Electrical Saftey.pptx

A
Electrical Safety
 Rules to provided substation safety
Rule-1-Clearance
 Enough clearance from energized parts should be provided to avoid
accidental contact with them. If that can’t be met, live parts should
be guarded or enclosed.
Rule-2- Minimum height
 A minimum height from the ground to any ungrounded part of an
electrical installation should be 8’-6”, so a person staying on the
ground can’t touch a substation element or its part which may
become energized accidentally. For example, the bottom of a post
insulator supporting an energized bus does not normally have any
potential.
Rule-3- illumination
 There should be sufficient illumination for personnel to clearly see
their surroundings and perform any work safely. Required
illumination levels are specified in NESC® [1].
Con…
Rule-4- Passageways
 All passageways and stairs should be wide enough for
personnel to navigate them safely, adequate railing should be
provided, and floor openings should have guard rails.
Rule-5-Evacuation routs
 Exits should be clearly marked and evacuation routes should
be free from obstructions. Depending on the function of the
building (for example, control house), it may require several exits
to avoid personnel being trapped during equipment fault, fire,
etc.
Rule-6-Grounding
 All substation metallic structures, fences, and equipment tanks
should be connected to a station ground grid which should be
designed to ensure that step and touch potential values are lower
than the ones stipulated in the applicable standards.
In addition to the above the following points are also important
for safe work environment:
 Make sure that people who are working with electricity are
competent to do the job. Even simple tasks such as wiring a plug
can lead to danger - ensure that people know what they are doing
before they start.
 Check that:
 suspect or faulty equipment is taken out of use, labeled ‘DO
NOT USE’ and kept secure until examined by a competent
person;
 where possible, tools and power socket-outlets are switched off
before plugging in or unplugging;
 equipment is switched off and/or unplugged before cleaning or
making adjustments.
 More complicated tasks, such as equipment repairs or alterations
to an electrical installation, should only be tackled by people
with a knowledge of the risks and the precautions needed.
 You must not allow work on or near exposed live parts of
equipment unless it is absolutely unavoidable and suitable
precautions have been taken to prevent injury, both to the
workers and to anyone else who may be in the area.
 All electric supply lines and apparatus shall be of sufficient
ratings for power, insulation and estimated fault current and of
sufficient mechanical strength, for the duty which they may be
required to perform under the environmental conditions of
installation, and shall be constructed, installed, protected, worked
and maintained in such a manner as to ensure safety of human
beings, animals and property.
 Every electric supply line other than the earth or earthed neutral
conductor of any system or the earthed external conductor of a
concentric cable shall be protected by a suitable cut-out by its
owner.
 Understandings the use of safety equipment required for an
electrician working on or near a low voltage installations eg.
Rubber insulating gloves, Hard hat/Helmet, Face shields, Safety
glasses and goggles, Rubber insulating blankets, Hot sticks,
Rubber mat etc
 Completed wiring must be free from short circuits and
grounds (other than those required in the Standard).
 Grounding is the method used to connect an electrical
system to the earth with a wire. Grounding adds critical
protection against electric shock and electrocution by using
a grounding rod to provide a third path for conducting
electricity in the event of a short circuit or an overload.
Grounding will help protect the person working on the
system, the system itself, and any appliances and equipment
that are connected to the system.
 electrical safety equipment products including arc flash
protective clothing, insulating gloves & sleeves, insulating
blankets, switchboard matting, insulated tools, grounding
equipment, hot sticks, lockout/tag out, ground fault circuit
interrupters (GFCI's) and much more.
Lightening Arrester
Lightning arresters are designed to limit the line-to-ground voltage in the event
of lightning or other excessive transient voltage conditions.
Working principle : is, once the voltage surge travel throughout the
conductor then it reaches the location of the arrester where it is installed. So it
will break down the insulation of the lighting arrestor for a moment, so voltage
surge can be discharged toward the ground . Once the voltage of the system falls
under the fixed value, then the insulation will be restored among the ground and
conductor. Further, the current flow toward the ground will be stopped.
Type of arrester
A. surge arrester
B. rod gap lighting arrester
C. Sphere gap lighting arrester
D. horn gap lighting arrester
E. multi gap lighting arrester
F. electrolyte type lighting arrester
H. metal-oxide lighting arrester
Instrument Transformer
The term instrument transformer refers to current and
voltage transformers that are used to scale down actual
power system quantities for metering, protective
relaying, and/or system monitoring equipment.
