MPFIM4
www.meba.net
Residual Current
Circuit Breaker
128
MPFIM4 Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: MPFIM4
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
Specification:
MPFIM4, Residual CurrentDevices for earthleakage detection. It is tobe used in association with miniaturecircuit breakers, itsfunction
is to detectearth leakage currentand open the connected circuit to protect people and equipment, major usedin industrial app lication.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Technical parameter:
Electromagnetic and Electronic type
35mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(In): 30, 100, 300, 500mA
Rated residual non-operating current(Ino): 0.5 In
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
Dimensions:
77 0.8
35.60.3
44.5
66
5.5
45
830.8
35.5 0.3
72
66.30.3
36
CF-362 Residual Current Circuit Breaker
www.meba.net
Residual Current
Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: CF-362
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
Specification:
CF-362, Residual CurrentDevices for earthleakage detection. Itis to beused in associationwith miniature circuitbreakers, its function
is todetect earth leakage current and open theconnected circuit to protect people andequipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Technical parameter:
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
CF-364 Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: CF-364
Type: Residual Current Circuit Breaker or Residual Current Device)
Poles Number: 4P
Specification:
CF-364, Residual CurrentDevices for earthleakage detection. Itis to beused in associationwith miniature circuitbreakers, its function
is to detect earth leakage currentand open theconnected circuit toprotect people andequipment , major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Technical parameter:
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
CF-362 CF-364
129
www.meba.net
Specification:
Technical parameter:
Specification:
Technical parameter:
Residual Current
Circuit Breaker
CF-462 Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: CF-462
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
CF-462, Residual CurrentDevices for earthleakage detection. It is to beused in associationwith miniature circuitbreakers, its function
is to detect earth leakage curre nt and open the connected circuit to protect peopleand equipment, majorused in industrialapplication.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
CF-464 Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: CF-464
Type: Residual Current Circuit Breaker or Residual Current Device)
Poles Number: 4P
CF-464, Residual CurrentDevices for earthleakage detection. Itis to beused in associationwith miniature circuitbreakers, its function
is to detect earth leakage current andopen the connectedcircuit to protectpeople and equipment, major used in industri al application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
CF-462 CF-464
130
www.meba.net
Residual Current
Circuit Breaker
DZ30L-32 Residual Current Circuit Breaker
Specification:
Technical parameter:
Residual current circuit breaker with overload protection(RCBO)
Brand Name: Meba
Model Number: DZ30L-32
Type: Residual current circuit breaker with overload protection(RCBO)
Poles Number: DPN
DZ30L-32(DPN), combination by mini circuit breaker and leakage. Which protect human from the fault of electric because of over-
current, short circuit, earth fault current. It is self-protecting up to a maximum short-circuit current 63A. All breakingcapacities comply
with Standard IEC/EN 61009.
Residual current device with overcurrent protection
Combine in residual current device function and MCB over-current protection function
Short circuit capacity: 3KA
Rated current(A): 6, 16, 20, 25, 32A
Rated leakage operating current(mA): 30, 100, 300mA
AC types, B-C characteristic
Modular Din Rail products 35mm.
DZ47LE-63-2P Residual Current Circuit Breaker
Specification:
Technical parameter:
Residual current circuit breaker with overload protection(RCBO)
Brand Name: Meba
Model Number: DZ47LE-63
Type: Residual current circuit breaker with overload protection(RCBO)
Poles Number: 2 pole MCB + ELCB
DZ47LE-63 2Pole, combination by mini circuit breaker and leakage. Which protect human from the fault of electric because of over-
current, short circuit, earth fault current. It is self-protecting up toa maximum short-circuit current 63A. All breaking capacitiescomply
with Standard IEC/EN 61009.
Residual current device with overcurrent protection
Combine in residual current device function and MCB over-current protection function
Short circuit capacity: 6KA
Rated current(A): 6,16,20,25,32,40,50,63A
Rated leakage operating current(mA): 30,100,300mA
AC types, B-C characteristic
Modular Din Rail products 35mm.
131
DZ30L-32 DZ47LE-63-2P
M
www.meba.net
Specification:
Technical parameter:
Residual Current
Circuit Breaker
DZ47LE-63-4P Residual Current Circuit Breaker
Residual current circuit breaker with overload protection(RCBO)
Brand Name: Meba
Model Number: DZ47LE-63
Type: Residual current circuit breaker with overload protection(RCBO)
Poles Number: 4 pole MCB + ELCB
DZ47LE-63 4Pole, combination by mini circuit breaker and leakage. Which protect human from the fault of electric because of over-
current, short circuit, earth fault current. It is self-protecting up to a maximum short-circuit current 63A. All breakingcapacities comply
with Standard IEC/EN 61009.
Residual current device with overcurrent protection
Combine in residual current device function and MCB over-current protection function
Short circuit capacity: 6KA
Rated current(A): 6, 16, 20, 25, 32, 40, 50, 63A
Rated leakage operating current(mA): 30, 100, 300mA
AC types, B-C characteristic
Modular Din Rail products 35mm.
132
DZ47LE-63-4P
M Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: M
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
Specification:
M series Residual Cur rent Devices for earth leakage detection. Itis to beused in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(In): 30, 100, 300, 500mA
Technical parameter:
Rated residual non-operating current(Ino): 0.5 In
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
www.meba.net
Residual Current
Circuit Breaker
133
MB089/MB090 Residual Current Circuit Breaker
Applications:
Specification:
Standard
Rated voltage(Un)
Rated current(In)
Rated residual operating current(In)
Rated residual non-operating current(I no)
Breaking capacity(A)
Residual current off-time
Operating temperature
IEC61008-1
1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC
10, 16, 20, 25, 32, 40A
30, 100, 300, 500mA
0.5ls n
6000A
0.1s
-5 +55
Dimensions:
O. OFF
94
35.6
O. OFF
71.2
61.5
76
45
83
MB089/ MB090 4P RCD provide the function of isolation switchingand earth leakageprotection of electricalcircuits. They open a circuit
automatically in the event of an earth fault between phase and earth and/or netural and earth. A wide range of current ratings and
sensitivities are available. Suitable for domestic, commercial and industrial applications.
MB089 MB090
www.meba.net
Residual Current
Circuit Breaker
134
MB7L2-63 Residual Current Circuit Breaker
Applications:
MB7L2-63 RCCB provide the function of isolation switching and earth leakage protection of electrical circuits. They open a circuit
automatically in the event of an earth fault between phase and earth and/or netural and earth. Awide range of current ratings and
sensitivities are available. Suitable for domestic, commercial and industrial applications.
Specification:
Standard
Rated voltage(Un)
Rated current(In)
Rated residual operating current(In)
Rated residual non-operating current(I no)
Breaking capacity(A)
Residual current off-time
Operating temperature
IEC61008-1
1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC
10, 16, 20, 25, 32, 40A, 50A, 63A
30, 100, 300, 500mA
0.5ls n
6000A
0.1s
-5 +55
MB7L4-63 Residual Current Circuit Breaker
Applications:
Specification:
Standard
Rated voltage(Un)
Rated current(In)
Rated residual operating current(In)
Rated residual non-operating current(I no)
Breaking capacity(A)
Residual current off-time
Operating temperature
IEC61008-1
1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC
10, 16, 20, 25, 32, 40A, 50A, 63A
30, 100, 300, 500mA
0.5ls n
6000A
0.1s
-5 +55
MB7L4-63 RCCB provide the function of isolation switching and earth leakage protection of electrical circuits. They open a circuit
automatically in the event of an earth fault between phase and earth and/or netural and earth. A wide range of current ratings and
sensitivities are available. Suitable for domestic, commercial and industrial applications.
MB7L2-63 MB7L4-63
MBB8LE-63-1P
www.meba.net
Residual Current
Circuit Breaker
135
Applications:
Specification:
Standard
Rated voltage(Un)
Rated current(In)
Rated residual operating current(In)
Rated residual non-operating current(I no)
Breaking capacity(A)
Residual current off-time
Operating temperature
IEC61008-1
1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC
10, 16, 20, 25, 32, 40A
30, 100, 300, 500mA
0.5ls n
6000A
0.1s
-5 +55
MBACH2 Residual Current Circuit Breaker
MBACH2RCCBprovidethe function ofisolation switching andearth leakage protectionof electrical circuits.Theyopena circuit automatically
