Lecture 7 - Flexure
June 16, 2003
CVEN 444
Lecture GoalsLecture Goals
Doubly Reinforced beams
T Beams and L Beams
Pan Joist
Analysis of FlangedAnalysis of Flanged
SectionSection
Floor systems with slabs and beams are placed
in monolithic pour.
Slab acts as a top flange to the beam; T-
beams, and Inverted L(Spandrel) Beams.
Analysis of FlangedAnalysis of Flanged
SectionsSections
Positive and Negative Moment Regions in a T-beam
Analysis of FlangedAnalysis of Flanged
SectionsSections
If the neutral axis falls
within the slab depth
analyze the beam as a
rectangular beam,
otherwise as a T-beam.
Analysis of FlangedAnalysis of Flanged
SectionsSections
Effective Flange Width
Portions near the webs are more highly stressed than
areas away from the web.
Analysis of FlangedAnalysis of Flanged
SectionsSections
Effective width (beff)
beff is width that is stressed uniformly to give the same
compression force actually developed in compression
zone of width b(actual)
ACI Code Provisions forACI Code Provisions for
Estimating bEstimating beffeff
From ACI 318, Section 8.10.2
T Beam Flange:
eff
f w
actual
4
16
L
b
h b
b
≤
≤ +
≤
ACI Code Provisions forACI Code Provisions for
Estimating bEstimating beffeff
From ACI 318, Section 8.10.3
Inverted L Shape Flange
( )
eff w
f w
actual w
12
6
0.5* clear distance to next web
L
b b
h b
b b
≤ +
≤ +
≤ = +
ACI Code Provisions forACI Code Provisions for
Estimating bEstimating beffeff
From ACI 318, Section 8.10
Isolated T-Beams
weff
w
f
4
2
bb
b
h
≤
≥
Various Possible Geometries ofVarious Possible Geometries of
T-BeamsT-Beams
Single Tee
Twin Tee
Box
Analysis of T-BeamAnalysis of T-Beam
Case 1: Same as rectangular section
Steel is yielding
under reinforced
Check fha ≤
fha ≤
ysysAssume ff =⇒≥ εε
Analysis of T-BeamAnalysis of T-Beam
Case 1:
Equilibrium
fha ≤
s y
c eff0.85
A f
T C a
f b
= ⇒ =
′
Analysis of T-BeamAnalysis of T-Beam
Case 1:
Confirm
fha ≤
ycus
1
ys
εεε
β
εε
≥




 −
=
=
≥
c
cd
a
c
Analysis of T-BeamAnalysis of T-Beam
Case 1:
Calculate Mn
fha ≤






−=
2
ysn
a
dfAM
Analysis of T-BeamAnalysis of T-Beam
Case 2: Assume steel yieldsfha >
( )
ys
wcw
fwcf
85.0
85.0
fAT
abfC
hbbfC
=
′=
−′=
Analysis of T-BeamAnalysis of T-Beam
Case 2: Assume steel yieldsfha >
( )c w f
sf
y
0.85 f b b h
A
f
′ −
=
The flanges are considered to be equivalent
compression steel.
Analysis of T-BeamAnalysis of T-Beam
Case 2: Equilibriumfha >
( )s sf y
f w
c w0.85
A A f
T C C a
f b
−
= + ⇒ =
′
Analysis of T-BeamAnalysis of T-Beam
Case 2:
Confirm
fha >
f
1
s cu 0.005
a h
a
c
d c
c
β
ε ε
>
=
− 
= ≥ ÷
 
Analysis of T-BeamAnalysis of T-Beam
Case 2:
Confirm
fha >
y
c
f f
1
1.18
or
f
f
d
h h a
ϖ ρ
ϖ
β
=
′
≤ ≤
Analysis of T-BeamAnalysis of T-Beam
Case 2:
Calculate nominal
moments
fha >
( )
n n1 n2
n1 s sf y
f
n2 sf y
2
2
M M M
a
M A A f d
h
M A f d
= +
 
= − − ÷
 
 
= − ÷
 
Analysis of T-BeamsAnalysis of T-Beams
The definition of Mn1 and Mn2 for the T-Beam are given
as:
Analysis of T-BeamsAnalysis of T-Beams
The ultimate moment Mu for the T-Beam are given as:
u nM M
c
f
d
φ
φ
=
 
=  ÷
 
For a T-Beam with the
tension steel yielded using a
function c/d
Limitations on ReinforcementLimitations on Reinforcement
for Flange Beamsfor Flange Beams
Lower Limits
 Flange in compression
c
ys
min
w
y
3
larger of
200
f
fA
b d
f
ρ
 ′


= = 



Limitations on ReinforcementLimitations on Reinforcement
for Flange Beamsfor Flange Beams
Lower Limits
 Flange in tension
















 ′
′
=
db
f
db
f
f
db
f
f
A
eff
y
eff
y
c
w
y
c
s(min)
200
3
oflarger
6
ofsmaller
Limitations on ReinforcementLimitations on Reinforcement
for Flange Beamsfor Flange Beams
Lower Limits
 If As(provided) 4/3 As(req’d) based on analysis
then As(min) is not required (i.e.)
φMn
4/3Mu for As(provided)
See ACI 10.5.3
≥
≥
Example - T-BeamExample - T-Beam
Find Mn and Mu for T-Beam.
beff = 54 in. hf = 3 in. b = 7 ft.
d = 16.5 in. As = 8.5 in2
fy = 50 ksi fc = 3 ksi
bw= 12 in L = 18 ft
Example of L-BeamExample of L-Beam
Confirm beff
( )
eff
f w
12 in.
18 ft
ft.
54 in.
4 4
16 16 3 in. 12 in.=60 in.
12 in.
7 ft. 84 in.
ft.
L
b
h b
b
 
