Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a Suresh Boorneni1 , A.V.Satyanarayana2, 1Department of Mechanical Engineering, G.P.R College of Engineering, Andhra Pradesh, India) 2ASSOCIATE PROFESSOR (Department Of Mechanical Engineering, G.P.R College of Engineering, Andhra Pradesh, India) 
I. INTRODUCTION 
Vapor compression Refrigeration system is an improved type of Mechanical refrigeration system. The ability of certain liquids to absorb enormous quantities of heat as they vaporize is the basis of this system. Compared to melting solids (say ice) to obtain refrigeration effect, vaporizing liquid refrigerant has more advantages. To mention a few, the refrigerating effect can be started or stopped at will, the rate of cooling can be predetermined, the vaporizing temperatures can be govern by controlling the pressure at which the liquid vaporizes. Moreover, the vapor can be readily collected and condensed back into liquid state so that same liquid can be recirculated over and over again to obtain refrigeration effect. Thus the vapor compression system employs a liquid refrigerant which evaporates and condenses readily. The System is a closed one since the refrigerant never leaves the system. The coefficient of performance of a refrigeration system is the ratio of refrigerating effect to the compression work; therefore the coefficient of performance can be increased by increasing the refrigerating effect or by decreasing the compression work.The Vapor compression refrigeration system is now-a-days used for all purpose refrigeration. It is generally used for all industrial purposes from a small domestic refrigerator to a big air-conditioning plant. 1.2 Statement of Problem The main components of refrigeration system are compressor, condenser, expansion valve and evaporator. In general refrigeration system the entire refrigeration circuit is exposed to atmosphere so that some losses may occur. So the entire refrigeration circuit is placed in the closed cabin. The emission of refrigerants like R12, R22, R134a etc… are causes the depletion of ozone layer. So that the refrigerant R600a has been chosen because it is natural refrigerant consist of hydrocarbon and eco friendly. In the present dissertation work the heat exchanger is incorporated i.e. the capillary tube is insulated together with suction line of the compressor. So that the heat transfer occur between vapour refrigerant in the suction line and the liquid refrigerant in the capillary tube, so that some precooled liquid refrigerant can enter in to evaporator which is more efficient than regular refrigeration system. This change in temperature of liquid refrigerant entering in to evaporator will increase the coefficient performance of the system. 
ABSTRACT 
The main objective in present dissertation has been focused on alternative refrigerant to conventional CFC refrigerant, CFC like R12, R22, R134a, etc… are not eco friendly. The emission of these refrigerants causes the depletion of ozone layer etc…. Hence to avoid above difficulty the alternative of refrigerant in the form of R600a has been choosing. R600a refrigerant are natural refrigerant consist of hydrocarbon. In the present work, the performance of the domestic refrigerator is determined using R600a (Isobutane) and comparison with R134a (Tetrafluoro-ethane) as the part of project work the refrigerator setup consists of evaporator, compressor, condenser and expansion valve are chosen with suitable specification. Also in the present work an attempt has been made to improve the coieffiecnt of performance (cop) of the system, by incorporating a heat exchanger before admitting refrigerant into the compressor. Thus the compressor work reduces and it may results increase the performance of the refrigeration system. 
KEYWORDS :Heat exchanger, coieffiecnt of performance, Isobutane, depletion of ozone, alternative refrigerants.
Improving and Comparing The Coefficient… 
www.ijceronline.com Open Access Journal Page 2 
1.3 objective of the work 
1. Determining the actual coefficient of performance of domestic refrigerator using refrigerants R-134a and R-600a. 
2. Comparison the coefficient of performance of domestic refrigerators between refrigerants using R-134a and R-600a. 
3. Experiments increasing coefficient of performance of vapour compression refrigeration system by incorporating heat exchanger. 
4. Comparison the coefficient of performance of domestic refrigerators between refrigerants using R-134a and R-600a after incorporating heat exchanger. 
II. EXPERIMENTAL SETUP AND DESIGN DETAILS 
Different experimental and theoretical comparison is performed by many researchers to evaluate the performance of domestic refrigerator by using different refrigerants. In this experimental R-600a is compared with the R-134a in a domestic refrigeration system. To perform the experiment 165L refrigerator is selected which was designed to work with R-134a.it is consists of an evaporator, air cooled condenser, reciprocating compressor. Heat exchanger incorporating in system, capillary tube rounded on the entire suction line of system. By the process rounding of capillary to the suction line we reduce that external type of heat exchanger. Figure.1 Fabrication of Refrigeration Tutor before Heat Exchanger Incorporation Figure.2 Fabrication of Refrigeration Tutor after Heat Exchanger Incorporation 