in the event of an earth fault between phase and earth and/or neutral and earth. A wide range of current ratings and sensitivities are
available. Suitable for domestic, commercial and industrial applications.
Specification:
Technical parameter:
MBB8LE-63-1P Residual Current Circuit Breaker
Residual current circuit breaker with overload protection(RCBO)
Brand Name: Meba
Model Number: MBB8LE-63
Type: Residual current circuit breaker with overload protection(RCBO)
Poles Number: 1 pole MCB + ELCB
MBB8LE-63 1Pole, combination by mini circuit breaker and leakage. Which protect human from the fault of electric because of over-
current, short circuit, earth fault current. It isself-protecting up to a maximum short-circuit current 63A. All breaking capacities comply
with Standard IEC/EN 61009.
Residual current device with overcurrent protection
Combine in residual current device function and MCB over-current protection function
Short circuit capacity: 6KA
Rated current(A): 6, 16, 20, 25, 32, 40, 50, 63A
Rated leakage operating current(mA): 30, 100, 300mA
AC types, B-C characteristic
Modular Din Rail products 35mm.
MBACH2
www.meba.net
Residual Current
Circuit Breaker
136
MBEA-63A Residual Current Circuit Breaker
Applications:
Specification:
Standard
Rated voltage(Un)
Rated current(In)
Rated residual operating current(In)
Rated residual non-operating current(I no)
Breaking capacity(A)
Residual current off-time
Operating temperature
IEC61008-1
1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC
10, 16, 20, 25, 32, 40A, 50A, 63A
30, 100, 300, 500mA
0.5ls n
6000A
0.1s
-5 +55
MBEA-63A RCCB provide the function of isolation switching and earth leakage protection of electrical circuits. They open a circuit
automatically in the event of an earth fault be tween phase and earth and/or neutral and earth. A wide range of current ratings and
sensitivities are available. Suitable for domestic, commercial and industrial applications.
MBB8LE-63-2P Residual Current Circuit Breaker
Residual current circuit breaker with overload protection(RCBO)
Brand Name: Meba
Model Number: MBB8LE-63
Type: Residual current circuit breaker with overload protection(RCBO)
Poles Number: 2 pole MCB + ELCB
Specification:
MBB8LE-63 2Pole, combination by mini circuit breaker and leakage. Which protect humanfrom the fault of electric because of over-
current, short circuit, earth fault current. It is self-protecting up to a maximum short-circuit current 63A. All breakingcapacities comply
with Standard IEC/EN 61009.
Technical parameter:
Residual current device with overcurrent protection
Combine in residual current device function and MCB over-current protection function
Short circuit capacity: 6KA
Rated current(A): 6, 16, 20, 25, 32, 40, 50, 63A
Rated leakage operating current(mA): 30, 100, 300mA
AC types, B-C characteristic
Modular Din Rail products 35mm.
MBB8LE-63-2P MBEA-63A
www.meba.net
Residual Current
Circuit Breaker
Applications:
MBEFI-2/MBEFI-4 Residual Current Circuit Breaker
Residual current circuitbreakers MBEFI areused for protectionagainst indirect touching of parts under voltage, for prevention of lasting
voltage on earthed par ts which should appear because of a defectin the electricalinstallation and for protection against direct conta cts
of parts under voltage in case of I n 30mA. Residual current circuit breakers can beused in TN-S, TN-C, TT and ITnetwork systems
or with other words in all systems where neutral and protective conductor are separated (VDE 0100 Teil 410).
Types - Our programme comprises residual current circuit breakers which are sensitive to alternating residu al current (AC-type) and
residual current circuit breakers which are sensitive to alternating and pulsating direct current (A-type).
For alternating residual current
For alternating and pulsating direct residual current
Short-circuit capacity with back-up fuse
lower temperature limit of application -25 C
VDE 0664, part 1 (up to 80 A)
Selective (time delayed min. 40 ms)
Short time delayed (min. 10 ms)
type A type AC type G type A type AC type S type G
MBEFI2 MBEFI4
MBEFI-2 Specification:
16
25
40
63
80
100
16
25
40
63
80
100
16
25
40
63
80
100
16
25
40
63
80
0,03
0,03
0,03
0,03
0,03
0,03
0,1
0,1
0,1
0,1
0,1
0,1
0,3
0,3
0,3
0,3
0,3
0,3
0.5
0,5
0,5
0,5
0,5
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
002062521
002062522
002062523
002062524
002062525
002063521
002063522
002063523
002063524
002063525
002063526
002064521
002064522
002064523
002064524
002064525
002064526
002065521
002065522
002065523
002065524
002065525
002062121
002062122
002062123
002062124
002062125
002062126
002063121
002063122
002063123
002063124
002063125
002064121
002064122
002064123
002064124
002064125
002064126
002065121
002065122
002065123
002065124
002065125
229
229
229
244
244
244
223
223
223
227
230
230
223
223
223
227
230
230
223
223
223
227
230
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
MBEFI-2 type A, MBEFI-2 type AC
In
[A]
I n
[A]
number
of poles code No.A code No.AC
weight
[g]
packaging
[pcs]
MBEFI-2 MBEFI-4
137
www.meba.net
Residual Current
Circuit Breaker
MBEFI-2/MBEFI-4 Residual Current Circuit Breaker
MBEFI-2 type G
25
25
40
40
0,03
0,1
0,3
0,1
2
2
2
2
002062722*
002063722*
002062723*
002063723*
220
220
220
220
1/54
1/54
1/54
1/54
In
[A]
I n
[A]
number
of poles code No.AC
weight
[g]
packaging
[pcs]
*The same housing as MBEFI-2 100 A.
* type with N-pole on the left side is also available.
16
25
40
63
80
100
16
25
40
63
80
100
16
25
40
63
80
100
16
25
40
63
80
0,03
0,03
0,03
0,03
0,03
0,03
0,1
0,1
0,1
0,1
0,1
0,1
0,3
0,3
0,3
0,3
0,3
0,3
0.5
0,5
0,5
0,5
0,5
MBEFI-4 type A, MBEFI-4 type AC
In
[A]
I n
[A]
number
of poles code No.A code No.AC
weight
[g]
packaging
[pcs]
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
002062541
002062542
002062543
002062544
002062545
002062546
002063541
002063542
002063543
002063544
002063545
002063546
002064541
002064542
002064543
002064544
002064545
002064546
002065541
002065542
002065543
002065544
002065545
002062141
002062142
002062143
002062144
002062145
002062146
002063141
002063142
002063143
002063144
002063145
002063146
002064141
002064142
002064143
002064144
002064145
002064146
002065141
002065142
002065143
002065144
002065145
393
393
393
400
407
407
393
393
393
400
407
407
364
364
364
372
372
372
364
364
364
372
372
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
MBEFI-4 type G
40
40
0,03
0,1
4
4
320
320
1/27
1/27
In
[A]
I n
[A]
number
of poles code No.AC
weight
[g]
packaging
[pcs]
*The same housingas MBEFI-4 100 A.
002062743*
002063743*
MBEFI-4 type S
40
63
0,3
0,3
4
4
400
400
1/27
1/27
In
[A]
I n
[A]
number
of poles code No.AC
weight
[g]
packaging
[pcs]
002064243
002064244
MBEFI-4 Specification:
MBETI also manufactures tripping relaysused in residual current circuit breakers-the range of products and their technical data is available in
technical information published separately.
MBEFI-2 MBEFI-4
138
www.meba.net
Residual Current
Circuit Breaker
PFIM-2P
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
Specification:
PFIM-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: PFIM
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
PFIM 2P, Residual CurrentDevices for earthleakage detection. It isto be used in associationwith miniature circuitbreakers, its function
is to detect earth leakage current and openthe connected circuit to protect people andequipment, major usedin industrial appli cation.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Technical parameter:
MBR2 Residual Current Circuit Breaker
Applications:
Specification:
Standard
Rated voltage(Un)
Rated current(In)
Rated residual operating current(In)
Rated residual non-operating current(I no)
Breaking capacity(A)
Residual current off-time
Operating temperature
IEC61008-1
1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC
10, 16, 20, 25, 32, 40A
30, 100, 300, 500mA
0.5ls n
6000A
0.1s
-5 +55
MBR2 RCCB provide the function of isolat ion switching and earth leakage protection of electrical circuits . They open a circuit automatically
in the event of an earth fault between phase and earth and/or neutral and earth. A wide range of current ratings and sen sitivities are
available. Suitable for domestic, commercial and industrial applications.
MBR2
139
www.meba.net
Residual Current
Circuit Breaker
PFIM-40-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: PFIM
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
Specification:
PFIM 2P, Residual CurrentDevicesfor earth leakage detection.It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Technical parameter:
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
PFIM-40-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: PFIM
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
Specification:
PFIM 4P, Residual CurrentDevices for earthleakage detection. Itis to beused in associationwith miniature circuitbreakers, its function
is to detect earth leakage current and open theconnected circuit toprotect people andequipment, major used in industrial applicati on.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
PFIM-40-2P PFIM-40-4P
Technical parameter:
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
140
www.meba.net
Residual Current
Circuit Breaker
