StacoVAR: Power Factor
Correction
POWER FACTOR
CORRECTION (PFC)
Power Factor (PF):
Term used in regard to the efficiency of
an electrical power distribution system.
Power factor is a measurement
between the current and voltage phase
shift waveforms.
PF COMPONENTS
Power factor consist of 3 components:
• KW, which is the working, or real, power
(does the actual work)
• KVA, which is called the apparent power
(relationship between KW and KVAR)
• KVAR, or reactive power
(does not do any beneficial work)
DETERMINE YOUR PF
Divide the working power (KW) by the
apparent power (KVA)
PF of 1, or unity, being the highest (or best)
power factor possible.
When correcting PF, in general, a measurement
of .9 or higher is considered good.
INDUSTRIES KNOWN TO
HAVE POOR PF
Industries where power factor problems
are common:
o Steel/Foundries
o Chemicals
o Textiles
o Pulp and paper processing
o Automotive and other automated assembly
o Rubber and plastics processing
o Breweries
o Electroplating
CAUSES OF PF PROBLEMS
Loads that cause power factor problems:
o Induction motors
o Electric arc furnaces
o Machining
o Stamping
o Welding
o Variable Frequency Drives (VFDs)
o Fluorescent lights with magnetic ballasts
o Computers
o Computer controlled equipment
BENEFITS OF IMPROVING
PF
Improving PF:
o Lowers your electrical cost
o Increases KVA capacity (increase the
KW used for the same KVA)
o Improves voltage regulation
o Allows for the size reductions in
cables, transformers and switchgear
o Allows for expansion without additional
electrical improvements
UTILITY COMPANY’S POINT
OF VIEW
Raising the average operating
PF of the entire grid network
from .70 to .90 means:
oReduced costs from inefficiencies
oIncreased generation and distribution
potential
oLower demand on the grid
BETTER PF MEANS
Utilities can save hundreds of thousands of tons of
fuel (and produce fewer emissions), have more
transformers available, and reduce building new
power plants and their support systems.
This is why more utility companies are starting to
charge a “Power Factor Penalty” so they can
recover additional cost they incur from
supporting an inefficient system.
PF IMPROVEMENT
EXAMPLE
Assume you have a load of 100kVA with a PF
of .80, then you have enough power to light 800
100-wattlight bulbs. If you improve the PF to .95,
you now have enough power to light 950 100-watt
light bulbs.
PF IMPROVEMENTS CAN
SAVE $
Because power factor correction
capacitors:
o Use less energy
o Lengthen the life of equipment
o Reduce electrical requirements for any new or future
equipment that is installed
UTILITY KVA BILLING
Most utilities use the kVA billing method
therefore:
o You are charged for the current your system draws from the grid
o Many utilities add a surcharge or adjustment for PF.
o Special tariffs applied
o Interruptible rates applied
o Off-peak rates
Some utilities give credits or bonuses for higher than average
PF, or one that is above a predetermined level
EXAMPLE
Most utilities use the kVA billing method therefore:
o You are charged for the current your system draws from the grid
o Many utilities add a surcharge or adjustment for PF.
o Special tariffs applied
o Interruptible rates applied
o Off-peak rates
Some utilities give credits or bonuses for higher than average
PF, or one that is above a predetermined level
RETURN ON INVESTMENT
(ROI)
Using the previous example, if you
are billed at $11.22 per kVA:
o100kW @ .70 PF = 142 kVA,
or $1,593
o100kW @ .95 PF = 105 kVA,
or $1,178
This represents a monthly savings of $415, or
$4,980 annually. Assuming the equipment cost
was $5,600 the ROI would be about 14 months.
After this period there can be an ongoing 26%
savings.
PF CORRECTION
CAPACITORS
A capacitor’s function is to:
o Provide kilovars to a system at the point of
connection
o Improve PF
o Reduce lagging components on the circuit
o Reduce power losses
o Reduce kVA load.
o Provide reactive power to replace the
VARs wasted by an inefficient load
PF CORRECTION
CAPACITORS
Are the most economical means
of improving PF because of
their:
oRelative Low Cost
oEasy Installation
oLow Installation Cost
oMinimal Maintenance
oHigh Efficiency and Low Losses
DETERMINING THE PF
Find poor PF problems by:
oMonitoring at the incoming service entrance
or at specific loads can identify problems
within a facility
o Conduct a Facility Power Study and have
reviewed by a power analyst / consultant
Some utilities offer analysis for businesses
wanting to improve their efficiency.
TYPES OF CAPACITOR
SYSTEMS
oSimple small fixed capacitors can be
installed at a single motor to be switched on
and off with the load, this is ideal.
• However, this can be expensive, and
can create technical problems, since it
may require a large number of low-
power units at several points throughout
the facility, making it difficult to monitor
and maintain over time
TYPES OF CAPACITOR
SYSTEMS
oAutomatic capacitor bank installed on the
bus bars of the distribution panel. This
method provides centralized PF
correction for an entire facility.
• It also allows for fixed capacitors to be added
to correct the power of any piece of
equipment that causes a significant problem.
INSTALLATIONS LOCATIONS
NEXT STEP - DETERMINE
THE KVAR
After you have determined what type capacitor
system you need, the next step is to determine
the size or amount of kVAR, you need to correct
the PF.
Staco Energy Products Co. has easy to use
