1 Introduction
With ever increasing fault current levels in today’s inter-
connected power systems it is necessary to ensure very low
grounding resistance of transformer stations. In order to get
the best techno-economic solution in the design of grounding
systems for given safety criteria (IEEE, IEC, or some other
National standard) only computer-aided design can give an
optimal and fast solution of the given task. Low grounding
resistance and acceptable distribution of touch and step volt-
ages (as uniform as possible) for a high fault current level can
be simultaneously achieved only by using a grid-grounding
system.
The task for designers of grounding systems is to arrange
a buried metallic conductor with adequate equivalent radii to
achieve the safety criteria. The safety criteria in this paper are
based on IEEE Std. 80, 188 editions and IEC 479-1, 1984 and
some Croatian safety requirements. Another task is to check
some existing grounding grids for an increased fault current
level, i.e., to determine the fault current level which satisfies
the safety criteria. A typical grounding grid is designed and
simulated using the HIFREQ module. A design problem is
© Czech Technical University Publishing House http://ctn.cvut.cz/ap/ 83
Acta Polytechnica Vol. 44 No. 2/2004
Computer Aided Design of Transformer
Station Grounding System Using CDEGS
Software
S. Nikolovski, T. Barić
This paper presents a computer-aided design of a transformer station grounding system. Fault conditions in a transformer station can
produce huge damage to transformer station equipment if the grounding system is not designed properly. A well designed grounding system
is a very important part of the project for transformer station design as a whole. This paper analyses a procedure for transformer grounding
system design and spatial distribution of touch and step voltage on the ground surface level, using the CDEGS (Current Distribution
Electromagnetic Interference Grounding and Soil Structure Analysis) software. Spatial distribution is needed for checking and finding
dangerous step and touch voltages above and around the transformer station. Apparent earth resistivity data is measured and analyzed
using the RESAP module of the CDEGS software. Because of the very high current flow into the grounding system during a single line to
ground fault or a three phase fault in the transformer station, very high and dangerous potentials can be induced on the metallic structures
including the fence, which can cause dangerous situations for people and animals near the station and for the personnel inside the station.
The PLOT module of CDEGS is used to view the results of the scalar potential, step and touch voltage on the surface. Graphic displays
include equipotent contour lines and potential profiles (gradients) in 3D and 2D perspective and apparent soil resistivity (Wm) versus inter
electrode spacing (m). The results of alternative grid designs may be displayed simultaneously for the purpose of comparison.
Keywords: computer-aided design, substation, grounding grid, soil, safety, touch and step voltage.
Fig. 1: Simplified geometrical model of a transformer station grounding system and the conducting part
described and verified for several (110/35/10 kV) transformer
substations: “TS Našice”, “TS Osijek”, and “TS Valpovo”.
These transformer substations are in the eastern part of the
Croatian power system. Due to their operational time, TS are
exposed to potential fault conditions. In this sample case a
single line to ground fault is relevant for the grounding de-
sign. According to the technical specifications, single line to
ground fault currents entering the grounding system of these
transformer substations are in the order of 6 to 10 kA. The
analysed grounding system consists of a 110×80 m ground-
ing grid with 20–30 additional grounding rods of 3 m length.
When this happens, the potentials on the surfaces inside the
TS and nearby are on a much higher level than the reference
point away from TS.
2 Mathematical expression of the
electromagnetic field
The conductor network is subdivided into small segments.
This allows the thin-wire approximation to be used, which in
turn enables us to use linear current sources. The method
used to obtain the scalar potential and the electromagnetic
field in the frequency domain is described by using the follow-
ing 3 equations. Maxwell’s equations can be used to describe
electric field E and magnetic field H in terms of scalar j and
vector potential A:
j
m q
=
-
Ñ ×
1
A (1)
E A= - + Ñjw j (2)
H = ×Ñ
1
m
x A (3)
q s w e= + j (4)
where: q complex conductivity of the medium,
m permeability of the medium,
s conductivity of the medium,
e permittivity of the medium.
3 Example of transformer station
grounding design
Through there is no conventional rule in designing trans-
former station grounding, some guidelines can be suggested
on the basis of this example using CDEGS, as follows. The
first step in the design of transformer station grounding is to
determine appropriate soil model, for predicting the effect
of the underlying soil characteristics on the performance of
the grounding system. From the resistivity measurement data
obtained using arbitrarily spaced 4-electrode configuration
methods (including Wenner or Schlumberger methods), the
RESAP module determines the equivalent soil layers. The
earth layers may be vertical or horizontal (a one-layer, a
two-layer or a multi-layer soil model). In this study, soil resis-
tivity is measured by a 4-point measurement (Schlumberger
method). The influence of seasonal variations in the last
several years on soil resistivity is estimated indirectly using sta-
tistical data collected in the course of preventive measure-
ments of the grounding impedance by a local utility. Accord-
ing to this simplified method, 100 Wm soil resistivitiy can be
assumed as the worst soil top layer resistivity. The RESAP
program interprets the measured apparent earth resistivity
(or resistance) data to determine the equivalent earth struc-
ture model that is necessary for analysing the grounding
systems. The measured soil resistivity data is shown in Table 1.
Measured data entered in the RESAP (computations) win-
dow is shown in Fig 2. The 4-point Schlumberger measure-
ment method with necessary data for calculating soil resistiv-
ity is also presented. The RESAP module calculates the resis-
tivity using the following generalised equation:
r p= + +
+
+
+
é
ë
ê
ù
û
ú2
1 1 1 1
1 2 1 2
R
S S S S S Se e e i e i
(5)
where: Se1 distance between current C1 and potential P1
electrodes,
Se2 distance between current C2 and potential P2
electrodes,
Si distance between potential electrodes,
r resistivity of soil,
R measurement of soil resistance.
The apparent soil resistivity in an Wm (versus inter-elec-
trode spacing in m) relevant in this study is shown in Fig. 3.
According to Fig 3., after 2 m below the surface the apparent
resistivity becomes practically constant. Fig. 3. represents one
measurement series, which cannot represent the resistivity
during seasons. It is useful to remember that current depth
penetration in soil depends on current electrode spacing. It is
therefore useful to perform some additional measurements
with a very close inter-electrode to get a better interpolation
of the soil layer just below the surface, since the apparent re-
