DCS EVOLUTION-CENTRALISED CONTROL
DCS EVOLUTION-DISTRIBUTED CONTROL
DCS EVOLUTION-FIELDBUS CONTROL
DCS EVOLUTION- WEB CONTROL
DCS EVOLUTION-WEB CONTROL APPLICATION
ABB DCS ARCITECTURE
ABB DCS HARDWARE
CONTROL SYSTEMS TREND

1) PLC
2) DCS
3) PC - Based Control.

• PLC : Introduced in the late 1960 to replace Relays and Hard-wired
  Programming.
DCS : Introduced in the Mid-1970 to
replace pneumatic controls by using
computers.
• PC-Based Control : Introduced by the early 1980s to avoid the
  proprietary PLC & DCS systems.
DCS EVOLUTION
• LOCAL CONTROL : Initially control was performed local to the equipment
   control. The ADVANTAGE was low wiring costs .DISADVANTAGES were -
   not much control, monitoring, alarming & history.

• CENTRALISED CONTROL: With the advent of minicomputer, sensors and
   actuators were into the Central Control (Computer).

• DISTRIBUTED CONTROL: With the advent of microcomputer, Distributed
   control systems were installed in the plants near to the control room via
   proprietary digital communications lines called as Data Hiway. First DCS was
   developed by Honeywell,U.S in 1975.
          The ADVANTAGES were greatly reduced wiring costs, much more limited
    failure and less cost to add more points.
          The DISADVANTAGES were that wiring costs were that wiring costs
   were still significant and there was lack of interoperability among controllers of
   various manufacturers due to the proprietary protocols. Hence the user was
   locked into a single vendor.
DCS System Installations in RCF
1. Yokogawa - CS 3000                       :      Ammonia II
2. Yokogawa - CS 3000                       :      ANP
3. Yokogawa - CS 3000                       :      NNAP
4. Moore - APACS                            :     Methyl amine
5. Fisher - Rosemant - Delta V field Bus   : STP
6. Honeywell - GUS                             : Ammonia I Synthesis
7. Yokogawa - Centum Excel                   : Steam Generation Plant
8. Moore - APACS                              : Suphala
9. Yokogawa - Micro Excel                   : Methanol
10. Yokogawa - Micro Excel                  : S A P/C N A
11. ABB - Freelance 2000                      : ABC
12. Honeywell - TDC 3000                     : Ammonia I
13. Honeywell - GUS                           : Ammonia/Urea - Thal
14. Fox boro - I/A series                       : D M A C - Thal
15. Fisher - Rosemant RS3                      : PGR
16. Fisher - Rosemant RS3                      : Steam Generation - Thal
17. Moore - APACS                             : Water Treatment Plant -
   Thal
DCS
• The importance of DCS systems to increase as global competitive
    dynamics in food and beverage, specialty metals, pulp and paper,
    pharmaceutical and fire chemical processing.
•   The DCS has networking capabilities which are useful for business
    management.
•   The DCS has capacity for processing large number of I/O points.

                         TYPES OF DCS :
1) Conventional DCS .
2) PLC based DCS.
3) Hybrid DCS.
4) Open DCS System
CONVENTIONAL DCS
  This is a pure “Process only” control system. Usually purchased from
  one vendor. This DCS arranged into three categories:
• Small - Less than $ 100,000.
• Medium - Greater than $100,000 & Less than $500,000.
• Large - Greater than $500,000.
PLC Based DCS.
       This is a network of PLC’s used to perform the task of
  conventional DCS and programmable functionality when required.


Hybrid DCS.
       Performs both process and sequential control.

Open DCS System.
            This is Field-Bus Control. Advantages are lower wiring cost and
  less failure, smaller expansion costs and multi vendor interoperability
  DCS and PLC can be more closely and efficiently interconnected.
Honeywell TDC 3000 DCS Architecture



            US#1              US#2         HM

                                                 LCN A
                                                     B



                 HG

                                     AMC             Field
                                       EC Link
                                     AMC                 Field

    Data Hiway        A   B
Hiway Gateway (HG)
•    LCN Module. Provides a two way communication link between the Local
      Control Network and data hiway.
•    68020 based high performance intelligence module.
•    Converts data and protocol between Local Control Network and data hiway.
•    Scans the hiway for alarm conditions.
•    Synchronize time keeping for hiway-based process connected boxes.
•    One HG is required for each data hiway that is connected to the LCN. Up to
     20 data hiway pairs can be connected to an LCN.
•    Connects following hiway resident boxes to LCN
    1. AMCs
    2. CPC ( critical process controller ).
    3. DHP.
    4. Hiway traffic director etc…

    HG Functions :
    1. Data access :- gets box data requested from LCN modules.
    2. Event processing :- sends process and box alarm to LCN modules
    3. Database configuration :- 3000 points per hg can be configured.
Data Hiway




            Data hiway provides communication link between hiway
     gateway,
 preferred access devices and process connecting box. Data hiway
     operates at
250 kbps.
            It is redundant pair of 75 ohm coax cable connected to box.
     It may be
 20,000 feet long.
            There are 3 kinds of devices on the data hiway,
1. Respond only devices Ex:- A-MC (Advanced Multifunction
     controller)
2. Polled devices       Ex:- PIU’s (Process interface unit)
3. Preferred access devices
History Module



• LCN Module. Stores process and system
    information that can be displayed.
•   Based on microprocessors 68020.
•   Winchester disk for data storage.
•   Communicates with all Modules on the LCN.
•   Stores history and general information.
Universal Station
          Universal station (US) communicates with all modules on the
   LCN, process
 connected devices on the hiway via hiway gateway and UCN via network
   interface module
 (NIM).
          The following are the features of US,
• Intelligent man/machine interface in the TDC 3000 system.
• Stands on the LCN. Communicates with all Modules on LCN, process
   connected devices on the Hiway via Hiway Gateway.
• Provides comprehensive facilities to the process operator, process
   engineer and maintenance technician on the Universal Window.
          US provides comprehensive facilities to the following people,
• Process engineer
• Process operator
• Maintenance technician.
AMC
•    TDC 3000 controller
    1.   Based on Motorola 68000 Microprocessor.
    2.   Faster execution and control with 500 ms processing rate.
•    Multifunction – Modulating, sequence, logic, I/O monitoring
     communication and diagnostic.
•    Faster peer to peer communication over EC link ( 500 kbits/sec ).
•    Proven control techniques
    1.   Full function algorithms.
    2.   Process oriented programming.
•    Configured as a box on TDC 3000 Data Hiway. Supported by
    1.   LCN devices – US, AM, HM.
HONEYWELL - GUS
Printer                  Drive’s                                                          Printer
                         -     -

                             US#1   US#2                                US#3   US#4
          Universal
           Station


                                                                                                    HM
                                                                                                         History Module
                                                                                                                    A
                                                                                                                   B
                                                                                          Local Control Network


                Network Interface Module                               NIM
                                           Universal Control Network




                                                                                 HPM   High Performance Manager


                                                                                 HPM


                                                                                 HPM
Honeywell System Description




• Global User Station
• History Modules
• Network Interface Modules
• Communication Subsystem - Local Control Network & Universal
  Control Network
• High Performance Process Manager
Global User Station
    Overview
          The TPS system provides an integrated interface between the process
    and the end user. This interface is named as the Global User Station (GUS).
          GUS is an important part in the Honeywell Total plant Solutions
    offerings. It provides access to plant wide process network, plant or
    organization wide intranet or even Internet.
          The following hardware is available to enhance the functionality of the
    GUS:
•    Integrated Keyboard for Operators as well as Engineer.
•   Matrix printer supported by Windows NT.
•   8 * CD-ROM
•   100MB ZIP Drive
•   3.5” Floppy Drive
          GUS has following functionality's :
•   The “Human ” interface allows effective interaction of the Operator through
    the use of operating displays
•   Engineering functions such as data point building, display building and report
    building are available.
•   Communication with other LCN modules is accomplished.
•   Communication on Ethernet.
Honey well GUS Hardware:

•   Processor                  :        Pentium Pro / 200MHZ
•   Memory                     :        64MB RAM ECC
•   Cache                        :       256KB ECC
•   Storage                      :       2 GB hard disk drive, CD ROM,
    Cartridge Drive
•   Video                         :      21” high resolution screen 1280 * 1024
    Pixels
•   Colours                    :         256 color palette
•   Keyboard                   :         Integrated keyboard with mouse
•   PIN Connection            :         Built in Ethernet
•   Cursor Control            :         QWERTY & Mouse/Touch Screen

Peripherals supported
• Printer
• 8 * CD-ROM
• 1/4” Steamer Tape
• 3.5” Floppy Drive
• 100 Mb ZIP Drive
• Annunciator relay on the console-based keyboard
Honeywell GUS software




• Operating System             :    Windows NT version 4.0
• Base System                   :    Provides real time data
  exchange
  between the network and all GUS
         functions.
History Modules
      The History Modules is the bulk module that can be utilized by all module
     connected
 to the Local Control Network. It is as the name implies the mass memory of the
     TPS
 System. The memory components of this module are one 1.8 gigabyte
     Winchester discs.
 It is controlled by an M68040 microprocessor. This provides the module with
     significant
 computing power that this used to structure much of the incoming data and
     format it into
 a form for easy retrieval.
         The history in the model is provided by the History Module. Process
     variables are
 available for hourly, shift, daily and monthly average calculation and recording.
        All system event history such as process alarms, system status changes,
     and error
 messages are stored into the History Modules.
        Other modules have access to data in the History Modules for their
     functions.
The History Module provides two functions, storage only and data structuring
HM functions and Historization parameter
 HM functions :
         It can automatically backup the control databases in the HG, AM, CG.
 HM can store,
• Continuous process history.
• Event journal (history).
• Active system files.
• Static system files.
• On process analysis program (maintenance aid)

HM Historization parameters :
   There can be up to 10 HM’s on the LCN. There can be maximum of 150
   groups per
 HM. Each group can have up to 20 points. All points in the group must be in the
   same
 unit.
Network Interface Module (NIM)




 The Network Interface Module (NIM) provides the link between the local Control
Network and the Universal Control Network. As such it make the transition from
   the
transmission technique and protocol or the Local Control Network to the
   transmission
technique and the protocol of the Universal Control Network. The NIM provides
   access
by LCN modules data from UCN resident devices. The NIM is available in the
   redundant
configuration to provide continued operation in the event of the primary failure. It
   can
also do event processing.
       There can be up to 10 redundant NIM pairs per LCN. A NIM can host upto
   8000 tag
names and supports a data transfer rate of 2400 parameters per second.
Communication Subsystem

                               Local Control Network (LCN)




                The backbone of every TPS system is a communication network,
     known as
 Local Control Network. The LCN is a LAN through which TDC 3000 modules
communicate with each other. The LCN is a broadcast type of LAN. It is high speed
 redundant communication bus that connect all the control room equipment. All
     information
 is transferred on the network at 5 million bits per sec.,serially. It is based on the
     IEEE 802.4
 Token passing and Bus Standard.
                 Each LCN device that is connected to the Local Control Network is
     called a
 module. Up to 64 modules may be connected to the Local Control Network in a
     TPS
 system. The Local Control Network is designated as the primary and the other as
     the back
Communication Subsystem


                      Universal Control Network (UCN)

              The Universal Control Network is a high speed, high security
   process
control network based on open system interconnection standards. It
   features a 5
megabit/second, carrier band, token bus network compatible with IEEE and
   ISO
standards. It is used as the real time redundant Communications backbone
   for
process connected devices such as the High Performance Process Manager
(HPM), Advanced Process Manager . The UCN supports peer-to-peer
communication for sharing data and allowing greater co-ordination of
   control
strategies among network devices. The UCN uses redundant co-axial cables
   and can
support up to 32 redundant devices
               UCN supports 2 types of devices
High Performance Process Manager
   (HPM)

The High Performance Process Manager is the latest in the Progression of
    High
Performance control products offered by Honeywell for the application to
Improve controlling of existing and new industrial processes. High
    Performance
Process Manager is a fully integrated member of the TPS family. It is
    capable
 of :
• performing data acquisition and control functions
• fully communicating with operators and engineers at the GUSs and
    universal Work stations.
• Supporting higher-level strategies available on the Local Control
    Network through the Application Module and Host Computers.
High Performance Process Manager Overview

The High Performance Process Manager uses a powerful multi-processor
    architecture
 with separate microprocessors dedicated to perform specific tasks. The HPM
    consists
 of two modules Communication and Control Module (CCM) and the I/O
    subsystem
  the I/O subsystem consist of up to 40 Smart I/O Modules (SIOM). All control
operation are performed within the communication and control module. The
    process
engineer has complete flexibility of choice within the maximum HPM design
    limits.
 These selections are implemented using the interactive tools provided by
    both the
 GUS and Universal Work Station. The I/O processors, for example, provide
    such
 functions as engineering unit conversion and alarm limit checking
    independent of the
 communication and control modules.
YOKOGAWA CENTUM EXCEL ARCHITECTURE


                   EOPS                      EOPS                    ENGG.                            Micro-XL
                    /1                        /2                    STATION

     A
     B
HF BUS
(1 Mbps)
                               EFCD                 EFMS                  EFGW

       I/O #1
        ncst
                          Closed loop          Monitoring signals         Third party system with PLC,
       I/O #2             control signal       Through I/O NEST           Gas Analyser etc. thr RS 232C port
        ncst              Through I/O NEST                                At the rate of 9600 bps


       I/O #3
                            I/O #5             HF BUS : High frequency Bus: no. of station on HF Bus are 32
                             ncst              EOPS : Extended Operator station: Hard disk capacity of EOPS is 80 MB
                                               EFCD : Extended field control
       I/O #4                                           station : 80 laps per controller
                                               EFMS : Extended field mauture
                 A B                                    station Max 255 inputs
                NIO Bus                        EFGN : Extended field gateway unit
                                               ENGS : Engineering station
                                               NIO   : Nest I/O bus.
Windows NT Based Centum CS Configuration
                                                                                               INTERPLANT
                                                                                                NETWORK PC
                                                                                                (OPTIONAL)

                                          Ethernet Connectivity (optional)
OPERATOR/ENGINEERING
     STATION

                                                     OPERATOR STATION SUB-SYSTEM




                                                                  Inkjet
       HIS      DM                 HIS       HIS
                 Printer   PRT                         PRT         Printer


                                                                                           DUAL “V NET”
                                                                                               10 Mbps
                  FCS




                                       RIO BUS
                                                                             HIS – Human Interface Station.
        NIU                      NIU                                         FCS – Field Control Station.
                                                                             NIU – Node Interface Unit.
                                                                             RIO Bus – Remote I/O Bus.
Centum CS 3000 System Overview
   Centum CS 3000 is an integrated production control system for medium
  and large control
applications. This system is a synthesis of the latest technology with
  Yokogawa’s experience
and specialist know-how.

