© LANCO Group, All Rights Reserved© LANCO Group, All Rights Reserved
POWEREPC INFRASTRUCTURESOLAR RESOURCES
Lanco Babandh Power Ltd
(C&I Cables Testing Methods)
PRATYUSHA KHANDELWAL
Source : Thermo Cables Limited, Hyderabad: 19.Nov.2012-23.Nov.2012
© LANCO Group, All Rights Reserved
Types of Cables:
• Power Cables/Control Cables
• Instrument/TC/Signal Cables
Note: Only Instrument cables have drain wires
© LANCO Group, All Rights Reserved
Material used in Cables:
• TYPE: Y13 = Conductor Insulation(VDE 0207PT4)
• TYPE: A = Conductor Insulation
• XLPE = Conductor Insulation
• TYPE: YM1 = Inner Sheath (VDE 0207PT5)
• ST1 = Outer Sheath
• ST2 = Outer Sheath
*Note: Credentials validity must be up to 5 yrs approved by CPRI/NABL/NTH etc
© LANCO Group, All Rights Reserved
Nomenclature:
Ex: 3C/P/T/Q 16 SQ MM 1100V FRLS TCL 2012 315M
Job ID: XXXXXX
Customer No. DVWS
Job No./ASC: 303468
Size: 8P x 0.5 sq.mm
DRM No. 1004883
QTY: 465 M
*ASC= Armoured Screen Cable
© LANCO Group, All Rights Reserved
Tests for Cables:
Type/Routine Tests: (100% of the given lot)
1) HV Test/High Pot. Test
2) Conductor Resistance Test
3) Drain Wire Resistance Test
4) Insulation Resistance Test
© LANCO Group, All Rights Reserved
Tests for Cables:
Acceptance Tests: (10% of offered lot of each cable size as applicable)
1) Construction detail verification(Conductor/Insulation system/ Pairing/
Laying/Pair/Overall Shielding/Inner sheathing /Armoring/Outer sheathing)
2) Conductor Resistance Test
3) Capacitance, Inductance & L/R Ratio Test
4) Tensile strength and elongation at break for insulation and sheath before and
after ageing
5) Thermal Stability Test
6) Cross Talk/Attenuation Test
7) Insulation Resistance measurement
8) Insulation thickness measurement
9) Color identification of cores
10) Annealing Test
11) Volume Resistivity Test
12) Hot Deformation Test
© LANCO Group, All Rights Reserved
Acceptance Tests:
FRLS & ART:
1) Oxygen Index Test.
2) Temperature Index Test.
3) Smoke Density Test.
4) Flammability.
5) Swedish chimney/Flame Retardant Test.
6) Acid gas generation test.
7) Anti rodent test.
© LANCO Group, All Rights Reserved
HV Test:
IS : 10810 Part 45
• HV Tester
• ForControlCables: 3kV ACrms for 5 minutes(C-C)
3kV ACrms for 5 minutes(C-Armour)
• ForTC/InstrumentCables: 1kV ACrms for 1 minutes(C-C)
1kV ACrms for 1 minutes(C-Screen)
*Note: Drain wires are only present in Instrument cables
© LANCO Group, All Rights Reserved
Conductor Resistance & Drain Wire Resistance Test:
• BS: 5308 Part-2
• IS: 10810 Part-5
• Digital Ohm Meter
• Probe Calibration Test- 0.0 at NTP
• At 20°C, R= [Rx.k.1000/L]; Ω/km [max. 36.6]
where, k= 250/(230+T)
*Drain wire: 30 Ω,max /Conductor Wire: 36.6 Ω,max
© LANCO Group, All Rights Reserved
Insulation Resistance Test:
• IS: 10810 Part-43
• Insulation Tester
• IRconstant = LxR/[1000Log10(D/d)]; MΩ-km
• Min. 100MΩ/km
• C-C
• C-Shield
• Insulation
• L/R
© LANCO Group, All Rights Reserved
Capacitance, Inductance & L/R Ratio Test:
• BS: 5308 – I & II
• Digital LCR Q Meter
• Frequency is set at 1kHz
• OC & SC test is done
• Capacitance b/w cores= Cc x 1000/L in nf/km [max. 250]
• Capacitance b/w core to shield + armor = Cs x 1000/L in nf/km
[max. 400]
• Inductance = L x 1000 x 1000/L in mH/km [max. 1]
• L/R = obs. Inductance/loop resistance; µH/Ω [max. 25]
© LANCO Group, All Rights Reserved
continued…
PARAMETER PVC INSULATION XLPE/LDPE INSULATION
Capacitance b/w cores Max. 250 nf/km Max. 100 nf/km
Capacitance b/w core-shield Max. 400 nf/km Max. 400 nf/km
Inductance for signal cables Max.1mH/km Max.1mH/km
Inductance for TC cables Max. 4mH/km Max. 4mH/km
L/R ratio up to 1 mm² Max. 25µH/Ω Max. 25µH/Ω
L/R ratio 1- 1.5 mm² Max. 40µH/Ω Max. 40µH/Ω
L/R ratio 2.5 mm² Max. 50µH/Ω Max. 50µH/Ω
© LANCO Group, All Rights Reserved
Ageing Test:
• IS: 10810 Part-11
• Tensile strength and elongation at break for insulation and sheath before and after ageing is done.
• 7 Days test at specific temp. of 80°C, 100°C etc
• Sheath-dumb-bell shape & Insulation-tubular shape; each sample of ≥ 100mm is taken.
• 20 mm marking is done on each test sample and tested at 50kg wt. tensile & elongation tester.
• Tubular Cross sectional Area, A = ∏/4[ D² – d²]; mm²
• Dumb-bell Cross sectional Area, A = width x thickness; mm²
• T.S. = BL x 9.8/ A; N/mm²
• % Elongation = [L-L0]/L0 x 100 in %
• Variation in T.S. = [TS0 – TSx]/TS0 x 100 in %
• Variation in Elongation = [EL0- ELx]/EL0 x 100 in %
Note: BL at fractured point shall not be greater than 250 mm/min.
Material T.S. % Elongation
PVC 12.5 N/mm² min. Min. 150 %
LDPE 10 N/mm² min. Min. 300%
XLPE 12.5N/mm² min. Min. 200%
© LANCO Group, All Rights Reserved
Ageing Test: continued…
Material Variation in T.S. Variation In Elongation
TYPE A Max. ± 20% Max. ± 20%
TYPE C Max. ± 25% Max. ± 35%
TYPE ST1 Max. ± 20% Max. ± 20%
TYPE ST2 Max. ± 25% Max. ± 25%
TYPE ST2 with FR/FRLS Max. ± 25% Max. ± 25%
XLPE Max. ± 25% Max. ± 25%
Material Set Temperature Duration of Test
TYPE A 80±2 °C 7 Days
TYPE C 135±2 °C 7 Days
TYPE ST1 80±2 °C 7 Days
TYPE ST2 100±2 °C 7 Days
TYPE ST2 with FR/FRLS 100±2 °C 7 Days
XLPE 135±2 °C 7 Days
© LANCO Group, All Rights Reserved
