Soft Power Factor Modification Using Static
VAR Compensator on Dynamic Load
Amam Hossain Bagdadee
Asian Institute of Technology, Thailand
Energy Field of Study
Abstract: A good power quality at a system can optimize the efficiency of electrical energy utilization.
Comparison of active power and apparent power will produce a power factor (COS ø).Capacitors bank can
maintain optimum power factor with compensating some reactive power to the system. Static VAR
Compensator (SVC) is generally composed of a conventional capacitor bank in parallel with the load contactor
switch. This leads to a very large inrush current to the capacitor which will resulting damage to the
contactor switches and also capacitors. To reduce inrush current, thyristor is used as a replacement of
contactor switch. Switch can be set by adjusting the firing angle of thyristor. Power factor improvement consists
of a voltage sensor, current sensor, zero crossing detector, thyristor driver and the capacitor bank. The existing
load on the system consists of induction motor 125W, rectifier with load of series of incandescent lamp with
ballasts 85W and fluorescent lamp 20W.Cos phi variation of the load is 0.49 (lag), 0.99 (lag), 0.92 (lag) and 0.62
(lag) when all the loads connect to the system. Through the calculation, the value of capacitor that can
compensate the reactive power to the system is 5.12 µF, 2.71 µF, 2.41 µF and 9.55µF. The capacitor
installation obtain good response because it can increase the cos phi of system to 0.99 (lag) and the current
consumption of the system is smaller than the pre-installation of capacitors, which can reduce the line system
current up to 30% of the system current.
Keywords: Power quality, Power factor, Inrush current, Soft switches.
I. INTRODUCTION
Good power quality in a system can optimize the maximum power demand and efficiency of utilization of electrical
energy. One way to do is to use capacitor banks to maintain the power factor. Types of loads that affect the quality of
electric power is inductive loads and non-linear loads such as converters and inverters for motor drives , welding
machines , arc furnaces , computers, air conditioners , TVs , fluorescent lamp and others. The use of non- linear inductive
load and power factor is exacerbating thereby increasing the power loss. Disturbance in the form of voltage unbalance is
caused by unbalanced load distribution.
Therefore, to maintain good power quality Static VAR Compensator necessary equipment (SVC) is used to compensate
reactive power. Conventional SVC generally consists of a bank of capacitors connected in parallel to the load through an
electromechanical switch contactor switch (EMS) . This leads to a very large inrush current to the capacitor itself. This
happened repeatedly and will cause damage to the contactor switches and capacitors
II. METHOD
Work steps of the implementation of this final project are as follows:
2.1. Literature Study
Study the literature on the concept of power quality, switching solid state relay (SSR), power electronics and other
material relevant to the discussion of this final project.
International Journal of Novel Research in Electrical and Mechanical Engineering
Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com
Page | 24
Novelty Journals
2.2. Simulation System
At the end of the project, using as a media PSIM simulation program.
2.3. System Design
At the end of the project will be improved using a soft switch power factor at SVC for dynamic loads. Block diagram of
the whole system is:
2.4 Integration and Testing System
To find out all the systems that have been designed in accordance with the expected result of integration of each device
III. BASIC THEORY
3.1. Use of Power Triangle and Table Cos φ Power factor improvement for Analysis
Figure 1: Power triangle
The sum of active power and reactive power generating real power
22
QPS 
Where: P = active power (kW)
S = apparent power (KVA)
Q = reactive power (KVAR)
Power factor:
P = VI COS φ
(Active Power) / (Power Pseudo) = P / S = COS φ
Reactive power compensator:
Description:
P: Power on (watts)
Q: Compensator Reactive Power (VAR)
θ: Angle before repaired
φ: Angle after being repaired
Inrush Current
Inrush current is instantaneous inrush current with a value several times the normal flow arising on the electrical
equipment at the beginning connected with a voltage source. This flow can occur in electrical equipment, among others,
the incandescent light bulb, AC electric motors, power converters and transformers. In rush, current wave is similar to a
sinusoidal wave but not symmetrical. Here is an example of inrush current curve:
International Journal of Novel Research in Electrical and Mechanical Engineering
Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com
Page | 25
Novelty Journals
Figure 2: Flow curves Inrush
In a capacitor bank switching , inrush current formulation obtained as follows :
î = ( √ 2 × Un ) / √ ( X_C × X_L )
Where : î : Inrush currents ( Inrush current)
Un : Voltage Line – line
XC : reactance capacitive
XL : inductive reactance
Inrush current at switching on the capacitor can reach 20 times the normal current rating of the capacitor . This happens
because at the time of the switching frequency over a very large capacitor banks that capacitive reactance becomes very
small, according to the following formula:
X_C = 1 / ( 2 × π × f × C )
Thus the current through the capacitor bank will be very large .Planning System
