User Manual
(Catalog Number 1757-ABRIO)
Process Remote I/O (RIO)
Communication Interface Module
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local
Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences
between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves
that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability
for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Allen-Bradley, Rockwell Automation, RSLogix 5000, ControlLogix, ProcessLogix, RSLinx, ControlFlash, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a
hazardous environment, which may lead to personal injury or death, property damage, or
economic loss.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and
recognize the consequence
SHOCK HAZARD Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.
BURN HAZARD Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.
3Publication 1757-UM007D-EN-P - December 2008 3
Table of Contents
Preface Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Who Should Use this Manual. . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1
Introduction Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Process Remote I/O (RIO) Communication Interface Module . 9
RSLinx Software Requirements. . . . . . . . . . . . . . . . . . . . . . . 10
ProcessLogix System Quick Start . . . . . . . . . . . . . . . . . . . . . 11
RSLogix 5000 System Quick Start . . . . . . . . . . . . . . . . . . . . . 12
Update the 1757-ABRIO Module’s Firmware. . . . . . . . . . . . . 14
Using ControlFlash Software. . . . . . . . . . . . . . . . . . . . . . 14
Using NTools with ProcessLogix Software. . . . . . . . . . . . 15
Chapter 2
Configure the 1757-ABRIO Module Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
AbRioCfg Software Overview. . . . . . . . . . . . . . . . . . . . . . . . 17
Mapping and Accessing RIO Network Data . . . . . . . . . . . . . 18
Installing AbRioCfg Software . . . . . . . . . . . . . . . . . . . . . . . . 19
Autoconfigure the I/O Racks . . . . . . . . . . . . . . . . . . . . . . . . 19
Adding Block Transfer Modules. . . . . . . . . . . . . . . . . . . . . . 23
Addressing Modes for 1771 . . . . . . . . . . . . . . . . . . . . . . 24
Configuring Block Transfer Modules . . . . . . . . . . . . . . . . . . 25
Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Input Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Output Scaling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Tags Defined . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Create a Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Mapping Data to Tags in AbRioCfg Software . . . . . . . . . . . . 31
Block Transfers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Deleting Mapped Data . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Tips for Configuring Modules . . . . . . . . . . . . . . . . . . . . . . . 32
Add Racks Offline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Delete Racks Offline . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Change the Baud Rate Offline . . . . . . . . . . . . . . . . . . . . 35
Download the Configuration . . . . . . . . . . . . . . . . . . . . . . . . 35
Upload the Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4 Publication 1757-UM007D-EN-P - December 2008
Table of Contents
Chapter 3
Creating Generic Modules in
AbRioCfg Software
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Generic Module Overview. . . . . . . . . . . . . . . . . . . . . . . . . . 37
Generic Module Configuration File . . . . . . . . . . . . . . . . . . . 38
Configuration Block Transfer Write. . . . . . . . . . . . . . . . . 38
Data Block Transfer Read. . . . . . . . . . . . . . . . . . . . . . . . 41
Data Block Transfer Write . . . . . . . . . . . . . . . . . . . . . . . 45
Creating a Generic Module in AbRioCfg software . . . . . . . . . 48
Chapter 4
Configuring the ProcessLogix
Controller to Access Data on the
1757-ABRIO Module
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
CONFIG Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
INACTIVE Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
ACTIVE Mode (Run) . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
FORCED ACTIVE Mode . . . . . . . . . . . . . . . . . . . . . . . . . 52
Configure the 1757-PLX52 Controller . . . . . . . . . . . . . . . . . . 53
Chapter 5
Configuring RSLogix 5000
Software to Access Data on the
1757-ABRIO Module
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
CONFIG Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
INACTIVE Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
ACTIVE Mode (Run) . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
FORCED ACTIVE Mode . . . . . . . . . . . . . . . . . . . . . . . . . 59
Scheduled Digital I/O Connections in RSLogix 5000 Programs .
60
Scheduled Connection Types . . . . . . . . . . . . . . . . . . . . . 60
Setup an Exclusive-owner Connection . . . . . . . . . . . . . . 60
Setup Input-only Connections . . . . . . . . . . . . . . . . . . . . 63
Unscheduled I/O Connections in ControlLogix. . . . . . . . . . . 67
Create Message Commands to Read and Write All RIO
Network Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Chapter 6
Accessing Data through a DDE or
OPC Server
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Accessing Data from a DDE or OPC Server . . . . . . . . . . . . . 75
Configuring a Topic in RSLinx Software . . . . . . . . . . . . . 75
Accessing the Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Publication 1757-UM007D-EN-P - December 2008 5
Table of Contents
Chapter 7
Monitoring the 1757-ABRIO
Module
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Monitoring the Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Monitoring Digital I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Monitoring the Data Value of Tags. . . . . . . . . . . . . . . . . . . . 78
Monitoring the Status of a Block Transfer. . . . . . . . . . . . . . . 79
Monitoring the Scanner Log. . . . . . . . . . . . . . . . . . . . . . . . . 80
Monitoring Diagnostic Counters. . . . . . . . . . . . . . . . . . . . . . 81
Active Rack List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Global Diagnostic Counters . . . . . . . . . . . . . . . . . . . . . . 81
Fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Chapter 8
Supported 1771 Modules Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Module Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
1771-IFE Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 85
I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
1771-OFE Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 89
I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
1771-IR Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 92
I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
1771-IXE Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 95
I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
1771-IL Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 98
I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
1771-NOC Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 101
I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
1771-NOV Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 104
I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
6 Publication 1757-UM007D-EN-P - December 2008
Table of Contents
1771-NIV Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 107
I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
1771-NR Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 111
I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Chapter 9
Accessing HART Data Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Sending HART Commands Using RSLogix 5000 Software MSG .
115
HART Command Data . . . . . . . . . . . . . . . . . . . . . . . . . 117
Reply Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Example: HART Command 36 . . . . . . . . . . . . . . . . . . . 122
1770-HT1 Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Rack Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Configuring the 1770-HT1 Module . . . . . . . . . . . . . . . . 124
HART Command status . . . . . . . . . . . . . . . . . . . . . . . . 129
Appendix A
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Appendix B
Troubleshooting Interpret the Status Indicators . . . . . . . . . . . . . . . . . . . . . . 133
RIO Status Indicator – Remote Devices Status . . . . . . . . 133
SYS Status Indicator – ControlBus Status . . . . . . . . . . . . 133
OK Status Indicator – Module Health . . . . . . . . . . . . . . 134
Status Display Power-up Messages. . . . . . . . . . . . . . . . . . . 134
Power Supply Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Interpret the Alphanumeric Display . . . . . . . . . . . . . . . . . . 135
Using AbRioCfg Software for Troubleshooting . . . . . . . . . . 136
Troubleshooting Problems. . . . . . . . . . . . . . . . . . . . . . . . . 137
Using RSLogix 5000 to Diagnose Problems. . . . . . . . . . . . . 138
General Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Connection Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Module Info Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Backplane Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Using Control Builder Software to Diagnose Problems . . . . 140
Troubleshooting 1757-ABRIO Module Communications . . . 140
Publication 1757-UM007D-EN-P - December 2008 7
Table of Contents
Appendix C
Operational Comparison Between
the 1757-ABRIO Module and a
PLC-5 System
Normal Operational Messages . . . . . . . . . . . . . . . . . . . . . . 143
Exception Handling Messages . . . . . . . . . . . . . . . . . . . . . . 145
Appendix D
Tag Descriptions for Scheduled
Data in RSLogix 5000 Software
Configuration Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
I and O Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Status Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
8 Publication 1757-UM007D-EN-P - December 2008
Table of Contents
7Publication 1757-UM007D-EN-P - December 2008 7
Preface
Purpose of this Manual This manual describes how to configure and troubleshoot your
Process Remote I/O (RIO) Communication Interface Module.
For installation information, refer to the Process Remote I/O (RIO)
Communication Interface Module Installation Instructions, publication
1757-IN916.
Who Should Use this
Manual
We assume you have a good understanding of Remote I/O (RIO)
modules as well as the host controller system (ProcessLogix or
ControlLogix).
Additional Resources These documents contain additional information concerning related
Rockwell Automation products.
See I/O Module Documentation on page 84 for a listing of related
ControlLogix documentation.
You can view or download publications at
http://literature.rockwellautomation.com. To order paper copies of
technical documentation, contact your local Rockwell Automation
distributor or sales representative.
Resource Description
Process Remote I/O (RIO) Communication
Interface Module Installation Instructions,
publication 1757-IN916
Provides details on how to install the
1757-ABRIO module.
Process Remote I/O (RIO) Communication
Interface Module Release Notes,
publication 1757-RN520
Provides release details on the 1757-ABRIO
module.
Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
Provides general guidelines for installing a
Rockwell Automation industrial system.
Product Certifications website,
http://ab.com
Provides declarations of conformity,
certificates, and other certification details.
8 Publication 1757-UM007D-EN-P - December 2008
Table of Contents Preface
9Publication 1757-UM007D-EN-P - December 2008 9
Chapter 1
Introduction
Introduction This chapter:
describes the 1757-ABRIO Remote I/O Module.
lists the RSLinx software requirements.
provides update procedures for the module’s firmware.
Process Remote I/O (RIO)
Communication Interface
Module
This document is a user guide for the 1757-ABRIO module, which lets
Rockwell Automation controllers (ProcessLogix or ControlLogix)
communicate with Allen-Bradley remote I/O. The module acts as a
RIO network scanner. The 1757-ABRIO module facilitates connection
to analog and discrete I/O devices as well as any block transfer
modules.
1757-ABRIO Module Example Topology
43290
Supports
Block
Transfers -
limit of 32
words in a
block
ProcessLogix
System Server
Flex Ex Modules
PLC5/C
Controller
ControlNet
Network
SLC Controller
Data Highway + Network
ControlNet Network
PLC5
Controller
ProcessLogix and ControlLogix Controllers
Remote I/O Network
1771 Remote I/O
1746 Remote I/O
Drive
10 Publication 1757-UM007D-EN-P - December 2008
Chapter 1 Introduction
As an RIO network scanner, the module:
scans 1771 racks with rack numbers from 1 to 37 octal.
supports baud rates of 57.6, 115.2 and 230.4 kilobaud.
supports up to 32 adapters with any mix of full/partial racks.
automatically manages and performs block transfers, update
time can be defined for each block transfer.
provides full diagnostic counters for alarms and maintenance.
automatically performs scaling of raw analog data.
supports scheduled connections to update digital data with a
ControlLogix controller.
implements a watchdog timer in the module’s hardware.
If the firmware does not kick the watchdog within the time-out
period the watchdog times out and places the module into the
configured safe failure state.
automatically provides fault/fail safe commands to I/O modules
and controllers.
implements a jabber inhibit timer.
If the network transmitter is on longer than 150% of the longest
network frame time, the 1757-ABRIO module turns the
transmitter off and places the module into the configured safe
failure state.
supports firmware updates using NTools or ControlFlash
software.
supports direct DDE/OPC data access.
provides support for Rockwell Automation’s 1770-HT1,
1770-HT8, and 1770-HT16 HART interface products.
provides HART command set for calibration and diagnostics.
RSLinx Software
Requirements
The AbRioCfg software requires RSLinx OEM software or above. You
cannot use RSLinx Lite software. To access the module using OPC or
DDE, you must have RSLinx 2.31 software or above.
If you are using ProcessLogix software, refer to the corresponding
ProcessLogix Installation and Upgrade Guide to determine the
appropriate RSLinx software version for your release.
Publication 1757-UM007D-EN-P - December 2008 11
Introduction Chapter 1
ProcessLogixSystemQuick
Start
Use the following steps to quickly get the module running in a
ProcessLogix system. Detailed information about each step is available
in other sections of this manual or in the installation manual. You can
only have one scanner per RIO network. Remove any other scanners
on the RIO network before continuing.
1. Install the 1757-ABRIO module in the chassis and connect it to
the RIO network.
See the Process Remote I/O (RIO) Communication Interface
Module Installation Instructions, publication 1757-IN916.
2. Flash the controller with the latest firmware.
See Using NTools with ProcessLogix Software on page 15.
3. Install the AbRioCfg software.
See Installing AbRioCfg Software on page 19.
4. Autoconfigure or manually configure the RIO racks. This step
locates all connected racks.
See Autoconfigure the I/O Racks on page 19 and Add Racks
Offline on page 33.
5. Add and configure block transfer modules.
See Adding Block Transfer Modules on page 23.
6. Create tags for access by the ProcessLogix controller.
See Create a Tag on page 30.
7. Map I/O data to the tags and save the configuration file.
See Mapping Data to Tags in AbRioCfg Software on page 31.
8. Download the configuration to the 1757-ABRIO module.
See Download the Configuration on page 35.
9. Configure the ProcessLogix controller to access information
within the 1757-ABRIO module using Control Builder software.
See Configure the 1757-PLX52 Controller on page 53.
10. Access live data from the 1757-ABRIO module.
See Live Data Examples on page 56.
12 Publication 1757-UM007D-EN-P - December 2008
Chapter 1 Introduction
RSLogix 5000 System Quick
Start
Use the following steps to quickly get the module running in an
RSLogix 5000 system. Detailed information about each step is
available in other sections of this manual or in the installation manual.
You can only have one scanner per RIO network. Remove any other
scanners on the RIO network before continuing.
1. Install the 1757-ABRIO module in the chassis and connect it to
the RIO network.
See the Process Remote I/O (RIO) Communication Interface
Module Installation Instructions, publication 1757-IN916.
2. Flash the Controller with the latest firmware.
See Using ControlFlash Software on page 14.
3. Install the AbRioCfg software.
See Installing AbRioCfg Software on page 19.
4. Autoconfigure or manually configure the RIO racks. This step
locates all connected racks.
See Autoconfigure the I/O Racks on page 19 and Add Racks
Offline on page 33.
5. Add and configure block transfer modules.
See Adding Block Transfer Modules on page 23.
6. Create tags to access analog data from the ControlLogix
controller.
See Create a Tag on page 30.
OR
Use scheduled updates to access digital data from the
ControlLogix controller.
See Scheduled Digital I/O Connections in RSLogix 5000
Programs on page 60.
7. Map I/O data to the tags and save the configuration file.
See Mapping Data to Tags in AbRioCfg Software on page 31.
8. Download the configuration to 1757-ABRIO module.
See Download the Configuration on page 35.
Publication 1757-UM007D-EN-P - December 2008 13
Introduction Chapter 1
9. If you are using:
a. a scheduled network, establish an Exclusive Owner or Input
Only connection from the ControlLogix controller to access
digital data within the 1757-ABRIO module.
See Setup an Exclusive-owner Connection on page 60 or
Setup Input-only Connections on page 63.
b. an unscheduled network, configure tags and ladder logic in
RSLogix 5000 software to access information within the
1757-ABRIO module.
See Unscheduled I/O Connections in ControlLogix on
page 67.
10. If you are using a scheduled ControlNet network, schedule your
network through RSNetWorx for ControlNet software.
See the RSNetWorx Help and the ControlNet Modules in
Logix5000 Control Systems User Manual, publication
CNET-UM001.
11. Access live data from the 1757-ABRIO module via:
a. scheduled connections.
See Scheduled Digital I/O Connections in RSLogix 5000
Programs on page 60 and Live Data Example on page 66.
b. unscheduled connections.
See Unscheduled I/O Connections in ControlLogix on
page 67 and Live Data Example on page 73.
TIP If you are using a scheduled ControlNet network, you
must also complete 9b to access analog or text data
from the 1757-ABRIO module.
14 Publication 1757-UM007D-EN-P - December 2008
Chapter 1 Introduction
Update the 1757-ABRIO
Module’s Firmware
The 1757-ABRIO module supports firmware upgrades using
ControlFLASH or NTools software. The firmware version is displayed
on the 1757-ABRIO module’s 4-character display when you power up
the module.
For ProcessLogix software users, if your 1757-ABRIO module revision
is:
at or less than 1.2, use ControlFlash software to update the
module firmware.
greater than 1.2, use NTools software to update the module
firmware.
Using ControlFlash Software
Use the following procedure to update the module firmware using
ControlFLASH software.
1. Insert the 1757-ABRIO CD.
2. Click Start>Run.
3. Type this path or Browse to:
D:(or your CD-ROM drive letter)ControlFlashsetup.exe
4. Click OK.
5. At the Welcome to ControlFLASH Setup window, click Next.
6. To accept the License Agreement, click Yes.
7. To accept the default location, click Next.
8. At the Setup Complete window,
a. Uncheck the Yes, I want to view the README file checkbox.
b. Check the Yes, I want to launch ControlFLASH checkbox.
c. Click Finish.
9. At the Welcome to ControlFLASH window, click Next.
IMPORTANT The module ships with the latest firmware installed.
You do not need to download firmware to the
1757-ABRIO module when you first receive it.
Publication 1757-UM007D-EN-P - December 2008 15
Introduction Chapter 1
10. Click 1757-ABRIO and click Next.
11. Expand the RSLinx Tree window to the location of the
1757-ABRIO module you wish to flash.
12. Select the module icon and click OK.
13. Confirm new revision for this update and click Next.
14. At the Summary window, click Finish.
15. To confirm the flash, click Yes.
16. Click OK.
If this update is successful, the Update Status window displays
the following message in green:
Update Complete. Please verify this new firmware update before
using the target device in its intended application.
17. Click OK and then click Cancel at the Welcome to ControlFLASH
Setup window.
18. Click Yes to end the configuration session.
Using NTools with ProcessLogix Software
On a ProcessLogix system, if the module firmware is at 1.2 or greater,
use the following procedure to update the module firmware using
NTools.
1. On the ProcessLogix Server, click Start>Run.
2. Type >ntools -c -u<.
3. To launch the Network Tools application, click OK.
4. Click OK at the warning about monitoring through Control
Builder software.
5. To initiate the network scan, click Resume.
6. Select the appropriate CNB or ENET icon.
7. Select the module to be updated in the chassis graphic.
16 Publication 1757-UM007D-EN-P - December 2008
Chapter 1 Introduction
8. Click the firmware button and click Yes to acknowledge the
warning.
9. Navigate to:
D:(or your CD-ROM drive letter)Firmware_NTools
10. Select the appropriate .nvs file.
11. To start the firmware load, click Open.
12. To confirm, click Yes.
The Status field in the lower portion of the Network Tools
window tracks the load progress.
13. When the load completes, click OK.
17Publication 1757-UM007D-EN-P - December 2008 17
Chapter 2
Configure the 1757-ABRIO Module
Introduction This chapter:
provides an overview of the AbRioCfg software.
gives an introduction to mapping and accessing RIO network
data.
explains how to install the AbRioCfg software.
explains how to autoconfigure I/O racks.
explains how to add and configure block transfer modules.
AbRioCfg Software
Overview
The 1757-ABRIO module ships with configuration software, called
AbRioCfg. This configuration software is an online configuration tool.
Use the configuration software to:
query the RIO network to determine the location and size of the
racks present.
manually add and configure racks present in RIO network.
add and configure supported block transfer modules.
import comma separated variable files to define the Generic
Module as any block transfer module that uses 16-bit integer
data.
add, edit, and delete racks offline.
create tags for access by the controller.
map I/O data to those tags.
download the configuration to the module, using RSLinx
software.
monitor data and diagnostics on the module.
change the baud rate of network communications in a
configuration and download to the module.
change the configuration of racks in a configuration and
download to the module.
upload a configuration from a module.
print the configuration.
18 Publication 1757-UM007D-EN-P - December 2008
Chapter 2 Configure the 1757-ABRIO Module
Mapping and Accessing
RIO Network Data
Use the provided AbRioCfg software to create tags which are arrays of
digital, floating point or text values that the host controller reads or
writes using unscheduled messages.
You map data that the module receives or sends into these tags. The
data mapping is stored in flash memory on the 1757-ABRIO module.
The 1757-ABRIO Module and Data Mapping
WARNING
It is essential that the control program on the host controller
matches the addresses in the mapping configuration on the
1757-ABRIO module. Otherwise the control program may
inadvertently write to the incorrect I/O locations. If you change
the data mappings on the 1757-ABRIO module, make sure that
the control program is using the correct addresses.
1757-ABRIO Module
Tag
Tag
ControlLogix or
ProcessLogix
Controller
Write Data
Remote I/O
Modules
R/W Analog Data with Block Transfer Status
R/W digital Data
Scales Analog Data
Analog/Digital Modules
Hard Configured for Safe/Fault States
RIO Network
Read Data
Scan
List
RIO Network
Scanner
Remote I/O
Modules
Publication 1757-UM007D-EN-P - December 2008 19
Configure the 1757-ABRIO Module Chapter 2
Installing AbRioCfg
Software
1. Verify that RSLinx software and RSLinx OEM or RSLinx
Professional (not RSLinx Lite) software is installed before you
install the AbRioCfg software.
2. Insert the CD supplied with the 1757-ABRIO module and run the
program setup.exe.
3. Confirm that you have RSLinx OEM or RSLinx Professional (not
RSLinx Lite) software installed.
Before you install a new version of AbRioCfg software, you must
delete the old version. Use the Add or Remove Programs utility in
your Windows Control Panel to remove the previous version.
Autoconfigure the I/O
Racks
The first step in building a configuration is to perform an
autoconfiguration. To complete an autoconfiguration, the RIO
network must be connected to the 1757-ABRIO module and the
module must be in “inactive” mode.
1. Start AbRioCfg software.
IMPORTANT Messages about the DTL32.DLL during installation or when you
run the software indicate problems with the RSLinx software
installation.
If you get these messages, install the proper version of RSLinx
software before you continue.
IMPORTANT Removing the software does not delete stored configuration
files.
TIP If you see question marks for the 1757-ABRIO module when
running RSNetWorx or RSLinx software, install the EDS file
from the provided CD.
You do not need to load the firmware on the CD into your
1757-ABRIO module as the module ships with the latest version
of firmware. The firmware is on the CD for archival purposes
only.
ATTENTION When using AbRioCfg software, you must left-click to
select/highlight before you can right-click to activate menu
options.
20 Publication 1757-UM007D-EN-P - December 2008
Chapter 2 Configure the 1757-ABRIO Module
2. Click Hardware Config to highlight it and activate the AbRioCfg
menu toolbar.
3. Click the Autoconfig button in the toolbar.
An RSWho window opens.
TIP With AbRioCfg software, 2.0 and higher, you can also manually
configure the I/O racks in your network. Refer to Add Racks
Offline on page 33 for more information.
Publication 1757-UM007D-EN-P - December 2008 21
Configure the 1757-ABRIO Module Chapter 2
4. Navigate to the 1757-ABRIO module.
5. Select the module and click OK.
The Select Baud Rate dialog box opens.
6. Select the appropriate baud rate and click OK.
The baud rate in this example is set by
switches on the 1771-ASB adapter. See
your device documentation for how to
set the desired baud rate. All racks or
devices on one RIO network must
operate at the same baud rate.
22 Publication 1757-UM007D-EN-P - December 2008
Chapter 2 Configure the 1757-ABRIO Module
The 1757-ABRIO module sends messages to all possible racks
and builds the network rack configuration from the responses. It
displays a list of the racks it found in the network tree.
If you expand a rack, the partial racks that make up that rack
number are displayed.
7. If you are using 1771 remote I/O modules,
a. Right-click the rack in the network tree and select Enter Rack
Switch Setting.
The Select Rack Setting dialog box opens.
Publication 1757-UM007D-EN-P - December 2008 23
Configure the 1757-ABRIO Module Chapter 2
b. Select the value that matches the Last State switch setting in
the backplane of the I/O chassis, either De-energize or Hold
Last State.
This setting tells the 1757-ABRIO module what to do if the
controller stops updating the tag to which this chassis’s digital
data is mapped.
c. Repeat steps 7a and 7b for all racks that contain 1771 remote
I/O modules.
Adding Block Transfer
Modules
Autoconfiguration can locate the racks present on the network but it
cannot detect the analog I/O modules in those racks. Remote I/O
protocol does not allow for module identification to be communicated
on the network. Because of this, Block Transfer modules need to be
added manually. You do not have to add digital modules.
To add a block transfer module, complete the following steps.
1. Expand the rack that contains the analog I/O module in the
network tree.
2. Right-click the partial rack that contains the module and select
Add Module.
The Add BT Module dialog box opens.
3. Select the Module Type from the pull-down menu.
24 Publication 1757-UM007D-EN-P - December 2008
Chapter 2 Configure the 1757-ABRIO Module
4. Select the slot location for the module.
To do this, you should be familiar with Allen-Bradley addresses
and, in particular, with 1771 addressing modes (see below).
See I/O Module Documentation on page 84 for a list of related
ControlLogix documentation.
5. Click OK.
Addressing Modes for 1771
The 1771 chassis have three addressing modes - 1/2-slot, 1-slot and
2-slot addressing. The addressing mode is set by switches in the
backplane of the chassis and is set on a per-chassis basis. The
addressing mode determines how physical block transfer modules
map into logical addresses (rack, I/O group and slot).
In the following tables, the addresses used for modules in a 16-slot
rack in each addressing mode. The rack switches are set for rack 1,
starting I/O group 0.
As illustrated in the 2-slot addressing table below, the controller
addresses two I/O module slots as one I/O group. For example, for a
chassis at rack 1, starting I/O group 0, a block transfer module in the
first slot would be at address rack 1, I/O group 0, slot 0. A module in
the next slot would be at rack 1, I/O group 0, slot 1.
As illustrated in the 1-slot addressing table below, the controller
addresses one I/O module slot as one I/O group. For example, for a
chassis at rack 1, starting I/O group 0, a block transfer module in the
first slot would be at address rack 1, I/O group 0, slot 0. A module in
the next slot would be at rack 1, I/O group 1, slot 0.
2-Slot Addressing
Slot in chassis 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Rack 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
I/O Group 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7
Slot 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
1-Slot Addressing
Slot in chassis 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Rack 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2
I/O Group 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
Slot 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Publication 1757-UM007D-EN-P - December 2008 25
Configure the 1757-ABRIO Module Chapter 2
As illustrated in the 1/2-slot addressing table below, the controller
addresses 1/2 of an I/O module slot as one I/O group. For example,
for a chassis at rack 1, starting I/O group 0, a block transfer module in
the first slot would be at address rack 1, I/O group 0, slot 0. A module
in the next slot would be at rack 1, I/O group 2, slot 0.
Configuring Block Transfer
Modules
When you add a block transfer module, the configuration dialog box
for that module opens. The contents of the dialog box are specific to
each module type.
See Supported 1771 Modules on page 83 or the online help for
information on configuring individual modules.
To edit the configuration for a module, double-click the module in the
network tree, or right-click the module and select Configure.
1/2-Slot Addressing