tables that will assist you in determining the
required kVAR you need to add to your system
to improve the PF.
NEXT STEP
Example: If your existing PF is .71 and you want to bring it
up to .95, the number in the table is .663 (kW multiplier).
Multiply .663 by the number of kW your system uses (say
590). The total kVAR would require 390 kVAR, which would
be rounded up to 400 kVAR. Therefore a 400kVAr rated unit
would be used.
FINAL STEP
Purchase a Staco
Automatic Switched
400 kVAR StacoVAR
System,
OF COURSE!
FIXED CAPACITOR
ASSEMBLIES
Fixed capacitor assemblies, also called motor load
capacitors, are ideal for improving PF where
induction motors are located. They are also used
anywhere there are small kVAR requirements.
You can achieve maximum benefits from capacitors
when located at the load. Because the capacitor is
Usually switched on and off with the load, over
correction is also avoided
SIZING FIXED CAPACITORS
Capacitors must be carefully sized when switched
with the motor as a unit, because:
o Dangerous over voltages and transient torques can
occur if the kVAR exceeds the motor’s magnetizing
current
WHAT YOU NEED TO KNOW!
When sizing fixed capacitors you
need the following
Motor information:
oU-Frame (U, T etc.)
oNEMA Class (B, 2B, C, D etc.)
oA or B Normal Starting Torque – Normal
Running Current
INSTALLATION LOCATIONS
1. Motor Side of Overload Relay
o Use this for new motor installations where overloads
can be sized in reference to reduced current draw
o Existing motors where no overload change is needed
2. Motor Side of Starter
o Use this for existing motors when the overload rating
exceeds code
3. Line Side of Starter
o Use this for Multi-speed motors
o Motors that are jogged or reversed
o Motors that star frequently
o Starters that disconnect/reconnect capacitors during
cycle and starters with open transitions
o High inertia loads, when disconnecting the motor with
the capacitor turns the motor into a self-exciting
generator
INSTALLATION LOCATIONS
MOTOR REFERENCE
TABLES
Staco Energy Products Co. has
all the reference tables
available to make it easier to
select and size the correct
StacoVAR Motor Load
Capacitor for your application.
STACOVAR SOLUTIONS
Staco Energy provides various solutions,
specific to correction of poor power
factor and/or harmonics. Equipment
available:
o Fixed capacitors from 2 to 400kvar.
o Automatically switched type from 75 to
600kvar (240vac) and 100 to 2400kvar (480
and 600vac).
STACOVAR FIXED MODELS
Fixed Power Factor Correction: PF
Model
o Wall mounted/freestanding motor load “ML”
products include liquid filled long life three phase
power capacitors and freestanding (larger kvar)
products with heavy duty, dry type three phase
power capacitors, and both types include
discharge resistors and over pressure protection.
o Fixed only, no switching, no control, located at
individual motor loads.
STACOVAR STANDARD
FEATURES
Automatic Power Factor Correction Standard Features:
o NEMA 1 enclosure, with bottom entry access and modular
design allowing for easy future expansion.
o UL 508A listed, complete assembly.
o Heavy duty, dry type three phase power capacitors, with
discharge resistors and over pressure protection.
o PA units accommodate up to 10% THD environment.
o (PH, PT, and PR units use 480 volt rated capacitors for 240 volt
system and 690 volt rated capacitors for 480 volt system, for
even higher harmonic level protection).
o 5-year warranty on the capacitors.
o Individual step fuse protection (200kaic) with blown fuse
indication.
o Control power transformer with fused primary & secondary, and
nickel-plated electrical grade cooper bus bar system.
STACOVAR AUTOMATIC PA
MODELS
Automatic Power Factor Correction:
PA Model
Additional features:
o Type of Switching: Electro-mechanical contactors with
damping resistors to reduce switching inrush currents.
o Controller: adjustable (0.5 to 300) second response
microprocessor based power factor controller (twelve-step
regulation) with front panel LED display.
o Automatically switched (contactors), basic, economical.
Product accommodates most requirements.
STACOVAR AUTOMATIC PH
MODELS
Automatic Power Factor Correction:
PH Model
Additional features:
o Type of Switching: Electro-mechanical, heavy duty contactors.
o Controller: adjustable (0.5 to 300) second response
microprocessor based power factor controller (twelve-step
regulation) with front panel LED display.
o Reactor: Three phase 5TH order, iron-core reactors with a
227hz tuning frequency.
o Automatically switched (contactors), for a harmonic
environment where capacitors may be damaged. Use of iron-
core reactors necessary for a detuning - majority of
requirements for the 5th order. Product accommodates many
applications and is cost effective.
STACOVAR OPTIONS
Automatic Power Factor Correction
Options:
o Circuit Breakers: Circuit breakers are three-pole molded
case type, with a thermal-magnetic trip. Amperes are
based upon breaker frame size. Circuit Breaker option
may increase standard cabinet dimensions, consult
factory for sizing.
o TVSS – Surge Protection.
o CT – Current Transformer: multi-tap, (3000:5, 2500:5,
2200:5, 2000:5, 1500:5, 1200:5, 1000:5, 800:5, 500:5,
300:5), split core type for ease of installation. CT’s
shipped loose. 1-5% accuracy depending on ratio.
QUESTIONS?
Toll Free: 866.261.1191 | sales@stacoenergy.com | www.stacoenergy.com