Thermal Stability Test:
• IS : 5831-1984
• Digital Temperature Controller
• Temp.: 200°C
• Time: 40 Minutes
• PH paper color changes
Type of Material Test Duration
TYPE A, FRLS, PVC 80 minutes( min.)
TYPE C 100 minutes( min.)
TYPE ST1, FRLS 40 minutes( min.)
TYPE ST2, FRLS 80 minutes( min.)
© LANCO Group, All Rights Reserved
Cross Talk/Attenuation Test:
• LF Source & Selective Level Meter
• Frequency is set at 800Hz, Voltage = 10mV
• Attenuation = 20 log10[Vmax/Vmin]; dB
• It should be ≤ 1.2 dB(max.)
• Cross Talk ≥ 60 dB(min.)
© LANCO Group, All Rights Reserved
Annealing Test:
• Test Sample: L1 = 250 mm marked
• %age = [(L2 – L1)/ L1] x 100
• Annealing Test for conductor must be min. 18%
• Ex: L1 : 250, L2 : 310
24%
© LANCO Group, All Rights Reserved
Volume Resistivity Test/Water Immersion Test:
• IS: 10810 Part-45
• VR is tested at ambient temp. and at rated temp. of 70°C
• Voltage = 500V
• Test Sample, L = 3.5 mtrs
• VR = [observed resistivity x 2∏ x L x e⁸]/ log(core dia./conductor dia.); MΩ-cm
Material At ambient temp.(27°C) At rated temp.(70°C)
PVC Type A Min. 1 x 10^13 Ω-cm Min. 1 x 10^10 Ω-cm at 70°C
PVC Type A, FRLS Min. 1 x 10^13 Ω-cm Min. 1 x 10^10 Ω-cm at 70°C
PVC Type C Min. 1 x 10^13 Ω-cm Min. 1 x 10^10 Ω-cm at 85°C
XLPE Min. 1 x 10^14 Ω-cm Min. 1 x 10^12 Ω-cm at 90°C
LDPE Min. 1 x 10^15 Ω-cm Min. 1 x 10^12 Ω-cm at 70°C
© LANCO Group, All Rights Reserved
Smoke Density Test:
• ASTM D 2843
• Smoke Density test apparatus
• Pressure gauge pointer
• Gas flow at 40 psi or 2.8 kg/cm²
• % of light absorbed at 15 sec interval for 4 minutes ie 16 values.
• Rating = [ (Sum of 1 to 15 values) x 2 + 16th value] / 32 in %
• 60% for FRLS PVC (max.)
• 20% for ZHFR (max.)
• Vdc = 5.8V
• Ex: For a sample, the absorption % is as follows:
1 min : 14%
2 min : 28%
3 min : 31%
4 min : 29%
© LANCO Group, All Rights Reserved
Swedish chimney/Flame Retardant Test:
• IS: 10810 Part-61 & SS 424-1475 F3
• Specimen Length: 850 mm and ext. dia. should not exceed 35
mm
• Stop watch
• Unaffected portion from top shall be min. 300mm
• Ex: Test Sample Dia, D =20 mm
Ethanol Qty(ml) = Time(min) x 20 = [1+D/5] x 20
= 100 ml
Total Length = 850 mm; Undamaged sample after test= 610 mm
© LANCO Group, All Rights Reserved
Oxygen Index Test/ Temperature Index Test:
• ASTM D 2863
• Oxygen is 100% and N2 is 0%
• Flame is inserted
• OI = 29%(min.) and Temp. : 30°C;
• At 32, 32.5, +0.5°C likewise increases it.
• TI, at 50°C, 80°C
• TI = 250°C(min.)
© LANCO Group, All Rights Reserved
Flammability:
• IEC: 332 Part-3
• Ladder length : 4 meters
• Cable length : 2.5 meters
• Time : 20 minutes
• LPG flow: 0.25 kg/cm²
• Air flow: 2.4 kg/cm²
• Sample Result: 1.35 mtrs burned
© LANCO Group, All Rights Reserved
Acid gas generation test:
• IEC: 60754-Part I
• Test Sample: 1 gms
• Electronic Balance
• Digital Temp. Controller
• Pressure air flow meter
Procedure:
• 4 gm NaOH+ 1 ltrs distill water is made
• 440ml soln of NaOH is made.
• 200ml soln is taken out seperately.(Original Sample)
• One sample is put at 800°C for 40 minutes (Test Sample)
© LANCO Group, All Rights Reserved
Acid gas generation test: continued
Titration:
• 200ml soln. of each is taken out from 440ml NaOH+ 1000ml distill water
• 4ml Nitric Acid is added in both samples
• 3ml Nitro Benzene(C6H5NO2) is added in both samples
• 20ml AgNO3 is added in both samples
• 1ml (40% ferric ammonium) is added in both samples
• 0.1 M Ammonium Tryo Cyanate, NH4CNS (50ml) filled in burate
• Now, original sample is stirred, and burate valve is opened.
• Original Soln. color changes at X ml and Test soln. color changes at X+Y ml
• % of HCL can be max. 20 in mg/g
© LANCO Group, All Rights Reserved
Acid gas generation test: continued
• Ex: Cable: 3C x 16 sq.mm
• Test Sample: 1.0071 gms
• Original Soln.: 23ml & Test Soln.: 37ml
• HCL % = 3.65 x 0.1 x (B-T) x (1000/200)/Weight of test sample
= 3.65 x 0.1 x (23-14) x (1000/200)/ 1.0071
= 16.30 %
© LANCO Group, All Rights Reserved
ART: Anti rodent & termite repulsion test:
• IS : 5831-1984
• Ash of cable is taken.
• Sodium Sulphide flakes(fused), Na2S.xH2O are mixed with distill water in
other bowl.
• Ammonium Acetate soln. + Distill water + Ash all the three are put in oven
for 10 minutes at 80 °C
• After 10 minutes, sample is filtered and mixed with H2SO4.
• We get brown spots, it means Lead is present in the given sample.
© LANCO Group, All Rights Reserved
Important Cable Testing Standards:
• IS 5831: PVC Compound
• BS 7655: ZHFR
• IS 8784, IEC 60584-1&3, ANSI MC 96.1: TC Cables
• IS 10810: Methods of tests for cables
• BS 5308-I&II : L/R Ratio
• BS 5308P2, IS 10810P5: Drain wire test
• IS 5831, IS 10810P60: Thermal Stability
• ASTM D 2863: Oxygen Index & Temp. Index Test
• ASTM D 2843: Smoke Density Test
• IEC-60754P1: HCL gas test
• IS 10810P62, IEC 332P3: Flame Retardance Test for bunch of cables
• IS 10810P61 & SS 424-1475: Swedish Chimney Test
• IEC 332P1: Flammability Test
• IEC 60331: Fire Survival Test
• IS 10810P12: Shrinkage Test
• IS 10810P10: Loss of mass
• IS 10810P14: Hot shock Test
Data Sheets
Test Certificates
© LANCO Group, All Rights Reserved
PK
p.khandelwal@lancogroup.com
9/14/2015 12:12 AM

