Home Condition Survey
Property Address:



                                   Sample survey report

Report Reference Number:        xxxxxxx

Date of Inspection:        16 January 2008




                              Page 1 of 27
Contents

Introduction and terms on which this report is prepared

       Introduction
       What this report tells you
       What this report does not tell you
       What is inspected
       Condition rating definition
       How the inspection is carried out


Section A - General information

Section B - Summary and general description

Section C - Conveyancing and health and safety issues

Section D - Outside condition

Section E - Inside condition

Section F - Services

Section G - Grounds (including shared parts for flats)

Information about SAVA and your surveyor

Photographs
Introduction and terms on which this report is prepared


Introduction

When you buy a home it is sensible to have an independent report on the condition of the property.

This Home Condition Survey is produced by a surveyor who is a member of the SAVA Home Inspector
Certification Scheme. The surveyor must provide an objective opinion about the condition of the property
which you, as the buyer, will be able to rely on and use.

To become a member of The SAVA Home Inspector Certification Scheme and be able to produce Home
Condition Surveys, the surveyor has to:

    �   Pass an assessment of skills, in line with National Occupational Standards; and obtain the Diploma
        in Home Inspection
    �   Have insurance that provides cover if a surveyor is negligent

The surveyor must follow the inspection standards and code of conduct set by SAVA. To ensure
compliance all members are continuously monitored and before membership is granted a Criminal Records
Bureau check is undertaken. SAVA can revoke membership if a surveyor fails to maintain the expected
professional or ethical standards.

The Home Condition Survey is in a standard format and is based on these terms, which set out what you
should expect of both the surveyor and the Home Condition Survey. Neither you nor the surveyor can
amend these terms for the survey to be covered by the SAVA Certification Scheme. The surveyor may
provide you with other services, however, any other services the surveyor may provide are not covered by
these terms nor by the SAVA Certification Scheme and so must be covered by a separate contract.

All surveyors who are members of the SAVA Home Inspector Certification Scheme have a complaints
procedure which can be escalated to SAVA. If you have any complaint about this report, you can complain
by following the complaints procedure. This is explained in more detail towards the end of this document.

What this report tells you

This report tells you:

    �   About the construction and condition of the home on the date it was inspected
    �   Whether more enquiries or investigations are needed
    �   The Reinstatement Cost for insurance purposes derived from data supplied by the Building Cost
        Information Service (BCIS) except where the property is very large or historic, or if it incorporates
        special features, or is of unusual construction not covered by the Building Cost Information Service;
        in which circumstance a specialist would be needed to assess the reinstatement cost


The main aim of the report is to tell you about any defects that need urgent attention or are serious. It also
tells you about things that need further investigations to prevent damage to the structure of the building.

The report applies ‘condition ratings’ to the major parts of the main building (it does not give condition
ratings to outbuildings). The property is broken down into separate elements and each element has been
given a condition rating 1, 2 or 3 or NI – see more on definitions below.

What this report does not tell you:

This report does not tell you the value of your home or cover things that will be considered when a
valuation is provided, such as the area the home is in or the availability of public transport or facilities.

It does not tell you about any minor defects that would not normally affect your decision to buy.

    �   The report does not give advice on the cost of any repair work or the types of repair which should be
        used
    �   The report is not an asbestos inspection under the Control of Asbestos at Work Regulations 2002
If you need advice on subjects that are not covered by the Home Condition Survey, you must arrange for it
to be provided separately.

What is inspected?

The surveyor undertakes a visual inspection of the inside and outside of the main building and all
permanent outbuildings, and the parts of the gas, electricity, water and drainage services that can be seen.

Condition rating definition

The surveyor gives each part of the structure of the main building a condition rating, to make the report
easy to follow. The condition ratings are as follows.

    �   Condition Rating 1
        No repair is currently needed. Normal maintenance must be carried out
    �   Condition Rating 2
        Repairs or replacements are needed but the surveyor does not consider these to be serious or
        urgent
    �   Condition Rating 3
        These are defects which are either serious and/or require urgent repair or replacement or where the
        surveyor feels that further investigation is required (for instance where he/she has reason to believe
        repair work is needed but an invasive investigation is required to confirm this). A serious defect is
        one which could lead to rapid deterioration in the property or one which is likely to cost more than
        2.5% of the reinstatement cost to put right. You may wish to obtain quotes for additional work where
        a condition rating 3 is given, prior to exchange of contract
    �   NI
        Not inspected (see “How the Inspection is carried out” below)

How the Inspection is carried out

The inspection is visual and non invasive. This means that the surveyor does not take up carpets, floor
coverings or floorboards, move heavy furniture or remove contents of cupboards. Also, the surveyor does
not remove secure panels or undo electrical fittings.

The surveyor will state at the start of sections D, E and F of the report if it was not possible to inspect any
parts of the home that are normally reported on. If the surveyor is concerned about these parts, the report
will tell you about any further investigations that are needed. The surveyor does not provide estimates on
the cost of any work to correct defects or comment on how repairs should be carried out.
Section A - General Information

 Full address and
 postcode of the
 property




Surveyor's name        Mr John Smith

Report reference
number

Surveyor's SAVA
                       SAVA00XXXX
membership number



Company/organisation
                       Chichester & District Home Information Pack Servic
name

Company address
                       31 Whyke Lane, Chichester, PO19 7US
and postcode

Company contact        Email             info@chips.uk.com
details
                       Telephone         08703 834 805

                       Fax               07092 875 218



Date of inspection     16 January 2008
Section B - Summary

 Type of property              The property is a detached bungalow.

 Approximate year
 when property was             The property was built around 1981.
 built

 If converted from
 another use,
 approximate year              Not converted.
 when property was
 converted

 Approximate year
 when property was             The rear extension was built in 1989.
 extended

 Weather conditions at
                               It was dry at the time of the inspection.
 the time of inspection

 The state of the
 property when                 The property was occupied, in a habitable condition and fully furnished. .
 inspected

 Is the property in an
 area with special             No.
 restrictions?

 Property listing              Not listed.


                                             Summary of Accomodation
            Living     Bed      Bath or      Separate             Utility   Conser-   Other     Name(s) of other
Storey                                                  Kitchen
            rooms      rooms    shower       toilet               room(s)   vatory    room(s)   room(s)
Lower
ground

Ground          2        3             2                   1                              1          Study

First

Second

Third

Fourth

Roof
space

TOTALS          2        3             2         0         1          0         0         1             -
Gross external floor
area in square                 158m²
metres
Reinstatement                         Note: This reinstatement cost is the estimated cost of completely rebuilding the
                        £ 223000
 Cost                                  property based on information from BCIS, a service which provides building cost
                                       information and which is approved by the Association of British Insurers. It
                                       represents the sum at which the home should be insured against fire and other
                                       risks. It is based on building and other related costs and does not include the
                                       value of the land the home is built on. It does not include leisure facilities such
                                       as swimming pools and tennis courts. The figure should be reviewed regularly as
                                       building costs change. Importantly, it is not a valuation of the property.

                                       If the property is very large or historic, or if it incorporates special features or is of
                                       unusual construction, then BCIS data cannot cover it and a specialist would be
                                       needed to assess the reinstatement cost. In such circumstances no cost figure
                                       is provided and the report will indicate that a specialist is needed.



General Description


 A short general         XXXX is a detached bungalow originally constructed in 1980/1. The walls are
 description of the      of brick-block cavity construction and there is evidence that the cavity has
 construction (main      been retro filled with insulation material. The roof is of trussed timber
 walls, roof, floors,    construction and is covered with concrete interlocking tiles. The windows are
 windows)                all uPVC framed double glazed units which were fitted (according to the sellers
                         information supplied) in 1999. At the rear of the property is a single storey
                         cavity walled extension constructed in 1989 (again, according to information
                         supplied). Detached from the property is a brick built double garage with felt
                         flat roof.