More Related Content

What's hot

Automatic Power Factor Improvement by Using PLC & SCADA
Automatic Power Factor Improvement by Using PLC & SCADAAutomatic Power Factor Improvement by Using PLC & SCADA
Automatic Power Factor Improvement by Using PLC & SCADA
ferozpatowary
 
Automatic power factor correction unit
Automatic power factor correction unitAutomatic power factor correction unit
Automatic power factor correction unit
Biswajit Pratihari
 
1590053 634881478003587500
1590053 6348814780035875001590053 634881478003587500
1590053 634881478003587500
Navyasri Jiguru
 
power factor correction using smart relay
power factor correction using smart relaypower factor correction using smart relay
power factor correction using smart relay
Hatem Seoudy
 
Automatic Power Factor Corrector Using Arduino report
Automatic Power Factor Corrector Using Arduino reportAutomatic Power Factor Corrector Using Arduino report
Automatic Power Factor Corrector Using Arduino report
Self-employed
 

What's hot (20)

Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System Report
 
power factor correction soham+niraj
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+niraj
 
automatic power factor controller
automatic power factor controllerautomatic power factor controller
automatic power factor controller
 
Power factor
Power factorPower factor
Power factor
 
Automatic Power Factor Improvement by Using PLC & SCADA
Automatic Power Factor Improvement by Using PLC & SCADAAutomatic Power Factor Improvement by Using PLC & SCADA
Automatic Power Factor Improvement by Using PLC & SCADA
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
Automatic power factor correction unit
Automatic power factor correction unitAutomatic power factor correction unit
Automatic power factor correction unit
 
1590053 634881478003587500
1590053 6348814780035875001590053 634881478003587500
1590053 634881478003587500
 
Power Factor Basics
Power Factor BasicsPower Factor Basics
Power Factor Basics
 
Power factor(r)
Power factor(r)Power factor(r)
Power factor(r)
 
Power Factor
Power FactorPower Factor
Power Factor
 
Project report soofi
Project report soofiProject report soofi
Project report soofi
 
automatic power factor correction
automatic power factor correction automatic power factor correction
automatic power factor correction
 
