ANSI/TIA-568-C Series

Herbert V. Congdon II, PE
Tyco Electronics
568-C – Why?

• ANSI mandates a 5-year life for published standards
 – Revised, reaffirmed or withdrawn
• TIA-568B published May 2001
 – >5 years ago
• Many addenda since publication
 – 6 addenda to 568-B.1
 – 10 addenda to 568-B.2
 – 1 addendum to 568-B.3




                                                        page 2 / October 16, 2008
568-C Series Documents

• One New Standard (568-C.0)
 – 568-C.0 – generic structured cabling – RELEASED (October)
• Three Revisions
 – 568-C.1 – commercial building cabling – RELEASED (October)
  • Office-oriented buildings
 – 568-C.2 – copper cabling components – expected in 2009
 – 568-C.3 – fiber cabling components - PUBLISHED




                                                       page 3 / October 16, 2008
Improvement Opportunity

• Complaint: Duplicated information
 – Cause: Synchronizing and updating multiple documents is
   complicated
 – Solution: Centralize common information




                                                        page 4 / October 16, 2008
Improvement Opportunity

• Complaint: Lengthy development of new Standards
 – Cause: Creating new premise Standards is unnecessarily repetitive
 – Solution: Establish common information in one document




                                                         page 5 / October 16, 2008
Improvement Opportunity

• Complaint: Gaps in Standards coverage
 – Cause: Standards tend to be too specific in scope
  • Result: 568-B (for office-oriented commercial buildings) applied to
    non-office-oriented locations
 – Solution: Start with common information applicable everywhere,
  then manage exceptions and allowances specific to the premise




                                                           page 6 / October 16, 2008
Solution: A Generic Cabling Standard

• A new standard for generic cabling - 568-C.0, Generic
 Telecommunications Cabling for Customer Premises
 – The foundation for future Standards
 – The cabling Standard when documents specific to a premises are
   not available
 – Consolidates common information in one document
   • Content from 568-B.1 & addenda split between C.0 and C.1




                                                          page 7 / October 16, 2008
Splitting 568-B.1


            568-B.1
            (94 pgs)




568-C.0                568-C.1
Generic                CBC
(~60 pgs)              (~35 pgs)


                        page 8 / October 16, 2008
Other TR-42 Documents

• Starting the processes to make other documents more generic
 – Ex: removing commercial building focus from Pathways and Spaces
• Segregating documents into three categories:
 – Common Standards – generically applicable documents
 – Premise Standards – specific to one type of premise
 – Component Standards – performance requirement
• Intended Customers
 – End-users, contractors, designers: Common and Premise Standards
 – Manufacturers: Component Standards




                                                         page 9 / October 16, 2008
• Three Document Types
 – Common Standards
   • Generic
   • Pathways & Spaces
   • Administration, etc.
 – Premise Standards
   • Commercial Building
   • Residential
   • Data Centers, etc.
 – Component Standards
   • Copper
   • Optical Fiber


                            page 10 / October 16, 2008
Looking Forward


• Over the next 3-5 years
 – Other premises Standards will be revised to acknowledge 568-C.0
   • List appropriate exceptions and allowances
 – Existing common Standards modified to broaden scope
   • Replace “commercial building” focus and terminology
   • Become more generic in nature
• New Standards will be built on the foundation of 568-C.0




                                                             page 11 / October 16, 2008
568-C.0 Generic Cabling
568-C.0 Generic Cabling

• 568-C.0 Establishes How a Star Network Topology Is Constructed
 – Does not need to be repeated in every document
 – Premise standards define appropriate allowances and exceptions
• 568-C.0 Establishes Cabling Requirements
 – Applicable to all premise Standards unless noted as an exception or
  allowance
• 568-C.0 Uses Generic Cabling Nomenclature
 – Cabling Subsystem 1, Cabling Subsystem 2 and Cabling Subsystem 3
 – Distributor A, Distributor B, Distributor C and Equipment Outlet
 – Specific nomenclature assigned in premise Standards




                                                           page 13 / October 16, 2008
568-C.0 - Generic Cabling Topology

                                                         DC

                                Cabling                                                Cabling
                            Subsystem 3                                                Subsystem 3


  Part 1 of Figure 2                           DB                  DB


                                Cabling
                            Subsystem 2


                                               DA        DA                            Cabling
                                                                                       Subsystem 1

                                Cabling
                            Subsystem 1
Legend:
EO      Equipment Outlet                  EO   EO   EO   EO   EO   EO        EO
DA      Distributor A
DB      Distributor B
DC      Distributor C
        Optional cabling

        Optional consolidation point



                                                                        page 14 / October 16, 2008
568-C.0 - Generic Cabling Topology

                                                      DC



      Part 2 of Figure 2
                                            Cabling
Legend:                                Subsystem 3
EO      Equipment Outlet
DA      Distributor A                                                       Cabling
DB      Distributor B                                                       Subsystem 1
DC      Distributor C
        Optional cabling
                                                      DB
        Optional consolidation point

