Boiler Drum Level                             01/02/01                              Tech Paper #909




   Improving Boiler Room Efficiencies
             A Seminar on the ways and means of increasing boiler room efficiencies.

                  Boiler Drum Level
               Measurement and Control




                                         Presented by
                                       David C. Farthing
                        Federal Corporation
              A proud Oklahoma partner for over 80 years!
                    Providing over 80 years of boiler and boiler room experience.
                                                Rev 9/00




                                                                                                 1
Boiler Drum Level                                                              01/02/01                                                           Tech Paper #909



                                                                           Contents


A MESSAGE FROM THE SPEAKER...........................................................................................................................3

INTRODUCTION ............................................................................................................................................................3

STEAM PLANT OPTIMIZATION & AUTOMATION.............................................................................................3

LIQUID LEVEL MEASUREMENT................................................................................................................................4
   INFERENTIAL LEVEL M EASUREMENT ..................................................................................................................... 4
   VOLUMETRIC LEVEL M EASUREMENT ..................................................................................................................... 4
   DIFFERENTIAL PRESSURE LEVEL M EASUREMENT ................................................................................................ 5
   THE BOILER W ATER/STEAM DRUM........................................................................................................................ 5
BOILER DRUM LEVEL CONTROL - ON/OFF VS. MODULATING....................................................................6

THE EFFECT OF FEEDWATER TEMPERATURE ON BOILER PERFORMANCE............................................6
     Btu Required to Raise Boiler Water to Steaming Temperature at Pressure................................................6
     What Really Happens.............................................................................................................................................8
   EXAMPLE OT THE EFFECT OF FEEDWATER TEMPERATURE ON BOILER PERFORMANCE ............................ 8
BOILER LEVEL CONTROL STRATEGIES ..............................................................................................................9
   SINGLE-ELEMENT CONTROL..................................................................................................................................... 9
   TWO-ELEMENT CONTROL ....................................................................................................................................... 10
   THREE-ELEMENT DRUM LEVEL CONTROL........................................................................................................... 11
CONCLUSION...............................................................................................................................................................12
   A BOUT THE A UTHOR............................................................................................................................................... 13
   BIBLIOGRAPHY........................................................................................................................................................... 13




                                                                                                                                                                           2
Boiler Drum Level                      01/02/01                        Tech Paper #909



A Message from the speaker
Energy costs today are at there highest in recent history. Gaining whatever
efficiencies may be found in thermal processes can help to stabilize the effects of
rising energy cost.
Also today’s economic and environmental demands dictate that we get the greatest
practical efficiencies from our plants. To do this we must have a basic
understanding of what those efficiencies are and how we may implement them.
My hope for you today is, that you will leave this seminar with a clearer
understanding of some of the economically and technically feasible opportunities
you have to improve your steam plant.

Regards,
David C. Farthing
Industrial Sales Manager
Federal Corporation


Introduction
Improved efficiency can have many connotations everything from fuel savings,
improved equipment operation and useful life span, to labor and manpower savings.
This paper will focus on the effects of boiler drum level and feedwater control as a
means of energy savings by thermal/mass balancing the boiler. This paper will also
discuss the effects of steam drum pressure and feedwater temperature on the
overall efficiency of the boiler.

Steam Plant Optimization & Automation
Steam plant optimization is the overall improvement of the plant’s operation. The
most common strategies used to accomplish this task includes, and generally
focuses on, the improvement of primary equipment operating efficiency, i.e. fuel and
energy savings. In heavy commercial and industrial boiler applications these
efficiencies are normally found in the application of waste heat recovery equipment,
systems and process automation, and improved operating practices.

Boiler Drum Level Control has historically benefited from improvements in systems
and process automation techniques. As such three separate control strategies,
single element, two element and three-element control will be analyzed in this paper.




                                                                                    3
Boiler Drum Level                          01/02/01                             Tech Paper #909



Liquid Level Measurement
The measurement of liquid level enables us to locate the surface of a liquid with respect
to some referenced level. Level measurement is necessary in Boiler Drum Level
Measurement for the safe and efficient operation of the boiler.

Inferential Level Measurement
One of the most flexible and convenient means of measuring liquid level is the static
pressure or inferential method. This method is based on the fact that the static pressure
exerted by any fluid is directly proportional to the height of the liquid above the point of
measurement, irrespective of volume. Thus any instrument which is affected by
pressure can be calibrated in terms of the height of a given liquid. The liquid sightglass is
based on this method of measurement as the weight of water will find its own level in any
open or closed loop.

Inferential Measurement is heavily influenced by sudden changes in liquid density,
pressure or level disturbances and thus requires a stilling well to help dampen these
disturbences. The use of a water column on the boiler drum acts as a stilling well for the
level control devices and the sightglass.

In steam boiler applications the communication lines to the measurement instrument
must remain unobstructed. Interruption of the vapor side communication line will result in
an artificially low reading due to the effects of the drum pressure acting on the water
column to compress the reading. While interruption of the liquid communication line will
result in an artificially high reading, as condensate from the vapor line will tend to
condense in the chamber and fill it up.

Volumetric Level Measurement
Volumetric Level Measurement is found in the form of float (displacement) type devices,
which transmit the level in a vessel by simply floating on the surface of the liquid. Float
operated liquid level measurement is a direct measurement in which the float rises and
falls with the surface of the liquid level. In this method, the float, through a transmitter
arm, can actuate a pointer, recording pen or electronic/pneumatic transmitter.

One of the most important aspects of float measurement is the effect of density on the
level reading. As density falls the liquid loses its ability to support the float and the float
rides deeper in the fluid suppressing the level reading accordingly. Thus it is important to
know the density range that the float is to operate in and design accordingly. As an
example, a float designed for 60 degree ‘F’ water, with a density of 1.0, would sink and fail
to register any level in a tank filled with say gasoline having a density of 0.60.

Most single element drum level sensing devices and mechanical level switches use
volumetric level measurement.




                                                                                             4
Boiler Drum Level                         01/02/01                            Tech Paper #909


Differential Pressure Level Measurement
One of the simplest methods of measuring liquid level in a closed tank is to use a
differential pressure device having a range equal to the liquid head being measured.
Again, product density is important as the head pressure exerted on the differential
element is in direct relationship to the density of the liquid being measured.
Liquid levels in closed tanks under pressure may be measured by this method. In these
applications, the reference leg of the differential meter body must be connected to the
pressure in the tank being measured so that the differential being measured will be
independent of any pressure changes other than those due to changes in level.
In closed tank applications with condensing liquids, the reference line should be filled with
the liquid being measured during installation. As noted the density of liquids change with
temperature and the reference leg, which is at condensing temperature, will always read
heavy in relation to the level measurement leg resulting in a zero shift. Therefore the
meter body must be calibrated with a full liquid reference leg in order to correct for the
zero shift.

The Boiler Water/Steam Drum
The boiler water/steam drum, or steam drum, is an integral part of the boiler’s design.
This vessel has three specific purposes; 1] provide a volume space to hold the boiling
water in the boiler, 2] provide enough water volume to allow for good thermal mixing of
the cooler bottom drum water with the hotter surface interface water, and 3] provide
surface area and volume for the efficient release of the entrained steam bubbles from the
boiler water.
The surface area and volume of the vapor space in the water/steam drum is critical to
the efficient separation of the steam bubbles from the water. Too small an area can
result in an excessive surface tension and high velocities, which result in wasted heat
and drum water carry-over. Too large an area is simply a waste of materials and labor to
construct the vessel.
The boiler water/steam drum also provides a logical location for 1] addition of feedwater,
2] addition of chemical water treatment and 3] surface blowdown, which helps reduce the
surface tension of the water/steam interface to allow better steam release.
Because all of these task involve the removal and addition of some mass (water or
steam) the water/steam interface is always in a state of flux. Maintaining a stable
interface level is critical to the safe and efficient operation of the boiler.
Low water levels affect the internal thermal recirculation of the boiler water resulting in
cold spots in the boiler water and steam collapse. This lack of circulation also reduces
the effectiveness of the chemical water treatment and can cause precipitation of the
chemicals as chemical salts or foams.
High water levels raise steam exit velocities and result in priming or boiler water carry-
over in to the distribution system. Priming results in wet dirty steam while carry-over can
result in dangerous water hammer and pipe or equipment damage.




