PERFORMANCE ANALYSIS OF THREE PHASE SHUNT HYBRID
ACTIVE POWER FILTER
Sangamesh Bukka1
, Mohammad Yunus M Hakim2
, Sanjeev T.M3
, S. G. Ankaliki4
1
PG Scholar, Electrical & Electronics, SDMCET Dharwad, Karnataka, India
2
PG Scholar, Electrical & Electronics, SDMCET Dharwad, Karnataka, India
3
PG Scholar, Electrical & Electronics, SDMCET Dharwad, Karnataka, India
4
Professor, Electrical & Electronics, SDMCET Dharwad, Karnataka, India
Abstract
Active filtering of electric power has now become a mature technology for harmonic and reactive power Compensation in AC
networks. The past several years have seen a rapid increase of power electronics-based loads connected to low and medium voltage
power distribution systems. These loads draw non-sinusoidal current from the mains, degrading the power quality by causing
harmonic distortion. This paper proposes a three phase Shunt Hybrid Active Filter (SHAF) topology for harmonic reduction and
power factor improvement in low voltage power distribution systems. The compensation current reference for the proposed SHAF
topology is obtained by using synchronous reference frame theorem. This theorem simplifies the equations for the current reference
estimation in d-q co-ordinates thus leading to a more efficient and fast computation. To generate the compensation current that
follows the current reference, the hysteresis current control method is adopted for 2-level VSI in low voltage system, the system is
verified by developing simulation model using MATLAB/Simulink simulation package and the results are presented. The performance
of shunt active filter and the proposed shunt hybrid active filter topology in reducing total harmonic distortion (THD) is compared for
low voltage distribution system.
Keywords: SAPF, SHPF, PI control, THD, Hysteresis current pulse width modulation, D-Q reference frame theory.
----------------------------------------------------------------------***------------------------------------------------------------------------
1. INTRODUCTION
In recent years, with the increasing use of adjustable speed
drives, arc furnace, controlled and uncontrolled rectifiers and
other nonlinear loads, the power distribution system is
polluted with harmonics. Such harmonics not only create more
voltage and current stress but also are responsible for
Electromagnetic interference, more losses, capacitor failure
due to overloading, harmonic resonance, etc. Introduction of
strict legislation such as IEEE519 [2] limits the maximum
amount of harmonics (THD-Total Harmonic Distortion) that a
supply system can tolerate for a particular type of load.
Therefore, use of active or passive type filters is essential. To
solve the current harmonic related problems, passive filters
connected in several circuit configurations present a low cost
solution. However passive filter implementations to filter out
the current harmonics have the following disadvantages:
• Possibility of resonances with the source
Impedance
• Supply impedance dependent system performance
• Fixed compensation
In order to diminish the preceding disadvantages of the
passive filters, active power filters (APF) have been worked
on and developed in recent years. Elimination of the current
harmonics, reactive power compensation and voltage
regulation are the main functions of active filters for the
improvement of power quality. APFs have a number of
advantages over the passive filters. First of all, they can
suppress not only the supply current harmonics, but also the
reactive currents. Moreover, unlike passive filters, they do not
cause harmful resonances with the power distribution systems.
Consequently, the APF performances are independent of the
power distribution system properties [8]. On the other hand,
APFs have some drawbacks. APF necessitates fast switching
of high currents in the power circuit resulting high frequency
noise that may cause an electromagnetic interference (EMI) in
the power distribution systems [5]. Akagi, H. [1] proposed the
classification of active filters based on their objectives, system
configuration, power circuits and control strategy. APF can be
mainly connected in three circuit configurations, namely shunt
APF, series APF and hybrid APF. Shunt hybrid active power
filter consisting of shunt active power filter and shunt tuned
passive filter connected to the terminals of SAPF at PCC as
shown in Fig. 1.0(a).
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 257
Fig -1: Basic Shunt Hybrid Power Filter
In this proposed work, the function of the Shunt hybrid APF
thus can be divided into two parts: the Tuned passive filter (for
5th & 7th harmonic reduction) and Shunt active filter for
overall harmonic elimination. Hybrid APFs, inheriting the
advantages of both passive filters and APFs provide improved
performance and cost-effective solution. The idea behind this
scheme is to simultaneously reduce the switching noise and
electromagnetic interference.
2. OPERATION PRINCIPLE OF THE PROPOSED
SHUNT HYBRID APF TOPOLOGY
The operation principle of the proposed shunt hybrid APF
topology is illustrated in Fig. 2
Fig -2: Operation Principle of the Basic Shunt Hybrid Power
Filter
The operation principle of the proposed shunt hybrid APF
topology is illustrated in Fig. 2.1. It consists of a shunt active
filter and tuned passive filters (TPFs) connected in parallel
with the nonlinear load which is connected to ac source. The
two TPFs are designed to absorb 5th and 7th harmonic
currents with the principle of series resonance and SAF
compensates remaining harmonics. The SAF generates
compensation current (if) equal to harmonic load current (iLh)
but in opposite phase to it and injects in to the point of
common coupling (PCC) through an interfacing inductor.
Therefore source current (is) is desired to be sinusoidal and in
phase with the source voltage (Vs) to yield maximum power
factor. The SAF is a VSI and a capacitor connected on the DC
side acts as storage element.
3. MODELLING OF SHUNT HYBRID ACTIVE
POWER FILTER
The low voltage power distribution system of interest consists
of a three phase, 2000 V (r.m.s), 50 Hz sinusoidal AC voltage
source (Table 1). The source inductor is considered as Ls. A
full-bridge diode rectifier with R-L load is selected as the
nonlinear load as shown in Fig. 3.3; this interfacing inductor
provides isolation from the distribution line. A large
interfacing inductor is preferable because it results in small
switching ripple. However, the large interfacing inductor
limits the dynamic response of the compensation current.
Therefore, there is a compromise involved in sizing the
interfacing inductor. This VSI uses DC-bus capacitor (Cdc) as
the supply source and switches at high-frequency to generate a
compensation current that follows the estimated reference
current. Therefore the voltage across the DC-bus capacitor
(Vdc) must be maintained at a constant value that is higher
than the amplitude of the source voltage
Fig-3.1 Simulation model of 3Ph shunt hybrid active filter
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 258
Table 1- System Specification [11]
Parameters name Numerical value
