Time Series Foundation Models - current state and future directions
Heating or Chilled Water Energy Measurement From Outside The Pipe – Simple & Low Cost Heat Meters
1. The new heat/energy metering solution
from Micronics. Simple, low cost, hot
or chilled water energy measurement
from outside the pipe. A smarter
solution than in-line meters!
The U1000 HM is an ultrasonic clamp-on heat/energy meter that uses
ultrasound to measure flow rate and PT100 temperature sensors to
measure flow and return temperatures. The U1000 HM displays energy rate
and totalised energy with pulse output and Modbus communication, so it can
be used as a standalone meter or as an integral part of an aM&T or BEM’s
system.
Simple to install – clamp-on to the pipe, set the pipe diameter and connect the
power, no specialist skills or tools required and Modbus compatible.
• Rate and totalised heat/energy demand
• Easy to install
• Clamp-on flow and temperature sensors
• Lower installed cost than in-line meters
Ultraflo U1000 HM
For further information please visit:
www.micronicsflowmeters.com
or call
+44 (0)1628 810456
MADE IN
BRITAIN
Tel: +44 (0)191 490 1547
Fax: +44 (0)191 477 5371
Email: northernsales@thorneandderrick.co.uk
Website: www.heattracing.co.uk
www.thorneanderrick.co.uk
2. U1000 HM Specification
Measurement Technique: Transit time and PT100
Class B 4 wire
Turn Down Ratio: 200:01
Heat Meter Standard: The Heat/Energy calculation is
designed to comply with EN1434 section 6, third party
certification pending.
Accuracy: +/-1-3% of flow reading for 0.3m/s
Flow Velocity Range: 0.1 to 10m/s
Pipe Range: 25mm – 115mm OD
Water Temp Range: 0°C to 85°C
Temperature sensors: Clamp-on PT100 Class B 4 wire,
range 0 to 85°C, resolution 0.1 °C
Output: Pulse or Frequency, Energy or Volume flow
Modbus Communication: Modbus RTU slave, RS485
serial link hardware layer. Energy, power, temperature
and flow.
External Power Supply: 12V-24V +/- 10% AC/DC
at 7 watts
Electronics Enclosure: IP54
Input/Output Cable: 5m x 6 core for power in and
data out
Dimensions: 250mm x 48mm x 90mm
(electronics + guide rail)
U1000 HM – Fixed Ultrasonic Heat/Energy Meter
with Modbus Communication
Ultraflo U1000 HM
INDUSTRIES:
n Energy Management
n Building Services
RECOMMENDED FOR:
n Hot water 85°C
n Chilled water
APPLICATION/USE:
n Heat/energy metering in energy management
or building services applications for LTHW or
chilled water circuits.
PIPE MATERIALS:
n Steel
n Plastic
n Copper
Micronics Limited accepts no responsibility or liability if
this product has not been installed in accordance with the
installation instructions applicable to the product.
Micronics reserve the right to alter any specification without
notification.
Tel: +44 (0)191 490 1547
Fax: +44 (0)191 477 5371
Email: northernsales@thorneandderrick.co.uk
Website: www.heattracing.co.uk
www.thorneanderrick.co.uk
3. Clamp-on with Micronics for
major installation savings, minimal
downtime and dry servicing.
The U3000 U1000 latest generation of clamp-on,
ultrasonic flow meters from Micronics are a viable
alternative to in-line meters for HVAC metering, in
both retrofit and new build applications, delivering
major installation savings, minimal downtime,
maximised availability and significant maintenance
benefits.
Liquid flow metering including LTHW, Chilled water
and DHWS plus flow measurement for Thermal
Energy measurement are all areas where clamp-
on meters offer a best value solution for Building
Services or Energy Management i.e. they will be
significantly cheaper to install than traditional in-line
meters and as they’re non-invasive they deliver
maximum availability through dry servicing and
minimal maintenance.
The larger the pipe size the greater the installed
saving will be but with the elimination of flanges and
by-pass valves significant savings are available for a
wide range of pipe sizes with major savings for larger
applications! The following is a comparison of new
build installation costs the comparable savings for
retrofit would be higher:
Pipe Size mm –
Steel Pipe
Total cost of
installing insertion
meters with
maintenance
bypass
Cost of installing
clamp on ultrasonic
meter, half hour
labour up to 50mm,
1 hour labour from
50mm
Additional cost of
insertion meter
installation i.e.
potential savings –
wiring assumed to
be equal:
25 £468 £6.20 £462
40 £601 £6.20 £595
50 £704 £6.20 £697
65 £1,681 £12.40 £1,669
80 £1,992 £12.40 £1,980
125 £3,873 £12.40 £3,860
150 £4,840 £12.40 £4,828
Insulation of clamp on and insertion meters assumed to be similar
Costs from Spons ME
It’s appreciated that competitive tendering would reduce these cost estimates.
MADE IN
BRITAIN
The above demonstrates the potential installation price savings from
using a clamp-on solution, which would deliver an installed clamp-on
meter price with savings ranging from significant to major from 50mm
upwards. And with the added benefits of being non-invasive, requiring
only dry servicing and maximising availability.
U3000/U1000
4. CLAMP-ON WITH MICRONICS FOR MAJOR
INSTALLATION SAVINGS, MINIMAL
DOWNTIME AND DRY SERVICING.
The U3000 U1000 latest generation of
clamp-on, ultrasonic flow meters from Micronics
are a viable alternative to in-line meters for HVAC
metering, in both retrofit and new build applications,
delivering major installation savings, minimal
downtime, maximised availability and significant
maintenance benefits.
Liquid flow metering including LTHW, Chilled water
and DHWS plus flow measurement for Thermal
Energy measurement are all areas where clamp-
on meters offer a best value solution for Building
Services or Energy Management i.e. they will be
significantly cheaper to install than traditional in-line
meters and as they’re non-invasive they deliver
maximum availability through dry servicing and
minimal maintenance.
The larger the pipe size the greater the installed
saving will be but with the elimination of flanges and
by-pass valves significant savings are available for a
wide range of pipe sizes with major savings for larger
applications! The following is a comparison of new
build installation costs the comparable savings for
retrofit would be higher:
Pipe Size
mm
Steel Pipe
Total cost of
installing insertion
meters with
maintenance
bypass
Cost of installing
clamp on ultrasonic
meter, half hour
labour up to 50mm,
1 hour labour from
50mm
Additional cost of
insertion meter
installation i.e.
potential savings –
wiring assumed to
be equal:
25 £468 £6.20 £462
40 £601 £6.20 £595
50 £704 £6.20 £697
65 £1,681 £12.40 £1,669
80 £1,992 £12.40 £1,980
125 £3,873 £12.40 £3,860
150 £4,840 £12.40 £4,828
Insulation of clamp on and insertion meters assumed to be similar
Costs from Spons ME
It’s appreciated that competitive tendering would reduce these cost estimates.
MADE IN
BRITAIN
The above demonstrates the potential installation price savings from
using a clamp-on solution, which would deliver an installed clamp-on
meter price with savings ranging from significant to major from 50mm
upwards. And with the added benefits of being non-invasive, requiring
only dry servicing and maximising availability.