Demonstration Thermography report




Company    Testo Ltd                        Tester:

           Cheriton House, Newman           Andy McGrath - Testo
           Lane,                            Phone:     01420 544433
           Alton, Hampshire, GU34 2QJ
                                            E-Mail:    info@testo.co.uk


Device     Testo 875-2                      Serial No.: 01799300


Customer   Power Flushing Contractor        Measuring Site:

           Newman Lane                      Power Flushing Customer
           Alton, Hampshire, GU34 2QJ       Testo Avenue,
                                            Alton
                                            Measuring Date: 12th July 2011


Task       Demonstration Thermography Report to highlight the capabilities of the
           Testo 875 series Thermal Imaging camera to a Heating / Power Flushing
           Contractor for the application of Power Flushing of Radiators.




                                Page 1/21
Demonstration Thermography report

File:           IV_00797.BMT                                                            Date:     12/07/2011
lens type:      Standard 32°            lens serial no.:       20223817                 Measuri 08:24:54
                                                                                        ng Time:




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects            Temp. [°C]     Emiss.       Refl. temp. [°C]   Remarks
Measure point 1                  54.1          0.95               20.0        -
Measure point 2                  55.7          0.95               20.0        -
Measure point 3                  29.1          0.95               20.0        -
Cold spot 1                      22.0          0.95               20.0        -



Profile line:




Remarks:
Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their
condition prior to conducting the process.
The images are of the Lounge radiator, prior to conducting the Power Flushing Process.
As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the
presence of quite a substantial amount of contamination /sludge in this area of the radiator.
Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance.
The Auto Cold Spot Indicator has been applied to the thermal image to automatically indicate the coldest
point CS1 in the defined area of the image.
Additional Spot Temperature markers have been added to the thermal image for temperature comparisons.
A Temperature profile line Graph has been applied to the thermal image to highlight the temperature
variation across the radiator.
The Thermal Image is displayed in " Iron " Palette.




                                                  Page 2/21
Demonstration Thermography report

File:         IV_00800.BMT                                                              Date:     12/07/2011
lens type:    Standard 32°              lens serial no.:      20223817                  Measuri 08:26:52
                                                                                        ng Time:




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects            Temp. [°C]     Emiss.       Refl. temp. [°C] Remarks
Measure point 1                   52.9          0.95              20.0         -
Measure point 2                   22.9          0.95              20.0         -
Measure point 3                   49.9          0.95              20.0         -
Hot spot 1                        58.9          0.95              20.0         -
Remarks:
Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their
condition prior to conducting the process.
The images are of the Lounge radiator, prior to conducting the Power Flushing Process.
As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the
presence of quite a substantial amount of contamination /sludge in this area of the radiator.
Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance.
The Auto Hot Spot Indicator has been applied to the thermal image to automatically indicate the hottest point
HS1 in the defined area of the image.
Additional Spot Temperature markers have been added to the thermal image for temperature comparisons.

The Thermal Image is displayed in " Iron " Palette.




                                                  Page 3/21
Demonstration Thermography report

File:           IV_00802.BMT                                                            Date:     12/07/2011
lens type:      Standard 32°            lens serial no.:       20223817                 Measuri 08:30:49
                                                                                        ng Time:




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects            Temp. [°C]     Emiss.       Refl. temp. [°C]   Remarks
Measure point 1                  57.1          0.95               20.0        -
Measure point 2                  58.3          0.95               20.0        -
Measure point 3                  31.0          0.95               20.0        -
Cold spot 1                      22.9          0.95               20.0        -



Profile line:




Remarks:
Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their
condition prior to conducting the process.
The images are of the Hall radiator, prior to conducting the Power Flushing Process.
As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the
presence of quite a substantial amount of contamination /sludge in this area of the radiator.
Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance.
The Auto Cold Spot Indicator has been applied to the thermal image to automatically indicate the coldest
point CS1 in the defined area of the image.
Additional Spot Temperature markers have been added to the thermal image for temperature comparisons.
A Temperature profile line Graph has been applied to the thermal image to highlight the temperature
variation across the radiator.
The Thermal Image is displayed in " Iron " Palette.




                                                  Page 4/21
Demonstration Thermography report

File:         IV_00824.BMT                                                             Date:     12/07/2011
lens type:    Standard 32°              lens serial no.:      20223817                 Measuri 08:54:34
                                                                                       ng Time:




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects            Temp. [°C]      Emiss.      Refl. temp. [°C] Remarks
Measure point 1                   52.3          0.95              20.0         -
Measure point 2                   28.5          0.95              20.0         -
Measure point 3                   50.1          0.95              20.0         -
Hot spot 1                        55.6          0.95              20.0         -
Remarks:
Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their
condition prior to conducting the process.
The images are of the Hall radiator, prior to conducting the Power Flushing Process.
As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the
presence of quite a substantial amount of contamination /sludge in this area of the radiator.
Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance.
The Auto Hot Spot Indicator has been applied to the thermal image to automatically indicate the Hottest point
HS1 in the defined area of the image.
Additional Spot Temperature markers have been added to the thermal image for temperature comparisons.

The Thermal Image is displayed in " Iron " Palette.




                                                  Page 5/21
Demonstration Thermography report

File:           IV_00808.BMT                                                            Date:     12/07/2011
lens type:      Standard 32°            lens serial no.:       20223817                 Measuri 08:35:40
                                                                                        ng Time:




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects            Temp. [°C]     Emiss.       Refl. temp. [°C]   Remarks
Measure point 1                  56.3          0.95               20.0        -
Measure point 2                  50.6          0.95               20.0        -
Measure point 3                  38.3          0.95               20.0        -
Cold spot 1                      26.5          0.95               20.0        -



Profile line:




Remarks:
Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their
condition prior to conducting the process.
The images are of the Front Bedroom No 1 radiator, prior to conducting the Power Flushing Process.
As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the
presence of quite a substantial amount of contamination /sludge in this area of the radiator.
Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance.
The Auto Cold Spot Indicator has been applied to the thermal image to automatically indicate the coldest
point CS1 in the defined area of the image.
Additional Spot Temperature markers have been added to the thermal image for temperature comparisons.
A Temperature profile line Graph has been applied to the thermal image to highlight the temperature
variation across the radiator.
The Thermal Image is displayed in " Iron " Palette.