Power factor presentation
Power factor presentationPower factor presentation
Power factor presentation
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
 
power factor correction using smart relay
power factor correction using smart relaypower factor correction using smart relay
power factor correction using smart relay
 
Power Quality Systems and Power Factor Correction Presentation
Power Quality Systems and Power Factor Correction PresentationPower Quality Systems and Power Factor Correction Presentation
Power Quality Systems and Power Factor Correction Presentation
 
Power factor introduction and its correction final
Power factor introduction and its correction final Power factor introduction and its correction final
Power factor introduction and its correction final
 
Benifits of power factor improvement for industry
Benifits of power factor improvement for industryBenifits of power factor improvement for industry
Benifits of power factor improvement for industry
 
Automatic Power Factor Corrector Using Arduino report
Automatic Power Factor Corrector Using Arduino reportAutomatic Power Factor Corrector Using Arduino report
Automatic Power Factor Corrector Using Arduino report
 

Viewers also liked

Power factor improvement of an induction motor
Power factor improvement of an induction motorPower factor improvement of an induction motor
Power factor improvement of an induction motor
IIT Roorkee
 
Soft power factor modification using static
Soft power factor modification using staticSoft power factor modification using static
Soft power factor modification using static
chodachude
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
slmnsvn
 

Viewers also liked (19)

Power factor improvement of an induction motor
Power factor improvement of an induction motorPower factor improvement of an induction motor
Power factor improvement of an induction motor
 
3 Phase Power Factor Correction (PFC)
3 Phase Power Factor Correction (PFC)3 Phase Power Factor Correction (PFC)
3 Phase Power Factor Correction (PFC)
 
Kvar Presentation Ppt 8.8.08[1]
Kvar Presentation Ppt 8.8.08[1]Kvar Presentation Ppt 8.8.08[1]
Kvar Presentation Ppt 8.8.08[1]
 
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
 
Power Factor
Power FactorPower Factor
Power Factor
 
Soft power factor modification using static
Soft power factor modification using staticSoft power factor modification using static
Soft power factor modification using static
 
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
 
Ashutosh CV
Ashutosh CVAshutosh CV
Ashutosh CV
 
IEEE Sustech Presentation - Energy and Environment in Indonesia
IEEE Sustech Presentation - Energy and Environment in IndonesiaIEEE Sustech Presentation - Energy and Environment in Indonesia
IEEE Sustech Presentation - Energy and Environment in Indonesia
 
Basic ML
Basic MLBasic ML
Basic ML
 
Design of a 3-phase FC-TCR Static Var Compensator for Power factor correction...
Design of a 3-phase FC-TCR Static Var Compensator for Power factor correction...Design of a 3-phase FC-TCR Static Var Compensator for Power factor correction...
Design of a 3-phase FC-TCR Static Var Compensator for Power factor correction...
 
Kvar Power Point
Kvar Power PointKvar Power Point
Kvar Power Point
 
AccuSine pfv+
AccuSine pfv+ AccuSine pfv+
AccuSine pfv+
 
Identifying & correcting poor power factor
Identifying & correcting poor power factor Identifying & correcting poor power factor
Identifying & correcting poor power factor
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
Energy & Environment Engg
Energy & Environment EnggEnergy & Environment Engg
Energy & Environment Engg
 
generating equipment
generating equipmentgenerating equipment
generating equipment
 
Three phase power factor improvement using Vienna Rectifier
Three phase power factor improvement using Vienna Rectifier Three phase power factor improvement using Vienna Rectifier
Three phase power factor improvement using Vienna Rectifier
 
P.F.C. Methods in Non-Linear Loads
P.F.C. Methods in Non-Linear LoadsP.F.C. Methods in Non-Linear Loads
P.F.C. Methods in Non-Linear Loads
 

Similar to Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Correction

Energy Efficiency in Electrical Systems.pptx
Energy  Efficiency in Electrical Systems.pptxEnergy  Efficiency in Electrical Systems.pptx
Energy Efficiency in Electrical Systems.pptx
PoojaAnupGarg
 

Similar to Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Correction (20)

APFC AMTL 30.01.2015
APFC  AMTL  30.01.2015APFC  AMTL  30.01.2015
APFC AMTL 30.01.2015
 
Sme apfc panel catalogue
Sme apfc panel catalogueSme apfc panel catalogue
Sme apfc panel catalogue
 
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUESpower factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
 
