2. Mitsubishi Presents the WS Series, Satisfied with
the High Demands of the 21st Century Global Market.
Best-Solution
High-Performance
Various line-up and
high flexibility
One-rank higher
breaking performance
High-Reliability
Customer Friendly
Safety and reliability provided
Easy handling and
retrofitted solution
3. Contents
■
Concept
■
Line up
■
Best Solution
■
High-Performance
High-Reliability
■
Customer Friendly
■
External appearance and
skeleton product structure
■
Product Specification
■
Connections
■
Charging
■
Accessories
For breaker unit
For drawout type
■
Electronic trip relay
Feature
For general use: WS
For generator protection use: WM
For special use: WB
Accessories
Additional functions
Network
Electronic trip relay circuit diagram
Setting procedure
■
Wiring diagram
■
Outline dimensions
Drawout type
Fixed type
Panel-cut,Drawout handle,Terminal adapter
Neutral CT,External ZCT
ETR external units
■
Technical information
■
Ordering information
■
Service network
Line up ( 630 to 6300A )
Rated current (A)
630
1000
1250
1600
2000
2500
3200
AE630-SW AE1000-SW AE1250-SW AE1600-SW AE2000-SWA
SW series
—
4000
5000
6300
—
—
AE2000-SW AE2500-SW AE3200-SW AE4000-SWA
—
SH series
AE4000-SW AE5000-SW AE6300-SW
AE630-SH AE1000-SH AE1250-SH AE1600-SH AE2000-SH AE2500-SH AE3200-SH
—
Note : Please contact us for the details of AE-SH series.
4. Through Flexible and Various Options,
To be Built up the Suitable Functions.
Electronic Trip Relay
Main setting module
1
With interchangeable & add-on modules, flexible functions built up.
WS1
WS2 General use
WS3
WM1
Generator
WM2 protection use
WM3
WB1
WB2 Special use
WB3
LTD+ STD + INST / MCR
LTD+ STD+ INST / MCR
INST / MCR only
Note : *For optimum protective coordination with upstream and/or downstream protective devices such as fuses
and OCRs, WF relay (WF1/WF2/WF3) are provided.
As for the details about WF relay, please make inquiries.
2
Optional setting module
With optional setting modules, GFR, ER etc are added easily.
G1
E1
AP
N5
3
Ground fault
protection (GFR)
Earth leakage (ER)
(1)
Neutral pole (2)
50% protection
2nd Additional Pre-alarm
Note (1) : combination with ZCT
(2) : With "N5" optional module, Neutral pole protection will be changed from 100% (standard) to 50%.
1
Power supply
3
It is neccessary for Display and
LEDs. (see page 19, 20.)
100-240V AC•DC
P2
24-60V DC
P3
100-240V AC / 100-125V DC with output contact
P4
24-60V DC with output contact
P5
2
P1
100-240V DC with output contact (SSR)
Additional function
EX1
Extension module
DP1
Display
TAL
Temperature alarm
The TAL is operated by an
unusual temperature of the
breaker contacts.
Module for display and
communication
Current,Voltage,Power,
Harmonics,Trip current,etc.
Note : The VT unit is required to
display the measured data
except the load current.
MCR-SW
MCR switch
Making current release is
possible with MCR switch.
■ Secure protection by actual effective value detection
For spread of electronic devices such as inverter, the actual effective
value detection method is adopted, which is strong against deformed
waveform and is detected from each phase independently .
Distorted
current
Effective value
conversion
Sin wave
current
5. Network
By using various application software for PLC, users can also connect to the network
SCADA system.
Personal
Computer
MELSECNET/10
Interface card
MELSECNET/10
CC-Link® / PROFIBUS-DP / MODBUS®
Interface
Unit
PLC
I/O Unit
Eco Monitor Pro
ME110NSR
MDU
AE-SW
Note : Some device types are excluded.
Interface unit
CC-Link®
I/O unit
PROFIBUS-DP
MODBUS®(RS-485)
BIF-CON
ON, OFF, Spring charge, Digital input
Option to interface unit
I/O unit enables to turn ON/OFF the breaker
and the spring charge via network.
And by addition of the drawout position
switch, it is possible to transmit the breaker
drawout position.
BIF-CC
BIF-PR
BIF-MD
Display unit for Panel board
Communication items
Current, Voltage, Power, Harmonics, etc
Measurement / alarm
DP2
It has the same function as the breaker
display unit.
In the case where the breaker is installed
in the panel, it becomes possible to view
the measurement information from the
outside of the panel board.
Tripping cause/current
Alarm (PAL,TAL,Self diagnosis)
Breaker ON,OFF
Breaker control
Spring charge
ON/OFF
Note : The VT unit is required to display the measured
data except the load current.
Breaker status
Drawout position
Note : The VT unit is required to display the measured data except the load
current.
VT unit
VT
VT unit enables to measure voltages,
electric powers, harmonics and etc.
Electronic Trip Relay type code
Additional function
Extension module(EX1)
● Main setting module
WS1, WB1, WM1 AE630–1600-SW,
AE2000–3200-SW,
AE4000-SW
WS2, WB2, WM2 AE2000-SWA,
AE4000-SWA,
AE5000-SW
WS3,WB3,WM3 AE6300-SW
WS : General use
WM : Generator protection use
WB : INST/MCR only
● Optional setting module
● Power supply
G1: Ground fault protection
P1: AC•DC100-240V
N5: Neutral pole 50% protection
P2: DC24-60V
E1: Earth leakage protection
P3: AC100-240V / DC100-125V
with output contact
P4: DC24-60V with output contact
AP: 2nd Additional Pre-alarm
NA: Without optional setting
P5: DC100-240V
with output contact (SSR)
Display(DP1)
Display onto panel board(DP2)
VT unit(VT)
Temperature alarm(TAL)
MCR switch(MCR-SW)
Network
BIF-CC
BIF-PR
BIF-MD
6. The safety of valuable circuits can be securely maintained.
Higher short circuit protection performance
by improving breaking capacity
Wider choice coordination range by improving
rated short-time withstand current
In case of 690V AC, Icu = Ics improved
from 50 kA to 65 kA for AE630-SW~AE2000-SWA
from 50 kA to 75 kA for AE2000-SW~AE4000-SWA
from 50 kA to 85 kA for AE4000-SW~AE6300-SW
Icw (1s) improved
from 65 kA to 75 kA for AE2000-SW~AE4000-SWA
from 85 kA to 100 kA for AE4000-SW~AE6300-SW
(Former model)
AE630-SW
(New model)
(AE630-SW~AE2000-SWA)
(Former model)
(New model)
(AE2000-SW~AE4000-SWA)
(Former model)
690V AC
65
AE2000-SWA ~ 500V AC
(Former model)
65
600V AC
(New model)
(AE4000-SW~AE6300-SW)
65
AE1600-SW
AE2000-SW
AE2500-SW
AE3200-SW
AE4000-SWA
690V AC
75
50
75
2s
85
75
3s
65
100
1s
AE4000-SW
AE5000-SW
60
1s
85
690V AC
65
3s
AE2000-SW
AE2500-SW
AE3200-SW
AE4000-SWA
~ 500V AC
(New model)
(AE4000-SW~AE6300-SW)
2s
75
600V AC
(Former model)
1s
AE630-SW
AE1000-SW
AE1250-SW
AE1600-SW
AE2000-SWA
AE1000-SW
AE1250-SW
(New model)
(AE2000-SW~AE4000-SWA)
AE4000-SW
85
600V AC
2s
85
3s
AE5000-SW
AE6300-SW
85
AE6300-SW
~ 500V AC
130
0
20
40
60
80
100
120
140
(kA)
Icu=Ics
0
20
40
60
100
(kA)
Icw
80
Higher safety by improving insulation
performance
Rated impulse withstand voltage (Uimp) for the main circuit is improved
from 8 kV to 12 kV.
(New model)
(Former model)
Higher reliability by High operating durability
■ Mechanical
■ Electrical
The new models are sharply improved in mechanical durability
compared to the former model.
✽ V2:High durability models
Former model
New model
10000
25000
AE630-SW AE1000-SW
AE1250-SW AE1600-SW
25000
AE2000-SWA
10000
2000
0
10000
5000
5000
8000
1500 (3200A: 1000)
AE2000-SW AE2500-SW
AE3200-SW
AE4000-SWA
500
0
(3-Pole)
10000
15000
20000
25000
(times)
12000
AE2000-SWA
20000
5000
AE4000-SWA
Former model
New model (V2)
AE630-SW AE1000-SW
AE1250-SW AE1600-SW
20000
AE2000-SW AE2500-SW
AE3200-SW
AE4000-SW AE5000-SW
AE6300-SW
The new models (V2 ✽) are sharply improved in electrical
durability compared to the former model.
6000
5000
2000
4000
6000
8000
10000
12000
(times/500V AC)
7. For convenience
3 sizes
Compact size AE2000-SWA!
■ The compact AE2000-SWA can reduce the panel size.
Size1
AE630 AE1000 AE1250 AE1600 AE2000
-SW
-SW
-SW
-SW
-SWA
Volume and weight
Size2
AE2000 AE2500 AE3200 AE4000
-SW
-SW
-SW
-SWA
Size3
AE4000 AE5000 AE6300
-SW
-SW
-SW
AE2000-SS
(Former)
The former model (AE-SS) can be retrofitted.
■ It is same as the former model (AE-SS) in installation
AE2000-SWA
(New)
Bus bar
Interchangeable
dimension and outline dimension, and the former model can
be replaced with the new one.
■ ACB main body with drawout frame can be replaced.
■ It can be installed to the existing connection bus bar without
any special connection kit.
(Except AE2000-SWA, AE4000-SWA)
Former model
New model
Zero arc space
Reverse connection available
Arc exhaust to the outside of the breaker is drastically reduced
for safer operation.
(AE630-SW~AE4000-SWA models ≤ 600V AC)
(refer to page 54 : Insulation distance)
Line and Load is not defined on the Main circuit terminals.
Therefore, reverse connection is available without any
limitation.
8. Fixed type
AE-SW Series
1 Arc extinguishing chamber
2
2 Control circuit terminal block
1
3 Electronic trip relay
3
4 OFF button
9
5 ON button
4
5
6 Padlock hook
6
7 Charging indicator
8
8 ON/OFF indicator
7
9 Manual reset button(Optional)
AE1600-SW 3P
In case of the fixed type,Lifting hooks (HP) are attached.
Drawout type
AE-SW Series
2
1
1 Cradle
3
2 Control circuit terminal block
3 Lifting hole
4 Charging handle
5 Drawout position indicator
4
6 Extension rail
7 Position lock
6
7
8 Aperture for the drawout handle
9 Drawout handle
8
5
9
AE1600-SW 3P
In case of the drawout type, Drawout handle is attached.