                                            Cabling
                                       Subsystem 1

                                                      EO   EO   EO




                                                                page 15 / October 16, 2008
568-C.0 – Generic Cabling

– 568-C.0 Incorporates some of the 568-B.1 Addenda
 • Centralized cabling, patch cord bend radius, etc.
– 568-C.0 Collected Common Information from 568-B.1 and others
 • Choosing media
 • Cabling lengths
 • Bonding and grounding
 • Polarity
 • Installation requirements
 • Application support tables
 • Optical fiber testing & limits
   – NOTE: balanced twisted-pair testing and limits will be in 568-C.2



                                                         page 16 / October 16, 2008
568-C.0 – Technical Changes

• Installation minimum bend radius for balanced twisted-pair cable
 – Changed to 4x cable OD for both shielded and unshielded
   • Note: Worst case minimum bend radius is now 1.5 inches (not 1.0
    inch) since the largest allowable cable OD is 0.354 inches (per
    568-B.2-11)
• Adds Augmented Category 6 (shielded and unshielded) as a
 recognized medium
• Patch cable bend radius for balanced twisted-pair cabling
 – Changed to “1x cable OD” from “0.25 inches”
• Maximum untwist for Category 6A cable termination
 – Added and set to 13mm (same as Category 6)



                                                          page 17 / October 16, 2008
568-C.0 – Generic Cabling - Status

• 2nd default ballot closed in August 2008
   • Approve & Approve with comments (21)
   • Do Not Approve (0)
 – Comments were resolved in August teleconference
   • ~1 technical comment, 1 editorial comment
 – Motion to release for publication was unanimously approved
 – TR-42 Plenary approval for publication expected in early October




                                                         page 18 / October 16, 2008
568-C.1 Commercial Building Cabling
568-C.1 – Commercial Building

• Builds on information in 568-C.0
• Contains appropriate allowances and exceptions specific to office-
 oriented commercial building cabling
• Retains use of 568-B.1 nomenclature
   • Main Cross-connect (Distributor C in 568-C.0)
   • Interbuilding backbone cabling (Cabling Subsystem 3 in 568-C.0)
   • Intermediate Cross-connect (Distributor B in 568-C.0)
   • Intrabuilding backbone cabling (Cabling Subsystem 2 in 568-C.0)
   • Horizontal Cross-connect (Distributor A in 568-C.0)
   • Horizontal cabling (Cabling Subsystem 1 in 568-C.0)
   • The Telecommunications Outlet (Equipment Outlet in 568-C.0)



                                                             page 20 / October 16, 2008
568-C.1 – Commercial Building Cabling

                                                                       MC

                                        Backbone                                                      Backbone
                                          Cabling                                                     Cabling


                                                             IC                   IC
  Part 1 of Figure 5
                                        Backbone
                                          Cabling


                                                             HC        HC                             Horizontal
                                                                                                      Cabling

                                        Horizontal
                                          Cabling

                                                        TO   TO   TO   TO   TO    TO        TO
Legend:
TO       Telecommunications Outlet (Equipment Outlet)
HC      Horizontal Cross-connect (Distributor A)
IC      Intermediate Cross-connect (Distributor B)
MC      Main Cross-connect (Distributor C)
         Optional cabling

         Optional consolidation point


                                                                                 page 21 / October 16, 2008
568-C.1 – Commercial Building Cabling

                                                                     MC



   Part 2 of Figure 5
                                                        Backbone
Legend:                                                   Cabling
TO       Telecommunications Outlet (Equipment Outlet)
HC      Horizontal Cross-connect (Distributor A)                                           Horizontal
IC      Intermediate Cross-connect (Distributor B)                                         Cabling
MC      Main Cross-connect (Distributor C)
        Optional cabling
                                                                     HC
         Optional consolidation point

                                                        Horizontal
                                                          Cabling

                                                                     TO   TO   TO




                                                                               page 22 / October 16, 2008
568-C.1 – Technical Changes

• From 568-B.1 Addenda
 – Inclusion of category 6 balanced twisted-pair cabling
 – Inclusion of augmented category 6 twisted-pair cabling
 – Inclusion of 850 nm laser-optimized 50/125 µm MM fiber
 – Inclusion of telecommunications enclosures (TEs)
• Inclusion of centralized cabling in the main body of document
• A recommendation to select 850 nm laser-optimized 50/125 µm as the
 multimode fiber for commercial buildings




                                                            page 23 / October 16, 2008
568-C.1 – Technical Changes

• Removal of common information (this was moved into 568-C.0)
• Removal of 150-Ohm STP cabling
• Removal of category 5 cabling
• Removal of 50-ohm and 75-ohm coaxial cabling
• Removal of balanced twisted-pair cabling performance and test
 requirements (these will be in the ANSI/TIA-568-C.2 document)
 – NOTE: optical fiber cabling performance and test requirements in
   568-C.0




                                                         page 24 / October 16, 2008
568-C.1 – Commercial Building

• 2nd default ballot closed in August
   • Approve & Approve with Comments (22)
   • Do Not Approve (0)
 – Comments resolution completed in February
   • No technical comments, 1 editorial comment
 – Motion to release for publication was unanimously approved
 – TR-42 Plenary approval for publication expected in early October




                                                          page 25 / October 16, 2008
568-C.2 Balanced Twisted-pair
Components
568-C.2 Copper Cabling Components

