Secure Power design considerations
Confidential Property of Schneider Electric |
Summary
Page 2Confidential Property of Schneider Electric |
1 Introduction
2 How do we ensure reliable power..?
3 How can we reduce these risk?
4 UPS Topologies
5 Installation considerations
6 UPS Architectures
7 Multi- mode - operation
8 Energy Storage
UPS range9
More
ELECTRIC
Increase by 50% in the
next 25 years
More
CONNECTED
Connect 50bn devices
by 2020
More
DISTRIBUTED
Solar PV and Storage to
Account for ~50% of new capacity
additions by 2030
More
EFFICIENT
Still.. 2/3 energy efficiency
potential.. remains untapped .!!
Our World Will Be…
Back to index
Mining (Metals & Minerals)
Water & Wastewater
Datacenter
Healthcare
Oil and Gas
Building
No matter the type of business… reliable power is essential
Confidential Property of Schneider Electric | Page 5
Confidential Property of Schneider Electric |
How do we ensure reliable
power..?
Heavy
Industry
Commercial
& Industrial
Industry
Buildings
Data Centres
Residential
Infrastructure
EHV/HV
Centralised
Generation
HV/MV Substation
(Primary substation)
Switching
Substation
MV/MV
Heavy
Industry
MV / LV
Substation
Connexion to
HV network
Connexion to
MV network
ConsumersEnergy Producers Utility Transmission Utility Distribution
Heavy
Industry
Commercial
& Industrial
Industry
Buildings
Data Centres
Residential
Infrastructure
EHV/HV
Centralised
Generation
HV/MV Substation
(Primary substation)
Switching
Substation
MV/MV
Heavy
Industry
MV / LV
Substation
Connexion to
HV network
Connexion to
MV network
ConsumersEnergy Producers Utility Transmission Utility Distribution
Power failure, Voltage spikes,
Under voltage, Frequency variations
Harmonics,
Power Factor
Disturbances
Voltage variations
Frequency variations
Micro outages
Long outages
Confidential Property of Schneider Electric | Page 8
Confidential Property of Schneider Electric |
How can we reduce these risk?
- Power failure
- Voltage spikes
- Under voltage
- Frequency variations
UPS - “Uninterruptible Power
Supply”
Page 9Confidential Property of Schneider Electric |
PFC
Rectifier
UPS
AC: Alternating Current
DC: Direct Current
PFC: Power Factor Correction
What is a “UPS” & what is the
purpose of a UPS?
Main functions of a UPS:
“Uninterruptible Power Supply”
•Short term backup (Batteries)
•Input current conditioned by the PFC
•Output Voltage conditioned by the Inverter
•Isolation / Protection against:
• Voltage spikes
• Over voltage
• Under voltage
• Frequency variations
• Harmonics
• Power Factor
Heavy
Industry
Commercial
& Industrial
Industry
Buildings
Data Centres
Residential
Infrastructure
EHV/HV
Centralised
Generation
HV/MV Substation
(Primary substation)
Switching
Substation
MV/MV
Heavy
Industry
MV / LV
Substation
Connexion to
HV network
Connexion to
MV network
Energy Producers Utility Transmission Utility Distribution
Power failure, Voltage spikes,
Under voltage, Frequency variations
Harmonics,
Power Factor
UPS Consumers
Heavy
Industry
Commercial
& Industrial
Industry
Buildings
Data Centres
Residential
Infrastructure
EHV/HV
Centralised
Generation
HV/MV Substation
(Primary substation)
Switching
Substation
MV/MV
Heavy
Industry
MV / LV
Substation
Connexion to
HV network
Connexion to
MV network
Energy Producers Utility Transmission Utility Distribution
Power failure, Voltage spikes,
Under voltage, Frequency variations
Harmonics,
Power Factor
Power
Grid
Customer
Grid
UPS Consumers
Reliable &
safe Power
Harmonics created by the
load is reduced by the UPS
UPS ON
UPS Topologies
Page 13Confidential Property of Schneider Electric |
- The simplest solution, used for applications that support a cut of 4 to 10ms when detecting the fault of the
source and transfer to the battery
- This technology is for low powers (Apparent Power: 330 VA – 900 VA)
- This solution is inexpensive with a good efficiency
UPS’s - Different topologies – Off-Line
Back-UPS
®
ES
Surge Filter
Static
Switch
Batteries
charger Batteries Inverter
UPS’s - Different topologies – Line-interactive Easy UPS BV
Smart-UPS green
- This technology is an improvement of the first, the coupling / decoupling device is more sophisticated (static or
fast system) and a regulating device of the mains voltage can be added
- The DC / AC converter is generally a bi-directional converter or reversible, providing the battery and the load
power in case of power cut
- This solution is used little above 5000 VA
Static
switch
Voltage
regulator Filter
Rectifier Inverter
Batteries
UPS’s - Different topologies – On-line Double conversion
- The load is permanently supplied by the converter, which allows to regulate frequency and voltage
- This technology is particularly suitable for very disturbed networks or very sensitive applications
- This technology is used for power supplies up to 1,6 MVA
Smart-UPS RT
Gamme Galaxy
By-pass static
switch
Rectifier Inverter
Batteries
Installation considerations
Click each logo to learn more.
Because these are the primary organizations that create the requirements for UPS systems,
you should have a general understanding of how they work and how Schneider Electric works
with them.
Page 18Confidential Property of Schneider Electric |
Standards - UPS Requirements
Appro : 550kg
3-Phase UPS - Installation considerations - Dimensions
Example of dimension of UPS : Galaxy 3500 => 20kVA 3:3 15min
Page 22Confidential Property of Schneider Electric |
3-Phase UPS - Installation considerations - Battery room
layout
Page 23Confidential Property of Schneider Electric |
• Ventilation (2)
• Layout of cells (3)
• Service flooring (4)
• Battery connection (5)
• Battery-protection circuit
breaker (6)
• Fire-fighting equipment (7)
• Safety equipment (8)
• Inspection equipment (9)
• Sensors (10)
Technical room airflow requirements : example : Galaxy VM 160kVA
Page 24Confidential Property of Schneider Electric |
3-Phase UPS - Installation considerations - Ventilation, air-
conditioning
Galaxy 3500
IP 51
Galaxy 5500 Marine IP 22 Gutor PXC
IP 42
Some applications where a reinforcement of IP level is required :
Emergency application (smoke extraction systems) => IP 30
Marine : IP 22
Industry where corrosion or dust are there => up to IP 55. Above IP32, Gutor offer is required
3-Phase UPS - Installation considerations - IP degree of
protection
Note: Most of UPS’s are IP 20
Page 25Confidential Property of Schneider Electric |
UPS Architectures
Page 26Confidential Property of Schneider Electric |
Page 27Confidential Property of Schneider Electric |
UPS efficiency
• ECO mode
• Intelligent inverter
• Efficiency Booster Mode
• High efficiency
UPS’s Architectures - Industry dilemma
Power availability
• UPS architecture
• Redundancy
• MTTR/MTBF
• Ease operation
• Flexibility
Single UPS
Page 28Confidential Property of Schneider Electric |
20kVA
UPS
A
UPS
B
In Out
For Capacity
40kVA
In Out
UPS
A
UPS
B
For Redundancy
20kVA
N+1
In Out
For Modularity
UPS
A 16kW, 32kW or 48kW
16kW, 32kW N+1
In Out
UPS’s - Understanding the costumer needs (Various UPS
protection levels)
Pros:
• Cost efficient, Low footprint
Cons:
• Service capability
Availability Maintainability Upgradeability
MediumMediumHigh
Single UPS
20kVA
Input Supply Output to Equipment
Up to 20 kVA
Office, ATM, Cash register
& others
UPS configuration - for a fixed load
Single UPS
Input Supply Output to Equipment
Availability Maintainability Upgradeability
MediumMediumMedium
UPS
A
UPS
B
For Capacity
40kVA
Office, ATM, Cash register
& others
Pros:
•
Cons:
• Installation cost, Service ability,
Service cost
UPS configuration - for increased load
Up to 40 kVA
Input Supply Output to Equipment
Availability Maintainability Upgradeability
MediumHighVery High
UPS
A
UPS
B
Office, ATM, Cash register
& others
For Redundancy
20kVA
N+1
Pros:
• High Reliability, Good Serviceability
Cons:
• Footprint, Higher upfront Cost,
Lower Efficiency
UPS BUPS A
UPS configuration - for power Redundancy N+1
Up to 20 kVA
WhitespaceRow:B
16kW
32kW
48kW
64kW
160kW
144kW
128kW
112kW
96kW
80kW
Available Power
20KW40KW60KW80KW100KW120KW140KW 160KW
Data Center
Pros:
• Modularity, Scalability, Efficiency, Serviceability, Reliability
Cons:
• Higher Cost
Input Supply Output to Equipment
Availability Maintainability Upgradeability
Very HighVery HighVery High
16 to 160kW
UPS configuration - for modularity, Scalability & Redundancy
Page 32Confidential Property of Schneider Electric |
Single UPS
Page 33Confidential Property of Schneider Electric |
20kVA
UPS
A
UPS
B
In Out
For Capacity
40kVA
In Out
UPS
A
UPS
B
For Redundancy
20kVA
N+1
In Out
For Modularity
UPS
A 16kW, 32kW or 48kW
16kW, 32kW N+1
In Out
Availability
Maintainability
Upgradeability
Medium
High
Medium
Availability
Maintainability
Upgradeability
Medium
Medium
Medium
Availability
Maintainability
Upgradeability
Medium
Very High
High
Availability
Maintainability
Upgradeability
Very High
Very High
Very High
UPS’s - Understanding the costumer needs (Various UPS
protection levels)
“SBC”SystemBypassCabinet
GalaxyVX1250kW
“UPS A” “BBC”
BatteryBreakerCabinet
“BATT”
BatteryCabinet
Input
Output
1
1 2
2 3
3
4
4