The design of the overall system can be described as the block diagram below:
Sumber energi
listrik 1 fasa
Sensor
tegangan
Sensor
Arus
Zero
Crossing
Detector
Mikrokontroller
Display
Soft Switch
Bank Kapasitor
Static Var Compensator
Multi
Beban
Auto
Switch
Driver SCR
(TCA785)
Figure 3: System Design
Table 1. Data for Simulation
1-Phase Induction Motor
V 220 V
I 1.1 A
PF 0.26 Lag
74,930
Rectifier
load Incandescent lamps of 100 W
Ballast 40 W, PF = 0.54
TL lamps
P 40 Watt fluorescent lamp
International Journal of Novel Research in Electrical and Mechanical Engineering
Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com
Page | 26
Novelty Journals
1. Planning a soft switch with SCR
Soft switches using SCR fueled by the microcontroller to improve the power factor and eliminate inrush currents.
The means used to eliminate inrush current when the SCR is lit at the time of peak voltage (dv / dt = 0).
SCR = 0 voltage (Vth = 0), is reached when:
Vth = Vs - Vc as Vc = - Vm
Vth = Vm Sin ωt + Vm
= Vm (1 + Sin ωt)
Thus, Sin ωt = -1  ωt = Sin-1 (-1)
= 270o
Figure 4: Soft Switch circuit SCR
Calculation of capacitor banks needed the motor load can be determined via equation 3.9, 3:10 equations and equation
3.11. To calculate the value of the capacitor bank must be specified PF value of the target, thus it can be seen that the
value of the capacitor banks as required. If the supply of reactive power of the capacitor bank is too large it will result in
cos θ is negative and the current signal will precede the voltage signal. If the supply of reactive power of the capacitor
bank is too small then it will lead to improvement of the power factor is not maximal.
From the simulation results, it can be sorted lowest that real power is 1 only when the load is located on the system, and
the highest is when the second load is on the system with the value of each parameter listed in the following table.
Table 2. Simulation Results before Installation of Capacitors
No load V P I cos phi remark
1
TL lamps
220 35 0.29 0.922 lag
2
Rectifier with load Lamp +
Ballast
220 130 1.22 0.49 lag
3 Induction motors 220 85 0.39 0.99 lag
4 combination 220 236 1.72 0.62 lag
Further more, the calculation of the value of the capacitor to achieve Cos θ = 1 is as follows:
International Journal of Novel Research in Electrical and Mechanical Engineering
Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com
Page | 27
Novelty Journals
PF target = 1  θ2 = 00
,
1. Reactive power to be injected into the system
From the results of these calculations, it can be sorted that reactive power to be injected is lowest when the load 2 are
located on the system, and the highest is when the second load is on the system.
Determination of capacitor step will be installed, will be adapted to the conditions in which was done by determining the
lowest Q, and then determined the difference between each value of Q to Q supreme. When the Load 2 are working, then
the required reactive power requirement is 36.596 VAR then step 1 capacitor bank is worth as needed.
Furthermore, when the Load 1 only the work, it would require additional reactive power to be injected at 145.237 VAR,
so step 1 and 2 lit. And when the second load of work together, it is necessary to return additional reactive power at
41.232 VAR, under these conditions, the third step should be lit to meet the target CO phi.
2. Capacitor value
π
π
π
IV. TESTING SYSTEM
System testing performed in this study based on the design that has been made.
4.1. Voltage sensor
The results of the sensor voltage using a voltage divider circuit in line with expectations. The result of the voltage sensor
is used to detect the phase difference at the zero crossing circuit.
International Journal of Novel Research in Electrical and Mechanical Engineering
Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com
Page | 28
Novelty Journals
Table 3. Voltage sensor test data
From the table it can be seen that the output voltage of the sensor output either AC or DC voltage output theory
approach.
4.2. ACS current sensor 712
Of ACS application circuit IC 712, the result output of AC voltage without a DC component. The resulting output signal
IC ACS 712 is an inverting of the input signal. So, we need inverting amplifier output signal that is equal to the input
signal IC ACS 712.
ACS trial data table:
Table 4. ACS current sensor experimental data 712
Because, the output voltage signal of the IC 712 ACS is inverting the circuit using inverting amplifier with a gain of 20
times. So in the calculation of Rf and Ri as follows:
........... ( ) ................(3.5)
If the gain 20 times, then
I
Thus, form the equation 3.5:
No. Arus AC [Aac] Vout-AC (mV) Vout-rec (V)
1 0.75 93 1.87
2 1 114 1.89
3 1.25 135 1.914
4 1.5 160 1.94
5 1.75 175 1.97
6 2 206 1.99
7 2.5 257 2.04
8 3 295 2.09
9 3.5 342 2.14
10 4 390 2.195
11 4.5 440 2.25
12 5 488 2.32
No. V input-ac
Vout-ac [V] Vout-rec [V] % Error
Vout-recpractice Theory practice Theory
1 100 V 1.566 1.363 1.305 1.23 6.1
2 120 V 1.806 1.629 1.576 1.47 7.2
3 140 V 2.18 1.909 1.827 1.72 6.2
4 160 V 2.498 2.181 2.025 1.96 3.3
5 180 V 2.806 2.454 2.315
[1]
2.21
4.7
6 200 V 3.12 2.727 2.486 2.46 1.1
7 220 V 3.42 3 2.88 2.7 1.6
International Journal of Novel Research in Electrical and Mechanical Engineering
Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com
Page | 29
Novelty Journals
First set R1=1k, then:


