Safety BASICs

TM

Electrical Hazards
Bussmann® Awareness of Safety Issues Campaign

©2004 Cooper Bussmann
Electrical Hazards

What are the hazards as you approach
electrical equipment to perform work?
©2004 Cooper Bussmann
Electrical Hazards
• Shock
• Arc flash
– Heat
– Fire

• Arc blast
– Pressure
– Shrapnel
– Sound
Example of an arcing fault
©2004 Cooper Bussmann
Basic Electrical Theory
I=V/Z
• What happens with shock?
• What happens when there is a fault?
• What is the difference between a shortcircuit and an arcing fault?
©2004 Cooper Bussmann
Electric Shock
• Over 30,000 non-fatal electrical shock
accidents occur each year
• Over 600 people die from electrocution
each year
• Electrocution remains the fourth (4th)
highest cause of industrial fatalities
• Most injuries and deaths could be
avoided
©2004 Cooper Bussmann
Human Resistance Values
Resistance (ohms)
Condition

Dry

Wet

40,000 to 1,000,000

4,000 to 15,000

Hand holding wire

15,000 to 50,000

3,000 to 6,000

Finger-thumb grasp

10,000 to 30,000

2,000 to 5,000

Hand holding pliers

5,000 to 10,000

1,000 to 3,000

Palm touch

3,000 to 8,000

1,000 to 2,000

Hand around 1-1/2 inch pipe

1,000 to 3,000

500 to 1,500

500 to 1,500

250 to 750

Finger touch

Two hands around 1-1/2 inch pipe
Hand immersed

200 to 500

Foot immersed

100 to 300

Human body, internal, excluding
skin

200 to 1,000

This table was compiled from data developed by Kouwenhoven and Milnor.
©2004 Cooper Bussmann
Electric Shock
Human body resistance (hand to hand)
across the body is about 1000 Ω
Ohms law: I = V / R amps
= 480 volts / 1000 Ω
= 0.48 amps (480 mA)
Product safety standards consider 5 mA
to be the safe upper limit for children
and adults
©2004 Cooper Bussmann
Electric Shock
mA
0.5 - 3
3 - 10
10 - 40
30 - 75
100 - 200
200 - 500
1500 +
©2004 Cooper Bussmann

Affect on person
- Tingling sensations
- Muscle contractions and pain
- “Let-go” threshold
- Respiratory paralysis
- Ventricular fibrillation
- Heart clamps tight
- Tissue and organs start to burn
Electric Current Pathways

(A) Touch Potential

(B) Step Potential

(C and D) Touch / Step Potential

Current passing through the heart and lungs is the most serious

©2004 Cooper Bussmann
Electric Shock Injury

©2004 Cooper Bussmann
Arc Flash
As much as 80% of all electrical injuries are
burns resulting from an arc-flash and ignition
of flammable clothing
Arc temperature can reach 35,000°F - this is
four times hotter than the surface of the sun
Fatal burns can occur at distances over 10 ft
Over 2000 people are admitted into burn
centers each year with severe electrical burns
©2004 Cooper Bussmann
Arc Blast
An arc fault develops a “pressure wave”
Sources of this blast include:
– Copper expands 67,000 times its original volume
when vaporized
– Heat from the arc, causes air to expand, in the
same way that thunder is created from a lightning
strike

This may result in a violent explosion of circuit
components and thrown shrapnel
The blast can destroy structures, knock workers
from ladders, or across the room
©2004 Cooper Bussmann
Bolted
Short Circuit

Arcing
Fault

Current
Thru Air

A
©2004 Cooper Bussmann

B

A

B
Electric Arc
35,000 °F

Molten Metal
Pressure Waves
Sound Waves
Shrapnel

Copper Vapor:
Solid to Vapor
Expands by
67,000 times

Hot Air-Rapid Expansion
Intense Light

©2004 Cooper Bussmann
Personnel Hazards Associated
With Arc Flash & Arc Blast
• Heat – burns & ignition of material
– Arc temperature of 35,000oF
– Molten metal, copper vapor, heated air

• Second degree burn threshold:
– 80oC / 175oF (0.1 sec), 2nd degree burn

• Third degree burn threshold:
– 96oC / 205oF (0.1 sec), 3rd degree burn

• Intense light
– Eye damage, cataracts
©2004 Cooper Bussmann
Personnel Hazards Associated
With Arc Flash & Arc Blast
• Pressures from expansion of metals &
air
• Eardrum rupture threshold:
– 720 lbs/ft2

• Lung damage threshold:
– 1728 - 2160 lbs/ft2

• Shrapnel
• Flung across room or from
ladder/bucket
©2004 Cooper Bussmann
Overcurrent Protection Role
Flash protection boundaries and
incident energy exposure calculations
both dependent upon:
Duration of arc-fault or time to clear
• Speed of the overcurrent protective
device

Arc-fault current magnitude
• Available fault current
• Current-limitation can reduce
©2004 Cooper Bussmann
IEEE / PCIC & NFPA 70E
• Ad Hoc Safety Subcommittee
– Users
– Consultants
– Manufacturers
– Medical experts

• Following are some of the tests run
– All of the devices used for this testing were
applied according to their listed ratings
©2004 Cooper Bussmann
IEEE / PCIC Staged Arc Flash Test
Set-up

©2004 Cooper Bussmann
Test No. 4

22.6 KA Symmetrical
Available Fault Current
@ 480V, 3 Phase

6 cycle STD
Set @ 6 cycle opening

640A OCPD
Non Current Limiting
with Short Time Delay

Fault Initiated on
Line Side of 30A
Fuse
30A RK-1
Current Limiting Fuse
Size 1 Starter

©2004 Cooper Bussmann
©2004 Cooper Bussmann
Test 4 Still Photo

©2004 Cooper Bussmann
Test 4 Still Photo

©2004 Cooper Bussmann
Test 4 Still Photo

©2004 Cooper Bussmann
Test 4 Still Photo

©2004 Cooper Bussmann
Test 4 Still Photo

©2004 Cooper Bussmann
Test 4 Still Photo

©2004 Cooper Bussmann
Test 4 Still Photo

©2004 Cooper Bussmann
Results: Test No.4
Sound

141.5 db @ 2 ft.

P1

T2

>2160 lbs/ft2

o

o

>225 C/437 F

o

T3
o

T1

o

50 C/122 F

>225 C/
o
437 F

> Indicates Meter Pegged
©2004 Cooper Bussmann
Test No. 3

22.6 KA Symmetrical
Available Fault Current
@ 480V, 3 Phase

601A.
Class L
Current Limiting Fuse

Fault Initiated on
Line Side of 30A
Fuse

30A RK-1
Current Limiting Fuse

Size 1 Starter
©2004 Cooper Bussmann
©2004 Cooper Bussmann
Test 3 Still Photo

©2004 Cooper Bussmann
Test 3 Still Photo

©2004 Cooper Bussmann
Test 3 Still Photo

©2004 Cooper Bussmann
Test 3 Still Photo

©2004 Cooper Bussmann
Results: Test No.3
Sound

133 db @ 2 ft.
T2
o

o

62 C/143.6 F
T3
(No Change
From Ambient)

P1
504 lbs/ft2
T1
> 175 C/
o
347 F

> Indicates Meter Pegged
©2004 Cooper Bussmann

o
Test No. 1

22.6 KA Symmetrical
Available Fault Current
@ 480V, 3 Phase

601A.
Class L
Current Limiting
Fuse

30A RK-1
Current Limiting
Fuse
Fault Initiated on
Load Side of 30A
Fuse
©2004 Cooper Bussmann