                                                  Page 6/21
Demonstration Thermography report

File:         IV_00811.BMT                                                             Date:     12/07/2011
lens type:    Standard 32°              lens serial no.:      20223817                 Measuri 08:37:02
                                                                                       ng Time:




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects            Temp. [°C]     Emiss.       Refl. temp. [°C] Remarks
Measure point 1                   52.4          0.95              20.0         -
Measure point 2                   34.7          0.95              20.0         -
Measure point 3                   47.4          0.95              20.0         -
Hot spot 1                        57.7          0.95              20.0         -
Remarks:
Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their
condition prior to conducting the process.
The images are of the Front Bedroom No 1 radiator, prior to conducting the Power Flushing Process.
As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the
presence of quite a substantial amount of contamination /sludge in this area of the radiator.
Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance.
The Auto Hot Spot Indicator has been applied to the thermal image to automatically indicate the Hottest point
HS1 in the defined area of the image.
Additional Spot Temperature markers have been added to the thermal image for temperature comparisons.

The Thermal Image is displayed in " Iron " Palette.




                                                  Page 7/21
Demonstration Thermography report

File:         IV_00812.BMT                                                              Date:     12/07/2011
lens type:    Standard 32°              lens serial no.:      20223817                  Measuri 08:40:36
                                                                                        ng Time:




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects            Temp. [°C]     Emiss.       Refl. temp. [°C] Remarks
Measure point 1                   48.4          0.95              20.0         -
Measure point 2                   36.6          0.95              20.0         -
Measure point 3                   57.9          0.95              20.0         -
Cold spot 1                       29.4          0.95              20.0         -
Remarks:
Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their
condition prior to conducting the process.
The images are of the Front Bedroom No 2, prior to conducting the Power Flushing Process.
As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the
presence of quite a substantial amount of contamination /sludge in this area of the radiator.
Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance.
The Auto Cold Spot Indicator has been applied to the thermal image to automatically indicate the coldest
point CS1 in the defined area of the image.
Additional Spot Temperature markers have been added to the thermal image for temperature comparisons.

The Thermal Image is displayed in " Iron " Palette.




                                                  Page 8/21
Demonstration Thermography report

File:           IV_00813.BMT                                                            Date:    12/07/2011
lens type:      Standard 32°            lens serial no.:       20223817                 Measuri 08:41:02
                                                                                        ng Time:




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects            Temp. [°C]     Emiss.       Refl. temp. [°C]   Remarks
Measure point 1                  59.2          0.95               20.0        -
Measure point 2                  56.1          0.95               20.0        -
Hot spot 1                       60.0          0.95               20.0        -



Profile line:




Remarks:
Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their
condition prior to conducting the process.
The images are of the Front Bedroom No 2 radiator, prior to conducting the Power Flushing Process.
As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the
presence of quite a substantial amount of contamination /sludge in this area of the radiator.
Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance.
The Auto Hot Spot Indicator has been applied to the thermal image to automatically indicate the Hottest point
HS1 in the defined area of the image.
Additional Spot Temperature markers have been added to the thermal image for temperature comparisons.
A Temperature profile line Graph has been applied to the thermal image to highlight the temperature
variation across the radiator.
The Thermal Image is displayed in " Iron " Palette.




                                                  Page 9/21
Demonstration Thermography report

File:        IV_00836.BMT                                              Date:   12/07/2011
lens type:   Standard 32°            lens serial no.:       20223817   Measuri 09:18:02
                                                                       ng Time:




Picture parameters:
Emissivity:                   0.95
Refl. temp. [°C]:             20.0


Remarks:
The images are of the Power Flushing equipment.




                                               Page 10/21
Demonstration Thermography report

File:        IV_00839.BMT                                                           Date:     12/07/2011
lens type:   Standard 32°             lens serial no.:       20223817               Measuri 09:31:04
                                                                                    ng Time:




Picture parameters:
Emissivity:                    0.95
Refl. temp. [°C]:              20.0


Remarks:
The images are of the Lounge Radiator, during the Power Flushing process, showing the gradual removal of
the contaminant/sludge.




                                                Page 11/21
Demonstration Thermography report

File:        IV_00840.BMT                                                           Date:     12/07/2011
lens type:   Standard 32°             lens serial no.:       20223817               Measuri 09:33:31
                                                                                    ng Time:




Picture parameters:
Emissivity:                    0.95
Refl. temp. [°C]:              20.0


Remarks:
The images are of the Lounge Radiator, during the Power Flushing process, showing the gradual removal of
the contaminant/sludge.




                                                Page 12/21
Demonstration Thermography report

File:        IV_00845.BMT                                                           Date:     12/07/2011
lens type:   Standard 32°             lens serial no.:       20223817               Measuri 09:46:33
                                                                                    ng Time:




Picture parameters:
Emissivity:                    0.95
Refl. temp. [°C]:              20.0


Remarks:
The images are of the Lounge Radiator, during the Power Flushing process, showing the gradual removal of
the contaminant/sludge.




                                                Page 13/21
Demonstration Thermography report

File:         IV_00842.BMT                                                             Date:     12/07/2011
lens type:    Standard 32°             lens serial no.:       20223817                 Measuri 09:39:14
                                                                                       ng Time:




Picture parameters:
Emissivity:                     0.95
Refl. temp. [°C]:               20.0


Remarks:
Images of the Magnets from the Power Flushing unit, highlighting the significant amount of contaminant /
sludge removed from one radiator.




                                                 Page 14/21
Demonstration Thermography report

File:         IV_00843.BMT                                                             Date:     12/07/2011
lens type:    Standard 32°             lens serial no.:       20223817                 Measuri 09:40:53
                                                                                       ng Time:




Picture parameters:
Emissivity:                     0.95
Refl. temp. [°C]:               20.0


Remarks:
Images of the Magnets from the Power Flushing unit, highlighting the significant amount of contaminant /
sludge removed from one radiator.




                                                 Page 15/21
Demonstration Thermography report

File:           IV_00878.BMT                                                            Date:   12/07/2011
lens type:      Standard 32°            lens serial no.:       20223817                 Measuri 14:36:24
                                                                                        ng Time:




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects            Temp. [°C]     Emiss.       Refl. temp. [°C]   Remarks
Measure point 1                  55.5          0.95               20.0        -
Measure point 2                  52.2          0.95               20.0        -
Measure point 3                  54.3          0.95               20.0        -



Profile line:




Remarks:
Thermal Images of the radiators after the Power Flushing process were captured as a record of their
condition following the process.
The boiler has now been switched on again and the heating system is now operational and been running for
a short period of time.
The images are of the Lounge radiator, as can be seen, in comparison to image 0797, the significant cold
area in the middle of the radiator,is now removed and the radiator now shows a consistant overall
temperature.
Thus verifying that the process of Power Flushing the radiator has considerably improved the radiator
efficiency / performance.
Spot Temperature markers have been added to the thermal image for temperature comparisons.
A Temperature profile line Graph has been applied to the thermal image to highlight the temperature
variation across the radiator and shows consistancy across the radiator.
The Thermal Image is displayed in " Iron " Palette.