III. EXPERIMENTAL PROCEDURE 
While coming experiment two types of refrigerant using in the refrigerator R134a & R600a ,Putting the freezer regulator at top position so that no need of cut-off easily taken for system..Take down which refrigerant is in application. Take down the energy meter reading no of seconds for 5 revolution of energy meter Take down the reading of compressor pressure discharge inlet & condenser outlet from the pressure gauges. Take down the temperature readings of compressor suction line, discharge temperature, temperature of evaporator and condenser outlet temperature of system. Calculate coefficient of performance & energy consumption. And the experiment is repeated for other refrigerant and the readings are tabulated in the tabular column.
Improving and Comparing The Coefficient… 
www.ijceronline.com Open Access Journal Page 3 
IV. RESULTS AND DISCUSSION 
Table reading taken from the experimental procedure of R134a refrigerant placed in the experimental setup. Note the reading of compressor inlet, compressor outlet condenser outlet, evaporator temperature pressure & of various parameters in the setup. Table.1 Reading of R134a Refrigerant without Heat Exchanger 
Operating freezer point 
N (rev/sec) 
T1 °c 
T2 °c 
T3 °c 
P1 (bar) 
P2 (bar) 
P3 (bar) 
C.O.P 
1 2 3 4 
61:07 61:12 60:00 59:00 
-3.7 -5.9 -9.3 -11 
53 56.9 57.5 60 
40 42 44 46 
0.68 0.62 0.55 0.55 
9.6 10.34 11.72 11.72 
9.31 9.65 11.03 11.03 
4.22 4.20 4.16 3.81 
Table .2 Reading of R134a Refrigerant with Heat Exchanger 
Operating freezer point 
N (rev/sec) 
T1 °c 
T2 °c 
T3 °c 
P1 (bar) 
P2 (bar) 
P3 (bar) 
C.O.P 
1 2 3 4 5 6 7 
46:10 49:18 50:30 49:29 51:20 53:12 52 
-7.9 -7.9 -9.6 -12 -15 -17.8 -19 
54.8 54.9 55.6 57 58.5 59.2 60.1 
44.3 42.3 41.6 42.6 43 43.1 43.1 
0.68 0.55 0.58 0.58 0.37 0.344 0.310 
17.24 15.51 15.72 15.86 15.17 15.17 14.48 
16.55 14.62 15.03 15.17 14.48 14.48 14.13 
4.55 4.44 4.30 3.9 3.87 3.64 3.40 
Table reading taken from the experimental procedure of R600a refrigerant placed in the experimental setup. Note down reading as per procedure placed. Table .3 Reading for R600a without Heat Exchanger 
Operating freezer point 
N (rev/sec) 
T1 °c 
T2 °c 
T3 °c 
P1 (bar) 
P2 (bar) 
P3 (bar) 
C.O.P 
1 2 3 4 5 6 7 
54 55 54 57 60 57 60 
-10.6 -11.6 -12.2 -14.1 -16.8 -17.7 -18.3 
55.9 57.4 56.8 57.2 58.4 59.3 60 
45.2 45.1 43.9 43 44 43.8 44.3 
0.14 0.13 0.14 0.07 0.08 0.07 0.08 
9.2 8.9 9.1 8.06 8.34 8 7.92 
8.21 8.12 7.94 7.79 7.94 7.35 7.24 
5.76 4.12 4.76 3.9 3.8 3.7 4.08 
Table .4 Reading for R600a Refrigerant with Heat Exchanger 
Operating freezer point 
N (rev/sec) 
T1 °c 
T2 °c 
T3 °c 
P1 (bar) 
P2 (bar) 
P3 (bar) 
C.O.P 
1 2 3 4 5 6 7 
55:10 55:10 56:60 56:10 60:20 60:09 60:05 
-11.6 -11.9 -12.9 -14.6 -17.6 -19.2 -19.6 
51.9 51.7 52.3 53.6 53.7 53.3 53.5 
41.3 39.4 41.7 39.6 38 39.2 38.6 
0.13 0.13 0.14 0.06 0.06 0.07 0.06 
8.2 8.4 8.2 8.06 7.93 7.44 7.33 
7.93 7.93 7.91 7.79 7.58 7.24 7.17 
5.2 5.19 5.21 4.15 3.6 4.01 4.06
Improving and Comparing The Coefficient… 
www.ijceronline.com Open Access Journal Page 4 
Figure .3 Shows R600a refrigerant Evaporator point Vs C.O.P Colour Represent in graph Green colour : refrigerant with H.E Red colour : refrigerant without H.E Figure .4 Shows R134a refrigerant Evaporator point Vs C.O.P Figure .5 Represent R600a evaporator Temp Vs Discharge Temp
Improving and Comparing The Coefficient… 
www.ijceronline.com Open Access Journal Page 5 
Figure .6 Represent R134a evaporator Temp Vs Discharge Temp 
V. CONCLUSIONS 
An experiment is conducted on domestic refrigerator by with & without incorporating heat exchanger in the system by using various refrigerants in the fabrication system and their coefficient of performance & energy consumption of the system is calculated. 
 Refrigerator carried out using without & with heat exchanger of refrigerant R134a & R600a in system, in which coefficient of performance of refrigerator 0.95 increased by using heat exchanger. 
 In the same way the discharge temperature of compressor is decreased with 10% by using heat exchanger , energy consumption refrigerator gradually increased with 3% of compared to normal domestic refrigerator. 
REFERENCES 
[1] R. Yajima et al., 1994, "The Performance Evaluation of HFC Alternative Refrigerants for HCFC-22", IIR Joint meeting, CFCs The Day After, Padova [2] K. Furuhama et al., 1994, "Performance Evaluation of Residential Air Conditioner with HFC32/125 Mixture, The International Symposium HCFC Alternative Refrigerants, Kobe [3] E. Johnson, Global warming from HFC, Environ. Impact Assessment Rev. 18 (1998) 485–492. [4] M.A. Hammad, M.A. Alsaad, The use of hydrocarbon mixtures as refrigerants in domestic refrigerators, Applied Thermal Engineering 19 (1999) 1181–1189. [5] Douglas J D, Braun J E, Groll E A and Tree D R (1999), “A Cost Method Comparing Alternative Refrigerant Applied to R-22 System”, International Journal of Refrigeration, Vol. 22, pp. 107-125. [6] B. O. Bolaji, Experimental study of R152a and R32 to replace R134a in a domestic refrigerator, Energy 35 (2010) 3793–3798.