I. Current Transformers
Current transformers or CTs are used to scale down the
high magnitude of current flowing in high-voltage
conductors to a level much easier to work with safely
type of current transformer
Wound current transformer
Toroidal current transformer
Bar type current transformer
Instrument Transformer…
II. Potential Transformer
Similarly, potential transformers (PTs) are used to scale down
very high voltages to levels that are safer to work with.
Type of voltage transformer
Single and three phase voltage transformer
Single and double pole three phase voltage transformer
Single phase earthed type voltage transformer
The Voltage transformer maybe:
Electromagnetic type of transformer or
Capacitive voltage transformer -100kv above
Con…
Accuracy Class and Burden
CT accuracy class is the class assigned to the ct with
the specified limits of ratio error and phase angle error
Example 5P20
loads/impedances connected to CT secondary is called
CT burden
Power Transformer
 Transformers are essential components in electric power systems. They come
in all shapes and sizes. Power transformers are used to convert high voltage
power to low-voltage power and vice versa. Power can flow in both
directions: from the high-voltage side to the low-voltage side or from the low-
voltage side to the high-voltage side. Generation plants use large step up
transformers to raise the voltage of the generated power for efficient transport
of power over long distances. Then step-down transformers convert the power
to sub transmission.
Power transformer
 Power transformers consist of two or more windings for each phase and these
windings are usually wound around an iron core. The iron core improves the
efficiency of the transformer by concentrating the magnetic field and reduces
transformer losses. The high-voltage and low-voltage windings have a unique
number of coil turns. The turns ratio between the coils dictates the voltage and
current relationships between the high- and low-voltage sides
Autotransformers
 Autotransformers are a specially constructed variations of regular two winding
transformers. Autotransformers share a winding. Single-phase, two-winding
autotransformers contain a primary winding and a secondary winding on a
common core. However, part of the high-voltage winding is shared with the
low-voltage winding on an autotransformer.
Transformer
Transformer
Non-electrical
Main tank & OLTC
WINDING AND OIL TEMPARTURE INDICATOR
Disconnector
 A disconnector is a no-load switch (not designed to break load
current or fault current) used primarily in substations and
occasionally in distribution.
 Disconnector provides permanent opening of a circuit after the
tripping of a circuit breaker under fault condition. Further it provides
visual confirmation of a circuit condition (open or close) assuring
safety to substation service personnel. They also enable
sectionalizing lines during maintenance / fault isolation.
Electrical Saftey.pptx
Circuit Breaker
Circuit breaker : a switch that automatically stop the flow of electricity to a place or
device if the current becomes too strong or another dangerous problem occurs
Operating principle-a circuit breaker essentially consists of fixed and moving
contact , make or break a circuit either manually or by remote control under
normal conditions
Types of circuit breaker
A. Oil type
In such circuit breakers, some insulating oil is used as an arc quenching medium
Advantages. The advantages of oil as an arc quenching medium are :
(i) It absorbs the arc energy to decompose the oil into gases which have excellent
cooling properties
(ii) It acts as an insulator and permits smaller clearance between live conductors and
earthed components.
(iii) The surrounding oil presents cooling surface in close proximity to the arc.
Disadvantages. The disadvantages of oil as an arc quenching medium are :
(i) It is inflammable and there is a risk of a fire.
(ii) It may form an explosive mixture with air
(iii) The arcing products (e.g., carbon) remain in the oil and its quality deteriorates
with successive operations. This necessitates periodic checking and replacement
of oil.
B. FS6-sulphur hexafluoride
In such circuit breakers, sulphur hexafluoride (SF6) gas is used as the
arc quenching medium
Advantages. Due to the superior arc quenching properties of SF6 gas,
the SF6 circuit breakers have many advantages over oil or air circuit
breakers. Some of them are
(i) Due to the superior arc quenching property of SF6, such circuit
breakers have very short arcing time.
(ii) Since the dielectric strength of SF6 gas is 2 to 3 times that of air,
such breakers can interrupt much larger currents.
(iii) The SF6 circuit breaker gives noiseless operation due to its closed
gas circuit and no exhaust to atmosphere unlike the air blast circuit
breaker.
(iv) The closed gas enclosure keeps the interior dry so that there is no
moisture problem.
(v) There is no risk of fire in such breakers because SF6 gas is non-
inflammable.
(vi) There are no carbon deposits so that tracking and insulation problems
are eliminated.
(vii) The SF6 breakers have low maintenance cost, light foundation
requirements and minimum auxiliary equipment.