                                                  Page 16/21
Demonstration Thermography report

File:           IV_00882.BMT                                                            Date:     12/07/2011
lens type:      Standard 32°            lens serial no.:       20223817                 Measuri 14:38:41
                                                                                        ng Time:




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects            Temp. [°C]     Emiss.       Refl. temp. [°C]   Remarks
Measure point 1                  57.6          0.95               20.0        -
Measure point 2                  55.7          0.95               20.0        -
Measure point 3                  53.6          0.95               20.0        -



Profile line:




Remarks:
Thermal Images of the radiators after the Power Flushing process were captured as a record of their
condition following the process.
The boiler has now been switched on again and the heating system is now operational and been running for
a short period of time.
The images are of the Hall radiator, as can be seen, in comparison to image 0802, the significant cold area in
the middle of the radiator,is now removed and the radiator now shows a consistant overall temperature.
Thus verifying that the process of Power Flushing the radiator has considerably improved the radiator
efficiency / performance.
Spot Temperature markers have been added to the thermal image for temperature comparisons.
A Temperature profile line Graph has been applied to the thermal image to highlight the temperature
variation across the radiator and shows consistancy across the radiator.
The Thermal Image is displayed in " Iron " Palette.




                                                  Page 17/21
Demonstration Thermography report

File:           IV_00872.BMT                                                            Date:   12/07/2011
lens type:      Standard 32°            lens serial no.:       20223817                 Measuri 14:32:33
                                                                                        ng Time:




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects            Temp. [°C]     Emiss.       Refl. temp. [°C]   Remarks
Measure point 1                  58.8          0.95               20.0        -
Measure point 2                  54.7          0.95               20.0        -
Measure point 3                  52.6          0.95               20.0        -



Profile line:




Remarks:
Thermal Images of the radiators after the Power Flushing process, were captured as a record of their
condition following the process.
The boiler has now been switched on again and the heating system is now operational and been running for
a short period of time.
The images are of the radiator in the Front Bedroom No 1, as can be seen, in comparison to image 0808, the
significant cold area in the middle of the radiator,is now removed and the radiator now shows a consistant
overall temperature.
Thus verifying that the process of Power Flushing the radiator has considerably improved the radiator
efficiency / performance.
Spot Temperature markers have been added to the thermal image for temperature comparisons.
A Temperature profile line Graph has been applied to the thermal image to highlight the temperature
variation across the radiator and shows consistancy across the radiator.
The Thermal Image is displayed in " Iron " Palette.




                                                  Page 18/21
Demonstration Thermography report

File:           IV_00869.BMT                                                            Date:   12/07/2011
lens type:      Standard 32°            lens serial no.:       20223817                 Measuri 14:30:48
                                                                                        ng Time:




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects            Temp. [°C]     Emiss.       Refl. temp. [°C]   Remarks
Measure point 1                  57.0          0.95               20.0        -
Measure point 2                  55.5          0.95               20.0        -
Measure point 3                  54.0          0.95               20.0        -



Profile line:




Remarks:
Thermal Images of the radiators after the Power Flushing process were captured as a record of their
condition following the process.

The boiler has now been switched on again and the heating system is now operational and been running for
a short period of time.

The images are of the radiator in the Front Bedroom No 2, as can be seen, in comparison to image 0812, the
significant cold area in the middle of the radiator,is now removed and the radiator now shows a consistant
overall temperature.
Thus verifying that the process of Power Flushing the radiator has considerably improved the radiator
efficiency / performance.

Spot Temperature markers have been added to the thermal image for temperature comparisons.

A Temperature profile line Graph has been applied to the thermal image to highlight the temperature
variation across the radiator and shows consistancy across the radiator.
The Thermal Image is displayed in " Iron " Palette.
                                                  Page 19/21
The images are of the radiator in the Front Bedroom No 2, as can be seen, in comparison to image 0812, the
significant cold area in the middle of the radiator,is now removed and the radiator now shows a consistant
overall temperature.
Thus verifying that the process of Power Flushing the radiator has considerably improved the radiator
efficiency / performance.

Spot Temperature markers have been added to the thermal image for temperature comparisons.
Demonstration Thermography report
A Temperature profile line Graph has been applied to the thermal image to highlight the temperature
variation across the radiator and shows consistancy across the radiator.
The Thermal Image is displayed in " Iron " Palette.

Review:
Demonstration Thermography Report to highlight the capabilities of the Testo 875 series Thermal Imaging
camera and the Testo IR software.

This is an example report for Demonstration purposes only. The report format is using the "Standard" report
template from the selection of Report Templates available in the Testo IR software.

A demonstration of the Testo 875-2 Thermal Imaging camera was conducted for a Heating / Power Fluching
Contractor, during the course of Power Flushing being conducted at Dwelling.
The objective was to demonstrate how a Testo 875-2 Thermal Imaging camera could be used to record
Thermal and Digital images during the course of the Power Flushing process, to show the conditions of the
radiators prior to and after the process and to verify the the improvements made, using Power Flushing
.
The Boiler was switched on just prior to arrival and images were subsequently captured of the radiators, to
record their condition / performance.
With reference to the images at this stage, a number of the radiators had significant cold areas, indicating
substantial contaminant / sludge and the need for Power Flushing.
Images of the Lounge, Hall, Bedroom 1 and Bedroom 2 Radiators, (which were the radiators in the worst
condition), were recorded for the purpose of comparison, following the process.

Images were also recorded during the Power Flushing process and specifically the images 0839, 0840 & 0845
show the Lounge radiator changing / improving condition during the process.

Following completion of the Power Flushing process on all the radiators, the boiler was switched on and the
heating system was operational and images of the Lounge, Hall, Bedroom 1 and Bedroom 2 radiators were
recorded for comparison purposes and to highlight the significant improvements in Condition / Performance.


As can be seen, the thermal images clearly show the conditions of the radiators before, during and after the
Power Flushing process and verify the improvements that this process produces.

The purpose of the report is to demonstrate the capabilities of the Testo 875-2, a 160 x 120 pixel configuration
Thermal Imaging camera in respect of the image quality / resolution that is recorded/produced with this level of
Thermal Imaging camera and to demonstrate how it can be used to verify the Power Flushing process.

Please note that any temperatures indicated on the images are "Apparent Temperatures" and may not be
truely representative. An overall emissivity value has been used in the images for these demonstration
purposes. For accurate temperature measurement, the relevant emissivity value to the specific material to be
measured, would have to be established.

It should be noted that Testo do not provide a Thermography Consultancy Service, the images are purely for
Equipment Demonstration purposes to highlight the capabilities of the Testo range of Thermal Imaging
cameras and the Testo IR software.
It is not the purpose of the images/report to specifically identify/highlight any faults or Thermal Anomalies, or to
provide comment/observation relating to any anomalies.

Some of the features of the camera and software have also been applied to the Thermal images.

Spot Temperature markers have been added to the thermal images to indicate temperatures.