• Editing committee created the first draft
 – Incorporates Cat 3, Cat 5e, Cat 6 and Cat 6A
• 2nd committee ballot closed in July
   • Document size is 221 pages (down from over 400!)
 – 7 Approve, 5 Do Not Approve
• Interim meeting in August to review document comments
 – 175 Technical Comments, 76 Editorial Comments
• Comment resolution completed in August
 – A 1st industry (45-day) ballot was issued
   • Interim meeting scheduled for December to review comments
• Plans to publish by mid-2009 still viable



                                                          page 27 / October 16, 2008
568-C.3 Optical Fiber Components
568-C.3 – Optical Cabling Components

• Released for Publication
 – Released by ANSI in July 2008




                                   page 29 / October 16, 2008
568-C.3 Purpose

• Serve as a stand-alone Standard
 – No longer tied to commercial building cabling
• Specify component transmission performance
 – Cable, connectivity and cords
• Intended to be used by
 – Manufacturers (primarily)
 – May also be of use to users, designers and installers (secondarily)
• Common reference for optical fiber components in all TR-42
 standards




                                                           page 30 / October 16, 2008
Table of Contents (Summary)

• Scope
• Normative References
• Definitions, Abbreviations, Acronyms & Units of Measure
• Optical Fiber Cable
• Connecting Hardware
• Optical Fiber Patch Cords & Transitions
• Annex A: Connector Performance Specifications
• Annex B: Bibliography & References


• Note: Field testing and limits in 568-C.0




                                                            page 31 / October 16, 2008
Documents Incorporated into 568-C.3

• ANSI/TIA/EIA-568-B.3, Optical Fiber Cabling Component Standard
• ANSI/TIA/EIA-568-B.3-1, Additional Transmission Performance
 Specifications for 50/125 µm Optical Fiber Cables
• Some information from ANSI/TIA-568-B.1-7, Guidelines for
 Maintaining Polarity Using Array Connectors
 – Component requirements – how to make them
 – Note: System requirements – how to use them – in 568-C.0




                                                        page 32 / October 16, 2008
Fiber Nomenclature

• Transmission performance parameters (Table 1) includes references
 to ISO nomenclature (see example below)
 – OM1, OM2 and OM3
 – OS1 and OS2




“850 nm Laser-Optimized 50/125 µm Multimode
           TIA 492AAAC (OM3)”



                                                       page 33 / October 16, 2008
Cable Requirements

• Cabled Fiber Performance Requirements
 – Attenuation, Bandwidth
• References for optical fiber cable requirements:
 – TIA 472C000-B/ICEA S-83-596-2001, Fiber Optic Premises
   Distribution Cable
 – TIA 472D000-B/ICEA S-87-640-1999, Fiber Optic Outside Plant
   Communications Cable
 – TIA 472E000/ICEA S-104-696-2003, Standard For Indoor-Outdoor
   Optical Cable
 – TIA 472F000/ICEA S-110-717-2003, Optical Drop Cables




                                                      page 34 / October 16, 2008
Connectors and Adapters

• Duplex Connectors
 – Shall meet the requirements of the corresponding TIA Fiber Optic
   Connector Intermateability Standard (FOCIS) and Annex A
   Requirements
• Array Connectors
 – Shall meet the requirements of the corresponding TIA Fiber Optic
   Connector Intermateability Standard (FOCIS) and Annex A
   Requirements
• Keying and fiber positions
• Adapters
 – Type A (key-up to key-down) and Type B (key-up to key-up)



                                                         page 35 / October 16, 2008
Connectors: Strain Relief and Adapter
Housing Colors
• Unless color coding is used for some other purpose, the connector
 strain relief and adapter housing should be identifiable by the
 following colors:
 – 850nm laser-optimized 50/125µm fiber – aqua
 – 50/125µm fiber – black
 – 62.5/125µm fiber – beige
 – Single-mode fiber – blue
 – Angled contact ferrule single-mode connectors – green




                                                            page 36 / October 16, 2008
Connectors: Plug Body Colors

• In addition, unless color coding is used for some other purpose, the
 connector plug body should be generically identified by the following
 colors, where possible:
 – Multimode – beige, black or aqua
 – Single-mode – blue
 – Angled contact ferrule single-mode connectors – green




                                                           page 37 / October 16, 2008
Optical Fiber Patch Cords

• Simplex Patch Cords have been included
• Duplex Patch Cords: Two Types
 – A-to-B (the “normal” patch cord)




                 A-to-B duplex optical fiber patch cord




                                                          page 38 / October 16, 2008
Optical Fiber Patch Cords

• Duplex Patch Cords: Two Types
 – A-to-A (special use patch cord)




                 A-to-A duplex optical fiber patch cord




                                                          page 39 / October 16, 2008
Optical Fiber Patch Cords

• Array
 – Three array patch cord constructions are included (others are
   allowed)
   • Type A: Fibers positioned sequentially (1 to 1, 2 to 2,…12 to 12)
   • Type B: Fibers positioned in reverse sequence (1 to 12, 2 to
    11,…12 to 1)
   • Type C: Fibers positioned in flipped pairs (1 to 2, 2 to 1,…11 to 12,
    12 to 11)
 – Transitions (or “break outs”) position fibers sequentially (1 to 1, 2 to
   2,…12 to 12)


