiotic resistance
 
A transformational generative approach towards understanding al-istifham
A transformational  generative approach towards understanding al-istifhamA transformational  generative approach towards understanding al-istifham
A transformational generative approach towards understanding al-istifham
 
A time series analysis of the determinants of savings in namibia
A time series analysis of the determinants of savings in namibiaA time series analysis of the determinants of savings in namibia
A time series analysis of the determinants of savings in namibia
 
A therapy for physical and mental fitness of school children
A therapy for physical and mental fitness of school childrenA therapy for physical and mental fitness of school children
A therapy for physical and mental fitness of school children
 
A theory of efficiency for managing the marketing executives in nigerian banks
A theory of efficiency for managing the marketing executives in nigerian banksA theory of efficiency for managing the marketing executives in nigerian banks
A theory of efficiency for managing the marketing executives in nigerian banks
 
A systematic evaluation of link budget for
A systematic evaluation of link budget forA systematic evaluation of link budget for
A systematic evaluation of link budget for
 
A synthetic review of contraceptive supplies in punjab
A synthetic review of contraceptive supplies in punjabA synthetic review of contraceptive supplies in punjab
A synthetic review of contraceptive supplies in punjab
 
A synthesis of taylor’s and fayol’s management approaches for managing market...
A synthesis of taylor’s and fayol’s management approaches for managing market...A synthesis of taylor’s and fayol’s management approaches for managing market...
A synthesis of taylor’s and fayol’s management approaches for managing market...
 
A survey paper on sequence pattern mining with incremental
A survey paper on sequence pattern mining with incrementalA survey paper on sequence pattern mining with incremental
A survey paper on sequence pattern mining with incremental
 
A survey on live virtual machine migrations and its techniques
A survey on live virtual machine migrations and its techniquesA survey on live virtual machine migrations and its techniques
A survey on live virtual machine migrations and its techniques
 
A survey on data mining and analysis in hadoop and mongo db
A survey on data mining and analysis in hadoop and mongo dbA survey on data mining and analysis in hadoop and mongo db
A survey on data mining and analysis in hadoop and mongo db
 
A survey on challenges to the media cloud
A survey on challenges to the media cloudA survey on challenges to the media cloud
A survey on challenges to the media cloud
 
A survey of provenance leveraged
A survey of provenance leveragedA survey of provenance leveraged
A survey of provenance leveraged
 
A survey of private equity investments in kenya
A survey of private equity investments in kenyaA survey of private equity investments in kenya
A survey of private equity investments in kenya
 
A study to measures the financial health of
A study to measures the financial health ofA study to measures the financial health of
A study to measures the financial health of
 

Último

Glenn Lazarus- Why Your Observability Strategy Needs Security Observability
Glenn Lazarus- Why Your Observability Strategy Needs Security ObservabilityGlenn Lazarus- Why Your Observability Strategy Needs Security Observability
Glenn Lazarus- Why Your Observability Strategy Needs Security Observabilityitnewsafrica
 
Modern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better StrongerModern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better Strongerpanagenda
 
React JS; all concepts. Contains React Features, JSX, functional & Class comp...
React JS; all concepts. Contains React Features, JSX, functional & Class comp...React JS; all concepts. Contains React Features, JSX, functional & Class comp...
React JS; all concepts. Contains React Features, JSX, functional & Class comp...Karmanjay Verma
 
Generative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdfGenerative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdfIngrid Airi González
 
Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...Farhan Tariq
 
A Glance At The Java Performance Toolbox
A Glance At The Java Performance ToolboxA Glance At The Java Performance Toolbox
A Glance At The Java Performance ToolboxAna-Maria Mihalceanu
 
QMMS Lesson 2 - Using MS Excel Formula.pdf
QMMS Lesson 2 - Using MS Excel Formula.pdfQMMS Lesson 2 - Using MS Excel Formula.pdf
QMMS Lesson 2 - Using MS Excel Formula.pdfROWELL MARQUINA
 