Auto Hot / Cold Spot Indicator has been applied, which automatically highlights the Hottest or Coldest point
in the defined area.

Temperature Profile Line Graph shows the temperature variation in graph form across the subject.

Palettes a variety of palettes have been used for the thermal images. Eight palettes are available on the
camera and in the software.

                                                    Page 20/21
Demonstration Thermography report


The images are automatically Time and Date Stamped to verify the time and date when the images were
taken.

The report also details the Emissivity value relating to the image taken.




                                                           12/07/2011 ,

                                                                            Andy McGrath - Testo




                                                   Page 21/21

More Related Content

Similar to Demonstration thermography report 2 radiator power flushing

Demonstration thermography report testo 882 dwelling images
Demonstration thermography report testo 882 dwelling imagesDemonstration thermography report testo 882 dwelling images
Demonstration thermography report testo 882 dwelling imagesTesto Limited
 
Testo thermal imaging power flushing application story
Testo thermal imaging power flushing application storyTesto thermal imaging power flushing application story
Testo thermal imaging power flushing application storyTesto Limited
 
Demonstration thermography report for super resolution 1
Demonstration thermography report for super resolution 1 Demonstration thermography report for super resolution 1
Demonstration thermography report for super resolution 1 Testo Limited
 
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...Testo Limited
 
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...Testo Limited
 
Besi - TSV Summit 2015 - Handout
Besi - TSV Summit 2015 - HandoutBesi - TSV Summit 2015 - Handout
Besi - TSV Summit 2015 - HandoutHugo Pristauz
 
Heat simulator design Problem 1
Heat simulator design Problem 1Heat simulator design Problem 1
Heat simulator design Problem 1James Li
 
IRJET- Study of Mechanism of Quenching & Calculate the Cooling Rate of Quench...
IRJET- Study of Mechanism of Quenching & Calculate the Cooling Rate of Quench...IRJET- Study of Mechanism of Quenching & Calculate the Cooling Rate of Quench...
IRJET- Study of Mechanism of Quenching & Calculate the Cooling Rate of Quench...IRJET Journal
 
Case Study: Energy Audit For Cooling Tower
Case Study: Energy Audit For Cooling Tower Case Study: Energy Audit For Cooling Tower
Case Study: Energy Audit For Cooling Tower Hina Gupta
 
Ams2750 e presentation
Ams2750 e presentationAms2750 e presentation
Ams2750 e presentationPeter Sherwin
 
L20-Heat and Power Integration(1fgffffffffffffffffff).pptx
L20-Heat and Power Integration(1fgffffffffffffffffff).pptxL20-Heat and Power Integration(1fgffffffffffffffffff).pptx
L20-Heat and Power Integration(1fgffffffffffffffffff).pptxktmbych2016
 
L20-Heat and Pdfffffffffffffffower Integration(1).pptx
L20-Heat and Pdfffffffffffffffower Integration(1).pptxL20-Heat and Pdfffffffffffffffower Integration(1).pptx
L20-Heat and Pdfffffffffffffffower Integration(1).pptxktmbych2016
 
L20 heat and power integration
L20 heat and power integrationL20 heat and power integration
L20 heat and power integration2k17che26
 
temperature measurement
temperature measurementtemperature measurement
temperature measurementDimaJawhar
 
Last Rev. August 2014 Calibration and Temperature Measurement.docx
Last Rev. August 2014 Calibration and Temperature Measurement.docxLast Rev. August 2014 Calibration and Temperature Measurement.docx
Last Rev. August 2014 Calibration and Temperature Measurement.docxsmile790243
 
Monisha Alam_1412059
Monisha Alam_1412059Monisha Alam_1412059
Monisha Alam_1412059Monisha Alam
 
Case study Energy Audit for Chiller Plant
Case study Energy Audit for Chiller PlantCase study Energy Audit for Chiller Plant
Case study Energy Audit for Chiller PlantHina Gupta
 
Contact temperature sensor calibration
Contact temperature sensor calibrationContact temperature sensor calibration
Contact temperature sensor calibrationTempsens Instruments
 
Ea of cw, ct & cond. system
Ea of cw, ct & cond. systemEa of cw, ct & cond. system
Ea of cw, ct & cond. systemD.Pawan Kumar
 

Similar to Demonstration thermography report 2 radiator power flushing (20)

Demonstration thermography report testo 882 dwelling images
Demonstration thermography report testo 882 dwelling imagesDemonstration thermography report testo 882 dwelling images
Demonstration thermography report testo 882 dwelling images
 
Testo thermal imaging power flushing application story
Testo thermal imaging power flushing application storyTesto thermal imaging power flushing application story
Testo thermal imaging power flushing application story
 
Demonstration thermography report for super resolution 1
Demonstration thermography report for super resolution 1 Demonstration thermography report for super resolution 1
Demonstration thermography report for super resolution 1
 
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
 
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
 
Besi - TSV Summit 2015 - Handout
Besi - TSV Summit 2015 - HandoutBesi - TSV Summit 2015 - Handout
Besi - TSV Summit 2015 - Handout
 
Heat simulator design Problem 1
Heat simulator design Problem 1Heat simulator design Problem 1
Heat simulator design Problem 1
 
IRJET- Study of Mechanism of Quenching & Calculate the Cooling Rate of Quench...
IRJET- Study of Mechanism of Quenching & Calculate the Cooling Rate of Quench...IRJET- Study of Mechanism of Quenching & Calculate the Cooling Rate of Quench...
IRJET- Study of Mechanism of Quenching & Calculate the Cooling Rate of Quench...
 
Case Study: Energy Audit For Cooling Tower
Case Study: Energy Audit For Cooling Tower Case Study: Energy Audit For Cooling Tower
Case Study: Energy Audit For Cooling Tower
 
Ams2750 e presentation
Ams2750 e presentationAms2750 e presentation
Ams2750 e presentation
 
L20-Heat and Power Integration(1fgffffffffffffffffff).pptx
L20-Heat and Power Integration(1fgffffffffffffffffff).pptxL20-Heat and Power Integration(1fgffffffffffffffffff).pptx
L20-Heat and Power Integration(1fgffffffffffffffffff).pptx
 
L20-Heat and Pdfffffffffffffffower Integration(1).pptx
L20-Heat and Pdfffffffffffffffower Integration(1).pptxL20-Heat and Pdfffffffffffffffower Integration(1).pptx
L20-Heat and Pdfffffffffffffffower Integration(1).pptx
 
L20 heat and power integration
L20 heat and power integrationL20 heat and power integration
L20 heat and power integration
 
LAB 01.pdf
LAB 01.pdfLAB 01.pdf
LAB 01.pdf
 
temperature measurement
temperature measurementtemperature measurement
temperature measurement
 
