Chilled Water Systems
Total Cost of Ownership
April 17, 2008
Todd Brown
Business Development Manager - Chillers
AGENDA
• Low temperature, low flow
• Primary-Secondary vs Variable Primary Flow
• Chillers in Series-Series Counterflow
• Chiller-Tower Optimization
Goal:
Minimize Capital & Operating Costs
Without Sacrificing:
Reliability, Efficiency, & Comfort
• Good for Business...
– Offers lower first cost and lower operating
cost.
• Good for the Environment:
– Reduced utility generated greenhouse gas
emissions.
High Performance Chilled Water Systems:
Base Design: 450 Tons
• Design
wet bulb: 78 F(25.5C)
• Entering condenser
water temperature
(ECWT): 85 F(29.4C)
• Evaporator and
condenser
temperature
differences: 10 F
(5.6C)
• Coil, valve and
chilled water piping
pressure drop: 80 ft
• Condenser water
piping pressure
drop: 30 ft
• Pump efficiency:
75%
• Pump motor
efficiency: 93%
Example: Low Flow/ High Delta T
Chiller (2.4, 3.0 gpm/ton)
• Consumption:
256 kW (0.569 kW/ton)
• Evaporator
pressure drop: 21.0 ft
• Condenser
pressure drop: 21.3 ft
example chilled water plant …
Cooling Tower (3.0 gpm/ton)
• Power rating:
30 hp
• Tower static head:
10.0 ft
example chilled water plant …
Design Formulas
DP2/DP1 = (Flow2/Flow1)
kW =
0.746 x hp
motor efficiency
hp =
gpm x PD
3960 x pump efficiency
1.85
gpm œ rpm
Head œ (gpm)²
Power œ (gpm)³
example chilled water plant …
Chilled Water Pump (2.4 gpm/ton)
• System conditions …
– System head: 80 ft
– Bundle head: 21.0 ft
– Flow rate: 1080 gpm
• Pump power …
– 36.7 hp
– 29.5 kW
• System conditions …
– System head: 26.0 ft
– Bundle head: 21.3 ft
– Tower static: 10.0 ft
– Flow rate: 1350 gpm
• Pump power …
– 26.0 hp
– 20.8 kW
example chilled water plant …
Condenser Water Pump (3.0 gpm/ton)
example chilled water plant …
System Energy Consumption
• With 2.4, 3.0 gpm/ton flows …
(0.043, 0.054 L/S/KW)
2.4/3.0
Chiller 256.0
Chilled Water Pump 29.5
Condenser Water Pump 20.8
Cooling Tower 24.1
Total kW 330.4
example chilled water plant …
Low Flow System
Base Case Low Flow……………….
ARI 42, 16dT 44 F, 14dT 44 F, 14dT; 83.3 F 42 F, 16dT
2.4/3.0 1.5/3.0 1.7/2.0 1.7/2.0 1.5/2.0
Chiller 256.0 268.0 288.0 269.0 296.0
Chilled Water Pump 29.5 16.2 19.0 19.0 16.2
Condenser Water Pump 20.8 20.8 11.3 11.3 11.3
Cooling Tower 24.1 24.1 16.0 24.1 16.0
Total kW 330.4 329.1 334.6 323.4 339.5
What About Part Load Operation?
We’ll use …
• Chiller kW values for NPLV
– Derived from the selection program
• Cooling tower kW
– Tower energy at part load based on being linear with speed
reduction
And constant kW values for the …
• Chilled water pump
• Condenser water pump
Part Load Operation
you’ve got more …
System Design Options
Either …
• Take full energy (operating
cost) savings
Or …
• Reduce piping size and cost
Experienced designers use pump,
piping and tower savings to select an
even more efficient chiller
Decoupled Systems
moving to…
Variable Flow Systems
58.0°F
2571 gpm
44.0°F
2571 gpm
58.0°F
857 gpm
(each)
bypass
(decoupler)
Primary–
Secondary
design
primary
pumps
secondary
pumps
2571 gpm
44.0°F
44.0°F
44.0°F
58.0°F
58.0°F
58.0°F
857 gpm
857 gpm
857 gpm
58.0°F
2571 gpm
44.0°F
2571 gpm
58.0°F
Variable
Primary
design
2571 gpm
44.0°F
44.0°F
44.0°F
58.0°F
58.0°F
58.0°F
857 gpm
857 gpm
857 gpm
DP
(typical)
56.0°F
1050 gpm
44.0°F
1050 gpm
56.0°F
Variable Primary part load
1050 gpm
44.0°F
56.0°F
1050
off
off
DP
(typical)
Maximum Flow = 1300 gpm
Minimum Flow = 244 gpm
Selection Flow = 750 gpm
56.0°F
1050 gpm
44.0°F
1050 gpm
56.0°F
Variable Primary part load
1050 gpm
44.0°F
56.0°F
525
525
off
DP
(typical)
Maximum Flow = 1300 gpm
Minimum Flow = 244 gpm
Selection Flow = 750 gpm
44.0°F
56.0°F
56.0°F
1050 gpm
44.0°F
1050 gpm
51.2°F
857 gpm
(each)
664 gpm
Primary–
Secondary
design
primary
pumps
secondary
pumps
1714 gpm
44.0°F