                                                                                           5
Boiler Drum Level                               01/02/01                          Tech Paper #909



Boiler Drum Level Control - ON/OFF vs. Modulating
The objective of the boiler drum level control strategy is to maintain the water/steam
interface at its optimum level to provide a continuous mass/heat balance by replacing
every pound of steam leaving the boiler with a pound of feedwater to replace it.
The interface level is subjected to several disturbances in the water/steam drum; not the
least of which, are drum pressure and feedwater temperature. As steam pressure rises
or falls due to load demand there is a transient change in drum level due to the expansion
or contraction of the steam bubbles in the drum water. When the steam pressure is
lowered the water level rises as the steam bubbles expand (swell). Conversely as the
steam pressure rises the water level lowers as the steam bubbles compress (shrink).
Also as sub-cooled feedwater enters the water/steam drum it will cool the drum water at
the entry point to below the operating pressure boiling point. This acts to condense the
steam bubbles in the boiler drum water and collapse the steam blanket. Thus it is
important that the water/steam drum is large enough to absorb this sub-cooled water
without being overly effected by its influence.

The Effect of Feedwater Temperature on Boiler Performance
It is the influence of feedwater temperature on packaged boilers, which is most
commonly overlooked when selecting a feedwater strategy. If we acknowledge that
boilers are rated from and at feedwater temperatures of 212 degrees ‘F’ and zero PSIG,
then the choice between ON/OFF feedwater control or Modulating feedwater control
becomes of great importance as boiler horsepower, volumes and load swings increase.
To gain operating pressure in the boiler drum additional Btu input is required to raise the
water temperature from the threshold of 212 degrees ‘F’ steaming temperature to that of
operating pressure. The steam tables and the chart below help to expand on this.

Btu Required to Raise Boiler Water to Steaming Temperature at Pressure
          Additional BTU Required to Develop 1 Boiler Horsepower vs. Feedwater Temperature
 Feedwater                                            Boiler Operating Pressure
Temperature       0      25       50       75    100    125    150     175    200   225     250
    50          5,766   7,664    8,733    9,492 10,113 10,631 11,079 11,459 11,838 12,149 12,459
    100         4,041   5,939    7,008    7,767 8,388 8,906 9,354 9,734 10,113 10,424 10,734
    125         3,179   5,076    6,146    6,905 7,526 8,043 8,492 8,871 9,251       9,561    9,872
    150         2,316   4,214    5,283    6,042 6,663 7,181 7,629 8,009 8,388       8,699    9,009
    175         1,454   3,351    4,421    5,180 5,801 6,318 6,767 7,146 7,526       7,836    8,147
    200           591   2,489    3,558    4,317 4,938 5,456 5,904 6,284 6,663       6,974    7,284
    212           177   2,075    3,144    3,903 4,524 5,042 5,490 5,870 6,249       6,560    6,870
    225                 1,626    2,696    3,455 4,076 4,593 5,042 5,421 5,801       6,111    6,422
    230                 1,454    2,523    3,282 3,903 4,421 4,869 5,249 5,628       5,939    6,249
    240                 1,109    2,178    2,937 3,558 4,076 4,524 4,904 5,283       5,594    5,904
    250                   764    1,833    2,592 3,213 3,731 4,179 4,559 4,938       5,249    5,559
    260                   419    1,488    2,247 2,868 3,386 3,834 4,214 4,593       4,904    5,214
    270                    74    1,143    1,902 2,523 3,041 3,489 3,869 4,248       4,559    4,869
    275                            971    1,730 2,351 2,868 3,317 3,696 4,076       4,386    4,697
    280                         798      1,557 2,178 2,696 3,144 3,524 3,903 4,214        4,524




                                                                                               6
Boiler Drum Level                        01/02/01                           Tech Paper #909


ON/OFF feedwater control introduces sudden volumes of sub-cooled water at twice the
boilers steaming capacity, which results in large excursions in the boiler water
temperature, drum level and drum pressure.              These excursions reduce boiler
performance and fuel to steam efficiency by sub-cooling the boiler feedwater and
requiring the burner to over-fire to compensate for the sudden mass/heat upset. While
this may be acceptable in small boiler applications, it can become both inconvenient and
dangerous in larger boilers.
As an example a 500 Bhp (17,250 PPH) (287 PPM) boiler is operating at 225 PSIG with a
boiler water temperature of 397 degrees ‘F’. The boiler is operating at 75% firing rate and
80 percent efficiency producing 12,900 PPH (215 PPM) steam flow (15,686,720 Btu
Input). The feedwater system is ON/OFF and has a recovery volume of 3% low water
capacity (517.5 Lbs.) at the call for water switch point and a 2% over capacity (345 Lbs.)
at a stop water switch point for a total of 5% water recovery capacity. This is 862.5
pounds of water. At the current steaming rate the feedwater cycle is 4.01 minutes
(862.5/215).
The feedwater pump in this application would be capable of delivering 575 pounds of
water per minute, i.e. twice the maximum steaming rate. Feedwater temperature is 180
degrees ‘F’ as it is assumed no deaerator or economizer is being used since neither of
these components can function in an ON/OFF feedwater system.
Thermal Dynamics #1: It takes 1 Btu to raise 1Lb. of water 1 deg. ‘F’ in 1 hour.

Resultant impact on our boiler example:
Ø 862.5 Lbs. water fed at 575 pounds/minute = 1.5 minutes total delivery time at a 217
  degree rise.
Ø First effect = Boiler water sub-cooled from original 397 degrees ‘F’ to 386.15 deg ‘F’.
  ü 95% of Water @ 397 + 5% Water @ 180 = 377.15 + 9 = 386.15 ‘F’ boiler water.
Ø Second effect = Steaming pressure falls from 225 to 195 PSIG due to sub-cooling.
  ü Steam Pressure @ 397 ‘F’ = 225 PSIG, Steam Pressure @ 386 ‘F’ = 195 PSIG.
  ü This is a 13% drop in steaming pressure.
Ø Third effect = Steam nozzle discharge velocity goes form 4,049 to 4,618 Ft./Min. due
  to specific volume difference between 225 PSI steam and 195 PSI steam. 400 Ft./Min
  under critical velocity for carry over. Priming most like to occur.
Ø Fourth effect = The boiler must increase its firing rate by 5,598,600 Btu or 26.76% of
  total firing rate in 1.5 minutes if it is to recover steaming pressure and temperature
  before the next feedwater cycle. However since the boiler is already operating at 75%
  of firing capacity the addition of another 26.76% would mean that the boiler would
  have to fire at 101.76% to recover. It becomes obvious the boiler will not recover full
  horspower.
Ø Fifth effect = Drum level will artificially rise about ½ to 1.0 inch due to the lowered
  steaming pressure resulting in a short cycling of the drum level control signal and
  shut the feed supply off ½ inch early.
Ø Sixth effect = Once boiler drum pressure reaches operating pressure the water level
  will shrink by ½ to 1.0” due to the higher steaming pressure.
It is obvious the mass/heat balance in the boiler has been upset and a great deal of
energy must be expended to recover the upset and bring the process back into balance.




                                                                                         7
Boiler Drum Level                         01/02/01                            Tech Paper #909


What Really Happens
In actual operation the boiler simply fires at a higher firing rate trying to maintain boiler
horsepower, wasting energy, until some semblance of mass/heat balance is made. And
if the load is somewhat steady state the occurrences of priming, carryover or high/low
water trips are generally tolerated as just a matter of how the system operates.
Conversely if the boiler where to be mass/heat balanced matching pounds of water in
with pounds of steam (water vapor) out, the result would be as follows:
12,900 PPH X 217 deg ‘F’ rise X 1 Hour =2,799,300 Btu/Hr or a 17.84 % steady state
increase in firing rate to make up for the sub-cooled feed water. An energy savings of
over 17% can readily be realized by moving from an ON/OFF feedwater system to a
modulating feedwater system in this example. Plus the additional benefits of reducing
priming, carryover, nuisance level trips and improved steam delivery.
Of course once you have committed to a modulating feedwater system you can gain the
benefits of pressurized and per-heated feedwater systems and economizers both of
which, serve to reduce the amount of additional heat input required for sub-cooled
feedwater. (See Improving Boiler Room Efficiencies, Economizers; D.Farthing)