9. Skeleton
8
10
9
3
4
5
6
7
30
31
28
26
27
24
25
2
1
12
29
11
13
14
15
16
1 Air circuit breaker
21
18
20
12 Dust cover (DUC)
22 Counter (CNT)
2 Cradle
17
13 Push button cover (BC-L)
23 Cylinder lock (CYL)
3 CC-Link® Interface unit
14 Auxiliary switch
24 Door interlock (DI)
4 PROFIBUS-DP Interface unit
22
5 MODBUS® Interface unit
23
standard (AX)
25 Mechanical interlock (MI)
15 Auxiliary switch
26 Safety shutters (SST)
high capacity type (HAX)
6 I/O unit
27 Safety shutter lock ( SST-LOCK)
7 Extension module
17 Closing coil (CC)
28 Cell switch (CL)
8 ETR unit
18 Under voltage trip device (UVT)
29 Interphase Barrier (BA)
9 Main setting module
19 UVT-controller (U-CON)
30 Horizontal terminal
10 Optional setting module
20 Condenser trip device (COT)
31 Vertical terminal
11 Door frame (DF)
19
16 Shunt trip device (SHT)
21 Motor charging device (MD)
Product introduction
1
2
Type
3
Standard
4
Connection
AE630-SW
AE1000-SW
AE1250-SW
AE1600-SW
AE2000-SWA
AE2000-SW
AE2500-SW
AE3200-SW
AE4000-SWA
AE4000-SW
AE5000-SW
AE6300-SW
IEC 60947-2
EN 60947-2(CE)
VDE
JIS C 8201-2-1
GB 14048.2(CCC)
(Shipping Approvals)
LR
GL
BV
DNV
ABS
CCS
NK
Drawout type
Horizontal terminal
Vertical terminal
Front terminal
6
7
8
Mechanical
accessories
Push button cover
Counter
Cylinder lock
Terminal cover
Electronic
trip relay
General use
WS type
Generator protection use
WM type
Door frame
Dust cover
Interphase barrier
Mechanical interlock
Door interlock
Special use
WB type
Optional
G1:Ground fault protection
E1:Earth leakage protection
AP:2nd Additional Pre-alarm
N5:Neutral pole 50% protection
5
Drawout type
accessories
Cell switch
Shorting b-contact
Lifting hooks
Safety shutter
Safety shutter lock
Mis-insertion preventor
Test jumper
Fixed type
9
Relay
accessories
Extension module
Display
Temperature alarm
MCR switch
Neutral CT
External ZCT
VT unit
Network
CC-Link® Interface unit
PROFIBUS-DP Interface unit
MODBUS® Interface unit
I/O unit
Electrical
accessories
Auxiliary switch
Motor charging device
Closing coil
Shunt trip device
Under voltage trip device
Condenser trip device
10. ●
Specification
Type
AE630-SW
AE1000-SW
AE1250-SW
AE1600-SW
630
1000
1250
1600
(A)
Frame size
Rated insulation voltage (Ui)
(AC.V)
1000
Rated operational voltage (Ue)
(AC.V)
690
(kV)
12
Rated impulse withstand voltage (Uimp)
Pollution degree
3
Number of poles
3, 4
Rated current In (CT rating)
630
(
General use
Current rating adjustable
0.5 to 1.0 × In 0.05 step
Generator protection use
(Current rating fixed)
Rated current of neutral pole
500-550-600-650700-750-800-850900-950-1000
160 ≤ Ir ≤ 630
)
Current setting Ir (A) (40˚C)
1000
315-346.5-378-409.5441-472.5-504-535.5567-598.5-630 (Note 5)
400 ≤ Ir ≤ 1000
800 ≤ Ir ≤ 1250
1000 ≤ Ir ≤ 1600
630
1000
1250
1600
(A)
1250
690V AC
Ultimate breaking capacity
Icu (kA rms)
65
600V AC
65
240-500V AC
65
690V AC
IEC60947-2
EN60947-2
BS
VDE
JIS C 8201-2-1
65
600V AC
65
with MCR
240-500V AC
65
690V AC
25 (Note1)
without
Instantaneous
25 (Note1)
500V AC
Rated service breaking capacity Ics (kA rms) %Icu
100%
690V AC
143
600V AC
143
240-500V AC
143
690V AC
143
600V AC
143
Rated making capacity
Icm (kA peak)
with MCR
240-500V AC
143
690V AC
52.5
500V AC
1s
52.5
2s
60
without
Instantaneous
Rated short time
withstand current
Icw (kA rms)
65
3s
50
Maximum total breaking time
(ms)
Maximum closing time
Number of operating
cycles
(Note 2)
Connecting terminal
1600
625-687.5-750-812.5800-880-960-1040875-937.5-1000-1062.5- 1120-1200-1280-13601125-1187.5-1250
1440-1520-1600
40 (Note 6)
(ms)
80
AC500V In
5000
AC690V In
With rated
current
5000
Without rated current
25000 (Note 4)
Horizontal terminal
Vertical terminal
Front terminal
Outline dimension (mm)
H×W×D
3-pole
410×340×290
4-pole
Fixed type
410×425×290
3-pole
430×300×368
4-pole
Drawout type
430×385×368
3-pole
40
41
42
4-pole
50
51
52
Drawout type
3-pole
63
64
65
(including cradle)
4-pole
77
78
79
Cradle only
Weight (kg)
(without Accessory)
3-pole
Fixed type
26
4-pole
Marine approval
30
(LR, GL, BV, DNV, ABS, NK, CCS)
3-pole
(Note 1) The columns for “without instantaneous” are the values when the bare main body and the external relay is combined.
(Note 2) The number of operating cycles without rated current also include the number of operating cycles with rated current.
(Note 3) AE2000-SWA, AE4000-SWA and AE4000-SW~AE6300-SW apply for only vertical terminal of connecting terminal.
(Note 4) This value is max. operating cycle for just ACB body not including any accessories.
(The max. operating cycles for the accessories like AX, MD,CC, SHT and UVT are half of this value.)
(Note 5) Products with low rating types is available.
AE 630-SW
3 kinds of products with low rating types is available.
250-275-300-325-350-375-400-425-450-475-500(CT 500A)
• 157.5-173.3-189-204.8-220.5-236.3-252-267.8-283.5-299.3-315(CT 315A)
• 125-137.5-150-162.5-175-187.5-200-212.5-225-237.5-250(CT 250A)
•
AE 2000-SW
2 kinds of products with low rating types is available.
800-880-960-1040-1120-1200-1280-1360-1440-1520-1600(CT 1600A)
• 625-687.5-750-812.5-875-937.5-1000-1062.5-1125-1187.5-1250(CT 1250A)
•
11. AE2000-SWA
AE2000-SW
AE2500-SW
AE3200-SW
AE4000-SWA
AE4000-SW
AE5000-SW
AE6300-SW
2000
2000
2500
3200
4000
4000
5000
6300
1000
1000
690
690
12
12
3
2000
2000
3
3, 4
3, 4 (HN, FN) (Note7)
2500
3200
4000
4000
1000-1100-1200-1300- 1000-1100-1200-1300- 1250-1375-1500-1625- 1600-1760-1920-2080- 2000-2200-2400-26001400-1500-1600-1700- 1400-1500-1600-1700- 1750-1875-2000-2125- 2240-2400-2560-2720- 2800-3000-3200-34001800-1900-2000
2250-2375-2500
1800-1900-2000 (Note 5)
2880-3040-3200
3600-3800-4000
800 ≤ Ir ≤ 2000
1600 ≤ Ir ≤ 2500
2000
2000
2000 ≤ Ir ≤ 3200
2500 ≤ Ir ≤ 4000
3200
1250 ≤ Ir ≤ 2000
4000
2500
5000
2500 ≤ Ir ≤ 4000
3150 ≤ Ir ≤ 5000
85
75
85
85
130 (Note9)
75
85
75
85
75
100
45 (Note1)
65 (Note1)
45 (Note1)
65 (Note1)
100%
100%
165
187
165
187
187
286
165
187
165
187
165
220
94.5
143
94.5
143
75
100
75
85
65
85
40 (Note 6)
50 (Note 6)
80
1500
1500
4000 ≤ Ir ≤ 6300
2000 (4000) (Note8) 2500 (5000) (Note8) 3150 (6300) (Note8)
75
1500
6300
2000-2200-2400-2600- 2500-2750-3000-3250- 3150-3465-3780-40952800-3000-3200-3400- 3500-3750-4000-4250- 4410-4725-5040-53553600-3800-4000
4500-4750-5000
5670-5985-6300
1500
80
1000
500
1000
1000
500
1000
20000 (Note 4)
10000 (3P) / 5000 (4P)
-
-
-
(Note 3)
(Note 3)
(Note 3)
-
-
-
410×475×290
414×873×290
410×605×290
414×1003(1133)×290 (Note 8)
430×435×368
430×439×368
480×875×368
430×565×368
430×569×368
480×1005(1135)×368 (Note 8)
47
60
61
63
81
160
160
160
57
72
73
75
99
180 (200) (Note8)
180 (200) (Note8)
180 (200) (Note8)
70
92
93
95
108
233
233
240
84
113
114
116
136
256 (279) (Note8)
256 (279) (Note8)
263 (286) (Note8)
31
35
36
49
118
118
125
35
43
44
61
133 (148) (Note8)
133 (148) (Note8)
140 (155) (Note8)
(LR, GL, BV, DNV, ABS, NK, CCS)
(Note 6) This value means the instantaneous breaking time at shortcircuit interruption.
As for accessories (SHT, UVT), refer to page 13 and 14.
(Note 7) 4(HN) means the neutral poles current capacity is 50% of the rated current, for 4 poles.
4(FN) means the neutral poles current capacity is 100% of the rated current, for 4 poles.
(Note 8) ( ) shows the value for 4P FN type.
(Note 9) Marine approval value is 138kA.
(NK), available soon (LR, GL, BV, ABS)
(Remark) All models conform the isolating function according to IEC 60947-2.
Reverse connection is possible.
12. Over view (AE630~1600-SW, AE2000~3200-SW)
Type
Horizontal
Standard
Vertical
(VT)
Front
(FT)
Vertical terminal
adapter
(VTA)
Front terminal
adapter
(FTA)
FIX-VTA
Connections
FIX-FTA
DR-VTA
DR-FTA
Fixed type (FIX)
Drawout type (DR)
DR-VT
DR-FT
● Connection image : AE630~1600-SW, 3-pole type
Over view (AE2000-SWA, AE4000-SWA, AE4000~6300-SW)
Connections
Vertical
(VT)
Type
Standard
Fixed type (FIX)
FIX-VT
Drawout type (DR)
DR-VT
● Connection image : AE2000-SWA, 3-pole
type
● For AE2000-SWA, AE4000-SWA, AE4000SW, AE5000-SW and AE6300-SW models,
vertical terminal only is available.
Available connections
Breakers
Connections
Horizontal
Fixed type
(FIX)
FIX-VT
FIX-VTA
FIX-FTA
Horizontal
DR-VT
Drawout type
DR-FT
(DR)
DR-VTA
DR-FTA
AE630-SW
AE1000-SW AE1250-SW AE1600-SW AE2000-SWA AE2000-SW AE2500-SW AE3200-SW AE4000-SWA AE4000-SW AE5000-SW AE6300-SW
13. Manual charging
The closing spring is charged by the manual charging handle. The breaker is closed
when the ON button is pressed, and opened when the OFF button is pressed.
● When the closing spring is completely charged, the charging indicator will show
"CHARGED".
● The indicator shows the ON or OFF state of the main contacts.
● The breaker cannot be closed while the OFF button is being pressed. (Safety feature)
● OFF lock is available by padlock (See P7, P17) as standard.
Motor charging device (MD)
The closing spring is charged by an electric motor. When the breaker is closed, the
spring is charged automatically (ON-charge method.) The closing coil (CC) is required
to remotely close, and the shunt trip device is required to remotely open the breaker.
1
● Manual charging operation is also possible.
● Pumping prevention is assured both electrically and mechanically.
● As the charging completion contact is separate from the electrical charging circuit, its
function in the control scheme can be arranged as desired.
Charged
signal
Charging completion
switch
413
414
Charging limit
switch
U1
Control
supply
z
M
U2
Motor
Control
relay
Motor charging circuit
Breaker
OFF charging method
Polarity of DC circuit use
U1
+
U2
–
Axb
Control
supply
OFF charging method is also available.
The closing spring is charged
automatically when the breaker is
opened. This is available only by
externally connecting b contact (AXb) of
the auxiliary switch to the motor
charging circuit in series.
In case of DC power supply, please use
high capacity auxiliary switch (HAX).
U1
U2
Please inquire as to further details of 24V DC and 48V DC.
Motor charging rating
Inrush
Applicable Applied
Rated
Steady
voltage (V) voltage voltage (V) current(Peak current (A)
value) (A)
range (V)
DC24
DC48
AC/DC
100-125
AC/DC
200-250
18 ~ 26.4
36 ~ 52.8
85 ~ 137.5
170 ~ 275
24
48
100
125
200
250
22
14
10(10)
12(12)
5(7)
6(8)
6
3
3(4)
3(4)
1(2)
1(2)
Charging
time (s)
Criterion for
power
requirement
(VA)
500
≤5
700
1000
700
1000
Values in parentheses show values for AE4000-SWA 4 pole and AE4000-SW ~
AE6300-SW.
We cannot manufacture AE4000-SWA 4 pole and AE4000-SW ~ AE6300-SW in DC
24V and DC 48V rating.
14. 2
3
6
5
4
4
7
1
9
8
Closing coil (CC)
2
The closing coil is a device to close the breaker by remote control.
● An interlock to prevent pumping is provided electrically.
Rated voltage
(Applicable voltage range)
Operating voltage • Operating inrush current (VA)
AC
–
DC24-48V
(18~52.8)
AC • DC common
100-250V
(75-275)
DC
CC circuit diagram
Closing
time (Note1)
DC24V 3.0A (100W)
–
Breaker
Min. 80ms
CC unit
A1
DC48V 6.0A (200W)
AC100V
0.7A (100VA)
1.7A (200VA)
0.08 s
or less
One-pulse
circuit
A2
DC100V 0.8A (100W)
AC250V
CC
Control
supply
DC250V 1.8A (250W)
N o t e 1 ) In case of double rating of rated voltage, it is the value for the lower rating.
Diode rectifier is not used for control source 24~48V DC.
(Example) In case of DC24 to 48, it is operating time for DC24V.
● Closing time means time from the initial energization of the closing coil up to the complete closing of the main contacts.
● As CC is one-pulse driven, it is not necessary to insert AXb for burning prevention purposes. Inserting AXb will cause
anti-pumping function to be ineffective.
Shunt trip device (SHT)
3
The shunt trip device is a device to open the breaker by remote control. A cut-off switch is included.
SHT circuit diagram
Operating voltage • Operating inrush current (VA) Operating
Rated voltage
time (Note1)
(Applicable voltage range)
DC
AC
DC24-48V
(16.8~52.8)
–
–
AC100V 0.4A (100VA)
DC100V 0.6A (100W)
AC250V 1.4A (150VA)
DC250V 1.6A (200W)
AC380~500V
(266~550)
AC380V 0.5A (250VA)
AC500V 0.7A (300VA)
Cut-off switch
SHT unit
C1
DC48V 6.0A (200W)
AC • DC common
100-250V(70-275)
Breaker
Min. 40ms
DC24V 2.5A (100W)
-
0.04 s
or less
N o t e 1 ) In case of double rating of rated voltage, it is the value for the lower rating.
(Example) In case of DC24 to 48V, it is operating time for DC24V.
N o t e 2 ) Operating time for AE4000-SW~AE6300-SW is 0.05s or less.
