PROTECTION OF POWER
TRANSFORMER
1
TRANSFORMER
Introduction
A transformer is a static electrical device used in
electric power systems to transfer power between circuits
through the use of electromagnetic induction.
Transformers are devices that transfer energy from one
circuit to another by means of a common magneticfield.
When an alternating current flows in a conductor,a
magnetic field exists around the conductor.If another
conductor is placed in the field created by the first
conductor such that the flux lines link the second
conductor,then a voltage is induced into the second
conductor.The use of a magnetic field from one coil to
induce a voltage into a second coil is the principle on
which transformer theory and application is based.
Transformers range in size from thumbnail-sized used in
microphones to units weighing hundreds of tons
interconnecting the power grid.A wide range of
transformer designs are used in electronic and electric
2
power applications. Transformers are essential for the
transmission,distributionandutilization of electrical
energy.
Induction Law
The transformer is based on two principles:
1. An electric current can produce a magnetic field.
2. A changing magnetic field within a coil of wire induces
a voltage across the ends of the coil (electromagnetic
induction).
Referring to the figure here, current passing through the
primary coil creates a magnetic field. The primary and
secondary coils are wrapped around a core of very
high magnetic permeability, so that most of the magnetic
flux passes through both the primary and secondary coils.
Any secondary winding connected load causes current
3
and voltage induction from primary to secondary circuits
in indicated directions.
POWER TRANSFORMERS
The term power transformer is used to refer to those
transformers used in the generatorand the distribution
circuits, and these are usually rated at 500 KVA and
above. Power systems typicallyconsist of a large number
of generation locations, distribution points, and
interconnections within thesystem or with nearby
systems, such as a neighboring utility. The complexity of
the system leads to avariety of transmission and
distribution voltages. Power transformers must be used at
each of these pointswhere there is a transition between
voltage levels.
4
Fig.An example of a power transformer used in electric power system
CAUSE OF FAULTS IN POWER TRANSFORMER
Transformers are prone to variety of faults :
1. The most common type of fault being the winding to
core faults because of weakening of insulation.Phase
faults inside the transformers are rare.However,such faults
may occur on terminals,which fall within the transformer
protection zone.
2. Power transformers are generally provided with on-line
tap changing (OLTC) gear.This is another major area of
occurrence of fault.
5
3. All large transformers are oil immersed type.There is a
possibility of oil leakage.
4. Transformers experience large inrush currents that are
rich in harmonic content at the time of switching if they
happen to be unloaded.
5. A transformer may develop inter turn faults giving rise
to local hot spots within the winding.
6. Transformers may suffer from over fluxing due to
under frequency operation at rated voltage.Over fluxing
may also be caused when the transformer is subjected to
over voltage at the rated frequency.
7. In case of sustained overload conditions,the
transformer should not be allowed to operate for long
duration.
PROTECTION OF POWER TRANSFORMERS
(A) PERCENTAGE DIFFERENTIAL PROTECTION
This scheme is employed for the protection of
transformers against internal short circuits. It provides the
best overall protection for internal faults.However in case
of ungroundedor high impedance grounding it cannot
provide ground fault protection.
6
The following factors affect the differential current in
transformers and should be consideredwhile applying
differential protection. These factors can result in a
differential current even underbalanced power in & out
conditions:
1.Magnetizing inrush current– The normal magnetizing
current drawn is 2–5% of therated current. However
during Magnetizing inrush the current can be as high as
8–30times the rated current for typically 10 cycles,
depending upon the transformer andsystem resistance.
2. Overexcitation–This is normally of concern in
generator–transformer units.Transformers are typically
designed to operate just below the flux saturation level.
Anyfurther increase from the max permissible voltage
level (or Voltage/Frequency ratio), could lead to
saturation of the core, in turn leading to substantial