Power Factor.ppt
Power Factor.pptPower Factor.ppt
Power Factor.ppt
 
powerfactor.pdf
powerfactor.pdfpowerfactor.pdf
powerfactor.pdf
 
Power Factor : Basics and Benefits of Improvement
Power Factor : Basics and  Benefits of ImprovementPower Factor : Basics and  Benefits of Improvement
Power Factor : Basics and Benefits of Improvement
 
Automatic power factor correction and its advantage
Automatic power factor correction and its advantageAutomatic power factor correction and its advantage
Automatic power factor correction and its advantage
 
Product: Power Factor & Harmonics: StacoSine: Technical
Product: Power Factor & Harmonics: StacoSine: TechnicalProduct: Power Factor & Harmonics: StacoSine: Technical
Product: Power Factor & Harmonics: StacoSine: Technical
 
Reducing Your Electric bills & your Carbon Footprint
Reducing Your Electric bills & your Carbon FootprintReducing Your Electric bills & your Carbon Footprint
Reducing Your Electric bills & your Carbon Footprint
 
Automatic Power Factor Corrector
Automatic Power Factor CorrectorAutomatic Power Factor Corrector
Automatic Power Factor Corrector
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
 
capacitors
capacitorscapacitors
capacitors
 
2011 ced capacitors
2011 ced capacitors2011 ced capacitors
2011 ced capacitors
 
Solar ppt
Solar pptSolar ppt
Solar ppt
 
General Power Quality
General Power QualityGeneral Power Quality
General Power Quality
 
Power Shaver Energy Saving Systems
Power Shaver Energy Saving SystemsPower Shaver Energy Saving Systems
Power Shaver Energy Saving Systems
 
Electrical energy issues presented by arshad khan chiniot power limited
Electrical energy issues presented by arshad khan chiniot  power limitedElectrical energy issues presented by arshad khan chiniot  power limited
Electrical energy issues presented by arshad khan chiniot power limited
 
09 rasool opportunities and challenges in using advanced inverter functionality
09 rasool opportunities and challenges in using advanced inverter functionality09 rasool opportunities and challenges in using advanced inverter functionality
09 rasool opportunities and challenges in using advanced inverter functionality
 
Improvement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using CapacitorImprovement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using Capacitor
 
Energy Efficiency in Electrical Systems.pptx
Energy  Efficiency in Electrical Systems.pptxEnergy  Efficiency in Electrical Systems.pptx
Energy Efficiency in Electrical Systems.pptx
 

More from Staco Energy

More from Staco Energy (19)

FirstLine PE
FirstLine PEFirstLine PE
FirstLine PE
 
FirstLine P: 300-500 kVA
FirstLine P: 300-500 kVAFirstLine P: 300-500 kVA
FirstLine P: 300-500 kVA
 
Staco Energy: Corporate Overview
Staco Energy: Corporate OverviewStaco Energy: Corporate Overview
Staco Energy: Corporate Overview
 
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
Product: Power Factor & Harmonics: StacoSine: MGE filter presentationProduct: Power Factor & Harmonics: StacoSine: MGE filter presentation
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
 
Product: Power Factor & Harmonics: StacoSine: Harmonics
Product: Power Factor & Harmonics: StacoSine: HarmonicsProduct: Power Factor & Harmonics: StacoSine: Harmonics
Product: Power Factor & Harmonics: StacoSine: Harmonics
 
Product: Battery Monitoring: FirstLine BMS
Product: Battery Monitoring: FirstLine BMSProduct: Battery Monitoring: FirstLine BMS
Product: Battery Monitoring: FirstLine BMS
 
General: Power Quality Presentation
General: Power Quality PresentationGeneral: Power Quality Presentation
General: Power Quality Presentation
 
General: Power Problems
General: Power ProblemsGeneral: Power Problems
General: Power Problems
 
Product: UPS: FirstLine XD
Product: UPS: FirstLine XDProduct: UPS: FirstLine XD
Product: UPS: FirstLine XD
 
Product: Voltage Control: StacoAVR
Product: Voltage Control: StacoAVRProduct: Voltage Control: StacoAVR
Product: Voltage Control: StacoAVR
 
Product: UPS: UniStar VP
Product: UPS: UniStar VPProduct: UPS: UniStar VP
Product: UPS: UniStar VP
 
