    Chief Inspection Services
    Professional Building Consultants Since 2002
         FL Certified General Contractor #CGC058361 FL Certified Building Inspector #BN 5316
               FL Certified Home Inspector #725 Registered Professional Inspector # 0437
 
 


    HOME INSPECTION REPORT
     THIS INSPECTION MEETS OR EXCEEDS THE CURRENT FABI “STANDARDS OF PRACTICE”
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                        1567 Yourstreet, Hometown, FL 12345
                        This report is prepared exclusively for:
                               Mr. & Mrs. Homebuyer
 
 




 
 
                                       FL State Certified
                                      Home Inspector #725
 
 
 
 
 
 
    P.O. Box 700937    St. Cloud, FL 34770-0937        Ph. 407-383-7241      Fax 407-891-7410
                        Chief Inspection Services
                            Certified Inspection Report
 
 
 
 
    Client Name:        Mr. & Mrs. Homebuyer
    Property Address:   1567 Yourstret
    City, State:        Hometown, FL 32725
 
    Date and Time of Inspection: October 10, 2011 @ 11:00am
 
    Weather Conditions: Cloudy
 
    Temperature: 84     Humidity: 48%
 


               HOME INSPECTION REPORT TABLE OF CONTENTS


           CLIENT INFO & REPORT INDEX                     Page 1
           INSPECTION AUTHORIZATION                       Page 2 - 3
           EXTERIOR                                       Page 4
           ROOF                                           Page 5
           ATTIC                                          Page 6
           WINDOWS / DOORS                                Page 7
           KITCHEN / APPLIANCES                           Page 8
           PLUMBING                                       Page 9
           HEATING / AIR CONDITIONING                     Page 10
           ELECTRICAL                                     Page 11
           POOL / SCREEN ENCLOSURE                        Page 12
           HOME INSPECTION SUMMARY PAGE                   Page 13




                                                                       1
Chief Inspection Services
                                       Certified Inspection Report



             Home Inspection Authorization Form
This home inspection is performed in accordance with the Standards of Practice of Florida Association of
Building Inspectors and is an examination of the mechanical and physical components of real property
identified on page 1 of the report as they exist at the time of the inspection through visual means and
operation of normal user controls. The home inspector does not necessarily possess licenses authorizing
the rendering of detailed opinions regarding all of the systems, structures, and components of a building.
Chief Inspection Services. may have an affiliation with third-party service providers (“TPSP”) in order to
offer value-added services to its Clients. By signing this agreement you authorize our third party service
providers to call you at the numbers you have provided to discuss special service offers.

What We Do:
  1. We perform a visual inspection in a good and workmanlike manner.
  2. We tell you whether each item we inspect is performing the function for which it was intended or is
      in need of immediate repair.
  3. We will explain any deficiencies that are present on the items we inspect.
  4. The report will meet the current Standards of Practice of the Florida Association of Building
      Inspectors. A copy of the current Standards of Practice and Code of Ethics can be viewed at
      WWW.FABI.org .

What the Client Must Do:
1. Client must notify us in writing of any complaints regarding our inspection within seven (7) days after
receipt of our report.
2. If we report that an item is in need of immediate repair or is not performing its intended function and
Client intends to purchase the property anyway, we recommend that Client have that item, as well as the
entire system, examined by a licensed professional or a specialist.
3. It is agreed by all parties that, to the extent allowed by law, any damages for breach of this contract are
limited to the amount of the inspection fee.
4. If Client sues on this contract but does not prevail, Client agrees to pay our reasonable attorney fees.
5. Client acknowledges that the inspector has not made any oral representations that differ from or modify
what is written in this report.
6. Client must not allow anyone else to use or rely on this report. A copy of this report and/or summary
page may be provided to their realtor upon request of the client.

Client agrees that:
“Any dispute, controversy, interpretation or claim including claims for, but not limited to, breach of contract,
any form of negligence, fraud or misrepresentation arising out of, from, or related to this contract or arising
out of, from or related to the inspection or inspection report shall be submitted to final and binding
arbitration under the Rules and Procedures of the Expedited Arbitration of Home Inspection Dispute of
Construction Arbitration Services, Inc. The decision of the arbitrator appointed thereunder shall be final
and binding judgement on the Award and may be entered into any Court of competent jurisdiction.”




                                                                                                              2
                                   Chief Inspection Services
                                          Certified Inspection Report
 
 
 
 
    What We Do Not Do:
      1. We do not make guarantees, representations or insure the performance or condition of any item
          after the date and time of this inspection. Please remember that almost every component in any
          house, except new construction, is in used condition and has ordinary wear and tear.
      2. We do not inspect any item which we cannot see in a normal inspection. For example, we do not
          move furniture, floor or wall coverings, or other furnishings.
      3. We do not inspect buried pipes or wiring. We cannot see items covered by walls or flooring.
          Repairs, painting or remodeling may hide evidence of prior damage or defects.
      4. We do not dismantle equipment to inspect component parts. We do suggest that you ask the
          owner about repairs, covered up items or previous problems.
      5. We do not check heating elements in central air conditioning units when the outside ambient
          temperature is above 65 degrees. We do not check central air conditioners in the cooling cycle
          when the outside ambient temperatures are below 65 degrees.
      6. We do not check window air conditioners, refrigerators, washers, dryers or icemakers.
      7. We do not inspect for formaldehyde, lead, Chinese drywall, mold, radon or other environmental
          hazards unless specifically included in the line item prices.
      8. We do not walk on roof surfaces with an eave height above 8 feet or a slope greater than 4/12.
          We do not walk on tile roofs due to possible damage.
      9. We do not enter crawl spaces with a clearance of less than 24 inches from soil to bottom of floor
          joists.
      10. We do not inspect for building codes, soil analysis, gas leaks, adequacy of design, capacity,
          efficiency, size, value, flood plain, pollution or habitability. Please remember that older houses do
          not meet the same standard as newer houses even though items in both might be performing
          functions for which they are intended.
      11. We do not hold ourselves out to be specialists for any particular item.
      12. We are a general real estate inspection company. If we report that an item is not performing its
          intended function or needs repair, we urge you to have that item, as well as the entire system,
          examined by a specialist before purchasing the property.
      13. We do not give estimates of the cost to repair any item. Repair cost estimates can be furnished
          upon request for an additional fee of $85.00.
      14. If the water is off at the main water shut off valve or the meter location at the time of inspection,
          Chief Inspection Services at their discretion may or may not activate the water service for
          inspection. Certain restrictions apply.
      15. Chief Inspection Services will perform a complete inspection on one (1) mobilization only. If
          electric or water is not on at the time of inspection, additional service call charges in the amount of
          $75.00 will be billed for additional trips to the property. Client is responsible for payment of
          additional trip charges. Client will be responsible to get reimbursement for addition trip charges
          from seller, sellers agent or other parties at their discretion if necessary.
 
 
    Inspection Fee of $XXX.00 was paid by                              upon completion and
    prior to issuance of the report.
 
 
 
                                                     Date:
    Client Signature
 
 
 
                                                     Date: October 10, 2011
    Jeff Clair
    Chief Inspection Services


                                                                                                              3
Chief Inspection Services
                                                                      Certified Inspection Report

                                                                                EXTERIOR




                REPAIR OR REPLACE


                                    INTENDED FUNCTION
                NEEDS IMMEDIATE
NOT INSPECTED                                              NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE
                                                           OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME



                                    PERFORMING
                                                           OF THIS INSPECTION.

                                                           THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY.




                X                                       WALL STRUCTURE       Type: Masonry Block w/ Wood framed addition

                X                                       PATIO

                                    X                   FOUNDATION          Type: concrete slab

                X                                       WATER DRAINAGE

NA                                                      SPRINKLER SYSTEM
                                                        No. of zones:
                X                                       EXTERIOR FINISHES             Type: Cementicious Coating / cement board siding

                X                                       WINDOW / DOOR TRIM

                                    X                   DRIVEWAY / PARKING

NA                                                      GARAGE DOOR

NA                                                      GARAGE DOOR OPENER

COMMENTS / RECOMMENDATIONS –
Wood framed addition is non compliant in several areas. Structural damage to framing was
observed, water infiltration under the exterior walls and ponding inside was observed, improper
electrical and plumbing issues were observed.
Recommend the entire rear addition is removed and replaced with proper construction
techniques and permitting for safety and effective water control issues.
Page.