Source voltage Vs 2828 V , 50 Hz
(line r.m.s)
DC capacitors 4700 μF
D.C capacitor reference
Voltage
400V
Sampling Time 5e-5
Diode rectifier Non- linear
Load resistance and
Inductance
20 Ω, 0.1 mH
Filter inductance, resistance
and capacitor
2mH, 0.1 ohm and
100 μF
Source resistance and
inductance
1mH, 0.1 ohm
The objective the control strategy of the proposed three-phase
shunt hybrid active filter is to produce appropriate gating
signals for the switching transistors of VSI. The Overall
control system consists of synchronous reference frame
theorem based compensation current estimator, hysteresis
current controller for gate signal generation and PI controller
to maintain the DC bus voltage constant as shown fig below.
Fig-3.2 Overall control block subsystem
3.1. Compensation Current Reference Estimation
using d-q-0 Theory
In this control strategy three phase load currents are sensed
and transformed from a-b-c reference frame to d-q coordinates
which are DC components using park’s transformation.
Passing these d-q components of load currents through low
pass filter, the low frequency fundamental components only
will be passed through and harmonic component is stopped.
By subtracting fundamental component from non-filtered
signal will result in harmonic component in load current.
Control signal from PI controller is added to this signal to
obtain the reference compensating signal in d-q reference
frame. By transforming these components in d-q reference to
a-b-c reference frame using inverse Park’s transformation, the
information about harmonic current component in a-b-c
reference frame is obtained. As shown in fig.3.1.1 [6].
Fig 3.1.1 Current Reference Estimation Using d-q-0 Theory
Suppose the three phase source currents are Isa, Isb, Isc, the
nonlinear load currents are ILa, ILb, ILc and active filter
compensating currents are Ifa, Ifb, Ifc for phases A, B, C
respectively. The load currents in a-b-c synchronous reference
frame components can be converted in to d-q reference frame
components using Park‟s transformation as shown in equation
(3.11).
These currents can be decomposed into fundamental and
harmonic components as shown in equations (3.12).
Id =Iddc + Idh, Iq = Iqdc + Iqh (3.12).
The fundamental component of load current will appear as DC
quantity in d-q reference frame. Therefore Iddc = Id1 and Iqdc
= Iq1. The harmonic component of load current is obtained by
subtracting high frequency harmonic current signal from total
load current.
Idh = IL-LPF ( Id), Iqh = IL-LPF(Iq) (3.13)
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 259
These reference currents are transformed into a-b-c
coordinates by applying Inverse Park‟s transformation to
obtain reference currents in a-b-c coordinates
These reference currents are applied to hysteresis current
controller which produces required gating pulses to switching
devices of VSI. Since it deals with mainly DC quantities and
computation is instantaneous this theory is considered in this
work for estimating reference compensating current
3.2. Hysteresis Current Control for Switching Signal
Generation
In this thesis Hysteresis band Current Controller model is used
for generating switching signals for the transistors of VSI, and
is illustrated in Fig. 3.2.1.This current control technique
imposes a bang-bang type instantaneous control that forces the
compensation current to follow its estimated reference. The
actual compensation current is subtracted from its estimated
reference. The resulting error is sent through a hysteresis
controller to determine the appropriate gating signals. In the
simulation model, the hysteresis band (H) is chosen as 0.1 A
with 0.05 as upper limit and -0.05 as lower limit.
Fig.3.2.1 Simulink model of Hysteresis current controller
3.3. DC Bus Voltage control by using PI controller
For maintaining DC bus voltage constant at a reference value,
Proportional and Integral (PI) Controller is employed in this
simulation work as shown in fig 3.3.1. In this control process
the dc bus voltage of the active filter is used as feedback
signals to PI controller. The reference dc capacitor voltage
(4700v) is compared with actual capacitor voltage and the
error is given to the PI controller [5][10]. The output of the PI
controller provides the reference in-phase components
Fig 3.3.1 PI controller subsystem
3.4. Tuned Passive Filter
The proposed shunt hybrid active power filter consists of
tuned passive filters connected in parallel with the load to
absorb specified harmonic currents. The common types of
passive harmonic filters include single tuned, double tuned
and high pass filters. However for simplicity single tuned
filters are considered in this work. The basic shunt passive
filtering principle is to trap harmonic currents in LC circuits,
tuned up to the harmonic filtering frequency, and to eliminate
from power system. A single tuned 1st order filter
configuration consists of RLC elements in series as shown in
Fig.3.4. In single-tuned passive filter, the reactance of inductor
is equal to that of capacitor at resonant frequency fn. The
relationship among L, C, R, Q values are given in
Eqn.(3.4)[4].
Cn = 1/Ln(2πfn)2
, Rn=Ln(2 πfn)/Q, Q=Rn√(Cn/Ln) .(3.4)
Where fn=frequency of harmonic component, n=order of
harmonic, Q=Quality factor, Rn=Resistance of nth harmonic
filter, Ln=inductance of nth harmonic filter. In the proposed
hybrid filter the shunt passive filters are tuned to absorb 5th
and 7th harmonic currents and other higher order harmonics
are to be suppressed by SAF. Hence burden on SAF is reduced
resulting in reduced rating of SAF and effective filtering of
higher order harmonics. Therefore source needs to supply only
fundamental component of load current
Fig-3.4 Tuned passive filter
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 260
For 5th
harmonic filter the resonance frequency is 250Hz and
for 7th
harmonic it is 350Hz. Quality factor of the filter is
selected as 75[4] and the filter capacitance value is fixed at
30μF.
4. RESULTS
4.1. LV Test System without any Compensation:
The results of simulation for LV test system (Configuration
shown in appendix) are shown in Fig. 4.1. including three
phase load current waveforms, three phase source current
waveforms and Phase angle comparison between source
voltage and source current waveforms without any type of
compensation, As Shown the current waveforms are more
distorted (i.e. not pure sinusoidal) due to presence of non
linear load.
Fig-4.1.1 Load current
Fig-4.1.2 Source current
Fig-4.1.3 Phase angle comparison between source voltage and
source current for phase-A
Fig-4.1.4 Harmonic spectrum of phase-a load current of
LV test system without any compensation
The THD is the most common indicator to determine the
quality of AC waveforms. Using the Fast Fourier Transform
(FFT), the harmonic spectrum of the source current under
different compensation conditions is presented. Then, the
THD comparison is carried out for the simulation results and
from the spectra plot, it can be seen that the source current
contains large amount of harmonic current components (5th &
7th components are higher magnitude i.e 11 and 7 respectively