Slot in chassis 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Rack 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4
I/O Group 0 2 4 6 0 2 4 6 0 2 4 6 0 2 4 6
Slot 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
TIP You cannot change the location of a module in the
configuration once you have created it. You must delete the
module and create a new one at the new location.
26 Publication 1757-UM007D-EN-P - December 2008
Chapter 2 Configure the 1757-ABRIO Module
Scaling Part of the configuration procedure for analog modules is entering
scaling values. The 1757-ABRIO module performs scaling between
raw I/O data and floating point user values.
You can send floating point output values to the 1757-ABRIO module
which it converts to raw output values using the scaling values you
supplied in the configuration. Similarly, the 1757-ABRIO module
converts raw input data to floating point values, using the scaling you
enter. The 1757-ABRIO module supports scaling values from -3.4e38
to 3.4e38. Scaling is done on a per-channel basis.
Input Scaling
For analog input modules, you must supply the floating point values
to which you want the minimum and maximum raw data scaled.
Minimum corresponds to the lowest raw value.
Maximum corresponds to the maximum raw value.
EXAMPLE If a raw input range is 1 5 V dc and you set the minimum
scaling value to 12.3 and the maximum scaling value to 77.4,
a raw input voltage of 1 produces a scaled input value of 12.3.
A raw input voltage of 5 V dc produces a scaled input value of
77.4
A raw input value outside the range of 1 5 V dc produces an
input of NaN (not a number). Modules also have underrange
and overrange bits to indicate data overflows.
Publication 1757-UM007D-EN-P - December 2008 27
Configure the 1757-ABRIO Module Chapter 2
Output Scaling
For output modules, you supply the floating point values you want to
correspond to the minimum and maximum raw output values.
ATTENTION
The minimum scale value may not be larger than the maximum
scale value
EXAMPLE If a channel has a range of 1 5 V dc and you set the minimum
scaling value to 12.3 and the maximum scaling value to 77.4,
when you set the output value to 12.3, the module produces a
raw output value of 1 V dc. When you set the output value to
77.4, the module produces a raw output of 5 V dc.
If you set the value outside the minimum and maximum scaling
values, the raw output is clamped at the minimum or maximum.
28 Publication 1757-UM007D-EN-P - December 2008
Chapter 2 Configure the 1757-ABRIO Module
Tags Defined The ProcessLogix or ControlLogix controller accesses data for the
1757-ABRIO module using unscheduled messages that read or write
tags. For more information on how the controllers access this data, see
Configuring the ProcessLogix Controller to Access Data on the
1757-ABRIO Module on page 51 and Configuring RSLogix 5000
Software to Access Data on the 1757-ABRIO Module on page 57.
Before you program the controller to read or write to the 1757-ABRIO
module, you must define the tags in AbRioCfg software.
The 1757-ABRIO module supports the following five types of tags.
Numeric Read (1) and Numeric Write (2) tags
– Numeric read and numeric write tags are arrays of 64 scaled
floating point values.
– You can map data from block transfer modules to these tags.
Publication 1757-UM007D-EN-P - December 2008 29
Configure the 1757-ABRIO Module Chapter 2
Flag Read (3) and Flag Write (4) tags
– Flag read and write tags are arrays of 512 bits.
– Block transfer modules also have status bits that can be
mapped to flag read tags.
– Dragging an entire I/O Grp to a Flag Read or Flag Write tag
will expose all discrete read or write values for that rack as
well as the Rack Global Status tag.
Text Read (5) tags
– Text read tags are arrays of 64 bytes.
– They are used only with the 1770-HT1 HART module.
From the ProcessLogix or ControlLogix perspective, the HART
interface is read only. You can read text and tags from the
HART, but you can’t write data to the HART.
30 Publication 1757-UM007D-EN-P - December 2008
Chapter 2 Configure the 1757-ABRIO Module
Create a Tag
If you are planning to use automatic digital tags via a scheduled
connection to the 1757-ABRIO module from a ControlLogix controller,
do not create tags. Refer to Scheduled Digital I/O Connections in
RSLogix 5000 Programs on page 60. For all other tag types (analog,
text) and unscheduled connections, tags must be manually created.
To create a tag, complete the following steps.
1. Select the appropriate tab for the type of tag you want to create.
2. Right-click the root of the tree in the tag area and select Add
Tag.
The Add a Tag dialog box opens.
3. Type a tag name.
Tag names can be from 1 to 32 characters in length and must be
unique.
4. Type a message timeout time.
This is the time during which the host controller must update
the tag. The range of values is from 100 to 15000 ms. The default
is 5000 ms.
If the message timeout is exceeded, the tag times out and the
1757-ABRIO module takes the appropriate action.
5. Click OK to accept the tag.
You can create a maximum of 64 tags, of any combination of
types.
Publication 1757-UM007D-EN-P - December 2008 31
Configure the 1757-ABRIO Module Chapter 2
Mapping Data to Tags in
AbRioCfg Software
If you are using a ControlLogix controller, no actions are necessary to
read or write digital data with scheduled connections. Refer to
Scheduled Digital I/O Connections in RSLogix 5000 Programs on
page 60 for more information.
If you are using a ProcessLogix controller, you need to create flag
read and flag write tags in AbRioCfg software to have access to this
data.
Block Transfers
When mapping block transfer modules, drag the analog module from
the network tree to the location in the tag where you want the data to
be located.
Block transfer read data can be mapped to numeric read tags.
Block transfer write data can be mapped to numeric write tags.
You cannot map individual registers; all the data for a rack or I/O
module is mapped to the tag. You can map data from many I/O
modules into the same tag.
Mappings must be unique. You cannot map a block transfer module
to more than one tag of the same type or to multiple locations within
the same tag.
In addition, block transfer modules have status information that can
be mapped to flag read tags. Refer to Supported 1771 Modules on
page 83 for detailed information on status information.
TIP Rack Digital Data
If you would like to use scheduled ControlNet connections to
the 1757-ABRIO module via a ControlLogix controller, do not
map any racks to digital tags. This is done for you when the
scheduled connection is established. Refer to Scheduled Digital
I/O Connections in RSLogix 5000 Programs on page 60 for more
information.
32 Publication 1757-UM007D-EN-P - December 2008
Chapter 2 Configure the 1757-ABRIO Module
I/O
To map I/O data to a tag, complete the following steps.
1. Expand the tag to show the tag elements.
2. Scroll to display the destination in the tag where you want to
add the data.
3. Drag the rack or block transfer module to the desired location in
the tag.
Deleting Mapped Data
To delete mapped data from a tag, complete the following steps.
1. Select any element of the data.
2. Click Delete.
You cannot delete individual elements of the data for an I/O module.
When you delete an element you delete all the data for the particular
module. Data is not affected for the other modules mapped to the
same tag.
Tips for Configuring
Modules
Use the largest range of raw values possible for the 1757-ABRIO
module and optimum data resolution. The scaling should be done to
engineering units in the module.
The following operations are features of firmware version 2.1. To use
these features, you need the following:
Firmware version 2.1 or above for the 1757-ABRIO module
AbRioCfg software version 2.0 or above
AbRioCfg software version 2.0 or above can open or upload
configurations made with previous versions of AbRioCfg
software.
Publication 1757-UM007D-EN-P - December 2008 33
Configure the 1757-ABRIO Module Chapter 2
Add Racks Offline
To add a rack, complete the following steps.
1. Right-click Hardware Config and select Add A Rack.
2. Enter the Rack Number (1 to 37 octal), Starting I/O Group
(0,2,4,6) and Ending I/O Group (1,3,5,7) and click OK.
34 Publication 1757-UM007D-EN-P - December 2008
Chapter 2 Configure the 1757-ABRIO Module
Delete Racks Offline
To delete racks offline, complete the following steps.
1. Right-click the partial rack and select Delete Rack.
A warning dialog box opens.
2. Click OK.
When you delete a rack, all I/O modules on the rack and flag
mappings for the rack are deleted. If this partial rack is the only one in
the rack number, the rack number will be deleted from the tree.
Publication 1757-UM007D-EN-P - December 2008 35
Configure the 1757-ABRIO Module Chapter 2
Change the Baud Rate Offline
To change the baud rate offline, complete the following steps.
1. Select Actions>Change Baud Rate.
The Select Baud Rate dialog box opens.
2. Select the desired baud rate and click OK.
A warning window opens
3. To select the path to the 1757-ABRIO module from an RSWho
window, click Yes.
To make this change in the offline file only, click No.
Download the
Configuration
To download the configuration to the 1757-ABRIO module from
AbRioCfg software, select Actions>Download config or click the
Download Configuration to Module button on the toolbar.
WARNING
Downloading a configuration disrupts communication between
the 1757-ABRIO module and the RIO network.
If the module is in active or forced active mode, the
configuration program asks if you want to remove it from
active mode.
Scaling data for modules that have not been mapped to tags is
not downloaded with the configuration.
36 Publication 1757-UM007D-EN-P - December 2008
Chapter 2 Configure the 1757-ABRIO Module
Upload the Configuration To upload a configuration from a 1757-ABRIO module, select
Actions>Upload config or click the Upload Config From Module
button on the toolbar.
37Publication 1757-UM007D-EN-P - December 2008 37
Chapter 3
Creating Generic Modules in AbRioCfg
Software
Introduction This chapter describes using a generic module type which supports
any block transfer I/O module that uses 16-bit integer data. To use
these features, you need the following:
Firmware version 2.1 or above of the firmware for the
1757-ABRIO module
AbRioCfg software version 2.1 or above
AbRioCfg software version 2.1 or above can open or upload
configurations made with previous versions of AbRioCfg
software.
If you are using a 1771 module refer to Supported 1771 Modules on
page 83.
If you need to access HART data refer to Accessing HART Data on
page 115.
Generic Module Overview The generic module type makes it possible to do the following:
Configure and communicate with any block transfer I/O module
that uses 16-bit integer data. You create the configuration file as
a comma-separated variable (CSV) file, using a spreadsheet or
text editor, and import it using AbRioCfg software.
Configure a block transfer module that is already supported by
AbRioCfg software in ways that the standard configuration does
not allow, for example, using fewer channels than in the
standard module configuration, or adding features not
supported by the standard configuration.
Have up to 100 different generic module types in an
1757-ABRIO configuration file, and an unlimited number of
modules made from those 100 types.
38 Publication 1757-UM007D-EN-P - December 2008
Chapter 3 Creating Generic Modules in AbRioCfg Software
Generic Module
Configuration File
The Generic Module configuration file consists of these sections.
– the configuration block transfer write (BTW)
– the data block transfer read
– the data block transfer write
Most configuration files have a configuration block transfer write.
Some may have both data block transfer read and data block transfer
write sections; others will have just one or the other. The maximum
size for each section is 64 words of data.
You can add comments to the file by preceding them with a
semicolon. Comments can be added to the end of an existing line or
can occupy separate lines. The configuration file can be created as a
text file or as a spreadsheet using a program like Excel and saved as a
CSV file.
To use a text file, separate the data fields with commas. To use a
spreadsheet, put the data values in separate columns.
Configuration Block Transfer Write
The configuration block transfer write section (Config BTW) contains
the data that is sent to the module to set how it operates. The
configuration block transfer write is sent:
at powerup
when communication is restored after being lost
when the remote I/O network switches from program to run
The first line of the configuration block transfer write is the keyword
“configbtw”, followed by the block transfer length, in words.
This is followed by data definitions that consist of an offset and a
value.
IMPORTANT The length of a CSV filename must not exceed 31 characters.
TIP Sample configuration files are available for your use. The files
are located in the GenProfile directory on the supplied
1757-ABRIO CD.
EXAMPLE configbtw, 13
Publication 1757-UM007D-EN-P - December 2008 39
Creating Generic Modules in AbRioCfg Software Chapter 3
The offset is the offset into the block transfer and ranges from 0 to the
block transfer length - 1. For example, if the block transfer is 10 words
long, the allowed offsets range from 0 to 9.
The value can be in one of the following formats:
Binary values start with a leading “0b”. Hexadecimal values start with
a leading “0x”. It's usually easier and less prone to error to enter the
values in binary or hexadecimal.
Format Range
Binary 0b0000000000000000 to 0b1111111111111111
Hexadecimal 0x0000 to 0xFFFF
Unsigned integer 0 to 65535
Signed integer -32768 to 32767
TIP If a module does not require a configuration block transfer
write, you can omit the Config BTW section of the configuration
file. For example, an SLC analog module does not require a
Config BTW section in the file.
EXAMPLE 0, 0b1011001100100001
7, 0xB321
11, 45857
Only non-zero values need be entered; all other values in the
configuration block transfer will default to 0.
40 Publication 1757-UM007D-EN-P - December 2008
Chapter 3 Creating Generic Modules in AbRioCfg Software
Example: 1771-IFE Module
The following configuration block transfer write file configures a
1771-IFE for the following:
differential operation (8 input channels)
each channel set for 1-5 VDC or 4-20 mA
two's complement binary data format
each channel's raw data scaled between 0 and 4095
Refer to the 1771-IFE module documentation for configuration details.
configbtw, 21 ; length 21
0, 0
1, 0
2, 0x0500 ; differential inputs, binary
3, 0
4, 0
5, 0
6, 0x4095 ; channel 1 scaling
7, 0
8, 0x4095 ; channel 2 scaling
9, 0
10, 0x4095 ; channel 3 scaling
11, 0
12, 0x4095 ; channel 4 scaling
13, 0
14, 0x4095 ; channel 5 scaling
15, 0
16, 0x4095 ; channel 6 scaling
17, 0
18, 0x4095 ; channel 7 scaling
19, 0
20, 0x4095 ; channel 8 scaling
Publication 1757-UM007D-EN-P - December 2008 41
Creating Generic Modules in AbRioCfg Software Chapter 3
Example: 1771-OFE module
The following configuration block transfer write file configures a
1771-OFE for:
binary data format
raw data from 0 to 0x0fff (0 to 4095 decimal) on each channel
0 values have been omitted.
Refer to the 1771-OFE module documentation for the details.
Data Block Transfer Read
The data block transfer read defines the cyclic block transfer read that
is used to read data from an input module, and is sometimes used to
read status data from an output module.
The data block transfer read consists of a numeric section and a flag
section.
The beginning of the data block transfer read section is marked by the
keyword “databtr”, followed by the block transfer read length.
Numeric Data
The numeric section of the data block transfer read defines the I/O
data - its location, format, and scaling.
The beginning of the numeric section is marked by the keyword
“numeric”, followed by the number of values to be defined, and the
data format.
EXAMPLE databtr, 15
configbtw, 13 ; length 13
4, 0x8000 ; binary data format
6, 0x0fff ; maximum raw value channel 1
8, 0x0fff ; maximum raw value channel 2
10, 0x0fff ; maximum raw value channel 3
12, 0x0fff ; maximum raw value channel 4
42 Publication 1757-UM007D-EN-P - December 2008
Chapter 3 Creating Generic Modules in AbRioCfg Software
AbRioCfg software checks the number of values to be defined against
the actual number of definitions and indicates an error if they do not
match.
The format can be one of:
All items must have the same format.
This is followed by definitions for the I/O data values, each on a row
of the spreadsheet (or line of a text file). Each definition consists of
the following fields:
Some modules have data underrange and overrange bits to indicate
out-of-range inputs.
If the underrange or overrange bit is set, the AbRioCfg software
sets the I/O value to NaN.
Format Range of values
BCD 0 to 9999
Unsigned 0 to 65535
Integer -32768 to 32767
EXAMPLE numeric, 4, BCD
numeric, 8, integer
Quantity Description
BTR offset Offset into BTR data The BTR offset is the offset into
the BTR data for the I/O data value
Underrange offset(1)
(1) If the offset is not used, the field must be left blank (not 0).
Word offset of underrange bit, 0–15
Underrange bit Bit number, 0–15
Overrange offset(1) Word offset of overrange bit, 0–15
Overrange bit Bit number, 0–15
Polarity offset(1) Word offset of polarity bit, 0–15
Polarity bit Bit number, 0–15
Minimum raw value Minimum raw input
Maximum raw value Maximum raw input
Minimum scale value Minimum floating point scaled value that corresponds
to minimum raw value
Maximum scale value Maximum floating point scaled value that
corresponds to maximum raw value
Publication 1757-UM007D-EN-P - December 2008 43
Creating Generic Modules in AbRioCfg Software Chapter 3
If the module does not have overrange or underrange bits, leave
those fields blank in the configuration file.
Some modules have a separate polarity bit to indicate the sign of an
input.
If the polarity bit is set, the 1757-ABRIO module assigns the
corresponding data a negative value.
the 1757-ABRIO module uses the polarity offset and bit only for
the BCD data type. It ignores them for the other data types.
If the data type is BCD, enter the raw minimum and maximum values
in decimal, not hexadecimal. For example is the range is 0 to 9999,
enter the value as 9999, not 0x9999.
Flag Data
In some cases the block transfer read contains data that we want to
map to flag read tags, for example, a module error bit. If a module has
flag data defined, you can then map it to flag read data in AbRioCfg
software.
The flag data section of the Data Block Transfer read defines the
location of this discrete data.
The beginning of the flag section is marked by a line containing the
keyword “flag”, followed by the total length of the flags data, in bits.
The length must be a multiple of 8.
This is followed by a number of lines that define where the flag data
is found. Each line consists of an offset and a length. The maximum
number of flag data definition lines is 4.
EXAMPLE A 1771-IFE module has channel 1 data at offset 4, the
underrange bit is in offset 1, bit 0, the overrange bit is in offset
2, bit 0, and the polarity bit is in offset 3, bit 0. The raw data
ranges from 0 to 4095. We want to scale the raw data to
floating point values from 0 to 1000.
In a text file:
4,1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000
In a spreadsheet:
EXAMPLE flag, 32
numeric 4 BCD
4 1 0 2 0 3 0 0 4095 0 1000
44 Publication 1757-UM007D-EN-P - December 2008
Chapter 3 Creating Generic Modules in AbRioCfg Software
The offset is an offset into the block transfer. It can range from 0 to
the length of the block transfer - 1. If the offset is followed by an “H”,
it refers to the high byte of the block transfer word. The length can
range from 8 to 504 and must be a multiple of 8. The sum of the
lengths in the data definitions must match the length in the “flag” line.
Example: 1771-IFE Module
The following definitions assign the underrange and overrange bits
from a 1771-IFE module to flag data.
Special Flag Read Data
In addition to any flag read data you define in the configuration file,
the Generic Module always has 8 bits of predefined flag read data.
This data is found at the beginning of the flag data for the module. It
consists of the following flags:
EXAMPLE flag, 32
Bit Description
0 Good communication, set to 1 if the block transfer to the module is
updating, 0 otherwise.
1 BTR Raw underrange bit, set if the raw input to the module is less than the
defined raw minimum. The module sets the scaled input to NaN.
2 BTR raw overrange, set if the raw input to the module is greater than the
defined raw maximum. The module sets the scaled input to NaN.
3 Reserved
4 Reserved
5 BTW raw underrange, set if the calculated output value is less than the
defined raw minimum. The module clamps the output at the raw minimum.
6 BTW raw overrange, set if the calculated output value is greater than the
defined raw maximum. The module clamps the value at the raw maximum.
7 BTW NaN, set if the floating point value written from the host is NaN.
0,8
2H,8
4,16
flag, 32
1,16
2,16
Publication 1757-UM007D-EN-P - December 2008 45
Creating Generic Modules in AbRioCfg Software Chapter 3
Sample 1771-IFE Configuration File
Data Block Transfer Write
The data block transfer write defines the cyclic block transfer read that
is used to write data to an output module. The data block transfer
write consists of a numeric section and a flag section. The beginning
of the data block transfer write section is marked by the keyword
“databtw, followed by the block transfer write length.
EXAMPLE databtw, 12
configbtw, 21 ; length 21
2, 0x0500 ; differential inputs, binary
5, 0
6, 0x4095 ; channel 1 scaling
7, 0
8, 0x4095 ; channel 2 scaling
9, 0
10, 0x4095 ; channel 3 scaling
11, 0
12, 0x4095 ; channel 4 scaling
13, 0
14, 0x4095 ; channel 5 scaling
15, 0
16, 0x4095 ; channel 6 scaling
17, 0
18, 0x4095 ; channel 7 scaling
19, 0
20, 0x4095 ; channel 8 scaling
databtr, 12
numeric, 4, signed
4, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000
5, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000
6, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000
7, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000
8, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000
9, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000
10, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000
11, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000
flag, 32
1, 16
2, 16
46 Publication 1757-UM007D-EN-P - December 2008
Chapter 3 Creating Generic Modules in AbRioCfg Software
Numeric Data
The numeric section of the data block transfer write defines the I/O
data - its location, format, and scaling.
The beginning of the numeric section is marked by the keyword
“numeric”, the number of values to be defined, and the data format.
AbRioCfg software checks the number of values to be defined against
the actual number of definitions and indicates an error if they do not
match.
The format can be one of the following.
All items must have the same format.
This line is followed by definitions for the I/O data values, each on a
row of the spreadsheet (or line of a text file). Each definition consists
of the following fields:
The BTW offset is the offset into the BTW data for the I/O data value.
Some modules have a separate polarity bit to indicate the sign of an
input. If the data being written is negative, the 1757-ABRIO module
sets the polarity bit.
Format Range of values
BCD 0 to 9999
Unsigned 0 to 65535
Integer -32768 to 32767
EXAMPLE numeric, 4, BCD
numeric, 8, integer
Quantity Description
BTW offset Offset into BTW data
Polarity offset Word offset of polarity bit
Polarity bit Bit number, 0-15
Minimum raw value Minimum raw output
Maximum raw value Maximum raw output
Minimum scale value Minimum floating point scaled value that corresponds
to minimum raw value
Maximum scale value Maximum floating point scaled value that corresponds
to maximum raw value
Publication 1757-UM007D-EN-P - December 2008 47
Creating Generic Modules in AbRioCfg Software Chapter 3
The 1757-ABRIO module uses the polarity offset and bit only for the
BCD data type. It ignores them for the other data types.
If the scaled valued written is NaN, the raw output gets set to the
corresponding value in the configuration data. For example, if an I/O
data value is at offset 7 in the data block transfer write, the value at
offset 7 in the configuration block transfer write is written if the host
controller writes NaN to the tag that is mapped to the I/O value.
Flag Data
In some cases the block transfer write contains data that we want to
map to flag write tags.
The flag data section of the Data Block Transfer write defines the
location of this discrete data.
The beginning of the flag section is marked by a line containing the
keyword “flag”, followed by the total length of the flags data, in bits.
The length can be from 8 to 504 and must be a multiple of 8.
This is followed by a number of lines that define where the flag data
is found. Each line consists of an offset and a length. The maximum
number of flag definition lines is 4.
The offset is an offset into the block transfer. It can range from 0 to
the length of the block transfer - 1. If the offset is followed by an “H”,
it refers to the high byte of the block transfer word.
The length can range from 8 to 504 and must be a multiple of 8.
TIP If the data type is BCD, enter the raw minimum and maximum
values in decimal, not hexadecimal. For example is the range is
0 to 9999, enter the value as 9999, not 0x9999.
EXAMPLE A 1771-OFE module has channel 1 data at offset 0. The polarity
bit is offset 4 bit 0. We want to write floating point values from
0 to 1000 and have them scaled to the raw values 0 to 4095.
In a text file:
0, 4, 0, 0, 4095, 0, 1000
In a spreadsheet:
EXAMPLE flag, 32
0 4 0 0 4095 0 1000
48 Publication 1757-UM007D-EN-P - December 2008
Chapter 3 Creating Generic Modules in AbRioCfg Software
The sum of the lengths in the data definitions must match the length
in the “flag” line.
Example 1771-OFE Configuration File
Creating a Generic Module
in AbRioCfg software
To add a generic module in AbRioCfg software, complete the
following steps.
1. Right-click the rack to which the module will be added and
select Add Module.
EXAMPLE flag, 32
0,8
2H,8
4,16
configbtw, 13 ; length 13
4, 0x8000 ; binary data format
6, 0x0fff ; maximum raw value channel 1
8, 0x0fff ; maximum raw value channel 2
10, 0x0fff ; maximum raw value channel 3
12, 0x0fff ; maximum raw value channel 4
databtw, 12
numeric, 4
0, 4, 0, 0, 4095, 0, 1000
1, 4, 1, 0, 4095, 0, 1000
2, 4, 2, 0, 4095, 0, 1000
3, 4, 3, 0, 4095, 0, 1000
Publication 1757-UM007D-EN-P - December 2008 49
Creating Generic Modules in AbRioCfg Software Chapter 3
2. Select a Module Type of Generic Module, the location for the
module and click OK.
3. Browse to or type the CSV file and path and click Import.
AbRioCfg software imports the configuration file and displays
the contents, or gives an error message if it finds problems with
the file.
4. Assign values for the BTR and BTW Update Times.
5. Click OK to accept the module.
You can now map the data to tags by dragging the Generic module to
the desired numeric read, numeric write, flag read or flag write tag.
To change the configuration, re-import the configuration. If the
generic module was mapped to tags, the mappings will be deleted
and must be reassigned.
50 Publication 1757-UM007D-EN-P - December 2008
Chapter 3 Creating Generic Modules in AbRioCfg Software
You can export the generic module configuration by clicking the
Export button in the Generic Module dialog box. Since comments in
the original file are not imported (and therefore are not exported), it is
usually better to modify the original configuration file and save it with
a new name. Export may be useful if you upload a configuration that
contains a generic module from a 1757-ABRIO module and you do
not have the original file.
51Publication 1757-UM007D-EN-P - December 2008 51
Chapter 4
Configuring the ProcessLogix Controller to
Access Data on the 1757-ABRIO Module
Introduction This chapter describes:
the operating modes of the 1757-ABRIO module.
how to access data on the module from a ProcessLogix
controller.
Modes of Operation There are four modes of operation for the module.
CONFIG
INACTIVE (Program)
ACTIVE (Run)
FORCED ACTIVE
The mode of the 1757-ABRIO module determines the RIO network
mode.
Modes related to RIO network operations:
INACTIVE (Program) mode, digital inputs continue to update
but digital outputs and block transfers do not.
ACTIVE (Run) mode, digital inputs and outputs update, and
block transfers update.
CONFIG Mode
The module is in CONFIG mode while AbRioCfg software downloads
a configuration. CONFIG mode is largely invisible to the user unless
the configuration being downloaded is large. After downloading, the
software returns the module to INACTIVE mode.
52 Publication 1757-UM007D-EN-P - December 2008
Chapter 4 Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module
INACTIVE Mode
The module is in INACTIVE mode when it is not receiving messages
from either a host controller or via OPC/DDE. The module is also in
INACTIVE mode when it has not been put in FORCED ACTIVE mode
by AbRioCfg software.
When the module is in INACTIVE mode, the RIO network is placed in
program mode with input updates but no output updates. The
1757-ABRIO module must be in the INACTIVE mode to accept a
download.
ACTIVE Mode (Run)
The module is in ACTIVE mode when it receives a message from
either a host controller or from an OPC or DDE server. When the
module is in ACTIVE mode, the RIO network is in run mode.
The module is in ACTIVE mode as long as any tag is being updated.
Each tag has an associated time-out. The tag is considered to be
updating until the time-out expires. If all tags have timed out, the
1757-ABRIO module automatically switches to INACTIVE mode.
If you try to download a configuration when the module is in ACTIVE
mode, AbRioCfg software asks if you want to take the module out of
ACTIVE mode. If you click OK, AbRioCfg software changes the mode,
downloads the configuration, then puts the module in INACTIVE
mode.
FORCED ACTIVE Mode
The module is in FORCED ACTIVE mode when you set ACTIVE mode
from the AbRioCfg program. FORCED ACTIVE mode lets you send
and receive data without having to create messages in the module. It
is intended primarily for setting up and testing RIO networks.
If you try to download a configuration when the module is in
FORCED ACTIVE mode, AbRioCfg software asks if you want to take
the module out of ACTIVE mode. If you click OK, AbRioCfg software
changes the mode, downloads the configuration, then puts the
module in INACTIVE mode.
IMPORTANT When the module is in FORCED ACTIVE mode, the RIO network
is in run mode.
Publication 1757-UM007D-EN-P - December 2008 53
Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module Chapter 4
Configure the 1757-PLX52
Controller
To access tag data on the 1757-ABRIO module from a ProcessLogix
controller, use the REQNUMARRAY, REQFLAGARRAY and
REQTEXTARRAY Exchange Blocks with CIPREAD and CIPWRITE