Control
supply
C2
SHT
Diode rectifier is not used for control source 24~48V DC.
15. Under voltage trip device (UVT)
4
This is the device that automatically trips the breaker when the circuit voltage drops below the
nominal voltage, and comprises UVT coil and UVT controller. There are 3 kinds of tripping time,
INST, 0.5s and 3.0s.
Rated voltage
Frequency
operating time
(time delay)
Pick-up
voltage
AC100-120V
Drop-out
voltage
65~85V
DC24V
DC48V
-
UVT circuit diagram
D1
90~140V
DC100-110V
65~85V
D2
78~102V
UVT
coil
Trip button
DT1
20VA
DT2
max.2m
Breaker
45~70V
DC120-125V
UVT
controller
~
Inst(0.2s) 247~323V 171~266V With open
circuit of
0.5s(Min.) 15.6~20.4V 10.8~16.8V DT1,DT2
3.0s(Min.) 31.2~40.8V 21.6~33.6V terminals.
AC380-460V
Power
consumption
45~70V
130~170V
50/60Hz
AC200-240V
Trip function
54~84V
UVT circuit diagram (In case of AC380~460V)
IN1
Note1) In case of 380-460V AC, the external unit is attached additionally.
Note2) The operating time is a guarantee value when it drops from 85% or more of rated voltage.
IN2
Note3) Time delay should be allowed for 1.5s between applying the voltage to the UVT and
closing the breaker.
OUT3
D1
External unit
(attached to
UVT controller)
~
OUT4
UVT
controller
D2
UVT
coil
Trip button
Note4) If a remote trip function is required, remove the shorting bar (DT1 DT2) and connect a
normally closed switch, rated 0.5A at 150VDC across them.
DT1
min.
0.2s
max.2m
DT2
Note5) Usage ambient temperature should be in the range from max. 40°C to min. -5°C.
Breaker
OCR alarm (AL) [ Automatic reset type (30ms) ]
Short-time operation
5
OCR alarm (AL) is provided as standard if ETR is equipped. OCR alarm (AL) is the contact (1a) of
short-time operation (30ms), being output when the breaker is tripped by the electronic trip relay.
Two types of automatic reset type (standard) and manual reset type (optional) are available. When
ordering, specify either automatic reset or Manual reset.
Switch rating
Current (A)
Voltage (V)
3
2
125
5
3
240
0.2
0.2
125
0.4
0.4
30
DC
Inductive load
240
AC
Resistive load
4
3
97
OCR alarm
switch
98
Note1) Though the control power supply is unnecessary to activate OCR
alarm (AL), the self-holding circuit is necessary since the contact
output is activated for the short time (30ms).
Note2) This works when tripping occurs in LTD, STD, INST, GFR or ER.
Note3) If any continuous output of OCR alarm (AL) is necessary, use the
trip indicator (TI) output contact of the electronic trip relay.
OCR alarm (AL) [MRE : Manual reset type]
On the manual reset type (optional), the gray manual reset button on the front side of the breaker
will stick out to continuously output OCR alarm (AL) if the breaker is tripped by the electronic trip
relay. After tripping, the breaker can not be turned on unless the manual reset button is pressed for
resetting.
Auxiliary switch
Standard (AX) • High capacity type (HAX)
6
This is the contact that remotely indicates the ON or OFF status of the breaker.
Switch rating
Current (A)
Voltage (V)
Standard (AX)
High capacity type (HAX)
Resistive load
Inductive load
2
5
10
10
10
10
10
0.3
3
1.5
125
0.6
0.6
10
6
30
10
6
10
b-contact (NC)
OFF
ON
10
0.3
a-contact (NO)
ON
OFF
10
10
Breaker state
ON
OFF
2.5
250
250
DC
Resistive load
5
125
AC
Inductive load
460
Change-over
sequence
10
Maximum contacts
5a5b
5a5b
● The a and b conacts may turn simultaneously to ON instantaneously at the time of changing the contact;
Pay attention to the contact state when designing circuits.
● The chattering time at the time of contact ON-OFF is below 0.025 s.
● For special environment specification, the contact capacity gets deteriorated.
Make inquiries for more details.
16. Push button cover (BC-L)
7
The cover prevents careless manual operation (ON,OFF) of the push buttons.
BC-L can be locked by a padlock (The padlock should be supplied by the customer.)
For the suitable size of a padlock, refer to Page 17.
Cylinder lock(CYL)
8
The breaker is locked OFF with the cylinder lock.
● Since it is an interlock which only allows the key to be removed when the breaker is locked off, it can be used
for interlocking two or more breakers.
Counter(CNT)
9
The open/close operations of the breaker are shown by a 5 digit counter.
Door frame(DF)
The door frame improves the appearance, after cutting out the panel door to install the breaker.
As for panel cut-out dimensions, refer to page 49.
Door interlock(DI)
The panel door cannot be opened unless the breaker is open position.
● A wire type mechanical interlock allows flexibility in positioning breakers in the switchboard.
● The parts of the Door panel should be supplied by the customer.
● DI can not be installed by combining with "Mechanical interlock(MI)for 3 breakers."
Interphase Barrier(BA)
This enhances the interphase insulation between the terminal portions of the breaker, and prevents
short-circuit due to conductive inclusion or dust. It can be attached and detached easily. As for its
availability, refer to the following table.
Type
Connections
Horizontal (FIX)
Vertical terminal (FIX-VT)
Vertical terminal adaptor (VTA)
Front terminal adaptor (FIX-FTA)
Horizontal (DR)
Vertical terminal (DR-VT)
Drawout type
Front terminal (DR-FT)
(DR)
Vertical terminal adaptor (VTA)
Front terminal adaptor (DR-FTA)
Fixed type
(FIX)
● Available for the insulation
AE630-SW~
AE2000-SW~
AE4000-SW~
AE4000-SWA
AE2000-SWA
AE1600-SW
AE3200-SW
AE6300-SW
●
●
▲
–
▲
▲
▲
▲
▲
●
●
▲
▲
●
▲
▲
▲
–
▲
▲
▲
▲
▲ Available for separating terminals
Not existing type
– Attachment is impossible
Terminal Cover(TTC)
The transparent terminal cover prevents from careless touching to the live control terminals.
Protection degree is IP20.
17. Mechanical interlock (MI)
This is the device to prevent parallel charge of 2 or 3 units of breakers, and it can interlock the
breakers mechanically without fail.
All combinations are available among any models from AE630-SW to AE4000-SWA.
Please make inquiries about installation to AE4000-SW~AE6300-SW.
Further the interlock is possible among the different connection types or poles, such as fixed type or
drawout type, 3 pole or 4 pole.
In combination with electric interlock, the higher safety interlock system can be secured.
● In case of drawout type,the interlock works at "CONNECTED" position, and in another position the
interlock is released, which assures easy maintenance and inspection of the breaker.
● When turning OFF one breaker and then turning ON another breakers, please take an interval 0.5 seconds or
more.
● MI for 3 breakers can not be installed by combining with Door Interlock (DI).
Breaker layout(630AF-4000AF)
Interlock combinations
(mm)
Vertical installation
Case circuit
Switching states (for 2 ACBs)
Type
Horizontal installation
1
3
2
: ACB open
: ACB closed
ACB1
ACB1
ACB2
ACB1
ACB2
ACB3
ACB1
ACB2
ACB3
ACB1
ACB2
ACB3
ACB2
0~12
2 devices : 1 normal power supply and 1 emergency power supply
144
Switching states (for 3 ACBs)
47(Max.)
Type
3
2
4
5
6
7
ACB2
1000(Max.)
ACB3
1000(Max.)
3 devices : 2 sources and 1 coupling
Type
1
2
3
4
ACB1
ACB2
ACB3
1000(Max.)
Breaker
1
ACB1
134
3 devices : 3 sources,only 1 device closed
Type
1
2
3
4
5
ACB1
ACB2
ACB3
3 devices : 2 normal power supplies and 1 emergency power supply
Condenser trip device (COT)
Even if the power supply fails, the breaker can be electrically opened by remote operation
within a definite time. This device is used in combination with the shunt trip device (SHT).
KF-100CD
KF-200CD
AC100/110
Type
Rated input voltage (V)
AC200/220
50-60
Rated frequency (Hz)
Rated charging voltage (V) Note1
140/155
820
Condenser capacity (μF)
70~125%
Voltage range
Power supply capacity (VA)
1 VA max
Charging time (s)
1sec. max
Trip limit time
Note2
Paint color
Withstand voltage (1minute)
Applicable SHT type (Rated voltage)
Note 1: The rated charging voltage is the voltage stored during
condenser saturation. It is continuously supplied by the
rectified voltage of the rated AC input voltage.
Note 2: The trip limit time means the time period in which the shunt trip
device (SHT) can make a tripping operation once, even after
the charged condenser with 100% supply voltage would be
stopped to charge. It can be tripped up to 30 seconds.
Note 3: Usage ambient temperature is in a range of max. 40°C to min.
-20°C.
30 sec.
Transformer (In case of KF-200CD)
Black
AC 2000V
AC . DC 100-250V
AC1
DC+
Open button
R1
C
As for outline dimensions, refer to page 49.
R3
R2
AC2
LED
DC-
C1
SHT
C2
Circuit diagram
Dust cover (DUC)
Dust cover prevents the dust or water entering into the panel board from the breaker panel cut.
Protection degree is IP54.
18. Drawout interlock (standard)
This is the safety device that prevents insertion and drawout operation. When the breaker is ON, the
drawout handle cannot be inserted, and insertion and drawout operation cannot be done unless the
OFF button is pressed.
2
Position lock (standard)
This is the device that locks automatically the drawout mechanism at "TEST" or "CONNECTED"
positions during insertion and drawout operation. When the lock plate is pushed in, lock is released
and operation can be continued.
φ5
Padlock
A padlock can be arranged at the lock plate. Thereby, it is possible to prevent the connection
position from being changed unnecessarily. A padlock of φ5 should to be supplied by customer. As
for outline dimensions of the padlock, please refer to the left figure.
35
(mm)
Outline dimensions
(reference)
Operating position of drawout type
CONNECTED position
● Both main and control circuits
are connected.
● Normal in use condition.
● Lock plate is protruding
TEST position
● Main circuit is disconnected, but
the control circuit is connected.
● The breaker operation can be
tested with the door closed.
● Lock plate is protruding
DISCONNECTED position
DRAWOUT position
● Both main and control circuits
are disconnected.
● This is the position for removing
the breaker.
● The door can be closed.
● The breaker is drawn out of the
cradle on the extension rails.
19. Cell switch (CL)
This is the switch to show the drawout position (CONNECTED, TEST, and DISCONNECTED) of
the breaker. An arbitrary combination up to 4 pieces is available.
Operating sequence
Switch rating
Drawout position
of breaker
Disconnected
DISCON
CL-C
(CONNECTED)
CL-T
(TEST)
CL-D
(DISCONNECTED)
TEST
CONNECT
OFF
ON
2.5
10
10
250
3
1.5
125
10
6
30
10
10
125
ON
DC
OFF
Note 1: The setting is available for change by customer later.
A preliminary setting of CL at factory shipment is as follows.
CL1:1C CL2:1C1D CL3:1C1T1D CL4:2C1T1D
Inductive load
5
250
ON
OFF
Resistive load
460
AC
Change-over sequence
(a-contact)
Switch function
Display position of
drawout operation
Current (A)
Voltage (V)
Connected
Maximum contacts
Total 4c max.
Standard pattern
CL-C
CL-T
CL-D
CL1
1
–
–
CL2
1
–
1
CL3
1
1
1
CL4
2
1
1
Shorting b-contact (SBC)
When moving the breaker from the connected to
the test positions, this contact is used to short
circuit auxiliary switch (AXb) thus maintaining
the correct sequence of operation of the
external control circuit. When ordering, SBC
with the same number of contacts as auxiliary
switches (AXb) will be provided.
Switch rating
Current (A)
Voltage (V)
DC
Inductive load
250
10
2
125
10
3
250
AC
Resistive load
0.2
0.2
125
0.4
0.4
30
4
3
Lifting hook(HP)
This is the metal fitting to suspend the main body when the breaker is removed from the drawout
cradle. The fixed type breaker is equipped with HP as standard.
Safety shutter(SST)
The safety shutters cover the conductors (cradle side) and prevent contact with them when the
breaker is drawn out.
Safety shutter lock(SST-Lock)
This kit is used to lock the safety shutters using 2 padlocks (the padlocks to be customer's supply).
The safety shutters close when the breakers drawn out to prevent accidental contact with the main
contacts.
Mis-insertion preventor(MIP)
This prevents other breakers than specified from inserting into the cradle, and max.5 patterns are
available.
Not available for AE4000-SW~AE6300-SW
Test jumper(TJ)
With the breaker taken out of its cradle, this device enables the breaker to be electrically opened
and closed, and the operating sequence to be checked. 3m length of cable is equipped as standard
shipment.
20. 3
Power supply module
This module provides control source for
DISPLAY module,Trip indicator and several
indicators (LEDs).
(Even when the control power source is off, the
function of over current protection and ground
fault protection are effective.)
There are two types of power supply modules,
one is only of power supply function, the other
is power supply function with output contact (6
contacts).