UPS’s - Understanding Single UPS configuration with all Aux.
Page 34Confidential Property of Schneider Electric |
Multi-mode-operation
Page 35Confidential Property of Schneider Electric |
Galaxy VX
Galaxy VM
Galaxy VS “2018”
Multi-mode operation - for best performance for a given environment
Battery
DC/DC
PFC Recfifier Inverter
LoadAC in
AC in
Bypass Switch
Battery
DC/DC
PFC Recfifier Inverter
LoadAC in
AC in
Bypass Switch
May be on to
allow battery
recharge
Battery
DC/DC
PFC Recfifier Inverter
LoadAC in
AC in
Bypass Switch
Double conversion mode with 4-level inverter
provide best performance with >96% efficiency
up to 30% load.
ECO mode supply to load a bypass mains
power without power conditioning and provides
highest efficiency of 99%.
ECOnversion mode provides near double
conversion performance at near ECO mode
efficiency. ECOnversion provides power
conditioning at efficiency >98% to 99%.
This unique flexibility of Galaxy VM & VX allows customer to operate the UPS in any of the above
mode depending on load profile, site environment and schedule during the lifecycle of the UPS.
ECOnversion mode™Double conversion ECO mode
Page 36Confidential Property of Schneider Electric |
Multi-mode operation - for best performance for a given environment
What if.. we could have the best from both?
• Load is powered through PFC and Inverter
• Conditioned output voltage by inverter
• Conditioned input current by PFC
• Grid and load is coupled through DC bus
• Efficiency above 96%
• Load is powered through Bypass by unconditioned grid
• Output voltage by grid (No filtering, No protection)
• Input current by load (No current correction of the Load)
• Small ”break” in output Voltage doing transfer to Battery
• Efficiency above 99%
Double Conversion mode ECO mode (not recommended to use)
Page 37Confidential Property of Schneider Electric |
• Main flow of power is through bypass path => High efficiency
• Inverter is kept on => Reduced drop of output voltage at mains failure
• Regulation of input current => ”Diesel friendly”, no harmonics or VARs
• Regulation of DC bus => Allows battery recharge in ECOnversion
• Novel control method of bypass SCRs => Tolerant to mains short circuits
ECOnversiontm - for reduced operating costs
Battery
DC/DC
PFC Recfifier Inverter
LoadAC in
AC in
Bypass Switch
ECOnversiontm mode combines the best from ECO mode & Double conversion mode:
Page 38Confidential Property of Schneider Electric |
Back to index
Battery
DC/DC
PFC Recfifier Inverter
LoadAC in
AC in
Bypass Switch
Efficiency in On-line mode, ECO mode & the ECOnversiontm On-line mode, ECO mode & the ECOnversiontm
Page 39Confidential Property of Schneider Electric |
Galaxy VX in Double Conversion with 1000kW load:
UPS Efficiency : 95,1% (at 1000kW)
UPS Efficiency Losses : 49 kW (of heat)
Yearly Efficiency Losses in kW/hours: 429,240 kW
Yearly Efficiency Losses in Euro: 51.509 EUR (12 cent/kW)
Galaxy VX in ECOnversion with 1000kW load:
UPS Efficiency : 99,1% (at 1000kW)
UPS Efficiency Losses : 9,4 kW (of heat)
Yearly Efficiency Losses in kW/hours: 82.344 kW
Yearly Efficiency Losses in Euro: 9.881 EUR (12 cent/kW)
Double Conversion vs. ECOnversion mode:
Yearly Efficiency Losses savings in kW: 346.896 kW
Yearly Efficiency Losses savings in EUR: 41.628 EUR
5 Years Efficiency Losses savings in EUR: 208.140 EUR
Galaxy VX - ECOnversiontm - economical comparison
Page 39Confidential Property of Schneider Electric |
SPoT mode
Page 40Confidential Property of Schneider Electric |
Galaxy VX
Galaxy VM
Galaxy 7000
Back to index
SPoT: Load
bank test
savings
-15%
Power
Module
Scalability
250kW
Galaxy VX - Smart Power Test “SPoT mode”
The Smart Power Test in normal operation is conducted by circulating power from the inverter
back through the static bypass switch and into the power factor correction module. By
circulating the power, each of the UPS converters is energized and loaded in the same way as
though a UPS was feeding a load bank. The test shall be configurable for 100% rated power
continuously or 110% of rated power for 10 minutes. During Smart Power Test, the UPS shall
draw only enough power from utility to make up for system losses during the test procedure.
No need for loadbank
Page 41Confidential Property of Schneider Electric |
SPoT makes it economical to test UPS before connecting
critical load after commissioning and servicing
Inverter, PFC &
SSW Test
• Inverter is turned on while UPS is in Requested Static Bypass
• Output power from Inverter is recycled via bypass to input mains
• Power consumption equals system losses in Inverter, PFC, and Static Switch
• Requires output to be connected via bypass to input mains
• Can run at 100% continuous or 110% for 10min
Page 42Confidential Property of Schneider Electric |
1) Normal Operation & SSW Test
Galaxy VX - Smart Power Test “SPoT mode”
• Charger is turned on while in battery operation and charge power is recycled via PFC
back to DC bus
• Power consumption equals system loss only in Charger and PFC
• Selectable Charger load percentage 100 or 110% of charger capacity
2) Charger Operation Test
Charger Test
Battery, Inverter
& SSW Test
• Inverter is turned on while UPS is in Requested Static Bypass
• Output power from Inverter is recycled via static bypass to mains
• Requires output to be connected via bypass to input mains
• Can run at 100% continuous
*Back-feeding power to the grid may require local approval
3) Battery Discharge Test
Energy Storage
Page 43Confidential Property of Schneider Electric |
Customer Need:
Frequent
Flywheel Ultracaps
Energy Storage available
Page 44Confidential Property of Schneider Electric |
Example : Need 2 min 600 kW
• Batteries
– Sealed lead-acid The most commonly employed solution today
– Vented lead-acid
– Nickel cadmium Harsh environment
– Lithium-ion Alternative solution to lead-acid
• Ultracapacitors
• Flywheels
The various technologies currently available are the following
Li-ion Battery
Page 45Confidential Property of Schneider Electric |
Range available
• Galaxy VX
• Galaxy VM
• Galaxy 7000
• Symmetra MW
• Symmetra PX250/500
Back to index
Lithium-ion Battery
Page 46Confidential Property of Schneider Electric |
The Schneider Electric Li-ion battery solution for
three-phase UPSs is a high-value, innovative
energy storage protection solution for data centers,
industrial processes, or critical infrastructure.
This solution is supported by Schneider Electric
Symmetra MW, Galaxy 7000, Galaxy VM, and
Galaxy VX UPS’s and brings the following benefits:
• Significantly reduced battery footprint & weight to
allow for a more effective use of space
• Double the life and simplified maintenance vs.
traditional batteries
• Reduced cooling requirements
• Improved backup storage predictability and
manageability (BMS system included)
• Reduced TCO
Back to index
Li-ion Battery Technology vs. VRLA
Less Footprint
40-60%
Less Weight
60-70%
Expected Life
2-3X
# Cycles
10X
Initial CAPEX
1.5-2X
TCO Savings
30-50%
AND
Recharge
Time
Faster
Operating
Temperature
Higher
BMS
Integrated
BMS
Back to index
Schneider Electric’s LIB Solution
A modular solution accomodating a wider range of needs
13 or 17
per rack
Cell Module
(8 cells)
Switch Gear &
Rack BMS
LIB Rack
(W600xD650xH2100mm)
LIB Requirements
for UPS application
• Top safety technology
• High energy and power density:
35kWh and up to 230kW per rack
• Backup time from 5/6min to 30+min
• 15-years design life
• Competitive CapEx (~1,5-2X VRLA)
• Breakthrough TCO (-30-50%)
• Partnership with leading li-ion
manufacturer
From 1-32 racks
depending on power
and backup time
SMPS &
System BMS
1 Gateway (System BMS)
per system
(1U, fit in one of the LIB racks)
Page 48Confidential Property of Schneider Electric |
Back to index
Food and Beverage
Large data centers -and
other critical sites- are
striving to improve their
competitiveness
…improvements in
backup storage
technology are a key
enabler
Improve battery lifetime/reduce
maintenance
Improve backup storage
predictability and manageability
Reduce footprint
Reduce weight
Reduce cooling constraints
Reduce TCO
What can be improved from the
current VRLA battery solution?
Page 49Confidential Property of Schneider Electric |
UPS Range
1-Phase UPS - Offer
375-1100 VA 0,55 – 1,5 kVA 0,75 - 5 kVA 0,5 – 1,1 kVA
Surge Arrest
Smart UPS
SMT
Back UPS
Line
interactive
Surge
protection
Back UPS SX3
online
1 - 20 kVA 2 - 16 kVA 1-10 kVA
Smart UPS RT Smart UPS SR1
Confidential Property of Schneider Electric Page 51
Symmetra LX
Back UPS Pro Back VS
Smart RVS
IT &
Non-IT
IT
Data Center
10kVA 40kVA 200kVA
Symmetra PX
3-Phase UPS - Offer
Symmetra MW 500-1600kVA
Galaxy
3500
Smart-UPS
VT
10-40 kVA
10-40 kVA 10-80 kVA 20-120 kVA 160-200 kVA 250-500 kVA 500-1500kVA
10-500 kVA 400-1600 kVA
PX 40/48 kW PX 250/500 kWPX 100/160kW
Galaxy VM Galaxy VXGalaxy
4000/5000/5500
STAND-
ALONE
MODULAR
Galaxy 7000
Fully
Customized
5-160 kVA 5-220 kVA
Gutor PXC
Gutor
PXP
Gutor PEW
&
Gutor PDW
Confidential Property of Schneider Electric Page 52
Galaxy
300
10- 40 KVA 10-80 kVA
IT
Data centers
Non-IT
IT &
Non-IT
Easy
UPS 3S
5