as shown in fig 4.1.4) of frequencies below 1 kHz and the
THD is 12.4% (According to IEEE-519 standards the THD
limits on the magnitude of harmonic current frequencies
should be within 5% [1][2]).
4.2. LV Test System with Shunt Active Filter
The three phase SAF compensating currents and source
currents of the test system with SAF compensation are shown
in Fig. 4.2. It is seen that due to SAF compensating currents
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 261
the source currents attained near sinusoidal form. Source
voltage and source currents are in-phase as shown in fig 4.2.3
for phase a
Fig- 4.2.1 3-phase source currents and voltages of SAPF
Fig-4.2.2 Three phase SAPF compensation currents
Fig-4.2.3 Source voltage and source current for phase–a
Fig-4.2.4 Harmonic spectrum of phase-a source current of
LV test system with SAPF compensation
From Fig.4.2.4 it is seen that the basic shunt APF successfully
filters the harmonic current components caused by the
nonlinear load. This is evident by the reduction of source
current THD from 12.4% to nearly 2.11%, but still there are
some low order harmonics (5th and 7th harmonic components
of magnitude 1.7% and 0.6% respectively) present in the
source current harmonic spectrum.
4.3. LV Test System with Proposed SHAF
Compensation
Fig. 4.3.1 shows the simulation results for three phase source
current and voltages of test system model with the proposed
Shunt Hybrid Active Filter (SHAF) compensation. When
SHAF is applied, the injected compensation current (if) forces
the source current (is) to become near sinusoidal waveform
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 262
and in phase with the source voltage waveform, resulting in
nearly unity power factor.
Fig- 4.3.1 Three phase source currents and voltages of SHPF
Fig. 4.3.2 shows the harmonic spectrum of the source current
with the proposed SHAF compensation. It is seen that the
THD is reduced to 0.98%. In comparison to Fig.4.2.4, the
source current harmonic spectrum is almost free of harmonic
components. This implies that the proposed SHAF
compensates the distorted source currents including dominant
5th and 7th order harmonic (Reduced to 0.25% and 0.05%
respectively).
Fig-4.3.2 Harmonic spectrum of phase-a source current of LV
test system with SHPF compensation
5. CONCLUSIONS
This Paper presented the results obtained from the simulations
of SHAF compensated LV test system. Simulations were
conducted aiming to illustrate the effectiveness of the
proposed shunt hybrid APF in harmonic mitigation in LV test
system. The effectiveness of d-q theory in estimating
compensation reference current is demonstrated. In addition,
the effectiveness of PI controller in maintaining DC bus
voltage is discussed. The simulation results are analyzed and
discussed. Finally, a detailed THD analysis on source current
spectrums is carried out to validate the harmonic filtering
performance of the proposed SHAPF topology in comparison
to the basic SAPF compensation in LV system. The source
current THD is reduced from 12.4 % to 2.11 % with basic
shunt APF. With the proposed SHAF, the source current THD
is further reduced to 0.98 %. Thus, the harmonic filtering
performance of the proposed SHAF topology is superior
compared to the basic shunt APF and which is well below the
harmonic limit imposed by IEEE Standard- 519(i.e. THD
within 5%)
REFERENCES
[1]. H. Akagi, “New Trends in Active Filters for Power
Conditioning. IEEE Trans. on Industry Applications”, 32(6),
1996, pp.1312-1322
[2]. B. Singh, K. Al-Haddad and A.Chandra, “A Review of
Active Filters for Power Quality Improvement, IEEE Trans.
on Industrial Electronics”, 46(5), 1999, pp. 960-971
[3]. L. Chen and A. Jouanne, “A Comparison and Assessment
of Hybrid Filter Topologies and Control Algorithms”,
Proceedings of The IEEE Power Electronics Specialists
Conference (PESC), June 17-21, 2001, Vancouver, Canada:
IEEE Trans. 2001, Pp. 565-570
[4]. D. A. Gonzalez, and J. C. McCall, “Design of Filters to
Reduce Harmonic Distortion in Industrial Power Systems”,
IEEE Trans. on Industry Applications, IA-23, 1987.
[5]. Vikas Anand, Dr.S.Srivastava “Performance Investigation
Of Shunt Active Power Filter Using Hysteresis Current
Control Method” International Journal Of Engineering
Research & Technology (IJERT) Vol. 1 Issue 4, June - 2012
Issn: 2278-0181
[6]. Hongyu Li., Fang Zhuo, Zhaoan Wang, Lei W. and Wu
L., “A novel time domain current detection algorihm for shunt
active power filters” IEEE Trans. power systems, vol.20,
(2005):pp. 644–651.
[7]. Sebasthi Rani, K., Porkumaran, K. Performance
Evaluation of PI and Fuzzy controller based Shunt
ActivePower Filter” European Journal of Scientific Research,
ISSN 1450-216X,Vol.61,No.3(2011).
[8]. “Evaluation Of Reference Signal Estimation Techniques
For The Control Of Shunt Active Power Filter” By Norani Bt
Atan, Bahisham Bte Yunus At Proceedings Of ICEE 2009 3rd
International Conference On Energy And Environment
,December 2009, Mala, Malaysia.
[9]. Elsa Susan Daniel and G.Abirami “Selective Harmonic
Elimination Using Shunt Hybrid Active Power Filters
Operating At Different Switching Frequencies” International
Journal of Innovative Research In Electrical & Electronics,
Instrumentation And Control Engineering Vol. 1, Issue 1,
April 2013.
[10]. T.Mahalekshmi “Current Harmonic Compensation and
Power Factor Improvement by Hybrid Shunt Active Power
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 263
Filter” International Journal of Computer Applications (0975 –
8887) Volume 4 – No.3, July 2010.
[11]. G. Jayakrishna, K.S.R. Anjaneyulu., “Fuzzy Logic
Control based Three Phase Shunt Active Filter for Voltage
Regulation and Harmonic Reduction”, International Journal of
Computer Applications (ISSN 0975-8887), Vol. 10, No.5,
Nov. 2010, pp.13-19.
BIOGRAPHIES
Sangamesh, PG Scholar of EEE Dept, SDMCET
Dharwad. He has done his B.E in Electrical
Engineering from DSCE Bangalore in 2011 and
he is Currently pursuing his M.Tech in Power
System
MohammadYunus M Hakim , PG Scholar of
EEE Dept, SDMCET Dharwad. He has done his
B.E in Electrical Engineering from BLDEA’s
Engg college,Bijapur in 2012 and he is Currently
pursuing his M.Tech in Power System.
Sanjeev Kumar T.M , PG Scholar of EEE Dept,
SDMCET Dharwad. He has done his B.E in
Electrical Engineering from STJIT’s Engg college,
Ranibennur in 2012 and he is Currently pursuing
his M.Tech in Power System.
Dr. Shekhappa. G. Ankaliki obtained his B.E
(E&EE), M. Tech. (Power System) from Mysore
University and Ph.D. from Visvesvaraya
Technological University, Belgaum, Karnataka,
INDIA respectively. He is a life member of
ISTE, ISWE and MIE. He is presently working in Electrical &
Electronics Engineering Department, SDM College of
Engineering & Technology, Dhavalagiri, Dharwad-580 002,
INDIA as a Professor and PG Coordinator. His research
interest includes AI application to Power Systems, Smart
Grid/Micro grids, SCADA and DSCADA, Energy Audit,
Energy Management and Demand Side Management. He has
published 26 papers in International Journals and 28 papers in
National and International Conference Proceedings.

