  1. Cliente Dirección Artefacto Tramo Pot (kW) L Real (m) Q (m3/h) Codo 90° Codo 45° Tee a 180° Tee a 90° L Equiv. (m) L Total (m) Ø Nominal Material Ø Real (mm) Velocidad (m/s) ∆p (mbar) Presión Final (mbar) CM-T1 96.37 4.00 8.72 0 0 0 0 0.00 4.00 2025 - PAP 20.000 5.82 1.214 T1-C1 8.79 5.80 0.80 0 0 0 1 1.20 7.00 2025 - PAP 20.000 0.53 0.027 1.241 APROBADO CM-T1 96.37 4.00 8.72 0 0 0 0 0.00 4.00 2025 - PAP 20.000 5.82 1.214 T1-T2 87.58 17.95 7.93 0 0 1 0 0.40 18.35 2025 - PAP 20.000 5.30 4.684 T2-T3 70.00 1.05 6.34 0 0 1 0 0.40 1.45 2025 - PAP 20.000 4.22 0.246 T3-F1 35.00 5.15 3.17 0 0 0 1 1.20 6.35 2025 - PAP 20.000 2.11 0.305 6.448 APROBADO CM-T1 96.37 4.00 8.72 0 0 0 0 0.00 4.00 2025 - PAP 20.000 5.82 1.214 T1-T2 87.58 17.95 7.93 0 0 1 0 0.40 18.35 2025 - PAP 20.000 5.30 4.684 T2-T3 70.00 1.05 6.34 0 0 1 0 0.40 1.45 2025 - PAP 20.000 4.22 0.246 T3-F2 35.00 5.75 3.17 0 0 1 0 0.40 6.15 2025 - PAP 20.000 2.11 0.295 6.438 APROBADO CM-T1 96.37 4.00 8.72 0 0 0 0 0.00 4.00 2025 - PAP 20.000 5.82 1.214 T1-T2 87.58 17.95 7.93 0 0 1 0 0.40 18.35 2025 - PAP 20.000 5.30 4.684 T2-C2 17.58 5.80 1.59 0 0 0 1 1.20 7.00 2025 - PAP 20.000 1.06 0.096 5.993 APROBADO N° Suministro 162397 CTG-GCO-F-VC-009 TABLA DE CÁLCULO DE INSTALACIONES INTERNAS - ALTA PRESIÓN CHECHO'S DNI / RUC 21855208 CÁLCULOS DE LA INSTALACIÓN INTERNA - RENOUARD CUADRATICA - ALTA PRESIÓN COCINA 1 337.26 Caída de Presión Acumulada Caída de Presión Acumulada FREIDORA1 332.06 Caída de Presión Acumulada 332.51 Caída de Presión Acumulada FREIDORA2 COCINA 2 332.05