Más contenido relacionado

La actualidad más candente

Principles of Cable Selection
Principles of Cable SelectionPrinciples of Cable Selection
Principles of Cable SelectionLeonardo ENERGY
 
Power cable selection, cable selection Methodology
Power cable selection, cable selection Methodology Power cable selection, cable selection Methodology
Power cable selection, cable selection Methodology wessam alaslmi
 
Earthing and bonding - Power cables
Earthing and bonding - Power cablesEarthing and bonding - Power cables
Earthing and bonding - Power cablesLeonardo ENERGY
 
Design and construction of underground cable transmission line
Design and construction of underground cable transmission lineDesign and construction of underground cable transmission line
Design and construction of underground cable transmission lineFazlur Rahman
 
UNDERGROUND CABLES PRESENTATION
UNDERGROUND CABLES  PRESENTATIONUNDERGROUND CABLES  PRESENTATION
UNDERGROUND CABLES PRESENTATIONPANKAJ KUMAR
 
Underground cables
Underground cablesUnderground cables
Underground cablesAnu71
 
Sf6 circuit breakers
Sf6 circuit breakersSf6 circuit breakers
Sf6 circuit breakersjawaharramaya
 
Overhead line work ppt
Overhead line work pptOverhead line work ppt
Overhead line work pptDemsew Mitiku
 
Types of cables
Types of cables Types of cables
Types of cables Nisarg Amin
 
Get Complete Information about Circuit Breaker
Get Complete Information about Circuit BreakerGet Complete Information about Circuit Breaker
Get Complete Information about Circuit BreakerSystem Protection
 
Types of wires and cables ic
Types of wires and cables icTypes of wires and cables ic
Types of wires and cables icVishal Patel
 
Installation Operation & Maintenance of 33kV & 11kV Switchgear
Installation   Operation & Maintenance of 33kV & 11kV SwitchgearInstallation   Operation & Maintenance of 33kV & 11kV Switchgear
Installation Operation & Maintenance of 33kV & 11kV SwitchgearSheikh Nazmul Islam
 
UNIT - 06 TRANSMISSION LINES AND SUBSTATIONS
UNIT - 06 TRANSMISSION LINES AND SUBSTATIONSUNIT - 06 TRANSMISSION LINES AND SUBSTATIONS
UNIT - 06 TRANSMISSION LINES AND SUBSTATIONSPremanandDesai
 
Presentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformerPresentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformerSMDDTech
 

La actualidad más candente (20)

Underground cables
Underground cablesUnderground cables
Underground cables
 
Basics of Wires and Cables
Basics of Wires and CablesBasics of Wires and Cables
Basics of Wires and Cables
 
Types of cables
Types of cablesTypes of cables
Types of cables
 
Principles of Cable Selection
Principles of Cable SelectionPrinciples of Cable Selection
Principles of Cable Selection
 
Power cable selection, cable selection Methodology
Power cable selection, cable selection Methodology Power cable selection, cable selection Methodology
Power cable selection, cable selection Methodology
 