See photos next




                                                                                                                                         4
Chief Inspection Services
   Certified Inspection Report




                                 5
Chief Inspection Services
                                                                              Certified Inspection Report

                                                                                             ROOF




                REPAIR OR REPLACE


                                    INTENDED FUNCTION
                NEEDS IMMEDIATE
NOT INSPECTED                                                NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE
                                                             OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME



                                    PERFORMING
                                                             OF THIS INSPECTION.

                                                             THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY.




                X                                       ROOF COVERING                Type: 3 tab Composition Shingles
                                                        Roof was inspected via walking on surface
                X                                       FLASHINGS

                X                                       GUTTERS / DOWNSPOUTS

                                    X                   FACIA

                1                   X                   VENT CAPS

                                    X                   SOFFITS

                                    X                   ROOF FRAMING
                                                        Type: Pre engineered trusses @ 24” on center
                                                        Style: Gable
5 – 7 Years                                             ESTIMATED AGE OF ROOF COVERING

COMMENTS / RECOMMENDATIONS –
Roof covering at low sloped roof surface is at or beyond it’s useful life and should be replaced
as soon as practical.
Evidence of improper laps were observed on rolled roofing.
Flashing at rolled roofing and shingles is improper and should be corrected to prevent roof
leaks.
Visible roof leaks were observed at rear addition and soffit areas.
Gutters and downspouts have failed and water is draining into structure.
Recommend repairs are made as necessary to control roof drainage away from structure.

See photos next page.




                                                                                                                           6
Chief Inspection Services
   Certified Inspection Report




                                 7
Chief Inspection Services
                                                                        Certified Inspection Report

                                                                                   ATTIC




                                    INTENDED FUNCTION
                REPAIR OR REPLACE
                                                           NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE

                NEEDS IMMEDIATE
NOT INSPECTED
                                                           OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME



                                    PERFORMING
                                                           OF THIS INSPECTION.

                                                           THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY.




                                    X                   INSULATION        Type: Blown Cellulose    R-11

                                    X                   ROOF INTERIOR     Water Stains: None visible

                                    X                   ROOF VENTS         Type: Eave, Off ridge

                                    X                   ELECTRICAL BOXES

                                    X                   ROOF FRAMING

                                    X                   EXHAUST VENTS

                  X                                     ATTIC ACCESS

COMMENTS / RECOMMENDATIONS – Attic was inspected from opening due to restricted access;
attic space over rear addition was not visible.
Recommend drywall ceiling is removed at rear addition to provide access for further evaluation
of structural wall connections to roof framing.




                                                                                                                         8
Chief Inspection Services
                                                                        Certified Inspection Report

                                                                     DOORS / WINDOWS / INTERIOR




                REPAIR OR REPLACE


                                    INTENDED FUNCTION
                NEEDS IMMEDIATE
NOT INSPECTED                                              NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE
                                                           OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME



                                    PERFORMING
                                                           OF THIS INSPECTION.

                                                           THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY.




                                    X                   FRONT ENTRY DOOR

                                    X                   DOOR BELL

NA                                                      SLIDING DOORS

                                    X                   INTERIOR DOORS            Type: Hollow core

                                    X                   WINDOWS / SCREENS         Type: Single Hung

                                    X                   CLOSET DOORS

                X                                       EXTERIOR DOORS

                X                                       INTERIOR WALLS & CEILINGS      Type: Drywall

                X                                       FLOORING

N                                                       FIREPLACE
A
COMMENTS / RECOMMENDATIONS –
Exterior doors are rubbing the jambs and wood rot / moisture damage was observed at rear
addition.
Exterior door at patio area does not open correctly due to sloping floors.
Interior walls and floor of rear addition exhibited significant water infiltration as evidenced by
ponding water, 100% moisture readings and improper sloping of exterior grades.
Peeling paint was observed in 1st bathroom that should be removed and replaced to prevent
moisture buildup on interior walls.




                                                                                                                         9
Chief Inspection Services
                                                                                   Certified Inspection Report

                                                                                    KITCHEN / APPLIANCES




                REPAIR OR REPLACE


                                    INTENDED FUNCTION
                NEEDS IMMEDIATE
NOT INSPECTED                                                 NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE
                                                              OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME



                                    PERFORMING
                                                              OF THIS INSPECTION.

                                                              THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY.




                X                                       DISHWASHER
                                                        Manufacturer: Frigidaire    Color: white
                X                                       RANGE / OVEN                    Type: Free standing; electric
                                                        Manufacturer: Frigidaire Color: white
                                    X                   VENTHOOD                       Type: Recirculating
NA                                                      DISPOSAL
                X                                       KITCHEN SINK
                                    X                   CABINETS
                X                                       RECEPTACLES
NA                                                      MICROWAVE
                                                        Manufacturer: Gold Star Color: white
                X                                       COUNTERTOPS                   Type: Laminate
COMMENTS / RECOMMENDATIONS –
Dishwasher is missing the interior components and did not function.
Stove burners did not function when tested.
Refrigerator is missing freezer parts.
Bottom of sink bas cabinet is deteriorated and should be replaced with newer materials due to
previous water damage.
Countertops are uneven and should be corrected as necessary.




                                                                                                                            10
Chief Inspection Services
                                                                              Certified Inspection Report

                                                                                      PLUMBING




                REPAIR OR REPLACE


                                    INTENDED FUNCTION
                NEEDS IMMEDIATE
NOT INSPECTED                                                NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE
                                                             OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME



                                    PERFORMING
                                                             OF THIS INSPECTION.

                                                             THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY.




                X
                                                        BATH VANITY CABINETS & SINKS
                X
                                                        BATH TUBS
                X
                                                        SHOWERS
                X
                                                        TOILETS
                X                                       WATER HEATER              Age: 2007   Type: electric      Size: 40 Gal
                                                        Manufacturer: Whirlpool
                X
                                                        OUTSIDE FAUCETS
                X
                                                        FIXTURE SHUT OFF VALVES

                X                                       WASHER / DRYER CONNECTIONS
                                                        DRYER HEAT SOURCE: NA
                                                        DRYER VENTED THROUGH NA:
                X
                                                        MAIN WATER SHUT OFF VALVE                Location: L Side of house

GALVANIZED /                                            SUPPLY PIPING
CPVC
                                                        WATER PRESSURE: 53 PSI

Cast iron    DRAIN / VENT PIPING
COMMENT / RECOMMENDATIONS –
Plumbing system is installed improperly at rear addition and rear bathroom as evidenced by
unsupported piping, mismatched pipe materials and exposed fittings.
Water heater has been on without water inside the tank which can damage the heating
elements.
Water supply was off at time of inspection and the water meter valve was difficult to operate
which prohibited fully inspecting the supply piping.
Cast iron drain lines were visible at the main house and should be video inspected to determine
actual condition due to the cast iron becoming brittle over time.
Vent pipe at roof surface was capped with rubber plug and restricting proper venting of drain
system.
Galvanized water supply piping was observed in several areas which indicates the system is
beyond it’s useful life.
Recommend the entire water supply system is replaced.
Floor drains at rear patio drained to mysterious location and should be video inspected to
determine end of line.
See photos next page.


                                                                                                                                 12
Chief Inspection Services
                                                                                 Certified Inspection Report
                                                                                HEATING / AIR CONDITIONING




                REPAIR OR REPLACE


                                    INTENDED FUNCTION
                NEEDS IMMEDIATE
                                                              NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE
NOT INSPECTED                                                 OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME




                                    PERFORMING
                                                              OF THIS INSPECTION.

                                                              THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY.