Centum CS 3000 system features :
• Synthesis of DCS with Personal computers.
• Online Documentation.
• Powerful Operation and Monitoring Functions.
• Two Types of Control Station.
• Compact I/O Modules.
• Powerful Control and Communication Functions.
• Efficient Engineering.
• Virtual Test functions don’t require Control Station hardware.
• Full-Featured Batch Package.
• CENTUM CS micro-XL Integration ( to be released ).
Centum CS 3000 System Overview

Centum CS 3000 is an integrated production control system for medium and large control
applications. This system is a synthesis of the latest technology with Yokogawa’s experience
and specialist know-how.

Centum CS 3000 system features :

•Synthesis of DCS with Personal computers.
•Truly open system for integrating multi-vendor solutions.
•High Reliability of computed process data by the unique fault tolerant control processor.
•Powerful built in “RISC PROCESSOR” with high speed and dynamic error correcting code.
•Remote I/O concept enables geographically distribution of I/O Modules thereby reducing
  cabling cost.
•1:1 Redundancy at almost all the system levels except for control processor which employs a
  special Redundancy with 4 identical CPU’s.
•Powerful Control Tools and Communication Functions.
•Virtual Test functions don’t require Control Station hardware.
•Full-Featured Batch Package.
•Built in security features to prevent mal-operations.
•CENTUM CS micro-XL Integration ( to be released ).
CS3000 – System Configuration                                                 INTERPLANT
                                                                                              NETWORK PC
                                                                                              (OPTIONAL)

                                          Ethernet Connectivity (optional)
OPERATOR/ENGINEERING
     STATION

                                                     OPERATOR STATION SUB-SYSTEM


                                                                                   Remote Domain System

                                                                                   CGW
                                                                  Inkjet
       HIS      DM                 HIS       HIS
                 Printer   PRT                         PRT         Printer

                                                                                                      V NET

                                                                                            10 Mbps

                  FCS
                                                                             BCV


                                       RIO BUS                           CS, CS 1000
                                                                    Centum – XL, -V, -MXL
        NIU                      NIU               HIS – Human Interface Station.
                                                   FCS – Field Control Station.
                                                   NIU – Node Interface Unit.
                                                   RIO Bus – Remote I/O Bus.
                                                   CGW – Communication gateway unit
                                                   BCV – Bus Converter
CENTUM CS 3000 NETWORK


                          HIS         HIS




        HIS




                                            V net




              FCS   FCS         FCS
CENTUM CS3000 SYSTEM SPECIFICATION


•   NO. OF TAGS MONITORED         1,00,000
•   TOTAL NO. OF STATION           256
•   NO. OF DOMAINS                 16
•   NO. OF STATIONS IN A DOMAIN    64
•   NO. OF HIS / DOMAIN            16 NOS
CENTUM CS3000 SYSTEM SPECIFICATION
•   Max. no. of stations                  :      256 / system
•   Max. no. of Domains           :           16 / system
•   Numbering of Domains          :                 1 to 64
•   Domain No. CS3000 Domain
      (V net Domain)              :           1 to 16
•   Max. no. of stations/Domain       :           64
•   Domain No.Virtual Domain
      (Non V net Domain)                       :             17 to 64
•   Station NO. HIS                       :        1 to 64 in descending
    order
•   Station NO. FCS               :      1 to 64 in ascending order
•   Max. No. of ICS / Domain      :     16
•   Max. No. of NIU / FCS           :       8
•   Max. No. of IOU / FCS           :       40        ( Max. 5/ IOU)
•   Max. length of Vnet           :      20 Km
•   Max. length of RIO bus            :       20 Km (750m ~
    20Km)
Centum CS-3000 Communication
V net
   V net is 10 mbps real time control bus which links station such as FCS , HIS , BCV
   and
 CGW. It can be dual redundant. It can be up to 500m using coaxial cable alone, or
   up to 20
Km when repeater are used or optical fiber is used.

• 10BASE2 cable
     used by HIS, maximum segment length = 185 m
•   10BASE5 cable
     used by stations other than HIS(FCS,CGW etc.) maximum segment length = 500
    m
V net Communication




                                         HIS   HIS




                                                                 V net


Protocol       : IEEE802.4
Access Control : Token Passing
Trans. Speed : 10 Mbps
Trans. Distance: 500m to 20Km
Media          : Coaxial/optical fiber
                                                     FCS   FCS
V net specification


   ITEM                    SPECIFICATION
   Transmission route      Coaxial or fiber optical
                           cable
   Type                    Bus type or Multi-drop type

   Communication rate      10 Mbps

   Transmission Distance   500M –20Km Max

   Redundancy              Dual-redundant

   Proto type              Token passing
V- net Features

• Real time control bus. ( Dual redundant possible )
• Cable : 50 ohm coax. cable with BNC connector ( 10Base2
    comp. )
•   Communication speed : 10 Mbps.
•   High reliable token passing communication
      ( performance guaranteed )
•   Std. max. length : 185 m.                         BNC Connector

•   Max. length : 20 Km ( with optical fiber )
                     1.6 Km ( with coax. Repeater )
                                       VL net
                                        cable
                                                      VL net I/F card ( PCI )
Ethernet

      HIS and ENG, HIS and supervisory systems can be
 connected by an
Ethernet LAN; supervisory computers and personal
 computers on the Ethernet
LAN can access messages and trend data in the CS 3000
 system. The Ethernet
can also be used for sending trend data files from the HIS
 to supervisory
computers, or for equalizing the data in the two HIS station
 ( rather than using
the V net control bus to do this ). A system with only one
 HIS with engineering
functions installed, does not need Ethernet – but in general
 Ethernet ( and
corresponding network engineering ) is required.
Ethernet Specification

ITEM                    SPECIFICATION
Transmission Route      Coaxial or Fiber optical cable

Type                    Bus type or Multi–drop type

Communication Rate      10 Mbps

Transmission Distance   500m – 2.5 Km max.

Redundancy              Not available

Proto type              CSMA/CD Type
TYPES OF HIS


•   Console type HIS
•   Desk top type HIS
•   PHIS Yokogawa brand OPS
HIS Hardware
• CPU                 Pentium 166
• Main memory                96MB or larger(for op &
  monitoring only)
• Hard disk           1 GB or larger
• Display             256Colors min. resolution 800*600
                      1024*768 recommend(1280*1024 best)
• Serial port         RS232C*1 or more (for operation
  keyboard)
• Parallel port       1 port for printer or more
• OS                   Windows NT 4.0 Workstation
• Operator stations    Max. 8 stations
Field Control Station Configuration
                                                                         Ethernet




                  HIS                 HIS




                                                                 HIS

                                                                              V net




               I/O Unit
                                                               RIO Bus

                                        Node
                                        Interface
  Sub system                             Unit
                               Node
                                                    I/O Unit


                                                                       Sub system




                 Compact FCS                                     Standard FCS
Connection to Centum CS 3000 System


                                             Exapilot client
                                        (engineering, operation)
           Ethernet

                      HIS         ENG            Exaopc
Exapilot client
(engineering,
  operation)                                            Exapilot server
                                                    (engineering, operation)


        V-net


                                         Exapilot communication data
                                         Process data read/write

                      FCS   FCS
Features of Exapilot
•   Standardize and Automate Manual Procedures
•   Improve Plant Operating Efficiency
•   Improve safety of Plant Operation




                     Features of Event Analysis Package

• Analysis DCS Event History to Help You Enhance Efficiency.
• Enhance Process Stability: Balance Process Events and Operator Actions.
• When, Where, What (3W) Filters Help You Narrow Focus of Analysis.
OPEN DCS SYSTEM
Ethernet

           Field Bus Power Supply                         Flow Trans.

                                            Terminator


    HMI
                                                             Control Valve




                           Safety Barrier



                                                         Pressure TX.
Field bus
 It is a standardized digital communication protocol between a process
    Control field devices
and the Control room. It is a simple pair of wires to power and carry the
    communication
 signal between the field devices and the Control room.

FEATURES :
• Drastic reduction in cable, conduits cable trays, marshallive racks, and
  connectors etc.
• Drastic reduction in installation cost.
• Fewer non field devices.
• More reliability due to the smaller number of devices.
• More efficient operation due to better accuracy (no A/D and D/A
  conversion).
• Easy integration into plant management system.
• Flexibility for different suppliers are interoperable and interchangeable.
• Major reduction in maintenance cost.
Field-bus Benefits

                     Wire           Screw            I/O    IS
Wiring               (pair)         Terms           Cards   Barriers

Traditional            3500’         168              2       2
Field bus              640’           64              1       1


Savings               2860’          104              1       1
Savings %               82%           63%            50%     50%

Savings $             $ 3000 Material
                      $ 2000 Labor
                      $ 5000 Total
Typically comments from a plant personal :

•Easy to identify what’s out there.
•Consistent calibration procedure.
•Two days versus four days to commission system.
•Familiar with twisted pair wiring – comfortable.
FOUNDATION™ fieldbus Vocabulary
Blocks
         Basic Components
 Valve
                      Resource
                      Resource
                       Block
                        Block


                                      FOUNDATION™
         Transducer                     fieldbus
           (Servo)
                          Function
                          Function
            Block         Block(s)
                           Block(s)
FOUNDATION™ fieldbus Vocabulary
Blocks
         Basic Components

                           Resource
                           Resource
                            Block
                             Block


                                           FOUNDATION™
                                             fieldbus
              Transducer       Function
                               Function
                 Block         Block(s)
                                Block(s)

Temperature
Transmitter
FOUNDATION™ fieldbus Vocabulary
H1 and H2
• H1 Segment               • H2 Segment
  – Moderate speed           – High speed
  – Use existing wiring      – Link multiple H1
  – Bus powered                Segments
  – Can be intrinsically     – I/O subsystem bus
    safe                     – Replace
  – Low power 2 wire           proprietary
    devices                    networks
  – 4 wire devices           – New wiring
  – Replace analog &
    proprietary digital
FOUNDATION™ fieldbus Vocabulary
New Approach for H2
• 100 Meg Ethernet technology with extensions
  –   Improve time to market
  –   High speed
  –   Mandatory redundancy
  –   Widely available technology and silicon
  –   Widely available tools
  –   Limited incremental development
  –   Many suppliers
  –   High volume for low cost
  –   Works with installed equipment
  –   Evergreen technology
• Better than ANY other solution!
FOUNDATION™ fieldbus Vocabulary
H1/H2 Bridges

                   Server
                            H2 Segment 100 Meg Ethernet
                             Control   PLC
                   H1/H2     Module
                   Bridge
H1/H2 Bridge
 H1/H2 Bridge                                  H1 Segment
  Replaces
   Replaces
Traditional I/O
 Traditional I/O
                                  H1 Segment


          H1 Segment
FOUNDATION™ fieldbus Standards
Organizations

• IEC
  – International Electro-technical Commission
• ISA
  – International Society for Measurement and Control
    (formerly: Instrument Society of America)
      • SP50
• CENELEC
  – European standards body
     • Parallel (competitive?) Working Groups to IEC
FOUNDATION™ fieldbus Topography
      H1 Fieldbus Installations
                                                                       Cost savings:
                                                                        Cost savings:
                                                                          •• wiring
                                                                              wiring
                                                                          •• I/O cards &
                                                                              I/O cards &
                 Controller                                                  cables
                                                                              cables
 Similar I/O Cards                        Reduced Wiring    Junction      •• terminations
                                                                              terminations
  Similar I/O Cards             H1 I/O     Reduced Wiring   Box           •• IS barriers
                                Interface                                     IS barriers
                                                                          •• marshaling
                                                                              marshaling
                                H1 I/O
                                Terminations
                                                                       FewerTerminations
                                                                        FewerTerminations
                                   H1 Fieldbus
                                   all-digital

                                Marshaling              H1 Fieldbus
                                                         all-digital


Fewer Terminations
 Fewer Terminations              IS (Ex i)
                                 Barriers


           Fewer IS barriers
            Fewer IS barriers
FOUNDATION™ fieldbus Topography
Intrinsic Safety




          Barriers
DeltaV System Architecture
                      Engineering station                                     Operator station
       Printer                                               Printer




                                  8 port Hub                            8 port Hub
                                    primary                               Redundant

                                                                                                                               1
2 wide carrier for                                                     8 wide carrier for
Power/Controller P            P                     A AA DDD            I/O subsystem
                     Contr.


                                  Contr.
                                           Serial




                 S            S                     I I O I I O


Power supply                                                                                                                  H1
  Controller                                                       I/O extension cable                                     Connector

                                       RS232 Modbus

                     PLC For
                                                           Blank




                                                                          H
                                                           Blank

                                                           Blank


                                                           Blank




                                                       D
                                                           Blank

                                                           Blank




                     8 DI &
                      8 DO                             O
                                                                          I
                                                                                            Fieldbus Transmitter   Pressure Transmitter
                                                                                            3244MVF1NAB4           3051TG2A2B21AB4M5FF
                                                                                                                                   Smart valve positioner
                                                                                                                                   FSDVC0400-201
                                                                         Fieldbus Power
DCS communication system Hierarchy
        Level 5
        Management                                 MIS
        Low data rates
                                                                                    High
        Superior responsibility


       Level 4
       Scheduling
                                               SCHED.
                                                                                    Low


    Level 3
    Supervisory control           SUP.                               SUP.