 ÷
 ≤ = =
≤ + = +
 
≤ = = ÷
 
Example - T-BeamExample - T-Beam
( )( )
( ) ( )
2
s y
c eff
1
s
8.5 in 50 ksi
3.09 in.
0.85 0.85 3 ksi 54 in.
3.09 in
3.63 in.
0.85
16.5 in.
1 0.003 1 0.003 0.0106 0.005
3.63 in.
A f
a
f b
a
c
d
c
β
ε
= = =
′
= = =
   
= − = − = >   
   
Compute the equivalent c value and check the strain
in the steel, εs
Steel will yield in the tension zone.
Example - T-BeamExample - T-Beam
( )
( ) ( )
2
s
w
y
min min
c
y
8.5 in
0.0429
12 in. 16.5 in.
200 200
0.004
50000
0.004
3 3 3000
0.00329
50000
0.0429 0.004
A
b d
f
f
f
ρ
ρ ρ
= = =

= =

= ⇒ =
 = =


>
Compute the reinforcement ρ and check to make sure it
is greater than ρmin
Section works for minimum
reinforcement.
Example - T-BeamExample - T-Beam
( ) ( )
y
c
f
1
f
50 ksi
0.0429 0.7155
3 ksi
1.18 0.7155 16.5 in.1.18
3 in. 16.388
0.85
3 in. 3.09 in.
f
f
d
h
h a
ϖ ρ
ϖ
β
 
= = = ÷′  
≤ ⇒ ≤ =
≤ ⇒ ≤
Compute ω and check that the c value is greater than hf
Analysis the beam as a T-beam.
Example - T-BeamExample - T-Beam
Compute ω and check that the c value is greater than hf
Compute a
( ) ( ) ( ) ( )
( )
c eff w f
sf
y
2
0.85 0.85 3 ksi 54 in. 12 in. 3 in.
50 ksi
6.426 in
f b b h
A
f
′ − −
= =
=
( ) ( )( )
( ) ( )
2 2
s sf y
c w
8.5 in 6.426 in 50 ksi
0.85 0.85 3 ksi 12 in.
3.889 in.
A A f
a
f b
−−
= =
′
=
Example - T-BeamExample - T-Beam
Compute nominal moment components
( )( )2f
n2 sf y
3 in.
6.426 in 50 ksi 16.5 in.
2 2
4819.5 k-in.
h
M A f d
   
= − = −   
   
=
( )
( )( )
n1 s sf y
2 2
2
3.889 in.
8.5 in 6.426 in 50 ksi 16.5 in.
2
1535.34 k-in.
a
M A A f d
 
= − − 
 
 
= − − 
 
=
Example - T-BeamExample - T-Beam
Compute nominal moment
( )u n 0.9 529.57 k-ft.
416.6 k-ft.
M Mφ= =
=
n n1 n2
1535.34 k-in. 4819.5 k-in.
6354.84 k-in. 529.57 k-ft.
M M M= +
= +
= ⇒
Compute ultimate moment
Example of L-BeamExample of L-Beam
Determine the
effective b for the
spandrel beam and
do the analysis.
Use 4 #9 bars and
find the ultimate
moment capacity.
fy=50 ksi, fc = 3 ksi
Example of L-BeamExample of L-Beam
Compute beff
( )
eff w
f w
actual w
12
6
0.5* clear distance to next web
L
b b
h b
b b
≤ +
≤ +
≤ = +
Example of L-BeamExample of L-Beam
Compute beff
( )
( )
eff w
f w
actual w
12 in.
20 ft
ft
12 in. =32 in.
12 12
6 6 6 in. 12 in. = 48 in.
0.5* clear distance to next web
12 in.
12 in. + 0.5* 7 ft 54 i
ft
L
b b
h b
b b
 
 ÷
 ≤ + = +
≤ + = +
≤ = +
  
= = ÷ ÷
  
n.
Example of L-BeamExample of L-Beam
The value beff and As
( )
eff
2 2
s
= 32 in.
4 1.0 in 4.0 in
b
A = =
Example - L-BeamExample - L-Beam
( )( )
( ) ( )
2
s y
c eff
1
s
4.0 in 50 ksi
2.45 in.
0.85 0.85 3 ksi 32 in.
2.45 in
2.88 in.
0.85
24 in.
1 0.003 1 0.003 0.0220 0.005
2.88 in.
A f
a
f b
a
c
d
c
β
ε
= = =
′
= = =
   
= − = − = > ÷  ÷
   
Compute the equivalent c value and check the strain
in the steel, εs
Steel will yield in the tension zone.
Example - L-BeamExample - L-Beam
( )
( ) ( )
2
s
w
y
min min
c
y
4.0 in
0.0139
12 in. 24 in.
200 200
0.004
50000
0.004
3 3 3000
0.00329
50000
0.0139 0.004
A
b d
f
f
f
ρ
ρ ρ
= = =

= =

= ⇒ =
 = =


>
Compute the reinforcement ρ and check to make sure it
is greater than ρmin
Section works for minimum
reinforcement.
Example - L-BeamExample - L-Beam
( ) ( )
y
c
f
1
f
50 ksi
0.0139 0.2315
3 ksi
1.18 0.2315 24 in.1.18
6 in. 7.71 in.
0.85
6 in. 2.45 in.
f
f
d
h
h a
ϖ ρ
ϖ
β
 
