AWP x EWP
No. of =
luminaires (lumens/lamp) x (lamps/luminaires)
x CU x LLFTOTAL
The coefficient of utilization is a factor used to
determine the efficiency of a lighting fixture in
delivering light for a specific application
The coefficient of utilization is determined as a
ratio of light output from the luminaire that reaches
the workplane to the light output of the lamps alone
Coefficient of Utilization (CU)
Coefficient of Utilization (CU)
Factors influencing coefficient of utilization:
The efficiency of the luminaire
The luminaire distribution
The geometry of the space
The reflectance's of the room surface
Each luminaire has its own CU table specific to that
luminaire’s light distribution and efficiency. CU values are
listed in tables for different room geometries and room
surface reflectance.
For a given room, the cavity ratios are in direct proportion to
their respective cavity heights. For the case where the
luminaires are mounted on the surface of the ceiling or are
recessed into the ceiling, the ceiling cavity ratio is zero.
It is necessary to convert the actual ceiling reflectance into an
effective ceiling cavity reflectance (pCC) and the actual floor
reflectance must be converted to an effective floor cavity
reflectance (pFC).
CU Determination
Step 1. Determine the room cavity ratio using the equation below
Room cavity height (hRC) = Luminaire height – Workplane height
RCR = 5 x Room cavity height (Length + Width)
Length x Width
Step 2. Since the Lumen Method considers what occurs only
within the room cavity, the ceiling and floor reflection factor are
replaced with their effective reflectances.
Ceiling reflection factor:
70% For very light colours and white
50% For light colours
30% for medium shades
Wall reflection factor:
50% For light colours and white
30% For medium shades
10% For dark shades
To find the effective reflectance of a floor or ceiling
cavity, find the floor cavity ratio and ceiling cavity ratio using
the equations below
• Step 3. Find the effective cavity reflectances using cavity
surface reflectances.
Step 4. Once all room cavity reflectances and the
room cavity ratio are known, the CU value can be
determined by selecting the appropriate value from
the luminaire’s CU table.
Example 1
Classroom 20’ x 27’ x 12’ E=50 fc
WP= 2’-6” AFF
ρc= 80% hcc= 0.0’
ρw= 50% hrc= 9.5’
ρf= 20% hfc= 2.5’
fixture: fluorescent (#38)
maintenance: yearly
replacement: on burnout
voltages & ballast: normal
environment: medium clean
Example 1
Confirm fixture data
S: T.15.1 p. 641
Example 1
Complete #1-6
Example 1
7. Determine lumens per luminaire
Obtain lamp lumens from manufacturer’s data
(or see Stein: Chapter 12)
S: T. 12.5 p. 546
Lumen Flux
Method
8. Record
dimensional
data
20’
27’
0’
9.5’
2.5’
ρc= 80%
ρw= 50%
ρf= 20%
Coefficient of
Utilization
Factor(CU)
Calculation
9. Calculate
Cavity
Ratios
Example 1: Cavity Ratios
CR = 5 H x (L+W)/(L x W)
RCR = 5 Hrc x (L+W)/(LxW) = 4.1
CCR = 5 Hcc x (L+W)/(LxW) = 0
FCR = 5 Hfc x (L+W)/(LxW) = 1.1
Coefficient of
Utilization
Factor(CU)
Calculation
10. Calculate
Effective
Ceiling
Reflectance
3. Obtain effective ceiling reflectance:
Example 1: Coefficient of Utilization (CU)
S: T.15.2 p. 667
Example 1
11. Calculate
Effective
Floor
Reflectance
Stein: T.15.2 P. 666
3. Obtain effective ceiling reflectance:
Example 1: Coefficient of Utilization (CU)
S: T.15.2 p. 667
CU= 0.19  0.20
Example 1
12. Select CU
from mfr’s
data or see
CU=0.32
Example 1: Coefficient of Utilization (CU)
RCR CU
4.0 0.39
4.1 X
5.0 0.35
CU= 0.386
S: T.15.1 p. 641

More Related Content

What's hot

Lighting design considerations
Lighting design considerationsLighting design considerations
Lighting design considerations
mominzaki
 
Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings
Vijay Kumar
 
Building Services Engg. (Electrical installations)
Building Services Engg. (Electrical installations)Building Services Engg. (Electrical installations)
Building Services Engg. (Electrical installations)
Ritesh Ambadkar
 

What's hot (20)

Illumination Example 4
Illumination Example 4Illumination Example 4
Illumination Example 4
 
Lighting design considerations
Lighting design considerationsLighting design considerations
Lighting design considerations
 
Electrical wiring system
Electrical wiring systemElectrical wiring system
Electrical wiring system
 
Basics of Indoor Lighting
Basics of Indoor LightingBasics of Indoor Lighting
Basics of Indoor Lighting
 
Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings
 
electrical lighting calculation
electrical lighting calculationelectrical lighting calculation
electrical lighting calculation
 
Illumination basic and lightning scheme
Illumination basic and lightning schemeIllumination basic and lightning scheme
Illumination basic and lightning scheme
 
Illumination.
Illumination.Illumination.
Illumination.
 