44.0°F
51.2°F
51.2°F
857 gpm
857 gpm
off
44.0°F
Lower Capital Cost Variable Primary advantages
• Fewer …
– Pumps
– Motors
– Pump bases
– Starters and wiring
– Fittings and piping
– Controls
• Less labor
More Available Space
Opportunity to …
–Add other equipment
–Select larger, more efficient chillers
–Improve service access
Simplified Control
• Unfetters chillers from
flow-based control
• Operates distribution pumps
to transport water
… not to start/stop chillers
Improved Reliability
Provides system with …
–Fewer pumps and accessories
–Fewer chiller recovery options
–Fewer pump recovery options
–Better balance between pumps
and chillers online
Chiller Selection Considerations
• Evaporator flow limits
• Rate-of-change tolerance
• Flow “range-ability”
–Difference between selection flow rate
and evaporator minimum flow limit
What are other’s
saying???
Variable Primary Flow Chilled Water
Plant Design …
VFP systems:
• Reduces total annual plant energy 3-8%
• Reduces first cost 4-8%
• Reduces life-cycle cost 3-5%*
*Relative to conventional Decoupled chilled-water systems.
VPF System
More information
• “Don’t Ignore Variable Flow,” Waltz, Contracting Business, July
1997
• “Primary-Only vs. Primary-Secondary Variable Flow Systems,”
Taylor, ASHRAE Journal, February 2002
• “Comparative Analysis of Variable and Constant Primary-Flow
Chilled-Water-Plant Performance,” Bahnfleth and Peyer, HPAC
Engineering, April 2001
• “Campus Cooling: Retrofitting Systems,” Kreutzmann, HPAC
Engineering, July 2002
unsuited for
Variable Primary Flow
• Inadequate control capability
– Insufficient chiller unloading
– Vintage chiller controls
• Poor financial return
(Consider chilled water reset instead)
Parallel VPF Systems
moving to…
Series Evaporator
Systems
VPF system configurations
Series-Counter Flow
VFD
41°F
57°F
48.96°F
103.82°F 89.6°F
96.63°F
89.6°F
103.82°F
96.63°F
48.96°F
Single
Compressor
Chiller
103.82° F
Lift
62.82° F
41° F
103.82° F
Lift
54.86° F
48.96° F
Series-Counter flow
Arrangement
Upstream Chiller
96.63° F
Lift
55.63° F
41° F
Downstream Chiller
• Upstream chiller: 103.82 - 48.96 = 54.86
• Downstream chiller: 96.63 - 41 = 55.63
• Average lift: 55.24
(vs. 62.82 for single compressor (12%))
Better chiller efficiency, but high DP
VPF system configurations
Series-Counter Flow
Chiller–Tower Optimization …
Do It Right!
chiller–tower optimization
The Question …
• What’s the “right” condenser water temperature?
Or Said Another Way …
0
50
100
150
200
250
300
350
400
72 73 74 75 76 77 78 79 80 81 82 83 84 85
Chiller kW
Tower kW
Total kW
Condenser Water Temperature
kW
chiller–tower optimization
How Do You Do It?
With real-life controls!
• MicroTech II and BAS Combination
The optimized method requires auto-adaptive
controls. This control logic constantly adjusts the
condenser water supply temperature to the value that
uses the least amount of power. The controller
measures the power requirement for the chiller and
cooling tower. The condenser water temperature
setpoint then is altered and the power consumption is
checked again. If the total power consumption goes
down, a similar adjustment is made and the total power
is checked again.
How do you do it?
What’s good for the component …
may NOT be good for the system!
where’s the meter?
The Only Possible Response …
On the building!
chiller–tower optimization
In Summary …
• Defines the optimal entering condenser
temperature
• Optimal control is the right thing to do …
AND it saves money
• Savings are real and can be quantified
• The control strategy is available NOW!
First
Cost
Operating
Cost
Exploit technology!
• Low flow
• Low temperature
• High efficiency
• Controls
Leverage:
• Optimized Controls
• Variable Primary Flow
• Series Evaporators
Lowest Total Cost of Ownership
Questions or Comments?