sistivity has changed rapidly in one layer.
The computed soil resistivity and layer thickness for a
2-layer soil model are given by the text report, and are shown
below in the computer generated report.
84 © Czech Technical University Publishing House http://ctn.cvut.cz/ap/
Acta Polytechnica Vol. 44 No. 2/2004
Measurement number 1. 2. 3. 4. 5. 6. 7. 8. 9. 10.
Distance between electrode [m]
Se 0.25 0.75 1.25 1.75 2.25 2.75 3.25 3.75 4.75 5.75
Si 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
Measured resistance [W] R 42.200 6.130 2.530 1.372 0.906 0.604 0.446 0.338 0.214 0.148
Table 1: Measurement data
R E S I S T I V I T Y
(SYSTEM INFORMATION SUMMARY)
System of Units: Meters
Soil Type Selected: Multi-Layer Horizontal
RMS error between measured and calculated: 2.08052 %
resistivities
Soil layer resistivity calculated by RESAP is the initial data
for a further study. From the computer generated report for
soil resistivity, a two-layer soil model is made, which gives sat-
isfactory solutions in most cases including this study. The data
entered in the second module HIFREQ is shown in Fig. 4.
Data for relative permeability and permittivity is irrelevant in
this study.
The grounding system described in this study consists of a
110×80 m grounding grid plus an additional ring 5m away
from the grid. The grounding system is buried 0.8 meters be-
low the transformer station surface. The ground fault current
in this study is assumed to be 7 kA. The grounding grid con-
© Czech Technical University Publishing House http://ctn.cvut.cz/ap/ 85
Acta Polytechnica Vol. 44 No. 2/2004
Fig. 2: RESAP (computations) window with measurement data relevant in this study
Fig. 3: Apparent soil resistivity versus inter-electrode spacing
Layer
Number
Resistivity
(Wm)
Thickness
(m)
Coefficient
(p.u.)
Contrast
Ratio
1 infinite infinite 0.0 1.0
2 78.17224 0.2106636 -1.0000 0.78172E-18
3 33.55941 infinite -0.39929 0.42930
Fig. 4: A HIFREQ (Soil type) window is used to specify the type
of soil
sists of rectangular cross section Fe/Zn conductors (30×4 mm)
with an equivalent radius equal to 10.83 mm. A geometrical
position of the grounding grid is shown in Fig 5.
This first iteration is without additional rods, e.g., the
grounding could consist of the grounding grid, with rods and
an additional ring around it at the same depth. Division of the
grid into smaller windows is not appropriate in the first
design iteration. The result of simulation is presented in the
following figures. First, a 3D plot of scalar potential at the
surface of TS is shown in Fig. 6. The scalar potential peaks
correspond to the nodes of the grid, e.g., the valleys corre-
spond to the centre of the windows in the grid (see Fig. 6).
This 3D view is useful in visualisation of the scalar potential
shape. This shape should look as uniform as possible. Fig. 7
shows the reach touch voltages in 3D view with references to
the worst system grounding potential rise (GPR). Fig. 7 shows
that the reach touch voltages are worst in the corners of TS,
and additional measures must be taken to decrease these volt-
ages below safety limits.
Since a 3D plot loses some detailed information about
scalar potential or step/touch voltages, an additional investi-
gation must be made for suspicious areas or profiles. An addi-
tional inspection can be made in a 2D view for arbitrary pro-
files (see Fig. 8). Reach touch voltages for the worst system
GPR at the surface of TS, for three profiles with numbers 1, 3
and 100, are shown in Fig. 8.
86 © Czech Technical University Publishing House http://ctn.cvut.cz/ap/
Acta Polytechnica Vol. 44 No. 2/2004
Fig. 5: Geometry of the grounding grid with data relevant in this study
Fig. 6: Scalar potential at the surface of TS
A similar investigation can be made in a 2D view, as shown
in Fig. 9. These 2D contour views show lines of the same reach
touch voltages with the superposed grid.
The safety limits for step and touch voltages are generated
by CDEGS according to user defined standards. Several dif-
ferent standards can be chosen ( IEEE, IEC or some national
© Czech Technical University Publishing House http://ctn.cvut.cz/ap/ 87
Acta Polytechnica Vol. 44 No. 2/2004
Fig. 7: Reach touch voltages in 3D plot, corresponding to the worst system GPR
Profile
Number 1.
Profile
Number 3.
Profile
Number 100.
Fig. 8: Reach touch voltages/worst system GPR
88 © Czech Technical University Publishing House http://ctn.cvut.cz/ap/
Acta Polytechnica Vol. 44 No. 2/2004
Fig. 9: Reach touch voltages/ worst system GPR contour plot
Fig. 10: Reach step voltages/ worst system GPR contour plot
standard). In this study the fibrillation current is calculated
according to the C1-IEC standard and body resistance for
95 % population, see Fig. 11. If crushed rock is used to im-
prove the safety limits for step and touch voltage, it can be
included and entered in the window.
4 Conclusion
Manual calculation of the equivalent resistance of com-
posite grounding can lead to incorrect results if the mirroring
effect is not taken into account. Because of the large geo-
metric structure of a grid, all additional metallic conductors
such as rods, rings and another additional structures can
influence each other. This gives advantages to computer
design, especially to specialised programs that take into ac-
count all physical phenomena. Since TS is a restricted area for
non-operating personnel (civilian personnel), it is protected
by a metallic fence. Attention must be taken to prevent the rise
in the potential of fence due to fault conditions in TS. Fatal ac-
cidents caused by dangerous touch voltages when someone
touches the fence can be avoided by placing an additional
buried ring conductor outside TS, one meter away from the
fence, which is in galvanic contact with the main grounding
but not with the fence. This additional ring is added in this
study. The main purpose of this additional ring conductor is
to shape the electric potential at the surface around the fence.
References
[1] Ma J., Dawalibi F. P.: “Modern Computational Methods
for the Design and Analysis of Power System Ground-
ing.” Proceedings of the 1998 International Conference
on Power System Technology, Beijing, August 18–21,
1998, p. 122–126.
[2] Dawalibi F. P., Barbeito N.: “Measurements and Com-
putations of the Performance of Grounding Systems
Buried in Multilayer Soils.” IEEE Transactions on Power
Delivery, Vol. 6, No. 4, October 1991, p. 1483–1490.
[3] Nikolovski S., Fortin S.: “Lightning Transient Response
of 400 kV Transmission Tower with Associated Ground-
ing System.” EMC 1998 Roma International Symposium
on Electromagnetic Compatibility, Rome, Italy, Septem-
ber 14, 1998.
[4] Nikolovski S., Fortin S.: “Frequency Domain Analysis
of 110/35 kV Transformer Station Grounding System
Subject to Lightning Strike.” Proceedings of the IEEE
PowerTech '99 Conference, Budapest, Hungary, August
29–September 2, 1999.
Srete Nikolovski Ph.D
e-mail: Srete.Nikolovski@etfos.hr
Tomislav Barić B.Sc.
e-mail: Tomislav.Baric@etfos.hr
Power System Department
Faculty of Electrical Engineering Osijek
K. Trpimira 2B
31000 Osijek, Croatia
© Czech Technical University Publishing House http://ctn.cvut.cz/ap/ 89
Acta Polytechnica Vol. 44 No. 2/2004
Fig. 11: Window for Safety assessment limits with data relevant in this study
Fig. 12: Computed safety Step and Touch Voltage for an addi-
tional layer (rocks) at the surface of TS