Más contenido relacionado

La actualidad más candente

Accenture Financial Services Sourcing and Procurement Solution Infographic
Accenture Financial Services Sourcing and Procurement Solution InfographicAccenture Financial Services Sourcing and Procurement Solution Infographic
Accenture Financial Services Sourcing and Procurement Solution Infographicaccenture
 
Presales, solution design & bid management an overview
Presales, solution design & bid management   an overviewPresales, solution design & bid management   an overview
Presales, solution design & bid management an overviewMukesh Yadav
 
IT Infrastructure Managed Services and RIMS
IT Infrastructure Managed Services and RIMSIT Infrastructure Managed Services and RIMS
IT Infrastructure Managed Services and RIMSRazak Mohammed Ali
 
Maximizing SD-WAN Architecture with Service Chaining - VeloCloud
Maximizing SD-WAN Architecture with Service Chaining - VeloCloudMaximizing SD-WAN Architecture with Service Chaining - VeloCloud
Maximizing SD-WAN Architecture with Service Chaining - VeloCloudVeloCloud Networks, Inc.
 
Schneider Electric
Schneider ElectricSchneider Electric
Schneider ElectricFMA Summits
 
Reduce Operating Costs and Accelerate Efficiency by Migrating Your SAP Applic...
Reduce Operating Costs and Accelerate Efficiency by Migrating Your SAP Applic...Reduce Operating Costs and Accelerate Efficiency by Migrating Your SAP Applic...
Reduce Operating Costs and Accelerate Efficiency by Migrating Your SAP Applic...Amazon Web Services
 
Network Operations | SlideShare | Accenture
Network Operations | SlideShare | AccentureNetwork Operations | SlideShare | Accenture
Network Operations | SlideShare | AccentureAccenture Operations
 
Electric house summary profile
Electric house summary profileElectric house summary profile
Electric house summary profileMostafaAli623537
 
tutorial_pscad.pptx
tutorial_pscad.pptxtutorial_pscad.pptx
tutorial_pscad.pptxdfddfdf5
 
Huawei Digital Transformation
Huawei Digital TransformationHuawei Digital Transformation
Huawei Digital TransformationMyles Freedman
 
Managed Services Presentation
Managed Services PresentationManaged Services Presentation
Managed Services PresentationIISGL
 
IIoT and how Smart Machines help shape the future
IIoT and how Smart Machines help shape the futureIIoT and how Smart Machines help shape the future
IIoT and how Smart Machines help shape the futureSchneider Electric
 
AWS re:Invent 2016: Discovery Channel's Broadcast Workflows and Channel Origi...
AWS re:Invent 2016: Discovery Channel's Broadcast Workflows and Channel Origi...AWS re:Invent 2016: Discovery Channel's Broadcast Workflows and Channel Origi...
AWS re:Invent 2016: Discovery Channel's Broadcast Workflows and Channel Origi...Amazon Web Services
 
Staff Augmentation
Staff AugmentationStaff Augmentation
Staff AugmentationBrizGo
 
From leased lines to optical spectrum services
From leased lines to optical spectrum servicesFrom leased lines to optical spectrum services
From leased lines to optical spectrum servicesADVA
 
An Enterprise Architecture Design Build Approach - Innovate Vancouver.pdf
An Enterprise Architecture Design  Build Approach - Innovate Vancouver.pdfAn Enterprise Architecture Design  Build Approach - Innovate Vancouver.pdf
An Enterprise Architecture Design Build Approach - Innovate Vancouver.pdfInnovate Vancouver
 
Business Partnership Proposal PowerPoint Presentation Slides
Business Partnership Proposal PowerPoint Presentation SlidesBusiness Partnership Proposal PowerPoint Presentation Slides
Business Partnership Proposal PowerPoint Presentation SlidesSlideTeam
 
Landis+Gyr Smart Grid Presentation
Landis+Gyr Smart Grid PresentationLandis+Gyr Smart Grid Presentation
Landis+Gyr Smart Grid Presentationlg_slideshare
 

La actualidad más candente (20)

Accenture Financial Services Sourcing and Procurement Solution Infographic
Accenture Financial Services Sourcing and Procurement Solution InfographicAccenture Financial Services Sourcing and Procurement Solution Infographic
Accenture Financial Services Sourcing and Procurement Solution Infographic
 
Presales, solution design & bid management an overview
Presales, solution design & bid management   an overviewPresales, solution design & bid management   an overview
Presales, solution design & bid management an overview
 
IT Infrastructure Managed Services and RIMS
IT Infrastructure Managed Services and RIMSIT Infrastructure Managed Services and RIMS
IT Infrastructure Managed Services and RIMS
 
Maximizing SD-WAN Architecture with Service Chaining - VeloCloud
Maximizing SD-WAN Architecture with Service Chaining - VeloCloudMaximizing SD-WAN Architecture with Service Chaining - VeloCloud
Maximizing SD-WAN Architecture with Service Chaining - VeloCloud
 
Schneider Electric
Schneider ElectricSchneider Electric
Schneider Electric
 
Reduce Operating Costs and Accelerate Efficiency by Migrating Your SAP Applic...
Reduce Operating Costs and Accelerate Efficiency by Migrating Your SAP Applic...Reduce Operating Costs and Accelerate Efficiency by Migrating Your SAP Applic...
Reduce Operating Costs and Accelerate Efficiency by Migrating Your SAP Applic...
 
Network Operations | SlideShare | Accenture
Network Operations | SlideShare | AccentureNetwork Operations | SlideShare | Accenture
Network Operations | SlideShare | Accenture
 
Electric house summary profile
Electric house summary profileElectric house summary profile
Electric house summary profile
 
tutorial_pscad.pptx
tutorial_pscad.pptxtutorial_pscad.pptx
tutorial_pscad.pptx
 
Huawei Digital Transformation
Huawei Digital TransformationHuawei Digital Transformation
Huawei Digital Transformation
 
Managed Services Presentation
Managed Services PresentationManaged Services Presentation
Managed Services Presentation
 
IIoT and how Smart Machines help shape the future
IIoT and how Smart Machines help shape the futureIIoT and how Smart Machines help shape the future
IIoT and how Smart Machines help shape the future
 
AWS re:Invent 2016: Discovery Channel's Broadcast Workflows and Channel Origi...
AWS re:Invent 2016: Discovery Channel's Broadcast Workflows and Channel Origi...AWS re:Invent 2016: Discovery Channel's Broadcast Workflows and Channel Origi...
AWS re:Invent 2016: Discovery Channel's Broadcast Workflows and Channel Origi...
 
Staff Augmentation
Staff AugmentationStaff Augmentation
Staff Augmentation
 
From leased lines to optical spectrum services
From leased lines to optical spectrum servicesFrom leased lines to optical spectrum services
From leased lines to optical spectrum services
 
SIMPLEX Fire Detection and Alarm Certificate
SIMPLEX Fire Detection and Alarm CertificateSIMPLEX Fire Detection and Alarm Certificate
SIMPLEX Fire Detection and Alarm Certificate
 
Smart metering infrastructure Architecture and analytics
Smart metering infrastructure Architecture and analyticsSmart metering infrastructure Architecture and analytics
Smart metering infrastructure Architecture and analytics
 
An Enterprise Architecture Design Build Approach - Innovate Vancouver.pdf
An Enterprise Architecture Design  Build Approach - Innovate Vancouver.pdfAn Enterprise Architecture Design  Build Approach - Innovate Vancouver.pdf
An Enterprise Architecture Design Build Approach - Innovate Vancouver.pdf
 
Business Partnership Proposal PowerPoint Presentation Slides
Business Partnership Proposal PowerPoint Presentation SlidesBusiness Partnership Proposal PowerPoint Presentation Slides
Business Partnership Proposal PowerPoint Presentation Slides
 
Landis+Gyr Smart Grid Presentation
Landis+Gyr Smart Grid PresentationLandis+Gyr Smart Grid Presentation
Landis+Gyr Smart Grid Presentation
 

Similar a Secure Power design considerations for reliable operations

PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmPC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmElektrumlv
 
Off grid rooftop pv – elsol solar
Off grid rooftop pv – elsol solarOff grid rooftop pv – elsol solar
Off grid rooftop pv – elsol solarelsolsolar
 
Schneider Electric risinājumi serveru telpu infrastruktūrai
Schneider Electric risinājumi serveru telpu infrastruktūraiSchneider Electric risinājumi serveru telpu infrastruktūrai
Schneider Electric risinājumi serveru telpu infrastruktūraiElektrumlv
 
Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power - High Reliability Australian Technology Innovative, Customise...Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power - High Reliability Australian Technology Innovative, Customise...Magellan Power
 
GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)
GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)
GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)GE코리아
 
Huawei ups product and solution 02 (20140318)
Huawei ups product and solution 02 (20140318)Huawei ups product and solution 02 (20140318)
Huawei ups product and solution 02 (20140318)Jason Koffler
 
