work safety for RME

SAFETY WORK
for
RME
FRUMENCIO T. TAN
Accredited Safety Consultant
work safety for RME
work safety for RME
What Does an Electrician Do?
Reading blueprints
For safety, electricians follow the Philippine Electrical
Code (OSHS)
Connecting all types of wires and circuit breakers,
outlets, and a host of other components
Regular assessments of electrical equipment and
electrical systems
Work involves adding and replacing wires, fuses, circuit
breakers, connections
Test electrical devices
Electricity - The Dangers
Causes 12% of
young worker
workplace deaths
Takes very little
electricity to cause
harm
Significant risk of
causing fires
work safety for RME
Accident Description
October 11, 2004
SLAC Supervisor directs subcontractor electrician to
install breaker in live 480 volt dist. panel.
Supervisor did not obtain required working “EEW”
permit.
The electrician wore a short sleeved cotton/polyester
shirt, leather gloves over Voltage (V) rated gloves, safety
glasses, and a hardhat.
When the accident occurred, the electrician had
connected phases B and C and was in the process of
connecting phase A.
work safety for RME
work safety for RME
work safety for RME
work safety for RME
work safety for RME
work safety for RME
work safety for RME
work safety for RME
Identified Key Deficiencies
A Pre Work Hazards Analysis form was not completed
There was no approved Energized Electrical Work Permit
No one in the SLAC management chain had been informed of the
decision by the supervisor to install the circuit breaker in an
energized panel
The workers did not wear the appropriate flame resistant clothing,
and all required PPE
The SLAC safety officials were not involved
The subcontractor laborer was not trained to be a backup for the
electrician
Full Revolution Press Machine
Safety Device: Two-Hand Position Switch
Point of Operation
(Switches Connected in Series)
Substandard Condition:
• By-passed safety device
(2-hand switch)
Substandard Act:
•Failed to LO/TO
•Tampering with safety
device
Foot switch
Ram Movement
work safety for RME
Electrical Injuries
There are four main types of electrical
injuries:
Direct:
Electrocution or death due to electrical
shock
Electrical shock
Burns
Indirect - Falls
Burns
Most common shock-
related injury
Occurs when you touch
electrical wiring or
equipment that is
improperly used or
maintained
Typically occurs on hands
Very serious injury that
needs immediate attention
Electrical Burns
Entrance Wound
Exit Wound
Arc or Flash Burns Thermal Contact Burns
Internal/External Injuries
Involuntary Muscle
Contraction
Current flows through the body from the entrance point,
until finally exiting where the body is closest to the ground.
Worst case of electrical-related accident!
work safety for RME
AVOID THE FOLLOWING UNSAFE ACTS:
Worker’s attitude such as working
without appropriate PPEs.
Improper working method
Wearing of metal objects as
watches, necklaces & rings.
Working in wet and/or damp
locations
AVOID THE FOLLOWING UNSAFE ACTS:
AVOID THE FOLLOWING UNSAFE ACTS:
AVOID THE FOLLOWING UNSAFE ACTS:
Failure to de-energize, lockout and
tagout hazards during maintenance,
repair or inspections of fuse box.
Use of defective and unsafe tools.
Use of tools or equipment too close to
energized parts.
Not draining off stored energy in
capacitors.
work safety for RME
work safety for RME
Double Insulated Tool
AVOID THE FOLLOWING UNSAFE ACTS:
Using 3 wire cord with a 2 wire plug.
Remove and replace wrong fuse.
Not verifying power is off when making
repair.
UNSAFE EQUIPMENT
What equipment can cause electrical accidents:
Faults in facilities such as exposed
charged part of electrical machines and
equipment
Damaged insulation of electrical wirings
Short Circuit
Overloading
Improper grounding
ELECTRICAL HAZARDS TO WATCH OUT FOR
Loose electrical connections
Cord with frayed insulations
Plugs that do not match their outlets,
e.g., 3-prong male plug to 2-plug
female outlet
Non-waterproof cords, plugs and outlets
used outdoors
Equipment running over capacity
Deteriorated cords, where the exterior
insulation has cracked, exposing the wires
inside.
Cords and/ or plugs produced from
substandard materials.
Use of cords which have no appropriate
current (amp) rating for either the plug or the
equipment.
ELECTRICAL HAZARDS TO WATCH OUT FOR
Electrical Plugs and Extension Cords
Electrical Plugs and Extension Cords
MEASURES TO PREVENT ELECTRIC SHOCK
Use grounding system
Install GFCI
Isolation of electrical conductors
Vault & boxes
Warning signs
Safe Clearance
Elevation (at least 10ft/ 3m
minimum) of electrical cable
specifically at construction site
Minimum approach distance
Contact with Power Lines
Overhead and buried power lines at a
construction site are especially hazardous
because they carry extremely high voltage. Fatal
electrocution is the main risk, but burns and falls
from elevation are also hazards. Using tools and
equipment that can contact power lines increases