Size 1 Starter
©2004 Cooper Bussmann
Test 1 Still Photo

©2004 Cooper Bussmann
Test 1 Still Photo

©2004 Cooper Bussmann
Test 1 Still Photo

©2004 Cooper Bussmann
Test 1 Still Photo

©2004 Cooper Bussmann
Results: Test No.1
Sound
(No Change
From Ambient)

T2
(No Change
From Ambient)

T3
(No Change
From Ambient)
©2004 Cooper Bussmann

P1
(No Change
From Ambient)

T1
(No Change
From Ambient)
Current-Limitation: Arc Energy
Reduction
Test 4

Non-Current Limiting

Test 3

Reduced Fault Current
via Current-Limitation

©2004 Cooper Bussmann

Test 1
Summary
• Shock, arc flash and arc blast are the
three recognized electrical hazards
• Shock injuries result from electrical
current flowing through the body
• Arcing faults can generate enormous
amounts of energy
• Injuries from arcing faults are a result of
the tremendous heat and pressure
generated
©2004 Cooper Bussmann
Summary
• Overcurrent protective devices have an
impact on the two most important
variables of arc flash hazards:
– Time (speed of the OCPD)
– Fault current magnitude (current-limitation
may help reduce)

• Current-limitation may be able to
significantly reduce the energy released
during arcing faults
©2004 Cooper Bussmann

More Related Content

What's hot

Electrical Arc Flash Safety and Risk Management
Electrical Arc Flash Safety and Risk ManagementElectrical Arc Flash Safety and Risk Management
Electrical Arc Flash Safety and Risk ManagementSchneider Electric
 
Electrical safety ppt
Electrical safety pptElectrical safety ppt
Electrical safety pptEr Ramgarhia
 
Electrical safety slideshare
Electrical safety slideshareElectrical safety slideshare
Electrical safety slideshareYokeshDhanabal
 
Electrical safety ppt
Electrical safety pptElectrical safety ppt
Electrical safety pptconstruction
 
Electrical Safety and Risk Assessments
Electrical Safety and Risk AssessmentsElectrical Safety and Risk Assessments
Electrical Safety and Risk AssessmentsMohd Azmatullah
 
Electrical Safety In The Workplace
Electrical Safety In The WorkplaceElectrical Safety In The Workplace
Electrical Safety In The WorkplaceCurrent Solutions PC
 
Electrical Safety Techniques
Electrical Safety TechniquesElectrical Safety Techniques
Electrical Safety TechniquesLiving Online
 
Electrical Safety Joliet Distribution Center
Electrical Safety Joliet Distribution CenterElectrical Safety Joliet Distribution Center
Electrical Safety Joliet Distribution Centertrevor_heller
 
General Electrical Safety Training by BGSU
General Electrical Safety Training by BGSUGeneral Electrical Safety Training by BGSU
General Electrical Safety Training by BGSUAtlantic Training, LLC.
 
Electrical safety
Electrical safetyElectrical safety
Electrical safetyAna Metaxas
 
Electrical safety training based on osha 1910 standards sw
Electrical safety training based on osha 1910 standards swElectrical safety training based on osha 1910 standards sw
Electrical safety training based on osha 1910 standards swAniruddha Kulkarni
 
ELECTRICAL SAFETY PRESENTATION.ppt
ELECTRICAL SAFETY PRESENTATION.pptELECTRICAL SAFETY PRESENTATION.ppt
ELECTRICAL SAFETY PRESENTATION.pptVIDHYUTtech
 
Electrical safety in construction
Electrical safety in constructionElectrical safety in construction
Electrical safety in constructionsrinivas2036
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flashmichaeljmack
 

What's hot (20)

Electrical Arc Flash Safety and Risk Management
Electrical Arc Flash Safety and Risk ManagementElectrical Arc Flash Safety and Risk Management
Electrical Arc Flash Safety and Risk Management
 
Electrical safety ppt
Electrical safety pptElectrical safety ppt
Electrical safety ppt
 
Electrical safety slideshare
Electrical safety slideshareElectrical safety slideshare
Electrical safety slideshare
 
Electrical safety new
Electrical safety newElectrical safety new
Electrical safety new
 
Electrical safety ppt
Electrical safety pptElectrical safety ppt
Electrical safety ppt
 
Electrical Safety
Electrical SafetyElectrical Safety
Electrical Safety
 
Electrical Safety and Risk Assessments
Electrical Safety and Risk AssessmentsElectrical Safety and Risk Assessments
Electrical Safety and Risk Assessments
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Electrical Safety In The Workplace
Electrical Safety In The WorkplaceElectrical Safety In The Workplace
Electrical Safety In The Workplace
 
Electrical Safety Techniques
Electrical Safety TechniquesElectrical Safety Techniques
Electrical Safety Techniques
 
Electrical Safety Joliet Distribution Center
Electrical Safety Joliet Distribution CenterElectrical Safety Joliet Distribution Center
Electrical Safety Joliet Distribution Center
 
General Electrical Safety Training by BGSU
General Electrical Safety Training by BGSUGeneral Electrical Safety Training by BGSU
General Electrical Safety Training by BGSU
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Arc Flash Solutions
Arc Flash SolutionsArc Flash Solutions
Arc Flash Solutions
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Electrical safety training based on osha 1910 standards sw
Electrical safety training based on osha 1910 standards swElectrical safety training based on osha 1910 standards sw
Electrical safety training based on osha 1910 standards sw
 
Electrical Safety by OSHA
Electrical Safety by OSHAElectrical Safety by OSHA
Electrical Safety by OSHA
 
ELECTRICAL SAFETY PRESENTATION.ppt
ELECTRICAL SAFETY PRESENTATION.pptELECTRICAL SAFETY PRESENTATION.ppt
ELECTRICAL SAFETY PRESENTATION.ppt
 
Electrical safety in construction
Electrical safety in constructionElectrical safety in construction
Electrical safety in construction
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 

Viewers also liked

Electrical hazardous
Electrical hazardousElectrical hazardous
Electrical hazardousDashne DM
 
Practical Electrical Substation Safety for Engineers and Technicians
Practical Electrical Substation Safety for Engineers and TechniciansPractical Electrical Substation Safety for Engineers and Technicians
Practical Electrical Substation Safety for Engineers and TechniciansLiving Online
 
The issues of electrical hazards at site and steps to prevent.
The issues of electrical hazards at site  and steps to prevent.The issues of electrical hazards at site  and steps to prevent.
The issues of electrical hazards at site and steps to prevent.tfkc1212
 
Electrical safety and Arc Flash Training
Electrical safety and Arc Flash TrainingElectrical safety and Arc Flash Training
Electrical safety and Arc Flash TrainingLarry Riley
 
Trapping and Crushing in MEWPS - Guidance from Strategic Forum Plant Safety ...
Trapping and Crushing in MEWPS -  Guidance from Strategic Forum Plant Safety ...Trapping and Crushing in MEWPS -  Guidance from Strategic Forum Plant Safety ...
Trapping and Crushing in MEWPS - Guidance from Strategic Forum Plant Safety ...Alan Bassett
 
Safety and order in electrical substations
Safety and order in electrical substationsSafety and order in electrical substations
Safety and order in electrical substationsYunz contracting
 
Electrical Hazards and their safety
Electrical Hazards and their safetyElectrical Hazards and their safety
Electrical Hazards and their safetyMoxit Khandhar
 
Top 10 rules for electric safety
Top 10 rules for electric safetyTop 10 rules for electric safety
Top 10 rules for electric safetyRock Wood
 

Viewers also liked (14)

Electrical hazardous
Electrical hazardousElectrical hazardous
Electrical hazardous
 
Electrical Hazarad
Electrical HazaradElectrical Hazarad
Electrical Hazarad
 
Practical Electrical Substation Safety for Engineers and Technicians
Practical Electrical Substation Safety for Engineers and TechniciansPractical Electrical Substation Safety for Engineers and Technicians
Practical Electrical Substation Safety for Engineers and Technicians
 
The issues of electrical hazards at site and steps to prevent.
The issues of electrical hazards at site  and steps to prevent.The issues of electrical hazards at site  and steps to prevent.
The issues of electrical hazards at site and steps to prevent.
 