QCon London: Mastering long-running processes in modern architectures
QCon London: Mastering long-running processes in modern architecturesQCon London: Mastering long-running processes in modern architectures
QCon London: Mastering long-running processes in modern architecturesBernd Ruecker
 
Assure Ecommerce and Retail Operations Uptime with ThousandEyes
Assure Ecommerce and Retail Operations Uptime with ThousandEyesAssure Ecommerce and Retail Operations Uptime with ThousandEyes
Assure Ecommerce and Retail Operations Uptime with ThousandEyesThousandEyes
 
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Mark Goldstein
 
Generative AI - Gitex v1Generative AI - Gitex v1.pptx
Generative AI - Gitex v1Generative AI - Gitex v1.pptxGenerative AI - Gitex v1Generative AI - Gitex v1.pptx
Generative AI - Gitex v1Generative AI - Gitex v1.pptxfnnc6jmgwh
 
Microservices, Docker deploy and Microservices source code in C#
Microservices, Docker deploy and Microservices source code in C#Microservices, Docker deploy and Microservices source code in C#
Microservices, Docker deploy and Microservices source code in C#Karmanjay Verma
 
Top 10 Hubspot Development Companies in 2024
Top 10 Hubspot Development Companies in 2024Top 10 Hubspot Development Companies in 2024
Top 10 Hubspot Development Companies in 2024TopCSSGallery
 
Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...
Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...
Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...panagenda
 
JET Technology Labs White Paper for Virtualized Security and Encryption Techn...
JET Technology Labs White Paper for Virtualized Security and Encryption Techn...JET Technology Labs White Paper for Virtualized Security and Encryption Techn...
JET Technology Labs White Paper for Virtualized Security and Encryption Techn...amber724300
 
Infrared simulation and processing on Nvidia platforms
Infrared simulation and processing on Nvidia platformsInfrared simulation and processing on Nvidia platforms
Infrared simulation and processing on Nvidia platformsYoss Cohen
 
Connecting the Dots for Information Discovery.pdf
Connecting the Dots for Information Discovery.pdfConnecting the Dots for Information Discovery.pdf
Connecting the Dots for Information Discovery.pdfNeo4j
 
Manual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance AuditManual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance AuditSkynet Technologies
 
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotesMuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotesManik S Magar
 
Testing tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examplesTesting tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examplesKari Kakkonen
 

Último (20)

Glenn Lazarus- Why Your Observability Strategy Needs Security Observability
Glenn Lazarus- Why Your Observability Strategy Needs Security ObservabilityGlenn Lazarus- Why Your Observability Strategy Needs Security Observability
Glenn Lazarus- Why Your Observability Strategy Needs Security Observability
 
Modern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better StrongerModern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
 
React JS; all concepts. Contains React Features, JSX, functional & Class comp...
React JS; all concepts. Contains React Features, JSX, functional & Class comp...React JS; all concepts. Contains React Features, JSX, functional & Class comp...
React JS; all concepts. Contains React Features, JSX, functional & Class comp...
 
Generative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdfGenerative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdf
 
Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...
 
A Glance At The Java Performance Toolbox
A Glance At The Java Performance ToolboxA Glance At The Java Performance Toolbox
A Glance At The Java Performance Toolbox
 
QMMS Lesson 2 - Using MS Excel Formula.pdf
QMMS Lesson 2 - Using MS Excel Formula.pdfQMMS Lesson 2 - Using MS Excel Formula.pdf
QMMS Lesson 2 - Using MS Excel Formula.pdf
 
QCon London: Mastering long-running processes in modern architectures
QCon London: Mastering long-running processes in modern architecturesQCon London: Mastering long-running processes in modern architectures
QCon London: Mastering long-running processes in modern architectures
 
Assure Ecommerce and Retail Operations Uptime with ThousandEyes
Assure Ecommerce and Retail Operations Uptime with ThousandEyesAssure Ecommerce and Retail Operations Uptime with ThousandEyes
Assure Ecommerce and Retail Operations Uptime with ThousandEyes
 