the risk.
Examples of equipment that can contact power
lines:
Backhoes
Concrete pumpers
Cranes
Long-handled cement finishing floats
Metal building materials
Metal ladders
Raised dump truck beds
Scaffolds
Overhead power lines are
un-insulated and can carry
tens of thousands of volts,
making them extremely
dangerous to employees
who work in their vicinity.
Contact with Power Lines continued…
How Do I Avoid Hazards?
Look for overhead power lines and buried
power line indicators. Post warning signs.
Contact utilities for buried power line
locations.
Stay at least 10 feet away from overhead
power lines. Unless you know otherwise,
assume that overhead lines are energized.
De-energize and ground lines when working
near them. Other protective measures
include guarding or insulating the lines.
Use non-conductive wood or fiberglass
ladders when working near power lines.
Deaths Due to Contact With Power Lines
Scaffold too close to power line
Eight employees of a masonry company were erecting a brick wall from a
tubular, welded-frame scaffold approximately 24 feet high. The scaffold
had been constructed only 21 horizontal inches across from a 7,620-volt
power line. A laborer carried a piece of wire reinforcement (10 feet long
by 8 inches wide) along the top section of the scaffold and contacted the
power line with it. The laborer, who was wearing leather gloves, received
an electric shock and dropped the wire reinforcement, which fell across
the power line and simultaneously contacted the metal rail of the scaffold,
energizing the entire scaffold. All the workers standing on the work
platform in contact with the main scaffold were electrocuted.
Source: OSHA
Fatality – metal gutter touches power line – from WorkSafe BC
work safety for RME
PREVENTIVE MEASURE ON ELECTRIC
SHOCK
Insulation
Use double-insulated royal cord for
tools
Insure insulation between feet and
moist ground
Use Lock-Out and Tag-Out
training and instruction
knowledge of the risks involved
Ground Fault Circuit Interrupters
Portable Ground Fault
Circuit Interrupters
GFCI Panel Mounts
Ground Fault Circuit Interrupters
Electrical insulating rubber shielding
is engineered to protect personnel,
equipment, and work areas from
electrical hazards up to 7,500 volts.
The shielding is flame, oil, ozone, and
puncture resistant, remains flexible to
-60° F, and will not melt. CIP's
insulating shielding is available in
convenient "safety yellow" rolls, and
is 100% tested to meet ASTM
standards.
Type 2 Insulating - Flame, Oil, and
Ozone Resistant
ASTM Standard F2320-03
Electrical Insulating Protective Shielding
Preventing Electrical Hazards - PPE
Switchboard Corrugated Matting
ASTM D178-01 Type I Insulating - Non-
Oil Resistant
Switchboard matting is rubber matting
designed for electrical insulation, as a floor
covering to prevent shock around high
voltage electrical apparatus, fuse boxes,
switchgear, control panels, and heavy
machinery. It meets and exceeds current
ASTM, ANSI, (Plus IEC Division of ANSI,
Tech. Committee-78) specifications for this
material. In addition, OSHA requirement's
intent to eliminate the electrical hazards of
high voltage shock in the workplace is
abundantly clear. CIP switchboard matting
is designed specifically for this purpose. It
is not designed to be used as a "Hot" Rail
Blanket. Also, matting with punctures or
cracks should not be placed in service.
Insulated Hand Tools
Gloves and SleevesComposite Tools
Tool Sets and Kits
Hot Stick Arc Rated Harness Grounding Sets
Safety Rescue Hook Voltage Detector Kits
Non-contact, wide
range of detection, 80
V to 275 kV, audible
and visual indication
275 kV automatic self-
test beep every two
seconds
Dielectric Deep Heel Overshoes provide extra
safety when climbing ladders and poles
where the deep heel cavity can lock onto the
rungs. These boots and overshoes are made
from an ozone resistant yellow rubber that's
100% waterproof. The construction is hand-
layered in full-cut patterns to fit over work
boots. The fabric lining makes them easy to
get on and off. The sole is an anti-skid bar
tread. All of these overshoes meet ANSI Z41
requirements and have been tested to 20,000
volts.
The 17" Super Dielectric Boot offers a high
level of protection from electrical shock to
utility workers, electric contractors, and
others working dangerously close to
electrical hazards. These boots meet ASTM
F1117 requirements, and have been tested to
15,000 volts AC and 45,000 volts DC. The
boots are completely waterproof and resistant
to ozone. The tough fabric lining makes the fit
comfortable and easy to take on and off.
Dielectric Boots
SIMPLE RULES TO FOLLOW
DO NOT GUESS
FOLLOW PEC
USE PROPER INSTRUMENTS
ALWAYS USE SAFETY DEVICES
LOCKING & TAGGING PROCEDURE
EEW PERMIT
ARC FLASH ANALYSIS
JHA
NEVER WORK ALONE
USE DANGER SIGNS
Final Advice
Treat electricity with
the respect it demands,
and it will serve you
efficiently and effectively
work safety for RME
THANK YOU ALL!
1 de 57