  Level 2
  Direct digital
  Control (DDC)          DDC                 DDC             DDC                DDC
Level 1
Sensors (S)
& Actuators (A)
High data rates      S        A   A      S         A     S   S   S    A     S   S   A
Low responsibility
                                               PLANT
History of Process Control Signal
          Around 50 years ago, most plant used 3-15psi pneumatic signal to control their
    process.
 The last change change in signal standard was the open protocol HART digital
    communications
 format. The HART protocol provides simultaneous digital communications with the 4-20
    mA
 output.
            The next protocol change will be fieldbus. Fieldbus is entirely digital-there is
    no analog
Signal. Fieldbus also allows migration of control functions to field devices.
               Process control Timeline – The Evolution of Signal Standard
          Signal standards have evolved over the years, starting with the 3-15 psi
    standard.
 There are also other communication methods, but they have not gained widespread
                                                                             Digital: Fieldbus
    acceptance.                                         Digital plus Analog: HART with 4-20mA
          With many standard there is typically a slow transition period as plant
                                Analog: 4-20mA
    engineers and
        Pneumatic: 3-15 psi
 managers test period does gain widespread acceptance. However, once the benefits of
    the
     1940             1950   1960      1970    1980      1990            2000              2010
 Fieldbus become tested and proven, more plant will install Fieldbus because of its
I/O Bus Network Protocol

                        I/O Bus Network

            Device bus network    Process bus network




        Discrete                                   Analog




Byte-wide          Bit-wide                  Several Hundred
  Data               data                       Data Bytes
Protocol Standard

                           Field Bus Foundation
                            (Field Bus std.)
Process bus network
                           Profibus Trade Organization
                             (Profibus std.)


                                                       Device net
                      Byte-Wide    CAN Bus
                          Data                         SDS
                                         Inter Bus-S
Device bus network                       Seriplex
                      Bit-Wide
                          Data           ASI

                                         Inter Bus Loop
Fieldbus Architecture
Fieldbus is more than just a new signal communications protocol, but a whole new way
    to
 control the process. With the release of the low fieldbus (H1), the entire fieldbus will
    be
 defined. Most of the recent published literature has focused on the intricate details of
    the
 fieldbus architecture, especially those layers that have not been released. However,
    except                                         Maintenance
                                   Workstation     information
 physical layer and the user layer, these layer are transparent to the engineers and the
                                                   system
    manager.
                                     User Layer




                                                                            System management
                                                       Network Management
                                 Application Layer




                                                                                                stack
                                    Data Layer


                                  Physical Layer




                          Multivariable Valve      Level     Pump
                          Transmitter               Transmitter
Open System Interconnected Reference
    Model

               MBAP, SMB, FTP, SMTP, FMS,        Physical – Provides the standard for transmitting raw
Application                                      electrical signals over the communication channels.
               IEC 61158, ANSI/ISA S50.2,IEEE 1451
Presentation                                     Data link – Contains the rule for interpreting electrical
                                                 signals as data, error checking and physical addressing
  Session                                        Network – Describes the rule for routing messages
 Transport     TCP, SPX, UDP                     through a complex network and deals with congestion.
                                                 Transport – Establishes a dependable end-to-end
  Network      IP, IPX, NetBeui
                                                 connection between two host.
               HDLC, ETHERNET, ANSI/ISA S50.02 Session – provides Management and Synchronization
 Data link
                                                 of complex data transaction.
  Physical     EIA-485, ETHERNET,ANSI/ISA S50.02
                                                 Presentation – Establishes protocol for data format
                                                 conversion, encryption and security.
                                                 Application – Contains protocol that accomplish task
                                                 such as e-mail, file transfer or reading a set of registers
                                                 from a PLC.




       For the purpose of Process control, the top and bottom four layers are used.
        Layers 5 and 6 are important to large commercial networks.
Field Bus
Field Bus is a bi-directional digital communication that interconnects smart field
    devices to
 control system or to instrument located in the control room.
Field Bus is based on the OSI (Open System Interconnect), which was developed by
    the ISO
(International Standard Organization) to represent the various functions required in
    any
                                      Layer              Function
Communication network.
                     7            Application         Provides formatted
                                                      data
                     6            Presentation        Converts data

                     5            Session             Handles the dialogue

                     4            Transport           Secures the transport
                                                      connection
                     3            Network             Establishes network
                                                      connections
                     2            Link                Establishes the data
                                                      link connection
                     1            Physical            Connects the
                                                      equipment
Field Bus




 The OSI model consists of seven layers. However for real time application
   layers 3 to 6 are
  not considered since they deal with transference of data among networks.
   For such
  application following layers are used:
• LAYER 1 - PHYSICAL LAYER
     Defines the type of signal, transmitting medium, data transmission
   speed, etc.
• LAYER 2 – DATALINK LAYER
   Define the interface between the physical layer and the application layer.
   It establishes
     how the messages shall be structured and normalizes the use of
   multiple masters.
• LAYER 3 – APPLICATION LAYER
   Defines howwas invented by an Indian engineer Mr. Ramrepresentation.
    The Fieldbus data is specified, its addresses and its Ramchandran
                                                  ( M.S in Comp. Tech , Texas)
PHYSICAL LAYER
The Physical layer defines the medium that transport the messages frames, the signal
    shape and
 amplitude limits, data transfer rate, and power distribution.
Technical Characteristics:
Physical Medium
          Three types are defined: wires, optic fiber, and radio signals. The
    specification for
          wire has been already approved.
Bit rate for wire media
          31.25 Kbps (H1)
          1 megabits and 2.5 megabits (H2).
          H1 and H2 are classification of the two hanks of Field Bus target applications.
    H1 has
          low speed and utilizes existing wires. H2 has high speed and may require
    independent
          wires to power up field devices.
Number of devices per link (31.25Kbps)
          2 to 32 devices, without power and no IS (intrinsic safety).
          2 to 6 with power and IS.
Maximum distance
          Up to 1900 meters for 31.25Kbps, without repeaters. Up to 750 meters for 1
          megabits. Up to 500 meter for 2.5 megabits.
PHYSICAL LAYER
Signal Modulation
        Manchester bi phase L synchronous.

Physical layer preamble
          on transmissions, the physical layer will add to the data sent by the layer
   above a
          preamble and one start delimiter in the beginning of the frame and one end
   delimiter
          at the end delimiter at the end of the of the frame.
DATA LINK LAYER
The Data Link Layer will assure the integrity of the message by using the frame check
   sequence:
Two bytes added to the frames and a polynomial calculation of all frame data.
The Data Link Layer also checks to see that the data reaches the devices correctly.

Technical characteristics
Medium Access: There are three forms to access the network:
• Token passing:
         Token is the right to initiate a transaction on the bus. A device must have the
   token to
         initiate a conversation. As soon it finishes it will return the token to the LAS
   (Link
         Active Scheduler). The LAS send the token to the unit that requested in either
   in a
         pre-configured way or via scheduling.
• Immediate response:
         A master station will give an opportunity to the station to reply with one frame.
• Requested token:
         a device request a token by using a code in any of the response sent to the
   bus. The
APPLICATION LAYER AND MANAGEMENT

The Application Layer provides a simple interface to the end user’s application.
    Basically , it
 defines how to read, write , interpret and execute a message or command. A
    big part of this job
 is to define the message syntax. The contents include the requested message,
    action taken, and
 the response message.

The management defines how to initialize the network : tag assignment,
   address assignment,
clock assignment, clock synchronization, distributed application scheduling
   across the network
or association of the input and output parameters of the function blocks. It
   also controls the
operation of the network with statistic of faults and detection of the addition of
   the new element
or the absence of a station. The system always look for the new stations on
   the bus by polling
the possible station addresses.
Digital Communication Protocol
ISO             - International Standard Organization. Responsible for developing
   the
                   model that the communication specification are based upon as
   well as
                    standards for each layer of communication specification.
IEEE            - Institute of Electrical and Electronics Engineers. Formed the IEEE
   802
                   project for defining standards for network media and access
   methods.
SP72            - Institute Society of America, Standards and Practice committee
   Number 72
                   Developing EIA1393 companion standard for process control
   messaging.
SP50            - Institute Society of America, Standards and Practice committee
   Number 50
                   Developing standards for digital communication between field
    devices.
F.I.P            - Factory Information Protocol, approved French National Standard.
Profibus        - Process Fieldbus, approved German National Standard.
HART COMMUNICATION PROTOCOL
Why HART protocol ?
 4-20 ma is tried, tested and widely used standard but only limited amount of
       information
  is sent by a 4-20 ma signal.
 HART (Hiway Addressable Remote Transducer) protocol enhances these
       operations by
  transmitting digital data along with the 4-20 ma signal – without interfering with
       it !
 HART permits two-way communications. It also has all digital mode that allows
  instrument to be connected to a single cable, cutting installation costs
       dramatically.

Features :
    1. Field proven concept that is easy to understand and use.
    2. Compatible with existing 4-20 ma systems.
    3. Simultaneous point-to-point 4-20 ma and digital communication.
    4. Alternative multi-drop mode.
    5. Measured variables, tag no. , range and span settings, device
        information, diagnostics and simple messages transmitted.
    6. Digital response time of 500 msec; burst mode response of 300 msec.
    7. Open architecture; freely available to any vendor and every user.
HART COMMUNICATION PROTOCOL
Method of Operation :
 The Hart protocol operates using the FSK principal. The digital data is
  made up from two
  frequencies –1200 Hz and 2200 Hz representing bits 1 and 0
  respectively. Sinusoidal
  waves of these frequencies are superimposed on the DC analog signal
  cables to give
  simultaneous analog and digital communications




HART Protocol Structure :
 HART follows the basic Open Systems Interconnection (OSI) reference
  model, developed
 by the International Organization for Standard (ISO). The HART protocol
  uses a reduced
 OSI model, implementing only layers 1,2 and 7
HART COMMUNICATION PROTOCOL
                                OSI reference model
Open Systems Interconnections

                 LAYER               FUNCTIONS             HART
       7         Application         Provides formatted HART instructions
                                     data
       6         Presentation        Converts data

       5         Session             Handles the
                                     dialogue
       4         Transport           Secures the
                                     transport
                                     connection
       3         Network             Establishes
                                     network
                                     connections
       2         Link                Establishes the    HART protocol
                                     data link          regulations
                                     connection
       1         Physical            Connects the       Bell 202
HART PROTOCOL LAYERS
Layer 1, the physical layer, operates on the FSK principle
   Data transfer rate: 1200 bit/s
   Logic “0” frequency: 2200 Hz
   Logic “1” frequency: 1200 Hz
 the vast majority of existing wiring is used for this type of digital communication.

Layer 2, the link layer establishes the format for a hart message. HART is a
   master/slave
 protocol.
  the structure of these messages is given below:
          Preambl SD       AD     CD    BC    Statu   Dat    Parity
          e                                   s       a


 SD – start character.                      AD – display terminal and field
  addresses.
 CD – HART instruction.                 BC – Byte count.
  Status – Field device and communication status (only from field device to
  master)
  The individual characters are : 1 start bit, 8 data bits, 1 bit for odd parity and 1
HART PROTOCOL LAYERS


Layer 7, the application layer, brings the HART instruction into play. The master
  sends
 messages with requests for specified values, actual values and any other data or
  parameters
 available from the device. The field device interprets these instruction as defined
  in the
HART protocol. The response message provides the master with the status
  information
 and data from the slave.
For slave devices, logical uniform communication is provided by the following
  command
 sets:
  Universal commands – understood by all field devices.
  Common practice commands – provide functions which can be carried out by
  many,
     though not all, field devices.
  Drive-specific commands – provide functions which are restricted to an
  individual
HART PROTOCOL – TECHNICAL DATA
DATA TRANSMISSION
 Types of data transmission            :   Frequency shift keying (FSK)
 Transfer rate                          :    1200 bit/s.
 ‘0’ bit information frequency        :   2200 Hz
 ‘1’ bit information frequency        :   1200 Hz
 Signal structure                       :   1 start bit, 8 data bits, 1 bit for
   odd parity, 1 stop bit.
 Transfer rate for simple variables   :     Approximately 2/s (poll/response)

DATA INTEGRITY
 Physical layer        : Error rate destination circuit : 1/(10^5)
 Link layer             : Recognizes : all groups up to 3 corrupt bits and
   practically all longer
                              and multiple groups.
 Application layer : Communication status terminated in a response
   message.
MODBUS
          The MODBUS protocol describes an industrial communication and
 distributed
control system developed by Gould-Modicon. MODBUS is a Master/Slave
communications protocol, whereby one device (Master), controls all serial
 activities by
selectively polling one or more slave devices. The protocol provides for one master
 device
and up to 247 slave devices on a common line. Each device is assigned an
 address to
distinguish it from all other connected device.
          Only a master initiates a transaction. Transactions are either a
 query/response type,
or a broadcast/no-response type. A transaction comprises a single query and
 single
response frame or a single broadcast frame.
          Certain characteristic of a MODBUS protocol are fixed such as frame
 format, frame
sequences, handling of communication errors and exception conditions, and the
 functions
performed.
RS-232 Communication



         RS-232 is an asynchronous communication network. Normally, a binary
   system is
used to transmit data in ASCII (American Standard Code for Information
   Interchange)
format. This code translates human readable code (letter/numbers) into “computer
   readable”
code(1’s and 0’s).
         There are 2 types of RS-232 devices. The first is called a DTE (Data Terminal
Equipment) device and a common example is a computer. The other type of device is
   called
DCE (Data Communication Equipment) device and a common example is a modem.
         In RS-232 the first thing a terminal send is start bit. This start bit is a
   synchronizing
bit added just before each character being send. The last thing send is a stop bit.
   This stop bit
informs to the receiving terminal that the last character has just being send.
RS-232 Communication
RS-232 communication is done through Serial port which usually has a 9-pin
 configuration. The pin and their purposes are shown below.