commands to read and write tags.
Use Control Builder software to complete the following steps.
1. Select the Exchange Block from the Library in Control Builder.
2. Add the desired Exchange Block to the CM (Control Module) by
dragging it into the CM window.
– REQFLAGARRAY for flag data
– REQNUMARRAY for numeric data
– REQTEXTARRAY for text data
3. Expand the Exchange Block by double-clicking on it.
4. Select the Main tab.
5. Give the block a name and set the execution order.
6. Select either CIPREAD or CIPWRITE for the message command.
54 Publication 1757-UM007D-EN-P - December 2008
Chapter 4 Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module
7. Set the number of values to be read or written.
a. Flag arrays, 512 max
b. Numeric arrays, 64 max
c. Text arrays, 64 max
Array Examples
8. Set the data type to be read or written.
a. Numeric arrays, set Data Type in Target Device to FLOAT32.
b. Text arrays, set the Number of String Values to 1 and the Char
Length of String Values to 64.
9. Select the Communications tab.
10. Set the Path from the ProcessLogix controller to the 1757-ABRIO
module.
See the tip on page 72 or Control Builder Help for information
on entering the path.
Flag Arrays Numeric Arrays Text Arrays
Publication 1757-UM007D-EN-P - December 2008 55
Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module Chapter 4
11. Set the File Name in the Exchange Blocks to the names of the
tags you created in the 1757-ABRIO module.
12. Perform any other configuration required by your application on
the other tabs.
13. Click OK to accept the block.
14. Wire the ready flag (READYFL) to the send flag (SENDFL) for
each exchange block.
15. Download the CM to the ProcessLogix controller and activate it.
IMPORTANT Be sure to expose the Error codes in your Exchange Blocks.
56 Publication 1757-UM007D-EN-P - December 2008
Chapter 4 Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module
Live Data Examples
Double-click function block
57Publication 1757-UM007D-EN-P - December 2008 57
Chapter 5
Configuring RSLogix 5000 Software to Access
Data on the 1757-ABRIO Module
Introduction This chapter describes:
the operating modes of the 1757-ABRIO module.
how to access data on the module from a ControlLogix
controller.
Modes of Operation There are four modes of operation for the module.
CONFIG
INACTIVE (Program)
ACTIVE (Run)
FORCED ACTIVE
The mode of the 1757-ABRIO module determines the RIO network
mode.
Modes related to RIO network operations:
INACTIVE (Program) mode, digital inputs continue to update
but digital outputs and block transfers do not.
ACTIVE (Run) mode, digital inputs and outputs update, and
block transfers update.
CONFIG Mode
The module is in CONFIG mode while AbRioCfg software downloads
a configuration. CONFIG mode is largely invisible to the user unless
the configuration being downloaded is large. After downloading, the
software returns the module to INACTIVE mode.
58 Publication 1757-UM007D-EN-P - December 2008
Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module
INACTIVE Mode
The module is in INACTIVE mode when it is not receiving messages
from either a host controller or via OPC/DDE. The module is also in
INACTIVE mode when it has not been put in FORCED ACTIVE mode
by AbRioCfg software.
When the module is in INACTIVE mode, the RIO network is placed in
program mode with input updates but no output updates. The
1757-ABRIO module must be in the INACTIVE mode to accept a
download.
When scheduled connections are used, the 1757-ABRIO module’s
mode will always follow the ControlLogix controller’s mode regardless
if it is receiving messages. For example, when the controller is in
PROGRAM mode, the module is in INACTIVE mode.
ACTIVE Mode (Run)
The module is in ACTIVE mode when it receives a message from
either a host controller or from an OPC or DDE server. When the
module is in ACTIVE mode, the RIO network is in run mode.
The module is in ACTIVE mode as long as any tag is being updated.
Each tag has an associated time-out. The tag is considered to be
updating until the time-out expires. If all tags have timed out, the
1757-ABRIO module automatically switches to INACTIVE mode.
If you try to download a configuration when the module is in ACTIVE
mode, AbRioCfg software asks if you want to take the module out of
ACTIVE mode. If you click OK, AbRioCfg software changes the mode,
downloads the configuration, then puts the module in INACTIVE
mode.
When scheduled connections are used, the 1757-ABRIO module’s
mode will always follow the ControlLogix controller’s mode regardless
if it is receiving messages. For example, when the controller is in RUN
mode, the module is in ACTIVE mode.
Publication 1757-UM007D-EN-P - December 2008 59
Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5
FORCED ACTIVE Mode
The module is in FORCED ACTIVE mode when you set ACTIVE mode
from the AbRioCfg program. FORCED ACTIVE mode lets you send
and receive data without having to create messages in the module. It
is intended primarily for setting up and testing RIO networks.
If you try to download a configuration when the module is in
FORCED ACTIVE mode, AbRioCfg software asks if you want to take
the module out of ACTIVE mode. If you click OK, AbRioCfg software
changes the mode, downloads the configuration, then puts the
module in INACTIVE mode.
IMPORTANT When the module is in FORCED ACTIVE mode, the RIO network
is in run mode.
60 Publication 1757-UM007D-EN-P - December 2008
Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module
Scheduled Digital I/O
Connections in RSLogix
5000 Programs
1757-ABRIO module firmware versions 1.2 and above support
scheduled connections for exchanging digital input and output data
between the 1757-ABRIO module and the host ControlLogix
controller. This results in much faster updates for the digital data than
is possible using unscheduled messages. This section describes how
to configure the module and the format of the scheduled data.
When you add a 1757-ABRIO module to the I/O Configuration of an
RSLogix 5000 program using the generic 1757-MODULE profile, a data
connection is created for the digital remote I/O data. See Tag
Descriptions for Scheduled Data in RSLogix 5000 Software on
page 149 for more information about the status tag when using
ControlLogix. The status tag gives global status for digital data and
individual rack status.
Scheduled Connection Types
There are two types of scheduled connection.
Exclusive Owner, read/write
Input Only, read only
Setup an Exclusive-owner Connection
Configure a generic module profile in RSLogix 5000 software to
represent the 1757-ABRIO module. This dictates the format and
amount of scheduled data, and how often the scheduled data is
transferred. The ControlLogix controller is the owner of the
connection and controls the digital outputs. The connection is referred
to as an exclusive-owner connection.
TIP In order to access any numeric read, numeric write, or text read
data from the ControlLogix controller you must also complete
Unscheduled I/O Connections in ControlLogix on page 67.
IMPORTANT In order for the scheduled connection to control the outputs of a
chassis, the chassis must not be mapped to any flag write tag
in the AbRioCfg software configuration that has been
downloaded to the 1757-ABRIO module.
Publication 1757-UM007D-EN-P - December 2008 61
Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5
Remote I/O Operating Modes
If there is an exclusive-owner connection to the 1757-ABRIO module,
the module’s remote I/O mode (run or program) follows the owner
ControlLogix controller’s Run or Program mode. If the owner
ControlLogix controller is in Program mode, the 1757-ABRIO module
is in program mode (even if the module is receiving messages). If the
ControlLogix controller is in Remote Test mode, the remote I/O mode
for the 1757-ABRIO module is program.
The remote I/O mode is not affected by the operating mode of a
ControlLogix controller that has an input-only connection to the
1757-ABRIO module. In the absence of an exclusive-owner
connection, the 1757-ABRIO module’s remote I/O mode is determined
by whether it is receiving messages, as before.
Add a Module as an Exclusive-owner Connection
To configure the 1757-ABRIO module in RSLogix 5000 software, the
ControlLogix controller must be offline.
1. Create a new project for your type of controller.
2. Type a name for the controller, and select the slot it occupies in
the ControlLogix chassis.
3. Click OK.
4. Right-click on I/O configuration and select New Module.
5. Under Other, select the 1756-MODULE Generic 1756 Module
and click OK.
The Module Properties dialog box opens.
62 Publication 1757-UM007D-EN-P - December 2008
Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module
6. Type a Name and a Description for the module, if desired.
7. Set the Slot number for the module in the ControlLogix chassis.
8. For the Comm Format, select Data - INT - With Status.
9. Select the following values for the Connection Parameters.
10. Verify that the Open Module Properties checkbox is checked
and click OK.
11. Set the module’s Requested Packet Interval (RPI).
This is how often the module's scheduled data is updated in the
controller. The value can range from 0.2 to 750 ms. The default
time is 5 ms.
12. Click OK.
13. Save the program and download it to the ControlLogix
controller.
Assembly
Instance
Size
Input 1 250
Output 2 248
Configuration 4 0
Status Input 5 10
Status Output 6 N/A
Publication 1757-UM007D-EN-P - December 2008 63
Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5
Output Priority
If a digital rack is mapped to a flag write tag in the AbRioCfg software,
the flag data takes precedence over the digital outputs in the
scheduled connection, even if nothing is writing to the flag write tag.
To control outputs on a chassis using a scheduled connection, make
sure the chassis is not mapped to a flag write tag.
Setup Input-only Connections
The 1757-ABRIO module also supports input-only connections. In a
ControlLogix system, multiple controllers can receive inputs from a
module, but only one controller can control the outputs. An
input-only connection does not require the presence of an exclusive
owner connection. More than one ControlLogix controller can open
an input-only connection to the 1757-ABRIO module and receive its
inputs.
Add a Module as an Input-only Connection
To configure an input-only connection to the 1757-ABRIO module in
RSLogix 5000 software, you must be offline.
1. Create a new project for your type of controller.
2. Type a name for the controller, and select the slot it occupies in
the ControlLogix chassis.
3. Click OK.
4. Right-click on I/O configuration and select New Module.
5. Under Other, select the 1756-MODULE Generic 1756 Module
and click OK.
64 Publication 1757-UM007D-EN-P - December 2008
Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module
The Module Properties dialog box opens.
6. Type a Name and a Description for the module, if desired.
7. Set the Slot number for the module in the ControlLogix chassis.
8. For the Comm Format, select Input Data - INT - With Status.
9. Select the following values for the Connection Parameters.
Assembly
Instance
Size
Input 1 250
Output 3 N/A
Configuration 4 0
Status Input 5 10
Status Output 6 N/A
Publication 1757-UM007D-EN-P - December 2008 65
Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5
10. Verify that the Open Module Properties checkbox is checked
and click OK.
11. Set the module’s Requested Packet Interval.
This is how often the module's scheduled data is updated in the
controller. The value can range from 0.2 to 750 ms. The default
is 5 ms.
66 Publication 1757-UM007D-EN-P - December 2008
Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module
12. Click OK.
13. Save the program and download it to the ControlLogix
controller.
Live Data Example
Click the 1757-ABRIO module to
display the new tags. See Tag
Descriptions for Scheduled Data in
RSLogix 5000 Software on
page 149 for details.
Publication 1757-UM007D-EN-P - December 2008 67
Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5
Unscheduled I/O
Connections in
ControlLogix
There are several tasks you need to complete before you can access
data from ControlLogix. You need to create the following:
Tags for messages
Tags for storage areas
Message commands to read RIO network data
Message commands to write RIO network data
Use RSLogix 5000 message instructions (MSG) to access tags on the
1757-ABRIO module. Refer to RSLogix 5000 Online Help and the
Logix5000 Controllers General Instructions Reference Manual,
publication 1756-RM003, for details on messages.
Before you create the MSG instruction, create a tag of type MESSAGE
to act as a control for the MSG instruction. You must also create a
source (write) or destination (read) tag for the data written to or read
from the 1757-ABRIO module.
1. Create Tags For All Messages and All Storage Areas
RSLogix 5000 Example Tags in Program Mode
For message type,
select CIP Data
Table Read or
Data Table Write.
On a Read, the
source is a
1757-ABRIO Tag
Name. The
Destination, on a
Read, is an
RSLogix 5000 Tag
Name.
These are the tags
you will reference
in your message
commands.
68 Publication 1757-UM007D-EN-P - December 2008
Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module
2. Create Message Commands to Read and Write All RIO
Network Data
RSLogix 5000 Example Message Commands in Program Mode
This table shows the source (write) or destination (read) data type to
use with each 1757-ABRIO tag type and the size for each type.
Use the Browse
button ( ) to
locate the
read/write tags
you want to
reference in your
message
commands. See
Create a Tag on
page 30 for more
information.
ControlLogix Data types
1757-ABRIO Tag Source/destination Type Storage Data Size
Numeric read REAL 64
Numeric write REAL 64
Flag read DINT 16
Flag Write DINT 16
Text read SINT 64
Publication 1757-UM007D-EN-P - December 2008 69
Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5
Use the following steps to add the MSG instruction.
1. Add the MSG instruction to the ladder logic, along with
whatever logic you want to use to cause the instruction to
execute.
2. Open the Message Configuration dialog box by clicking the
button in the instruction.
3. Select the Message Type.
The Message type should be either CIP Data Table Read to read
a tag from the 1757-ABRIO module or CIP Data Table Write to
write a tag to the 1757-ABRIO module.
WARNING
The EN_CC bit in a ControlLogix MESSAGE tag defaults to on. If
the message executes successfully even once, it gets retried
periodically, even if the ladder logic has disabled the message.
If you want to keep the connection open no matter what, turn
on the bit.
Turn off the EN_CC bit in any ControlLogix MESSAGE tag you
use in a MSG instruction to access data on the 1757-ABRIO
module.
70 Publication 1757-UM007D-EN-P - December 2008
Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module
4. Select the Source Element.
If you are writing to the 1757-ABRIO module, this is the
ControlLogix controller tag.
If you are reading from the 1757-ABRIO module, this is the
name of the tag in the 1757-ABRIO module.
The 1757-ABRIO module must return different data types to
ProcessLogix and ControlLogix controllers. For example, to read
a tag with name FlagRead, you would create a MSG instruction
with Source Element set to FlagRead[100].
5. Type the Number of Elements.
This is usually the number from the table on page 68. You can
select a size smaller than the maximum if not all of the elements
in the 1757-ABRIO module tag have been mapped.
6. Select the Destination Element.
TIP
IMPORTANT If you are reading flag read tags using a ControlLogix controller,
you must append [100] to the 1757-ABRIO tag name. This tells
the 1757-ABRIO module that the message is coming from a
ControlLogix controller.
Use this tag To
All_Analog_Read Read data from input modules.
The tag is listed under Numeric Read Tags.
All_Flag_Read[100] Flag read for status and digital data.
This is the message needed to get to analog
data.
Publication 1757-UM007D-EN-P - December 2008 71
Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5
7. Select the Communication tab.
8. Type the path from the ControlLogix controller to the
1757-ABRIO module.
72 Publication 1757-UM007D-EN-P - December 2008
Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module
When you are using scheduled connections in ControlLogix this
is automatically populated with your 1757-ABRIO module’s
name and address through an RSNetworx network polling.
9. Click OK to accept the MSG instruction.
10. After all message instructions are configured, save the program
and download it to the ControlLogix controller.
TIP The 1757-ABRIO module, ProcessLogix controller and
ControlLogix controller (most likely) will not be in the same
racks. Refer to RSLogix 5000 Online Help and the Logix5000
Controllers General Instructions Reference Manual, publication
1756-RM003 for details on MSG paths.
TIP If you need to manually input the communications path to a module, follow this
general example of how to find the path to the rack.
Illustrated is the path from the
ProcessLogix or the ControlLogix
controller to the remote 1757-ABRIO
module.
Path = 1,4,2,20,1,2
1: From the backplane
4: Node, 1756-CNBR Module in slot 4
2: Path out of the CNBR, ControlNet
20: MAC ID of the target CNBR in the remote rack
2:Slot location of the 1757-ABRIO module
1: From the CNBR, via the backplane
Publication 1757-UM007D-EN-P - December 2008 73
Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5
Live Data Example
74 Publication 1757-UM007D-EN-P - December 2008
Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module
Ladder Rung Example
75Publication 1757-UM007D-EN-P - December 2008 75
Chapter 6
Accessing Data through a DDE or OPC Server
Introduction This chapter describes how to access data on the module using a DDE
or OPC Server.
Accessing Data from a DDE
or OPC Server
You can access data on the 1757-ABRIO module directly using a DDE
or OPC server such as RSLinx software, without the intervention of a
host controller.
Configuring a Topic in RSLinx Software
Use the following procedure to use RSLinx software as a DDE or OPC
server to access data on the 1757-ABRIO module.
1. Start RSLinx software
2. Select DDE/OPC Topic Configuration from the main menu.
3. Click New to create a new DDE or OPC topic, and give the topic
a name.
4. Select the Data Source tab and browse to the 1757-ABRIO
module.
5. Select the Data Collection tab.
6. Set the Processor Type to Logix5000.
7. Check Polled Messages and set the poll period to an appropriate
value.
8. Un-check Unsolicited Messages.
9. Leave the remaining values at their default values and click
Apply.
10. Select the Advanced Communication tab.
11. Select the Communications Driver you are using.
76 Publication 1757-UM007D-EN-P - December 2008
Chapter 6 Accessing Data through a DDE or OPC Server
12. Change Local or Remote Addressing defaults to Local.
If you are using a bridge device to communicate with the
1757-ABRIO module, select Remote and configure the bridging.
Refer to the RSLinx software documentation for detailed
information on how to configure bridging.
13. Click Done to accept the DDE/OPC topic.
Accessing the Data
1. Start your DDE or OPC client.
2. Connect to RSLinx software.
The 1757-ABRIO module supports browsing of tags.
3. Type or browse to the tags you want to monitor in the client.
77Publication 1757-UM007D-EN-P - December 2008 77
Chapter 7
Monitoring the 1757-ABRIO Module
Introduction This chapter provides the following information on:
monitoring the operation of the 1757-ABRIO module.
monitoring the data value of tags.
monitoring the status of a block transfer.
monitoring the scanner log.
recognizing and clearing fatal errors.
Monitoring the Operation The AbRioCfg software lets you monitor the operation of the module
and perform maintenance operations. Tag, block transfer, and module
diagnostic counters are available only from AbRioCfg software, and
are not available to a ProcessLogix or ControlLogix controller.
AbRioCfg software can be used to:
display the current values of the digital inputs and outputs.
display the current values of block transfer data, along with
diagnostic information on the block transfer.
display the current contents of a tag.
display the module log, which consists of messages from the
firmware running on the module.
clear the log.
copy the contents of the log to the clipboard for use by another
application. This is often useful for technical support.
clear fatal errors and dump the fatal error log to a file for use by
technical support.
Monitoring Digital I/O To monitor the current value of digital inputs or digital outputs on all
racks, select Tools>Monitor Inputs or Tools>Monitor Outputs.
Rows correspond to racks 1 to 37 octal; columns correspond
to I/O groups 0 to 7.
Data can be displayed in hexadecimal, signed decimal, or
unsigned decimal using the View menu or buttons on the
toolbar. The default format is hexadecimal. One hexadecimal
digit corresponds to 4 digital bits.
You can use the monitor program to edit data.
78 Publication 1757-UM007D-EN-P - December 2008
Chapter 7 Monitoring the 1757-ABRIO Module
Use the Edit>Write toolbar button or the menu item to enable editing.
You can now change any data and it will be written to the network
(outputs) or to the data table (inputs). However if the same data is
being updated by I/O modules or the controller, the value you write is
overwritten the next time this I/O module is scanned.
Monitoring the Data Value
of Tags
To monitor the current data value in a tag, complete the following
steps.
1. Select the corresponding tab for the data type of the tag you
want to monitor (Numeric read, etc.).
2. Select the tag you want to monitor.
3. Right-click the tag and select Monitor Tag.
The tag monitor displays the raw data for the tag, as well as
diagnostic data.
The raw data can be displayed as floating point, hexadecimal, signed,
or unsigned integer.
Refer to the following table for tag diagnostic information.
To clear the diagnostic counters, select Actions>ClearDiagCounters or
click the Clear Diag Counters button on the toolbar.
Tag Diagnostic Counters
Counter Description
Tag Name The tag name in AbRioCfg software
Command Read or write
Type Numeric, flag or text
MsgNum 0 to 63, used internally by the 1757-ABRIO module
Len Tag length, units are bytes for flag and text tags, floats for
numeric tags
Req count Number of updates this tag has been accessed (read or written)
Avg Req Time Average update time for this tag, in ms. This is the average of
the previous 64 updates.
Min Req Time Minimum request time for this tag, in ms
Max Req Time Maximum update time for this tag, in ms
Time out The message time-out, in ms
Status Active or Inactive
Publication 1757-UM007D-EN-P - December 2008 79
Monitoring the 1757-ABRIO Module Chapter 7
If you attempt to monitor a tag that has not been downloaded to the
1757-ABRIO module, AbRioCfg software displays a message that
indicates there is a configuration mismatch between the configuration
in AbRioCfg software and the configuration in the 1757-ABRIO
module.
Monitoring the Status of a
Block Transfer
To monitor the current status of a block transfer, complete the
following steps.
1. Expand the chassis where the block transfer module you want
to monitor is located.
2. Select the module you want to monitor.
3. Right-click the module to highlight and select Monitor BT from
the menu.
The block transfer monitor displays the raw data for the block transfer
and some diagnostic information. For input modules there is both a
block transfer read and a block transfer write. The write consists of
configuration data.
The raw data can be displayed as hexadecimal, signed, or unsigned
integer. The default for block transfer data is hexadecimal.
Refer to the following table for diagnostic information on block
transfer reads.
TIP Use the same procedure to monitor digital and text data.
Block Transfer Read Diagnostics
Counter Description
State Active/Inactive
Type Module type
BTR Len Block transfer read length
Req Update Time Requested update time in the module configuration, in ms
Avg Update Time Average update time for this block transfer read, in ms. This
is the average of the previous 8 updates.
Min Update Time Minimum update time for this block transfer read, in ms
Max Update Time Maximum update time for this block transfer read, in ms
Update Count Running count of updates for this block transfer read
80 Publication 1757-UM007D-EN-P - December 2008
Chapter 7 Monitoring the 1757-ABRIO Module
Refer to the following table for block transfer write diagnostics.
Monitoring the Scanner Log The scanner log displays messages from the 1757-ABRIO firmware,
showing its normal operation and error messages. It may be useful in
tracking down errors and for Technical Support.
To monitor the scanner log, select Tools>Monitor Scanner Log.
To clear the scanner log, select Edit>ClearLog or click the Clear Log
button.
To copy the contents of the log to the Windows clipboard for use in
another application, select Edit>Copy or click Select All then the Copy
button.
Ignored Req Running count of update requests ignored by the block
transfer module.
Prot Errors Running count of protocol errors for this block transfer read.
If this counter is incrementing, the module isn't responding
correctly. Possible causes are length mismatch, invalid reply.
Request Count Count of the number of times on successive scans this block
transfer was requested. If this is consistently a high number,
increase the requested update time - the module cannot
respond quickly enough at the current requested time. The
counter applies to both the BTR and BTW for this module.
Block Transfer Write Diagnostic Data
Counter Description
CFG len Length of the configuration data for this module.
BTW data len data length
Req Update Time Requested update time in module configuration, in ms.
Avg Update Time Average update time for this block transfer write, in ms. This
is the average of the previous 8 updates.
Min Update Time Minimum update time for this block transfer write, in ms.
Max Update Time Maximum update time for this block transfer write, in ms.
Update Count Running count of updates for this block transfer write.
Ignored Req Running count of update requests ignored by the destination
module for this block transfer write.
Prot Errs Running count of protocol errors for this block transfer write.
Block Transfer Read Diagnostics
Counter Description
Publication 1757-UM007D-EN-P - December 2008 81
Monitoring the 1757-ABRIO Module Chapter 7
Monitoring Diagnostic
Counters
The 1757-ABRIO module maintains diagnostic counters that indicate
the state of communication on the entire RIO network, as well as
counters related to each chassis. It also maintains an active rack list.
To monitor the diagnostic counters, select Tools>Monitor Diagnostic
Counters or click the Start the Diagnostics Counters Monitor button.
Active Rack List
The active rack list shows where the racks are located. If the bit is set
there is a rack at that rack number and starting I/O group. It does not
show the rack size.
The rows represent starting I/O groups. The columns represent the
rack numbers.
Global Diagnostic Counters
The global diagnostic counters consist of the following.
Global Diagnostic Counters
Counter Description
Tx This counter increments each time the 1757-ABRIO module transmits a
packet.
RxGood This counter increments when the 1757-ABRIO module receives a good
packet.
RxTout This counter increments when the 1757-ABRIO module sends a packet
but does not receive a reply.
RxBadCRC This counter increments when the 1757-ABRIO module receives a
packet with a bad CRC. Check cabling and termination on the RIO
network.
RxNoise This counter increments when the 1757-ABRIO module hears a carrier
without receiving a packet. Check cabling and termination on the RIO
network.
RxAbort This counter increments when the 1757-ABRIO module receives an
opening flag, then the packet ends without a closing flag.
PrtclErr This counter increments when the 1757-ABRIO module receives a
packet that makes no sense in terms of the protocol.
UpdAvg Average update time for all configured racks. This is the average of the
previous 64 updates.
UpdMin Minimum update time for all configured racks.
UpdMax Maximum update time for all configured racks.
82 Publication 1757-UM007D-EN-P - December 2008
Chapter 7 Monitoring the 1757-ABRIO Module
The rack diagnostic counters consist of the following counters for
each partial rack.
Fatal Errors Fatal errors occur when the firmware on the module encounters an
unexpected condition. The module stops scanning, turns all three
status indicators red, displays the fatal error number on the 4-character
display, and stores a fatal error log that indicates the cause of the fatal
error.
To clear the fatal error and capture the fatal error log:
1. Cycle power to the module.
The 4-character display should show “FatalErrorCapture
required”.
2. Start AbRioCfg software.
3. Select Tools>Fatal Error Capture.
4. Store the fatal error log to a file.
This also clears the fatal error on the module.
5. Contact Rockwell Automation Technical Support and provide
them with the fatal error log, which will help diagnose the cause
of the problem.
Clearing fatal errors also clears the configuration on the module. After
you clear the fatal error, download the configuration to the module
using AbRioCfg software.
Rack Diagnostic Counters
Counter Description
Rx This counter increments when the 1757-ABRIO module receives a
packet from this rack.
Crc This counter increments when the 1757-ABRIO module receives a
packet with a bad CRC from this rack.
Tout This counter increments when the 1757-ABRIO module sends a packet
to this rack and does not receive a reply within the time-out period.
Prtcl This counter increments when the 1757-ABRIO module receives a
packet from this rack that does not make sense in terms of the
protocol.
83Publication 1757-UM007D-EN-P - December 2008 83
Chapter 8
Supported 1771 Modules
Introduction This chapter:
lists the supported 1771 modules.
describes module configuration, I/O Data, and diagnostic data.
Module Description The 1757-ABRIO module supports all digital 1771 modules and the
following 1771 block transfer modules. For information on how to
communicate with other block transfer I/O modules, see Creating
Generic Modules in AbRioCfg Software on page 37.
Refer to the corresponding pages in this chapter for information about
configuring these modules with the 1757-ABRIO module.
The AbRioCfg software handles the details of module configuration
using the parameters you supply. For applicable modules, the
1757-ABRIO module scales the raw data to floating point values using
optimal data resolution on the I/O module.
Supported modules
Module Description Page
1771-IFE Analog input module 84
1771-OFE Analog output module 89
1771-IR RTD input module 92
1771-IXE Thermocouple/millivolt module 95
1771-IL Analog input module 98
1771-NOC High resolution current output module 101
1771-NIV High resolution voltage input module 107
1771-NOV High resolution voltage output module 104
1771-NR RTD input module 110
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio
Red rio

