Thermon TESH Heat Tracing Cable

TESH TM 
Series Constant Watt Heating Cable Product Specifications 
Application . . . 
Long Line Temperature Maintenance or Freeze Protec-tion 
TESH series resistance constant Watt heating cables 
are used where circuit lengths exceed the limitations of 
parallel resistance heating cables. TESH withstands the tem-perature 
exposures associated with steam purging. 
The series circuitry of TESH provides consistent Watt-per-metre 
power output along the entire length of the cable 
with no voltage drop. A glassceramic tape layer adds ad-ditional 
protection to the heating cable and a fluoropolymer 
overjacket provides chemical resistance while maintaining 
maximum flexibility. The construction of the cable meets the 
7 Joule impact test per EN50019. 
TESH cables are approved for use in ordinary (nonclassi-fied) 
areas and Catagories 2 and 3 ATEX classified areas. 
Ratings . . . 
Maximum Watt density..............................................25 W/m 
Maximum supply voltage............................................750 Vac 
Maximum continuous exposure temperature 
Power-off................................................................. 260°C 
Minimum installation temperature................................. -60°C 
Minimum bend radius.......................................5 x cable O.D. 
T-rating1 .................................................................... T2 to T6 
(using the principles of stabilized design or limiters)2 
Stabilised Design . . . 
The Watt density limitation for TESH cables is directly relat-ed 
to the desired maintain temperature. Thermon is able to 
ensure the T-rating based on a stabilised design that enables 
series constant Watt heating cables to operate in hazardous 
areas without limiting thermostats. TESH cable output and T-rating 
are dependent upon supply voltage, cable resistance, 
temperature conditions as well as additional variables. 
Contact Thermon for design assistance. 
Basic Accessories3 . . . 
Power Connection: TESH cables typically require nonheat-ing 
terminations at each end of the circuit before connect-ing 
to power. Contact Thermon for complete information. 
Notes . . . 
1. T-rating per internationally recognised testing agency guidelines. 
2. Thermon heating cables are approved for the listed T-ratings using the stabilised 
design method. This enables the cable to operate in hazardous areas without limit-ing 
thermostats. The T-rating may be determined using CompuTrace® Electric Heat 
Tracing Design Software or contact Thermon for design assistance. 
THERMON . . . The Heat Tracing Specialists® 
www.thermon.com 
1 
2 
Corporate Headquarters 
100 Thermon Dr. • PO Box 609 
San Marcos, TX 78667-0609 • U.S.A. 
Phone: +1 512-396-5801 • Facsimile: +1 512-396-3627 
European Headquarters 
Boezemweg 25 • 2641 KG Pijnacker 
PO Box 205 • 2640 AE Pijnacker • The Netherlands 
Phone: +31 (0) 15-36 15 370 • Facsimile: +31 (0) 15-36 15 379 
Construction . . . 
1 Heating Conductor 
2 Fluoropolymer Dielectric Insulation 
3 Glassceramic Tape 
4 Nickel-Plated Copper Braid (BN) 
5 Fluoropolymer Overjacket 
Certification/Approval . . . 
European Organisation for Electrotechnical 
Standardisation 
Hazardous (Classified) Locations 
3 
4 
5 
II 2 G EEx e IIC T2 to T6 LCIE 05 ATEX 6135 
TESH has additional hazardous area approvals 
including: 
• GGTN • Kazakhstan 
Product Features . . . 
• Withstands continuous flamibility testing 
according to IEC 60332-1: 1993 
• Allows cable to be installed at temperatures 
to -60°C 
Tel: +44 (0)191 490 1547 
Fax: +44 (0)191 477 5371 
Email: northernsales@thorneandderrick.co.uk 
Website: www.heattracing.co.uk 
www.thorneanderrick.co.uk
TESH TM 
Series Constant Watt Heating Cable 
Available Cables . . . 
Product Specifications 
Circuit Breaker Sizing and Type . . . 
Maximum circuit lengths for TESH heating cables will be a 
function of cable resistance, circuit length and operating 
voltage. Circuit length, breaker sizing and earth-fault protec-tion 
should be based on applicable local codes. 
Earth-fault protection of equipment should be provided for 
each branch circuit supplying electric heating equipment. 
Resistance 
Ohm/m 
at 20°C 
Note . . . 
1. Longer circuit lengths are possible based on earth-fault protection with higher earth-fault 
Form TEP0070U-1205 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change. 
ratings; contact Thermon. 
Conductor 
Size 
mm2 
Max. Cable Length1 
m (with 30 mA earth-fault 
protection) 
Cable 
Diameter 
mm 
TESH 2.9 0.0029 6.00 1435 7.0 
TESH 4.4 0.0044 4.00 1525 6.3 
TESH 7 0.0072 2.50 1855 5.5 
TESH 10 0.010 1.79 1775 5.1 
TESH 11.7 0.0117 1.50 2025 4.9 
TESH 15 0.015 1.20 2090 4.7 
TESH 17.8 0.0178 1.00 2275 4.6 
TESH 25 0.025 1.11 2525 4.6 
TESH 31.5 0.0315 1.60 2400 4.9 
TESH 50 0.050 1.02 2335 4.7 
TESH 65 0.065 0.75 1890 4.4 
TESH 80 0.080 1.21 2190 4.3 
TESH 100 0.100 1.50 2025 4.9 
TESH 150 0.150 1.02 2335 4.6 
TESH 200 0.200 0.75 2605 4.4 
TESH 320 0.320 0.92 2420 4.5 
TESH 380 0.380 0.79 2555 4.4 
TESH 480 0.480 0.64 2765 4.3 
TESH 600 0.600 0.49 3010 4.2 
TESH 700 0.700 0.43 3155 4.1 
TESH 810 0.810 0.62 2780 4.3 
TESH 1000 1.000 0.49 3010 4.2 
TESH 1440 1.440 0.34 3395 4.1 
TESH 1750 1.750 0.29 3615 4.1 
TESH 2000 2.000 0.55 2900 4.2 
TESH 3000 3.000 0.34 3395 4.1 
TESH 8000 8.000 0.14 4455 3.8