Specification:
Technical parameter:
Specification:
Technical parameter:
RCCB-OLL4-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL4
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL4, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCCB-OLL4-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL4
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL4, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCCB-OLL4-2P RCCB-OLL4-4P
141
Technical parameter:
www.meba.net
Specification:
Technical parameter:
Specification:
Residual Current
Circuit Breaker
RCD-FIN-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: FIN
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
FIN 2P, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-FIN-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: FIN
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
FIN, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is
to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industr ial applicati on.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-FIN-2P RCD-FIN-4P
142
www.meba.net
Residual Current
Circuit Breaker
Specification:
Technical parameter:
Specification:
Technical parameter:
RCD-ID-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: ID
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
ID 2P, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-ID-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: ID
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
ID, Residual Current Devices for earth leakage det ection. It is to be used in association with miniature circuit breakers, its function is
to detect earth leakag e current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-ID-2P RCD-ID-4P
143
Technical parameter:
www.meba.net
Specification:
Technical parameter:
Specification:
Residual Current
Circuit Breaker
RCD-MNL-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: MNL
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
MNL, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-MNL-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: MNL
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
MNL, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-MNL-2P RCD-MNL-4P
144
www.meba.net
Residual Current
Circuit Breaker
Specification:
Technical parameter:
Specification:
Technical parameter:
RCD-NFIN Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: NFIN
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
NFIN, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-OLL1-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL1
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL1, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-NFIN RCD-OLL1-2P
145
Specification:
OLL18-63, replace of DZ18-20, Residual Current Devic es for
earth leakage detection. Itis tobe usedin associationwith miniature
circuit breakers, its function is todetect earth leakagecurrent and
open the connectedcircuit to protect people and equipment, major
used in industrial application. These devices are designed to meet
the Earth LeakageProtection Standards of the IEC: IEC/EN 61008.
Technical parameter:
www.meba.net
Specification:
Technical parameter:
Residual Current
Circuit Breaker
RCD-OLL1-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL1
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL1-4P, Residual CurrentDevices for earthleakage detection. It is to be usedin association with miniaturecircuit breakers, itsfunction
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-OLL18-63 Residual Current Circuit Breaker
Brand Name: Meba
Model Number: OLL18-63
Type: Residual Current CircuitBreaker or ResidualCurrent Device
Release Type:Electromagnetic
Electromagnetic
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
Dimensions(mm):
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
N 2
N 1
26.3 0.3
62 0.8
740.8
82.50.8
61 0.8
RCD-OLL1-4P RCD-OLL18-63
146
www.meba.net
Residual Current
Circuit Breaker
Specification:
Technical parameter:
Specification:
Technical parameter:
RCD-OLL2-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL2
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL2, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-OLL2-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL2
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL2, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-OLL2-2P RCD-OLL2-4P
147
www.meba.net
Specification:
Technical parameter:
Residual Current
Circuit Breaker
RCD-OLL2-N-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL2-N
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL2-N, Residual Current Devices for earth leakage detection. It is tobe used inassociation with miniaturecircuit breakers, itsfunction
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-OLL2-N-4P Residual Current Circuit Breaker
Specification:
Technical parameter:
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL2-N
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL2-N, Residual Current Devic es for earth leakage detection. It is tobe used inassociation with miniaturecircuit breakers, itsfunction
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-OLL2-N-2P RCD-OLL2-N-4P
148
www.meba.net
Residual Current
Circuit Breaker
Specification:
Technical parameter:
Specification:
Technical parameter:
RCD-OLL7-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL7
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL7, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
RCD-OLL7-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL7
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL7, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole devices Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
RCD-OLL7-2P RCD-OLL7-4P
149
www.meba.net
Specification:
Technical parameter:
Residual Current
Circuit Breaker
Specification:
Technical parameter:
RCD-OLL7-3-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL7-3
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL7-3, Resid ual Current Devices forearth leakage detection. It is tobe used inassociati on with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
RCD-OLL7-3-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL7-3
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL7-3, Residual Current Devices for earth leakag e detection. It is to beused in associationwith miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
RCD-OLL7-3-2P RCD-OLL7-3-4P
150
www.meba.net
Residual Current
Circuit Breaker
Specification:
Technical parameter:
Specification:
Technical parameter:
RCD-OLL7-4-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL7-4
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL7-4, Residual Current Devices forearth leakage detection.It is tobe used in associat ion with miniature circuit breakers, its fun ction
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
RCD-OLL7-4-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL7-4
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL7-4, Residual CurrentDevices for earthleakage detection. It isto be usedin association withminiatur e circuit breaker s, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole devices Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
RCD-OLL7-4-2P RCD-OLL7-4-4P
151
Technical parameter:
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
www.meba.net
Residual Current
Circuit Breaker
RCD-PF-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Specification:
Brand Name: Meba
Model Number: PF-2P
Type: ResidualCurrent Circuit Breakeror Residual Current Device
Poles Number: 2P
Flexibility:
Model PF, four pole, Residual Current Devices for earth leakage
detection to thestandards of IEC.It is tobe used inassociation with
miniature circuit breakers, its function is to detect earth leakage
current and open the connected circuit to protect people and
equip ment, major used in industrial application.These devicesare
designed to meet the Earth Leakage Protection Standardsof the
IEC: IEC/EN 61008.
With a wide range of currents and rated trip current available, the appropriate level of protection can be chosen for specific applications
for either personnel or equipment protection.
Specification:
Flexibility:
Technical parameter:
RCD-PF-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: PF-4P
Type: Residual CurrentCircuit Breaker orResidual Current Device
Poles Number: 4P
Model PF, four pole, Residual Current Devices for earth leakage
detection to thestandards of IEC.It is tobe used inassociation with
miniature circuit breakers, its function isto detect earth leakage
current and open the connected circuit to protect people and
equipment , major used in industrial application.These devicesare
designed to meet the Earth Leakage Protection Standards of the
IEC: IEC/EN 61008.
With a wide range of currents andrated trip current available, the
appropriate level ofprotection can bechosen for specificapplications
for either personnel or equipment protection.
Electromagnetic and Electronic type
70mm wide for 4 pole devices Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
1 N
2 N
H
1 3 5 N
2 4 6 N
H
Operation Principle Fig:
Dimensions(mm):
77 0.8
35.60.3
44.5
66
5.5
45
83.2
66.30.3
35.3 0.3
7236
RCD-PF-2P RCD-PF-4P
152