All products brochure
All products brochureAll products brochure
All products brochureJason Becker
 
Online UPS,Battery, Solar Inverter Supplier
Online UPS,Battery, Solar Inverter SupplierOnline UPS,Battery, Solar Inverter Supplier
Online UPS,Battery, Solar Inverter Suppliersuman bala
 
Webinaire - Meet some of the Belgian hardware frontrunners SME’s for energy c...
Webinaire - Meet some of the Belgian hardware frontrunners SME’s for energy c...Webinaire - Meet some of the Belgian hardware frontrunners SME’s for energy c...
Webinaire - Meet some of the Belgian hardware frontrunners SME’s for energy c...Cluster TWEED
 
IRPTF_Workshop_Presentations (1).pdf
IRPTF_Workshop_Presentations (1).pdfIRPTF_Workshop_Presentations (1).pdf
IRPTF_Workshop_Presentations (1).pdfPowerSystemDynamicsS
 
Brian Patterson: Reinventing Building Power
Brian Patterson: Reinventing Building PowerBrian Patterson: Reinventing Building Power
Brian Patterson: Reinventing Building PowerEnergyTech2015
 
DPE Company Profile - KV Ref 2
DPE Company Profile - KV Ref 2DPE Company Profile - KV Ref 2
DPE Company Profile - KV Ref 2Sarel Meyer
 
Nidec asi wind farm applications
Nidec asi wind farm applicationsNidec asi wind farm applications
Nidec asi wind farm applicationsNidec Corporation
 
3 p strategy sems 10-v4
3 p strategy  sems 10-v43 p strategy  sems 10-v4
3 p strategy sems 10-v4guestec6b92bb
 
UPS2000-A-(6-10kVA) V100R002 Training 02.ppt
UPS2000-A-(6-10kVA) V100R002 Training 02.pptUPS2000-A-(6-10kVA) V100R002 Training 02.ppt
UPS2000-A-(6-10kVA) V100R002 Training 02.pptssuser49a8ea
 
Efore News, December 2015
Efore News, December 2015Efore News, December 2015
Efore News, December 2015EFORE Group
 

Similar a Secure Power design considerations for reliable operations (20)

PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmPC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
 
Off grid rooftop pv – elsol solar
Off grid rooftop pv – elsol solarOff grid rooftop pv – elsol solar
Off grid rooftop pv – elsol solar
 
Schneider Electric risinājumi serveru telpu infrastruktūrai
Schneider Electric risinājumi serveru telpu infrastruktūraiSchneider Electric risinājumi serveru telpu infrastruktūrai
Schneider Electric risinājumi serveru telpu infrastruktūrai
 
Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power - High Reliability Australian Technology Innovative, Customise...Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power - High Reliability Australian Technology Innovative, Customise...
 
GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)
GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)
GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)
 
Huawei ups product and solution 02 (20140318)
Huawei ups product and solution 02 (20140318)Huawei ups product and solution 02 (20140318)
Huawei ups product and solution 02 (20140318)
 
All products brochure
All products brochureAll products brochure
All products brochure
 
Online UPS,Battery, Solar Inverter Supplier
Online UPS,Battery, Solar Inverter SupplierOnline UPS,Battery, Solar Inverter Supplier
Online UPS,Battery, Solar Inverter Supplier
 
Aps
ApsAps
Aps
 
Webinaire - Meet some of the Belgian hardware frontrunners SME’s for energy c...
Webinaire - Meet some of the Belgian hardware frontrunners SME’s for energy c...Webinaire - Meet some of the Belgian hardware frontrunners SME’s for energy c...
Webinaire - Meet some of the Belgian hardware frontrunners SME’s for energy c...
 
IRPTF_Workshop_Presentations (1).pdf
IRPTF_Workshop_Presentations (1).pdfIRPTF_Workshop_Presentations (1).pdf
IRPTF_Workshop_Presentations (1).pdf
 
Energy Storage solutions
Energy Storage solutionsEnergy Storage solutions
Energy Storage solutions
 
ABB Low Voltage LV Capacitors, ABB CLMD
ABB Low Voltage LV Capacitors, ABB CLMDABB Low Voltage LV Capacitors, ABB CLMD
ABB Low Voltage LV Capacitors, ABB CLMD
 
Capacitors and filters
Capacitors and filtersCapacitors and filters
Capacitors and filters
 
Brian Patterson: Reinventing Building Power
Brian Patterson: Reinventing Building PowerBrian Patterson: Reinventing Building Power
Brian Patterson: Reinventing Building Power
 
DPE Company Profile - KV Ref 2
DPE Company Profile - KV Ref 2DPE Company Profile - KV Ref 2
DPE Company Profile - KV Ref 2
 
Nidec asi wind farm applications
Nidec asi wind farm applicationsNidec asi wind farm applications
Nidec asi wind farm applications
 
3 p strategy sems 10-v4
3 p strategy  sems 10-v43 p strategy  sems 10-v4
3 p strategy sems 10-v4
 
UPS2000-A-(6-10kVA) V100R002 Training 02.ppt
UPS2000-A-(6-10kVA) V100R002 Training 02.pptUPS2000-A-(6-10kVA) V100R002 Training 02.ppt
UPS2000-A-(6-10kVA) V100R002 Training 02.ppt
 
Efore News, December 2015
Efore News, December 2015Efore News, December 2015
Efore News, December 2015
 

Más de Schneider Electric

Digital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsDigital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsSchneider Electric
 
32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing 32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing Schneider Electric
 
Key Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsKey Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsSchneider Electric
 
Zelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingZelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingSchneider Electric
 
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSpacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSchneider Electric
 
Relay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingRelay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingSchneider Electric
 
Magelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingMagelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingSchneider Electric
 
Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Schneider Electric
 
EcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesEcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesSchneider Electric
 
Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Schneider Electric
 
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.Schneider Electric
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580Schneider Electric
 
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...Schneider Electric
 
Connected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTConnected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTSchneider Electric
 
Telemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingTelemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingSchneider Electric
 
Telemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingTelemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingSchneider Electric
 
Telemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingTelemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingSchneider Electric
 
Telemecanique Pressure Switches Briefing
Telemecanique Pressure Switches BriefingTelemecanique Pressure Switches Briefing
Telemecanique Pressure Switches BriefingSchneider Electric
 

Más de Schneider Electric (20)

Digital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsDigital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting Investors
 
32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing 32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing
 
Key Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsKey Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation Trends
 
Magelis Basic HMI Briefing
Magelis Basic HMI Briefing Magelis Basic HMI Briefing
Magelis Basic HMI Briefing
 
Zelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingZelio Time Electronic Relay Briefing
Zelio Time Electronic Relay Briefing
 
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSpacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
 
Relay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingRelay Control Zelio SSR Briefing
Relay Control Zelio SSR Briefing
 
Magelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingMagelis HMI, iPC and software Briefing
Magelis HMI, iPC and software Briefing
 
Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?
 
EcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesEcoStruxure for Intuitive Industries
EcoStruxure for Intuitive Industries
 
Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017
 
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580
 
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
 
Connected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTConnected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoT
 
Telemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingTelemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories Briefing
 
Telemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingTelemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors Briefing
 
Telemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingTelemecanique Limit Switches Briefing
Telemecanique Limit Switches Briefing
 
Telemecanique Pressure Switches Briefing
Telemecanique Pressure Switches BriefingTelemecanique Pressure Switches Briefing
Telemecanique Pressure Switches Briefing
 
Proximity Switches Briefing
Proximity Switches BriefingProximity Switches Briefing
Proximity Switches Briefing
 

Último

Microservices, Docker deploy and Microservices source code in C#
Microservices, Docker deploy and Microservices source code in C#Microservices, Docker deploy and Microservices source code in C#
Microservices, Docker deploy and Microservices source code in C#Karmanjay Verma
 
QCon London: Mastering long-running processes in modern architectures
QCon London: Mastering long-running processes in modern architecturesQCon London: Mastering long-running processes in modern architectures
QCon London: Mastering long-running processes in modern architecturesBernd Ruecker
 
UiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to HeroUiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to HeroUiPathCommunity
 
4. Cobus Valentine- Cybersecurity Threats and Solutions for the Public Sector
4. Cobus Valentine- Cybersecurity Threats and Solutions for the Public Sector4. Cobus Valentine- Cybersecurity Threats and Solutions for the Public Sector
4. Cobus Valentine- Cybersecurity Threats and Solutions for the Public Sectoritnewsafrica
 
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Mark Goldstein
 
Landscape Catalogue 2024 Australia-1.pdf
Landscape Catalogue 2024 Australia-1.pdfLandscape Catalogue 2024 Australia-1.pdf
Landscape Catalogue 2024 Australia-1.pdfAarwolf Industries LLC
 
Modern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better StrongerModern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better Strongerpanagenda
 
Digital Tools & AI in Career Development
Digital Tools & AI in Career DevelopmentDigital Tools & AI in Career Development
Digital Tools & AI in Career DevelopmentMahmoud Rabie
 
Abdul Kader Baba- Managing Cybersecurity Risks and Compliance Requirements i...
Abdul Kader Baba- Managing Cybersecurity Risks  and Compliance Requirements i...Abdul Kader Baba- Managing Cybersecurity Risks  and Compliance Requirements i...
Abdul Kader Baba- Managing Cybersecurity Risks and Compliance Requirements i...itnewsafrica
 