A variable resistor is Rf. The value used is 20K  order to produce a gain of 20 times.
4.3. The circuit Zero Crossing and Phase Detector (Detector phase)
The circuit zero crossing detector and a continuation phase current sensors and voltage sensors . The resulting sensor
output signal voltage and current sensors, and then processed by the zero crossing circuit and generates 2 -step signal
which has a phase difference equal to the ac voltage and current signals. Then processed by the IC - XOR and generate
signals that inform the data step phase difference between voltage and current .IC - XOR 2 is used as the summing of the
input signal that is current and voltage signals that are output from the zero crossing that has a different phase, with the
work as follows:
1. If both inputs same logic would then output is logic "0"
2. If both logic inputs are not equal then the output would be worth a logic " 1 " .Square wave signal coming out of the
current and voltage zero crossing comparator circuit to get into compared to using IC 74LS86 TTL XOR to know the
difference between the phase angle of the voltage and current flowing in the load.
Figure 5: wave voltage sensor and current sensor
Figure 6: Wave output voltage divider voltage sensor and current sensor
International Journal of Novel Research in Electrical and Mechanical Engineering
Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com
Page | 30
Novelty Journals
Figure 7: wave output of the EX-OR 74hc86 (phase detector parameters)
4.4. Testing System
To test the results of this system, obtained the following results:
Tabel 5. Validation System Without Capacitor With Meter
No load V P I cos phi
% Error
Vout-rec
1
TL lamps
220 35 0.29 0.922 2%
2
Rectifier with load Lamp +
Ballast
220 130 1.22 0.49 2.1%
3 Pump motors 220 85 0.39 0.99 1.2%
4
All expenses
1,2,3
220 236 1.72 0.62 11.2%
In table 5 of the test system without capacitor can be seen that for COS phi reading on LCD graphics readout COS phi
compared with analog meter has a high % error. On the third reading of the COS phi currently installed load is by 11.29
% when all load is attached. While at C0S phi readings on the percent error % lower reaches 1:01 .Error reading on the
LCD due to the number of works on frequency control circuit and is also caused due to poor materials /components used
in the circuit. Here are the results of testing the system before and after installation of capacitor banks, which, seen an
increase in the value of the COS phi to 0.49 lag to 0.99 lag pump motor after installation of 5.12 µF capacitor.
Similarly, when the three loads connected directly together, which are the initial COS phi 0.62 to 0.99 lag increases with
the addition of the 9:55 µF. In terms of the current line in the system, there is a reduction in current consumption due to
the injection line from the capacitor bank reactive VAR. Seemingly that be saran a flow when the pump motor is initially
to 0.82 A 1:22 A similarly when the combined load of 1.72 A to 0.94 A. rectifier load current on the line is not too
powerful due COS phi initial value system that has both is 0.99 and 0.92 for fluorescent lamp load.
Table 6. System Testing Results before and after the installation of capacitor bank
No Load
V
(V)
I
(A)
Cos phi P(Watt) S(VA) C(F)
1 Pump Motor
=222 1.22 0.49 lag 135
271 5,12
220 0.82 0.99 lag 179
2 TL Lamp
222 0.29 0.92 lag 35
62 2,71
220 0.28 0.99 lag 61
3
Rectifier burden
Lamp + Ballast
222 0.30 0.99 lag 85
68.2 2,41
220 0.31 0.99 lag 84.94
4
All expenses
1,2,3
222 1.72 0.62 lag 237
207 9.55
220 0,94 0.99 lag 218
International Journal of Novel Research in Electrical and Mechanical Engineering
Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com
Page | 31
Novelty Journals
V. CONCLUSION
From the experimental results it can be concluded as follows:
1. In testing the motor load, COS phi can improve from 00:49 (lag) before mounting the capacitor, be COS phi 0.99 (lag)
after the installation of capacitors and minimize current consumption from 1:22 A to 0.82 A.
2. In testing with TL lamps and rectifier load, COS phi is basically a system that is already well 0.92 (lag) and 0.99 (lag).
After installation of the capacitor, COS phi be 0.99 (lag).
3. Testing the system with the entire load connected to the system, capacitor banks can increase the COS phi of 0.62 (lag)
to 0.99 (lag) and can minimize current consumption of 1.72 A to 0.94 A.
4. Linear sensor readings are needed to get a quick response sat COS phi changes to the system.
REFERENCES
[1] R. Grünbaum, M. Noroozian and B. Thorvaldsson, “FACTS – Powerful Systems for Flexible Power
Transmission”, ABB Review, May 1999, pp. 4-17.
[2] Neil H. Woodley, “Field Experience with Dynamic Voltage Restorer Systems”, IEEE Power Engineering Society
Winter Meeting 2000, Singapore.
[3] Saha, Tapan K. and Nguyen, P. T. (2004) Dynamic Voltage Restorer Against Balanced and Unbalanced Voltage
Sags: Modelling and Simulation, IEEE Power Engineering Society General Meeting, 6-10 June, 2004, Denver,
Colorado, USA.
[4] H. Okayama, T. Fujii, S. Tamai, S. Jochi, M. Takeda, R. Hellested, G. Reed, “Application and Development
Concepts for a New Transformer-less FACTS Device: the Multimode Static Series Compensator (MSSC)”,
Proceedings of the EEE PES, Conference & Expo, Dallas, TX, September 2003.
[5] X. Wei, J. H. Chow, B. Fardanesh, and Abdel-Aty Edris, “A Common Modeling Framework of Voltage-Sourced
Converters for Load Flow, Sensitivity, and Dispatch Analysis”, IEEE Transactions on Power Systems, Vol. 19, Nº.
2, May 2004, pp. 934-941.
[6] Xuan Wei, Joe H. Chow, B. Fardanesh, and Abdel-Aty Edris, “A Dispatch Strategy for an Interline Power Flow
Controller Operating At Rated Capacity”, PSCE 2004, 2004 IEEE/PES Power Systems Conference and Exposition,
Oct. 10-13, 2004, New York, NY, USA.
[7] [2] Cesar A. Luongo, “Superconducting Storage Systems: An Overview,” IEEE Trans. on Magnetics., Vol. 32,
No.4, 1996, pp. 2214-2223.
[8] Matthew J. Superczynski, “Analysis of the Power Conditioning System for a Superconducting Magnetic Energy
Storage Unit”, Master Thesis, Virginia Polytechnic Institute and State University, August 2000.
[9] “Reassessment of Superconducting Magnetic Energy Storage (SMES) Transmission System Benefits”, Report
number 01006795, March 2002.
[10] Issarachai Ngamroo (2005) "Robust Frequency Stabilisation By Coordinated Superconducting Magnetic Energy
Storage With Static Synchronous Series Compensator", International Journal of Emerging Electric Power Systems:
Vol. 3: No. 1, August 2005.
.

