•	 EXPLOIT THE EMPTY SPACES LEFT BY THE RACKS TO ENSURE BETTER
COOLING FOR THE SERVER.
• 	 REAR INTAKE FROM WARM CORRIDOR
•	 FRONT DELIVERY TOWARDS COLD CORRIDOR WITH HORIZONTAL FLOW;
THIS REDUCES INTERNAL PRESSURE DROPS, WITH CONSEQUENT
REDUCTION OF THE POWER ABSORBED BY THE FANS.
•	 EASY FRONT AND READ ACCESS FOR SIMPLIFIED MAINTENANCE.
•	 COOLING, HYDRAULIC AND ELECTRICAL CONNECTIONS FROM TOP OR
BOTTOM.
CHARACTERISTICS
precision air conditioners in the R Series have build
features and dimensions suitable for installation next to
data centre racks.
CONFIGURATIONS
RXA: air conditioners with delivery downwards and
direct expansion with air or water condensation.
RXU: air conditioners with air delivery
horizontal with cooled water.
CHARACTERISTICS
Precision air conditioners in the R series are designed
and built to have the same dimensions as the racks, rear
intake from the warm corridor and front delivery
towards the cold corridor.
The range has been designed and optimised for opera-
tion with ozone benign refrigerant R410A.
STRUCTURE
The set-up comprises a dark grey (RAL7024) epoxy
powder painted steel frame ensuring a long-lasting fin-
ish. Self-extinguishing thermal-acoustic insulation pan-
els finished with anti-friction film. The ventilation sub-
base is supplied separately and must be connected
electrically on site or in loco.
COILS
Coils with large surface area installed in ideal positions
to optimise air flow and heat transfer; in refrigeration-
quality copper piping with mechanically mounted alu-
minium fins, equipped as standard with 3-way motor-
driven valves (also available as 2-way version in the
selection stage).
COMPRESSORS
Brushless DC compressors with inverter adjustment,
high yield and low electrical power consumption. FANS
Centrifugal fans with backwards curved blades (plug-
fan) and EC motor directly coupled to the electronic
control to minimise electricity consumption and noise
levels.
FILTERS
Undulated filters, single-use, self-extinguishing, effi-
ciency class G4 (according to EN 779).
differential pressure switch (AS STANDARD) to signal 'fil-
ter dirty' status.
ELECTRONIC ADJUSTMENT
Thanks to control through the Modbus® Master proto-
col. all the main components in the unit are constantly
supervised, with more than 50 different variables to
ensure real-time monitoring of all operating cycles.
Thanks to specific functions dedicated to energy saving
and optimised management of all the unit's operating
cycles, with direct expansion and cooled water alike.
Thanks to the built-in RS485 Modbus® card and the
BACnet, LonWorks and SNMP interface gateway, hadst
and easy interfacing is possible with monitoring devic-
es and BMS (Building Management System).
Display of all operating parameters in 8 languages.
Precision air conditioners installation type In Rack:
A	 direct air or water condensate expansion
U	 cooled water
	 Cooling capacity 20÷35kW
Execution for“In-row”installation with front
and side air delivery.
Latest generation
control panel.
DIRECT EXPANSION.
•	 Power supply line for remote condenser
•	 Power supply line for remote condenser speed
adjuster
•	 Condenser adjustment with 0-10V signal remote
condenser with EC fans
•	 “Kit LT”for operating with low outside air
temperature with the remote condenser
•	 Oversized liquid receiver tank
•	 Non-return valves on the delivery and liquid lines
•	 Water condenser
•	 Water condenser with condensing temperature
adjustment valve
COOLED WATER
•	 Modulating 2-way valves
•	 Water temperature probes on inlet & outlet
•	 “Power valve”kit
HEATING:
•	 Electrical coils with low thermal inertia and
adjustment over differential stages
	HUMIDIFICATION:
•	 Ambient humidity probe
•	 Delivery humidity probe
•	 Immersed electrode humidifier
	 MECHANICAL AND STRUCTURAL:
•	 Condensate discharge pump
•	 Air filter on intake, efficiency M5 (EU5)
•	 Closed front panel for side delivery
•	 Closed side panels for front delivery
•	 Handling wheels
	ELECTRICAL:
•	 Alternative voltages available: 460V/3ph/60Hz -
380V/3ph/60Hz - 230V/3ph/60Hz
•	 Power supply line without neutral
•	 Automatic line selector switch (ATS) -“Basic”version
•	 Automatic line selector switch (ATS) -“Advanced”
version
	REGULATION:
•	 Ventilation adjustment at constant capacity
•	 Ventilation adjustment at constant pressure
•	 Setting and cable for local network connection
•	 User terminal for remote installation
•	 Flooding detection system
ACCESSORIES
Note: For further information refer to the selection program.
SMARTNET
The innovative SMARTNET system revolutionises the local network concept.
This system exploits the modulating capacities of the components to actively divide the work load between all units present in the local network.
Compared to the Duty Stand-by latent redundancy system (n+1 o n+n), where the backup units were on hold waiting for a problem to arise, the SMARTNET system means that
the units connected in the network are always active.
DUTY / STAND-BY SMARTNET
On 100% Stand-byOn 100%
On 100% Stand-by
On 60% On 60%On 60%
On 60% On 60%
TECHNICAL DATA
(1) Cooling: condensing temperature 45°C incoming air 24°C-45%; incoming air 24°C-45%; water 7/12°C; static external pressure: 30Pa.
The stated performance levels do not take into account the heat generated by the fans, that should be added to the thermal impact of the installation.
(2) EER: Energy Efficiency Ratio; total cooling capacity / input power from compressors + fans (air condensers excluded).
(3) Sound pressure declared data at a distance of 2m in a free field in accordance with UNI EN ISO 3744:2010
RXA: horizontal air delivery - direct expansion with air or water condensation
Sizes 231 361
Total cooling capacity (1) kW 20,4 28,2
Sensible cooling capacity (1) kW 19,7 21,7
EER (2) 3,29 2,95
Fans type Plug fan EC
Air flow rate m3/h 6000 7500
Sound Data
Sound pressure (3) dB(A) 56 56
Possible configurations
Free Cooling •
Two Sources •
RXU: horizontal air delivery - cooled water
Sizes 40
Total cooling capacity (1) kW 35,4
Sensible cooling capacity (1) kW 33,5
EER (2) 27,65
Fans type Plug fan EC
Air flow rate m3/h 9000
Sound Data
Sound pressure (3) dB(A) 61
Possible configurations
Two Sources •
Aermec S.p.A.
Via Roma, 996 - 37040 Bevilacqua (VR) - Italy
Tel. 0442633111 - Telefax 044293577
www.aermec.com
All specifications are subject to change without prior notice.
Although every effort has been made to ensure accuracy, Aermec
does not assume responsibility or liability for eventual errors or
omissions.
DIMENSIONS
Dimensional data RXA 231 361
Height A mm 2000 2000
Width B mm 600 600
Depth C mm 1180 1180
Weight kg 215 215
Dimensional data RXU 40
Height A mm 2000
Width B mm 600
Depth C mm 1180
Weight kg 190
B
C
A