Glenn Lazarus- Why Your Observability Strategy Needs Security Observability
Glenn Lazarus- Why Your Observability Strategy Needs Security ObservabilityGlenn Lazarus- Why Your Observability Strategy Needs Security Observability
Glenn Lazarus- Why Your Observability Strategy Needs Security Observabilityitnewsafrica
 
[Webinar] SpiraTest - Setting New Standards in Quality Assurance
[Webinar] SpiraTest - Setting New Standards in Quality Assurance[Webinar] SpiraTest - Setting New Standards in Quality Assurance
[Webinar] SpiraTest - Setting New Standards in Quality AssuranceInflectra
 
Generative AI - Gitex v1Generative AI - Gitex v1.pptx
Generative AI - Gitex v1Generative AI - Gitex v1.pptxGenerative AI - Gitex v1Generative AI - Gitex v1.pptx
Generative AI - Gitex v1Generative AI - Gitex v1.pptxfnnc6jmgwh
 
React Native vs Ionic - The Best Mobile App Framework
React Native vs Ionic - The Best Mobile App FrameworkReact Native vs Ionic - The Best Mobile App Framework
React Native vs Ionic - The Best Mobile App FrameworkPixlogix Infotech
 
JET Technology Labs White Paper for Virtualized Security and Encryption Techn...
JET Technology Labs White Paper for Virtualized Security and Encryption Techn...JET Technology Labs White Paper for Virtualized Security and Encryption Techn...
JET Technology Labs White Paper for Virtualized Security and Encryption Techn...amber724300
 
Top 10 Hubspot Development Companies in 2024
Top 10 Hubspot Development Companies in 2024Top 10 Hubspot Development Companies in 2024
Top 10 Hubspot Development Companies in 2024TopCSSGallery
 
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...Alkin Tezuysal
 
Irene Moetsana-Moeng: Stakeholders in Cybersecurity: Collaborative Defence fo...
Irene Moetsana-Moeng: Stakeholders in Cybersecurity: Collaborative Defence fo...Irene Moetsana-Moeng: Stakeholders in Cybersecurity: Collaborative Defence fo...
Irene Moetsana-Moeng: Stakeholders in Cybersecurity: Collaborative Defence fo...itnewsafrica
 
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotesMuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotesManik S Magar
 
Emixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native developmentEmixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native developmentPim van der Noll
 
A Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersA Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersNicole Novielli
 

Último (20)

Microservices, Docker deploy and Microservices source code in C#
Microservices, Docker deploy and Microservices source code in C#Microservices, Docker deploy and Microservices source code in C#
Microservices, Docker deploy and Microservices source code in C#
 
QCon London: Mastering long-running processes in modern architectures
QCon London: Mastering long-running processes in modern architecturesQCon London: Mastering long-running processes in modern architectures
QCon London: Mastering long-running processes in modern architectures
 
UiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to HeroUiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to Hero
 
4. Cobus Valentine- Cybersecurity Threats and Solutions for the Public Sector
4. Cobus Valentine- Cybersecurity Threats and Solutions for the Public Sector4. Cobus Valentine- Cybersecurity Threats and Solutions for the Public Sector
4. Cobus Valentine- Cybersecurity Threats and Solutions for the Public Sector
 
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
 
Landscape Catalogue 2024 Australia-1.pdf
Landscape Catalogue 2024 Australia-1.pdfLandscape Catalogue 2024 Australia-1.pdf
Landscape Catalogue 2024 Australia-1.pdf
 
Modern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better StrongerModern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
 
Digital Tools & AI in Career Development
Digital Tools & AI in Career DevelopmentDigital Tools & AI in Career Development
Digital Tools & AI in Career Development
 
Abdul Kader Baba- Managing Cybersecurity Risks and Compliance Requirements i...
Abdul Kader Baba- Managing Cybersecurity Risks  and Compliance Requirements i...Abdul Kader Baba- Managing Cybersecurity Risks  and Compliance Requirements i...
Abdul Kader Baba- Managing Cybersecurity Risks and Compliance Requirements i...
 
Glenn Lazarus- Why Your Observability Strategy Needs Security Observability
Glenn Lazarus- Why Your Observability Strategy Needs Security ObservabilityGlenn Lazarus- Why Your Observability Strategy Needs Security Observability
Glenn Lazarus- Why Your Observability Strategy Needs Security Observability
 
[Webinar] SpiraTest - Setting New Standards in Quality Assurance
[Webinar] SpiraTest - Setting New Standards in Quality Assurance[Webinar] SpiraTest - Setting New Standards in Quality Assurance
[Webinar] SpiraTest - Setting New Standards in Quality Assurance
 
Generative AI - Gitex v1Generative AI - Gitex v1.pptx
Generative AI - Gitex v1Generative AI - Gitex v1.pptxGenerative AI - Gitex v1Generative AI - Gitex v1.pptx
Generative AI - Gitex v1Generative AI - Gitex v1.pptx
 
React Native vs Ionic - The Best Mobile App Framework
React Native vs Ionic - The Best Mobile App FrameworkReact Native vs Ionic - The Best Mobile App Framework
React Native vs Ionic - The Best Mobile App Framework
 
JET Technology Labs White Paper for Virtualized Security and Encryption Techn...
JET Technology Labs White Paper for Virtualized Security and Encryption Techn...JET Technology Labs White Paper for Virtualized Security and Encryption Techn...
JET Technology Labs White Paper for Virtualized Security and Encryption Techn...
 
Top 10 Hubspot Development Companies in 2024
Top 10 Hubspot Development Companies in 2024Top 10 Hubspot Development Companies in 2024
Top 10 Hubspot Development Companies in 2024
 
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
 
Irene Moetsana-Moeng: Stakeholders in Cybersecurity: Collaborative Defence fo...
Irene Moetsana-Moeng: Stakeholders in Cybersecurity: Collaborative Defence fo...Irene Moetsana-Moeng: Stakeholders in Cybersecurity: Collaborative Defence fo...
Irene Moetsana-Moeng: Stakeholders in Cybersecurity: Collaborative Defence fo...
 
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotesMuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
 
Emixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native developmentEmixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native development
 
A Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersA Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software Developers
 