Recomendados

Electrical safetyElectrical safety
Electrical safetyHazem Al-Muallem
36K vistas27 diapositivas
Electrical HazaradElectrical Hazarad
Electrical HazaradBINAYAK SWAIN
2.2K vistas74 diapositivas
Electrical safety slideshareElectrical safety slideshare
Electrical safety slideshareYokeshDhanabal
3.2K vistas63 diapositivas
Electrical safetyElectrical safety
Electrical safetyprabakaran G
916 vistas43 diapositivas
Electrical safetyElectrical safety
Electrical safetyDabbroto Binoy Bhadra
805 vistas10 diapositivas
Electrical safetyElectrical safety
Electrical safetyPrem kumar
498 vistas16 diapositivas

Más contenido relacionado

La actualidad más candente(20)

Electrical safetyElectrical safety
Electrical safety
Manish Bharadwaj1.8K vistas
Electrical Safety by OSHAElectrical Safety by OSHA
Electrical Safety by OSHA
Atlantic Training, LLC.1.2K vistas
Electrical power point SlideElectrical power point Slide
Electrical power point Slide
Syed Neyaz Ahmad87 vistas
Appliance Test and Tag Part 1Appliance Test and Tag Part 1
Appliance Test and Tag Part 1
ACME Test & Tagging Pty Ltd922 vistas
Electrical hazardousElectrical hazardous
Electrical hazardous
Dashne DM1.9K vistas
Construction Electrical SafetyConstruction Electrical Safety
Construction Electrical Safety
دكتور تامر عبدالله شراكى320 vistas
Safety Practices and Requirements Electrical Arc Flash Hazard ProtectionSafety Practices and Requirements Electrical Arc Flash Hazard Protection
Safety Practices and Requirements Electrical Arc Flash Hazard Protection
دكتور تامر عبدالله شراكى747 vistas
Arc Blast FlashArc Blast Flash
Arc Blast Flash
jboullemet4.3K vistas
Fire and electrical hazardsFire and electrical hazards
Fire and electrical hazards
Reshma Fathima .K10.8K vistas
Electrical Safety29 CFR 1910.332Electrical Safety29 CFR 1910.332
Electrical Safety 29 CFR 1910.332
دكتور تامر عبدالله شراكى550 vistas
English module electrical hazardsEnglish module electrical hazards
English module electrical hazards
Awais Tahir360 vistas
Arc flash guidebookArc flash guidebook
Arc flash guidebook
دكتور تامر عبدالله شراكى1.3K vistas
Electrical Safety Training by Georgia TechElectrical Safety Training by Georgia Tech
Electrical Safety Training by Georgia Tech
Atlantic Training, LLC.12.1K vistas
How to control electrical safety riskHow to control electrical safety risk
How to control electrical safety risk
Verde Ventures Pvt. Ltd.2.3K vistas
NFPA 70E Training By SASCONFPA 70E Training By SASCO
NFPA 70E Training By SASCO
Atlantic Training, LLC.3K vistas

Similar a work safety for RME

Electrical SafetyElectrical Safety
Electrical SafetyTristan Hart
188 vistas26 diapositivas

Similar a work safety for RME(20)