Más contenido relacionado

La actualidad más candente

Samsung gt s5230 código master resert
Samsung gt s5230 código master resertSamsung gt s5230 código master resert
Samsung gt s5230 código master resertLuis Martins
 
Placas base evolucion[1]
Placas base evolucion[1]Placas base evolucion[1]
Placas base evolucion[1]zuzanitah
 
Trustone tsg-550 750-install_user manual
Trustone tsg-550 750-install_user manualTrustone tsg-550 750-install_user manual
Trustone tsg-550 750-install_user manualProtocol Corporation
 
GXV3000 Video Grandstream
GXV3000 Video GrandstreamGXV3000 Video Grandstream
GXV3000 Video GrandstreamLojamundi
 
GeoVision : Integration Solutions : CCTV and Access Control Monitor Entry or ...
GeoVision : Integration Solutions : CCTV and Access Control Monitor Entry or ...GeoVision : Integration Solutions : CCTV and Access Control Monitor Entry or ...
GeoVision : Integration Solutions : CCTV and Access Control Monitor Entry or ...TSOLUTIONS
 
P4 m8p m7c-0227c_b
P4 m8p m7c-0227c_bP4 m8p m7c-0227c_b
P4 m8p m7c-0227c_bIsma Othman
 
Reuse Your Old Personal Gsm Phone For Sms Control And Monitoring
Reuse Your Old Personal Gsm Phone For Sms Control And MonitoringReuse Your Old Personal Gsm Phone For Sms Control And Monitoring
Reuse Your Old Personal Gsm Phone For Sms Control And MonitoringIonela
 
Bt Synergy 3005 User Guide from Telephones Online www.telephonesonline.co.uk
Bt Synergy 3005 User Guide from Telephones Online  www.telephonesonline.co.ukBt Synergy 3005 User Guide from Telephones Online  www.telephonesonline.co.uk
Bt Synergy 3005 User Guide from Telephones Online www.telephonesonline.co.ukTelephones Online
 
Polycom soundpoint ip300 user guide
Polycom soundpoint ip300 user guidePolycom soundpoint ip300 user guide
Polycom soundpoint ip300 user guidebest4systems
 
Bt Synergy 3105 User Guide from Telephones Online www.telephonesonline.co.uk
Bt Synergy 3105 User Guide from Telephones Online  www.telephonesonline.co.ukBt Synergy 3105 User Guide from Telephones Online  www.telephonesonline.co.uk
Bt Synergy 3105 User Guide from Telephones Online www.telephonesonline.co.ukTelephones Online
 
Hp laptop keyboard
Hp laptop keyboardHp laptop keyboard
Hp laptop keyboardbattguide
 
F5 m instruction manual
F5 m instruction manualF5 m instruction manual
F5 m instruction manualToàn Huỳnh
 
Connection manual (non mitsubishi products 2 for gt works3)
Connection manual (non mitsubishi products 2 for gt works3)Connection manual (non mitsubishi products 2 for gt works3)
Connection manual (non mitsubishi products 2 for gt works3)nguyen_nbn
 

La actualidad más candente (20)

Samsung gt s5230 código master resert
Samsung gt s5230 código master resertSamsung gt s5230 código master resert
Samsung gt s5230 código master resert
 
Readme
ReadmeReadme
Readme
 
Placas base evolucion[1]
Placas base evolucion[1]Placas base evolucion[1]
Placas base evolucion[1]
 
Trustone tsg-550 750-install_user manual
Trustone tsg-550 750-install_user manualTrustone tsg-550 750-install_user manual
Trustone tsg-550 750-install_user manual
 
GXV3000 Video Grandstream
GXV3000 Video GrandstreamGXV3000 Video Grandstream
GXV3000 Video Grandstream
 
Sa 1.01 changes
Sa 1.01 changesSa 1.01 changes
Sa 1.01 changes
 
GeoVision : Integration Solutions : CCTV and Access Control Monitor Entry or ...
GeoVision : Integration Solutions : CCTV and Access Control Monitor Entry or ...GeoVision : Integration Solutions : CCTV and Access Control Monitor Entry or ...
GeoVision : Integration Solutions : CCTV and Access Control Monitor Entry or ...
 
M7vcm10
M7vcm10M7vcm10
M7vcm10
 
P4 m8p m7c-0227c_b
P4 m8p m7c-0227c_bP4 m8p m7c-0227c_b
P4 m8p m7c-0227c_b
 
Asterisk: ¡dongled!
Asterisk: ¡dongled!Asterisk: ¡dongled!
Asterisk: ¡dongled!
 
Reuse Your Old Personal Gsm Phone For Sms Control And Monitoring
Reuse Your Old Personal Gsm Phone For Sms Control And MonitoringReuse Your Old Personal Gsm Phone For Sms Control And Monitoring
Reuse Your Old Personal Gsm Phone For Sms Control And Monitoring
 
Bt Synergy 3005 User Guide from Telephones Online www.telephonesonline.co.uk
Bt Synergy 3005 User Guide from Telephones Online  www.telephonesonline.co.ukBt Synergy 3005 User Guide from Telephones Online  www.telephonesonline.co.uk
Bt Synergy 3005 User Guide from Telephones Online www.telephonesonline.co.uk
 
06.Manual Sg80
06.Manual Sg8006.Manual Sg80
06.Manual Sg80
 
3 diagnostic
3 diagnostic3 diagnostic
3 diagnostic
 
Polycom soundpoint ip300 user guide
Polycom soundpoint ip300 user guidePolycom soundpoint ip300 user guide
Polycom soundpoint ip300 user guide
 
Bt Synergy 3105 User Guide from Telephones Online www.telephonesonline.co.uk
Bt Synergy 3105 User Guide from Telephones Online  www.telephonesonline.co.ukBt Synergy 3105 User Guide from Telephones Online  www.telephonesonline.co.uk
Bt Synergy 3105 User Guide from Telephones Online www.telephonesonline.co.uk
 
Hp laptop keyboard
Hp laptop keyboardHp laptop keyboard
Hp laptop keyboard
 
Gsmae GSM Alarm System user's manual
Gsmae GSM Alarm System user's manualGsmae GSM Alarm System user's manual
Gsmae GSM Alarm System user's manual
 
F5 m instruction manual
F5 m instruction manualF5 m instruction manual
F5 m instruction manual
 
Connection manual (non mitsubishi products 2 for gt works3)
Connection manual (non mitsubishi products 2 for gt works3)Connection manual (non mitsubishi products 2 for gt works3)
Connection manual (non mitsubishi products 2 for gt works3)
 

Destacado

Password hacking
Password hackingPassword hacking
Password hackingAbhay pal
 
TOGY KUWAIT 2016 cover
TOGY KUWAIT 2016 coverTOGY KUWAIT 2016 cover
TOGY KUWAIT 2016 coverTomas Engle
 
Password Recovery Tools
Password Recovery ToolsPassword Recovery Tools
Password Recovery ToolsAndrey Belenko
 
Competition Track project ( Max Retail )
Competition Track project  ( Max Retail )Competition Track project  ( Max Retail )
Competition Track project ( Max Retail )Akash Jaiswal
 

Destacado (7)

Password hacking
Password hackingPassword hacking
Password hacking
 
SDATA CompanyProfile
SDATA CompanyProfileSDATA CompanyProfile
SDATA CompanyProfile
 
TOGY KUWAIT 2016 cover
TOGY KUWAIT 2016 coverTOGY KUWAIT 2016 cover
TOGY KUWAIT 2016 cover
 
Splash retail
Splash retailSplash retail
Splash retail
 
Memory card recovery software
Memory card recovery softwareMemory card recovery software
Memory card recovery software
 
Password Recovery Tools
Password Recovery ToolsPassword Recovery Tools
Password Recovery Tools
 
Competition Track project ( Max Retail )
Competition Track project  ( Max Retail )Competition Track project  ( Max Retail )
Competition Track project ( Max Retail )
 

Similar a Red rio (20)

Manual guia power flex525
Manual guia power flex525Manual guia power flex525
Manual guia power flex525
 
520com um001 -en-e
520com um001 -en-e520com um001 -en-e
520com um001 -en-e
 
Manual micrologix 1100
Manual micrologix 1100Manual micrologix 1100
Manual micrologix 1100
 
Manual del usuario Satloc bantam
Manual del usuario Satloc bantamManual del usuario Satloc bantam
Manual del usuario Satloc bantam
 
20him um001 -en-p
20him um001 -en-p20him um001 -en-p
20him um001 -en-p
 
Win plc engine-en
Win plc engine-enWin plc engine-en
Win plc engine-en
 
Man hinh dieu khien
Man hinh dieu khienMan hinh dieu khien
Man hinh dieu khien
 
475 manual
475 manual475 manual
475 manual
 
Modicon m241 logic
Modicon m241 logicModicon m241 logic
Modicon m241 logic
 
Netgear User Manual
Netgear User ManualNetgear User Manual
Netgear User Manual
 
Analog module omron
Analog module omronAnalog module omron
Analog module omron
 
ABB PROFIBUS.
ABB   PROFIBUS.    ABB   PROFIBUS.
ABB PROFIBUS.
 