Example of the Effect of Feedwater Temperature on Boiler Performance
                                        Factory Design
Boiler Type Watertube/Firetube                 W
Name Plate Rated Boiler BHP                   500
Normal Operating Pressure                     225                       Deaerator          Typical
Calculated BTU Input for boiler type     22,485,674.16    As Observed First Recovery     Economizer
Observed Feedwater Temp                       212             180           225              262
Hours Day Operated                             16             16             16              16
Days per Month                                 22             22             22              22
Calculated Bhp BTU Output Bhp            16,732,500.00
Calculated Efficiency (Input/Output)         74.41
Calculated Bhp                              500.00
Rated Steam PPH at 100% Firing               17250
BTU addition for Operating Pressure           3,279,750       3,918,000      3,055,500       2,451,750
BTU Lost/Gained Per Hour                      0.00        -552,000.00     224,250.00      862,500.00
Boiler HP Lost or Gained/ Hr.                 0.00           (16.49)         6.70            25.77
Net Boiler Horsepower                         500              484            507             526
Net Steam Output                            17250.0         16680.9        17481.2         18139.2
Net Efficiency                               74.41            71.96          75.41           78.25
Percent Increase/Decrease BHP               0.000%          -3.299%         1.340%          5.155%




                                                                                           8
Boiler Drum Level                           01/02/01                         Tech Paper #909



Boiler Level Control Strategies
Modulating control of the water/steam interface level is normally addressed in one of
three principal strategies, single-element, two-element or three-element control. The
application of any one of these strategies depends on the specific boiler size
(economics) and load variations (dynamics).

Single-Element Control
Single-Element control is perhaps the simplest strategy. In this system drum level is
measured using a single measurement device and provides a control signal to the
feedwater regulator in direct relation to the current operating drum level. This system is
used in both ON/OFF and modulating feedwater control strategies.
The single-element drum level strategy is only effective for smaller boilers with relatively
steady demands and slow to very moderate load changes. This is because the shrink
and swell effect causes an incorrect initial control reaction, which can lead to over/under
filling of the drum. (See ON/OFF control example above.)
As steam demand increases, there is an initial lowering of the drum pressure resulting in
an artificial rise in drum level as the steam bubbles expand and swell the drum water
level. This phenomenon sends a false control signal to reduce feedwater flow, when in
fact the feedwater flow should be increasing to maintain mass balance.
Conversely, on a loss of steam demand, there is an initial rising of steam drum pressure
which acts to lower the drum level by compressing the steam bubbles and shrinking the
drum water level. This sends a false signal to increase feedwater flow when in fact it
should be decreasing to maintain mass balance.




                                 Drawing courtiousy of Honeywell


Processes experienceing sudden or large load changes, can result in ‘phasing’ of the
shrink and swell effect causing the water level controller to lose control of the drum level
and result in nuisance low water trips or high water priming and carry-over.



                                                                                           9
Boiler Drum Level                             01/02/01                          Tech Paper #909


Two-Element Control
The two-element drum level strategy is suitable for processes with moderate load swings
and speeds, and it can be used on any size of boiler. This system uses the two
variables, drum level and steam flow to mass balance the feedwater demand.
Drum level is measured and the error between the desired setpoint and the actual control
point is sent to a math summer as one of two process variables. Steam flow is
measured and added (summed) to the math summer as the second process variable.
The result of the math summer is the control output to the feedwater control valve.
Since steam flow is very dynamic, the result of this strategy is that it will sense the rise or
fall in load demand before the drum level begins to change. The startegy then adds or
subtracts control output to stabilize the reaction of the drum level controller on the
feedwater control valve. And since steam flow is normally the larger variable it can easily
over ride the trim effect of the drum level measurement on moderate load changes,
insuring a correct response to the demand change. During steady load the drum level
controller influences the feedwater control valve and acts to trim the level to the desired
setpoint.




                         Two-Element Control, drawing courtiousy of Honeywell

This strategy has two drawbacks, which should be considered. First like the single
element strategy the two-element control can not adjust for pressure or load
disturbances in the feedwater supply, as this is not a measured variable in this strategy.
And second the two-element control cannot eliminate phasing interaction between
feedwater flow and drum level because only the relatively slow process of the drum level
is controlled. This second issue can lead to sub-cooled drum water on a large increase
in demand by allowing excessive feedwater to enter the drum without consideration to the
boilers thermal dynamic capabilities.




                                                                                            10
Boiler Drum Level                           01/02/01                           Tech Paper #909


Three-Element Drum Level Control
To address the issues of phasing still present in the two-element control strategy, a third
element, feedwater flow is added to the drum level control strategy. In this system the
math summer output of the two-element controller is cascaded down to a second
Feedwater Flow Controller to act as a Remote Setpoint.
The feedwater controller is a fast acting flow controller, which uses feedwater flow as its
process variable and steam flow as its setpoint. Thus for every pound of steam flow
leaving the boiler a pound of feedwater is added. This loop has final control on the
feedwater valve. As the remote setpoint from the two element level control changes with
steam flow and drum level variations due to blowdown or other minor losses, the
feedwater controller modulates its output to regulate the necessary feedwater flow to
keep the drum level in a mass/heat balanced and level state.
Independent tuning of each controller allows for very precise control of the drum level
regardless of steam demand and feedwater influences. However it is very important to
take the thermal dynamics of the boiler’s recovery rate into account when tuning the
feedwater controller. If you fail to do this and set the controller reset too fast on the
feedwater controller you may inadvertently sub-cool the drum and start a cyclic phasing
action much like that found in a two-element system. Do the math it will save you a lot of
heartache.




                                 Drawing courtiousy of Honeywell

The three-element control strategy can easily handle large and rapid load changes
because it is matching the mass balance between the steam flow from the boiler and the
feedwater flow to it. This strategy is a must on multiple boilers sharing the same
feedwater header and supply system, due to the variations in the available feedwater flow
to any one boiler, while two or more boilers are on line. This is irrespective to boiler size.
Additionally if the boilers are subjected to sudden or unpredictable demand changes such
as in a batching process, this strategy is capable of matching these demands without
operator trim corrections or supervision.




                                                                                           11
Boiler Drum Level                    01/02/01                        Tech Paper #909



Conclusion
As you can see from the examples we have evaluated, managing feedwater efficiently
does have its practical benefits.




                                                                                 12
Boiler Drum Level                                 01/02/01                               Tech Paper #909


About the Author




David C. Farthing

Mr. Farthing combines his twenty-eight years of experience in thermal processes with a degree in General
Engineering Technology from Oklahoma State University as well as a degree in Business from the
University of Central Oklahoma. He is both a practitioner and academic in the field of boilers and thermal
process control systems, as Sales Manager for Federal Corporation and adjunct instructor of ‘ oiler B
Construction, Operations, and Maintenance’ for Oklahoma State University, Oklahoma City campus.


Bibliography
Frederick M. Steingress & Harold J. Frost, High Pressure Steam Boilers 2 nd edition,
American Technical Publishers

Honeywell Industrial Control and Automation

Mark’s Engineering Handbook, 7th Edition

David C. Farthing, <‘TechStuff’>, www.federalcorp.com

Kewanee Boiler Manufacturing, Kewanee, Illinois

Nebraska Boiler, Lincoln, Nebraska




                                                                                                       13

Más contenido relacionado

La actualidad más candente

Boiler Controls and Instrumentation
Boiler Controls and InstrumentationBoiler Controls and Instrumentation
Boiler Controls and InstrumentationDell Technologies
 
Turbine Governing System
Turbine Governing SystemTurbine Governing System
Turbine Governing SystemSalil Vaidya
 
Boiler Loss of Flame Protection- MFT
Boiler Loss of Flame Protection- MFTBoiler Loss of Flame Protection- MFT
Boiler Loss of Flame Protection- MFTTahoor Alam Khan
 
Heat rate audit in thermal power plant
Heat rate audit in thermal power plantHeat rate audit in thermal power plant
Heat rate audit in thermal power plantSHIVAJI CHOUDHURY
 
Steam turbine and its types
Steam turbine and its typesSteam turbine and its types
Steam turbine and its typesSanila Khalid
 
Frequently asked questions on turbines Part 1
Frequently asked questions on turbines Part 1Frequently asked questions on turbines Part 1
Frequently asked questions on turbines Part 1Manohar Tatwawadi
 
steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)Billa ParameswaraRao
 
Handling of turbine side emergencies
Handling of turbine side emergenciesHandling of turbine side emergencies
Handling of turbine side emergenciesManohar Tatwawadi
 