More Related Content

What's hot

C&S Electric Summer Training Report
C&S Electric Summer Training ReportC&S Electric Summer Training Report
C&S Electric Summer Training ReportParas Pratap
 
Earth leakege circuit breaker
Earth leakege circuit breakerEarth leakege circuit breaker
Earth leakege circuit breakerSooraj Maurya
 
Electrical protective devices ec
Electrical protective devices ecElectrical protective devices ec
Electrical protective devices ectrg12345
 
Circuit protection devices perfect ppt
Circuit protection devices perfect ppt Circuit protection devices perfect ppt
Circuit protection devices perfect ppt vikram rajpurohit
 
MCB And Earth Leakage Circuit
MCB And Earth Leakage CircuitMCB And Earth Leakage Circuit
MCB And Earth Leakage CircuitNavin Patle
 
Fuses vs. Circuit Breakers
Fuses vs. Circuit BreakersFuses vs. Circuit Breakers
Fuses vs. Circuit BreakersSima Yildirim
 
Smart under and over voltage protection system for
Smart under and over voltage protection system forSmart under and over voltage protection system for
Smart under and over voltage protection system forShuvadip das
 
Implementationof over voltageunder-voltageprotectionsystem
Implementationof over voltageunder-voltageprotectionsystemImplementationof over voltageunder-voltageprotectionsystem
Implementationof over voltageunder-voltageprotectionsystemSumaira Mustafa
 
39 alfred a. mello - 5910878 - method and apparatus for protecting electric...
39   alfred a. mello - 5910878 - method and apparatus for protecting electric...39   alfred a. mello - 5910878 - method and apparatus for protecting electric...
39 alfred a. mello - 5910878 - method and apparatus for protecting electric...Mello_Patent_Registry
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentationNikhil Kachare
 
Report on live wire detector
Report on live wire detectorReport on live wire detector
Report on live wire detectory751993
 
Medium-Voltage, Gas-Insulated Arc-Resistant Switchgear Types 8DA10 & 8DB10
Medium-Voltage, Gas-Insulated Arc-Resistant Switchgear Types 8DA10 & 8DB10Medium-Voltage, Gas-Insulated Arc-Resistant Switchgear Types 8DA10 & 8DB10
Medium-Voltage, Gas-Insulated Arc-Resistant Switchgear Types 8DA10 & 8DB10Power System Operation
 
Invisible broken wire detector
Invisible broken wire detectorInvisible broken wire detector
Invisible broken wire detectorRITESH D. PATIL
 

What's hot (19)

C&S Electric Summer Training Report
C&S Electric Summer Training ReportC&S Electric Summer Training Report
C&S Electric Summer Training Report
 
Report on MCB
Report on MCBReport on MCB
Report on MCB
 
Earth leakege circuit breaker
Earth leakege circuit breakerEarth leakege circuit breaker
Earth leakege circuit breaker
 
Electrical protective devices ec
Electrical protective devices ecElectrical protective devices ec
Electrical protective devices ec
 
Circuit protection devices perfect ppt
Circuit protection devices perfect ppt Circuit protection devices perfect ppt
Circuit protection devices perfect ppt
 
MCB And Earth Leakage Circuit
MCB And Earth Leakage CircuitMCB And Earth Leakage Circuit
MCB And Earth Leakage Circuit
 
Fuses and mcb
Fuses and mcbFuses and mcb
Fuses and mcb
 
How to check the quality of miniature circuit breaker (mcb)
How to check the quality of miniature circuit breaker (mcb)How to check the quality of miniature circuit breaker (mcb)
How to check the quality of miniature circuit breaker (mcb)
 
Fuses vs. Circuit Breakers
Fuses vs. Circuit BreakersFuses vs. Circuit Breakers
Fuses vs. Circuit Breakers
 
Smart under and over voltage protection system for
Smart under and over voltage protection system forSmart under and over voltage protection system for
Smart under and over voltage protection system for
 
Implementationof over voltageunder-voltageprotectionsystem
Implementationof over voltageunder-voltageprotectionsystemImplementationof over voltageunder-voltageprotectionsystem
Implementationof over voltageunder-voltageprotectionsystem
 
Failure of fuse & mcb
Failure of fuse & mcbFailure of fuse & mcb
Failure of fuse & mcb
 
39 alfred a. mello - 5910878 - method and apparatus for protecting electric...
39   alfred a. mello - 5910878 - method and apparatus for protecting electric...39   alfred a. mello - 5910878 - method and apparatus for protecting electric...
39 alfred a. mello - 5910878 - method and apparatus for protecting electric...
 
Surge supressor
Surge supressorSurge supressor
Surge supressor
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Report on live wire detector
Report on live wire detectorReport on live wire detector
Report on live wire detector
 
Medium-Voltage, Gas-Insulated Arc-Resistant Switchgear Types 8DA10 & 8DB10
Medium-Voltage, Gas-Insulated Arc-Resistant Switchgear Types 8DA10 & 8DB10Medium-Voltage, Gas-Insulated Arc-Resistant Switchgear Types 8DA10 & 8DB10
Medium-Voltage, Gas-Insulated Arc-Resistant Switchgear Types 8DA10 & 8DB10
 
Invisible broken wire detector
Invisible broken wire detectorInvisible broken wire detector
Invisible broken wire detector
 

Viewers also liked (20)

Teori kwh meter
Teori kwh meterTeori kwh meter
Teori kwh meter
 
Earthing
EarthingEarthing
Earthing
 
Basics of earthing
Basics of earthingBasics of earthing
Basics of earthing
 
Earthing
EarthingEarthing
Earthing
 
Electric shock
Electric shockElectric shock
Electric shock
 
Electric shock.powerpoint
Electric shock.powerpointElectric shock.powerpoint
Electric shock.powerpoint
 
Catalogue ELCB Fuji - Earth Leakage Circuit Breaker Fuji - Beeteco.com
 Catalogue ELCB Fuji - Earth Leakage Circuit Breaker  Fuji - Beeteco.com Catalogue ELCB Fuji - Earth Leakage Circuit Breaker  Fuji - Beeteco.com
Catalogue ELCB Fuji - Earth Leakage Circuit Breaker Fuji - Beeteco.com
 
Moulded case circuit breaker
Moulded case circuit breakerMoulded case circuit breaker
Moulded case circuit breaker
 
AC Contactor
AC ContactorAC Contactor
AC Contactor
 
Moulded case circuit breaker
Moulded case circuit breakerMoulded case circuit breaker
Moulded case circuit breaker
 
High voltage products
High voltage productsHigh voltage products
High voltage products
 
Mini circuit breaker
Mini circuit breakerMini circuit breaker
Mini circuit breaker
 
Temperature controller
Temperature controllerTemperature controller
Temperature controller
 
Industrial socket&plug
Industrial socket&plugIndustrial socket&plug
Industrial socket&plug
 
Distribution box
Distribution boxDistribution box
Distribution box
 
Light bar&elec bell
Light bar&elec bellLight bar&elec bell
Light bar&elec bell
 
Earth leakage circuit breaker
Earth leakage circuit breakerEarth leakage circuit breaker
Earth leakage circuit breaker
 
Distribution box
Distribution boxDistribution box
Distribution box
 
Meba push button switches
Meba push button switchesMeba push button switches
Meba push button switches
 
Residual current circuit_breakers
Residual current circuit_breakersResidual current circuit_breakers
Residual current circuit_breakers
 

Similar to Residual current-circuit-breaker www.meba.net

Dc circuit supplementary protectors for photovoltaic installations
Dc circuit supplementary protectors for photovoltaic installationsDc circuit supplementary protectors for photovoltaic installations
Dc circuit supplementary protectors for photovoltaic installationsLangir Electric
 
Low voltage circuit breakers & contactors general leaflet ls
Low voltage circuit breakers & contactors general leaflet   lsLow voltage circuit breakers & contactors general leaflet   ls
Low voltage circuit breakers & contactors general leaflet lsmaianhbao_6519
 
Ls catalog thiet bi dien electric products e 1108
Ls catalog thiet bi dien electric products e 1108Ls catalog thiet bi dien electric products e 1108
Ls catalog thiet bi dien electric products e 1108Dien Ha The
 