Man hinh otd
Man hinh otdMan hinh otd
Man hinh otd
 
Omron CS1D
Omron CS1DOmron CS1D
Omron CS1D
 
Phasor series operating_manual
Phasor series operating_manualPhasor series operating_manual
Phasor series operating_manual
 
Smart otdr JDSU
Smart otdr JDSUSmart otdr JDSU
Smart otdr JDSU
 
Simocode dp = manual de parametrização e operação
Simocode dp = manual de parametrização e operaçãoSimocode dp = manual de parametrização e operação
Simocode dp = manual de parametrização e operação
 
software-eng.pdf
software-eng.pdfsoftware-eng.pdf
software-eng.pdf
 
Tso clist unknown
Tso clist   unknownTso clist   unknown
Tso clist unknown
 
Pci 8158 manual-10
Pci 8158 manual-10Pci 8158 manual-10
Pci 8158 manual-10
 

Último

FUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENTFUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENTSneha Padhiar
 
SOFTWARE ESTIMATION COCOMO AND FP CALCULATION
SOFTWARE ESTIMATION COCOMO AND FP CALCULATIONSOFTWARE ESTIMATION COCOMO AND FP CALCULATION
SOFTWARE ESTIMATION COCOMO AND FP CALCULATIONSneha Padhiar
 
Immutable Image-Based Operating Systems - EW2024.pdf
Immutable Image-Based Operating Systems - EW2024.pdfImmutable Image-Based Operating Systems - EW2024.pdf
Immutable Image-Based Operating Systems - EW2024.pdfDrew Moseley
 
ROBOETHICS-CCS345 ETHICS AND ARTIFICIAL INTELLIGENCE.ppt
ROBOETHICS-CCS345 ETHICS AND ARTIFICIAL INTELLIGENCE.pptROBOETHICS-CCS345 ETHICS AND ARTIFICIAL INTELLIGENCE.ppt
ROBOETHICS-CCS345 ETHICS AND ARTIFICIAL INTELLIGENCE.pptJohnWilliam111370
 
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithmComputer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithmDeepika Walanjkar
 
Novel 3D-Printed Soft Linear and Bending Actuators
Novel 3D-Printed Soft Linear and Bending ActuatorsNovel 3D-Printed Soft Linear and Bending Actuators
Novel 3D-Printed Soft Linear and Bending ActuatorsResearcher Researcher
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating SystemRashmi Bhat
 
Detection&Tracking - Thermal imaging object detection and tracking
Detection&Tracking - Thermal imaging object detection and trackingDetection&Tracking - Thermal imaging object detection and tracking
Detection&Tracking - Thermal imaging object detection and trackinghadarpinhas1
 
priority interrupt computer organization
priority interrupt computer organizationpriority interrupt computer organization
priority interrupt computer organizationchnrketan
 
Stork Webinar | APM Transformational planning, Tool Selection & Performance T...
Stork Webinar | APM Transformational planning, Tool Selection & Performance T...Stork Webinar | APM Transformational planning, Tool Selection & Performance T...
Stork Webinar | APM Transformational planning, Tool Selection & Performance T...Stork
 
"Exploring the Essential Functions and Design Considerations of Spillways in ...
"Exploring the Essential Functions and Design Considerations of Spillways in ..."Exploring the Essential Functions and Design Considerations of Spillways in ...
"Exploring the Essential Functions and Design Considerations of Spillways in ...Erbil Polytechnic University
 
Katarzyna Lipka-Sidor - BIM School Course
Katarzyna Lipka-Sidor - BIM School CourseKatarzyna Lipka-Sidor - BIM School Course
Katarzyna Lipka-Sidor - BIM School Coursebim.edu.pl
 
The Satellite applications in telecommunication
The Satellite applications in telecommunicationThe Satellite applications in telecommunication
The Satellite applications in telecommunicationnovrain7111
 
Substation Automation SCADA and Gateway Solutions by BRH
Substation Automation SCADA and Gateway Solutions by BRHSubstation Automation SCADA and Gateway Solutions by BRH
Substation Automation SCADA and Gateway Solutions by BRHbirinder2
 
AntColonyOptimizationManetNetworkAODV.pptx
AntColonyOptimizationManetNetworkAODV.pptxAntColonyOptimizationManetNetworkAODV.pptx
AntColonyOptimizationManetNetworkAODV.pptxLina Kadam
 
Prach: A Feature-Rich Platform Empowering the Autism Community
Prach: A Feature-Rich Platform Empowering the Autism CommunityPrach: A Feature-Rich Platform Empowering the Autism Community
Prach: A Feature-Rich Platform Empowering the Autism Communityprachaibot
 
Cost estimation approach: FP to COCOMO scenario based question
Cost estimation approach: FP to COCOMO scenario based questionCost estimation approach: FP to COCOMO scenario based question
Cost estimation approach: FP to COCOMO scenario based questionSneha Padhiar
 
Input Output Management in Operating System
Input Output Management in Operating SystemInput Output Management in Operating System
Input Output Management in Operating SystemRashmi Bhat
 
Artificial Intelligence in Power System overview
Artificial Intelligence in Power System overviewArtificial Intelligence in Power System overview
Artificial Intelligence in Power System overviewsandhya757531
 
CME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTES
CME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTESCME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTES
CME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTESkarthi keyan
 

Último (20)

FUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENTFUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
 
SOFTWARE ESTIMATION COCOMO AND FP CALCULATION
SOFTWARE ESTIMATION COCOMO AND FP CALCULATIONSOFTWARE ESTIMATION COCOMO AND FP CALCULATION
SOFTWARE ESTIMATION COCOMO AND FP CALCULATION
 
Immutable Image-Based Operating Systems - EW2024.pdf
Immutable Image-Based Operating Systems - EW2024.pdfImmutable Image-Based Operating Systems - EW2024.pdf
Immutable Image-Based Operating Systems - EW2024.pdf
 
ROBOETHICS-CCS345 ETHICS AND ARTIFICIAL INTELLIGENCE.ppt
ROBOETHICS-CCS345 ETHICS AND ARTIFICIAL INTELLIGENCE.pptROBOETHICS-CCS345 ETHICS AND ARTIFICIAL INTELLIGENCE.ppt
ROBOETHICS-CCS345 ETHICS AND ARTIFICIAL INTELLIGENCE.ppt
 
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithmComputer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithm
 
Novel 3D-Printed Soft Linear and Bending Actuators
Novel 3D-Printed Soft Linear and Bending ActuatorsNovel 3D-Printed Soft Linear and Bending Actuators
Novel 3D-Printed Soft Linear and Bending Actuators
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating System
 
Detection&Tracking - Thermal imaging object detection and tracking
Detection&Tracking - Thermal imaging object detection and trackingDetection&Tracking - Thermal imaging object detection and tracking
Detection&Tracking - Thermal imaging object detection and tracking
 
priority interrupt computer organization
priority interrupt computer organizationpriority interrupt computer organization
priority interrupt computer organization
 
Stork Webinar | APM Transformational planning, Tool Selection & Performance T...
Stork Webinar | APM Transformational planning, Tool Selection & Performance T...Stork Webinar | APM Transformational planning, Tool Selection & Performance T...
Stork Webinar | APM Transformational planning, Tool Selection & Performance T...
 
"Exploring the Essential Functions and Design Considerations of Spillways in ...
"Exploring the Essential Functions and Design Considerations of Spillways in ..."Exploring the Essential Functions and Design Considerations of Spillways in ...
"Exploring the Essential Functions and Design Considerations of Spillways in ...
 
Katarzyna Lipka-Sidor - BIM School Course
Katarzyna Lipka-Sidor - BIM School CourseKatarzyna Lipka-Sidor - BIM School Course
Katarzyna Lipka-Sidor - BIM School Course
 
The Satellite applications in telecommunication
The Satellite applications in telecommunicationThe Satellite applications in telecommunication
The Satellite applications in telecommunication
 
Substation Automation SCADA and Gateway Solutions by BRH
Substation Automation SCADA and Gateway Solutions by BRHSubstation Automation SCADA and Gateway Solutions by BRH
Substation Automation SCADA and Gateway Solutions by BRH
 
AntColonyOptimizationManetNetworkAODV.pptx
AntColonyOptimizationManetNetworkAODV.pptxAntColonyOptimizationManetNetworkAODV.pptx
AntColonyOptimizationManetNetworkAODV.pptx
 
Prach: A Feature-Rich Platform Empowering the Autism Community
Prach: A Feature-Rich Platform Empowering the Autism CommunityPrach: A Feature-Rich Platform Empowering the Autism Community
Prach: A Feature-Rich Platform Empowering the Autism Community
 
Cost estimation approach: FP to COCOMO scenario based question
Cost estimation approach: FP to COCOMO scenario based questionCost estimation approach: FP to COCOMO scenario based question
Cost estimation approach: FP to COCOMO scenario based question
 
Input Output Management in Operating System
Input Output Management in Operating SystemInput Output Management in Operating System
Input Output Management in Operating System
 
Artificial Intelligence in Power System overview
Artificial Intelligence in Power System overviewArtificial Intelligence in Power System overview
Artificial Intelligence in Power System overview
 
CME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTES
CME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTESCME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTES
CME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTES
 