• Note: Use of these components is covered in 568-C.0


                                                              page 40 / October 16, 2008
Annex A: Mechanical and Environmental
Testing for Connecting Hardware
• Normative
• Optical fiber connector performance specifications
 – required number of test samples
 – performance requirements
• Annex A now a subset of IEC Testing
• IEC Compliance incorporates TIA 568-C.3 Annex A Compliance
 – TIA compliance does not mean IEC compliance




                                                       page 41 / October 16, 2008
Purchasing Standards
Purchasing Standards

• TIA releases published documents to Global Engineering Documents
• Global Engineering Documents acts as a clearing house for order
 processing for multiple Standards Developing Organizations (SDOs)
• News:
 – Now Global Engineering Documents is “IHS”
 – www.ihs.com




                                                        page 43 / October 16, 2008
800-553-0938
                                  www.ampnetconnect.com
                             networking.help@tycoelectronics.com


AMP, AMP NETCONNECT, NETCONNECT and TYCO are trademarks.

More Related Content

What's hot

FTTX with Passive Optical Networks
FTTX with Passive Optical NetworksFTTX with Passive Optical Networks
FTTX with Passive Optical Networks
Anuradha Udunuwara
 
Arquitecturas redes catv
Arquitecturas redes catvArquitecturas redes catv
Arquitecturas redes catv
Julio Yugar
 

What's hot (20)

Concepts of optical fiber communication
Concepts of optical fiber communicationConcepts of optical fiber communication
Concepts of optical fiber communication
 
Economic of FTTH - Open Access Concept
Economic of FTTH - Open Access ConceptEconomic of FTTH - Open Access Concept
Economic of FTTH - Open Access Concept
 
GPON
GPONGPON
GPON
 
optical fiber communication system
optical fiber communication systemoptical fiber communication system
optical fiber communication system
 
UPLINK, DOWNLINK AND OVERALL LINK PERFORMANCE INTER-SATELLITE LINKS
UPLINK, DOWNLINK ANDOVERALL LINK PERFORMANCE INTER-SATELLITE LINKSUPLINK, DOWNLINK ANDOVERALL LINK PERFORMANCE INTER-SATELLITE LINKS
UPLINK, DOWNLINK AND OVERALL LINK PERFORMANCE INTER-SATELLITE LINKS
 
bharat-electronics-limited
bharat-electronics-limitedbharat-electronics-limited
bharat-electronics-limited
 
FTTX with Passive Optical Networks
FTTX with Passive Optical NetworksFTTX with Passive Optical Networks
FTTX with Passive Optical Networks
 
Mimo [new]
Mimo [new]Mimo [new]
Mimo [new]
 
Arquitecturas redes catv
Arquitecturas redes catvArquitecturas redes catv
Arquitecturas redes catv
 
GPON - Gigabit Pasive Optical Network
GPON - Gigabit Pasive Optical NetworkGPON - Gigabit Pasive Optical Network
GPON - Gigabit Pasive Optical Network
 
FTTH Basics
FTTH BasicsFTTH Basics
FTTH Basics
 
Medical appplication of Fiber optics
Medical appplication of Fiber opticsMedical appplication of Fiber optics
Medical appplication of Fiber optics
 
Webinar DataNet BICSI "Redes ópticas pasivas: un nuevo horizonte al cableado ...
Webinar DataNet BICSI "Redes ópticas pasivas: un nuevo horizonte al cableado ...Webinar DataNet BICSI "Redes ópticas pasivas: un nuevo horizonte al cableado ...
Webinar DataNet BICSI "Redes ópticas pasivas: un nuevo horizonte al cableado ...
 
Wdm
WdmWdm
Wdm
 
Fiber Optic Cable Installation and Handling Instructions
Fiber Optic Cable Installation and Handling InstructionsFiber Optic Cable Installation and Handling Instructions
Fiber Optic Cable Installation and Handling Instructions
 
Televes. curso ict2
Televes. curso ict2Televes. curso ict2
Televes. curso ict2
 
Packets never lie: An in-depth overview of 802.11 frames
Packets never lie: An in-depth overview of 802.11 framesPackets never lie: An in-depth overview of 802.11 frames
Packets never lie: An in-depth overview of 802.11 frames
 
Optical Wireless Communications - from the space to the chip.
Optical Wireless Communications - from the space to the chip.Optical Wireless Communications - from the space to the chip.
Optical Wireless Communications - from the space to the chip.
 