            9-PIN          PURPOSE
                 1         Frame ground
                 2         Receive data (RD)
                 3         Transmit data (TD)
                 4         Data terminal ready (DTR)
                 5         Signal ground (GND)
                 6         Data set ready (DSR)
                 7         Request to send (RTS)
                 8         Clear to Send (CTS)
                 9         Ring indicator (RI) *only for modems*
PC-to-PC Communication through Serial Port


 CD 10                            01   CD

RXD 20                            02   RXD
TXD 30                            03   TXD

DTR 40                            04   DTR

GND 50                            05   GND

DSR 60                            06   DSR

RTS 70                            07   RTS

CTS 80                            08 CTS

 RI 90                            09 RI


              9-Pin D Connector
PC-to-PC Communication through LPT1 Port
       1                  1
       2                  2
       3                  3
       4                  4
       5                  5
       6                  6
       7                  7
       8                  8
       9                  9
       10                 10
       11                 11
       12                 12
       13                 13
       14                 14
       15                 15
       16                 16
       17                 17
       18                 18
       19                 19
       20                 20
       21                 21
       22                 22
       23                 23
       24                 24
       25                 25
Flavours of Internet Telephony

PC-to-PC
                                           The
                                         Internet

                                                                    PC
        PC
              Dial-up or Local ISP                    Local ISP
              Leased Line

PC-to-Phone

                                           The
                                         Internet
        PC                                                               Phone

                            Local ISP                 Local ISP
                                                    Voice Gateway

Phone-to-Phone     Access
                   Code

                                          The
                                        Internet
           Phone                                                         Phone
                                                      Local ISP
                          Local ISP
                        Voice Gateway               Voice Gateway
APACS - Operation Platform
Database Ownership


Operator Console   Engineer Console    Operator Console         Console Level




                                                          Controller Level
                   Controller Module




                                                                 I/O Level
                    I/O Modules
                                                               •TAGS
                                                               •Range
                                                               •Engineering Unit
     Transmitter          Interlock          I/P Valve         •Diagnostics
TODAYS INDUSTRIAL SYSTEMS

                                                          Planning
Application       HMI           -----------------------
                                                           HMI

 Drivers      1         2   3                             4   5     6




    Devices

                                                              I/O
                  PLC                   DCS
PC Based Industrial Systems



OPC Client
                                                                   Planning
 Application
                HMI           ----------------------------------
                                                                    HMI

   OPC
   Server
            1         2   3




     Devices
                                                                       I/O
                PLC                       DCS
Enterprise Automation Schemes



                                         Windows NT


Corporate
 IT Network

                                         Windows NT


    Server




Control
 network                              Embedded
                                      Real System
Windows NT (“New technology”)
FEATURES:
• A true 32 bit processing.
• A very reliable operating system.
• Real operating system.

TECHNICAL ASPECT:
• Multiprocessing, Multithreading and partitioned memory space.
• Security - C2 compliance.
• In-built networking.
• Internationalization .
• Human interface as Windows 95.
• Object - based : DCOM/OLE - ActiveX.
• for special need of the process industries. DCOM and OLE are not robust,
   deterministic and secure.
• Client - Server architecture.
Windows NT Interconnectivity
Transparent inter-connectivity to typical business systems in plants:
         1) ODBC : It provides access to most SQL databases.
         2) ActiveX/OLE : Supports data access between application and
   embedding of
                                one applications function within another.
        3) DDE : Dynamic Data Exchange supports simple data exchange
   between
                     applications such as plant data populating an Excel spread
   sheets.
Windows NT features
 Windows NT is gaining ground in open control because of the following advantages :
• User acceptance.
• Corporate interoperability
• Ease of use.
• Connectivity.
• Scalability for small and large application.


    However, Windows NT has the following disadvantages :
•   Needs a lot memory and processing power.
•   Optimized for office, not control, requirements.
•   Requires a disk drive which may fail.
•   Depends on single vendor.
•   Reboots at unexpected times
•   Unstable operating system.
Embedded control Operating System - QNX
QNX real-time operating system, has evolved from the first-ever micro-kernel
     operating
system for PCs into one of the best selling and most trusted operating systems for
     mission
critical application. Today, QNX is the real time operating system in industrial
     automation,
 hand held devices, controllers and soft PLCs


QNX is recognized as :
• The fastest and most dependable real time operating system.
• The most proven high speed, deterministic real time kernel.
• Having a hard real time engine that gives PLC-style control.
• Enabling data acquisition with milliseconds resolution.
• Providing a fault-tolerant architecture on which you can run control, events,
  alarms in a virtually crash-proof environment.
Windows NT - for Process control
Windows NT features :
• A true 32 bit processing.
• A very reliable operating system.
• Real operating system.
• Multiprocessing, Multithreading and partitioned memory space.
• Security - C2 compliance.
• In-built networking.
• Internationalization.
• Human interface.
• Object-based DCOM/OLE :
       The sending object is shown as client and receiving object is known as
   server. The
       MS technology allows any developer to produce small, self contain objects
   that have
       “packaged” visual component and specific action. These components are
   called
       “ActiveX” objects. NT’s OLE technology is part of Microsoft’s Distributed
       Component Object Model (DCOM) operating across networks. Anyone can
   develop
      ActiveX Object using VC++ or even VB on a PC. For special needs of the
   process
     control industries DCOM and OLE are not secure, deterministic and robust
   enough.
Ethernet
       Ethernet was originally designed by Digital, Intel and Xerox (DIX) in the early
     1970’s
and has been designed as a broadcast system. The original format for Ethernet was
     developed
in Xerox Palo Alto Research center (PARC), California in 1972. The two inventors
     were
Robert Metcalf and David Boggs.
       Ethernet version 1.0 and 2.0 followed until the IEEE 802.3 committee re-
     jigged the
Ethernet II packet to form the Ethernet 802.3 packet. Nowadays you will see either
Ethernet II (DIX) format or Ethernet 802.3 format being used.
       The ‘Ether’ part of Ethernet denotes that the system is not meant to be
     restricted only to
one medium type, copper cables, fiber cables and even radio waves can be used.
       Briefly, stated Ethernet what is referred to as the Physical layer and the Data-
     link layers
protocols. The physical layer defines the cable types, connectors and electrical
     characteristics.
The Data link layer defines the format an Ethernet frames, the error checking
     method and the
Ethernet
10Base5
       Traditionally, Ethernet is used over ‘thick’ coaxial cable called 10Base5 (
   the 10
denotes 10 Mbps, base means that the signal is baseband i.e, takes the whole
   bandwidth
of the cable, 5 denotes 500m maximum length ). The minimum length
   between stations
is 2.5m.
       The cable is run in one long length forming a ‘Bus Topology’. The
   segments are
terminated by 50 ohm resistor and the shield should be grounded at one end
   only.


10Base2
     Thin Ethernet (Thinnet) uses RG-58 cable and is called 10Base2 (the 2
  denotes
200 mtr maximum length cable). Each station connects to the Thinnet by way
  of
Ethernet



10BaseT
       Nowadays, it is becoming increasingly important to use Ethernet across
   Unshielded
Twisted Pair (UTP) or Shielded Twisted Pair (STP), this being called 10BaseT (the T
denotes twisted pair). UTP is installed in star wire format and Ethernet Hubs with
   UTP ports
(RJ45) centrally located. Also there should be no more than a 11.5db signal loss and
   the
minimum distance between devices is 2.5 meters.
      The advantages of the UTP/STP technology are gained from the flexibility of
   the
system, with respect to moves, changes, fault finding, reliability and security.

10BaseF
       10BaseF standard developed by IEEE 802.3 committee defines the use of Fiber
   for
 Ethernet. 10BaseFB allows up to 2 Km per segment and is defined for Backbone
Ethernet

The following table shows the RJ45 pin outs for 10BaseT :

             RJ45 Pin           Function           Colour
                      1             Transmit       White/Orange

                      2             Transmit       Orange/White

                      3             Receive        White/Green

                      4                            Blue/White

                      5                            White/Blue

                      6             Receive        Green/White

                      7                            White/Brown

                      8                            Brown/White
PC-to-PC Communication through
Ethernet

     RJ45                 RJ45
       1                   1

       2                   2

       3                   3

       4                   4

       5                   5

       6                   6

       7                   7
       8                   8
Ethernet Topology
   Segmented (star) topology                                 Bus topology




Workstation             Workstation            Workstation            Workstation




                          Switched Hub




                                                                    Controller

                                         Controller
   Controller            Controller
Wireless LAN
Wireless LAN is based on standard IEEE 802.11b which throughput of up to 11Mbps in
    the
2.4 Ghz band. Similar Wireless Personal Area Network (WPAN) are Bluetooth and
    Infrared.
   Ethernet works on the CSMA/CD technology but wireless LAN has difficulty of
    detecting
collision in Radio frequency. Therefore they are using CSMA/CA (Collision Sense Multiple
Access / Collision Avoidance) technology to transmit data. Physical Layer is either
    Photonic or
Radio frequency.
Process control Software characteristics
 The most important feature of process control system is that it needs to be
      reliable. The
process control system used has to be completely crash-proof and any changes in
      the
system need to be made on-line.
 The process control needs to be made real time, which means that it can
      update the I/O
data table and process the control program in the time required by the process.
 A process control system that is deterministic refers to whether the operating
      system
allows the highest priority task to work without interruption from task with lower
      priority.
 Software offerings in the automation and the process control fields must be
      versatile and
open enough to address the needs of different applications.
 Finally the chosen solution must deliver tangible, quantifiable values such as :
1. Reducing project implementation time and cost.
2. Improving time-to-market.
3. Achieving higher production and quality.
4. Cutting maintenance and training cost.
PC-based control system features
  Unlike the other systems, PCs provide a more open architecture making them ideal
    for
 improving, optimizing and integrating the overall automation process, as well as
    conducting
 control task.
  In addition PCs offer the following features :
• Lower cost.
• Ease of use.
• Graphical user interface.
• Easy integration of logic, motion and process control.
• Simplified application development.
• Software portability
• Independence from proprietary control system.
  Using PCs enable the following functions,
• Millisecond time stamping which is essential to utilities.
• Real time control.
• Sequence of events.
• Alarming.
• Data collection.
PLC conceptual overview

                                        SCADA
Process    History &    Alarm &                        Other Aspect
                                      configuration
Graphics    Trend        Events                           system
                                         editor


                       OP Client                SCADA Control
                                                   Aspect


                             OPC server


                                             SCADA           Real-time
                                              server          database


                                                        Protocol Protocol
                          opc      Modbus    comli         xx       yy

                                   Siemens    Allen      GE
                       ABB                   Bradley    Fanuc     ….
PLC Programming Standards


              The open, manufacturer-independent programming standard for
  automation is
IEC 61131-3. You can thus choose what configuration interface you wish to use
  when
writing your application :

•   Ladder Diagram
•   Instruction List
•   Function Block Diagram
•   Sequential Function Chart
•   Structured Text

                All users, be they plant electrician or computer scientists, thus have
    a configuration interface in which they can feel at home.
Industrial IT Trends

The availability of information is becoming increasingly crucial in the view of growing
       global
 competition. In future, a decisive competitive edge can only be achieved by providing
       the
 right information at the right time, in the right place and in the right form for the right
       person.
 these leading- edge application are continuously optimized and repositioned.
 Industrial IT consists of five components:

              1.   Engineering IT
              2.   Operation IT
              3.   Production IT
              4.   Optimization IT
              5.   Evolution / Information
Industrial IT Trend


                                                                         Business
                 Sales &                                                 Systems
                 Marketing



Planning &




                                                    e-PROD
Scheduling

                         Real-time                                              ION
                                                                      OPTIMIZAT




                                                           UCTIVI
                       Automation &         ASSET
Plant &                 Information




                                                                 TY
Process Eng.




   Operation &
   Maintenance               Distribution
                                                               Plant
Distributed Control System Basics

Más contenido relacionado

La actualidad más candente

DCS - Distributed Control System
DCS - Distributed Control System DCS - Distributed Control System
DCS - Distributed Control System Pratheep M
 
Scada system ( Overview )
Scada system ( Overview )Scada system ( Overview )
Scada system ( Overview )Ali Al Sarraf
 
Practical Distributed Control Systems (DCS) for Engineers and Technicians
Practical Distributed Control Systems (DCS) for Engineers and TechniciansPractical Distributed Control Systems (DCS) for Engineers and Technicians
Practical Distributed Control Systems (DCS) for Engineers and TechniciansLiving Online
 
PLC, DCS and PLC vs DCS Presentation by Jitender Singh Shekhawat
PLC, DCS and PLC vs DCS Presentation by Jitender Singh ShekhawatPLC, DCS and PLC vs DCS Presentation by Jitender Singh Shekhawat
PLC, DCS and PLC vs DCS Presentation by Jitender Singh ShekhawatJitender Singh Shekhawat
 
BASICS OF FIELDBUS
BASICS OF FIELDBUSBASICS OF FIELDBUS
BASICS OF FIELDBUSShivam Singh
 
What Is a Programmable Logic Controller (PLC)
What Is a Programmable Logic Controller (PLC)What Is a Programmable Logic Controller (PLC)
What Is a Programmable Logic Controller (PLC)yogesh8418
 
YOKOGAWA CENTUM CS 3000 R3
YOKOGAWA CENTUM CS 3000 R3YOKOGAWA CENTUM CS 3000 R3
YOKOGAWA CENTUM CS 3000 R3Rehan Fazal
 
Honeywell Experion HS
Honeywell Experion HSHoneywell Experion HS
Honeywell Experion HSShivam Singh
 

La actualidad más candente (20)

Dcs vs scada
Dcs vs scadaDcs vs scada
Dcs vs scada
 
DCS Or PLC
DCS Or PLCDCS Or PLC
DCS Or PLC
 
All about scada
All about scadaAll about scada
All about scada
 
DCS an overview
DCS an overviewDCS an overview
DCS an overview
 
DCS - Distributed Control System
DCS - Distributed Control System DCS - Distributed Control System
DCS - Distributed Control System
 
DCS
DCSDCS
DCS
 
Scada system ( Overview )
Scada system ( Overview )Scada system ( Overview )
Scada system ( Overview )
 
Dcs course
Dcs courseDcs course
Dcs course
 
Practical Distributed Control Systems (DCS) for Engineers and Technicians
Practical Distributed Control Systems (DCS) for Engineers and TechniciansPractical Distributed Control Systems (DCS) for Engineers and Technicians
Practical Distributed Control Systems (DCS) for Engineers and Technicians
 
PLC, DCS and PLC vs DCS Presentation by Jitender Singh Shekhawat
PLC, DCS and PLC vs DCS Presentation by Jitender Singh ShekhawatPLC, DCS and PLC vs DCS Presentation by Jitender Singh Shekhawat
PLC, DCS and PLC vs DCS Presentation by Jitender Singh Shekhawat
 