Más contenido relacionado

La actualidad más candente

Analysis of transient enclosure voltages in gis (emtp simulation studies)
Analysis of transient enclosure voltages in gis (emtp simulation studies)Analysis of transient enclosure voltages in gis (emtp simulation studies)
Analysis of transient enclosure voltages in gis (emtp simulation studies)eSAT Publishing House
 
NON-SPLIT PERFECTLY MATCHED LAYER BOUNDARY CONDITIONS FOR NUMERICAL SOLUTION ...
NON-SPLIT PERFECTLY MATCHED LAYER BOUNDARY CONDITIONS FOR NUMERICAL SOLUTION ...NON-SPLIT PERFECTLY MATCHED LAYER BOUNDARY CONDITIONS FOR NUMERICAL SOLUTION ...
NON-SPLIT PERFECTLY MATCHED LAYER BOUNDARY CONDITIONS FOR NUMERICAL SOLUTION ...ijeljournal
 
Non-split Perfectly Matched Layer Boundary Conditions for Numerical Solution ...
Non-split Perfectly Matched Layer Boundary Conditions for Numerical Solution ...Non-split Perfectly Matched Layer Boundary Conditions for Numerical Solution ...
Non-split Perfectly Matched Layer Boundary Conditions for Numerical Solution ...ijeljournal
 
Optimization of Surface Impedance for Reducing Surface Waves between Antennas
Optimization of Surface Impedance for Reducing Surface Waves between AntennasOptimization of Surface Impedance for Reducing Surface Waves between Antennas
Optimization of Surface Impedance for Reducing Surface Waves between AntennasIJMER
 
Effect of mesh grid structure in reducing hot carrier effect of nmos device s...
Effect of mesh grid structure in reducing hot carrier effect of nmos device s...Effect of mesh grid structure in reducing hot carrier effect of nmos device s...
Effect of mesh grid structure in reducing hot carrier effect of nmos device s...ijcsa
 
Adjusting third zone distance protection
Adjusting third zone distance protectionAdjusting third zone distance protection
Adjusting third zone distance protectionravi yadav
 
The influences of T-joint core design on no-load losses in transformers
The influences of T-joint core design on no-load losses in transformersThe influences of T-joint core design on no-load losses in transformers
The influences of T-joint core design on no-load losses in transformersUpwork
 
MODELING OF PLANAR METAMATERIAL STRUCTURE AND ITS EFFECTIVE PARAMETER EXTRACTION
MODELING OF PLANAR METAMATERIAL STRUCTURE AND ITS EFFECTIVE PARAMETER EXTRACTIONMODELING OF PLANAR METAMATERIAL STRUCTURE AND ITS EFFECTIVE PARAMETER EXTRACTION
MODELING OF PLANAR METAMATERIAL STRUCTURE AND ITS EFFECTIVE PARAMETER EXTRACTIONIAEME Publication
 