Más contenido relacionado

La actualidad más candente

Lcp hybrid –_effi_cient_performance_with_heat_pipe_technology
Lcp hybrid –_effi_cient_performance_with_heat_pipe_technologyLcp hybrid –_effi_cient_performance_with_heat_pipe_technology
Lcp hybrid –_effi_cient_performance_with_heat_pipe_technologyEeu SC
 
Sb in rack-ver.1.0_en
Sb in rack-ver.1.0_enSb in rack-ver.1.0_en
Sb in rack-ver.1.0_enYury Naumov
 
Precision Cooling System
Precision Cooling SystemPrecision Cooling System
Precision Cooling SystemRamMohan Pandey
 
Danfoss control components for district heating
Danfoss control  components for district heating    Danfoss control  components for district heating
Danfoss control components for district heating DanfossDistrictEnergy
 
Kamstrup RHI Compliant Heat Meters & Thermal Energy Measurement - Multical 40...
Kamstrup RHI Compliant Heat Meters & Thermal Energy Measurement - Multical 40...Kamstrup RHI Compliant Heat Meters & Thermal Energy Measurement - Multical 40...
Kamstrup RHI Compliant Heat Meters & Thermal Energy Measurement - Multical 40...Thorne & Derrick UK
 
Control and instrumentation
Control and instrumentationControl and instrumentation
Control and instrumentationVSRAGHU
 
HVAC, Heating Ventilation Air Conditioning BMS
HVAC, Heating Ventilation Air Conditioning BMSHVAC, Heating Ventilation Air Conditioning BMS
HVAC, Heating Ventilation Air Conditioning BMSMohammad Azam Khan
 
Heat interface units brochure - Docherty Group
Heat interface units brochure  - Docherty GroupHeat interface units brochure  - Docherty Group
Heat interface units brochure - Docherty GroupDocherty Group
 