Type: Central air & heat                                                     Fuel: Electric             Manufacturer: Carrier


                X                                       CONDENSOR / COMPRESSOR (Outside unit)
                                                        Model: 38CKC036330 Size: 3 TONS Age: 1998
                                    X                   REFRIGERATION LINES

                X                                       DISTRIBUTION DUCTS

                                    X                   CONTROLS

                X                                       BLOWER / FAN

                X                                       EVAPORATOR COIL (Air handler)
                                                        Model: FA4ANF036 Size: 3 TONS Age: 1998
                                    X                   CONDENSATE DRAIN

                                                        TEMPERATURE CHANGE AT COILS
                X                                       Supply Temp: 68.7   Return Temp: 74.8 Temp Difference: 61. degrees
                                                        Normal Temperature Difference should be between 16-21 degrees
                x                                       AIR FILTER               Location: Return grill at bottom of unit
                                                        Recommend changing the filters every 30 days.
COMMENTS / RECOMMENDATIONS –
The temperature change during the cooling cycle was below the normal ranges at the time of
inspection. HVAC equipment is beyond it’s useful life and should be upgraded with newer, more
efficient models.
Distribution ducts are deteriorated and not sealed at the connections to the boxes within the
attic space. Recommend all grey plastic duct is replaced with new materials.
Recommend System is further evaluated and repaired as necessary by a licensed HVAC
contractor.




                                                                                                                                13
Chief Inspection Services
   Certified Inspection Report




                                 14
Chief Inspection Services
                                                                           Certified Inspection Report

                                                                                     ELECTRICAL




                REPAIR OR REPLACE


                                    INTENDED FUNCTION
                NEEDS IMMEDIATE
NOT INSPECTED                                              NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE
                                                           OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME



                                    PERFORMING
                                                           OF THIS INSPECTION.

                                                           THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY.




Size: 100 Amps                                                   Location: Rear of house                      Type: Underground

                                     X                  SERVICE ENTRANCE              Conductor Type: Aluminum

                                     X                  SWITCHES
                                     X                  INSTALLED FIXTURES
                                     X                  ATTIC ELECTRICAL
                 X                                      MAIN PANEL / DISCONNECT                 Location: L Side of house
                 X                                      SUB PANEL                               Location: Garage

                 X                                      BRANCH WIRING                           Type: NM Cable

                                                        KITCHEN & BATHROOM GFI OUTLETS
                 X
                                                        ROOM OUTLETS
                                     X
                                                        EXTERIOR OUTLETS
                 X
                                     X                  EXHAUST FANS

                                     X                  EQUIPMENT DISCONNECTS
                                                        SMOKE DETECTORS
                 X                                      Recommend all batteries are changed upon occupancy.
COMMENTS / RECOMMENDATIONS –
Electrical panel is “sizzling” at intermittent times and is beyond it’s useful life.
Recommend panel is replaced with a newer, more reliable model.
Branch circuit wiring is unsafe at rear addition and needs immediate attention for safety.
Kitchen, bathroom and exterior receptacles are not GFI type and should be replaced with
GFI type for safety.
Recommend entire system is further evaluated by a licensed electrician for safety.




                                                                                                                                  15
Chief Inspection Services
   Certified Inspection Report




                                 16
Chief Inspection Services
                                                                         Certified Inspection Report

                                                                       POOL / SPA / SCREENED AREA




                REPAIR OR REPLACE


                                    INTENDED FUNCTION
                NEEDS IMMEDIATE
NOT INSPECTED                                               NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE
                                                            OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME



                                    PERFORMING
                                                            OF THIS INSPECTION.

                                                            THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY.




X                                   X                   POOL SURFACE         Type: Gunite

X                                   X                   PUMP Type:

X                                   X                   DECKING              Type: Concrete

NA                                                      POOL HEATER         Type:
                                                        Temp. change was not checked due to control panel being locked.
NA                                                      SCREEN DOORS

NA                                                      SCREEN ENCLOSURES

NA                                                      FILTER / SKIMMER

NA                                                      SPA JETS

NA                                                      POOL ACCESSORIES
COMMENTS / RECOMMENDATIONS –
Pool was filled with algae and could not be inspected at this time.
Evidence of pool surface cracks were observed above the water line.
Recommend pool is drained and professional cleaned by a licensed Pool specialist.
Recommend door and window alarms are installed as well as pool safety fence is installed
to prohibit unauthorized access to pool area.




                                                                                                                          17
                                    Chief Inspection Services
                                          Certified Inspection Report
 
                         HOME INSPECTION REPORT SUMMARY PAGE
 
            Client Name:              Mr. & Mrs. Homebuyer
            Property Address:         1567 Yourstreet, Hometown, FL 32725
            Date and Time of Inspection: October 10, 2011 @ 11:00am
 
    The items noted below were found to be inoperable, non-functioning or defective at the time our
    inspection was conducted. We urge you to have these items, as well as the entire system
    repaired, replaced or further evaluated by a licensed professional prior to closing.
 
    Exterior
    Wood framed addition is non compliant in several areas. Structural damage to framing was observed,
    water infiltration under the exterior walls and ponding inside was observed, improper electrical and
    plumbing issues were observed.
    Recommend the entire rear addition is removed and replaced with proper construction techniques and
    permitting for safety and effective water control issues.
    Page.
 
    Roof
    Roof covering at low sloped roof surface is at or beyond it’s useful life and should be replaced as soon as
    practical.
    Evidence of improper laps were observed on rolled roofing.
    Flashing at rolled roofing and shingles is improper and should be corrected to prevent roof leaks.
    Visible roof leaks were observed at rear addition and soffit areas.
    Gutters and downspouts have failed and water is draining into structure.
    Recommend repairs are made as necessary to control roof drainage away from structure.
 
    Attic
    Attic was inspected from opening due to restricted access; attic space over rear addition was not visible.
    Recommend drywall ceiling is removed at rear addition to provide access for further evaluation of
    structural wall connections to roof framing.
 
    Doors/Windows/Interior
    Exterior doors are rubbing the jambs and wood rot / moisture damage was observed at rear addition.
    Exterior door at patio area does not open correctly due to sloping floors.
    Interior walls and floor of rear addition exhibited significant water infiltration as evidenced by ponding
    water, 100% moisture readings and improper sloping of exterior grades.
    Peeling paint was observed in 1st bathroom that should be removed and replaced to prevent moisture
    buildup on interior walls.
 
    Kitchen / Appliances
    Dishwasher is missing the interior components and did not function.
    Stove burners did not function when tested.
    Refrigerator is missing freezer parts.
    Bottom of sink bas cabinet is deteriorated and should be replaced with newer materials due to previous
    water damage.
    Countertops are uneven and should be corrected as necessary.




                                                                                                                 18
                                   Chief Inspection Services
                                          Certified Inspection Report
 
                       HOME INSPECTION REPORT SUMMARY PAGE Cont’d.
 
            Client Name:              Mr. & Mrs. Homebuyer
            Property Address:         1567 Yourstreet, Hometown, FL 32725
            Date and Time of Inspection: October 10, 2011 @ 11:00am
 
    The items noted below were found to be inoperable, non-functioning or defective at the time our
    inspection was conducted. We urge you to have these items, as well as the entire system
    repaired, replaced or further evaluated by a licensed professional prior to closing.
 
    Plumbing
    Plumbing system is installed improperly at rear addition and rear bathroom as evidenced by unsupported
    piping, mismatched pipe materials and exposed fittings.
    Water heater has been on without water inside the tank which can damage the heating elements.
    Water supply was off at time of inspection and the water meter valve was difficult to operate which
    prohibited fully inspecting the supply piping.
    Cast iron drain lines were visible at the main house and should be video inspected to determine actual
    condition due to the cast iron becoming brittle over time.
    Vent pipe at roof surface was capped with rubber plug and restricting proper venting of drain system.
    Galvanized water supply piping was observed in several areas which indicates the system is beyond it’s
    useful life.
    Recommend the entire water supply system is replaced.
    Floor drains at rear patio drained to mysterious location and should be video inspected to determine end of
    line.
 
    HVAC
    The temperature change during the cooling cycle was below the normal ranges at the time of inspection.
    HVAC equipment is beyond it’s useful life and should be upgraded with newer, more efficient models.
    Distribution ducts are deteriorated and not sealed at the connections to the boxes within the attic space.
    Recommend all grey plastic duct is replaced with new materials.
    Recommend System is further evaluated and repaired as necessary by a licensed HVAC contractor.
 
    Electrical
    Electrical panel is “sizzling” at intermittent times and is beyond it’s useful life.
    Recommend panel is replaced with a newer, more reliable model.
    Branch circuit wiring is unsafe at rear addition and needs immediate attention for safety.
    Kitchen, bathroom and exterior receptacles are not GFI type and should be replaced with GFI type for
    safety.
    Recommend entire system is further evaluated by a licensed electrician for safety.
 