Electrical safety and Arc Flash Training
Electrical safety and Arc Flash TrainingElectrical safety and Arc Flash Training
Electrical safety and Arc Flash Training
 
Appliance Test and Tag Part 1
Appliance Test and Tag Part 1Appliance Test and Tag Part 1
Appliance Test and Tag Part 1
 
Overhead lines electrical_hazards
Overhead lines electrical_hazardsOverhead lines electrical_hazards
Overhead lines electrical_hazards
 
Trapping and Crushing in MEWPS - Guidance from Strategic Forum Plant Safety ...
Trapping and Crushing in MEWPS -  Guidance from Strategic Forum Plant Safety ...Trapping and Crushing in MEWPS -  Guidance from Strategic Forum Plant Safety ...
Trapping and Crushing in MEWPS - Guidance from Strategic Forum Plant Safety ...
 
Safety and order in electrical substations
Safety and order in electrical substationsSafety and order in electrical substations
Safety and order in electrical substations
 
253 642-1-pb
253 642-1-pb253 642-1-pb
253 642-1-pb
 
Session 2 General Safety Requirements
Session 2   General Safety RequirementsSession 2   General Safety Requirements
Session 2 General Safety Requirements
 
Electrical Hazards and their safety
Electrical Hazards and their safetyElectrical Hazards and their safety
Electrical Hazards and their safety
 
NFPA 70E Training By SASCO
NFPA 70E Training By SASCONFPA 70E Training By SASCO
NFPA 70E Training By SASCO
 
Top 10 rules for electric safety
Top 10 rules for electric safetyTop 10 rules for electric safety
Top 10 rules for electric safety
 

Similar to Electrical Hazards by Cooper Bussmann

Arc Blast Flash
Arc Blast FlashArc Blast Flash
Arc Blast Flashjboullemet
 
SafetyPresentation12.15.06.pdf
SafetyPresentation12.15.06.pdfSafetyPresentation12.15.06.pdf
SafetyPresentation12.15.06.pdfImranShah585030
 
ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING
ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHINGARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING
ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHINGAmit Chakraborty
 
Electrical Hazards and Arc Flash Awareness by RCC
Electrical Hazards and Arc Flash Awareness by RCCElectrical Hazards and Arc Flash Awareness by RCC
Electrical Hazards and Arc Flash Awareness by RCCAtlantic Training, LLC.
 
Arc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyArc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyAtlantic Training, LLC.
 
Arc Flash booklet -
Arc Flash booklet -Arc Flash booklet -
Arc Flash booklet -John Locher
 
Fire safety of Bank Premises
Fire safety of Bank PremisesFire safety of Bank Premises
Fire safety of Bank PremisesRanjeet Kumar
 
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...Thorne & Derrick International
 
Arc welding & safty
Arc welding & saftyArc welding & safty
Arc welding & saftyillpa
 
ELECTRICAL SAFETY AWARENES.pdf
ELECTRICAL SAFETY AWARENES.pdfELECTRICAL SAFETY AWARENES.pdf
ELECTRICAL SAFETY AWARENES.pdfJansenSunga
 
Global solar power presentation by jmv lps july2017
Global solar power presentation by jmv lps july2017Global solar power presentation by jmv lps july2017
Global solar power presentation by jmv lps july2017Mahesh Chandra Manav
 
Electrical Products and Human Live safety Umbrealla(SACHET) NBC2016
Electrical Products and Human Live safety Umbrealla(SACHET) NBC2016Electrical Products and Human Live safety Umbrealla(SACHET) NBC2016
Electrical Products and Human Live safety Umbrealla(SACHET) NBC2016Mahesh Chandra Manav
 
Practical Arc Flash Protection for Electrical Safety Engineers and Technicians
Practical Arc Flash Protection for Electrical Safety Engineers and TechniciansPractical Arc Flash Protection for Electrical Safety Engineers and Technicians
Practical Arc Flash Protection for Electrical Safety Engineers and TechniciansLiving Online
 

Similar to Electrical Hazards by Cooper Bussmann (20)

Arc Blast Flash
Arc Blast FlashArc Blast Flash
Arc Blast Flash
 
SafetyPresentation12.15.06.pdf
SafetyPresentation12.15.06.pdfSafetyPresentation12.15.06.pdf
SafetyPresentation12.15.06.pdf
 
ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING
ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHINGARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING
ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING
 
Frank Conte Arc flash program
Frank Conte Arc flash programFrank Conte Arc flash program
Frank Conte Arc flash program
 
Electrical Hazards and Arc Flash Awareness by RCC
Electrical Hazards and Arc Flash Awareness by RCCElectrical Hazards and Arc Flash Awareness by RCC
Electrical Hazards and Arc Flash Awareness by RCC
 
Arc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyArc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of Technology
 
Arc Flash booklet -
Arc Flash booklet -Arc Flash booklet -
Arc Flash booklet -
 
Fire safety of Bank Premises
Fire safety of Bank PremisesFire safety of Bank Premises
Fire safety of Bank Premises
 
Lv arc-flash-paper
Lv arc-flash-paperLv arc-flash-paper
Lv arc-flash-paper
 
FAMECA Transmission Earthing Devices
FAMECA Transmission Earthing Devices FAMECA Transmission Earthing Devices
FAMECA Transmission Earthing Devices
 
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
 
Arc welding & safty
Arc welding & saftyArc welding & safty
Arc welding & safty
 
ELECTRICAL SAFETY AWARENES.pdf
ELECTRICAL SAFETY AWARENES.pdfELECTRICAL SAFETY AWARENES.pdf
ELECTRICAL SAFETY AWARENES.pdf
 
Global solar power presentation by jmv lps july2017
Global solar power presentation by jmv lps july2017Global solar power presentation by jmv lps july2017
Global solar power presentation by jmv lps july2017
 
Prysmian Afumex Low Smoke Zero Halogen Cables
Prysmian Afumex Low Smoke Zero Halogen CablesPrysmian Afumex Low Smoke Zero Halogen Cables
Prysmian Afumex Low Smoke Zero Halogen Cables
 
Electrical safety.pptx
Electrical safety.pptxElectrical safety.pptx
Electrical safety.pptx
 
Fire cable sizing
Fire cable sizingFire cable sizing
Fire cable sizing
 
KEMET EMC Filters
KEMET EMC FiltersKEMET EMC Filters
KEMET EMC Filters
 
Electrical Products and Human Live safety Umbrealla(SACHET) NBC2016
Electrical Products and Human Live safety Umbrealla(SACHET) NBC2016Electrical Products and Human Live safety Umbrealla(SACHET) NBC2016
Electrical Products and Human Live safety Umbrealla(SACHET) NBC2016
 
Practical Arc Flash Protection for Electrical Safety Engineers and Technicians
Practical Arc Flash Protection for Electrical Safety Engineers and TechniciansPractical Arc Flash Protection for Electrical Safety Engineers and Technicians
Practical Arc Flash Protection for Electrical Safety Engineers and Technicians
 

More from Atlantic Training, LLC.