BASICS OF FIELDBUS
BASICS OF FIELDBUSBASICS OF FIELDBUS
BASICS OF FIELDBUS
 
SIEMENS S7-300c.ppt
SIEMENS S7-300c.pptSIEMENS S7-300c.ppt
SIEMENS S7-300c.ppt
 
CENTUM CS300 R3
CENTUM CS300 R3CENTUM CS300 R3
CENTUM CS300 R3
 
Automation(plc&scada)
Automation(plc&scada)Automation(plc&scada)
Automation(plc&scada)
 
DCS Introduction
DCS IntroductionDCS Introduction
DCS Introduction
 
What Is a Programmable Logic Controller (PLC)
What Is a Programmable Logic Controller (PLC)What Is a Programmable Logic Controller (PLC)
What Is a Programmable Logic Controller (PLC)
 
What is hmi
What is hmi What is hmi
What is hmi
 
YOKOGAWA CENTUM CS 3000 R3
YOKOGAWA CENTUM CS 3000 R3YOKOGAWA CENTUM CS 3000 R3
YOKOGAWA CENTUM CS 3000 R3
 
Honeywell Experion HS
Honeywell Experion HSHoneywell Experion HS
Honeywell Experion HS
 
Scada ppt
Scada  pptScada  ppt
Scada ppt
 

Destacado

Ratio control
Ratio controlRatio control
Ratio controlsaki909
 
Process Instrumentation & Control
Process Instrumentation & ControlProcess Instrumentation & Control
Process Instrumentation & ControlZin Eddine Dadach
 
cascade and ratio control word doc
cascade and ratio control word doccascade and ratio control word doc
cascade and ratio control word docUmer Farooq
 
Scada
ScadaScada
ScadaTribi
 
When is a SIL Rating of a Valve Required?
When is a SIL Rating of a Valve Required?When is a SIL Rating of a Valve Required?
When is a SIL Rating of a Valve Required?ISA Interchange
 
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management SystemA CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management SystemHashim Badat
 
Matematica slides tx2
Matematica slides tx2Matematica slides tx2
Matematica slides tx2educacao f
 
Basics Of Instrumentation
Basics Of InstrumentationBasics Of Instrumentation
Basics Of InstrumentationVinoth Ganesh
 
Electro magnetic interference and compatibility(ECM,ECI)
Electro magnetic interference and compatibility(ECM,ECI)Electro magnetic interference and compatibility(ECM,ECI)
Electro magnetic interference and compatibility(ECM,ECI)Palani murugan
 
Controller Area Network (Basic Level Presentation)
Controller Area Network (Basic Level Presentation)Controller Area Network (Basic Level Presentation)
Controller Area Network (Basic Level Presentation)Vikas Kumar
 

Destacado (19)

Ratio control
Ratio controlRatio control
Ratio control
 
Ratio control system
Ratio control systemRatio control system
Ratio control system
 
Process Instrumentation & Control
Process Instrumentation & ControlProcess Instrumentation & Control
Process Instrumentation & Control
 
cascade and ratio control word doc
cascade and ratio control word doccascade and ratio control word doc
cascade and ratio control word doc
 
Scada
ScadaScada
Scada
 
When is a SIL Rating of a Valve Required?
When is a SIL Rating of a Valve Required?When is a SIL Rating of a Valve Required?
When is a SIL Rating of a Valve Required?
 
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management SystemA CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
 
Valves used in industry
Valves used in industryValves used in industry
Valves used in industry
 
Matematica slides tx2
Matematica slides tx2Matematica slides tx2
Matematica slides tx2
 
Boiler explosion at exxon mobil singapore
Boiler explosion at exxon mobil singaporeBoiler explosion at exxon mobil singapore
Boiler explosion at exxon mobil singapore
 
Safe Operation and Explosions in Boilers
Safe Operation and Explosions in BoilersSafe Operation and Explosions in Boilers
Safe Operation and Explosions in Boilers
 
107 basic instrumentation
107 basic instrumentation 107 basic instrumentation
107 basic instrumentation
 
Caldeiras
CaldeirasCaldeiras
Caldeiras
 
Boiler Maintenance & Safety
Boiler Maintenance & SafetyBoiler Maintenance & Safety
Boiler Maintenance & Safety
 
Basic instrumentation
Basic instrumentationBasic instrumentation
Basic instrumentation
 
Basics Of Instrumentation
Basics Of InstrumentationBasics Of Instrumentation
Basics Of Instrumentation
 
Embedded Systems in Automotive
Embedded Systems in Automotive Embedded Systems in Automotive
Embedded Systems in Automotive
 
Electro magnetic interference and compatibility(ECM,ECI)
Electro magnetic interference and compatibility(ECM,ECI)Electro magnetic interference and compatibility(ECM,ECI)
Electro magnetic interference and compatibility(ECM,ECI)
 
Controller Area Network (Basic Level Presentation)
Controller Area Network (Basic Level Presentation)Controller Area Network (Basic Level Presentation)
Controller Area Network (Basic Level Presentation)
 

Similar a Distributed Control System Basics

DISTRIBUTED CONTROL SYSTEMS BASICS.
DISTRIBUTED  CONTROL     SYSTEMS  BASICS.    DISTRIBUTED  CONTROL     SYSTEMS  BASICS.
DISTRIBUTED CONTROL SYSTEMS BASICS. Ashok Kumar Barla
 
Ls catalog thiet bi tu dong master p 5000-e_dienhathe.vn
Ls catalog thiet bi tu dong master p 5000-e_dienhathe.vnLs catalog thiet bi tu dong master p 5000-e_dienhathe.vn
Ls catalog thiet bi tu dong master p 5000-e_dienhathe.vnDien Ha The
 
Ls catalog thiet bi tu dong master p 5000-e
Ls catalog thiet bi tu dong master p 5000-eLs catalog thiet bi tu dong master p 5000-e
Ls catalog thiet bi tu dong master p 5000-eDien Ha The
 
Can based collision aviodance system for automobiles
Can based collision aviodance system for automobilesCan based collision aviodance system for automobiles
Can based collision aviodance system for automobilesPurnima Kurella
 
PLC Introduction Details
PLC Introduction DetailsPLC Introduction Details
PLC Introduction Detailssuhaskhadake
 
Networking of multiple microcontrollers
Networking of multiple microcontrollersNetworking of multiple microcontrollers
Networking of multiple microcontrollersEdgefxkits & Solutions
 
X tel gsm-wcdma-datasheet
X tel gsm-wcdma-datasheetX tel gsm-wcdma-datasheet
X tel gsm-wcdma-datasheetDlip Nyk
 
02 umts network architecturenew
02 umts network architecturenew02 umts network architecturenew
02 umts network architecturenewsivakumar D
 
Introduction to DSP Processors-UNIT-6
Introduction to DSP Processors-UNIT-6Introduction to DSP Processors-UNIT-6
Introduction to DSP Processors-UNIT-6Ananda Gopathoti
 
Pms System Training
Pms System TrainingPms System Training
Pms System Trainingvkmalik
 
Case Study At91RM9200 Data Hub Controller
Case Study At91RM9200 Data Hub ControllerCase Study At91RM9200 Data Hub Controller
Case Study At91RM9200 Data Hub ControllerPromwad
 
Frame Relay And Leased Lines Essay
Frame Relay And Leased Lines EssayFrame Relay And Leased Lines Essay
Frame Relay And Leased Lines EssayRenee Jones
 
Honeywell PLC ML-50 (MLM-DR16S)
Honeywell PLC ML-50 (MLM-DR16S)Honeywell PLC ML-50 (MLM-DR16S)
Honeywell PLC ML-50 (MLM-DR16S)Shivam Singh
 

Similar a Distributed Control System Basics (20)

DISTRIBUTED CONTROL SYSTEMS BASICS.
DISTRIBUTED  CONTROL     SYSTEMS  BASICS.    DISTRIBUTED  CONTROL     SYSTEMS  BASICS.
DISTRIBUTED CONTROL SYSTEMS BASICS.
 
Ls catalog thiet bi tu dong master p 5000-e_dienhathe.vn
Ls catalog thiet bi tu dong master p 5000-e_dienhathe.vnLs catalog thiet bi tu dong master p 5000-e_dienhathe.vn
Ls catalog thiet bi tu dong master p 5000-e_dienhathe.vn
 
Ls catalog thiet bi tu dong master p 5000-e
Ls catalog thiet bi tu dong master p 5000-eLs catalog thiet bi tu dong master p 5000-e
Ls catalog thiet bi tu dong master p 5000-e
 
Embedded system Basic
Embedded system BasicEmbedded system Basic
Embedded system Basic
 
Embedded system
Embedded systemEmbedded system
Embedded system
 
CAN, BY MD.ABDULLAH
CAN, BY MD.ABDULLAHCAN, BY MD.ABDULLAH
CAN, BY MD.ABDULLAH
 
Can based collision aviodance system for automobiles
Can based collision aviodance system for automobilesCan based collision aviodance system for automobiles
Can based collision aviodance system for automobiles
 
PLC Introduction Details
PLC Introduction DetailsPLC Introduction Details
PLC Introduction Details
 
i2c.pdf
i2c.pdfi2c.pdf
i2c.pdf
 
Nokia 3G UTRAN
Nokia 3G UTRANNokia 3G UTRAN
Nokia 3G UTRAN
 
SudheerV_resume_a
SudheerV_resume_aSudheerV_resume_a
SudheerV_resume_a
 
Networking of multiple microcontrollers
Networking of multiple microcontrollersNetworking of multiple microcontrollers
Networking of multiple microcontrollers
 
Wsn handbook
Wsn handbookWsn handbook
Wsn handbook
 
X tel gsm-wcdma-datasheet
X tel gsm-wcdma-datasheetX tel gsm-wcdma-datasheet
X tel gsm-wcdma-datasheet
 
02 umts network architecturenew
02 umts network architecturenew02 umts network architecturenew
02 umts network architecturenew
 
Introduction to DSP Processors-UNIT-6
Introduction to DSP Processors-UNIT-6Introduction to DSP Processors-UNIT-6
Introduction to DSP Processors-UNIT-6
 
Pms System Training
Pms System TrainingPms System Training
Pms System Training
 
Case Study At91RM9200 Data Hub Controller
Case Study At91RM9200 Data Hub ControllerCase Study At91RM9200 Data Hub Controller
Case Study At91RM9200 Data Hub Controller
 
Frame Relay And Leased Lines Essay
Frame Relay And Leased Lines EssayFrame Relay And Leased Lines Essay
Frame Relay And Leased Lines Essay
 
Honeywell PLC ML-50 (MLM-DR16S)
Honeywell PLC ML-50 (MLM-DR16S)Honeywell PLC ML-50 (MLM-DR16S)
Honeywell PLC ML-50 (MLM-DR16S)
 

Último

The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptxThe Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptxLoriGlavin3
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek SchlawackFwdays
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii SoldatenkoFwdays
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Mark Simos
 
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxUse of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxLoriGlavin3
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfMounikaPolabathina
 
TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024Lonnie McRorey
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024Stephanie Beckett
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsRizwan Syed
 
Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebUiPathCommunity
 
Connect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationConnect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationSlibray Presentation
 
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfAddepto
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsSergiu Bodiu
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Mattias Andersson
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyAlfredo García Lavilla
 
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxA Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxLoriGlavin3
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenHervé Boutemy
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Commit University
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brandgvaughan
 

Último (20)

The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptxThe Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
 
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxUse of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdf
 
TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL Certs
 
Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio Web
 
Connect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationConnect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck Presentation
 
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdf
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platforms
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easy
 
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxA Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache Maven
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brand
 