Red rio

  • 1. User Manual (Catalog Number 1757-ABRIO) Process Remote I/O (RIO) Communication Interface Module
  • 2. Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. Allen-Bradley, Rockwell Automation, RSLogix 5000, ControlLogix, ProcessLogix, RSLinx, ControlFlash, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. WARNING Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. IMPORTANT Identifies information that is critical for successful application and understanding of the product. ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence SHOCK HAZARD Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
  • 3. 3Publication 1757-UM007D-EN-P - December 2008 3 Table of Contents Preface Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Who Should Use this Manual. . . . . . . . . . . . . . . . . . . . . . . . . 7 Additional Resources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Chapter 1 Introduction Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Process Remote I/O (RIO) Communication Interface Module . 9 RSLinx Software Requirements. . . . . . . . . . . . . . . . . . . . . . . 10 ProcessLogix System Quick Start . . . . . . . . . . . . . . . . . . . . . 11 RSLogix 5000 System Quick Start . . . . . . . . . . . . . . . . . . . . . 12 Update the 1757-ABRIO Module’s Firmware. . . . . . . . . . . . . 14 Using ControlFlash Software. . . . . . . . . . . . . . . . . . . . . . 14 Using NTools with ProcessLogix Software. . . . . . . . . . . . 15 Chapter 2 Configure the 1757-ABRIO Module Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 AbRioCfg Software Overview. . . . . . . . . . . . . . . . . . . . . . . . 17 Mapping and Accessing RIO Network Data . . . . . . . . . . . . . 18 Installing AbRioCfg Software . . . . . . . . . . . . . . . . . . . . . . . . 19 Autoconfigure the I/O Racks . . . . . . . . . . . . . . . . . . . . . . . . 19 Adding Block Transfer Modules. . . . . . . . . . . . . . . . . . . . . . 23 Addressing Modes for 1771 . . . . . . . . . . . . . . . . . . . . . . 24 Configuring Block Transfer Modules . . . . . . . . . . . . . . . . . . 25 Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Input Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Output Scaling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Tags Defined . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Create a Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Mapping Data to Tags in AbRioCfg Software . . . . . . . . . . . . 31 Block Transfers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Deleting Mapped Data . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Tips for Configuring Modules . . . . . . . . . . . . . . . . . . . . . . . 32 Add Racks Offline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Delete Racks Offline . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Change the Baud Rate Offline . . . . . . . . . . . . . . . . . . . . 35 Download the Configuration . . . . . . . . . . . . . . . . . . . . . . . . 35 Upload the Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 36
  • 4. 4 Publication 1757-UM007D-EN-P - December 2008 Table of Contents Chapter 3 Creating Generic Modules in AbRioCfg Software Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Generic Module Overview. . . . . . . . . . . . . . . . . . . . . . . . . . 37 Generic Module Configuration File . . . . . . . . . . . . . . . . . . . 38 Configuration Block Transfer Write. . . . . . . . . . . . . . . . . 38 Data Block Transfer Read. . . . . . . . . . . . . . . . . . . . . . . . 41 Data Block Transfer Write . . . . . . . . . . . . . . . . . . . . . . . 45 Creating a Generic Module in AbRioCfg software . . . . . . . . . 48 Chapter 4 Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 CONFIG Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 INACTIVE Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 ACTIVE Mode (Run) . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 FORCED ACTIVE Mode . . . . . . . . . . . . . . . . . . . . . . . . . 52 Configure the 1757-PLX52 Controller . . . . . . . . . . . . . . . . . . 53 Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 CONFIG Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 INACTIVE Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 ACTIVE Mode (Run) . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 FORCED ACTIVE Mode . . . . . . . . . . . . . . . . . . . . . . . . . 59 Scheduled Digital I/O Connections in RSLogix 5000 Programs . 60 Scheduled Connection Types . . . . . . . . . . . . . . . . . . . . . 60 Setup an Exclusive-owner Connection . . . . . . . . . . . . . . 60 Setup Input-only Connections . . . . . . . . . . . . . . . . . . . . 63 Unscheduled I/O Connections in ControlLogix. . . . . . . . . . . 67 Create Message Commands to Read and Write All RIO Network Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Chapter 6 Accessing Data through a DDE or OPC Server Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Accessing Data from a DDE or OPC Server . . . . . . . . . . . . . 75 Configuring a Topic in RSLinx Software . . . . . . . . . . . . . 75 Accessing the Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
  • 5. Publication 1757-UM007D-EN-P - December 2008 5 Table of Contents Chapter 7 Monitoring the 1757-ABRIO Module Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Monitoring the Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Monitoring Digital I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Monitoring the Data Value of Tags. . . . . . . . . . . . . . . . . . . . 78 Monitoring the Status of a Block Transfer. . . . . . . . . . . . . . . 79 Monitoring the Scanner Log. . . . . . . . . . . . . . . . . . . . . . . . . 80 Monitoring Diagnostic Counters. . . . . . . . . . . . . . . . . . . . . . 81 Active Rack List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Global Diagnostic Counters . . . . . . . . . . . . . . . . . . . . . . 81 Fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Chapter 8 Supported 1771 Modules Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Module Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 1771-IFE Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 85 I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 1771-OFE Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 89 I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 1771-IR Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 92 I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 1771-IXE Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 95 I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 1771-IL Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 98 I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 1771-NOC Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 101 I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 1771-NOV Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 104 I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
  • 6. 6 Publication 1757-UM007D-EN-P - December 2008 Table of Contents 1771-NIV Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 107 I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 1771-NR Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 111 I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Chapter 9 Accessing HART Data Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 Sending HART Commands Using RSLogix 5000 Software MSG . 115 HART Command Data . . . . . . . . . . . . . . . . . . . . . . . . . 117 Reply Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 Example: HART Command 36 . . . . . . . . . . . . . . . . . . . 122 1770-HT1 Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Rack Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Configuring the 1770-HT1 Module . . . . . . . . . . . . . . . . 124 HART Command status . . . . . . . . . . . . . . . . . . . . . . . . 129 Appendix A Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Appendix B Troubleshooting Interpret the Status Indicators . . . . . . . . . . . . . . . . . . . . . . 133 RIO Status Indicator – Remote Devices Status . . . . . . . . 133 SYS Status Indicator – ControlBus Status . . . . . . . . . . . . 133 OK Status Indicator – Module Health . . . . . . . . . . . . . . 134 Status Display Power-up Messages. . . . . . . . . . . . . . . . . . . 134 Power Supply Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . 134 Interpret the Alphanumeric Display . . . . . . . . . . . . . . . . . . 135 Using AbRioCfg Software for Troubleshooting . . . . . . . . . . 136 Troubleshooting Problems. . . . . . . . . . . . . . . . . . . . . . . . . 137 Using RSLogix 5000 to Diagnose Problems. . . . . . . . . . . . . 138 General Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 Connection Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 Module Info Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139 Backplane Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139 Using Control Builder Software to Diagnose Problems . . . . 140 Troubleshooting 1757-ABRIO Module Communications . . . 140
  • 7. Publication 1757-UM007D-EN-P - December 2008 7 Table of Contents Appendix C Operational Comparison Between the 1757-ABRIO Module and a PLC-5 System Normal Operational Messages . . . . . . . . . . . . . . . . . . . . . . 143 Exception Handling Messages . . . . . . . . . . . . . . . . . . . . . . 145 Appendix D Tag Descriptions for Scheduled Data in RSLogix 5000 Software Configuration Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 I and O Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 Status Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
  • 8. 8 Publication 1757-UM007D-EN-P - December 2008 Table of Contents
  • 9. 7Publication 1757-UM007D-EN-P - December 2008 7 Preface Purpose of this Manual This manual describes how to configure and troubleshoot your Process Remote I/O (RIO) Communication Interface Module. For installation information, refer to the Process Remote I/O (RIO) Communication Interface Module Installation Instructions, publication 1757-IN916. Who Should Use this Manual We assume you have a good understanding of Remote I/O (RIO) modules as well as the host controller system (ProcessLogix or ControlLogix). Additional Resources These documents contain additional information concerning related Rockwell Automation products. See I/O Module Documentation on page 84 for a listing of related ControlLogix documentation. You can view or download publications at http://literature.rockwellautomation.com. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative. Resource Description Process Remote I/O (RIO) Communication Interface Module Installation Instructions, publication 1757-IN916 Provides details on how to install the 1757-ABRIO module. Process Remote I/O (RIO) Communication Interface Module Release Notes, publication 1757-RN520 Provides release details on the 1757-ABRIO module. Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Product Certifications website, http://ab.com Provides declarations of conformity, certificates, and other certification details.
  • 10. 8 Publication 1757-UM007D-EN-P - December 2008 Table of Contents Preface
  • 11. 9Publication 1757-UM007D-EN-P - December 2008 9 Chapter 1 Introduction Introduction This chapter: describes the 1757-ABRIO Remote I/O Module. lists the RSLinx software requirements. provides update procedures for the module’s firmware. Process Remote I/O (RIO) Communication Interface Module This document is a user guide for the 1757-ABRIO module, which lets Rockwell Automation controllers (ProcessLogix or ControlLogix) communicate with Allen-Bradley remote I/O. The module acts as a RIO network scanner. The 1757-ABRIO module facilitates connection to analog and discrete I/O devices as well as any block transfer modules. 1757-ABRIO Module Example Topology 43290 Supports Block Transfers - limit of 32 words in a block ProcessLogix System Server Flex Ex Modules PLC5/C Controller ControlNet Network SLC Controller Data Highway + Network ControlNet Network PLC5 Controller ProcessLogix and ControlLogix Controllers Remote I/O Network 1771 Remote I/O 1746 Remote I/O Drive
  • 12. 10 Publication 1757-UM007D-EN-P - December 2008 Chapter 1 Introduction As an RIO network scanner, the module: scans 1771 racks with rack numbers from 1 to 37 octal. supports baud rates of 57.6, 115.2 and 230.4 kilobaud. supports up to 32 adapters with any mix of full/partial racks. automatically manages and performs block transfers, update time can be defined for each block transfer. provides full diagnostic counters for alarms and maintenance. automatically performs scaling of raw analog data. supports scheduled connections to update digital data with a ControlLogix controller. implements a watchdog timer in the module’s hardware. If the firmware does not kick the watchdog within the time-out period the watchdog times out and places the module into the configured safe failure state. automatically provides fault/fail safe commands to I/O modules and controllers. implements a jabber inhibit timer. If the network transmitter is on longer than 150% of the longest network frame time, the 1757-ABRIO module turns the transmitter off and places the module into the configured safe failure state. supports firmware updates using NTools or ControlFlash software. supports direct DDE/OPC data access. provides support for Rockwell Automation’s 1770-HT1, 1770-HT8, and 1770-HT16 HART interface products. provides HART command set for calibration and diagnostics. RSLinx Software Requirements The AbRioCfg software requires RSLinx OEM software or above. You cannot use RSLinx Lite software. To access the module using OPC or DDE, you must have RSLinx 2.31 software or above. If you are using ProcessLogix software, refer to the corresponding ProcessLogix Installation and Upgrade Guide to determine the appropriate RSLinx software version for your release.
  • 13. Publication 1757-UM007D-EN-P - December 2008 11 Introduction Chapter 1 ProcessLogixSystemQuick Start Use the following steps to quickly get the module running in a ProcessLogix system. Detailed information about each step is available in other sections of this manual or in the installation manual. You can only have one scanner per RIO network. Remove any other scanners on the RIO network before continuing. 1. Install the 1757-ABRIO module in the chassis and connect it to the RIO network. See the Process Remote I/O (RIO) Communication Interface Module Installation Instructions, publication 1757-IN916. 2. Flash the controller with the latest firmware. See Using NTools with ProcessLogix Software on page 15. 3. Install the AbRioCfg software. See Installing AbRioCfg Software on page 19. 4. Autoconfigure or manually configure the RIO racks. This step locates all connected racks. See Autoconfigure the I/O Racks on page 19 and Add Racks Offline on page 33. 5. Add and configure block transfer modules. See Adding Block Transfer Modules on page 23. 6. Create tags for access by the ProcessLogix controller. See Create a Tag on page 30. 7. Map I/O data to the tags and save the configuration file. See Mapping Data to Tags in AbRioCfg Software on page 31. 8. Download the configuration to the 1757-ABRIO module. See Download the Configuration on page 35. 9. Configure the ProcessLogix controller to access information within the 1757-ABRIO module using Control Builder software. See Configure the 1757-PLX52 Controller on page 53. 10. Access live data from the 1757-ABRIO module. See Live Data Examples on page 56.
  • 14. 12 Publication 1757-UM007D-EN-P - December 2008 Chapter 1 Introduction RSLogix 5000 System Quick Start Use the following steps to quickly get the module running in an RSLogix 5000 system. Detailed information about each step is available in other sections of this manual or in the installation manual. You can only have one scanner per RIO network. Remove any other scanners on the RIO network before continuing. 1. Install the 1757-ABRIO module in the chassis and connect it to the RIO network. See the Process Remote I/O (RIO) Communication Interface Module Installation Instructions, publication 1757-IN916. 2. Flash the Controller with the latest firmware. See Using ControlFlash Software on page 14. 3. Install the AbRioCfg software. See Installing AbRioCfg Software on page 19. 4. Autoconfigure or manually configure the RIO racks. This step locates all connected racks. See Autoconfigure the I/O Racks on page 19 and Add Racks Offline on page 33. 5. Add and configure block transfer modules. See Adding Block Transfer Modules on page 23. 6. Create tags to access analog data from the ControlLogix controller. See Create a Tag on page 30. OR Use scheduled updates to access digital data from the ControlLogix controller. See Scheduled Digital I/O Connections in RSLogix 5000 Programs on page 60. 7. Map I/O data to the tags and save the configuration file. See Mapping Data to Tags in AbRioCfg Software on page 31. 8. Download the configuration to 1757-ABRIO module. See Download the Configuration on page 35.
  • 15. Publication 1757-UM007D-EN-P - December 2008 13 Introduction Chapter 1 9. If you are using: a. a scheduled network, establish an Exclusive Owner or Input Only connection from the ControlLogix controller to access digital data within the 1757-ABRIO module. See Setup an Exclusive-owner Connection on page 60 or Setup Input-only Connections on page 63. b. an unscheduled network, configure tags and ladder logic in RSLogix 5000 software to access information within the 1757-ABRIO module. See Unscheduled I/O Connections in ControlLogix on page 67. 10. If you are using a scheduled ControlNet network, schedule your network through RSNetWorx for ControlNet software. See the RSNetWorx Help and the ControlNet Modules in Logix5000 Control Systems User Manual, publication CNET-UM001. 11. Access live data from the 1757-ABRIO module via: a. scheduled connections. See Scheduled Digital I/O Connections in RSLogix 5000 Programs on page 60 and Live Data Example on page 66. b. unscheduled connections. See Unscheduled I/O Connections in ControlLogix on page 67 and Live Data Example on page 73. TIP If you are using a scheduled ControlNet network, you must also complete 9b to access analog or text data from the 1757-ABRIO module.
  • 16. 14 Publication 1757-UM007D-EN-P - December 2008 Chapter 1 Introduction Update the 1757-ABRIO Module’s Firmware The 1757-ABRIO module supports firmware upgrades using ControlFLASH or NTools software. The firmware version is displayed on the 1757-ABRIO module’s 4-character display when you power up the module. For ProcessLogix software users, if your 1757-ABRIO module revision is: at or less than 1.2, use ControlFlash software to update the module firmware. greater than 1.2, use NTools software to update the module firmware. Using ControlFlash Software Use the following procedure to update the module firmware using ControlFLASH software. 1. Insert the 1757-ABRIO CD. 2. Click Start>Run. 3. Type this path or Browse to: D:(or your CD-ROM drive letter)ControlFlashsetup.exe 4. Click OK. 5. At the Welcome to ControlFLASH Setup window, click Next. 6. To accept the License Agreement, click Yes. 7. To accept the default location, click Next. 8. At the Setup Complete window, a. Uncheck the Yes, I want to view the README file checkbox. b. Check the Yes, I want to launch ControlFLASH checkbox. c. Click Finish. 9. At the Welcome to ControlFLASH window, click Next. IMPORTANT The module ships with the latest firmware installed. You do not need to download firmware to the 1757-ABRIO module when you first receive it.
  • 17. Publication 1757-UM007D-EN-P - December 2008 15 Introduction Chapter 1 10. Click 1757-ABRIO and click Next. 11. Expand the RSLinx Tree window to the location of the 1757-ABRIO module you wish to flash. 12. Select the module icon and click OK. 13. Confirm new revision for this update and click Next. 14. At the Summary window, click Finish. 15. To confirm the flash, click Yes. 16. Click OK. If this update is successful, the Update Status window displays the following message in green: Update Complete. Please verify this new firmware update before using the target device in its intended application. 17. Click OK and then click Cancel at the Welcome to ControlFLASH Setup window. 18. Click Yes to end the configuration session. Using NTools with ProcessLogix Software On a ProcessLogix system, if the module firmware is at 1.2 or greater, use the following procedure to update the module firmware using NTools. 1. On the ProcessLogix Server, click Start>Run. 2. Type >ntools -c -u<. 3. To launch the Network Tools application, click OK. 4. Click OK at the warning about monitoring through Control Builder software. 5. To initiate the network scan, click Resume. 6. Select the appropriate CNB or ENET icon. 7. Select the module to be updated in the chassis graphic.
  • 18. 16 Publication 1757-UM007D-EN-P - December 2008 Chapter 1 Introduction 8. Click the firmware button and click Yes to acknowledge the warning. 9. Navigate to: D:(or your CD-ROM drive letter)Firmware_NTools 10. Select the appropriate .nvs file. 11. To start the firmware load, click Open. 12. To confirm, click Yes. The Status field in the lower portion of the Network Tools window tracks the load progress. 13. When the load completes, click OK.
  • 19. 17Publication 1757-UM007D-EN-P - December 2008 17 Chapter 2 Configure the 1757-ABRIO Module Introduction This chapter: provides an overview of the AbRioCfg software. gives an introduction to mapping and accessing RIO network data. explains how to install the AbRioCfg software. explains how to autoconfigure I/O racks. explains how to add and configure block transfer modules. AbRioCfg Software Overview The 1757-ABRIO module ships with configuration software, called AbRioCfg. This configuration software is an online configuration tool. Use the configuration software to: query the RIO network to determine the location and size of the racks present. manually add and configure racks present in RIO network. add and configure supported block transfer modules. import comma separated variable files to define the Generic Module as any block transfer module that uses 16-bit integer data. add, edit, and delete racks offline. create tags for access by the controller. map I/O data to those tags. download the configuration to the module, using RSLinx software. monitor data and diagnostics on the module. change the baud rate of network communications in a configuration and download to the module. change the configuration of racks in a configuration and download to the module. upload a configuration from a module. print the configuration.
  • 20. 18 Publication 1757-UM007D-EN-P - December 2008 Chapter 2 Configure the 1757-ABRIO Module Mapping and Accessing RIO Network Data Use the provided AbRioCfg software to create tags which are arrays of digital, floating point or text values that the host controller reads or writes using unscheduled messages. You map data that the module receives or sends into these tags. The data mapping is stored in flash memory on the 1757-ABRIO module. The 1757-ABRIO Module and Data Mapping WARNING It is essential that the control program on the host controller matches the addresses in the mapping configuration on the 1757-ABRIO module. Otherwise the control program may inadvertently write to the incorrect I/O locations. If you change the data mappings on the 1757-ABRIO module, make sure that the control program is using the correct addresses. 1757-ABRIO Module Tag Tag ControlLogix or ProcessLogix Controller Write Data Remote I/O Modules R/W Analog Data with Block Transfer Status R/W digital Data Scales Analog Data Analog/Digital Modules Hard Configured for Safe/Fault States RIO Network Read Data Scan List RIO Network Scanner Remote I/O Modules
  • 21. Publication 1757-UM007D-EN-P - December 2008 19 Configure the 1757-ABRIO Module Chapter 2 Installing AbRioCfg Software 1. Verify that RSLinx software and RSLinx OEM or RSLinx Professional (not RSLinx Lite) software is installed before you install the AbRioCfg software. 2. Insert the CD supplied with the 1757-ABRIO module and run the program setup.exe. 3. Confirm that you have RSLinx OEM or RSLinx Professional (not RSLinx Lite) software installed. Before you install a new version of AbRioCfg software, you must delete the old version. Use the Add or Remove Programs utility in your Windows Control Panel to remove the previous version. Autoconfigure the I/O Racks The first step in building a configuration is to perform an autoconfiguration. To complete an autoconfiguration, the RIO network must be connected to the 1757-ABRIO module and the module must be in “inactive” mode. 1. Start AbRioCfg software. IMPORTANT Messages about the DTL32.DLL during installation or when you run the software indicate problems with the RSLinx software installation. If you get these messages, install the proper version of RSLinx software before you continue. IMPORTANT Removing the software does not delete stored configuration files. TIP If you see question marks for the 1757-ABRIO module when running RSNetWorx or RSLinx software, install the EDS file from the provided CD. You do not need to load the firmware on the CD into your 1757-ABRIO module as the module ships with the latest version of firmware. The firmware is on the CD for archival purposes only. ATTENTION When using AbRioCfg software, you must left-click to select/highlight before you can right-click to activate menu options.
  • 22. 20 Publication 1757-UM007D-EN-P - December 2008 Chapter 2 Configure the 1757-ABRIO Module 2. Click Hardware Config to highlight it and activate the AbRioCfg menu toolbar. 3. Click the Autoconfig button in the toolbar. An RSWho window opens. TIP With AbRioCfg software, 2.0 and higher, you can also manually configure the I/O racks in your network. Refer to Add Racks Offline on page 33 for more information.
  • 23. Publication 1757-UM007D-EN-P - December 2008 21 Configure the 1757-ABRIO Module Chapter 2 4. Navigate to the 1757-ABRIO module. 5. Select the module and click OK. The Select Baud Rate dialog box opens. 6. Select the appropriate baud rate and click OK. The baud rate in this example is set by switches on the 1771-ASB adapter. See your device documentation for how to set the desired baud rate. All racks or devices on one RIO network must operate at the same baud rate.
  • 24. 22 Publication 1757-UM007D-EN-P - December 2008 Chapter 2 Configure the 1757-ABRIO Module The 1757-ABRIO module sends messages to all possible racks and builds the network rack configuration from the responses. It displays a list of the racks it found in the network tree. If you expand a rack, the partial racks that make up that rack number are displayed. 7. If you are using 1771 remote I/O modules, a. Right-click the rack in the network tree and select Enter Rack Switch Setting. The Select Rack Setting dialog box opens.
  • 25. Publication 1757-UM007D-EN-P - December 2008 23 Configure the 1757-ABRIO Module Chapter 2 b. Select the value that matches the Last State switch setting in the backplane of the I/O chassis, either De-energize or Hold Last State. This setting tells the 1757-ABRIO module what to do if the controller stops updating the tag to which this chassis’s digital data is mapped. c. Repeat steps 7a and 7b for all racks that contain 1771 remote I/O modules. Adding Block Transfer Modules Autoconfiguration can locate the racks present on the network but it cannot detect the analog I/O modules in those racks. Remote I/O protocol does not allow for module identification to be communicated on the network. Because of this, Block Transfer modules need to be added manually. You do not have to add digital modules. To add a block transfer module, complete the following steps. 1. Expand the rack that contains the analog I/O module in the network tree. 2. Right-click the partial rack that contains the module and select Add Module. The Add BT Module dialog box opens. 3. Select the Module Type from the pull-down menu.
  • 26. 24 Publication 1757-UM007D-EN-P - December 2008 Chapter 2 Configure the 1757-ABRIO Module 4. Select the slot location for the module. To do this, you should be familiar with Allen-Bradley addresses and, in particular, with 1771 addressing modes (see below). See I/O Module Documentation on page 84 for a list of related ControlLogix documentation. 5. Click OK. Addressing Modes for 1771 The 1771 chassis have three addressing modes - 1/2-slot, 1-slot and 2-slot addressing. The addressing mode is set by switches in the backplane of the chassis and is set on a per-chassis basis. The addressing mode determines how physical block transfer modules map into logical addresses (rack, I/O group and slot). In the following tables, the addresses used for modules in a 16-slot rack in each addressing mode. The rack switches are set for rack 1, starting I/O group 0. As illustrated in the 2-slot addressing table below, the controller addresses two I/O module slots as one I/O group. For example, for a chassis at rack 1, starting I/O group 0, a block transfer module in the first slot would be at address rack 1, I/O group 0, slot 0. A module in the next slot would be at rack 1, I/O group 0, slot 1. As illustrated in the 1-slot addressing table below, the controller addresses one I/O module slot as one I/O group. For example, for a chassis at rack 1, starting I/O group 0, a block transfer module in the first slot would be at address rack 1, I/O group 0, slot 0. A module in the next slot would be at rack 1, I/O group 1, slot 0. 2-Slot Addressing Slot in chassis 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Rack 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I/O Group 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 Slot 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1-Slot Addressing Slot in chassis 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Rack 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 I/O Group 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 Slot 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
  • 27. Publication 1757-UM007D-EN-P - December 2008 25 Configure the 1757-ABRIO Module Chapter 2 As illustrated in the 1/2-slot addressing table below, the controller addresses 1/2 of an I/O module slot as one I/O group. For example, for a chassis at rack 1, starting I/O group 0, a block transfer module in the first slot would be at address rack 1, I/O group 0, slot 0. A module in the next slot would be at rack 1, I/O group 2, slot 0. Configuring Block Transfer Modules When you add a block transfer module, the configuration dialog box for that module opens. The contents of the dialog box are specific to each module type. See Supported 1771 Modules on page 83 or the online help for information on configuring individual modules. To edit the configuration for a module, double-click the module in the network tree, or right-click the module and select Configure. 1/2-Slot Addressing Slot in chassis 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Rack 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 I/O Group 0 2 4 6 0 2 4 6 0 2 4 6 0 2 4 6 Slot 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TIP You cannot change the location of a module in the configuration once you have created it. You must delete the module and create a new one at the new location.