= = = ÷′  
≤ ⇒ ≤ =
≤ ⇒ ≤
Compute ω and check that the c value is greater than hf
Analysis the beam as a Singly reinforced beam.
False!
Example - L-BeamExample - L-Beam
Compute a
( )( )
( ) ( )
2
s y
c
4.0 in 50 ksi
0.85 0.85 3 ksi 32 in.
2.451 in.
A f
a
f b
= =
′
=
Example - L-BeamExample - L-Beam
Compute nominal moment
( )( )
n s y
2
2
2.451 in.
4.0 in 50 ksi 24.0 in.
2
4554.9 k-in. 379.58 k-ft.
a
M A f d
 
= − ÷
 
 
= − ÷
 
= ⇒
Example - L-BeamExample - L-Beam
( )u n 0.9 379.58 k-ft.
341.62 k-ft.
M Mφ= =
=
Compute ultimate moment
Pan Joist Floor SystemsPan Joist Floor Systems
View of Pan Joist Slab from Below Walter P. Moore & Assoc.
Pan Joist Floor SystemsPan Joist Floor Systems
View of Double Skip Joist Slab from Below
Walter P. Moore & Assoc.
Pan Joist FloorPan Joist Floor
SystemsSystems
Placing Reinforcement
for a Pan Joist Slab
Walter P. Moore & Assoc.
Pan Joist Floor SystemsPan Joist Floor Systems
General framing layout of
the pan joist system.
Pan Joist FloorPan Joist Floor
SystemsSystems
Pouring a Pan Joist Slab
Walter P. Moore & Assoc.
Pan Joist Floor SystemsPan Joist Floor Systems
Definition: The type of slab is also called a
ribbed slab. It consists of a floor slab, usually
2-4 in. thick, supported by reinforced concrete
ribs. The ribs are usually tapered and
uniformly spaced at distances that do not
exceed 30 in. The ribs are supported on
girders that rest on columns. In some ribbed
slabs, the space between ribs may be filled
with permanent fillers to provide a horizontal
slab soffit.
One-Way JoistOne-Way Joist
ConstructionConstruction
MacGregor, Fig. 10-28
Definition: Pan joist floor
systems are series of closely
spaced cast-in-place T-beams
or joists used for long-span
floors with relatively light
loads. Typically removable
metal forms (fillers or pans)
are used to form joists.
One-Way Joist ConstructionOne-Way Joist Construction
Details of ribbed floor
with removable steel
pans.
Ribbed-floor cross
sections.
One-Way JoistOne-Way Joist
ConstructionConstruction
The design of a ribbed floor
with steel pan forms and
average weight of the floor.
One-Way Joist ConstructionOne-Way Joist Construction
The design of a ribbed floor with steel pan forms and
average weight of the floor.
One-Way Joist ConstructionOne-Way Joist Construction
Joist Details
Pan Joist Floor SystemsPan Joist Floor Systems
ACI Requirements for Joist Construction
(Sec. 8.11, ACI 318-02)
 Slabs and ribs must be cast monolithically.
 Ribs must be spaced consistently
 Ribs may not be less than 4 inches in width
Pan Joist Floor SystemsPan Joist Floor Systems
ACI Requirements for Joist Construction (cont.)
(Sec. 8.11.2, ACI 318-02)
 Depth of ribs may not be more than 3.5 times
the minimum rib width
 Clear spacing between ribs shall not exceed
30 inches.
** Ribbed slabs not meeting these
requirements are designed as slabs and
beams. **
Pan Joist Floor SystemsPan Joist Floor Systems
Slab Thickness
 (ACI Sec. 8.11.6.1)
t 2 in. for joints formed with 20 in. wide pans
t 2.5 in. for joints formed with 30 in. wide
pans (1/12 distance)≥
≥
Pan Joist Floor SystemsPan Joist Floor Systems
Slab Thickness (cont.)
 Building codes give minimum fire resistance
rating:
1-hour fire rating: ¾ in. cover, 3”-3.5” slab
thickness
2-hour fire rating: 1 in. cover, 4.5” slab
thickness
FloorFloor
SystemsSystems
Standard
Removable Form
Dimensions
 Note the shapes
Pan Joist Floor SystemsPan Joist Floor Systems
Standard Removable Form Dimensions
 Standard Widths: 20 in. & 30 in.
(measured at bottom of ribs)
 Standard Depths: 6, 8, 10, 12, 14, 16 or
20 in.
Pan Joist Floor SystemsPan Joist Floor Systems
Standard Removable Form Dimensions
(cont.)
 End Forms: one end is closed (built-in) to
form the supporting beam
 Tapered End Forms: provide additional
shear capacity at ends of joists by tapering
ends to increase rib width.
Pan Joist
Slabs
Standard Pan Joist
Form Dimensions
Ref. CECO Concrete
Construction Catalog
Pan Joist
Slabs
Standard Pan Joist
Form Dimensions
Ref. CECO Concrete Construction
Catalog
Pan Joist Floor SystemsPan Joist Floor Systems
Laying Out Pan Joist Floors
 Rib/slab thickness
Governed by strength, fire rating,
available space
 Overall depth and rib thickness
Governed by deflections and shear
Pan Joist Floor SystemsPan Joist Floor Systems
Laying Out Pan Joist Floors (cont.)
 Typically no stirrups are used in joists
 Reducing Forming Costs:
Use constant joist depth for entire floor
Use same depth for joists and beams
(not always possible)
Pan Joist Floor SystemsPan Joist Floor Systems
Distribution Ribs
 Placed perpendicular to joists*
 Spans < 20 ft.: None
 Spans 20-30 ft.: Provided a midspan
 Spans > 30 ft.: Provided at third-points
 At least one continuous #4 bar is provided at top
and bottom of distribution rib.
*Note: not required by ACI Code, but typically used
in construction
Member DepthMember Depth
ACI provides minimum member depth and
slab thickness requirements that can be used
without a deflection calculation (Sec. 9.5 ACI
318)
 Useful for selecting preliminary member
sizes
Member DepthMember Depth
ACI 318 - Table 9.5a:
 Min. thickness, h (for beams or ribbed one-way
slab)
For beams with one end continuous: L/18.5
For beams with both ends continuous: L/21
L is span length in inches
 Table 9.5a usually gives a depth too shallow for
design, but should be checked as a minimum.
MemberMember
DepthDepth
ACI 318-99: Table 9.5a
Member DepthMember Depth
Rule of Thumb:
 hb (in.) ~ L (ft.)
 Ex.) 30 ft. span -> hb ~ 30 in.
 May be a little large, but okay as a start to
calc. DL
Another Rule of Thumb:
 wDL (web below slab) ~ 15% (wSDL+ wLL)
Note: For design, start with maximum
moment for beam to finalize depth.
Select b as a function of d
 b ~ (0.45 to 0.65) (d)