Más contenido relacionado

Similar a Thermon TESH Heat Tracing Cable - Spec Sheet(20)

Nelson Heat Tracing Cables - Product CatalogueNelson Heat Tracing Cables - Product Catalogue
Nelson Heat Tracing Cables - Product Catalogue
Thorne & Derrick UK2K vistas
Thermon KSX 5-2 Heat Tracing Cable - Spec SheetThermon KSX 5-2 Heat Tracing Cable - Spec Sheet
Thermon KSX 5-2 Heat Tracing Cable - Spec Sheet
Thorne & Derrick UK1.1K vistas
Thermon KSX 10-2 Heat Tracing Cable  - Spec SheetThermon KSX 10-2 Heat Tracing Cable  - Spec Sheet
Thermon KSX 10-2 Heat Tracing Cable - Spec Sheet
Thorne & Derrick UK506 vistas
Thermon KSX 15-2 Heat Tracing Cable - Spec SheetThermon KSX 15-2 Heat Tracing Cable - Spec Sheet
Thermon KSX 15-2 Heat Tracing Cable - Spec Sheet
Thorne & Derrick UK732 vistas
Thermon BSX Self-Regulating Heating CableThermon BSX Self-Regulating Heating Cable
Thermon BSX Self-Regulating Heating Cable
Thorne & Derrick International16.6K vistas
Eltherm ELKM-AG-L Heat Trace Cable - Spec SheetEltherm ELKM-AG-L Heat Trace Cable - Spec Sheet
Eltherm ELKM-AG-L Heat Trace Cable - Spec Sheet
Thorne & Derrick UK367 vistas
Thermon KSR-2 Heat Tracing Cable - Spec SheetThermon KSR-2 Heat Tracing Cable - Spec Sheet
Thermon KSR-2 Heat Tracing Cable - Spec Sheet
Thorne & Derrick UK2.2K vistas
Eltherm ELK-MI-INC Heat Trace Cable - Spec SheetEltherm ELK-MI-INC Heat Trace Cable - Spec Sheet
Eltherm ELK-MI-INC Heat Trace Cable - Spec Sheet
Thorne & Derrick UK164 vistas
Eltherm ELK-AG-N Heat Trace Cable - Spec SheetEltherm ELK-AG-N Heat Trace Cable - Spec Sheet
Eltherm ELK-AG-N Heat Trace Cable - Spec Sheet
Thorne & Derrick UK227 vistas
Thermon TEK Heat Tracing Cable - Spec SheetThermon TEK Heat Tracing Cable - Spec Sheet
Thermon TEK Heat Tracing Cable - Spec Sheet
Thorne & Derrick UK1.1K vistas
Eltherm ELK-MI_CN Heat Trace Cable - Spec SheetEltherm ELK-MI_CN Heat Trace Cable - Spec Sheet
Eltherm ELK-MI_CN Heat Trace Cable - Spec Sheet
Thorne & Derrick UK290 vistas
Thermon 3-FLX-2 Heat Tracing CableThermon 3-FLX-2 Heat Tracing Cable
Thermon 3-FLX-2 Heat Tracing Cable
Thorne & Derrick UK1.2K vistas
Thermon FLX Heat Tracing Cable - Spec SheetThermon FLX Heat Tracing Cable - Spec Sheet
Thermon FLX Heat Tracing Cable - Spec Sheet
Thorne & Derrick UK986 vistas
Thermon 5-FLX-2 Heat Tracing Cable - Spec SheetThermon 5-FLX-2 Heat Tracing Cable - Spec Sheet
Thermon 5-FLX-2 Heat Tracing Cable - Spec Sheet
Thorne & Derrick UK715 vistas
Thermon 8-FLX-2 Heat Tracing Cable - Spec SheetThermon 8-FLX-2 Heat Tracing Cable - Spec Sheet
Thermon 8-FLX-2 Heat Tracing Cable - Spec Sheet
Thorne & Derrick UK759 vistas
Thermon 10-FLX-2 Heat Tracing Cable - Spec SheetThermon 10-FLX-2 Heat Tracing Cable - Spec Sheet
Thermon 10-FLX-2 Heat Tracing Cable - Spec Sheet
Thorne & Derrick UK405 vistas
Thermon HSX 55-2 Heat Tracing Cable - Spec SheetThermon HSX 55-2 Heat Tracing Cable - Spec Sheet
Thermon HSX 55-2 Heat Tracing Cable - Spec Sheet
Thorne & Derrick UK295 vistas
Thermon HSX 50-2 Heat Tracing Cable - Spec SheetThermon HSX 50-2 Heat Tracing Cable - Spec Sheet
Thermon HSX 50-2 Heat Tracing Cable - Spec Sheet
Thorne & Derrick UK497 vistas