Más contenido relacionado

La actualidad más candente

Bidirectional syngas generator TSW work on advanced large scale non steady st...
Bidirectional syngas generator TSW work on advanced large scale non steady st...Bidirectional syngas generator TSW work on advanced large scale non steady st...
Bidirectional syngas generator TSW work on advanced large scale non steady st...
Steve Wittrig
 
Heat recovery design for starbucks store retrofit_BS
Heat recovery design for starbucks store retrofit_BSHeat recovery design for starbucks store retrofit_BS
Heat recovery design for starbucks store retrofit_BS
Chris Anderson
 
Coal fired electric power plants23
Coal fired electric power plants23Coal fired electric power plants23
Coal fired electric power plants23
Munna Sagar
 

La actualidad más candente (20)

Design With Solid works Software and Planning Calculation Analysis of Fire Tu...
Design With Solid works Software and Planning Calculation Analysis of Fire Tu...Design With Solid works Software and Planning Calculation Analysis of Fire Tu...
Design With Solid works Software and Planning Calculation Analysis of Fire Tu...
 
Hmt lab manual
Hmt lab manualHmt lab manual
Hmt lab manual
 
4 ch1
4 ch14 ch1
4 ch1
 
Bidirectional syngas generator TSW work on advanced large scale non steady st...
Bidirectional syngas generator TSW work on advanced large scale non steady st...Bidirectional syngas generator TSW work on advanced large scale non steady st...
Bidirectional syngas generator TSW work on advanced large scale non steady st...
 
STUDY OF PERFORMANCE EVALUATION OF DOMESTIC REFRIGERATOR WORKING WITH MIXTURE...
STUDY OF PERFORMANCE EVALUATION OF DOMESTIC REFRIGERATOR WORKING WITH MIXTURE...STUDY OF PERFORMANCE EVALUATION OF DOMESTIC REFRIGERATOR WORKING WITH MIXTURE...
STUDY OF PERFORMANCE EVALUATION OF DOMESTIC REFRIGERATOR WORKING WITH MIXTURE...
 