ELECTRICAL SAFETY PRESENTATION.pptELECTRICAL SAFETY PRESENTATION.ppt
ELECTRICAL SAFETY PRESENTATION.ppt
VIDHYUTtech111 vistas
Electrical SafetyElectrical Safety
Electrical Safety
Tristan Hart188 vistas
ELECTRICAL SAFETY AWARENES.pdfELECTRICAL SAFETY AWARENES.pdf
ELECTRICAL SAFETY AWARENES.pdf
JansenSunga36 vistas
Lab # 01 Workshop Practice.pptxLab # 01 Workshop Practice.pptx
Lab # 01 Workshop Practice.pptx
TALHA RIAZ PERSOTA39 vistas
Electrical Hazards and their safetyElectrical Hazards and their safety
Electrical Hazards and their safety
Moxit Khandhar39.3K vistas
Basic Electrical Safety by TECBasic Electrical Safety by TEC
Basic Electrical Safety by TEC
Atlantic Training, LLC.6.8K vistas
Electrical Workplace SafetyElectrical Workplace Safety
Electrical Workplace Safety
RickCKnight20.3K vistas
electrical safetyelectrical safety
electrical safety
Piyushjauhari3102 vistas
Electrical Safety.pptElectrical Safety.ppt
Electrical Safety.ppt
IsmaelABautista62 vistas
beeeppt.pptxbeeeppt.pptx
beeeppt.pptx
AsthaChaurasia45 vistas
Electrical Safety by OSHAElectrical Safety by OSHA
Electrical Safety by OSHA
Atlantic Training, LLC.6.6K vistas
Electrical Safety and Risk AssessmentsElectrical Safety and Risk Assessments
Electrical Safety and Risk Assessments
Mohd Azmatullah12.8K vistas
Electrical 2Electrical 2
Electrical 2
FFSafety4.3K vistas
Electrical2Electrical2
Electrical2
cainacinacniacnian1.3K vistas
Electrical safetyElectrical safety
Electrical safety
Christopher Maahs288 vistas
Electrical hazards & safety trainingElectrical hazards & safety training
Electrical hazards & safety training
SYED HAIDER ABBAS26.8K vistas

Último(20)

Investor PresentationInvestor Presentation
Investor Presentation
eser sevinç10 vistas
SWM L1-L14_drhasan (Part 1).pdfSWM L1-L14_drhasan (Part 1).pdf
SWM L1-L14_drhasan (Part 1).pdf
MahmudHasan74787038 vistas
CHI-SQUARE ( χ2) TESTS.pptxCHI-SQUARE ( χ2) TESTS.pptx
CHI-SQUARE ( χ2) TESTS.pptx
ssusera597c511 vistas
Wire RopeWire Rope
Wire Rope
Iwiss Tools Co.,Ltd8 vistas
FLOW IN PIPES NOTES.pdfFLOW IN PIPES NOTES.pdf
FLOW IN PIPES NOTES.pdf
Dearest Arhelo82 vistas
Paper 3.pdfPaper 3.pdf
Paper 3.pdf
Javad Kadkhodapour6 vistas
Activated sludge process .pdfActivated sludge process .pdf
Activated sludge process .pdf
8832RafiyaAltaf6 vistas
SNMPxSNMPx
SNMPx
Amatullahbutt10 vistas
performance uploading.pptxperformance uploading.pptx
performance uploading.pptx
SanthiS107 vistas
Codes and Conventions.pptxCodes and Conventions.pptx
Codes and Conventions.pptx
IsabellaGraceAnkers5 vistas
Electrical CrimpingElectrical Crimping
Electrical Crimping
Iwiss Tools Co.,Ltd18 vistas
Wire Cutting & StrippingWire Cutting & Stripping
Wire Cutting & Stripping
Iwiss Tools Co.,Ltd6 vistas
Solar PVSolar PV
Solar PV
Iwiss Tools Co.,Ltd10 vistas
Sanitary Landfill- SWM.pptxSanitary Landfill- SWM.pptx
Sanitary Landfill- SWM.pptx
Vinod Nejkar5 vistas