Earthing and bonding - Power cables
Earthing and bonding - Power cablesEarthing and bonding - Power cables
Earthing and bonding - Power cables
 
Design and construction of underground cable transmission line
Design and construction of underground cable transmission lineDesign and construction of underground cable transmission line
Design and construction of underground cable transmission line
 
Underground cables (1)
Underground cables  (1)Underground cables  (1)
Underground cables (1)
 
UNDERGROUND CABLES PRESENTATION
UNDERGROUND CABLES  PRESENTATIONUNDERGROUND CABLES  PRESENTATION
UNDERGROUND CABLES PRESENTATION
 
Power cables
Power cablesPower cables
Power cables
 
Underground cables
Underground cablesUnderground cables
Underground cables
 
Sf6 circuit breakers
Sf6 circuit breakersSf6 circuit breakers
Sf6 circuit breakers
 
Overhead line work ppt
Overhead line work pptOverhead line work ppt
Overhead line work ppt
 
Types of cables
Types of cables Types of cables
Types of cables
 
Get Complete Information about Circuit Breaker
Get Complete Information about Circuit BreakerGet Complete Information about Circuit Breaker
Get Complete Information about Circuit Breaker
 
Types of wires and cables ic
Types of wires and cables icTypes of wires and cables ic
Types of wires and cables ic
 
Installation Operation & Maintenance of 33kV & 11kV Switchgear
Installation   Operation & Maintenance of 33kV & 11kV SwitchgearInstallation   Operation & Maintenance of 33kV & 11kV Switchgear
Installation Operation & Maintenance of 33kV & 11kV Switchgear
 
UNIT - 06 TRANSMISSION LINES AND SUBSTATIONS
UNIT - 06 TRANSMISSION LINES AND SUBSTATIONSUNIT - 06 TRANSMISSION LINES AND SUBSTATIONS
UNIT - 06 TRANSMISSION LINES AND SUBSTATIONS
 
Presentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformerPresentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformer
 
Power cables
Power cablesPower cables
Power cables
 

Destacado

Testing Of Instrumentation Cable
Testing Of Instrumentation CableTesting Of Instrumentation Cable
Testing Of Instrumentation CableSHIVAJI CHOUDHURY
 
Insulation testing of power cable
Insulation testing of power cableInsulation testing of power cable
Insulation testing of power cableSyed Atif Naseem
 
EE-55 Power Cables Testing & Fault Location
EE-55 Power Cables Testing & Fault LocationEE-55 Power Cables Testing & Fault Location
EE-55 Power Cables Testing & Fault LocationRina Florentes
 
cable testing and intallation
cable testing and intallationcable testing and intallation
cable testing and intallationmanishgoswami66
 
Heinputter 2
Heinputter 2Heinputter 2
Heinputter 2Thang Nd
 
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...Thorne & Derrick International
 
Seminar on Partial Discharge detection methods
Seminar on Partial Discharge detection methodsSeminar on Partial Discharge detection methods
Seminar on Partial Discharge detection methodsHarshit Bhandari
 
Partial Discharge Detection Products by EA Technology
Partial Discharge Detection Products by EA TechnologyPartial Discharge Detection Products by EA Technology
Partial Discharge Detection Products by EA TechnologyRyan McFallo
 
IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...
IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...
IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...Thorne & Derrick International
 
EE2353 / High Voltage Engineering - Testing of Cables
EE2353 / High Voltage Engineering - Testing of CablesEE2353 / High Voltage Engineering - Testing of Cables
EE2353 / High Voltage Engineering - Testing of CablesRajesh Ramesh
 
Precise kilometer calculation by underground cable fault detector
Precise kilometer calculation by underground cable fault detectorPrecise kilometer calculation by underground cable fault detector
Precise kilometer calculation by underground cable fault detectorvivekmv716
 
Basics of Automation, PLC and SCADA
Basics of Automation, PLC and SCADABasics of Automation, PLC and SCADA
Basics of Automation, PLC and SCADAIndira Kundu
 

Destacado (17)

Testing Of Instrumentation Cable
Testing Of Instrumentation CableTesting Of Instrumentation Cable
Testing Of Instrumentation Cable
 
Insulation testing of power cable
Insulation testing of power cableInsulation testing of power cable
Insulation testing of power cable
 
EE-55 Power Cables Testing & Fault Location
EE-55 Power Cables Testing & Fault LocationEE-55 Power Cables Testing & Fault Location
EE-55 Power Cables Testing & Fault Location
 
Hv Cable Testing
Hv Cable TestingHv Cable Testing
Hv Cable Testing
 
cable testing and intallation
cable testing and intallationcable testing and intallation
cable testing and intallation
 
Heinputter 2
Heinputter 2Heinputter 2
Heinputter 2
 
Deis talk-nov-2014-revised
Deis talk-nov-2014-revisedDeis talk-nov-2014-revised
Deis talk-nov-2014-revised
 
Basic Partial Discharge
Basic Partial DischargeBasic Partial Discharge
Basic Partial Discharge
 
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
 
Seminar on Partial Discharge detection methods
Seminar on Partial Discharge detection methodsSeminar on Partial Discharge detection methods
Seminar on Partial Discharge detection methods
 
Partial Discharge Detection Products by EA Technology
Partial Discharge Detection Products by EA TechnologyPartial Discharge Detection Products by EA Technology
Partial Discharge Detection Products by EA Technology
 
IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...
IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...
IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...
 