 Summary of mains        Drainage                             A mains drainage system is present.
 services
                         Gas                                  No mains gas connected.

                         Electricity                          Mains electricity connected.

                         Water                                Mains water supply connected.

 Central heating         The central heating is provided by an oil fired boiler feeding hot water radiators
                         in most rooms. The boiler is a Myson Velaire 50/70 believed to have been
                         fitted when the property was originally built (information supplied by the
                         sellers). The heating and hot water are controlled by a thermostat integral with
                         the boiler and a wall mounted programmer.

 Outside facilities      There is a double on site garage. There are 6 parking spaces located onsite.
                         There are no permanent outbuildings.
                         All roads and footpaths are made-up unless otherwise stated.
A Summary of the Condition Ratings

Section of the Report   Part   Name                                     Identifier (if more than one)   Rating
                        No
D: Outside              D1     Chimney stacks                                                              1
                        D2     Roof coverings                                                              1
                        D3     Rainwater pipes & gutters                                                   1
                        D4     Main walls (including claddings)                                            1
                        D5     Windows                                                                     1
                        D6     Outside doors (incl. patio doors)                                           1
                        D7     All other woodwork                                                          1
                        D8     Outside decoration                                                          X
                        D9     Other outside detail                                                        X
E: Inside               E1     Roof structure                                                              1
                        E2     Ceilings                                                                    1
                        E3     Inside walls, partitions & plasterwork                                      1
                        E4     Floors                                                                      1
                        E5     Fireplaces & chimney breasts                                                3
                        E6     Built-in fittings                                                           1
                        E7     Inside woodwork                                                             1
                        E8     Bathroom fittings                                                           1
                        E9     Other issues                                                                X
F: Services             F1     Electricity                                                                 1
                        F2     Gas / Oil                                                                   1
                        F3     Water                                                                       1
                        F4     Heating                                                                     1
                        F5     Drainage                                                                    1
Summary of Structural Movement

There is no evidence of structural movement.




Summary of Dampness

High moisture meter readings were recorded in the roofspace on the chimney breast serving the central
heating boiler. This is the westerly chimney, to the right of the property when viewed from the front.




Further Investigations

Your attention is drawn to the following matters for which further investigation is recommended by someone
who is appropriately qualified.


Recommended investigation of defects seen or          dampness
suspected.
Section C - Issues for Conveyancers and Health and Safety Issues

Issues for Conveyancers

The surveyor does not act as 'the conveyancer'. If during the inspection, however, the surveyor identifies
issues that your conveyancer may need to investigate further, the surveyor will refer to these in the report
and you should give your conveyancer a copy of this report.

The surveyor will not have seen the legal and other documents.

     Roads and footpaths

     Drainage

     Water

     Drains

     Planning and other permissions needed


     Freehold owner consents

     Flying freeholds

     Mining

     Rights of way
                                                          The boundary to the right side of the property is
     Boundaries (including party walls)                   undefined.


     Easements

     Repairs to shared parts

     Previous structural repairs

     New building warranties

     Building insurance (ongoing claims)


     Tree preservation orders

     Property let
                                                          There is a grille for the public drain located at the
                                                          front of the property (adjacent to the road) within
     Drain to front                                       the apparent boundaries of the property. You
                                                          should investigate any matters that may relate to
                                                          this.
Contaminated Land and Flooding

The surveyor assumes that the home is not built with, nor contains, hazardous materials and is not built on
contaminated land. If any materials are found during the inspection which may contain hazardous materials,
or if the surveyor finds any evidence to suggest that the land may be contaminated, this will be shown here
along with recommendations for further investigations.

                                                          The property is understood to be situated near an
     Contamination                                        area of land that may be affected by
                                                          contamination.

     Flooding

Health and Safety Risks

These will include defects that require repair or replacement as well as issues that have existed for a long
time and cannot reasonably be changed, but may present a risk to occupiers or visitors.

     Escape windows

     Fire control

     Fire doors

     Safety glass


     Lead pipes

     Radon gas

     Gas

     Handrails


     Asbestos

     Unsafe fittings
                                                          There is no evidence to confirm the recent testing
                                                          and / or servicing of the boiler. Failure to test the
                                                          services increases the safety risk.

     Recent testing                                       There is no evidence to confirm the recent testing
                                                          and / or servicing of the electrical installation.
                                                          Failure to test the services increases the safety
                                                          risk.

     Inappropriate living
Handrail position

Banister spacing

Insect nests

Smoke detector

Roof space partition
Section D - Outside Condition

The surveyor carries out a visual, non invasive inspection of the outside of the main building and permanent
outbuildings from various points within the boundaries of the property and from public areas such as
footpaths and open spaces, but does not enter neighbouring private property. High level features are
inspected either from a point within the property using binoculars or using a ladder, where it is safe to do so.
Due to the risk of causing damage, the surveyor does not walk on any flat roofs.

When inspecting blocks of flats it is often difficult to see the whole outside of a building or block and its
maintenance is rarely the responsibility of one person. The surveyor only carries out a non invasive
inspection to the level of detail set out above to the main walls, windows and roof over the flat. The surveyor
does not inspect the rest of the block to this level of detail but instead has formed an opinion based on a
general inspection of the rest of the block. Information is given about the outside and shared parts so that
the conveyancer can check whether the maintenance clauses in the lease or other title documents are
adequate. The surveyor inspects the shared access to the flat together with the area where car parking and
any garage for the flat are, along with access to that area, but does not inspect other shared parts (such as
separate hall, stairs and access ways to other flats in the block, the lift motor room and cleaning cupboards.)

                  Description and Justification for Rating and any comments                Condition Rating




 D1.              There are two chimney stacks. Both are brick built.
 Chimney
 stacks           Normal maintenance must be undertaken.
                  The chimney stack to the right (west) side shows some signs of salt
                  deposits on the brick surfaces. This is associated with damp                      1
                  recorded within the roofspace. See section E5.
                  The sellers advise that the "main chimney" (assumed to mean the
                  left side, or east, chimney) was rebuilt above roof level after being
                  blown down during storms in 1987.


 D2.              The main roof is pitched and covered with concrete interlocking
 Roof             tiles. The extension roof is pitched and covered with concrete
 coverings        interlocking tiles.

                  Normal maintenance must be undertaken.
                  All the roof pitches appear to be in good condition with no evidence
                  of slipped or broken tiles.                                                       1
                  There is some moss growth on most roof pitches which should be
                  cleared periodically to prevent undue weight build-up on the roof
                  surface. The valley gutter between the roof pitches at the front of
                  the property (above the main entrance area) is partially blocked
                  with debris and moss. This should be cleared out.
D3.            The rainwater fittings are PVC.
Rainwater
pipes &        No repair is presently required. Normal maintenance must be
gutters        undertaken.
                                                                                        1
               As it was dry at the time of inspection it was not possible to check
               the operation of the gutters and downpipes. However surface moss
               growth on the gutters suggests that they may overflow at times.
               This is probably due to debris and moss and therefore may require
               cleaning out.


D4.            The outside walls are brick faced and of cavity construction. There
Main walls     is evidence of retro fitted cavity wall insulation.
(including
claddings)     No repair is presently required. Normal maintenance must be
               undertaken.
               Minor cracking in the mortar-brick joints was seen in some areas,
                                                                                        1
               notably to the right side of the front wall. These cracks are probably
               due to thermal movement of the brickwork and are a minor defect.
               Some areas of soft and flaking mortar were found, notably on the
               left side wall towards the front of the property. This is probably due
               to the mortar mix used in the original construction.
               For both these defects some repointing is required.