Más de Thorne & Derrick UK(20)

Dart Valley Systems CatalogueDart Valley Systems Catalogue
Dart Valley Systems Catalogue
Thorne & Derrick UK1.2K vistas
Sika Measuring Metering Calibration InstrumentsSika Measuring Metering Calibration Instruments
Sika Measuring Metering Calibration Instruments
Thorne & Derrick UK2.2K vistas
SICK - Sensors & Sensor Solutions - CatalogueSICK - Sensors & Sensor Solutions - Catalogue
SICK - Sensors & Sensor Solutions - Catalogue
Thorne & Derrick UK4.6K vistas
Patol Analogue Linear Heat Detection CablePatol Analogue Linear Heat Detection Cable
Patol Analogue Linear Heat Detection Cable
Thorne & Derrick UK1.9K vistas

Último(20)

Liqid: Composable CXL PreviewLiqid: Composable CXL Preview
Liqid: Composable CXL Preview
CXL Forum114 vistas
ChatGPT and AI for Web DevelopersChatGPT and AI for Web Developers
ChatGPT and AI for Web Developers
Maximiliano Firtman143 vistas
Architecting multi-cloud ready applicationsArchitecting multi-cloud ready applications
Architecting multi-cloud ready applications
Swaminathan Vetri43 vistas
ISWC2023-McGuinnessTWC16x9FinalShort.pdfISWC2023-McGuinnessTWC16x9FinalShort.pdf
ISWC2023-McGuinnessTWC16x9FinalShort.pdf
Deborah McGuinness80 vistas
AMD: 4th Generation EPYC CXL DemoAMD: 4th Generation EPYC CXL Demo
AMD: 4th Generation EPYC CXL Demo
CXL Forum113 vistas