Inject precise synchronization into open compute servers
Inject precise synchronization into open compute serversInject precise synchronization into open compute servers
Inject precise synchronization into open compute servers
 
Fiber Optics Presentation
Fiber Optics PresentationFiber Optics Presentation
Fiber Optics Presentation
 

Similar to 568 c0 c1_and_c3_overview

120190675 - Hamada Hossam El abadla - Appendix A- 10-2-2023.pptx
120190675 - Hamada Hossam El abadla - Appendix A- 10-2-2023.pptx120190675 - Hamada Hossam El abadla - Appendix A- 10-2-2023.pptx
120190675 - Hamada Hossam El abadla - Appendix A- 10-2-2023.pptx
HamadaElabadla
 

Similar to 568 c0 c1_and_c3_overview (20)

Breaking the rules! bicsi
Breaking the rules! bicsi  Breaking the rules! bicsi
Breaking the rules! bicsi
 
High_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.pptHigh_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.ppt
 
21955068-High-Low-Impedance-BusBar-Protection.ppt
21955068-High-Low-Impedance-BusBar-Protection.ppt21955068-High-Low-Impedance-BusBar-Protection.ppt
21955068-High-Low-Impedance-BusBar-Protection.ppt
 
1 Introduction To Premises Cabling System
1 Introduction To Premises Cabling System1 Introduction To Premises Cabling System
1 Introduction To Premises Cabling System
 
FIBER OPTICS NETWORK DESIGN__.pptx
FIBER OPTICS NETWORK DESIGN__.pptxFIBER OPTICS NETWORK DESIGN__.pptx
FIBER OPTICS NETWORK DESIGN__.pptx
 
SSDACPart B Installation.pdf
SSDACPart B Installation.pdfSSDACPart B Installation.pdf
SSDACPart B Installation.pdf
 
Protección de barra distribuido concentrada
Protección de barra distribuido concentradaProtección de barra distribuido concentrada
Protección de barra distribuido concentrada
 
PON design considerations for FTTH FTTx
PON design considerations for FTTH FTTxPON design considerations for FTTH FTTx
PON design considerations for FTTH FTTx
 
IC Adapters & Interposers | Interconnect Systems ISI - a Molex company
IC Adapters & Interposers | Interconnect Systems ISI - a Molex companyIC Adapters & Interposers | Interconnect Systems ISI - a Molex company
IC Adapters & Interposers | Interconnect Systems ISI - a Molex company
 
TechShanghai2016 - Wireless Power – Ready for Prime Time
TechShanghai2016 - Wireless Power – Ready for Prime TimeTechShanghai2016 - Wireless Power – Ready for Prime Time
TechShanghai2016 - Wireless Power – Ready for Prime Time
 
DesignCon 2019 112-Gbps Electrical Interfaces: An OIF Update on CEI-112G
DesignCon 2019 112-Gbps Electrical Interfaces: An OIF Update on CEI-112GDesignCon 2019 112-Gbps Electrical Interfaces: An OIF Update on CEI-112G
DesignCon 2019 112-Gbps Electrical Interfaces: An OIF Update on CEI-112G
 
IRJET-Modern Z-Source Power Conversion Topologies: A Review
IRJET-Modern Z-Source Power Conversion Topologies: A ReviewIRJET-Modern Z-Source Power Conversion Topologies: A Review
IRJET-Modern Z-Source Power Conversion Topologies: A Review
 
i2c.pdf
i2c.pdfi2c.pdf
i2c.pdf
 
CSS L13 STRUCTURED CABLING SYSTEM
CSS L13 STRUCTURED CABLING SYSTEMCSS L13 STRUCTURED CABLING SYSTEM
CSS L13 STRUCTURED CABLING SYSTEM
 
Specifications
SpecificationsSpecifications
Specifications
 
Ftth pon training guide part iv
Ftth pon training guide part ivFtth pon training guide part iv
Ftth pon training guide part iv
 
PPT_ BXE Unit 2 (1).pptx
PPT_ BXE Unit 2 (1).pptxPPT_ BXE Unit 2 (1).pptx
PPT_ BXE Unit 2 (1).pptx
 
Guide to forms of separation
Guide to forms of separationGuide to forms of separation
Guide to forms of separation
 
120190675 - Hamada Hossam El abadla - Appendix A- 10-2-2023.pptx
120190675 - Hamada Hossam El abadla - Appendix A- 10-2-2023.pptx120190675 - Hamada Hossam El abadla - Appendix A- 10-2-2023.pptx
120190675 - Hamada Hossam El abadla - Appendix A- 10-2-2023.pptx
 
Ia ec200-c-r1
Ia ec200-c-r1Ia ec200-c-r1
Ia ec200-c-r1
 

Recently uploaded

+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
?#DUbAI#??##{{(☎️+971_581248768%)**%*]'#abortion pills for sale in dubai@
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Safe Software
 

Recently uploaded (20)

Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
FWD Group - Insurer Innovation Award 2024
FWD Group - Insurer Innovation Award 2024FWD Group - Insurer Innovation Award 2024
FWD Group - Insurer Innovation Award 2024
 
Manulife - Insurer Transformation Award 2024
Manulife - Insurer Transformation Award 2024Manulife - Insurer Transformation Award 2024
Manulife - Insurer Transformation Award 2024
 
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
 
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, AdobeApidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
 
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
 
Artificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : UncertaintyArtificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : Uncertainty
 
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost SavingRepurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
 
Apidays Singapore 2024 - Scalable LLM APIs for AI and Generative AI Applicati...
Apidays Singapore 2024 - Scalable LLM APIs for AI and Generative AI Applicati...Apidays Singapore 2024 - Scalable LLM APIs for AI and Generative AI Applicati...
Apidays Singapore 2024 - Scalable LLM APIs for AI and Generative AI Applicati...
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
 
Automating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps ScriptAutomating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps Script
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
Ransomware_Q4_2023. The report. [EN].pdf
Ransomware_Q4_2023. The report. [EN].pdfRansomware_Q4_2023. The report. [EN].pdf
Ransomware_Q4_2023. The report. [EN].pdf
 
A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?
 