More Related Content

What's hot

Power control in power systems
Power control in power systemsPower control in power systems
Power control in power systemsAbhinash Yadav
 
Unit 2 Reactive Power Management
Unit 2 Reactive Power ManagementUnit 2 Reactive Power Management
Unit 2 Reactive Power ManagementSANTOSH GADEKAR
 
Control of Active And reactive power flow in transmission line and power Osci...
Control of Active And reactive power flow in transmission line and power Osci...Control of Active And reactive power flow in transmission line and power Osci...
Control of Active And reactive power flow in transmission line and power Osci...AM Publications
 
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeed
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeedAnalyses of reactive power compensation schemes in MV/LV Networks with RE infeed
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeedAushiq Ali Memon
 
static series synchronus compensator
static series synchronus compensatorstatic series synchronus compensator
static series synchronus compensatorbhupendra kumar
 
Symmetrical Fault Analysis
Symmetrical Fault AnalysisSymmetrical Fault Analysis
Symmetrical Fault AnalysisSANTOSH GADEKAR
 
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLERPOWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLERJournal For Research
 
A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...
A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...
A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...IJMER
 
Power Factor
Power FactorPower Factor
Power FactorTim Cohen
 
Power factor introduction and its correction final
Power factor introduction and its correction final Power factor introduction and its correction final
Power factor introduction and its correction final manpreetsingh1076
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlSANTOSH GADEKAR
 
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...IOSR Journals
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportTheory to Practical
 
Automatic Power Factor Correction using Microcontroller 8051
Automatic Power Factor Correction using Microcontroller 8051Automatic Power Factor Correction using Microcontroller 8051
Automatic Power Factor Correction using Microcontroller 8051Neehar NLN
 
Reactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomReactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomHussain Ali
 
129 venezuelan static var compensator
129 venezuelan static var compensator129 venezuelan static var compensator
129 venezuelan static var compensatorwmelis
 
APFC project presentation
APFC project presentationAPFC project presentation
APFC project presentationkartickmp613
 

What's hot (20)

Power control in power systems
Power control in power systemsPower control in power systems
Power control in power systems
 
Unit 2 Reactive Power Management
Unit 2 Reactive Power ManagementUnit 2 Reactive Power Management
Unit 2 Reactive Power Management
 
Control of Active And reactive power flow in transmission line and power Osci...
Control of Active And reactive power flow in transmission line and power Osci...Control of Active And reactive power flow in transmission line and power Osci...
Control of Active And reactive power flow in transmission line and power Osci...
 
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeed
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeedAnalyses of reactive power compensation schemes in MV/LV Networks with RE infeed
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeed
 
static series synchronus compensator
static series synchronus compensatorstatic series synchronus compensator
static series synchronus compensator
 
Symmetrical Fault Analysis
Symmetrical Fault AnalysisSymmetrical Fault Analysis
Symmetrical Fault Analysis
 
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLERPOWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
 
Unit 3 FACTS Technology
Unit 3 FACTS TechnologyUnit 3 FACTS Technology
Unit 3 FACTS Technology
 
A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...
A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...
A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
Power Factor
Power FactorPower Factor
Power Factor
 
Power factor introduction and its correction final
Power factor introduction and its correction final Power factor introduction and its correction final
Power factor introduction and its correction final
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation Control
 
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System Report
 
Reactive power management in india
Reactive power  management in indiaReactive power  management in india
Reactive power management in india
 
Automatic Power Factor Correction using Microcontroller 8051
Automatic Power Factor Correction using Microcontroller 8051Automatic Power Factor Correction using Microcontroller 8051
Automatic Power Factor Correction using Microcontroller 8051
 
Reactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomReactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcom
 
129 venezuelan static var compensator
129 venezuelan static var compensator129 venezuelan static var compensator
129 venezuelan static var compensator
 
APFC project presentation
APFC project presentationAPFC project presentation
APFC project presentation
 

Viewers also liked

A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...IOSR Journals
 
Power factor correction
Power factor correctionPower factor correction
Power factor correctionslmnsvn
 
Electrical machines
Electrical machinesElectrical machines
Electrical machinesPrabhu R
 
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...Staco Energy
 
The Best Study Tips Revealed
The Best Study Tips RevealedThe Best Study Tips Revealed
The Best Study Tips RevealedLinkedIn
 
Seminar on all electrical injection moulding machine main
Seminar on all electrical injection moulding machine mainSeminar on all electrical injection moulding machine main
Seminar on all electrical injection moulding machine mainanymona1991
 
Electric machine
Electric machineElectric machine
Electric machineashok261084
 
FIRING ANGLE SVC MODEL FOR ANALYZING THE PERFORMANCE OF TRANSMISSION NETWORK ...
FIRING ANGLE SVC MODEL FOR ANALYZING THE PERFORMANCE OF TRANSMISSION NETWORK ...FIRING ANGLE SVC MODEL FOR ANALYZING THE PERFORMANCE OF TRANSMISSION NETWORK ...
FIRING ANGLE SVC MODEL FOR ANALYZING THE PERFORMANCE OF TRANSMISSION NETWORK ...IAEME Publication
 
92 electrical interview questions and answers
92 electrical interview questions and answers92 electrical interview questions and answers
92 electrical interview questions and answersElectricalCareer66
 

Viewers also liked (14)

A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
 
Basic ML
Basic MLBasic ML
Basic ML
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
Electrical machines
Electrical machinesElectrical machines
Electrical machines
 