Más contenido relacionado

La actualidad más candente

Paper id 2520147
Paper id 2520147Paper id 2520147
Paper id 2520147
IJRAT
 
Pll based shunt active harmonic filter to compensate multiple non linear loads
Pll based shunt active harmonic filter to compensate multiple non linear loadsPll based shunt active harmonic filter to compensate multiple non linear loads
Pll based shunt active harmonic filter to compensate multiple non linear loads
IAEME Publication
 
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
eSAT Journals
 
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
IJERA Editor
 
Enhancement of upfc performance with matrix converter using advanced direct p...
Enhancement of upfc performance with matrix converter using advanced direct p...Enhancement of upfc performance with matrix converter using advanced direct p...
Enhancement of upfc performance with matrix converter using advanced direct p...
eSAT Journals
 

La actualidad más candente (20)

Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
 
Enhancement for Power Quality in Distribution Side Using Custom Power Devices
Enhancement for Power Quality in Distribution Side Using Custom Power DevicesEnhancement for Power Quality in Distribution Side Using Custom Power Devices
Enhancement for Power Quality in Distribution Side Using Custom Power Devices
 
Distributed Power-Flow Controller (DPFC) Simulation
Distributed Power-Flow Controller (DPFC) SimulationDistributed Power-Flow Controller (DPFC) Simulation
Distributed Power-Flow Controller (DPFC) Simulation
 
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
 
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
 
Paper id 2520147
Paper id 2520147Paper id 2520147
Paper id 2520147
 
Power Quality Improvement of DC Drive by Reduction of Circulating Current
Power Quality Improvement of DC Drive by Reduction of Circulating CurrentPower Quality Improvement of DC Drive by Reduction of Circulating Current
Power Quality Improvement of DC Drive by Reduction of Circulating Current
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
 
Pll based shunt active harmonic filter to compensate multiple non linear loads
Pll based shunt active harmonic filter to compensate multiple non linear loadsPll based shunt active harmonic filter to compensate multiple non linear loads
Pll based shunt active harmonic filter to compensate multiple non linear loads
 
Enhancement of Power Quality by an Application FACTS Devices
Enhancement of Power Quality by an Application FACTS DevicesEnhancement of Power Quality by an Application FACTS Devices
Enhancement of Power Quality by an Application FACTS Devices
 
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
 
Analysis of dc capacitor voltage balance method for h bridge inverter based p...
Analysis of dc capacitor voltage balance method for h bridge inverter based p...Analysis of dc capacitor voltage balance method for h bridge inverter based p...
Analysis of dc capacitor voltage balance method for h bridge inverter based p...
 
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
 
Sensitivity based optimal location of tcsc for improvement of power system se...
Sensitivity based optimal location of tcsc for improvement of power system se...Sensitivity based optimal location of tcsc for improvement of power system se...
Sensitivity based optimal location of tcsc for improvement of power system se...
 
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
 
Analysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load inAnalysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load in
 
Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...
 
Ae4301167171
Ae4301167171Ae4301167171
Ae4301167171
 
Enhancement of upfc performance with matrix converter using advanced direct p...
Enhancement of upfc performance with matrix converter using advanced direct p...Enhancement of upfc performance with matrix converter using advanced direct p...
Enhancement of upfc performance with matrix converter using advanced direct p...
 

Destacado

Parallel k nn on gpu architecture using opencl
Parallel k nn on gpu architecture using openclParallel k nn on gpu architecture using opencl
Parallel k nn on gpu architecture using opencl
eSAT Publishing House
 
Dynamic thresholding on speech segmentation
Dynamic thresholding on speech segmentationDynamic thresholding on speech segmentation
Dynamic thresholding on speech segmentation
eSAT Publishing House
 

Destacado (20)

Design of shunt active power filter to mitigate harmonic
Design of shunt active power filter to mitigate harmonicDesign of shunt active power filter to mitigate harmonic
Design of shunt active power filter to mitigate harmonic
 
Active Power Filter
Active Power FilterActive Power Filter
Active Power Filter
 
Analytical study and implementation of digital excitation system for diesel g...
Analytical study and implementation of digital excitation system for diesel g...Analytical study and implementation of digital excitation system for diesel g...
Analytical study and implementation of digital excitation system for diesel g...
 
Parallel k nn on gpu architecture using opencl
Parallel k nn on gpu architecture using openclParallel k nn on gpu architecture using opencl
Parallel k nn on gpu architecture using opencl
 
“Development and performance analysis of a multi evaporating system”
“Development and performance analysis of a multi evaporating system”“Development and performance analysis of a multi evaporating system”
“Development and performance analysis of a multi evaporating system”
 
Dynamic thresholding on speech segmentation
Dynamic thresholding on speech segmentationDynamic thresholding on speech segmentation
Dynamic thresholding on speech segmentation
 
Experimental investigations of diesel engine using fish oil biodiesel and its...
Experimental investigations of diesel engine using fish oil biodiesel and its...Experimental investigations of diesel engine using fish oil biodiesel and its...
Experimental investigations of diesel engine using fish oil biodiesel and its...
 
A model for performance testing of ajax based web applications
A model for performance testing of ajax based web applicationsA model for performance testing of ajax based web applications
A model for performance testing of ajax based web applications
 
Surface morphology of mg f2yf3 multi layer thin films
Surface morphology of mg f2yf3 multi layer thin filmsSurface morphology of mg f2yf3 multi layer thin films
Surface morphology of mg f2yf3 multi layer thin films
 
Impact assessment of factors affecting information technology projects in riv...
Impact assessment of factors affecting information technology projects in riv...Impact assessment of factors affecting information technology projects in riv...
Impact assessment of factors affecting information technology projects in riv...
 
Analysis of economic load dispatch using fuzzified pso
Analysis of economic load dispatch using fuzzified psoAnalysis of economic load dispatch using fuzzified pso
Analysis of economic load dispatch using fuzzified pso
 
A detection technique of signal in mimo system
A detection technique of signal in mimo systemA detection technique of signal in mimo system
A detection technique of signal in mimo system
 
Spatio temporal modeling of snow flake crystals using packard’s cellular auto...
Spatio temporal modeling of snow flake crystals using packard’s cellular auto...Spatio temporal modeling of snow flake crystals using packard’s cellular auto...
Spatio temporal modeling of snow flake crystals using packard’s cellular auto...
 
Design and development of high frequency resonant transition converter
Design and development of high frequency resonant transition converterDesign and development of high frequency resonant transition converter
Design and development of high frequency resonant transition converter
 
Mhd effects on non newtonian micro polar fluid with
Mhd effects on non newtonian micro polar fluid withMhd effects on non newtonian micro polar fluid with
Mhd effects on non newtonian micro polar fluid with
 
Software testing effort estimation with cobb douglas function a practical app...
Software testing effort estimation with cobb douglas function a practical app...Software testing effort estimation with cobb douglas function a practical app...
Software testing effort estimation with cobb douglas function a practical app...
 