Data Centre Efficiency
Data Centre EfficiencyData Centre Efficiency
Data Centre Efficiencyemoclew
 
day 3: Control Concepts & BMS
day 3: Control Concepts & BMS day 3: Control Concepts & BMS
day 3: Control Concepts & BMS RCREEE
 
Turbocor oil-free centrifugal compressors - For air-conditioning systems
Turbocor oil-free centrifugal compressors -  For air-conditioning systemsTurbocor oil-free centrifugal compressors -  For air-conditioning systems
Turbocor oil-free centrifugal compressors - For air-conditioning systemsDanfoss India
 
Close control and turbocor chiller
Close control and turbocor chillerClose control and turbocor chiller
Close control and turbocor chillerIonela Truica
 
Sb compact dx_ver.1.0_en
Sb compact dx_ver.1.0_enSb compact dx_ver.1.0_en
Sb compact dx_ver.1.0_enYury Naumov
 
VARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOWVARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOWRIDDHESH VARIK
 

La actualidad más candente (20)

Lcp hybrid –_effi_cient_performance_with_heat_pipe_technology
Lcp hybrid –_effi_cient_performance_with_heat_pipe_technologyLcp hybrid –_effi_cient_performance_with_heat_pipe_technology
Lcp hybrid –_effi_cient_performance_with_heat_pipe_technology
 
Product manual hps
Product manual hpsProduct manual hps
Product manual hps
 
Sb in rack-ver.1.0_en
Sb in rack-ver.1.0_enSb in rack-ver.1.0_en
Sb in rack-ver.1.0_en
 
Precision Cooling System
Precision Cooling SystemPrecision Cooling System
Precision Cooling System
 
Danfoss control components for district heating
Danfoss control  components for district heating    Danfoss control  components for district heating
Danfoss control components for district heating
 
Kamstrup RHI Compliant Heat Meters & Thermal Energy Measurement - Multical 40...
Kamstrup RHI Compliant Heat Meters & Thermal Energy Measurement - Multical 40...Kamstrup RHI Compliant Heat Meters & Thermal Energy Measurement - Multical 40...
Kamstrup RHI Compliant Heat Meters & Thermal Energy Measurement - Multical 40...
 
Electrical Systems: Designing electrical rooms
Electrical Systems: Designing electrical roomsElectrical Systems: Designing electrical rooms
Electrical Systems: Designing electrical rooms
 
C&i systems
C&i systemsC&i systems
C&i systems
 
Control and instrumentation
Control and instrumentationControl and instrumentation
Control and instrumentation
 
VRF II VRV
VRF II VRVVRF II VRV
VRF II VRV
 
Ank y na60_00
Ank y na60_00Ank y na60_00
Ank y na60_00
 
Gangschottung gb
Gangschottung gbGangschottung gb
Gangschottung gb
 
HVAC, Heating Ventilation Air Conditioning BMS
HVAC, Heating Ventilation Air Conditioning BMSHVAC, Heating Ventilation Air Conditioning BMS
HVAC, Heating Ventilation Air Conditioning BMS
 
Heat interface units brochure - Docherty Group
Heat interface units brochure  - Docherty GroupHeat interface units brochure  - Docherty Group
Heat interface units brochure - Docherty Group
 
Data Centre Efficiency
Data Centre EfficiencyData Centre Efficiency
Data Centre Efficiency
 
day 3: Control Concepts & BMS
day 3: Control Concepts & BMS day 3: Control Concepts & BMS
day 3: Control Concepts & BMS
 
Turbocor oil-free centrifugal compressors - For air-conditioning systems
Turbocor oil-free centrifugal compressors -  For air-conditioning systemsTurbocor oil-free centrifugal compressors -  For air-conditioning systems
Turbocor oil-free centrifugal compressors - For air-conditioning systems
 
Close control and turbocor chiller
Close control and turbocor chillerClose control and turbocor chiller
Close control and turbocor chiller
 
Sb compact dx_ver.1.0_en
Sb compact dx_ver.1.0_enSb compact dx_ver.1.0_en
Sb compact dx_ver.1.0_en
 
VARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOWVARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOW
 

Similar a R y un50_00

Ventilation
VentilationVentilation
VentilationDantherm
 
Sb in row-gen.ii-1.0_en
Sb in row-gen.ii-1.0_enSb in row-gen.ii-1.0_en
Sb in row-gen.ii-1.0_enYury Naumov
 