Ls catalog thiet bi dien electric products e 1108_dienhathe.vn
Ls catalog thiet bi dien electric products e 1108_dienhathe.vnLs catalog thiet bi dien electric products e 1108_dienhathe.vn
Ls catalog thiet bi dien electric products e 1108_dienhathe.vnDien Ha The
 
Catalogue mccb doi moi cua hang h yundai
Catalogue mccb doi moi cua hang h yundaiCatalogue mccb doi moi cua hang h yundai
Catalogue mccb doi moi cua hang h yundaiDien Ha The
 
Tongou electrical catalogue
Tongou electrical catalogue Tongou electrical catalogue
Tongou electrical catalogue Johnson lim
 
Catalog ls lvcb dienhathe.vn
Catalog ls lvcb dienhathe.vnCatalog ls lvcb dienhathe.vn
Catalog ls lvcb dienhathe.vnDien Ha The
 
LS Circuit Breaker Catalogue
LS Circuit Breaker CatalogueLS Circuit Breaker Catalogue
LS Circuit Breaker Cataloguehairxoawn
 
Domestic products range
Domestic products rangeDomestic products range
Domestic products rangeHavells India
 
Loop Powered Isolated Signal Transmitters and Splitters
Loop Powered Isolated Signal Transmitters and SplittersLoop Powered Isolated Signal Transmitters and Splitters
Loop Powered Isolated Signal Transmitters and SplittersInstrument Specialties, Inc.
 
Process Signal Isolated Transmitters, 4-20 ma
Process Signal Isolated Transmitters, 4-20 maProcess Signal Isolated Transmitters, 4-20 ma
Process Signal Isolated Transmitters, 4-20 maM.S. Jacobs & Associates
 
Ls catalog thiet bi dien electric products e 1104_dienhathe.vn
Ls catalog thiet bi dien electric products e 1104_dienhathe.vnLs catalog thiet bi dien electric products e 1104_dienhathe.vn
Ls catalog thiet bi dien electric products e 1104_dienhathe.vnDien Ha The
 

Similar to Residual current-circuit-breaker www.meba.net (20)

adw2q2qsad
adw2q2qsadadw2q2qsad
adw2q2qsad
 
Dc mini-breaker
Dc mini-breakerDc mini-breaker
Dc mini-breaker
 
Dc circuit supplementary protectors for photovoltaic installations
Dc circuit supplementary protectors for photovoltaic installationsDc circuit supplementary protectors for photovoltaic installations
Dc circuit supplementary protectors for photovoltaic installations
 
Low voltage circuit breakers & contactors general leaflet ls
Low voltage circuit breakers & contactors general leaflet   lsLow voltage circuit breakers & contactors general leaflet   ls
Low voltage circuit breakers & contactors general leaflet ls
 
Ls catalog thiet bi dien electric products e 1108
Ls catalog thiet bi dien electric products e 1108Ls catalog thiet bi dien electric products e 1108
Ls catalog thiet bi dien electric products e 1108
 
Ls catalog thiet bi dien electric products e 1108_dienhathe.vn
Ls catalog thiet bi dien electric products e 1108_dienhathe.vnLs catalog thiet bi dien electric products e 1108_dienhathe.vn
Ls catalog thiet bi dien electric products e 1108_dienhathe.vn
 
L.v tech presentation 2
L.v tech presentation 2L.v tech presentation 2
L.v tech presentation 2
 
Catalogue mccb doi moi cua hang h yundai
Catalogue mccb doi moi cua hang h yundaiCatalogue mccb doi moi cua hang h yundai
Catalogue mccb doi moi cua hang h yundai
 
Mcb catalogue
Mcb catalogueMcb catalogue
Mcb catalogue
 
Tongou electrical catalogue
Tongou electrical catalogue Tongou electrical catalogue
Tongou electrical catalogue
 
Thông số MCB LS
Thông số MCB LSThông số MCB LS
Thông số MCB LS
 
Catalog ls lvcb
Catalog ls lvcbCatalog ls lvcb
Catalog ls lvcb
 
Catalog ls lvcb dienhathe.vn
Catalog ls lvcb dienhathe.vnCatalog ls lvcb dienhathe.vn
Catalog ls lvcb dienhathe.vn
 
LS Circuit Breaker Catalogue
LS Circuit Breaker CatalogueLS Circuit Breaker Catalogue
LS Circuit Breaker Catalogue
 
Rccb catalogue
Rccb catalogueRccb catalogue
Rccb catalogue
 
Thông số kĩ thuật siemens rccb 5 sm
Thông số kĩ thuật siemens rccb 5 smThông số kĩ thuật siemens rccb 5 sm
Thông số kĩ thuật siemens rccb 5 sm
 
Domestic products range
Domestic products rangeDomestic products range
Domestic products range
 
Loop Powered Isolated Signal Transmitters and Splitters
Loop Powered Isolated Signal Transmitters and SplittersLoop Powered Isolated Signal Transmitters and Splitters
Loop Powered Isolated Signal Transmitters and Splitters
 
Process Signal Isolated Transmitters, 4-20 ma
Process Signal Isolated Transmitters, 4-20 maProcess Signal Isolated Transmitters, 4-20 ma
Process Signal Isolated Transmitters, 4-20 ma
 
Ls catalog thiet bi dien electric products e 1104_dienhathe.vn
Ls catalog thiet bi dien electric products e 1104_dienhathe.vnLs catalog thiet bi dien electric products e 1104_dienhathe.vn
Ls catalog thiet bi dien electric products e 1104_dienhathe.vn
 

More from Meba Electric Co.,Ltd (18)

Earth leakage circuit breaker
Earth leakage circuit breakerEarth leakage circuit breaker
Earth leakage circuit breaker
 
Changeover switch
Changeover switchChangeover switch
Changeover switch
 
Meters made by Meba Electric Co.,Ltd
Meters made by Meba Electric Co.,LtdMeters made by Meba Electric Co.,Ltd
Meters made by Meba Electric Co.,Ltd
 
Low voltage-distribution-cabinet
Low voltage-distribution-cabinetLow voltage-distribution-cabinet
Low voltage-distribution-cabinet
 
Push button switches
Push button switchesPush button switches
Push button switches
 
Meba proximity switch
Meba proximity switchMeba proximity switch
Meba proximity switch
 
Meba fuse
Meba fuseMeba fuse
Meba fuse
 
Switch power supply
Switch power supplySwitch power supply
Switch power supply
 
4.RCCB -Meba
4.RCCB -Meba 4.RCCB -Meba
4.RCCB -Meba
 
3.RCBO -Meba
3.RCBO -Meba3.RCBO -Meba
3.RCBO -Meba
 
2.MCCB -Meba
2.MCCB -Meba2.MCCB -Meba
2.MCCB -Meba
 
1.MCB -Meba
1.MCB -Meba1.MCB -Meba
1.MCB -Meba
 
Surge Protective Device -Meba
Surge Protective Device -MebaSurge Protective Device -Meba
Surge Protective Device -Meba
 
Distribution Box -Meba
Distribution Box -MebaDistribution Box -Meba
Distribution Box -Meba
 
Meba Energy Kwh Meter Electronic Catalogue
Meba Energy Kwh Meter Electronic CatalogueMeba Energy Kwh Meter Electronic Catalogue
Meba Energy Kwh Meter Electronic Catalogue
 
MEBA Moulded Case Circuit Breaker
MEBA Moulded Case Circuit BreakerMEBA Moulded Case Circuit Breaker
MEBA Moulded Case Circuit Breaker
 
Meba Terminal and Connector Catalogue
Meba Terminal and Connector CatalogueMeba Terminal and Connector Catalogue
Meba Terminal and Connector Catalogue
 
Meba Terminal Block Catalogue
Meba Terminal Block CatalogueMeba Terminal Block Catalogue
Meba Terminal Block Catalogue
 