Basic controls for boilers
Basic controls for boilersBasic controls for boilers
Basic controls for boilersAasheesh Tandon
 
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam TurbineThermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam TurbineManohar Tatwawadi
 
AUTOMATIC TURBINE RUNUP SYSTEM
AUTOMATIC TURBINE RUNUP SYSTEMAUTOMATIC TURBINE RUNUP SYSTEM
AUTOMATIC TURBINE RUNUP SYSTEMkumarswamy927
 
ROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANT
ROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANTROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANT
ROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANTGaurav Rai
 
Boiler Reheater protection
Boiler Reheater  protectionBoiler Reheater  protection
Boiler Reheater protectionanujkumarsingh79
 
660 mw turbo governing &amp; protection system
660 mw turbo  governing &amp; protection system660 mw turbo  governing &amp; protection system
660 mw turbo governing &amp; protection systemAshvani Shukla
 
Feedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsFeedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsSHIVAJI CHOUDHURY
 
A technical overview of thermal power plant
A technical overview of thermal power plantA technical overview of thermal power plant
A technical overview of thermal power plantMirdul Amin Sarkar
 
Unit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdownUnit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdownNitin Mahalle
 
Turbine governing system an overview
Turbine governing system an overviewTurbine governing system an overview
Turbine governing system an overviewGaurav Kaushik
 
Steam Turbine Parts.pdf
Steam Turbine Parts.pdfSteam Turbine Parts.pdf
Steam Turbine Parts.pdfKAhmedRehman
 

La actualidad más candente (20)

Boiler Controls and Instrumentation
Boiler Controls and InstrumentationBoiler Controls and Instrumentation
Boiler Controls and Instrumentation
 
Turbine Governing System
Turbine Governing SystemTurbine Governing System
Turbine Governing System
 
Boiler Loss of Flame Protection- MFT
Boiler Loss of Flame Protection- MFTBoiler Loss of Flame Protection- MFT
Boiler Loss of Flame Protection- MFT
 
Heat rate audit in thermal power plant
Heat rate audit in thermal power plantHeat rate audit in thermal power plant
Heat rate audit in thermal power plant
 
Steam turbine and its types
Steam turbine and its typesSteam turbine and its types
Steam turbine and its types
 
Frequently asked questions on turbines Part 1
Frequently asked questions on turbines Part 1Frequently asked questions on turbines Part 1
Frequently asked questions on turbines Part 1
 
steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)
 
200 mw FSSS
200 mw FSSS200 mw FSSS
200 mw FSSS
 
Handling of turbine side emergencies
Handling of turbine side emergenciesHandling of turbine side emergencies
Handling of turbine side emergencies
 
Basic controls for boilers
Basic controls for boilersBasic controls for boilers
Basic controls for boilers
 
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam TurbineThermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
 
AUTOMATIC TURBINE RUNUP SYSTEM
AUTOMATIC TURBINE RUNUP SYSTEMAUTOMATIC TURBINE RUNUP SYSTEM
AUTOMATIC TURBINE RUNUP SYSTEM
 
ROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANT
ROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANTROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANT
ROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANT
 
Boiler Reheater protection
Boiler Reheater  protectionBoiler Reheater  protection
Boiler Reheater protection
 
660 mw turbo governing &amp; protection system
660 mw turbo  governing &amp; protection system660 mw turbo  governing &amp; protection system
660 mw turbo governing &amp; protection system
 
Feedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsFeedwater heaters in thermal power plants
Feedwater heaters in thermal power plants
 
A technical overview of thermal power plant
A technical overview of thermal power plantA technical overview of thermal power plant
A technical overview of thermal power plant
 
Unit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdownUnit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdown
 
Turbine governing system an overview
Turbine governing system an overviewTurbine governing system an overview
Turbine governing system an overview
 
Steam Turbine Parts.pdf
Steam Turbine Parts.pdfSteam Turbine Parts.pdf
Steam Turbine Parts.pdf
 

Similar a Drum level

Process Control and instrumentation
Process Control and instrumentationProcess Control and instrumentation
Process Control and instrumentationPaul O Gorman
 
Importance of three elements boiler drum level control and its installation i...
Importance of three elements boiler drum level control and its installation i...Importance of three elements boiler drum level control and its installation i...
Importance of three elements boiler drum level control and its installation i...ijics
 
Ammonia plant efficiency
Ammonia plant efficiencyAmmonia plant efficiency
Ammonia plant efficiencyHimanshu Sharma
 
IRJET- Optimisation of Soot Blower Operation in Boiler to Improve Efficiency
IRJET- Optimisation of Soot Blower Operation in Boiler to Improve EfficiencyIRJET- Optimisation of Soot Blower Operation in Boiler to Improve Efficiency
IRJET- Optimisation of Soot Blower Operation in Boiler to Improve EfficiencyIRJET Journal
 
Guide to-choosing-the-right-valve
Guide to-choosing-the-right-valveGuide to-choosing-the-right-valve
Guide to-choosing-the-right-valveChevronelle
 
Best Practices in Measuring Tank Level
Best Practices in Measuring Tank LevelBest Practices in Measuring Tank Level
Best Practices in Measuring Tank LevelSetra Systems
 
Practical Boiler Control & Instrumentation for Engineers & Technicians
Practical Boiler Control & Instrumentation for Engineers & TechniciansPractical Boiler Control & Instrumentation for Engineers & Technicians
Practical Boiler Control & Instrumentation for Engineers & TechniciansLiving Online
 
Improving Energy Efficiency of Pumps and Fans
Improving Energy Efficiency of Pumps and FansImproving Energy Efficiency of Pumps and Fans
Improving Energy Efficiency of Pumps and Fanseecfncci
 
Indusrial training -MUKUL KUMAR
Indusrial training -MUKUL KUMARIndusrial training -MUKUL KUMAR
Indusrial training -MUKUL KUMARMUKUL KUMAR
 
Catálogo Geral Milton Roy
Catálogo Geral Milton RoyCatálogo Geral Milton Roy
Catálogo Geral Milton RoyVibropac
 
Aeration unit Lab Report(Separation Lab)
Aeration unit Lab Report(Separation Lab)Aeration unit Lab Report(Separation Lab)
Aeration unit Lab Report(Separation Lab)Chaudhary Zubair Qadir
 
Boiler
BoilerBoiler
Boileravik
 
Tube Wall Temperature Measurement On Steam Reformers - Best Practices
Tube Wall Temperature Measurement On Steam Reformers - Best PracticesTube Wall Temperature Measurement On Steam Reformers - Best Practices
Tube Wall Temperature Measurement On Steam Reformers - Best PracticesGerard B. Hawkins
 
Optimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery ProcessOptimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery ProcessM.S. Jacobs & Associates
 
Optimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery ProcessOptimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery ProcessBelilove Company-Engineers
 
Boiler instrumentation-and-controls
Boiler instrumentation-and-controlsBoiler instrumentation-and-controls
Boiler instrumentation-and-controlsDARSHAN B S
 
Training on OJT of Boiler Operation00.pdf
Training on OJT of Boiler Operation00.pdfTraining on OJT of Boiler Operation00.pdf
Training on OJT of Boiler Operation00.pdfMadan Karki
 

Similar a Drum level (20)

Industrial Boiler Optimization Toolkit
Industrial Boiler Optimization ToolkitIndustrial Boiler Optimization Toolkit
Industrial Boiler Optimization Toolkit
 
Process Control and instrumentation
Process Control and instrumentationProcess Control and instrumentation
Process Control and instrumentation
 
Importance of three elements boiler drum level control and its installation i...
Importance of three elements boiler drum level control and its installation i...Importance of three elements boiler drum level control and its installation i...
Importance of three elements boiler drum level control and its installation i...
 