Sb ls freecool-screw-inverter_1.2_en
Sb ls freecool-screw-inverter_1.2_enSb ls freecool-screw-inverter_1.2_en
Sb ls freecool-screw-inverter_1.2_enYury Naumov
 
Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)Beeteco
 
TIDA-01070-Design-Guide
TIDA-01070-Design-GuideTIDA-01070-Design-Guide
TIDA-01070-Design-GuideBrian Dempsey
 
Sb ls screw-fixed-speed_ver.3.0_en
Sb ls screw-fixed-speed_ver.3.0_enSb ls screw-fixed-speed_ver.3.0_en
Sb ls screw-fixed-speed_ver.3.0_enYury Naumov
 
Water Cooled Portable Air Conditioners
Water Cooled Portable Air ConditionersWater Cooled Portable Air Conditioners
Water Cooled Portable Air ConditionersMead O'Brien, Inc.
 
PNGC-048-400-50-Hz-CPRC20-5-002.pdf
PNGC-048-400-50-Hz-CPRC20-5-002.pdfPNGC-048-400-50-Hz-CPRC20-5-002.pdf
PNGC-048-400-50-Hz-CPRC20-5-002.pdfXmergeKuwait
 
Sb delta cw-cwu-ver.3.0_en
Sb delta cw-cwu-ver.3.0_enSb delta cw-cwu-ver.3.0_en
Sb delta cw-cwu-ver.3.0_enYury Naumov
 
Reverse Cycle Air Conditioning Brochure
Reverse Cycle Air Conditioning BrochureReverse Cycle Air Conditioning Brochure
Reverse Cycle Air Conditioning BrochureInfinitiAir
 
Portfolio overview - Blue Jay Fans - Aereco
Portfolio overview - Blue Jay Fans - AerecoPortfolio overview - Blue Jay Fans - Aereco
Portfolio overview - Blue Jay Fans - AerecoLéonore Jardinier
 
Sb ic lambda_cwu_ver.1.3_en
Sb ic lambda_cwu_ver.1.3_enSb ic lambda_cwu_ver.1.3_en
Sb ic lambda_cwu_ver.1.3_enYury Naumov
 

Similar a R y un50_00 (20)

Rtx 17-23 y-un50_00
Rtx 17-23 y-un50_00Rtx 17-23 y-un50_00
Rtx 17-23 y-un50_00
 
Rpf y un50_00
Rpf y un50_00Rpf y un50_00
Rpf y un50_00
 
Ventilation
VentilationVentilation
Ventilation
 
Unico System for Commercial HVAC Promotional Flyer
Unico System for Commercial HVAC Promotional FlyerUnico System for Commercial HVAC Promotional Flyer
Unico System for Commercial HVAC Promotional Flyer
 
Urhe cf y-un50_00
Urhe cf y-un50_00Urhe cf y-un50_00
Urhe cf y-un50_00
 
Urhe cf y-un50_00
Urhe cf y-un50_00Urhe cf y-un50_00
Urhe cf y-un50_00
 
Trs y un50_00
Trs y un50_00Trs y un50_00
Trs y un50_00
 
Sb in row-gen.ii-1.0_en
Sb in row-gen.ii-1.0_enSb in row-gen.ii-1.0_en
Sb in row-gen.ii-1.0_en
 
Sb ls freecool-screw-inverter_1.2_en
Sb ls freecool-screw-inverter_1.2_enSb ls freecool-screw-inverter_1.2_en
Sb ls freecool-screw-inverter_1.2_en
 
Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)
 
Mva mono y-un50_00
Mva mono y-un50_00Mva mono y-un50_00
Mva mono y-un50_00
 
TIDA-01070-Design-Guide
TIDA-01070-Design-GuideTIDA-01070-Design-Guide
TIDA-01070-Design-Guide
 
Sb ls screw-fixed-speed_ver.3.0_en
Sb ls screw-fixed-speed_ver.3.0_enSb ls screw-fixed-speed_ver.3.0_en
Sb ls screw-fixed-speed_ver.3.0_en
 
Water Cooled Portable Air Conditioners
Water Cooled Portable Air ConditionersWater Cooled Portable Air Conditioners
Water Cooled Portable Air Conditioners
 
Komfortecsb200250een
Komfortecsb200250eenKomfortecsb200250een
Komfortecsb200250een
 
PNGC-048-400-50-Hz-CPRC20-5-002.pdf
PNGC-048-400-50-Hz-CPRC20-5-002.pdfPNGC-048-400-50-Hz-CPRC20-5-002.pdf
PNGC-048-400-50-Hz-CPRC20-5-002.pdf
 