More Related Content

What's hot

Moment Co-efficient Method
Moment Co-efficient MethodMoment Co-efficient Method
Moment Co-efficient Method
Yousuf Bin Aziz
 
52436966 lecture-13-plate-girders
52436966 lecture-13-plate-girders52436966 lecture-13-plate-girders
52436966 lecture-13-plate-girders
Saleem Malik
 

What's hot (20)

_lateral_earth_pressure_(foundation engineering)
_lateral_earth_pressure_(foundation engineering)_lateral_earth_pressure_(foundation engineering)
_lateral_earth_pressure_(foundation engineering)
 
Design of two way slabs(d.d.m.)
Design of two way slabs(d.d.m.)Design of two way slabs(d.d.m.)
Design of two way slabs(d.d.m.)
 
Design of column base plates anchor bolt
Design of column base plates anchor boltDesign of column base plates anchor bolt
Design of column base plates anchor bolt
 
Design of torsion reinforcement
 Design of torsion reinforcement Design of torsion reinforcement
Design of torsion reinforcement
 
Axially loaded columns
Axially loaded columnsAxially loaded columns
Axially loaded columns
 
Examples on effective stress
Examples on effective stressExamples on effective stress
Examples on effective stress
 
Problems on piles and deep footing
Problems on piles and deep footingProblems on piles and deep footing
Problems on piles and deep footing
 
Moment Co-efficient Method
Moment Co-efficient MethodMoment Co-efficient Method
Moment Co-efficient Method
 
Influence lines (structural analysis theories)
Influence lines (structural analysis theories)Influence lines (structural analysis theories)
Influence lines (structural analysis theories)
 
SINGLY REINFORCED BEAM
SINGLY REINFORCED BEAM SINGLY REINFORCED BEAM
SINGLY REINFORCED BEAM
 
NSCP 2010 , Volume 1
NSCP 2010 , Volume 1NSCP 2010 , Volume 1
NSCP 2010 , Volume 1
 
Design of compression members
Design of compression membersDesign of compression members
Design of compression members
 
Examples on seepage
Examples on seepageExamples on seepage
Examples on seepage
 
Square footing design
Square footing designSquare footing design
Square footing design
 
Reviewer for materials engineer
Reviewer for materials engineerReviewer for materials engineer
Reviewer for materials engineer
 
Prestressed Concrete Design
Prestressed Concrete DesignPrestressed Concrete Design
Prestressed Concrete Design
 
19-Examples for Beam Column (Steel Structural Design & Prof. Shehab Mourad)
19-Examples for Beam Column (Steel Structural Design & Prof. Shehab Mourad)19-Examples for Beam Column (Steel Structural Design & Prof. Shehab Mourad)
19-Examples for Beam Column (Steel Structural Design & Prof. Shehab Mourad)
 
Structural Analysis (Solutions) Chapter 9 by Wajahat
Structural Analysis (Solutions) Chapter 9 by WajahatStructural Analysis (Solutions) Chapter 9 by Wajahat
Structural Analysis (Solutions) Chapter 9 by Wajahat
 
52436966 lecture-13-plate-girders
52436966 lecture-13-plate-girders52436966 lecture-13-plate-girders
52436966 lecture-13-plate-girders
 
Numerical Problem and solution on Bearing Capacity ( Terzaghi and Meyerhof T...
Numerical Problem and solution on Bearing Capacity  ( Terzaghi and Meyerhof T...Numerical Problem and solution on Bearing Capacity  ( Terzaghi and Meyerhof T...
Numerical Problem and solution on Bearing Capacity ( Terzaghi and Meyerhof T...
 