Ammonia plant efficiency
Ammonia plant efficiencyAmmonia plant efficiency
Ammonia plant efficiency
 
IRJET- Optimisation of Soot Blower Operation in Boiler to Improve Efficiency
IRJET- Optimisation of Soot Blower Operation in Boiler to Improve EfficiencyIRJET- Optimisation of Soot Blower Operation in Boiler to Improve Efficiency
IRJET- Optimisation of Soot Blower Operation in Boiler to Improve Efficiency
 
Agc wp-vacuumdistil
Agc wp-vacuumdistilAgc wp-vacuumdistil
Agc wp-vacuumdistil
 
Guide to-choosing-the-right-valve
Guide to-choosing-the-right-valveGuide to-choosing-the-right-valve
Guide to-choosing-the-right-valve
 
Best Practices in Measuring Tank Level
Best Practices in Measuring Tank LevelBest Practices in Measuring Tank Level
Best Practices in Measuring Tank Level
 
Practical Boiler Control & Instrumentation for Engineers & Technicians
Practical Boiler Control & Instrumentation for Engineers & TechniciansPractical Boiler Control & Instrumentation for Engineers & Technicians
Practical Boiler Control & Instrumentation for Engineers & Technicians
 
Improving Energy Efficiency of Pumps and Fans
Improving Energy Efficiency of Pumps and FansImproving Energy Efficiency of Pumps and Fans
Improving Energy Efficiency of Pumps and Fans
 
Indusrial training -MUKUL KUMAR
Indusrial training -MUKUL KUMARIndusrial training -MUKUL KUMAR
Indusrial training -MUKUL KUMAR
 
Catálogo Geral Milton Roy
Catálogo Geral Milton RoyCatálogo Geral Milton Roy
Catálogo Geral Milton Roy
 
Aeration unit Lab Report(Separation Lab)
Aeration unit Lab Report(Separation Lab)Aeration unit Lab Report(Separation Lab)
Aeration unit Lab Report(Separation Lab)
 
Selection and Calibration of a Turbine Flow Meter
Selection and Calibration of a Turbine Flow MeterSelection and Calibration of a Turbine Flow Meter
Selection and Calibration of a Turbine Flow Meter
 
Boiler
BoilerBoiler
Boiler
 
Tube Wall Temperature Measurement On Steam Reformers - Best Practices
Tube Wall Temperature Measurement On Steam Reformers - Best PracticesTube Wall Temperature Measurement On Steam Reformers - Best Practices
Tube Wall Temperature Measurement On Steam Reformers - Best Practices
 
Optimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery ProcessOptimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery Process
 
Optimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery ProcessOptimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery Process
 
Boiler instrumentation-and-controls
Boiler instrumentation-and-controlsBoiler instrumentation-and-controls
Boiler instrumentation-and-controls
 
Training on OJT of Boiler Operation00.pdf
Training on OJT of Boiler Operation00.pdfTraining on OJT of Boiler Operation00.pdf
Training on OJT of Boiler Operation00.pdf
 

Último

Effective Strategies for Maximizing Your Profit When Selling Gold Jewelry
Effective Strategies for Maximizing Your Profit When Selling Gold JewelryEffective Strategies for Maximizing Your Profit When Selling Gold Jewelry
Effective Strategies for Maximizing Your Profit When Selling Gold JewelryWhittensFineJewelry1
 
Send Files | Sendbig.comSend Files | Sendbig.com
Send Files | Sendbig.comSend Files | Sendbig.comSend Files | Sendbig.comSend Files | Sendbig.com
Send Files | Sendbig.comSend Files | Sendbig.comSendBig4
 
Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03DallasHaselhorst
 
1911 Gold Corporate Presentation Apr 2024.pdf
1911 Gold Corporate Presentation Apr 2024.pdf1911 Gold Corporate Presentation Apr 2024.pdf
1911 Gold Corporate Presentation Apr 2024.pdfShaun Heinrichs
 
BAILMENT & PLEDGE business law notes.pptx
BAILMENT & PLEDGE business law notes.pptxBAILMENT & PLEDGE business law notes.pptx
BAILMENT & PLEDGE business law notes.pptxran17april2001
 
Guide Complete Set of Residential Architectural Drawings PDF
Guide Complete Set of Residential Architectural Drawings PDFGuide Complete Set of Residential Architectural Drawings PDF
Guide Complete Set of Residential Architectural Drawings PDFChandresh Chudasama
 
NAB Show Exhibitor List 2024 - Exhibitors Data
NAB Show Exhibitor List 2024 - Exhibitors DataNAB Show Exhibitor List 2024 - Exhibitors Data
NAB Show Exhibitor List 2024 - Exhibitors DataExhibitors Data
 
20200128 Ethical by Design - Whitepaper.pdf
20200128 Ethical by Design - Whitepaper.pdf20200128 Ethical by Design - Whitepaper.pdf
20200128 Ethical by Design - Whitepaper.pdfChris Skinner
 
Lucia Ferretti, Lead Business Designer; Matteo Meschini, Business Designer @T...
Lucia Ferretti, Lead Business Designer; Matteo Meschini, Business Designer @T...Lucia Ferretti, Lead Business Designer; Matteo Meschini, Business Designer @T...
Lucia Ferretti, Lead Business Designer; Matteo Meschini, Business Designer @T...Associazione Digital Days
 
Welding Electrode Making Machine By Deccan Dynamics
Welding Electrode Making Machine By Deccan DynamicsWelding Electrode Making Machine By Deccan Dynamics
Welding Electrode Making Machine By Deccan DynamicsIndiaMART InterMESH Limited
 
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptxGo for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptxRakhi Bazaar
 
business environment micro environment macro environment.pptx
business environment micro environment macro environment.pptxbusiness environment micro environment macro environment.pptx
business environment micro environment macro environment.pptxShruti Mittal
 
TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024Adnet Communications
 
WSMM Technology February.March Newsletter_vF.pdf
WSMM Technology February.March Newsletter_vF.pdfWSMM Technology February.March Newsletter_vF.pdf
WSMM Technology February.March Newsletter_vF.pdfJamesConcepcion7
 
APRIL2024_UKRAINE_xml_0000000000000 .pdf
APRIL2024_UKRAINE_xml_0000000000000 .pdfAPRIL2024_UKRAINE_xml_0000000000000 .pdf
APRIL2024_UKRAINE_xml_0000000000000 .pdfRbc Rbcua
 
digital marketing , introduction of digital marketing
digital marketing , introduction of digital marketingdigital marketing , introduction of digital marketing
digital marketing , introduction of digital marketingrajputmeenakshi733
 
Excvation Safety for safety officers reference
Excvation Safety for safety officers referenceExcvation Safety for safety officers reference
Excvation Safety for safety officers referencessuser2c065e
 
Pitch Deck Teardown: Xpanceo's $40M Seed deck
Pitch Deck Teardown: Xpanceo's $40M Seed deckPitch Deck Teardown: Xpanceo's $40M Seed deck
Pitch Deck Teardown: Xpanceo's $40M Seed deckHajeJanKamps
 
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...Operational Excellence Consulting
 
Church Building Grants To Assist With New Construction, Additions, And Restor...
Church Building Grants To Assist With New Construction, Additions, And Restor...Church Building Grants To Assist With New Construction, Additions, And Restor...
Church Building Grants To Assist With New Construction, Additions, And Restor...Americas Got Grants
 

Último (20)

Effective Strategies for Maximizing Your Profit When Selling Gold Jewelry
Effective Strategies for Maximizing Your Profit When Selling Gold JewelryEffective Strategies for Maximizing Your Profit When Selling Gold Jewelry
Effective Strategies for Maximizing Your Profit When Selling Gold Jewelry
 
Send Files | Sendbig.comSend Files | Sendbig.com
Send Files | Sendbig.comSend Files | Sendbig.comSend Files | Sendbig.comSend Files | Sendbig.com
Send Files | Sendbig.comSend Files | Sendbig.com
 
Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03
 
1911 Gold Corporate Presentation Apr 2024.pdf
1911 Gold Corporate Presentation Apr 2024.pdf1911 Gold Corporate Presentation Apr 2024.pdf
1911 Gold Corporate Presentation Apr 2024.pdf
 
BAILMENT & PLEDGE business law notes.pptx
BAILMENT & PLEDGE business law notes.pptxBAILMENT & PLEDGE business law notes.pptx
BAILMENT & PLEDGE business law notes.pptx
 
Guide Complete Set of Residential Architectural Drawings PDF
Guide Complete Set of Residential Architectural Drawings PDFGuide Complete Set of Residential Architectural Drawings PDF
Guide Complete Set of Residential Architectural Drawings PDF
 
NAB Show Exhibitor List 2024 - Exhibitors Data
NAB Show Exhibitor List 2024 - Exhibitors DataNAB Show Exhibitor List 2024 - Exhibitors Data
NAB Show Exhibitor List 2024 - Exhibitors Data
 
20200128 Ethical by Design - Whitepaper.pdf
20200128 Ethical by Design - Whitepaper.pdf20200128 Ethical by Design - Whitepaper.pdf
20200128 Ethical by Design - Whitepaper.pdf
 
Lucia Ferretti, Lead Business Designer; Matteo Meschini, Business Designer @T...
Lucia Ferretti, Lead Business Designer; Matteo Meschini, Business Designer @T...Lucia Ferretti, Lead Business Designer; Matteo Meschini, Business Designer @T...
Lucia Ferretti, Lead Business Designer; Matteo Meschini, Business Designer @T...
 