  • 28. 26 Publication 1757-UM007D-EN-P - December 2008 Chapter 2 Configure the 1757-ABRIO Module Scaling Part of the configuration procedure for analog modules is entering scaling values. The 1757-ABRIO module performs scaling between raw I/O data and floating point user values. You can send floating point output values to the 1757-ABRIO module which it converts to raw output values using the scaling values you supplied in the configuration. Similarly, the 1757-ABRIO module converts raw input data to floating point values, using the scaling you enter. The 1757-ABRIO module supports scaling values from -3.4e38 to 3.4e38. Scaling is done on a per-channel basis. Input Scaling For analog input modules, you must supply the floating point values to which you want the minimum and maximum raw data scaled. Minimum corresponds to the lowest raw value. Maximum corresponds to the maximum raw value. EXAMPLE If a raw input range is 1 5 V dc and you set the minimum scaling value to 12.3 and the maximum scaling value to 77.4, a raw input voltage of 1 produces a scaled input value of 12.3. A raw input voltage of 5 V dc produces a scaled input value of 77.4 A raw input value outside the range of 1 5 V dc produces an input of NaN (not a number). Modules also have underrange and overrange bits to indicate data overflows.
  • 29. Publication 1757-UM007D-EN-P - December 2008 27 Configure the 1757-ABRIO Module Chapter 2 Output Scaling For output modules, you supply the floating point values you want to correspond to the minimum and maximum raw output values. ATTENTION The minimum scale value may not be larger than the maximum scale value EXAMPLE If a channel has a range of 1 5 V dc and you set the minimum scaling value to 12.3 and the maximum scaling value to 77.4, when you set the output value to 12.3, the module produces a raw output value of 1 V dc. When you set the output value to 77.4, the module produces a raw output of 5 V dc. If you set the value outside the minimum and maximum scaling values, the raw output is clamped at the minimum or maximum.
  • 30. 28 Publication 1757-UM007D-EN-P - December 2008 Chapter 2 Configure the 1757-ABRIO Module Tags Defined The ProcessLogix or ControlLogix controller accesses data for the 1757-ABRIO module using unscheduled messages that read or write tags. For more information on how the controllers access this data, see Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module on page 51 and Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module on page 57. Before you program the controller to read or write to the 1757-ABRIO module, you must define the tags in AbRioCfg software. The 1757-ABRIO module supports the following five types of tags. Numeric Read (1) and Numeric Write (2) tags – Numeric read and numeric write tags are arrays of 64 scaled floating point values. – You can map data from block transfer modules to these tags.
  • 31. Publication 1757-UM007D-EN-P - December 2008 29 Configure the 1757-ABRIO Module Chapter 2 Flag Read (3) and Flag Write (4) tags – Flag read and write tags are arrays of 512 bits. – Block transfer modules also have status bits that can be mapped to flag read tags. – Dragging an entire I/O Grp to a Flag Read or Flag Write tag will expose all discrete read or write values for that rack as well as the Rack Global Status tag. Text Read (5) tags – Text read tags are arrays of 64 bytes. – They are used only with the 1770-HT1 HART module. From the ProcessLogix or ControlLogix perspective, the HART interface is read only. You can read text and tags from the HART, but you can’t write data to the HART.
  • 32. 30 Publication 1757-UM007D-EN-P - December 2008 Chapter 2 Configure the 1757-ABRIO Module Create a Tag If you are planning to use automatic digital tags via a scheduled connection to the 1757-ABRIO module from a ControlLogix controller, do not create tags. Refer to Scheduled Digital I/O Connections in RSLogix 5000 Programs on page 60. For all other tag types (analog, text) and unscheduled connections, tags must be manually created. To create a tag, complete the following steps. 1. Select the appropriate tab for the type of tag you want to create. 2. Right-click the root of the tree in the tag area and select Add Tag. The Add a Tag dialog box opens. 3. Type a tag name. Tag names can be from 1 to 32 characters in length and must be unique. 4. Type a message timeout time. This is the time during which the host controller must update the tag. The range of values is from 100 to 15000 ms. The default is 5000 ms. If the message timeout is exceeded, the tag times out and the 1757-ABRIO module takes the appropriate action. 5. Click OK to accept the tag. You can create a maximum of 64 tags, of any combination of types.
  • 33. Publication 1757-UM007D-EN-P - December 2008 31 Configure the 1757-ABRIO Module Chapter 2 Mapping Data to Tags in AbRioCfg Software If you are using a ControlLogix controller, no actions are necessary to read or write digital data with scheduled connections. Refer to Scheduled Digital I/O Connections in RSLogix 5000 Programs on page 60 for more information. If you are using a ProcessLogix controller, you need to create flag read and flag write tags in AbRioCfg software to have access to this data. Block Transfers When mapping block transfer modules, drag the analog module from the network tree to the location in the tag where you want the data to be located. Block transfer read data can be mapped to numeric read tags. Block transfer write data can be mapped to numeric write tags. You cannot map individual registers; all the data for a rack or I/O module is mapped to the tag. You can map data from many I/O modules into the same tag. Mappings must be unique. You cannot map a block transfer module to more than one tag of the same type or to multiple locations within the same tag. In addition, block transfer modules have status information that can be mapped to flag read tags. Refer to Supported 1771 Modules on page 83 for detailed information on status information. TIP Rack Digital Data If you would like to use scheduled ControlNet connections to the 1757-ABRIO module via a ControlLogix controller, do not map any racks to digital tags. This is done for you when the scheduled connection is established. Refer to Scheduled Digital I/O Connections in RSLogix 5000 Programs on page 60 for more information.
  • 34. 32 Publication 1757-UM007D-EN-P - December 2008 Chapter 2 Configure the 1757-ABRIO Module I/O To map I/O data to a tag, complete the following steps. 1. Expand the tag to show the tag elements. 2. Scroll to display the destination in the tag where you want to add the data. 3. Drag the rack or block transfer module to the desired location in the tag. Deleting Mapped Data To delete mapped data from a tag, complete the following steps. 1. Select any element of the data. 2. Click Delete. You cannot delete individual elements of the data for an I/O module. When you delete an element you delete all the data for the particular module. Data is not affected for the other modules mapped to the same tag. Tips for Configuring Modules Use the largest range of raw values possible for the 1757-ABRIO module and optimum data resolution. The scaling should be done to engineering units in the module. The following operations are features of firmware version 2.1. To use these features, you need the following: Firmware version 2.1 or above for the 1757-ABRIO module AbRioCfg software version 2.0 or above AbRioCfg software version 2.0 or above can open or upload configurations made with previous versions of AbRioCfg software.
  • 35. Publication 1757-UM007D-EN-P - December 2008 33 Configure the 1757-ABRIO Module Chapter 2 Add Racks Offline To add a rack, complete the following steps. 1. Right-click Hardware Config and select Add A Rack. 2. Enter the Rack Number (1 to 37 octal), Starting I/O Group (0,2,4,6) and Ending I/O Group (1,3,5,7) and click OK.
  • 36. 34 Publication 1757-UM007D-EN-P - December 2008 Chapter 2 Configure the 1757-ABRIO Module Delete Racks Offline To delete racks offline, complete the following steps. 1. Right-click the partial rack and select Delete Rack. A warning dialog box opens. 2. Click OK. When you delete a rack, all I/O modules on the rack and flag mappings for the rack are deleted. If this partial rack is the only one in the rack number, the rack number will be deleted from the tree.
  • 37. Publication 1757-UM007D-EN-P - December 2008 35 Configure the 1757-ABRIO Module Chapter 2 Change the Baud Rate Offline To change the baud rate offline, complete the following steps. 1. Select Actions>Change Baud Rate. The Select Baud Rate dialog box opens. 2. Select the desired baud rate and click OK. A warning window opens 3. To select the path to the 1757-ABRIO module from an RSWho window, click Yes. To make this change in the offline file only, click No. Download the Configuration To download the configuration to the 1757-ABRIO module from AbRioCfg software, select Actions>Download config or click the Download Configuration to Module button on the toolbar. WARNING Downloading a configuration disrupts communication between the 1757-ABRIO module and the RIO network. If the module is in active or forced active mode, the configuration program asks if you want to remove it from active mode. Scaling data for modules that have not been mapped to tags is not downloaded with the configuration.
  • 38. 36 Publication 1757-UM007D-EN-P - December 2008 Chapter 2 Configure the 1757-ABRIO Module Upload the Configuration To upload a configuration from a 1757-ABRIO module, select Actions>Upload config or click the Upload Config From Module button on the toolbar.
  • 39. 37Publication 1757-UM007D-EN-P - December 2008 37 Chapter 3 Creating Generic Modules in AbRioCfg Software Introduction This chapter describes using a generic module type which supports any block transfer I/O module that uses 16-bit integer data. To use these features, you need the following: Firmware version 2.1 or above of the firmware for the 1757-ABRIO module AbRioCfg software version 2.1 or above AbRioCfg software version 2.1 or above can open or upload configurations made with previous versions of AbRioCfg software. If you are using a 1771 module refer to Supported 1771 Modules on page 83. If you need to access HART data refer to Accessing HART Data on page 115. Generic Module Overview The generic module type makes it possible to do the following: Configure and communicate with any block transfer I/O module that uses 16-bit integer data. You create the configuration file as a comma-separated variable (CSV) file, using a spreadsheet or text editor, and import it using AbRioCfg software. Configure a block transfer module that is already supported by AbRioCfg software in ways that the standard configuration does not allow, for example, using fewer channels than in the standard module configuration, or adding features not supported by the standard configuration. Have up to 100 different generic module types in an 1757-ABRIO configuration file, and an unlimited number of modules made from those 100 types.
  • 40. 38 Publication 1757-UM007D-EN-P - December 2008 Chapter 3 Creating Generic Modules in AbRioCfg Software Generic Module Configuration File The Generic Module configuration file consists of these sections. – the configuration block transfer write (BTW) – the data block transfer read – the data block transfer write Most configuration files have a configuration block transfer write. Some may have both data block transfer read and data block transfer write sections; others will have just one or the other. The maximum size for each section is 64 words of data. You can add comments to the file by preceding them with a semicolon. Comments can be added to the end of an existing line or can occupy separate lines. The configuration file can be created as a text file or as a spreadsheet using a program like Excel and saved as a CSV file. To use a text file, separate the data fields with commas. To use a spreadsheet, put the data values in separate columns. Configuration Block Transfer Write The configuration block transfer write section (Config BTW) contains the data that is sent to the module to set how it operates. The configuration block transfer write is sent: at powerup when communication is restored after being lost when the remote I/O network switches from program to run The first line of the configuration block transfer write is the keyword “configbtw”, followed by the block transfer length, in words. This is followed by data definitions that consist of an offset and a value. IMPORTANT The length of a CSV filename must not exceed 31 characters. TIP Sample configuration files are available for your use. The files are located in the GenProfile directory on the supplied 1757-ABRIO CD. EXAMPLE configbtw, 13
  • 41. Publication 1757-UM007D-EN-P - December 2008 39 Creating Generic Modules in AbRioCfg Software Chapter 3 The offset is the offset into the block transfer and ranges from 0 to the block transfer length - 1. For example, if the block transfer is 10 words long, the allowed offsets range from 0 to 9. The value can be in one of the following formats: Binary values start with a leading “0b”. Hexadecimal values start with a leading “0x”. It's usually easier and less prone to error to enter the values in binary or hexadecimal. Format Range Binary 0b0000000000000000 to 0b1111111111111111 Hexadecimal 0x0000 to 0xFFFF Unsigned integer 0 to 65535 Signed integer -32768 to 32767 TIP If a module does not require a configuration block transfer write, you can omit the Config BTW section of the configuration file. For example, an SLC analog module does not require a Config BTW section in the file. EXAMPLE 0, 0b1011001100100001 7, 0xB321 11, 45857 Only non-zero values need be entered; all other values in the configuration block transfer will default to 0.
  • 42. 40 Publication 1757-UM007D-EN-P - December 2008 Chapter 3 Creating Generic Modules in AbRioCfg Software Example: 1771-IFE Module The following configuration block transfer write file configures a 1771-IFE for the following: differential operation (8 input channels) each channel set for 1-5 VDC or 4-20 mA two's complement binary data format each channel's raw data scaled between 0 and 4095 Refer to the 1771-IFE module documentation for configuration details. configbtw, 21 ; length 21 0, 0 1, 0 2, 0x0500 ; differential inputs, binary 3, 0 4, 0 5, 0 6, 0x4095 ; channel 1 scaling 7, 0 8, 0x4095 ; channel 2 scaling 9, 0 10, 0x4095 ; channel 3 scaling 11, 0 12, 0x4095 ; channel 4 scaling 13, 0 14, 0x4095 ; channel 5 scaling 15, 0 16, 0x4095 ; channel 6 scaling 17, 0 18, 0x4095 ; channel 7 scaling 19, 0 20, 0x4095 ; channel 8 scaling
  • 43. Publication 1757-UM007D-EN-P - December 2008 41 Creating Generic Modules in AbRioCfg Software Chapter 3 Example: 1771-OFE module The following configuration block transfer write file configures a 1771-OFE for: binary data format raw data from 0 to 0x0fff (0 to 4095 decimal) on each channel 0 values have been omitted. Refer to the 1771-OFE module documentation for the details. Data Block Transfer Read The data block transfer read defines the cyclic block transfer read that is used to read data from an input module, and is sometimes used to read status data from an output module. The data block transfer read consists of a numeric section and a flag section. The beginning of the data block transfer read section is marked by the keyword “databtr”, followed by the block transfer read length. Numeric Data The numeric section of the data block transfer read defines the I/O data - its location, format, and scaling. The beginning of the numeric section is marked by the keyword “numeric”, followed by the number of values to be defined, and the data format. EXAMPLE databtr, 15 configbtw, 13 ; length 13 4, 0x8000 ; binary data format 6, 0x0fff ; maximum raw value channel 1 8, 0x0fff ; maximum raw value channel 2 10, 0x0fff ; maximum raw value channel 3 12, 0x0fff ; maximum raw value channel 4
  • 44. 42 Publication 1757-UM007D-EN-P - December 2008 Chapter 3 Creating Generic Modules in AbRioCfg Software AbRioCfg software checks the number of values to be defined against the actual number of definitions and indicates an error if they do not match. The format can be one of: All items must have the same format. This is followed by definitions for the I/O data values, each on a row of the spreadsheet (or line of a text file). Each definition consists of the following fields: Some modules have data underrange and overrange bits to indicate out-of-range inputs. If the underrange or overrange bit is set, the AbRioCfg software sets the I/O value to NaN. Format Range of values BCD 0 to 9999 Unsigned 0 to 65535 Integer -32768 to 32767 EXAMPLE numeric, 4, BCD numeric, 8, integer Quantity Description BTR offset Offset into BTR data The BTR offset is the offset into the BTR data for the I/O data value Underrange offset(1) (1) If the offset is not used, the field must be left blank (not 0). Word offset of underrange bit, 0–15 Underrange bit Bit number, 0–15 Overrange offset(1) Word offset of overrange bit, 0–15 Overrange bit Bit number, 0–15 Polarity offset(1) Word offset of polarity bit, 0–15 Polarity bit Bit number, 0–15 Minimum raw value Minimum raw input Maximum raw value Maximum raw input Minimum scale value Minimum floating point scaled value that corresponds to minimum raw value Maximum scale value Maximum floating point scaled value that corresponds to maximum raw value
  • 45. Publication 1757-UM007D-EN-P - December 2008 43 Creating Generic Modules in AbRioCfg Software Chapter 3 If the module does not have overrange or underrange bits, leave those fields blank in the configuration file. Some modules have a separate polarity bit to indicate the sign of an input. If the polarity bit is set, the 1757-ABRIO module assigns the corresponding data a negative value. the 1757-ABRIO module uses the polarity offset and bit only for the BCD data type. It ignores them for the other data types. If the data type is BCD, enter the raw minimum and maximum values in decimal, not hexadecimal. For example is the range is 0 to 9999, enter the value as 9999, not 0x9999. Flag Data In some cases the block transfer read contains data that we want to map to flag read tags, for example, a module error bit. If a module has flag data defined, you can then map it to flag read data in AbRioCfg software. The flag data section of the Data Block Transfer read defines the location of this discrete data. The beginning of the flag section is marked by a line containing the keyword “flag”, followed by the total length of the flags data, in bits. The length must be a multiple of 8. This is followed by a number of lines that define where the flag data is found. Each line consists of an offset and a length. The maximum number of flag data definition lines is 4. EXAMPLE A 1771-IFE module has channel 1 data at offset 4, the underrange bit is in offset 1, bit 0, the overrange bit is in offset 2, bit 0, and the polarity bit is in offset 3, bit 0. The raw data ranges from 0 to 4095. We want to scale the raw data to floating point values from 0 to 1000. In a text file: 4,1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000 In a spreadsheet: EXAMPLE flag, 32 numeric 4 BCD 4 1 0 2 0 3 0 0 4095 0 1000
  • 46. 44 Publication 1757-UM007D-EN-P - December 2008 Chapter 3 Creating Generic Modules in AbRioCfg Software The offset is an offset into the block transfer. It can range from 0 to the length of the block transfer - 1. If the offset is followed by an “H”, it refers to the high byte of the block transfer word. The length can range from 8 to 504 and must be a multiple of 8. The sum of the lengths in the data definitions must match the length in the “flag” line. Example: 1771-IFE Module The following definitions assign the underrange and overrange bits from a 1771-IFE module to flag data. Special Flag Read Data In addition to any flag read data you define in the configuration file, the Generic Module always has 8 bits of predefined flag read data. This data is found at the beginning of the flag data for the module. It consists of the following flags: EXAMPLE flag, 32 Bit Description 0 Good communication, set to 1 if the block transfer to the module is updating, 0 otherwise. 1 BTR Raw underrange bit, set if the raw input to the module is less than the defined raw minimum. The module sets the scaled input to NaN. 2 BTR raw overrange, set if the raw input to the module is greater than the defined raw maximum. The module sets the scaled input to NaN. 3 Reserved 4 Reserved 5 BTW raw underrange, set if the calculated output value is less than the defined raw minimum. The module clamps the output at the raw minimum. 6 BTW raw overrange, set if the calculated output value is greater than the defined raw maximum. The module clamps the value at the raw maximum. 7 BTW NaN, set if the floating point value written from the host is NaN. 0,8 2H,8 4,16 flag, 32 1,16 2,16
  • 47. Publication 1757-UM007D-EN-P - December 2008 45 Creating Generic Modules in AbRioCfg Software Chapter 3 Sample 1771-IFE Configuration File Data Block Transfer Write The data block transfer write defines the cyclic block transfer read that is used to write data to an output module. The data block transfer write consists of a numeric section and a flag section. The beginning of the data block transfer write section is marked by the keyword “databtw, followed by the block transfer write length. EXAMPLE databtw, 12 configbtw, 21 ; length 21 2, 0x0500 ; differential inputs, binary 5, 0 6, 0x4095 ; channel 1 scaling 7, 0 8, 0x4095 ; channel 2 scaling 9, 0 10, 0x4095 ; channel 3 scaling 11, 0 12, 0x4095 ; channel 4 scaling 13, 0 14, 0x4095 ; channel 5 scaling 15, 0 16, 0x4095 ; channel 6 scaling 17, 0 18, 0x4095 ; channel 7 scaling 19, 0 20, 0x4095 ; channel 8 scaling databtr, 12 numeric, 4, signed 4, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000 5, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000 6, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000 7, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000 8, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000 9, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000 10, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000 11, 1, 0, 2, 0, 3, 0, 0, 4095, 0, 1000 flag, 32 1, 16 2, 16
  • 48. 46 Publication 1757-UM007D-EN-P - December 2008 Chapter 3 Creating Generic Modules in AbRioCfg Software Numeric Data The numeric section of the data block transfer write defines the I/O data - its location, format, and scaling. The beginning of the numeric section is marked by the keyword “numeric”, the number of values to be defined, and the data format. AbRioCfg software checks the number of values to be defined against the actual number of definitions and indicates an error if they do not match. The format can be one of the following. All items must have the same format. This line is followed by definitions for the I/O data values, each on a row of the spreadsheet (or line of a text file). Each definition consists of the following fields: The BTW offset is the offset into the BTW data for the I/O data value. Some modules have a separate polarity bit to indicate the sign of an input. If the data being written is negative, the 1757-ABRIO module sets the polarity bit. Format Range of values BCD 0 to 9999 Unsigned 0 to 65535 Integer -32768 to 32767 EXAMPLE numeric, 4, BCD numeric, 8, integer Quantity Description BTW offset Offset into BTW data Polarity offset Word offset of polarity bit Polarity bit Bit number, 0-15 Minimum raw value Minimum raw output Maximum raw value Maximum raw output Minimum scale value Minimum floating point scaled value that corresponds to minimum raw value Maximum scale value Maximum floating point scaled value that corresponds to maximum raw value
  • 49. Publication 1757-UM007D-EN-P - December 2008 47 Creating Generic Modules in AbRioCfg Software Chapter 3 The 1757-ABRIO module uses the polarity offset and bit only for the BCD data type. It ignores them for the other data types. If the scaled valued written is NaN, the raw output gets set to the corresponding value in the configuration data. For example, if an I/O data value is at offset 7 in the data block transfer write, the value at offset 7 in the configuration block transfer write is written if the host controller writes NaN to the tag that is mapped to the I/O value. Flag Data In some cases the block transfer write contains data that we want to map to flag write tags. The flag data section of the Data Block Transfer write defines the location of this discrete data. The beginning of the flag section is marked by a line containing the keyword “flag”, followed by the total length of the flags data, in bits. The length can be from 8 to 504 and must be a multiple of 8. This is followed by a number of lines that define where the flag data is found. Each line consists of an offset and a length. The maximum number of flag definition lines is 4. The offset is an offset into the block transfer. It can range from 0 to the length of the block transfer - 1. If the offset is followed by an “H”, it refers to the high byte of the block transfer word. The length can range from 8 to 504 and must be a multiple of 8. TIP If the data type is BCD, enter the raw minimum and maximum values in decimal, not hexadecimal. For example is the range is 0 to 9999, enter the value as 9999, not 0x9999. EXAMPLE A 1771-OFE module has channel 1 data at offset 0. The polarity bit is offset 4 bit 0. We want to write floating point values from 0 to 1000 and have them scaled to the raw values 0 to 4095. In a text file: 0, 4, 0, 0, 4095, 0, 1000 In a spreadsheet: EXAMPLE flag, 32 0 4 0 0 4095 0 1000
  • 50. 48 Publication 1757-UM007D-EN-P - December 2008 Chapter 3 Creating Generic Modules in AbRioCfg Software The sum of the lengths in the data definitions must match the length in the “flag” line. Example 1771-OFE Configuration File Creating a Generic Module in AbRioCfg software To add a generic module in AbRioCfg software, complete the following steps. 1. Right-click the rack to which the module will be added and select Add Module. EXAMPLE flag, 32 0,8 2H,8 4,16 configbtw, 13 ; length 13 4, 0x8000 ; binary data format 6, 0x0fff ; maximum raw value channel 1 8, 0x0fff ; maximum raw value channel 2 10, 0x0fff ; maximum raw value channel 3 12, 0x0fff ; maximum raw value channel 4 databtw, 12 numeric, 4 0, 4, 0, 0, 4095, 0, 1000 1, 4, 1, 0, 4095, 0, 1000 2, 4, 2, 0, 4095, 0, 1000 3, 4, 3, 0, 4095, 0, 1000
  • 51. Publication 1757-UM007D-EN-P - December 2008 49 Creating Generic Modules in AbRioCfg Software Chapter 3 2. Select a Module Type of Generic Module, the location for the module and click OK. 3. Browse to or type the CSV file and path and click Import. AbRioCfg software imports the configuration file and displays the contents, or gives an error message if it finds problems with the file. 4. Assign values for the BTR and BTW Update Times. 5. Click OK to accept the module. You can now map the data to tags by dragging the Generic module to the desired numeric read, numeric write, flag read or flag write tag. To change the configuration, re-import the configuration. If the generic module was mapped to tags, the mappings will be deleted and must be reassigned.
  • 52. 50 Publication 1757-UM007D-EN-P - December 2008 Chapter 3 Creating Generic Modules in AbRioCfg Software You can export the generic module configuration by clicking the Export button in the Generic Module dialog box. Since comments in the original file are not imported (and therefore are not exported), it is usually better to modify the original configuration file and save it with a new name. Export may be useful if you upload a configuration that contains a generic module from a 1757-ABRIO module and you do not have the original file.
  • 53. 51Publication 1757-UM007D-EN-P - December 2008 51 Chapter 4 Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module Introduction This chapter describes: the operating modes of the 1757-ABRIO module. how to access data on the module from a ProcessLogix controller. Modes of Operation There are four modes of operation for the module. CONFIG INACTIVE (Program) ACTIVE (Run) FORCED ACTIVE The mode of the 1757-ABRIO module determines the RIO network mode. Modes related to RIO network operations: INACTIVE (Program) mode, digital inputs continue to update but digital outputs and block transfers do not. ACTIVE (Run) mode, digital inputs and outputs update, and block transfers update. CONFIG Mode The module is in CONFIG mode while AbRioCfg software downloads a configuration. CONFIG mode is largely invisible to the user unless the configuration being downloaded is large. After downloading, the software returns the module to INACTIVE mode.
  • 54. 52 Publication 1757-UM007D-EN-P - December 2008 Chapter 4 Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module INACTIVE Mode The module is in INACTIVE mode when it is not receiving messages from either a host controller or via OPC/DDE. The module is also in INACTIVE mode when it has not been put in FORCED ACTIVE mode by AbRioCfg software. When the module is in INACTIVE mode, the RIO network is placed in program mode with input updates but no output updates. The 1757-ABRIO module must be in the INACTIVE mode to accept a download. ACTIVE Mode (Run) The module is in ACTIVE mode when it receives a message from either a host controller or from an OPC or DDE server. When the module is in ACTIVE mode, the RIO network is in run mode. The module is in ACTIVE mode as long as any tag is being updated. Each tag has an associated time-out. The tag is considered to be updating until the time-out expires. If all tags have timed out, the 1757-ABRIO module automatically switches to INACTIVE mode. If you try to download a configuration when the module is in ACTIVE mode, AbRioCfg software asks if you want to take the module out of ACTIVE mode. If you click OK, AbRioCfg software changes the mode, downloads the configuration, then puts the module in INACTIVE mode. FORCED ACTIVE Mode The module is in FORCED ACTIVE mode when you set ACTIVE mode from the AbRioCfg program. FORCED ACTIVE mode lets you send and receive data without having to create messages in the module. It is intended primarily for setting up and testing RIO networks. If you try to download a configuration when the module is in FORCED ACTIVE mode, AbRioCfg software asks if you want to take the module out of ACTIVE mode. If you click OK, AbRioCfg software changes the mode, downloads the configuration, then puts the module in INACTIVE mode. IMPORTANT When the module is in FORCED ACTIVE mode, the RIO network is in run mode.
  • 55. Publication 1757-UM007D-EN-P - December 2008 53 Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module Chapter 4 Configure the 1757-PLX52 Controller To access tag data on the 1757-ABRIO module from a ProcessLogix controller, use the REQNUMARRAY, REQFLAGARRAY and REQTEXTARRAY Exchange Blocks with CIPREAD and CIPWRITE commands to read and write tags. Use Control Builder software to complete the following steps. 1. Select the Exchange Block from the Library in Control Builder. 2. Add the desired Exchange Block to the CM (Control Module) by dragging it into the CM window. – REQFLAGARRAY for flag data – REQNUMARRAY for numeric data – REQTEXTARRAY for text data 3. Expand the Exchange Block by double-clicking on it. 4. Select the Main tab. 5. Give the block a name and set the execution order. 6. Select either CIPREAD or CIPWRITE for the message command.