A
D
B
1
Main setting module
This module provides the function of over
current protection.
It is possible to select the three setting module
according to application. (see page 21-26)
Neutral protection of rated current (100%)
function is standard at 4 pole breaker.
C
F
E
2
Optional setting module (option)
Additional functions and characteristics can be
selected by optional setting modules.
H
G
F
A
Display (option)
F
Several measuring data (current, voltage, power etc) and
alarms can be displayed with this module.
B
This indicator displays the Pre-Alarm situation when exceed
the setting current. When it installed power supply module
with contact, the output contact of Pre Alarm is available.
Extension module (option)
* The output is reset when the electric current goes below the set
level after an alarm is set off.
This module is required when installed VT unit, display
module and each interface unit.
C
Load current LED (standard)
G
RUN LED, ERR. LED (standard)
This indicator displays the ETR situation (Run or Error)
E
Trip indicator LED (standard)
This indicator displays the trip cause.
RESET button (standard)
When push this reset button, trip indicator, and Pre-Alarm
will be reseted. And when the instantaneous test by
MITSUBISHI special tester and push this reset button, as a
result of LTD and STD function become ineffective.
This indicator displays the maximum current of phase.
D
Pre-alarm(PAL) (standard)
H
TEST terminal (standard)
This terminal already installed as standard. This terminal is
used for testing by the field test device (Y-2000). (see page 30)
OCR alarm (AL) (standard)
When it happen to trip by over current, ground fault ( GFR ) and Earth leakage ( ER ), it issue a warning alarm.
Neutral pole overcurrent protection (NP) (standard)
When harmonics in load current are large, the current on neutral pole exceeding rated current may flow. Harmonics may cause
some troubles. Neutral pole overcurrent protection prevents them by operating at 100% of rated current on neutral pole.
MCR:Making current release (option)
Just under the breaker closing operation ( from open to close ), Instantaneous characteristic become effective, but after closing
the breaker, instantaneous characteristic become ineffective.
When you order the MCR switch, MCR switch is built in the main body.
If MCR switch is built in the main body and the adjust dial of INST/MCR on main setting module is set the MCR position,MCR
function become effective.
TAL (option)
When the temperature of main contacts exceed normal temperature level, temperature alarm is indicated at LED ( on main
setting module ) and output by contact ( only installed power supply with output contact ).
If TAL is installed in the breaker according your order, Temperature alarm ( LED ) function become effective.
When the temperature goes down within normal tempter level, the temperature alarm will be reset.
NCT (option)
Neutral CT is required for Ground fault or Neutral pole protection, when 3 pole breaker is used for 3 phase 4 wires system.
ZCT (option)
ZCT is required for a few amperes earth leakage protection, and is combining ER plug. (see page 28)
21. Characteristic table
NA
G1
E1
AP
N5
Nothing
Ground fault
Earth leakage
2nd additional Pre-alarm
Neutral pole
50% protection
2
1
WS
General use
LTD+STD+
INST/MCR
WM
Generator protection use
LTD+STD+
INST/MCR
WB
Special use
INST/MCR
Power supply module
Type
100-240V
P1
3
Contact capacity(Type code P3, P4)
Rating
alarm output
Current (A)
Resistive load
Inductive load
cosφ=1.0
Nothing
AC•DC
cosφ=0.4
L/R=7ms
240
1
0.5
120
1
1
125
0.1
0.05
30
1
1
Voltage(V)
P2
24-60V DC
Nothing
P3
100-240V AC
100-125V DC
6 output contacts
P4
24-60V DC
6 output contacts
P5
100-240V DC
6 output contacts (SSR)
AC
DC
Note1: Over current protection and ground fault protection operates without control power source.
Note2: Factory setting of 6 output contacts is as follows.
➀
➁
➂
➃
➄
➅
LTD
G1/E1/AP
to
Self-holding Self-holding Refer table
lower
ETR dial set
TRIP side
STD/INST
G1
E1
PAL
Automatic
reset
AP
Self-holding Self-holding
ALARM side Automatic
reset
Automatic
reset
—
Automatic
reset
TAL
Automatic
reset
ERR
Automatic
reset
Current capacity(Type code P5)
AC
Self-holding:
The output is maintained until it resets.
Automatic reset:
The output will be reset if it backs to
normal condition.
Normal
current
Peak inrush
current
ON resistance
(max.)
240
0.1A
0.3A
5Ω
120
0.1A
0.3A
5Ω
240
0.1A
0.3A
5Ω
30
0.1A
0.3A
5Ω
Voltage(V)
DC
CT rating table
AE630-SW
630A
AE1000-SW AE1250-SW AE1600-SW AE2000-SWA
1000A
1250A
1600A
2000A
AE2000-SW AE2500-SW AE3200-SW AE4000-SWA
250A
315A
500A
1250A
1600A
2000A
2500A
3200A
Note1: AE630-SW and AE2000-SW has low rating type.
Please refer to the “Ordering information sheet.” (Page 57-59)
Note2: Low rating type of AE630-SW is not available for the ground fault protection.
Note3: As for details of ratings, refer to page 9 and page 10.
4000A
AE4000-SW AE5000-SW AE6300-SW
4000A
5000A
6300A
Electronic trip relay(ETR) type code
Additional function
Extension module(EX1)
● Main setting module
● Optional setting module
WS1, WB1, WM1 AE630–1600-SW,
AE2000–3200-SW,
AE4000-SW
WS2, WB2, WM2 AE2000-SWA,
AE4000-SWA,
AE5000-SW
WS3,WB3,WM3 AE6300-SW
WS : General use
WM : Generator protection use
WB : INST/MCR only
● Power supply
G1: Ground fault protection
P1: AC DC100-240V
N5: Neutral pole 50% protection
P2: DC24-60V
E1: Earth leakage protection
P3: AC100-240V / DC100-125V
with output contact
P4: DC24-60V with output contact
AP: 2nd Additional Pre-alarm
NA: Without optional setting
•
P5: DC100-240V
with output contact (SSR)
Display(DP1)
Display onto panel board(DP2)
VT unit(VT)
Temperature alarm(TAL)
MCR switch(MCR-SW)
Network
BIF-CC
BIF-PR
BIF-MD
22. A Trip indicator LED
B Pre-alarm LED
C Temperature alarm LED
D Load current LED
E RUN LED
F ERR. LED
G
G Current setting dial
L
H Uninterrupted current setting dial
D
I LTD time setting dial
H
I
E
J STD pick-up setting dial
K STD time setting dial
L INST/MCR pick-up current setting dial
F
J
M Optional setting module (P.27~29)
B
N Pre-alarm current setting dial
O RESET button (TEST L/S LOCK button)
K
A
P TEST terminal
C
M
Note: The figure shown WS type with G1 plug.
G1 is option.
O
Relation of setting dial
P
In (CT rating)
Ir
Iu
Ip
Ig (P.27)
Isd
Ip2 (P.29)
Ii
Load current LED
N
(60, 80, 100%, OVER)
Adjustable setting range
No. Setting item
Accuracy
1.05 x Iu…Non Pick-up
1.25 x Iu…Pick-up
Ir
0.5 ~ 1.0 (0.05step) x In (CT rating)
H
Uninterrupted
current
Iu
0.8 ~ 1.0 x Ir (0.02step), Pick-up current : 1.15 x Iu
I
LTD time
TL
12–25–50–100–150s
J
STD pick-up
current
Isd
1.5–2–2.5–3–4–5–6–7–8–9–10 x Ir
K
STD time
Tsd
at Iu x 2
0.5–0.4–0.3–0.2–0.1–0.06–0.06–0.1–0.2–0.3–0.4–0.5s
(I2t ON)
(I2t OFF)
at Isd x 1.5
AE630-SW~AE1600-SW
AE2000-SW~AE3200-SW 16-12-10-8-6-4-2-2-4-6-8-10-12-16 x Ir
(INST)
(MCR)
WS1
AE4000-SW
L
INST/MCR
pick-up current
Ii
AE2000-SWA, AE4000-SWA
AE5000-SW
AE6300-SW
12-10-8-6-4-2-2-4-6-8-10-12 x Ir
(INST)
(MCR)
1.0
150
± 15%
Current setting
1.0
± 20%
G
Factory default
value
—
Adjustable setting range
Mark
10
± 20%
It operates in the
range between 0.04
and 0.08s when the
time set at 0.06s.
0.5 (I2t ON)
WS1…16 (INST)
± 15%
10-8-6-4-2-2-4-6-8-10 x Ir
(INST)
(MCR)
WS2…12 (INST)
WS2
WS3…10 (INST)
WS3
N
Pre-alarm current
Ip
Iu x 0.68 ~ 1.0 (0.04step) –OVER
± 10%
OVER
—
Pre-alarm time
Tp
1/2 TL at Iu x 2 (after 1/2 TL, PAL contact output turns on.)
± 20%
—
Upper figure and table denote the case optional MCR function is included.
23. ■Operating characteristic curve (for general use : WS)
5000
(h)
4000
1
3000
40
2000
30
20
1000
PAL current : Ip
Iu x 0.68~1.0(0.04step)-OVER ±10%
15
10
Uninterrupted current : Iu
0.8~1.0 x Ir(0.02step)
…
LTD Pick-up 1.05 x Iu…Non pick-up
1.25 x Iu Pick-up
500
400
300
8
(min)
6
4
200
2
LTD time : TL
12-25-50-100-150(s) ±20%
(at Iu x 2)
100
60
1
50
50
40
40
30
30
operating time (s)
20
20
PAL time : Tp
TL/2 ±20%(at Iu x 2)
10
10
STD pick-up current : Isd
Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ±15%
5
5
4
4
3
3
2
2
(s)
With MCR
1
1
STD time : Tsd
Note1
0.06-0.1-0.2-0.3-0.4-0.5(s) ±20%
(at Isd x 1.5)
.5
.4
.5
.4
.3
.3
.2
.2
.1
.1
LTD Pick-up, Ip…% of Uninterrupted current Iu
Current
.04
I2t ON
(ramp)
Iu, Isd, Ii………% of Current setting Ir
.05
I2t OFF
.05
.04
.03
.03
.02
INST/MCR pick-up current : Ii
Ir x 2-4-6-8-10-12-16 ±15% WS1
Ir x 2-4-6-8-10-12 ±15% WS2
Ir x 2-4-6-8-10 ±15% WS3
Note1 When Tsd="0.06"setting,operating time is 0.04~0.08s.
I2t is selectable ON or OFF.
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
.02
.01
1
2
5
10
20
50
100 125 150 200
500
1000
1600 2000
5000
current (%)
Note :
The slope of LTD curve can be changed easily in case a relay for protective coordination (WF relay) is used instead of WS relay.
As for the details about WF relay, please make inquiries.
.01
10000
24. A Trip indicator LED
B Pre-alarm LED
C Temperature alarm LED
D Load current LED
E RUN LED
F ERR. LED
K
G LTD pick-up current
D
H LTD time setting dial
I STD pick-up setting dial
E
J STD time setting dial
G
K INST/MCR pick-up current setting dial
F
L Optional setting module (P.27~29)
H
M Pre-alarm current setting dial
I
B
N RESET button (TEST L/S LOCK button)
O TEST terminal
A
J
Note: The figure shown WM1 type with G1 plug and Display (DP1).
G1 and DP1 are options.
C
L
Relation of setting dial
N
IL
Ip
Isd
Ip2 (P.29)
Ii
O
Ir (Fixed)
Ig (P.27)
In (CT rating)
Load current LED
(40, 60, 80, 100%)
M
Adjustable setting range
No. Setting item
Mark
Accuracy
0.63 ~ 1.0 x In (Adjust by factory : Fixed)
G
LTD pick-up
current
IL
1.0–1.05–1.1–1.15–1.2 x Ir
H
LTD time
TL
15–20–25–30–40–60s
I
STD pick-up
current
Isd
1.5–2–2.5–3–3.5–4–4.5–5 x Ir
J
STD time
Tsd
at IL x 1.2
0.5–0.4–0.3–0.2–0.1–0.06–0.06–0.1–0.2–0.3–0.4–0.5s
(I2t ON)
(I2t OFF)
at Isd x 1.5
AE630-SW~AE1600-SW
AE2000-SW~AE3200-SW 16-12-10-8-6-4-2-2-4-6-8-10-12-16 x Ir
(INST)
(MCR)
WM1
AE4000-SW
K
INST/MCR
pick-up current
Ii
AE2000-SWA, AE4000-SWA
AE5000-SW
12-10-8-6-4-2-2-4-6-8-10-12 x Ir
AE6300-SW
(INST)
(MCR)
20
± 15%
Ir
1.15
± 20%
Current setting
Comply with
ordering sheet
± 5%
—
Factory default
value
—
Adjustable setting range
5
± 20%
It operates in the
range between 0.04
and 0.08s when the
time set at 0.06s.
0.5 (I2t ON)
WM1…16 (INST)
± 15%
10-8-6-4-2-2-4-6-8-10 x Ir
(INST)
(MCR)
WM2…12 (INST)
WM2
WM3…10 (INST)
WM3
M
Pre-alarm current
Ip
IL x 0.68 ~ 1.0 (0.04step) –OVER
± 5%
OVER
—
Pre-alarm time
Tp
1/2 TL at IL x 1.2 (after 1/2 TL, PAL contact output turns on.)
