3. Objectives :
During the Fault conditions, the
Relays will identify the faulty area and
will isolate the Unhealthy section from
the network.
Ex : Motor Protection, Generator
Protection, Bus Protection,
Line Protection…
4. Protective Relaying
Primary Relaying( Main Protection):
Main relay to operate in the event
of faults
Secondary Relaying ( Backup Prot) :
If main relay fails to operate, these
relays will operate and clear the fault.
These relays are generally of time delay and
cause more disturbance to the system
6. Protective Relaying
Relays Requires any of the following
Quantities to operate:
Magnitude ie. Current / Voltage / Power
Frequency ie. Under Freq / Over freq
Phase Angle
Duration ie. Timers
Rate of Change ie. df/dt, dZ/dt
Direction ie. Directional O/C
Harmonics ie. 3rd harmonic
8. Basic Relays
Current Relays
Instantaneous Over Current Relays
Definite Time Over Current Relay
Inverse Definite Over Current Relay
Voltage Relays
Under Voltage Relays
Over Voltage Relays
Impedance Relays
Reactance Relays
Differential Relays
9. Instantaneous Over Current Relay
This Relay operates when ever the
current exceeds the Set value
Application : Generator Inter turn,
GT Restricted E/F prot.
Example : CAG Relay of EE make
10. Definite Time Over Current Relay
This Relay operates when ever the
current exceeds the Set value and
that current shall persist for
defined time
Application : Blocked Rotor
Protection, Over Load Alarm
etc..
Example : CTU Relay of EE make
&
Operation
Current Time
11. Inverse Definite Time Over Current Relay
t
Current
This Relay operates when
ever the current exceeds
the Set value. The relay
operation time is
inversely proportional to
the magnitude of Current
Application: GT Standby
E/F prot., LT Motor
Prot.
Example : CDG Relay of EE
make
12. Over Voltage Relay
Whenever the Voltage exceeds the
set value, the relay operates.
Application : Generator Over Voltage
Protection.
Example : VAG of EE make
13. Under Voltage Relay
Whenever the Voltage falls below the
set value, the relay operates.
Application : Bus Under Voltage
Protection.
Example : VAGM of EE make
14. Impedance Relays
These relays are uses MHO principle.
If the Impedance is less than the Set
Value, the Relay operates. These
Relays are Under Impedance Relays
Application: Line Protection,
Generator B/U Prot.
Ex : YCG Relays of EE Make
16. Reactance Relays
If the Reactance is less than the Set
Value, the Relay operates. Generally,
these Relays are Under Reactance
Relays
Application: Line Protection,
Ex : XCG Relays of EE Make
18. Differential Relays
If there is any difference of currents,
the relay operates.
Application :
Transformer Differential
Generator Differential
Bus Bar Differential ….
Ex : ALSTOM Make DTH Relays