Stress and Worker Safety by Pennsylvania L&I
Stress and Worker Safety by Pennsylvania L&IStress and Worker Safety by Pennsylvania L&I
Stress and Worker Safety by Pennsylvania L&IAtlantic Training, LLC.
 
Workplace Harassment Prevention by UT EAP
Workplace Harassment Prevention by  UT EAPWorkplace Harassment Prevention by  UT EAP
Workplace Harassment Prevention by UT EAPAtlantic Training, LLC.
 
Preventing Falls, Slips and Trips by MGSU
Preventing Falls, Slips and Trips by MGSUPreventing Falls, Slips and Trips by MGSU
Preventing Falls, Slips and Trips by MGSUAtlantic Training, LLC.
 
Preventing Workplace Harassment by Pennsylvania L&I
Preventing Workplace Harassment by Pennsylvania L&IPreventing Workplace Harassment by Pennsylvania L&I
Preventing Workplace Harassment by Pennsylvania L&IAtlantic Training, LLC.
 
Warehouses In Emergencies by WFP Logistics
Warehouses In Emergencies by WFP LogisticsWarehouses In Emergencies by WFP Logistics
Warehouses In Emergencies by WFP LogisticsAtlantic Training, LLC.
 
Sexual Harassment in the Workplace Training by Shumaker
Sexual Harassment in the Workplace Training by ShumakerSexual Harassment in the Workplace Training by Shumaker
Sexual Harassment in the Workplace Training by ShumakerAtlantic Training, LLC.
 
New Employee Safety Orientation by Oregon State University
New Employee Safety Orientation by Oregon State UniversityNew Employee Safety Orientation by Oregon State University
New Employee Safety Orientation by Oregon State UniversityAtlantic Training, LLC.
 

More from Atlantic Training, LLC. (20)

Wellness for Supervisors by SWOSU
Wellness for Supervisors by SWOSUWellness for Supervisors by SWOSU
Wellness for Supervisors by SWOSU
 
Workplace Wellness by PHA
Workplace Wellness by PHAWorkplace Wellness by PHA
Workplace Wellness by PHA
 
Stress Management Training by SG
Stress Management Training by  SGStress Management Training by  SG
Stress Management Training by SG
 
Stress Management Training by SW
Stress Management Training by SWStress Management Training by SW
Stress Management Training by SW
 
Stress and Worker Safety by Pennsylvania L&I
Stress and Worker Safety by Pennsylvania L&IStress and Worker Safety by Pennsylvania L&I
Stress and Worker Safety by Pennsylvania L&I
 
Respectful Workplace by RDTC
Respectful Workplace by RDTCRespectful Workplace by RDTC
Respectful Workplace by RDTC
 
Workplace Harassment by CLGW
Workplace Harassment by CLGWWorkplace Harassment by CLGW
Workplace Harassment by CLGW
 
Workplace Harassment Prevention by UT EAP
Workplace Harassment Prevention by  UT EAPWorkplace Harassment Prevention by  UT EAP
Workplace Harassment Prevention by UT EAP
 
Welding Safety by Pennsylvania L&I
Welding Safety by Pennsylvania L&IWelding Safety by Pennsylvania L&I
Welding Safety by Pennsylvania L&I
 
Slips Trips & Falls Training by Signal
Slips Trips & Falls Training by SignalSlips Trips & Falls Training by Signal
Slips Trips & Falls Training by Signal
 
Preventing Falls, Slips and Trips by MGSU
Preventing Falls, Slips and Trips by MGSUPreventing Falls, Slips and Trips by MGSU
Preventing Falls, Slips and Trips by MGSU
 
Preventing Workplace Harassment by Pennsylvania L&I
Preventing Workplace Harassment by Pennsylvania L&IPreventing Workplace Harassment by Pennsylvania L&I
Preventing Workplace Harassment by Pennsylvania L&I
 
Warehouses In Emergencies by WFP Logistics
Warehouses In Emergencies by WFP LogisticsWarehouses In Emergencies by WFP Logistics
Warehouses In Emergencies by WFP Logistics
 
Prevention of Sexual Harassment by USMC
Prevention of Sexual Harassment by USMCPrevention of Sexual Harassment by USMC
Prevention of Sexual Harassment by USMC
 
Sexual Harassment by DEOMI
Sexual Harassment by DEOMISexual Harassment by DEOMI
Sexual Harassment by DEOMI
 
Sexual Harassment in the Workplace Training by Shumaker
Sexual Harassment in the Workplace Training by ShumakerSexual Harassment in the Workplace Training by Shumaker
Sexual Harassment in the Workplace Training by Shumaker
 
Sexual Harassment Training by NAP
Sexual Harassment Training by NAPSexual Harassment Training by NAP
Sexual Harassment Training by NAP
 
Scaffolds Training by Pennsylvania L&I
Scaffolds Training by Pennsylvania L&IScaffolds Training by Pennsylvania L&I
Scaffolds Training by Pennsylvania L&I
 
Supervision
SupervisionSupervision
Supervision
 
New Employee Safety Orientation by Oregon State University
New Employee Safety Orientation by Oregon State UniversityNew Employee Safety Orientation by Oregon State University
New Employee Safety Orientation by Oregon State University
 

Recently uploaded

MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?Olivia Kresic
 
Annual General Meeting Presentation Slides
Annual General Meeting Presentation SlidesAnnual General Meeting Presentation Slides
Annual General Meeting Presentation SlidesKeppelCorporation
 
FULL ENJOY Call girls in Paharganj Delhi | 8377087607
FULL ENJOY Call girls in Paharganj Delhi | 8377087607FULL ENJOY Call girls in Paharganj Delhi | 8377087607
FULL ENJOY Call girls in Paharganj Delhi | 8377087607dollysharma2066
 
Global Scenario On Sustainable and Resilient Coconut Industry by Dr. Jelfina...
Global Scenario On Sustainable  and Resilient Coconut Industry by Dr. Jelfina...Global Scenario On Sustainable  and Resilient Coconut Industry by Dr. Jelfina...
Global Scenario On Sustainable and Resilient Coconut Industry by Dr. Jelfina...ictsugar
 
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdfNewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdfKhaled Al Awadi
 
8447779800, Low rate Call girls in Saket Delhi NCR
8447779800, Low rate Call girls in Saket Delhi NCR8447779800, Low rate Call girls in Saket Delhi NCR
8447779800, Low rate Call girls in Saket Delhi NCRashishs7044
 
Innovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdfInnovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdfrichard876048
 
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
Keppel Ltd. 1Q 2024 Business Update  Presentation SlidesKeppel Ltd. 1Q 2024 Business Update  Presentation Slides
Keppel Ltd. 1Q 2024 Business Update Presentation SlidesKeppelCorporation
 
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...lizamodels9
 
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607dollysharma2066
 
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCRashishs7044
 
Kenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby AfricaKenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby Africaictsugar
 
International Business Environments and Operations 16th Global Edition test b...
International Business Environments and Operations 16th Global Edition test b...International Business Environments and Operations 16th Global Edition test b...
International Business Environments and Operations 16th Global Edition test b...ssuserf63bd7
 