More Related Content

What's hot

Introduction to hvac systems
Introduction to hvac systemsIntroduction to hvac systems
Introduction to hvac systems
michaeljmack
 
228932756-Turbine-Fundamentals.ppt
228932756-Turbine-Fundamentals.ppt228932756-Turbine-Fundamentals.ppt
228932756-Turbine-Fundamentals.ppt
samisaleem9
 
Air refrigeration system by Bell Coleman cycle and Vortex tube
Air refrigeration system by Bell Coleman cycle and Vortex tubeAir refrigeration system by Bell Coleman cycle and Vortex tube
Air refrigeration system by Bell Coleman cycle and Vortex tube
aparnamalyala
 

What's hot (20)

Introduction to VRF
Introduction to VRF Introduction to VRF
Introduction to VRF
 
Gas Air Heater (Air Pre Heater)
Gas Air Heater (Air Pre Heater)Gas Air Heater (Air Pre Heater)
Gas Air Heater (Air Pre Heater)
 
HP LP Bypass system of 110 MW Steam Turbine
HP LP Bypass system of 110 MW Steam TurbineHP LP Bypass system of 110 MW Steam Turbine
HP LP Bypass system of 110 MW Steam Turbine
 
Super-Critical Boiler.ppt
Super-Critical Boiler.pptSuper-Critical Boiler.ppt
Super-Critical Boiler.ppt
 
Types of air preheaters and its advantages
Types of air preheaters and its advantagesTypes of air preheaters and its advantages
Types of air preheaters and its advantages
 
Introduction to hvac systems
Introduction to hvac systemsIntroduction to hvac systems
Introduction to hvac systems
 
Cooling Systems - Chiller Technologies
Cooling Systems - Chiller TechnologiesCooling Systems - Chiller Technologies
Cooling Systems - Chiller Technologies
 
Chiller ppt
Chiller pptChiller ppt
Chiller ppt
 
vapour absorption refrigeration system
vapour absorption refrigeration systemvapour absorption refrigeration system
vapour absorption refrigeration system
 
Air conditioning system
Air conditioning systemAir conditioning system
Air conditioning system
 
Cooling water system
Cooling water systemCooling water system
Cooling water system
 
Heat pump presentation
Heat pump presentation Heat pump presentation
Heat pump presentation
 
REFRIGERATION AND AIR CONDITIONING
REFRIGERATION AND AIR CONDITIONINGREFRIGERATION AND AIR CONDITIONING
REFRIGERATION AND AIR CONDITIONING
 
OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS
OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTSOVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS
OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS
 
Krzywa grzewcza - regulacja wydajnosci instalacji grzewczej
Krzywa grzewcza - regulacja wydajnosci instalacji grzewczejKrzywa grzewcza - regulacja wydajnosci instalacji grzewczej
Krzywa grzewcza - regulacja wydajnosci instalacji grzewczej
 
228932756-Turbine-Fundamentals.ppt
228932756-Turbine-Fundamentals.ppt228932756-Turbine-Fundamentals.ppt
228932756-Turbine-Fundamentals.ppt
 
Cooling Load Calculation
Cooling Load CalculationCooling Load Calculation
Cooling Load Calculation
 
Basics of Refrigerartion
Basics of RefrigerartionBasics of Refrigerartion
Basics of Refrigerartion
 
Air refrigeration system by Bell Coleman cycle and Vortex tube
Air refrigeration system by Bell Coleman cycle and Vortex tubeAir refrigeration system by Bell Coleman cycle and Vortex tube
Air refrigeration system by Bell Coleman cycle and Vortex tube
 
10 najczęstszych błędów przy zastosowaniu pompy ciepła
10 najczęstszych błędów przy zastosowaniu pompy ciepła10 najczęstszych błędów przy zastosowaniu pompy ciepła
10 najczęstszych błędów przy zastosowaniu pompy ciepła
 

Similar to Chilled Water Systems Total Cost of Ownership.ppt

Refrigeration and air conditioning system
Refrigeration and air conditioning systemRefrigeration and air conditioning system
Refrigeration and air conditioning system
bikramstalion
 