Determination of Surface Currents on Circular Microstrip Antennas
Determination of Surface Currents on Circular Microstrip AntennasDetermination of Surface Currents on Circular Microstrip Antennas
Determination of Surface Currents on Circular Microstrip AntennaswailGodaymi1
 
Impact of rail impedance intrinsic variability on railway system operation, E...
Impact of rail impedance intrinsic variability on railway system operation, E...Impact of rail impedance intrinsic variability on railway system operation, E...
Impact of rail impedance intrinsic variability on railway system operation, E...IJECEIAES
 
DWS MODELING OF MULTICONDUCTOR TRANSMISSION LINES
DWS MODELING OF MULTICONDUCTOR TRANSMISSION LINESDWS MODELING OF MULTICONDUCTOR TRANSMISSION LINES
DWS MODELING OF MULTICONDUCTOR TRANSMISSION LINESPiero Belforte
 
6.[36 45]seven level modified cascaded inverter for induction motor drive app...
6.[36 45]seven level modified cascaded inverter for induction motor drive app...6.[36 45]seven level modified cascaded inverter for induction motor drive app...
6.[36 45]seven level modified cascaded inverter for induction motor drive app...Alexander Decker
 
11.seven level modified cascaded inverter for induction motor drive applications
11.seven level modified cascaded inverter for induction motor drive applications11.seven level modified cascaded inverter for induction motor drive applications
11.seven level modified cascaded inverter for induction motor drive applicationsAlexander Decker
 
Analysis-And-Design-Of-220kv-Transmission-Line-Tower-In-Different-Zones-I-&-V...
Analysis-And-Design-Of-220kv-Transmission-Line-Tower-In-Different-Zones-I-&-V...Analysis-And-Design-Of-220kv-Transmission-Line-Tower-In-Different-Zones-I-&-V...
Analysis-And-Design-Of-220kv-Transmission-Line-Tower-In-Different-Zones-I-&-V...Deepak Saxena
 
Wide Area Fault Location for Power Transmission Network using Reactance Based...
Wide Area Fault Location for Power Transmission Network using Reactance Based...Wide Area Fault Location for Power Transmission Network using Reactance Based...
Wide Area Fault Location for Power Transmission Network using Reactance Based...Muhd Hafizi Idris
 
Mesoscale modeling for wind resource assessment
Mesoscale modeling for wind resource assessmentMesoscale modeling for wind resource assessment
Mesoscale modeling for wind resource assessmentJean-Claude Meteodyn
 
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...IOSR Journals
 

La actualidad más candente (19)

Analysis of transient enclosure voltages in gis (emtp simulation studies)
Analysis of transient enclosure voltages in gis (emtp simulation studies)Analysis of transient enclosure voltages in gis (emtp simulation studies)
Analysis of transient enclosure voltages in gis (emtp simulation studies)
 
10.1.1.192.9435(1)
10.1.1.192.9435(1)10.1.1.192.9435(1)
10.1.1.192.9435(1)
 
NON-SPLIT PERFECTLY MATCHED LAYER BOUNDARY CONDITIONS FOR NUMERICAL SOLUTION ...
NON-SPLIT PERFECTLY MATCHED LAYER BOUNDARY CONDITIONS FOR NUMERICAL SOLUTION ...NON-SPLIT PERFECTLY MATCHED LAYER BOUNDARY CONDITIONS FOR NUMERICAL SOLUTION ...
NON-SPLIT PERFECTLY MATCHED LAYER BOUNDARY CONDITIONS FOR NUMERICAL SOLUTION ...
 
Non-split Perfectly Matched Layer Boundary Conditions for Numerical Solution ...
Non-split Perfectly Matched Layer Boundary Conditions for Numerical Solution ...Non-split Perfectly Matched Layer Boundary Conditions for Numerical Solution ...
Non-split Perfectly Matched Layer Boundary Conditions for Numerical Solution ...
 
Optimization of Surface Impedance for Reducing Surface Waves between Antennas
Optimization of Surface Impedance for Reducing Surface Waves between AntennasOptimization of Surface Impedance for Reducing Surface Waves between Antennas
Optimization of Surface Impedance for Reducing Surface Waves between Antennas
 
Effect of mesh grid structure in reducing hot carrier effect of nmos device s...
Effect of mesh grid structure in reducing hot carrier effect of nmos device s...Effect of mesh grid structure in reducing hot carrier effect of nmos device s...
Effect of mesh grid structure in reducing hot carrier effect of nmos device s...
 
Adjusting third zone distance protection
Adjusting third zone distance protectionAdjusting third zone distance protection
Adjusting third zone distance protection
 
The influences of T-joint core design on no-load losses in transformers
The influences of T-joint core design on no-load losses in transformersThe influences of T-joint core design on no-load losses in transformers
The influences of T-joint core design on no-load losses in transformers
 
MODELING OF PLANAR METAMATERIAL STRUCTURE AND ITS EFFECTIVE PARAMETER EXTRACTION
MODELING OF PLANAR METAMATERIAL STRUCTURE AND ITS EFFECTIVE PARAMETER EXTRACTIONMODELING OF PLANAR METAMATERIAL STRUCTURE AND ITS EFFECTIVE PARAMETER EXTRACTION
MODELING OF PLANAR METAMATERIAL STRUCTURE AND ITS EFFECTIVE PARAMETER EXTRACTION
 
Determination of Surface Currents on Circular Microstrip Antennas
Determination of Surface Currents on Circular Microstrip AntennasDetermination of Surface Currents on Circular Microstrip Antennas
Determination of Surface Currents on Circular Microstrip Antennas
 
Impact of rail impedance intrinsic variability on railway system operation, E...
Impact of rail impedance intrinsic variability on railway system operation, E...Impact of rail impedance intrinsic variability on railway system operation, E...
Impact of rail impedance intrinsic variability on railway system operation, E...
 