/:Call Girls In Indirapuram Ghaziabad ➥9990211544 Independent Best Escorts In...
/:Call Girls In Indirapuram Ghaziabad ➥9990211544 Independent Best Escorts In.../:Call Girls In Indirapuram Ghaziabad ➥9990211544 Independent Best Escorts In...
/:Call Girls In Indirapuram Ghaziabad ➥9990211544 Independent Best Escorts In...lizamodels9
 
APRIL2024_UKRAINE_xml_0000000000000 .pdf
APRIL2024_UKRAINE_xml_0000000000000 .pdfAPRIL2024_UKRAINE_xml_0000000000000 .pdf
APRIL2024_UKRAINE_xml_0000000000000 .pdfRbc Rbcua
 
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCRashishs7044
 
Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...
Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...
Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...lizamodels9
 
Contemporary Economic Issues Facing the Filipino Entrepreneur (1).pptx
Contemporary Economic Issues Facing the Filipino Entrepreneur (1).pptxContemporary Economic Issues Facing the Filipino Entrepreneur (1).pptx
Contemporary Economic Issues Facing the Filipino Entrepreneur (1).pptxMarkAnthonyAurellano
 

Recently uploaded (20)

MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?
 
Annual General Meeting Presentation Slides
Annual General Meeting Presentation SlidesAnnual General Meeting Presentation Slides
Annual General Meeting Presentation Slides
 
FULL ENJOY Call girls in Paharganj Delhi | 8377087607
FULL ENJOY Call girls in Paharganj Delhi | 8377087607FULL ENJOY Call girls in Paharganj Delhi | 8377087607
FULL ENJOY Call girls in Paharganj Delhi | 8377087607
 
Global Scenario On Sustainable and Resilient Coconut Industry by Dr. Jelfina...
Global Scenario On Sustainable  and Resilient Coconut Industry by Dr. Jelfina...Global Scenario On Sustainable  and Resilient Coconut Industry by Dr. Jelfina...
Global Scenario On Sustainable and Resilient Coconut Industry by Dr. Jelfina...
 
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdfNewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
 
8447779800, Low rate Call girls in Saket Delhi NCR
8447779800, Low rate Call girls in Saket Delhi NCR8447779800, Low rate Call girls in Saket Delhi NCR
8447779800, Low rate Call girls in Saket Delhi NCR
 
Innovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdfInnovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdf
 
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
Keppel Ltd. 1Q 2024 Business Update  Presentation SlidesKeppel Ltd. 1Q 2024 Business Update  Presentation Slides
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
 
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
 
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
 
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
 
Kenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby AfricaKenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby Africa
 
International Business Environments and Operations 16th Global Edition test b...
International Business Environments and Operations 16th Global Edition test b...International Business Environments and Operations 16th Global Edition test b...
International Business Environments and Operations 16th Global Edition test b...
 
/:Call Girls In Indirapuram Ghaziabad ➥9990211544 Independent Best Escorts In...
/:Call Girls In Indirapuram Ghaziabad ➥9990211544 Independent Best Escorts In.../:Call Girls In Indirapuram Ghaziabad ➥9990211544 Independent Best Escorts In...
/:Call Girls In Indirapuram Ghaziabad ➥9990211544 Independent Best Escorts In...
 
APRIL2024_UKRAINE_xml_0000000000000 .pdf
APRIL2024_UKRAINE_xml_0000000000000 .pdfAPRIL2024_UKRAINE_xml_0000000000000 .pdf
APRIL2024_UKRAINE_xml_0000000000000 .pdf
 
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
 
Japan IT Week 2024 Brochure by 47Billion (English)
Japan IT Week 2024 Brochure by 47Billion (English)Japan IT Week 2024 Brochure by 47Billion (English)
Japan IT Week 2024 Brochure by 47Billion (English)
 
Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...
Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...
Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...
 
Corporate Profile 47Billion Information Technology
Corporate Profile 47Billion Information TechnologyCorporate Profile 47Billion Information Technology
Corporate Profile 47Billion Information Technology
 
Contemporary Economic Issues Facing the Filipino Entrepreneur (1).pptx
Contemporary Economic Issues Facing the Filipino Entrepreneur (1).pptxContemporary Economic Issues Facing the Filipino Entrepreneur (1).pptx
Contemporary Economic Issues Facing the Filipino Entrepreneur (1).pptx
 