Agile software development and challenges
Agile software development and challengesAgile software development and challenges
Agile software development and challenges
 
Energy efficient task scheduling algorithms for cloud data centers
Energy efficient task scheduling algorithms for cloud data centersEnergy efficient task scheduling algorithms for cloud data centers
Energy efficient task scheduling algorithms for cloud data centers
 
Maintenance performance metrics for manufacturing industry
Maintenance performance metrics for manufacturing industryMaintenance performance metrics for manufacturing industry
Maintenance performance metrics for manufacturing industry
 
Distance protection of hvdc transmission line with novel fault location techn...
Distance protection of hvdc transmission line with novel fault location techn...Distance protection of hvdc transmission line with novel fault location techn...
Distance protection of hvdc transmission line with novel fault location techn...
 

Similar a Performance analysis of three phase shunt hybrid active power filter

Simulation and Performance Investigation of Unified Power Quality Conditioner...
Simulation and Performance Investigation of Unified Power Quality Conditioner...Simulation and Performance Investigation of Unified Power Quality Conditioner...
Simulation and Performance Investigation of Unified Power Quality Conditioner...
Dr. Sudhir Kumar Srivastava
 

Similar a Performance analysis of three phase shunt hybrid active power filter (20)

Pi controller based of multi level upqc using dq0 transformation to improve p...
Pi controller based of multi level upqc using dq0 transformation to improve p...Pi controller based of multi level upqc using dq0 transformation to improve p...
Pi controller based of multi level upqc using dq0 transformation to improve p...
 
Power system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filterPower system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filter
 
Design of Smart Filter for Cancellation of Current and Voltage Harmonics in T...
Design of Smart Filter for Cancellation of Current and Voltage Harmonics in T...Design of Smart Filter for Cancellation of Current and Voltage Harmonics in T...
Design of Smart Filter for Cancellation of Current and Voltage Harmonics in T...
 
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
 
A Review on Unified Power Quality Conditioner for 3P4W System
A Review on Unified Power Quality Conditioner for 3P4W SystemA Review on Unified Power Quality Conditioner for 3P4W System
A Review on Unified Power Quality Conditioner for 3P4W System
 
Design of Shunt Hybrid Active Power Filter to Reduce Harmonics on AC Side Due...
Design of Shunt Hybrid Active Power Filter to Reduce Harmonics on AC Side Due...Design of Shunt Hybrid Active Power Filter to Reduce Harmonics on AC Side Due...
Design of Shunt Hybrid Active Power Filter to Reduce Harmonics on AC Side Due...
 
A new fuzzy based control strategy for three phase shunt active power filters
A new fuzzy based control strategy for three phase shunt active power filtersA new fuzzy based control strategy for three phase shunt active power filters
A new fuzzy based control strategy for three phase shunt active power filters
 
Power quality improvement by series active power filter- a review
Power quality improvement by series active power filter- a reviewPower quality improvement by series active power filter- a review
Power quality improvement by series active power filter- a review
 
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQCIRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
 
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active FilterHarmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
 
Simulation and Performance Investigation of Unified Power Quality Conditioner...
Simulation and Performance Investigation of Unified Power Quality Conditioner...Simulation and Performance Investigation of Unified Power Quality Conditioner...
Simulation and Performance Investigation of Unified Power Quality Conditioner...
 
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQCIRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
 
Optimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi ControllerOptimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi Controller
 
Photovoltaic array fed inverter
Photovoltaic array fed inverterPhotovoltaic array fed inverter
Photovoltaic array fed inverter
 
Power quality improvement in a weak bus system using
Power quality improvement in a weak bus system usingPower quality improvement in a weak bus system using
Power quality improvement in a weak bus system using
 
Power System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterPower System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power Filter
 
Decomposition of current through active power filter for compensating harmoni...
Decomposition of current through active power filter for compensating harmoni...Decomposition of current through active power filter for compensating harmoni...
Decomposition of current through active power filter for compensating harmoni...
 
IRJET- Review: Active Power Filtering Techniques for Power System
IRJET- Review: Active Power Filtering Techniques for Power SystemIRJET- Review: Active Power Filtering Techniques for Power System
IRJET- Review: Active Power Filtering Techniques for Power System
 
IRJET- Power Quality Improvement using Active Power Filter
IRJET- Power Quality Improvement using Active Power FilterIRJET- Power Quality Improvement using Active Power Filter
IRJET- Power Quality Improvement using Active Power Filter
 
Power quality improvement in a weak bus system using facts controller
Power quality improvement in a weak bus system using facts controllerPower quality improvement in a weak bus system using facts controller
Power quality improvement in a weak bus system using facts controller
 

Más de eSAT Publishing House

Likely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnamLikely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnam
eSAT Publishing House
 
Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...
eSAT Publishing House
 
Hudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnamHudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnam
eSAT Publishing House
 
Groundwater investigation using geophysical methods a case study of pydibhim...
Groundwater investigation using geophysical methods  a case study of pydibhim...Groundwater investigation using geophysical methods  a case study of pydibhim...
Groundwater investigation using geophysical methods a case study of pydibhim...
eSAT Publishing House
 
Flood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, indiaFlood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, india
eSAT Publishing House
 
Enhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity buildingEnhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity building
eSAT Publishing House
 
Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...
eSAT Publishing House
 
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
eSAT Publishing House
 
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...
eSAT Publishing House
 
Shear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a reviewShear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a review
eSAT Publishing House
 
Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...
eSAT Publishing House
 
Risk analysis and environmental hazard management
Risk analysis and environmental hazard managementRisk analysis and environmental hazard management
Risk analysis and environmental hazard management
eSAT Publishing House
 
Review study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear wallsReview study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear walls
eSAT Publishing House
 
Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...
eSAT Publishing House
 
Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...
eSAT Publishing House
 
Coastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of indiaCoastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of india
eSAT Publishing House
 
Can fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structuresCan fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structures
eSAT Publishing House
 
Assessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildingsAssessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildings
eSAT Publishing House
 
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
eSAT Publishing House
 
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
eSAT Publishing House
 

Más de eSAT Publishing House (20)

Likely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnamLikely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnam
 
Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...
 
Hudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnamHudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnam
 
Groundwater investigation using geophysical methods a case study of pydibhim...
Groundwater investigation using geophysical methods  a case study of pydibhim...Groundwater investigation using geophysical methods  a case study of pydibhim...
Groundwater investigation using geophysical methods a case study of pydibhim...
 
Flood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, indiaFlood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, india
 
Enhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity buildingEnhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity building
 
Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...
 