Last Rev. August 2014 Calibration and Temperature Measurement.docx
Last Rev. August 2014 Calibration and Temperature Measurement.docxLast Rev. August 2014 Calibration and Temperature Measurement.docx
Last Rev. August 2014 Calibration and Temperature Measurement.docx
 
Monisha Alam_1412059
Monisha Alam_1412059Monisha Alam_1412059
Monisha Alam_1412059
 
Case study Energy Audit for Chiller Plant
Case study Energy Audit for Chiller PlantCase study Energy Audit for Chiller Plant
Case study Energy Audit for Chiller Plant
 
Contact temperature sensor calibration
Contact temperature sensor calibrationContact temperature sensor calibration
Contact temperature sensor calibration
 
Ea of cw, ct & cond. system
Ea of cw, ct & cond. systemEa of cw, ct & cond. system
Ea of cw, ct & cond. system
 

More from Testo Limited

Cloud based monitoring
Cloud based monitoringCloud based monitoring
Cloud based monitoringTesto Limited
 
Testo - STA guide - Feb 2014
Testo - STA guide - Feb 2014Testo - STA guide - Feb 2014
Testo - STA guide - Feb 2014Testo Limited
 
Testo - Plant and Works Engineering - Feb 2014
Testo - Plant and Works Engineering - Feb 2014Testo - Plant and Works Engineering - Feb 2014
Testo - Plant and Works Engineering - Feb 2014Testo Limited
 
Testo - PHAM News - Feb 2014
Testo - PHAM News - Feb 2014Testo - PHAM News - Feb 2014
Testo - PHAM News - Feb 2014Testo Limited
 
Testo - Industrial Plant and Equipment - Feb 2014
Testo - Industrial Plant and Equipment - Feb 2014Testo - Industrial Plant and Equipment - Feb 2014
Testo - Industrial Plant and Equipment - Feb 2014Testo Limited
 
Testo - Heating Ventillation and Plumbing - Feb 2014
Testo - Heating Ventillation and Plumbing - Feb 2014Testo - Heating Ventillation and Plumbing - Feb 2014
Testo - Heating Ventillation and Plumbing - Feb 2014Testo Limited
 
Testo - Heating and Ventillation Review - Feb 2014
Testo - Heating and Ventillation Review - Feb 2014Testo - Heating and Ventillation Review - Feb 2014
Testo - Heating and Ventillation Review - Feb 2014Testo Limited
 
Testo - Food and Drink Network UK - Feb 2014
Testo - Food and Drink Network UK - Feb 2014Testo - Food and Drink Network UK - Feb 2014
Testo - Food and Drink Network UK - Feb 2014Testo Limited
 
Testo - Food and Drink International - Feb 2014
Testo - Food and Drink International - Feb 2014Testo - Food and Drink International - Feb 2014
Testo - Food and Drink International - Feb 2014Testo Limited
 
Testo - Environment and Energy Management - Feb 2014
Testo - Environment and Energy Management - Feb 2014Testo - Environment and Energy Management - Feb 2014
Testo - Environment and Energy Management - Feb 2014Testo Limited
 
Testo - Registered Gas Engineer - Feb 2014
Testo - Registered Gas Engineer - Feb 2014Testo - Registered Gas Engineer - Feb 2014
Testo - Registered Gas Engineer - Feb 2014Testo Limited
 
Testo (PWE) Jan 2014
Testo (PWE) Jan 2014Testo (PWE) Jan 2014
Testo (PWE) Jan 2014Testo Limited
 
Testo (plumbing and heating NI) Jan 2014
Testo (plumbing and heating NI) Jan 2014Testo (plumbing and heating NI) Jan 2014
Testo (plumbing and heating NI) Jan 2014Testo Limited
 
Testo (PHAM news) Jan 2014
Testo (PHAM news) Jan 2014Testo (PHAM news) Jan 2014
Testo (PHAM news) Jan 2014Testo Limited
 
Testo (mepca) Jan 2014
Testo (mepca) Jan 2014Testo (mepca) Jan 2014
Testo (mepca) Jan 2014Testo Limited
 
Testo (meat management) Jan 2014
Testo (meat management) Jan 2014Testo (meat management) Jan 2014
Testo (meat management) Jan 2014Testo Limited
 
Testo (laboratory news) Jan 2014
Testo (laboratory news) Jan 2014Testo (laboratory news) Jan 2014
Testo (laboratory news) Jan 2014Testo Limited
 
Testo (Connecting Industry instrumentation) Jan 2014
Testo (Connecting Industry instrumentation) Jan 2014Testo (Connecting Industry instrumentation) Jan 2014
Testo (Connecting Industry instrumentation) Jan 2014Testo Limited
 
Testo (installer) Jan 2014
Testo (installer) Jan 2014Testo (installer) Jan 2014
Testo (installer) Jan 2014Testo Limited
 
Testo (hvr) Jan 2014
Testo (hvr) Jan 2014Testo (hvr) Jan 2014
Testo (hvr) Jan 2014Testo Limited
 

More from Testo Limited (20)

Cloud based monitoring
Cloud based monitoringCloud based monitoring
Cloud based monitoring
 
Testo - STA guide - Feb 2014
Testo - STA guide - Feb 2014Testo - STA guide - Feb 2014
Testo - STA guide - Feb 2014
 
Testo - Plant and Works Engineering - Feb 2014
Testo - Plant and Works Engineering - Feb 2014Testo - Plant and Works Engineering - Feb 2014
Testo - Plant and Works Engineering - Feb 2014
 
Testo - PHAM News - Feb 2014
Testo - PHAM News - Feb 2014Testo - PHAM News - Feb 2014
Testo - PHAM News - Feb 2014
 
Testo - Industrial Plant and Equipment - Feb 2014
Testo - Industrial Plant and Equipment - Feb 2014Testo - Industrial Plant and Equipment - Feb 2014
Testo - Industrial Plant and Equipment - Feb 2014
 
Testo - Heating Ventillation and Plumbing - Feb 2014
Testo - Heating Ventillation and Plumbing - Feb 2014Testo - Heating Ventillation and Plumbing - Feb 2014
Testo - Heating Ventillation and Plumbing - Feb 2014
 
Testo - Heating and Ventillation Review - Feb 2014
Testo - Heating and Ventillation Review - Feb 2014Testo - Heating and Ventillation Review - Feb 2014
Testo - Heating and Ventillation Review - Feb 2014
 
Testo - Food and Drink Network UK - Feb 2014
Testo - Food and Drink Network UK - Feb 2014Testo - Food and Drink Network UK - Feb 2014
Testo - Food and Drink Network UK - Feb 2014
 
Testo - Food and Drink International - Feb 2014
Testo - Food and Drink International - Feb 2014Testo - Food and Drink International - Feb 2014
Testo - Food and Drink International - Feb 2014
 