(HTS) High Temperature Shift Catalyst (VSG-F101) - Comprehensiev Overview
(HTS) High Temperature Shift Catalyst (VSG-F101) - Comprehensiev Overview(HTS) High Temperature Shift Catalyst (VSG-F101) - Comprehensiev Overview
(HTS) High Temperature Shift Catalyst (VSG-F101) - Comprehensiev Overview
 
Hp heater ch-8.3
Hp heater ch-8.3Hp heater ch-8.3
Hp heater ch-8.3
 
Effect of approching temperature on the performance and size of li br water v...
Effect of approching temperature on the performance and size of li br water v...Effect of approching temperature on the performance and size of li br water v...
Effect of approching temperature on the performance and size of li br water v...
 
Heat recovery design for starbucks store retrofit_BS
Heat recovery design for starbucks store retrofit_BSHeat recovery design for starbucks store retrofit_BS
Heat recovery design for starbucks store retrofit_BS
 
Lab%201
Lab%201Lab%201
Lab%201
 
Assessment of boiler performance
Assessment of boiler performanceAssessment of boiler performance
Assessment of boiler performance
 
Steam Reformer Surveys - Techniques for Optimization of Primary Reformer Oper...
Steam Reformer Surveys - Techniques for Optimization of Primary Reformer Oper...Steam Reformer Surveys - Techniques for Optimization of Primary Reformer Oper...
Steam Reformer Surveys - Techniques for Optimization of Primary Reformer Oper...
 
Supercritical Thermal Power plant
Supercritical Thermal Power plantSupercritical Thermal Power plant
Supercritical Thermal Power plant
 
IRJET- A Review on Developing a Model that Uses Waste Heat from Condenser in ...
IRJET- A Review on Developing a Model that Uses Waste Heat from Condenser in ...IRJET- A Review on Developing a Model that Uses Waste Heat from Condenser in ...
IRJET- A Review on Developing a Model that Uses Waste Heat from Condenser in ...
 
Coal fired electric power plants23
Coal fired electric power plants23Coal fired electric power plants23
Coal fired electric power plants23
 
Steam Basics
Steam BasicsSteam Basics
Steam Basics
 
Thermal analysis
Thermal analysisThermal analysis
Thermal analysis
 
95396211 heat-transfer-lab-manual
95396211 heat-transfer-lab-manual95396211 heat-transfer-lab-manual
95396211 heat-transfer-lab-manual
 
Chapter 5 Fundamentals of Refrigeration
Chapter 5  Fundamentals of RefrigerationChapter 5  Fundamentals of Refrigeration
Chapter 5 Fundamentals of Refrigeration
 
Energy conservation
Energy conservationEnergy conservation
Energy conservation
 

Destacado

IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
ijceronline
 

Destacado (10)

G04702074087
G04702074087G04702074087
G04702074087
 
H04702088094
H04702088094H04702088094
H04702088094
 
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
 
F04702062073
F04702062073F04702062073
F04702062073
 
J04701080085
J04701080085J04701080085
J04701080085
 
A Brief Study on Usability Principles of Mobile Commerce
A Brief Study on Usability Principles of Mobile CommerceA Brief Study on Usability Principles of Mobile Commerce
A Brief Study on Usability Principles of Mobile Commerce
 
Enhancement of the Performance of Hydraulic Power Pack by Increasing Heat Dis...
Enhancement of the Performance of Hydraulic Power Pack by Increasing Heat Dis...Enhancement of the Performance of Hydraulic Power Pack by Increasing Heat Dis...
Enhancement of the Performance of Hydraulic Power Pack by Increasing Heat Dis...
 
K0470201120114
K0470201120114K0470201120114
K0470201120114
 
On (1,2)*-πgθ-CLOSED SETS IN BITOPOLOGICAL SPACES
On (1,2)*-πgθ-CLOSED SETS IN BITOPOLOGICAL SPACESOn (1,2)*-πgθ-CLOSED SETS IN BITOPOLOGICAL SPACES
On (1,2)*-πgθ-CLOSED SETS IN BITOPOLOGICAL SPACES
 
Stochastic Model to Find the Diagnostic Reliability of Gallbladder Ejection F...
Stochastic Model to Find the Diagnostic Reliability of Gallbladder Ejection F...Stochastic Model to Find the Diagnostic Reliability of Gallbladder Ejection F...
Stochastic Model to Find the Diagnostic Reliability of Gallbladder Ejection F...
 