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
 
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...
 
Shear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a reviewShear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a review
 
Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...
 
Risk analysis and environmental hazard management
Risk analysis and environmental hazard managementRisk analysis and environmental hazard management
Risk analysis and environmental hazard management
 
Review study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear wallsReview study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear walls
 
Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...
 
Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...
 
Coastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of indiaCoastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of india
 
Can fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structuresCan fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structures
 
Assessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildingsAssessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildings
 
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
 
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
 

Último

UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
rknatarajan
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Dr.Costas Sachpazis
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 

Último (20)

Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 

Performance analysis of three phase shunt hybrid active power filter

  • 1. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 256 PERFORMANCE ANALYSIS OF THREE PHASE SHUNT HYBRID ACTIVE POWER FILTER Sangamesh Bukka1 , Mohammad Yunus M Hakim2 , Sanjeev T.M3 , S. G. Ankaliki4 1 PG Scholar, Electrical & Electronics, SDMCET Dharwad, Karnataka, India 2 PG Scholar, Electrical & Electronics, SDMCET Dharwad, Karnataka, India 3 PG Scholar, Electrical & Electronics, SDMCET Dharwad, Karnataka, India 4 Professor, Electrical & Electronics, SDMCET Dharwad, Karnataka, India Abstract Active filtering of electric power has now become a mature technology for harmonic and reactive power Compensation in AC networks. The past several years have seen a rapid increase of power electronics-based loads connected to low and medium voltage power distribution systems. These loads draw non-sinusoidal current from the mains, degrading the power quality by causing harmonic distortion. This paper proposes a three phase Shunt Hybrid Active Filter (SHAF) topology for harmonic reduction and power factor improvement in low voltage power distribution systems. The compensation current reference for the proposed SHAF topology is obtained by using synchronous reference frame theorem. This theorem simplifies the equations for the current reference estimation in d-q co-ordinates thus leading to a more efficient and fast computation. To generate the compensation current that follows the current reference, the hysteresis current control method is adopted for 2-level VSI in low voltage system, the system is verified by developing simulation model using MATLAB/Simulink simulation package and the results are presented. The performance of shunt active filter and the proposed shunt hybrid active filter topology in reducing total harmonic distortion (THD) is compared for low voltage distribution system. Keywords: SAPF, SHPF, PI control, THD, Hysteresis current pulse width modulation, D-Q reference frame theory. ----------------------------------------------------------------------***------------------------------------------------------------------------ 1. INTRODUCTION In recent years, with the increasing use of adjustable speed drives, arc furnace, controlled and uncontrolled rectifiers and other nonlinear loads, the power distribution system is polluted with harmonics. Such harmonics not only create more voltage and current stress but also are responsible for Electromagnetic interference, more losses, capacitor failure due to overloading, harmonic resonance, etc. Introduction of strict legislation such as IEEE519 [2] limits the maximum amount of harmonics (THD-Total Harmonic Distortion) that a supply system can tolerate for a particular type of load. Therefore, use of active or passive type filters is essential. To solve the current harmonic related problems, passive filters connected in several circuit configurations present a low cost solution. However passive filter implementations to filter out the current harmonics have the following disadvantages: • Possibility of resonances with the source Impedance • Supply impedance dependent system performance • Fixed compensation In order to diminish the preceding disadvantages of the passive filters, active power filters (APF) have been worked on and developed in recent years. Elimination of the current harmonics, reactive power compensation and voltage regulation are the main functions of active filters for the improvement of power quality. APFs have a number of advantages over the passive filters. First of all, they can suppress not only the supply current harmonics, but also the reactive currents. Moreover, unlike passive filters, they do not cause harmful resonances with the power distribution systems. Consequently, the APF performances are independent of the power distribution system properties [8]. On the other hand, APFs have some drawbacks. APF necessitates fast switching of high currents in the power circuit resulting high frequency noise that may cause an electromagnetic interference (EMI) in the power distribution systems [5]. Akagi, H. [1] proposed the classification of active filters based on their objectives, system configuration, power circuits and control strategy. APF can be mainly connected in three circuit configurations, namely shunt APF, series APF and hybrid APF. Shunt hybrid active power filter consisting of shunt active power filter and shunt tuned passive filter connected to the terminals of SAPF at PCC as shown in Fig. 1.0(a).
  • 2. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 257 Fig -1: Basic Shunt Hybrid Power Filter In this proposed work, the function of the Shunt hybrid APF thus can be divided into two parts: the Tuned passive filter (for 5th & 7th harmonic reduction) and Shunt active filter for overall harmonic elimination. Hybrid APFs, inheriting the advantages of both passive filters and APFs provide improved performance and cost-effective solution. The idea behind this scheme is to simultaneously reduce the switching noise and electromagnetic interference. 2. OPERATION PRINCIPLE OF THE PROPOSED SHUNT HYBRID APF TOPOLOGY The operation principle of the proposed shunt hybrid APF topology is illustrated in Fig. 2 Fig -2: Operation Principle of the Basic Shunt Hybrid Power Filter The operation principle of the proposed shunt hybrid APF topology is illustrated in Fig. 2.1. It consists of a shunt active filter and tuned passive filters (TPFs) connected in parallel with the nonlinear load which is connected to ac source. The two TPFs are designed to absorb 5th and 7th harmonic currents with the principle of series resonance and SAF compensates remaining harmonics. The SAF generates compensation current (if) equal to harmonic load current (iLh) but in opposite phase to it and injects in to the point of common coupling (PCC) through an interfacing inductor. Therefore source current (is) is desired to be sinusoidal and in phase with the source voltage (Vs) to yield maximum power factor. The SAF is a VSI and a capacitor connected on the DC side acts as storage element. 3. MODELLING OF SHUNT HYBRID ACTIVE POWER FILTER The low voltage power distribution system of interest consists of a three phase, 2000 V (r.m.s), 50 Hz sinusoidal AC voltage source (Table 1). The source inductor is considered as Ls. A full-bridge diode rectifier with R-L load is selected as the nonlinear load as shown in Fig. 3.3; this interfacing inductor provides isolation from the distribution line. A large interfacing inductor is preferable because it results in small switching ripple. However, the large interfacing inductor limits the dynamic response of the compensation current. Therefore, there is a compromise involved in sizing the interfacing inductor. This VSI uses DC-bus capacitor (Cdc) as the supply source and switches at high-frequency to generate a compensation current that follows the estimated reference current. Therefore the voltage across the DC-bus capacitor (Vdc) must be maintained at a constant value that is higher than the amplitude of the source voltage Fig-3.1 Simulation model of 3Ph shunt hybrid active filter