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
 
Mohsin rana
Mohsin ranaMohsin rana
Mohsin rana
 
The Best Study Tips Revealed
The Best Study Tips RevealedThe Best Study Tips Revealed
The Best Study Tips Revealed
 
Chapter 4 dc machine [autosaved]
Chapter 4   dc machine [autosaved]Chapter 4   dc machine [autosaved]
Chapter 4 dc machine [autosaved]
 
Motors
MotorsMotors
Motors
 
Seminar on all electrical injection moulding machine main
Seminar on all electrical injection moulding machine mainSeminar on all electrical injection moulding machine main
Seminar on all electrical injection moulding machine main
 
Electric machine
Electric machineElectric machine
Electric machine
 
Power Electronics
Power ElectronicsPower Electronics
Power Electronics
 
FIRING ANGLE SVC MODEL FOR ANALYZING THE PERFORMANCE OF TRANSMISSION NETWORK ...
FIRING ANGLE SVC MODEL FOR ANALYZING THE PERFORMANCE OF TRANSMISSION NETWORK ...FIRING ANGLE SVC MODEL FOR ANALYZING THE PERFORMANCE OF TRANSMISSION NETWORK ...
FIRING ANGLE SVC MODEL FOR ANALYZING THE PERFORMANCE OF TRANSMISSION NETWORK ...
 
92 electrical interview questions and answers
92 electrical interview questions and answers92 electrical interview questions and answers
92 electrical interview questions and answers
 

Similar to Soft power factor modification using static

Project on STATCOM
Project on STATCOMProject on STATCOM
Project on STATCOMSutirtha Das
 
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Areaijceronline
 
A Simulink Model for Damping Power System Oscillations Using Fact Devices
A Simulink Model for Damping Power System Oscillations Using Fact DevicesA Simulink Model for Damping Power System Oscillations Using Fact Devices
A Simulink Model for Damping Power System Oscillations Using Fact DevicesIOSR Journals
 
Augmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
Augmentation of Real & Reactive Power in Grid by Unified Power Flow ControllerAugmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
Augmentation of Real & Reactive Power in Grid by Unified Power Flow ControllerIJERA Editor
 
Improvement of Power Quality by using Injection Super Capacitor UPQC for BLDC...
Improvement of Power Quality by using Injection Super Capacitor UPQC for BLDC...Improvement of Power Quality by using Injection Super Capacitor UPQC for BLDC...
Improvement of Power Quality by using Injection Super Capacitor UPQC for BLDC...IJMTST Journal
 
Improved dynamic response of dstatcom using genetic algorithm
Improved dynamic response of dstatcom using genetic algorithmImproved dynamic response of dstatcom using genetic algorithm
Improved dynamic response of dstatcom using genetic algorithmAlexander Decker
 
COMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWERCOMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWERST Chowhury
 
The International Journal of Engineering and Science (IJES)
The International Journal of Engineering and Science (IJES)The International Journal of Engineering and Science (IJES)
The International Journal of Engineering and Science (IJES)theijes
 
1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv system1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv systemEditorJST
 

Similar to Soft power factor modification using static (20)

Thyristor switched capacitor
Thyristor switched capacitorThyristor switched capacitor
Thyristor switched capacitor
 
Project on STATCOM
Project on STATCOMProject on STATCOM
Project on STATCOM
 
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
 
A Simulink Model for Damping Power System Oscillations Using Fact Devices
A Simulink Model for Damping Power System Oscillations Using Fact DevicesA Simulink Model for Damping Power System Oscillations Using Fact Devices
A Simulink Model for Damping Power System Oscillations Using Fact Devices
 
Augmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
Augmentation of Real & Reactive Power in Grid by Unified Power Flow ControllerAugmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
Augmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
 
Performance Analysis of FC-TCR
Performance Analysis of FC-TCRPerformance Analysis of FC-TCR
Performance Analysis of FC-TCR
 
Apfc project 2016 17
Apfc project 2016 17Apfc project 2016 17
Apfc project 2016 17
 
Computer Application in Power system: Chapter two - load flow analysis
Computer Application in Power system: Chapter two - load flow analysisComputer Application in Power system: Chapter two - load flow analysis
Computer Application in Power system: Chapter two - load flow analysis
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Improvement of Power Quality by using Injection Super Capacitor UPQC for BLDC...
Improvement of Power Quality by using Injection Super Capacitor UPQC for BLDC...Improvement of Power Quality by using Injection Super Capacitor UPQC for BLDC...
Improvement of Power Quality by using Injection Super Capacitor UPQC for BLDC...
 
Exp6
Exp6Exp6
Exp6
 
[IJET-V2I3P17] Authors: R.C.Rohini, G.Srividhya
[IJET-V2I3P17] Authors: R.C.Rohini, G.Srividhya[IJET-V2I3P17] Authors: R.C.Rohini, G.Srividhya
[IJET-V2I3P17] Authors: R.C.Rohini, G.Srividhya
 
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
 
Improved dynamic response of dstatcom using genetic algorithm
Improved dynamic response of dstatcom using genetic algorithmImproved dynamic response of dstatcom using genetic algorithm
Improved dynamic response of dstatcom using genetic algorithm
 
COMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWERCOMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWER
 
G046033742
G046033742G046033742
G046033742
 
The International Journal of Engineering and Science (IJES)
The International Journal of Engineering and Science (IJES)The International Journal of Engineering and Science (IJES)
The International Journal of Engineering and Science (IJES)
 
1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv system1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv system
 
Bc4102392396
Bc4102392396Bc4102392396
Bc4102392396
 
EDS Unit 5.pptx
EDS Unit 5.pptxEDS Unit 5.pptx
EDS Unit 5.pptx
 

Recently uploaded

CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLManishPatel169454
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueBhangaleSonal
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Standamitlee9823
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
 