Product: UPS: UniStar V
Product: UPS: UniStar VProduct: UPS: UniStar V
Product: UPS: UniStar V
 
Product: UPS: UniStar SCLI924
Product: UPS: UniStar SCLI924Product: UPS: UniStar SCLI924
Product: UPS: UniStar SCLI924
 
Product: UPS: FirstLine PL 924
Product: UPS: FirstLine PL 924Product: UPS: FirstLine PL 924
Product: UPS: FirstLine PL 924
 
Product: UPS: FirstLine P
Product: UPS: FirstLine PProduct: UPS: FirstLine P
Product: UPS: FirstLine P
 
Product: UPS: Different Types of UPS
Product: UPS: Different Types of UPSProduct: UPS: Different Types of UPS
Product: UPS: Different Types of UPS
 
Product: Power Factor & Harmonics: StacoVAR: Part Numbers
Product: Power Factor & Harmonics: StacoVAR: Part NumbersProduct: Power Factor & Harmonics: StacoVAR: Part Numbers
Product: Power Factor & Harmonics: StacoVAR: Part Numbers
 
Company: Intro to Staco
Company: Intro to StacoCompany: Intro to Staco
Company: Intro to Staco
 
Company: Staco Solutions and Applications
Company: Staco Solutions and ApplicationsCompany: Staco Solutions and Applications
Company: Staco Solutions and Applications
 

Recently uploaded

FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
dollysharma2066
 
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
amitlee9823
 
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
lizamodels9
 
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
amitlee9823
 
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service BangaloreCall Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
amitlee9823
 

Recently uploaded (20)

Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
 
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 MonthsSEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
 
Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1
 
Business Model Canvas (BMC)- A new venture concept
Business Model Canvas (BMC)-  A new venture conceptBusiness Model Canvas (BMC)-  A new venture concept
Business Model Canvas (BMC)- A new venture concept
 
Eluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
Eluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort ServiceEluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
Eluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
 
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
 
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort ServiceMalegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
 
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
 
Famous Olympic Siblings from the 21st Century
Famous Olympic Siblings from the 21st CenturyFamous Olympic Siblings from the 21st Century
Famous Olympic Siblings from the 21st Century
 
Falcon Invoice Discounting platform in india
Falcon Invoice Discounting platform in indiaFalcon Invoice Discounting platform in india
Falcon Invoice Discounting platform in india
 
JAYNAGAR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
JAYNAGAR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRLJAYNAGAR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
JAYNAGAR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
 
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
 
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service BangaloreCall Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
 
Falcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business GrowthFalcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business Growth
 