Ph3426792682
Ph3426792682Ph3426792682
Ph3426792682
 
DWS MODELING OF MULTICONDUCTOR TRANSMISSION LINES
DWS MODELING OF MULTICONDUCTOR TRANSMISSION LINESDWS MODELING OF MULTICONDUCTOR TRANSMISSION LINES
DWS MODELING OF MULTICONDUCTOR TRANSMISSION LINES
 
6.[36 45]seven level modified cascaded inverter for induction motor drive app...
6.[36 45]seven level modified cascaded inverter for induction motor drive app...6.[36 45]seven level modified cascaded inverter for induction motor drive app...
6.[36 45]seven level modified cascaded inverter for induction motor drive app...
 
11.seven level modified cascaded inverter for induction motor drive applications
11.seven level modified cascaded inverter for induction motor drive applications11.seven level modified cascaded inverter for induction motor drive applications
11.seven level modified cascaded inverter for induction motor drive applications
 
Analysis-And-Design-Of-220kv-Transmission-Line-Tower-In-Different-Zones-I-&-V...
Analysis-And-Design-Of-220kv-Transmission-Line-Tower-In-Different-Zones-I-&-V...Analysis-And-Design-Of-220kv-Transmission-Line-Tower-In-Different-Zones-I-&-V...
Analysis-And-Design-Of-220kv-Transmission-Line-Tower-In-Different-Zones-I-&-V...
 
Wide Area Fault Location for Power Transmission Network using Reactance Based...
Wide Area Fault Location for Power Transmission Network using Reactance Based...Wide Area Fault Location for Power Transmission Network using Reactance Based...
Wide Area Fault Location for Power Transmission Network using Reactance Based...
 
Mesoscale modeling for wind resource assessment
Mesoscale modeling for wind resource assessmentMesoscale modeling for wind resource assessment
Mesoscale modeling for wind resource assessment
 
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
 

Similar a Ieee depth

Investigation of overvoltage on square, rectangular and L-shaped ground grid...
Investigation of overvoltage on square, rectangular and  L-shaped ground grid...Investigation of overvoltage on square, rectangular and  L-shaped ground grid...
Investigation of overvoltage on square, rectangular and L-shaped ground grid...IJECEIAES
 
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...inventionjournals
 
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...inventionjournals
 
Performance Analysis of Actual Step and Mesh Voltage of Substation Grounding ...
Performance Analysis of Actual Step and Mesh Voltage of Substation Grounding ...Performance Analysis of Actual Step and Mesh Voltage of Substation Grounding ...
Performance Analysis of Actual Step and Mesh Voltage of Substation Grounding ...Editor IJCATR
 
Analysis of transient enclosure voltages in gis (emtp simulation studies)
Analysis of transient enclosure voltages in gis (emtp simulation studies)Analysis of transient enclosure voltages in gis (emtp simulation studies)
Analysis of transient enclosure voltages in gis (emtp simulation studies)eSAT Journals
 
ESDEMC_PB2009.08 A Measurement Technique for ESD Current Spreading on A PCB u...
ESDEMC_PB2009.08 A Measurement Technique for ESD Current Spreading on A PCB u...ESDEMC_PB2009.08 A Measurement Technique for ESD Current Spreading on A PCB u...
ESDEMC_PB2009.08 A Measurement Technique for ESD Current Spreading on A PCB u...ESDEMC Technology LLC
 
Transient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning currentTransient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning currentHimmelstern
 
EVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVEL
EVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVELEVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVEL
EVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVELPiero Belforte
 
Design of Grounding System for Substation
Design of Grounding System for SubstationDesign of Grounding System for Substation
Design of Grounding System for Substationijtsrd
 
Evaluation of earth fault location algorithm in medium voltage distribution n...
Evaluation of earth fault location algorithm in medium voltage distribution n...Evaluation of earth fault location algorithm in medium voltage distribution n...
Evaluation of earth fault location algorithm in medium voltage distribution n...IJECEIAES
 
Designing Safe & Reliable Grounding In AC Substations With Poor Soil Resistiv...
Designing Safe & Reliable Grounding In AC Substations With Poor Soil Resistiv...Designing Safe & Reliable Grounding In AC Substations With Poor Soil Resistiv...
Designing Safe & Reliable Grounding In AC Substations With Poor Soil Resistiv...Thorne & Derrick International
 
An Upgraded Transverse Electromagnetic Parallel Plates for Dielectric Measure...
An Upgraded Transverse Electromagnetic Parallel Plates for Dielectric Measure...An Upgraded Transverse Electromagnetic Parallel Plates for Dielectric Measure...
An Upgraded Transverse Electromagnetic Parallel Plates for Dielectric Measure...TELKOMNIKA JOURNAL
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePower System Operation
 
Development of A 3d Model Eddy Current Testing
Development of A 3d Model Eddy Current TestingDevelopment of A 3d Model Eddy Current Testing
Development of A 3d Model Eddy Current Testinginventionjournals
 
Substation grounding
Substation groundingSubstation grounding
Substation groundingSyed Ubaid
 

Similar a Ieee depth (20)

Investigation of overvoltage on square, rectangular and L-shaped ground grid...
Investigation of overvoltage on square, rectangular and  L-shaped ground grid...Investigation of overvoltage on square, rectangular and  L-shaped ground grid...
Investigation of overvoltage on square, rectangular and L-shaped ground grid...
 