Distributed Control System Basics

  • 1.
  • 9. CONTROL SYSTEMS TREND 1) PLC 2) DCS 3) PC - Based Control. • PLC : Introduced in the late 1960 to replace Relays and Hard-wired Programming.
  • 10. DCS : Introduced in the Mid-1970 to replace pneumatic controls by using computers. • PC-Based Control : Introduced by the early 1980s to avoid the proprietary PLC & DCS systems.
  • 11. DCS EVOLUTION • LOCAL CONTROL : Initially control was performed local to the equipment control. The ADVANTAGE was low wiring costs .DISADVANTAGES were - not much control, monitoring, alarming & history. • CENTRALISED CONTROL: With the advent of minicomputer, sensors and actuators were into the Central Control (Computer). • DISTRIBUTED CONTROL: With the advent of microcomputer, Distributed control systems were installed in the plants near to the control room via proprietary digital communications lines called as Data Hiway. First DCS was developed by Honeywell,U.S in 1975. The ADVANTAGES were greatly reduced wiring costs, much more limited failure and less cost to add more points. The DISADVANTAGES were that wiring costs were that wiring costs were still significant and there was lack of interoperability among controllers of various manufacturers due to the proprietary protocols. Hence the user was locked into a single vendor.
  • 12. DCS System Installations in RCF 1. Yokogawa - CS 3000 : Ammonia II 2. Yokogawa - CS 3000 : ANP 3. Yokogawa - CS 3000 : NNAP 4. Moore - APACS : Methyl amine 5. Fisher - Rosemant - Delta V field Bus : STP 6. Honeywell - GUS : Ammonia I Synthesis 7. Yokogawa - Centum Excel : Steam Generation Plant 8. Moore - APACS : Suphala 9. Yokogawa - Micro Excel : Methanol 10. Yokogawa - Micro Excel : S A P/C N A 11. ABB - Freelance 2000 : ABC 12. Honeywell - TDC 3000 : Ammonia I 13. Honeywell - GUS : Ammonia/Urea - Thal 14. Fox boro - I/A series : D M A C - Thal 15. Fisher - Rosemant RS3 : PGR 16. Fisher - Rosemant RS3 : Steam Generation - Thal 17. Moore - APACS : Water Treatment Plant - Thal
  • 13. DCS • The importance of DCS systems to increase as global competitive dynamics in food and beverage, specialty metals, pulp and paper, pharmaceutical and fire chemical processing. • The DCS has networking capabilities which are useful for business management. • The DCS has capacity for processing large number of I/O points. TYPES OF DCS : 1) Conventional DCS . 2) PLC based DCS. 3) Hybrid DCS. 4) Open DCS System
  • 14. CONVENTIONAL DCS This is a pure “Process only” control system. Usually purchased from one vendor. This DCS arranged into three categories: • Small - Less than $ 100,000. • Medium - Greater than $100,000 & Less than $500,000. • Large - Greater than $500,000. PLC Based DCS. This is a network of PLC’s used to perform the task of conventional DCS and programmable functionality when required. Hybrid DCS. Performs both process and sequential control. Open DCS System. This is Field-Bus Control. Advantages are lower wiring cost and less failure, smaller expansion costs and multi vendor interoperability DCS and PLC can be more closely and efficiently interconnected.
  • 15. Honeywell TDC 3000 DCS Architecture US#1 US#2 HM LCN A B HG AMC Field EC Link AMC Field Data Hiway A B
  • 16. Hiway Gateway (HG) • LCN Module. Provides a two way communication link between the Local Control Network and data hiway. • 68020 based high performance intelligence module. • Converts data and protocol between Local Control Network and data hiway. • Scans the hiway for alarm conditions. • Synchronize time keeping for hiway-based process connected boxes. • One HG is required for each data hiway that is connected to the LCN. Up to 20 data hiway pairs can be connected to an LCN. • Connects following hiway resident boxes to LCN 1. AMCs 2. CPC ( critical process controller ). 3. DHP. 4. Hiway traffic director etc… HG Functions : 1. Data access :- gets box data requested from LCN modules. 2. Event processing :- sends process and box alarm to LCN modules 3. Database configuration :- 3000 points per hg can be configured.
  • 17. Data Hiway Data hiway provides communication link between hiway gateway, preferred access devices and process connecting box. Data hiway operates at 250 kbps. It is redundant pair of 75 ohm coax cable connected to box. It may be 20,000 feet long. There are 3 kinds of devices on the data hiway, 1. Respond only devices Ex:- A-MC (Advanced Multifunction controller) 2. Polled devices Ex:- PIU’s (Process interface unit) 3. Preferred access devices
  • 18. History Module • LCN Module. Stores process and system information that can be displayed. • Based on microprocessors 68020. • Winchester disk for data storage. • Communicates with all Modules on the LCN. • Stores history and general information.
  • 19. Universal Station Universal station (US) communicates with all modules on the LCN, process connected devices on the hiway via hiway gateway and UCN via network interface module (NIM). The following are the features of US, • Intelligent man/machine interface in the TDC 3000 system. • Stands on the LCN. Communicates with all Modules on LCN, process connected devices on the Hiway via Hiway Gateway. • Provides comprehensive facilities to the process operator, process engineer and maintenance technician on the Universal Window. US provides comprehensive facilities to the following people, • Process engineer • Process operator • Maintenance technician.
  • 20. AMC • TDC 3000 controller 1. Based on Motorola 68000 Microprocessor. 2. Faster execution and control with 500 ms processing rate. • Multifunction – Modulating, sequence, logic, I/O monitoring communication and diagnostic. • Faster peer to peer communication over EC link ( 500 kbits/sec ). • Proven control techniques 1. Full function algorithms. 2. Process oriented programming. • Configured as a box on TDC 3000 Data Hiway. Supported by 1. LCN devices – US, AM, HM.
  • 21. HONEYWELL - GUS Printer Drive’s Printer - - US#1 US#2 US#3 US#4 Universal Station HM History Module A B Local Control Network Network Interface Module NIM Universal Control Network HPM High Performance Manager HPM HPM
  • 22. Honeywell System Description • Global User Station • History Modules • Network Interface Modules • Communication Subsystem - Local Control Network & Universal Control Network • High Performance Process Manager
  • 23. Global User Station Overview The TPS system provides an integrated interface between the process and the end user. This interface is named as the Global User Station (GUS). GUS is an important part in the Honeywell Total plant Solutions offerings. It provides access to plant wide process network, plant or organization wide intranet or even Internet. The following hardware is available to enhance the functionality of the GUS: • Integrated Keyboard for Operators as well as Engineer. • Matrix printer supported by Windows NT. • 8 * CD-ROM • 100MB ZIP Drive • 3.5” Floppy Drive GUS has following functionality's : • The “Human ” interface allows effective interaction of the Operator through the use of operating displays • Engineering functions such as data point building, display building and report building are available. • Communication with other LCN modules is accomplished. • Communication on Ethernet.
  • 24. Honey well GUS Hardware: • Processor : Pentium Pro / 200MHZ • Memory : 64MB RAM ECC • Cache : 256KB ECC • Storage : 2 GB hard disk drive, CD ROM, Cartridge Drive • Video : 21” high resolution screen 1280 * 1024 Pixels • Colours : 256 color palette • Keyboard : Integrated keyboard with mouse • PIN Connection : Built in Ethernet • Cursor Control : QWERTY & Mouse/Touch Screen Peripherals supported • Printer • 8 * CD-ROM • 1/4” Steamer Tape • 3.5” Floppy Drive • 100 Mb ZIP Drive • Annunciator relay on the console-based keyboard
  • 25. Honeywell GUS software • Operating System : Windows NT version 4.0 • Base System : Provides real time data exchange between the network and all GUS functions.
  • 26. History Modules The History Modules is the bulk module that can be utilized by all module connected to the Local Control Network. It is as the name implies the mass memory of the TPS System. The memory components of this module are one 1.8 gigabyte Winchester discs. It is controlled by an M68040 microprocessor. This provides the module with significant computing power that this used to structure much of the incoming data and format it into a form for easy retrieval. The history in the model is provided by the History Module. Process variables are available for hourly, shift, daily and monthly average calculation and recording. All system event history such as process alarms, system status changes, and error messages are stored into the History Modules. Other modules have access to data in the History Modules for their functions. The History Module provides two functions, storage only and data structuring
  • 27. HM functions and Historization parameter HM functions : It can automatically backup the control databases in the HG, AM, CG. HM can store, • Continuous process history. • Event journal (history). • Active system files. • Static system files. • On process analysis program (maintenance aid) HM Historization parameters : There can be up to 10 HM’s on the LCN. There can be maximum of 150 groups per HM. Each group can have up to 20 points. All points in the group must be in the same unit.
  • 28. Network Interface Module (NIM) The Network Interface Module (NIM) provides the link between the local Control Network and the Universal Control Network. As such it make the transition from the transmission technique and protocol or the Local Control Network to the transmission technique and the protocol of the Universal Control Network. The NIM provides access by LCN modules data from UCN resident devices. The NIM is available in the redundant configuration to provide continued operation in the event of the primary failure. It can also do event processing. There can be up to 10 redundant NIM pairs per LCN. A NIM can host upto 8000 tag names and supports a data transfer rate of 2400 parameters per second.
  • 29. Communication Subsystem Local Control Network (LCN) The backbone of every TPS system is a communication network, known as Local Control Network. The LCN is a LAN through which TDC 3000 modules communicate with each other. The LCN is a broadcast type of LAN. It is high speed redundant communication bus that connect all the control room equipment. All information is transferred on the network at 5 million bits per sec.,serially. It is based on the IEEE 802.4 Token passing and Bus Standard. Each LCN device that is connected to the Local Control Network is called a module. Up to 64 modules may be connected to the Local Control Network in a TPS system. The Local Control Network is designated as the primary and the other as the back
  • 30. Communication Subsystem Universal Control Network (UCN) The Universal Control Network is a high speed, high security process control network based on open system interconnection standards. It features a 5 megabit/second, carrier band, token bus network compatible with IEEE and ISO standards. It is used as the real time redundant Communications backbone for process connected devices such as the High Performance Process Manager (HPM), Advanced Process Manager . The UCN supports peer-to-peer communication for sharing data and allowing greater co-ordination of control strategies among network devices. The UCN uses redundant co-axial cables and can support up to 32 redundant devices UCN supports 2 types of devices
  • 31. High Performance Process Manager (HPM) The High Performance Process Manager is the latest in the Progression of High Performance control products offered by Honeywell for the application to Improve controlling of existing and new industrial processes. High Performance Process Manager is a fully integrated member of the TPS family. It is capable of : • performing data acquisition and control functions • fully communicating with operators and engineers at the GUSs and universal Work stations. • Supporting higher-level strategies available on the Local Control Network through the Application Module and Host Computers.
  • 32. High Performance Process Manager Overview The High Performance Process Manager uses a powerful multi-processor architecture with separate microprocessors dedicated to perform specific tasks. The HPM consists of two modules Communication and Control Module (CCM) and the I/O subsystem the I/O subsystem consist of up to 40 Smart I/O Modules (SIOM). All control operation are performed within the communication and control module. The process engineer has complete flexibility of choice within the maximum HPM design limits. These selections are implemented using the interactive tools provided by both the GUS and Universal Work Station. The I/O processors, for example, provide such functions as engineering unit conversion and alarm limit checking independent of the communication and control modules.
  • 33. YOKOGAWA CENTUM EXCEL ARCHITECTURE EOPS EOPS ENGG. Micro-XL /1 /2 STATION A B HF BUS (1 Mbps) EFCD EFMS EFGW I/O #1 ncst Closed loop Monitoring signals Third party system with PLC, I/O #2 control signal Through I/O NEST Gas Analyser etc. thr RS 232C port ncst Through I/O NEST At the rate of 9600 bps I/O #3 I/O #5 HF BUS : High frequency Bus: no. of station on HF Bus are 32 ncst EOPS : Extended Operator station: Hard disk capacity of EOPS is 80 MB EFCD : Extended field control I/O #4 station : 80 laps per controller EFMS : Extended field mauture A B station Max 255 inputs NIO Bus EFGN : Extended field gateway unit ENGS : Engineering station NIO : Nest I/O bus.
  • 34. Windows NT Based Centum CS Configuration INTERPLANT NETWORK PC (OPTIONAL) Ethernet Connectivity (optional) OPERATOR/ENGINEERING STATION OPERATOR STATION SUB-SYSTEM Inkjet HIS DM HIS HIS Printer PRT PRT Printer DUAL “V NET” 10 Mbps FCS RIO BUS HIS – Human Interface Station. NIU NIU FCS – Field Control Station. NIU – Node Interface Unit. RIO Bus – Remote I/O Bus.
  • 35. Centum CS 3000 System Overview Centum CS 3000 is an integrated production control system for medium and large control applications. This system is a synthesis of the latest technology with Yokogawa’s experience and specialist know-how. Centum CS 3000 system features : • Synthesis of DCS with Personal computers. • Online Documentation. • Powerful Operation and Monitoring Functions. • Two Types of Control Station. • Compact I/O Modules. • Powerful Control and Communication Functions. • Efficient Engineering. • Virtual Test functions don’t require Control Station hardware. • Full-Featured Batch Package. • CENTUM CS micro-XL Integration ( to be released ).
  • 36. Centum CS 3000 System Overview Centum CS 3000 is an integrated production control system for medium and large control applications. This system is a synthesis of the latest technology with Yokogawa’s experience and specialist know-how. Centum CS 3000 system features : •Synthesis of DCS with Personal computers. •Truly open system for integrating multi-vendor solutions. •High Reliability of computed process data by the unique fault tolerant control processor. •Powerful built in “RISC PROCESSOR” with high speed and dynamic error correcting code. •Remote I/O concept enables geographically distribution of I/O Modules thereby reducing cabling cost. •1:1 Redundancy at almost all the system levels except for control processor which employs a special Redundancy with 4 identical CPU’s. •Powerful Control Tools and Communication Functions. •Virtual Test functions don’t require Control Station hardware. •Full-Featured Batch Package. •Built in security features to prevent mal-operations. •CENTUM CS micro-XL Integration ( to be released ).
  • 37. CS3000 – System Configuration INTERPLANT NETWORK PC (OPTIONAL) Ethernet Connectivity (optional) OPERATOR/ENGINEERING STATION OPERATOR STATION SUB-SYSTEM Remote Domain System CGW Inkjet HIS DM HIS HIS Printer PRT PRT Printer V NET 10 Mbps FCS BCV RIO BUS CS, CS 1000 Centum – XL, -V, -MXL NIU NIU HIS – Human Interface Station. FCS – Field Control Station. NIU – Node Interface Unit. RIO Bus – Remote I/O Bus. CGW – Communication gateway unit BCV – Bus Converter
  • 38. CENTUM CS 3000 NETWORK HIS HIS HIS V net FCS FCS FCS
  • 39. CENTUM CS3000 SYSTEM SPECIFICATION • NO. OF TAGS MONITORED 1,00,000 • TOTAL NO. OF STATION 256 • NO. OF DOMAINS 16 • NO. OF STATIONS IN A DOMAIN 64 • NO. OF HIS / DOMAIN 16 NOS