Viewers also liked

T Beam USD
T Beam USDT Beam USD
T Beam USD
S M Rahat Rahman
 
Test before Final ( T Beam )
Test before Final ( T Beam )Test before Final ( T Beam )
Test before Final ( T Beam )
S M Rahat Rahman
 
T-Beam Design by WSD Method
T-Beam Design by WSD MethodT-Beam Design by WSD Method
T-Beam Design by WSD Method
Md Tanvir Alam
 
Metrado de cargas vigas - columnas
Metrado de cargas   vigas - columnasMetrado de cargas   vigas - columnas
Metrado de cargas vigas - columnas
Cesar Simon
 

Viewers also liked (10)

T Beam USD
T Beam USDT Beam USD
T Beam USD
 
T beam design by WSD method
T beam design by WSD methodT beam design by WSD method
T beam design by WSD method
 
Test before Final ( T Beam )
Test before Final ( T Beam )Test before Final ( T Beam )
Test before Final ( T Beam )
 
T beam wsd method singly and doubly reinforcement
T beam wsd method singly and doubly reinforcementT beam wsd method singly and doubly reinforcement
T beam wsd method singly and doubly reinforcement
 
T-Beam Design by WSD Method
T-Beam Design by WSD MethodT-Beam Design by WSD Method
T-Beam Design by WSD Method
 
DICEÑO DE VIGA DOBLEMENTE REFORZADA
DICEÑO DE VIGA DOBLEMENTE REFORZADADICEÑO DE VIGA DOBLEMENTE REFORZADA
DICEÑO DE VIGA DOBLEMENTE REFORZADA
 
Metrado de cargas vigas - columnas
Metrado de cargas   vigas - columnasMetrado de cargas   vigas - columnas
Metrado de cargas vigas - columnas
 
T-Beam Design by USD method-10.01.03.102
T-Beam Design by USD method-10.01.03.102T-Beam Design by USD method-10.01.03.102
T-Beam Design by USD method-10.01.03.102
 
T beam TYPES
T beam TYPEST beam TYPES
T beam TYPES
 
Análisis y diseño de Vigas de Concreto armado
Análisis y diseño de Vigas de Concreto armadoAnálisis y diseño de Vigas de Concreto armado
Análisis y diseño de Vigas de Concreto armado
 

Similar to Analysis of T-Beam

Rectangular tank example_latest
Rectangular tank example_latestRectangular tank example_latest
Rectangular tank example_latest
Vedachalam Mani
 
Columns lecture#2
Columns lecture#2Columns lecture#2
Columns lecture#2
Irfan Malik
 
10346 07 08 examination paper
10346 07 08 examination paper10346 07 08 examination paper
10346 07 08 examination paper
Eddy Ching
 

Similar to Analysis of T-Beam (20)

Doubly reinforced beam]
Doubly reinforced beam]Doubly reinforced beam]
Doubly reinforced beam]
 
Ch 8.pdf
Ch 8.pdfCh 8.pdf
Ch 8.pdf
 
thesis defense presentation
thesis defense presentationthesis defense presentation
thesis defense presentation
 
1.4 latifs 17 dramix sog
1.4 latifs 17 dramix sog 1.4 latifs 17 dramix sog
1.4 latifs 17 dramix sog
 
1.4 latifs 17 dramix sog
1.4 latifs 17 dramix sog 1.4 latifs 17 dramix sog
1.4 latifs 17 dramix sog
 
10-design of singly reinforced beams
10-design of singly reinforced beams10-design of singly reinforced beams
10-design of singly reinforced beams
 
Lec 20 21-22
Lec 20 21-22Lec 20 21-22
Lec 20 21-22
 
Lec 20 21-22 -flexural analysis and design of beams-2007-r
Lec 20 21-22 -flexural analysis and design of beams-2007-rLec 20 21-22 -flexural analysis and design of beams-2007-r
Lec 20 21-22 -flexural analysis and design of beams-2007-r
 
Lec.8 strength design method t beams
Lec.8   strength design method t beamsLec.8   strength design method t beams
Lec.8 strength design method t beams
 
Slender columnn and two-way slabs
Slender columnn and two-way slabsSlender columnn and two-way slabs
Slender columnn and two-way slabs
 
Rectangular tank example_latest
Rectangular tank example_latestRectangular tank example_latest
Rectangular tank example_latest
 
Formulas for RCC.pdf
Formulas for RCC.pdfFormulas for RCC.pdf
Formulas for RCC.pdf
 
Rcc member design steps
Rcc member design stepsRcc member design steps
Rcc member design steps
 
Sasoli1
Sasoli1Sasoli1
Sasoli1
 
FREE VIBRATION ANALYSIS OF BEAMS AND PLATES
 FREE VIBRATION ANALYSIS OF BEAMS AND PLATES FREE VIBRATION ANALYSIS OF BEAMS AND PLATES
FREE VIBRATION ANALYSIS OF BEAMS AND PLATES
 
Columns lecture#2
Columns lecture#2Columns lecture#2
Columns lecture#2
 
Mathcad 17-slab design
Mathcad   17-slab designMathcad   17-slab design
Mathcad 17-slab design
 
10346 07 08 examination paper
10346 07 08 examination paper10346 07 08 examination paper
10346 07 08 examination paper
 
RCC BMD
RCC BMDRCC BMD
RCC BMD
 
Analysis and Design of Reinforced Concrete Beams
Analysis and Design of Reinforced Concrete BeamsAnalysis and Design of Reinforced Concrete Beams
Analysis and Design of Reinforced Concrete Beams
 

Recently uploaded

Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 

Recently uploaded (20)

Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 

Analysis of T-Beam

  • 1. Lecture 7 - Flexure June 16, 2003 CVEN 444
  • 2. Lecture GoalsLecture Goals Doubly Reinforced beams T Beams and L Beams Pan Joist
  • 3. Analysis of FlangedAnalysis of Flanged SectionSection Floor systems with slabs and beams are placed in monolithic pour. Slab acts as a top flange to the beam; T- beams, and Inverted L(Spandrel) Beams.
  • 4. Analysis of FlangedAnalysis of Flanged SectionsSections Positive and Negative Moment Regions in a T-beam
  • 5. Analysis of FlangedAnalysis of Flanged SectionsSections If the neutral axis falls within the slab depth analyze the beam as a rectangular beam, otherwise as a T-beam.
  • 6. Analysis of FlangedAnalysis of Flanged SectionsSections Effective Flange Width Portions near the webs are more highly stressed than areas away from the web.
  • 7. Analysis of FlangedAnalysis of Flanged SectionsSections Effective width (beff) beff is width that is stressed uniformly to give the same compression force actually developed in compression zone of width b(actual)
  • 8. ACI Code Provisions forACI Code Provisions for Estimating bEstimating beffeff From ACI 318, Section 8.10.2 T Beam Flange: eff f w actual 4 16 L b h b b ≤ ≤ + ≤
  • 9. ACI Code Provisions forACI Code Provisions for Estimating bEstimating beffeff From ACI 318, Section 8.10.3 Inverted L Shape Flange ( ) eff w f w actual w 12 6 0.5* clear distance to next web L b b h b b b ≤ + ≤ + ≤ = +
  • 10. ACI Code Provisions forACI Code Provisions for Estimating bEstimating beffeff From ACI 318, Section 8.10 Isolated T-Beams weff w f 4 2 bb b h ≤ ≥
  • 11. Various Possible Geometries ofVarious Possible Geometries of T-BeamsT-Beams Single Tee Twin Tee Box
  • 12. Analysis of T-BeamAnalysis of T-Beam Case 1: Same as rectangular section Steel is yielding under reinforced Check fha ≤ fha ≤ ysysAssume ff =⇒≥ εε
  • 13. Analysis of T-BeamAnalysis of T-Beam Case 1: Equilibrium fha ≤ s y c eff0.85 A f T C a f b = ⇒ = ′
  • 14. Analysis of T-BeamAnalysis of T-Beam Case 1: Confirm fha ≤ ycus 1 ys εεε β εε ≥      − = = ≥ c cd a c
  • 15. Analysis of T-BeamAnalysis of T-Beam Case 1: Calculate Mn fha ≤       −= 2 ysn a dfAM
  • 16. Analysis of T-BeamAnalysis of T-Beam Case 2: Assume steel yieldsfha > ( ) ys wcw fwcf 85.0 85.0 fAT abfC hbbfC = ′= −′=
  • 17. Analysis of T-BeamAnalysis of T-Beam Case 2: Assume steel yieldsfha > ( )c w f sf y 0.85 f b b h A f ′ − = The flanges are considered to be equivalent compression steel.
  • 18. Analysis of T-BeamAnalysis of T-Beam Case 2: Equilibriumfha > ( )s sf y f w c w0.85 A A f T C C a f b − = + ⇒ = ′
  • 19. Analysis of T-BeamAnalysis of T-Beam Case 2: Confirm fha > f 1 s cu 0.005 a h a c d c c β ε ε > = −  = ≥ ÷  
  • 20. Analysis of T-BeamAnalysis of T-Beam Case 2: Confirm fha > y c f f 1 1.18 or f f d h h a ϖ ρ ϖ β = ′ ≤ ≤
  • 21. Analysis of T-BeamAnalysis of T-Beam Case 2: Calculate nominal moments fha > ( ) n n1 n2 n1 s sf y f n2 sf y 2 2 M M M a M A A f d h M A f d = +   = − − ÷     = − ÷  
  • 22. Analysis of T-BeamsAnalysis of T-Beams The definition of Mn1 and Mn2 for the T-Beam are given as:
  • 23. Analysis of T-BeamsAnalysis of T-Beams The ultimate moment Mu for the T-Beam are given as: u nM M c f d φ φ =   =  ÷   For a T-Beam with the tension steel yielded using a function c/d
  • 24. Limitations on ReinforcementLimitations on Reinforcement for Flange Beamsfor Flange Beams Lower Limits  Flange in compression c ys min w y 3 larger of 200 f fA b d f ρ  ′   = =    
  • 25. Limitations on ReinforcementLimitations on Reinforcement for Flange Beamsfor Flange Beams Lower Limits  Flange in tension                  ′ ′ = db f db f f db f f A eff y eff y c w y c s(min) 200 3 oflarger 6 ofsmaller
  • 26. Limitations on ReinforcementLimitations on Reinforcement for Flange Beamsfor Flange Beams Lower Limits  If As(provided) 4/3 As(req’d) based on analysis then As(min) is not required (i.e.) φMn 4/3Mu for As(provided) See ACI 10.5.3 ≥ ≥
  • 27. Example - T-BeamExample - T-Beam Find Mn and Mu for T-Beam. beff = 54 in. hf = 3 in. b = 7 ft. d = 16.5 in. As = 8.5 in2 fy = 50 ksi fc = 3 ksi bw= 12 in L = 18 ft
  • 28. Example of L-BeamExample of L-Beam Confirm beff ( ) eff f w 12 in. 18 ft ft. 54 in. 4 4 16 16 3 in. 12 in.=60 in. 12 in. 7 ft. 84 in. ft. L b h b b    ÷  ≤ = = ≤ + = +   ≤ = = ÷  