± 20%
—
Upper figure and table denote the case optional MCR function is included.
Pre-alarm current “OVER” setting is equal to 1.0.
25. ■Operating characteristic curve (for generator protection use : WM)
5000
(h)
4000
1
3000
40
2000
30
20
Pre-alarm current : Ip
IL x 0.68 ~ 1.0(0.04step) ±10%
0.68 ~ 1.0(0.04step) ±5%
1000
15
10
500
LTD pick-up current : IL
1.0-1.05-1.1-1.15-1.2 ±5%
Factory setting position is 1.15
400
300
8
(min)
6
4
200
2
100
60
LTD time : TL
15-20-25-30-40-60(s) ±20%
(at IL x 1.2)
50
40
1
50
40
30
20
operating time (s)
30
20
Pre-alarm time : Tp
TL/2 ±20%(at IL x 1.2)
10
10
STD pick-up current : Isd
Ir x 1.5-2-2.5-3-3.5-4-4.5-5 ±15%
5
5
4
4
3
3
STD time : Tsd
Note1
0.06-0.1-0.2-0.3-0.4-0.5(s) ±20%
(at Isd x 1.5)
2
2
(s)
With MCR
1
1
.5
.5
.4
.4
.3
.3
.2
.2
.1
.1
I2t ON
(ramp)
.05
.04
Current
.03
.02
.05
.04
2
I t OFF
IL, Isd, Ii …… % of Current setting Ir
Ip…% of LTD pick-up current IL
.03
INST/MCR pick-up current : Ii
Ir x 2-4-6-8-10-12-16 ±15% WM1
Ir x 2-4-6-8-10-12 ±15% WM2
Ir x 2-4-6-8-10 ±15% WM3
Note1 When Tsd="0.06"setting,operating time is 0.04~0.08s.
I2t is ON/OFF selectable.
Max. breaking time
(In case of AE4000-SW~
6300-SW, is 0.05s)
6300-SS it it is 0.05s)
.01
1
2
5
10
20
50
100 120 150 200
current (%)
500
1000
1600 2000
5000
.02
.01
10000
26. A Trip indicator LED
B Pre-alarm LED
C Temperature alarm LED
D
D Load current LED
G
E RUN LED
E
F ERR. LED
G Current setting dial
F
H INST/MCR pick-up current setting dial
H
I Pre-alarm current setting dial
B
J RESET button
A
K TEST terminal
C
Relation of setting dial
In (CT rating)
K
Ir
Ii
Ig (P.27)
J
Ip
Ip2 (P.29)
Load current LED
(60, 80, 100%, OVER)
I
Adjustable setting range
No. Setting item
G
Current setting
Mark
Ir
Accuracy
0.5 ~ 1.0 (0.05step) x In (CT rating)
Factory default
value
—
Adjustable setting range
1.0
AE630-SW~AE1600-SW
AE2000-SW~AE3200-SW 16-12-10-8-6-4-2-2-4-6-8-10-12-16 x Ir
(INST)
(MCR)
WB1
AE4000-SW
H
INST/MCR
pick-up current
Ii
AE2000-SWA, AE4000-SWA
AE5000-SW
12-10-8-6-4-2-2-4-6-8-10-12 x Ir
AE6300-SW
(INST)
(MCR)
WB1…16 (INST)
± 15%
10-8-6-4-2-2-4-6-8-10 x Ir
(INST)
(MCR)
WB2…12 (INST)
WB2
WB3…10 (INST)
WB3
I
Pre-alarm current
Ip
Ir x 0.68 ~ 1.0 (0.04step) –OVER
± 10%
OVER
–
Pre-alarm time
Tp
75s at Ir x 2 (after 75s, PAL contact output turns on.)
± 20%
—
Upper figure and table denote the case optional MCR function is included.
27. ■Operating characteristic curve (for special use : WB)
5000
(h)
4000
1
3000
40
2000
30
20
1000
15
10
Pre-alarm current: Ip
Ir x 0.68 ~ 1.0(0.04step)-OVER ±10%
500
400
Max. time of
let-through current
8
6
Pre-alarm time: Tp
75s ±20% at Ir x 2
300
200
(min)
4
2
Max. Setting of
External OCR
100
1
50
50
40
40
30
30
20
operating time (s)
60
20
10
10
5
5
4
4
INST/MCR pick-up current: Ii
Ir x 2-4-6-8-10-12-16 ±15% WB1
Ir x 2-4-6-8-10-12 ±15% WB2
Ir x 2-4-6-8-10- ±15% WB3
3
2
3
Up to Icw
2
(s)
1
1
.5
.5
.4
.4
Up to Icw
.3
.3
.2
.2
.1
.1
.05
.05
.04
.04
.03
.03
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
.02
Current Ip, Ii …… % of Current setting Ir
.01
1
2
5
10
20
50
100 125
current(%)
200
500
1000
1600 2000
.02
5000
.01
10000
28. Accessories
Ground fault protection(GFR)
The ground fault protection (GFR) of several hundred amperes is possible. This function can be
selected for trip and alarm (no trip). Power supply is necessary for this function, even if there is not
power supply, it can function at 0.2xIn or higher.
Accuracy
Factory
default value
±20%
Mark Adjustable setting range
Setting item
1.0
GFR pick-up current Ig
0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0 x In
GFR time
3-1.5-0.8-0.5-0.3-0.15-<0.1 - <0.1-0.15-0.3-0.5-0.8-1.5-3s
±20% 3s (TRIP)
TRIP
ALARM
(at 1.5 x Ig)
Tg
alarm output
—
TRIP side : Self-holding/ALARM side : Automatic reset
Neutral CT(NCT)
—
TRIP side
(Self-holding)
Only use for AE-SW
The Neutral CT is used for ground fault protection when the 3 pole breaker is used on a 3 phase 4
wires system and for over current protection on N phase. Please use this CT in combination with
ground fault protection (GFR). As for outline dimensions, refer to page 50.
The length of the cable (attached) for NCT is 2m.
GFR function block diagram (In case of 4pole breaker)
ACB
Ground fault protection characteristics
30
20
Alarm
contact
output
ETR
P1
513
P2
544
Control
power
supply
Pick-up current : Ig
In x 0.1~1.0 ±20%
(0.1step)
10
8
0.1
1.0
6
5
4
Block diagram with NCT function
3.0 ±20%
3
ACB
ETR
P1
513
P2
Control
power
supply
N2
544
N1
Alarm
contact
output
operating time (s)
2
1
Ground fault time: Tg
<0.1-0.15-0.3-0.5-0.8-1.5-3.0s
.5
.4
.3
NCT
.2
NCT type name
ACB type name / CT rating
0.15 ±20%
Applicable NCT type name
AE630-SW 630A
NCT06
AE1000-SW 1000A
NCT10
AE1250-SW 1250A
AE2000-SW 1250A
AE2000-SW 1600A
NCT16
AE2000-SWA 2000A
AE2000-SW 2000A
NCT20
AE2500-SW 2500A
NCT25
AE3200-SW 3200A
NCT32
AE4000-SWA 4000A
NCT40
<0.1
(0.04~0.1)
NCT12
AE1600-SW 1600A
.1
As for outline dimensional drawing, refer to page 50.
.05
.04
.03
.02
10
20
50
100
150 200
300
Ground fault current (% of CT rating In)
500
1000
29. Earth leakage protection(ER)
By combining the ETR with earth leakage protection (ER) and External ZCT, earth leakage
protection is possible. Earth leakage protection, earth leakage tripping and earth leakage alarm can
be selected. Control supply is necessary for this function.
Mark Adjustable setting range
Accuracy
Factory
default value
ER pick-up current IΔn
1A-2A-3A-5A-10A
+0%
–30%
10A
ER time
3-1.5-0.8-0.5-0.3-0.15-<0.1 - <0.1-0.15-0.3-0.5-0.8-1.5-3s
±20% 3s (TRIP)
TRIP
ALARM
(at 1.5 x IΔn)
Setting item
Te
alarm output
—
TRIP side : Self-holding/ALARM side : Automatic reset
—
TRIP side
(Self-holding)
External ZCT
This option is used to detect several amperes of earth leakage when use in combination with a
electronic trip relay that has the earth leakage tripping (ER) option.
Two methods are available. The first is where the all load conductors pass through the ZCT.
The other method uses a smaller ZCT through which the supply transformer's ground wire passes
through to earth.
ZCT for load circuit
ZCT for transformer ground wire
ZCT type name
ACB type name
ZCT163
AE630-SW ~ AE1600-SW 3-pole
ZCT323
ZCT324
ZT15B ZT30B ZT40B ZT60B ZT80B ZT100B
AE630-SW ~ AE1600-SW 4-pole
AE2000-SW ~ AE3200-SW 3-pole
AE2000-SW ~ AE3200-SW 4-pole
As for outline dimensions refer to page 50. Make choice
of suitable ZCT in comformity to the BUSBAR size.
Earth leakage protection characteristics
ER function block diagram (for load circuit method)
30
ACB
20
ZCT
Pick-up current : IΔn
+0
1-2-3-5-10A -30%
10
8
ETR with ER
Z1
Z2
P1
513
P2
544
1A
10A
6
5
4
Control
power
supply
3.0 ±20%
3
ER function block diagram (transformer ground wire method)
ACB
operating time (s)
2
Alarm contact
output
1
Earth leakage protection operating time :Te
<0.1-0.15-0.3-0.5-0.8-1.5-3.0s
.5
.4
.3
ZCT
Z1
ETR with ER
.2
0.15 ±20%
Z2
513
544
Alarm contact
output
P1
P2
Control
power
supply
.1
<0.1
(0.04~0.1)
.05
.04
.03
.02
0.7
1
2
3
5
7
10
Earth leakage current (A)
20
50
100
30. Accessories
2nd Additional Pre-alarm (AP)
The Pre-Alarm (1st) function already installed in standard breaker, the 2nd additional Pre-Alarm
function can be installed as option, thereby it is possible to monitor (observer) electric circuit in more
detail by 2nd additional Pre-Alarm function.
Setting item
Mark
2nd Additional
Pre-alarm
pick-up current
Ip2
2nd Additional
Pre-alarm
time
Tp2
Adjustable setting range
Accuracy
Factory
default value
0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 x Iu WS ±10% WS
0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 x IL WM
±5% WM
0.9-0.8-0.7-0.6-0.5-0.4-0.3 x TL - 5-10-15-20-30-40-60s
(FLAT)
(x TL)
±20%
Pre-alarm timing chart
1.0
0.9 (x TL)
Current
Ip
Current
PAL LED
PAL OUT
(contact output)
Lighting
Blinking
ON
OFF
1/2 TL
Neutral pole 50% protection(N5)
Neutral pole overcurrent protection (operating at 100% of rated current) come already eqipped with
ETR as standard features.
But if you would like to operate at 50% of rated current on neutral pole, neutral pole 50% protection
is availabe with this optional module unit.
31. MCR switch (MCR-SW)
If MCR switch is built in the breaker and the dial for INST/MCR on Main setting module is set to the
range of MCR position, MCR function is operative.
MCR function:
During a closing operation of the breaker, Instantaneous characteristics is operative.
And it becomes inoperative when the breaker is in the closed position.
Temperature alarm (TAL)
If TAL sensor is built in the breaker, temperature alarm is operative. When the temperature of main
contact exceeds normal level, temperature alarm is indicated by LED on main setting module and
also the output contact is made energize if power supply with output contact is installed.
It is possible to know temperature rising which is caused by wear of main contact because TAL
sensor is installed near main contact. When the temperature of main contact goes down to the
normal level, temperature alarm turns off automatically.
Field test device (Y-2000)
The electronic trip relay can be checked by this field test device when the breaker is at test position
or disconnect position. The breaker will trip when tested with this device.
Y-2000 specification
TEST ITEM
LTD,STD,INST,GFR,PAL
TEST SIGNAL RANGE
1% ~ 2500%
OUTLINE DIMENSION
230(W) x 120(H) x 290(D)
TIMER
0.000 ~ 999.999s
POWER SUPPLY
100 – 240V AC 50 / 60Hz
32. Additional functions
By adding the extension module unit in ETR, additional functions like measuring, display
and communication become available.
List of extension unit
Type
Name
Description
Extension module
EX1
Base module for display and interface function (indispensable)
Display module (relay attachment)
DP1
Display module for ETR
Display module (panel attachment)
DP2
Display module for panel board
VT unit
VT
CC-Link® interface unit
Module for measuring of voltage, active power and active energy
BIF-CC
Interface unit for CC-Link®
PROFIBUS-DP interface unit
BIF-PR
Interface unit for PROFIBUS-DP
MODBUS® (RS-485) interface unit
BIF-MD
Interface unit for MODBUS® (RS-485)
BIF-CON
I/O unit
BIF-CL
Drawout position switch
Module for breaker remote control (Interface unit is required)
Switch for detecting the drawout position of the breaker
(Interface unit and I/O unit are required.)