Similar a Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Am318385
Am318385Am318385
Am318385
IJMER
 

Similar a Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a (20)

Cu4201638643
Cu4201638643Cu4201638643
Cu4201638643
 
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review PaperIRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
 
K10854 Experimental evaluation of cascade refrigeration plant
K10854 Experimental evaluation of cascade refrigeration plantK10854 Experimental evaluation of cascade refrigeration plant
K10854 Experimental evaluation of cascade refrigeration plant
 
IRJET- Comparative Analysis of the Performance of R22 with its Alternative ...
IRJET- 	 Comparative Analysis of the Performance of R22 with its Alternative ...IRJET- 	 Comparative Analysis of the Performance of R22 with its Alternative ...
IRJET- Comparative Analysis of the Performance of R22 with its Alternative ...
 
IRJET- Comparison of COP of R134A with Hydrocarbons by using VCR Cycle
IRJET- Comparison of COP of R134A with Hydrocarbons by using VCR CycleIRJET- Comparison of COP of R134A with Hydrocarbons by using VCR Cycle
IRJET- Comparison of COP of R134A with Hydrocarbons by using VCR Cycle
 
Am318385
Am318385Am318385
Am318385
 
Experimental investigation of waste heat recovery system for domestic refrige...
Experimental investigation of waste heat recovery system for domestic refrige...Experimental investigation of waste heat recovery system for domestic refrige...
Experimental investigation of waste heat recovery system for domestic refrige...
 
IRJET- Thermodynamic Performance Comparison between Ethylene and Ethane in Tr...
IRJET- Thermodynamic Performance Comparison between Ethylene and Ethane in Tr...IRJET- Thermodynamic Performance Comparison between Ethylene and Ethane in Tr...
IRJET- Thermodynamic Performance Comparison between Ethylene and Ethane in Tr...
 
C012441216
C012441216C012441216
C012441216
 
Thermodynamic analysis of_actual_vapour_compression_system_with_r22_and_its_e...
Thermodynamic analysis of_actual_vapour_compression_system_with_r22_and_its_e...Thermodynamic analysis of_actual_vapour_compression_system_with_r22_and_its_e...
Thermodynamic analysis of_actual_vapour_compression_system_with_r22_and_its_e...
 
EXPERIMENTAL INVESTIGATION OF WASTE HEAT RECOVERY SYSTEM FOR DOMESTIC REFRIGE...
EXPERIMENTAL INVESTIGATION OF WASTE HEAT RECOVERY SYSTEM FOR DOMESTIC REFRIGE...EXPERIMENTAL INVESTIGATION OF WASTE HEAT RECOVERY SYSTEM FOR DOMESTIC REFRIGE...
EXPERIMENTAL INVESTIGATION OF WASTE HEAT RECOVERY SYSTEM FOR DOMESTIC REFRIGE...
 
IJREI_A thermodynamic analysis of ejector type vapour refrigeration system us...
IJREI_A thermodynamic analysis of ejector type vapour refrigeration system us...IJREI_A thermodynamic analysis of ejector type vapour refrigeration system us...
IJREI_A thermodynamic analysis of ejector type vapour refrigeration system us...
 
Complete Evaluation of Vapour Compression Refrigeration System using R407C an...
Complete Evaluation of Vapour Compression Refrigeration System using R407C an...Complete Evaluation of Vapour Compression Refrigeration System using R407C an...
Complete Evaluation of Vapour Compression Refrigeration System using R407C an...
 
To study the application of nanorefrigerant in refrigeration system a review
To study the application of nanorefrigerant in refrigeration system a reviewTo study the application of nanorefrigerant in refrigeration system a review
To study the application of nanorefrigerant in refrigeration system a review
 
Simulation of N2 Gas Separation Process from Air
Simulation of N2 Gas Separation Process from AirSimulation of N2 Gas Separation Process from Air
Simulation of N2 Gas Separation Process from Air
 
IRJET- Design and Fabrication of Simultaneous Heating and Cooling in VCR ...
IRJET-  	  Design and Fabrication of Simultaneous Heating and Cooling in VCR ...IRJET-  	  Design and Fabrication of Simultaneous Heating and Cooling in VCR ...
IRJET- Design and Fabrication of Simultaneous Heating and Cooling in VCR ...
 