  • 3. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 258 Table 1- System Specification [11] Parameters name Numerical value Source voltage Vs 2828 V , 50 Hz (line r.m.s) DC capacitors 4700 μF D.C capacitor reference Voltage 400V Sampling Time 5e-5 Diode rectifier Non- linear Load resistance and Inductance 20 Ω, 0.1 mH Filter inductance, resistance and capacitor 2mH, 0.1 ohm and 100 μF Source resistance and inductance 1mH, 0.1 ohm The objective the control strategy of the proposed three-phase shunt hybrid active filter is to produce appropriate gating signals for the switching transistors of VSI. The Overall control system consists of synchronous reference frame theorem based compensation current estimator, hysteresis current controller for gate signal generation and PI controller to maintain the DC bus voltage constant as shown fig below. Fig-3.2 Overall control block subsystem 3.1. Compensation Current Reference Estimation using d-q-0 Theory In this control strategy three phase load currents are sensed and transformed from a-b-c reference frame to d-q coordinates which are DC components using park’s transformation. Passing these d-q components of load currents through low pass filter, the low frequency fundamental components only will be passed through and harmonic component is stopped. By subtracting fundamental component from non-filtered signal will result in harmonic component in load current. Control signal from PI controller is added to this signal to obtain the reference compensating signal in d-q reference frame. By transforming these components in d-q reference to a-b-c reference frame using inverse Park’s transformation, the information about harmonic current component in a-b-c reference frame is obtained. As shown in fig.3.1.1 [6]. Fig 3.1.1 Current Reference Estimation Using d-q-0 Theory Suppose the three phase source currents are Isa, Isb, Isc, the nonlinear load currents are ILa, ILb, ILc and active filter compensating currents are Ifa, Ifb, Ifc for phases A, B, C respectively. The load currents in a-b-c synchronous reference frame components can be converted in to d-q reference frame components using Park‟s transformation as shown in equation (3.11). These currents can be decomposed into fundamental and harmonic components as shown in equations (3.12). Id =Iddc + Idh, Iq = Iqdc + Iqh (3.12). The fundamental component of load current will appear as DC quantity in d-q reference frame. Therefore Iddc = Id1 and Iqdc = Iq1. The harmonic component of load current is obtained by subtracting high frequency harmonic current signal from total load current. Idh = IL-LPF ( Id), Iqh = IL-LPF(Iq) (3.13)
  • 4. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 259 These reference currents are transformed into a-b-c coordinates by applying Inverse Park‟s transformation to obtain reference currents in a-b-c coordinates These reference currents are applied to hysteresis current controller which produces required gating pulses to switching devices of VSI. Since it deals with mainly DC quantities and computation is instantaneous this theory is considered in this work for estimating reference compensating current 3.2. Hysteresis Current Control for Switching Signal Generation In this thesis Hysteresis band Current Controller model is used for generating switching signals for the transistors of VSI, and is illustrated in Fig. 3.2.1.This current control technique imposes a bang-bang type instantaneous control that forces the compensation current to follow its estimated reference. The actual compensation current is subtracted from its estimated reference. The resulting error is sent through a hysteresis controller to determine the appropriate gating signals. In the simulation model, the hysteresis band (H) is chosen as 0.1 A with 0.05 as upper limit and -0.05 as lower limit. Fig.3.2.1 Simulink model of Hysteresis current controller 3.3. DC Bus Voltage control by using PI controller For maintaining DC bus voltage constant at a reference value, Proportional and Integral (PI) Controller is employed in this simulation work as shown in fig 3.3.1. In this control process the dc bus voltage of the active filter is used as feedback signals to PI controller. The reference dc capacitor voltage (4700v) is compared with actual capacitor voltage and the error is given to the PI controller [5][10]. The output of the PI controller provides the reference in-phase components Fig 3.3.1 PI controller subsystem 3.4. Tuned Passive Filter The proposed shunt hybrid active power filter consists of tuned passive filters connected in parallel with the load to absorb specified harmonic currents. The common types of passive harmonic filters include single tuned, double tuned and high pass filters. However for simplicity single tuned filters are considered in this work. The basic shunt passive filtering principle is to trap harmonic currents in LC circuits, tuned up to the harmonic filtering frequency, and to eliminate from power system. A single tuned 1st order filter configuration consists of RLC elements in series as shown in Fig.3.4. In single-tuned passive filter, the reactance of inductor is equal to that of capacitor at resonant frequency fn. The relationship among L, C, R, Q values are given in Eqn.(3.4)[4]. Cn = 1/Ln(2πfn)2 , Rn=Ln(2 πfn)/Q, Q=Rn√(Cn/Ln) .(3.4) Where fn=frequency of harmonic component, n=order of harmonic, Q=Quality factor, Rn=Resistance of nth harmonic filter, Ln=inductance of nth harmonic filter. In the proposed hybrid filter the shunt passive filters are tuned to absorb 5th and 7th harmonic currents and other higher order harmonics are to be suppressed by SAF. Hence burden on SAF is reduced resulting in reduced rating of SAF and effective filtering of higher order harmonics. Therefore source needs to supply only fundamental component of load current Fig-3.4 Tuned passive filter