Recently uploaded (20)

CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 

Soft power factor modification using static

  • 1. International Journal of Novel Research in Electrical and Mechanical Engineering Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com Page | 23 Novelty Journals Soft Power Factor Modification Using Static VAR Compensator on Dynamic Load Amam Hossain Bagdadee Asian Institute of Technology, Thailand Energy Field of Study Abstract: A good power quality at a system can optimize the efficiency of electrical energy utilization. Comparison of active power and apparent power will produce a power factor (COS ø).Capacitors bank can maintain optimum power factor with compensating some reactive power to the system. Static VAR Compensator (SVC) is generally composed of a conventional capacitor bank in parallel with the load contactor switch. This leads to a very large inrush current to the capacitor which will resulting damage to the contactor switches and also capacitors. To reduce inrush current, thyristor is used as a replacement of contactor switch. Switch can be set by adjusting the firing angle of thyristor. Power factor improvement consists of a voltage sensor, current sensor, zero crossing detector, thyristor driver and the capacitor bank. The existing load on the system consists of induction motor 125W, rectifier with load of series of incandescent lamp with ballasts 85W and fluorescent lamp 20W.Cos phi variation of the load is 0.49 (lag), 0.99 (lag), 0.92 (lag) and 0.62 (lag) when all the loads connect to the system. Through the calculation, the value of capacitor that can compensate the reactive power to the system is 5.12 µF, 2.71 µF, 2.41 µF and 9.55µF. The capacitor installation obtain good response because it can increase the cos phi of system to 0.99 (lag) and the current consumption of the system is smaller than the pre-installation of capacitors, which can reduce the line system current up to 30% of the system current. Keywords: Power quality, Power factor, Inrush current, Soft switches. I. INTRODUCTION Good power quality in a system can optimize the maximum power demand and efficiency of utilization of electrical energy. One way to do is to use capacitor banks to maintain the power factor. Types of loads that affect the quality of electric power is inductive loads and non-linear loads such as converters and inverters for motor drives , welding machines , arc furnaces , computers, air conditioners , TVs , fluorescent lamp and others. The use of non- linear inductive load and power factor is exacerbating thereby increasing the power loss. Disturbance in the form of voltage unbalance is caused by unbalanced load distribution. Therefore, to maintain good power quality Static VAR Compensator necessary equipment (SVC) is used to compensate reactive power. Conventional SVC generally consists of a bank of capacitors connected in parallel to the load through an electromechanical switch contactor switch (EMS) . This leads to a very large inrush current to the capacitor itself. This happened repeatedly and will cause damage to the contactor switches and capacitors II. METHOD Work steps of the implementation of this final project are as follows: 2.1. Literature Study Study the literature on the concept of power quality, switching solid state relay (SSR), power electronics and other material relevant to the discussion of this final project.
  • 2. International Journal of Novel Research in Electrical and Mechanical Engineering Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com Page | 24 Novelty Journals 2.2. Simulation System At the end of the project, using as a media PSIM simulation program. 2.3. System Design At the end of the project will be improved using a soft switch power factor at SVC for dynamic loads. Block diagram of the whole system is: 2.4 Integration and Testing System To find out all the systems that have been designed in accordance with the expected result of integration of each device III. BASIC THEORY 3.1. Use of Power Triangle and Table Cos φ Power factor improvement for Analysis Figure 1: Power triangle The sum of active power and reactive power generating real power 22 QPS  Where: P = active power (kW) S = apparent power (KVA) Q = reactive power (KVAR) Power factor: P = VI COS φ (Active Power) / (Power Pseudo) = P / S = COS φ Reactive power compensator: Description: P: Power on (watts) Q: Compensator Reactive Power (VAR) θ: Angle before repaired φ: Angle after being repaired Inrush Current Inrush current is instantaneous inrush current with a value several times the normal flow arising on the electrical equipment at the beginning connected with a voltage source. This flow can occur in electrical equipment, among others, the incandescent light bulb, AC electric motors, power converters and transformers. In rush, current wave is similar to a sinusoidal wave but not symmetrical. Here is an example of inrush current curve:
  • 3. International Journal of Novel Research in Electrical and Mechanical Engineering Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com Page | 25 Novelty Journals Figure 2: Flow curves Inrush In a capacitor bank switching , inrush current formulation obtained as follows : î = ( √ 2 × Un ) / √ ( X_C × X_L ) Where : î : Inrush currents ( Inrush current) Un : Voltage Line – line XC : reactance capacitive XL : inductive reactance Inrush current at switching on the capacitor can reach 20 times the normal current rating of the capacitor . This happens because at the time of the switching frequency over a very large capacitor banks that capacitive reactance becomes very small, according to the following formula: X_C = 1 / ( 2 × π × f × C ) Thus the current through the capacitor bank will be very large .Planning System The design of the overall system can be described as the block diagram below: Sumber energi listrik 1 fasa Sensor tegangan Sensor Arus Zero Crossing Detector Mikrokontroller Display Soft Switch Bank Kapasitor Static Var Compensator Multi Beban Auto Switch Driver SCR (TCA785) Figure 3: System Design Table 1. Data for Simulation 1-Phase Induction Motor V 220 V I 1.1 A PF 0.26 Lag 74,930 Rectifier load Incandescent lamps of 100 W Ballast 40 W, PF = 0.54 TL lamps P 40 Watt fluorescent lamp