Residual current-circuit-breaker www.meba.net

  • 1. MPFIM4 www.meba.net Residual Current Circuit Breaker 128 MPFIM4 Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: MPFIM4 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 4P Specification: MPFIM4, Residual CurrentDevices for earthleakage detection. It is tobe used in association with miniaturecircuit breakers, itsfunction is to detectearth leakage currentand open the connected circuit to protect people and equipment, major usedin industrial app lication. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Technical parameter: Electromagnetic and Electronic type 35mm wide for 4 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(In): 30, 100, 300, 500mA Rated residual non-operating current(Ino): 0.5 In Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA Dimensions: 77 0.8 35.60.3 44.5 66 5.5 45 830.8 35.5 0.3 72 66.30.3 36
  • 2. CF-362 Residual Current Circuit Breaker www.meba.net Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: CF-362 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P Specification: CF-362, Residual CurrentDevices for earthleakage detection. Itis to beused in associationwith miniature circuitbreakers, its function is todetect earth leakage current and open theconnected circuit to protect people andequipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Technical parameter: Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA CF-364 Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: CF-364 Type: Residual Current Circuit Breaker or Residual Current Device) Poles Number: 4P Specification: CF-364, Residual CurrentDevices for earthleakage detection. Itis to beused in associationwith miniature circuitbreakers, its function is to detect earth leakage currentand open theconnected circuit toprotect people andequipment , major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Technical parameter: Electromagnetic and Electronic type 70mm wide for 4 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA CF-362 CF-364 129
  • 3. www.meba.net Specification: Technical parameter: Specification: Technical parameter: Residual Current Circuit Breaker CF-462 Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: CF-462 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P CF-462, Residual CurrentDevices for earthleakage detection. It is to beused in associationwith miniature circuitbreakers, its function is to detect earth leakage curre nt and open the connected circuit to protect peopleand equipment, majorused in industrialapplication. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA CF-464 Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: CF-464 Type: Residual Current Circuit Breaker or Residual Current Device) Poles Number: 4P CF-464, Residual CurrentDevices for earthleakage detection. Itis to beused in associationwith miniature circuitbreakers, its function is to detect earth leakage current andopen the connectedcircuit to protectpeople and equipment, major used in industri al application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 70mm wide for 4 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA CF-462 CF-464 130
  • 4. www.meba.net Residual Current Circuit Breaker DZ30L-32 Residual Current Circuit Breaker Specification: Technical parameter: Residual current circuit breaker with overload protection(RCBO) Brand Name: Meba Model Number: DZ30L-32 Type: Residual current circuit breaker with overload protection(RCBO) Poles Number: DPN DZ30L-32(DPN), combination by mini circuit breaker and leakage. Which protect human from the fault of electric because of over- current, short circuit, earth fault current. It is self-protecting up to a maximum short-circuit current 63A. All breakingcapacities comply with Standard IEC/EN 61009. Residual current device with overcurrent protection Combine in residual current device function and MCB over-current protection function Short circuit capacity: 3KA Rated current(A): 6, 16, 20, 25, 32A Rated leakage operating current(mA): 30, 100, 300mA AC types, B-C characteristic Modular Din Rail products 35mm. DZ47LE-63-2P Residual Current Circuit Breaker Specification: Technical parameter: Residual current circuit breaker with overload protection(RCBO) Brand Name: Meba Model Number: DZ47LE-63 Type: Residual current circuit breaker with overload protection(RCBO) Poles Number: 2 pole MCB + ELCB DZ47LE-63 2Pole, combination by mini circuit breaker and leakage. Which protect human from the fault of electric because of over- current, short circuit, earth fault current. It is self-protecting up toa maximum short-circuit current 63A. All breaking capacitiescomply with Standard IEC/EN 61009. Residual current device with overcurrent protection Combine in residual current device function and MCB over-current protection function Short circuit capacity: 6KA Rated current(A): 6,16,20,25,32,40,50,63A Rated leakage operating current(mA): 30,100,300mA AC types, B-C characteristic Modular Din Rail products 35mm. 131 DZ30L-32 DZ47LE-63-2P
  • 5. M www.meba.net Specification: Technical parameter: Residual Current Circuit Breaker DZ47LE-63-4P Residual Current Circuit Breaker Residual current circuit breaker with overload protection(RCBO) Brand Name: Meba Model Number: DZ47LE-63 Type: Residual current circuit breaker with overload protection(RCBO) Poles Number: 4 pole MCB + ELCB DZ47LE-63 4Pole, combination by mini circuit breaker and leakage. Which protect human from the fault of electric because of over- current, short circuit, earth fault current. It is self-protecting up to a maximum short-circuit current 63A. All breakingcapacities comply with Standard IEC/EN 61009. Residual current device with overcurrent protection Combine in residual current device function and MCB over-current protection function Short circuit capacity: 6KA Rated current(A): 6, 16, 20, 25, 32, 40, 50, 63A Rated leakage operating current(mA): 30, 100, 300mA AC types, B-C characteristic Modular Din Rail products 35mm. 132 DZ47LE-63-4P M Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: M Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P Specification: M series Residual Cur rent Devices for earth leakage detection. Itis to beused in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(In): 30, 100, 300, 500mA Technical parameter: Rated residual non-operating current(Ino): 0.5 In Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA
  • 6. www.meba.net Residual Current Circuit Breaker 133 MB089/MB090 Residual Current Circuit Breaker Applications: Specification: Standard Rated voltage(Un) Rated current(In) Rated residual operating current(In) Rated residual non-operating current(I no) Breaking capacity(A) Residual current off-time Operating temperature IEC61008-1 1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC 10, 16, 20, 25, 32, 40A 30, 100, 300, 500mA 0.5ls n 6000A 0.1s -5 +55 Dimensions: O. OFF 94 35.6 O. OFF 71.2 61.5 76 45 83 MB089/ MB090 4P RCD provide the function of isolation switchingand earth leakageprotection of electricalcircuits. They open a circuit automatically in the event of an earth fault between phase and earth and/or netural and earth. A wide range of current ratings and sensitivities are available. Suitable for domestic, commercial and industrial applications. MB089 MB090
  • 7. www.meba.net Residual Current Circuit Breaker 134 MB7L2-63 Residual Current Circuit Breaker Applications: MB7L2-63 RCCB provide the function of isolation switching and earth leakage protection of electrical circuits. They open a circuit automatically in the event of an earth fault between phase and earth and/or netural and earth. Awide range of current ratings and sensitivities are available. Suitable for domestic, commercial and industrial applications. Specification: Standard Rated voltage(Un) Rated current(In) Rated residual operating current(In) Rated residual non-operating current(I no) Breaking capacity(A) Residual current off-time Operating temperature IEC61008-1 1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC 10, 16, 20, 25, 32, 40A, 50A, 63A 30, 100, 300, 500mA 0.5ls n 6000A 0.1s -5 +55 MB7L4-63 Residual Current Circuit Breaker Applications: Specification: Standard Rated voltage(Un) Rated current(In) Rated residual operating current(In) Rated residual non-operating current(I no) Breaking capacity(A) Residual current off-time Operating temperature IEC61008-1 1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC 10, 16, 20, 25, 32, 40A, 50A, 63A 30, 100, 300, 500mA 0.5ls n 6000A 0.1s -5 +55 MB7L4-63 RCCB provide the function of isolation switching and earth leakage protection of electrical circuits. They open a circuit automatically in the event of an earth fault between phase and earth and/or netural and earth. A wide range of current ratings and sensitivities are available. Suitable for domestic, commercial and industrial applications. MB7L2-63 MB7L4-63