    Pool / Screen Enclosure
    Pool was filled with algae and could not be inspected at this time.
    Evidence of pool surface cracks were observed above the water line.
    Recommend pool is drained and professional cleaned by a licensed Pool specialist.
    Recommend door and window alarms are installed as well as pool safety fence is installed to prohibit
    unauthorized access to pool area.
 
    Please contact Jeff Clair at 407-383-7241 if you have any questions regarding this inspection
    report. Thank you for choosing Chief Inspection Services.
 
 
 
 
 
    Jeff Clair
    RPI-0437
    State Certified Home Inspector #725


                                                                                                            19

More Related Content

What's hot

Valuation Format
Valuation FormatValuation Format
Valuation FormatRohit Digra
 
Professional Practice II
Professional Practice IIProfessional Practice II
Professional Practice IIseenyeeyong
 
Construction Project Process Flow
Construction Project Process FlowConstruction Project Process Flow
Construction Project Process FlowRajasekar M
 
Assignment - Preliminary Cost Appraisal
Assignment - Preliminary Cost AppraisalAssignment - Preliminary Cost Appraisal
Assignment - Preliminary Cost AppraisalKai Yun Pang
 
Contracts & Claims Management Workshop (Session-1)
Contracts & Claims Management Workshop (Session-1)Contracts & Claims Management Workshop (Session-1)
Contracts & Claims Management Workshop (Session-1)Tahir B Mirza
 
SMM7 Bill of Quantities
SMM7 Bill of QuantitiesSMM7 Bill of Quantities
SMM7 Bill of QuantitiesNatalie Reid
 
Software presentation
Software presentationSoftware presentation
Software presentationTimun Loh
 
Types of resources in civil engineering field
Types of resources in civil engineering fieldTypes of resources in civil engineering field
Types of resources in civil engineering fieldswetha110
 
Measurement III:Doors & Windows
Measurement III:Doors & WindowsMeasurement III:Doors & Windows
Measurement III:Doors & Windows마 이환
 
Quantity surveyor (ici+itd)
Quantity surveyor (ici+itd)Quantity surveyor (ici+itd)
Quantity surveyor (ici+itd)ALISON TANG
 
Variations in works contracts
Variations in works contractsVariations in works contracts
Variations in works contractsDr K M SONI
 
Provisional sum prime cost sum
Provisional sum  prime cost sumProvisional sum  prime cost sum
Provisional sum prime cost sumEst
 
Smm2 second edition
Smm2 second editionSmm2 second edition
Smm2 second editionBt Lee
 
Tendering process, Bid Evaluation & Award Process
Tendering process, Bid Evaluation & Award ProcessTendering process, Bid Evaluation & Award Process
Tendering process, Bid Evaluation & Award ProcessPrateek Kashyap
 

What's hot (20)

Valuation Format
Valuation FormatValuation Format
Valuation Format
 
contract procedure
contract procedurecontract procedure
contract procedure
 
Professional Practice II
Professional Practice IIProfessional Practice II
Professional Practice II
 
Construction Project Process Flow
Construction Project Process FlowConstruction Project Process Flow
Construction Project Process Flow
 
Assignment - Preliminary Cost Appraisal
Assignment - Preliminary Cost AppraisalAssignment - Preliminary Cost Appraisal
Assignment - Preliminary Cost Appraisal
 
METHOD STATEMENT
METHOD STATEMENTMETHOD STATEMENT
METHOD STATEMENT
 
bs:copbs101
bs:copbs101bs:copbs101
bs:copbs101
 
Contracts & Claims Management Workshop (Session-1)
Contracts & Claims Management Workshop (Session-1)Contracts & Claims Management Workshop (Session-1)
Contracts & Claims Management Workshop (Session-1)
 
Site possession
Site possessionSite possession
Site possession
 
SMM7 Bill of Quantities
SMM7 Bill of QuantitiesSMM7 Bill of Quantities
SMM7 Bill of Quantities
 
Property Inspection Report
Property Inspection ReportProperty Inspection Report
Property Inspection Report
 
Software presentation
Software presentationSoftware presentation
Software presentation
 
BS course bldg diagnostic
BS course bldg diagnosticBS course bldg diagnostic
BS course bldg diagnostic
 
Types of resources in civil engineering field
Types of resources in civil engineering fieldTypes of resources in civil engineering field
Types of resources in civil engineering field
 
Measurement III:Doors & Windows
Measurement III:Doors & WindowsMeasurement III:Doors & Windows
Measurement III:Doors & Windows
 
Quantity surveyor (ici+itd)
Quantity surveyor (ici+itd)Quantity surveyor (ici+itd)
Quantity surveyor (ici+itd)
 
Variations in works contracts
Variations in works contractsVariations in works contracts
Variations in works contracts
 
Provisional sum prime cost sum
Provisional sum  prime cost sumProvisional sum  prime cost sum
Provisional sum prime cost sum
 
Smm2 second edition
Smm2 second editionSmm2 second edition
Smm2 second edition
 
Tendering process, Bid Evaluation & Award Process
Tendering process, Bid Evaluation & Award ProcessTendering process, Bid Evaluation & Award Process
Tendering process, Bid Evaluation & Award Process
 

Viewers also liked

Electrical inspect ir sample report
Electrical inspect ir sample reportElectrical inspect ir sample report
Electrical inspect ir sample reportpropertyinspectir
 
Sample Home Inspection Report
Sample Home Inspection ReportSample Home Inspection Report
Sample Home Inspection Reporttspargo
 
Roof lube 25 point inspection & dealer installer bundles
Roof lube  25 point  inspection & dealer installer bundlesRoof lube  25 point  inspection & dealer installer bundles
Roof lube 25 point inspection & dealer installer bundlesCool Roof Innovations
 
Industrial inspection sample report
Industrial inspection sample reportIndustrial inspection sample report
Industrial inspection sample reportpropertyinspectir
 
Quality Assurance in PEB - Pre Engineered steel buildings
Quality Assurance in PEB - Pre Engineered steel buildingsQuality Assurance in PEB - Pre Engineered steel buildings
Quality Assurance in PEB - Pre Engineered steel buildingsmbphenix
 
EOT Crane Inspection Check list, helpful for safety officers during inspection
EOT Crane Inspection Check list, helpful for safety officers during inspectionEOT Crane Inspection Check list, helpful for safety officers during inspection
EOT Crane Inspection Check list, helpful for safety officers during inspectionBimal Chandra Das
 
Contractor camp inspection check list rev 9 12 16.00hr
Contractor camp inspection check list rev 9 12 16.00hrContractor camp inspection check list rev 9 12 16.00hr
Contractor camp inspection check list rev 9 12 16.00hranshse2
 
Daily mobile crane inspection checklist
Daily mobile crane inspection checklist  Daily mobile crane inspection checklist
Daily mobile crane inspection checklist Rahmat Mohamed
 
summer inter report
summer inter reportsummer inter report
summer inter reportabhijit rai
 
Guest room preventative maintenance checklist
Guest room preventative maintenance checklistGuest room preventative maintenance checklist
Guest room preventative maintenance checklistRyan Snow
 

Viewers also liked (11)

Electrical inspect ir sample report
Electrical inspect ir sample reportElectrical inspect ir sample report
Electrical inspect ir sample report
 
Sample Home Inspection Report
Sample Home Inspection ReportSample Home Inspection Report
Sample Home Inspection Report
 
Atlanta Sample Home Inspection Report
Atlanta Sample Home Inspection ReportAtlanta Sample Home Inspection Report
Atlanta Sample Home Inspection Report
 
Roof lube 25 point inspection & dealer installer bundles
Roof lube  25 point  inspection & dealer installer bundlesRoof lube  25 point  inspection & dealer installer bundles
Roof lube 25 point inspection & dealer installer bundles
 
Industrial inspection sample report
Industrial inspection sample reportIndustrial inspection sample report
Industrial inspection sample report
 
Quality Assurance in PEB - Pre Engineered steel buildings
Quality Assurance in PEB - Pre Engineered steel buildingsQuality Assurance in PEB - Pre Engineered steel buildings
Quality Assurance in PEB - Pre Engineered steel buildings
 
EOT Crane Inspection Check list, helpful for safety officers during inspection
EOT Crane Inspection Check list, helpful for safety officers during inspectionEOT Crane Inspection Check list, helpful for safety officers during inspection
EOT Crane Inspection Check list, helpful for safety officers during inspection
 
Contractor camp inspection check list rev 9 12 16.00hr
Contractor camp inspection check list rev 9 12 16.00hrContractor camp inspection check list rev 9 12 16.00hr
Contractor camp inspection check list rev 9 12 16.00hr
 
Daily mobile crane inspection checklist
Daily mobile crane inspection checklist  Daily mobile crane inspection checklist
Daily mobile crane inspection checklist
 
summer inter report
summer inter reportsummer inter report
summer inter report
 
Guest room preventative maintenance checklist
Guest room preventative maintenance checklistGuest room preventative maintenance checklist
Guest room preventative maintenance checklist
 

Similar to Sample Home Inspection Report.