Welding Electrode Making Machine By Deccan Dynamics
Welding Electrode Making Machine By Deccan DynamicsWelding Electrode Making Machine By Deccan Dynamics
Welding Electrode Making Machine By Deccan Dynamics
 
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptxGo for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
 
business environment micro environment macro environment.pptx
business environment micro environment macro environment.pptxbusiness environment micro environment macro environment.pptx
business environment micro environment macro environment.pptx
 
TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024
 
WSMM Technology February.March Newsletter_vF.pdf
WSMM Technology February.March Newsletter_vF.pdfWSMM Technology February.March Newsletter_vF.pdf
WSMM Technology February.March Newsletter_vF.pdf
 
APRIL2024_UKRAINE_xml_0000000000000 .pdf
APRIL2024_UKRAINE_xml_0000000000000 .pdfAPRIL2024_UKRAINE_xml_0000000000000 .pdf
APRIL2024_UKRAINE_xml_0000000000000 .pdf
 
digital marketing , introduction of digital marketing
digital marketing , introduction of digital marketingdigital marketing , introduction of digital marketing
digital marketing , introduction of digital marketing
 
Excvation Safety for safety officers reference
Excvation Safety for safety officers referenceExcvation Safety for safety officers reference
Excvation Safety for safety officers reference
 
Pitch Deck Teardown: Xpanceo's $40M Seed deck
Pitch Deck Teardown: Xpanceo's $40M Seed deckPitch Deck Teardown: Xpanceo's $40M Seed deck
Pitch Deck Teardown: Xpanceo's $40M Seed deck
 
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
 
Church Building Grants To Assist With New Construction, Additions, And Restor...
Church Building Grants To Assist With New Construction, Additions, And Restor...Church Building Grants To Assist With New Construction, Additions, And Restor...
Church Building Grants To Assist With New Construction, Additions, And Restor...
 