Sb delta cw-cwu-ver.3.0_en
Sb delta cw-cwu-ver.3.0_enSb delta cw-cwu-ver.3.0_en
Sb delta cw-cwu-ver.3.0_en
 
Reverse Cycle Air Conditioning Brochure
Reverse Cycle Air Conditioning BrochureReverse Cycle Air Conditioning Brochure
Reverse Cycle Air Conditioning Brochure
 
Portfolio overview - Blue Jay Fans - Aereco
Portfolio overview - Blue Jay Fans - AerecoPortfolio overview - Blue Jay Fans - Aereco
Portfolio overview - Blue Jay Fans - Aereco
 
Sb ic lambda_cwu_ver.1.3_en
Sb ic lambda_cwu_ver.1.3_enSb ic lambda_cwu_ver.1.3_en
Sb ic lambda_cwu_ver.1.3_en
 

Más de Oliverh Kalprit (20)

Tubommzen
TubommzenTubommzen
Tubommzen
 
Rte 1 en
Rte 1 enRte 1 en
Rte 1 en
 
Blsileodesignleaflet201802en
Blsileodesignleaflet201802enBlsileodesignleaflet201802en
Blsileodesignleaflet201802en
 
Gloryen
GloryenGloryen
Gloryen
 
Nlc 0280-1250-co y-un50_00
Nlc 0280-1250-co y-un50_00Nlc 0280-1250-co y-un50_00
Nlc 0280-1250-co y-un50_00
 
Bltower svshleaflet201804en
Bltower svshleaflet201804enBltower svshleaflet201804en
Bltower svshleaflet201804en
 
Nrp 0800-1800-hp-t y-un50_00
Nrp 0800-1800-hp-t y-un50_00Nrp 0800-1800-hp-t y-un50_00
Nrp 0800-1800-hp-t y-un50_00
 
Vento expert duo_a30_1_wen
Vento expert duo_a30_1_wenVento expert duo_a30_1_wen
Vento expert duo_a30_1_wen
 
Komforteclblbeen
KomforteclblbeenKomforteclblbeen
Komforteclblbeen
 
Ersr y un50_00
Ersr y un50_00Ersr y un50_00
Ersr y un50_00
 
Sc y un50_00
Sc y un50_00Sc y un50_00
Sc y un50_00
 
Bavaria100 catalog
Bavaria100 catalogBavaria100 catalog
Bavaria100 catalog
 
Ta y sa60_00
Ta y sa60_00Ta y sa60_00
Ta y sa60_00
 
Nlc co y-na60_02
Nlc co y-na60_02Nlc co y-na60_02
Nlc co y-na60_02
 
Ventosolarv60propro2en
Ventosolarv60propro2enVentosolarv60propro2en
Ventosolarv60propro2en
 
Blturboleaflet201804en
Blturboleaflet201804enBlturboleaflet201804en
Blturboleaflet201804en
 
Iceen
IceenIceen
Iceen
 
Smartiren
SmartirenSmartiren
Smartiren
 
Ventoergoa251proen
Ventoergoa251proenVentoergoa251proen
Ventoergoa251proen
 
Vento expert a50_1_wen
Vento expert a50_1_wenVento expert a50_1_wen
Vento expert a50_1_wen
 

Último

Comprehensive energy systems.pdf Comprehensive energy systems.pdf
Comprehensive energy systems.pdf Comprehensive energy systems.pdfComprehensive energy systems.pdf Comprehensive energy systems.pdf
Comprehensive energy systems.pdf Comprehensive energy systems.pdfalene1
 
Cost estimation approach: FP to COCOMO scenario based question
Cost estimation approach: FP to COCOMO scenario based questionCost estimation approach: FP to COCOMO scenario based question
Cost estimation approach: FP to COCOMO scenario based questionSneha Padhiar
 
Forming section troubleshooting checklist for improving wire life (1).ppt
Forming section troubleshooting checklist for improving wire life (1).pptForming section troubleshooting checklist for improving wire life (1).ppt
Forming section troubleshooting checklist for improving wire life (1).pptNoman khan
 
Input Output Management in Operating System
Input Output Management in Operating SystemInput Output Management in Operating System
Input Output Management in Operating SystemRashmi Bhat
 
US Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionUS Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionMebane Rash
 