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
 

Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Correction

  • 2. POWER FACTOR CORRECTION (PFC) Power Factor (PF): Term used in regard to the efficiency of an electrical power distribution system. Power factor is a measurement between the current and voltage phase shift waveforms.
  • 3. PF COMPONENTS Power factor consist of 3 components: • KW, which is the working, or real, power (does the actual work) • KVA, which is called the apparent power (relationship between KW and KVAR) • KVAR, or reactive power (does not do any beneficial work)
  • 4. DETERMINE YOUR PF Divide the working power (KW) by the apparent power (KVA) PF of 1, or unity, being the highest (or best) power factor possible. When correcting PF, in general, a measurement of .9 or higher is considered good.
  • 5. INDUSTRIES KNOWN TO HAVE POOR PF Industries where power factor problems are common: o Steel/Foundries o Chemicals o Textiles o Pulp and paper processing o Automotive and other automated assembly o Rubber and plastics processing o Breweries o Electroplating
  • 6. CAUSES OF PF PROBLEMS Loads that cause power factor problems: o Induction motors o Electric arc furnaces o Machining o Stamping o Welding o Variable Frequency Drives (VFDs) o Fluorescent lights with magnetic ballasts o Computers o Computer controlled equipment
  • 7. BENEFITS OF IMPROVING PF Improving PF: o Lowers your electrical cost o Increases KVA capacity (increase the KW used for the same KVA) o Improves voltage regulation o Allows for the size reductions in cables, transformers and switchgear o Allows for expansion without additional electrical improvements
  • 8. UTILITY COMPANY’S POINT OF VIEW Raising the average operating PF of the entire grid network from .70 to .90 means: oReduced costs from inefficiencies oIncreased generation and distribution potential oLower demand on the grid
  • 9. BETTER PF MEANS Utilities can save hundreds of thousands of tons of fuel (and produce fewer emissions), have more transformers available, and reduce building new power plants and their support systems. This is why more utility companies are starting to charge a “Power Factor Penalty” so they can recover additional cost they incur from supporting an inefficient system.
  • 10. PF IMPROVEMENT EXAMPLE Assume you have a load of 100kVA with a PF of .80, then you have enough power to light 800 100-wattlight bulbs. If you improve the PF to .95, you now have enough power to light 950 100-watt light bulbs.
  • 11. PF IMPROVEMENTS CAN SAVE $ Because power factor correction capacitors: o Use less energy o Lengthen the life of equipment o Reduce electrical requirements for any new or future equipment that is installed
  • 12. UTILITY KVA BILLING Most utilities use the kVA billing method therefore: o You are charged for the current your system draws from the grid o Many utilities add a surcharge or adjustment for PF. o Special tariffs applied o Interruptible rates applied o Off-peak rates Some utilities give credits or bonuses for higher than average PF, or one that is above a predetermined level
  • 13. EXAMPLE Most utilities use the kVA billing method therefore: o You are charged for the current your system draws from the grid o Many utilities add a surcharge or adjustment for PF. o Special tariffs applied o Interruptible rates applied o Off-peak rates Some utilities give credits or bonuses for higher than average PF, or one that is above a predetermined level
  • 14. RETURN ON INVESTMENT (ROI) Using the previous example, if you are billed at $11.22 per kVA: o100kW @ .70 PF = 142 kVA, or $1,593 o100kW @ .95 PF = 105 kVA, or $1,178 This represents a monthly savings of $415, or $4,980 annually. Assuming the equipment cost was $5,600 the ROI would be about 14 months. After this period there can be an ongoing 26% savings.
  • 15. PF CORRECTION CAPACITORS A capacitor’s function is to: o Provide kilovars to a system at the point of connection o Improve PF o Reduce lagging components on the circuit o Reduce power losses o Reduce kVA load. o Provide reactive power to replace the VARs wasted by an inefficient load
  • 16. PF CORRECTION CAPACITORS Are the most economical means of improving PF because of their: oRelative Low Cost oEasy Installation oLow Installation Cost oMinimal Maintenance oHigh Efficiency and Low Losses
  • 17. DETERMINING THE PF Find poor PF problems by: oMonitoring at the incoming service entrance or at specific loads can identify problems within a facility o Conduct a Facility Power Study and have reviewed by a power analyst / consultant Some utilities offer analysis for businesses wanting to improve their efficiency.
  • 18. TYPES OF CAPACITOR SYSTEMS oSimple small fixed capacitors can be installed at a single motor to be switched on and off with the load, this is ideal. • However, this can be expensive, and can create technical problems, since it may require a large number of low- power units at several points throughout the facility, making it difficult to monitor and maintain over time
  • 19. TYPES OF CAPACITOR SYSTEMS oAutomatic capacitor bank installed on the bus bars of the distribution panel. This method provides centralized PF correction for an entire facility. • It also allows for fixed capacitors to be added to correct the power of any piece of equipment that causes a significant problem.