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
 
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
 
Performance Analysis of Actual Step and Mesh Voltage of Substation Grounding ...
Performance Analysis of Actual Step and Mesh Voltage of Substation Grounding ...Performance Analysis of Actual Step and Mesh Voltage of Substation Grounding ...
Performance Analysis of Actual Step and Mesh Voltage of Substation Grounding ...
 
Analysis of transient enclosure voltages in gis (emtp simulation studies)
Analysis of transient enclosure voltages in gis (emtp simulation studies)Analysis of transient enclosure voltages in gis (emtp simulation studies)
Analysis of transient enclosure voltages in gis (emtp simulation studies)
 
ESDEMC_PB2009.08 A Measurement Technique for ESD Current Spreading on A PCB u...
ESDEMC_PB2009.08 A Measurement Technique for ESD Current Spreading on A PCB u...ESDEMC_PB2009.08 A Measurement Technique for ESD Current Spreading on A PCB u...
ESDEMC_PB2009.08 A Measurement Technique for ESD Current Spreading on A PCB u...
 
Transient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning currentTransient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning current
 
EVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVEL
EVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVELEVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVEL
EVALUATION OF RADIATED EMISSIONS FROM PCB AND CABLES AT POST-LAYOUT LEVEL
 
Permeameter_Salahun
Permeameter_SalahunPermeameter_Salahun
Permeameter_Salahun
 
Design of Grounding System for Substation
Design of Grounding System for SubstationDesign of Grounding System for Substation
Design of Grounding System for Substation
 
Evaluation of earth fault location algorithm in medium voltage distribution n...
Evaluation of earth fault location algorithm in medium voltage distribution n...Evaluation of earth fault location algorithm in medium voltage distribution n...
Evaluation of earth fault location algorithm in medium voltage distribution n...
 
grad project IEEE paper
grad project IEEE papergrad project IEEE paper
grad project IEEE paper
 
Designing Safe & Reliable Grounding In AC Substations With Poor Soil Resistiv...
Designing Safe & Reliable Grounding In AC Substations With Poor Soil Resistiv...Designing Safe & Reliable Grounding In AC Substations With Poor Soil Resistiv...
Designing Safe & Reliable Grounding In AC Substations With Poor Soil Resistiv...
 
An Upgraded Transverse Electromagnetic Parallel Plates for Dielectric Measure...
An Upgraded Transverse Electromagnetic Parallel Plates for Dielectric Measure...An Upgraded Transverse Electromagnetic Parallel Plates for Dielectric Measure...
An Upgraded Transverse Electromagnetic Parallel Plates for Dielectric Measure...
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
ملزمة
ملزمةملزمة
ملزمة
 
Development of A 3d Model Eddy Current Testing
Development of A 3d Model Eddy Current TestingDevelopment of A 3d Model Eddy Current Testing
Development of A 3d Model Eddy Current Testing
 
Substation grounding
Substation groundingSubstation grounding
Substation grounding
 
earth mat design for metro station
earth mat design for metro stationearth mat design for metro station
earth mat design for metro station
 
Earth MAT design for Metro Station
Earth MAT design for Metro StationEarth MAT design for Metro Station
Earth MAT design for Metro Station
 

Último

(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 

Último (20)