  • 29. Example - T-BeamExample - T-Beam ( )( ) ( ) ( ) 2 s y c eff 1 s 8.5 in 50 ksi 3.09 in. 0.85 0.85 3 ksi 54 in. 3.09 in 3.63 in. 0.85 16.5 in. 1 0.003 1 0.003 0.0106 0.005 3.63 in. A f a f b a c d c β ε = = = ′ = = =     = − = − = >        Compute the equivalent c value and check the strain in the steel, εs Steel will yield in the tension zone.
  • 30. Example - T-BeamExample - T-Beam ( ) ( ) ( ) 2 s w y min min c y 8.5 in 0.0429 12 in. 16.5 in. 200 200 0.004 50000 0.004 3 3 3000 0.00329 50000 0.0429 0.004 A b d f f f ρ ρ ρ = = =  = =  = ⇒ =  = =   > Compute the reinforcement ρ and check to make sure it is greater than ρmin Section works for minimum reinforcement.
  • 31. Example - T-BeamExample - T-Beam ( ) ( ) y c f 1 f 50 ksi 0.0429 0.7155 3 ksi 1.18 0.7155 16.5 in.1.18 3 in. 16.388 0.85 3 in. 3.09 in. f f d h h a ϖ ρ ϖ β   = = = ÷′   ≤ ⇒ ≤ = ≤ ⇒ ≤ Compute ω and check that the c value is greater than hf Analysis the beam as a T-beam.
  • 32. Example - T-BeamExample - T-Beam Compute ω and check that the c value is greater than hf Compute a ( ) ( ) ( ) ( ) ( ) c eff w f sf y 2 0.85 0.85 3 ksi 54 in. 12 in. 3 in. 50 ksi 6.426 in f b b h A f ′ − − = = = ( ) ( )( ) ( ) ( ) 2 2 s sf y c w 8.5 in 6.426 in 50 ksi 0.85 0.85 3 ksi 12 in. 3.889 in. A A f a f b −− = = ′ =
  • 33. Example - T-BeamExample - T-Beam Compute nominal moment components ( )( )2f n2 sf y 3 in. 6.426 in 50 ksi 16.5 in. 2 2 4819.5 k-in. h M A f d     = − = −        = ( ) ( )( ) n1 s sf y 2 2 2 3.889 in. 8.5 in 6.426 in 50 ksi 16.5 in. 2 1535.34 k-in. a M A A f d   = − −      = − −    =
  • 34. Example - T-BeamExample - T-Beam Compute nominal moment ( )u n 0.9 529.57 k-ft. 416.6 k-ft. M Mφ= = = n n1 n2 1535.34 k-in. 4819.5 k-in. 6354.84 k-in. 529.57 k-ft. M M M= + = + = ⇒ Compute ultimate moment
  • 35. Example of L-BeamExample of L-Beam Determine the effective b for the spandrel beam and do the analysis. Use 4 #9 bars and find the ultimate moment capacity. fy=50 ksi, fc = 3 ksi
  • 36. Example of L-BeamExample of L-Beam Compute beff ( ) eff w f w actual w 12 6 0.5* clear distance to next web L b b h b b b ≤ + ≤ + ≤ = +
  • 37. Example of L-BeamExample of L-Beam Compute beff ( ) ( ) eff w f w actual w 12 in. 20 ft ft 12 in. =32 in. 12 12 6 6 6 in. 12 in. = 48 in. 0.5* clear distance to next web 12 in. 12 in. + 0.5* 7 ft 54 i ft L b b h b b b    ÷  ≤ + = + ≤ + = + ≤ = +    = = ÷ ÷    n.
  • 38. Example of L-BeamExample of L-Beam The value beff and As ( ) eff 2 2 s = 32 in. 4 1.0 in 4.0 in b A = =
  • 39. Example - L-BeamExample - L-Beam ( )( ) ( ) ( ) 2 s y c eff 1 s 4.0 in 50 ksi 2.45 in. 0.85 0.85 3 ksi 32 in. 2.45 in 2.88 in. 0.85 24 in. 1 0.003 1 0.003 0.0220 0.005 2.88 in. A f a f b a c d c β ε = = = ′ = = =     = − = − = > ÷  ÷     Compute the equivalent c value and check the strain in the steel, εs Steel will yield in the tension zone.
  • 40. Example - L-BeamExample - L-Beam ( ) ( ) ( ) 2 s w y min min c y 4.0 in 0.0139 12 in. 24 in. 200 200 0.004 50000 0.004 3 3 3000 0.00329 50000 0.0139 0.004 A b d f f f ρ ρ ρ = = =  = =  = ⇒ =  = =   > Compute the reinforcement ρ and check to make sure it is greater than ρmin Section works for minimum reinforcement.
  • 41. Example - L-BeamExample - L-Beam ( ) ( ) y c f 1 f 50 ksi 0.0139 0.2315 3 ksi 1.18 0.2315 24 in.1.18 6 in. 7.71 in. 0.85 6 in. 2.45 in. f f d h h a ϖ ρ ϖ β   = = = ÷′   ≤ ⇒ ≤ = ≤ ⇒ ≤ Compute ω and check that the c value is greater than hf Analysis the beam as a Singly reinforced beam. False!
  • 42. Example - L-BeamExample - L-Beam Compute a ( )( ) ( ) ( ) 2 s y c 4.0 in 50 ksi 0.85 0.85 3 ksi 32 in. 2.451 in. A f a f b = = ′ =
  • 43. Example - L-BeamExample - L-Beam Compute nominal moment ( )( ) n s y 2 2 2.451 in. 4.0 in 50 ksi 24.0 in. 2 4554.9 k-in. 379.58 k-ft. a M A f d   = − ÷     = − ÷   = ⇒
  • 44. Example - L-BeamExample - L-Beam ( )u n 0.9 379.58 k-ft. 341.62 k-ft. M Mφ= = = Compute ultimate moment
  • 45. Pan Joist Floor SystemsPan Joist Floor Systems View of Pan Joist Slab from Below Walter P. Moore & Assoc.
  • 46. Pan Joist Floor SystemsPan Joist Floor Systems View of Double Skip Joist Slab from Below Walter P. Moore & Assoc.
  • 47. Pan Joist FloorPan Joist Floor SystemsSystems Placing Reinforcement for a Pan Joist Slab Walter P. Moore & Assoc.
  • 48. Pan Joist Floor SystemsPan Joist Floor Systems General framing layout of the pan joist system.
  • 49. Pan Joist FloorPan Joist Floor SystemsSystems Pouring a Pan Joist Slab Walter P. Moore & Assoc.