D5.            The windows are PVCu and are double glazed.
Windows
               No repair is presently required. Normal maintenance must be              1
               undertaken.
               The sellers advise that the windows were replaced in 1999.


D6.            The outside doors are PVCu with glazed panels.
Outside
doors (incl.   No repair is presently required. Normal maintenance must be              1
patio doors)   undertaken.



D7.            The other woodwork includes such items as woodwork at the roof
All other      edges and cladding to the front of the property.
woodwork
                                                                                        1
               No repair is presently required.
               All woodwork has been replaced by uPVC cladding. The sellers
               advise that this was fitted in 2003.
Section E - Inside Condition

The surveyor carries out a visual, non invasive inspection of all the parts of the home that can be seen
without causing damage to the fabric of the property or any fixtures, fittings or furnishings present at the time
of inspection.

The surveyor checks for damp in vulnerable areas by using a moisture-measuring meter.

The surveyor inspects the roof structure from inside the roof space where it is safe to access and move
around the roof space, but will not move or lift insulation material, stored goods and other contents. A
representative selection of windows and all doors will be opened unless the surveyor determines that to do
so could compromise the security of the property or they are locked and no key is available at the time of
inspection.

Floor surfaces are inspected where readily and safely accessible, but fitted floor coverings and heavy
furniture are not moved.

The surveyor does not comment on sound insulation or noise.

The surveyor inspects the inside of the flat in the same way as is described under ‘The outside of the
property’ in section D. They inspect the roof space however, only where they can get safe access from
within the flat itself and where there is no risk of trespass. The surveyor does not go into the roof space if
access is only possible from the shared parts or from within another flat.

                  Description and Justification for Rating and any comments                 Condition Rating




 E1.              The extension roof is constructed using a prefabricated timber
 Roof             frame. The main roof is constructed using a prefabricated timber
 structure        frame.

                  No repair is presently required.
                  The structure of the roof prevented safe access to all areas of the                1
                  roof space but those areas of the timbers inspected were found to
                  be free from dampness, cracking, rot or other defects.
                  The roof is lined with approximately 100mm of wool type insulating
                  material at joist level. Current recommendations are for 250mm of
                  insulation in the roof space.


 E2.              The ceilings are constructed from plasterboard and finished with
 Ceilings         textured paint.

                  No repair is presently required. Normal maintenance must be
                  undertaken.
                                                                                                     1
                  There is some cracking to ceilings in most rooms, and evidence of
                  previous repairs in the living room. The cracking is mostly confined
                  to areas that would correspond to joints in the sheets of
                  plasterboard used at the time of construction and are not significant
                  or indicative of more serious movement of the property.
E3.             The internal walls and partitions are partly of masonry and partly of
Inside walls,   timber construction.
partitions &
plasterwork     No repair is presently required.
                                                                                          1
                Timber stud walls have been used to create a small office from an
                area of the rear bedroom. You should ensure that any work
                associated with this construction met regulatory requirements at
                the time of construction.


E4.             The floors are of concrete construction.
Floors
                No repair is presently required.
                                                                                          1
                The floors are laid with fitted carpet, vinyl or laminate coverings and
                cannot therefore be directly inspected. However no undue
                unevenness or dampness was noted.


E5.             The chimney breasts are of masonry construction.
Fireplaces &    The easterly (to the left when viewed from the front of the property)
chimney         chimney serves an open fire in the living room.
breasts         The westerly chimney serves the boiler in the kitchen.

                This is considered serious and in need of urgent repair or
                replacement. Further advice should be obtained.
                Very high moisture meter readings were recorded on the westerley
                chimney breast at upper levels in the roof space. The mortar was          3
                found to be soft and crumbly and salt deposits were noted on the
                brickwork. No parts of the chimney breast can be examined at
                ground level. The evidence suggests that exhaust gasses from the
                boiler are leeching into the brickwork of the chimney breast. This
                may be due to the absence or failure of the chimney liner, and
                requires urgent rectification.
                Examination of the easterly chimney breast suggests that a liner is
                present and that no such similar defect is present.


E6.             The kitchen fittings are modern. The fitted wardrobes are modern.
Built-in
                                                                                          1
fittings        No repair is presently required. Normal maintenance must be
                undertaken.


E7.             The internal woodwork includes such items as: doors, frames, and
Inside          skirting.
woodwork                                                                                  1
                No repair is presently required. Normal maintenance must be
                undertaken.
E8.        The sanitary fittings in the main bathroom include such items as:
Bathroom   bath, basin, WC, and are of good quality.
fittings   The sanitary fittings in the en-suite bathroom include such items as:
           shower, basin, WC, and are of good quality.

           No repair is presently required. Normal maintenance must be             1
           undertaken.
           The operation of all facilities was checked and found to be
           satisfactory. It was noted that there was a long delay before hot
           water was delivered from the taps, due to the long run of pipework
           from the hot water cylinder.
Section F - Services

The surveyor carries out a visual, non invasive inspection of the services, but specialist tests are not carried
out. If any services (such as the boiler or mains water) are turned off, the surveyor will state that in the report
and will not turn them on.

The surveyor reports only on the services covered in this section (electricity, gas, oil, water, heating and
drainage). All other services and domestic appliances are not included in the inspection: for example
security and door answering systems, smoke alarms, television, cable, wireless and satellite communication
systems, cookers, hobs, washing machines and fridges (even where built in).

                  Description and Justification for Rating and any comments                  Condition Rating


 F1.              There is an electrical supply and the meter and consumer unit [fuse
 Electricity      box] are located in the high level cupboard in the kitchen.

                  No repair is presently required. Normal maintenance must be
                                                                                                      1
                  undertaken.
                  The consumer unit is an older hard wired cartridge fuse type.
                  There is no evidence of recent inspection of the electrical system.
                  See section C6.


 F2.              There is an oil store that is located on the side path to the right side
 Gas / Oil        of the property.

                  No repair is presently required. Normal maintenance must be
                                                                                                      1
                  undertaken.
                  The 1200 litre plastic oil storage tank feeds the oil fired boiler
                  through a pipe running along the side of the property. This pipe
                  could be vulnerable to damage and care should therefore be taken.


 F3.              There is a mains water supply. The pipework is copper and the
 Water            stop valve is in the kitchen.

                  No repair is presently required. Normal maintenance must be
                  undertaken.
                  Hot water is supplied from a standard low pressure hot water
                  system. The cold water cistern is located in the roof space and is
                                                                                                      1
                  adequately insulated and supported.
                  The hot water storage tank is located in a cupboard in the hallway.
                  It has a single immersion heater element fitted and approximately
                  30mm of spray foam insulation.
                  Examination of the pipework associated with the hot water system
                  revealed no obvious defects other than some peeling of the hot
                  water storage tank insulation.


 F4.              The heating and hot water is provided by an oil boiler.
 Heating
                  No repair is presently required. Normal maintenance must be
                  undertaken.
                                                                                                      1
                  The sellers indicate that the boiler was fitted at the time of original
                  construction of the property and is therefore in excess of 20 years
                  old. More modern heating systems would feature more efficient
                  boilers, and wall/radiator thermostats.
F5.        There is a mains drainage system.
Drainage
           No repair is presently required. Normal maintenance must be
           undertaken.
           There are five inspection chambers located within the boundaries
                                                                                  1
           of the property. The covers for three of these were lifted and water
           run through the drains. Water was seen to run freely from the
           chambers at the right side of the property to the chamber closest to
           the road.
Section G - Grounds (including shared parts for flats)

The surveyor inspects the condition of the boundary walls, outbuildings and areas in common (shared) use
from within the grounds and any public areas, but not from neighbouring private property.