Electrical lighting design and calculations
Electrical lighting design and calculationsElectrical lighting design and calculations
Electrical lighting design and calculations
 
Lighting Design - Theory and Calculations
Lighting Design - Theory and CalculationsLighting Design - Theory and Calculations
Lighting Design - Theory and Calculations
 
Load list calculation
Load list calculationLoad list calculation
Load list calculation
 
The illumination
The illuminationThe illumination
The illumination
 
Building Services Engg. (Electrical installations)
Building Services Engg. (Electrical installations)Building Services Engg. (Electrical installations)
Building Services Engg. (Electrical installations)
 
Lighting architecture notes lectureLighting architecture lecture 5
Lighting architecture notes lectureLighting architecture  lecture 5Lighting architecture notes lectureLighting architecture  lecture 5
Lighting architecture notes lectureLighting architecture lecture 5
 
BUILDING SERVICES-II (ELECTRICAL)
BUILDING SERVICES-II (ELECTRICAL)BUILDING SERVICES-II (ELECTRICAL)
BUILDING SERVICES-II (ELECTRICAL)
 
Building Service Chapter 1
Building Service Chapter 1Building Service Chapter 1
Building Service Chapter 1
 
The plumbing code
The plumbing codeThe plumbing code
The plumbing code
 
Building Services Electrical (MEP)
Building Services Electrical (MEP)Building Services Electrical (MEP)
Building Services Electrical (MEP)
 
sunpath diagrams- different forms and their uses in functional design
sunpath diagrams- different forms and their uses in functional designsunpath diagrams- different forms and their uses in functional design
sunpath diagrams- different forms and their uses in functional design
 
Light and architecture
Light and architectureLight and architecture
Light and architecture
 

Similar to Coefficient of utilization (cu)

How to measure illumination
How to measure illuminationHow to measure illumination
How to measure illumination
ajsatienza
 
(5) bs-ii-electricity-unit-v-2012-five
(5) bs-ii-electricity-unit-v-2012-five(5) bs-ii-electricity-unit-v-2012-five
(5) bs-ii-electricity-unit-v-2012-five
Battula Choudary
 
Technical Report - Lamp Performance vs Colour Quality
Technical Report - Lamp Performance vs Colour QualityTechnical Report - Lamp Performance vs Colour Quality
Technical Report - Lamp Performance vs Colour Quality
Martin Jesson
 

Similar to Coefficient of utilization (cu) (20)

Electrical Fixtures Electrical Fittings
Electrical Fixtures Electrical Fittings Electrical Fixtures Electrical Fittings
Electrical Fixtures Electrical Fittings
 
GROUP-8-BU-2.pptx
GROUP-8-BU-2.pptxGROUP-8-BU-2.pptx
GROUP-8-BU-2.pptx
 
Lighting & power design citam
Lighting & power design citamLighting & power design citam
Lighting & power design citam
 
288 lecture23 2011
288 lecture23 2011288 lecture23 2011
288 lecture23 2011
 
288Lecture23-2011.pptx
288Lecture23-2011.pptx288Lecture23-2011.pptx
288Lecture23-2011.pptx
 
How to measure illumination
How to measure illuminationHow to measure illumination
How to measure illumination
 
seminar 2021.pptx
seminar 2021.pptxseminar 2021.pptx
seminar 2021.pptx
 
Lighting design lecture
Lighting design lectureLighting design lecture
Lighting design lecture
 
Bb science project 2
Bb science project 2Bb science project 2
Bb science project 2
 
Lighting nilanka
Lighting nilankaLighting nilanka
Lighting nilanka
 
Building Science II
Building Science IIBuilding Science II
Building Science II
 
BUILDING SCIENCE 2 PROJECT 2 REPORT
BUILDING SCIENCE 2 PROJECT 2 REPORTBUILDING SCIENCE 2 PROJECT 2 REPORT
BUILDING SCIENCE 2 PROJECT 2 REPORT
 
Building science 2 final
Building science 2 finalBuilding science 2 final
Building science 2 final
 
(5) bs-ii-electricity-unit-v-2012-five
(5) bs-ii-electricity-unit-v-2012-five(5) bs-ii-electricity-unit-v-2012-five
(5) bs-ii-electricity-unit-v-2012-five
 
Technical Report - Lamp Performance vs Colour Quality
Technical Report - Lamp Performance vs Colour QualityTechnical Report - Lamp Performance vs Colour Quality
Technical Report - Lamp Performance vs Colour Quality
 
Building science ii project 2 (1)
Building science ii project 2  (1)Building science ii project 2  (1)
Building science ii project 2 (1)
 
lighting-design-essentials.pdf
lighting-design-essentials.pdflighting-design-essentials.pdf
lighting-design-essentials.pdf
 
Correlated Color Temperature and Total Luminous Flux Influenced by Electrical...
Correlated Color Temperature and Total Luminous Flux Influenced by Electrical...Correlated Color Temperature and Total Luminous Flux Influenced by Electrical...
Correlated Color Temperature and Total Luminous Flux Influenced by Electrical...
 