  • 56. 54 Publication 1757-UM007D-EN-P - December 2008 Chapter 4 Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module 7. Set the number of values to be read or written. a. Flag arrays, 512 max b. Numeric arrays, 64 max c. Text arrays, 64 max Array Examples 8. Set the data type to be read or written. a. Numeric arrays, set Data Type in Target Device to FLOAT32. b. Text arrays, set the Number of String Values to 1 and the Char Length of String Values to 64. 9. Select the Communications tab. 10. Set the Path from the ProcessLogix controller to the 1757-ABRIO module. See the tip on page 72 or Control Builder Help for information on entering the path. Flag Arrays Numeric Arrays Text Arrays
  • 57. Publication 1757-UM007D-EN-P - December 2008 55 Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module Chapter 4 11. Set the File Name in the Exchange Blocks to the names of the tags you created in the 1757-ABRIO module. 12. Perform any other configuration required by your application on the other tabs. 13. Click OK to accept the block. 14. Wire the ready flag (READYFL) to the send flag (SENDFL) for each exchange block. 15. Download the CM to the ProcessLogix controller and activate it. IMPORTANT Be sure to expose the Error codes in your Exchange Blocks.
  • 58. 56 Publication 1757-UM007D-EN-P - December 2008 Chapter 4 Configuring the ProcessLogix Controller to Access Data on the 1757-ABRIO Module Live Data Examples Double-click function block
  • 59. 57Publication 1757-UM007D-EN-P - December 2008 57 Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Introduction This chapter describes: the operating modes of the 1757-ABRIO module. how to access data on the module from a ControlLogix controller. Modes of Operation There are four modes of operation for the module. CONFIG INACTIVE (Program) ACTIVE (Run) FORCED ACTIVE The mode of the 1757-ABRIO module determines the RIO network mode. Modes related to RIO network operations: INACTIVE (Program) mode, digital inputs continue to update but digital outputs and block transfers do not. ACTIVE (Run) mode, digital inputs and outputs update, and block transfers update. CONFIG Mode The module is in CONFIG mode while AbRioCfg software downloads a configuration. CONFIG mode is largely invisible to the user unless the configuration being downloaded is large. After downloading, the software returns the module to INACTIVE mode.
  • 60. 58 Publication 1757-UM007D-EN-P - December 2008 Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module INACTIVE Mode The module is in INACTIVE mode when it is not receiving messages from either a host controller or via OPC/DDE. The module is also in INACTIVE mode when it has not been put in FORCED ACTIVE mode by AbRioCfg software. When the module is in INACTIVE mode, the RIO network is placed in program mode with input updates but no output updates. The 1757-ABRIO module must be in the INACTIVE mode to accept a download. When scheduled connections are used, the 1757-ABRIO module’s mode will always follow the ControlLogix controller’s mode regardless if it is receiving messages. For example, when the controller is in PROGRAM mode, the module is in INACTIVE mode. ACTIVE Mode (Run) The module is in ACTIVE mode when it receives a message from either a host controller or from an OPC or DDE server. When the module is in ACTIVE mode, the RIO network is in run mode. The module is in ACTIVE mode as long as any tag is being updated. Each tag has an associated time-out. The tag is considered to be updating until the time-out expires. If all tags have timed out, the 1757-ABRIO module automatically switches to INACTIVE mode. If you try to download a configuration when the module is in ACTIVE mode, AbRioCfg software asks if you want to take the module out of ACTIVE mode. If you click OK, AbRioCfg software changes the mode, downloads the configuration, then puts the module in INACTIVE mode. When scheduled connections are used, the 1757-ABRIO module’s mode will always follow the ControlLogix controller’s mode regardless if it is receiving messages. For example, when the controller is in RUN mode, the module is in ACTIVE mode.
  • 61. Publication 1757-UM007D-EN-P - December 2008 59 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5 FORCED ACTIVE Mode The module is in FORCED ACTIVE mode when you set ACTIVE mode from the AbRioCfg program. FORCED ACTIVE mode lets you send and receive data without having to create messages in the module. It is intended primarily for setting up and testing RIO networks. If you try to download a configuration when the module is in FORCED ACTIVE mode, AbRioCfg software asks if you want to take the module out of ACTIVE mode. If you click OK, AbRioCfg software changes the mode, downloads the configuration, then puts the module in INACTIVE mode. IMPORTANT When the module is in FORCED ACTIVE mode, the RIO network is in run mode.
  • 62. 60 Publication 1757-UM007D-EN-P - December 2008 Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Scheduled Digital I/O Connections in RSLogix 5000 Programs 1757-ABRIO module firmware versions 1.2 and above support scheduled connections for exchanging digital input and output data between the 1757-ABRIO module and the host ControlLogix controller. This results in much faster updates for the digital data than is possible using unscheduled messages. This section describes how to configure the module and the format of the scheduled data. When you add a 1757-ABRIO module to the I/O Configuration of an RSLogix 5000 program using the generic 1757-MODULE profile, a data connection is created for the digital remote I/O data. See Tag Descriptions for Scheduled Data in RSLogix 5000 Software on page 149 for more information about the status tag when using ControlLogix. The status tag gives global status for digital data and individual rack status. Scheduled Connection Types There are two types of scheduled connection. Exclusive Owner, read/write Input Only, read only Setup an Exclusive-owner Connection Configure a generic module profile in RSLogix 5000 software to represent the 1757-ABRIO module. This dictates the format and amount of scheduled data, and how often the scheduled data is transferred. The ControlLogix controller is the owner of the connection and controls the digital outputs. The connection is referred to as an exclusive-owner connection. TIP In order to access any numeric read, numeric write, or text read data from the ControlLogix controller you must also complete Unscheduled I/O Connections in ControlLogix on page 67. IMPORTANT In order for the scheduled connection to control the outputs of a chassis, the chassis must not be mapped to any flag write tag in the AbRioCfg software configuration that has been downloaded to the 1757-ABRIO module.
  • 63. Publication 1757-UM007D-EN-P - December 2008 61 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5 Remote I/O Operating Modes If there is an exclusive-owner connection to the 1757-ABRIO module, the module’s remote I/O mode (run or program) follows the owner ControlLogix controller’s Run or Program mode. If the owner ControlLogix controller is in Program mode, the 1757-ABRIO module is in program mode (even if the module is receiving messages). If the ControlLogix controller is in Remote Test mode, the remote I/O mode for the 1757-ABRIO module is program. The remote I/O mode is not affected by the operating mode of a ControlLogix controller that has an input-only connection to the 1757-ABRIO module. In the absence of an exclusive-owner connection, the 1757-ABRIO module’s remote I/O mode is determined by whether it is receiving messages, as before. Add a Module as an Exclusive-owner Connection To configure the 1757-ABRIO module in RSLogix 5000 software, the ControlLogix controller must be offline. 1. Create a new project for your type of controller. 2. Type a name for the controller, and select the slot it occupies in the ControlLogix chassis. 3. Click OK. 4. Right-click on I/O configuration and select New Module. 5. Under Other, select the 1756-MODULE Generic 1756 Module and click OK. The Module Properties dialog box opens.
  • 64. 62 Publication 1757-UM007D-EN-P - December 2008 Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module 6. Type a Name and a Description for the module, if desired. 7. Set the Slot number for the module in the ControlLogix chassis. 8. For the Comm Format, select Data - INT - With Status. 9. Select the following values for the Connection Parameters. 10. Verify that the Open Module Properties checkbox is checked and click OK. 11. Set the module’s Requested Packet Interval (RPI). This is how often the module's scheduled data is updated in the controller. The value can range from 0.2 to 750 ms. The default time is 5 ms. 12. Click OK. 13. Save the program and download it to the ControlLogix controller. Assembly Instance Size Input 1 250 Output 2 248 Configuration 4 0 Status Input 5 10 Status Output 6 N/A
  • 65. Publication 1757-UM007D-EN-P - December 2008 63 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5 Output Priority If a digital rack is mapped to a flag write tag in the AbRioCfg software, the flag data takes precedence over the digital outputs in the scheduled connection, even if nothing is writing to the flag write tag. To control outputs on a chassis using a scheduled connection, make sure the chassis is not mapped to a flag write tag. Setup Input-only Connections The 1757-ABRIO module also supports input-only connections. In a ControlLogix system, multiple controllers can receive inputs from a module, but only one controller can control the outputs. An input-only connection does not require the presence of an exclusive owner connection. More than one ControlLogix controller can open an input-only connection to the 1757-ABRIO module and receive its inputs. Add a Module as an Input-only Connection To configure an input-only connection to the 1757-ABRIO module in RSLogix 5000 software, you must be offline. 1. Create a new project for your type of controller. 2. Type a name for the controller, and select the slot it occupies in the ControlLogix chassis. 3. Click OK. 4. Right-click on I/O configuration and select New Module. 5. Under Other, select the 1756-MODULE Generic 1756 Module and click OK.
  • 66. 64 Publication 1757-UM007D-EN-P - December 2008 Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module The Module Properties dialog box opens. 6. Type a Name and a Description for the module, if desired. 7. Set the Slot number for the module in the ControlLogix chassis. 8. For the Comm Format, select Input Data - INT - With Status. 9. Select the following values for the Connection Parameters. Assembly Instance Size Input 1 250 Output 3 N/A Configuration 4 0 Status Input 5 10 Status Output 6 N/A
  • 67. Publication 1757-UM007D-EN-P - December 2008 65 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5 10. Verify that the Open Module Properties checkbox is checked and click OK. 11. Set the module’s Requested Packet Interval. This is how often the module's scheduled data is updated in the controller. The value can range from 0.2 to 750 ms. The default is 5 ms.
  • 68. 66 Publication 1757-UM007D-EN-P - December 2008 Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module 12. Click OK. 13. Save the program and download it to the ControlLogix controller. Live Data Example Click the 1757-ABRIO module to display the new tags. See Tag Descriptions for Scheduled Data in RSLogix 5000 Software on page 149 for details.
  • 69. Publication 1757-UM007D-EN-P - December 2008 67 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5 Unscheduled I/O Connections in ControlLogix There are several tasks you need to complete before you can access data from ControlLogix. You need to create the following: Tags for messages Tags for storage areas Message commands to read RIO network data Message commands to write RIO network data Use RSLogix 5000 message instructions (MSG) to access tags on the 1757-ABRIO module. Refer to RSLogix 5000 Online Help and the Logix5000 Controllers General Instructions Reference Manual, publication 1756-RM003, for details on messages. Before you create the MSG instruction, create a tag of type MESSAGE to act as a control for the MSG instruction. You must also create a source (write) or destination (read) tag for the data written to or read from the 1757-ABRIO module. 1. Create Tags For All Messages and All Storage Areas RSLogix 5000 Example Tags in Program Mode For message type, select CIP Data Table Read or Data Table Write. On a Read, the source is a 1757-ABRIO Tag Name. The Destination, on a Read, is an RSLogix 5000 Tag Name. These are the tags you will reference in your message commands.
  • 70. 68 Publication 1757-UM007D-EN-P - December 2008 Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module 2. Create Message Commands to Read and Write All RIO Network Data RSLogix 5000 Example Message Commands in Program Mode This table shows the source (write) or destination (read) data type to use with each 1757-ABRIO tag type and the size for each type. Use the Browse button ( ) to locate the read/write tags you want to reference in your message commands. See Create a Tag on page 30 for more information. ControlLogix Data types 1757-ABRIO Tag Source/destination Type Storage Data Size Numeric read REAL 64 Numeric write REAL 64 Flag read DINT 16 Flag Write DINT 16 Text read SINT 64
  • 71. Publication 1757-UM007D-EN-P - December 2008 69 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5 Use the following steps to add the MSG instruction. 1. Add the MSG instruction to the ladder logic, along with whatever logic you want to use to cause the instruction to execute. 2. Open the Message Configuration dialog box by clicking the button in the instruction. 3. Select the Message Type. The Message type should be either CIP Data Table Read to read a tag from the 1757-ABRIO module or CIP Data Table Write to write a tag to the 1757-ABRIO module. WARNING The EN_CC bit in a ControlLogix MESSAGE tag defaults to on. If the message executes successfully even once, it gets retried periodically, even if the ladder logic has disabled the message. If you want to keep the connection open no matter what, turn on the bit. Turn off the EN_CC bit in any ControlLogix MESSAGE tag you use in a MSG instruction to access data on the 1757-ABRIO module.
  • 72. 70 Publication 1757-UM007D-EN-P - December 2008 Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module 4. Select the Source Element. If you are writing to the 1757-ABRIO module, this is the ControlLogix controller tag. If you are reading from the 1757-ABRIO module, this is the name of the tag in the 1757-ABRIO module. The 1757-ABRIO module must return different data types to ProcessLogix and ControlLogix controllers. For example, to read a tag with name FlagRead, you would create a MSG instruction with Source Element set to FlagRead[100]. 5. Type the Number of Elements. This is usually the number from the table on page 68. You can select a size smaller than the maximum if not all of the elements in the 1757-ABRIO module tag have been mapped. 6. Select the Destination Element. TIP IMPORTANT If you are reading flag read tags using a ControlLogix controller, you must append [100] to the 1757-ABRIO tag name. This tells the 1757-ABRIO module that the message is coming from a ControlLogix controller. Use this tag To All_Analog_Read Read data from input modules. The tag is listed under Numeric Read Tags. All_Flag_Read[100] Flag read for status and digital data. This is the message needed to get to analog data.
  • 73. Publication 1757-UM007D-EN-P - December 2008 71 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5 7. Select the Communication tab. 8. Type the path from the ControlLogix controller to the 1757-ABRIO module.
  • 74. 72 Publication 1757-UM007D-EN-P - December 2008 Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module When you are using scheduled connections in ControlLogix this is automatically populated with your 1757-ABRIO module’s name and address through an RSNetworx network polling. 9. Click OK to accept the MSG instruction. 10. After all message instructions are configured, save the program and download it to the ControlLogix controller. TIP The 1757-ABRIO module, ProcessLogix controller and ControlLogix controller (most likely) will not be in the same racks. Refer to RSLogix 5000 Online Help and the Logix5000 Controllers General Instructions Reference Manual, publication 1756-RM003 for details on MSG paths. TIP If you need to manually input the communications path to a module, follow this general example of how to find the path to the rack. Illustrated is the path from the ProcessLogix or the ControlLogix controller to the remote 1757-ABRIO module. Path = 1,4,2,20,1,2 1: From the backplane 4: Node, 1756-CNBR Module in slot 4 2: Path out of the CNBR, ControlNet 20: MAC ID of the target CNBR in the remote rack 2:Slot location of the 1757-ABRIO module 1: From the CNBR, via the backplane
  • 75. Publication 1757-UM007D-EN-P - December 2008 73 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Chapter 5 Live Data Example
  • 76. 74 Publication 1757-UM007D-EN-P - December 2008 Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module Ladder Rung Example
  • 77. 75Publication 1757-UM007D-EN-P - December 2008 75 Chapter 6 Accessing Data through a DDE or OPC Server Introduction This chapter describes how to access data on the module using a DDE or OPC Server. Accessing Data from a DDE or OPC Server You can access data on the 1757-ABRIO module directly using a DDE or OPC server such as RSLinx software, without the intervention of a host controller. Configuring a Topic in RSLinx Software Use the following procedure to use RSLinx software as a DDE or OPC server to access data on the 1757-ABRIO module. 1. Start RSLinx software 2. Select DDE/OPC Topic Configuration from the main menu. 3. Click New to create a new DDE or OPC topic, and give the topic a name. 4. Select the Data Source tab and browse to the 1757-ABRIO module. 5. Select the Data Collection tab. 6. Set the Processor Type to Logix5000. 7. Check Polled Messages and set the poll period to an appropriate value. 8. Un-check Unsolicited Messages. 9. Leave the remaining values at their default values and click Apply. 10. Select the Advanced Communication tab. 11. Select the Communications Driver you are using.
  • 78. 76 Publication 1757-UM007D-EN-P - December 2008 Chapter 6 Accessing Data through a DDE or OPC Server 12. Change Local or Remote Addressing defaults to Local. If you are using a bridge device to communicate with the 1757-ABRIO module, select Remote and configure the bridging. Refer to the RSLinx software documentation for detailed information on how to configure bridging. 13. Click Done to accept the DDE/OPC topic. Accessing the Data 1. Start your DDE or OPC client. 2. Connect to RSLinx software. The 1757-ABRIO module supports browsing of tags. 3. Type or browse to the tags you want to monitor in the client.
  • 79. 77Publication 1757-UM007D-EN-P - December 2008 77 Chapter 7 Monitoring the 1757-ABRIO Module Introduction This chapter provides the following information on: monitoring the operation of the 1757-ABRIO module. monitoring the data value of tags. monitoring the status of a block transfer. monitoring the scanner log. recognizing and clearing fatal errors. Monitoring the Operation The AbRioCfg software lets you monitor the operation of the module and perform maintenance operations. Tag, block transfer, and module diagnostic counters are available only from AbRioCfg software, and are not available to a ProcessLogix or ControlLogix controller. AbRioCfg software can be used to: display the current values of the digital inputs and outputs. display the current values of block transfer data, along with diagnostic information on the block transfer. display the current contents of a tag. display the module log, which consists of messages from the firmware running on the module. clear the log. copy the contents of the log to the clipboard for use by another application. This is often useful for technical support. clear fatal errors and dump the fatal error log to a file for use by technical support. Monitoring Digital I/O To monitor the current value of digital inputs or digital outputs on all racks, select Tools>Monitor Inputs or Tools>Monitor Outputs. Rows correspond to racks 1 to 37 octal; columns correspond to I/O groups 0 to 7. Data can be displayed in hexadecimal, signed decimal, or unsigned decimal using the View menu or buttons on the toolbar. The default format is hexadecimal. One hexadecimal digit corresponds to 4 digital bits. You can use the monitor program to edit data.
  • 80. 78 Publication 1757-UM007D-EN-P - December 2008 Chapter 7 Monitoring the 1757-ABRIO Module Use the Edit>Write toolbar button or the menu item to enable editing. You can now change any data and it will be written to the network (outputs) or to the data table (inputs). However if the same data is being updated by I/O modules or the controller, the value you write is overwritten the next time this I/O module is scanned. Monitoring the Data Value of Tags To monitor the current data value in a tag, complete the following steps. 1. Select the corresponding tab for the data type of the tag you want to monitor (Numeric read, etc.). 2. Select the tag you want to monitor. 3. Right-click the tag and select Monitor Tag. The tag monitor displays the raw data for the tag, as well as diagnostic data. The raw data can be displayed as floating point, hexadecimal, signed, or unsigned integer. Refer to the following table for tag diagnostic information. To clear the diagnostic counters, select Actions>ClearDiagCounters or click the Clear Diag Counters button on the toolbar. Tag Diagnostic Counters Counter Description Tag Name The tag name in AbRioCfg software Command Read or write Type Numeric, flag or text MsgNum 0 to 63, used internally by the 1757-ABRIO module Len Tag length, units are bytes for flag and text tags, floats for numeric tags Req count Number of updates this tag has been accessed (read or written) Avg Req Time Average update time for this tag, in ms. This is the average of the previous 64 updates. Min Req Time Minimum request time for this tag, in ms Max Req Time Maximum update time for this tag, in ms Time out The message time-out, in ms Status Active or Inactive
  • 81. Publication 1757-UM007D-EN-P - December 2008 79 Monitoring the 1757-ABRIO Module Chapter 7 If you attempt to monitor a tag that has not been downloaded to the 1757-ABRIO module, AbRioCfg software displays a message that indicates there is a configuration mismatch between the configuration in AbRioCfg software and the configuration in the 1757-ABRIO module. Monitoring the Status of a Block Transfer To monitor the current status of a block transfer, complete the following steps. 1. Expand the chassis where the block transfer module you want to monitor is located. 2. Select the module you want to monitor. 3. Right-click the module to highlight and select Monitor BT from the menu. The block transfer monitor displays the raw data for the block transfer and some diagnostic information. For input modules there is both a block transfer read and a block transfer write. The write consists of configuration data. The raw data can be displayed as hexadecimal, signed, or unsigned integer. The default for block transfer data is hexadecimal. Refer to the following table for diagnostic information on block transfer reads. TIP Use the same procedure to monitor digital and text data. Block Transfer Read Diagnostics Counter Description State Active/Inactive Type Module type BTR Len Block transfer read length Req Update Time Requested update time in the module configuration, in ms Avg Update Time Average update time for this block transfer read, in ms. This is the average of the previous 8 updates. Min Update Time Minimum update time for this block transfer read, in ms Max Update Time Maximum update time for this block transfer read, in ms Update Count Running count of updates for this block transfer read
  • 82. 80 Publication 1757-UM007D-EN-P - December 2008 Chapter 7 Monitoring the 1757-ABRIO Module Refer to the following table for block transfer write diagnostics. Monitoring the Scanner Log The scanner log displays messages from the 1757-ABRIO firmware, showing its normal operation and error messages. It may be useful in tracking down errors and for Technical Support. To monitor the scanner log, select Tools>Monitor Scanner Log. To clear the scanner log, select Edit>ClearLog or click the Clear Log button. To copy the contents of the log to the Windows clipboard for use in another application, select Edit>Copy or click Select All then the Copy button. Ignored Req Running count of update requests ignored by the block transfer module. Prot Errors Running count of protocol errors for this block transfer read. If this counter is incrementing, the module isn't responding correctly. Possible causes are length mismatch, invalid reply. Request Count Count of the number of times on successive scans this block transfer was requested. If this is consistently a high number, increase the requested update time - the module cannot respond quickly enough at the current requested time. The counter applies to both the BTR and BTW for this module. Block Transfer Write Diagnostic Data Counter Description CFG len Length of the configuration data for this module. BTW data len data length Req Update Time Requested update time in module configuration, in ms. Avg Update Time Average update time for this block transfer write, in ms. This is the average of the previous 8 updates. Min Update Time Minimum update time for this block transfer write, in ms. Max Update Time Maximum update time for this block transfer write, in ms. Update Count Running count of updates for this block transfer write. Ignored Req Running count of update requests ignored by the destination module for this block transfer write. Prot Errs Running count of protocol errors for this block transfer write. Block Transfer Read Diagnostics Counter Description
  • 83. Publication 1757-UM007D-EN-P - December 2008 81 Monitoring the 1757-ABRIO Module Chapter 7 Monitoring Diagnostic Counters The 1757-ABRIO module maintains diagnostic counters that indicate the state of communication on the entire RIO network, as well as counters related to each chassis. It also maintains an active rack list. To monitor the diagnostic counters, select Tools>Monitor Diagnostic Counters or click the Start the Diagnostics Counters Monitor button. Active Rack List The active rack list shows where the racks are located. If the bit is set there is a rack at that rack number and starting I/O group. It does not show the rack size. The rows represent starting I/O groups. The columns represent the rack numbers. Global Diagnostic Counters The global diagnostic counters consist of the following. Global Diagnostic Counters Counter Description Tx This counter increments each time the 1757-ABRIO module transmits a packet. RxGood This counter increments when the 1757-ABRIO module receives a good packet. RxTout This counter increments when the 1757-ABRIO module sends a packet but does not receive a reply. RxBadCRC This counter increments when the 1757-ABRIO module receives a packet with a bad CRC. Check cabling and termination on the RIO network. RxNoise This counter increments when the 1757-ABRIO module hears a carrier without receiving a packet. Check cabling and termination on the RIO network. RxAbort This counter increments when the 1757-ABRIO module receives an opening flag, then the packet ends without a closing flag. PrtclErr This counter increments when the 1757-ABRIO module receives a packet that makes no sense in terms of the protocol. UpdAvg Average update time for all configured racks. This is the average of the previous 64 updates. UpdMin Minimum update time for all configured racks. UpdMax Maximum update time for all configured racks.
  • 84. 82 Publication 1757-UM007D-EN-P - December 2008 Chapter 7 Monitoring the 1757-ABRIO Module The rack diagnostic counters consist of the following counters for each partial rack. Fatal Errors Fatal errors occur when the firmware on the module encounters an unexpected condition. The module stops scanning, turns all three status indicators red, displays the fatal error number on the 4-character display, and stores a fatal error log that indicates the cause of the fatal error. To clear the fatal error and capture the fatal error log: 1. Cycle power to the module. The 4-character display should show “FatalErrorCapture required”. 2. Start AbRioCfg software. 3. Select Tools>Fatal Error Capture. 4. Store the fatal error log to a file. This also clears the fatal error on the module. 5. Contact Rockwell Automation Technical Support and provide them with the fatal error log, which will help diagnose the cause of the problem. Clearing fatal errors also clears the configuration on the module. After you clear the fatal error, download the configuration to the module using AbRioCfg software. Rack Diagnostic Counters Counter Description Rx This counter increments when the 1757-ABRIO module receives a packet from this rack. Crc This counter increments when the 1757-ABRIO module receives a packet with a bad CRC from this rack. Tout This counter increments when the 1757-ABRIO module sends a packet to this rack and does not receive a reply within the time-out period. Prtcl This counter increments when the 1757-ABRIO module receives a packet from this rack that does not make sense in terms of the protocol.
  • 85. 83Publication 1757-UM007D-EN-P - December 2008 83 Chapter 8 Supported 1771 Modules Introduction This chapter: lists the supported 1771 modules. describes module configuration, I/O Data, and diagnostic data. Module Description The 1757-ABRIO module supports all digital 1771 modules and the following 1771 block transfer modules. For information on how to communicate with other block transfer I/O modules, see Creating Generic Modules in AbRioCfg Software on page 37. Refer to the corresponding pages in this chapter for information about configuring these modules with the 1757-ABRIO module. The AbRioCfg software handles the details of module configuration using the parameters you supply. For applicable modules, the 1757-ABRIO module scales the raw data to floating point values using optimal data resolution on the I/O module. Supported modules Module Description Page 1771-IFE Analog input module 84 1771-OFE Analog output module 89 1771-IR RTD input module 92 1771-IXE Thermocouple/millivolt module 95 1771-IL Analog input module 98 1771-NOC High resolution current output module 101 1771-NIV High resolution voltage input module 107 1771-NOV High resolution voltage output module 104 1771-NR RTD input module 110