Selection samples of additional function modules
(
Name
Display
VT unit
Type
Additional function
Extension
module
EX1
DP1 or/and DP2
VT
BIF-CC
VT unit
(placed
separately)
BIF-CC
:required optional modules)
Interface unit
BIF-PR
BIF-MD
Load current Display
Communication CC-Link®
PROFIBUS-DP
MODBUS®
Display &
CC-Link®
Communication
PROFIBUS-DP
MODBUS®
Voltage
Power
Energy
Harmonics
current
etc.
Display
Communication CC-Link®
PROFIBUS-DP
MODBUS®
Display &
CC-Link®
Communication
PROFIBUS-DP
MODBUS®
DP2
(on the Panel)
DP1 EX1(inside breaker)
BIF-PR
BIF-MD
Interface unit (placed separately)
Electronic trip relay(ETR) type code
Additional function
Extension module(EX1)
● Main setting module
WS1, WB1, WM1 AE630–1600-SW,
AE2000–3200-SW,
AE4000-SW
WS2, WB2, WM2 AE2000-SWA,
AE4000-SWA,
AE5000-SW
WS3,WB3,WM3 AE6300-SW
WS : General use
WM : Generator protection use
WB : INST/MCR only
● Optional setting module
● Power supply
G1: Ground fault protection
P1: AC•DC100-240V
N5: Neutral pole 50% protection
P2: DC24-60V
E1: Earth leakage protection
P3: AC100-240V / DC100-125V
with output contact
P4: DC24-60V with output contact
AP: 2nd Additional Pre-alarm
NA: Without optional setting
P5: DC100-240V
with output contact (SSR)
Display(DP1)
Display onto panel board(DP2)
VT unit(VT)
Network
BIF-CC
BIF-PR
BIF-MD
Temperature alarm(TAL)
MCR switch(MCR-SW)
Wire system (when EX1 is specified)
3φ3W
3φ4W
EX1
Normal connection
Inverse connection
33. Extension module (EX1)
This is the base module that provides various additional functions with combining Display module
(DP1 / DP2), Interface unit (BIF-CC / BIF-PR / BIF-MD) and VT unit (VT).
1 Various measuring elements, high measuring accuracy
By adopting high-performance ASIC, various measuring elememts (load current, voltage, energy,
harmonics, etc.) and high measuring accuracy are attained. Refer to page 34 for more
details.
2 Communication function
2 display modules and 1 interface unit can be connected simultaneously with its advanced
internal communication.
Display module (DP1/DP2)
This is the module that displays and sets various information, for example, displays of
measurement, trip and alarm, setting of output contacts and so on.
1 Multi display of measuring element
It enables to easily monitor the comparison of each measuring element with its multi display
(4 phases multi display of load current and voltage) on one screen.
2 Two-color back light
Under trip or alarm, back light color changes from green to red automatically, which visually
shows an abnormal situation.
3 Graphical display
By adopting dot matrix type LCD, graphical display such as bar graph display of load
current, harmonic currents and characteristic curve is available.
There are 2 types of display module. One is the ETR attachment type (DP1). Another is the
panel attachment type (DP2), which can be connected to extension terminals of control circuit
with 2m cable. 2 units of display modules (DP1 and DP2) can be attached on one breaker.
(As for outline dimensions of DP2, refer to page 51.)
Note;
● Extension module (EX1) is required.
● VT unit (VT) is required to display the measured data except load current.
VT unit (VT)
VT unit enables to measure voltages, powers, energies, harmonic currents and etc.
by connecting the ETR with Extension module (EX1).
(outline dimensions are shown in page 52.)
Note;
● The length of the cable attached for VT unit is 2m.
34. Network
Interface unit (BIF-CC/BIF-PR/BIF-MD)
These Interface units can expand the future possibility in various communication and Intelligent control.
2
1 Applicable to various open networks.
These units are applicable to various open network systems such as CC-Link®,
PROFIBUS-DP and MODBUS® (RS-485), which can be built in easily.
2 Intelligent control by Multi-data communication
It comes into being the Intelligent control by Multi-data communication through these
interface units to PLC/SCADA, which transfer the measurement Information, setting values,
error information and trip and alarm informations.
BIF-CC (CC-Link®)
By using various application softwares for PLC, users can also connect to the
network SCADA system.
Personal
Computer
MELSECNET/10
Interface card
MELSECNET/10
BIF-PR (PROFIBUS-DP)
CC-Link® / PROFIBUS-DP / MODBUS®
Interface
Unit
PLC
I/O Unit
Eco Monitor Pro
ME110NSR
MDU
AE-SW
Note: Some device types are excluded.
The length of the cable for interface unit is 2m.
Note:
● Extension module (EX1) is required.
BIF-MD (MODBUS®(RS-485))
● VT unit (VT) is required to transmit the measured data except load current.
I/O unit (BIF-CON)
The Input & Output Controlling Unit (BIF-CON) is available for the remote controlling and remote
monitoring of the breaker condition through the various network systems.
With this BIF-CON unit in addition to the Interface Unit, it become possible to control the breaker
remotely, like a ON or OFF operations or Spring-charging.
Function
Description
Note
Breaker ON operation
BIF-CON
Monitor
Breaker OFF operation
1a contact for Shunt trip device (SHT)
(not applicable for AC380-500V rating)
Spring charge
Control
1a contact for Closing coil (CC)
1a contact for Motor charging (MD)
For BIF-CC and BIF-MD, Max. 3 contacts
Digital Input (DI) monitoring monitoring are available.
For BIF-PR, 1 contact monitoring is available.
Drawout position switch (BIF-CL)
With this Drawout position switch (BIF-CL) in addition to Interface unit and I/O unit (BIF-CON), the
remote monitoring of draw-out position become available in case of the breaker draw-out type.
Function
Monitor
BIF-CL
Description
Breaker Drawout position
Note
Position : Connect or Test or Disconnect
35. : can be displayed by DP1/DP2
: can be displayed and set by DP1/DP2
+
Combination sample
➀
Type
➀Main setting module
WS
➁
-
➂
+ +
Note 1)
;EX1;DP1(;DP2)
WM
WB
➀
WS
➁
-
➂
Note 1)
;EX1;DP1(;DP2),VT
WB
WM
➁Optional setting module NA AP G1 E1 NA AP G1 E1 NA AP G1 E1 NA AP G1 E1 NA AP G1 E1 NA AP G1 E1
➂Power supply
P1~P5
P1~P5
Measurement
Load current (±2.5%)
Leakage current (±15%)
Note 4)
Voltage (±2.5%)
Power (active,reactive,apparent) (±2.5%)
Power factor (±5%)
Energy (active,reactive) (±2.5%)
(3.5...19th)
Harmonics current (±2.5%)
Frequency (±2.5%)
Trip history
LTD
STD
INST
GFR
ER
UVT
Note 2)
Note 2)
Note 3)
Note 3)
Alarm history
PAL1
PAL2
OVER
GFR
EPAL
ER
TAL
Characteristic setting (panel attachment product [DP2] only)
LTD
STD
INST
PAL1
PAL2
GFR
EPAL
ER
Setting
Contact outputs setting change
Date & Time
Demand time
Alarm holding method
Reset
Trip and alarm information
Measurement information (min. and max. values)
ETR information
Main / Optional setting module information
Error information
CT rating (In)
Phase line method
Normal connection or reverse connection
Note 1 )
Note 2 )
Note 3 )
Note 4 )
2 units of display modules can be attached.
Display is available only when UVT module is attached.
Display is available only when TAL sensor is attached.
Included the accuracy of ZCT.
36. Electronic trip relay circuit diagram
Upper side terminal
Electronic trip relay (ETR)
Trip coil
➅
Power supply circuit
Rectifier circuit
V1+
0V
➄
Microprocessor
➃ ASIC
Constant voltage
circuit
Setting input
➆
Trigger circuit
Power supply CT
V2+
Load current LED
60-80-100-OVER
PAL LED
CPU
N1
N2
Z1
Z2
Ground fault Integration/
composition circuit
and Earth leakage circuit
Test
connector
W.D.T.
Trip indicator LED
➇
Power supply
with contact output
513
Alarm contact control circuit
A/D
Characteristics and Alarm s/w
Phase selection
sampling
RUN, ERR. LED
Integration circuit
➁
Current sensor coil
➀
Characteristic Setting module
➂
I/O
534
544
554
564
574
RESET
CIRCUIT
V2+
N
524
RS1
RS2
Control power
circuit
P1
P2
P4
0V
FG
Lower side terminal
➀ Power supply CT
Energy is supplied for the operation of the overcurrent tripping and ground fault tripping(GFR) function of the
electronic trip relay.
➁ Current sensor coil
The current in each phase flowing through in the breaker is detected. A air core coil which has good linearity is achieved.
➂ Power supply circuit
This part convert power supply CT energy to constant voltage for respective circuits in the ETR.
➃ ASIC
This amplifies signal detected by the current sensor coil, and detects ground fault current by vector composition.
➄ Microprocessor
The microprocessor integrates each phase current waveforms from the ASIC and performs processing for overcurrent
protection and others.
➅ Characteristic setting module
The module for the characteristic setting of the ETR.
➆ Several LEDs
The load current LED give a figure of current in percent by CT energy.
Trip indicator and pre-alarm are indicated by control power supply.
RUN and ERR. LED indicate breaker's condition by control power supply or ten-odd percent of CT energy.
➇ Power supply with contact output
This outputs contact signal at fault cause (including pre-alarm) and at other alarms.
A control supply is necessary for this function.
37. Setting procedure
1 Prepare a small flat tipped screwdriver.
0.8mm max. 6mm max.
Press the screwdriver in the direction
of the arrow to open the cover
Side view of the flat tip
ETR cover
2 Insert the flat tipped screwdriver into the opening of the ETR cover.
Then, lightly turn the screwdriver to the upside as shown in the left
figure, and the ETR cover will open.
Sealing hole
Operating hole for resetting
3 There are two kinds of switches for characteristics setting and for trip
indicator reset. They should be used as follows.
➀ Adjustable in steps
Rotary code switch is used. Do not set the switch at points
between steps. The setting value is same when the switch is
positioned at the thick line. (Set the switch with a torque of
0.02N•m or below.)
(XIu)
➁ Push-button
This is for temporary operation, and press it with force of 3N or
less.
➀Adjustable
in steps
➁Push-button
4 When the characteristic is set up, use a device like a field tester, etc
to make sure that the required characteristic has been set.
5 At sealing, seal the ETR cover by using the sealing hole at the top of
the ETR cover.
Sealing hole
38. 97
Reset circuit
Power circuit
SHT
CC
564
554
544
534
524
STD/INST
LTD
98
C2
A2
FG
Dielectric test forbidden
Electronic trip relay
Control power circuit / alarm contact
Terminal description
D1
DT2 DT1
Short
bar
ZCT *
* Voltage forbid to be applied
Main circuit
574
G1/E1/AP
P4
PAL
Z2
TAL
NCT *
Z1
D2
UVT
ERR
N2
A1
Alarm contacts
Electronic trip
relay(ETR)
N1
C1
413
U1
CLS
P2
M
414
U2
Open to trip
(less than 2m)
OCR
alarm
Charged
P1
UVT
Controller
513
ON
See Fig.1.
AL
RS1 RS2
Power supply
OFF
Extension terminals
Less than 2m
Cut-off switch
RESET
L1 L2 L3 N
Common
● The following diagram shown accessories fully equiped.
Electrical operation circuit
Accessory Symbols
13
14
~
53
54
Auxiliary switch "a"
11
12
~
51
52
Auxiliary switch "b"
U1
U2
Motor charging
413
414
Charged signal
Voltage Input terminal of UVT
D1
D2
DT1
DT2
A1
A2
CC
97
98
Power supply for ETR
Auxiliary switch
OCR alarm switch
Charge limit switch
SBC
Shorting b-contact
CL
Cell switch
Alarm reset (Trip cause LED, alarm contact)
Internal wiring
513 , 524 ~ 574
Alarm contacts
Z1
Z2
For external ZCT
N1
N2
For Neutral CT
(Note)
For external display DP2
Extension terminals
UVT coil
CLS
FG of power supply (FG:Frame Ground)
RS2
UVT
AL
OCR alarm
RS1
Motor(Motor charging device)
AX
Shunt trip
P4
Closing coil
M
Closing coil
C2
P2
Shunt tripping device
Trip terminal of UVT (Remote trip)
C1
P1
SHT
For Interface unit
For VT unit
Note; Do not connect the NCT type CW-40LM (for AE-SS series).
External wiring (user's wiring)
Control circuit connecter (drawout type)
39. Breaker
43
33
23
13
42
32
22
12
54
44
Breaker
Auxiliary switch(normal close)
380-460V AC type
input
IN2
+
D1
14
344
342
334
332
324
CL
311
322
314
312
Cell switch
Cell switch
Note;
input
D2
24
Auxiliary switch(normal open)
Fig.1
UVT controller wiring
100-120V AC type
200-240V AC type
DC types
34
ON
OFF
52
321
CL
331
CL
341
CL
AX
AX
AX
AX
AX
SBC
53
SBC
11
AX
SBC
21
AX
AX
AX
AX
31
SBC
41
SBC
51
IN1
external unit
OUT4
OUT3
D2
D1
● On the drawout type, the cables should have the length which allow the control circuit
terminal block to be moved to the left or right by 5mm.
● When a coil load is connected in the same control circuit as the ETR, surge absorbers are
required to absorb the surge voltage.