  • 8. MBB8LE-63-1P www.meba.net Residual Current Circuit Breaker 135 Applications: Specification: Standard Rated voltage(Un) Rated current(In) Rated residual operating current(In) Rated residual non-operating current(I no) Breaking capacity(A) Residual current off-time Operating temperature IEC61008-1 1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC 10, 16, 20, 25, 32, 40A 30, 100, 300, 500mA 0.5ls n 6000A 0.1s -5 +55 MBACH2 Residual Current Circuit Breaker MBACH2RCCBprovidethe function ofisolation switching andearth leakage protectionof electrical circuits.Theyopena circuit automatically in the event of an earth fault between phase and earth and/or neutral and earth. A wide range of current ratings and sensitivities are available. Suitable for domestic, commercial and industrial applications. Specification: Technical parameter: MBB8LE-63-1P Residual Current Circuit Breaker Residual current circuit breaker with overload protection(RCBO) Brand Name: Meba Model Number: MBB8LE-63 Type: Residual current circuit breaker with overload protection(RCBO) Poles Number: 1 pole MCB + ELCB MBB8LE-63 1Pole, combination by mini circuit breaker and leakage. Which protect human from the fault of electric because of over- current, short circuit, earth fault current. It isself-protecting up to a maximum short-circuit current 63A. All breaking capacities comply with Standard IEC/EN 61009. Residual current device with overcurrent protection Combine in residual current device function and MCB over-current protection function Short circuit capacity: 6KA Rated current(A): 6, 16, 20, 25, 32, 40, 50, 63A Rated leakage operating current(mA): 30, 100, 300mA AC types, B-C characteristic Modular Din Rail products 35mm. MBACH2
  • 9. www.meba.net Residual Current Circuit Breaker 136 MBEA-63A Residual Current Circuit Breaker Applications: Specification: Standard Rated voltage(Un) Rated current(In) Rated residual operating current(In) Rated residual non-operating current(I no) Breaking capacity(A) Residual current off-time Operating temperature IEC61008-1 1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC 10, 16, 20, 25, 32, 40A, 50A, 63A 30, 100, 300, 500mA 0.5ls n 6000A 0.1s -5 +55 MBEA-63A RCCB provide the function of isolation switching and earth leakage protection of electrical circuits. They open a circuit automatically in the event of an earth fault be tween phase and earth and/or neutral and earth. A wide range of current ratings and sensitivities are available. Suitable for domestic, commercial and industrial applications. MBB8LE-63-2P Residual Current Circuit Breaker Residual current circuit breaker with overload protection(RCBO) Brand Name: Meba Model Number: MBB8LE-63 Type: Residual current circuit breaker with overload protection(RCBO) Poles Number: 2 pole MCB + ELCB Specification: MBB8LE-63 2Pole, combination by mini circuit breaker and leakage. Which protect humanfrom the fault of electric because of over- current, short circuit, earth fault current. It is self-protecting up to a maximum short-circuit current 63A. All breakingcapacities comply with Standard IEC/EN 61009. Technical parameter: Residual current device with overcurrent protection Combine in residual current device function and MCB over-current protection function Short circuit capacity: 6KA Rated current(A): 6, 16, 20, 25, 32, 40, 50, 63A Rated leakage operating current(mA): 30, 100, 300mA AC types, B-C characteristic Modular Din Rail products 35mm. MBB8LE-63-2P MBEA-63A
  • 10. www.meba.net Residual Current Circuit Breaker Applications: MBEFI-2/MBEFI-4 Residual Current Circuit Breaker Residual current circuitbreakers MBEFI areused for protectionagainst indirect touching of parts under voltage, for prevention of lasting voltage on earthed par ts which should appear because of a defectin the electricalinstallation and for protection against direct conta cts of parts under voltage in case of I n 30mA. Residual current circuit breakers can beused in TN-S, TN-C, TT and ITnetwork systems or with other words in all systems where neutral and protective conductor are separated (VDE 0100 Teil 410). Types - Our programme comprises residual current circuit breakers which are sensitive to alternating residu al current (AC-type) and residual current circuit breakers which are sensitive to alternating and pulsating direct current (A-type). For alternating residual current For alternating and pulsating direct residual current Short-circuit capacity with back-up fuse lower temperature limit of application -25 C VDE 0664, part 1 (up to 80 A) Selective (time delayed min. 40 ms) Short time delayed (min. 10 ms) type A type AC type G type A type AC type S type G MBEFI2 MBEFI4 MBEFI-2 Specification: 16 25 40 63 80 100 16 25 40 63 80 100 16 25 40 63 80 100 16 25 40 63 80 0,03 0,03 0,03 0,03 0,03 0,03 0,1 0,1 0,1 0,1 0,1 0,1 0,3 0,3 0,3 0,3 0,3 0,3 0.5 0,5 0,5 0,5 0,5 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 002062521 002062522 002062523 002062524 002062525 002063521 002063522 002063523 002063524 002063525 002063526 002064521 002064522 002064523 002064524 002064525 002064526 002065521 002065522 002065523 002065524 002065525 002062121 002062122 002062123 002062124 002062125 002062126 002063121 002063122 002063123 002063124 002063125 002064121 002064122 002064123 002064124 002064125 002064126 002065121 002065122 002065123 002065124 002065125 229 229 229 244 244 244 223 223 223 227 230 230 223 223 223 227 230 230 223 223 223 227 230 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 1/54 MBEFI-2 type A, MBEFI-2 type AC In [A] I n [A] number of poles code No.A code No.AC weight [g] packaging [pcs] MBEFI-2 MBEFI-4 137
  • 11. www.meba.net Residual Current Circuit Breaker MBEFI-2/MBEFI-4 Residual Current Circuit Breaker MBEFI-2 type G 25 25 40 40 0,03 0,1 0,3 0,1 2 2 2 2 002062722* 002063722* 002062723* 002063723* 220 220 220 220 1/54 1/54 1/54 1/54 In [A] I n [A] number of poles code No.AC weight [g] packaging [pcs] *The same housing as MBEFI-2 100 A. * type with N-pole on the left side is also available. 16 25 40 63 80 100 16 25 40 63 80 100 16 25 40 63 80 100 16 25 40 63 80 0,03 0,03 0,03 0,03 0,03 0,03 0,1 0,1 0,1 0,1 0,1 0,1 0,3 0,3 0,3 0,3 0,3 0,3 0.5 0,5 0,5 0,5 0,5 MBEFI-4 type A, MBEFI-4 type AC In [A] I n [A] number of poles code No.A code No.AC weight [g] packaging [pcs] 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 002062541 002062542 002062543 002062544 002062545 002062546 002063541 002063542 002063543 002063544 002063545 002063546 002064541 002064542 002064543 002064544 002064545 002064546 002065541 002065542 002065543 002065544 002065545 002062141 002062142 002062143 002062144 002062145 002062146 002063141 002063142 002063143 002063144 002063145 002063146 002064141 002064142 002064143 002064144 002064145 002064146 002065141 002065142 002065143 002065144 002065145 393 393 393 400 407 407 393 393 393 400 407 407 364 364 364 372 372 372 364 364 364 372 372 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 1/27 MBEFI-4 type G 40 40 0,03 0,1 4 4 320 320 1/27 1/27 In [A] I n [A] number of poles code No.AC weight [g] packaging [pcs] *The same housingas MBEFI-4 100 A. 002062743* 002063743* MBEFI-4 type S 40 63 0,3 0,3 4 4 400 400 1/27 1/27 In [A] I n [A] number of poles code No.AC weight [g] packaging [pcs] 002064243 002064244 MBEFI-4 Specification: MBETI also manufactures tripping relaysused in residual current circuit breakers-the range of products and their technical data is available in technical information published separately. MBEFI-2 MBEFI-4 138
  • 12. www.meba.net Residual Current Circuit Breaker PFIM-2P Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA Specification: PFIM-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: PFIM Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P PFIM 2P, Residual CurrentDevices for earthleakage detection. It isto be used in associationwith miniature circuitbreakers, its function is to detect earth leakage current and openthe connected circuit to protect people andequipment, major usedin industrial appli cation. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Technical parameter: MBR2 Residual Current Circuit Breaker Applications: Specification: Standard Rated voltage(Un) Rated current(In) Rated residual operating current(In) Rated residual non-operating current(I no) Breaking capacity(A) Residual current off-time Operating temperature IEC61008-1 1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC 10, 16, 20, 25, 32, 40A 30, 100, 300, 500mA 0.5ls n 6000A 0.1s -5 +55 MBR2 RCCB provide the function of isolat ion switching and earth leakage protection of electrical circuits . They open a circuit automatically in the event of an earth fault between phase and earth and/or neutral and earth. A wide range of current ratings and sen sitivities are available. Suitable for domestic, commercial and industrial applications. MBR2 139
  • 13. www.meba.net Residual Current Circuit Breaker PFIM-40-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: PFIM Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P Specification: PFIM 2P, Residual CurrentDevicesfor earth leakage detection.It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Technical parameter: Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA PFIM-40-4P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: PFIM Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 4P Specification: PFIM 4P, Residual CurrentDevices for earthleakage detection. Itis to beused in associationwith miniature circuitbreakers, its function is to detect earth leakage current and open theconnected circuit toprotect people andequipment, major used in industrial applicati on. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. PFIM-40-2P PFIM-40-4P Technical parameter: Electromagnetic and Electronic type 70mm wide for 4 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA 140
  • 14. www.meba.net Residual Current Circuit Breaker Specification: Technical parameter: Specification: Technical parameter: RCCB-OLL4-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL4 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P OLL4, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCCB-OLL4-4P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL4 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 4P OLL4, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 70mm wide for 4 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCCB-OLL4-2P RCCB-OLL4-4P 141