Similar to Sample Home Inspection Report. (20)

Insp. auth. form.
Insp. auth. form.Insp. auth. form.
Insp. auth. form.
 
Sample Report
Sample ReportSample Report
Sample Report
 
Sample
SampleSample
Sample
 
Sample Report
Sample ReportSample Report
Sample Report
 
Sample 2007 built_rural_area
Sample 2007 built_rural_areaSample 2007 built_rural_area
Sample 2007 built_rural_area
 
Contract
ContractContract
Contract
 
Contract
ContractContract
Contract
 
Sample one year_builder_warranty
Sample one year_builder_warrantySample one year_builder_warranty
Sample one year_builder_warranty
 
Sample inspection report copy
Sample inspection report copySample inspection report copy
Sample inspection report copy
 
Inspection agreement page
Inspection agreement pageInspection agreement page
Inspection agreement page
 
Contract
ContractContract
Contract
 
Contract
ContractContract
Contract
 
Contract
ContractContract
Contract
 
Our inspection agreement
Our inspection agreementOur inspection agreement
Our inspection agreement
 
Sample report residential 1[1]
Sample report residential 1[1]Sample report residential 1[1]
Sample report residential 1[1]
 
Preview inspectionfull
Preview inspectionfullPreview inspectionfull
Preview inspectionfull
 
Sample inspection agreement
Sample inspection agreementSample inspection agreement
Sample inspection agreement
 
Sample commercial inspection
Sample commercial inspectionSample commercial inspection
Sample commercial inspection
 
All-Star Home Inspections Sample Report
All-Star Home Inspections Sample ReportAll-Star Home Inspections Sample Report
All-Star Home Inspections Sample Report
 
Texas.PDF
Texas.PDFTexas.PDF
Texas.PDF
 

Recently uploaded

Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️
Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️
Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️soniya singh
 
9990771857 Call Girls in Dwarka Sector 1 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 1 Delhi (Call Girls) Delhi9990771857 Call Girls in Dwarka Sector 1 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 1 Delhi (Call Girls) Delhidelhimodel235
 
Majestique Viman Nagar Pune Brochure.pdf
Majestique Viman Nagar Pune Brochure.pdfMajestique Viman Nagar Pune Brochure.pdf
Majestique Viman Nagar Pune Brochure.pdfBabyrudram
 
9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhidelhimodel235
 
9990771857 Call Girls in Dwarka Sector 2 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 2 Delhi (Call Girls) Delhi9990771857 Call Girls in Dwarka Sector 2 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 2 Delhi (Call Girls) Delhidelhimodel235
 
Low Rate ↬Call Girls in Trilokpuri Delhi ↫8447779280}Escorts Service In Delhi
Low Rate ↬Call Girls in Trilokpuri Delhi ↫8447779280}Escorts Service In DelhiLow Rate ↬Call Girls in Trilokpuri Delhi ↫8447779280}Escorts Service In Delhi
Low Rate ↬Call Girls in Trilokpuri Delhi ↫8447779280}Escorts Service In Delhiasmaqueen5
 
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports WorkTENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports WorkTurbo Tenant
 
Telibagh & Call Girls Lucknow - 450+ Call Girl Cash Payment 🎂 8923113531 🎪 Ne...
Telibagh & Call Girls Lucknow - 450+ Call Girl Cash Payment 🎂 8923113531 🎪 Ne...Telibagh & Call Girls Lucknow - 450+ Call Girl Cash Payment 🎂 8923113531 🎪 Ne...
Telibagh & Call Girls Lucknow - 450+ Call Girl Cash Payment 🎂 8923113531 🎪 Ne...gurkirankumar98700
 
Call Girls In Mayur Vihar Delhi ☆↫8447779280 ❤Escorts Service In Delhi
Call Girls In Mayur Vihar Delhi ☆↫8447779280 ❤Escorts Service In DelhiCall Girls In Mayur Vihar Delhi ☆↫8447779280 ❤Escorts Service In Delhi
Call Girls In Mayur Vihar Delhi ☆↫8447779280 ❤Escorts Service In Delhiasmaqueen5
 
Purva Soukhyam in Guduvancheri Chennai.pdf
Purva Soukhyam in Guduvancheri Chennai.pdfPurva Soukhyam in Guduvancheri Chennai.pdf
Purva Soukhyam in Guduvancheri Chennai.pdfpritika141199
 
Greater Vancouver Realtors Statistics Package April 2024
Greater Vancouver Realtors Statistics Package April 2024Greater Vancouver Realtors Statistics Package April 2024
Greater Vancouver Realtors Statistics Package April 2024VickyAulakh1
 
Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...delhimodel235
 
Kohinoor Hinjewadi Phase 2 Pune E-Brochure.pdf
Kohinoor Hinjewadi Phase 2 Pune  E-Brochure.pdfKohinoor Hinjewadi Phase 2 Pune  E-Brochure.pdf
Kohinoor Hinjewadi Phase 2 Pune E-Brochure.pdfManishSaxena95
 
9990771857 Call Girls in Dwarka Sector 137 Noida (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 137 Noida (Call Girls) Delhi9990771857 Call Girls in Dwarka Sector 137 Noida (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 137 Noida (Call Girls) Delhidelhimodel235
 
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️soniya singh
 
Call Girls In Vasant Vihar Delhi 💯Call Us 🔝8264348440🔝
Call Girls In Vasant Vihar Delhi 💯Call Us 🔝8264348440🔝Call Girls In Vasant Vihar Delhi 💯Call Us 🔝8264348440🔝
Call Girls In Vasant Vihar Delhi 💯Call Us 🔝8264348440🔝soniya singh
 
M3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
M3M The Line Brochure - Premium Investment Opportunity for Commercial VenturesM3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
M3M The Line Brochure - Premium Investment Opportunity for Commercial Venturessheltercareglobal
 
Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|
Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|
Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|AkshayJoshi575980
 
Best Deal Virtual Space in Satya The Hive Tata Zudio 750 Sqft 1.89 Cr All inc...
Best Deal Virtual Space in Satya The Hive Tata Zudio 750 Sqft 1.89 Cr All inc...Best Deal Virtual Space in Satya The Hive Tata Zudio 750 Sqft 1.89 Cr All inc...
Best Deal Virtual Space in Satya The Hive Tata Zudio 750 Sqft 1.89 Cr All inc...ApartmentWala1
 
Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...
Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...
Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...asmaqueen5
 

Recently uploaded (20)

Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️
Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️
Call Girls in shastri nagar Delhi 8264348440 ✅ call girls ❤️
 
9990771857 Call Girls in Dwarka Sector 1 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 1 Delhi (Call Girls) Delhi9990771857 Call Girls in Dwarka Sector 1 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 1 Delhi (Call Girls) Delhi
 
Majestique Viman Nagar Pune Brochure.pdf
Majestique Viman Nagar Pune Brochure.pdfMajestique Viman Nagar Pune Brochure.pdf
Majestique Viman Nagar Pune Brochure.pdf
 
9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi
 
9990771857 Call Girls in Dwarka Sector 2 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 2 Delhi (Call Girls) Delhi9990771857 Call Girls in Dwarka Sector 2 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 2 Delhi (Call Girls) Delhi
 
Low Rate ↬Call Girls in Trilokpuri Delhi ↫8447779280}Escorts Service In Delhi
Low Rate ↬Call Girls in Trilokpuri Delhi ↫8447779280}Escorts Service In DelhiLow Rate ↬Call Girls in Trilokpuri Delhi ↫8447779280}Escorts Service In Delhi
Low Rate ↬Call Girls in Trilokpuri Delhi ↫8447779280}Escorts Service In Delhi
 
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports WorkTENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
 
Telibagh & Call Girls Lucknow - 450+ Call Girl Cash Payment 🎂 8923113531 🎪 Ne...
Telibagh & Call Girls Lucknow - 450+ Call Girl Cash Payment 🎂 8923113531 🎪 Ne...Telibagh & Call Girls Lucknow - 450+ Call Girl Cash Payment 🎂 8923113531 🎪 Ne...
Telibagh & Call Girls Lucknow - 450+ Call Girl Cash Payment 🎂 8923113531 🎪 Ne...
 