Joints and terminations
Joints and terminationsJoints and terminations
Joints and terminations
 
EE2353 / High Voltage Engineering - Testing of Cables
EE2353 / High Voltage Engineering - Testing of CablesEE2353 / High Voltage Engineering - Testing of Cables
EE2353 / High Voltage Engineering - Testing of Cables
 
Precise kilometer calculation by underground cable fault detector
Precise kilometer calculation by underground cable fault detectorPrecise kilometer calculation by underground cable fault detector
Precise kilometer calculation by underground cable fault detector
 
Cable and laying
Cable and layingCable and laying
Cable and laying
 
Basics of Automation, PLC and SCADA
Basics of Automation, PLC and SCADABasics of Automation, PLC and SCADA
Basics of Automation, PLC and SCADA
 

Similar a C&I Cables Tests

KEMET Webinar -C44U_C44P-R Power Can Film Capacitors
KEMET Webinar -C44U_C44P-R Power Can Film CapacitorsKEMET Webinar -C44U_C44P-R Power Can Film Capacitors
KEMET Webinar -C44U_C44P-R Power Can Film CapacitorsIvana Ivanovska
 
PPT on Mdpe inspection.pptx
PPT on Mdpe inspection.pptxPPT on Mdpe inspection.pptx
PPT on Mdpe inspection.pptxHimanshu Shukla
 
ORGANIC COATINGS FOR CORROSION PROTECTION OF TRANSFORMERS IN UNDERGROUND CHAM...
ORGANIC COATINGS FOR CORROSION PROTECTION OF TRANSFORMERS IN UNDERGROUND CHAM...ORGANIC COATINGS FOR CORROSION PROTECTION OF TRANSFORMERS IN UNDERGROUND CHAM...
ORGANIC COATINGS FOR CORROSION PROTECTION OF TRANSFORMERS IN UNDERGROUND CHAM...Adriana de Araujo
 
Explosion Proof Continuous Vertical Liquid Level Sensor (LVCS-FP)
Explosion Proof Continuous Vertical Liquid Level Sensor (LVCS-FP)Explosion Proof Continuous Vertical Liquid Level Sensor (LVCS-FP)
Explosion Proof Continuous Vertical Liquid Level Sensor (LVCS-FP)Thorne & Derrick International
 
Dynasonics dfx datasheet badger meter doppler ultrasonic flow meter
Dynasonics dfx datasheet badger meter doppler ultrasonic flow meterDynasonics dfx datasheet badger meter doppler ultrasonic flow meter
Dynasonics dfx datasheet badger meter doppler ultrasonic flow meterENVIMART
 
Drager Polytron 5000 Fixed Gas Detector - Spec Sheet
Drager Polytron 5000 Fixed Gas Detector - Spec SheetDrager Polytron 5000 Fixed Gas Detector - Spec Sheet
Drager Polytron 5000 Fixed Gas Detector - Spec SheetThorne & Derrick UK
 
Fujikura mechanical splicer
Fujikura mechanical splicerFujikura mechanical splicer
Fujikura mechanical splicerAgus Riyadi
 
Explosion Proof/Flame Proof (Ex D) Sensors for Hazardous Area Now Available i...
Explosion Proof/Flame Proof (Ex D) Sensors for Hazardous Area Now Available i...Explosion Proof/Flame Proof (Ex D) Sensors for Hazardous Area Now Available i...
Explosion Proof/Flame Proof (Ex D) Sensors for Hazardous Area Now Available i...Ives Equipment
 
Анализатор LGA 4000
Анализатор LGA 4000Анализатор LGA 4000
Анализатор LGA 4000СокТрейд
 
Stator Resistance Temperature Detector (RTD) Catalog
Stator Resistance Temperature Detector (RTD) CatalogStator Resistance Temperature Detector (RTD) Catalog
Stator Resistance Temperature Detector (RTD) CatalogDakshesh Shah
 
Stator Resistance Temperature Detector (RTD) - Catalog
Stator Resistance Temperature Detector (RTD) - CatalogStator Resistance Temperature Detector (RTD) - Catalog
Stator Resistance Temperature Detector (RTD) - CatalogHiren Panchal
 
Box DC Link in industrial and automotive applications
Box DC Link in industrial and automotive applicationsBox DC Link in industrial and automotive applications
Box DC Link in industrial and automotive applicationsKEMET Electronics Corporation
 
Mill-Pro-XS-hot-cure-LongKey-process-Jan-2014-rev2
Mill-Pro-XS-hot-cure-LongKey-process-Jan-2014-rev2Mill-Pro-XS-hot-cure-LongKey-process-Jan-2014-rev2
Mill-Pro-XS-hot-cure-LongKey-process-Jan-2014-rev2Daniel Chen
 

Similar a C&I Cables Tests (20)

KEMET Webinar -C44U_C44P-R Power Can Film Capacitors
KEMET Webinar -C44U_C44P-R Power Can Film CapacitorsKEMET Webinar -C44U_C44P-R Power Can Film Capacitors
KEMET Webinar -C44U_C44P-R Power Can Film Capacitors
 
PPT on Mdpe inspection.pptx
PPT on Mdpe inspection.pptxPPT on Mdpe inspection.pptx
PPT on Mdpe inspection.pptx
 
P 3_Spain_ACF-NT_Hbl_01.ppt
P 3_Spain_ACF-NT_Hbl_01.pptP 3_Spain_ACF-NT_Hbl_01.ppt
P 3_Spain_ACF-NT_Hbl_01.ppt
 
ORGANIC COATINGS FOR CORROSION PROTECTION OF TRANSFORMERS IN UNDERGROUND CHAM...
ORGANIC COATINGS FOR CORROSION PROTECTION OF TRANSFORMERS IN UNDERGROUND CHAM...ORGANIC COATINGS FOR CORROSION PROTECTION OF TRANSFORMERS IN UNDERGROUND CHAM...
ORGANIC COATINGS FOR CORROSION PROTECTION OF TRANSFORMERS IN UNDERGROUND CHAM...
 