(viii) Since SF6 breakers are totally enclosed and sealed from
atmosphere, they are particularly suitable where explosion hazard
exists e.g., coal mines.
Disadvantages
(i) SF6 breakers are costly due to the high cost of SF6.
(ii) (ii) Since SF6 gas has to be reconditioned after every operation of the
breaker, additional equipment is required for this purpose
C. Vacuum type
 In such breakers, vacuum is used as the arc quenching medium.
Vacuum circuit breakers have the following advantages
(i) They are compact, reliable and have longer life.
(ii) There are no fire hazards.
(iii) There is no generation of gas during and after operation.
(iv) They can interrupt any fault current. The outstanding feature
of a VCB is that it can break any heavy fault current perfectly
just before the contacts reach the definite open position.
(v) They require little maintenance and are quiet in operation.
(vi) They can successfully withstand lightning surges.
(vii) They have low arc energy.
(viii) They have low inertia and hence require smaller power for
control mechanism.
 Battery Bank- To maintain the D.C. supply continuity
during A.C. supply failure for keeping equipment in
operation for normal & abnormal conditions
 Capacitor Bank- To Improve the power factor of the
system & provide compensation to reactive power absorbed
by inductive loads, reduce the over loading of the cables,
transmission lines & transformers for the same load to be
handled
 Earthing Switch- To discharge the voltage on dead lines to
earth
 Bus Section- For connecting Incoming / Outgoing Circuits
Parallel operation of Transformers
 Parallel operation is the connection of two or more
power sources of the same size and output volt- age to
obtain a higher output cur- rent. Conditions for parallel
operations are- Convenient & Mandatory.
 The convenients are:
 same voltage ratio and turns ratio
 same percentage impedance
 same kva rating and
 same position of tap changer.
 The mandatory conditions are :
 same phase angle shift
 same polarity
 same phase sequence and
 same frequency.
Operation sequence
 The operating sequence during opening and closing of a
circuit is given as follow:
During Opening – First open circuit breaker, open isolator,
and then close earthing switch is provided.
During Closing – First open earthing switch, close isolator,
and then close the circuit breaker.
Relay
A device that detects the fault and initiates the operation of
the Circuit breaker to isolate the defective element from the
rest of the system.
The relays detect the abnormal conditions in the electrical
circuits by constantly measuring the electrical quantities
which are different under normal and faulty conditions.
Selectivity- Ability to select the faulty part and isolate that
part without disturbing the rest of the system.
Speed - Ability to disconnect the faulty part at the earliest
possible time
Senstivity- Ability of the relay to operate with low value of
actuating quantity.
Reliablity- Ability of the system to operate under pre-
determined conditions
thank you!
1 de 26

Más contenido relacionado

Similar a Electrical Saftey.pptx

Electrical Installation.pptxElectrical Installation.pptx
Electrical Installation.pptxbharath364108
244 vistas57 diapositivas
Anurag Attri.pptxAnurag Attri.pptx
Anurag Attri.pptxAsif682330
5 vistas24 diapositivas

Similar a Electrical Saftey.pptx(20)

132 KV Substation Gajraula.pptx132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx
Asif68233025 vistas
Electrical Installation.pptxElectrical Installation.pptx
Electrical Installation.pptx
bharath364108244 vistas
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptx
Satish Pydimarla6 vistas
Anurag Attri.pptxAnurag Attri.pptx
Anurag Attri.pptx
Asif6823305 vistas
Switchgear and protection lecture 1Switchgear and protection lecture 1
Switchgear and protection lecture 1
anuphowlader14K vistas
Study tour to optclStudy tour to optcl
Study tour to optcl
SoumyaRanjanDas13334 vistas
Sub station training pptSub station training ppt
Sub station training ppt
sitesh950742.9K vistas
Lightning protection.pptLightning protection.ppt
Lightning protection.ppt
YashVarshney349 vistas
Summer Training presentation on 132/33 KV sub-station Minto park, AllahabadSummer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Sudhir Cement Industries Pvt. Ltd. Meerut25.3K vistas