Call Girls In Mayur Vihar Delhi ☆↫8447779280 ❤Escorts Service In Delhi
Call Girls In Mayur Vihar Delhi ☆↫8447779280 ❤Escorts Service In DelhiCall Girls In Mayur Vihar Delhi ☆↫8447779280 ❤Escorts Service In Delhi
Call Girls In Mayur Vihar Delhi ☆↫8447779280 ❤Escorts Service In Delhi
 
Purva Soukhyam in Guduvancheri Chennai.pdf
Purva Soukhyam in Guduvancheri Chennai.pdfPurva Soukhyam in Guduvancheri Chennai.pdf
Purva Soukhyam in Guduvancheri Chennai.pdf
 
Greater Vancouver Realtors Statistics Package April 2024
Greater Vancouver Realtors Statistics Package April 2024Greater Vancouver Realtors Statistics Package April 2024
Greater Vancouver Realtors Statistics Package April 2024
 
Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
 
Kohinoor Hinjewadi Phase 2 Pune E-Brochure.pdf
Kohinoor Hinjewadi Phase 2 Pune  E-Brochure.pdfKohinoor Hinjewadi Phase 2 Pune  E-Brochure.pdf
Kohinoor Hinjewadi Phase 2 Pune E-Brochure.pdf
 
9990771857 Call Girls in Dwarka Sector 137 Noida (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 137 Noida (Call Girls) Delhi9990771857 Call Girls in Dwarka Sector 137 Noida (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 137 Noida (Call Girls) Delhi
 
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
 
Call Girls In Vasant Vihar Delhi 💯Call Us 🔝8264348440🔝
Call Girls In Vasant Vihar Delhi 💯Call Us 🔝8264348440🔝Call Girls In Vasant Vihar Delhi 💯Call Us 🔝8264348440🔝
Call Girls In Vasant Vihar Delhi 💯Call Us 🔝8264348440🔝
 
M3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
M3M The Line Brochure - Premium Investment Opportunity for Commercial VenturesM3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
M3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
 
Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|
Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|
Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|
 
Best Deal Virtual Space in Satya The Hive Tata Zudio 750 Sqft 1.89 Cr All inc...
Best Deal Virtual Space in Satya The Hive Tata Zudio 750 Sqft 1.89 Cr All inc...Best Deal Virtual Space in Satya The Hive Tata Zudio 750 Sqft 1.89 Cr All inc...
Best Deal Virtual Space in Satya The Hive Tata Zudio 750 Sqft 1.89 Cr All inc...
 
Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...
Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...
Call girls in new Ashok NagarDelhi꧁ 8447779280꧂ Escort Service Women Seeking ...
 

Sample Home Inspection Report.