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
 
Generative AI - Gitex v1Generative AI - Gitex v1.pptx
Generative AI - Gitex v1Generative AI - Gitex v1.pptxGenerative AI - Gitex v1Generative AI - Gitex v1.pptx
Generative AI - Gitex v1Generative AI - Gitex v1.pptx
 
Microservices, Docker deploy and Microservices source code in C#
Microservices, Docker deploy and Microservices source code in C#Microservices, Docker deploy and Microservices source code in C#
Microservices, Docker deploy and Microservices source code in C#
 
Top 10 Hubspot Development Companies in 2024
Top 10 Hubspot Development Companies in 2024Top 10 Hubspot Development Companies in 2024
Top 10 Hubspot Development Companies in 2024
 
Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...
Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...
Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...
 
JET Technology Labs White Paper for Virtualized Security and Encryption Techn...
JET Technology Labs White Paper for Virtualized Security and Encryption Techn...JET Technology Labs White Paper for Virtualized Security and Encryption Techn...
JET Technology Labs White Paper for Virtualized Security and Encryption Techn...
 
Infrared simulation and processing on Nvidia platforms
Infrared simulation and processing on Nvidia platformsInfrared simulation and processing on Nvidia platforms
Infrared simulation and processing on Nvidia platforms
 
Connecting the Dots for Information Discovery.pdf
Connecting the Dots for Information Discovery.pdfConnecting the Dots for Information Discovery.pdf
Connecting the Dots for Information Discovery.pdf
 
Manual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance AuditManual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance Audit
 
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotesMuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
 
Testing tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examplesTesting tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examples
 