The report provides a summary of the general condition of any garden walls, fences and permanent
outbuildings. Conservatories with translucent or clear roofs attached to the main building are treated as
outbuildings, as are garages and permanent store sheds. Buildings containing swimming pools and sports
facilities are also treated as outbuildings, but the surveyor does not report on the leisure facilities such as the
pool itself and its equipment.

                      Description and comments


 Garages              There is a brick built double garage to the rear side of the main building. The garage
                      has a flat bitumen felt roof. No leaks in the roof were apparent at the time of
                      inspection. The garage is fitted with power and light, and a metal up and over type
                      door which appears to operate normally. Some areas of rot were noted at the bottom
                      of the door frames, but otherwise the garage appears to be in good condition.


 Conservatories       There is no conservatory.


 Permanent            There are no permanent outbuildings.
 outbuildings


 Boundary and         The boundaries are defined by a mixture of timber fencing and trees/shrubs. The
 retaining walls      fences appear to be in good condition. The front boundary to the right of the property
                      comprises conifer trees but it is unclear exactly where the boundary lies. This should
                      be clarified with your conveyancer.


 Paved areas          There are paved areas and paths to the front and side consisting of tarmacadam that
                      are uneven and moss covered. This makes them dangerous when wet and liable to
                      ponding.


 Grounds              The grounds to the front and rear are mainly lawned with associated flower borders.
                      The grounds appear to be well tended. The proximity of any trees does not currently
                      present any threat to the buildings.


 Common
 (shared) areas
Information about SAVA and your surveyor

All Home Condition Surveys are produced by a surveyor who is a member of SAVA Home Inspector
Certification Scheme. All reports are held on a register kept by SAVA. The insurance company which
provides professional indemnity cover for the surveyor requires that we keep a register for the purposes of
monitoring the competency of the surveyor and in order to undertake an investigation if you have a
complaint about this report or the surveyor.


 Surveyor's
                            SAVA00XXXX
 membership number

 Name                       Mr John Smith

 Qualifications             DipHI

 Address                    31 Whyke Lane, Chichester, PO19 7US

 Contact details            Email                @chips.uk.com

                            Telephone          08703 834 805

                            Fax                07092 875 218

 Date of making the
                            16 January 2008
 report


Signature



What to do if you have a complaint

    If you have a complaint about this Home Condition Survey or the surveyor who carried it out you
    should follow the procedures set out below:­

        �   Ask the company who provided the report (the company named on the front of the report) or
            the surveyor who carried out the report to give you a copy of its complaints handling
            procedure. All surveyors must have a written procedure and make it available to you if you
            ask
        �   Follow the guidance given in the document, which includes making a formal complaint
        �   Companies that provide Home Condition Surveys must handle your complaint in accordance
            with their procedure

    You may ask The SAVA Certification Scheme to investigate the complaint if:­

        �   Your complaint involves an allegation of criminal activity
        �   The company fails to handle your complaint in line with its procedure
        �   You are not happy with how the surveyor has handled your complaint

                                                  SAVA
                                        The National Energy Centre
                                               Davy Avenue
                                                 Knowlhill
                                         Milton Keynes MK5 8NA
                                             www.sava.org.uk
Photographs




              Moss growth on roof and salt deposits on chimney




                           Debris in valley gutter
Unclear boundary at front




Soft mortar to front of side wall
Oil storage tank with exposed pipe




Salt deposits on chimney in roof space
Rot at base of garage door frame




Inspection chamber at roadside
Public drain on property

Más contenido relacionado

La actualidad más candente

ECA Workshop - Brief
ECA Workshop - BriefECA Workshop - Brief
ECA Workshop - BriefKai Yun Pang
 
Payments in the construction industry
Payments in the construction industryPayments in the construction industry
Payments in the construction industryKheng Hoe Advocates
 
Professional practice 1 report
Professional practice 1 reportProfessional practice 1 report
Professional practice 1 reportNgo Jia Haur
 
10) int floor-finishes-1-query-list
10) int floor-finishes-1-query-list10) int floor-finishes-1-query-list
10) int floor-finishes-1-query-listJeanne Hoo
 
Scale of fees (rev. 2004)
Scale of fees (rev. 2004)Scale of fees (rev. 2004)
Scale of fees (rev. 2004)helmie84
 
Sustainability in built environment: Green Building Index (GBI) Platinum Cert...
Sustainability in built environment: Green Building Index (GBI) Platinum Cert...Sustainability in built environment: Green Building Index (GBI) Platinum Cert...
Sustainability in built environment: Green Building Index (GBI) Platinum Cert...ESD UNU-IAS
 
Final Bills of Quantity
Final Bills of QuantityFinal Bills of Quantity
Final Bills of QuantityArissa Loh
 
Eca presentation
Eca presentationEca presentation
Eca presentationKailyn Lee
 
PP2 Assignment: Group
PP2 Assignment: GroupPP2 Assignment: Group
PP2 Assignment: GroupFarah Sham
 
Standard bill of quantities
Standard bill of quantitiesStandard bill of quantities
Standard bill of quantitiesBt Lee
 
Unit 1 tender 1.1
Unit 1 tender 1.1Unit 1 tender 1.1
Unit 1 tender 1.1Mara
 
Professional practice 2
Professional practice 2Professional practice 2
Professional practice 2Shze Hwa Lee
 
ECA Workshop - ECA Form
ECA Workshop - ECA FormECA Workshop - ECA Form
ECA Workshop - ECA FormKai Yun Pang
 
Building maintenance management in malaysia
Building maintenance management in malaysiaBuilding maintenance management in malaysia
Building maintenance management in malaysiaNur Zakaria
 
Buildingservices2 bld60503
Buildingservices2 bld60503Buildingservices2 bld60503
Buildingservices2 bld60503Kailyn Lee
 
Elemental cost analysis Presentation Slides
Elemental cost analysis Presentation SlidesElemental cost analysis Presentation Slides
Elemental cost analysis Presentation SlidesArissa Loh
 
Tatacara Kaedah Tender
Tatacara Kaedah TenderTatacara Kaedah Tender
Tatacara Kaedah TenderIszwan Shah
 
2) int walls element query sheet
2) int walls element   query sheet2) int walls element   query sheet
2) int walls element query sheetJeanne Hoo
 

La actualidad más candente (20)

ECA Workshop - Brief
ECA Workshop - BriefECA Workshop - Brief
ECA Workshop - Brief
 
Payments in the construction industry
Payments in the construction industryPayments in the construction industry
Payments in the construction industry
 
Professional practice 1 report
Professional practice 1 reportProfessional practice 1 report
Professional practice 1 report
 
10) int floor-finishes-1-query-list
10) int floor-finishes-1-query-list10) int floor-finishes-1-query-list
10) int floor-finishes-1-query-list
 
Scale of fees (rev. 2004)
Scale of fees (rev. 2004)Scale of fees (rev. 2004)
Scale of fees (rev. 2004)
 
Sustainability in built environment: Green Building Index (GBI) Platinum Cert...
Sustainability in built environment: Green Building Index (GBI) Platinum Cert...Sustainability in built environment: Green Building Index (GBI) Platinum Cert...
Sustainability in built environment: Green Building Index (GBI) Platinum Cert...
 