Drum level

  • 1. Boiler Drum Level 01/02/01 Tech Paper #909 Improving Boiler Room Efficiencies A Seminar on the ways and means of increasing boiler room efficiencies. Boiler Drum Level Measurement and Control Presented by David C. Farthing Federal Corporation A proud Oklahoma partner for over 80 years! Providing over 80 years of boiler and boiler room experience. Rev 9/00 1
  • 2. Boiler Drum Level 01/02/01 Tech Paper #909 Contents A MESSAGE FROM THE SPEAKER...........................................................................................................................3 INTRODUCTION ............................................................................................................................................................3 STEAM PLANT OPTIMIZATION & AUTOMATION.............................................................................................3 LIQUID LEVEL MEASUREMENT................................................................................................................................4 INFERENTIAL LEVEL M EASUREMENT ..................................................................................................................... 4 VOLUMETRIC LEVEL M EASUREMENT ..................................................................................................................... 4 DIFFERENTIAL PRESSURE LEVEL M EASUREMENT ................................................................................................ 5 THE BOILER W ATER/STEAM DRUM........................................................................................................................ 5 BOILER DRUM LEVEL CONTROL - ON/OFF VS. MODULATING....................................................................6 THE EFFECT OF FEEDWATER TEMPERATURE ON BOILER PERFORMANCE............................................6 Btu Required to Raise Boiler Water to Steaming Temperature at Pressure................................................6 What Really Happens.............................................................................................................................................8 EXAMPLE OT THE EFFECT OF FEEDWATER TEMPERATURE ON BOILER PERFORMANCE ............................ 8 BOILER LEVEL CONTROL STRATEGIES ..............................................................................................................9 SINGLE-ELEMENT CONTROL..................................................................................................................................... 9 TWO-ELEMENT CONTROL ....................................................................................................................................... 10 THREE-ELEMENT DRUM LEVEL CONTROL........................................................................................................... 11 CONCLUSION...............................................................................................................................................................12 A BOUT THE A UTHOR............................................................................................................................................... 13 BIBLIOGRAPHY........................................................................................................................................................... 13 2
  • 3. Boiler Drum Level 01/02/01 Tech Paper #909 A Message from the speaker Energy costs today are at there highest in recent history. Gaining whatever efficiencies may be found in thermal processes can help to stabilize the effects of rising energy cost. Also today’s economic and environmental demands dictate that we get the greatest practical efficiencies from our plants. To do this we must have a basic understanding of what those efficiencies are and how we may implement them. My hope for you today is, that you will leave this seminar with a clearer understanding of some of the economically and technically feasible opportunities you have to improve your steam plant. Regards, David C. Farthing Industrial Sales Manager Federal Corporation Introduction Improved efficiency can have many connotations everything from fuel savings, improved equipment operation and useful life span, to labor and manpower savings. This paper will focus on the effects of boiler drum level and feedwater control as a means of energy savings by thermal/mass balancing the boiler. This paper will also discuss the effects of steam drum pressure and feedwater temperature on the overall efficiency of the boiler. Steam Plant Optimization & Automation Steam plant optimization is the overall improvement of the plant’s operation. The most common strategies used to accomplish this task includes, and generally focuses on, the improvement of primary equipment operating efficiency, i.e. fuel and energy savings. In heavy commercial and industrial boiler applications these efficiencies are normally found in the application of waste heat recovery equipment, systems and process automation, and improved operating practices. Boiler Drum Level Control has historically benefited from improvements in systems and process automation techniques. As such three separate control strategies, single element, two element and three-element control will be analyzed in this paper. 3
  • 4. Boiler Drum Level 01/02/01 Tech Paper #909 Liquid Level Measurement The measurement of liquid level enables us to locate the surface of a liquid with respect to some referenced level. Level measurement is necessary in Boiler Drum Level Measurement for the safe and efficient operation of the boiler. Inferential Level Measurement One of the most flexible and convenient means of measuring liquid level is the static pressure or inferential method. This method is based on the fact that the static pressure exerted by any fluid is directly proportional to the height of the liquid above the point of measurement, irrespective of volume. Thus any instrument which is affected by pressure can be calibrated in terms of the height of a given liquid. The liquid sightglass is based on this method of measurement as the weight of water will find its own level in any open or closed loop. Inferential Measurement is heavily influenced by sudden changes in liquid density, pressure or level disturbances and thus requires a stilling well to help dampen these disturbences. The use of a water column on the boiler drum acts as a stilling well for the level control devices and the sightglass. In steam boiler applications the communication lines to the measurement instrument must remain unobstructed. Interruption of the vapor side communication line will result in an artificially low reading due to the effects of the drum pressure acting on the water column to compress the reading. While interruption of the liquid communication line will result in an artificially high reading, as condensate from the vapor line will tend to condense in the chamber and fill it up. Volumetric Level Measurement Volumetric Level Measurement is found in the form of float (displacement) type devices, which transmit the level in a vessel by simply floating on the surface of the liquid. Float operated liquid level measurement is a direct measurement in which the float rises and falls with the surface of the liquid level. In this method, the float, through a transmitter arm, can actuate a pointer, recording pen or electronic/pneumatic transmitter. One of the most important aspects of float measurement is the effect of density on the level reading. As density falls the liquid loses its ability to support the float and the float rides deeper in the fluid suppressing the level reading accordingly. Thus it is important to know the density range that the float is to operate in and design accordingly. As an example, a float designed for 60 degree ‘F’ water, with a density of 1.0, would sink and fail to register any level in a tank filled with say gasoline having a density of 0.60. Most single element drum level sensing devices and mechanical level switches use volumetric level measurement. 4
  • 5. Boiler Drum Level 01/02/01 Tech Paper #909 Differential Pressure Level Measurement One of the simplest methods of measuring liquid level in a closed tank is to use a differential pressure device having a range equal to the liquid head being measured. Again, product density is important as the head pressure exerted on the differential element is in direct relationship to the density of the liquid being measured. Liquid levels in closed tanks under pressure may be measured by this method. In these applications, the reference leg of the differential meter body must be connected to the pressure in the tank being measured so that the differential being measured will be independent of any pressure changes other than those due to changes in level. In closed tank applications with condensing liquids, the reference line should be filled with the liquid being measured during installation. As noted the density of liquids change with temperature and the reference leg, which is at condensing temperature, will always read heavy in relation to the level measurement leg resulting in a zero shift. Therefore the meter body must be calibrated with a full liquid reference leg in order to correct for the zero shift. The Boiler Water/Steam Drum The boiler water/steam drum, or steam drum, is an integral part of the boiler’s design. This vessel has three specific purposes; 1] provide a volume space to hold the boiling water in the boiler, 2] provide enough water volume to allow for good thermal mixing of the cooler bottom drum water with the hotter surface interface water, and 3] provide surface area and volume for the efficient release of the entrained steam bubbles from the boiler water. The surface area and volume of the vapor space in the water/steam drum is critical to the efficient separation of the steam bubbles from the water. Too small an area can result in an excessive surface tension and high velocities, which result in wasted heat and drum water carry-over. Too large an area is simply a waste of materials and labor to construct the vessel. The boiler water/steam drum also provides a logical location for 1] addition of feedwater, 2] addition of chemical water treatment and 3] surface blowdown, which helps reduce the surface tension of the water/steam interface to allow better steam release. Because all of these task involve the removal and addition of some mass (water or steam) the water/steam interface is always in a state of flux. Maintaining a stable interface level is critical to the safe and efficient operation of the boiler. Low water levels affect the internal thermal recirculation of the boiler water resulting in cold spots in the boiler water and steam collapse. This lack of circulation also reduces the effectiveness of the chemical water treatment and can cause precipitation of the chemicals as chemical salts or foams. High water levels raise steam exit velocities and result in priming or boiler water carry- over in to the distribution system. Priming results in wet dirty steam while carry-over can result in dangerous water hammer and pipe or equipment damage. 5
  • 6. Boiler Drum Level 01/02/01 Tech Paper #909 Boiler Drum Level Control - ON/OFF vs. Modulating The objective of the boiler drum level control strategy is to maintain the water/steam interface at its optimum level to provide a continuous mass/heat balance by replacing every pound of steam leaving the boiler with a pound of feedwater to replace it. The interface level is subjected to several disturbances in the water/steam drum; not the least of which, are drum pressure and feedwater temperature. As steam pressure rises or falls due to load demand there is a transient change in drum level due to the expansion or contraction of the steam bubbles in the drum water. When the steam pressure is lowered the water level rises as the steam bubbles expand (swell). Conversely as the steam pressure rises the water level lowers as the steam bubbles compress (shrink). Also as sub-cooled feedwater enters the water/steam drum it will cool the drum water at the entry point to below the operating pressure boiling point. This acts to condense the steam bubbles in the boiler drum water and collapse the steam blanket. Thus it is important that the water/steam drum is large enough to absorb this sub-cooled water without being overly effected by its influence. The Effect of Feedwater Temperature on Boiler Performance It is the influence of feedwater temperature on packaged boilers, which is most commonly overlooked when selecting a feedwater strategy. If we acknowledge that boilers are rated from and at feedwater temperatures of 212 degrees ‘F’ and zero PSIG, then the choice between ON/OFF feedwater control or Modulating feedwater control becomes of great importance as boiler horsepower, volumes and load swings increase. To gain operating pressure in the boiler drum additional Btu input is required to raise the water temperature from the threshold of 212 degrees ‘F’ steaming temperature to that of operating pressure. The steam tables and the chart below help to expand on this. Btu Required to Raise Boiler Water to Steaming Temperature at Pressure Additional BTU Required to Develop 1 Boiler Horsepower vs. Feedwater Temperature Feedwater Boiler Operating Pressure Temperature 0 25 50 75 100 125 150 175 200 225 250 50 5,766 7,664 8,733 9,492 10,113 10,631 11,079 11,459 11,838 12,149 12,459 100 4,041 5,939 7,008 7,767 8,388 8,906 9,354 9,734 10,113 10,424 10,734 125 3,179 5,076 6,146 6,905 7,526 8,043 8,492 8,871 9,251 9,561 9,872 150 2,316 4,214 5,283 6,042 6,663 7,181 7,629 8,009 8,388 8,699 9,009 175 1,454 3,351 4,421 5,180 5,801 6,318 6,767 7,146 7,526 7,836 8,147 200 591 2,489 3,558 4,317 4,938 5,456 5,904 6,284 6,663 6,974 7,284 212 177 2,075 3,144 3,903 4,524 5,042 5,490 5,870 6,249 6,560 6,870 225 1,626 2,696 3,455 4,076 4,593 5,042 5,421 5,801 6,111 6,422 230 1,454 2,523 3,282 3,903 4,421 4,869 5,249 5,628 5,939 6,249 240 1,109 2,178 2,937 3,558 4,076 4,524 4,904 5,283 5,594 5,904 250 764 1,833 2,592 3,213 3,731 4,179 4,559 4,938 5,249 5,559 260 419 1,488 2,247 2,868 3,386 3,834 4,214 4,593 4,904 5,214 270 74 1,143 1,902 2,523 3,041 3,489 3,869 4,248 4,559 4,869 275 971 1,730 2,351 2,868 3,317 3,696 4,076 4,386 4,697 280 798 1,557 2,178 2,696 3,144 3,524 3,903 4,214 4,524 6