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
 
A Beginners Guide to Building a RAG App Using Open Source Milvus
A Beginners Guide to Building a RAG App Using Open Source MilvusA Beginners Guide to Building a RAG App Using Open Source Milvus
A Beginners Guide to Building a RAG App Using Open Source Milvus
 

568 c0 c1_and_c3_overview

  • 1. ANSI/TIA-568-C Series Herbert V. Congdon II, PE Tyco Electronics
  • 2. 568-C – Why? • ANSI mandates a 5-year life for published standards – Revised, reaffirmed or withdrawn • TIA-568B published May 2001 – >5 years ago • Many addenda since publication – 6 addenda to 568-B.1 – 10 addenda to 568-B.2 – 1 addendum to 568-B.3 page 2 / October 16, 2008
  • 3. 568-C Series Documents • One New Standard (568-C.0) – 568-C.0 – generic structured cabling – RELEASED (October) • Three Revisions – 568-C.1 – commercial building cabling – RELEASED (October) • Office-oriented buildings – 568-C.2 – copper cabling components – expected in 2009 – 568-C.3 – fiber cabling components - PUBLISHED page 3 / October 16, 2008
  • 4. Improvement Opportunity • Complaint: Duplicated information – Cause: Synchronizing and updating multiple documents is complicated – Solution: Centralize common information page 4 / October 16, 2008
  • 5. Improvement Opportunity • Complaint: Lengthy development of new Standards – Cause: Creating new premise Standards is unnecessarily repetitive – Solution: Establish common information in one document page 5 / October 16, 2008
  • 6. Improvement Opportunity • Complaint: Gaps in Standards coverage – Cause: Standards tend to be too specific in scope • Result: 568-B (for office-oriented commercial buildings) applied to non-office-oriented locations – Solution: Start with common information applicable everywhere, then manage exceptions and allowances specific to the premise page 6 / October 16, 2008
  • 7. Solution: A Generic Cabling Standard • A new standard for generic cabling - 568-C.0, Generic Telecommunications Cabling for Customer Premises – The foundation for future Standards – The cabling Standard when documents specific to a premises are not available – Consolidates common information in one document • Content from 568-B.1 & addenda split between C.0 and C.1 page 7 / October 16, 2008
  • 8. Splitting 568-B.1 568-B.1 (94 pgs) 568-C.0 568-C.1 Generic CBC (~60 pgs) (~35 pgs) page 8 / October 16, 2008
  • 9. Other TR-42 Documents • Starting the processes to make other documents more generic – Ex: removing commercial building focus from Pathways and Spaces • Segregating documents into three categories: – Common Standards – generically applicable documents – Premise Standards – specific to one type of premise – Component Standards – performance requirement • Intended Customers – End-users, contractors, designers: Common and Premise Standards – Manufacturers: Component Standards page 9 / October 16, 2008
  • 10. • Three Document Types – Common Standards • Generic • Pathways & Spaces • Administration, etc. – Premise Standards • Commercial Building • Residential • Data Centers, etc. – Component Standards • Copper • Optical Fiber page 10 / October 16, 2008
  • 11. Looking Forward • Over the next 3-5 years – Other premises Standards will be revised to acknowledge 568-C.0 • List appropriate exceptions and allowances – Existing common Standards modified to broaden scope • Replace “commercial building” focus and terminology • Become more generic in nature • New Standards will be built on the foundation of 568-C.0 page 11 / October 16, 2008
  • 13. 568-C.0 Generic Cabling • 568-C.0 Establishes How a Star Network Topology Is Constructed – Does not need to be repeated in every document – Premise standards define appropriate allowances and exceptions • 568-C.0 Establishes Cabling Requirements – Applicable to all premise Standards unless noted as an exception or allowance • 568-C.0 Uses Generic Cabling Nomenclature – Cabling Subsystem 1, Cabling Subsystem 2 and Cabling Subsystem 3 – Distributor A, Distributor B, Distributor C and Equipment Outlet – Specific nomenclature assigned in premise Standards page 13 / October 16, 2008
  • 14. 568-C.0 - Generic Cabling Topology DC Cabling Cabling Subsystem 3 Subsystem 3 Part 1 of Figure 2 DB DB Cabling Subsystem 2 DA DA Cabling Subsystem 1 Cabling Subsystem 1 Legend: EO Equipment Outlet EO EO EO EO EO EO EO DA Distributor A DB Distributor B DC Distributor C Optional cabling Optional consolidation point page 14 / October 16, 2008
  • 15. 568-C.0 - Generic Cabling Topology DC Part 2 of Figure 2 Cabling Legend: Subsystem 3 EO Equipment Outlet DA Distributor A Cabling DB Distributor B Subsystem 1 DC Distributor C Optional cabling DB Optional consolidation point Cabling Subsystem 1 EO EO EO page 15 / October 16, 2008