22 m. abdel salam--218-232

  • 1. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 Laboratory Validation of Calculations of Magnetic Field Mitigation Underneath Transmission Lines Using Passive and Active Shield Wires Roshdy Radwan Department of Electrical Power and Machines, Faculty of Engineering, Cairo University, Giza, Egypt Email: roshdyradwan@yahoo.com Mazen Abdel-Salam (Corresponding author) Electrical Engineering Department, Faculty of Engineering, Assuit University, Assuit, Egypt Email: mazen2000as@yahoo.com Abdel-Bary Mahdy Department of Electrical Power and Machines, Faculty of Engineering, Cairo University, Giza, Egypt Email: abomohdy@yahoo.co.uk Mohamed Samy Electrical Engineering Department, Faculty of Industrial Education, Beni Suief University, Beni Suief, Egypt Email: mohamed_samy227@yahoo.com Abstract This paper is aimed at reporting experimental measurements and calculations of how the magnetic field underneath overhead transmission lines is mitigated using passive and active shield wires. The magnetic field values were compared to those calculated using the current simulation technique (CST). A laboratory transmission line model representing the Egyptian 500 kV EHV line was built with dimensions scaled down in the ratio 10:1. The flat single circuit of the line was modeled in the laboratory by phase separation of 1.2 m and conductor diameter of 2.76 mm at height of 1.9 m. The shield wires were spaced 4.3 m at a height of 1.45 m. Magnetic field measurements were carried out for load currents of 5.7 and 10 A. The field was measured at 0.3 m above ground level with and without passive and active shield wires for several different lateral positions. The measured and calculated field values generally agreed reasonably with an error ranging between 2.5 and 20 % within the ROW. The maximum reduction of magnetic field from the passive shield wires is 10% at the edge of right of way. With active shield wires carrying a current of 5 A (one half of the conductor current), the reduction of magnetic field reached 17% at the edge of ROW. Keywords: Current Simulation Technique, Magnetic Field Measurements, Magnetic Field Mitigation, Shield Wires, Transmission Lines, Health Effects. 1. Introduction Prior to about 1982, electric fields were the main concern. With the publication of two papers by (Wertheimer & Leeper 1979 and 1982) and the subsequent appearance of papers from other sources, serious concerns have developed about magnetic field exposure. Therefore, calculation and measurement of the magnetic field distribution underneath transmission lines is of great importance (Abdel-Salam 1999, Swanson 1995, Caola 1983, Cruz 2002, Nicolaou 2011, Bakhashwain 2003, and Filippopouls 2005) and should be elaborated on. 218
  • 2. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 Several studies have reported that children living near high voltage transmission and distribution lines had a higher cancer and leukemia incidence than other children (Chung 2007). However, limited studies have been reported regarding adults who live near high voltage transmission and distribution lines. In addition, various research work have suggested that exposure to electromagnetic fields could lead to DNA damages in cells under certain conditions (Kim 2010). These effects depend on factors such as mode of exposure, type of cell and intensity and duration of exposure. For the above reasons, magnetic fields should be mitigated to overcome their harmful effects on the people living or work adjacent to the transmission lines. There are many strategies and approaches to cancel and mitigate magnetic fields underneath the power transmission lines (Stewart 1993, Jonsson 1994, Memari 1996, Lindberg 1998, Pettersson 1996, Rashkes1998, Yamazaki 2000, Cruz 2003, Ippolito 2004, Kalhor 2005, Faria 2007 and Romero 2007). One of the approaches is to use active or passive shield wires underneath the line conductors. The main purpose of this work is to validate experimental and calculation of magnetic field under transmission lines with passive and active shield wires to assess how effective are these wires in mitigating the magnetic field. The measurements were made underneath a laboratory model of 500 kV transmission line. The calculations are based on the current simulation technique. 