Thermon TESH Heat Tracing Cable - Spec Sheet

  • 1. TESH TM Series Constant Watt Heating Cable Product Specifications Application . . . Long Line Temperature Maintenance or Freeze Protec-tion TESH series resistance constant Watt heating cables are used where circuit lengths exceed the limitations of parallel resistance heating cables. TESH withstands the tem-perature exposures associated with steam purging. The series circuitry of TESH provides consistent Watt-per-metre power output along the entire length of the cable with no voltage drop. A glassceramic tape layer adds ad-ditional protection to the heating cable and a fluoropolymer overjacket provides chemical resistance while maintaining maximum flexibility. The construction of the cable meets the 7 Joule impact test per EN50019. TESH cables are approved for use in ordinary (nonclassi-fied) areas and Catagories 2 and 3 ATEX classified areas. Ratings . . . Maximum Watt density..............................................25 W/m Maximum supply voltage............................................750 Vac Maximum continuous exposure temperature Power-off................................................................. 260°C Minimum installation temperature................................. -60°C Minimum bend radius.......................................5 x cable O.D. T-rating1 .................................................................... T2 to T6 (using the principles of stabilized design or limiters)2 Stabilised Design . . . The Watt density limitation for TESH cables is directly relat-ed to the desired maintain temperature. Thermon is able to ensure the T-rating based on a stabilised design that enables series constant Watt heating cables to operate in hazardous areas without limiting thermostats. TESH cable output and T-rating are dependent upon supply voltage, cable resistance, temperature conditions as well as additional variables. Contact Thermon for design assistance. Basic Accessories3 . . . Power Connection: TESH cables typically require nonheat-ing terminations at each end of the circuit before connect-ing to power. Contact Thermon for complete information. Notes . . . 1. T-rating per internationally recognised testing agency guidelines. 2. Thermon heating cables are approved for the listed T-ratings using the stabilised design method. This enables the cable to operate in hazardous areas without limit-ing thermostats. The T-rating may be determined using CompuTrace® Electric Heat Tracing Design Software or contact Thermon for design assistance. THERMON . . . The Heat Tracing Specialists® www.thermon.com 1 2 Corporate Headquarters 100 Thermon Dr. • PO Box 609 San Marcos, TX 78667-0609 • U.S.A. Phone: +1 512-396-5801 • Facsimile: +1 512-396-3627 European Headquarters Boezemweg 25 • 2641 KG Pijnacker PO Box 205 • 2640 AE Pijnacker • The Netherlands Phone: +31 (0) 15-36 15 370 • Facsimile: +31 (0) 15-36 15 379 Construction . . . 1 Heating Conductor 2 Fluoropolymer Dielectric Insulation 3 Glassceramic Tape 4 Nickel-Plated Copper Braid (BN) 5 Fluoropolymer Overjacket Certification/Approval . . . European Organisation for Electrotechnical Standardisation Hazardous (Classified) Locations 3 4 5 II 2 G EEx e IIC T2 to T6 LCIE 05 ATEX 6135 TESH has additional hazardous area approvals including: • GGTN • Kazakhstan Product Features . . . • Withstands continuous flamibility testing according to IEC 60332-1: 1993 • Allows cable to be installed at temperatures to -60°C Tel: +44 (0)191 490 1547 Fax: +44 (0)191 477 5371 Email: northernsales@thorneandderrick.co.uk Website: www.heattracing.co.uk www.thorneanderrick.co.uk
  • 2. TESH TM Series Constant Watt Heating Cable Available Cables . . . Product Specifications Circuit Breaker Sizing and Type . . . Maximum circuit lengths for TESH heating cables will be a function of cable resistance, circuit length and operating voltage. Circuit length, breaker sizing and earth-fault protec-tion should be based on applicable local codes. Earth-fault protection of equipment should be provided for each branch circuit supplying electric heating equipment. Resistance Ohm/m at 20°C Note . . . 1. Longer circuit lengths are possible based on earth-fault protection with higher earth-fault Form TEP0070U-1205 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change. ratings; contact Thermon. Conductor Size mm2 Max. Cable Length1 m (with 30 mA earth-fault protection) Cable Diameter mm TESH 2.9 0.0029 6.00 1435 7.0 TESH 4.4 0.0044 4.00 1525 6.3 TESH 7 0.0072 2.50 1855 5.5 TESH 10 0.010 1.79 1775 5.1 TESH 11.7 0.0117 1.50 2025 4.9 TESH 15 0.015 1.20 2090 4.7 TESH 17.8 0.0178 1.00 2275 4.6 TESH 25 0.025 1.11 2525 4.6 TESH 31.5 0.0315 1.60 2400 4.9 TESH 50 0.050 1.02 2335 4.7 TESH 65 0.065 0.75 1890 4.4 TESH 80 0.080 1.21 2190 4.3 TESH 100 0.100 1.50 2025 4.9 TESH 150 0.150 1.02 2335 4.6 TESH 200 0.200 0.75 2605 4.4 TESH 320 0.320 0.92 2420 4.5 TESH 380 0.380 0.79 2555 4.4 TESH 480 0.480 0.64 2765 4.3 TESH 600 0.600 0.49 3010 4.2 TESH 700 0.700 0.43 3155 4.1 TESH 810 0.810 0.62 2780 4.3 TESH 1000 1.000 0.49 3010 4.2 TESH 1440 1.440 0.34 3395 4.1 TESH 1750 1.750 0.29 3615 4.1 TESH 2000 2.000 0.55 2900 4.2 TESH 3000 3.000 0.34 3395 4.1 TESH 8000 8.000 0.14 4455 3.8