Final Bills of Quantity
Final Bills of QuantityFinal Bills of Quantity
Final Bills of Quantity
 
Eca presentation
Eca presentationEca presentation
Eca presentation
 
PP2 Assignment: Group
PP2 Assignment: GroupPP2 Assignment: Group
PP2 Assignment: Group
 
Standard bill of quantities
Standard bill of quantitiesStandard bill of quantities
Standard bill of quantities
 
BS Role
BS RoleBS Role
BS Role
 
Unit 1 tender 1.1
Unit 1 tender 1.1Unit 1 tender 1.1
Unit 1 tender 1.1
 
Professional practice 2
Professional practice 2Professional practice 2
Professional practice 2
 
ECA Workshop - ECA Form
ECA Workshop - ECA FormECA Workshop - ECA Form
ECA Workshop - ECA Form
 
Building maintenance management in malaysia
Building maintenance management in malaysiaBuilding maintenance management in malaysia
Building maintenance management in malaysia
 
Buildingservices2 bld60503
Buildingservices2 bld60503Buildingservices2 bld60503
Buildingservices2 bld60503
 
Elemental cost analysis Presentation Slides
Elemental cost analysis Presentation SlidesElemental cost analysis Presentation Slides
Elemental cost analysis Presentation Slides
 
land acquisition
land acquisitionland acquisition
land acquisition
 
Tatacara Kaedah Tender
Tatacara Kaedah TenderTatacara Kaedah Tender
Tatacara Kaedah Tender
 
2) int walls element query sheet
2) int walls element   query sheet2) int walls element   query sheet
2) int walls element query sheet
 

Similar a Home Condition Survey

RHS Survey Level Two Survey Valuation.pdf
RHS Survey Level Two Survey Valuation.pdfRHS Survey Level Two Survey Valuation.pdf
RHS Survey Level Two Survey Valuation.pdfGB Home Surveys
 
RHS Survey Level Three.pdf
RHS Survey Level Three.pdfRHS Survey Level Three.pdf
RHS Survey Level Three.pdfGB Home Surveys
 
RHS Survey Level Two Survey Only.pdf
RHS Survey Level Two Survey Only.pdfRHS Survey Level Two Survey Only.pdf
RHS Survey Level Two Survey Only.pdfGB Home Surveys
 
PrePurchaseSampleReport
PrePurchaseSampleReportPrePurchaseSampleReport
PrePurchaseSampleReportMike Linklater
 
Sample Report
Sample ReportSample Report
Sample Reportedreeve
 
Sample 2007 built_rural_area
Sample 2007 built_rural_areaSample 2007 built_rural_area
Sample 2007 built_rural_areaHomePro4214913
 
Sample wind apartment ins val rep
Sample wind apartment ins val repSample wind apartment ins val rep
Sample wind apartment ins val repIndependentgroup
 
Sample 1994with deferred_maintenance
Sample 1994with deferred_maintenanceSample 1994with deferred_maintenance
Sample 1994with deferred_maintenanceHomePro4214913
 
Sample one year_builder_warranty
Sample one year_builder_warrantySample one year_builder_warranty
Sample one year_builder_warrantyHomePro4214913
 
Sample new construction-completed_over_a_year_earlier
Sample new construction-completed_over_a_year_earlierSample new construction-completed_over_a_year_earlier
Sample new construction-completed_over_a_year_earlierHomePro4214913
 
Sample Home Inspection Report.
Sample Home Inspection Report.Sample Home Inspection Report.
Sample Home Inspection Report.chiefinspector
 
Sample commercial inspection
Sample commercial inspectionSample commercial inspection
Sample commercial inspectionHomePro4214913
 
Capital Needs Assessment Example
Capital Needs Assessment ExampleCapital Needs Assessment Example
Capital Needs Assessment ExampleAdam Hoeksema
 
Tri-Tech Multi-Family lead paint testing-What to expect-FAQ
Tri-Tech Multi-Family lead paint testing-What to expect-FAQTri-Tech Multi-Family lead paint testing-What to expect-FAQ
Tri-Tech Multi-Family lead paint testing-What to expect-FAQDIYSampleTesting.com
 
Basement finish package
Basement finish packageBasement finish package
Basement finish packageStan Perlinski
 
Visual Building Inspection Report - House Check NSW
Visual Building Inspection Report - House Check NSWVisual Building Inspection Report - House Check NSW
Visual Building Inspection Report - House Check NSWHouse Check NSW
 

Similar a Home Condition Survey (20)

RHS Survey Level Two Survey Valuation.pdf
RHS Survey Level Two Survey Valuation.pdfRHS Survey Level Two Survey Valuation.pdf
RHS Survey Level Two Survey Valuation.pdf
 
RHS Survey Level Three.pdf
RHS Survey Level Three.pdfRHS Survey Level Three.pdf
RHS Survey Level Three.pdf
 
Building Dilapidations International Sample Report with Gauge
Building Dilapidations International Sample Report with GaugeBuilding Dilapidations International Sample Report with Gauge
Building Dilapidations International Sample Report with Gauge
 
RHS Survey Level Two Survey Only.pdf
RHS Survey Level Two Survey Only.pdfRHS Survey Level Two Survey Only.pdf
RHS Survey Level Two Survey Only.pdf
 
PrePurchaseSampleReport
PrePurchaseSampleReportPrePurchaseSampleReport
PrePurchaseSampleReport
 
Sample Report
Sample ReportSample Report
Sample Report
 
Sample 2007 built_rural_area
Sample 2007 built_rural_areaSample 2007 built_rural_area
Sample 2007 built_rural_area
 
Standard House
Standard HouseStandard House
Standard House
 
Sample wind apartment ins val rep
Sample wind apartment ins val repSample wind apartment ins val rep
Sample wind apartment ins val rep
 
Sample 1994with deferred_maintenance
Sample 1994with deferred_maintenanceSample 1994with deferred_maintenance
Sample 1994with deferred_maintenance
 
Sample one year_builder_warranty
Sample one year_builder_warrantySample one year_builder_warranty
Sample one year_builder_warranty
 
Homeowners guide for Rental Units
Homeowners guide for Rental UnitsHomeowners guide for Rental Units
Homeowners guide for Rental Units
 
Sample new construction-completed_over_a_year_earlier
Sample new construction-completed_over_a_year_earlierSample new construction-completed_over_a_year_earlier
Sample new construction-completed_over_a_year_earlier
 
Sample Home Inspection Report.
Sample Home Inspection Report.Sample Home Inspection Report.
Sample Home Inspection Report.
 
Sample commercial inspection
Sample commercial inspectionSample commercial inspection
Sample commercial inspection
 
Capital Needs Assessment Example
Capital Needs Assessment ExampleCapital Needs Assessment Example
Capital Needs Assessment Example
 
Tri-Tech Multi-Family lead paint testing-What to expect-FAQ
Tri-Tech Multi-Family lead paint testing-What to expect-FAQTri-Tech Multi-Family lead paint testing-What to expect-FAQ
Tri-Tech Multi-Family lead paint testing-What to expect-FAQ
 
Basement finish package
Basement finish packageBasement finish package
Basement finish package
 
Visual Building Inspection Report - House Check NSW
Visual Building Inspection Report - House Check NSWVisual Building Inspection Report - House Check NSW
Visual Building Inspection Report - House Check NSW
 
Sample report residential 1[1]
Sample report residential 1[1]Sample report residential 1[1]
Sample report residential 1[1]
 