● OCR alarm (AL)
The contact output of the OCR alarm(Standard type AL) is the one-pulse output and the
output time is 30~50ms.
For this reason, this output needs self-holding circuit.
● Closing coil (CC)
As CC is one-pulse driven, it is not necessary to insert AXb for burning prevention purposes.
Inserting AXb will cause anti-pumping function to be ineffective.
● Under voltage trip device (UVT)
Use the switch that can open and close DC150V, 0.5A to remote trip.
Remote trip terminal has short bar at shipment, so remove it before using this function.
Disconnect the voltage input wires during dielectric testing of main circuit.
● Alarm contacts 513 , 524 ~ 574 are also reset by removing P1 , P2 power supply
voltage. (longer than 1sec.)
40. Drawout type AE630-SW,AE1000-SW, AE1250-SW, AE1600-SW
(mm)
Side view
Front face of control terminal
4P
Horizontal
(standard)
terminal
*200
149
48
368
Fully drawout
position
15
Earth terminal
M8 screw
23
*220
452
234(149)
172
40
Panel
4-φ14
15
53
25
40
15
15
50
15
42.5
Front
terminal
132
132
430
340
Aperture for the
drawout handle
Vertical
terminal
15
Neutral pole
50
3P
Lifting hook hole
283
66
57
15
61
366
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
Inside of the panel
(thickness 1.6~3.2)
Rear view
Horizontal terminal
Vertical terminal
85
Front terminal
Operating panel center
Operating panel center
Operating panel center
85
85
85
85
85
85
85
85
50
Neutral pole
Insulation
block
50
50
Neutral
pole
Outline
of breaker
4P
3P
15
Outline
of breaker
Neutral
pole
4P
Outline
of breaker
3P
4P
Main circuit terminal dimension
Horizontal terminal(standard)
Vertical terminal
Front terminal
Connecting area
2-φ13
50
15
25
38
370
Test 35
228
92
Disconnected 54
117
235(150)
370
150
Control terminal
(M3.5 screw)
92
Operating panel center
100
Front view
3P
41. Drawout type AE2000-SWA
(mm)
Front view
Side view
Operating panel center
150
235(150)
Control terminal
(M3.5 screw)
Front face of control terminal
Disconnected 54
Test 35
228
Lifting hook hole
283
3P
4P
370
57 100
340
430
Aperture for the
drawout handle
157
Neutral pole
*200
149
40
Panel
4-ø14
48
452
234(149)
Fully drawout
position
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
100
172
*220
29.5
25
40
42.5
23
104
368
366
Inside of the panel
(thickness 1.6~3.2)
Rear view
Operating panel center
115
Operating panel center
105
105
115
10
10
105
10
Neutral
pole
Outline
of breaker
3P
Outline
of breaker
4P
Main circuit terminal dimension
Connecting area
100
15
25 25 25
38
4-φ13
79.5
15
15
Earth terminal
M8 screw
42. Drawout type AE2000-SW, AE2500-SW, AE3200-SW
(mm)
Front view
Side view
Operating panel center
Control terminal
(M3.5 screw)
Front face of control terminal
Disconnected 54
324(194)
368
61
366
Fully drawout
position
T
83
Earth terminal
M8 screw
Dimensions
23
*220
452
57
T
(mm)
Type
T
AE2000-SW AE2500-SW
AE3200-SW
Inside of the panel (thickness 1.6~3.2)
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
20
25
Rear view
Horizontal terminal(standard)
23
130
130
Front terminal
Vertical terminal
Operating panel center
Operating panel center
Operating panel center
23
130
130
130
23
130
130
130
130
W
Insulation
block
W
T
Outline
of breaker
Outline
of breaker
4P
3P
Neutral pole
4P
Neutral pole
Outline
of breaker
3P
Neutral pole
4P
3P
Main circuit terminal dimensions
38
Connecting area
15
4-φ13
34
Connecting area
5-φ13
125
15
25 25 25 25
W
15
Front terminal
Dimensions
(mm)
W
Connecting area
25 25 25
38
Vertical terminal
25 25 25
Horizontal terminal(standard)
370
53
25
48
67
T
40
239
172
40
Panel
4-φ14
92
15
15
42.5
132
182
132
430
340
Aperture for
the drawout
handle
T
125
T
Neutral pole
*200
Front
terminal
Horizontal
(standard) Vertical
terminal
terminal
4P
125
3P
Lifting hook hole
283
92
Test 35
228
370
325(195)
240
W
AE2000-SW AE2500-SW
AE3200-SW
4-φ13
Type
95
103
43. Drawout type AE4000-SWA
(mm)
Front view
Side view
Operating panel center
Control terminal
(M3.5 screw)
Front face of control terminal
Lifting hook hole
Disconnected 54
325(195)
Test 35
228
Connecting busbar size
All poles:
T10xW150x4BUS/pole
283
Neutral pole
25
40
67
15
15
42.5
*200
Panel
4-φ14
Earth terminal
M8 screw
23
368
109
366
Fully drawout
position
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
172
*220
452
324(194)
239
40
48
Inside of the panel (thickness 1.6~3.2)
Rear view
Operating panel center
Operating panel center
23
190
170
190
Outline
of breaker
52
10
170
43
170
Outline
of breaker
52
10
Note) 11
Note) 11
197
242
Neutral pole
327
242
4P
3P
Note) Spacers are not required when fastening connecting conductors (T10). The necessary contact area can be obtained with ACB terminal bent by tightening the screw.
Main circuit terminal dimension
Connecting area
125
20
25 25 25 25
48
5-φ13.5
370
430
125
Aperture for
the drawout
handle
182
4P
340
3P
125
240
44. Drawout type AE4000-SW, AE5000-SW, AE6300-SW
(mm)
Front view
Side view
Neutral pole
Control terminals
(M3.5 screw)
588.5(458.5)
Operating panel
center
373.5
28
228
Front face of
control terminal
Disconnected 54
28
Test 35
4P
HN
3P
Lifting hook hole
M12 Weld nut
283
Mounting angle
75
Fixing bolts
2-M12
Panel
42.5
4-M12
*530
395
172
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
48
*220
123
14 or more
Bus bar
366
Fully drawout
position
Aperture for the drawout handle
Earth terminal
M8 screw
23
368
400
610(480)
420
117
15
90
177
15
345.5
182
125
340
480
Drawout handle
radius 100
125
Insulation block
Inside of the panel (thickness 1.6~3.2)
Main circuit terminal dimension
Rear view
Operating panel center
2-M12 for mounting
*431.5
262
262
25
Mounting angle
(non-magnetic steel)
W
14
235
Connecting area
*382
25
125
196
53
25 25 25 25
42.5
*561.5(431.5)
Outline of breaker
5-φ13
103
(mm)
Dimensions
4P
HN
W
T
AE4000-SW AE5000-SW
100
20
AE6300-SW
3P
105
25
Type
T
The mounting angle should be prepared by the customer.
4P FN type
Front view
Rear view
Control terminals
(M3.5 screw)
588.5
Operating panel
center
28
503.5
Neutral pole
2-M12 for mounting
Neutral pole
28
228
Operating panel center
*692.5
262
Mounting angle
(non-magnetic steel)
*430.5
88.5
262
262
W
14
235
*382
90
177
Drawout handle
radius 100
42.5
*42.5
399.5
6-M12
*714
525
610
Aperture for the drawout handle
Side view dimensions are same as 3 pole.
Fixing bolts
2-M12
T
45. Fixed type AE630-SW, AE1000-SW, AE1250-SW, AE1600-SW
(mm)
Front view
Side view
Operating panel center
142
227(142)
275
3P
93.5
Control terminal
(M3.5 screw)
139
4P
15
132
5
72
4-φ14
410
340
7
350
15
Neutral pole
Earth terminal
M8 screw
(Left side)
228
*156
170
Panel
40
*175
*241(156)
290
255(170)
288
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
Inside of the panel
(thickness 1.6~3.2)
Rear view
Operating panel center
85
85
85
50
Neutral pole
Outline of breaker
4P
3P
Main circuit terminal dimension
Connecting
area
2-φ13
50
17
25
38
31
40
Earth terminal
M8 screw
(Left side)
46. Fixed type AE2000-SWA
(mm)
Front view
Side view
Operating panel center
142
227(142)
93.5
Control terminal
(M3.5 screw)
275
3P
139
4P
410
350
340
57 100
7
157
Neutral pole
228
*156
*241(156)
170
*175
Panel
290
255(170)
24.5
40
5
Earth terminal
M8 screw
(Left side)
31
108
288
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
Inside of the panel
(thickness 1.6~3.2)
Rear view
Operating panel center
115
Operating panel center
115
105
10
105
10
105
10
Neutral pole
Outline of breaker
Outline of breaker
3P
4P
Main circuit terminal dimension
Connecting
area
100
15
25 25 25
38
4-φ13
74.5
100
4-φ14
Earth terminal
M8 screw
(Left side)
47. Fixed type AE2000-SW, AE2500-SW, AE3200-SW
(mm)
Front view
Side view
Operating panel center
Control terminal
(M3.5 screw)
317(187)
232
93.5
139
275
132
20
4-φ14
40
5
Earth terminal
M8 screw
(Left side)
228
*246
*175
Panel
*331(201)
260
290
345(215)
288
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
Inside of the panel
(thickness 1.6~3.2)
Rear view
Operating panel center
130
23
130
130
95
Neutral pole
Outline of breaker
4P
3P
Main circuit terminal dimension
Connecting area
4-φ13
95
17
25 25 25
38
410
340
7
350
20
Neutral pole
4P
72
3P
31
40
Earth terminal
M8 screw
(Left side)
48. Fixed type AE4000-SWA
(mm)
Front view
Side view
Operating panel center
232
Control terminal
(M3.5 screw)
317(187)
93.5
275
Connecting busbar size
All poles:
T10xW150x3BUS/pole
139
Neutral pole
4P
410
182
340
57
7
350
125
3P
228
Panel
*246
*175
*331(201)
290
345(215)
260
4.5
40
5
Earth terminal
M8 screw
(Left side)
67
129.5
4-φ14
31
117
Earth terminal
M8 screw
(Left side)
288
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
Inside of the panel (thickness 1.6~3.2)
Rear view
Operating panel center
Operating panel center
152
30.5
145
23
145
152
145
31
31
Note) 11
Note) 11
10
10
Outline
of breaker
Outline
of breaker
Neutral
pole
3P
4P
Note) Spacers are not required when fastening connecting conductors (T10). The necessary contact area can be obtained with ACB terminal bent by tightening the screw.
Main circuit terminal dimension
Connecting area
125
20
25 25 25 25
48
5-φ13.5
49. Fixed type AE4000-SW, AE5000-SW, AE6300-SW
(mm)
Front view
Side view
Control terminals
(M3.5 screw)
Neutral pole
581.5(451.5)
Bus bar
275
93.5
139
4P
HN
354
57
7
182
340
125
3P
14 or more
366.5
414
Operating panel
center
4-φ14
9
228
*595.5(465.5)
*175
Panel
290
609.5(479.5)
394.5
10
40
*380.5
31
Earth terminal
M8 screw
(Left side)
136
288
* : Mounting pitch
The numerals shown in
parentheses are for 3 poles.
Inside of the panel (thickness 1.6~3.2)
Rear view
Main circuit terminal dimension
Operating panel center
Neutral
pole
72.5
135
Earth terminal
M8 screw
(Left side)
53
42.5
Connecting area
25
197
262
262
20
Outline of breaker
4P
HN
125
20
25 25 25 25
100
5-φ13
3P
4P FN type
Front view
Earth terminal
M8 screw
(Left side)
Rear view
Operating panel
center
496.5
Control terminals
(M3.5 screw)
581.5
275
Neutral
pole
Neutral pole
Operating panel center
89
263
263
263
100
20
4-φ14
228
*510.5
*595.5
524.5
609.5
Side view dimensions are same as 3 pole.