Testo - Environment and Energy Management - Feb 2014
Testo - Environment and Energy Management - Feb 2014Testo - Environment and Energy Management - Feb 2014
Testo - Environment and Energy Management - Feb 2014
 
Testo - Registered Gas Engineer - Feb 2014
Testo - Registered Gas Engineer - Feb 2014Testo - Registered Gas Engineer - Feb 2014
Testo - Registered Gas Engineer - Feb 2014
 
Testo (PWE) Jan 2014
Testo (PWE) Jan 2014Testo (PWE) Jan 2014
Testo (PWE) Jan 2014
 
Testo (plumbing and heating NI) Jan 2014
Testo (plumbing and heating NI) Jan 2014Testo (plumbing and heating NI) Jan 2014
Testo (plumbing and heating NI) Jan 2014
 
Testo (PHAM news) Jan 2014
Testo (PHAM news) Jan 2014Testo (PHAM news) Jan 2014
Testo (PHAM news) Jan 2014
 
Testo (mepca) Jan 2014
Testo (mepca) Jan 2014Testo (mepca) Jan 2014
Testo (mepca) Jan 2014
 
Testo (meat management) Jan 2014
Testo (meat management) Jan 2014Testo (meat management) Jan 2014
Testo (meat management) Jan 2014
 
Testo (laboratory news) Jan 2014
Testo (laboratory news) Jan 2014Testo (laboratory news) Jan 2014
Testo (laboratory news) Jan 2014
 
Testo (Connecting Industry instrumentation) Jan 2014
Testo (Connecting Industry instrumentation) Jan 2014Testo (Connecting Industry instrumentation) Jan 2014
Testo (Connecting Industry instrumentation) Jan 2014
 
Testo (installer) Jan 2014
Testo (installer) Jan 2014Testo (installer) Jan 2014
Testo (installer) Jan 2014
 
Testo (hvr) Jan 2014
Testo (hvr) Jan 2014Testo (hvr) Jan 2014
Testo (hvr) Jan 2014
 

Recently uploaded

Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...lizamodels9
 
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...allensay1
 
Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...
Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...
Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...Sheetaleventcompany
 
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...lizamodels9
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...Aggregage
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...amitlee9823
 
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 MonthsSEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 MonthsIndeedSEO
 
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876dlhescort
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsP&CO
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptxnandhinijagan9867
 
Falcon's Invoice Discounting: Your Path to Prosperity
Falcon's Invoice Discounting: Your Path to ProsperityFalcon's Invoice Discounting: Your Path to Prosperity
Falcon's Invoice Discounting: Your Path to Prosperityhemanthkumar470700
 
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort ServiceMalegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort ServiceDamini Dixit
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...Sheetaleventcompany
 
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...rajveerescorts2022
 
RSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors DataRSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors DataExhibitors Data
 
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...daisycvs
 
Call Now ☎️🔝 9332606886🔝 Call Girls ❤ Service In Bhilwara Female Escorts Serv...
Call Now ☎️🔝 9332606886🔝 Call Girls ❤ Service In Bhilwara Female Escorts Serv...Call Now ☎️🔝 9332606886🔝 Call Girls ❤ Service In Bhilwara Female Escorts Serv...
Call Now ☎️🔝 9332606886🔝 Call Girls ❤ Service In Bhilwara Female Escorts Serv...Anamikakaur10
 

Recently uploaded (20)

Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
 
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
 
Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...
Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...
Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...
 
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
 
(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7
(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7
(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
 
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 MonthsSEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
 
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptx
 
Falcon's Invoice Discounting: Your Path to Prosperity
Falcon's Invoice Discounting: Your Path to ProsperityFalcon's Invoice Discounting: Your Path to Prosperity
Falcon's Invoice Discounting: Your Path to Prosperity
 
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort ServiceMalegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabiunwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
 
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
 
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
 
RSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors DataRSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors Data
 
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
 
Call Now ☎️🔝 9332606886🔝 Call Girls ❤ Service In Bhilwara Female Escorts Serv...
Call Now ☎️🔝 9332606886🔝 Call Girls ❤ Service In Bhilwara Female Escorts Serv...Call Now ☎️🔝 9332606886🔝 Call Girls ❤ Service In Bhilwara Female Escorts Serv...
Call Now ☎️🔝 9332606886🔝 Call Girls ❤ Service In Bhilwara Female Escorts Serv...
 