2. Calculation method The idea of current simulation technique is very simple and is similar to the charge simulation method applied for calculating electric fields (Abdel-Salam & Radwan 1999 and 2010). For a three phase transmission line of m subconductors per phase, the total number of subconductors is 3m as shown in Fig. 1. Each subconductor current is simulated by a finite number n of filamentary line currents distributed on a fictitious cylindrical surface of radius Rs which is a fraction of the subconductor radius R. The simulation currents ik, k = 1, 2, --------------, 3nm must satisfy the following conditions: 1- Zero normal component of the magnetic field strength on the subconductors' surfaces, following Biot–Savart law. 2- The sum of the filamentary line currents simulating the subconductor current must be equal to the subconductor current. A set of equations are formulated at a number of boundary points chosen on the subconductors' surfaces to satisfy the boundary conditions as follows: 3nm p k 1 kj ki  0, j  1,2,3,..............,3m(n  1) (1) nq i k k ( q 1) n 1  I cq , q  1,2,3,..............,3m (2) Where Pkj is the magnetic normal field coefficient determined by the coordinates of the j th boundary point and the kth filamentary line current and is given by: 1 p  sin  kj (3) kj 2l kj with  kj   kj   j (Fig. 2). The set of equations 1 and 2 are to be solved simultaneously for determining the 3nm unknown filamentary line currents. Once the set of equations 1 and 2 are solved for the unknown filamentary line currents, the deviation of the normal component of the magnetic field strength from the zero value is calculated at a set of check-points arbitrary chosen on the subconductors' surfaces and considered as a measure of simulation accuracy. When the simulation currents satisfy the boundary conditions at the check-points with a considerable accuracy, the magnetic field could be calculated at any point in space is given by: 219
  • 3. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 1 nm   ( y  yk )ax  ( x  xk )a y ( y  yk )ax  ( x  xk )a y  H   ik    (4) 2 k 1  ( x  xk ) 2  ( y  yk ) 2 ( x  xk ) 2  ( y  y k ) 2  Where (x, y) and (xk ,yk) are the calculation point and the location of the kth simulation line current respectively. To calculate the magnetic field from the transmission line and shield wires the following simplifying assumptions are considered: 1. Phase and shield conductors are straight and infinitely long, located at a height equal to the lowest point of the conductor sag [two-dimensional (2-D) problem] (Cruz 2003). 2. Investigated transmission line configurations are without ground wires. 3. Induced current effect on phase current is negligible. 4. Passive shield wires carry zero current. 5. Each two shield wires constitute a single loop and each three wires constitute two loops with a common wire. 6. Cross-sectional area of the shield wires is half that of the phase conductor. This is because the maximum shield current is variable up to half the phase current. 3. Experimental model An experimental laboratory model was built to validate the calculation of the magnetic field obtained by the current simulation technique. The model was constructed at the high voltage laboratory of the faculty of Engineering Cairo University as a scale model of the actual of the 500 kV Egyptian transmission line as shown in Fig. 3 (a). A horizontally arranged three phase power transmission line was built and fed from a three-phase star supply. Each phase has one conductor with cross section of 6 mm2. One loop consisting of two shield wires, each of area 3 mm2, is positioned underneath line conductors. The phase currents were 5.7 and 10 A and the shield current varied in the range 10 to 50% of the phase current. Fig. 3 (b, c) shows the arrangement of the phase conductors, control and measuring instruments for the model experiment. The line conductors were supported by a wooden frame. The ends of the three phase conductors were connected together as a star connection at one end. The parameters which affect the measured magnetic field are the values of the phase and loop currents, the height Hs of the shield wires above the ground surface and the spacing S between shield wires. Three digital multi-meters were used to measure the phase currents in the range 0 to 10 A with accuracy of 0.5%. Two types of variable resistors were used to control the phase currents and the loop current in case of active shielding as shown in Fig 3 (c). The first one was used to control the phase currents up to a maximum value of 15 A, at a voltage ranging from 200 to 250 V. The second one was used in controlling shield wire current up to 30 A at 200 V. An AC ammeter model 2013 with accuracy of 0.5% was used to measure the current in the shield wires. Two miniature circuit breakers were used for the phase and loop circuits with maximum current of 20 A at 380 V. A power frequency field meter model 113 manufactured by the Electric Field Measurements Company was used to measure the magnetic field. 