Electrical Hazards by Cooper Bussmann

  • 1. Safety BASICs TM Electrical Hazards Bussmann® Awareness of Safety Issues Campaign ©2004 Cooper Bussmann
  • 2. Electrical Hazards What are the hazards as you approach electrical equipment to perform work? ©2004 Cooper Bussmann
  • 3. Electrical Hazards • Shock • Arc flash – Heat – Fire • Arc blast – Pressure – Shrapnel – Sound Example of an arcing fault ©2004 Cooper Bussmann
  • 4. Basic Electrical Theory I=V/Z • What happens with shock? • What happens when there is a fault? • What is the difference between a shortcircuit and an arcing fault? ©2004 Cooper Bussmann
  • 5. Electric Shock • Over 30,000 non-fatal electrical shock accidents occur each year • Over 600 people die from electrocution each year • Electrocution remains the fourth (4th) highest cause of industrial fatalities • Most injuries and deaths could be avoided ©2004 Cooper Bussmann
  • 6. Human Resistance Values Resistance (ohms) Condition Dry Wet 40,000 to 1,000,000 4,000 to 15,000 Hand holding wire 15,000 to 50,000 3,000 to 6,000 Finger-thumb grasp 10,000 to 30,000 2,000 to 5,000 Hand holding pliers 5,000 to 10,000 1,000 to 3,000 Palm touch 3,000 to 8,000 1,000 to 2,000 Hand around 1-1/2 inch pipe 1,000 to 3,000 500 to 1,500 500 to 1,500 250 to 750 Finger touch Two hands around 1-1/2 inch pipe Hand immersed 200 to 500 Foot immersed 100 to 300 Human body, internal, excluding skin 200 to 1,000 This table was compiled from data developed by Kouwenhoven and Milnor. ©2004 Cooper Bussmann
  • 7. Electric Shock Human body resistance (hand to hand) across the body is about 1000 Ω Ohms law: I = V / R amps = 480 volts / 1000 Ω = 0.48 amps (480 mA) Product safety standards consider 5 mA to be the safe upper limit for children and adults ©2004 Cooper Bussmann
  • 8. Electric Shock mA 0.5 - 3 3 - 10 10 - 40 30 - 75 100 - 200 200 - 500 1500 + ©2004 Cooper Bussmann Affect on person - Tingling sensations - Muscle contractions and pain - “Let-go” threshold - Respiratory paralysis - Ventricular fibrillation - Heart clamps tight - Tissue and organs start to burn
  • 9. Electric Current Pathways (A) Touch Potential (B) Step Potential (C and D) Touch / Step Potential Current passing through the heart and lungs is the most serious ©2004 Cooper Bussmann
  • 10. Electric Shock Injury ©2004 Cooper Bussmann
  • 11. Arc Flash As much as 80% of all electrical injuries are burns resulting from an arc-flash and ignition of flammable clothing Arc temperature can reach 35,000°F - this is four times hotter than the surface of the sun Fatal burns can occur at distances over 10 ft Over 2000 people are admitted into burn centers each year with severe electrical burns ©2004 Cooper Bussmann
  • 12. Arc Blast An arc fault develops a “pressure wave” Sources of this blast include: – Copper expands 67,000 times its original volume when vaporized – Heat from the arc, causes air to expand, in the same way that thunder is created from a lightning strike This may result in a violent explosion of circuit components and thrown shrapnel The blast can destroy structures, knock workers from ladders, or across the room ©2004 Cooper Bussmann
  • 14. Electric Arc 35,000 °F Molten Metal Pressure Waves Sound Waves Shrapnel Copper Vapor: Solid to Vapor Expands by 67,000 times Hot Air-Rapid Expansion Intense Light ©2004 Cooper Bussmann
  • 15. Personnel Hazards Associated With Arc Flash & Arc Blast • Heat – burns & ignition of material – Arc temperature of 35,000oF – Molten metal, copper vapor, heated air • Second degree burn threshold: – 80oC / 175oF (0.1 sec), 2nd degree burn • Third degree burn threshold: – 96oC / 205oF (0.1 sec), 3rd degree burn • Intense light – Eye damage, cataracts ©2004 Cooper Bussmann
  • 16. Personnel Hazards Associated With Arc Flash & Arc Blast • Pressures from expansion of metals & air • Eardrum rupture threshold: – 720 lbs/ft2 • Lung damage threshold: – 1728 - 2160 lbs/ft2 • Shrapnel • Flung across room or from ladder/bucket ©2004 Cooper Bussmann
  • 17. Overcurrent Protection Role Flash protection boundaries and incident energy exposure calculations both dependent upon: Duration of arc-fault or time to clear • Speed of the overcurrent protective device Arc-fault current magnitude • Available fault current • Current-limitation can reduce ©2004 Cooper Bussmann
  • 18. IEEE / PCIC & NFPA 70E • Ad Hoc Safety Subcommittee – Users – Consultants – Manufacturers – Medical experts • Following are some of the tests run – All of the devices used for this testing were applied according to their listed ratings ©2004 Cooper Bussmann
  • 19. IEEE / PCIC Staged Arc Flash Test Set-up ©2004 Cooper Bussmann
  • 20. Test No. 4 22.6 KA Symmetrical Available Fault Current @ 480V, 3 Phase 6 cycle STD Set @ 6 cycle opening 640A OCPD Non Current Limiting with Short Time Delay Fault Initiated on Line Side of 30A Fuse 30A RK-1 Current Limiting Fuse Size 1 Starter ©2004 Cooper Bussmann
  • 22. Test 4 Still Photo ©2004 Cooper Bussmann
  • 23. Test 4 Still Photo ©2004 Cooper Bussmann
  • 24. Test 4 Still Photo ©2004 Cooper Bussmann
  • 25. Test 4 Still Photo ©2004 Cooper Bussmann
  • 26. Test 4 Still Photo ©2004 Cooper Bussmann
  • 27. Test 4 Still Photo ©2004 Cooper Bussmann
  • 28. Test 4 Still Photo ©2004 Cooper Bussmann
  • 29. Results: Test No.4 Sound 141.5 db @ 2 ft. P1 T2 >2160 lbs/ft2 o o >225 C/437 F o T3 o T1 o 50 C/122 F >225 C/ o 437 F > Indicates Meter Pegged ©2004 Cooper Bussmann
  • 30. Test No. 3 22.6 KA Symmetrical Available Fault Current @ 480V, 3 Phase 601A. Class L Current Limiting Fuse Fault Initiated on Line Side of 30A Fuse 30A RK-1 Current Limiting Fuse Size 1 Starter ©2004 Cooper Bussmann
  • 32. Test 3 Still Photo ©2004 Cooper Bussmann
  • 33. Test 3 Still Photo ©2004 Cooper Bussmann
  • 34. Test 3 Still Photo ©2004 Cooper Bussmann
  • 35. Test 3 Still Photo ©2004 Cooper Bussmann
  • 36. Results: Test No.3 Sound 133 db @ 2 ft. T2 o o 62 C/143.6 F T3 (No Change From Ambient) P1 504 lbs/ft2 T1 > 175 C/ o 347 F > Indicates Meter Pegged ©2004 Cooper Bussmann o
  • 37. Test No. 1 22.6 KA Symmetrical Available Fault Current @ 480V, 3 Phase 601A. Class L Current Limiting Fuse 30A RK-1 Current Limiting Fuse Fault Initiated on Load Side of 30A Fuse ©2004 Cooper Bussmann Size 1 Starter
  • 39. Test 1 Still Photo ©2004 Cooper Bussmann
  • 40. Test 1 Still Photo ©2004 Cooper Bussmann
  • 41. Test 1 Still Photo ©2004 Cooper Bussmann
  • 42. Test 1 Still Photo ©2004 Cooper Bussmann
  • 43. Results: Test No.1 Sound (No Change From Ambient) T2 (No Change From Ambient) T3 (No Change From Ambient) ©2004 Cooper Bussmann P1 (No Change From Ambient) T1 (No Change From Ambient)
  • 44. Current-Limitation: Arc Energy Reduction Test 4 Non-Current Limiting Test 3 Reduced Fault Current via Current-Limitation ©2004 Cooper Bussmann Test 1
  • 45. Summary • Shock, arc flash and arc blast are the three recognized electrical hazards • Shock injuries result from electrical current flowing through the body • Arcing faults can generate enormous amounts of energy • Injuries from arcing faults are a result of the tremendous heat and pressure generated ©2004 Cooper Bussmann
  • 46. Summary • Overcurrent protective devices have an impact on the two most important variables of arc flash hazards: – Time (speed of the OCPD) – Fault current magnitude (current-limitation may help reduce) • Current-limitation may be able to significantly reduce the energy released during arcing faults ©2004 Cooper Bussmann