Explosion Proof Continuous Vertical Liquid Level Sensor (LVCS-FP)
Explosion Proof Continuous Vertical Liquid Level Sensor (LVCS-FP)Explosion Proof Continuous Vertical Liquid Level Sensor (LVCS-FP)
Explosion Proof Continuous Vertical Liquid Level Sensor (LVCS-FP)
 
Dynasonics dfx datasheet badger meter doppler ultrasonic flow meter
Dynasonics dfx datasheet badger meter doppler ultrasonic flow meterDynasonics dfx datasheet badger meter doppler ultrasonic flow meter
Dynasonics dfx datasheet badger meter doppler ultrasonic flow meter
 
Drager Polytron 5000 Fixed Gas Detector - Spec Sheet
Drager Polytron 5000 Fixed Gas Detector - Spec SheetDrager Polytron 5000 Fixed Gas Detector - Spec Sheet
Drager Polytron 5000 Fixed Gas Detector - Spec Sheet
 
Fujikura mechanical splicer
Fujikura mechanical splicerFujikura mechanical splicer
Fujikura mechanical splicer
 
Pittcon 2002
Pittcon 2002Pittcon 2002
Pittcon 2002
 
Explosion Proof/Flame Proof (Ex D) Sensors for Hazardous Area Now Available i...
Explosion Proof/Flame Proof (Ex D) Sensors for Hazardous Area Now Available i...Explosion Proof/Flame Proof (Ex D) Sensors for Hazardous Area Now Available i...
Explosion Proof/Flame Proof (Ex D) Sensors for Hazardous Area Now Available i...
 
M Morales Sealed Rpcs
M Morales Sealed RpcsM Morales Sealed Rpcs
M Morales Sealed Rpcs
 
M Morales Sealed Rpcs
M Morales Sealed RpcsM Morales Sealed Rpcs
M Morales Sealed Rpcs
 
Анализатор LGA 4000
Анализатор LGA 4000Анализатор LGA 4000
Анализатор LGA 4000
 
Stator Resistance Temperature Detector (RTD) Catalog
Stator Resistance Temperature Detector (RTD) CatalogStator Resistance Temperature Detector (RTD) Catalog
Stator Resistance Temperature Detector (RTD) Catalog
 
Stator Resistance Temperature Detector (RTD) - Catalog
Stator Resistance Temperature Detector (RTD) - CatalogStator Resistance Temperature Detector (RTD) - Catalog
Stator Resistance Temperature Detector (RTD) - Catalog
 
Box DC Link in industrial and automotive applications
Box DC Link in industrial and automotive applicationsBox DC Link in industrial and automotive applications
Box DC Link in industrial and automotive applications
 
Crowcon T3 Gas Detector
Crowcon T3 Gas DetectorCrowcon T3 Gas Detector
Crowcon T3 Gas Detector
 
TRANSISTORES
TRANSISTORESTRANSISTORES
TRANSISTORES
 
Mill-Pro-XS-hot-cure-LongKey-process-Jan-2014-rev2
Mill-Pro-XS-hot-cure-LongKey-process-Jan-2014-rev2Mill-Pro-XS-hot-cure-LongKey-process-Jan-2014-rev2
Mill-Pro-XS-hot-cure-LongKey-process-Jan-2014-rev2
 