  • 1.   Chief Inspection Services Professional Building Consultants Since 2002 FL Certified General Contractor #CGC058361 FL Certified Building Inspector #BN 5316 FL Certified Home Inspector #725 Registered Professional Inspector # 0437     HOME INSPECTION REPORT THIS INSPECTION MEETS OR EXCEEDS THE CURRENT FABI “STANDARDS OF PRACTICE”                                                       1567 Yourstreet, Hometown, FL 12345 This report is prepared exclusively for: Mr. & Mrs. Homebuyer         FL State Certified Home Inspector #725             P.O. Box 700937 St. Cloud, FL 34770-0937 Ph. 407-383-7241 Fax 407-891-7410
  • 2.   Chief Inspection Services Certified Inspection Report         Client Name: Mr. & Mrs. Homebuyer Property Address: 1567 Yourstret City, State: Hometown, FL 32725   Date and Time of Inspection: October 10, 2011 @ 11:00am   Weather Conditions: Cloudy   Temperature: 84 Humidity: 48%   HOME INSPECTION REPORT TABLE OF CONTENTS CLIENT INFO & REPORT INDEX Page 1 INSPECTION AUTHORIZATION Page 2 - 3 EXTERIOR Page 4 ROOF Page 5 ATTIC Page 6 WINDOWS / DOORS Page 7 KITCHEN / APPLIANCES Page 8 PLUMBING Page 9 HEATING / AIR CONDITIONING Page 10 ELECTRICAL Page 11 POOL / SCREEN ENCLOSURE Page 12 HOME INSPECTION SUMMARY PAGE Page 13   1
  • 3. Chief Inspection Services Certified Inspection Report Home Inspection Authorization Form This home inspection is performed in accordance with the Standards of Practice of Florida Association of Building Inspectors and is an examination of the mechanical and physical components of real property identified on page 1 of the report as they exist at the time of the inspection through visual means and operation of normal user controls. The home inspector does not necessarily possess licenses authorizing the rendering of detailed opinions regarding all of the systems, structures, and components of a building. Chief Inspection Services. may have an affiliation with third-party service providers (“TPSP”) in order to offer value-added services to its Clients. By signing this agreement you authorize our third party service providers to call you at the numbers you have provided to discuss special service offers. What We Do: 1. We perform a visual inspection in a good and workmanlike manner. 2. We tell you whether each item we inspect is performing the function for which it was intended or is in need of immediate repair. 3. We will explain any deficiencies that are present on the items we inspect. 4. The report will meet the current Standards of Practice of the Florida Association of Building Inspectors. A copy of the current Standards of Practice and Code of Ethics can be viewed at WWW.FABI.org . What the Client Must Do: 1. Client must notify us in writing of any complaints regarding our inspection within seven (7) days after receipt of our report. 2. If we report that an item is in need of immediate repair or is not performing its intended function and Client intends to purchase the property anyway, we recommend that Client have that item, as well as the entire system, examined by a licensed professional or a specialist. 3. It is agreed by all parties that, to the extent allowed by law, any damages for breach of this contract are limited to the amount of the inspection fee. 4. If Client sues on this contract but does not prevail, Client agrees to pay our reasonable attorney fees. 5. Client acknowledges that the inspector has not made any oral representations that differ from or modify what is written in this report. 6. Client must not allow anyone else to use or rely on this report. A copy of this report and/or summary page may be provided to their realtor upon request of the client. Client agrees that: “Any dispute, controversy, interpretation or claim including claims for, but not limited to, breach of contract, any form of negligence, fraud or misrepresentation arising out of, from, or related to this contract or arising out of, from or related to the inspection or inspection report shall be submitted to final and binding arbitration under the Rules and Procedures of the Expedited Arbitration of Home Inspection Dispute of Construction Arbitration Services, Inc. The decision of the arbitrator appointed thereunder shall be final and binding judgement on the Award and may be entered into any Court of competent jurisdiction.” 2
  • 4.   Chief Inspection Services Certified Inspection Report         What We Do Not Do: 1. We do not make guarantees, representations or insure the performance or condition of any item after the date and time of this inspection. Please remember that almost every component in any house, except new construction, is in used condition and has ordinary wear and tear. 2. We do not inspect any item which we cannot see in a normal inspection. For example, we do not move furniture, floor or wall coverings, or other furnishings. 3. We do not inspect buried pipes or wiring. We cannot see items covered by walls or flooring. Repairs, painting or remodeling may hide evidence of prior damage or defects. 4. We do not dismantle equipment to inspect component parts. We do suggest that you ask the owner about repairs, covered up items or previous problems. 5. We do not check heating elements in central air conditioning units when the outside ambient temperature is above 65 degrees. We do not check central air conditioners in the cooling cycle when the outside ambient temperatures are below 65 degrees. 6. We do not check window air conditioners, refrigerators, washers, dryers or icemakers. 7. We do not inspect for formaldehyde, lead, Chinese drywall, mold, radon or other environmental hazards unless specifically included in the line item prices. 8. We do not walk on roof surfaces with an eave height above 8 feet or a slope greater than 4/12. We do not walk on tile roofs due to possible damage. 9. We do not enter crawl spaces with a clearance of less than 24 inches from soil to bottom of floor joists. 10. We do not inspect for building codes, soil analysis, gas leaks, adequacy of design, capacity, efficiency, size, value, flood plain, pollution or habitability. Please remember that older houses do not meet the same standard as newer houses even though items in both might be performing functions for which they are intended. 11. We do not hold ourselves out to be specialists for any particular item. 12. We are a general real estate inspection company. If we report that an item is not performing its intended function or needs repair, we urge you to have that item, as well as the entire system, examined by a specialist before purchasing the property. 13. We do not give estimates of the cost to repair any item. Repair cost estimates can be furnished upon request for an additional fee of $85.00. 14. If the water is off at the main water shut off valve or the meter location at the time of inspection, Chief Inspection Services at their discretion may or may not activate the water service for inspection. Certain restrictions apply. 15. Chief Inspection Services will perform a complete inspection on one (1) mobilization only. If electric or water is not on at the time of inspection, additional service call charges in the amount of $75.00 will be billed for additional trips to the property. Client is responsible for payment of additional trip charges. Client will be responsible to get reimbursement for addition trip charges from seller, sellers agent or other parties at their discretion if necessary.     Inspection Fee of $XXX.00 was paid by upon completion and prior to issuance of the report.         Date: Client Signature         Date: October 10, 2011 Jeff Clair Chief Inspection Services   3
  • 5. Chief Inspection Services Certified Inspection Report EXTERIOR REPAIR OR REPLACE INTENDED FUNCTION NEEDS IMMEDIATE NOT INSPECTED NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME PERFORMING OF THIS INSPECTION. THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY. X WALL STRUCTURE Type: Masonry Block w/ Wood framed addition X PATIO X FOUNDATION Type: concrete slab X WATER DRAINAGE NA SPRINKLER SYSTEM No. of zones: X EXTERIOR FINISHES Type: Cementicious Coating / cement board siding X WINDOW / DOOR TRIM X DRIVEWAY / PARKING NA GARAGE DOOR NA GARAGE DOOR OPENER COMMENTS / RECOMMENDATIONS – Wood framed addition is non compliant in several areas. Structural damage to framing was observed, water infiltration under the exterior walls and ponding inside was observed, improper electrical and plumbing issues were observed. Recommend the entire rear addition is removed and replaced with proper construction techniques and permitting for safety and effective water control issues. Page. See photos next 4
  • 6. Chief Inspection Services Certified Inspection Report 5
  • 7. Chief Inspection Services Certified Inspection Report ROOF REPAIR OR REPLACE INTENDED FUNCTION NEEDS IMMEDIATE NOT INSPECTED NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME PERFORMING OF THIS INSPECTION. THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY. X ROOF COVERING Type: 3 tab Composition Shingles Roof was inspected via walking on surface X FLASHINGS X GUTTERS / DOWNSPOUTS X FACIA 1 X VENT CAPS X SOFFITS X ROOF FRAMING Type: Pre engineered trusses @ 24” on center Style: Gable 5 – 7 Years ESTIMATED AGE OF ROOF COVERING COMMENTS / RECOMMENDATIONS – Roof covering at low sloped roof surface is at or beyond it’s useful life and should be replaced as soon as practical. Evidence of improper laps were observed on rolled roofing. Flashing at rolled roofing and shingles is improper and should be corrected to prevent roof leaks. Visible roof leaks were observed at rear addition and soffit areas. Gutters and downspouts have failed and water is draining into structure. Recommend repairs are made as necessary to control roof drainage away from structure. See photos next page. 6
  • 8. Chief Inspection Services Certified Inspection Report 7
  • 9. Chief Inspection Services Certified Inspection Report ATTIC INTENDED FUNCTION REPAIR OR REPLACE NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE NEEDS IMMEDIATE NOT INSPECTED OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME PERFORMING OF THIS INSPECTION. THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY. X INSULATION Type: Blown Cellulose R-11 X ROOF INTERIOR Water Stains: None visible X ROOF VENTS Type: Eave, Off ridge X ELECTRICAL BOXES X ROOF FRAMING X EXHAUST VENTS X ATTIC ACCESS COMMENTS / RECOMMENDATIONS – Attic was inspected from opening due to restricted access; attic space over rear addition was not visible. Recommend drywall ceiling is removed at rear addition to provide access for further evaluation of structural wall connections to roof framing. 8
  • 10. Chief Inspection Services Certified Inspection Report DOORS / WINDOWS / INTERIOR REPAIR OR REPLACE INTENDED FUNCTION NEEDS IMMEDIATE NOT INSPECTED NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME PERFORMING OF THIS INSPECTION. THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY. X FRONT ENTRY DOOR X DOOR BELL NA SLIDING DOORS X INTERIOR DOORS Type: Hollow core X WINDOWS / SCREENS Type: Single Hung X CLOSET DOORS X EXTERIOR DOORS X INTERIOR WALLS & CEILINGS Type: Drywall X FLOORING N FIREPLACE A COMMENTS / RECOMMENDATIONS – Exterior doors are rubbing the jambs and wood rot / moisture damage was observed at rear addition. Exterior door at patio area does not open correctly due to sloping floors. Interior walls and floor of rear addition exhibited significant water infiltration as evidenced by ponding water, 100% moisture readings and improper sloping of exterior grades. Peeling paint was observed in 1st bathroom that should be removed and replaced to prevent moisture buildup on interior walls. 9