increase in theexcitation current drawn by the
transformer.
3. CT Saturation – External fault currents can lead to CT
saturation. This can cause relayoperating current to flow
due to distortion of the saturated CT current.
7
4. Different primary and secondary voltage levels, that is
the primary & secondary CT’s areof different types and
ratios
5. Phase displacement in Delta-Wye transformers.
Transformer Differential Relay
To account for the above variables less sensitive
Percentage Differential Relays withpercentage
characteristics in the range of 15 to 60% are applied to
transformers. Additionally, inmodern microprocessor and
numeric relays harmonic restraints can be applied.
Transformer Differential RelayConnections:
8
Fig. Percentage Differential Relay Connections
Harmonic Restraint:
The percentage differential scheme tends to maloperate
due to magnetizing inrush.The inrush current waveform is
rich in harmonics whereas the internal fault current
consists of only the fundamental component. So to solve
the problem of inrush current, which is neither an
abnormal condition nor a fault, additional restraint is
developed which comes to picture only during inrush
condition and is ineffective during internal faults.
(B) RESTRICTED EARTH FAULT PROTECTION :
9
A percentage differential relay has a certain minimum
value of pick up for internal faults.Faults with current
below this value are not detected by the relay.
Winding-to-core faults, which are single phase to
ground type, involving high resistance,fall in this
category.
Therefore for such type of faults RESTRICTED EARTH
FAULT PROTECTION is used.The reach of such a
protection must be restricted to the winding of the
transformer; otherwise it may operate for any ground
fault, anywhere in the system, beyond the transformer,
hence the name of this scheme.
10
EARTH FAULT PROTECTION FOR THE DELTA
SIDE OF DELTA STAR TRANSFORMER :
(C) OVER CURRENT PROTECTION :
Over current protection is used for the purpose of
providing back up protection for large transformers.
(above 5MVA).Two phase fault and one ground fault
relay is sufficient to provide OC protection to star delta
transformer.
11
(D) PROTECTION AGAINST OVERFLUXING :
The magnetic flux increases when voltage increases. This
results in increased iron loss and magnetizing current. The
core and core bolts gets heated and the lamination
insulation is affected. Protection against overfluxing is
required where overfluxing due to sustained overvoltage
can occur.The reduction in frequency also increases the
flux density and thus has the same effect of overfluxing.
The expression for flux ina transformer is given by
Φ = K E/f
Where Φ = flux, f = frequency, E = applied voltage and K
is a constant.
12
To control flux, the ratio E/ f is controlled. When the ratio
exceeds a threshold value, it has to be detected. Electronic
circuits with suitable relays are available to measure this
ratio. Overfluxing does not require high speed tripping
and hence instantaneous operation is undesirable when
momentary disturbances occur. But the transformer
should be isolated in one or two minutes at the most if
overfluxing persists.
(E) PROTECTION AGAINST OVERHEATING :
The rating of a transformer depends on the temperature
rise above an assumed maximum ambient temperature.
Sustained overload is not allowed if the ambient
temperature is equal to the assumed ambient temperature.
The maximum safe overloading is that which doesnot
overheat the winding.The maximum allowed temperature
is about 95°C. Thus the protection against overload
depends on the winding temperature which is usually
measured by thermal image technique.
In thermal image technique,a temperature sensing device
like silicon resistor is placed in the transformer oil near
the top of the transformer tank. A CT is employed on the
L.V. side to supply current to a small heater. Both the
temperature sensing device and the heater are placed in a
small pocket. The silistor is used as an arm of a resistance
bridge supplied from the stabilized dc source. An
indicating instrument is energized from the out of balance
13
voltage of the bridge.Also the voltage across the silistor is
applied to a static control circuit which controls cooling
pumps and fans,gives warning of overheating and
ultimately trips the transformer circuit breakers.
(F) PROTECTION AGAINST INCIPIENT FAULTS:
INCIPIENT FAULTS: Faults which are not serious at the
beginning but which slowly develops into serious faults
are known as incipient faults.
BUCHHOLZRELAY :
It is a gas actuated relay. When a fault develops slowly,it