(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 

Ieee depth

  • 1. 1 Introduction With ever increasing fault current levels in today’s inter- connected power systems it is necessary to ensure very low grounding resistance of transformer stations. In order to get the best techno-economic solution in the design of grounding systems for given safety criteria (IEEE, IEC, or some other National standard) only computer-aided design can give an optimal and fast solution of the given task. Low grounding resistance and acceptable distribution of touch and step volt- ages (as uniform as possible) for a high fault current level can be simultaneously achieved only by using a grid-grounding system. The task for designers of grounding systems is to arrange a buried metallic conductor with adequate equivalent radii to achieve the safety criteria. The safety criteria in this paper are based on IEEE Std. 80, 188 editions and IEC 479-1, 1984 and some Croatian safety requirements. Another task is to check some existing grounding grids for an increased fault current level, i.e., to determine the fault current level which satisfies the safety criteria. A typical grounding grid is designed and simulated using the HIFREQ module. A design problem is © Czech Technical University Publishing House http://ctn.cvut.cz/ap/ 83 Acta Polytechnica Vol. 44 No. 2/2004 Computer Aided Design of Transformer Station Grounding System Using CDEGS Software S. Nikolovski, T. Barić This paper presents a computer-aided design of a transformer station grounding system. Fault conditions in a transformer station can produce huge damage to transformer station equipment if the grounding system is not designed properly. A well designed grounding system is a very important part of the project for transformer station design as a whole. This paper analyses a procedure for transformer grounding system design and spatial distribution of touch and step voltage on the ground surface level, using the CDEGS (Current Distribution Electromagnetic Interference Grounding and Soil Structure Analysis) software. Spatial distribution is needed for checking and finding dangerous step and touch voltages above and around the transformer station. Apparent earth resistivity data is measured and analyzed using the RESAP module of the CDEGS software. Because of the very high current flow into the grounding system during a single line to ground fault or a three phase fault in the transformer station, very high and dangerous potentials can be induced on the metallic structures including the fence, which can cause dangerous situations for people and animals near the station and for the personnel inside the station. The PLOT module of CDEGS is used to view the results of the scalar potential, step and touch voltage on the surface. Graphic displays include equipotent contour lines and potential profiles (gradients) in 3D and 2D perspective and apparent soil resistivity (Wm) versus inter electrode spacing (m). The results of alternative grid designs may be displayed simultaneously for the purpose of comparison. Keywords: computer-aided design, substation, grounding grid, soil, safety, touch and step voltage. Fig. 1: Simplified geometrical model of a transformer station grounding system and the conducting part
  • 2. described and verified for several (110/35/10 kV) transformer substations: “TS Našice”, “TS Osijek”, and “TS Valpovo”. These transformer substations are in the eastern part of the Croatian power system. Due to their operational time, TS are exposed to potential fault conditions. In this sample case a single line to ground fault is relevant for the grounding de- sign. According to the technical specifications, single line to ground fault currents entering the grounding system of these transformer substations are in the order of 6 to 10 kA. The analysed grounding system consists of a 110×80 m ground- ing grid with 20–30 additional grounding rods of 3 m length. When this happens, the potentials on the surfaces inside the TS and nearby are on a much higher level than the reference point away from TS. 2 Mathematical expression of the electromagnetic field The conductor network is subdivided into small segments. This allows the thin-wire approximation to be used, which in turn enables us to use linear current sources. The method used to obtain the scalar potential and the electromagnetic field in the frequency domain is described by using the follow- ing 3 equations. Maxwell’s equations can be used to describe electric field E and magnetic field H in terms of scalar j and vector potential A: j m q = - Ñ × 1 A (1) E A= - + Ñjw j (2) H = ×Ñ 1 m x A (3) q s w e= + j (4) where: q complex conductivity of the medium, m permeability of the medium, s conductivity of the medium, e permittivity of the medium. 3 Example of transformer station grounding design Through there is no conventional rule in designing trans- former station grounding, some guidelines can be suggested on the basis of this example using CDEGS, as follows. The first step in the design of transformer station grounding is to determine appropriate soil model, for predicting the effect of the underlying soil characteristics on the performance of the grounding system. From the resistivity measurement data obtained using arbitrarily spaced 4-electrode configuration methods (including Wenner or Schlumberger methods), the RESAP module determines the equivalent soil layers. The earth layers may be vertical or horizontal (a one-layer, a two-layer or a multi-layer soil model). In this study, soil resis- tivity is measured by a 4-point measurement (Schlumberger method). The influence of seasonal variations in the last several years on soil resistivity is estimated indirectly using sta- tistical data collected in the course of preventive measure- ments of the grounding impedance by a local utility. Accord- ing to this simplified method, 100 Wm soil resistivitiy can be assumed as the worst soil top layer resistivity. The RESAP program interprets the measured apparent earth resistivity (or resistance) data to determine the equivalent earth struc- ture model that is necessary for analysing the grounding systems. The measured soil resistivity data is shown in Table 1. Measured data entered in the RESAP (computations) win- dow is shown in Fig 2. The 4-point Schlumberger measure- ment method with necessary data for calculating soil resistiv- ity is also presented. The RESAP module calculates the resis- tivity using the following generalised equation: r p= + + + + + é ë ê ù û ú2 1 1 1 1 1 2 1 2 R S S S S S Se e e i e i (5) where: Se1 distance between current C1 and potential P1 electrodes, Se2 distance between current C2 and potential P2 electrodes, Si distance between potential electrodes, r resistivity of soil, R measurement of soil resistance. The apparent soil resistivity in an Wm (versus inter-elec- trode spacing in m) relevant in this study is shown in Fig. 3. According to Fig 3., after 2 m below the surface the apparent resistivity becomes practically constant. Fig. 3. represents one measurement series, which cannot represent the resistivity during seasons. It is useful to remember that current depth penetration in soil depends on current electrode spacing. It is therefore useful to perform some additional measurements with a very close inter-electrode to get a better interpolation of the soil layer just below the surface, since the apparent re- sistivity has changed rapidly in one layer. The computed soil resistivity and layer thickness for a 2-layer soil model are given by the text report, and are shown below in the computer generated report. 84 © Czech Technical University Publishing House http://ctn.cvut.cz/ap/ Acta Polytechnica Vol. 44 No. 2/2004 Measurement number 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Distance between electrode [m] Se 0.25 0.75 1.25 1.75 2.25 2.75 3.25 3.75 4.75 5.75 Si 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 Measured resistance [W] R 42.200 6.130 2.530 1.372 0.906 0.604 0.446 0.338 0.214 0.148 Table 1: Measurement data