Secure Power design considerations for reliable operations

  • 1. Secure Power design considerations Confidential Property of Schneider Electric |
  • 2. Summary Page 2Confidential Property of Schneider Electric | 1 Introduction 2 How do we ensure reliable power..? 3 How can we reduce these risk? 4 UPS Topologies 5 Installation considerations 6 UPS Architectures 7 Multi- mode - operation 8 Energy Storage UPS range9
  • 3. More ELECTRIC Increase by 50% in the next 25 years More CONNECTED Connect 50bn devices by 2020 More DISTRIBUTED Solar PV and Storage to Account for ~50% of new capacity additions by 2030 More EFFICIENT Still.. 2/3 energy efficiency potential.. remains untapped .!! Our World Will Be…
  • 4. Back to index Mining (Metals & Minerals) Water & Wastewater Datacenter Healthcare Oil and Gas Building No matter the type of business… reliable power is essential
  • 5. Confidential Property of Schneider Electric | Page 5 Confidential Property of Schneider Electric | How do we ensure reliable power..?
  • 6. Heavy Industry Commercial & Industrial Industry Buildings Data Centres Residential Infrastructure EHV/HV Centralised Generation HV/MV Substation (Primary substation) Switching Substation MV/MV Heavy Industry MV / LV Substation Connexion to HV network Connexion to MV network ConsumersEnergy Producers Utility Transmission Utility Distribution
  • 7. Heavy Industry Commercial & Industrial Industry Buildings Data Centres Residential Infrastructure EHV/HV Centralised Generation HV/MV Substation (Primary substation) Switching Substation MV/MV Heavy Industry MV / LV Substation Connexion to HV network Connexion to MV network ConsumersEnergy Producers Utility Transmission Utility Distribution Power failure, Voltage spikes, Under voltage, Frequency variations Harmonics, Power Factor Disturbances Voltage variations Frequency variations Micro outages Long outages
  • 8. Confidential Property of Schneider Electric | Page 8 Confidential Property of Schneider Electric | How can we reduce these risk? - Power failure - Voltage spikes - Under voltage - Frequency variations
  • 9. UPS - “Uninterruptible Power Supply” Page 9Confidential Property of Schneider Electric |
  • 10. PFC Rectifier UPS AC: Alternating Current DC: Direct Current PFC: Power Factor Correction What is a “UPS” & what is the purpose of a UPS? Main functions of a UPS: “Uninterruptible Power Supply” •Short term backup (Batteries) •Input current conditioned by the PFC •Output Voltage conditioned by the Inverter •Isolation / Protection against: • Voltage spikes • Over voltage • Under voltage • Frequency variations • Harmonics • Power Factor
  • 11. Heavy Industry Commercial & Industrial Industry Buildings Data Centres Residential Infrastructure EHV/HV Centralised Generation HV/MV Substation (Primary substation) Switching Substation MV/MV Heavy Industry MV / LV Substation Connexion to HV network Connexion to MV network Energy Producers Utility Transmission Utility Distribution Power failure, Voltage spikes, Under voltage, Frequency variations Harmonics, Power Factor UPS Consumers
  • 12. Heavy Industry Commercial & Industrial Industry Buildings Data Centres Residential Infrastructure EHV/HV Centralised Generation HV/MV Substation (Primary substation) Switching Substation MV/MV Heavy Industry MV / LV Substation Connexion to HV network Connexion to MV network Energy Producers Utility Transmission Utility Distribution Power failure, Voltage spikes, Under voltage, Frequency variations Harmonics, Power Factor Power Grid Customer Grid UPS Consumers Reliable & safe Power Harmonics created by the load is reduced by the UPS UPS ON
  • 13. UPS Topologies Page 13Confidential Property of Schneider Electric |
  • 14. - The simplest solution, used for applications that support a cut of 4 to 10ms when detecting the fault of the source and transfer to the battery - This technology is for low powers (Apparent Power: 330 VA – 900 VA) - This solution is inexpensive with a good efficiency UPS’s - Different topologies – Off-Line Back-UPS ® ES Surge Filter Static Switch Batteries charger Batteries Inverter
  • 15. UPS’s - Different topologies – Line-interactive Easy UPS BV Smart-UPS green - This technology is an improvement of the first, the coupling / decoupling device is more sophisticated (static or fast system) and a regulating device of the mains voltage can be added - The DC / AC converter is generally a bi-directional converter or reversible, providing the battery and the load power in case of power cut - This solution is used little above 5000 VA Static switch Voltage regulator Filter Rectifier Inverter Batteries
  • 16. UPS’s - Different topologies – On-line Double conversion - The load is permanently supplied by the converter, which allows to regulate frequency and voltage - This technology is particularly suitable for very disturbed networks or very sensitive applications - This technology is used for power supplies up to 1,6 MVA Smart-UPS RT Gamme Galaxy By-pass static switch Rectifier Inverter Batteries
  • 18. Click each logo to learn more. Because these are the primary organizations that create the requirements for UPS systems, you should have a general understanding of how they work and how Schneider Electric works with them. Page 18Confidential Property of Schneider Electric | Standards - UPS Requirements
  • 19. Appro : 550kg 3-Phase UPS - Installation considerations - Dimensions Example of dimension of UPS : Galaxy 3500 => 20kVA 3:3 15min Page 22Confidential Property of Schneider Electric |
  • 20. 3-Phase UPS - Installation considerations - Battery room layout Page 23Confidential Property of Schneider Electric | • Ventilation (2) • Layout of cells (3) • Service flooring (4) • Battery connection (5) • Battery-protection circuit breaker (6) • Fire-fighting equipment (7) • Safety equipment (8) • Inspection equipment (9) • Sensors (10)
  • 21. Technical room airflow requirements : example : Galaxy VM 160kVA Page 24Confidential Property of Schneider Electric | 3-Phase UPS - Installation considerations - Ventilation, air- conditioning
  • 22. Galaxy 3500 IP 51 Galaxy 5500 Marine IP 22 Gutor PXC IP 42 Some applications where a reinforcement of IP level is required : Emergency application (smoke extraction systems) => IP 30 Marine : IP 22 Industry where corrosion or dust are there => up to IP 55. Above IP32, Gutor offer is required 3-Phase UPS - Installation considerations - IP degree of protection Note: Most of UPS’s are IP 20 Page 25Confidential Property of Schneider Electric |
  • 23. UPS Architectures Page 26Confidential Property of Schneider Electric |
  • 24. Page 27Confidential Property of Schneider Electric | UPS efficiency • ECO mode • Intelligent inverter • Efficiency Booster Mode • High efficiency UPS’s Architectures - Industry dilemma Power availability • UPS architecture • Redundancy • MTTR/MTBF • Ease operation • Flexibility
  • 25. Single UPS Page 28Confidential Property of Schneider Electric | 20kVA UPS A UPS B In Out For Capacity 40kVA In Out UPS A UPS B For Redundancy 20kVA N+1 In Out For Modularity UPS A 16kW, 32kW or 48kW 16kW, 32kW N+1 In Out UPS’s - Understanding the costumer needs (Various UPS protection levels)
  • 26. Pros: • Cost efficient, Low footprint Cons: • Service capability Availability Maintainability Upgradeability MediumMediumHigh Single UPS 20kVA Input Supply Output to Equipment Up to 20 kVA Office, ATM, Cash register & others UPS configuration - for a fixed load
  • 27. Single UPS Input Supply Output to Equipment Availability Maintainability Upgradeability MediumMediumMedium UPS A UPS B For Capacity 40kVA Office, ATM, Cash register & others Pros: • Cons: • Installation cost, Service ability, Service cost UPS configuration - for increased load Up to 40 kVA
  • 28. Input Supply Output to Equipment Availability Maintainability Upgradeability MediumHighVery High UPS A UPS B Office, ATM, Cash register & others For Redundancy 20kVA N+1 Pros: • High Reliability, Good Serviceability Cons: • Footprint, Higher upfront Cost, Lower Efficiency UPS BUPS A UPS configuration - for power Redundancy N+1 Up to 20 kVA
  • 29. WhitespaceRow:B 16kW 32kW 48kW 64kW 160kW 144kW 128kW 112kW 96kW 80kW Available Power 20KW40KW60KW80KW100KW120KW140KW 160KW Data Center Pros: • Modularity, Scalability, Efficiency, Serviceability, Reliability Cons: • Higher Cost Input Supply Output to Equipment Availability Maintainability Upgradeability Very HighVery HighVery High 16 to 160kW UPS configuration - for modularity, Scalability & Redundancy Page 32Confidential Property of Schneider Electric |
  • 30. Single UPS Page 33Confidential Property of Schneider Electric | 20kVA UPS A UPS B In Out For Capacity 40kVA In Out UPS A UPS B For Redundancy 20kVA N+1 In Out For Modularity UPS A 16kW, 32kW or 48kW 16kW, 32kW N+1 In Out Availability Maintainability Upgradeability Medium High Medium Availability Maintainability Upgradeability Medium Medium Medium Availability Maintainability Upgradeability Medium Very High High Availability Maintainability Upgradeability Very High Very High Very High UPS’s - Understanding the costumer needs (Various UPS protection levels)