Demonstration thermography report 2 radiator power flushing

  • 1. Demonstration Thermography report Company Testo Ltd Tester: Cheriton House, Newman Andy McGrath - Testo Lane, Phone: 01420 544433 Alton, Hampshire, GU34 2QJ E-Mail: info@testo.co.uk Device Testo 875-2 Serial No.: 01799300 Customer Power Flushing Contractor Measuring Site: Newman Lane Power Flushing Customer Alton, Hampshire, GU34 2QJ Testo Avenue, Alton Measuring Date: 12th July 2011 Task Demonstration Thermography Report to highlight the capabilities of the Testo 875 series Thermal Imaging camera to a Heating / Power Flushing Contractor for the application of Power Flushing of Radiators. Page 1/21
  • 2. Demonstration Thermography report File: IV_00797.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 08:24:54 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 54.1 0.95 20.0 - Measure point 2 55.7 0.95 20.0 - Measure point 3 29.1 0.95 20.0 - Cold spot 1 22.0 0.95 20.0 - Profile line: Remarks: Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their condition prior to conducting the process. The images are of the Lounge radiator, prior to conducting the Power Flushing Process. As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the presence of quite a substantial amount of contamination /sludge in this area of the radiator. Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance. The Auto Cold Spot Indicator has been applied to the thermal image to automatically indicate the coldest point CS1 in the defined area of the image. Additional Spot Temperature markers have been added to the thermal image for temperature comparisons. A Temperature profile line Graph has been applied to the thermal image to highlight the temperature variation across the radiator. The Thermal Image is displayed in " Iron " Palette. Page 2/21
  • 3. Demonstration Thermography report File: IV_00800.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 08:26:52 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 52.9 0.95 20.0 - Measure point 2 22.9 0.95 20.0 - Measure point 3 49.9 0.95 20.0 - Hot spot 1 58.9 0.95 20.0 - Remarks: Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their condition prior to conducting the process. The images are of the Lounge radiator, prior to conducting the Power Flushing Process. As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the presence of quite a substantial amount of contamination /sludge in this area of the radiator. Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance. The Auto Hot Spot Indicator has been applied to the thermal image to automatically indicate the hottest point HS1 in the defined area of the image. Additional Spot Temperature markers have been added to the thermal image for temperature comparisons. The Thermal Image is displayed in " Iron " Palette. Page 3/21
  • 4. Demonstration Thermography report File: IV_00802.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 08:30:49 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 57.1 0.95 20.0 - Measure point 2 58.3 0.95 20.0 - Measure point 3 31.0 0.95 20.0 - Cold spot 1 22.9 0.95 20.0 - Profile line: Remarks: Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their condition prior to conducting the process. The images are of the Hall radiator, prior to conducting the Power Flushing Process. As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the presence of quite a substantial amount of contamination /sludge in this area of the radiator. Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance. The Auto Cold Spot Indicator has been applied to the thermal image to automatically indicate the coldest point CS1 in the defined area of the image. Additional Spot Temperature markers have been added to the thermal image for temperature comparisons. A Temperature profile line Graph has been applied to the thermal image to highlight the temperature variation across the radiator. The Thermal Image is displayed in " Iron " Palette. Page 4/21
  • 5. Demonstration Thermography report File: IV_00824.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 08:54:34 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 52.3 0.95 20.0 - Measure point 2 28.5 0.95 20.0 - Measure point 3 50.1 0.95 20.0 - Hot spot 1 55.6 0.95 20.0 - Remarks: Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their condition prior to conducting the process. The images are of the Hall radiator, prior to conducting the Power Flushing Process. As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the presence of quite a substantial amount of contamination /sludge in this area of the radiator. Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance. The Auto Hot Spot Indicator has been applied to the thermal image to automatically indicate the Hottest point HS1 in the defined area of the image. Additional Spot Temperature markers have been added to the thermal image for temperature comparisons. The Thermal Image is displayed in " Iron " Palette. Page 5/21
  • 6. Demonstration Thermography report File: IV_00808.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 08:35:40 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 56.3 0.95 20.0 - Measure point 2 50.6 0.95 20.0 - Measure point 3 38.3 0.95 20.0 - Cold spot 1 26.5 0.95 20.0 - Profile line: Remarks: Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their condition prior to conducting the process. The images are of the Front Bedroom No 1 radiator, prior to conducting the Power Flushing Process. As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the presence of quite a substantial amount of contamination /sludge in this area of the radiator. Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance. The Auto Cold Spot Indicator has been applied to the thermal image to automatically indicate the coldest point CS1 in the defined area of the image. Additional Spot Temperature markers have been added to the thermal image for temperature comparisons. A Temperature profile line Graph has been applied to the thermal image to highlight the temperature variation across the radiator. The Thermal Image is displayed in " Iron " Palette. Page 6/21
  • 7. Demonstration Thermography report File: IV_00811.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 08:37:02 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 52.4 0.95 20.0 - Measure point 2 34.7 0.95 20.0 - Measure point 3 47.4 0.95 20.0 - Hot spot 1 57.7 0.95 20.0 - Remarks: Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their condition prior to conducting the process. The images are of the Front Bedroom No 1 radiator, prior to conducting the Power Flushing Process. As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the presence of quite a substantial amount of contamination /sludge in this area of the radiator. Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance. The Auto Hot Spot Indicator has been applied to the thermal image to automatically indicate the Hottest point HS1 in the defined area of the image. Additional Spot Temperature markers have been added to the thermal image for temperature comparisons. The Thermal Image is displayed in " Iron " Palette. Page 7/21
  • 8. Demonstration Thermography report File: IV_00812.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 08:40:36 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 48.4 0.95 20.0 - Measure point 2 36.6 0.95 20.0 - Measure point 3 57.9 0.95 20.0 - Cold spot 1 29.4 0.95 20.0 - Remarks: Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their condition prior to conducting the process. The images are of the Front Bedroom No 2, prior to conducting the Power Flushing Process. As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the presence of quite a substantial amount of contamination /sludge in this area of the radiator. Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance. The Auto Cold Spot Indicator has been applied to the thermal image to automatically indicate the coldest point CS1 in the defined area of the image. Additional Spot Temperature markers have been added to the thermal image for temperature comparisons. The Thermal Image is displayed in " Iron " Palette. Page 8/21
  • 9. Demonstration Thermography report File: IV_00813.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 08:41:02 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 59.2 0.95 20.0 - Measure point 2 56.1 0.95 20.0 - Hot spot 1 60.0 0.95 20.0 - Profile line: Remarks: Thermal Images of the radiators prior to the Power Flushing process were captured as a record of their condition prior to conducting the process. The images are of the Front Bedroom No 2 radiator, prior to conducting the Power Flushing Process. As can be seen, there is a significant cold area in the middle of the radiator,which is indicative of the presence of quite a substantial amount of contamination /sludge in this area of the radiator. Thus verifying the requirement to Power Flush the radiator to improve the radiator efficiency / performance. The Auto Hot Spot Indicator has been applied to the thermal image to automatically indicate the Hottest point HS1 in the defined area of the image. Additional Spot Temperature markers have been added to the thermal image for temperature comparisons. A Temperature profile line Graph has been applied to the thermal image to highlight the temperature variation across the radiator. The Thermal Image is displayed in " Iron " Palette. Page 9/21
  • 10. Demonstration Thermography report File: IV_00836.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 09:18:02 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Remarks: The images are of the Power Flushing equipment. Page 10/21
  • 11. Demonstration Thermography report File: IV_00839.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 09:31:04 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Remarks: The images are of the Lounge Radiator, during the Power Flushing process, showing the gradual removal of the contaminant/sludge. Page 11/21
  • 12. Demonstration Thermography report File: IV_00840.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 09:33:31 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Remarks: The images are of the Lounge Radiator, during the Power Flushing process, showing the gradual removal of the contaminant/sludge. Page 12/21