Editor's Notes

  1. Intended to be used with Safety BASICs handbook – starting on page 14
  2. Electricity has become such an integral part of our society that it often is taken for granted. Yet, electricity remains a very dangerous hazard for people working on or near it. Many electrical circuits do not directly pose serious shock or burn hazards by themselves. However, many of these circuits are found adjacent to circuits with potentially lethal levels of energy. Even a minor shock can cause a worker to rebound into a lethal circuit or cause the worker to drop a tool into the circuit. Involuntary reaction to a shock might also result in bruises, bone fractures, and even death from collisions or falls.
  3. The following are recognized as common electrical hazards that can cause injury, and even death, while a person works on or near electrical equipment and systems: • Electrical shock • Electrical burns from contact (current) and flash (radiant) • Arc-blast impact from expanding air and vaporized materials
  4. The equation helps in the understanding of both the hazard of shock and short circuit currents. A bolted short circuit current has the phase conductors in contact (bolted) and the short circuit current is dissipated throughout all the circuit components. This type fault can create major mechanical and thermal stresses on all the components. If a component does not have sufficient short circuit ratings it may be damaged or rupture. An arcing fault is where two conductors, or a conductor to ground, faults but through air. An arc is created – i.e. the fault current path is through air. In this type of fault, most of the energy is dissipated in the arc, releasing tremendous amounts of thermal energy. Later in the slides there is a model of an arcing fault. Workers can get injured when a bolted fault occurs if a component explodes. A major hazard occurs if a worker is near electrical equipment and an arcing fault occurs. The tremendous amount of energy that is released in the arcing can be lethal. Arcing faults can occur if a worker is working on energized equipment and a metal part drops across live phase conductors.
  5. More than 30,000 non-fatal electrical shock incidents are estimated to occur each year. The National Safety Council estimates that from 600 to 1,000 people die every year from electrocution. Of those killed with voltages less than 600V, nearly half were working on exposed energized circuits at the time the fatal injury occurred. Electrocution continues to rank as the fourth highest cause of industrial fatalities (behind traffic, violence/homicide, and construction incidents). Most personnel are aware of the danger of electrical shock, even electrocution. It is the one electrical hazard around which most electrical safety standards have been built. However, few really understand just how little current is required to cause injury, even death. Actually, the current drawn by a 7 W, 120V lamp, passing across the chest, from hand-to-hand or hand-to-foot, is enough to cause fatal electrocution. The effects of electric current on the human body depend on the following: • Circuit characteristics (current, resistance, frequency, and voltage) • Contact resistance and internal resistance of the body • The current’s pathway through the body, determined by contact location and internal body chemistry • Duration of the contact • Environmental conditions that affect the body’s contact resistance
  6. To understand the currents possible in the human body, it is important to understand the contact resistance of skin (see Table V(A)(1) page 15). The skin’s resistance can change as a function of the moisture present in its external and internal layers, with changes due to such factors as ambient temperatures, humidity, fright, and anxiety. Body tissue, vital organs, blood vessels and nerve (non-fat) tissue in the human body contain water and electrolytes, and are highly conductive with limited resistance to alternating electrical current. As the resistance of the skin is broken down by electrical current, resistance drops and current levels increase.
  7. The human body could be considered as a resistor with hand-to-hand resistance (R) of only 1,000 Ohms. The voltage (V) determines the amount of current passing through the body. While 1,000 Ohms might appear to be low, even lower levels can be approached by a person with sweat soaked cloth gloves on both hands and a full-hand grasp of a large, energized conductor and a grounded pipe or conduit. Moreover, cuts, abrasions or blisters on hands can negate skin resistance, leaving only internal body resistance to oppose current flow. A circuit in the range of 50V could be dangerous in this instance. Ohm’s Law: I (amps) = V (volts) / R (ohms) Example 1: I = 480 / 1000 = 480mA (or 0.480A) Product standards consider 4 to 6mA to be the safe upper limit for children and adults (hence the reason a 5-milliamp-rated GFCI circuit). Note: GFCIs do not protect against a line-to-neutral or a line-to-line shock.
  8. Electrical currents can cause muscles to lock up, resulting in an inability of a person to release his or her grip from the current source. This is known as the “let-go” threshold current. At 60Hz, most females have a “let-go” limit of about 6 milliamperes (mA), with an average of 10.5mA. Most males have a “let-go” limit above 9mA, with an average of 15.5mA. (These limits are based on smaller average size of females. Therefore, a small man could have a lower limit, or a larger woman a higher limit.) Sensitivity, and potential injury, also increase with time. A victim who cannot “let go” of a current source is much more likely to be electrocuted than someone whose reaction removes them from the circuit more quickly. The victim who is exposed for only a fraction of a second is less likely to sustain an injury.
  9. The most damaging path for electrical current is through the chest cavity (see A and D in Figure V(A) page 16) and head. In short, any prolonged exposure to 60Hz current of 10mA or more might be fatal. Fatal ventricular fibrillation of the heart (stopping of rhythmic pumping action) can be initiated by a current flow of as little as several milliamps. These injuries can cause fatalities resulting from either direct paralysis of the respiratory system, failure of the rhythmic heart pumping action, or immediate heart stoppage. During fibrillation, the victim might become unconscious. On the other hand, he or she might be conscious, deny needing help, walk a few feet, and then collapse. Death could occur within a few minutes or take hours. Prompt medical attention is needed for anyone receiving electrical shock. Many of these people can be saved, provided they receive proper medical treatment, including cardiopulmonary resuscitation (CPR) with Automatic External Defibrillation (AED) devices quickly.
  10. Think of electrical shock injuries as “icebergs,” where most of the injury is unseen, below the surface. Entrance and exit wounds are usually coagulated areas and might have some charring, or these areas might be missing, having “exploded” away from the body due to the level of energy present. The smaller the area of contact, the greater the heat produced. For a given current, damage in the limbs might be the greatest, due to the higher current flux per unit of cross-sectional area. Within the body, the current can burn internal body parts in its path. This type of injury might be difficult to diagnose, as the only initial signs of injury are the entry and exit wounds. Damage to the internal tissues, while not apparent immediately, might cause delayed internal tissue swelling and irritation. Prompt medical attention can minimize possible loss of blood circulation and the potential for amputation of the affected extremity, and can prevent death.
  11. 80% of electrical injuries are burns - source: C. M. Kent and H. L Floyd, “Managing the Other Electrical Hazard: Electrical Arcs,” American Society of Safety Engineers Forum titles “Safety Technology 2000,” Orlando, Florida, June 19 ,1995 Only recently has the industry started to recognize arc-fault energies as an electrical hazard. Only recently has the industry started to develop safety standards to address them. In addition to severe burns to exposed skin, the heat generated from the arc energy can cause molten metal to be thrown from the arc. If inhaled, severe damage to the lungs will occur. The bright flash of light from an arc can also cause eye damage.
  12. Injury can occur from: Impact with objects shrapnel from damaged electrical circuit components falls from ladders impact with solid objects as victim is thrown from arc fault area hearing damage concussion
  13. Let’s examine the two types of faults. (Mouse click to trace current flow of bolted fault.) A bolted short circuit is characterized by the conductors of different potential being “bolted” together. Remember, for all practical purposes, the load is no longer in the circuit. (Mouse click to trace current flow of an arcing fault.) An arcing fault is characterized by the electric current going through the air. In the case of an arcing fault the air contains contaminates that permits the electrical potential to break down the normally good air insulation. An arcing fault has current flowing through the air. An arc quickly vaporizes the normal conductors at the points of the arc and this conductive vapor adds to the conductive nature of the “air path”. Either type of fault can be devastating since the energy of the source is only abated by the resistance (impedance) of the circuit components. The bolted fault dissipates the large amount of energy along the path of the circuit components. The smaller, higher resistance components take more of the stress. With an arcing fault, the circuit components also take on significant stress since a large fault current is flowing through them. However, a major difference is that a tremendous amount of energy is released at the point of the arc. One last point. In both cases the tremendous release of damaging energy can occur in a few thousandths of a second.