  • 31. “SBC”SystemBypassCabinet GalaxyVX1250kW “UPS A” “BBC” BatteryBreakerCabinet “BATT” BatteryCabinet Input Output 1 1 2 2 3 3 4 4 UPS’s - Understanding Single UPS configuration with all Aux. Page 34Confidential Property of Schneider Electric |
  • 32. Multi-mode-operation Page 35Confidential Property of Schneider Electric | Galaxy VX Galaxy VM Galaxy VS “2018”
  • 33. Multi-mode operation - for best performance for a given environment Battery DC/DC PFC Recfifier Inverter LoadAC in AC in Bypass Switch Battery DC/DC PFC Recfifier Inverter LoadAC in AC in Bypass Switch May be on to allow battery recharge Battery DC/DC PFC Recfifier Inverter LoadAC in AC in Bypass Switch Double conversion mode with 4-level inverter provide best performance with >96% efficiency up to 30% load. ECO mode supply to load a bypass mains power without power conditioning and provides highest efficiency of 99%. ECOnversion mode provides near double conversion performance at near ECO mode efficiency. ECOnversion provides power conditioning at efficiency >98% to 99%. This unique flexibility of Galaxy VM & VX allows customer to operate the UPS in any of the above mode depending on load profile, site environment and schedule during the lifecycle of the UPS. ECOnversion mode™Double conversion ECO mode Page 36Confidential Property of Schneider Electric |
  • 34. Multi-mode operation - for best performance for a given environment What if.. we could have the best from both? • Load is powered through PFC and Inverter • Conditioned output voltage by inverter • Conditioned input current by PFC • Grid and load is coupled through DC bus • Efficiency above 96% • Load is powered through Bypass by unconditioned grid • Output voltage by grid (No filtering, No protection) • Input current by load (No current correction of the Load) • Small ”break” in output Voltage doing transfer to Battery • Efficiency above 99% Double Conversion mode ECO mode (not recommended to use) Page 37Confidential Property of Schneider Electric |
  • 35. • Main flow of power is through bypass path => High efficiency • Inverter is kept on => Reduced drop of output voltage at mains failure • Regulation of input current => ”Diesel friendly”, no harmonics or VARs • Regulation of DC bus => Allows battery recharge in ECOnversion • Novel control method of bypass SCRs => Tolerant to mains short circuits ECOnversiontm - for reduced operating costs Battery DC/DC PFC Recfifier Inverter LoadAC in AC in Bypass Switch ECOnversiontm mode combines the best from ECO mode & Double conversion mode: Page 38Confidential Property of Schneider Electric |
  • 36. Back to index Battery DC/DC PFC Recfifier Inverter LoadAC in AC in Bypass Switch Efficiency in On-line mode, ECO mode & the ECOnversiontm On-line mode, ECO mode & the ECOnversiontm Page 39Confidential Property of Schneider Electric | Galaxy VX in Double Conversion with 1000kW load: UPS Efficiency : 95,1% (at 1000kW) UPS Efficiency Losses : 49 kW (of heat) Yearly Efficiency Losses in kW/hours: 429,240 kW Yearly Efficiency Losses in Euro: 51.509 EUR (12 cent/kW) Galaxy VX in ECOnversion with 1000kW load: UPS Efficiency : 99,1% (at 1000kW) UPS Efficiency Losses : 9,4 kW (of heat) Yearly Efficiency Losses in kW/hours: 82.344 kW Yearly Efficiency Losses in Euro: 9.881 EUR (12 cent/kW) Double Conversion vs. ECOnversion mode: Yearly Efficiency Losses savings in kW: 346.896 kW Yearly Efficiency Losses savings in EUR: 41.628 EUR 5 Years Efficiency Losses savings in EUR: 208.140 EUR Galaxy VX - ECOnversiontm - economical comparison Page 39Confidential Property of Schneider Electric |
  • 37. SPoT mode Page 40Confidential Property of Schneider Electric | Galaxy VX Galaxy VM Galaxy 7000
  • 38. Back to index SPoT: Load bank test savings -15% Power Module Scalability 250kW Galaxy VX - Smart Power Test “SPoT mode” The Smart Power Test in normal operation is conducted by circulating power from the inverter back through the static bypass switch and into the power factor correction module. By circulating the power, each of the UPS converters is energized and loaded in the same way as though a UPS was feeding a load bank. The test shall be configurable for 100% rated power continuously or 110% of rated power for 10 minutes. During Smart Power Test, the UPS shall draw only enough power from utility to make up for system losses during the test procedure. No need for loadbank Page 41Confidential Property of Schneider Electric | SPoT makes it economical to test UPS before connecting critical load after commissioning and servicing
  • 39. Inverter, PFC & SSW Test • Inverter is turned on while UPS is in Requested Static Bypass • Output power from Inverter is recycled via bypass to input mains • Power consumption equals system losses in Inverter, PFC, and Static Switch • Requires output to be connected via bypass to input mains • Can run at 100% continuous or 110% for 10min Page 42Confidential Property of Schneider Electric | 1) Normal Operation & SSW Test Galaxy VX - Smart Power Test “SPoT mode” • Charger is turned on while in battery operation and charge power is recycled via PFC back to DC bus • Power consumption equals system loss only in Charger and PFC • Selectable Charger load percentage 100 or 110% of charger capacity 2) Charger Operation Test Charger Test Battery, Inverter & SSW Test • Inverter is turned on while UPS is in Requested Static Bypass • Output power from Inverter is recycled via static bypass to mains • Requires output to be connected via bypass to input mains • Can run at 100% continuous *Back-feeding power to the grid may require local approval 3) Battery Discharge Test
  • 40. Energy Storage Page 43Confidential Property of Schneider Electric |
  • 41. Customer Need: Frequent Flywheel Ultracaps Energy Storage available Page 44Confidential Property of Schneider Electric | Example : Need 2 min 600 kW • Batteries – Sealed lead-acid The most commonly employed solution today – Vented lead-acid – Nickel cadmium Harsh environment – Lithium-ion Alternative solution to lead-acid • Ultracapacitors • Flywheels The various technologies currently available are the following
  • 42. Li-ion Battery Page 45Confidential Property of Schneider Electric | Range available • Galaxy VX • Galaxy VM • Galaxy 7000 • Symmetra MW • Symmetra PX250/500
  • 43. Back to index Lithium-ion Battery Page 46Confidential Property of Schneider Electric | The Schneider Electric Li-ion battery solution for three-phase UPSs is a high-value, innovative energy storage protection solution for data centers, industrial processes, or critical infrastructure. This solution is supported by Schneider Electric Symmetra MW, Galaxy 7000, Galaxy VM, and Galaxy VX UPS’s and brings the following benefits: • Significantly reduced battery footprint & weight to allow for a more effective use of space • Double the life and simplified maintenance vs. traditional batteries • Reduced cooling requirements • Improved backup storage predictability and manageability (BMS system included) • Reduced TCO
  • 44. Back to index Li-ion Battery Technology vs. VRLA Less Footprint 40-60% Less Weight 60-70% Expected Life 2-3X # Cycles 10X Initial CAPEX 1.5-2X TCO Savings 30-50% AND Recharge Time Faster Operating Temperature Higher BMS Integrated BMS
  • 45. Back to index Schneider Electric’s LIB Solution A modular solution accomodating a wider range of needs 13 or 17 per rack Cell Module (8 cells) Switch Gear & Rack BMS LIB Rack (W600xD650xH2100mm) LIB Requirements for UPS application • Top safety technology • High energy and power density: 35kWh and up to 230kW per rack • Backup time from 5/6min to 30+min • 15-years design life • Competitive CapEx (~1,5-2X VRLA) • Breakthrough TCO (-30-50%) • Partnership with leading li-ion manufacturer From 1-32 racks depending on power and backup time SMPS & System BMS 1 Gateway (System BMS) per system (1U, fit in one of the LIB racks) Page 48Confidential Property of Schneider Electric |
  • 46. Back to index Food and Beverage Large data centers -and other critical sites- are striving to improve their competitiveness …improvements in backup storage technology are a key enabler Improve battery lifetime/reduce maintenance Improve backup storage predictability and manageability Reduce footprint Reduce weight Reduce cooling constraints Reduce TCO What can be improved from the current VRLA battery solution? Page 49Confidential Property of Schneider Electric |
  • 48. 1-Phase UPS - Offer 375-1100 VA 0,55 – 1,5 kVA 0,75 - 5 kVA 0,5 – 1,1 kVA Surge Arrest Smart UPS SMT Back UPS Line interactive Surge protection Back UPS SX3 online 1 - 20 kVA 2 - 16 kVA 1-10 kVA Smart UPS RT Smart UPS SR1 Confidential Property of Schneider Electric Page 51 Symmetra LX Back UPS Pro Back VS Smart RVS IT & Non-IT IT Data Center
  • 49. 10kVA 40kVA 200kVA Symmetra PX 3-Phase UPS - Offer Symmetra MW 500-1600kVA Galaxy 3500 Smart-UPS VT 10-40 kVA 10-40 kVA 10-80 kVA 20-120 kVA 160-200 kVA 250-500 kVA 500-1500kVA 10-500 kVA 400-1600 kVA PX 40/48 kW PX 250/500 kWPX 100/160kW Galaxy VM Galaxy VXGalaxy 4000/5000/5500 STAND- ALONE MODULAR Galaxy 7000 Fully Customized 5-160 kVA 5-220 kVA Gutor PXC Gutor PXP Gutor PEW & Gutor PDW Confidential Property of Schneider Electric Page 52 Galaxy 300 10- 40 KVA 10-80 kVA IT Data centers Non-IT IT & Non-IT Easy UPS 3S
  • 50. 5