  • 16. 568-C.0 – Generic Cabling – 568-C.0 Incorporates some of the 568-B.1 Addenda • Centralized cabling, patch cord bend radius, etc. – 568-C.0 Collected Common Information from 568-B.1 and others • Choosing media • Cabling lengths • Bonding and grounding • Polarity • Installation requirements • Application support tables • Optical fiber testing & limits – NOTE: balanced twisted-pair testing and limits will be in 568-C.2 page 16 / October 16, 2008
  • 17. 568-C.0 – Technical Changes • Installation minimum bend radius for balanced twisted-pair cable – Changed to 4x cable OD for both shielded and unshielded • Note: Worst case minimum bend radius is now 1.5 inches (not 1.0 inch) since the largest allowable cable OD is 0.354 inches (per 568-B.2-11) • Adds Augmented Category 6 (shielded and unshielded) as a recognized medium • Patch cable bend radius for balanced twisted-pair cabling – Changed to “1x cable OD” from “0.25 inches” • Maximum untwist for Category 6A cable termination – Added and set to 13mm (same as Category 6) page 17 / October 16, 2008
  • 18. 568-C.0 – Generic Cabling - Status • 2nd default ballot closed in August 2008 • Approve & Approve with comments (21) • Do Not Approve (0) – Comments were resolved in August teleconference • ~1 technical comment, 1 editorial comment – Motion to release for publication was unanimously approved – TR-42 Plenary approval for publication expected in early October page 18 / October 16, 2008
  • 20. 568-C.1 – Commercial Building • Builds on information in 568-C.0 • Contains appropriate allowances and exceptions specific to office- oriented commercial building cabling • Retains use of 568-B.1 nomenclature • Main Cross-connect (Distributor C in 568-C.0) • Interbuilding backbone cabling (Cabling Subsystem 3 in 568-C.0) • Intermediate Cross-connect (Distributor B in 568-C.0) • Intrabuilding backbone cabling (Cabling Subsystem 2 in 568-C.0) • Horizontal Cross-connect (Distributor A in 568-C.0) • Horizontal cabling (Cabling Subsystem 1 in 568-C.0) • The Telecommunications Outlet (Equipment Outlet in 568-C.0) page 20 / October 16, 2008
  • 21. 568-C.1 – Commercial Building Cabling MC Backbone Backbone Cabling Cabling IC IC Part 1 of Figure 5 Backbone Cabling HC HC Horizontal Cabling Horizontal Cabling TO TO TO TO TO TO TO Legend: TO Telecommunications Outlet (Equipment Outlet) HC Horizontal Cross-connect (Distributor A) IC Intermediate Cross-connect (Distributor B) MC Main Cross-connect (Distributor C) Optional cabling Optional consolidation point page 21 / October 16, 2008
  • 22. 568-C.1 – Commercial Building Cabling MC Part 2 of Figure 5 Backbone Legend: Cabling TO Telecommunications Outlet (Equipment Outlet) HC Horizontal Cross-connect (Distributor A) Horizontal IC Intermediate Cross-connect (Distributor B) Cabling MC Main Cross-connect (Distributor C) Optional cabling HC Optional consolidation point Horizontal Cabling TO TO TO page 22 / October 16, 2008
  • 23. 568-C.1 – Technical Changes • From 568-B.1 Addenda – Inclusion of category 6 balanced twisted-pair cabling – Inclusion of augmented category 6 twisted-pair cabling – Inclusion of 850 nm laser-optimized 50/125 µm MM fiber – Inclusion of telecommunications enclosures (TEs) • Inclusion of centralized cabling in the main body of document • A recommendation to select 850 nm laser-optimized 50/125 µm as the multimode fiber for commercial buildings page 23 / October 16, 2008
  • 24. 568-C.1 – Technical Changes • Removal of common information (this was moved into 568-C.0) • Removal of 150-Ohm STP cabling • Removal of category 5 cabling • Removal of 50-ohm and 75-ohm coaxial cabling • Removal of balanced twisted-pair cabling performance and test requirements (these will be in the ANSI/TIA-568-C.2 document) – NOTE: optical fiber cabling performance and test requirements in 568-C.0 page 24 / October 16, 2008
  • 25. 568-C.1 – Commercial Building • 2nd default ballot closed in August • Approve & Approve with Comments (22) • Do Not Approve (0) – Comments resolution completed in February • No technical comments, 1 editorial comment – Motion to release for publication was unanimously approved – TR-42 Plenary approval for publication expected in early October page 25 / October 16, 2008
  • 27. 568-C.2 Copper Cabling Components • Editing committee created the first draft – Incorporates Cat 3, Cat 5e, Cat 6 and Cat 6A • 2nd committee ballot closed in July • Document size is 221 pages (down from over 400!) – 7 Approve, 5 Do Not Approve • Interim meeting in August to review document comments – 175 Technical Comments, 76 Editorial Comments • Comment resolution completed in August – A 1st industry (45-day) ballot was issued • Interim meeting scheduled for December to review comments • Plans to publish by mid-2009 still viable page 27 / October 16, 2008
  • 28. 568-C.3 Optical Fiber Components