  • 15. Technical parameter: www.meba.net Specification: Technical parameter: Specification: Residual Current Circuit Breaker RCD-FIN-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: FIN Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P FIN 2P, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-FIN-4P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: FIN Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 4P FIN, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industr ial applicati on. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 70mm wide for 4 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-FIN-2P RCD-FIN-4P 142
  • 16. www.meba.net Residual Current Circuit Breaker Specification: Technical parameter: Specification: Technical parameter: RCD-ID-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: ID Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P ID 2P, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-ID-4P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: ID Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 4P ID, Residual Current Devices for earth leakage det ection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakag e current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 70mm wide for 4 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-ID-2P RCD-ID-4P 143
  • 17. Technical parameter: www.meba.net Specification: Technical parameter: Specification: Residual Current Circuit Breaker RCD-MNL-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: MNL Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P MNL, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-MNL-4P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: MNL Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 4P MNL, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 70mm wide for 4 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-MNL-2P RCD-MNL-4P 144
  • 18. www.meba.net Residual Current Circuit Breaker Specification: Technical parameter: Specification: Technical parameter: RCD-NFIN Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: NFIN Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P NFIN, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-OLL1-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL1 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P OLL1, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-NFIN RCD-OLL1-2P 145
  • 19. Specification: OLL18-63, replace of DZ18-20, Residual Current Devic es for earth leakage detection. Itis tobe usedin associationwith miniature circuit breakers, its function is todetect earth leakagecurrent and open the connectedcircuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth LeakageProtection Standards of the IEC: IEC/EN 61008. Technical parameter: www.meba.net Specification: Technical parameter: Residual Current Circuit Breaker RCD-OLL1-4P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL1 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 4P OLL1-4P, Residual CurrentDevices for earthleakage detection. It is to be usedin association with miniaturecircuit breakers, itsfunction is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 70mm wide for 4 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-OLL18-63 Residual Current Circuit Breaker Brand Name: Meba Model Number: OLL18-63 Type: Residual Current CircuitBreaker or ResidualCurrent Device Release Type:Electromagnetic Electromagnetic Standsrd: IEC1008/EN61008 Rated Voltage(Un): 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA Dimensions(mm): Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) N 2 N 1 26.3 0.3 62 0.8 740.8 82.50.8 61 0.8 RCD-OLL1-4P RCD-OLL18-63 146
  • 20. www.meba.net Residual Current Circuit Breaker Specification: Technical parameter: Specification: Technical parameter: RCD-OLL2-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL2 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P OLL2, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-OLL2-4P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL2 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 4P OLL2, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 70mm wide for 4 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-OLL2-2P RCD-OLL2-4P 147
  • 21. www.meba.net Specification: Technical parameter: Residual Current Circuit Breaker RCD-OLL2-N-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL2-N Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P OLL2-N, Residual Current Devices for earth leakage detection. It is tobe used inassociation with miniaturecircuit breakers, itsfunction is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-OLL2-N-4P Residual Current Circuit Breaker Specification: Technical parameter: Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL2-N Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 4P OLL2-N, Residual Current Devic es for earth leakage detection. It is tobe used inassociation with miniaturecircuit breakers, itsfunction is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 70mm wide for 4 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 6KA RCD-OLL2-N-2P RCD-OLL2-N-4P 148
  • 22. www.meba.net Residual Current Circuit Breaker Specification: Technical parameter: Specification: Technical parameter: RCD-OLL7-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL7 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P OLL7, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 10KA RCD-OLL7-4P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL7 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 4P OLL7, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 70mm wide for 4 pole devices Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 10KA RCD-OLL7-2P RCD-OLL7-4P 149
  • 23. www.meba.net Specification: Technical parameter: Residual Current Circuit Breaker Specification: Technical parameter: RCD-OLL7-3-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL7-3 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P OLL7-3, Resid ual Current Devices forearth leakage detection. It is tobe used inassociati on with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 10KA RCD-OLL7-3-4P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL7-3 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 4P OLL7-3, Residual Current Devices for earth leakag e detection. It is to beused in associationwith miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 70mm wide for 4 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 10KA RCD-OLL7-3-2P RCD-OLL7-3-4P 150
  • 24. www.meba.net Residual Current Circuit Breaker Specification: Technical parameter: Specification: Technical parameter: RCD-OLL7-4-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL7-4 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 2P OLL7-4, Residual Current Devices forearth leakage detection.It is tobe used in associat ion with miniature circuit breakers, its fun ction is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 10KA RCD-OLL7-4-4P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: OLL7-4 Type: Residual Current Circuit Breaker or Residual Current Device Poles Number: 4P OLL7-4, Residual CurrentDevices for earthleakage detection. It isto be usedin association withminiatur e circuit breaker s, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. Electromagnetic and Electronic type 70mm wide for 4 pole devices Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 10KA RCD-OLL7-4-2P RCD-OLL7-4-4P 151
  • 25. Technical parameter: Electromagnetic and Electronic type 35mm wide for 2 pole Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 2pole, 230V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 10KA www.meba.net Residual Current Circuit Breaker RCD-PF-2P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Specification: Brand Name: Meba Model Number: PF-2P Type: ResidualCurrent Circuit Breakeror Residual Current Device Poles Number: 2P Flexibility: Model PF, four pole, Residual Current Devices for earth leakage detection to thestandards of IEC.It is tobe used inassociation with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equip ment, major used in industrial application.These devicesare designed to meet the Earth Leakage Protection Standardsof the IEC: IEC/EN 61008. With a wide range of currents and rated trip current available, the appropriate level of protection can be chosen for specific applications for either personnel or equipment protection. Specification: Flexibility: Technical parameter: RCD-PF-4P Residual Current Circuit Breaker Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB) Brand Name: Meba Model Number: PF-4P Type: Residual CurrentCircuit Breaker orResidual Current Device Poles Number: 4P Model PF, four pole, Residual Current Devices for earth leakage detection to thestandards of IEC.It is tobe used inassociation with miniature circuit breakers, its function isto detect earth leakage current and open the connected circuit to protect people and equipment , major used in industrial application.These devicesare designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008. With a wide range of currents andrated trip current available, the appropriate level ofprotection can bechosen for specificapplications for either personnel or equipment protection. Electromagnetic and Electronic type 70mm wide for 4 pole devices Din Rail installation. Standsrd: IEC1008/EN61008 Rated Voltage(Un): 4pole, 400V AC Rated Current(In): 25, 40, 63A Rated residual operating current(I n): 30, 100, 300, 500mA Rated residual non-operating current(I no): 0.5 I n Residual current off-time: 0.1s Minimum value of rated breaking capacity(lm): 630A Rated conditional short-circuit capacity (lnc): 10KA 1 N 2 N H 1 3 5 N 2 4 6 N H Operation Principle Fig: Dimensions(mm): 77 0.8 35.60.3 44.5 66 5.5 45 83.2 66.30.3 35.3 0.3 7236 RCD-PF-2P RCD-PF-4P 152