4. Results and discussions The current simulation technique is applied to the experimental model shown in Fig. 3. Measurements of the magnetic field under the laboratory model were carried out. Figures 4 to 11 show the calculated and measured results of the magnetic fields at load current 10 A. Figure 4 shows the measured and calculated magnetic field values with passive shield wires at a height of one meter from ground level. The error between the measured and calculated values did not exceed 12% 220
  • 4. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 within the ROW as shown in Fig. 5. When the shield wire height was changed from 1 to 1.45 m, the results obtained followed the same trend as before with field reduction of about 10%, Figs. 6 and 7. Figure 8 plots the measured and calculated magnetic field values with active shield wires at a height of 1 m from ground surface for different wire currents. The error between the measured and calculated values ranged between 5 and 20% when the active shield wire current is one half of the conductor current, see Fig. 9. When the height of the shield wire was changed to 1.45 m, the results obtained for the magnetic field, Figs. 10 and 11, followed the same trend as those shown in Figs. 8 and 9. When the load current was changed from 10 – 5.7 A the results obtained, Figs. 12 to 15, followed the same trend as those shown in Figs. 4 – 5 and Figs. 10 – 11. 5. Conclusions Passive shield wires have an appreciable effect on magnetic field reduction at ground level (0.3 m) underneath the line; the maximum reduction may reach 10%. Active shield wires have considerable effect on the measured magnetic field underneath the transmission line model; this reduction of the field may reach 17% at the edge of the ROW. The reduction in the magnetic field increases with the increase of the current in the shield wires. For the laboratory model, the dependency of the measured magnetic field values on the phase current and shield wires' current is the same as the calculated one. The error between the measured magnetic field values and those calculated reached up to 20%. References Wertheimer, N. and Leeper, E. (1979), "Electrical wiring configurations and childhood cancer", Am. J. Epidemiol. (109) 273–284. Wertheimer, N. and Leeper, E. (1982), "Adult cancer related to electrical wires near the home", Int. J. Epidemiol. (11) 345 – 455. Abdel-Salam, M., Abdullah, H., El-Mohandes, M.Th. and El-Kishky, H. (1999), "Calculation of magnetic fields from electric power transmission lines", Electric Power Systems Research, vol. 49, pp 99–105. Swanson, J. (1995), "Magnetic Fields from Transmission Lines: Comparison of Calculation and measurements", IEE Proc. -Generation Transmission. Distribution, vol. 142, no. 5, pp 481 – 486. Caola, R.J., Deno, D.W. and Dymek, V.S.W. (1983), "Measurements of Electric and Magnetic Fields in and Around Homes near a 500 kV Transmission Line", IEEE Transactions on Power Apparatus and Systems, vol. PAS-102, no. 10, October. Cruz P., Izquierdo, C., Burgos, M., Ferrer, L.F., Soto, F., Llanos, C. and Pacheco, J.D. (2002), "Magnetic field mitigation in power lines with passive and active loops" Proceeding of Cigré Session, Paper No. 36- 107, Paris. Nicolaou, C.P., Papadakis, A.P., Razis, P.A., Kyriacou, G.A. and Sahalos, J.N. (2011), "Measurements and predictions of electric and magnetic fields from power lines" ", Electric Power Systems Research, vol. 81, pp 1107–1116. Bakhashwain, J.M., Shwehdi, M.H., Johar, U.M. and AL-Naim, A.A. (2003), "Magnetic Fields Measurement and Evaluation of EHV Transmission Lines in Saudi Arabia", Proceedings of the International Conference on Non-Ionizing Radiation at UNITEN (ICNIR 2003) Electromagnetic Fields and Our Health 20th –22nd October. Filippopouls, G. and Tsanakas, D. (2005) "Analytical calculation of the magnetic field produced by electric power lines", IEEE Transaction on Power Delivery, vol. 20, no. 2, pp. 1474 –1482. Chung, Yi-Li., Sung, F.-C., Chen, F-L., Lee, P-C., Silva, M. and Mezei, G. (2007), "Extremely-low- frequency magnetic field exposure of children at schools near high voltage transmission lines", Science of the Total Environment, Vol. 376, pp 151– 159. 221