EE6702 Protection and SwitchgearEE6702 Protection and Switchgear
EE6702 Protection and Switchgear
rmkceteee375 vistas
Ashwani kumarAshwani kumar
Ashwani kumar
Ashwani Kumar1.8K vistas
Basic electrical comp upload1Basic electrical comp upload1
Basic electrical comp upload1
Ganesh Kumar4K vistas
Circuit breakerCircuit breaker
Circuit breaker
dipak doud125 vistas
REPORT ON 33/11KV SUBSTATION REPORT ON 33/11KV SUBSTATION
REPORT ON 33/11KV SUBSTATION
Ravi Phadtare24.6K vistas

Último(20)

Sanitary Landfill- SWM.pptxSanitary Landfill- SWM.pptx
Sanitary Landfill- SWM.pptx
Vinod Nejkar5 vistas
SICTECH CORPORATE PRESENTATIONSICTECH CORPORATE PRESENTATION
SICTECH CORPORATE PRESENTATION
SiCtechInduction15 vistas
SWM L1-L14_drhasan (Part 1).pdfSWM L1-L14_drhasan (Part 1).pdf
SWM L1-L14_drhasan (Part 1).pdf
MahmudHasan74787038 vistas
performance uploading.pptxperformance uploading.pptx
performance uploading.pptx
SanthiS107 vistas
Wire RopeWire Rope
Wire Rope
Iwiss Tools Co.,Ltd8 vistas
Dynamics of Hard-Magnetic Soft MaterialsDynamics of Hard-Magnetic Soft Materials
Dynamics of Hard-Magnetic Soft Materials
Shivendra Nandan11 vistas
Codes and Conventions.pptxCodes and Conventions.pptx
Codes and Conventions.pptx
IsabellaGraceAnkers5 vistas
What is Unit TestingWhat is Unit Testing
What is Unit Testing
Sadaaki Emura17 vistas
Pointers.pptxPointers.pptx
Pointers.pptx
Ananthi Palanisamy58 vistas
Electrical CrimpingElectrical Crimping
Electrical Crimping
Iwiss Tools Co.,Ltd18 vistas
What is Whirling Hygrometer.pdfWhat is Whirling Hygrometer.pdf
What is Whirling Hygrometer.pdf
IIT KHARAGPUR 10 vistas
Activated sludge process .pdfActivated sludge process .pdf
Activated sludge process .pdf
8832RafiyaAltaf6 vistas
FLOW IN PIPES NOTES.pdfFLOW IN PIPES NOTES.pdf
FLOW IN PIPES NOTES.pdf
Dearest Arhelo82 vistas

Electrical Saftey.pptx

  • 1. Electrical Safety  Rules to provided substation safety Rule-1-Clearance  Enough clearance from energized parts should be provided to avoid accidental contact with them. If that can’t be met, live parts should be guarded or enclosed. Rule-2- Minimum height  A minimum height from the ground to any ungrounded part of an electrical installation should be 8’-6”, so a person staying on the ground can’t touch a substation element or its part which may become energized accidentally. For example, the bottom of a post insulator supporting an energized bus does not normally have any potential. Rule-3- illumination  There should be sufficient illumination for personnel to clearly see their surroundings and perform any work safely. Required illumination levels are specified in NESC® [1].
  • 2. Con… Rule-4- Passageways  All passageways and stairs should be wide enough for personnel to navigate them safely, adequate railing should be provided, and floor openings should have guard rails. Rule-5-Evacuation routs  Exits should be clearly marked and evacuation routes should be free from obstructions. Depending on the function of the building (for example, control house), it may require several exits to avoid personnel being trapped during equipment fault, fire, etc. Rule-6-Grounding  All substation metallic structures, fences, and equipment tanks should be connected to a station ground grid which should be designed to ensure that step and touch potential values are lower than the ones stipulated in the applicable standards.
  • 3. In addition to the above the following points are also important for safe work environment:  Make sure that people who are working with electricity are competent to do the job. Even simple tasks such as wiring a plug can lead to danger - ensure that people know what they are doing before they start.  Check that:  suspect or faulty equipment is taken out of use, labeled ‘DO NOT USE’ and kept secure until examined by a competent person;  where possible, tools and power socket-outlets are switched off before plugging in or unplugging;  equipment is switched off and/or unplugged before cleaning or making adjustments.  More complicated tasks, such as equipment repairs or alterations to an electrical installation, should only be tackled by people with a knowledge of the risks and the precautions needed.