Robotics Group 10 (Control Schemes) cse.pdf
Robotics Group 10  (Control Schemes) cse.pdfRobotics Group 10  (Control Schemes) cse.pdf
Robotics Group 10 (Control Schemes) cse.pdfsahilsajad201
 
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithmComputer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithmDeepika Walanjkar
 
Substation Automation SCADA and Gateway Solutions by BRH
Substation Automation SCADA and Gateway Solutions by BRHSubstation Automation SCADA and Gateway Solutions by BRH
Substation Automation SCADA and Gateway Solutions by BRHbirinder2
 
priority interrupt computer organization
priority interrupt computer organizationpriority interrupt computer organization
priority interrupt computer organizationchnrketan
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating SystemRashmi Bhat
 
Theory of Machine Notes / Lecture Material .pdf
Theory of Machine Notes / Lecture Material .pdfTheory of Machine Notes / Lecture Material .pdf
Theory of Machine Notes / Lecture Material .pdfShreyas Pandit
 
CS 3251 Programming in c all unit notes pdf
CS 3251 Programming in c all unit notes pdfCS 3251 Programming in c all unit notes pdf
CS 3251 Programming in c all unit notes pdfBalamuruganV28
 
TEST CASE GENERATION GENERATION BLOCK BOX APPROACH
TEST CASE GENERATION GENERATION BLOCK BOX APPROACHTEST CASE GENERATION GENERATION BLOCK BOX APPROACH
TEST CASE GENERATION GENERATION BLOCK BOX APPROACHSneha Padhiar
 
Analysis and Evaluation of Dal Lake Biomass for Conversion to Fuel/Green fert...
Analysis and Evaluation of Dal Lake Biomass for Conversion to Fuel/Green fert...Analysis and Evaluation of Dal Lake Biomass for Conversion to Fuel/Green fert...
Analysis and Evaluation of Dal Lake Biomass for Conversion to Fuel/Green fert...arifengg7
 
Javier_Fernandez_CARS_workshop_presentation.pptx
Javier_Fernandez_CARS_workshop_presentation.pptxJavier_Fernandez_CARS_workshop_presentation.pptx
Javier_Fernandez_CARS_workshop_presentation.pptxJavier Fernández Muñoz
 
SOFTWARE ESTIMATION COCOMO AND FP CALCULATION
SOFTWARE ESTIMATION COCOMO AND FP CALCULATIONSOFTWARE ESTIMATION COCOMO AND FP CALCULATION
SOFTWARE ESTIMATION COCOMO AND FP CALCULATIONSneha Padhiar
 
Artificial Intelligence in Power System overview
Artificial Intelligence in Power System overviewArtificial Intelligence in Power System overview
Artificial Intelligence in Power System overviewsandhya757531
 
Gravity concentration_MI20612MI_________
Gravity concentration_MI20612MI_________Gravity concentration_MI20612MI_________
Gravity concentration_MI20612MI_________Romil Mishra
 
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENTFUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENTSneha Padhiar
 

Último (20)

Comprehensive energy systems.pdf Comprehensive energy systems.pdf
Comprehensive energy systems.pdf Comprehensive energy systems.pdfComprehensive energy systems.pdf Comprehensive energy systems.pdf
Comprehensive energy systems.pdf Comprehensive energy systems.pdf
 
Cost estimation approach: FP to COCOMO scenario based question
Cost estimation approach: FP to COCOMO scenario based questionCost estimation approach: FP to COCOMO scenario based question
Cost estimation approach: FP to COCOMO scenario based question
 
Forming section troubleshooting checklist for improving wire life (1).ppt
Forming section troubleshooting checklist for improving wire life (1).pptForming section troubleshooting checklist for improving wire life (1).ppt
Forming section troubleshooting checklist for improving wire life (1).ppt
 
Versatile Engineering Construction Firms
Versatile Engineering Construction FirmsVersatile Engineering Construction Firms
Versatile Engineering Construction Firms
 
Input Output Management in Operating System
Input Output Management in Operating SystemInput Output Management in Operating System
Input Output Management in Operating System
 
US Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionUS Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of Action
 
Robotics Group 10 (Control Schemes) cse.pdf
Robotics Group 10  (Control Schemes) cse.pdfRobotics Group 10  (Control Schemes) cse.pdf
Robotics Group 10 (Control Schemes) cse.pdf
 
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithmComputer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithm
 
