1. The document discusses the computer-aided design of grounding systems for transformer stations to ensure low grounding resistance and safe touch and step voltages. It presents the design of grounding systems for three transformer stations in Croatia using CDEGS software.
2. The design process involves measuring soil resistivity on site, modeling the soil as multiple layers, designing the grounding grid geometry, and simulating fault conditions to analyze touch and step voltages.
3. For a sample 110x80m grounding grid, the analysis shows that touch voltages are highest in the station corners. Additional measures like an outer ring conductor are recommended to improve safety.