  • 4.  You must not allow work on or near exposed live parts of equipment unless it is absolutely unavoidable and suitable precautions have been taken to prevent injury, both to the workers and to anyone else who may be in the area.  All electric supply lines and apparatus shall be of sufficient ratings for power, insulation and estimated fault current and of sufficient mechanical strength, for the duty which they may be required to perform under the environmental conditions of installation, and shall be constructed, installed, protected, worked and maintained in such a manner as to ensure safety of human beings, animals and property.  Every electric supply line other than the earth or earthed neutral conductor of any system or the earthed external conductor of a concentric cable shall be protected by a suitable cut-out by its owner.  Understandings the use of safety equipment required for an electrician working on or near a low voltage installations eg. Rubber insulating gloves, Hard hat/Helmet, Face shields, Safety glasses and goggles, Rubber insulating blankets, Hot sticks, Rubber mat etc
  • 5.  Completed wiring must be free from short circuits and grounds (other than those required in the Standard).  Grounding is the method used to connect an electrical system to the earth with a wire. Grounding adds critical protection against electric shock and electrocution by using a grounding rod to provide a third path for conducting electricity in the event of a short circuit or an overload. Grounding will help protect the person working on the system, the system itself, and any appliances and equipment that are connected to the system.  electrical safety equipment products including arc flash protective clothing, insulating gloves & sleeves, insulating blankets, switchboard matting, insulated tools, grounding equipment, hot sticks, lockout/tag out, ground fault circuit interrupters (GFCI's) and much more.
  • 6. Lightening Arrester Lightning arresters are designed to limit the line-to-ground voltage in the event of lightning or other excessive transient voltage conditions. Working principle : is, once the voltage surge travel throughout the conductor then it reaches the location of the arrester where it is installed. So it will break down the insulation of the lighting arrestor for a moment, so voltage surge can be discharged toward the ground . Once the voltage of the system falls under the fixed value, then the insulation will be restored among the ground and conductor. Further, the current flow toward the ground will be stopped. Type of arrester A. surge arrester B. rod gap lighting arrester C. Sphere gap lighting arrester D. horn gap lighting arrester E. multi gap lighting arrester F. electrolyte type lighting arrester H. metal-oxide lighting arrester
  • 7. Instrument Transformer The term instrument transformer refers to current and voltage transformers that are used to scale down actual power system quantities for metering, protective relaying, and/or system monitoring equipment. I. Current Transformers Current transformers or CTs are used to scale down the high magnitude of current flowing in high-voltage conductors to a level much easier to work with safely type of current transformer Wound current transformer Toroidal current transformer Bar type current transformer
  • 8. Instrument Transformer… II. Potential Transformer Similarly, potential transformers (PTs) are used to scale down very high voltages to levels that are safer to work with. Type of voltage transformer Single and three phase voltage transformer Single and double pole three phase voltage transformer Single phase earthed type voltage transformer The Voltage transformer maybe: Electromagnetic type of transformer or Capacitive voltage transformer -100kv above
  • 9. Con… Accuracy Class and Burden CT accuracy class is the class assigned to the ct with the specified limits of ratio error and phase angle error Example 5P20 loads/impedances connected to CT secondary is called CT burden
  • 10. Power Transformer  Transformers are essential components in electric power systems. They come in all shapes and sizes. Power transformers are used to convert high voltage power to low-voltage power and vice versa. Power can flow in both directions: from the high-voltage side to the low-voltage side or from the low- voltage side to the high-voltage side. Generation plants use large step up transformers to raise the voltage of the generated power for efficient transport of power over long distances. Then step-down transformers convert the power to sub transmission. Power transformer  Power transformers consist of two or more windings for each phase and these windings are usually wound around an iron core. The iron core improves the efficiency of the transformer by concentrating the magnetic field and reduces transformer losses. The high-voltage and low-voltage windings have a unique number of coil turns. The turns ratio between the coils dictates the voltage and current relationships between the high- and low-voltage sides Autotransformers  Autotransformers are a specially constructed variations of regular two winding transformers. Autotransformers share a winding. Single-phase, two-winding autotransformers contain a primary winding and a secondary winding on a common core. However, part of the high-voltage winding is shared with the low-voltage winding on an autotransformer.
  • 14. Main tank & OLTC
  • 15. WINDING AND OIL TEMPARTURE INDICATOR
  • 16. Disconnector  A disconnector is a no-load switch (not designed to break load current or fault current) used primarily in substations and occasionally in distribution.  Disconnector provides permanent opening of a circuit after the tripping of a circuit breaker under fault condition. Further it provides visual confirmation of a circuit condition (open or close) assuring safety to substation service personnel. They also enable sectionalizing lines during maintenance / fault isolation.