KEMET EMC Filters
KEMET EMC FiltersKEMET EMC Filters
KEMET EMC Filters
 

C&I Cables Tests

  • 1. © LANCO Group, All Rights Reserved© LANCO Group, All Rights Reserved POWEREPC INFRASTRUCTURESOLAR RESOURCES Lanco Babandh Power Ltd (C&I Cables Testing Methods) PRATYUSHA KHANDELWAL Source : Thermo Cables Limited, Hyderabad: 19.Nov.2012-23.Nov.2012
  • 2. © LANCO Group, All Rights Reserved Types of Cables: • Power Cables/Control Cables • Instrument/TC/Signal Cables Note: Only Instrument cables have drain wires
  • 3. © LANCO Group, All Rights Reserved Material used in Cables: • TYPE: Y13 = Conductor Insulation(VDE 0207PT4) • TYPE: A = Conductor Insulation • XLPE = Conductor Insulation • TYPE: YM1 = Inner Sheath (VDE 0207PT5) • ST1 = Outer Sheath • ST2 = Outer Sheath *Note: Credentials validity must be up to 5 yrs approved by CPRI/NABL/NTH etc
  • 4. © LANCO Group, All Rights Reserved Nomenclature: Ex: 3C/P/T/Q 16 SQ MM 1100V FRLS TCL 2012 315M Job ID: XXXXXX Customer No. DVWS Job No./ASC: 303468 Size: 8P x 0.5 sq.mm DRM No. 1004883 QTY: 465 M *ASC= Armoured Screen Cable
  • 5. © LANCO Group, All Rights Reserved Tests for Cables: Type/Routine Tests: (100% of the given lot) 1) HV Test/High Pot. Test 2) Conductor Resistance Test 3) Drain Wire Resistance Test 4) Insulation Resistance Test
  • 6. © LANCO Group, All Rights Reserved Tests for Cables: Acceptance Tests: (10% of offered lot of each cable size as applicable) 1) Construction detail verification(Conductor/Insulation system/ Pairing/ Laying/Pair/Overall Shielding/Inner sheathing /Armoring/Outer sheathing) 2) Conductor Resistance Test 3) Capacitance, Inductance & L/R Ratio Test 4) Tensile strength and elongation at break for insulation and sheath before and after ageing 5) Thermal Stability Test 6) Cross Talk/Attenuation Test 7) Insulation Resistance measurement 8) Insulation thickness measurement 9) Color identification of cores 10) Annealing Test 11) Volume Resistivity Test 12) Hot Deformation Test
  • 7. © LANCO Group, All Rights Reserved Acceptance Tests: FRLS & ART: 1) Oxygen Index Test. 2) Temperature Index Test. 3) Smoke Density Test. 4) Flammability. 5) Swedish chimney/Flame Retardant Test. 6) Acid gas generation test. 7) Anti rodent test.
  • 8. © LANCO Group, All Rights Reserved HV Test: IS : 10810 Part 45 • HV Tester • ForControlCables: 3kV ACrms for 5 minutes(C-C) 3kV ACrms for 5 minutes(C-Armour) • ForTC/InstrumentCables: 1kV ACrms for 1 minutes(C-C) 1kV ACrms for 1 minutes(C-Screen) *Note: Drain wires are only present in Instrument cables
  • 9. © LANCO Group, All Rights Reserved Conductor Resistance & Drain Wire Resistance Test: • BS: 5308 Part-2 • IS: 10810 Part-5 • Digital Ohm Meter • Probe Calibration Test- 0.0 at NTP • At 20°C, R= [Rx.k.1000/L]; Ω/km [max. 36.6] where, k= 250/(230+T) *Drain wire: 30 Ω,max /Conductor Wire: 36.6 Ω,max
  • 10. © LANCO Group, All Rights Reserved Insulation Resistance Test: • IS: 10810 Part-43 • Insulation Tester • IRconstant = LxR/[1000Log10(D/d)]; MΩ-km • Min. 100MΩ/km • C-C • C-Shield • Insulation • L/R
  • 11. © LANCO Group, All Rights Reserved Capacitance, Inductance & L/R Ratio Test: • BS: 5308 – I & II • Digital LCR Q Meter • Frequency is set at 1kHz • OC & SC test is done • Capacitance b/w cores= Cc x 1000/L in nf/km [max. 250] • Capacitance b/w core to shield + armor = Cs x 1000/L in nf/km [max. 400] • Inductance = L x 1000 x 1000/L in mH/km [max. 1] • L/R = obs. Inductance/loop resistance; µH/Ω [max. 25]
  • 12. © LANCO Group, All Rights Reserved continued… PARAMETER PVC INSULATION XLPE/LDPE INSULATION Capacitance b/w cores Max. 250 nf/km Max. 100 nf/km Capacitance b/w core-shield Max. 400 nf/km Max. 400 nf/km Inductance for signal cables Max.1mH/km Max.1mH/km Inductance for TC cables Max. 4mH/km Max. 4mH/km L/R ratio up to 1 mm² Max. 25µH/Ω Max. 25µH/Ω L/R ratio 1- 1.5 mm² Max. 40µH/Ω Max. 40µH/Ω L/R ratio 2.5 mm² Max. 50µH/Ω Max. 50µH/Ω
  • 13. © LANCO Group, All Rights Reserved Ageing Test: • IS: 10810 Part-11 • Tensile strength and elongation at break for insulation and sheath before and after ageing is done. • 7 Days test at specific temp. of 80°C, 100°C etc • Sheath-dumb-bell shape & Insulation-tubular shape; each sample of ≥ 100mm is taken. • 20 mm marking is done on each test sample and tested at 50kg wt. tensile & elongation tester. • Tubular Cross sectional Area, A = ∏/4[ D² – d²]; mm² • Dumb-bell Cross sectional Area, A = width x thickness; mm² • T.S. = BL x 9.8/ A; N/mm² • % Elongation = [L-L0]/L0 x 100 in % • Variation in T.S. = [TS0 – TSx]/TS0 x 100 in % • Variation in Elongation = [EL0- ELx]/EL0 x 100 in % Note: BL at fractured point shall not be greater than 250 mm/min. Material T.S. % Elongation PVC 12.5 N/mm² min. Min. 150 % LDPE 10 N/mm² min. Min. 300% XLPE 12.5N/mm² min. Min. 200%
  • 14. © LANCO Group, All Rights Reserved Ageing Test: continued… Material Variation in T.S. Variation In Elongation TYPE A Max. ± 20% Max. ± 20% TYPE C Max. ± 25% Max. ± 35% TYPE ST1 Max. ± 20% Max. ± 20% TYPE ST2 Max. ± 25% Max. ± 25% TYPE ST2 with FR/FRLS Max. ± 25% Max. ± 25% XLPE Max. ± 25% Max. ± 25% Material Set Temperature Duration of Test TYPE A 80±2 °C 7 Days TYPE C 135±2 °C 7 Days TYPE ST1 80±2 °C 7 Days TYPE ST2 100±2 °C 7 Days TYPE ST2 with FR/FRLS 100±2 °C 7 Days XLPE 135±2 °C 7 Days