Lighting basics book
Lighting basics bookLighting basics book
Lighting basics book
 
Final distribution book and bms
Final distribution book and bmsFinal distribution book and bms
Final distribution book and bms
 

More from Shanid Pazhamkavil

More from Shanid Pazhamkavil (8)

Insulation Resistance Test
Insulation Resistance TestInsulation Resistance Test
Insulation Resistance Test
 
Electric motors
Electric motorsElectric motors
Electric motors
 
Concept of renewable energy-various forms of renewable energy
Concept of renewable energy-various forms of renewable energy Concept of renewable energy-various forms of renewable energy
Concept of renewable energy-various forms of renewable energy
 
energy efficient operation of Fans and blowers
energy efficient operation of Fans and blowersenergy efficient operation of Fans and blowers
energy efficient operation of Fans and blowers
 
Electric motors
Electric motorsElectric motors
Electric motors
 
Online detection and locating of faulty nodes using
Online detection and locating of faulty nodes using  Online detection and locating of faulty nodes using
Online detection and locating of faulty nodes using
 
Wind energy and constructional features
Wind energy and constructional featuresWind energy and constructional features
Wind energy and constructional features
 
Energy problem and energy auditing
Energy problem and energy auditingEnergy problem and energy auditing
Energy problem and energy auditing
 

Recently uploaded

Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 

Recently uploaded (20)

Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 

Coefficient of utilization (cu)

  • 1. AWP x EWP No. of = luminaires (lumens/lamp) x (lamps/luminaires) x CU x LLFTOTAL The coefficient of utilization is a factor used to determine the efficiency of a lighting fixture in delivering light for a specific application The coefficient of utilization is determined as a ratio of light output from the luminaire that reaches the workplane to the light output of the lamps alone Coefficient of Utilization (CU)
  • 2. Coefficient of Utilization (CU) Factors influencing coefficient of utilization: The efficiency of the luminaire The luminaire distribution The geometry of the space The reflectance's of the room surface Each luminaire has its own CU table specific to that luminaire’s light distribution and efficiency. CU values are listed in tables for different room geometries and room surface reflectance.
  • 3.
  • 4.
  • 5.
  • 6. For a given room, the cavity ratios are in direct proportion to their respective cavity heights. For the case where the luminaires are mounted on the surface of the ceiling or are recessed into the ceiling, the ceiling cavity ratio is zero. It is necessary to convert the actual ceiling reflectance into an effective ceiling cavity reflectance (pCC) and the actual floor reflectance must be converted to an effective floor cavity reflectance (pFC).
  • 7. CU Determination Step 1. Determine the room cavity ratio using the equation below Room cavity height (hRC) = Luminaire height – Workplane height RCR = 5 x Room cavity height (Length + Width) Length x Width
  • 8. Step 2. Since the Lumen Method considers what occurs only within the room cavity, the ceiling and floor reflection factor are replaced with their effective reflectances. Ceiling reflection factor: 70% For very light colours and white 50% For light colours 30% for medium shades Wall reflection factor: 50% For light colours and white 30% For medium shades 10% For dark shades
  • 9. To find the effective reflectance of a floor or ceiling cavity, find the floor cavity ratio and ceiling cavity ratio using the equations below
  • 10. • Step 3. Find the effective cavity reflectances using cavity surface reflectances.
  • 11. Step 4. Once all room cavity reflectances and the room cavity ratio are known, the CU value can be determined by selecting the appropriate value from the luminaire’s CU table.
  • 12. Example 1 Classroom 20’ x 27’ x 12’ E=50 fc WP= 2’-6” AFF ρc= 80% hcc= 0.0’ ρw= 50% hrc= 9.5’ ρf= 20% hfc= 2.5’ fixture: fluorescent (#38) maintenance: yearly replacement: on burnout voltages & ballast: normal environment: medium clean
  • 13. Example 1 Confirm fixture data S: T.15.1 p. 641
  • 15. Example 1 7. Determine lumens per luminaire Obtain lamp lumens from manufacturer’s data (or see Stein: Chapter 12) S: T. 12.5 p. 546
  • 18. Example 1: Cavity Ratios CR = 5 H x (L+W)/(L x W) RCR = 5 Hrc x (L+W)/(LxW) = 4.1 CCR = 5 Hcc x (L+W)/(LxW) = 0 FCR = 5 Hfc x (L+W)/(LxW) = 1.1
  • 20. 3. Obtain effective ceiling reflectance: Example 1: Coefficient of Utilization (CU) S: T.15.2 p. 667
  • 22. 3. Obtain effective ceiling reflectance: Example 1: Coefficient of Utilization (CU) S: T.15.2 p. 667 CU= 0.19  0.20
  • 23. Example 1 12. Select CU from mfr’s data or see
  • 24. CU=0.32 Example 1: Coefficient of Utilization (CU) RCR CU 4.0 0.39 4.1 X 5.0 0.35 CU= 0.386 S: T.15.1 p. 641