Substation Automation SCADA and Gateway Solutions by BRH
Substation Automation SCADA and Gateway Solutions by BRHSubstation Automation SCADA and Gateway Solutions by BRH
Substation Automation SCADA and Gateway Solutions by BRH
 
priority interrupt computer organization
priority interrupt computer organizationpriority interrupt computer organization
priority interrupt computer organization
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating System
 
Theory of Machine Notes / Lecture Material .pdf
Theory of Machine Notes / Lecture Material .pdfTheory of Machine Notes / Lecture Material .pdf
Theory of Machine Notes / Lecture Material .pdf
 
CS 3251 Programming in c all unit notes pdf
CS 3251 Programming in c all unit notes pdfCS 3251 Programming in c all unit notes pdf
CS 3251 Programming in c all unit notes pdf
 
TEST CASE GENERATION GENERATION BLOCK BOX APPROACH
TEST CASE GENERATION GENERATION BLOCK BOX APPROACHTEST CASE GENERATION GENERATION BLOCK BOX APPROACH
TEST CASE GENERATION GENERATION BLOCK BOX APPROACH
 
Analysis and Evaluation of Dal Lake Biomass for Conversion to Fuel/Green fert...
Analysis and Evaluation of Dal Lake Biomass for Conversion to Fuel/Green fert...Analysis and Evaluation of Dal Lake Biomass for Conversion to Fuel/Green fert...
Analysis and Evaluation of Dal Lake Biomass for Conversion to Fuel/Green fert...
 
Javier_Fernandez_CARS_workshop_presentation.pptx
Javier_Fernandez_CARS_workshop_presentation.pptxJavier_Fernandez_CARS_workshop_presentation.pptx
Javier_Fernandez_CARS_workshop_presentation.pptx
 
SOFTWARE ESTIMATION COCOMO AND FP CALCULATION
SOFTWARE ESTIMATION COCOMO AND FP CALCULATIONSOFTWARE ESTIMATION COCOMO AND FP CALCULATION
SOFTWARE ESTIMATION COCOMO AND FP CALCULATION
 
Artificial Intelligence in Power System overview
Artificial Intelligence in Power System overviewArtificial Intelligence in Power System overview
Artificial Intelligence in Power System overview
 
Gravity concentration_MI20612MI_________
Gravity concentration_MI20612MI_________Gravity concentration_MI20612MI_________
Gravity concentration_MI20612MI_________
 
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENTFUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
 