E012262226
E012262226E012262226
E012262226
 
IRJET- Life Cycle Testing of Hermetic Compressor using Hydro-Carbon Refrigerant
IRJET- Life Cycle Testing of Hermetic Compressor using Hydro-Carbon RefrigerantIRJET- Life Cycle Testing of Hermetic Compressor using Hydro-Carbon Refrigerant
IRJET- Life Cycle Testing of Hermetic Compressor using Hydro-Carbon Refrigerant
 
IRJET- Enhancement of COP of Vapor Compression Refrigeration Cycle using CFD
IRJET- Enhancement of COP of Vapor Compression Refrigeration Cycle using CFDIRJET- Enhancement of COP of Vapor Compression Refrigeration Cycle using CFD
IRJET- Enhancement of COP of Vapor Compression Refrigeration Cycle using CFD
 
CASE-STUDY-OF-LIQUID-SUCTION-HEAT-EXCHANGER-IN.pptx
CASE-STUDY-OF-LIQUID-SUCTION-HEAT-EXCHANGER-IN.pptxCASE-STUDY-OF-LIQUID-SUCTION-HEAT-EXCHANGER-IN.pptx
CASE-STUDY-OF-LIQUID-SUCTION-HEAT-EXCHANGER-IN.pptx
 

Último

+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
?#DUbAI#??##{{(☎️+971_581248768%)**%*]'#abortion pills for sale in dubai@
 
Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and Myths
Joaquim Jorge
 

Último (20)

The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed texts
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
 
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
 
Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024
 
Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, AdobeApidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and Myths
 
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
AWS Community Day CPH - Three problems of Terraform
AWS Community Day CPH - Three problems of TerraformAWS Community Day CPH - Three problems of Terraform
AWS Community Day CPH - Three problems of Terraform
 
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data DiscoveryTrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
 
Tech Trends Report 2024 Future Today Institute.pdf
Tech Trends Report 2024 Future Today Institute.pdfTech Trends Report 2024 Future Today Institute.pdf
Tech Trends Report 2024 Future Today Institute.pdf
 
What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?
 
A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?
 