  • 4. International Journal of Novel Research in Electrical and Mechanical Engineering Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com Page | 26 Novelty Journals 1. Planning a soft switch with SCR Soft switches using SCR fueled by the microcontroller to improve the power factor and eliminate inrush currents. The means used to eliminate inrush current when the SCR is lit at the time of peak voltage (dv / dt = 0). SCR = 0 voltage (Vth = 0), is reached when: Vth = Vs - Vc as Vc = - Vm Vth = Vm Sin ωt + Vm = Vm (1 + Sin ωt) Thus, Sin ωt = -1  ωt = Sin-1 (-1) = 270o Figure 4: Soft Switch circuit SCR Calculation of capacitor banks needed the motor load can be determined via equation 3.9, 3:10 equations and equation 3.11. To calculate the value of the capacitor bank must be specified PF value of the target, thus it can be seen that the value of the capacitor banks as required. If the supply of reactive power of the capacitor bank is too large it will result in cos θ is negative and the current signal will precede the voltage signal. If the supply of reactive power of the capacitor bank is too small then it will lead to improvement of the power factor is not maximal. From the simulation results, it can be sorted lowest that real power is 1 only when the load is located on the system, and the highest is when the second load is on the system with the value of each parameter listed in the following table. Table 2. Simulation Results before Installation of Capacitors No load V P I cos phi remark 1 TL lamps 220 35 0.29 0.922 lag 2 Rectifier with load Lamp + Ballast 220 130 1.22 0.49 lag 3 Induction motors 220 85 0.39 0.99 lag 4 combination 220 236 1.72 0.62 lag Further more, the calculation of the value of the capacitor to achieve Cos θ = 1 is as follows:
  • 5. International Journal of Novel Research in Electrical and Mechanical Engineering Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com Page | 27 Novelty Journals PF target = 1  θ2 = 00 , 1. Reactive power to be injected into the system From the results of these calculations, it can be sorted that reactive power to be injected is lowest when the load 2 are located on the system, and the highest is when the second load is on the system. Determination of capacitor step will be installed, will be adapted to the conditions in which was done by determining the lowest Q, and then determined the difference between each value of Q to Q supreme. When the Load 2 are working, then the required reactive power requirement is 36.596 VAR then step 1 capacitor bank is worth as needed. Furthermore, when the Load 1 only the work, it would require additional reactive power to be injected at 145.237 VAR, so step 1 and 2 lit. And when the second load of work together, it is necessary to return additional reactive power at 41.232 VAR, under these conditions, the third step should be lit to meet the target CO phi. 2. Capacitor value π π π IV. TESTING SYSTEM System testing performed in this study based on the design that has been made. 4.1. Voltage sensor The results of the sensor voltage using a voltage divider circuit in line with expectations. The result of the voltage sensor is used to detect the phase difference at the zero crossing circuit.
  • 6. International Journal of Novel Research in Electrical and Mechanical Engineering Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com Page | 28 Novelty Journals Table 3. Voltage sensor test data From the table it can be seen that the output voltage of the sensor output either AC or DC voltage output theory approach. 4.2. ACS current sensor 712 Of ACS application circuit IC 712, the result output of AC voltage without a DC component. The resulting output signal IC ACS 712 is an inverting of the input signal. So, we need inverting amplifier output signal that is equal to the input signal IC ACS 712. ACS trial data table: Table 4. ACS current sensor experimental data 712 Because, the output voltage signal of the IC 712 ACS is inverting the circuit using inverting amplifier with a gain of 20 times. So in the calculation of Rf and Ri as follows: ........... ( ) ................(3.5) If the gain 20 times, then I Thus, form the equation 3.5: No. Arus AC [Aac] Vout-AC (mV) Vout-rec (V) 1 0.75 93 1.87 2 1 114 1.89 3 1.25 135 1.914 4 1.5 160 1.94 5 1.75 175 1.97 6 2 206 1.99 7 2.5 257 2.04 8 3 295 2.09 9 3.5 342 2.14 10 4 390 2.195 11 4.5 440 2.25 12 5 488 2.32 No. V input-ac Vout-ac [V] Vout-rec [V] % Error Vout-recpractice Theory practice Theory 1 100 V 1.566 1.363 1.305 1.23 6.1 2 120 V 1.806 1.629 1.576 1.47 7.2 3 140 V 2.18 1.909 1.827 1.72 6.2 4 160 V 2.498 2.181 2.025 1.96 3.3 5 180 V 2.806 2.454 2.315 [1] 2.21 4.7 6 200 V 3.12 2.727 2.486 2.46 1.1 7 220 V 3.42 3 2.88 2.7 1.6
  • 7. International Journal of Novel Research in Electrical and Mechanical Engineering Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com Page | 29 Novelty Journals First set R1=1k, then:   A variable resistor is Rf. The value used is 20K  order to produce a gain of 20 times. 4.3. The circuit Zero Crossing and Phase Detector (Detector phase) The circuit zero crossing detector and a continuation phase current sensors and voltage sensors . The resulting sensor output signal voltage and current sensors, and then processed by the zero crossing circuit and generates 2 -step signal which has a phase difference equal to the ac voltage and current signals. Then processed by the IC - XOR and generate signals that inform the data step phase difference between voltage and current .IC - XOR 2 is used as the summing of the input signal that is current and voltage signals that are output from the zero crossing that has a different phase, with the work as follows: 1. If both inputs same logic would then output is logic "0" 2. If both logic inputs are not equal then the output would be worth a logic " 1 " .Square wave signal coming out of the current and voltage zero crossing comparator circuit to get into compared to using IC 74LS86 TTL XOR to know the difference between the phase angle of the voltage and current flowing in the load. Figure 5: wave voltage sensor and current sensor Figure 6: Wave output voltage divider voltage sensor and current sensor