  • 11. Chief Inspection Services Certified Inspection Report KITCHEN / APPLIANCES REPAIR OR REPLACE INTENDED FUNCTION NEEDS IMMEDIATE NOT INSPECTED NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME PERFORMING OF THIS INSPECTION. THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY. X DISHWASHER Manufacturer: Frigidaire Color: white X RANGE / OVEN Type: Free standing; electric Manufacturer: Frigidaire Color: white X VENTHOOD Type: Recirculating NA DISPOSAL X KITCHEN SINK X CABINETS X RECEPTACLES NA MICROWAVE Manufacturer: Gold Star Color: white X COUNTERTOPS Type: Laminate COMMENTS / RECOMMENDATIONS – Dishwasher is missing the interior components and did not function. Stove burners did not function when tested. Refrigerator is missing freezer parts. Bottom of sink bas cabinet is deteriorated and should be replaced with newer materials due to previous water damage. Countertops are uneven and should be corrected as necessary. 10
  • 12. Chief Inspection Services Certified Inspection Report PLUMBING REPAIR OR REPLACE INTENDED FUNCTION NEEDS IMMEDIATE NOT INSPECTED NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME PERFORMING OF THIS INSPECTION. THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY. X BATH VANITY CABINETS & SINKS X BATH TUBS X SHOWERS X TOILETS X WATER HEATER Age: 2007 Type: electric Size: 40 Gal Manufacturer: Whirlpool X OUTSIDE FAUCETS X FIXTURE SHUT OFF VALVES X WASHER / DRYER CONNECTIONS DRYER HEAT SOURCE: NA DRYER VENTED THROUGH NA: X MAIN WATER SHUT OFF VALVE Location: L Side of house GALVANIZED / SUPPLY PIPING CPVC WATER PRESSURE: 53 PSI Cast iron DRAIN / VENT PIPING COMMENT / RECOMMENDATIONS – Plumbing system is installed improperly at rear addition and rear bathroom as evidenced by unsupported piping, mismatched pipe materials and exposed fittings. Water heater has been on without water inside the tank which can damage the heating elements. Water supply was off at time of inspection and the water meter valve was difficult to operate which prohibited fully inspecting the supply piping. Cast iron drain lines were visible at the main house and should be video inspected to determine actual condition due to the cast iron becoming brittle over time. Vent pipe at roof surface was capped with rubber plug and restricting proper venting of drain system. Galvanized water supply piping was observed in several areas which indicates the system is beyond it’s useful life. Recommend the entire water supply system is replaced. Floor drains at rear patio drained to mysterious location and should be video inspected to determine end of line. See photos next page. 12
  • 13. Chief Inspection Services Certified Inspection Report HEATING / AIR CONDITIONING REPAIR OR REPLACE INTENDED FUNCTION NEEDS IMMEDIATE NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE NOT INSPECTED OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME PERFORMING OF THIS INSPECTION. THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY. Type: Central air & heat Fuel: Electric Manufacturer: Carrier X CONDENSOR / COMPRESSOR (Outside unit) Model: 38CKC036330 Size: 3 TONS Age: 1998 X REFRIGERATION LINES X DISTRIBUTION DUCTS X CONTROLS X BLOWER / FAN X EVAPORATOR COIL (Air handler) Model: FA4ANF036 Size: 3 TONS Age: 1998 X CONDENSATE DRAIN TEMPERATURE CHANGE AT COILS X Supply Temp: 68.7 Return Temp: 74.8 Temp Difference: 61. degrees Normal Temperature Difference should be between 16-21 degrees x AIR FILTER Location: Return grill at bottom of unit Recommend changing the filters every 30 days. COMMENTS / RECOMMENDATIONS – The temperature change during the cooling cycle was below the normal ranges at the time of inspection. HVAC equipment is beyond it’s useful life and should be upgraded with newer, more efficient models. Distribution ducts are deteriorated and not sealed at the connections to the boxes within the attic space. Recommend all grey plastic duct is replaced with new materials. Recommend System is further evaluated and repaired as necessary by a licensed HVAC contractor. 13
  • 14. Chief Inspection Services Certified Inspection Report 14
  • 15. Chief Inspection Services Certified Inspection Report ELECTRICAL REPAIR OR REPLACE INTENDED FUNCTION NEEDS IMMEDIATE NOT INSPECTED NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME PERFORMING OF THIS INSPECTION. THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY. Size: 100 Amps Location: Rear of house Type: Underground X SERVICE ENTRANCE Conductor Type: Aluminum X SWITCHES X INSTALLED FIXTURES X ATTIC ELECTRICAL X MAIN PANEL / DISCONNECT Location: L Side of house X SUB PANEL Location: Garage X BRANCH WIRING Type: NM Cable KITCHEN & BATHROOM GFI OUTLETS X ROOM OUTLETS X EXTERIOR OUTLETS X X EXHAUST FANS X EQUIPMENT DISCONNECTS SMOKE DETECTORS X Recommend all batteries are changed upon occupancy. COMMENTS / RECOMMENDATIONS – Electrical panel is “sizzling” at intermittent times and is beyond it’s useful life. Recommend panel is replaced with a newer, more reliable model. Branch circuit wiring is unsafe at rear addition and needs immediate attention for safety. Kitchen, bathroom and exterior receptacles are not GFI type and should be replaced with GFI type for safety. Recommend entire system is further evaluated by a licensed electrician for safety. 15
  • 16. Chief Inspection Services Certified Inspection Report 16
  • 17. Chief Inspection Services Certified Inspection Report POOL / SPA / SCREENED AREA REPAIR OR REPLACE INTENDED FUNCTION NEEDS IMMEDIATE NOT INSPECTED NOTE: THIS REPORT CANNOT AND DOES NOT REPRESENT THE OPERATION OR CONDITION OF ANY ITEMS AFTER THE DATE AND TIME PERFORMING OF THIS INSPECTION. THIS REPORT IS THE RESULT OF A VISUAL INSPECTION ONLY. X X POOL SURFACE Type: Gunite X X PUMP Type: X X DECKING Type: Concrete NA POOL HEATER Type: Temp. change was not checked due to control panel being locked. NA SCREEN DOORS NA SCREEN ENCLOSURES NA FILTER / SKIMMER NA SPA JETS NA POOL ACCESSORIES COMMENTS / RECOMMENDATIONS – Pool was filled with algae and could not be inspected at this time. Evidence of pool surface cracks were observed above the water line. Recommend pool is drained and professional cleaned by a licensed Pool specialist. Recommend door and window alarms are installed as well as pool safety fence is installed to prohibit unauthorized access to pool area. 17
  • 18.   Chief Inspection Services Certified Inspection Report   HOME INSPECTION REPORT SUMMARY PAGE   Client Name: Mr. & Mrs. Homebuyer Property Address: 1567 Yourstreet, Hometown, FL 32725 Date and Time of Inspection: October 10, 2011 @ 11:00am   The items noted below were found to be inoperable, non-functioning or defective at the time our inspection was conducted. We urge you to have these items, as well as the entire system repaired, replaced or further evaluated by a licensed professional prior to closing.   Exterior Wood framed addition is non compliant in several areas. Structural damage to framing was observed, water infiltration under the exterior walls and ponding inside was observed, improper electrical and plumbing issues were observed. Recommend the entire rear addition is removed and replaced with proper construction techniques and permitting for safety and effective water control issues. Page.   Roof Roof covering at low sloped roof surface is at or beyond it’s useful life and should be replaced as soon as practical. Evidence of improper laps were observed on rolled roofing. Flashing at rolled roofing and shingles is improper and should be corrected to prevent roof leaks. Visible roof leaks were observed at rear addition and soffit areas. Gutters and downspouts have failed and water is draining into structure. Recommend repairs are made as necessary to control roof drainage away from structure.   Attic Attic was inspected from opening due to restricted access; attic space over rear addition was not visible. Recommend drywall ceiling is removed at rear addition to provide access for further evaluation of structural wall connections to roof framing.   Doors/Windows/Interior Exterior doors are rubbing the jambs and wood rot / moisture damage was observed at rear addition. Exterior door at patio area does not open correctly due to sloping floors. Interior walls and floor of rear addition exhibited significant water infiltration as evidenced by ponding water, 100% moisture readings and improper sloping of exterior grades. Peeling paint was observed in 1st bathroom that should be removed and replaced to prevent moisture buildup on interior walls.   Kitchen / Appliances Dishwasher is missing the interior components and did not function. Stove burners did not function when tested. Refrigerator is missing freezer parts. Bottom of sink bas cabinet is deteriorated and should be replaced with newer materials due to previous water damage. Countertops are uneven and should be corrected as necessary.   18
  • 19.   Chief Inspection Services Certified Inspection Report   HOME INSPECTION REPORT SUMMARY PAGE Cont’d.   Client Name: Mr. & Mrs. Homebuyer Property Address: 1567 Yourstreet, Hometown, FL 32725 Date and Time of Inspection: October 10, 2011 @ 11:00am   The items noted below were found to be inoperable, non-functioning or defective at the time our inspection was conducted. We urge you to have these items, as well as the entire system repaired, replaced or further evaluated by a licensed professional prior to closing.   Plumbing Plumbing system is installed improperly at rear addition and rear bathroom as evidenced by unsupported piping, mismatched pipe materials and exposed fittings. Water heater has been on without water inside the tank which can damage the heating elements. Water supply was off at time of inspection and the water meter valve was difficult to operate which prohibited fully inspecting the supply piping. Cast iron drain lines were visible at the main house and should be video inspected to determine actual condition due to the cast iron becoming brittle over time. Vent pipe at roof surface was capped with rubber plug and restricting proper venting of drain system. Galvanized water supply piping was observed in several areas which indicates the system is beyond it’s useful life. Recommend the entire water supply system is replaced. Floor drains at rear patio drained to mysterious location and should be video inspected to determine end of line.   HVAC The temperature change during the cooling cycle was below the normal ranges at the time of inspection. HVAC equipment is beyond it’s useful life and should be upgraded with newer, more efficient models. Distribution ducts are deteriorated and not sealed at the connections to the boxes within the attic space. Recommend all grey plastic duct is replaced with new materials. Recommend System is further evaluated and repaired as necessary by a licensed HVAC contractor.   Electrical Electrical panel is “sizzling” at intermittent times and is beyond it’s useful life. Recommend panel is replaced with a newer, more reliable model. Branch circuit wiring is unsafe at rear addition and needs immediate attention for safety. Kitchen, bathroom and exterior receptacles are not GFI type and should be replaced with GFI type for safety. Recommend entire system is further evaluated by a licensed electrician for safety.   Pool / Screen Enclosure Pool was filled with algae and could not be inspected at this time. Evidence of pool surface cracks were observed above the water line. Recommend pool is drained and professional cleaned by a licensed Pool specialist. Recommend door and window alarms are installed as well as pool safety fence is installed to prohibit unauthorized access to pool area.   Please contact Jeff Clair at 407-383-7241 if you have any questions regarding this inspection report. Thank you for choosing Chief Inspection Services.           Jeff Clair RPI-0437 State Certified Home Inspector #725   19