work safety for RME

  • 1. SAFETY WORK for RME FRUMENCIO T. TAN Accredited Safety Consultant
  • 4. What Does an Electrician Do? Reading blueprints For safety, electricians follow the Philippine Electrical Code (OSHS) Connecting all types of wires and circuit breakers, outlets, and a host of other components Regular assessments of electrical equipment and electrical systems Work involves adding and replacing wires, fuses, circuit breakers, connections Test electrical devices
  • 5. Electricity - The Dangers Causes 12% of young worker workplace deaths Takes very little electricity to cause harm Significant risk of causing fires
  • 7. Accident Description October 11, 2004 SLAC Supervisor directs subcontractor electrician to install breaker in live 480 volt dist. panel. Supervisor did not obtain required working “EEW” permit. The electrician wore a short sleeved cotton/polyester shirt, leather gloves over Voltage (V) rated gloves, safety glasses, and a hardhat. When the accident occurred, the electrician had connected phases B and C and was in the process of connecting phase A.
  • 16. Identified Key Deficiencies A Pre Work Hazards Analysis form was not completed There was no approved Energized Electrical Work Permit No one in the SLAC management chain had been informed of the decision by the supervisor to install the circuit breaker in an energized panel The workers did not wear the appropriate flame resistant clothing, and all required PPE The SLAC safety officials were not involved The subcontractor laborer was not trained to be a backup for the electrician
  • 17. Full Revolution Press Machine Safety Device: Two-Hand Position Switch Point of Operation (Switches Connected in Series) Substandard Condition: • By-passed safety device (2-hand switch) Substandard Act: •Failed to LO/TO •Tampering with safety device Foot switch Ram Movement
  • 19. Electrical Injuries There are four main types of electrical injuries: Direct: Electrocution or death due to electrical shock Electrical shock Burns Indirect - Falls
  • 20. Burns Most common shock- related injury Occurs when you touch electrical wiring or equipment that is improperly used or maintained Typically occurs on hands Very serious injury that needs immediate attention
  • 22. Arc or Flash Burns Thermal Contact Burns
  • 25. Current flows through the body from the entrance point, until finally exiting where the body is closest to the ground.
  • 26. Worst case of electrical-related accident!
  • 28. AVOID THE FOLLOWING UNSAFE ACTS: Worker’s attitude such as working without appropriate PPEs. Improper working method Wearing of metal objects as watches, necklaces & rings. Working in wet and/or damp locations
  • 29. AVOID THE FOLLOWING UNSAFE ACTS:
  • 30. AVOID THE FOLLOWING UNSAFE ACTS:
  • 31. AVOID THE FOLLOWING UNSAFE ACTS: Failure to de-energize, lockout and tagout hazards during maintenance, repair or inspections of fuse box. Use of defective and unsafe tools. Use of tools or equipment too close to energized parts. Not draining off stored energy in capacitors.
  • 35. AVOID THE FOLLOWING UNSAFE ACTS: Using 3 wire cord with a 2 wire plug. Remove and replace wrong fuse. Not verifying power is off when making repair.
  • 36. UNSAFE EQUIPMENT What equipment can cause electrical accidents: Faults in facilities such as exposed charged part of electrical machines and equipment Damaged insulation of electrical wirings Short Circuit Overloading Improper grounding
  • 37. ELECTRICAL HAZARDS TO WATCH OUT FOR Loose electrical connections Cord with frayed insulations Plugs that do not match their outlets, e.g., 3-prong male plug to 2-plug female outlet Non-waterproof cords, plugs and outlets used outdoors Equipment running over capacity
  • 38. Deteriorated cords, where the exterior insulation has cracked, exposing the wires inside. Cords and/ or plugs produced from substandard materials. Use of cords which have no appropriate current (amp) rating for either the plug or the equipment. ELECTRICAL HAZARDS TO WATCH OUT FOR
  • 39. Electrical Plugs and Extension Cords
  • 40. Electrical Plugs and Extension Cords
  • 41. MEASURES TO PREVENT ELECTRIC SHOCK Use grounding system Install GFCI Isolation of electrical conductors Vault & boxes Warning signs Safe Clearance Elevation (at least 10ft/ 3m minimum) of electrical cable specifically at construction site Minimum approach distance
  • 42. Contact with Power Lines Overhead and buried power lines at a construction site are especially hazardous because they carry extremely high voltage. Fatal electrocution is the main risk, but burns and falls from elevation are also hazards. Using tools and equipment that can contact power lines increases the risk. Examples of equipment that can contact power lines: Backhoes Concrete pumpers Cranes Long-handled cement finishing floats Metal building materials Metal ladders Raised dump truck beds Scaffolds Overhead power lines are un-insulated and can carry tens of thousands of volts, making them extremely dangerous to employees who work in their vicinity.