  • 15. © LANCO Group, All Rights Reserved Thermal Stability Test: • IS : 5831-1984 • Digital Temperature Controller • Temp.: 200°C • Time: 40 Minutes • PH paper color changes Type of Material Test Duration TYPE A, FRLS, PVC 80 minutes( min.) TYPE C 100 minutes( min.) TYPE ST1, FRLS 40 minutes( min.) TYPE ST2, FRLS 80 minutes( min.)
  • 16. © LANCO Group, All Rights Reserved Cross Talk/Attenuation Test: • LF Source & Selective Level Meter • Frequency is set at 800Hz, Voltage = 10mV • Attenuation = 20 log10[Vmax/Vmin]; dB • It should be ≤ 1.2 dB(max.) • Cross Talk ≥ 60 dB(min.)
  • 17. © LANCO Group, All Rights Reserved Annealing Test: • Test Sample: L1 = 250 mm marked • %age = [(L2 – L1)/ L1] x 100 • Annealing Test for conductor must be min. 18% • Ex: L1 : 250, L2 : 310 24%
  • 18. © LANCO Group, All Rights Reserved Volume Resistivity Test/Water Immersion Test: • IS: 10810 Part-45 • VR is tested at ambient temp. and at rated temp. of 70°C • Voltage = 500V • Test Sample, L = 3.5 mtrs • VR = [observed resistivity x 2∏ x L x e⁸]/ log(core dia./conductor dia.); MΩ-cm Material At ambient temp.(27°C) At rated temp.(70°C) PVC Type A Min. 1 x 10^13 Ω-cm Min. 1 x 10^10 Ω-cm at 70°C PVC Type A, FRLS Min. 1 x 10^13 Ω-cm Min. 1 x 10^10 Ω-cm at 70°C PVC Type C Min. 1 x 10^13 Ω-cm Min. 1 x 10^10 Ω-cm at 85°C XLPE Min. 1 x 10^14 Ω-cm Min. 1 x 10^12 Ω-cm at 90°C LDPE Min. 1 x 10^15 Ω-cm Min. 1 x 10^12 Ω-cm at 70°C
  • 19. © LANCO Group, All Rights Reserved Smoke Density Test: • ASTM D 2843 • Smoke Density test apparatus • Pressure gauge pointer • Gas flow at 40 psi or 2.8 kg/cm² • % of light absorbed at 15 sec interval for 4 minutes ie 16 values. • Rating = [ (Sum of 1 to 15 values) x 2 + 16th value] / 32 in % • 60% for FRLS PVC (max.) • 20% for ZHFR (max.) • Vdc = 5.8V • Ex: For a sample, the absorption % is as follows: 1 min : 14% 2 min : 28% 3 min : 31% 4 min : 29%
  • 20. © LANCO Group, All Rights Reserved Swedish chimney/Flame Retardant Test: • IS: 10810 Part-61 & SS 424-1475 F3 • Specimen Length: 850 mm and ext. dia. should not exceed 35 mm • Stop watch • Unaffected portion from top shall be min. 300mm • Ex: Test Sample Dia, D =20 mm Ethanol Qty(ml) = Time(min) x 20 = [1+D/5] x 20 = 100 ml Total Length = 850 mm; Undamaged sample after test= 610 mm
  • 21. © LANCO Group, All Rights Reserved Oxygen Index Test/ Temperature Index Test: • ASTM D 2863 • Oxygen is 100% and N2 is 0% • Flame is inserted • OI = 29%(min.) and Temp. : 30°C; • At 32, 32.5, +0.5°C likewise increases it. • TI, at 50°C, 80°C • TI = 250°C(min.)
  • 22. © LANCO Group, All Rights Reserved Flammability: • IEC: 332 Part-3 • Ladder length : 4 meters • Cable length : 2.5 meters • Time : 20 minutes • LPG flow: 0.25 kg/cm² • Air flow: 2.4 kg/cm² • Sample Result: 1.35 mtrs burned
  • 23. © LANCO Group, All Rights Reserved Acid gas generation test: • IEC: 60754-Part I • Test Sample: 1 gms • Electronic Balance • Digital Temp. Controller • Pressure air flow meter Procedure: • 4 gm NaOH+ 1 ltrs distill water is made • 440ml soln of NaOH is made. • 200ml soln is taken out seperately.(Original Sample) • One sample is put at 800°C for 40 minutes (Test Sample)
  • 24. © LANCO Group, All Rights Reserved Acid gas generation test: continued Titration: • 200ml soln. of each is taken out from 440ml NaOH+ 1000ml distill water • 4ml Nitric Acid is added in both samples • 3ml Nitro Benzene(C6H5NO2) is added in both samples • 20ml AgNO3 is added in both samples • 1ml (40% ferric ammonium) is added in both samples • 0.1 M Ammonium Tryo Cyanate, NH4CNS (50ml) filled in burate • Now, original sample is stirred, and burate valve is opened. • Original Soln. color changes at X ml and Test soln. color changes at X+Y ml • % of HCL can be max. 20 in mg/g
  • 25. © LANCO Group, All Rights Reserved Acid gas generation test: continued • Ex: Cable: 3C x 16 sq.mm • Test Sample: 1.0071 gms • Original Soln.: 23ml & Test Soln.: 37ml • HCL % = 3.65 x 0.1 x (B-T) x (1000/200)/Weight of test sample = 3.65 x 0.1 x (23-14) x (1000/200)/ 1.0071 = 16.30 %
  • 26. © LANCO Group, All Rights Reserved ART: Anti rodent & termite repulsion test: • IS : 5831-1984 • Ash of cable is taken. • Sodium Sulphide flakes(fused), Na2S.xH2O are mixed with distill water in other bowl. • Ammonium Acetate soln. + Distill water + Ash all the three are put in oven for 10 minutes at 80 °C • After 10 minutes, sample is filtered and mixed with H2SO4. • We get brown spots, it means Lead is present in the given sample.
  • 27. © LANCO Group, All Rights Reserved Important Cable Testing Standards: • IS 5831: PVC Compound • BS 7655: ZHFR • IS 8784, IEC 60584-1&3, ANSI MC 96.1: TC Cables • IS 10810: Methods of tests for cables • BS 5308-I&II : L/R Ratio • BS 5308P2, IS 10810P5: Drain wire test • IS 5831, IS 10810P60: Thermal Stability • ASTM D 2863: Oxygen Index & Temp. Index Test • ASTM D 2843: Smoke Density Test • IEC-60754P1: HCL gas test • IS 10810P62, IEC 332P3: Flame Retardance Test for bunch of cables • IS 10810P61 & SS 424-1475: Swedish Chimney Test • IEC 332P1: Flammability Test • IEC 60331: Fire Survival Test • IS 10810P12: Shrinkage Test • IS 10810P10: Loss of mass • IS 10810P14: Hot shock Test Data Sheets Test Certificates
  • 28. © LANCO Group, All Rights Reserved PK p.khandelwal@lancogroup.com 9/14/2015 12:12 AM