Fire resistant junction boxes and special Ex-rated enclosures for use in hazardous locations and potentially explosive environments. Fully ATEX compliant and with multiple international approvals.
3. Standard Fire Ratings
Available on Abtech Stainless and GRP ranges
IEC331 Fire Test
• 750°C for 3 hours followed by visual inspection
• Then 5kV insulation resistance test
BS6387 Fire Test - 3 separate tests
1.Fire alone: Category C
• Flame at 950°C for 3 hours, cables powered
2.Fire with Water: Category W
• Flame at 650°C for 15 minutes then flame and
water spray for 15 minutes
3.Fire with Mechanical shock: Category Z
• Flame at 950°C with mechanical shock applied
at 15s intervals for 15minutes
• Note: All fire rated enclosures must be fitted
with ceramic terminals
4. Extreme Fire Resistance Test
• 19kV High Voltage
Enclosure (HVJB) coated
with K-Mass™ fireproofing
• 1100°C for 1 hour
• Tested in accordance with
HC fire curve NEK 606
• Under conditions as
specified in ASTM E1725
(Section 4) & ASTM E1529
(Section 5)
• Independent test carried
out by Intertek and
witnessed by Worley
Parsons
5. Preparation for the Test
Fitted with ceramic pillars, side plates
and phase separators. Clad with K-
Mass™
19kV DC applied for 1 minute without
breakdown prior to test
6. 1100°C for 1 hour
• Required furnace temperature reached after 7min and 44 seconds. The
test then began
• A constant 4kVDC voltage was maintained for the duration of the test
• Leakage was monitored throughout the test
• There was no breakdown
10. Nautilus IP68
• Stainless Steel 316 Enclosure
• IP68 to EN60529
• 100m for 5 days
• 50m for 14 days
• ATEX & IECEx
• Ex e, Ex ia or Ex ib certified
• Terminal box only
• Ambient temperature -50°C to
+55°C
• Hinged cover with handle and
lifting eye straps fitted as
standard
11. SSD Enclosure
• Stainless Steel Ex d Enclosure
• Used for containing transformers,
circuit breakers, motor controls,
PLC’s etc
• ATEX & IECEx IIB or IIB+H2 certified
• Ambient range -20°C to +55°C
• Can be fitted with pushbuttons,
selector switches & windows
• Custom sizes available:
• Almost any size dictated by surface
area: from 560cm² to 18000cm²
• Maximum voltage 660V ac 120V dc
12. Combined Ex e & Ex d Enclosures
• Link SX (Ex e) and SSD
(Ex d) enclosures:
• Ex d Isolator enclosure
with Ex e high voltage
enclosure
• HMI display (Ex d) with
Ex e terminal
connections
13. Camera & Instrument Housing
• Stainless Steel 316 Ex d Enclosure with toughened glass window
• ATEX & IECEx certified
• Ingress protected to IP66/67 to EN60529
• Custom mounting brackets to suit installed device
• Maximum device voltage 60V dc
15. Ex-Rated High Voltage Enclosures
• Ex certified HV range based
on SX enclosure
• From 3.3kV up to 45kV and
3.2kA
• Suitable for -50°C
• Typical applications:
• Umbilical connection
• Down hole pumps
• Water injection pumps
• Fire suppression systems
• Temporary power supply
connections
16. HV Splitter Box
• A unique solution for the
termination of offshore
umbilical cables or onshore
distribution systems
• The power conductor
compartment houses the HV
cables
• A separate control
compartment is used for
terminating fibre optic or
control cables
• Ex e or Ex e op is
• Other ratings same as HVJB
series