  • 21. NEXT STEP - DETERMINE THE KVAR After you have determined what type capacitor system you need, the next step is to determine the size or amount of kVAR, you need to correct the PF. Staco Energy Products Co. has easy to use tables that will assist you in determining the required kVAR you need to add to your system to improve the PF.
  • 22. NEXT STEP Example: If your existing PF is .71 and you want to bring it up to .95, the number in the table is .663 (kW multiplier). Multiply .663 by the number of kW your system uses (say 590). The total kVAR would require 390 kVAR, which would be rounded up to 400 kVAR. Therefore a 400kVAr rated unit would be used.
  • 23. FINAL STEP Purchase a Staco Automatic Switched 400 kVAR StacoVAR System, OF COURSE!
  • 24. FIXED CAPACITOR ASSEMBLIES Fixed capacitor assemblies, also called motor load capacitors, are ideal for improving PF where induction motors are located. They are also used anywhere there are small kVAR requirements. You can achieve maximum benefits from capacitors when located at the load. Because the capacitor is Usually switched on and off with the load, over correction is also avoided
  • 25. SIZING FIXED CAPACITORS Capacitors must be carefully sized when switched with the motor as a unit, because: o Dangerous over voltages and transient torques can occur if the kVAR exceeds the motor’s magnetizing current
  • 26. WHAT YOU NEED TO KNOW! When sizing fixed capacitors you need the following Motor information: oU-Frame (U, T etc.) oNEMA Class (B, 2B, C, D etc.) oA or B Normal Starting Torque – Normal Running Current
  • 27. INSTALLATION LOCATIONS 1. Motor Side of Overload Relay o Use this for new motor installations where overloads can be sized in reference to reduced current draw o Existing motors where no overload change is needed 2. Motor Side of Starter o Use this for existing motors when the overload rating exceeds code 3. Line Side of Starter o Use this for Multi-speed motors o Motors that are jogged or reversed o Motors that star frequently o Starters that disconnect/reconnect capacitors during cycle and starters with open transitions o High inertia loads, when disconnecting the motor with the capacitor turns the motor into a self-exciting generator
  • 29. MOTOR REFERENCE TABLES Staco Energy Products Co. has all the reference tables available to make it easier to select and size the correct StacoVAR Motor Load Capacitor for your application.
  • 30. STACOVAR SOLUTIONS Staco Energy provides various solutions, specific to correction of poor power factor and/or harmonics. Equipment available: o Fixed capacitors from 2 to 400kvar. o Automatically switched type from 75 to 600kvar (240vac) and 100 to 2400kvar (480 and 600vac).
  • 31. STACOVAR FIXED MODELS Fixed Power Factor Correction: PF Model o Wall mounted/freestanding motor load “ML” products include liquid filled long life three phase power capacitors and freestanding (larger kvar) products with heavy duty, dry type three phase power capacitors, and both types include discharge resistors and over pressure protection. o Fixed only, no switching, no control, located at individual motor loads.
  • 32. STACOVAR STANDARD FEATURES Automatic Power Factor Correction Standard Features: o NEMA 1 enclosure, with bottom entry access and modular design allowing for easy future expansion. o UL 508A listed, complete assembly. o Heavy duty, dry type three phase power capacitors, with discharge resistors and over pressure protection. o PA units accommodate up to 10% THD environment. o (PH, PT, and PR units use 480 volt rated capacitors for 240 volt system and 690 volt rated capacitors for 480 volt system, for even higher harmonic level protection). o 5-year warranty on the capacitors. o Individual step fuse protection (200kaic) with blown fuse indication. o Control power transformer with fused primary & secondary, and nickel-plated electrical grade cooper bus bar system.
  • 33. STACOVAR AUTOMATIC PA MODELS Automatic Power Factor Correction: PA Model Additional features: o Type of Switching: Electro-mechanical contactors with damping resistors to reduce switching inrush currents. o Controller: adjustable (0.5 to 300) second response microprocessor based power factor controller (twelve-step regulation) with front panel LED display. o Automatically switched (contactors), basic, economical. Product accommodates most requirements.
  • 34. STACOVAR AUTOMATIC PH MODELS Automatic Power Factor Correction: PH Model Additional features: o Type of Switching: Electro-mechanical, heavy duty contactors. o Controller: adjustable (0.5 to 300) second response microprocessor based power factor controller (twelve-step regulation) with front panel LED display. o Reactor: Three phase 5TH order, iron-core reactors with a 227hz tuning frequency. o Automatically switched (contactors), for a harmonic environment where capacitors may be damaged. Use of iron- core reactors necessary for a detuning - majority of requirements for the 5th order. Product accommodates many applications and is cost effective.
  • 35. STACOVAR OPTIONS Automatic Power Factor Correction Options: o Circuit Breakers: Circuit breakers are three-pole molded case type, with a thermal-magnetic trip. Amperes are based upon breaker frame size. Circuit Breaker option may increase standard cabinet dimensions, consult factory for sizing. o TVSS – Surge Protection. o CT – Current Transformer: multi-tap, (3000:5, 2500:5, 2200:5, 2000:5, 1500:5, 1200:5, 1000:5, 800:5, 500:5, 300:5), split core type for ease of installation. CT’s shipped loose. 1-5% accuracy depending on ratio.
  • 36. QUESTIONS? Toll Free: 866.261.1191 | sales@stacoenergy.com | www.stacoenergy.com