  • 5. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 Kim, J., Ha, C.S., Lee, H.J. and Song, K. (2010), "Repetitive exposure to a 60 Hz time-varying magnetic field induces DNA double-strand breaks and apoptosis in human cells", Biochemical and Biophysical Research Communications vol.400, pp 739–744. Stewart, J.R., Dale, S.J. and Klein, K.W. (1993), "Magnetic field reduction using high phase order lines", IEEE Transaction on Power Delivery, vol. 8, no. 2, pp 628 – 636. Jonsson, U., Larsson, A. and Sjödin, J.O. (1994), "Optimized reduction of the magnetic field near Swedish 400 kV lines by advanced control of shield wire currents. Test results and economic evaluation", IEEE Transaction on Power Delivery., vol. 9, no. 2, 961– 969. Memari A.R. and Janischewskyj, W. (1996), "Mitigation of magnetic field near power line" ,IEEE Transaction on Power Delivery, vol. 11, no. 3, pp 1577– 1586. Lindberg, L. (1998), "Reduction of magnetic fields from electric power and installation lines", IEE Proceedings on Science, Measurement and Technology, vol. 145, no. 5, pp 215 – 221. Pettersson, P. (1996), "Principles in transmission line magnetic field reduction", IEEE Transaction on Power Delivery, vol. 11, no. 3, pp 1587–1592. Rashkes, V.S. and Lordan, R. (1998), "Magnetic field reduction methods: efficiency and cost", IEEE Transaction on Power Delivery, vol. 13, no. 2. pp. 5521–559. Yamazaki, K., Kawamoto, T. and Fujinami, H. (2000), "Requirements for Power Line Magnetic Field Mitigation Using a Passive Loop Conductor", IEEE Transactions on Power Delivery, vol. 15, no. 2, pp 646– 651. Cruz, P., Izquierdo, C. and Burgos, M. (2003), "Optimum Passive Shields for Mitigation of Power Lines Magnetic Field", IEEE Transaction on Power Delivery, vol. 18, no. 4, pp 1357 – 1362. Ippolito, L. and Siano, P. (2004), "Using multi-objective optimal power flow for reducing magnetic fields from power lines", Electric Power Systems Research, vol. 68, pp 93 – 101. Kalhor, H.A. and Zunoubi, M. R. (2005), "Mitigation of power frequency fields by proper choice of line configuration and shielding", journal of Electromagnetics, vol. 25, no. 3, pp 231–243. Faria, J.A.B. and Almeida, M.E. (2007), "accurate calculation of magnetic field intensity due to overhead power lines with or without mitigation loops with or without capacitor compensation", IEEE Transaction on Power Delivery, vol. 22, no. 2, pp 951– 959. Romero, P.C., Santos, J.R., López, J.C.D., Jaén, A.V. and Ramos, J.L.M. (2007), "A Comparative Analysis of Passive Loop-Based Magnetic Field Mitigation of Overhead Lines", IEEE Transaction on Power Delivery, vol. 22, no. 3, pp 1773 - 1781. Radwan, R. M., Abdel-Salam, M., Mahdy, A.M. and Samy, M.M. (2010), "Mitigation of Electric Fields Underneath EHV Transmission Lines Using Active and Passive Shield Wires," Proceedings of the 8th Regional Conference for National Committee of CIGRE in the Arab Countries, October 18-20, Doha, Qatar. 222
  • 6. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 Fig. 1: Three phase transmission line above ground with the images of line conductors. 223
  • 7. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 Fig. 2: Normal and tangential field components at a point on the subconductor surface. (a) CB R Ammeter 1 The Loop Conductor Three Phase Ammeter 2 Supply R Ammeter 3 R (b) Ammeter CB R Single Phase Supply R1 (c) Fig. 3 Arrangement of phase conductors and shield wires of an experimental circuit for the model 224
  • 8. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 (a) Transmission line model configuration (b) experimental model and (c) Active circuit to drive current in the loop. 0.008 Passive Calculated Passive Measured 0.007 Calculated No shield Measured No shield 0.006 Magnetic field denstity (µT) 0.005 0.004 0.003 0.002 0.001 0 1.2 1.7 2.2 2.7 3.2 3.7 4.2 Distance (m) Fig. 4: Comparison of the calculated and measured values of magnetic field distribution at 0.3 m height above the ground surface with and without passive shield wires, Hs=1 m, S=4.3 m. Phase current = 10 A. 225
  • 9. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 50 Perecntage Error of Passive Shield 40 Precentage Error% 30 20 Edge of ROW 10 0 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4 4.2 -10 Distance (m) Fig. 5: Percentage error of the magnetic field distribution at 0.3 m height above the ground surface using passive shield wires with Hs=1 m, S=4.3 m. Phase current = 10 A. 0.008 Passive Calculated Passive Measured 0.007 Calculated No shield Measured No shield 0.006 Magnetic field denstity (µT) 0.005 0.004 0.003 0.002 0.001 0 1.2 1.7 2.2 2.7 3.2 3.7 4.2 Distance (m) Fig. 6: Comparison of the calculated and measured values of magnetic field distribution at 0.3 m height above the ground level with and without passive shield wires, Hs=1.45 m, S=4.3 m. Phase current = 10 A. 226