  • 8. International Journal of Novel Research in Electrical and Mechanical Engineering Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com Page | 30 Novelty Journals Figure 7: wave output of the EX-OR 74hc86 (phase detector parameters) 4.4. Testing System To test the results of this system, obtained the following results: Tabel 5. Validation System Without Capacitor With Meter No load V P I cos phi % Error Vout-rec 1 TL lamps 220 35 0.29 0.922 2% 2 Rectifier with load Lamp + Ballast 220 130 1.22 0.49 2.1% 3 Pump motors 220 85 0.39 0.99 1.2% 4 All expenses 1,2,3 220 236 1.72 0.62 11.2% In table 5 of the test system without capacitor can be seen that for COS phi reading on LCD graphics readout COS phi compared with analog meter has a high % error. On the third reading of the COS phi currently installed load is by 11.29 % when all load is attached. While at C0S phi readings on the percent error % lower reaches 1:01 .Error reading on the LCD due to the number of works on frequency control circuit and is also caused due to poor materials /components used in the circuit. Here are the results of testing the system before and after installation of capacitor banks, which, seen an increase in the value of the COS phi to 0.49 lag to 0.99 lag pump motor after installation of 5.12 µF capacitor. Similarly, when the three loads connected directly together, which are the initial COS phi 0.62 to 0.99 lag increases with the addition of the 9:55 µF. In terms of the current line in the system, there is a reduction in current consumption due to the injection line from the capacitor bank reactive VAR. Seemingly that be saran a flow when the pump motor is initially to 0.82 A 1:22 A similarly when the combined load of 1.72 A to 0.94 A. rectifier load current on the line is not too powerful due COS phi initial value system that has both is 0.99 and 0.92 for fluorescent lamp load. Table 6. System Testing Results before and after the installation of capacitor bank No Load V (V) I (A) Cos phi P(Watt) S(VA) C(F) 1 Pump Motor =222 1.22 0.49 lag 135 271 5,12 220 0.82 0.99 lag 179 2 TL Lamp 222 0.29 0.92 lag 35 62 2,71 220 0.28 0.99 lag 61 3 Rectifier burden Lamp + Ballast 222 0.30 0.99 lag 85 68.2 2,41 220 0.31 0.99 lag 84.94 4 All expenses 1,2,3 222 1.72 0.62 lag 237 207 9.55 220 0,94 0.99 lag 218
  • 9. International Journal of Novel Research in Electrical and Mechanical Engineering Vol. 1, Issue 1, pp: (23-31), Month: September-October 2014, Available at: www.noveltyjournals.com Page | 31 Novelty Journals V. CONCLUSION From the experimental results it can be concluded as follows: 1. In testing the motor load, COS phi can improve from 00:49 (lag) before mounting the capacitor, be COS phi 0.99 (lag) after the installation of capacitors and minimize current consumption from 1:22 A to 0.82 A. 2. In testing with TL lamps and rectifier load, COS phi is basically a system that is already well 0.92 (lag) and 0.99 (lag). After installation of the capacitor, COS phi be 0.99 (lag). 3. Testing the system with the entire load connected to the system, capacitor banks can increase the COS phi of 0.62 (lag) to 0.99 (lag) and can minimize current consumption of 1.72 A to 0.94 A. 4. Linear sensor readings are needed to get a quick response sat COS phi changes to the system. REFERENCES [1] R. Grünbaum, M. Noroozian and B. Thorvaldsson, “FACTS – Powerful Systems for Flexible Power Transmission”, ABB Review, May 1999, pp. 4-17. [2] Neil H. Woodley, “Field Experience with Dynamic Voltage Restorer Systems”, IEEE Power Engineering Society Winter Meeting 2000, Singapore. [3] Saha, Tapan K. and Nguyen, P. T. (2004) Dynamic Voltage Restorer Against Balanced and Unbalanced Voltage Sags: Modelling and Simulation, IEEE Power Engineering Society General Meeting, 6-10 June, 2004, Denver, Colorado, USA. [4] H. Okayama, T. Fujii, S. Tamai, S. Jochi, M. Takeda, R. Hellested, G. Reed, “Application and Development Concepts for a New Transformer-less FACTS Device: the Multimode Static Series Compensator (MSSC)”, Proceedings of the EEE PES, Conference & Expo, Dallas, TX, September 2003. [5] X. Wei, J. H. Chow, B. Fardanesh, and Abdel-Aty Edris, “A Common Modeling Framework of Voltage-Sourced Converters for Load Flow, Sensitivity, and Dispatch Analysis”, IEEE Transactions on Power Systems, Vol. 19, Nº. 2, May 2004, pp. 934-941. [6] Xuan Wei, Joe H. Chow, B. Fardanesh, and Abdel-Aty Edris, “A Dispatch Strategy for an Interline Power Flow Controller Operating At Rated Capacity”, PSCE 2004, 2004 IEEE/PES Power Systems Conference and Exposition, Oct. 10-13, 2004, New York, NY, USA. [7] [2] Cesar A. Luongo, “Superconducting Storage Systems: An Overview,” IEEE Trans. on Magnetics., Vol. 32, No.4, 1996, pp. 2214-2223. [8] Matthew J. Superczynski, “Analysis of the Power Conditioning System for a Superconducting Magnetic Energy Storage Unit”, Master Thesis, Virginia Polytechnic Institute and State University, August 2000. [9] “Reassessment of Superconducting Magnetic Energy Storage (SMES) Transmission System Benefits”, Report number 01006795, March 2002. [10] Issarachai Ngamroo (2005) "Robust Frequency Stabilisation By Coordinated Superconducting Magnetic Energy Storage With Static Synchronous Series Compensator", International Journal of Emerging Electric Power Systems: Vol. 3: No. 1, August 2005. .