Notas del editor

  1. More Electric: Our world is becoming More Electric. Almost everything we interact with today is either already electric or becoming electric. Think about it. From the time you start your day in the morning to the time you finish your day – your home, your car, your work, your devices, your entertainment – almost everything is electric. Imagine the energy needed to power this. Electricity consumption will increase by 80% in next 25 years   More Connected: Our lives are also becoming more connected. The Internet has already transformed the way we live, work and play. Now the Connected Things is going to take this to a brand new level. 50 billion things connected in the next 5 years.   More Distributed: With such a widespread electrification and connectivity, energy models need rethinking as well. Which is why the generation of power needs to be closer to users. Distributed Energy is rapidly evolving globally. This is positive energy – renewable. In 2014 , Renewables overtook fossil fuels in investment value, with $295bn invested in renewables compared to $289bn invested in fossil fuels. And it is getting cheaper to do this.   More Efficient: When our world is more electric, more connected and more distributed, new opportunities emerge and allows us to tap into even more efficiency – in industrial processes, in the energy value chain, in buildings, in transportation, in the global supply chain and even in the comfort and peace-of-mind of our homes.    Additional Data Points:   MORE ELECTRIC: The rising demand for electricity driven by urbanisation, digitisation and sustainability – in particular buildings, industry, intelligent devices and even transportation -- demands proven energy management approaches.   Electricity consumption will DOUBLE within the next 20Y (urbanization). This is absolutely massive, esp. considering the yield of electricity production is around 30-40% only (3 units of primary energy to produce 1 unit of electricity). Most of the energy challenge lies into the growth of electricity production (& consumption).   MORE DISTRIBUTED: In many parts of the world, energy generation is getting increasingly distributed. This is driven by new capabilities to provide local energy to facilities, particularly around positive or renewable energy and micro grids.   Here are two cool reasons behind this trend: Energy storage has seen drastic improvements in its economics over the past 5 years Li-Ion Battery cost $/Kwhr dropping from 1000 in 2010 to around 200 in 2014 Falling prices of renewable energy Cost of Solar modules divided by 5 in last 5 years, to divide again by 2 in coming 20 years. This is now competitive with electricity prices and tariff. Only about 0.08% of the planet needs to be equipped with solar panels to cover world energy needs (125,000km²)   Solar will reach (& already does) competitiveness with retail (& some day wholesale) prices of electricity. > Considerable modification of the traditional electricity distribution paradigm (solar + battery cheaper than retail electricity). Go for distribution of energy (small units) rather than high capex/opex power plants.   Energy of the sun everyday = 3,500 times what humanity will consume in 2050…   MORE CONNECTED: The Internet of Things will connect 50 billion more devices in the next 5 years. Also, think of all the sensors and embedded electronics in machines on shopfloors and plants all over the world. This will add new operational intelligence from data uncovered. This, in turn, will drive vast efficiency opportunities. Connectivity, ladies and gentlemen, is pervasive – all industries, all levels of enterprise and society.   Data centers alone = 1-2% of total world electricity consumption, but the entire ICT sector = 10%. Consumption doubled btw 2000/2005, and grew at +56% btw 2005-2010. Digitization is also changing lives : Faster, simpler, more collaborative – More efficient   MORE EFFICINECY OPPORTUNITIES: Our more electric world; the more distributed energy world; and the more connected world… they come together to create a more efficient world for us.   However, two-thirds of the energy efficiency potential remains untapped1. There is massive energy efficiency opportunities in Industry, Infrastructure, Buildings and Datacenters. There is also significant energy wastage due to inefficient processes in industries such as refineries, steel, and cement, to name a few.   One way to reduce this wastage is to embrace new technologies which can drive more efficient processes. Typically, the adoption of new technologies can result about 30% savings in energy consumption.   Energy is wasted by inefficient transformation industries (refineries for instance). Around 760MTOE per Y in 2013 (out of 11BTOE consumed) Energy is wasted by inefficient power & heat transformation. Around 3,2BTOE per Y in 2013 (out of 11BTOE consumed) ! Reducing electricity consumption thus has a direct massive impact on primary resources consumption (which is why primary resource prices might remain durably low if large consumers such as Europe, NAM, China go forward with carbon reduction programs). This is just #1 topic. Energy is inefficiently used in all segments (ref. to the slide), and massive opportunities exist. Main paradigm: deploy what’s best (usually new tech easily consumes 30-50% less than old one). Few e.g.. Steel industry (electrical arc furnace 5GJ/t vs traditional furnace 14GJ/t). Cement plants (new tech 25% reduction at 3GJ/t). Aluminium plants (13% saving only with new process & equipment) Electric motors = 46% of total electricity consumption (64% in the industry). 21% could be saved (IEA) using EE techniques. Buildings = 30-60% saving depending on granularity (space / time) of the “Active controls” installed. Passive isolation brings 10-15%. Transport – Light duty = considerable progress over last decades. Up to 30% saving on fuel. And even more now with hybrid & full electric technologies. 80% of light duty transportation = small distances (within cities). Smart mobility can also take us there. Transport – Air industry. New Boeing 787 1,3MJ/seat/km vs Boeing 767 1,9MJ/seat/km >> considerable savings Transport – Marine. Shore connection Main issue: willingness to change, inertia of deployment of these new tech Lifetime of industrial plant ~ 50Y (or a power plant by the way) Buildings: by 2050, 75% of existing buildings will still be standing Transportation: sales of new vehicles = 7% of worldwide fleet every year + fleet is increasing (700M cars today vs 3B in 2050). >> very low rate of replacement
  2. Recommended Script :   To understand the emerging new world of distributed energy, we must first understand the old world of energy.   This old world of energy is going through a massive transformation -- from a centralized, linear fashion of power generation, distribution and consumption….. to a more distributed and connected one.   NEXT SLIDE
  3. Recommended Script :   To understand the emerging new world of distributed energy, we must first understand the old world of energy.   This old world of energy is going through a massive transformation -- from a centralized, linear fashion of power generation, distribution and consumption….. to a more distributed and connected one.   NEXT SLIDE
  4. We need to have a look inside a UPS We need to understand how a UPS works Everybody know a rectifier (Used for your phones, Laptop) This is called double conversion This is how most UPS’s are made
  5. Recommended Script :   To understand the emerging new world of distributed energy, we must first understand the old world of energy.   This old world of energy is going through a massive transformation -- from a centralized, linear fashion of power generation, distribution and consumption….. to a more distributed and connected one.   NEXT SLIDE
  6. Recommended Script :   To understand the emerging new world of distributed energy, we must first understand the old world of energy.   This old world of energy is going through a massive transformation -- from a centralized, linear fashion of power generation, distribution and consumption….. to a more distributed and connected one.   NEXT SLIDE
  7. L'utilisation est alimentée directement au travers d'un filtre lorsque l'alimentation normale est présente et de qualité suffisante. Lors d'une défaillance de cette alimentation, l'utilisation est alimentée par l'onduleur à partir de sa batterie . Ces alimentations sont réservées aux récepteurs de faible puissance de type bureautique ou micro informatique avec une alimentation normale peu perturbée. Le temps de transfert de l'alimentation normale vers l'onduleur est de quelques millisecondes à une dizaine de millisecondes habituellement ( temps de basculement d'un relais ) .
  8.   L'utilisation est alimentée directement au travers d'un dispositif de couplage / découplage lorsque l'alimentation normale est de qualité suffisante. L'onduleur est alors en parallèle avec l'utilisation et prélève l'énergie nécessaire à la charge de la batterie. Un dispositif de filtrage peut être intercalé entre l'alimentation normale et l'onduleur afin d'améliorer le taux de distorsion de la tension et également apporter une régulation de la tension de sortie. Dans ce dernier cas le courant réactif prélevé a l'alimentation normale peut être élevé puisque c'est généralement une inductance qui supporte la différence de tension entre les deux sources. Lors de la disparition de l'alimentation normale, le dispositif de découplage permet à l'onduleur d'alimenter directement l'utilisation. Ce dispositif de découplage doit évidemment être rapide pour éviter de perturber l'utilisation pendant le transfert des alimentations.   Bien que certaines alimentations puissent assurer une régulation de l'amplitude, la régulation de fréquence n'est pas possible et cette particularité limite leur utilisation à des alimentations normales ne présentant pas de perturbation de fréquence. Elles sont donc à éviter dans le cas où un groupe moteur thermique-générateur peut se substituer au réseau lorsque celui-ci disparaît, en raison des fluctuations de fréquence de tels dispositifs surtout pour les puissances faibles.
  9. L'utilisation est alimentée à travers la double conversion du redresseur et de l'onduleur, à partir de l'alimentation normale , lorsque celle-ci est dans les tolérances de tension et de fréquence admissibles par le redresseur . Lorsque l'alimentation normale sort de ces tolérances l'utilisation continue d'être alimentée par l'onduleur à partir de la batterie. L'utilisation est donc en permanence alimentée par l'onduleur qui délivre une tension dont la stabilité en amplitude et en fréquence peut être très élevée. De plus le nombre de phases ainsi que les fréquences en entrée et en sortie peuvent être différents. Le redresseur et la batterie délivrent une énergie hautement disponible que l'onduleur transforme en énergie de haute qualité.   Certaines ASI comportent en plus de la chaîne redresseur / batterie / onduleur une voie by-pass, permettant généralement à travers un contacteur statique, d'alimenter directement l'utilisation en cas de forte surcharge ou d'arrêt de la chaîne précédente. Cette voie by-pass peut être de plus raccordée à une source appelée alimentation 2, différente de l'alimentation normale afin d'augmenter la disponibilité.   Ces alimentations sont donc utilisées pour toutes les charges nécessitant un niveau de qualité élevé telles que les salles informatiques, les applications médicales ou les équipements de contrôle de procédés industriels. Elles s'imposent pour la plupart des applications lorsque l'alimentation normale est très perturbée comme dans les réseaux industriels ou ruraux.
  10. All customers have different needs for UPS protection, depending on the critical level of the bizz they a running Therefore is important that we listen and understand the customers needs Here some UPS configurations we support with our offering
  11. All customers have different needs for UPS protection, depending on the critical level of the bizz they a running Therefore is important that we listen and understand the customers needs Here some UPS configurations we support with our offering
  12. Let try to convert these boxes into real UPS’s A UPS is not just a UPS.....
  13. Galaxy VX is offering what we call.. multi-mode operation.. This is to ensure we can select the best possible operation mode… for best performance… for a given environment... Double conversion… ECO mode…& ECOnversion Galaxy VX is a Double conversion UPS... …developed with a 4-level inverter technology for high efficiency.. …and highest reliability in terms of UPS design And the way a double conv ups’s works… ..Power from the grid goes to the PFC… which converts the AC to DC store energy can be stored on the batteries. The Inverter the creates a new perfect sin wave to the load Galaxy VX also supports ECO mode..... Which is a operation mode.. which only offer high efficiency.. and very low reliability…not recommended to use Finally we have ECOnversion…. which is a combination of ECO mode… and Double Conversion…This is something NEW… we will also have a closer look at this doing the following slides -NEXT- ------ADD TO SLIDE AT SOME TIME------ Double conversion.. for tough environment ECO mode.. for none critical applications ECOnversion.. For the clever customer…
  14. So before I will introduce this new innovative way solution… we need to understand the basic functionality of how a UPS works…. “READ” Double line by line “READ” ECO mode line by line “Click”
  15. I would like present a new innovative UPS operation mode…. called ECOnversion… Read line by line…. (Novel : Ny)
  16. The benefit of ECOnversion…. is off cause the capability to safely protect the critical load.. and to remove any harmonics created by the load …and to correct the power factor.. caused by the load.. when needed…. Another major benefit of ECOnversion.. is that.. “all this” is achieved while using.. a minimum of energy… consumed by the UPS…UPS losses.. This results in “major” energy saving in the electricity consumption by the UPS… living more power to the load.. and big savings on the electricity bill for the customer.. ..Lets have a closer look at the savings… we can achieve by using ECOnversion “Read Double Conv.” “Read ECOnversion” “CLICK” -> “Read Result” -NEXT-
  17. SPoT mode… or Smart Power Test is a “On-side function test” of all critical components of the UPS.. like Power modules, SSW, Battery Charger and even the battery…. All performed with little preparation… or the requirement to rent a load bank…pulling cables to loadbank… etz. “Read line by line” The Smart Power Test.. in normal operation is conducted by….. 3 types of SPoT mode test are available
  18. 3 types of SPoT mode test are available SPoT mode is full functional test of the UPS… and is performed by the FSE before the critical load is connected to the UPS
  19. The Li-ion battery solution consist of a ”LIB Rack” Multible ”battery modules” (30,4V) are inserted in the ”Rack” Each ”battery Module” includes 8 LIB cell’s (each 3,8V) --READ SLIDE-- SOC: State of charge, for batteries SOH: State of health, for batteries System BMS - Voltage, SMPS information, SOC (State of charge), SOH (State of health), Fault/Alarm Rack BMS - Voltage, Current, MCCB information, SOC, SOH, Trip/Alarm Module BMS - Voltage, Temperature
  20. To summerize Li-ion -- READ LINE BY LINE –