produces heat, thereby decomposing solid or liquid
insulating material in the transformer. The decomposition
of the insulating material produces inflammable gases.
The Buchholz relay gives an alarm when a specified
amount of gas is formed. The analysis of the gas collected
in the relay chamber indicates the type of the incipient
fault.
There is a chamber to accommodate Buchholz relay,in
between the transformer tank and the conservator.The
Buchholz relay is a slow acting device,the minimum
operating time is 0.1 s and the average time is 0.2 s. Too
sensitive settings of the mercury contacts is undesirable
because they are subjected to false operation on shock and
vibration caused by conditions like mechanical shock to
the pipe,tap changer operation and heavy external faults.
14
Working : When an incipient fault such as a winding-to-
core fault or an inter-turn fault occurs on the transformer
winding, there is severe heating of the oil. This causes
gasesto be liberated from the oil around 350°C. There is a
build-up of oil pressure causing oilto rush into the
conservator. A vane is placed in the path of surge of oil
between thetransformer and the conservator. Aset of
contacts, operated by this vane, is used as tripcontacts of
the Buchholz relay This output of Buchholz relay may be
used to trip thetransformer.
15
The Buchholz relay also has another set of contacts
operated by a float. Thesecontacts stay open when the
transformer tank is filled with oil. However, in case
ofleakage of oil or decomposition of oil, the float sinks
causing the contacts to close. Lossof oil will no doubt
cause the transformer temperature to rise but does not
warrant immediate tripping. Hence, normally these
contacts are wired to an alarm which alertsthe operator.
GAS ANALYSIS :
The trapped gases in the conservator can give valuable
clue to the type of damage thattakes place inside the
transformer. This is because the insulation between the
windingturns, the insulation between the stampings of the
core and the oil, all liberate specificgases when they get
heated up due to a fault. The presence of these gases can
be usedas a signature of a particular type of damage that
may have taken place inside thetransformer.
16
PRESSURE RELIEF VALVE : An oil pressure
relief valve is fitted at the top of the transformer tank. It is
a spring controlled valve located at the end of an oil relief
pipe protruding from the top of the tank. Whenever a
surge in the oil is developed, it bursts , thereby allowing
the oil to discharge rapidly. It operates when the pressure
exceeds 10 psi but closes automatically when the pressure
falls below the critical level.This avoids the explosive
rupture of the tank and the risk of fire.
(G) PROTECTION AGAINST FIRE :
Power transformers are subject to fires from many
sources. Theyoften occur because of deterioration of
insulation in the transformer.This produces arcing which
in turn overheats the insulating oil andcauses the tanks to
rupture; further arcing then will start a fire. Firesare also
initiated by lightning and occasionally by dirty insulators
onthe outside of the tanks.
Proper maintenance can reduce these risks. Careful
protection againstfaults by shielding, grounding, lightning
arresters, interrupting devicesand relays can also decrease
the opportunity for a destructive fire.
In spite of protection by these measures and expert
maintenance, therisk of fire remains quite high, and a fire
protection system is alwaysrecommended and often
required. In addition, suppression systemsare frequently
installed.
17
Protection of a power transformer against fire
(H) PROTECTION AGAINST LIGHTNING:
Lightning overvoltage surges originate from atmospheric
discharges and they can reach their peak within a few
microseconds and subsequently decay very rapidly. The
surge voltage can reach up to 10 times the rated
transformer voltage and they pose the greatest threat to
transformers on the distribution networks. The charge
from the surge produces both short duration high current
18
impulse and long duration continuing current impulse
which affects the transformer insulation system.
Protection against such overvoltage surges can be
achieved by using Lightning Arresters.The distance
between the lightning (surge) arrester and the equipment
to be protected should be as short and straight as
possible. Therefore, integration of the surge arrester in
the equipment to be protected gives almost an ideal
protection.
Fig. Lightning Arrester used to protect the
powertransformer against lightning surges.
----------------------------------------------------------------------