Chiller Plant-EN - Catalogue
Chiller Plant-EN - CatalogueChiller Plant-EN - Catalogue
Chiller Plant-EN - Catalogue
Tomas Eriksson
 
2015 x472 class 04 - central and specialty
2015 x472 class 04 - central and specialty2015 x472 class 04 - central and specialty
2015 x472 class 04 - central and specialty
michaeljmack
 
Hydracarbons in Commercial Refrigeration
Hydracarbons in Commercial RefrigerationHydracarbons in Commercial Refrigeration
Hydracarbons in Commercial Refrigeration
UNEP OzonAction
 

Similar to Chilled Water Systems Total Cost of Ownership.ppt (20)

Refrigeration and air conditioning system
Refrigeration and air conditioning systemRefrigeration and air conditioning system
Refrigeration and air conditioning system
 
Air Source Heat Pumps - Thomas Dickson - Glow Worm
Air Source Heat Pumps - Thomas Dickson - Glow WormAir Source Heat Pumps - Thomas Dickson - Glow Worm
Air Source Heat Pumps - Thomas Dickson - Glow Worm
 
INTRODUCING AQUAFAN
INTRODUCING AQUAFANINTRODUCING AQUAFAN
INTRODUCING AQUAFAN
 
Presentation 1 Training Slides.pptx
Presentation 1 Training Slides.pptxPresentation 1 Training Slides.pptx
Presentation 1 Training Slides.pptx
 
Adm apn045-en 0912
Adm apn045-en 0912Adm apn045-en 0912
Adm apn045-en 0912
 
Condensate Return Solutions.ppt
Condensate Return Solutions.pptCondensate Return Solutions.ppt
Condensate Return Solutions.ppt
 
Adiabatic cooling tower v3 08.08
Adiabatic cooling tower v3 08.08Adiabatic cooling tower v3 08.08
Adiabatic cooling tower v3 08.08
 
Chiller Plant-EN - Catalogue
Chiller Plant-EN - CatalogueChiller Plant-EN - Catalogue
Chiller Plant-EN - Catalogue
 
Chiller Plant-EN - Catalogue
Chiller Plant-EN - CatalogueChiller Plant-EN - Catalogue
Chiller Plant-EN - Catalogue
 
Hvac chilled water distribution schemes
Hvac chilled water distribution schemesHvac chilled water distribution schemes
Hvac chilled water distribution schemes
 
140919783-Cooling-Water-Basics.ppt
140919783-Cooling-Water-Basics.ppt140919783-Cooling-Water-Basics.ppt
140919783-Cooling-Water-Basics.ppt
 
chilled-water-system-presentation.pdf
chilled-water-system-presentation.pdfchilled-water-system-presentation.pdf
chilled-water-system-presentation.pdf
 
Energy-Saving Designs for Existing Buildings
Energy-Saving Designs for Existing BuildingsEnergy-Saving Designs for Existing Buildings
Energy-Saving Designs for Existing Buildings
 
hvac and refrigeration system
hvac and refrigeration systemhvac and refrigeration system
hvac and refrigeration system
 
Ice Slurry TES for Turbine Inlet Cooling
Ice Slurry TES for Turbine Inlet CoolingIce Slurry TES for Turbine Inlet Cooling
Ice Slurry TES for Turbine Inlet Cooling
 
2015 x472 class 04 - central and specialty
2015 x472 class 04 - central and specialty2015 x472 class 04 - central and specialty
2015 x472 class 04 - central and specialty
 
Energy efficiency in Refrigeration Systems
Energy efficiency in Refrigeration SystemsEnergy efficiency in Refrigeration Systems
Energy efficiency in Refrigeration Systems
 
Feb. 2016 webinar_condensate_return_piping
Feb. 2016 webinar_condensate_return_pipingFeb. 2016 webinar_condensate_return_piping
Feb. 2016 webinar_condensate_return_piping
 
Condensing Boilers
Condensing BoilersCondensing Boilers
Condensing Boilers
 
Hydracarbons in Commercial Refrigeration
Hydracarbons in Commercial RefrigerationHydracarbons in Commercial Refrigeration
Hydracarbons in Commercial Refrigeration
 

Recently uploaded

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 

Recently uploaded (20)

UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 

Chilled Water Systems Total Cost of Ownership.ppt

  • 1. Chilled Water Systems Total Cost of Ownership April 17, 2008
  • 2. Todd Brown Business Development Manager - Chillers
  • 3. AGENDA • Low temperature, low flow • Primary-Secondary vs Variable Primary Flow • Chillers in Series-Series Counterflow • Chiller-Tower Optimization
  • 4. Goal: Minimize Capital & Operating Costs Without Sacrificing: Reliability, Efficiency, & Comfort
  • 5. • Good for Business... – Offers lower first cost and lower operating cost. • Good for the Environment: – Reduced utility generated greenhouse gas emissions. High Performance Chilled Water Systems:
  • 6. Base Design: 450 Tons • Design wet bulb: 78 F(25.5C) • Entering condenser water temperature (ECWT): 85 F(29.4C) • Evaporator and condenser temperature differences: 10 F (5.6C) • Coil, valve and chilled water piping pressure drop: 80 ft • Condenser water piping pressure drop: 30 ft • Pump efficiency: 75% • Pump motor efficiency: 93% Example: Low Flow/ High Delta T
  • 7. Chiller (2.4, 3.0 gpm/ton) • Consumption: 256 kW (0.569 kW/ton) • Evaporator pressure drop: 21.0 ft • Condenser pressure drop: 21.3 ft
  • 8. example chilled water plant … Cooling Tower (3.0 gpm/ton) • Power rating: 30 hp • Tower static head: 10.0 ft
  • 9. example chilled water plant … Design Formulas DP2/DP1 = (Flow2/Flow1) kW = 0.746 x hp motor efficiency hp = gpm x PD 3960 x pump efficiency 1.85 gpm œ rpm Head œ (gpm)² Power œ (gpm)³
  • 10. example chilled water plant … Chilled Water Pump (2.4 gpm/ton) • System conditions … – System head: 80 ft – Bundle head: 21.0 ft – Flow rate: 1080 gpm • Pump power … – 36.7 hp – 29.5 kW
  • 11. • System conditions … – System head: 26.0 ft – Bundle head: 21.3 ft – Tower static: 10.0 ft – Flow rate: 1350 gpm • Pump power … – 26.0 hp – 20.8 kW example chilled water plant … Condenser Water Pump (3.0 gpm/ton)
  • 12. example chilled water plant … System Energy Consumption • With 2.4, 3.0 gpm/ton flows … (0.043, 0.054 L/S/KW) 2.4/3.0 Chiller 256.0 Chilled Water Pump 29.5 Condenser Water Pump 20.8 Cooling Tower 24.1 Total kW 330.4
  • 13. example chilled water plant … Low Flow System Base Case Low Flow………………. ARI 42, 16dT 44 F, 14dT 44 F, 14dT; 83.3 F 42 F, 16dT 2.4/3.0 1.5/3.0 1.7/2.0 1.7/2.0 1.5/2.0 Chiller 256.0 268.0 288.0 269.0 296.0 Chilled Water Pump 29.5 16.2 19.0 19.0 16.2 Condenser Water Pump 20.8 20.8 11.3 11.3 11.3 Cooling Tower 24.1 24.1 16.0 24.1 16.0 Total kW 330.4 329.1 334.6 323.4 339.5
  • 14. What About Part Load Operation? We’ll use … • Chiller kW values for NPLV – Derived from the selection program • Cooling tower kW – Tower energy at part load based on being linear with speed reduction And constant kW values for the … • Chilled water pump • Condenser water pump
  • 16. you’ve got more … System Design Options Either … • Take full energy (operating cost) savings Or … • Reduce piping size and cost Experienced designers use pump, piping and tower savings to select an even more efficient chiller
  • 18. 58.0°F 2571 gpm 44.0°F 2571 gpm 58.0°F 857 gpm (each) bypass (decoupler) Primary– Secondary design primary pumps secondary pumps 2571 gpm 44.0°F 44.0°F 44.0°F 58.0°F 58.0°F 58.0°F 857 gpm 857 gpm 857 gpm
  • 19. 58.0°F 2571 gpm 44.0°F 2571 gpm 58.0°F Variable Primary design 2571 gpm 44.0°F 44.0°F 44.0°F 58.0°F 58.0°F 58.0°F 857 gpm 857 gpm 857 gpm DP (typical)
  • 20. 56.0°F 1050 gpm 44.0°F 1050 gpm 56.0°F Variable Primary part load 1050 gpm 44.0°F 56.0°F 1050 off off DP (typical) Maximum Flow = 1300 gpm Minimum Flow = 244 gpm Selection Flow = 750 gpm
  • 21. 56.0°F 1050 gpm 44.0°F 1050 gpm 56.0°F Variable Primary part load 1050 gpm 44.0°F 56.0°F 525 525 off DP (typical) Maximum Flow = 1300 gpm Minimum Flow = 244 gpm Selection Flow = 750 gpm 44.0°F 56.0°F
  • 22. 56.0°F 1050 gpm 44.0°F 1050 gpm 51.2°F 857 gpm (each) 664 gpm Primary– Secondary design primary pumps secondary pumps 1714 gpm 44.0°F 44.0°F 51.2°F 51.2°F 857 gpm 857 gpm off 44.0°F