  • 18. Circuit Breaker Circuit breaker : a switch that automatically stop the flow of electricity to a place or device if the current becomes too strong or another dangerous problem occurs Operating principle-a circuit breaker essentially consists of fixed and moving contact , make or break a circuit either manually or by remote control under normal conditions Types of circuit breaker A. Oil type In such circuit breakers, some insulating oil is used as an arc quenching medium Advantages. The advantages of oil as an arc quenching medium are : (i) It absorbs the arc energy to decompose the oil into gases which have excellent cooling properties (ii) It acts as an insulator and permits smaller clearance between live conductors and earthed components. (iii) The surrounding oil presents cooling surface in close proximity to the arc. Disadvantages. The disadvantages of oil as an arc quenching medium are : (i) It is inflammable and there is a risk of a fire. (ii) It may form an explosive mixture with air (iii) The arcing products (e.g., carbon) remain in the oil and its quality deteriorates with successive operations. This necessitates periodic checking and replacement of oil.
  • 19. B. FS6-sulphur hexafluoride In such circuit breakers, sulphur hexafluoride (SF6) gas is used as the arc quenching medium Advantages. Due to the superior arc quenching properties of SF6 gas, the SF6 circuit breakers have many advantages over oil or air circuit breakers. Some of them are (i) Due to the superior arc quenching property of SF6, such circuit breakers have very short arcing time. (ii) Since the dielectric strength of SF6 gas is 2 to 3 times that of air, such breakers can interrupt much larger currents. (iii) The SF6 circuit breaker gives noiseless operation due to its closed gas circuit and no exhaust to atmosphere unlike the air blast circuit breaker. (iv) The closed gas enclosure keeps the interior dry so that there is no moisture problem. (v) There is no risk of fire in such breakers because SF6 gas is non- inflammable.
  • 20. (vi) There are no carbon deposits so that tracking and insulation problems are eliminated. (vii) The SF6 breakers have low maintenance cost, light foundation requirements and minimum auxiliary equipment. (viii) Since SF6 breakers are totally enclosed and sealed from atmosphere, they are particularly suitable where explosion hazard exists e.g., coal mines. Disadvantages (i) SF6 breakers are costly due to the high cost of SF6. (ii) (ii) Since SF6 gas has to be reconditioned after every operation of the breaker, additional equipment is required for this purpose
  • 21. C. Vacuum type  In such breakers, vacuum is used as the arc quenching medium. Vacuum circuit breakers have the following advantages (i) They are compact, reliable and have longer life. (ii) There are no fire hazards. (iii) There is no generation of gas during and after operation. (iv) They can interrupt any fault current. The outstanding feature of a VCB is that it can break any heavy fault current perfectly just before the contacts reach the definite open position. (v) They require little maintenance and are quiet in operation. (vi) They can successfully withstand lightning surges. (vii) They have low arc energy. (viii) They have low inertia and hence require smaller power for control mechanism.
  • 22.  Battery Bank- To maintain the D.C. supply continuity during A.C. supply failure for keeping equipment in operation for normal & abnormal conditions  Capacitor Bank- To Improve the power factor of the system & provide compensation to reactive power absorbed by inductive loads, reduce the over loading of the cables, transmission lines & transformers for the same load to be handled  Earthing Switch- To discharge the voltage on dead lines to earth  Bus Section- For connecting Incoming / Outgoing Circuits
  • 23. Parallel operation of Transformers  Parallel operation is the connection of two or more power sources of the same size and output volt- age to obtain a higher output cur- rent. Conditions for parallel operations are- Convenient & Mandatory.  The convenients are:  same voltage ratio and turns ratio  same percentage impedance  same kva rating and  same position of tap changer.  The mandatory conditions are :  same phase angle shift  same polarity  same phase sequence and  same frequency.
  • 24. Operation sequence  The operating sequence during opening and closing of a circuit is given as follow: During Opening – First open circuit breaker, open isolator, and then close earthing switch is provided. During Closing – First open earthing switch, close isolator, and then close the circuit breaker.
  • 25. Relay A device that detects the fault and initiates the operation of the Circuit breaker to isolate the defective element from the rest of the system. The relays detect the abnormal conditions in the electrical circuits by constantly measuring the electrical quantities which are different under normal and faulty conditions. Selectivity- Ability to select the faulty part and isolate that part without disturbing the rest of the system. Speed - Ability to disconnect the faulty part at the earliest possible time Senstivity- Ability of the relay to operate with low value of actuating quantity. Reliablity- Ability of the system to operate under pre- determined conditions