  • 5. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 260 For 5th harmonic filter the resonance frequency is 250Hz and for 7th harmonic it is 350Hz. Quality factor of the filter is selected as 75[4] and the filter capacitance value is fixed at 30μF. 4. RESULTS 4.1. LV Test System without any Compensation: The results of simulation for LV test system (Configuration shown in appendix) are shown in Fig. 4.1. including three phase load current waveforms, three phase source current waveforms and Phase angle comparison between source voltage and source current waveforms without any type of compensation, As Shown the current waveforms are more distorted (i.e. not pure sinusoidal) due to presence of non linear load. Fig-4.1.1 Load current Fig-4.1.2 Source current Fig-4.1.3 Phase angle comparison between source voltage and source current for phase-A Fig-4.1.4 Harmonic spectrum of phase-a load current of LV test system without any compensation The THD is the most common indicator to determine the quality of AC waveforms. Using the Fast Fourier Transform (FFT), the harmonic spectrum of the source current under different compensation conditions is presented. Then, the THD comparison is carried out for the simulation results and from the spectra plot, it can be seen that the source current contains large amount of harmonic current components (5th & 7th components are higher magnitude i.e 11 and 7 respectively as shown in fig 4.1.4) of frequencies below 1 kHz and the THD is 12.4% (According to IEEE-519 standards the THD limits on the magnitude of harmonic current frequencies should be within 5% [1][2]). 4.2. LV Test System with Shunt Active Filter The three phase SAF compensating currents and source currents of the test system with SAF compensation are shown in Fig. 4.2. It is seen that due to SAF compensating currents
  • 6. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 261 the source currents attained near sinusoidal form. Source voltage and source currents are in-phase as shown in fig 4.2.3 for phase a Fig- 4.2.1 3-phase source currents and voltages of SAPF Fig-4.2.2 Three phase SAPF compensation currents Fig-4.2.3 Source voltage and source current for phase–a Fig-4.2.4 Harmonic spectrum of phase-a source current of LV test system with SAPF compensation From Fig.4.2.4 it is seen that the basic shunt APF successfully filters the harmonic current components caused by the nonlinear load. This is evident by the reduction of source current THD from 12.4% to nearly 2.11%, but still there are some low order harmonics (5th and 7th harmonic components of magnitude 1.7% and 0.6% respectively) present in the source current harmonic spectrum. 4.3. LV Test System with Proposed SHAF Compensation Fig. 4.3.1 shows the simulation results for three phase source current and voltages of test system model with the proposed Shunt Hybrid Active Filter (SHAF) compensation. When SHAF is applied, the injected compensation current (if) forces the source current (is) to become near sinusoidal waveform
  • 7. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 262 and in phase with the source voltage waveform, resulting in nearly unity power factor. Fig- 4.3.1 Three phase source currents and voltages of SHPF Fig. 4.3.2 shows the harmonic spectrum of the source current with the proposed SHAF compensation. It is seen that the THD is reduced to 0.98%. In comparison to Fig.4.2.4, the source current harmonic spectrum is almost free of harmonic components. This implies that the proposed SHAF compensates the distorted source currents including dominant 5th and 7th order harmonic (Reduced to 0.25% and 0.05% respectively). Fig-4.3.2 Harmonic spectrum of phase-a source current of LV test system with SHPF compensation 5. CONCLUSIONS This Paper presented the results obtained from the simulations of SHAF compensated LV test system. Simulations were conducted aiming to illustrate the effectiveness of the proposed shunt hybrid APF in harmonic mitigation in LV test system. The effectiveness of d-q theory in estimating compensation reference current is demonstrated. In addition, the effectiveness of PI controller in maintaining DC bus voltage is discussed. The simulation results are analyzed and discussed. Finally, a detailed THD analysis on source current spectrums is carried out to validate the harmonic filtering performance of the proposed SHAPF topology in comparison to the basic SAPF compensation in LV system. The source current THD is reduced from 12.4 % to 2.11 % with basic shunt APF. With the proposed SHAF, the source current THD is further reduced to 0.98 %. Thus, the harmonic filtering performance of the proposed SHAF topology is superior compared to the basic shunt APF and which is well below the harmonic limit imposed by IEEE Standard- 519(i.e. THD within 5%) REFERENCES [1]. H. Akagi, “New Trends in Active Filters for Power Conditioning. IEEE Trans. on Industry Applications”, 32(6), 1996, pp.1312-1322 [2]. B. Singh, K. Al-Haddad and A.Chandra, “A Review of Active Filters for Power Quality Improvement, IEEE Trans. on Industrial Electronics”, 46(5), 1999, pp. 960-971 [3]. L. Chen and A. Jouanne, “A Comparison and Assessment of Hybrid Filter Topologies and Control Algorithms”, Proceedings of The IEEE Power Electronics Specialists Conference (PESC), June 17-21, 2001, Vancouver, Canada: IEEE Trans. 2001, Pp. 565-570 [4]. D. A. Gonzalez, and J. C. McCall, “Design of Filters to Reduce Harmonic Distortion in Industrial Power Systems”, IEEE Trans. on Industry Applications, IA-23, 1987. [5]. Vikas Anand, Dr.S.Srivastava “Performance Investigation Of Shunt Active Power Filter Using Hysteresis Current Control Method” International Journal Of Engineering Research & Technology (IJERT) Vol. 1 Issue 4, June - 2012 Issn: 2278-0181 [6]. Hongyu Li., Fang Zhuo, Zhaoan Wang, Lei W. and Wu L., “A novel time domain current detection algorihm for shunt active power filters” IEEE Trans. power systems, vol.20, (2005):pp. 644–651. [7]. Sebasthi Rani, K., Porkumaran, K. Performance Evaluation of PI and Fuzzy controller based Shunt ActivePower Filter” European Journal of Scientific Research, ISSN 1450-216X,Vol.61,No.3(2011). [8]. “Evaluation Of Reference Signal Estimation Techniques For The Control Of Shunt Active Power Filter” By Norani Bt Atan, Bahisham Bte Yunus At Proceedings Of ICEE 2009 3rd International Conference On Energy And Environment ,December 2009, Mala, Malaysia. [9]. Elsa Susan Daniel and G.Abirami “Selective Harmonic Elimination Using Shunt Hybrid Active Power Filters Operating At Different Switching Frequencies” International Journal of Innovative Research In Electrical & Electronics, Instrumentation And Control Engineering Vol. 1, Issue 1, April 2013. [10]. T.Mahalekshmi “Current Harmonic Compensation and Power Factor Improvement by Hybrid Shunt Active Power
  • 8. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Issue: 03 | Mar-2014, Available @ http://www.ijret.org 263 Filter” International Journal of Computer Applications (0975 – 8887) Volume 4 – No.3, July 2010. [11]. G. Jayakrishna, K.S.R. Anjaneyulu., “Fuzzy Logic Control based Three Phase Shunt Active Filter for Voltage Regulation and Harmonic Reduction”, International Journal of Computer Applications (ISSN 0975-8887), Vol. 10, No.5, Nov. 2010, pp.13-19. BIOGRAPHIES Sangamesh, PG Scholar of EEE Dept, SDMCET Dharwad. He has done his B.E in Electrical Engineering from DSCE Bangalore in 2011 and he is Currently pursuing his M.Tech in Power System MohammadYunus M Hakim , PG Scholar of EEE Dept, SDMCET Dharwad. He has done his B.E in Electrical Engineering from BLDEA’s Engg college,Bijapur in 2012 and he is Currently pursuing his M.Tech in Power System. Sanjeev Kumar T.M , PG Scholar of EEE Dept, SDMCET Dharwad. He has done his B.E in Electrical Engineering from STJIT’s Engg college, Ranibennur in 2012 and he is Currently pursuing his M.Tech in Power System. Dr. Shekhappa. G. Ankaliki obtained his B.E (E&EE), M. Tech. (Power System) from Mysore University and Ph.D. from Visvesvaraya Technological University, Belgaum, Karnataka, INDIA respectively. He is a life member of ISTE, ISWE and MIE. He is presently working in Electrical & Electronics Engineering Department, SDM College of Engineering & Technology, Dhavalagiri, Dharwad-580 002, INDIA as a Professor and PG Coordinator. His research interest includes AI application to Power Systems, Smart Grid/Micro grids, SCADA and DSCADA, Energy Audit, Energy Management and Demand Side Management. He has published 26 papers in International Journals and 28 papers in National and International Conference Proceedings.