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

  • 1. ISSN (e): 2250 – 3005 || Vol, 04 || Issue, 8 || August – 2014 || International Journal of Computational Engineering Research (IJCER) www.ijceronline.com Open Access Journal Page 1 Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a Suresh Boorneni1 , A.V.Satyanarayana2, 1Department of Mechanical Engineering, G.P.R College of Engineering, Andhra Pradesh, India) 2ASSOCIATE PROFESSOR (Department Of Mechanical Engineering, G.P.R College of Engineering, Andhra Pradesh, India) I. INTRODUCTION Vapor compression Refrigeration system is an improved type of Mechanical refrigeration system. The ability of certain liquids to absorb enormous quantities of heat as they vaporize is the basis of this system. Compared to melting solids (say ice) to obtain refrigeration effect, vaporizing liquid refrigerant has more advantages. To mention a few, the refrigerating effect can be started or stopped at will, the rate of cooling can be predetermined, the vaporizing temperatures can be govern by controlling the pressure at which the liquid vaporizes. Moreover, the vapor can be readily collected and condensed back into liquid state so that same liquid can be recirculated over and over again to obtain refrigeration effect. Thus the vapor compression system employs a liquid refrigerant which evaporates and condenses readily. The System is a closed one since the refrigerant never leaves the system. The coefficient of performance of a refrigeration system is the ratio of refrigerating effect to the compression work; therefore the coefficient of performance can be increased by increasing the refrigerating effect or by decreasing the compression work.The Vapor compression refrigeration system is now-a-days used for all purpose refrigeration. It is generally used for all industrial purposes from a small domestic refrigerator to a big air-conditioning plant. 1.2 Statement of Problem The main components of refrigeration system are compressor, condenser, expansion valve and evaporator. In general refrigeration system the entire refrigeration circuit is exposed to atmosphere so that some losses may occur. So the entire refrigeration circuit is placed in the closed cabin. The emission of refrigerants like R12, R22, R134a etc… are causes the depletion of ozone layer. So that the refrigerant R600a has been chosen because it is natural refrigerant consist of hydrocarbon and eco friendly. In the present dissertation work the heat exchanger is incorporated i.e. the capillary tube is insulated together with suction line of the compressor. So that the heat transfer occur between vapour refrigerant in the suction line and the liquid refrigerant in the capillary tube, so that some precooled liquid refrigerant can enter in to evaporator which is more efficient than regular refrigeration system. This change in temperature of liquid refrigerant entering in to evaporator will increase the coefficient performance of the system. ABSTRACT The main objective in present dissertation has been focused on alternative refrigerant to conventional CFC refrigerant, CFC like R12, R22, R134a, etc… are not eco friendly. The emission of these refrigerants causes the depletion of ozone layer etc…. Hence to avoid above difficulty the alternative of refrigerant in the form of R600a has been choosing. R600a refrigerant are natural refrigerant consist of hydrocarbon. In the present work, the performance of the domestic refrigerator is determined using R600a (Isobutane) and comparison with R134a (Tetrafluoro-ethane) as the part of project work the refrigerator setup consists of evaporator, compressor, condenser and expansion valve are chosen with suitable specification. Also in the present work an attempt has been made to improve the coieffiecnt of performance (cop) of the system, by incorporating a heat exchanger before admitting refrigerant into the compressor. Thus the compressor work reduces and it may results increase the performance of the refrigeration system. KEYWORDS :Heat exchanger, coieffiecnt of performance, Isobutane, depletion of ozone, alternative refrigerants.
  • 2. Improving and Comparing The Coefficient… www.ijceronline.com Open Access Journal Page 2 1.3 objective of the work 1. Determining the actual coefficient of performance of domestic refrigerator using refrigerants R-134a and R-600a. 2. Comparison the coefficient of performance of domestic refrigerators between refrigerants using R-134a and R-600a. 3. Experiments increasing coefficient of performance of vapour compression refrigeration system by incorporating heat exchanger. 