  • 7. Boiler Drum Level 01/02/01 Tech Paper #909 ON/OFF feedwater control introduces sudden volumes of sub-cooled water at twice the boilers steaming capacity, which results in large excursions in the boiler water temperature, drum level and drum pressure. These excursions reduce boiler performance and fuel to steam efficiency by sub-cooling the boiler feedwater and requiring the burner to over-fire to compensate for the sudden mass/heat upset. While this may be acceptable in small boiler applications, it can become both inconvenient and dangerous in larger boilers. As an example a 500 Bhp (17,250 PPH) (287 PPM) boiler is operating at 225 PSIG with a boiler water temperature of 397 degrees ‘F’. The boiler is operating at 75% firing rate and 80 percent efficiency producing 12,900 PPH (215 PPM) steam flow (15,686,720 Btu Input). The feedwater system is ON/OFF and has a recovery volume of 3% low water capacity (517.5 Lbs.) at the call for water switch point and a 2% over capacity (345 Lbs.) at a stop water switch point for a total of 5% water recovery capacity. This is 862.5 pounds of water. At the current steaming rate the feedwater cycle is 4.01 minutes (862.5/215). The feedwater pump in this application would be capable of delivering 575 pounds of water per minute, i.e. twice the maximum steaming rate. Feedwater temperature is 180 degrees ‘F’ as it is assumed no deaerator or economizer is being used since neither of these components can function in an ON/OFF feedwater system. Thermal Dynamics #1: It takes 1 Btu to raise 1Lb. of water 1 deg. ‘F’ in 1 hour. Resultant impact on our boiler example: Ø 862.5 Lbs. water fed at 575 pounds/minute = 1.5 minutes total delivery time at a 217 degree rise. Ø First effect = Boiler water sub-cooled from original 397 degrees ‘F’ to 386.15 deg ‘F’. ü 95% of Water @ 397 + 5% Water @ 180 = 377.15 + 9 = 386.15 ‘F’ boiler water. Ø Second effect = Steaming pressure falls from 225 to 195 PSIG due to sub-cooling. ü Steam Pressure @ 397 ‘F’ = 225 PSIG, Steam Pressure @ 386 ‘F’ = 195 PSIG. ü This is a 13% drop in steaming pressure. Ø Third effect = Steam nozzle discharge velocity goes form 4,049 to 4,618 Ft./Min. due to specific volume difference between 225 PSI steam and 195 PSI steam. 400 Ft./Min under critical velocity for carry over. Priming most like to occur. Ø Fourth effect = The boiler must increase its firing rate by 5,598,600 Btu or 26.76% of total firing rate in 1.5 minutes if it is to recover steaming pressure and temperature before the next feedwater cycle. However since the boiler is already operating at 75% of firing capacity the addition of another 26.76% would mean that the boiler would have to fire at 101.76% to recover. It becomes obvious the boiler will not recover full horspower. Ø Fifth effect = Drum level will artificially rise about ½ to 1.0 inch due to the lowered steaming pressure resulting in a short cycling of the drum level control signal and shut the feed supply off ½ inch early. Ø Sixth effect = Once boiler drum pressure reaches operating pressure the water level will shrink by ½ to 1.0” due to the higher steaming pressure. It is obvious the mass/heat balance in the boiler has been upset and a great deal of energy must be expended to recover the upset and bring the process back into balance. 7
  • 8. Boiler Drum Level 01/02/01 Tech Paper #909 What Really Happens In actual operation the boiler simply fires at a higher firing rate trying to maintain boiler horsepower, wasting energy, until some semblance of mass/heat balance is made. And if the load is somewhat steady state the occurrences of priming, carryover or high/low water trips are generally tolerated as just a matter of how the system operates. Conversely if the boiler where to be mass/heat balanced matching pounds of water in with pounds of steam (water vapor) out, the result would be as follows: 12,900 PPH X 217 deg ‘F’ rise X 1 Hour =2,799,300 Btu/Hr or a 17.84 % steady state increase in firing rate to make up for the sub-cooled feed water. An energy savings of over 17% can readily be realized by moving from an ON/OFF feedwater system to a modulating feedwater system in this example. Plus the additional benefits of reducing priming, carryover, nuisance level trips and improved steam delivery. Of course once you have committed to a modulating feedwater system you can gain the benefits of pressurized and per-heated feedwater systems and economizers both of which, serve to reduce the amount of additional heat input required for sub-cooled feedwater. (See Improving Boiler Room Efficiencies, Economizers; D.Farthing) Example of the Effect of Feedwater Temperature on Boiler Performance Factory Design Boiler Type Watertube/Firetube W Name Plate Rated Boiler BHP 500 Normal Operating Pressure 225 Deaerator Typical Calculated BTU Input for boiler type 22,485,674.16 As Observed First Recovery Economizer Observed Feedwater Temp 212 180 225 262 Hours Day Operated 16 16 16 16 Days per Month 22 22 22 22 Calculated Bhp BTU Output Bhp 16,732,500.00 Calculated Efficiency (Input/Output) 74.41 Calculated Bhp 500.00 Rated Steam PPH at 100% Firing 17250 BTU addition for Operating Pressure 3,279,750 3,918,000 3,055,500 2,451,750 BTU Lost/Gained Per Hour 0.00 -552,000.00 224,250.00 862,500.00 Boiler HP Lost or Gained/ Hr. 0.00 (16.49) 6.70 25.77 Net Boiler Horsepower 500 484 507 526 Net Steam Output 17250.0 16680.9 17481.2 18139.2 Net Efficiency 74.41 71.96 75.41 78.25 Percent Increase/Decrease BHP 0.000% -3.299% 1.340% 5.155% 8
  • 9. Boiler Drum Level 01/02/01 Tech Paper #909 Boiler Level Control Strategies Modulating control of the water/steam interface level is normally addressed in one of three principal strategies, single-element, two-element or three-element control. The application of any one of these strategies depends on the specific boiler size (economics) and load variations (dynamics). Single-Element Control Single-Element control is perhaps the simplest strategy. In this system drum level is measured using a single measurement device and provides a control signal to the feedwater regulator in direct relation to the current operating drum level. This system is used in both ON/OFF and modulating feedwater control strategies. The single-element drum level strategy is only effective for smaller boilers with relatively steady demands and slow to very moderate load changes. This is because the shrink and swell effect causes an incorrect initial control reaction, which can lead to over/under filling of the drum. (See ON/OFF control example above.) As steam demand increases, there is an initial lowering of the drum pressure resulting in an artificial rise in drum level as the steam bubbles expand and swell the drum water level. This phenomenon sends a false control signal to reduce feedwater flow, when in fact the feedwater flow should be increasing to maintain mass balance. Conversely, on a loss of steam demand, there is an initial rising of steam drum pressure which acts to lower the drum level by compressing the steam bubbles and shrinking the drum water level. This sends a false signal to increase feedwater flow when in fact it should be decreasing to maintain mass balance. Drawing courtiousy of Honeywell Processes experienceing sudden or large load changes, can result in ‘phasing’ of the shrink and swell effect causing the water level controller to lose control of the drum level and result in nuisance low water trips or high water priming and carry-over. 9
  • 10. Boiler Drum Level 01/02/01 Tech Paper #909 Two-Element Control The two-element drum level strategy is suitable for processes with moderate load swings and speeds, and it can be used on any size of boiler. This system uses the two variables, drum level and steam flow to mass balance the feedwater demand. Drum level is measured and the error between the desired setpoint and the actual control point is sent to a math summer as one of two process variables. Steam flow is measured and added (summed) to the math summer as the second process variable. The result of the math summer is the control output to the feedwater control valve. Since steam flow is very dynamic, the result of this strategy is that it will sense the rise or fall in load demand before the drum level begins to change. The startegy then adds or subtracts control output to stabilize the reaction of the drum level controller on the feedwater control valve. And since steam flow is normally the larger variable it can easily over ride the trim effect of the drum level measurement on moderate load changes, insuring a correct response to the demand change. During steady load the drum level controller influences the feedwater control valve and acts to trim the level to the desired setpoint. Two-Element Control, drawing courtiousy of Honeywell This strategy has two drawbacks, which should be considered. First like the single element strategy the two-element control can not adjust for pressure or load disturbances in the feedwater supply, as this is not a measured variable in this strategy. And second the two-element control cannot eliminate phasing interaction between feedwater flow and drum level because only the relatively slow process of the drum level is controlled. This second issue can lead to sub-cooled drum water on a large increase in demand by allowing excessive feedwater to enter the drum without consideration to the boilers thermal dynamic capabilities. 10
  • 11. Boiler Drum Level 01/02/01 Tech Paper #909 Three-Element Drum Level Control To address the issues of phasing still present in the two-element control strategy, a third element, feedwater flow is added to the drum level control strategy. In this system the math summer output of the two-element controller is cascaded down to a second Feedwater Flow Controller to act as a Remote Setpoint. The feedwater controller is a fast acting flow controller, which uses feedwater flow as its process variable and steam flow as its setpoint. Thus for every pound of steam flow leaving the boiler a pound of feedwater is added. This loop has final control on the feedwater valve. As the remote setpoint from the two element level control changes with steam flow and drum level variations due to blowdown or other minor losses, the feedwater controller modulates its output to regulate the necessary feedwater flow to keep the drum level in a mass/heat balanced and level state. Independent tuning of each controller allows for very precise control of the drum level regardless of steam demand and feedwater influences. However it is very important to take the thermal dynamics of the boiler’s recovery rate into account when tuning the feedwater controller. If you fail to do this and set the controller reset too fast on the feedwater controller you may inadvertently sub-cool the drum and start a cyclic phasing action much like that found in a two-element system. Do the math it will save you a lot of heartache. Drawing courtiousy of Honeywell The three-element control strategy can easily handle large and rapid load changes because it is matching the mass balance between the steam flow from the boiler and the feedwater flow to it. This strategy is a must on multiple boilers sharing the same feedwater header and supply system, due to the variations in the available feedwater flow to any one boiler, while two or more boilers are on line. This is irrespective to boiler size. Additionally if the boilers are subjected to sudden or unpredictable demand changes such as in a batching process, this strategy is capable of matching these demands without operator trim corrections or supervision. 11
  • 12. Boiler Drum Level 01/02/01 Tech Paper #909 Conclusion As you can see from the examples we have evaluated, managing feedwater efficiently does have its practical benefits. 12
  • 13. Boiler Drum Level 01/02/01 Tech Paper #909 About the Author David C. Farthing Mr. Farthing combines his twenty-eight years of experience in thermal processes with a degree in General Engineering Technology from Oklahoma State University as well as a degree in Business from the University of Central Oklahoma. He is both a practitioner and academic in the field of boilers and thermal process control systems, as Sales Manager for Federal Corporation and adjunct instructor of ‘ oiler B Construction, Operations, and Maintenance’ for Oklahoma State University, Oklahoma City campus. Bibliography Frederick M. Steingress & Harold J. Frost, High Pressure Steam Boilers 2 nd edition, American Technical Publishers Honeywell Industrial Control and Automation Mark’s Engineering Handbook, 7th Edition David C. Farthing, <‘TechStuff’>, www.federalcorp.com Kewanee Boiler Manufacturing, Kewanee, Illinois Nebraska Boiler, Lincoln, Nebraska 13