  • 40. CENTUM CS3000 SYSTEM SPECIFICATION • Max. no. of stations : 256 / system • Max. no. of Domains : 16 / system • Numbering of Domains : 1 to 64 • Domain No. CS3000 Domain (V net Domain) : 1 to 16 • Max. no. of stations/Domain : 64 • Domain No.Virtual Domain (Non V net Domain) : 17 to 64 • Station NO. HIS : 1 to 64 in descending order • Station NO. FCS : 1 to 64 in ascending order • Max. No. of ICS / Domain : 16 • Max. No. of NIU / FCS : 8 • Max. No. of IOU / FCS : 40 ( Max. 5/ IOU) • Max. length of Vnet : 20 Km • Max. length of RIO bus : 20 Km (750m ~ 20Km)
  • 41. Centum CS-3000 Communication V net V net is 10 mbps real time control bus which links station such as FCS , HIS , BCV and CGW. It can be dual redundant. It can be up to 500m using coaxial cable alone, or up to 20 Km when repeater are used or optical fiber is used. • 10BASE2 cable used by HIS, maximum segment length = 185 m • 10BASE5 cable used by stations other than HIS(FCS,CGW etc.) maximum segment length = 500 m
  • 42. V net Communication HIS HIS V net Protocol : IEEE802.4 Access Control : Token Passing Trans. Speed : 10 Mbps Trans. Distance: 500m to 20Km Media : Coaxial/optical fiber FCS FCS
  • 43. V net specification ITEM SPECIFICATION Transmission route Coaxial or fiber optical cable Type Bus type or Multi-drop type Communication rate 10 Mbps Transmission Distance 500M –20Km Max Redundancy Dual-redundant Proto type Token passing
  • 44. V- net Features • Real time control bus. ( Dual redundant possible ) • Cable : 50 ohm coax. cable with BNC connector ( 10Base2 comp. ) • Communication speed : 10 Mbps. • High reliable token passing communication ( performance guaranteed ) • Std. max. length : 185 m. BNC Connector • Max. length : 20 Km ( with optical fiber ) 1.6 Km ( with coax. Repeater ) VL net cable VL net I/F card ( PCI )
  • 45. Ethernet HIS and ENG, HIS and supervisory systems can be connected by an Ethernet LAN; supervisory computers and personal computers on the Ethernet LAN can access messages and trend data in the CS 3000 system. The Ethernet can also be used for sending trend data files from the HIS to supervisory computers, or for equalizing the data in the two HIS station ( rather than using the V net control bus to do this ). A system with only one HIS with engineering functions installed, does not need Ethernet – but in general Ethernet ( and corresponding network engineering ) is required.
  • 46. Ethernet Specification ITEM SPECIFICATION Transmission Route Coaxial or Fiber optical cable Type Bus type or Multi–drop type Communication Rate 10 Mbps Transmission Distance 500m – 2.5 Km max. Redundancy Not available Proto type CSMA/CD Type
  • 47. TYPES OF HIS • Console type HIS • Desk top type HIS • PHIS Yokogawa brand OPS
  • 48. HIS Hardware • CPU Pentium 166 • Main memory 96MB or larger(for op & monitoring only) • Hard disk 1 GB or larger • Display 256Colors min. resolution 800*600 1024*768 recommend(1280*1024 best) • Serial port RS232C*1 or more (for operation keyboard) • Parallel port 1 port for printer or more • OS Windows NT 4.0 Workstation • Operator stations Max. 8 stations
  • 49. Field Control Station Configuration Ethernet HIS HIS HIS V net I/O Unit RIO Bus Node Interface Sub system Unit Node I/O Unit Sub system Compact FCS Standard FCS
  • 50. Connection to Centum CS 3000 System Exapilot client (engineering, operation) Ethernet HIS ENG Exaopc Exapilot client (engineering, operation) Exapilot server (engineering, operation) V-net Exapilot communication data Process data read/write FCS FCS
  • 51. Features of Exapilot • Standardize and Automate Manual Procedures • Improve Plant Operating Efficiency • Improve safety of Plant Operation Features of Event Analysis Package • Analysis DCS Event History to Help You Enhance Efficiency. • Enhance Process Stability: Balance Process Events and Operator Actions. • When, Where, What (3W) Filters Help You Narrow Focus of Analysis.
  • 52. OPEN DCS SYSTEM Ethernet Field Bus Power Supply Flow Trans. Terminator HMI Control Valve Safety Barrier Pressure TX.
  • 53. Field bus It is a standardized digital communication protocol between a process Control field devices and the Control room. It is a simple pair of wires to power and carry the communication signal between the field devices and the Control room. FEATURES : • Drastic reduction in cable, conduits cable trays, marshallive racks, and connectors etc. • Drastic reduction in installation cost. • Fewer non field devices. • More reliability due to the smaller number of devices. • More efficient operation due to better accuracy (no A/D and D/A conversion). • Easy integration into plant management system. • Flexibility for different suppliers are interoperable and interchangeable. • Major reduction in maintenance cost.
  • 54. Field-bus Benefits Wire Screw I/O IS Wiring (pair) Terms Cards Barriers Traditional 3500’ 168 2 2 Field bus 640’ 64 1 1 Savings 2860’ 104 1 1 Savings % 82% 63% 50% 50% Savings $ $ 3000 Material $ 2000 Labor $ 5000 Total Typically comments from a plant personal : •Easy to identify what’s out there. •Consistent calibration procedure. •Two days versus four days to commission system. •Familiar with twisted pair wiring – comfortable.
  • 55. FOUNDATION™ fieldbus Vocabulary Blocks Basic Components Valve Resource Resource Block Block FOUNDATION™ Transducer fieldbus (Servo) Function Function Block Block(s) Block(s)
  • 56. FOUNDATION™ fieldbus Vocabulary Blocks Basic Components Resource Resource Block Block FOUNDATION™ fieldbus Transducer Function Function Block Block(s) Block(s) Temperature Transmitter
  • 57. FOUNDATION™ fieldbus Vocabulary H1 and H2 • H1 Segment • H2 Segment – Moderate speed – High speed – Use existing wiring – Link multiple H1 – Bus powered Segments – Can be intrinsically – I/O subsystem bus safe – Replace – Low power 2 wire proprietary devices networks – 4 wire devices – New wiring – Replace analog & proprietary digital
  • 58. FOUNDATION™ fieldbus Vocabulary New Approach for H2 • 100 Meg Ethernet technology with extensions – Improve time to market – High speed – Mandatory redundancy – Widely available technology and silicon – Widely available tools – Limited incremental development – Many suppliers – High volume for low cost – Works with installed equipment – Evergreen technology • Better than ANY other solution!
  • 59. FOUNDATION™ fieldbus Vocabulary H1/H2 Bridges Server H2 Segment 100 Meg Ethernet Control PLC H1/H2 Module Bridge H1/H2 Bridge H1/H2 Bridge H1 Segment Replaces Replaces Traditional I/O Traditional I/O H1 Segment H1 Segment
  • 60. FOUNDATION™ fieldbus Standards Organizations • IEC – International Electro-technical Commission • ISA – International Society for Measurement and Control (formerly: Instrument Society of America) • SP50 • CENELEC – European standards body • Parallel (competitive?) Working Groups to IEC
  • 61. FOUNDATION™ fieldbus Topography H1 Fieldbus Installations Cost savings: Cost savings: •• wiring wiring •• I/O cards & I/O cards & Controller cables cables Similar I/O Cards Reduced Wiring Junction •• terminations terminations Similar I/O Cards H1 I/O Reduced Wiring Box •• IS barriers Interface IS barriers •• marshaling marshaling H1 I/O Terminations FewerTerminations FewerTerminations H1 Fieldbus all-digital Marshaling H1 Fieldbus all-digital Fewer Terminations Fewer Terminations IS (Ex i) Barriers Fewer IS barriers Fewer IS barriers
  • 63. DeltaV System Architecture Engineering station Operator station Printer Printer 8 port Hub 8 port Hub primary Redundant 1 2 wide carrier for 8 wide carrier for Power/Controller P P A AA DDD I/O subsystem Contr. Contr. Serial S S I I O I I O Power supply H1 Controller I/O extension cable Connector RS232 Modbus PLC For Blank H Blank Blank Blank D Blank Blank 8 DI & 8 DO O I Fieldbus Transmitter Pressure Transmitter 3244MVF1NAB4 3051TG2A2B21AB4M5FF Smart valve positioner FSDVC0400-201 Fieldbus Power
  • 64. DCS communication system Hierarchy Level 5 Management MIS Low data rates High Superior responsibility Level 4 Scheduling SCHED. Low Level 3 Supervisory control SUP. SUP. Level 2 Direct digital Control (DDC) DDC DDC DDC DDC Level 1 Sensors (S) & Actuators (A) High data rates S A A S A S S S A S S A Low responsibility PLANT
  • 65. History of Process Control Signal Around 50 years ago, most plant used 3-15psi pneumatic signal to control their process. The last change change in signal standard was the open protocol HART digital communications format. The HART protocol provides simultaneous digital communications with the 4-20 mA output. The next protocol change will be fieldbus. Fieldbus is entirely digital-there is no analog Signal. Fieldbus also allows migration of control functions to field devices. Process control Timeline – The Evolution of Signal Standard Signal standards have evolved over the years, starting with the 3-15 psi standard. There are also other communication methods, but they have not gained widespread Digital: Fieldbus acceptance. Digital plus Analog: HART with 4-20mA With many standard there is typically a slow transition period as plant Analog: 4-20mA engineers and Pneumatic: 3-15 psi managers test period does gain widespread acceptance. However, once the benefits of the 1940 1950 1960 1970 1980 1990 2000 2010 Fieldbus become tested and proven, more plant will install Fieldbus because of its
  • 66. I/O Bus Network Protocol I/O Bus Network Device bus network Process bus network Discrete Analog Byte-wide Bit-wide Several Hundred Data data Data Bytes
  • 67. Protocol Standard Field Bus Foundation (Field Bus std.) Process bus network Profibus Trade Organization (Profibus std.) Device net Byte-Wide CAN Bus Data SDS Inter Bus-S Device bus network Seriplex Bit-Wide Data ASI Inter Bus Loop
  • 68. Fieldbus Architecture Fieldbus is more than just a new signal communications protocol, but a whole new way to control the process. With the release of the low fieldbus (H1), the entire fieldbus will be defined. Most of the recent published literature has focused on the intricate details of the fieldbus architecture, especially those layers that have not been released. However, except Maintenance Workstation information physical layer and the user layer, these layer are transparent to the engineers and the system manager. User Layer System management Network Management Application Layer stack Data Layer Physical Layer Multivariable Valve Level Pump Transmitter Transmitter
  • 69. Open System Interconnected Reference Model MBAP, SMB, FTP, SMTP, FMS, Physical – Provides the standard for transmitting raw Application electrical signals over the communication channels. IEC 61158, ANSI/ISA S50.2,IEEE 1451 Presentation Data link – Contains the rule for interpreting electrical signals as data, error checking and physical addressing Session Network – Describes the rule for routing messages Transport TCP, SPX, UDP through a complex network and deals with congestion. Transport – Establishes a dependable end-to-end Network IP, IPX, NetBeui connection between two host. HDLC, ETHERNET, ANSI/ISA S50.02 Session – provides Management and Synchronization Data link of complex data transaction. Physical EIA-485, ETHERNET,ANSI/ISA S50.02 Presentation – Establishes protocol for data format conversion, encryption and security. Application – Contains protocol that accomplish task such as e-mail, file transfer or reading a set of registers from a PLC. For the purpose of Process control, the top and bottom four layers are used. Layers 5 and 6 are important to large commercial networks.
  • 70. Field Bus Field Bus is a bi-directional digital communication that interconnects smart field devices to control system or to instrument located in the control room. Field Bus is based on the OSI (Open System Interconnect), which was developed by the ISO (International Standard Organization) to represent the various functions required in any Layer Function Communication network. 7 Application Provides formatted data 6 Presentation Converts data 5 Session Handles the dialogue 4 Transport Secures the transport connection 3 Network Establishes network connections 2 Link Establishes the data link connection 1 Physical Connects the equipment
  • 71. Field Bus The OSI model consists of seven layers. However for real time application layers 3 to 6 are not considered since they deal with transference of data among networks. For such application following layers are used: • LAYER 1 - PHYSICAL LAYER Defines the type of signal, transmitting medium, data transmission speed, etc. • LAYER 2 – DATALINK LAYER Define the interface between the physical layer and the application layer. It establishes how the messages shall be structured and normalizes the use of multiple masters. • LAYER 3 – APPLICATION LAYER Defines howwas invented by an Indian engineer Mr. Ramrepresentation. The Fieldbus data is specified, its addresses and its Ramchandran ( M.S in Comp. Tech , Texas)
  • 72. PHYSICAL LAYER The Physical layer defines the medium that transport the messages frames, the signal shape and amplitude limits, data transfer rate, and power distribution. Technical Characteristics: Physical Medium Three types are defined: wires, optic fiber, and radio signals. The specification for wire has been already approved. Bit rate for wire media 31.25 Kbps (H1) 1 megabits and 2.5 megabits (H2). H1 and H2 are classification of the two hanks of Field Bus target applications. H1 has low speed and utilizes existing wires. H2 has high speed and may require independent wires to power up field devices. Number of devices per link (31.25Kbps) 2 to 32 devices, without power and no IS (intrinsic safety). 2 to 6 with power and IS. Maximum distance Up to 1900 meters for 31.25Kbps, without repeaters. Up to 750 meters for 1 megabits. Up to 500 meter for 2.5 megabits.
  • 73. PHYSICAL LAYER Signal Modulation Manchester bi phase L synchronous. Physical layer preamble on transmissions, the physical layer will add to the data sent by the layer above a preamble and one start delimiter in the beginning of the frame and one end delimiter at the end delimiter at the end of the of the frame.
  • 74. DATA LINK LAYER The Data Link Layer will assure the integrity of the message by using the frame check sequence: Two bytes added to the frames and a polynomial calculation of all frame data. The Data Link Layer also checks to see that the data reaches the devices correctly. Technical characteristics Medium Access: There are three forms to access the network: • Token passing: Token is the right to initiate a transaction on the bus. A device must have the token to initiate a conversation. As soon it finishes it will return the token to the LAS (Link Active Scheduler). The LAS send the token to the unit that requested in either in a pre-configured way or via scheduling. • Immediate response: A master station will give an opportunity to the station to reply with one frame. • Requested token: a device request a token by using a code in any of the response sent to the bus. The
  • 75. APPLICATION LAYER AND MANAGEMENT The Application Layer provides a simple interface to the end user’s application. Basically , it defines how to read, write , interpret and execute a message or command. A big part of this job is to define the message syntax. The contents include the requested message, action taken, and the response message. The management defines how to initialize the network : tag assignment, address assignment, clock assignment, clock synchronization, distributed application scheduling across the network or association of the input and output parameters of the function blocks. It also controls the operation of the network with statistic of faults and detection of the addition of the new element or the absence of a station. The system always look for the new stations on the bus by polling the possible station addresses.
  • 76. Digital Communication Protocol ISO - International Standard Organization. Responsible for developing the model that the communication specification are based upon as well as standards for each layer of communication specification. IEEE - Institute of Electrical and Electronics Engineers. Formed the IEEE 802 project for defining standards for network media and access methods. SP72 - Institute Society of America, Standards and Practice committee Number 72 Developing EIA1393 companion standard for process control messaging. SP50 - Institute Society of America, Standards and Practice committee Number 50 Developing standards for digital communication between field devices. F.I.P - Factory Information Protocol, approved French National Standard. Profibus - Process Fieldbus, approved German National Standard.