4. Comparison the coefficient of performance of domestic refrigerators between refrigerants using R-134a and R-600a after incorporating heat exchanger. II. EXPERIMENTAL SETUP AND DESIGN DETAILS Different experimental and theoretical comparison is performed by many researchers to evaluate the performance of domestic refrigerator by using different refrigerants. In this experimental R-600a is compared with the R-134a in a domestic refrigeration system. To perform the experiment 165L refrigerator is selected which was designed to work with R-134a.it is consists of an evaporator, air cooled condenser, reciprocating compressor. Heat exchanger incorporating in system, capillary tube rounded on the entire suction line of system. By the process rounding of capillary to the suction line we reduce that external type of heat exchanger. Figure.1 Fabrication of Refrigeration Tutor before Heat Exchanger Incorporation Figure.2 Fabrication of Refrigeration Tutor after Heat Exchanger Incorporation III. EXPERIMENTAL PROCEDURE While coming experiment two types of refrigerant using in the refrigerator R134a & R600a ,Putting the freezer regulator at top position so that no need of cut-off easily taken for system..Take down which refrigerant is in application. Take down the energy meter reading no of seconds for 5 revolution of energy meter Take down the reading of compressor pressure discharge inlet & condenser outlet from the pressure gauges. Take down the temperature readings of compressor suction line, discharge temperature, temperature of evaporator and condenser outlet temperature of system. Calculate coefficient of performance & energy consumption. And the experiment is repeated for other refrigerant and the readings are tabulated in the tabular column.
  • 3. Improving and Comparing The Coefficient… www.ijceronline.com Open Access Journal Page 3 IV. RESULTS AND DISCUSSION Table reading taken from the experimental procedure of R134a refrigerant placed in the experimental setup. Note the reading of compressor inlet, compressor outlet condenser outlet, evaporator temperature pressure & of various parameters in the setup. Table.1 Reading of R134a Refrigerant without Heat Exchanger Operating freezer point N (rev/sec) T1 °c T2 °c T3 °c P1 (bar) P2 (bar) P3 (bar) C.O.P 1 2 3 4 61:07 61:12 60:00 59:00 -3.7 -5.9 -9.3 -11 53 56.9 57.5 60 40 42 44 46 0.68 0.62 0.55 0.55 9.6 10.34 11.72 11.72 9.31 9.65 11.03 11.03 4.22 4.20 4.16 3.81 Table .2 Reading of R134a Refrigerant with Heat Exchanger Operating freezer point N (rev/sec) T1 °c T2 °c T3 °c P1 (bar) P2 (bar) P3 (bar) C.O.P 1 2 3 4 5 6 7 46:10 49:18 50:30 49:29 51:20 53:12 52 -7.9 -7.9 -9.6 -12 -15 -17.8 -19 54.8 54.9 55.6 57 58.5 59.2 60.1 44.3 42.3 41.6 42.6 43 43.1 43.1 0.68 0.55 0.58 0.58 0.37 0.344 0.310 17.24 15.51 15.72 15.86 15.17 15.17 14.48 16.55 14.62 15.03 15.17 14.48 14.48 14.13 4.55 4.44 4.30 3.9 3.87 3.64 3.40 Table reading taken from the experimental procedure of R600a refrigerant placed in the experimental setup. Note down reading as per procedure placed. Table .3 Reading for R600a without Heat Exchanger Operating freezer point N (rev/sec) T1 °c T2 °c T3 °c P1 (bar) P2 (bar) P3 (bar) C.O.P 1 2 3 4 5 6 7 54 55 54 57 60 57 60 -10.6 -11.6 -12.2 -14.1 -16.8 -17.7 -18.3 55.9 57.4 56.8 57.2 58.4 59.3 60 45.2 45.1 43.9 43 44 43.8 44.3 0.14 0.13 0.14 0.07 0.08 0.07 0.08 9.2 8.9 9.1 8.06 8.34 8 7.92 8.21 8.12 7.94 7.79 7.94 7.35 7.24 5.76 4.12 4.76 3.9 3.8 3.7 4.08 Table .4 Reading for R600a Refrigerant with Heat Exchanger Operating freezer point N (rev/sec) T1 °c T2 °c T3 °c P1 (bar) P2 (bar) P3 (bar) C.O.P 1 2 3 4 5 6 7 55:10 55:10 56:60 56:10 60:20 60:09 60:05 -11.6 -11.9 -12.9 -14.6 -17.6 -19.2 -19.6 51.9 51.7 52.3 53.6 53.7 53.3 53.5 41.3 39.4 41.7 39.6 38 39.2 38.6 0.13 0.13 0.14 0.06 0.06 0.07 0.06 8.2 8.4 8.2 8.06 7.93 7.44 7.33 7.93 7.93 7.91 7.79 7.58 7.24 7.17 5.2 5.19 5.21 4.15 3.6 4.01 4.06
  • 4. Improving and Comparing The Coefficient… www.ijceronline.com Open Access Journal Page 4 Figure .3 Shows R600a refrigerant Evaporator point Vs C.O.P Colour Represent in graph Green colour : refrigerant with H.E Red colour : refrigerant without H.E Figure .4 Shows R134a refrigerant Evaporator point Vs C.O.P Figure .5 Represent R600a evaporator Temp Vs Discharge Temp
  • 5. Improving and Comparing The Coefficient… www.ijceronline.com Open Access Journal Page 5 Figure .6 Represent R134a evaporator Temp Vs Discharge Temp V. CONCLUSIONS An experiment is conducted on domestic refrigerator by with & without incorporating heat exchanger in the system by using various refrigerants in the fabrication system and their coefficient of performance & energy consumption of the system is calculated.  Refrigerator carried out using without & with heat exchanger of refrigerant R134a & R600a in system, in which coefficient of performance of refrigerator 0.95 increased by using heat exchanger.  In the same way the discharge temperature of compressor is decreased with 10% by using heat exchanger , energy consumption refrigerator gradually increased with 3% of compared to normal domestic refrigerator. REFERENCES [1] R. Yajima et al., 1994, "The Performance Evaluation of HFC Alternative Refrigerants for HCFC-22", IIR Joint meeting, CFCs The Day After, Padova [2] K. Furuhama et al., 1994, "Performance Evaluation of Residential Air Conditioner with HFC32/125 Mixture, The International Symposium HCFC Alternative Refrigerants, Kobe [3] E. Johnson, Global warming from HFC, Environ. Impact Assessment Rev. 18 (1998) 485–492. [4] M.A. Hammad, M.A. Alsaad, The use of hydrocarbon mixtures as refrigerants in domestic refrigerators, Applied Thermal Engineering 19 (1999) 1181–1189. [5] Douglas J D, Braun J E, Groll E A and Tree D R (1999), “A Cost Method Comparing Alternative Refrigerant Applied to R-22 System”, International Journal of Refrigeration, Vol. 22, pp. 107-125. [6] B. O. Bolaji, Experimental study of R152a and R32 to replace R134a in a domestic refrigerator, Energy 35 (2010) 3793–3798.