  • 13. Demonstration Thermography report File: IV_00845.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 09:46:33 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Remarks: The images are of the Lounge Radiator, during the Power Flushing process, showing the gradual removal of the contaminant/sludge. Page 13/21
  • 14. Demonstration Thermography report File: IV_00842.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 09:39:14 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Remarks: Images of the Magnets from the Power Flushing unit, highlighting the significant amount of contaminant / sludge removed from one radiator. Page 14/21
  • 15. Demonstration Thermography report File: IV_00843.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 09:40:53 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Remarks: Images of the Magnets from the Power Flushing unit, highlighting the significant amount of contaminant / sludge removed from one radiator. Page 15/21
  • 16. Demonstration Thermography report File: IV_00878.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 14:36:24 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 55.5 0.95 20.0 - Measure point 2 52.2 0.95 20.0 - Measure point 3 54.3 0.95 20.0 - Profile line: Remarks: Thermal Images of the radiators after the Power Flushing process were captured as a record of their condition following the process. The boiler has now been switched on again and the heating system is now operational and been running for a short period of time. The images are of the Lounge radiator, as can be seen, in comparison to image 0797, the significant cold area in the middle of the radiator,is now removed and the radiator now shows a consistant overall temperature. Thus verifying that the process of Power Flushing the radiator has considerably improved the radiator efficiency / performance. Spot Temperature markers have been added to the thermal image for temperature comparisons. A Temperature profile line Graph has been applied to the thermal image to highlight the temperature variation across the radiator and shows consistancy across the radiator. The Thermal Image is displayed in " Iron " Palette. Page 16/21
  • 17. Demonstration Thermography report File: IV_00882.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 14:38:41 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 57.6 0.95 20.0 - Measure point 2 55.7 0.95 20.0 - Measure point 3 53.6 0.95 20.0 - Profile line: Remarks: Thermal Images of the radiators after the Power Flushing process were captured as a record of their condition following the process. The boiler has now been switched on again and the heating system is now operational and been running for a short period of time. The images are of the Hall radiator, as can be seen, in comparison to image 0802, the significant cold area in the middle of the radiator,is now removed and the radiator now shows a consistant overall temperature. Thus verifying that the process of Power Flushing the radiator has considerably improved the radiator efficiency / performance. Spot Temperature markers have been added to the thermal image for temperature comparisons. A Temperature profile line Graph has been applied to the thermal image to highlight the temperature variation across the radiator and shows consistancy across the radiator. The Thermal Image is displayed in " Iron " Palette. Page 17/21
  • 18. Demonstration Thermography report File: IV_00872.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 14:32:33 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 58.8 0.95 20.0 - Measure point 2 54.7 0.95 20.0 - Measure point 3 52.6 0.95 20.0 - Profile line: Remarks: Thermal Images of the radiators after the Power Flushing process, were captured as a record of their condition following the process. The boiler has now been switched on again and the heating system is now operational and been running for a short period of time. The images are of the radiator in the Front Bedroom No 1, as can be seen, in comparison to image 0808, the significant cold area in the middle of the radiator,is now removed and the radiator now shows a consistant overall temperature. Thus verifying that the process of Power Flushing the radiator has considerably improved the radiator efficiency / performance. Spot Temperature markers have been added to the thermal image for temperature comparisons. A Temperature profile line Graph has been applied to the thermal image to highlight the temperature variation across the radiator and shows consistancy across the radiator. The Thermal Image is displayed in " Iron " Palette. Page 18/21
  • 19. Demonstration Thermography report File: IV_00869.BMT Date: 12/07/2011 lens type: Standard 32° lens serial no.: 20223817 Measuri 14:30:48 ng Time: Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 57.0 0.95 20.0 - Measure point 2 55.5 0.95 20.0 - Measure point 3 54.0 0.95 20.0 - Profile line: Remarks: Thermal Images of the radiators after the Power Flushing process were captured as a record of their condition following the process. The boiler has now been switched on again and the heating system is now operational and been running for a short period of time. The images are of the radiator in the Front Bedroom No 2, as can be seen, in comparison to image 0812, the significant cold area in the middle of the radiator,is now removed and the radiator now shows a consistant overall temperature. Thus verifying that the process of Power Flushing the radiator has considerably improved the radiator efficiency / performance. Spot Temperature markers have been added to the thermal image for temperature comparisons. A Temperature profile line Graph has been applied to the thermal image to highlight the temperature variation across the radiator and shows consistancy across the radiator. The Thermal Image is displayed in " Iron " Palette. Page 19/21
  • 20. The images are of the radiator in the Front Bedroom No 2, as can be seen, in comparison to image 0812, the significant cold area in the middle of the radiator,is now removed and the radiator now shows a consistant overall temperature. Thus verifying that the process of Power Flushing the radiator has considerably improved the radiator efficiency / performance. Spot Temperature markers have been added to the thermal image for temperature comparisons. Demonstration Thermography report A Temperature profile line Graph has been applied to the thermal image to highlight the temperature variation across the radiator and shows consistancy across the radiator. The Thermal Image is displayed in " Iron " Palette. Review: Demonstration Thermography Report to highlight the capabilities of the Testo 875 series Thermal Imaging camera and the Testo IR software. This is an example report for Demonstration purposes only. The report format is using the "Standard" report template from the selection of Report Templates available in the Testo IR software. A demonstration of the Testo 875-2 Thermal Imaging camera was conducted for a Heating / Power Fluching Contractor, during the course of Power Flushing being conducted at Dwelling. The objective was to demonstrate how a Testo 875-2 Thermal Imaging camera could be used to record Thermal and Digital images during the course of the Power Flushing process, to show the conditions of the radiators prior to and after the process and to verify the the improvements made, using Power Flushing . The Boiler was switched on just prior to arrival and images were subsequently captured of the radiators, to record their condition / performance. With reference to the images at this stage, a number of the radiators had significant cold areas, indicating substantial contaminant / sludge and the need for Power Flushing. Images of the Lounge, Hall, Bedroom 1 and Bedroom 2 Radiators, (which were the radiators in the worst condition), were recorded for the purpose of comparison, following the process. Images were also recorded during the Power Flushing process and specifically the images 0839, 0840 & 0845 show the Lounge radiator changing / improving condition during the process. Following completion of the Power Flushing process on all the radiators, the boiler was switched on and the heating system was operational and images of the Lounge, Hall, Bedroom 1 and Bedroom 2 radiators were recorded for comparison purposes and to highlight the significant improvements in Condition / Performance. As can be seen, the thermal images clearly show the conditions of the radiators before, during and after the Power Flushing process and verify the improvements that this process produces. The purpose of the report is to demonstrate the capabilities of the Testo 875-2, a 160 x 120 pixel configuration Thermal Imaging camera in respect of the image quality / resolution that is recorded/produced with this level of Thermal Imaging camera and to demonstrate how it can be used to verify the Power Flushing process. Please note that any temperatures indicated on the images are "Apparent Temperatures" and may not be truely representative. An overall emissivity value has been used in the images for these demonstration purposes. For accurate temperature measurement, the relevant emissivity value to the specific material to be measured, would have to be established. It should be noted that Testo do not provide a Thermography Consultancy Service, the images are purely for Equipment Demonstration purposes to highlight the capabilities of the Testo range of Thermal Imaging cameras and the Testo IR software. It is not the purpose of the images/report to specifically identify/highlight any faults or Thermal Anomalies, or to provide comment/observation relating to any anomalies. Some of the features of the camera and software have also been applied to the Thermal images. Spot Temperature markers have been added to the thermal images to indicate temperatures. Auto Hot / Cold Spot Indicator has been applied, which automatically highlights the Hottest or Coldest point in the defined area. Temperature Profile Line Graph shows the temperature variation in graph form across the subject. Palettes a variety of palettes have been used for the thermal images. Eight palettes are available on the camera and in the software. Page 20/21
  • 21. Demonstration Thermography report The images are automatically Time and Date Stamped to verify the time and date when the images were taken. The report also details the Emissivity value relating to the image taken. 12/07/2011 , Andy McGrath - Testo Page 21/21