  • 77. HART COMMUNICATION PROTOCOL Why HART protocol ? 4-20 ma is tried, tested and widely used standard but only limited amount of information is sent by a 4-20 ma signal. HART (Hiway Addressable Remote Transducer) protocol enhances these operations by transmitting digital data along with the 4-20 ma signal – without interfering with it ! HART permits two-way communications. It also has all digital mode that allows instrument to be connected to a single cable, cutting installation costs dramatically. Features : 1. Field proven concept that is easy to understand and use. 2. Compatible with existing 4-20 ma systems. 3. Simultaneous point-to-point 4-20 ma and digital communication. 4. Alternative multi-drop mode. 5. Measured variables, tag no. , range and span settings, device information, diagnostics and simple messages transmitted. 6. Digital response time of 500 msec; burst mode response of 300 msec. 7. Open architecture; freely available to any vendor and every user.
  • 78. HART COMMUNICATION PROTOCOL Method of Operation : The Hart protocol operates using the FSK principal. The digital data is made up from two frequencies –1200 Hz and 2200 Hz representing bits 1 and 0 respectively. Sinusoidal waves of these frequencies are superimposed on the DC analog signal cables to give simultaneous analog and digital communications HART Protocol Structure : HART follows the basic Open Systems Interconnection (OSI) reference model, developed by the International Organization for Standard (ISO). The HART protocol uses a reduced OSI model, implementing only layers 1,2 and 7
  • 79. HART COMMUNICATION PROTOCOL OSI reference model Open Systems Interconnections LAYER FUNCTIONS HART 7 Application Provides formatted HART instructions data 6 Presentation Converts data 5 Session Handles the dialogue 4 Transport Secures the transport connection 3 Network Establishes network connections 2 Link Establishes the HART protocol data link regulations connection 1 Physical Connects the Bell 202
  • 80. HART PROTOCOL LAYERS Layer 1, the physical layer, operates on the FSK principle Data transfer rate: 1200 bit/s Logic “0” frequency: 2200 Hz Logic “1” frequency: 1200 Hz the vast majority of existing wiring is used for this type of digital communication. Layer 2, the link layer establishes the format for a hart message. HART is a master/slave protocol. the structure of these messages is given below: Preambl SD AD CD BC Statu Dat Parity e s a SD – start character. AD – display terminal and field addresses. CD – HART instruction. BC – Byte count. Status – Field device and communication status (only from field device to master) The individual characters are : 1 start bit, 8 data bits, 1 bit for odd parity and 1
  • 81. HART PROTOCOL LAYERS Layer 7, the application layer, brings the HART instruction into play. The master sends messages with requests for specified values, actual values and any other data or parameters available from the device. The field device interprets these instruction as defined in the HART protocol. The response message provides the master with the status information and data from the slave. For slave devices, logical uniform communication is provided by the following command sets: Universal commands – understood by all field devices. Common practice commands – provide functions which can be carried out by many, though not all, field devices. Drive-specific commands – provide functions which are restricted to an individual
  • 82. HART PROTOCOL – TECHNICAL DATA DATA TRANSMISSION Types of data transmission : Frequency shift keying (FSK) Transfer rate : 1200 bit/s. ‘0’ bit information frequency : 2200 Hz ‘1’ bit information frequency : 1200 Hz Signal structure : 1 start bit, 8 data bits, 1 bit for odd parity, 1 stop bit. Transfer rate for simple variables : Approximately 2/s (poll/response) DATA INTEGRITY Physical layer : Error rate destination circuit : 1/(10^5) Link layer : Recognizes : all groups up to 3 corrupt bits and practically all longer and multiple groups. Application layer : Communication status terminated in a response message.
  • 83. MODBUS The MODBUS protocol describes an industrial communication and distributed control system developed by Gould-Modicon. MODBUS is a Master/Slave communications protocol, whereby one device (Master), controls all serial activities by selectively polling one or more slave devices. The protocol provides for one master device and up to 247 slave devices on a common line. Each device is assigned an address to distinguish it from all other connected device. Only a master initiates a transaction. Transactions are either a query/response type, or a broadcast/no-response type. A transaction comprises a single query and single response frame or a single broadcast frame. Certain characteristic of a MODBUS protocol are fixed such as frame format, frame sequences, handling of communication errors and exception conditions, and the functions performed.
  • 84. RS-232 Communication RS-232 is an asynchronous communication network. Normally, a binary system is used to transmit data in ASCII (American Standard Code for Information Interchange) format. This code translates human readable code (letter/numbers) into “computer readable” code(1’s and 0’s). There are 2 types of RS-232 devices. The first is called a DTE (Data Terminal Equipment) device and a common example is a computer. The other type of device is called DCE (Data Communication Equipment) device and a common example is a modem. In RS-232 the first thing a terminal send is start bit. This start bit is a synchronizing bit added just before each character being send. The last thing send is a stop bit. This stop bit informs to the receiving terminal that the last character has just being send.
  • 85. RS-232 Communication RS-232 communication is done through Serial port which usually has a 9-pin configuration. The pin and their purposes are shown below. 9-PIN PURPOSE 1 Frame ground 2 Receive data (RD) 3 Transmit data (TD) 4 Data terminal ready (DTR) 5 Signal ground (GND) 6 Data set ready (DSR) 7 Request to send (RTS) 8 Clear to Send (CTS) 9 Ring indicator (RI) *only for modems*
  • 86. PC-to-PC Communication through Serial Port CD 10 01 CD RXD 20 02 RXD TXD 30 03 TXD DTR 40 04 DTR GND 50 05 GND DSR 60 06 DSR RTS 70 07 RTS CTS 80 08 CTS RI 90 09 RI 9-Pin D Connector
  • 87. PC-to-PC Communication through LPT1 Port 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25
  • 88. Flavours of Internet Telephony PC-to-PC The Internet PC PC Dial-up or Local ISP Local ISP Leased Line PC-to-Phone The Internet PC Phone Local ISP Local ISP Voice Gateway Phone-to-Phone Access Code The Internet Phone Phone Local ISP Local ISP Voice Gateway Voice Gateway
  • 89. APACS - Operation Platform Database Ownership Operator Console Engineer Console Operator Console Console Level Controller Level Controller Module I/O Level I/O Modules •TAGS •Range •Engineering Unit Transmitter Interlock I/P Valve •Diagnostics
  • 90. TODAYS INDUSTRIAL SYSTEMS Planning Application HMI ----------------------- HMI Drivers 1 2 3 4 5 6 Devices I/O PLC DCS
  • 91. PC Based Industrial Systems OPC Client Planning Application HMI ---------------------------------- HMI OPC Server 1 2 3 Devices I/O PLC DCS
  • 92. Enterprise Automation Schemes Windows NT Corporate IT Network Windows NT Server Control network Embedded Real System
  • 93. Windows NT (“New technology”) FEATURES: • A true 32 bit processing. • A very reliable operating system. • Real operating system. TECHNICAL ASPECT: • Multiprocessing, Multithreading and partitioned memory space. • Security - C2 compliance. • In-built networking. • Internationalization . • Human interface as Windows 95. • Object - based : DCOM/OLE - ActiveX. • for special need of the process industries. DCOM and OLE are not robust, deterministic and secure. • Client - Server architecture.
  • 94. Windows NT Interconnectivity Transparent inter-connectivity to typical business systems in plants: 1) ODBC : It provides access to most SQL databases. 2) ActiveX/OLE : Supports data access between application and embedding of one applications function within another. 3) DDE : Dynamic Data Exchange supports simple data exchange between applications such as plant data populating an Excel spread sheets.
  • 95. Windows NT features Windows NT is gaining ground in open control because of the following advantages : • User acceptance. • Corporate interoperability • Ease of use. • Connectivity. • Scalability for small and large application. However, Windows NT has the following disadvantages : • Needs a lot memory and processing power. • Optimized for office, not control, requirements. • Requires a disk drive which may fail. • Depends on single vendor. • Reboots at unexpected times • Unstable operating system.
  • 96. Embedded control Operating System - QNX QNX real-time operating system, has evolved from the first-ever micro-kernel operating system for PCs into one of the best selling and most trusted operating systems for mission critical application. Today, QNX is the real time operating system in industrial automation, hand held devices, controllers and soft PLCs QNX is recognized as : • The fastest and most dependable real time operating system. • The most proven high speed, deterministic real time kernel. • Having a hard real time engine that gives PLC-style control. • Enabling data acquisition with milliseconds resolution. • Providing a fault-tolerant architecture on which you can run control, events, alarms in a virtually crash-proof environment.
  • 97. Windows NT - for Process control Windows NT features : • A true 32 bit processing. • A very reliable operating system. • Real operating system. • Multiprocessing, Multithreading and partitioned memory space. • Security - C2 compliance. • In-built networking. • Internationalization. • Human interface. • Object-based DCOM/OLE : The sending object is shown as client and receiving object is known as server. The MS technology allows any developer to produce small, self contain objects that have “packaged” visual component and specific action. These components are called “ActiveX” objects. NT’s OLE technology is part of Microsoft’s Distributed Component Object Model (DCOM) operating across networks. Anyone can develop ActiveX Object using VC++ or even VB on a PC. For special needs of the process control industries DCOM and OLE are not secure, deterministic and robust enough.
  • 98. Ethernet Ethernet was originally designed by Digital, Intel and Xerox (DIX) in the early 1970’s and has been designed as a broadcast system. The original format for Ethernet was developed in Xerox Palo Alto Research center (PARC), California in 1972. The two inventors were Robert Metcalf and David Boggs. Ethernet version 1.0 and 2.0 followed until the IEEE 802.3 committee re- jigged the Ethernet II packet to form the Ethernet 802.3 packet. Nowadays you will see either Ethernet II (DIX) format or Ethernet 802.3 format being used. The ‘Ether’ part of Ethernet denotes that the system is not meant to be restricted only to one medium type, copper cables, fiber cables and even radio waves can be used. Briefly, stated Ethernet what is referred to as the Physical layer and the Data- link layers protocols. The physical layer defines the cable types, connectors and electrical characteristics. The Data link layer defines the format an Ethernet frames, the error checking method and the
  • 99. Ethernet 10Base5 Traditionally, Ethernet is used over ‘thick’ coaxial cable called 10Base5 ( the 10 denotes 10 Mbps, base means that the signal is baseband i.e, takes the whole bandwidth of the cable, 5 denotes 500m maximum length ). The minimum length between stations is 2.5m. The cable is run in one long length forming a ‘Bus Topology’. The segments are terminated by 50 ohm resistor and the shield should be grounded at one end only. 10Base2 Thin Ethernet (Thinnet) uses RG-58 cable and is called 10Base2 (the 2 denotes 200 mtr maximum length cable). Each station connects to the Thinnet by way of
  • 100. Ethernet 10BaseT Nowadays, it is becoming increasingly important to use Ethernet across Unshielded Twisted Pair (UTP) or Shielded Twisted Pair (STP), this being called 10BaseT (the T denotes twisted pair). UTP is installed in star wire format and Ethernet Hubs with UTP ports (RJ45) centrally located. Also there should be no more than a 11.5db signal loss and the minimum distance between devices is 2.5 meters. The advantages of the UTP/STP technology are gained from the flexibility of the system, with respect to moves, changes, fault finding, reliability and security. 10BaseF 10BaseF standard developed by IEEE 802.3 committee defines the use of Fiber for Ethernet. 10BaseFB allows up to 2 Km per segment and is defined for Backbone
  • 101. Ethernet The following table shows the RJ45 pin outs for 10BaseT : RJ45 Pin Function Colour 1 Transmit White/Orange 2 Transmit Orange/White 3 Receive White/Green 4 Blue/White 5 White/Blue 6 Receive Green/White 7 White/Brown 8 Brown/White
  • 102. PC-to-PC Communication through Ethernet RJ45 RJ45 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8
  • 103. Ethernet Topology Segmented (star) topology Bus topology Workstation Workstation Workstation Workstation Switched Hub Controller Controller Controller Controller
  • 104. Wireless LAN Wireless LAN is based on standard IEEE 802.11b which throughput of up to 11Mbps in the 2.4 Ghz band. Similar Wireless Personal Area Network (WPAN) are Bluetooth and Infrared. Ethernet works on the CSMA/CD technology but wireless LAN has difficulty of detecting collision in Radio frequency. Therefore they are using CSMA/CA (Collision Sense Multiple Access / Collision Avoidance) technology to transmit data. Physical Layer is either Photonic or Radio frequency.
  • 105. Process control Software characteristics The most important feature of process control system is that it needs to be reliable. The process control system used has to be completely crash-proof and any changes in the system need to be made on-line. The process control needs to be made real time, which means that it can update the I/O data table and process the control program in the time required by the process. A process control system that is deterministic refers to whether the operating system allows the highest priority task to work without interruption from task with lower priority. Software offerings in the automation and the process control fields must be versatile and open enough to address the needs of different applications. Finally the chosen solution must deliver tangible, quantifiable values such as : 1. Reducing project implementation time and cost. 2. Improving time-to-market. 3. Achieving higher production and quality. 4. Cutting maintenance and training cost.
  • 106. PC-based control system features Unlike the other systems, PCs provide a more open architecture making them ideal for improving, optimizing and integrating the overall automation process, as well as conducting control task. In addition PCs offer the following features : • Lower cost. • Ease of use. • Graphical user interface. • Easy integration of logic, motion and process control. • Simplified application development. • Software portability • Independence from proprietary control system. Using PCs enable the following functions, • Millisecond time stamping which is essential to utilities. • Real time control. • Sequence of events. • Alarming. • Data collection.
  • 107. PLC conceptual overview SCADA Process History & Alarm & Other Aspect configuration Graphics Trend Events system editor OP Client SCADA Control Aspect OPC server SCADA Real-time server database Protocol Protocol opc Modbus comli xx yy Siemens Allen GE ABB Bradley Fanuc ….
  • 108. PLC Programming Standards The open, manufacturer-independent programming standard for automation is IEC 61131-3. You can thus choose what configuration interface you wish to use when writing your application : • Ladder Diagram • Instruction List • Function Block Diagram • Sequential Function Chart • Structured Text All users, be they plant electrician or computer scientists, thus have a configuration interface in which they can feel at home.
  • 109. Industrial IT Trends The availability of information is becoming increasingly crucial in the view of growing global competition. In future, a decisive competitive edge can only be achieved by providing the right information at the right time, in the right place and in the right form for the right person. these leading- edge application are continuously optimized and repositioned. Industrial IT consists of five components: 1. Engineering IT 2. Operation IT 3. Production IT 4. Optimization IT 5. Evolution / Information
  • 110. Industrial IT Trend Business Sales & Systems Marketing Planning & e-PROD Scheduling Real-time ION OPTIMIZAT UCTIVI Automation & ASSET Plant & Information TY Process Eng. Operation & Maintenance Distribution Plant