Home Condition Survey

  • 1. Home Condition Survey Property Address: Sample survey report Report Reference Number: xxxxxxx Date of Inspection: 16 January 2008 Page 1 of 27
  • 2. Contents Introduction and terms on which this report is prepared Introduction What this report tells you What this report does not tell you What is inspected Condition rating definition How the inspection is carried out Section A - General information Section B - Summary and general description Section C - Conveyancing and health and safety issues Section D - Outside condition Section E - Inside condition Section F - Services Section G - Grounds (including shared parts for flats) Information about SAVA and your surveyor Photographs
  • 3. Introduction and terms on which this report is prepared Introduction When you buy a home it is sensible to have an independent report on the condition of the property. This Home Condition Survey is produced by a surveyor who is a member of the SAVA Home Inspector Certification Scheme. The surveyor must provide an objective opinion about the condition of the property which you, as the buyer, will be able to rely on and use. To become a member of The SAVA Home Inspector Certification Scheme and be able to produce Home Condition Surveys, the surveyor has to: � Pass an assessment of skills, in line with National Occupational Standards; and obtain the Diploma in Home Inspection � Have insurance that provides cover if a surveyor is negligent The surveyor must follow the inspection standards and code of conduct set by SAVA. To ensure compliance all members are continuously monitored and before membership is granted a Criminal Records Bureau check is undertaken. SAVA can revoke membership if a surveyor fails to maintain the expected professional or ethical standards. The Home Condition Survey is in a standard format and is based on these terms, which set out what you should expect of both the surveyor and the Home Condition Survey. Neither you nor the surveyor can amend these terms for the survey to be covered by the SAVA Certification Scheme. The surveyor may provide you with other services, however, any other services the surveyor may provide are not covered by these terms nor by the SAVA Certification Scheme and so must be covered by a separate contract. All surveyors who are members of the SAVA Home Inspector Certification Scheme have a complaints procedure which can be escalated to SAVA. If you have any complaint about this report, you can complain by following the complaints procedure. This is explained in more detail towards the end of this document. What this report tells you This report tells you: � About the construction and condition of the home on the date it was inspected � Whether more enquiries or investigations are needed � The Reinstatement Cost for insurance purposes derived from data supplied by the Building Cost Information Service (BCIS) except where the property is very large or historic, or if it incorporates special features, or is of unusual construction not covered by the Building Cost Information Service; in which circumstance a specialist would be needed to assess the reinstatement cost The main aim of the report is to tell you about any defects that need urgent attention or are serious. It also tells you about things that need further investigations to prevent damage to the structure of the building. The report applies ‘condition ratings’ to the major parts of the main building (it does not give condition ratings to outbuildings). The property is broken down into separate elements and each element has been given a condition rating 1, 2 or 3 or NI – see more on definitions below. What this report does not tell you: This report does not tell you the value of your home or cover things that will be considered when a valuation is provided, such as the area the home is in or the availability of public transport or facilities. It does not tell you about any minor defects that would not normally affect your decision to buy. � The report does not give advice on the cost of any repair work or the types of repair which should be used � The report is not an asbestos inspection under the Control of Asbestos at Work Regulations 2002
  • 4. If you need advice on subjects that are not covered by the Home Condition Survey, you must arrange for it to be provided separately. What is inspected? The surveyor undertakes a visual inspection of the inside and outside of the main building and all permanent outbuildings, and the parts of the gas, electricity, water and drainage services that can be seen. Condition rating definition The surveyor gives each part of the structure of the main building a condition rating, to make the report easy to follow. The condition ratings are as follows. � Condition Rating 1 No repair is currently needed. Normal maintenance must be carried out � Condition Rating 2 Repairs or replacements are needed but the surveyor does not consider these to be serious or urgent � Condition Rating 3 These are defects which are either serious and/or require urgent repair or replacement or where the surveyor feels that further investigation is required (for instance where he/she has reason to believe repair work is needed but an invasive investigation is required to confirm this). A serious defect is one which could lead to rapid deterioration in the property or one which is likely to cost more than 2.5% of the reinstatement cost to put right. You may wish to obtain quotes for additional work where a condition rating 3 is given, prior to exchange of contract � NI Not inspected (see “How the Inspection is carried out” below) How the Inspection is carried out The inspection is visual and non invasive. This means that the surveyor does not take up carpets, floor coverings or floorboards, move heavy furniture or remove contents of cupboards. Also, the surveyor does not remove secure panels or undo electrical fittings. The surveyor will state at the start of sections D, E and F of the report if it was not possible to inspect any parts of the home that are normally reported on. If the surveyor is concerned about these parts, the report will tell you about any further investigations that are needed. The surveyor does not provide estimates on the cost of any work to correct defects or comment on how repairs should be carried out.
  • 5. Section A - General Information Full address and postcode of the property Surveyor's name Mr John Smith Report reference number Surveyor's SAVA SAVA00XXXX membership number Company/organisation Chichester & District Home Information Pack Servic name Company address 31 Whyke Lane, Chichester, PO19 7US and postcode Company contact Email info@chips.uk.com details Telephone 08703 834 805 Fax 07092 875 218 Date of inspection 16 January 2008
  • 6. Section B - Summary Type of property The property is a detached bungalow. Approximate year when property was The property was built around 1981. built If converted from another use, approximate year Not converted. when property was converted Approximate year when property was The rear extension was built in 1989. extended Weather conditions at It was dry at the time of the inspection. the time of inspection The state of the property when The property was occupied, in a habitable condition and fully furnished. . inspected Is the property in an area with special No. restrictions? Property listing Not listed. Summary of Accomodation Living Bed Bath or Separate Utility Conser- Other Name(s) of other Storey Kitchen rooms rooms shower toilet room(s) vatory room(s) room(s) Lower ground Ground 2 3 2 1 1 Study First Second Third Fourth Roof space TOTALS 2 3 2 0 1 0 0 1 - Gross external floor area in square 158m² metres
  • 7. Reinstatement Note: This reinstatement cost is the estimated cost of completely rebuilding the £ 223000 Cost property based on information from BCIS, a service which provides building cost information and which is approved by the Association of British Insurers. It represents the sum at which the home should be insured against fire and other risks. It is based on building and other related costs and does not include the value of the land the home is built on. It does not include leisure facilities such as swimming pools and tennis courts. The figure should be reviewed regularly as building costs change. Importantly, it is not a valuation of the property. If the property is very large or historic, or if it incorporates special features or is of unusual construction, then BCIS data cannot cover it and a specialist would be needed to assess the reinstatement cost. In such circumstances no cost figure is provided and the report will indicate that a specialist is needed. General Description A short general XXXX is a detached bungalow originally constructed in 1980/1. The walls are description of the of brick-block cavity construction and there is evidence that the cavity has construction (main been retro filled with insulation material. The roof is of trussed timber walls, roof, floors, construction and is covered with concrete interlocking tiles. The windows are windows) all uPVC framed double glazed units which were fitted (according to the sellers information supplied) in 1999. At the rear of the property is a single storey cavity walled extension constructed in 1989 (again, according to information supplied). Detached from the property is a brick built double garage with felt flat roof. Summary of mains Drainage A mains drainage system is present. services Gas No mains gas connected. Electricity Mains electricity connected. Water Mains water supply connected. Central heating The central heating is provided by an oil fired boiler feeding hot water radiators in most rooms. The boiler is a Myson Velaire 50/70 believed to have been fitted when the property was originally built (information supplied by the sellers). The heating and hot water are controlled by a thermostat integral with the boiler and a wall mounted programmer. Outside facilities There is a double on site garage. There are 6 parking spaces located onsite. There are no permanent outbuildings. All roads and footpaths are made-up unless otherwise stated.