  • 43. Contact with Power Lines continued… How Do I Avoid Hazards? Look for overhead power lines and buried power line indicators. Post warning signs. Contact utilities for buried power line locations. Stay at least 10 feet away from overhead power lines. Unless you know otherwise, assume that overhead lines are energized. De-energize and ground lines when working near them. Other protective measures include guarding or insulating the lines. Use non-conductive wood or fiberglass ladders when working near power lines.
  • 44. Deaths Due to Contact With Power Lines Scaffold too close to power line Eight employees of a masonry company were erecting a brick wall from a tubular, welded-frame scaffold approximately 24 feet high. The scaffold had been constructed only 21 horizontal inches across from a 7,620-volt power line. A laborer carried a piece of wire reinforcement (10 feet long by 8 inches wide) along the top section of the scaffold and contacted the power line with it. The laborer, who was wearing leather gloves, received an electric shock and dropped the wire reinforcement, which fell across the power line and simultaneously contacted the metal rail of the scaffold, energizing the entire scaffold. All the workers standing on the work platform in contact with the main scaffold were electrocuted. Source: OSHA Fatality – metal gutter touches power line – from WorkSafe BC
  • 46. PREVENTIVE MEASURE ON ELECTRIC SHOCK Insulation Use double-insulated royal cord for tools Insure insulation between feet and moist ground Use Lock-Out and Tag-Out training and instruction knowledge of the risks involved
  • 47. Ground Fault Circuit Interrupters Portable Ground Fault Circuit Interrupters GFCI Panel Mounts
  • 48. Ground Fault Circuit Interrupters
  • 49. Electrical insulating rubber shielding is engineered to protect personnel, equipment, and work areas from electrical hazards up to 7,500 volts. The shielding is flame, oil, ozone, and puncture resistant, remains flexible to -60° F, and will not melt. CIP's insulating shielding is available in convenient "safety yellow" rolls, and is 100% tested to meet ASTM standards. Type 2 Insulating - Flame, Oil, and Ozone Resistant ASTM Standard F2320-03 Electrical Insulating Protective Shielding Preventing Electrical Hazards - PPE
  • 50. Switchboard Corrugated Matting ASTM D178-01 Type I Insulating - Non- Oil Resistant Switchboard matting is rubber matting designed for electrical insulation, as a floor covering to prevent shock around high voltage electrical apparatus, fuse boxes, switchgear, control panels, and heavy machinery. It meets and exceeds current ASTM, ANSI, (Plus IEC Division of ANSI, Tech. Committee-78) specifications for this material. In addition, OSHA requirement's intent to eliminate the electrical hazards of high voltage shock in the workplace is abundantly clear. CIP switchboard matting is designed specifically for this purpose. It is not designed to be used as a "Hot" Rail Blanket. Also, matting with punctures or cracks should not be placed in service.
  • 51. Insulated Hand Tools Gloves and SleevesComposite Tools Tool Sets and Kits
  • 52. Hot Stick Arc Rated Harness Grounding Sets Safety Rescue Hook Voltage Detector Kits Non-contact, wide range of detection, 80 V to 275 kV, audible and visual indication 275 kV automatic self- test beep every two seconds
  • 53. Dielectric Deep Heel Overshoes provide extra safety when climbing ladders and poles where the deep heel cavity can lock onto the rungs. These boots and overshoes are made from an ozone resistant yellow rubber that's 100% waterproof. The construction is hand- layered in full-cut patterns to fit over work boots. The fabric lining makes them easy to get on and off. The sole is an anti-skid bar tread. All of these overshoes meet ANSI Z41 requirements and have been tested to 20,000 volts. The 17" Super Dielectric Boot offers a high level of protection from electrical shock to utility workers, electric contractors, and others working dangerously close to electrical hazards. These boots meet ASTM F1117 requirements, and have been tested to 15,000 volts AC and 45,000 volts DC. The boots are completely waterproof and resistant to ozone. The tough fabric lining makes the fit comfortable and easy to take on and off. Dielectric Boots
  • 54. SIMPLE RULES TO FOLLOW DO NOT GUESS FOLLOW PEC USE PROPER INSTRUMENTS ALWAYS USE SAFETY DEVICES LOCKING & TAGGING PROCEDURE EEW PERMIT ARC FLASH ANALYSIS JHA NEVER WORK ALONE USE DANGER SIGNS
  • 55. Final Advice Treat electricity with the respect it demands, and it will serve you efficiently and effectively