  • 50. Pan Joist Floor SystemsPan Joist Floor Systems Definition: The type of slab is also called a ribbed slab. It consists of a floor slab, usually 2-4 in. thick, supported by reinforced concrete ribs. The ribs are usually tapered and uniformly spaced at distances that do not exceed 30 in. The ribs are supported on girders that rest on columns. In some ribbed slabs, the space between ribs may be filled with permanent fillers to provide a horizontal slab soffit.
  • 51. One-Way JoistOne-Way Joist ConstructionConstruction MacGregor, Fig. 10-28 Definition: Pan joist floor systems are series of closely spaced cast-in-place T-beams or joists used for long-span floors with relatively light loads. Typically removable metal forms (fillers or pans) are used to form joists.
  • 52. One-Way Joist ConstructionOne-Way Joist Construction Details of ribbed floor with removable steel pans. Ribbed-floor cross sections.
  • 53. One-Way JoistOne-Way Joist ConstructionConstruction The design of a ribbed floor with steel pan forms and average weight of the floor.
  • 54. One-Way Joist ConstructionOne-Way Joist Construction The design of a ribbed floor with steel pan forms and average weight of the floor.
  • 55. One-Way Joist ConstructionOne-Way Joist Construction Joist Details
  • 56. Pan Joist Floor SystemsPan Joist Floor Systems ACI Requirements for Joist Construction (Sec. 8.11, ACI 318-02)  Slabs and ribs must be cast monolithically.  Ribs must be spaced consistently  Ribs may not be less than 4 inches in width
  • 57. Pan Joist Floor SystemsPan Joist Floor Systems ACI Requirements for Joist Construction (cont.) (Sec. 8.11.2, ACI 318-02)  Depth of ribs may not be more than 3.5 times the minimum rib width  Clear spacing between ribs shall not exceed 30 inches. ** Ribbed slabs not meeting these requirements are designed as slabs and beams. **
  • 58. Pan Joist Floor SystemsPan Joist Floor Systems Slab Thickness  (ACI Sec. 8.11.6.1) t 2 in. for joints formed with 20 in. wide pans t 2.5 in. for joints formed with 30 in. wide pans (1/12 distance)≥ ≥
  • 59. Pan Joist Floor SystemsPan Joist Floor Systems Slab Thickness (cont.)  Building codes give minimum fire resistance rating: 1-hour fire rating: ¾ in. cover, 3”-3.5” slab thickness 2-hour fire rating: 1 in. cover, 4.5” slab thickness
  • 61. Pan Joist Floor SystemsPan Joist Floor Systems Standard Removable Form Dimensions  Standard Widths: 20 in. & 30 in. (measured at bottom of ribs)  Standard Depths: 6, 8, 10, 12, 14, 16 or 20 in.
  • 62. Pan Joist Floor SystemsPan Joist Floor Systems Standard Removable Form Dimensions (cont.)  End Forms: one end is closed (built-in) to form the supporting beam  Tapered End Forms: provide additional shear capacity at ends of joists by tapering ends to increase rib width.
  • 63. Pan Joist Slabs Standard Pan Joist Form Dimensions Ref. CECO Concrete Construction Catalog
  • 64. Pan Joist Slabs Standard Pan Joist Form Dimensions Ref. CECO Concrete Construction Catalog
  • 65. Pan Joist Floor SystemsPan Joist Floor Systems Laying Out Pan Joist Floors  Rib/slab thickness Governed by strength, fire rating, available space  Overall depth and rib thickness Governed by deflections and shear
  • 66. Pan Joist Floor SystemsPan Joist Floor Systems Laying Out Pan Joist Floors (cont.)  Typically no stirrups are used in joists  Reducing Forming Costs: Use constant joist depth for entire floor Use same depth for joists and beams (not always possible)
  • 67. Pan Joist Floor SystemsPan Joist Floor Systems Distribution Ribs  Placed perpendicular to joists*  Spans < 20 ft.: None  Spans 20-30 ft.: Provided a midspan  Spans > 30 ft.: Provided at third-points  At least one continuous #4 bar is provided at top and bottom of distribution rib. *Note: not required by ACI Code, but typically used in construction
  • 68. Member DepthMember Depth ACI provides minimum member depth and slab thickness requirements that can be used without a deflection calculation (Sec. 9.5 ACI 318)  Useful for selecting preliminary member sizes
  • 69. Member DepthMember Depth ACI 318 - Table 9.5a:  Min. thickness, h (for beams or ribbed one-way slab) For beams with one end continuous: L/18.5 For beams with both ends continuous: L/21 L is span length in inches  Table 9.5a usually gives a depth too shallow for design, but should be checked as a minimum.
  • 71. Member DepthMember Depth Rule of Thumb:  hb (in.) ~ L (ft.)  Ex.) 30 ft. span -> hb ~ 30 in.  May be a little large, but okay as a start to calc. DL Another Rule of Thumb:  wDL (web below slab) ~ 15% (wSDL+ wLL) Note: For design, start with maximum moment for beam to finalize depth. Select b as a function of d  b ~ (0.45 to 0.65) (d)