50. Panel cut-out, Drawout handle, Terminal adapter
Panel cut-out dimensions
Door frame panel cut-out dimensions
Panel cut-out dimensions
7.7
Operating panel center
8-φ7
Operating panel center
Outline
405
345
357
247
235
Breaker
mounting frame
(mm)
Type
AE630-SW~AE1600-SW Fixed Type
AE2000-SW~AE3200-SW
AE2000-SWA, AE4000-SWA Drawout Type
Fixed Type
AE4000-SW~AE6300-SW
Drawout Type
A
324
A
381
345
Dimensions
A
175
195
179
245
235
271
295
Breaker mounting frame
Vertical terminal adapter
Type
34
φ13
D
Mtg.holesφ13
(mm)
Connecting area
AE630-SW~1600-SW
20
AE3200-SW
Fixed
type
C
25
Fixed
AE2000-SW,2500-SW type
AE3200-SW
Fixed
type
Down side
Drawout type
Drawout handle dimensions
15
95
20
145
95
20
95
20
95
25
145
95
25
103 25
Condenser trip device (COT)
17
2-φ8
2-M6 Mounting screw
200
4-M4 screw
(for wiring)
169
75
110.6
14.3
16
45
Condenser
trip device
R6
4-
φ10
4
φ100
max 173
200
15
50
145
Up side
50
258.5
Drawout type
145
145
Down side
15
258.5
Up side
T
50
145
Down side
D
258.5
Up side
Drawout type
T
AE2000-SW,2500-SW
D
Dimensions
115
45
45
87
110
Breaker
Front view
T
Connecting area
φ13
Type
38
(mm)
42
Side view
45
37.5
Connecting area
Dimensions
15
53
C
25 25 25 25
T
15
38
100
φ13
25 25 25
100
15
50
25
15
φ13
φ13
25
125
15
15
φ13
25 25 25
50
25
φ13
38
15
38
AE630~
AE2000~
1600-SW 3200-SW
AE2000~3200-SW
T
AE630~1600-SW
Front terminal adapter
Drilling plan
51. Neutral CT (NCT), External ZCT
Neutral CT (NCT)
M5 screw
2500~4000A
630~2000A
162
4
68
M5 screw
160
51
219
5.5
105
137
97
R2
28
9
31
16.5
R3
122 Mounting pitch
38
142
66
11
48
Slit for M8 screw
192 Mounting pitch
55
Slit for M10 screw
212
87
External ZCT for transformer ground wire
Terminals M3.5 screw
A
Terminals M3.5 screw
F
30
28
E
12
D
C
B
3
2
C
G
B
D
7.7
H
E
Slit for M5 screw
100
52
70
A
40
90
Slit for M5 screw
Dimensions
(mm)
Dimensions
(mm)
A
B
C
D
E
F
G
H
A
B
C
D
ZT15B
48
15
29
62
46
15
70
25
ZT60B
140 60
73 150 46
ZT30B
68
30
37
82
66
30
90
50
ZT80B
160 80
82 169 48
ZT40B
85
40
43
92
81
40 100 50
E
ZT100B 185 100 93 190 50
External ZCT for load circuits
C
Terminals M3.5 screw
E
K
Dimensions
(mm)
B
C
D
E
ZCT163 230 60 323 250 47
B
200
A
ZCT323 370 108 460 400 47
ZCT324 500 108 600 550 48
A
Slit for M8 screw
72
D
92
52. UVT external unit
UVT external unit (AC380 ~ 460V)
30
30
20~24
Mounting bracket
Height of wiring
Terminal
IN1
IN2
OUT OUT
4
3
(mm)
Use the attached
mounting bracket.
(Not applicable to
35mm IEC rail)
Terminal
117
107
100
UVT
external unit
IN1
380-460V
AC
OUT4
To AE-SW terminals
of UVT controller
65
30
IN2
30
Mounting ø4.5 hole
90
OUT3
ETR external units
Display onto panel board (DP2)
(mm)
Operation display surface
64
48
Panel (Note)
42
16
Note : Use the panel of thickness 1mm ~ 3.2mm.
64
Panel attachment metal
49
1
R≤
51
64 max.
48
29.5
64
48
64
Upper side
3
Operation display
surface side
Panel attachment metal
Fixed screw M3
DP2 connection cable
connection position (connector)
Surface plate
hole dimension
CC-Link®, MODBUS® interface unit (BIF-CC, BIF-MD)
(mm)
77.5
30
Mounting bracket
5
Terminal
90
35
117
IEC35mm rail
107
100
30
23.5
37.5
67.5
35mm IEC
rail holder
65
30
Terminal
Frame Ground
M3 terminal screws
FG
P1 P2 SLD DG DB DA
35mm IEC
rail holder
Power supply
(100-240V AC•DC)
CC-Link®
30
Mounting φ4.5 hole
Frame Ground
Ter Ter FG
P1 P2 COM T/R- T/R+ SLD
Power supply
(100-240V AC•DC)
MODBUS®
54. Pre-cautions when making connections
Use M12 bolts, plain washers, and spring lock washers to connect the conductor. There are various size plain washers,
but use 24mm or smaller outside diameter washers. The washers may overlap if too large washers are used.
It is recommended to apply silver plating on the contact surface of the conductor which is used to connect with the
terminal of circuit breakers in order to prevent the increase of contact resistance due to moisture, etc. Tin plating or
nickel plating may be applied, but quickly connect with the circuit breaker terminal if nickel plating is applied because
nickel plating is less resistant to sulfur dioxide
gas.
Clean the contact surface and securely tighten
25mm
the bolts with a correct torque (M12: 40 to 50
Plain
N•m).
washer
The terminal which is applicable to connect
the conductor is different depending on the
shape of the terminal. Refer to the outline
Conductor (plating)
dimensions of P.39 to P.46.
25
ACB Terminal (silver plating)
Standard tightening torque
Screw size
M12
Plain
washer
Tightening torque(N•m)
40~50
Since fault current flowing through the conductors cause large electromagnetic forces,the conductors should be
secured firmly, using the values in the below table as a reference. Max distance between fixing support and ACB
bus bar should be less than 200mm.
Electromagnetic force in N per 1m conductor
(in the case of three phase short circuit)
Type
AE2000-SWA
AE630-SW~
AE1600-SW
Bus bar
3-Pole
Conductor distance(mm)
AE2000-SW~
AE3200-SW
4-Pole
115
(N)
AE4000-SWA
105
85
AE4000-SW~
AE6300-SW
Fixed type
Drawout type
3-Pole
4-Pole
3-Pole
4-Pole
130
190
170
152
145
262
Prospective fault current kA(pf)
30(0.2)
5700
6300
5100
3500
3900
4300
4500
2500
15100
11200
12200
9900
6800
7600
8500
8900
5000
50(0.2)
21400
15800
17300
14000
9600
10700
12000
12600
7000
65(0.2)
36100
26700
29300
23600
16200
18100
20200
21200
11800
75(0.2)
-
-
-
31500
21500
24100
26900
28200
15800
85(0.2)
-
-
-
40400
27600
30900
34500
36200
20000
100(0.2)
-
-
-
-
-
-
-
-
27800
130(0.2)
Max.200mm
Fixing support
7700
42(0.2)
AE–SW
-
-
-
-
-
-
-
-
47000
Conductor Size(IEC 60947-1; Ambient 40°C Temp., Open air)
When selecting conductors to be
connected to AE breakers, please ensure
that they have a sufficient current
capacity. Refer to the right table.
Rated current
Max.(A)
Connecting conductors(copper bus bar)
Quantity
Conductor size(mm)
630
2
40 x 5
1000
2
60 x 5
1250
2
80 x 5
1600
2
100 x 5
2000
3
100 x 5
2500
4
100 x 5
3150(3200)*1
3
100 x 10
4
150 x 10
4000
⎛ AE4000-SWA ⎞
⎝ Fixed type ⎠
3
150 x 10
4000
(AE4000-SW)
4
100 x 10
5000
4
150 x 10
6300
4
200 x 10
4000
⎛ AE4000-SWA ⎞
⎝ Drawout type ⎠
Arrangement
With long
surface vertical
*1 The temperature rise of rated current 3200A conforms to the requirement of IEC 60947-1 for
the connecting conductor size of a rated current 3150A. In case of more than 3200A,
conductor sizes are not defined in IEC 60947-1.
55. Insulation distance
When a short-circuit current is interrupted, discharged
hot gas blows out from the exhaust port of the arc
extinguishing chamber, so provide a clearance as
shown in the following table.
Note1:On the fixed type, maintenance is possible with
following clearance.
Dimensions
A
D
A
Electrical equipment,appliances or screen
B
(mm)
Type
C
Side
plate
B
Mounting
surface
Applicable voltage
A
B
Fixed type
C
D
A
B
Drawout type
C
D
AE4000-SW~
AE6300-SW
AE630-SW~AE3200-SW
AE2000-SWA AE4000-SWA
AC600V or less
(Note 1) 0
(Note 3) 50
162
(Note 2) 50
0
(Note 3) 50
240
(Note 2) 50
AC660V, 690V
(Note 1) 100
(Note 3) 50
162
(Note 2) 50
100
(Note 3) 50
240
(Note 2) 50
AC690V or less
(Note 1) 200
(Note 3) 50
200
(Note 1) 200
(Note 3) 50
200
Note1:300mm or more clearance is necessary to inspect the arc-extinguishing chamber and contacts.
Note2:The wiring space reguired for the control terminal block.
Note3:When using mechanical interlock, door interlock ,etc., dimension B becomes larger.
Service conditions
1. Normal service condition
Under ordinary conditions the following normal working conditions are all satisfied, the AE Series air
circuit breaker may be used unless otherwise specified.
1.Ambient temperature
A range of max. +40°C to min. -5°C is recommended.
And the average over 24 hours must not exceed +35°C.
2.Altitude
2,000m(6,600 feet) or less
3.Environmental conditions
The air must be clean, and the relative humidity must be 85% or less at max.
temp. +40°C.Do not use and store in atmospheres with sulfide gas and
ammonia gas etc.(H2S ≤ 0.01ppm, SO2 ≤ 0.1ppm, NH3 < a few ppm.)
4.Installation conditions
When installing the AE Series air circuit breaker, refer to the installation
instructions in the catalogue and instruction manual.
5.Storage temperature
A range of max. +60°C to min. -20°C is recommended to be stored.
And the average over 24 hours must not exceed +35°C.
6.Guideline for replacement
Within approx. 15 years.Please refer to the instruction manual.
2. Special service conditions
In case of special service condition, service life may become shorter in some cases.
1.Special environmental conditions
High temperature and/or high humidity
Corrosive gas
2.High ambient temperature
If the ambient temperature exceeds +40°C, the uninterrupted current rating
will be reduced. Since the derating value is different depending on the
applicable standard, refer to P56.
3.High altitude
Since the heat radiation rate is reduced for use at the 2,000m or higher,
accordingly the operating voltage, continuous current capacity and breaking
capacity are derated.Moreover the insulation durability is also decreased
owing to the atmospheric pressure. Please inquire us for further detail.
56. Internal resistance, reactance and power consumption (per pole)
Connection
Internal
resistance
(mΩ)
Reactance
(mΩ)
Power
consumption
(W)
Fixed type
0.028
0.059
11
Drawout type
0.042
0.089
17
Fixed type
0.026
0.060
26
Drawout type
0.040
0.091
40
Fixed type
0.024
0.060
38
Drawout type
0.038
0.091
60
Fixed type
0.016
0.063
41
Drawout type
0.030
0.095
77
Fixed type
0.016
0.063
64
Drawout type
0.025
0.095
100
Fixed type
0.010
0.047
40
Drawout type
0.020
0.071
80
Fixed type
0.008
0.047
50
Drawout type
0.018
0.071
113
Fixed type
0.007
0.048
72
Drawout type
0.014
0.072
143
Fixed type
0.009
0.048
144
Drawout type
0.015
0.072
240
Fixed type
0.010
0.038
160
Drawout type
0.013
0.062
210
Fixed type
0.009
0.038
225
Drawout type
0.011
0.062
275
Fixed type
0.008
0.038
318
Drawout type
Type
0.0085
0.062
340
AE630-SW
AE1000-SW
AE1250-SW
AE1600-SW
AE2000-SWA
AE2000-SW
AE2500-SW
AE3200-SW
AE4000-SWA
AE4000-SW
AE5000-SW
AE6300-SW
The above values are applicable for one pole. (at brandnew product)
57. Deratings by ambient temperature
(A)
IEC60947-2, BS, JIS C 8201-2-1 (Standard:40°C)
Standard
LR, GL, BV, DNV, ABS, NK, CCS (Standard:45°C)
Ambient Temperature
40°C
45°C
50°C
55°C
60°C
AE630-SW
630
630
630
630
630
AE1000-SW
1000
1000
1000
1000
1000
AE1250-SW
1250
1250
1250
1250
1200
AE1600-SW
1600
1600
1600
1550
1500
AE2000-SWA
2000
2000
1900
1800
1700
AE2000-SW
2000
2000
2000
2000
2000
AE2500-SW
2500
2500
2500
2450
2350
AE3200-SW
3200
3200
3200
3000
2900
AE4000-SWA
4000
4000
4000
3800
3600
AE4000-SW
4000
4000
4000
3900
3750
AE5000-SW
5000
5000
5000
5000
4750
AE6300-SW
6300
6300
5750
5500
5200
With Extension module, Display and Network
In case extension module (EX1), display (DP1) and network are attached, the following derating values shown in this table are applied.
(A)
IEC60947-2, BS, JIS C 8201-2-1 (Standard:40°C)
Standard
LR, GL, BV, DNV, ABS, NK, CCS (Standard:45°C)
Ambient Temperature
40°C
45°C
50°C
AE630-SW
630
630
630
AE1000-SW
1000
1000
1000
AE1250-SW
1250
1250
1250
AE1600-SW
1600
1600
1440
AE2000-SWA
2000
1900
1700
AE2000-SW
2000
2000
2000
AE2500-SW
2500
2500
2500
AE3200-SW
3200
3200
2880
AE4000-SWA
4000
3800
3600
The above table shows the maximum rated current per each ambient temperature for drawout type breaker with vertical connection
(at brandnew product), when breaker and bus bar are installed in open air.
Connection bus bar is according to IEC60947-1. For AE3200-SW, AE4000-SWA, AE4000-SW, AE5000-SW and AE6300-SW,
it is required to follow the manufacturer recommended size shown in Page 53.
As for ambient temperature exceeding 60°C, please inquire us.