  14. Following is a graphical model of an arcing fault and the physical consequences that can occur. The unique aspect of an arcing fault is that the fault current flows through the air between conductors or a conductor(s) and a grounded part. The arc has an associated arc voltage because there is arc impedance. The product of the fault current and arc voltage in a concentrated area, results in tremendous energy being released in several forms. The resulting energies can be in the form of radiant heat, intense light, and tremendous pressures. Intense radiant heat from the arcing source travels at the speed of light. The temperature of the arc terminals can reach approximately 35,000°F, or about four times as hot as the surface of the sun. No material on earth can withstand this temperature. The high arc temperature changes the state of conductors from solid to hot molten metal and to vapor. The immediate vaporization of the conductors is an explosive change in state from solid to vapor. Copper vapor expands to 67,000 times the volume of solid copper. Because of the expansive vaporization of conductive metal, a line-to-line or line-to-ground arcing fault can escalate into a three-phase arcing fault in less than a thousandth of a second. The extremely high release of thermal energy superheats the immediate surrounding air. The air also expands in an explosive manner. The rapid vaporization of conductors and superheating of air result in high pressure waves and a conductive plasma cloud, that if large enough, can engulf a person. The thermal shock and pressures can violently destroy circuit components. The pressure waves hurl the destroyed, fragmented components like shrapnel at high velocity; shrapnel fragments can be expelled in excess of 700 miles-per-hour. Molten metal droplets at high temperatures typically are blown out from the event due to the pressure waves.
  15. 35,000 degree F can occur at the arc tips. 35, 000 degrees is approximately four times the temperature on the surface of the sun. This high temperature vaporizes and melts the adjacent copper conductors and other materials. The high temperatures and molten metal can ignite improper clothing such as polyesters. Remember the thresholds for second and third degree burns. Later actual tests are shown that capture the resulting temperatures from arc faults on simulated workers. These values will be important to compare to the results measured from the tests.
  16. The vaporization of the metals and super heating of air creates a pressure blast. This blast can exert tremendous pressures on equipment and people. Medical research has shown that ear drums can rupture at the threshold levels shown. The angle of the ear opening can alter the effects. Lung damage such as collapse can occur at the threshold level shown. Remember the eardrum and lung damage thresholds to compare to results of upcoming tests.
  17. If an arcing fault occurs while a worker is in close proximity, the survivability of the worker is mostly dependent upon (1) the characteristics of the overcurrent protective devices, (2) the arc-fault current, and (3) precautions the worker has taken prior to the event, such as wearing personal protective equipment appropriate for the hazard. The selection and performance of overcurrent protective devices play a significant role in electrical safety. Extensive tests and analysis by industry have shown that the energy released during an arcing fault is related to two characteristics of the overcurrent protective device protecting the affected circuit: The time it takes the overcurrent protective device to open. The faster the fault is cleared by the overcurrent protective device, the lower the energy released. 2. The amount of fault current the overcurrent protective device lets through. Current-limiting overcurrent protective devices may reduce the current let-through (when the fault current is within the current-limiting range of the overcurrent protective device) and can reduce the energy released. Lowering the energy released is better for both worker safety and equipment protection. The videos and recorded sensor readings from actual arcing fault tests illustrate this point very well.
  18. An ad hoc electrical safety working group within the IEEE Petroleum and Chemical Industry Committee conducted these tests to investigate arc-fault hazards. These tests and others are detailed in “Staged Tests Increase Awareness of Arc-Fault Hazards in Electrical Equipment,” IEEE Petroleum and Chemical Industry Conference Record, September 1997, pp. 313-322. This paper can be found at www.bussmann.com under Services/Safety BASICs. One finding of this IEEE paper is that current-limiting overcurrent protective devices reduce damage and arc-fault energy (provided the fault current is within the current- limiting range).
  19. - View of the test area Testing in both combination starters(left) and MCC(rear) Mannequins to simulate workers Mannequins with sensors were used to capture data
  20. This is the first test we will review. It is Test 4. The fault is on the line side of the 30A branch overcurrent protective device (OCPD) The feeder OCPD is the device that will be called upon to react to this overcurrent. The feeder OCPD used in this test is a power circuit breaker with a short time delay (there is no instantaneous trip). Short time delay (STD) devices are used to achieve coordination between the branch and feeder OCP devices. Where continuity of service is important or critical, and where using circuit breakers, the feeder and main circuit breakers must be equipped with short time delay options. A short time delay option allows a circuit breaker to intentionally hold off opening when a fault occurs; this allows downstream devices to clear faults on their circuits without opening the circuit breaker with the STD. However, when a fault does occur on the circuit of the circuit breaker with a short time delay, the fault is permitted to flow for the time of the short time delay settings. This can allow a great deal of energy to flow while the short time delay times out. Industrial plants and commercial buildings that have circuit breakers and that require coordination, typically will have short time delays on their feeder and main circuit breakers. The users of the IEEE committee that participated in these tests typically use STD’s on their feeder circuits when they use circuit breakers as their feeder OCPD’s. In other words, this is a common application of circuit breakers. Notice the fault is created on the line side of the 30 amp fuse. So the 30 amp fuse is not in the faulted circuit. The fault has to be cleared by the 640 amp feeder circuit breaker.
  21. - Mention the noise level with this video This is a video in normal speed. (This video file is linked to this PowerPoint slide. If you keep this PowerPoint presentation and video file in the same folder they should run alright. If you are showing this on a video projector connected to your computer, you may need to transfer video from your laptop screen to video projector by using the appropriate “function keys” to toggle between laptop screen and the port to the video projector.) Move mouse over picture until the hand appears and then click on the picture. NOTE: Have Volume turned up on computer to display sound levels!
  22. Test set up prior to initiation of arc-fault. Mannequin nearest to combination motor starter is equipped with sensors. The mannequins have been propped up with 2x4’s. The closest mannequin’s hand is positioned near the screwdriver used to initiate the arcing fault.
  23. Note the intense light and plasma.
  24. Notice the wire way cover is blown off the wall and moving towards the mannequin’s head. Also not the molten metal spray.
  25. Now the wire way cover can be seen hitting the mannequin in the head.
  26. The closest mannequin is again engulfed in the plasma as the arc releases more energy.
  27. The mannequin closest to the arcing fault had sensors affixed to specific parts. The readings from the test can provide great insight to the hazards of arcing faults. Sound, pressure, and temperature measurements on the worker were recorded > 2160 lbs/sq. ft would damage the lungs and eardrums(remember thresholds) Temp (T1) and (T2) were well above the 3rd degree burn level of 205 deg F Sound intensity level well above shotgun level Temp (T3) read under cotton shirt. The shirt provided a good barrier against the high level temperatures The recorded results show that bare skin of the hand and neck would have incurred very serious burns since the recorders were pegged well above the incurable burn level. The pressure on the chest also was very severe. The pressure pegged the meter so it was beyond the threshold for lung damage.
  28. Test # 3 is the same as Test # 4 except the feeder overcurrent device is now a 601 ampere current-limiting overcurrent device (601 A Class L fuse). The fault again occurs on the line side of the 30 amp branch circuit OCPD.
  29. - Notice the dramatic reduction in activity
  30. There is very little energy released, only a small spatter of metal.
  31. Sound, pressure, and temperature measurements on the worker, were recorded Pressure dropped below level of eardrum rupture Temp (T1) still above the 3rd degree burn level of 205 deg F Temp (T2) dropped below second degree burn level (175 deg F) Sound intensity level at shotgun level The results when compared to the prior Test 4 are significantly less. It shows the benefit of limiting the current in magnitude and time (achieved in this test by 601 current limiting fuses).
  32. Next is Test 1. This is the same test circuit. However, the difference is that the arcing fault is created on the loadside of the 30 amp current limiting fuses. Test no. 1 had 22,600 amps available at 480 volts Test number 1 is similar to tests 3 & 4 except that the short is created on the load side of a 30 ampere current limiting Class RK1 fuse. Why is this important?(Now the branch device is relied upon to clear the fault) Even more current limitation is utilized in this test
  33. - Dramatic reduction in activity
  34. Measurements of sound, pressure, and temperature were minimal. Drastic reduction of time and energy limited activity down to the point that no changes from ambient were detected.
  35. The approximate wave forms for tests 4, 3, and 1. The energy released from an arc fault is related to the amount of current that flows and the time duration. Current-limiting overcurrent protective devices can substantially reduce the energy. Test 4 let through the full fault current and did not clear for six cycles. Test 3, with 601 amp current limiting fuses, limited the current let thru and cleared in less than a ½ cycle. Therefore the energy released was less than Test 4. Test 1, with a 30 amp current limiting fuse, was much more current limiting than even Test 3 results. This is due to the the high degree of current limitation of a 30 amp fuse and it cleared in less than a ¼ cycle.