  • 23. Lower Capital Cost Variable Primary advantages • Fewer … – Pumps – Motors – Pump bases – Starters and wiring – Fittings and piping – Controls • Less labor
  • 24. More Available Space Opportunity to … –Add other equipment –Select larger, more efficient chillers –Improve service access
  • 25. Simplified Control • Unfetters chillers from flow-based control • Operates distribution pumps to transport water … not to start/stop chillers
  • 26. Improved Reliability Provides system with … –Fewer pumps and accessories –Fewer chiller recovery options –Fewer pump recovery options –Better balance between pumps and chillers online
  • 27. Chiller Selection Considerations • Evaporator flow limits • Rate-of-change tolerance • Flow “range-ability” –Difference between selection flow rate and evaporator minimum flow limit
  • 28. What are other’s saying??? Variable Primary Flow Chilled Water Plant Design …
  • 29.
  • 30.
  • 31. VFP systems: • Reduces total annual plant energy 3-8% • Reduces first cost 4-8% • Reduces life-cycle cost 3-5%* *Relative to conventional Decoupled chilled-water systems.
  • 32. VPF System More information • “Don’t Ignore Variable Flow,” Waltz, Contracting Business, July 1997 • “Primary-Only vs. Primary-Secondary Variable Flow Systems,” Taylor, ASHRAE Journal, February 2002 • “Comparative Analysis of Variable and Constant Primary-Flow Chilled-Water-Plant Performance,” Bahnfleth and Peyer, HPAC Engineering, April 2001 • “Campus Cooling: Retrofitting Systems,” Kreutzmann, HPAC Engineering, July 2002
  • 33. unsuited for Variable Primary Flow • Inadequate control capability – Insufficient chiller unloading – Vintage chiller controls • Poor financial return (Consider chilled water reset instead)
  • 34. Parallel VPF Systems moving to… Series Evaporator Systems
  • 35. VPF system configurations Series-Counter Flow VFD 41°F 57°F 48.96°F 103.82°F 89.6°F 96.63°F 89.6°F 103.82°F 96.63°F 48.96°F
  • 36. Single Compressor Chiller 103.82° F Lift 62.82° F 41° F 103.82° F Lift 54.86° F 48.96° F Series-Counter flow Arrangement Upstream Chiller 96.63° F Lift 55.63° F 41° F Downstream Chiller • Upstream chiller: 103.82 - 48.96 = 54.86 • Downstream chiller: 96.63 - 41 = 55.63 • Average lift: 55.24 (vs. 62.82 for single compressor (12%)) Better chiller efficiency, but high DP VPF system configurations Series-Counter Flow
  • 38. chiller–tower optimization The Question … • What’s the “right” condenser water temperature?
  • 39. Or Said Another Way … 0 50 100 150 200 250 300 350 400 72 73 74 75 76 77 78 79 80 81 82 83 84 85 Chiller kW Tower kW Total kW Condenser Water Temperature kW
  • 40. chiller–tower optimization How Do You Do It? With real-life controls!
  • 41. • MicroTech II and BAS Combination The optimized method requires auto-adaptive controls. This control logic constantly adjusts the condenser water supply temperature to the value that uses the least amount of power. The controller measures the power requirement for the chiller and cooling tower. The condenser water temperature setpoint then is altered and the power consumption is checked again. If the total power consumption goes down, a similar adjustment is made and the total power is checked again. How do you do it?
  • 42. What’s good for the component … may NOT be good for the system!
  • 43. where’s the meter? The Only Possible Response … On the building!
  • 44. chiller–tower optimization In Summary … • Defines the optimal entering condenser temperature • Optimal control is the right thing to do … AND it saves money • Savings are real and can be quantified • The control strategy is available NOW!
  • 45. First Cost Operating Cost Exploit technology! • Low flow • Low temperature • High efficiency • Controls Leverage: • Optimized Controls • Variable Primary Flow • Series Evaporators Lowest Total Cost of Ownership