More Related Content

What's hot

Power system protection seminar report
Power system protection seminar reportPower system protection seminar report
Power system protection seminar report
Rahul Aman
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
Partha Parida
 

What's hot (20)

Over current protection
Over current protectionOver current protection
Over current protection
 
Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protection
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Power system protection seminar report
Power system protection seminar reportPower system protection seminar report
Power system protection seminar report
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guide
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
 
Basics of overcurrent protection
Basics of overcurrent protectionBasics of overcurrent protection
Basics of overcurrent protection
 
Alternator protection
Alternator protectionAlternator protection
Alternator protection
 
surge arrester
surge arrestersurge arrester
surge arrester
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of Generator
 
Protective relay
Protective relay Protective relay
Protective relay
 
Over current Relays
Over current RelaysOver current Relays
Over current Relays
 
surge diverters
surge diverterssurge diverters
surge diverters
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
Relays
RelaysRelays
Relays
 

Similar to Protection of power transformer

pptonprotectionofpowertransformers-161020085118 (1).pdf
pptonprotectionofpowertransformers-161020085118 (1).pdfpptonprotectionofpowertransformers-161020085118 (1).pdf
pptonprotectionofpowertransformers-161020085118 (1).pdf
Sunny268892
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
Priten Vasa
 

Similar to Protection of power transformer (20)

Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, AllahabadSummer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
 
Electrical q
Electrical qElectrical q
Electrical q
 
Anurag Attri.pptx
Anurag Attri.pptxAnurag Attri.pptx
Anurag Attri.pptx
 
Differential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in SubstationDifferential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in Substation
 
Transformer Protection Fundamentals
Transformer Protection FundamentalsTransformer Protection Fundamentals
Transformer Protection Fundamentals
 
132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx
 
pptonprotectionofpowertransformers-161020085118 (1).pdf
pptonprotectionofpowertransformers-161020085118 (1).pdfpptonprotectionofpowertransformers-161020085118 (1).pdf
pptonprotectionofpowertransformers-161020085118 (1).pdf
 
protection of transformer
protection of transformerprotection of transformer
protection of transformer
 
Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)
 
s.pdf
s.pdfs.pdf
s.pdf
 
substation internship report
substation internship report substation internship report
substation internship report
 
INDUSTRIAL TRAINING:SWITCHYARD STUDY
INDUSTRIAL TRAINING:SWITCHYARD STUDYINDUSTRIAL TRAINING:SWITCHYARD STUDY
INDUSTRIAL TRAINING:SWITCHYARD STUDY
 
Transient Suppressors
Transient SuppressorsTransient Suppressors
Transient Suppressors
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppt
 
Presentation1.pptx power system
Presentation1.pptx power systemPresentation1.pptx power system
Presentation1.pptx power system
 
Seminar presentation
Seminar presentationSeminar presentation
Seminar presentation
 
Power quality & demand side management
Power quality & demand side managementPower quality & demand side management
Power quality & demand side management
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
Unit 05 Protection of feeders and bus-bars
Unit  05 Protection of feeders and bus-bars Unit  05 Protection of feeders and bus-bars
Unit 05 Protection of feeders and bus-bars
 
Sub station training
Sub station trainingSub station training
Sub station training
 

Recently uploaded

Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in DelhiRussian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
kauryashika82
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
QucHHunhnh
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdf
ciinovamais
 

Recently uploaded (20)

Application orientated numerical on hev.ppt
Application orientated numerical on hev.pptApplication orientated numerical on hev.ppt
Application orientated numerical on hev.ppt
 
How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17
 
General Principles of Intellectual Property: Concepts of Intellectual Proper...
General Principles of Intellectual Property: Concepts of Intellectual  Proper...General Principles of Intellectual Property: Concepts of Intellectual  Proper...
General Principles of Intellectual Property: Concepts of Intellectual Proper...
 
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in DelhiRussian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
 
Holdier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfHoldier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdf
 
Dyslexia AI Workshop for Slideshare.pptx
Dyslexia AI Workshop for Slideshare.pptxDyslexia AI Workshop for Slideshare.pptx
Dyslexia AI Workshop for Slideshare.pptx
 
psychiatric nursing HISTORY COLLECTION .docx
psychiatric  nursing HISTORY  COLLECTION  .docxpsychiatric  nursing HISTORY  COLLECTION  .docx
psychiatric nursing HISTORY COLLECTION .docx
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
 
TỔNG ÔN TẬP THI VÀO LỚP 10 MÔN TIẾNG ANH NĂM HỌC 2023 - 2024 CÓ ĐÁP ÁN (NGỮ Â...
TỔNG ÔN TẬP THI VÀO LỚP 10 MÔN TIẾNG ANH NĂM HỌC 2023 - 2024 CÓ ĐÁP ÁN (NGỮ Â...TỔNG ÔN TẬP THI VÀO LỚP 10 MÔN TIẾNG ANH NĂM HỌC 2023 - 2024 CÓ ĐÁP ÁN (NGỮ Â...
TỔNG ÔN TẬP THI VÀO LỚP 10 MÔN TIẾNG ANH NĂM HỌC 2023 - 2024 CÓ ĐÁP ÁN (NGỮ Â...
 
Sociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning ExhibitSociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning Exhibit
 
Kodo Millet PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
Kodo Millet  PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...Kodo Millet  PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
Kodo Millet PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
 
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdf
 
Micro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdfMicro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdf
 
Unit-IV; Professional Sales Representative (PSR).pptx
Unit-IV; Professional Sales Representative (PSR).pptxUnit-IV; Professional Sales Representative (PSR).pptx
Unit-IV; Professional Sales Representative (PSR).pptx
 
Mehran University Newsletter Vol-X, Issue-I, 2024
Mehran University Newsletter Vol-X, Issue-I, 2024Mehran University Newsletter Vol-X, Issue-I, 2024
Mehran University Newsletter Vol-X, Issue-I, 2024
 
Spatium Project Simulation student brief
Spatium Project Simulation student briefSpatium Project Simulation student brief
Spatium Project Simulation student brief
 
How to Create and Manage Wizard in Odoo 17
How to Create and Manage Wizard in Odoo 17How to Create and Manage Wizard in Odoo 17
How to Create and Manage Wizard in Odoo 17
 
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17  How to Extend Models Using Mixin ClassesMixin Classes in Odoo 17  How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
 
Key note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdfKey note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdf
 

Protection of power transformer

  • 2. 1 TRANSFORMER Introduction A transformer is a static electrical device used in electric power systems to transfer power between circuits through the use of electromagnetic induction. Transformers are devices that transfer energy from one circuit to another by means of a common magneticfield. When an alternating current flows in a conductor,a magnetic field exists around the conductor.If another conductor is placed in the field created by the first conductor such that the flux lines link the second conductor,then a voltage is induced into the second conductor.The use of a magnetic field from one coil to induce a voltage into a second coil is the principle on which transformer theory and application is based. Transformers range in size from thumbnail-sized used in microphones to units weighing hundreds of tons interconnecting the power grid.A wide range of transformer designs are used in electronic and electric
  • 3. 2 power applications. Transformers are essential for the transmission,distributionandutilization of electrical energy. Induction Law The transformer is based on two principles: 1. An electric current can produce a magnetic field. 2. A changing magnetic field within a coil of wire induces a voltage across the ends of the coil (electromagnetic induction). Referring to the figure here, current passing through the primary coil creates a magnetic field. The primary and secondary coils are wrapped around a core of very high magnetic permeability, so that most of the magnetic flux passes through both the primary and secondary coils. Any secondary winding connected load causes current
  • 4. 3 and voltage induction from primary to secondary circuits in indicated directions. POWER TRANSFORMERS The term power transformer is used to refer to those transformers used in the generatorand the distribution circuits, and these are usually rated at 500 KVA and above. Power systems typicallyconsist of a large number of generation locations, distribution points, and interconnections within thesystem or with nearby systems, such as a neighboring utility. The complexity of the system leads to avariety of transmission and distribution voltages. Power transformers must be used at each of these pointswhere there is a transition between voltage levels.
  • 5. 4 Fig.An example of a power transformer used in electric power system CAUSE OF FAULTS IN POWER TRANSFORMER Transformers are prone to variety of faults : 1. The most common type of fault being the winding to core faults because of weakening of insulation.Phase faults inside the transformers are rare.However,such faults may occur on terminals,which fall within the transformer protection zone. 2. Power transformers are generally provided with on-line tap changing (OLTC) gear.This is another major area of occurrence of fault.
  • 6. 5 3. All large transformers are oil immersed type.There is a possibility of oil leakage. 4. Transformers experience large inrush currents that are rich in harmonic content at the time of switching if they happen to be unloaded. 5. A transformer may develop inter turn faults giving rise to local hot spots within the winding. 6. Transformers may suffer from over fluxing due to under frequency operation at rated voltage.Over fluxing may also be caused when the transformer is subjected to over voltage at the rated frequency. 7. In case of sustained overload conditions,the transformer should not be allowed to operate for long duration. PROTECTION OF POWER TRANSFORMERS (A) PERCENTAGE DIFFERENTIAL PROTECTION This scheme is employed for the protection of transformers against internal short circuits. It provides the best overall protection for internal faults.However in case of ungroundedor high impedance grounding it cannot provide ground fault protection.