  • 3. R E S I S T I V I T Y (SYSTEM INFORMATION SUMMARY) System of Units: Meters Soil Type Selected: Multi-Layer Horizontal RMS error between measured and calculated: 2.08052 % resistivities Soil layer resistivity calculated by RESAP is the initial data for a further study. From the computer generated report for soil resistivity, a two-layer soil model is made, which gives sat- isfactory solutions in most cases including this study. The data entered in the second module HIFREQ is shown in Fig. 4. Data for relative permeability and permittivity is irrelevant in this study. The grounding system described in this study consists of a 110×80 m grounding grid plus an additional ring 5m away from the grid. The grounding system is buried 0.8 meters be- low the transformer station surface. The ground fault current in this study is assumed to be 7 kA. The grounding grid con- © Czech Technical University Publishing House http://ctn.cvut.cz/ap/ 85 Acta Polytechnica Vol. 44 No. 2/2004 Fig. 2: RESAP (computations) window with measurement data relevant in this study Fig. 3: Apparent soil resistivity versus inter-electrode spacing Layer Number Resistivity (Wm) Thickness (m) Coefficient (p.u.) Contrast Ratio 1 infinite infinite 0.0 1.0 2 78.17224 0.2106636 -1.0000 0.78172E-18 3 33.55941 infinite -0.39929 0.42930 Fig. 4: A HIFREQ (Soil type) window is used to specify the type of soil
  • 4. sists of rectangular cross section Fe/Zn conductors (30×4 mm) with an equivalent radius equal to 10.83 mm. A geometrical position of the grounding grid is shown in Fig 5. This first iteration is without additional rods, e.g., the grounding could consist of the grounding grid, with rods and an additional ring around it at the same depth. Division of the grid into smaller windows is not appropriate in the first design iteration. The result of simulation is presented in the following figures. First, a 3D plot of scalar potential at the surface of TS is shown in Fig. 6. The scalar potential peaks correspond to the nodes of the grid, e.g., the valleys corre- spond to the centre of the windows in the grid (see Fig. 6). This 3D view is useful in visualisation of the scalar potential shape. This shape should look as uniform as possible. Fig. 7 shows the reach touch voltages in 3D view with references to the worst system grounding potential rise (GPR). Fig. 7 shows that the reach touch voltages are worst in the corners of TS, and additional measures must be taken to decrease these volt- ages below safety limits. Since a 3D plot loses some detailed information about scalar potential or step/touch voltages, an additional investi- gation must be made for suspicious areas or profiles. An addi- tional inspection can be made in a 2D view for arbitrary pro- files (see Fig. 8). Reach touch voltages for the worst system GPR at the surface of TS, for three profiles with numbers 1, 3 and 100, are shown in Fig. 8. 86 © Czech Technical University Publishing House http://ctn.cvut.cz/ap/ Acta Polytechnica Vol. 44 No. 2/2004 Fig. 5: Geometry of the grounding grid with data relevant in this study Fig. 6: Scalar potential at the surface of TS
  • 5. A similar investigation can be made in a 2D view, as shown in Fig. 9. These 2D contour views show lines of the same reach touch voltages with the superposed grid. The safety limits for step and touch voltages are generated by CDEGS according to user defined standards. Several dif- ferent standards can be chosen ( IEEE, IEC or some national © Czech Technical University Publishing House http://ctn.cvut.cz/ap/ 87 Acta Polytechnica Vol. 44 No. 2/2004 Fig. 7: Reach touch voltages in 3D plot, corresponding to the worst system GPR Profile Number 1. Profile Number 3. Profile Number 100. Fig. 8: Reach touch voltages/worst system GPR
  • 6. 88 © Czech Technical University Publishing House http://ctn.cvut.cz/ap/ Acta Polytechnica Vol. 44 No. 2/2004 Fig. 9: Reach touch voltages/ worst system GPR contour plot Fig. 10: Reach step voltages/ worst system GPR contour plot
  • 7. standard). In this study the fibrillation current is calculated according to the C1-IEC standard and body resistance for 95 % population, see Fig. 11. If crushed rock is used to im- prove the safety limits for step and touch voltage, it can be included and entered in the window. 4 Conclusion Manual calculation of the equivalent resistance of com- posite grounding can lead to incorrect results if the mirroring effect is not taken into account. Because of the large geo- metric structure of a grid, all additional metallic conductors such as rods, rings and another additional structures can influence each other. This gives advantages to computer design, especially to specialised programs that take into ac- count all physical phenomena. Since TS is a restricted area for non-operating personnel (civilian personnel), it is protected by a metallic fence. Attention must be taken to prevent the rise in the potential of fence due to fault conditions in TS. Fatal ac- cidents caused by dangerous touch voltages when someone touches the fence can be avoided by placing an additional buried ring conductor outside TS, one meter away from the fence, which is in galvanic contact with the main grounding but not with the fence. This additional ring is added in this study. The main purpose of this additional ring conductor is to shape the electric potential at the surface around the fence. References [1] Ma J., Dawalibi F. P.: “Modern Computational Methods for the Design and Analysis of Power System Ground- ing.” Proceedings of the 1998 International Conference on Power System Technology, Beijing, August 18–21, 1998, p. 122–126. [2] Dawalibi F. P., Barbeito N.: “Measurements and Com- putations of the Performance of Grounding Systems Buried in Multilayer Soils.” IEEE Transactions on Power Delivery, Vol. 6, No. 4, October 1991, p. 1483–1490. [3] Nikolovski S., Fortin S.: “Lightning Transient Response of 400 kV Transmission Tower with Associated Ground- ing System.” EMC 1998 Roma International Symposium on Electromagnetic Compatibility, Rome, Italy, Septem- ber 14, 1998. [4] Nikolovski S., Fortin S.: “Frequency Domain Analysis of 110/35 kV Transformer Station Grounding System Subject to Lightning Strike.” Proceedings of the IEEE PowerTech '99 Conference, Budapest, Hungary, August 29–September 2, 1999. Srete Nikolovski Ph.D e-mail: Srete.Nikolovski@etfos.hr Tomislav Barić B.Sc. e-mail: Tomislav.Baric@etfos.hr Power System Department Faculty of Electrical Engineering Osijek K. Trpimira 2B 31000 Osijek, Croatia © Czech Technical University Publishing House http://ctn.cvut.cz/ap/ 89 Acta Polytechnica Vol. 44 No. 2/2004 Fig. 11: Window for Safety assessment limits with data relevant in this study Fig. 12: Computed safety Step and Touch Voltage for an addi- tional layer (rocks) at the surface of TS