  • 8. A Summary of the Condition Ratings Section of the Report Part Name Identifier (if more than one) Rating No D: Outside D1 Chimney stacks 1 D2 Roof coverings 1 D3 Rainwater pipes & gutters 1 D4 Main walls (including claddings) 1 D5 Windows 1 D6 Outside doors (incl. patio doors) 1 D7 All other woodwork 1 D8 Outside decoration X D9 Other outside detail X E: Inside E1 Roof structure 1 E2 Ceilings 1 E3 Inside walls, partitions & plasterwork 1 E4 Floors 1 E5 Fireplaces & chimney breasts 3 E6 Built-in fittings 1 E7 Inside woodwork 1 E8 Bathroom fittings 1 E9 Other issues X F: Services F1 Electricity 1 F2 Gas / Oil 1 F3 Water 1 F4 Heating 1 F5 Drainage 1
  • 9. Summary of Structural Movement There is no evidence of structural movement. Summary of Dampness High moisture meter readings were recorded in the roofspace on the chimney breast serving the central heating boiler. This is the westerly chimney, to the right of the property when viewed from the front. Further Investigations Your attention is drawn to the following matters for which further investigation is recommended by someone who is appropriately qualified. Recommended investigation of defects seen or dampness suspected.
  • 10. Section C - Issues for Conveyancers and Health and Safety Issues Issues for Conveyancers The surveyor does not act as 'the conveyancer'. If during the inspection, however, the surveyor identifies issues that your conveyancer may need to investigate further, the surveyor will refer to these in the report and you should give your conveyancer a copy of this report. The surveyor will not have seen the legal and other documents. Roads and footpaths Drainage Water Drains Planning and other permissions needed Freehold owner consents Flying freeholds Mining Rights of way The boundary to the right side of the property is Boundaries (including party walls) undefined. Easements Repairs to shared parts Previous structural repairs New building warranties Building insurance (ongoing claims) Tree preservation orders Property let There is a grille for the public drain located at the front of the property (adjacent to the road) within Drain to front the apparent boundaries of the property. You should investigate any matters that may relate to this.
  • 11. Contaminated Land and Flooding The surveyor assumes that the home is not built with, nor contains, hazardous materials and is not built on contaminated land. If any materials are found during the inspection which may contain hazardous materials, or if the surveyor finds any evidence to suggest that the land may be contaminated, this will be shown here along with recommendations for further investigations. The property is understood to be situated near an Contamination area of land that may be affected by contamination. Flooding Health and Safety Risks These will include defects that require repair or replacement as well as issues that have existed for a long time and cannot reasonably be changed, but may present a risk to occupiers or visitors. Escape windows Fire control Fire doors Safety glass Lead pipes Radon gas Gas Handrails Asbestos Unsafe fittings There is no evidence to confirm the recent testing and / or servicing of the boiler. Failure to test the services increases the safety risk. Recent testing There is no evidence to confirm the recent testing and / or servicing of the electrical installation. Failure to test the services increases the safety risk. Inappropriate living
  • 12. Handrail position Banister spacing Insect nests Smoke detector Roof space partition
  • 13. Section D - Outside Condition The surveyor carries out a visual, non invasive inspection of the outside of the main building and permanent outbuildings from various points within the boundaries of the property and from public areas such as footpaths and open spaces, but does not enter neighbouring private property. High level features are inspected either from a point within the property using binoculars or using a ladder, where it is safe to do so. Due to the risk of causing damage, the surveyor does not walk on any flat roofs. When inspecting blocks of flats it is often difficult to see the whole outside of a building or block and its maintenance is rarely the responsibility of one person. The surveyor only carries out a non invasive inspection to the level of detail set out above to the main walls, windows and roof over the flat. The surveyor does not inspect the rest of the block to this level of detail but instead has formed an opinion based on a general inspection of the rest of the block. Information is given about the outside and shared parts so that the conveyancer can check whether the maintenance clauses in the lease or other title documents are adequate. The surveyor inspects the shared access to the flat together with the area where car parking and any garage for the flat are, along with access to that area, but does not inspect other shared parts (such as separate hall, stairs and access ways to other flats in the block, the lift motor room and cleaning cupboards.) Description and Justification for Rating and any comments Condition Rating D1. There are two chimney stacks. Both are brick built. Chimney stacks Normal maintenance must be undertaken. The chimney stack to the right (west) side shows some signs of salt deposits on the brick surfaces. This is associated with damp 1 recorded within the roofspace. See section E5. The sellers advise that the "main chimney" (assumed to mean the left side, or east, chimney) was rebuilt above roof level after being blown down during storms in 1987. D2. The main roof is pitched and covered with concrete interlocking Roof tiles. The extension roof is pitched and covered with concrete coverings interlocking tiles. Normal maintenance must be undertaken. All the roof pitches appear to be in good condition with no evidence of slipped or broken tiles. 1 There is some moss growth on most roof pitches which should be cleared periodically to prevent undue weight build-up on the roof surface. The valley gutter between the roof pitches at the front of the property (above the main entrance area) is partially blocked with debris and moss. This should be cleared out.
  • 14. D3. The rainwater fittings are PVC. Rainwater pipes & No repair is presently required. Normal maintenance must be gutters undertaken. 1 As it was dry at the time of inspection it was not possible to check the operation of the gutters and downpipes. However surface moss growth on the gutters suggests that they may overflow at times. This is probably due to debris and moss and therefore may require cleaning out. D4. The outside walls are brick faced and of cavity construction. There Main walls is evidence of retro fitted cavity wall insulation. (including claddings) No repair is presently required. Normal maintenance must be undertaken. Minor cracking in the mortar-brick joints was seen in some areas, 1 notably to the right side of the front wall. These cracks are probably due to thermal movement of the brickwork and are a minor defect. Some areas of soft and flaking mortar were found, notably on the left side wall towards the front of the property. This is probably due to the mortar mix used in the original construction. For both these defects some repointing is required. D5. The windows are PVCu and are double glazed. Windows No repair is presently required. Normal maintenance must be 1 undertaken. The sellers advise that the windows were replaced in 1999. D6. The outside doors are PVCu with glazed panels. Outside doors (incl. No repair is presently required. Normal maintenance must be 1 patio doors) undertaken. D7. The other woodwork includes such items as woodwork at the roof All other edges and cladding to the front of the property. woodwork 1 No repair is presently required. All woodwork has been replaced by uPVC cladding. The sellers advise that this was fitted in 2003.
  • 15. Section E - Inside Condition The surveyor carries out a visual, non invasive inspection of all the parts of the home that can be seen without causing damage to the fabric of the property or any fixtures, fittings or furnishings present at the time of inspection. The surveyor checks for damp in vulnerable areas by using a moisture-measuring meter. The surveyor inspects the roof structure from inside the roof space where it is safe to access and move around the roof space, but will not move or lift insulation material, stored goods and other contents. A representative selection of windows and all doors will be opened unless the surveyor determines that to do so could compromise the security of the property or they are locked and no key is available at the time of inspection. Floor surfaces are inspected where readily and safely accessible, but fitted floor coverings and heavy furniture are not moved. The surveyor does not comment on sound insulation or noise. The surveyor inspects the inside of the flat in the same way as is described under ‘The outside of the property’ in section D. They inspect the roof space however, only where they can get safe access from within the flat itself and where there is no risk of trespass. The surveyor does not go into the roof space if access is only possible from the shared parts or from within another flat. Description and Justification for Rating and any comments Condition Rating E1. The extension roof is constructed using a prefabricated timber Roof frame. The main roof is constructed using a prefabricated timber structure frame. No repair is presently required. The structure of the roof prevented safe access to all areas of the 1 roof space but those areas of the timbers inspected were found to be free from dampness, cracking, rot or other defects. The roof is lined with approximately 100mm of wool type insulating material at joist level. Current recommendations are for 250mm of insulation in the roof space. E2. The ceilings are constructed from plasterboard and finished with Ceilings textured paint. No repair is presently required. Normal maintenance must be undertaken. 1 There is some cracking to ceilings in most rooms, and evidence of previous repairs in the living room. The cracking is mostly confined to areas that would correspond to joints in the sheets of plasterboard used at the time of construction and are not significant or indicative of more serious movement of the property.