  • 7. 6 The following factors affect the differential current in transformers and should be consideredwhile applying differential protection. These factors can result in a differential current even underbalanced power in & out conditions: 1.Magnetizing inrush current– The normal magnetizing current drawn is 2–5% of therated current. However during Magnetizing inrush the current can be as high as 8–30times the rated current for typically 10 cycles, depending upon the transformer andsystem resistance. 2. Overexcitation–This is normally of concern in generator–transformer units.Transformers are typically designed to operate just below the flux saturation level. Anyfurther increase from the max permissible voltage level (or Voltage/Frequency ratio), could lead to saturation of the core, in turn leading to substantial increase in theexcitation current drawn by the transformer. 3. CT Saturation – External fault currents can lead to CT saturation. This can cause relayoperating current to flow due to distortion of the saturated CT current.
  • 8. 7 4. Different primary and secondary voltage levels, that is the primary & secondary CT’s areof different types and ratios 5. Phase displacement in Delta-Wye transformers. Transformer Differential Relay To account for the above variables less sensitive Percentage Differential Relays withpercentage characteristics in the range of 15 to 60% are applied to transformers. Additionally, inmodern microprocessor and numeric relays harmonic restraints can be applied. Transformer Differential RelayConnections:
  • 9. 8 Fig. Percentage Differential Relay Connections Harmonic Restraint: The percentage differential scheme tends to maloperate due to magnetizing inrush.The inrush current waveform is rich in harmonics whereas the internal fault current consists of only the fundamental component. So to solve the problem of inrush current, which is neither an abnormal condition nor a fault, additional restraint is developed which comes to picture only during inrush condition and is ineffective during internal faults. (B) RESTRICTED EARTH FAULT PROTECTION :
  • 10. 9 A percentage differential relay has a certain minimum value of pick up for internal faults.Faults with current below this value are not detected by the relay. Winding-to-core faults, which are single phase to ground type, involving high resistance,fall in this category. Therefore for such type of faults RESTRICTED EARTH FAULT PROTECTION is used.The reach of such a protection must be restricted to the winding of the transformer; otherwise it may operate for any ground fault, anywhere in the system, beyond the transformer, hence the name of this scheme.
  • 11. 10 EARTH FAULT PROTECTION FOR THE DELTA SIDE OF DELTA STAR TRANSFORMER : (C) OVER CURRENT PROTECTION : Over current protection is used for the purpose of providing back up protection for large transformers. (above 5MVA).Two phase fault and one ground fault relay is sufficient to provide OC protection to star delta transformer.
  • 12. 11 (D) PROTECTION AGAINST OVERFLUXING : The magnetic flux increases when voltage increases. This results in increased iron loss and magnetizing current. The core and core bolts gets heated and the lamination insulation is affected. Protection against overfluxing is required where overfluxing due to sustained overvoltage can occur.The reduction in frequency also increases the flux density and thus has the same effect of overfluxing. The expression for flux ina transformer is given by Φ = K E/f Where Φ = flux, f = frequency, E = applied voltage and K is a constant.
  • 13. 12 To control flux, the ratio E/ f is controlled. When the ratio exceeds a threshold value, it has to be detected. Electronic circuits with suitable relays are available to measure this ratio. Overfluxing does not require high speed tripping and hence instantaneous operation is undesirable when momentary disturbances occur. But the transformer should be isolated in one or two minutes at the most if overfluxing persists. (E) PROTECTION AGAINST OVERHEATING : The rating of a transformer depends on the temperature rise above an assumed maximum ambient temperature. Sustained overload is not allowed if the ambient temperature is equal to the assumed ambient temperature. The maximum safe overloading is that which doesnot overheat the winding.The maximum allowed temperature is about 95°C. Thus the protection against overload depends on the winding temperature which is usually measured by thermal image technique. In thermal image technique,a temperature sensing device like silicon resistor is placed in the transformer oil near the top of the transformer tank. A CT is employed on the L.V. side to supply current to a small heater. Both the temperature sensing device and the heater are placed in a small pocket. The silistor is used as an arm of a resistance bridge supplied from the stabilized dc source. An indicating instrument is energized from the out of balance