  • 10. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 50 Perecentage Error 45 of Passive Shields 40 35 Percentage Error % 30 25 20 15 Edge of ROW 10 5 0 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4 4.2 Distance (m) Fig. 7: Percentage error of the magnetic field distribution at 0.3 m height above the ground surface using passive shield wires with Hs=1.45 m, S=4.3 m. Phase current = 10 A. 0.008 Calculated No shield Calculated (Ish/I)=0.1 Calculated (Ish/I)=0.2 0.007 Calculated (Ish/I)=0.3 Calculated (Ish/I)=0.4 Calculated (Ish/I)=0.5 Measured No shield 0.006 Measured (Ish/I)=0.1 Measured (Ish/I)=0.2 Magnetic field density (µT) Measured (Ish/I)=0.3 Measured (Ish/I)=0.4 Measured (Ish/I)=0.5 0.005 0.004 0.003 0.002 0.001 0 1.2 1.7 2.2 2.7 3.2 3.7 4.2 Distance (m) 227
  • 11. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 Fig. 8: Comparison of the calculated and measured values of magnetic field distribution at 0.3 m height above the ground surface with and without active shield wires, Hs=1 m, S=4.3 m, variable shield wires' current. Phase current = 10 A. 40 Error (Ish/I=.1) Error(Ish/I=.2) 30 Error(Ish/I=.3) Error (Ish/I=.4) Error (Ish/I=.5) Edge of ROW 20 Perecentage Error % 10 0 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.79 3 3.2 3.4 3.6 3.8 4 4.2 -10 -20 -30 -40 Distance (m) Fig. 9: Percentage error of the magnetic field distribution at 0.3 m height above the ground surface with variable shield wires' current with Hs=1 m, S=4.3 m. Phase current = 10 A. 0.008 Calculated No shield Calculated (Ish/I)=0.1 0.007 Calculated (Ish/I)=0.2 Calculated (Ish/I)=0.3 Calculated (Ish/I)=0.4 Calculated (Ish/I)=0.5 0.006 Measured No shield Magnetic field density (µT) Measured (Ish/I)=0.1 Measured (Ish/I)=0.2 0.005 Measured (Ish/I)=0.3 Measured (Ish/I)=0.4 Measured (Ish/I)=0.5 0.004 0.003 0.002 0.001 0 1.2 1.7 2.2 2.7 3.2 3.7 4.2 Distance (m) 228
  • 12. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 Fig. 10: Comparison of the calculated and measured values of magnetic field distribution at 0.3 m height above the ground surface with and without active shield wires, Hs=1.45 m, S=4.3 m, variable shield wires' current. Phase current = 10 A. 100 Error(Ish/I)=0.1 90 Error(Ish/I)=0.2 Error(Ish/I)=0.3 80 Error(Ish/I)=0.4 70 Error(Ish/I)=0.5 60 Percentage Error % 50 40 30 Edge of ROW 20 10 0 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4 -10 -20 -30 Distance (m) Fig. 11: Percentage error of the magnetic field distribution at 0.3 m height above the ground surface at variable shield wires' current with Hs=1.45 m, S=4.3 m. Phase current = 10 A. 229
  • 13. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 0.006 Passive Calculated Passive Measured 0.005 Magnetic field denstity (µT) Calculated No shield Measured No shield 0.004 0.003 0.002 0.001 0 1.2 1.7 2.2 2.7 3.2 3.7 4.2 Distance (m) Fig. 12: Comparison of the calculated and measured values of magnetic field distribution at 0.3 m height above the ground surface with and without passive shield wires, Hs=1 m, S=4.3 m. Phase current = 5.7 A. 100 PR of Passive Shielding 80 PR of No Shield 60 Percentage Error % 40 Edge of ROW 20 0 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4 4.2 -20 -40 Distance (m) 230
  • 14. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 Fig. 13: Percentage error of the magnetic field distribution at 0.3 m height above the ground surface using passive shield wires with Hs=1 m, S=4.3 m. Phase current = 5.7 A. 0.006 Calculated No shield Calculated (Ish/I)=0.2 Calculated (Ish/I)=.3 Calculated (Ish/I)=0.4 0.005 Calculated (Ish/I)=.5 Measured No shield Measured (Ish/I)=.2 Magnetic field density (µT) Measured (Ish/I)=.3 0.004 Measured (Ish/I)=0.4 Measured (Ish/I)=.5 0.003 0.002 0.001 0 1.2 1.7 2.2 2.7 3.2 3.7 4.2 Distance (m) Fig. 14: Comparison of the calculated and measured values of magnetic field distribution at 0.3 m height above the ground surface with and without active shield wires, Hs=1.45 m, S=4.3 m, variable shield wires' current. Phase current = 5.7 A. 231
  • 15. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 4, 2011 35 Error No shield Error (Ish/I=.2) Error (Ish/I=.3) Error (Ish/I=0.4) 25 Error (Ish/I=.5) Edge of ROW Percentage Error % 15 5 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4 -5 -15 -25 Distance (m) Fig. 15: Percentage error of the magnetic field distribution at 0.3 m height above the ground surface at variable shield wires' current with Hs=1.45 m, S=4.3 m. Phase current = 5.7 A. 232