  • 16. E3. The internal walls and partitions are partly of masonry and partly of Inside walls, timber construction. partitions & plasterwork No repair is presently required. 1 Timber stud walls have been used to create a small office from an area of the rear bedroom. You should ensure that any work associated with this construction met regulatory requirements at the time of construction. E4. The floors are of concrete construction. Floors No repair is presently required. 1 The floors are laid with fitted carpet, vinyl or laminate coverings and cannot therefore be directly inspected. However no undue unevenness or dampness was noted. E5. The chimney breasts are of masonry construction. Fireplaces & The easterly (to the left when viewed from the front of the property) chimney chimney serves an open fire in the living room. breasts The westerly chimney serves the boiler in the kitchen. This is considered serious and in need of urgent repair or replacement. Further advice should be obtained. Very high moisture meter readings were recorded on the westerley chimney breast at upper levels in the roof space. The mortar was 3 found to be soft and crumbly and salt deposits were noted on the brickwork. No parts of the chimney breast can be examined at ground level. The evidence suggests that exhaust gasses from the boiler are leeching into the brickwork of the chimney breast. This may be due to the absence or failure of the chimney liner, and requires urgent rectification. Examination of the easterly chimney breast suggests that a liner is present and that no such similar defect is present. E6. The kitchen fittings are modern. The fitted wardrobes are modern. Built-in 1 fittings No repair is presently required. Normal maintenance must be undertaken. E7. The internal woodwork includes such items as: doors, frames, and Inside skirting. woodwork 1 No repair is presently required. Normal maintenance must be undertaken.
  • 17. E8. The sanitary fittings in the main bathroom include such items as: Bathroom bath, basin, WC, and are of good quality. fittings The sanitary fittings in the en-suite bathroom include such items as: shower, basin, WC, and are of good quality. No repair is presently required. Normal maintenance must be 1 undertaken. The operation of all facilities was checked and found to be satisfactory. It was noted that there was a long delay before hot water was delivered from the taps, due to the long run of pipework from the hot water cylinder.
  • 18. Section F - Services The surveyor carries out a visual, non invasive inspection of the services, but specialist tests are not carried out. If any services (such as the boiler or mains water) are turned off, the surveyor will state that in the report and will not turn them on. The surveyor reports only on the services covered in this section (electricity, gas, oil, water, heating and drainage). All other services and domestic appliances are not included in the inspection: for example security and door answering systems, smoke alarms, television, cable, wireless and satellite communication systems, cookers, hobs, washing machines and fridges (even where built in). Description and Justification for Rating and any comments Condition Rating F1. There is an electrical supply and the meter and consumer unit [fuse Electricity box] are located in the high level cupboard in the kitchen. No repair is presently required. Normal maintenance must be 1 undertaken. The consumer unit is an older hard wired cartridge fuse type. There is no evidence of recent inspection of the electrical system. See section C6. F2. There is an oil store that is located on the side path to the right side Gas / Oil of the property. No repair is presently required. Normal maintenance must be 1 undertaken. The 1200 litre plastic oil storage tank feeds the oil fired boiler through a pipe running along the side of the property. This pipe could be vulnerable to damage and care should therefore be taken. F3. There is a mains water supply. The pipework is copper and the Water stop valve is in the kitchen. No repair is presently required. Normal maintenance must be undertaken. Hot water is supplied from a standard low pressure hot water system. The cold water cistern is located in the roof space and is 1 adequately insulated and supported. The hot water storage tank is located in a cupboard in the hallway. It has a single immersion heater element fitted and approximately 30mm of spray foam insulation. Examination of the pipework associated with the hot water system revealed no obvious defects other than some peeling of the hot water storage tank insulation. F4. The heating and hot water is provided by an oil boiler. Heating No repair is presently required. Normal maintenance must be undertaken. 1 The sellers indicate that the boiler was fitted at the time of original construction of the property and is therefore in excess of 20 years old. More modern heating systems would feature more efficient boilers, and wall/radiator thermostats.
  • 19. F5. There is a mains drainage system. Drainage No repair is presently required. Normal maintenance must be undertaken. There are five inspection chambers located within the boundaries 1 of the property. The covers for three of these were lifted and water run through the drains. Water was seen to run freely from the chambers at the right side of the property to the chamber closest to the road.
  • 20. Section G - Grounds (including shared parts for flats) The surveyor inspects the condition of the boundary walls, outbuildings and areas in common (shared) use from within the grounds and any public areas, but not from neighbouring private property. The report provides a summary of the general condition of any garden walls, fences and permanent outbuildings. Conservatories with translucent or clear roofs attached to the main building are treated as outbuildings, as are garages and permanent store sheds. Buildings containing swimming pools and sports facilities are also treated as outbuildings, but the surveyor does not report on the leisure facilities such as the pool itself and its equipment. Description and comments Garages There is a brick built double garage to the rear side of the main building. The garage has a flat bitumen felt roof. No leaks in the roof were apparent at the time of inspection. The garage is fitted with power and light, and a metal up and over type door which appears to operate normally. Some areas of rot were noted at the bottom of the door frames, but otherwise the garage appears to be in good condition. Conservatories There is no conservatory. Permanent There are no permanent outbuildings. outbuildings Boundary and The boundaries are defined by a mixture of timber fencing and trees/shrubs. The retaining walls fences appear to be in good condition. The front boundary to the right of the property comprises conifer trees but it is unclear exactly where the boundary lies. This should be clarified with your conveyancer. Paved areas There are paved areas and paths to the front and side consisting of tarmacadam that are uneven and moss covered. This makes them dangerous when wet and liable to ponding. Grounds The grounds to the front and rear are mainly lawned with associated flower borders. The grounds appear to be well tended. The proximity of any trees does not currently present any threat to the buildings. Common (shared) areas
  • 21. Information about SAVA and your surveyor All Home Condition Surveys are produced by a surveyor who is a member of SAVA Home Inspector Certification Scheme. All reports are held on a register kept by SAVA. The insurance company which provides professional indemnity cover for the surveyor requires that we keep a register for the purposes of monitoring the competency of the surveyor and in order to undertake an investigation if you have a complaint about this report or the surveyor. Surveyor's SAVA00XXXX membership number Name Mr John Smith Qualifications DipHI Address 31 Whyke Lane, Chichester, PO19 7US Contact details Email @chips.uk.com Telephone 08703 834 805 Fax 07092 875 218 Date of making the 16 January 2008 report Signature What to do if you have a complaint If you have a complaint about this Home Condition Survey or the surveyor who carried it out you should follow the procedures set out below:­ � Ask the company who provided the report (the company named on the front of the report) or the surveyor who carried out the report to give you a copy of its complaints handling procedure. All surveyors must have a written procedure and make it available to you if you ask � Follow the guidance given in the document, which includes making a formal complaint � Companies that provide Home Condition Surveys must handle your complaint in accordance with their procedure You may ask The SAVA Certification Scheme to investigate the complaint if:­ � Your complaint involves an allegation of criminal activity � The company fails to handle your complaint in line with its procedure � You are not happy with how the surveyor has handled your complaint SAVA The National Energy Centre Davy Avenue Knowlhill Milton Keynes MK5 8NA www.sava.org.uk
  • 22. Photographs Moss growth on roof and salt deposits on chimney Debris in valley gutter
  • 23. Unclear boundary at front Soft mortar to front of side wall
  • 24. Oil storage tank with exposed pipe Salt deposits on chimney in roof space
  • 25. Rot at base of garage door frame Inspection chamber at roadside
  • 26. Public drain on property