  • 14. 13 voltage of the bridge.Also the voltage across the silistor is applied to a static control circuit which controls cooling pumps and fans,gives warning of overheating and ultimately trips the transformer circuit breakers. (F) PROTECTION AGAINST INCIPIENT FAULTS: INCIPIENT FAULTS: Faults which are not serious at the beginning but which slowly develops into serious faults are known as incipient faults. BUCHHOLZRELAY : It is a gas actuated relay. When a fault develops slowly,it produces heat, thereby decomposing solid or liquid insulating material in the transformer. The decomposition of the insulating material produces inflammable gases. The Buchholz relay gives an alarm when a specified amount of gas is formed. The analysis of the gas collected in the relay chamber indicates the type of the incipient fault. There is a chamber to accommodate Buchholz relay,in between the transformer tank and the conservator.The Buchholz relay is a slow acting device,the minimum operating time is 0.1 s and the average time is 0.2 s. Too sensitive settings of the mercury contacts is undesirable because they are subjected to false operation on shock and vibration caused by conditions like mechanical shock to the pipe,tap changer operation and heavy external faults.
  • 15. 14 Working : When an incipient fault such as a winding-to- core fault or an inter-turn fault occurs on the transformer winding, there is severe heating of the oil. This causes gasesto be liberated from the oil around 350°C. There is a build-up of oil pressure causing oilto rush into the conservator. A vane is placed in the path of surge of oil between thetransformer and the conservator. Aset of contacts, operated by this vane, is used as tripcontacts of the Buchholz relay This output of Buchholz relay may be used to trip thetransformer.
  • 16. 15 The Buchholz relay also has another set of contacts operated by a float. Thesecontacts stay open when the transformer tank is filled with oil. However, in case ofleakage of oil or decomposition of oil, the float sinks causing the contacts to close. Lossof oil will no doubt cause the transformer temperature to rise but does not warrant immediate tripping. Hence, normally these contacts are wired to an alarm which alertsthe operator. GAS ANALYSIS : The trapped gases in the conservator can give valuable clue to the type of damage thattakes place inside the transformer. This is because the insulation between the windingturns, the insulation between the stampings of the core and the oil, all liberate specificgases when they get heated up due to a fault. The presence of these gases can be usedas a signature of a particular type of damage that may have taken place inside thetransformer.
  • 17. 16 PRESSURE RELIEF VALVE : An oil pressure relief valve is fitted at the top of the transformer tank. It is a spring controlled valve located at the end of an oil relief pipe protruding from the top of the tank. Whenever a surge in the oil is developed, it bursts , thereby allowing the oil to discharge rapidly. It operates when the pressure exceeds 10 psi but closes automatically when the pressure falls below the critical level.This avoids the explosive rupture of the tank and the risk of fire. (G) PROTECTION AGAINST FIRE : Power transformers are subject to fires from many sources. Theyoften occur because of deterioration of insulation in the transformer.This produces arcing which in turn overheats the insulating oil andcauses the tanks to rupture; further arcing then will start a fire. Firesare also initiated by lightning and occasionally by dirty insulators onthe outside of the tanks. Proper maintenance can reduce these risks. Careful protection againstfaults by shielding, grounding, lightning arresters, interrupting devicesand relays can also decrease the opportunity for a destructive fire. In spite of protection by these measures and expert maintenance, therisk of fire remains quite high, and a fire protection system is alwaysrecommended and often required. In addition, suppression systemsare frequently installed.
  • 18. 17 Protection of a power transformer against fire (H) PROTECTION AGAINST LIGHTNING: Lightning overvoltage surges originate from atmospheric discharges and they can reach their peak within a few microseconds and subsequently decay very rapidly. The surge voltage can reach up to 10 times the rated transformer voltage and they pose the greatest threat to transformers on the distribution networks. The charge from the surge produces both short duration high current
  • 19. 18 impulse and long duration continuing current impulse which affects the transformer insulation system. Protection against such overvoltage surges can be achieved by using Lightning Arresters.The distance between the lightning (surge) arrester and the equipment to be protected should be as short and straight as possible. Therefore, integration of the surge arrester in the equipment to be protected gives almost an ideal protection. Fig. Lightning Arrester used to protect the powertransformer against lightning surges. ----------------------------------------------------------------------