R y un50_00

  • 1. R 40/361 • EXPLOIT THE EMPTY SPACES LEFT BY THE RACKS TO ENSURE BETTER COOLING FOR THE SERVER. • REAR INTAKE FROM WARM CORRIDOR • FRONT DELIVERY TOWARDS COLD CORRIDOR WITH HORIZONTAL FLOW; THIS REDUCES INTERNAL PRESSURE DROPS, WITH CONSEQUENT REDUCTION OF THE POWER ABSORBED BY THE FANS. • EASY FRONT AND READ ACCESS FOR SIMPLIFIED MAINTENANCE. • COOLING, HYDRAULIC AND ELECTRICAL CONNECTIONS FROM TOP OR BOTTOM. CHARACTERISTICS precision air conditioners in the R Series have build features and dimensions suitable for installation next to data centre racks. CONFIGURATIONS RXA: air conditioners with delivery downwards and direct expansion with air or water condensation. RXU: air conditioners with air delivery horizontal with cooled water. CHARACTERISTICS Precision air conditioners in the R series are designed and built to have the same dimensions as the racks, rear intake from the warm corridor and front delivery towards the cold corridor. The range has been designed and optimised for opera- tion with ozone benign refrigerant R410A. STRUCTURE The set-up comprises a dark grey (RAL7024) epoxy powder painted steel frame ensuring a long-lasting fin- ish. Self-extinguishing thermal-acoustic insulation pan- els finished with anti-friction film. The ventilation sub- base is supplied separately and must be connected electrically on site or in loco. COILS Coils with large surface area installed in ideal positions to optimise air flow and heat transfer; in refrigeration- quality copper piping with mechanically mounted alu- minium fins, equipped as standard with 3-way motor- driven valves (also available as 2-way version in the selection stage). COMPRESSORS Brushless DC compressors with inverter adjustment, high yield and low electrical power consumption. FANS Centrifugal fans with backwards curved blades (plug- fan) and EC motor directly coupled to the electronic control to minimise electricity consumption and noise levels. FILTERS Undulated filters, single-use, self-extinguishing, effi- ciency class G4 (according to EN 779). differential pressure switch (AS STANDARD) to signal 'fil- ter dirty' status. ELECTRONIC ADJUSTMENT Thanks to control through the Modbus® Master proto- col. all the main components in the unit are constantly supervised, with more than 50 different variables to ensure real-time monitoring of all operating cycles. Thanks to specific functions dedicated to energy saving and optimised management of all the unit's operating cycles, with direct expansion and cooled water alike. Thanks to the built-in RS485 Modbus® card and the BACnet, LonWorks and SNMP interface gateway, hadst and easy interfacing is possible with monitoring devic- es and BMS (Building Management System). Display of all operating parameters in 8 languages. Precision air conditioners installation type In Rack: A direct air or water condensate expansion U cooled water Cooling capacity 20÷35kW Execution for“In-row”installation with front and side air delivery. Latest generation control panel.
  • 2. DIRECT EXPANSION. • Power supply line for remote condenser • Power supply line for remote condenser speed adjuster • Condenser adjustment with 0-10V signal remote condenser with EC fans • “Kit LT”for operating with low outside air temperature with the remote condenser • Oversized liquid receiver tank • Non-return valves on the delivery and liquid lines • Water condenser • Water condenser with condensing temperature adjustment valve COOLED WATER • Modulating 2-way valves • Water temperature probes on inlet & outlet • “Power valve”kit HEATING: • Electrical coils with low thermal inertia and adjustment over differential stages HUMIDIFICATION: • Ambient humidity probe • Delivery humidity probe • Immersed electrode humidifier MECHANICAL AND STRUCTURAL: • Condensate discharge pump • Air filter on intake, efficiency M5 (EU5) • Closed front panel for side delivery • Closed side panels for front delivery • Handling wheels ELECTRICAL: • Alternative voltages available: 460V/3ph/60Hz - 380V/3ph/60Hz - 230V/3ph/60Hz • Power supply line without neutral • Automatic line selector switch (ATS) -“Basic”version • Automatic line selector switch (ATS) -“Advanced” version REGULATION: • Ventilation adjustment at constant capacity • Ventilation adjustment at constant pressure • Setting and cable for local network connection • User terminal for remote installation • Flooding detection system ACCESSORIES Note: For further information refer to the selection program. SMARTNET The innovative SMARTNET system revolutionises the local network concept. This system exploits the modulating capacities of the components to actively divide the work load between all units present in the local network. Compared to the Duty Stand-by latent redundancy system (n+1 o n+n), where the backup units were on hold waiting for a problem to arise, the SMARTNET system means that the units connected in the network are always active. DUTY / STAND-BY SMARTNET On 100% Stand-byOn 100% On 100% Stand-by On 60% On 60%On 60% On 60% On 60%
  • 3. TECHNICAL DATA (1) Cooling: condensing temperature 45°C incoming air 24°C-45%; incoming air 24°C-45%; water 7/12°C; static external pressure: 30Pa. The stated performance levels do not take into account the heat generated by the fans, that should be added to the thermal impact of the installation. (2) EER: Energy Efficiency Ratio; total cooling capacity / input power from compressors + fans (air condensers excluded). (3) Sound pressure declared data at a distance of 2m in a free field in accordance with UNI EN ISO 3744:2010 RXA: horizontal air delivery - direct expansion with air or water condensation Sizes 231 361 Total cooling capacity (1) kW 20,4 28,2 Sensible cooling capacity (1) kW 19,7 21,7 EER (2) 3,29 2,95 Fans type Plug fan EC Air flow rate m3/h 6000 7500 Sound Data Sound pressure (3) dB(A) 56 56 Possible configurations Free Cooling • Two Sources • RXU: horizontal air delivery - cooled water Sizes 40 Total cooling capacity (1) kW 35,4 Sensible cooling capacity (1) kW 33,5 EER (2) 27,65 Fans type Plug fan EC Air flow rate m3/h 9000 Sound Data Sound pressure (3) dB(A) 61 Possible configurations Two Sources •
  • 4. Aermec S.p.A. Via Roma, 996 - 37040 Bevilacqua (VR) - Italy Tel. 0442633111 - Telefax 044293577 www.aermec.com All specifications are subject to change without prior notice. Although every effort has been made to ensure accuracy, Aermec does not assume responsibility or liability for eventual errors or omissions. DIMENSIONS Dimensional data RXA 231 361 Height A mm 2000 2000 Width B mm 600 600 Depth C mm 1180 1180 Weight kg 215 215 Dimensional data RXU 40 Height A mm 2000 Width B mm 600 Depth C mm 1180 Weight kg 190 B C A