  • 29. 568-C.3 – Optical Cabling Components • Released for Publication – Released by ANSI in July 2008 page 29 / October 16, 2008
  • 30. 568-C.3 Purpose • Serve as a stand-alone Standard – No longer tied to commercial building cabling • Specify component transmission performance – Cable, connectivity and cords • Intended to be used by – Manufacturers (primarily) – May also be of use to users, designers and installers (secondarily) • Common reference for optical fiber components in all TR-42 standards page 30 / October 16, 2008
  • 31. Table of Contents (Summary) • Scope • Normative References • Definitions, Abbreviations, Acronyms & Units of Measure • Optical Fiber Cable • Connecting Hardware • Optical Fiber Patch Cords & Transitions • Annex A: Connector Performance Specifications • Annex B: Bibliography & References • Note: Field testing and limits in 568-C.0 page 31 / October 16, 2008
  • 32. Documents Incorporated into 568-C.3 • ANSI/TIA/EIA-568-B.3, Optical Fiber Cabling Component Standard • ANSI/TIA/EIA-568-B.3-1, Additional Transmission Performance Specifications for 50/125 µm Optical Fiber Cables • Some information from ANSI/TIA-568-B.1-7, Guidelines for Maintaining Polarity Using Array Connectors – Component requirements – how to make them – Note: System requirements – how to use them – in 568-C.0 page 32 / October 16, 2008
  • 33. Fiber Nomenclature • Transmission performance parameters (Table 1) includes references to ISO nomenclature (see example below) – OM1, OM2 and OM3 – OS1 and OS2 “850 nm Laser-Optimized 50/125 µm Multimode TIA 492AAAC (OM3)” page 33 / October 16, 2008
  • 34. Cable Requirements • Cabled Fiber Performance Requirements – Attenuation, Bandwidth • References for optical fiber cable requirements: – TIA 472C000-B/ICEA S-83-596-2001, Fiber Optic Premises Distribution Cable – TIA 472D000-B/ICEA S-87-640-1999, Fiber Optic Outside Plant Communications Cable – TIA 472E000/ICEA S-104-696-2003, Standard For Indoor-Outdoor Optical Cable – TIA 472F000/ICEA S-110-717-2003, Optical Drop Cables page 34 / October 16, 2008
  • 35. Connectors and Adapters • Duplex Connectors – Shall meet the requirements of the corresponding TIA Fiber Optic Connector Intermateability Standard (FOCIS) and Annex A Requirements • Array Connectors – Shall meet the requirements of the corresponding TIA Fiber Optic Connector Intermateability Standard (FOCIS) and Annex A Requirements • Keying and fiber positions • Adapters – Type A (key-up to key-down) and Type B (key-up to key-up) page 35 / October 16, 2008
  • 36. Connectors: Strain Relief and Adapter Housing Colors • Unless color coding is used for some other purpose, the connector strain relief and adapter housing should be identifiable by the following colors: – 850nm laser-optimized 50/125µm fiber – aqua – 50/125µm fiber – black – 62.5/125µm fiber – beige – Single-mode fiber – blue – Angled contact ferrule single-mode connectors – green page 36 / October 16, 2008
  • 37. Connectors: Plug Body Colors • In addition, unless color coding is used for some other purpose, the connector plug body should be generically identified by the following colors, where possible: – Multimode – beige, black or aqua – Single-mode – blue – Angled contact ferrule single-mode connectors – green page 37 / October 16, 2008
  • 38. Optical Fiber Patch Cords • Simplex Patch Cords have been included • Duplex Patch Cords: Two Types – A-to-B (the “normal” patch cord) A-to-B duplex optical fiber patch cord page 38 / October 16, 2008
  • 39. Optical Fiber Patch Cords • Duplex Patch Cords: Two Types – A-to-A (special use patch cord) A-to-A duplex optical fiber patch cord page 39 / October 16, 2008
  • 40. Optical Fiber Patch Cords • Array – Three array patch cord constructions are included (others are allowed) • Type A: Fibers positioned sequentially (1 to 1, 2 to 2,…12 to 12) • Type B: Fibers positioned in reverse sequence (1 to 12, 2 to 11,…12 to 1) • Type C: Fibers positioned in flipped pairs (1 to 2, 2 to 1,…11 to 12, 12 to 11) – Transitions (or “break outs”) position fibers sequentially (1 to 1, 2 to 2,…12 to 12) • Note: Use of these components is covered in 568-C.0 page 40 / October 16, 2008
  • 41. Annex A: Mechanical and Environmental Testing for Connecting Hardware • Normative • Optical fiber connector performance specifications – required number of test samples – performance requirements • Annex A now a subset of IEC Testing • IEC Compliance incorporates TIA 568-C.3 Annex A Compliance – TIA compliance does not mean IEC compliance page 41 / October 16, 2008
  • 43. Purchasing Standards • TIA releases published documents to Global Engineering Documents • Global Engineering Documents acts as a clearing house for order processing for multiple Standards Developing Organizations (SDOs) • News: – Now Global Engineering Documents is “IHS” – www.ihs.com page 43 / October 16, 2008